The Melsec FX Series: Mitsubishi Electric
The Melsec FX Series: Mitsubishi Electric
The Melsec FX Series: Mitsubishi Electric
5 3
4 12
7
6
0
IN
Square pulse output
ER N ER
FX BASE UNITS
R W
PO
R
U
O
R
(this applies only to transistor units.)
R
I
4M
H
-1
IS
1S
4 12 T
FX
U
B
0 O
5 3
U
S
IT
Two high speed pulse
M
Integration of interface, exten-
C
SE
outputs for frequencies up to
EL
M
sion, and functions adapters for 100 kHz for outputting
direct installation in the base unit and controlling stepping motors
Integrated real-time
clock with year, month,
day and time
Integrated serial RS422
interface for direct commu-
nication with computers
Your PLC programs are stored in a main-
tenance-free EEPROM user memory
with a capacity of 2,000 program steps,
Flexible installation with the so there is no need for a backup battery
integrated DIN rail adapter and to protect against power failures.
Password access protection
screw fastening holes for mount- facility for effective protection
ing on flat surfaces of your intellectual property.
Terminal cover
Fixing hole
Connection of the
power supply Terminals for
digital inputs
Adapter interface S/S X1 X3 X5 X7
LEDs for indicating
100-240 X2 X4 X6
L N X0
VAC
0 1 2 3 the input status
4 5 6 7
Slot for adapter IN
RUN/STOP switch
POWER
2 analog potentiometers RUN
ERROR LEDs for indicating the
Connection for FX1S-14MR
operating status
programming units OUT
Service voltage 0V Y0 Y1 Y2 Y4
Y5
14MR
-ES/UL
the output status
COM2 Y3
24V COM0 COM1
source MITSUBISHI
Housing cover
Terminals for
digital outputs
MITSUBISHI ELECTRIC 13
/// BASE UNITS FX1S SERIES
Special Features:
2
X3 X5 X7
S/S X1
100-240 X2 X4 X6
L N X0
VAC
0 1 2 3
4 5 6 7
IN Integrated power supply (AC or DC powered)
MITSUBISHI
Maintenance-free EEPROM memory
FX BASE UNITS
POWER
RUN
ERROR
Ample memory capacity (2000 steps) and device ranges
FX1S-14MR
High-speed operations
OUT
0 1 2 3
Incorporated positioning control
4 5
0V Y0 Y1
24V COM0 COM1C
Y2
OM2 Y3
Y4
Y5
14MR
-ES/UL Integrated real-time clock
System upgrades by exchangeable interface and I/O adapter
boards for direct fitting into the base unit
LEDs for indicating the input and output status
Standard programming unit interface
User-friendly programming systems, including IEC 61131.3
(EN 61131.3)-compatible programming software, HMIs and
hand-held programming units
14 MITSUBISHI ELECTRIC
BASE UNITS FX1S SERIES ///
Environmental Specifications
FX BASE UNITS
Vibration resistance Acc. to IEC/EN 68-2-6: 1G (resistance to vibrations from 57150 Hz for 80 minutes along all 3 axes); 0.5G for DIN rail mounting
Insulation resistance 500 V DC, 5 MW
Ground Class D: Grounding resistance 100 W or less
Fuse rating AC models: 250 V 1.0 A; DC models: 0.8 A
Environment Avoid environments containing corrosive gases, install in a dust-free location.
Certifications Please refer to pages 6667 in this catalogue
Electrical Specifications
Type Transistor
modules
Power supply 24 V DC (+10 %/-15 %) 100240 V AC (+10 %/-15 %), Switching voltage (max.) V <250 V AC, <30 V DC 530 V DC
50/60 Hz (10 %)
Max. output - per output A 2 0.5
Inrush current at ON 10 A/0.1 ms (at 24 V DC) 15 A/5 ms (at 100 V AC); current
25 A/5 ms (at 200 V AC) - per group* A 8 0.8
Allowable momentary power Max. switching - inductive load 80 VA 12 W
failure time 5 ms 10 ms current - lamp load W 100 1.2
Primary power supply 24 V DC, 400 mA Response time ms 10 0.2
External power supply (24 V DC) 400 mA 3,000,000 at 20 VA; 1,000,000 at 35 VA;
Life of contacts (switching times)** 200,000 at 80 VA
* The limitation applies only per reference terminal for each group, 1 and 4 outputs for relays and
transistors. Please observe the terminal assignments for the group identification.
** Not guaranteed by Mitsubishi Electric.
Programming Specifications
Program data
Program memory 2.000 steps EEPROM (internal)
Program execution Periodical execution of the stored program
Program protection Password protection with 3 protection levels. Note: Protection levels may only be changed with FX-10P/FX-20P/FX-30P.
Number of instructions 27 sequence instructions, 2 step ladder instructions, 85 applied instructions
Cycle period 0.550.7 s/logical instruction
Operands
Internal relays 512 total, with 384 general (M0M383) and 128 latched (M384M511)
Special relays 256 (M8000M8255)
State relays 128
Timers 64 (max. 63 timers, partially switchable to 100 ms and 10 ms)
External setpoint entry via potentiometer 2 potentiometers
Counter 32 (16 bit), C0C31
High-speed counter inputs 1 phase, 6 points max: 60kHz/2 points, 10kHz/4 points ; 2 phase, 2 points max: 30kHz/1 point, 5kHz/1 point
Data register 256 subtotal (128 general (D0D127) and 128 latched (D128D255))
Index register 16
Special register 256 (16 bit), D8000D8255
Pointer 64, P0P63
Nesting operands 8, N0N7
Interrupt inputs 6
Constants 16 bits: K: -32768 to +32767, hex: 0FFFF
32 bits: K: -2147483648 to +2147483647, hex: 0FFFF FFFF
MITSUBISHI ELECTRIC 15