Johnson Controls Central Plant Optimization 10 Application Note
Johnson Controls Central Plant Optimization 10 Application Note
Johnson Controls Central Plant Optimization 10 Application Note
Application Note
Code No. LIT-12011575
Software Release 10.1
Issued October 2, 2015
Refer to the QuickLIT website for the most up-to-date version of this document.
Introduction................................................................................................................................5
Key Concepts.............................................................................................................................5
Operation Overview............................................................................................................................5
Chiller Selector Overview......................................................................................................................5
Waterside Economizer Overview..........................................................................................................5
Chilled Water Pressure Control Loop Overview....................................................................................6
Temperature Control Loop Overview....................................................................................................6
Sequencing Methods Overview.........................................................................................................7
Building Load Overview........................................................................................................................7
Chiller Load Overview...........................................................................................................................7
Decouple Loop Flow (Flow Differential) Overview................................................................................7
Temperature Differential Overview........................................................................................................7
Chiller Coefficient of Performance (COP) Overview........................................................................7
Design.........................................................................................................................................8
Supported Plant Configurations........................................................................................................8
Primary Headered Chilled Water System.............................................................................................8
Primary Dedicated Chilled Water System.............................................................................................9
Primary with Secondary Chilled Water System...................................................................................10
Condenser Water Pump Systems.......................................................................................................11
Cooling Towers...................................................................................................................................13
Alternate Supported Plant Configurations.....................................................................................15
Waterside Economizer........................................................................................................................15
Sequencing Methods...............................................................................................................24
Building Load....................................................................................................................................24
Chiller Load.......................................................................................................................................24
Decouple Loop Flow (Flow Differential).........................................................................................25
Temperature Differential...................................................................................................................25
Application Distribution..........................................................................................................25
Determining the Application Size....................................................................................................26
Performance Considerations..............................................................................................................26
Subsystem Data Sharing Requirements.............................................................................................26
Degraded Mode of Operation...........................................................................................................42
Setup and Commissioning......................................................................................................43
Chiller Coefficient of Performance (COP).......................................................................................43
Determining Chiller COP.....................................................................................................................43
Configuring the Chiller Selector......................................................................................................45
Device Information Table (Chiller Selector).........................................................................................45
Sequence Table and Device Combinations........................................................................................46
Chiller Timers......................................................................................................................................48
Sequence Table Parameters (Chiller).................................................................................................51
Key Inputs and Parameters (Chiller)...................................................................................................51
Operational Data for Simulation and Commissioning (Chiller)............................................................54
Configuring the Pump Selector.......................................................................................................55
Application Note 3
Connecting the DedicatedHeadered_ChillerCommands Module.....................................................175
Adding the Custom Module DedicatedHeadered_MinCHWFlowModification..................................177
Connecting the DedicatedHeadered_MinCHWFlowModification Module.........................................178
Connecting Interlocks to the Chiller Enable Determination...............................................................180
Application Note 4
Introduction
Johnson Controls Central Plant Optimization 10 allows programming of complex chiller plant configurations through
the Controller Configuration Tool (CCT). This application supports the following:
selection and sequencing of up to eight chillers of different sizes
selection and sequencing of up to eight (each) primary and secondary chilled water pumps of varying pumping
capacities.
selection and sequencing of up to eight condenser water pumps
selection and sequencing of cooling towers and bypass valve, including single speed, multi-speed, and vernier
control (one variable speed fan with all other tower fans at constant speed)
selection and sequencing of up to four heat exchangers
sequencing of devices that considers user-defined efficiency rating, runtime equalization, and the
number-of-starts/number-of-stops equalization
control definition for the chiller plant in a single Field Equipment Controller (FEC), Advanced Application Field
Equipment Controller (FAC), Network Control Engine (NCE), if supported by available memory and point
Input/Output (I/O), or split across multiple FECs, FACs, and NCEs
This application note assumes you have a knowledge of chiller plant theory. This document describes:
supported plant configurations
chiller and heat exchanger sequencing methods
sequence of operation
alarms and interlocks
application distribution into multiple controllers
troubleshooting
Key Concepts
Operation Overview
The CPO application comprises up to six different subsystems. The subsystems include:
chillers
primary chilled water pumps
secondary chilled water pumps
condenser water pumps
towers
waterside economizers
One or more control loops exist within each subsystem. These control loops are described in the following sections.
Primary Chilled Water Constant Speed Water Pumps and Secondary Variable Speed Water Pumps Overview
The chiller primary constant speed pumps maintain flow through the chillers, and differential pressure control loop
modulates the speed of the secondary pumps to maintain system differential pressure.
Cooling Towers
Water cooled chillers pass the plants return condenser water through cooling towers where a portion of the water
evaporates, cooling the remaining water. Three cooling tower configurations are described in this section: individual
spray with a common sump, common sprays with a common sump, and individual sprays with individual sumps.
Note: The condenser water supply is provided by the cooling tower to the chiller, and the condenser water return
is provided by the chiller to the cooling tower.
Waterside Economizer
For a non-integrated waterside economizer, chilled water is either provided by a chiller or by a heat exchanger, but
not simultaneously. Chillers and heat exchangers may either be headered or dedicated (see the following figures).
Up to four heat exchangers may be staged up and down to meet the building load. The total number of controlled
devices (chillers plus heat exchangers) cannot exceed eight devices.
Note: For information on the heat exchanger, see Configuring the Heat Exchanger.
For a non-integrated waterside economizer, chilled water is either provided by a chiller or by a heat exchanger, but
not simultaneously. Chillers and heat exchangers may either be headered or dedicated (see the following figures).
Up to four heat exchangers may be staged up and down to meet the building load. The total number of controlled
devices (chillers plus heat exchangers) cannot exceed eight devices.
Note: For information on the heat exchanger, see Configuring the Heat Exchanger.
Building Load
The Building Load method, and specifically the use of a specialized Building Load device (such as a BTU meter AI)
produces the most accurate measurement of the chiller plant load.
The Load Calculation module applies the appropriate correction factors for the fluid media for Pure Water,
Water-Ethylene Glycol Solution, or Water-Propylene Glycol solutions. To specify which type of fluid media, edit the
details of the Load Calculation Media attribute.
When using the Building Load method, it is possible that the building load is not met because the operating chillers
cannot deliver their rated capacity. Reasons for this situation could be a fouled chiller or a day that is beyond the
Buildings cooling design day. The chiller may only be able to reach a 78% load, but is configured to reach 85% to
add another chiller. Therefore, the default application provides logic which derates the capacities of the active chillers,
forcing an upstage to occur under the following conditions:
The CHW Supply Temperature is greater than the CHW Supply Temperature Setpoint for more than a given
period of time (default = 20 minutes).
The CHW Supply Flow is greater than the CHW Max Flow for more than a given period of time (default = 20
minutes). The CHW Max Flow is the sum of the rated CHW Max Flows of requested chillers which are defined
by the user when configuring the Chiller Selector.
Chiller Load
Note: Waterside Economizer does not support chiller load sequencing.
The chiller plant load uses a Capacity Calculation based on % Full Loads Amps or Actual Amps. When % Full Load
Amps is selected, a Setpoint/Miscellaneous module Capacity Calculation Pct FLA module receives percent load
inputs from each chiller. The inputs are used with the device operating capacity to calculate each device load (in
tons), and then added to the other devices running to determine the current chiller plant capacity. This current chiller
plant capacity is compared with the total chiller plant capacity to determine the percentage of total chiller plant
available.
When Actual Amps is selected, a Setpoint/Miscellaneous module Capacity Calculation Amp for Actual Amp selection,
receive signals from current transducers from each chiller. The module adds the amperage of all the current devices.
The percent load is determined as a percentage of the total Actual Amperage of the chiller plant to the total chiller
plant available.
This method of load calculation is less expensive to implement than the Building Load method. One disadvantage
of this method is that the application uses a secondary data source (electric load), as compared to the Building Load
sensor, which uses a primary data source (heat flow).
Johnson Controls Central Plant Optimization 10 Application Note 24
Decouple Loop Flow (Flow Differential)
The Flow Differential method is used only with the primary/secondary chilled water pumping configuration.
Several different methods can determine the difference between primary and secondary chilled water flow.
Bi-directional Flow Sensor measures the Decouple flow directly.
Bi-directional Flow Sensor with BI input measures the Decouple flow directly, and the binary input gives indication
of either normal or reverse direction.
Note: A reverse flow occurs when the secondary flow is greater than the primary flow.
Calculate Decouple Flow receives its input from the Diff Flow Calc, which calculates the difference between the
Primary and Secondary Chilled Water Supply flows.
You can estimate the cooling load based on the measured flow differential, which is also the flow in the crossover
decoupler pipe. The Percent Load is the percentage of the current building load to the total chiller plant available.
This control mode is much less expensive to implement than either Building Load or Chiller Load, but the disadvantage
is that the Flow Differential uses half the information required to do the calculation. For example, to calculate the
energy flow, the chilled water flow and the temperature difference are required. This method assumes that the chillers
produce a constant temperature drop, which is not the case most of the time.
Temperature Differential
The cooling load is determined based on the measured chilled water supply and return temperature differential,
which is calculated in the Supply Return Water Differential module (a Setpoint/Miscellaneous module).
This module is designed to ensure chiller startup by providing a fixed temperature differential output of 14F (7C)
under startup conditions when the chilled water supply and return temperature differential is typically zero. After
startup, once the chilled water supply temperature falls to 46F (or below 10C), the module begins to output the
true chilled water supply-return temperature differential.
This building load is compared to the maximum rated temperature drop across the devices, as defined in the details
of the Chiller Selector Module as Max Delta CHWT. This method is inexpensive since it uses only temperature
sensors.
