S11 Engineering Specifications
S11 Engineering Specifications
Engineering Specification
PART 1 - GENERAL
1.0 Scope
This specification shall cover Toshiba S11 AC Variable Frequency Drives, 6 pulse for 3-
phase 200-240VAC, 380-500VAC and single phase 200V to 240VAC.
1.1 References
1.2 Submittal
Submittals shall include Toshiba standard operation manual. Schematics can be obtained
from factory upon request.
2.0 General
Page 1 of 6
S11 Adjustable Speed Drive
Engineering Specification
A. The drive shall have True Torque Control with Automatic energy-saving control.
B. The drive shall have two (2) frequency priority selection features.
C. The drive shall be capable of setting both upper and lower limit frequencies.
D. The ASD shall have a PWM carrier frequency adjustment range of 0.5 to 16.0
kHz. The default value is 12.0 kHz. The maximum acceptable full speed carrier
frequency (60 Hz) with no derating shall be 4 kHz.
E. The drive shall be capable of PID set point control.
F. One touch setup for motor operated potentiometer and three wire control.
G. The drive shall be able to start and stop from a two-wire control (dry contacts),
three wire momentary contact closure, keypad, and serial interface.
H. The drive shall have an adjustable retry function after a fault. The auto retry
function shall selectable up to 10 retry attempts.
I. The drive shall have two programmable functions of the following: acceleration
and deceleration rates, acceleration and deceleration patterns, electronic thermal
protection settings, base frequencies, voltage boosts, and stall protection
selections which can be chosen while running to run motor A or motor B.
Page 2 of 6
S11 Adjustable Speed Drive
Engineering Specification
A. The drive shall contain two separate acceleration/deceleration times (0.1 to 3200
seconds) with choice of linear and two S-curves.
B. The drive shall contain fifteen programmable preset speeds, which can be
activated from the terminal inputs or host computer.
C. The drive shall restart into a rotating motor operating in either the forward or
reverse direction and match that frequency.
D. The drive shall have adjustable soft stall (10% - 199%) which reduces frequency
and voltage of the inverter to sustain a run in an overload situation.
E. The drive shall have adjustable UL listed electronic overload protection (10% -
100%).
A. The drive shall contain three critical frequency jump points with individual
bandwidth.
B. The drive shall be UL rated for no less that 5,000 AIC without the use of input
fuses.
C. The drive shall have external fault input.
D. The drive shall be capable of re-setting faults remotely and locally.
E. The drive shall alarm in the following operating conditions:
1) Stall Prevention
2) Over voltage
3) Overload
4) Under-Voltage
5) Executing retry
Page 3 of 6
S11 Adjustable Speed Drive
Engineering Specification
6) Upper / Lower Limit setting error
Page 4 of 6
S11 Adjustable Speed Drive
Engineering Specification
6) Output Voltage
7) Input terminal status
8) Output terminal status
9) CPU version
10) Memory version
11) Four most recent faults
12) Cumulative run timer
13) Torque Current
14) PID Feedback Value
15) Drive Overload Ratio
16) DBR Overload Ratio
17) Input Power
18) Output Power
1) RS485
2) RS232
3) Modbus RTU
4) Modbus+
5) Devicenet
6) Profibus DP
7) Ethernet
8) Metasys
Page 5 of 6
S11 Adjustable Speed Drive
Engineering Specification
Page 6 of 6