CT Tender Specification
CT Tender Specification
CT Tender Specification
ANNEXURE- A
TECHNICAL SPECIFICATION OF 11KV/ LT PANELS
Busbars:-
630Amps. TP Al. with HR PVC sleeves
3.0 LT PANELS:
LT, indoor, cubicle pattern, floor/wall mounting type, dust and vermin proof Panel Boards suitable
for use 3 phase, 4 wire, 433V AC system.
Incomer 1(KSEB) : 1No 1600Amp 50KA, 4P,EDO type Micro Processor Based ACB fitted
with releases.3O/C+1E/F releases.
Instruments : 1No Multi Function Digital Meter with port ( Voltage, Current , PF,
Energy.)
Current Transformer : 3Nos 1600/5A, Cl: 1,15VA CT for metering
: 1No 1600/5A, Cl: 1,15VA CT for APFCR
: 4Nos 1600/5A Cl: P.S. , 15VA for Protection
: 1No 250/5A, Cl: 5P10, 15VA , NCT.
Indications : 1Set LED type RYB indicating lamps with control fuses.
Relay : 1 No Earth Leakage Relay
: 1No REF Relay.
Busbar:-
Main : Ph: 2Rx100x10mm Al
: Ne:1Rx100x10mm Al
Earthing : 25x 6 mm Cu
Panel Size : 4800x2075x1100mm
Busbar:-
: Ph: 1x40x10mm Al
: Ne: 1x40x6mm Al
Earthing : 25x 3 mm Cu
Panel Size : 1800x2000x300mm
3
Busbar:-
: Ph: 1x25x6mm Al
: Ne: 1x25x6mm Al
Earthing : 25x 3 mm Cu
Panel Size : 1000x2000x300mm
Busbar:-
: Ph: 1x25x6mm Al
: Ne: 1x25x6mm Al
Earthing : 25x 3 mm Cu
Panel Size : 1000x2000x300mm
4
1. Rating : 1600A
2. Phase :3
3. No of Wires :4
4. Short Circuit Current : 50KA
5. Type : Indoor, well ventilates
6. Ambient Temperature : 35Deg Centigrade
7. Material for Buses : Electrolyte Aluminium
8. Size of Busbar
Phase : 2Run of 101.6x9.53mm Al
Neutral : 1Run of 101.6x9.53mm Al
9. Support for Buses : SMC
10. Size of SMC Support : 70mm Width & 16mm Thick
11. No of Supports : 2Nos (one at top & other at bottom)
12. Spacing between supports : 400mm
13. Material for Enclosure : CRCA Sheet
14. Gauge of CRCA Sheet : 14SWG
15. Enclosure Size : 700X400mm
16. Painting : Powder Coating
17. Paint shade : Siemens Grey
18. Ingress Protection : IP52
19. Earthing : 25x6mmCu
4. Number of Phase :1
5. Number of Wires :2
6. Rated DC Output 30-40V
7. Trickle Chrger
Voltage Range :30-33V
Rated Current 10A
Type of Control : Automatic
8. Booster Charger
Voltage Range :30-40V
Rated Current 10A
Type of Control : Automatic
9. Float Booster selection : Selector Switch.
10 Ripple : <5%.
11. Efficiency : >75%.
12. Temperature Rise. : 40 Degree above ambient
13. Indicating Instruments. : Charger Voltmeter.
: Charger Current Ammeter.
: AC Input.Power ON Lamp
: Charger ON Lamp.
14. Protection Provided. : S/C Protection.
: Fuse Protection
15. Enclosure Protection : IP 22
16. Type of construction. : Cubicle.
17. Type of mounting : Floor mounting. . :
GENERAL
Fabrication : MSB-By using 14SWG CRCA sheet
: and other Panels by using 16SWG CRCA sheet.
Painting : Powder Coating
Paint shade : Siemens Grey
Ingress Protection : IP52
Bus Bar : Electrolyte grade Al 91E
Bus Bar support : FRP/SMC/DMC(Finger/L Type)
Door Beeding : A type
Hinges : Roller type
MAKE OF EQUIPMENTS
11 KV Metering Panel : Resitech/ Intrans
11KV CT/PT : Resitech/ Intrans
TOD Meter : L&T
11KV VCB Panel : ABB /Crompton/Megavin/Intrans
ACB/MCCB/SDF/1solator : L&T/GE/ABB/ Seimens
MCB/ELCB : MDS / Hagger/ Seimens/ABB
MCB DB : MDS / Hagger/ Seimens/ABB
HT Cables : Gloster/Havells/Nicco
LT Cables : Rallison/V-Guard/Goldcab/Prime Cab/Havells.
Light Fittings : Bajaj/ Crompton / Wipro
Modular Switchs : Havells / Crabtree./ABB
Flush Type Switchs. : Anchor / Elleys.
PVC Copper Wire : Finolex/ Q-Flex/ Havells.
Other Items are Indigenous make