The Temperature Differential method may be used only on primary constant speed pumps.
Application Distribution
Central plant applications may be very large and comprise up to eight chillers and heat exchangers, eight condenser
water pumps, eight primary chilled water pumps, eight secondary chilled water pumps, eight cooling towers, isolation
valves, bypass valves, and sensors. Large chiller plant applications may exceed the limits of one controller. These
limits include object count, object memory, downloadable file size, bandwidth, I/O count, and BACnet Object ID
(BACoid) count.
Large chiller plant applications are actually a collection of six loosely coupled subsystems, which allow a chiller plant
application to be separated into subsystems. The Metasys system software allows the placement of each of the
six subsystems (chillers, primary chilled water pumps, condenser water pumps, secondary chilled water pumps,
heat exchangers, and towers) in separate controllers.
This section describes how to determine when to divide an application, how to build a split application, and how to
pass data between the subsystems. For information on creating a distributed application, see Appendix: Creating
Distributed Applications.
Performance Considerations
The controllers processor may become busy causing unexpected behavior under certain conditions including:
too many frequently executed modules are loaded into a controller
an application has outputs feeding back to inputs via Last Value objects, and these values change quickly
The following CPO 10 modules consume the most CPU bandwidth and require special considerations regarding the
use of remote sensors:
Chiller Selector
- Bandwidth decreases by the use of the Sequence Table (see the Sequence Table and Device Combinations
section).
- Bandwidth increases exponentially with the number of devices.
Pump Selector (used with headered chilled water and headered condenser water pumping)
- Bandwidth increases exponentially with the number of devices.
Pump Differential Pressure Control
- The Pump Differential Pressure Control should use a local analog input for this module. The pressure sensor
should be connected to the FEC, FAC, or NCE which contains the pressure control modules. The sensor
should not be connected to an IOM as random communication delays can affect control safety.
Variable Speed Primary Minimum Flow Control
- This loop is an order of magnitude slower than the pressure control loop. The Variable Speed Primary Minimum
Flow Control should use a local analog input. Do not use an IOM.
Tower Subsystem
The tower subsystem requires information from the chillers subsystem and from the Condenser Water Pump
subsystem when using headered Condenser Water pumps. Figure 20 shows which information must be shared for
the dedicated condenser water system. For the dedicated condenser water system, the tower pulls all of the shared
data from the controller containing the chiller subsystem. Figure 21 shows which information must be shared for the
headered condenser water system. For the headered condenser water system, the tower pulls some of the data
from the controller containing the chiller subsystem, and some of the data from the controller containing the condenser
water pump control.
Figure 20: Dedicated Condenser Water Tower Subsystem
Figure 23: Headered Condenser Water Tower Subsystem with ASHRAE Open Loop Method
Figure 26: Headered Condenser Water Tower Subsystem with ASHRAE Open Loop Method (Hx)
Figure 29: Headered Condenser Water Pumping Subsystem with Constant Speed Pumps
Figure 30: Dedicated Condenser Water Pump Subsystem with Variable Speed Pumps
Figure 33: Dedicated Condenser Water Pump Subsystem with Constant Speed Pumps (Hx)
Figure 34: Headered Condenser Water Pump Subsystem with Variable Speed Pumps (Hx)
Figure 35: Headered Condenser Water Pumping Subsystem with Constant Speed Pumps (Hx)
Figure 41: Dedicated Variable Speed Primary Chilled Water Pumping (Hx)
Figure 42: Headered Variable Speed Primary Chilled Water Pumping (Hx)
Figure 43: Headered Constant Speed Primary Chilled Water Pumping (Hx)
The COP curve in Figure 46 represents what a variable speed chiller may look like. A curve representing a constant
speed chiller for example can be obtained by increasing the Max Pct Load COP point (to a maximum value equal
to the Peak COP) in order to more accurately represent the upper half of the actual COP curve. Note that, internally,
parts of the curve to the left of the Min Pct Load (minimum of 0) and to the right of the Max Pct Load (maximum of
100) are linearly extrapolated to the points (0, 0) and (110, 0) respectively.
1 The (X) indicates that the property applies to each chiller device.
The Sequence Table can explicitly specify combinations of devices that are allowed to run. Figure 48 shows the
device information and Sequence Tables for a system with five chillers.
Figure 48: Device Info and Sequence Table Five Device Example
For this system, the only allowed combinations of chillers and resulting capacities are outlined in Table 16.
Table 16: Five Chiller Sequence Table
Group A (10 Tons) Group B (20 Tons) Capacity (Total Tons)
1 0 10
0 1 20
1 1 30
3 0 30
3 1 50
Table 17 is an example of a central plant with three chillers and their capacities.
Table 17: Central Plant with Three Chillers
Chiller Number of Tons
Chiller 1 1,000 tons
Chiller 2 1,000 tons
Chiller 3 4,000 tons
If no sequence table is specified, the application chooses the combinations in Table 18.
Table 18: No Sequence Table Selected
Chiller 1 Chiller 2 Chiller 3 Capacity
1 0 0 1,000
0 1 0 1,000
1 1 0 2,000
0 0 1 4,000
1 0 1 5,000
0 1 1 5,000
1 1 1 6,000
Suppose the plant operator requires that the 1,000-ton chillers be commanded On together, not separately. Devices
1 and 2 would be marked as Device Type A, and Device 3 would be marked as Device B. Table 19 shows the new
Device Information Table.
Table 19: Device Information Table
Group A Group B Capacity
2 0 2,000
0 1 4,000
2 1 6,000
Chiller Timers
Table 20 provides descriptions of the chiller timers. For more information, see Transition Timing.
1 This property is found in the Engineering Values section, under the Device Information Table.
2 This property cannot be edited.
Coast Mode
Coast mode is designed to be used towards the end of the day, when plants are typically shut down. In these cases,
Coast mode can be scheduled for a time period immediately prior to shutdown of the plant to prevent a chiller from
starting up and then shutting down after a short cycle. Typically, Coast mode is scheduled for a period 30 to 60
minutes prior to the shutdown of the plant.
Hysteresis
Hysteresis is the value of an additional efficiency penalty applied before making a change. Larger values increase
the stability of the chiller combination currently operating, while forcing a greater drop in efficiency before making a
switch. The adjusted efficiency of the new combination includes this Hysteresis.
Staging Margin
To help prevent unnecessary staging and instability, the Staging Margin defines areas of the COP curve that indicate
potential alternative chiller combinations. However, the Staging Margin does not directly determine the timing or
direction of the Selector. The Upper and Lower Optimal Percent Load points are included in the Staging Margin,
which is applied to both the x-axis (percent load) and the y-axis (COP). The Staging Margin also defines the point
on the curve where each of the identified areas ends. See Stage Up Decision and Stage Down Decision.
Note: Since the Upper Optimal Pct Load is typically closer to 100% than the Lower Optimal Pct Load is to 0%, the
slope of the right-hand side curve is much steeper than the left-hand side slope. Therefore, when the load
is increasing, the system efficiency of the current combination drops faster compared with the slower increase
of efficiency of the new combination, allowing the algorithm to switch to a new stage.
Rotate Now
The Rotate Now feature is meant to immediately force the desired, long-term device combination to change; however,
the actual staging of the device may not occur right away. The selector must first respect its internal timers, such as
the Minimum On/Off Time and the Interstage timers. These timers are meant to protect the equipment from being
staged on and off too frequently. The Rotate Now feature cannot override these timers.
In the case of the Chiller Selector Module, if it has determined there is a change to which devices should be running,
it starts a chiller that should be on before disabling a chiller that is already running. When making the change, the
commanded flows need to be at least as high as the Min Rated flows in order to command the next device On.
When viewing outputs in the Pump Selector module, note that the values for Required Devices and Required Interim
Devices represent which pumps should be commanded on rather than which pumps are commanded on. The
following table describes these outputs.
Table 29: Key Outputs
Output Description
Required Devices Represents the desired steady state set of the pumps commanded on. For example, a value of 5
means 0-0-0-1-0-1, which indicates device 1 and 3 are on, and pumps 2, 4 and above are off.
Required Interim Represents the intermediate pumps requested to run while the pump selector moves toward the
Devices desired steady state.
The Cooling Tower Selector module is always included. You must provide basic tower information in the Tower
Selector module in order for it to operate and be reliable. To enter the information, edit the details of the module.
You must complete the table on the left side with Rated Capacity, Rated Current/Power, and Peak Efficiency in order
for the module to be reliable and the application to work. The tower efficiencies can be the same value. If one of the
towers is given a higher efficiency, it is considered the preferred device. When all the efficiencies are the same, the
selector looks at them equally, with consideration give to capacity, runtime, and starts to equalize.
When viewing outputs in the Cooling Tower Selector module, note that the values for Required Devices and Required
Interim Devices represent which devices should be commanded on rather than which devices are commanded on.
The following table describes these outputs.
Table 33: Key Outputs
Output Description
Required Devices Represents the desired steady state set of the devices commanded on. For example, a
value of 5 means 0-0-0-1-0-1, which indicates device 1 and 3 are on, and devices 2, 4 and
above are off.
Required Interim Devices Represents the intermediate devices requested to run while the selector moves toward the
desired steady state.
CW Min Flow Rated minimum condenser water flow (flow on the cooling tower side CW Min Flow = Rated CW Flow x 0.803
of the heat exchanger) in gpm or L/s.
CHW Min Flow Rated minimum chilled water flow (flow on the building side of the CHW Min Flow = Rated CHW Flow x 0.30
heat exchanger) in gpm or L/s.
