E-30-01
Apr. 2008
WATER SUPPLIES DEPARTMENT
STANDARD SPECIFICATION E-30-01
ELECTRICAL CABLES
1. GENERAL
1.1 Climate Conditions
The cables supplied shall be suitable for operation in tropical climate with maximum
relative humidity of 100% and for continuous operation at an ambient temperature of
40C.
1.2 Standards
1.2.1 The cables supplied shall comply with this Specification, the latest edition of the
General Specification for Electrical Installation in Government Buildings of the
HKSAR and the latest version of the following standards:
IEC 60227-3 Polyvinyl chloride insulated cables of rated voltages up to and
including 4501750V - Part 3: Non-sheathed cables for fixed wiring
IEC 60227-4 Polyvinyl chloride insulated cables of rated voltages up to and
including 4501750V - Part 4: Sheathed cables for fixed wiring
IEC 60228 Conductors of insulated cables
IEC 60502-1 Power cables with extruded insulation and their accessories for
rated voltages from lkV (Um=1.2kV) up to 30kV (Um=36kV)
Part 1: Cables for rated voltages of lkV (Um=1.2kV) and 3kV
(Um=3.6kV)
IEC 60502-2 Power cables with extruded insulation and their accessories for
rated voltages from lkV (Um=1.2kV) up to 30kV (Um=36kV)
Part 2: Cables for rated voltages from 6kV (Um=7.2kV) up to 30kV
(Um=36kV)
IEC 60702-1 Mineral insulated cables and their terminations with a rated voltage
not exceeding 750V - Part 1: Cables
IEC 60702-2 Mineral insulated cables and their terminations with a rated voltage
not exceeding 750V - Part 2: Terminations
IEC 60708 Low-frequency cables with polyolefin insulation and moisture
barrier polyolefin sheath
-2
E-30-01
Apr. 2008
1.2.2 Subject to the agreement of the Engineer, cables complying with the following British
Standards (BS) may also be accepted:
BS 5467 Thermosetting insulated, armoured cables for voltages of
60011000Vand 1900/3300V
BS 6004 PVC insulated, non-armoured cables for voltages up to and
including 4501750V, for electric power, lighting and internal wiring
BS 6234 Specification for polyethylene insulation and sheath of electric
cables
BS 6346 PVC insulated, armoured cables for voltages of 60011 OOOV and
1900/3300V
BS 6387 Specification for performance requirements for cables required to
maintain circuit integrity under fire conditions
BS 6622 Armoured cables with thermosetting insulation for rated voltages
from 3.8/6.6kV to 19/33kV
BS 6724 Thermosetting insulated, armoured cables for voltages of
60011000Vand 1900/3300V, having low emission of smoke and
corrosive gases when affected by fire
BS 7846 600/1000V armoured fire-resistant cables having thermosetting
insulation and low emission of smoke and corrosive gases when
affected by fire
1.2.3 Other equivalent standards issued by internationally recognized engineering
institutions or organizations may also be accepted. Manufacturers offering cables to
other standards shall provide duplicate copies of such standards in English together
with full details of any deviations from the standards referred above for evaluation.
The quality of the cables offered shall be equal to or better than that specified in the
standards stated above.
1.3 Test Certification
Type test certificates and sample test reports shall be submitted after the award of
contract and before the delivery of cables for approval. Certificates covering only part
of the specified requirements or not certified by a competent testing authority will not
be accepted.
The test samples shall be of the same design and manufacturing process as to the cable
supplied under the contract and shall be manufactured within a period not earlier than
18 months from the date of submission of the test reports.
-3
E-30-01
Apr. 2008
The following tests shall be covered in the type test certificates/sample test reports
submitted:
1.3.1 Cross-linked Polyethylene (XLPE) Insulated Cable
(a) Physical properties of insulation and sheaths
(b) Fire tests
(c) Conductor properties
(d) Armour resistance and physical properties
(e) Routine tests
1.3.2 PVC-insulated Cables (Non-armoured)
(a) Physical properties of PVC insulation
(b) Physical properties of sheath
(c) Conductor properties
(d) Fire tests
(e) Long term insulation resistance
(1) Routine tests
1.3.3 PVC-insulated Power and Control Cables (Armoured or Non-armoured)
(a) Insulation tests
(b) Oversheath tests
(c) Conductor properties
(d) Armour resistance and physical properties
(e) Fire tests
(1) Routine tests
1.3.4 PVC-insulated Cables for Panel Wiring
(a) Conductor properties
(b) Insulation tests
(c) Fire tests
1.3.5 Telecommunication Cables
(a) Electrical tests
(b) Mechanical tests
1.4 Cable Identification
The oversheath of cables shall be embossed with the following identification at
approximately 1 metre interval :
(a) manufacturer's name and/or trademark,
(b) voltage designation,
(c) cable type, and
(d) conductor size.
-4
E-30-01
Apr. 2008
1.5 High Voltage Cables
Cables with rated voltage of 3300V or above shall be directly delivered from the cable
manufacturer's works. Surplus cables which have been supplied to other projects will
not be accepted unless otherwise approved by the Engineer.
1.6 Packing and Shipping
Cables shall be wound onto robust drums and adequately protected and packed so as
to minimize the possibility of damage during shipment and handling. Fabricated and
painted steel drums shall be used if the gross weight exceeds 8 tonnes. All drums and
packing supplied shall be suitable to withstand rough handling and storage for long
periods outdoors and under adverse climatic conditions. All drums, packing cases and
other such materials supplied shall be non-returnable. Both ends of each cable shall be
sealed to prevent ingress of moisture and to facilitate testing. For the convenience of
testing, the inner end of the cable shall be brought through the side of the drum and
protected by a suitable cover.