1 Calculate values only if the manufacturer has not provided these settings.
2 For systems with multiple parallel (headered) primary or secondary chilled water pumps, this parameter must be set to a
non-zero value greater than the CHW Flow. Failure to do so may result in only one chilled water pump operating per heat
exchanger (additional pumps do not stage up).
3 For systems with dedicated heat exchangers with variable speed condenser water pumps, this parameter must be set to a
non-zero value. Failure to do so may prevent the condenser water pumps from speeding up (the condenser water pumps
may remain at minimum speed).
1 This property is found in the Engineering Values section, under the Device Information Table.
2 This property cannot be edited.
where dPmin is the minimum differential pressure setpoint, flowmin is the largest minimum flow requirement (all chillers)
and CV is the flow coefficient of the bypass valve (when open).
The pump dP setpoint is not reset to a value that exceeds the maximum dP setpoint (default = 40 psi).
Both the maintenance switch and the lockout switch inputs indicate the device is offline and unavailable for sequencing.
When the application detects the Maintenance switch is set to Disable, the chiller is removed from rotation. When
the lockout switch is set to Alarm, the pump or cooling tower is removed from rotation. In the selection tree, you can
choose hardware or network lockout and maintenance switches.
Figure 55: Chilled Water Pump Lockout Switch
Alarms
Pumps and towers support several alarm options. The following table shows the various subsystems and their
supported alarms.
Table 41: Supported Alarm Types
Subsystem Alarm Type
Frequency Converter Motor Overload Belt Alarm Vibration
Fault Tripped
Primary Chilled Water Variable Speed Pumps Constant Speed Pumps Yes No
Pump Only Only
Secondary Chilled Yes No Yes No
Water Pump
Some alarms are only supported for specific equipment types. For example, the frequency converter fault alarm is
only available for variable speed devices. The motor overload tripped fault alarm is only supported for constant
speed pumps and cooling tower fans. The selection tree provides options to set the alarms as either manual or
automatic reset as shown in Figure 57.
Using the selections in Figure 57, the resultant application has a variable speed chilled water pump system with
frequency converter alarm, which requires a manual reset, and an automatic reset belt alarm. Automatic reset alarms
clear as soon as the alarm input returns to the normal state. Manual reset alarms are latched so the alarm input
must return to a normal state and the user must reset the latch.
Unit Reset
The application has a unit reset input if any alarms or interlocks require a manual reset. At selection time, the user
has the option to select either a hardware or network input for unit reset.
In Figure 57, the Unit Reset Switch (BI) option is selected for the frequency converter fault, and the resultant application
has a hardware input to reset the alarm. If the Unit Reset Switch (BI) option is not selected, the application has a
network input. It is possible to choose a network input for some features, and a binary input for others.
Johnson Controls Central Plant Optimization 10 Application Note 78
Status
The CPO 10 application supports optional status inputs which provide feedback indicating whether the chillers,
isolation valves, pumps, and cooling towers are on or off. In some cases, the status is only monitored. In other cases,
the status can be compared to the command and the device may become locked out if the command and status
mismatch for a user-defined period of time.
Figure 58 shows an example of status selected for the primary chilled water pumps.
The application in Figure 58 has status inputs for the primary chilled water pumps, and the pump status is compared
to the commanded value of the pump. If the status and the command are mismatched for a user-defined period of
time (for example, 30 seconds), the pump is locked out and unavailable for rotation. Figure 59 shows manual restart
selected; therefore, the locked out pump is not available for rotation until the user manually resets the application.
The application also supports an automatic restart mode.
Figure 58: Primary Chilled Water Pump Status
Figure 59 shows Chiller Status selected. With Chiller Status selected, the application has a status input for the chiller,
but the status input is only monitored. Chiller status is not compared to the commanded value.
Automatic Restart
This application also supports an Automatic Restart option for locked out equipment. When you select this option,
the application automatically attempts a user-defined number of restarts at user-defined intervals. If all restart attempts
are unsuccessful, a manual restart is required.
Blocking Protection
The CPO 10 application has an optional blocking protection feature, which is intended to prevent a motor from seizing
up during long idle periods. The blocking protection function monitors a motor, and if the motor is off for an extended
period of time (such as a week), the blocking protect function commands the motor on for a brief period of time (such
as 30 seconds).
Retry Amount of time to wait before attempting to try the device again.
Interval
Retry Retry limit.
Attempts
1 When RetryCounter is greater than or equal to Retry Attempts, the primitive does not allow any more retries until you set the
Reset input.
Transition Timing
Figure 61 through Figure 64 show the desired sequence of events after the primitive determines the need to add or
remove chillers. Separate sequences exist for adding the first device and removing the last device. This is done to
avoid dead-heading the pumps. The outputs involved consist of:
CW Isolation Valve/Pump Commands
CHW Isolation Valve/Pump Commands
Required CW Flow, Required CHW Flow (bracketed by the Min and Max values)
Current Percent Load
Device nn Cmd
Capacity Limit
The CW and CHW Max Flows are the sum of the rated flows of the pumps commanded to On. The CW and CHW
Max Flow values are not outputs but internal variables of the primitive.
Headered systems use isolation valves and the pumps are commanded on or off by a dP control module. Dedicated
systems, on the other hand, do not use isolation valves and the pumps are directly commanded by the chiller selector
primitive. Therefore, since the primitive knows (CW Headered/Dedicated property) whether the CW loop is headered
or dedicated, the CW Iso Valve/Pump command behaves accordingly, that is, if it is dedicated, it is a Pump command
and if it is headered it is an Isolation Valve command.
Likewise, since the primitive knows (CHW Headered/Dedicated property) whether the CHW loop is headered or
dedicated, the CHW Iso Valve/Pump command behaves accordingly. That is, if the CHW loop is dedicated, the
CHW loop is a pump command; and if the CHW Iso Valve/Pump command is headered, the CHW Iso Valve/Pump
command is an isolation valve command.
Within the primitive, there are several timers that determine when certain events can occur. The following timers are
shown in the following figures:
InterstageOnTime: Time since the last chiller was commanded on
InterstageOffTime: Time since the need to add or remove 1 chiller was last detected
Figure 61 depicts the timing for the process of adding the first device. This is applicable to headered or dedicated
piping. The sequence for adding the first device is:
1. The need to start the first chiller has been determined (Add Device = True).
Note: No timers inhibit turning on the first device.
2. The (Headered) Iso Valve output immediately changes to True and the Isolation valve timer starts. For Dedicated
systems this timers duration should be zero. The isolation valve needs to open first to give the starting pump a
clear flow way.
3. When the Isolation valve timer expires and the Headered Tower Cmd Flow becomes greater than zero (signifying
at least one tower valve is completely open), the (Dedicated) Pump command changes to True, the Required
CW Flow, required CHW Flow, and Max CHW outputs are updated and the PumpOnTime (Dedicated) and
CommandedFlowSatisfiedTime (Headered) timers are started. If either side CW (or Tower) or CHW is headered,
the CommandedFlowSatisfiedTime timer starts only after the headered CW, Tower, and CHW Commanded
Flows are greater than or equal to their Minimum Required Flows. (For systems with all Dedicated piping, this
timer has already expired.) This sequence allows both flows (dedicated and headered) to exist at the same time.
4. After both the PumpOnTime and CommandedFlowSatisfiedTime timers (which both last for a Pump Delay)
expire, the Device nn command is set true (this is the signal to the chiller panel to start Chiller X) and the Current
Percent Load is updated.
5. When the chiller panel returns the status, confirming that the Chiller X started, Device nn Status is set to On.
Figure 62 depicts the process of adding an additional device. This process is similar to starting the first chillier and
only differs in the order of updating the requested flow and opening the isolation valves. This sequence applies to
the headered piping systems.
The algorithm determines that more devices are required based on the Process Variable (PV) input. Figure 62 shows
the transition from two devices running at 90% to three devices running at 60%.
Figure 63 depicts the sequence of removing any device, except the last. The sequence is as follows:
1. The need to remove one of multiple working devices has been detected (Remove Device = True).
2. Command Device nn to turn off (Device nn Cmd = False) and update the Current Percent Load.
3. Once the chiller panel reports that the device has turned off (Device nn Status = Off), start the Pump Down timer.
Finally, Figure 64 shows the sequence to remove the last device. This diagram differs from Figure 63 in the order
of changing the requested flow and closing the isolation valves. The differences are necessary in order to prevent
deadheading the pumps (running with isolation valves closed). The sequence is as follows:
1. The need to turn off the last device has been detected (Remove Device = True).
2. Command Device nn to turn off (Device nn Cmd = False), set the Required Tower Flow output to zero, and
update the Current Percent Load outputs.
3. Once the chiller panel reports that the device has turned off (Device nn Status = Off), start the Pump Down timer.
4. When the Pump Down timer expires, set the (Dedicated) Pump Cmd output to False and set the required variables
and outputs to zero and start the Pump Delay timer.
Figure 65 shows the sequence of events when a device is added or removed, and depicts what occurs when a
device is disabled in the middle of the start-up process. This finite state machine depicts any dedicated chiller, or
turning on the first headered chiller or turning off the last headered chiller.
Figure 66 shows the sequences of events when a device is added, removed, or disabled for headered chillers only.
This figure does not depict turning on the first device or turning off the last device.
Once a device starts the process of turning on or off, the sequence always completes. The only exception occurs
when the device is disabled.
Stage Up Decision
Figure 72 describes how the application chooses to stage up to a combination with more cooling capacity. Point 1
on the figure represents the existing combination of two chillers. The percent load is increasing, and the chiller
combination is not running as efficiently as it did with a lower load. The application searches through the list of
possible chiller combinations, and finds a group of three chillers which run more efficiently (point 2). The application
applies a staging margin (point 3) and hysteresis (point 4) to determine an expected adjusted COP for the combination
of three chillers.
Adjusted Capacity
If your chiller is not manufactured by York, you must determine the adjusted (increased) capacity of the chiller at
the reduced lift for the lowest temperature the cooling towers can deliver, or that the chiller can operate with for
extended periods of time. Contact the chiller manufacturer for the adjusted capacity, which you can then use to
calculate the chiller lift sensitivity.
If your chiller is manufactured by York, you can determine the adjusted capacity with Yorkworks software.
Once you have the adjusted capacity of the chiller, you can calculate Lift Sensitivity and enter this value into the
Device Info table of the Chiller Selector module in CCT.
Lift Sensitivity is calculated as follows:
where,
S = Lift Sensitivity
Ca = adjusted (increased) capacity of chiller at the adjusted (reduced) lift
Cr = rated capacity of chiller at the rated lift
La = adjusted (reduced) lift
Lr = rated lift
Derating a Chiller
Note: This feature only applies to system where Control Mode = Building Load or Chiller Load.
Important: Derating Percent values greater than 40% may indicated possible malfunction of the chillers and should
be investigated.
The Derating Percent is gradually reduced back to 0% at a rate of 2% per hour. For example, if the Derating Percent
is 10%, it lowers from 10% to 0% over 5 hours. This gradual decrease occurs so that the Derated Percent does not
remain at the initial Derated Capacity.
The Chiller Forced Upstage feature controls both the Derate Now and the Derate Reset input to the Chiller Selector
module. The Derate Reset resets the Derating Percent back to zero instantly.
Note: The Derate Now command may not force a chiller into operation immediately. At the Derated Capacity, the
chiller may still be able to meet the load. Derate Now command may start a chiller, but only if a chiller is
available, and the command must still respect the minimum timers and required chilled water, condenser
water, and tower capacities to support the chiller function.
7. Click Next.
8. Click Finish and then save the master application file.
3. Click Next.
4. Click Finish. The Rebuild Application Warning dialog box appears (Figure 79).
5. Click Yes.
6. When CCT finishes applying the selections, select File > Save As and enter a new filename to save the Chillers
subsystem (Figure 80).
Figure 80: Saving the Chiller Subsystem
3. Click Next.
4. Click Finish. The Rebuild Application Warning dialog box appears (Figure 79).
5. Click Yes.
6. Select File > Save As and enter a new filename to save the Condenser Water System subsystem.
Figure 82: Saving the Condenser Water (Tower) Subsystem
3. Click Next.
4. Click Finish. The Rebuild Application Warning dialog box appears (Figure 79).
5. Click Yes.
6. Select File > Save As and enter a name for the Primary Chill Water Pumps subsystem.
Figure 84: Saving the Primary Chill Water Pump Subsystem
4. Click Next.
5. Click Finish. The Rebuild Application Warning dialog box appears (Figure 79).
6. Click Yes.
7. Select File > Save As and enter the name of the Primary Cond Water Pump subsystem.
Figure 86: Saving the Primary Cond Water Pump Subsystem
You have successfully completed the first step for creating a distributed application. See Setting up Communication
between Controllers section to complete the operation.
3. Select options in the Central Cooling Plant Central Cooling Plant with Optimization tree using the single controller
application selections.
Note: At this point you can export a Master Preferences file. Click the Export button and enter name for your
master preferences file. Click Save.
4. Create subsystems from the master preferences.
7. Click Next.
8. Click Finish
9. Select File > Save.
10. In the Save dialog box, click Save. This completes the first subsystem, Chillers.
2. Enter the System Name. In this example, the name is Condenser Water.
3. From the System Type drop-down list, select Central Cooling.
4. From the System Configuration drop-down list, select Central Cooling with Optimization.
5. Click OK. The master application tree appears in System Selection wizard.
Figure 91: System Selection Wizard for Condenser Water
2. Enter the System Name. In this example, the name is Primary Chill Water Pumps.
3. From the System Type drop-down list, select Central Cooling.
4. From the System Configuration drop-down list, select Central Cooling with Optimization.
5. Click OK. The master application tree appears in System Selection wizard.
Figure 93: System Selection Wizard for Primary Chilled Water Pumps
Detailed Procedures
Selecting the Mechanical System and Control Logic for the CPO10 Application
1. Open CCT.
2. On the File menu, click New. The New System screen appears.
a. In the System Name text box, type a name for your system. This example uses the name
DedicatedHeadered_Example.
b. Click the System Type drop-down box and select Central Cooling Plants.
c. Click the System Configuration drop-down box and select Central Cooling with Optimization.
3. Click OK. The System Selection Wizard screen appears.
a. Under Central Cooling Plant Central Cooling with Optimization > Plant layout Configuration > Quantity of
Chillers, select the total number of chillers in the application. This example uses Five (three headered chillers
plus two dedicated chillers).
b. Under Central Cooling Plant Central Cooling with Optimization > CHW Pump Piping Layout > Parallel Primary
CHW Pumps, select the total number of headered pumps in the application. This example uses Four.
c. Under Central Cooling Plant Central Cooling with Optimization > CHW Pump Piping Layout > CHW Pump
Speed, select either Single Speed Pump or Variable Speed Pump. This example uses Variable Speed Pump.
d. Under Central Cooling Plant Central Cooling with Optimization > Condenser Pump Piping Layout > Parallel
Primary CW Pumps, select the total number of headered pumps in the application. This example uses Four.
e. Under Central Cooling Plant Central Cooling with Optimization > Condenser Pump Piping Layout > CW Pump
Speed, select either Single Speed Pump or Variable Speed Pump. This example uses Variable Speed Pump.
f. Under Chillers > Chiller Speed, select either Constant Speed or Variable Speed. This example uses Variable
Speed.
g. Under Chillers, select both CHW Isolation Valve and CW Isolation Valve.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 125
Combination of Dedicated and Headered Piping
Figure 96: System Selection Wizard Mechanical System Selection Part 1
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 126
Combination of Dedicated and Headered Piping
Figure 97: System Selection Wizard Mechanical System Selection Part 2
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 127
Combination of Dedicated and Headered Piping
Figure 98: Details Device Info Table
3. Click Edit.
4. For each field of the Device Info table, enter the values for each of the five chillers.
Note: Leave the flow values at 0 for any dedicated chillers.
5. Click Apply.
6. Click Close.
7. Save the application.
8. Go to Deleting the Isolation Valve Outputs and Associated Commands for Dedicated Chillers.
Deleting the Isolation Valve Outputs and Associated Commands for Dedicated Chillers
For this step, first delete the isolation valve outputs, and then the Isolation Valve last-value (LV) commands and
isolation valve interlock commands for all isolation valves that the application does not have.
1. In the Application pane, under Outputs, select all isolation valve outputs for all dedicated chillers in the application.
Note: The isolation valve outputs are named CHxCHWISOV-C or CHxCWISOV-C, where x represents the
chiller number.
2. Hold down the Ctrl key, and click each Isolation Valve output.
Note: In this example, we select the Isolation Valve outputs named CH4CHWISOV-C, CH4CWISOV-C,
CH5CHWISOV-C, and CH5CHWISOV-C.
3. Right-click and select Delete (following figure). The Confirm screen appears.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 128
Combination of Dedicated and Headered Piping
Figure 99: Deleting the Isolation Valve Commands for Dedicated Chillers
4. Click Yes.
5. Under Output Control, select all isolation valve LV outputs for all dedicated chillers in the application.
Note: The isolation valve LV outputs are named Chlrx CHW ISO Valve LV or Chlrx CW ISO Valve LV, where
x represents the chiller number.
6. Hold down the Ctrl key, and click each Isolation Valve LV output.
Note: In this example, we select the Isolation Valve outputs named Chlr4 CHW ISO Valve LV, Chlr4 CW ISO
Valve LV, Chlr5 CHW ISO Valve LV, and Chlr5 CW ISO Valve LV, since chillers 4 and 5 are dedicated.
Figure 100: Deleting the Isolation Valve LV Commands for Dedicated Chillers
7. Right-click one of the selected outputs and select Delete. The Confirm screen appears.
8. Click Yes.
9. Under Setpoint/Miscellaneous, select all isolation valve interlock commands for all dedicated chillers in the
application.
Note: The isolation valve interlock commands are named CHW x IsoVlv Interlock or CW x IsoVlv Interlock,
where x represents the chiller number.
10. Hold down the Ctrl key, and click each Isolation Valve Interlock command.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 129
Combination of Dedicated and Headered Piping
Note: In this example, we select the isolation valve interlock commands named CHW 4 IsoVlv Interlock, CHW
5 IsoVlv Interlock, CW 4 IsoVlv Interlock, and CW 5 IsoVlv Interlock, since chillers 4 and 5 are dedicated.
Figure 101: Deleting the Isolation Valve Interlock Commands for Dedicated Chillers
11. Right-click one of the selected outputs and select Delete. The Confirm screen appears.
12. Click Yes.
13. Go to Adding Dedicated CHW Pump Output Control Modules.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 130
Combination of Dedicated and Headered Piping
Figure 102: New Module Selection Module Selection for Output Control
4. Click Finish. In this example, Pump Output Control-1 and Pump Output Control-2 appear in the Output Control
column.
5. Right-click Pump Output Control-1 and select Rename. The Rename screen appears.
6. Change the Standard Name to CHW Pmp x Control, where x represents the number of the first dedicated CHW
pump in the application. In this example, the Standard Name becomes CHW Pump 5 Control.