Each cable drum shall be clearly stencilled with the purchase order number, drum
number, voltage designation, cable type, conductor size and length, and gross and nett
weight. Each packing case shall be clearly marked so that it can be easily identified
against the relevant shipping advice note.
The packing list and the works test reports shall be submitted with the delivered
cables for verification and acceptance.
2. XLPE INSULATED CABLE
2.1 Applicable Standards
XLPE insulated cable of voltage rating up to 1900/3300V shall comply with IEC
60502-1 or BS 5467.
XLPE insulated cable of voltage rating 6600111 OOOV shall comply with IEC 60502-2
or BS 6622.
2.2 Conductor
The conductor shall be high conductivity, stranded, plain, and annealed copper
complying with IEC 60228. Four-core cables shall have full size neutral conductors.
2.3 Insulation
The insulation shall consist of extruded XLPE.
2.4 Bedding
The bedding shall consist of an extruded PVC or polyethylene.
-5
E-30-01
Apr. 2008
2.5 Identification of Core
Cores of cables shall be identified continuously throughout its entire length.
Identification of cores shall take the form of appropriate color or number codes in
accordance with the following requirements:
Function of core Color code Number code
Phase conductor of a single Brown L
phase circuit
Phase conductor of a Brown or black or grey Ll or L2 or L3 according
three-phase circuit according to phase to phase concerned
concerned
Neutral conductor Blue N
Core used as protective conductors shall have an exclusive color identification of
Igreen-and-yellow.
2.6 Armour
Armour for multi-core cable shall consist of single layer of galvanised steel wires.
Armour for single core cable shall consist of single layer of aluminum wires or strips.
2.7 Oversheath
The oversheath shall consist of an extruded layer of black PVC. The oversheath shall
be termite proof and shall have flame retardant characteristics.
3. PVC INSULATED CABLE
3.1 Applicable Standards
PVC insulated non-armoured cables for power and lighting shall comply with IEC
60227-3 or BS 6004.
PVC insulated power and control cables shall comply with IEC 60502-1 or BS 6346.
PVC insulated cables for panel wiring shall comply with IEC 60227-3 or BS 6004.
3.2 Conductor
The conductor shall be of stranded, plain, annealed copper complying with IEC 60228.
Four core cables shall have full size neutral conductors.
-6
E-30-01
Apr. 2008
3.3 Insulation
The insulation shall be extruded PVC compound.
3.4 Bedding
The bedding shall consist of an extruded PVC.
3.5 Identification of Core
Requirements are same as those specified in Clause 2.5.
3.6 Armour
The wire armour shall consist of a single-layer galvanised steel wires for multi-core
cables and aluminum wires or strips for single-core cable.
3.7 Oversheath
The oversheath shall consist of an extruded PVc. The oversheath shall be of black
colour, termite proof and shall have flame retardant characteristics.
4. TELECOMMUNICAnON CABLE
4.1 Applicable Standards
Telecommunication cables shall comply with IEC 60708.
4.2 Conductor
The conductor shall be of high conductivity, plain, annealed copper complying with
IEC 60228.
4.3 Insulation
The insulation shall be of solid polyethylene compound. The insulation colours shall
be easily identifiable.
A minimum of 2 pairs of cables shall be individually screened by laminated
aluminumlPETP tape. Pairs shall be disposed with different lays to keep cross talk
between pairs to a minimum. The interlayer lapping tape shall be of polyethylene
terephthalate.
4.4 Armour
Where specified, armouring shall be of a single-layer galvanized steel wires laid
helically over the sheathed cable. The armour shall be protected against corrosion by
an extruded oversheath of black PVc.
-7
E-30-01
Apr. 2008
4.5 Oversheath
The oversheath shall be extruded as a continuous, seamless, close fitting tube of PVC.
The sheath shall be black colour, termite proof and shall have flame retardant
characteristic.
5. INSPECTION & TESTING IN MANUFACTURER'S WORKS
5.1 General
Where specified in the Particular Specification, the cables supplied shall be subject to
witnessed tests and inspections at the manufacturer's works by an Independent
Inspection Body (lIB) approved by the Purchaser.
A report shall be produced by the cable manufacturer at the time of testing giving the
readings obtained, performance calculations and any other details required to verify
that the equipment under test meets the requirements of this Specification. If the lIB is
employed to witness the tests, he shall endorse the test report with the original sent to
the Purchaser immediately after the tests and a copy sent to the contractor.
5.2 Inspection and Test Requirements
The following inspection/tests shall be carried out on the supplied cables to verify
compliance with the Specification:
Visual InspectionlExamination
(a) Identification of cable and cores
(b) Laying-up of cable cores
(c) Conductor material and construction
(d) Cable construction and overall dimensions
(e) Sealing and markings of cable ends
(t) Markings on drum
Works Test
(a) Dielectric test (except for telecommunication cables)
(b) Insulation resistance test
(c) Conductor resistance test
6. INFORMATION TO BE SUBMITTED UPON REQUEST
6.1 Technical Particulars
(a) Catalogues of the cables showing technical specifications, constructional
details, materials used, current carrying capacities, etc. shall be submitted upon
request by the Purchaser.
-8
E-30-01
Apr. 2008
(b) Recommended bending radius, depth of direct laying, method of installation
when direct laid in ground, in cable duct and in air.
(c) Cable group rating at different spacing. Effect of thermal resistivity of soil.
(d) Dimensions and weights, constructional details, cross-section drawing.
(e) Cable jointing and termination instructions, stripping dimensions, bonding of
semi-conducting layers etc.
- End of this Specification