Figure 103: Renaming the Pump Output Control
7. Click OK. Pump Output Control-1 appears in the Output Control column as CHW Pump 5 Control.
8. Repeat the steps in this section for each dedicated CHW pump in the application. In this example, Pump Output
Control-1 is renamed CHW Pump 5 Control, and Pump Output Control-2 is renamed CHW Pump 6 Control.
9. Go to Editing the Logic of Each Dedicated CHW Pump (CHW Pmp x Control).
Editing the Logic of Each Dedicated CHW Pump (CHW Pmp x Control)
1. Under Output Control, right-click CHW Pump x Control, where x represents the first dedicated CHW pump in
the application (in this example, CHW Pump 5 Control), and select View Logic. The Logic tab opens within the
Application pane.
2. Right-click State and select Rename.
3. In the User Name field, enter PCHWP x-State, where x represents the pump number. In this example, the User
Name is CWP 5-State.
4. Click OK. The State block is renamed PCHWP 5-State.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 131
Combination of Dedicated and Headered Piping
Figure 104: Renaming the PCHWP State
11. In the Activities tree, select another CHW Pump x Control. Repeat the steps in this section for each dedicated
CHW pump (CHW Pump x Control) in the application. In this example, this section must be completed for both
CHW Pump 5 Control and CHW Pump 6 Control.
12. Go to Configuring the Application Connections for Dedicated CHW Pumps.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 132
Combination of Dedicated and Headered Piping
Figure 106: Making a Connection on the System Enable
5. Click OK.
6. Right-click Ramp Time and select Make Connection. The Select Reference screen appears.
7. Select Network Inputs > PCHWP-RAMP.
Figure 108: Selecting PCHWP-RAMP
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 133
Combination of Dedicated and Headered Piping
8. Click OK.
9. Right-click Command and select Make Connection. The Select Reference screen appears.
10. Select Logic > Output Control > Chiller Selector xx, where xx represents the number. In this example, Chiller
Selector 05 is selected.
11. In the right pane, select the appropriate CHW Iso Valve/Pump x Cmd, where x represents the number of the
specific isolation valve pump command that corresponds to the selected pump.
Note: The number of the appropriate isolation valve pump command might not match the number of the selected
pump. In this example, CHW Iso Valve/Pump 4 Cmd (the first dedicated chiller) is the appropriate choice
for CHW Pmp 5 Control (the first dedicated CHW pump).
Figure 109: Selecting the CHW Iso Valve/Pump x Cmd
4. Click Finish. The Last Value (Enum) modules appear in the Output Control column.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 134
Combination of Dedicated and Headered Piping
5. Right-click a Last Value (Enum) and select Rename. The Rename screen appears.
6. Enter a Standard Name of PCHWPx Command LV, where x represents the number of the first dedicated CHW
pump in the application. In this example, the Standard Name becomes PCHWP5 Command LV.
Figure 111: Renaming the Last Value (Enum)
7. Click OK.
8. Right-click PCHWPx Command LV, where x represents the number of the first dedicated CHW pump in the
application (in this example, PCHWP Command LV), and select View Details. The Details screen appears.
9. Click Edit.
10. In the right pane, in the Inputs row, click the drop-down box for Units and select Off/On. The Default Value
automatically sets to Off.
Note: Make sure you select Off/On, not OffOn, which is also a selection option.
11. In the Outputs row, under Units, click the drop-down box for Units and select Off/On. The Default Value
automatically sets to Off.
Note: Make sure you select Off/On, not OffOn, which is also an option.
Figure 112: Setting the PCHWPx Command LV Units to Off/On
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 135
Combination of Dedicated and Headered Piping
20. Go to Configuring Interlock Modules for the Dedicated CHW Pump.
4. Click Finish. The Equipment Interlock modules appear in the Setpoint/Miscellaneous column.
5. Right-click an Equipment Interlock module and select Rename. The Rename screen appears.
6. In the Standard Name field, type CHW Pump x Interlock, where x represents the number of the first dedicated
CHW pump in the application. In this example, the Standard Name becomes CHW Pump 5 Interlock.
Figure 114: Renaming the Equipment Interlock
7. Click OK.
8. Select the CHW Pump x Interlock, where x represents the number of the first dedicated CHW pump in the
application. In this example, CHW Pump 5 Interlock is selected.
9. In the Features pane, click the Connections tab.
10. Under Input, right-click Command and select Make Connection. The Select Reference screen appears.
11. Select Logic > Output Control > PCHWPx Command LV, where x represents the number of the first dedicated
CHW pump in the application. In this example, PCHWP5 Command LV is selected.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 136
Combination of Dedicated and Headered Piping
Figure 115: Selecting the Preset Value
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 137
Combination of Dedicated and Headered Piping
Figure 117: Setting the Default Values
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 138
Combination of Dedicated and Headered Piping
Adding CHW Water Pump Application Outputs
Add a PCHWPx-O module and a PCHWPx-C module for each dedicated CHW pump.
Note: If the application does not have variable speed CHW pumps, then PCHWPx-O does not need to be added.
1. In the Application pane, right-click Outputs and select New. The New Module Selection screen appears.
2. In the Filter field, enter PCHWPx, where x represents the number of the first dedicated CHW pump for the
application. In this example, PCHWP5 is entered.
3. In the row that lists User Name PCHWPx-C, enter a Count value of 1.
4. In the row that lists User Name PCHWPx-O, enter a Count value of 1.
Figure 118: Setting the Count of Primary Water Pump x
5. Click Finish.
6. Select the CHW Pump x Control, where x represents the number of the first dedicated CHW pump in the
application. In this example, CHW Pump 5 Control is selected.
7. In the Features pane, click the Connections tab
8. Under Output, right-click PCHWP x-C, and then select Make Connection. The Select Reference screen appears.
9. Select Hardware > Outputs > PCHWPx-C, where x represents the number of the first dedicated CHW pump
in the application. In Figure 135, PCHWP5-C is selected.
10. Under Output, right-click PCHWPx-O, and then select Make Connection. The Select Reference screen appears.
11. Select Hardware > Outputs > PCHWPx-O, where x represents the number of the first dedicated CHW pump in
the application. In Figure 135, PCHWP5-O is selected.
12. Repeat all the steps in this section for each dedicated CHW pump in your application. In Figure 135, the steps
must be completed for CHW Pump 5 Control and CHW Pump 6 Control, since these are the two dedicated
CHW pumps.
13. Go to Adding Dedicated CW Pump Output Control Modules.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 139
Combination of Dedicated and Headered Piping
Adding Dedicated CW Pump Output Control Modules
For this step, you are adding CW Pump Output Control modules for each of the dedicated CW pumps in the application.
1. In the Application pane, right-click Output Control and select New. The New Module Selection for Output Control
screen appears.
2. In the Filter field, type Pump Output Control.
3. Click the up arrow or enter the number of Pump Output Controls for the number of dedicated CW pumps in this
application. For this example, the number is 2.
Figure 119: New Module Selection Module Selection for Output Control
4. Click Finish. In this example, Pump Output Control-1 and Pump Output Control-2 appear in the Output Control
column.
5. Right-click Pump Output Control-1 and select Rename. The Rename screen appears.
6. Change the User Name to CW Pmp x Control, where x represents the number of the first dedicated CW pump
in the application. In this example, the User Name becomes CW Pmp 5 Control.
Figure 120: Renaming the Pump Output Control
7. Click OK. Pump Output Control-1 appears in the Output Control column as CW Pmp 5 Control.
8. Repeat the steps in this section for each dedicated CW pump in the application. In this example, Pump Output
Control-1 is renamed CW Pmp 5 Control, and Pump Output Control-2 is renamed CW Pmp 6 Control.
9. Go to Editing the Logic of Each Dedicated CW Pump (CW Pmp x Control).
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 140
Combination of Dedicated and Headered Piping
Editing the Logic of Each Dedicated CW Pump (CW Pmp x Control)
1. Under Output Control, right-click CW Pmp x Control, where x represents the first dedicated CW pump in the
application (in this example, CW Pmp 5 Control), and select View Logic. The Logic tab opens within the
Application pane.
2. Right-click State and select Rename.
3. In the User Name field, enter CWP x-State, where x represents the pump number. In this example, the User
Name is CWP 5-State.
4. Click OK. The State block is renamed CWP 5-State.
Figure 121: Renaming the CWP State
11. In the Activities tree, select another CW Pmp x Control. Repeat the steps in this section for each dedicated CW
pump (CW Pmp x Control) in the application. In this example, this section must be completed for both CW Pmp
5 Control and CW Pmp 6 Control.
12. Go to Configuring the Application Connections for Dedicated CW Pumps.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 141
Combination of Dedicated and Headered Piping
2. In the Features pane, click the Connections tab.
3. Under Input, right-click System Enable and select Make Connection. The Select Reference screen appears.
Figure 123: Making a Connection on the System Enable True
5. Click OK.
6. Right-click Ramp Time and select Make Connection. The Select Reference screen appears.
7. Select Network Inputs > CWVFD-RT.
Figure 125: Selecting CWVFD-RT
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 142
Combination of Dedicated and Headered Piping
8. Click OK.
9. Right-click Command and select Make Connection. The Select Reference screen appears.
10. Select Logic > Output Control > Chiller Selector xx, where xx represents the number of chillers. In this example,
Chiller Selector 05 is selected.
11. In the right pane, select the appropriate CW Iso Valve/Pump x Cmd, where x represents the number of the
specific isolation valve pump command that corresponds to the selected pump.
Note: The number of the appropriate isolation valve pump command might not match the number of the selected
pump. In this example, CW Iso Valve/Pump 4 Cmd (the first dedicated chiller) is the appropriate choice
for CW Pmp 5 Control (the first dedicated CW pump).
Figure 126: Selecting the CW Iso Valve/Pump x Cmd
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 143
Combination of Dedicated and Headered Piping
5. Click Finish. The Last Value (Enum) modules appear in the Output Control column.
6. Right-click a Last Value (Enum) and select Rename. The Rename screen appears.
7. Enter a User Name of CWPx Command LV, where x represents the number of the first dedicated CW pump
in the application. In this example, the User Name becomes CWP5 Command LV.
Figure 128: Renaming the Last Value (Enum)
8. Click OK.
9. Right-click CWPx Command LV, where x represents the number of the first dedicated CW pump in the application
(in this example, CWP5 Command LV), and select View Details. The Details screen appears.
10. Click Edit.
11. In the right pane, in the Inputs row, click the drop-down box for Units and select Off/On. The Default Value
automatically sets to Off.
Note: Make sure you select Off/On, not OffOn, which is also an option.
12. In the Outputs row, under Units, click the drop-down box for Units and select Off/On. The Default Value
automatically sets to Off.
Note: Make sure you select Off/On, not OffOn, which is also an option.
Figure 129: Setting the CWPx Command LV Units to Off/On
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 144
Combination of Dedicated and Headered Piping
Configuring Interlock Modules for the Dedicated CW Pumps
1. In the Application pane, right-click Setpoint/Miscellaneous and select New. The New Module Selection for
Setpoint/Miscellaneous screen appears.
2. In the Filter field, type Equipment Interlock.
3. Click the up arrow or type a Count value to indicate the number of dedicated CW pumps in the application. In
this example, you add two.
Figure 130: Setting the Count of the Equipment Interlock
4. Click Finish. The Equipment Interlock modules appear in the Setpoint/Miscellaneous column.
5. Right-click an Equipment Interlock module and select Rename. The Rename screen appears.
6. In the User Name field, type CW Pump x Interlock, where x represents the number of the first dedicated CW
pump in the application. In this example, the User Name becomes CW Pump 5 Interlock.
Figure 131: Renaming the Equipment Interlock
7. Click OK.
8. Select the CW Pump x Interlock, where x represents the number of the first dedicated CW pump in the
application. In this example, CW Pump 5 Interlock is selected.
9. In the Features pane, click the Connections tab.
10. Under Input, right-click Command and select Make Connection. The Select Reference screen appears.
11. Select Logic > Output Control > CWPx Command LV, where x represents the number of the first dedicated
CW pump in the application. In this example, CWP5 Command LV is selected.
Figure 132: Selecting the Preset Value
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 145
Combination of Dedicated and Headered Piping
12. Click OK.
13. Right-click Device Enable and select Make Connection. The Select Reference screen appears.
14. From the list, select Logic > Output Control > CW Pmp x Control, where x represents the number of the first
dedicated CW pump in the application. In this example, CW Pmp 5 Control is selected.
Figure 133: Selecting the CW Pmp x Control
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 146
Combination of Dedicated and Headered Piping
23. Go to Adding Condenser Water Pump Application Outputs.
5. Click Finish.
6. Select CW Pmp x Control, where x represents the number of the first dedicated CW pump in the application.
In Figure 135, CW Pump 5 Control is Selected.
7. In the Features pane, click the Connections tab.
8. Under Output, right-click CWPx-C, and then select Make Connection. The Select Reference screen appears.
9. Select Hardware > Outputs > CWPx-C, where x represents the number of the first dedicated CW pump in the
application. In this example, CWP5-C is selected.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 147
Combination of Dedicated and Headered Piping
Figure 136: Selecting CWPx-C for Hardware Outputs
10. Under Output, right-click CWPx-O, and then select Make Connection. The Select Reference screen appears.
11. Select Hardware > Outputs > CWPx-O, where x represents the number of the first dedicated CW pump in the
application. In this example, CWP5-O is selected.
Figure 137: Selecting CWPx-O for Hardware Outputs
12. Repeat all the steps in this section for each dedicated CW pump in your application. In this example, the steps
must be completed for CW Pmp 5 Control and CW Pmp 6 Control, since these are the two dedicated CW pumps.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 148
Combination of Dedicated and Headered Piping
13. Go to Adding a Dedicated Variable Speed CW Pump Control v61 Module.
3. Click Finish.
4. In the Application pane, under Output Control, right-click Variable Speed CW with Low Limit v61 and select
Rename. The Rename screen appears.
5. Change the Standard Name to Dedicated Variable Speed CW Pump Control v61, and then click OK.
Figure 139: Renaming Dedicated Variable Speed CW Pump Control v61
6. Right-click Network Inputs and select New. The New Module Selection screen appears.
7. In the row that lists a Standard Name of CS Input (Float), enter a Count value of 1.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 149
Combination of Dedicated and Headered Piping
Figure 140: Setting the Count of CS Input (Float)
8. Click Finish.
9. In the Application pane, under Network Inputs, right-click INPUT-FLOAT and select Rename. The Rename
screen appears.
10. Change the User Name to CWDT-SP.
Figure 141: Renaming the INPUT-FLOAT
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 150
Combination of Dedicated and Headered Piping
Note: Depending on your system setup, you may need to select Inputs instead of Network Inputs.
19. In the Features pane, click the Connections tab.
20. Under Output, right-click O1 and select Make Connection. The Select Reference screen appears.
21. Select Logic > Output Control > Dedicated Variable Speed CW with Low Limit v61.
22. In the right pane, select Low Limit Process Variable.
Figure 143: Selecting Low Limit Process Variable
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 151
Combination of Dedicated and Headered Piping
Figure 144: Setting the Count of Chillerx CHW Entering and Leaving
5. Click Finish.
6. Go to Configuring the CW Temperature Diff Calc Module.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 152
Combination of Dedicated and Headered Piping
Figure 145: Entering the Count Value of CW Temperature Diff Calc
3. Click Finish.
4. Go to Connecting the Output and Input on the CW Temperature Diff Calc Module.
6. Click OK.
7. Repeat this section for each dedicated CW pump in the application. In this example, this section must be completed
for Command 5 and Command 6.
8. Go to Connecting the CHxCWE-T and CHxCWL-T Inputs to the CW Temperature Diff Calc Module.
Connecting the CHxCWE-T and CHxCWL-T Inputs to the CW Temperature Diff Calc Module
Connect all the CHxCWE-T and CHxCWL-T inputs to the CW Temp Diff Calc module. This section applies only to
variable speed dedicated CW pumps. For any other pump speeds, skip this entire section.
1. In the Application screen, under Setpoint/Miscellaneous, select CW Temperature Diff Calc.
2. In the Features pane, click the Connections tab.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 153
Combination of Dedicated and Headered Piping
3. In the Input column, scroll to Chlrx CW Entering Temp Dest, where x represents a number of a dedicated
chiller in the application.
4. Right-click Chlrx CW Entering Temp Dest and select Make Connection. The Select Reference screen appears.
5. Select CHxCWE-T.
6. Click OK.
7. In the CW Temperature Diff Calc pane, in the Input column, scroll to Chlrx CW Leaving Temp Dest, where x
represents a number of a dedicated chiller in the application.
8. Right-click Chlrx CW Leaving Temp Dest and select Make Connection. The Select Reference screen appears.
9. Select CHxCWL-T.
10. Click OK.
11. Go to Connecting the Output and Input on the Dedicated Variable Speed CW Pump Control v61 Module.
Connecting the Output on the Dedicated Variable Speed CW Pump Control v61 Module
Connect the output of the CW Temp Diff Calc module to the process variable input of the Dedicated Variable
Speed CW Pump Control v61 module. This section applies only to variable speed dedicated CW pumps. For any
other pumps, skip this entire section.
1. In the Application pane, under Output Control, select Dedicated Variable Speed CW with Low Limit v61.
2. In the Features pane, click the Connections tab.
3. Under Input, right-click Process Variable and select Make Connection. The Select Reference screen appears.
4. Select Logic > Setpoint/Miscellaneous > CW Temperature Diff Calc.
Figure 147: Selecting the CW Temperature Diff Calc
5. Click OK.
6. Go to Copying the Custom Modules.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 154
Combination of Dedicated and Headered Piping
Copying the Custom Modules
1. Navigate to the FSC Solutions Database.
Note: You can find a direct link to the FSC Solutions Database in the article Where can I find the custom
modules for creating a CPO10 Application with a combination of Dedicated and Headered Piping?
2. Locate your custom modules in the FSC Solutions Database.
3. Copy the custom modules to the Custom Control Modules Folder on your local hard drive at MetasysIII > CCT
> UI.
Note: The custom modules must be copied to your local hard drive before continuing to the next step.
4. Go to Adding the Custom Module DedicatedHeadered_CWMinFlowModification.
4. Click Finish.
5. In the Application pane, under Output Control, right-click
DedicatedHeadered_CWMinFlowModification.caf.module and select Rename. The Rename screen appears.
6. Change the User Name to DedicatedHeadered_CWMinFlowModification.
Figure 149: Renaming the DedicatedHeadered_CWMinFlowModification Module
7. Click OK.
8. Go to Connecting the CW Min Flow Setpoint to the Min Flow Input.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 155
Combination of Dedicated and Headered Piping
Connecting the CW Min Flow Setpoint to the Min Flow Input
Connect the CW Min Flow Setpoint from the Chiller Selector to the Min Flow input of the custom module
DedicatedHeadered_CWMinFlowModification. This section applies only to variable speed dedicated CW pumps.
For any other pumps, skip this entire section.
1. In the Application pane, under Output Control, select DedicatedHeadered_CWMinFlowModification.
2. In the Features pane, click the Connections tab.
3. Under Input, right-click CW Min Flow and select Make Connection. The Select Reference screen appears.
4. Select Logic > Output Control > Chiller Selector xx, where xx represents the number of the first dedicated chiller
in the application.
5. In the right pane, select Min CW Flow Setpoint.
Figure 150: Connecting the CW Min Flow Setpoint to the Min Flow
6. Click OK.
7. Repeat the steps of this section for all dedicated chillers in the application.
8. Go to Setting the Default Value for the Capacity to Min Flow Multiplier Input.
Setting the Default Value for the Capacity to Min Flow Multiplier Input
The Capacity to Min Flow Multiplier is the ratio of the minimum flow of the CW Pump over the capacity of the CW
Pump. Set the default value for the Capacity to Min Flow Multiplier input of the custom module
DedicatedHeadered_CWMinFlowModification. This section applies only to variable speed dedicated CW pumps.
For any other pumps, skip this entire section.
1. In the Application pane, under Output Control, right-click DedicatedHeadered_CWMinFlowModification and
select View Details. The Details screen appears.
2. In the upper-left corner, click Edit. You may need to expand the right pane in order to view the Inputs and Outputs
sections.
3. In the Inputs section, in the row that lists a Name of Capacity to Min Flow Multiplier, enter the appropriate
Default Value for your system.
Note: Reference the rated capacity and minimum flow requirement for the pump you are using to determine
the appropriate Default Value for your system. For example, a CWP Capacity of the 300 gpm and a CWP
Min Flow of 2400 gpm gives a Capacity to Min Flow Multiplier of 0.8.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 156
Combination of Dedicated and Headered Piping
Figure 151: Setting the Default Value
4. Click Apply.
5. Click Close.
6. Go to Connecting the Commands of the DedicatedHeadered_CWMinFlowModification.
7. Click OK.
8. Repeat the steps of this section for each dedicated chiller in the application.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 157
Combination of Dedicated and Headered Piping
9. Go to Breaking the Connection of the CW Min Flow LV from the Headered Variable Speed CW Pump Control
v61.
Disconnecting the CW Min Flow LV from the Headered Variable Speed CW Pump Control
v61
Break the connection of the CW Minimum Flow LV block connected to the Headered Variable Speed CW Pump
Control v61 module.
1. In the Application pane, under Output Control, select Headered Variable Speed CW Pump Control v61.
2. In the Features pane, click the Connections tab.
3. Under Input, right-click Low Limit Setpoint and select Break Connection.
4. Go to Adding a Last-Value (Float) Block Named CW Modified Minimum Flow LV.
4. Click Finish.
5. In the Application screen, under Output Control, right-click Last-Value (Float) and select Rename. The Rename
screen appears.
6. Fill in a User Name of CW Modified Minimum Flow LV.
Figure 154: Renaming the Last Value (Float)
7. Click OK.
8. Go to Connecting the Input of the CW Modified Minimum Flow LV to the DedicatedHeadered_MinFlowModification
Module Output.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 158
Combination of Dedicated and Headered Piping
Connecting the Input of the CW Modified Minimum Flow LV to the
DedicatedHeadered_MinFlowModification Module Output
Connect the Input of the CW Modified Minimum Flow LV to the DedicatedHeadered_MinFlowModification Module
Output. This section applies only to variable speed dedicated CW pumps. For any other pumps, skip this entire
section.
1. In the Application pane, under Output Control, select CW Modified Minimum Flow LV.
2. In the Features pane, click the Connections tab.
3. Under Input, right-click Input and select Make Connection. The Select Reference screen appears.
4. Select Logic > Output Control > DedicatedHeadered_CWMinFlowModification.
Figure 155: Connecting the ModifiedCWMinFlow Input to the
DedicatedHeadered_CWMinFlowModification Output
5. Click OK.
6. Go to Connecting the Output of the CW Modified Minimum Flow LV to the Variable Speed Modules.
Connecting the Output of the CW Modified Minimum Flow LV to the Variable Speed Modules
Connect the output of the CW Modified Minimum Flow LV to both the dedicated and headered variable speed
modules as the Low Limit Setpoint. This section applies only to variable speed dedicated CW pumps. For any
other pumps, skip this entire section.
1. In the Application pane, under Output Control, select CW Modified Minimum Flow LV.
2. In the Features pane, click the Connections tab.
3. Under Output, right-click Present Value and select Make Connection. The Select Reference screen appears.
4. Select Logic > Output Control > Dedicated Variable Speed CW Pump Control with Low Limit v61.
5. In the right pane, select Low Limit Setpoint.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 159
Combination of Dedicated and Headered Piping
Figure 156: Connecting the Output of the CW Modified Minimum Flow LV to the Variable Speed
Modules
6. Click OK.
7. Make a second connection. Under Output, right-click Present Value and select Make Connection. The Select
Reference screen appears.
8. Select Logic > Output Control > Headered Variable Speed CW Pump Control v61. In the right pane, select
Low Limit Setpoint.
9. Click OK.
10. Go to Adding the Custom Module DedicatedHeadered_TowerRequiredFlowModification.
3. Click Finish.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 160
Combination of Dedicated and Headered Piping
4. In the Application pane, under Output Control, right-click
DedicatedHeadered_TowerRequiredFlowModification.caf.module and select Rename. The Rename screen
appears.
5. Change the User Name to DedicatedHeadered_TowerRequiredFlowModification.
Figure 158: Renaming the DedicatedHeadered_TowerRequiredFlowModification
6. Under Input on the Connections Tab, right-click Dedicated CWPx Cmd, and then select Make Connection.
7. Select Logic > Output Control > Chiller Selector xx.
Note: xx represents the number of chillers in the application.
8. In the right pane, select CW Iso Valve/Pump x Cmd, and then select OK.
Note: x represents the number of the dedicated chiller.
Note: In the example, CW Iso Valve/Pump 4 Cmd is connected to Dedicated CWP5 Cmd on the
DedicatedHeadered_TowerRequiredFlowModification module.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 161
Combination of Dedicated and Headered Piping
Figure 160: Selecting the CW Iso Valve/Pump x Cmd
9. Repeats Step 6 though Step 8 for each dedicated chiller in the application.
10. In the Application pane, under Output Control, right click DedicatedHeadered_TowerRequiredFlowModification.
11. Select View Details. The Details window opens.
12. Under Inputs, set the Default Value of any dedicated CW pump capacity to Dedicated CWPx Capacity.
Note: x is the identifying number of a dedicated pump.
Figure 161: Setting the Default Value of Dedicated CW Pumps
13. In the Application pane, under Output Control, select Tower Required Flow LV.
14. In the Features pane, click the Connections tab.
15. Under Input, right-click Input, and then select Break Connection.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 162
Combination of Dedicated and Headered Piping
Figure 162: Breaking the Tower Required Flow LV Connection
21. Under Output, right-click Dedicated CWPx Capacity and select Make Connection. The Select Reference
screen appears.
Note: x represents the identifying number for a dedicated CW pump in the application.
22. Select Logic > Output Control > DedicatedHeadered_CWMinFlowModification.
23. In the right pane, select Dedicated CWPx Capacity. In this example, CWP5 and CWP6 are dedicated, so they
are connected.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 163
Combination of Dedicated and Headered Piping
Figure 164: Connecting a Dedicated Chiller
3. Click Finish.
4. In the Application pane, under Output Control, right-click
DedicatedHeadered_CWPercentCommandModification.caf.module and select Rename. The Rename screen
appears.
5. Change the User Name to DedicatedHeadered_CWPercentCommandModification.
Figure 166: Renaming the Custom Module
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 164
Combination of Dedicated and Headered Piping
Connecting the DedicatedHeadered_CWPercentCommandModification Module
1. In the Application pane, under Output Control, select DedicatedHeadered_CWPercentCommandModification.
2. In the Features pane, click the Connections tab.
3. Under Input, right-click Headered CW Percent Command and select Make Connection. The Select Reference
screen appears.
4. Select Logic > Output Control > Headered Variable Speed CW Pump Control v61.
5. In the right pane, select Percent Cmd.
Figure 167: Connecting to the Dedicated Headered Pump
6. In the Application pane, under Output Control, select Headered Variable Speed CW Pump Control v61.
7. In the Features pane, click the Connections tab.
8. Under Output, right-click each output and select Break Connection (except for the
DedicatedHeadered_CWPercentCommandModification connection).
Figure 168: Breaking Connections
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 165
Combination of Dedicated and Headered Piping
Figure 169: Connecting to the Dedicated Variable Speed CW Pump Control with Low Limit v61
14. Under Output, right-click CW Percent Command and select Make Connection. The Select Reference screen
appears.
15. Select Logic > Output Control > CW Pmp x Control.
Note: x represents an indicating number for each dedicated and headered CW pump in the application.
16. In the right pane, select Percent Cmd.
17. Repeat Step 15 and Step 16 for each CW pump.
Figure 170: Connecting to each CW Pump Control
18. Under Output, right-click CW Percent Command and select Make Connection. The Select Reference screen
appears.
19. Select Logic > Output Control > CWP Selector xx.
20. In the right pane, select Process Variable.
Figure 171: Connecting to a CWP Selector
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 166
Combination of Dedicated and Headered Piping
21. Go to Adding the Custom Module DedicatedHeadered_MainLogic.
3. Click Finish.
4. In the Application pane, under Output Control, right-click DedicatedHeadered_MainLogic.caf.module and
select Rename. The Rename screen appears.
5. Change the User Name to DedicatedHeadered_MainLogic.
Figure 173: Renaming Main Logic Module
3. Click Finish.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 167
Combination of Dedicated and Headered Piping
4. In the Application pane, under Output Control, right-click Last Value (Float) and select Rename. The Rename
screen appears.
5. Change the User Name to CW Commanded Flow LV.
6. In the Application pane, under Output Control, right-click Last Value (Float) and select Rename. The Rename
screen appears.
7. Change the User Name to CHW Commanded Flow LV.
8. In the Application pane, under Output Control, select DedicatedHeadered_MainLogic.
9. In the Features pane, click the Connections tab.
10. Under Input, right-click CWLV and select Make Connection. The Select Reference screen appears.
11. Select Logic > Output Control > Chiller Selector xx.
Note: xx represents the number of chiller in the application.
12. In the right pane, select Required CW Flow.
Figure 175: Selecting the Required CW Flow
13. Under Input, right-click CWMinLV and select Make Connection. The Select Reference screen appears.
14. Select Logic > Output Control > Chiller Selector xx.
15. In the right pane, select Min CW Flow Setpoint.
Figure 176: Selecting the Min CW Flow Setpoint
16. Under Input, right-click CHWLV and select Make Connection. The Select Reference screen appears.
17. Select Logic > Output Control > Chiller Selector.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 168
Combination of Dedicated and Headered Piping
18. In the right pane, select Required CHW Flow.
Figure 177: Selecting Required CHW Flow
19. Under Input, right-click CHWMinLV and select Make Connection. The Select Reference screen appears.
20. Select Logic > Output Control > Chiller Selector xx.
21. In the right pane, select Min CHW Flow Setpoint.
Figure 178: Selecting Min CHW Flow Setpoint
22. Under Input, right-click CWIsoVlvCmdx and select Make Connection. The Select Reference screen appears.
Note: x represents the number of a headered chiller in the application.
23. Select Logic > Output Control > Chiller Selector xx.
24. In the right pane, select CW Iso Valve/Pump x Cmd.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 169
Combination of Dedicated and Headered Piping
Figure 179: Selecting CW Iso Valve/Pump x Cmd
25. Repeat Step 22 through Step 24 for each chiller with headered pumping.
26. Under Input, right-click CHWIsoVlvCmdx and select Make Connection. The Select Reference screen appears.
Note: x represents the identifying number of each headered chiller in the application.
27. Select Logic > Output Control > Chiller Selector.
28. In the right pane, select CHW Iso Valve/Pump x Cmd.
Figure 180: Selecting CHW Iso Valve/Pump x Cmd
29. Repeat Step 26 through Step 28 for each chiller with headered pumping.
30. Under Input, right-click CW Commanded Flow and select Make Connection. The Select Reference screen
appears.
31. Select Logic > Output Control > CWP Selector xx.
Note: xx represents a number of a headered pump in the application.
32. In the right pane, select Current Capacity.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 170
Combination of Dedicated and Headered Piping
Figure 181: Selecting Current Capacity for a CWP Selector
38. Under Output, right-click CW Required Flow and select Make Connection. The Select Reference screen
appears.
39. Select Logic > Output Control > CW Cap Match LV.
40. In the right pane, select Input.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 171
Combination of Dedicated and Headered Piping
Figure 183: Selecting Input for CW Cap Match LV
41. Under Output, right-click CW Min Flow Setpoint and select Make Connection. The Select Reference screen
appears.
42. Select Logic > Output Control > CW Minimum Flow LV.
43. In the right pane, select Input.
Figure 184: Selecting Input for CW Minimum Flow LV
44. Under Output, right-click CHW Min Flow Setpoint and select Make Connection. The Select Reference screen
appears.
45. Select Logic > Output Control > CHW Pump Shed OK LV.
46. In the right pane, select Input.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 172
Combination of Dedicated and Headered Piping
Figure 185: Selecting Input for CHW Pump Shed OK LV
47. Under Output, right-click CHWIsoVlvCmdx and select Make Connection. The Select Reference screen appears.
Note: x represents a number of a headered chiller in the application.
48. Select Logic > Output Control > Chlrx Control.
49. In the right pane, select Isolation Valve Command.
50. Repeat Steps 45 through Step 47 for each chiller with headered pumping.
Figure 186: Selecting Isolation Valve Command for Chlr x Control
51. Under Output, right-click CHW Commanded Flow and select Make Connection. The Select Reference screen
appears.
52. Select Logic > Output Control > CHW Commanded Flow LV.
53. In the right pane, select Input.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 173
Combination of Dedicated and Headered Piping
Figure 187: Selecting Input for CHW Command Flow LV
54. Under Output, right-click CW Commanded Flow and select Make Connection. The Select Reference screen
appears.
55. Select Logic > Output Control > CW Commanded Flow LV.
56. In the right pane, select Input.
Figure 188: Selecting Input for CW Command Flow LV
57. In the Application pane, under Output Control, select CW Commanded Flow LV.
58. In the Features pane, click the Connections tab.
59. Under Output, right-click Present Value, and then select Make Connection. The Select Reference screen
appears.
60. Select Logic > Output Control > Chiller Selector xx.
Note: xx represents the number of chiller in the application.
61. In the right pane, select CW Commanded Flow.
62. In the Application pane, under Output Control, select CHW Commanded Flow LV.
63. In the Features pane, click the Connections tab.
64. Under Output, right-click Present Value, and then select Make Connection. The Select Reference screen
appears.
65. Select Logic > Output Control > Chiller Selector xx.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 174
Combination of Dedicated and Headered Piping
Note: xx represents the number of chiller in the application.
66. In the right pane, select CHW Commanded Flow.
67. Go to Adding the Custom Module DedicatedHeadered_ChillerCommands.
3. Click Finish.
4. In the Application pane, under Output Control, right-click DedicatedHeadered_ChillerCommands.caf.module
and select Rename. The Rename screen appears.
5. Change the User Name to DedicatedHeadered_ChillerCommands.
Figure 190: Renaming the DedicatedHeadered_ChilerCommands Module
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 175
Combination of Dedicated and Headered Piping
9. In the Application pane, under Output Control, right-click DedicatedHeadered_ChillerCommands, and then
select View Details. The details window appears.
10. Under Inputs, set the Pump Delay and IsoVlv Stroke Time default values to match the Pump Delay and
IsoVlvStrokeTime values from the Chiller Selector.
Figure 191: Matching the Input Values
15. Repeat Step 12 through Step 14 for each dedicated chiller in the application.
16. In the Features pane, click the Connections tab.
17. Under Output, right-click DedicatedChillerCmdx, and then select Make Connection.
Note: x represents a number of a dedicated chiller in the application.
18. Select Logic > Output Control > Chlrx Control.
19. In the right pane, select Chiller Command.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 176
Combination of Dedicated and Headered Piping
Figure 193: Selecting Chiller Command for Chlrx Control
3. Click Finish.
4. In the Application pane, under Output Control, right-click
DedicatedHeadered_MinCHWFlowModification.caf.module and select Rename. The Rename screen appears.
5. Change the User Name to DedicatedHeadered_MinCHWFlowModification.
Figure 195: Renaming the DedicatedHeadered_MinCHWFlowModification Module
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 177
Combination of Dedicated and Headered Piping
Connecting the DedicatedHeadered_MinCHWFlowModification Module
1. In the Application pane, under Output Control, select VF Primary Min Flow Control.
2. In the Features pane, click the Connections tab.
3. Under Input, right-click Setpoint, and then select Break Connection
Figure 196: Breaking Setpoint Connections
9. Under Input, right-click Dedicated CHWP x Cmd, and then select Make Connection.
Note: x represents a number of a dedicated CHW pump in the application.
10. Select Logic > Output Control > Chiller Selector xx.
Note: xx represents the number of chillers in the application
11. In the right pane, select CHW Iso Valve/Pump x Cmd.
Note: x represents a number of a dedicated CHW pump in the application.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 178
Combination of Dedicated and Headered Piping
Figure 198: Selecting the CHW Iso Valve/Pump x Cmd for Chiller Selector xx
12. Repeat Step 9 through Step 11 for each dedicated CHW Pump in the application.
13. In the Application pane, under Output Control, right-click DedicatedHeadered_MinCHWFlowModification,
and then select View Details. The details window appears.
14. Under Inputs, set the Dedicated CHWPx Min Flow input Default Value to match the values of the dedicated
CHW pump's minimum flow in the application.
Note: x represents a number of a dedicated CHW pump.
Figure 199: Setting the Dedicated CHWPx Min Flow to a Default Value
15. Select Logic > Output Control > VF Primary Min Flow Control.
16. Click the Connections tab.
17. Under Inputs, right-click Setpoint, and then select Break Connection.
18. Under Output, right-click Modified Min CHW Flow Setpoint, and then select Make Connection.
19. Select Logic > Output Control > VF Primary Min Flow Control.
20. In the right pane, select Setpoint.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 179
Combination of Dedicated and Headered Piping
Figure 200: Selecting the Setpoint for VF Primary Min Flow Control
6. Under Input, right-click Pump B Enable x, and then select Make Connection.
Note: x represents a number of a dedicated CHW pump in the application.
7. Select Logic > Setpoint/Miscellaneous > CHW Pump x Interlock.
8. In the right pane, select Device Enable, and then click OK.
Johnson Controls Central Plant Optimization 10 Application Note: Appendix: Creating an Application with a 180
Combination of Dedicated and Headered Piping
Figure 202: Selecting Device Enable for CHW Pump x Interlock
9. Repeat Step 3 through Step 8 for each dedicated pump in the application.
The configuration is complete.
Building Efficiency
507 E. Michigan Street, Milwaukee, WI 53202
Metasys and Johnson Controls are registered trademarks of Johnson Controls, Inc.
All other marks herein are the marks of their respective owners. 2015 Johnson Controls, Inc.