Module 15 Edition
Module 15 Edition
Hotel
Technical Standards
January 2016
15A
Mechanical Systems
Hotel
Technical Standards
January 2016
15A - Mechanical Systems
Contents
15A.1 General Requirements 1
15A.6 Pumps 9
15A.13 Laundry 28
Module Or ganization
This Module is a part of an integrated series of 17 Modules.
Coordination with information from other Modules is required.
The reference symbol <XX> is used to indicate a Module reference that includes related
information.
Mechanical Systems
15A.1 General Requirements
A. Design Criteria: This document establishes minimum Marriott
International (MI) requirements and is not intended to provide
complete design solutions to project speci c situations.
B. Codes & Standards:
1. Deviations: Submit in writing, proposed deviations
from systems, equipment or manufacturers to MI
Engineering for approval. For deviations that alter
operating costs, submit a complete computer simulated
life cycle cost analysis so that negative impacts are
reflected in the operating Pro-Forma.
2. Governing Regulations: If governing regulations
conflict with MIs Design Standards, contact MI
Engineering for resolution.
3. Documentation: Clearly identify on the design drawings,
systems and equipment required by this document and
provided by the contractor.
4. Zurich Global: Fired pressure vessels, boilers, boiler
tanks and their safety trains (controls that include
combustion safeguards, safety shutoff valves, over
temperature protection and pressure relief valves)
require Zurich Global approval.
C. Building Pressures: Design air systems to maintain positive
building pressure, maintain environmental requirements
(temperature and humidity) and ensure guest comfort.
1. Outside Air: Minimum outside air intake quantities
shall exceed building exhaust quantities by 10% for
public and back-of-house spaces. Provide complete
airflow matrix showing supply, return, exhaust, and
outside air quantities on a floor-by-floor basis.
2. High-rise Buildings: In high-rise buildings, the use of
entry vestibules with a revolving door will signi cantly
reduce chimney or stack effect. <2A>
D. Equipment Selection: Select equipment, rated for
applicable service, environment, temperatures and
pressures.
Design and select outdoor equipment for project speci c
conditions complete with factory applied corrosion resistant
coatings. Do not select equipment designed for indoor use at
outdoor locations.
6. Blower and Motor: Direct drive with VFD for supply air
balancing. Belt driven motors are not acceptable.
7. Winter Heating: rovide fully modulating hydronic or gas-
red hydronic heat to maintain a constant discharge air
temperature during heating season.
8. Preferred Manufacturer: Aaon, national account contact,
Tom Whiteley, (443) 832-1657 or e-mail tom.whiteley@
havtech.com.
9. Accepted Manufacturers: Trane, DesertAire, Advantix,
Seresco, and SolutionAir
F. Guestroom FCUs: <7A>
1. Sizing: Provide the larger of either 46 m2 (500 sf)/ton or
140 l/s (300 cfm) fan coil.
2. Location: Position FCU supply air to avoid blowing directly
on the bed. Coordinate supply grille, return grille and access
panel placement with MI Interior Design.
3. Type: Vertical stack or concealed horizontal with chilled
water cooling coil with 2-way control valve, hot water
heating coil with 2-way control valve. Based on climate
data, electric heat may be appropriate. Consult MI
Engineering for acceptance.
Hayes Fluid Controls Measurflo automatic flow control
valves on chilled and hot water, epoxy coated insulated
drain pan, lter return with 18 mm ( inch) MERV 8 lters
and foil faced insulation. Provide 3-way control valves at
the top of each riser or a the last FCU on a horizontal run.
a. Suites: Multiple, four pipe fan coil units. Provide
minimum one unit for each room or space.
b. Guest Floor Lounge: Air handling units (AHUs) or
multiple fan coil units (FCUs) discharging toward
exterior wall with hard ducted return air.
c. Bathrooms: In large 4 and 5 xture bathrooms and
bathrooms with solar gain from windows, provide
supply air to the bathroom from the fan coil unit.
d. Location: For horizontal FCUs locate above the entry
vestibule ceiling with hard ducted return air. Provide
full size access panel to allow for complete mainte-
nance access.
4. Guestroom Automation System:
a. Digital Thermostat: Provide with the following
features:
occupancy sensor - built-in
RFID signal from proximity door lock
lighting control - integrated
central network control interfaced with Property
Management System (PMS)
Employee Cafeteria
Other areas producing odors, fumes and excessive
heat.
2. Guestroom Tower: Total exhaust is typically 236 to
378 l/s (500 to 800 cfm) per floor. Provide exhaust at
the following:
Service Elevator Lobby
Laundry Chute Room
Housekeeping
Vending
Electrical Rooms to maintain 27 C (80 F)
3. Parking Structure Exhaust: Provide exhaust of 0.7 l/s/m2
(1.5 cfm/sf) minimum, controlled by carbon monoxide
sensors. Provide a minimum of one sensor per 700 m2
(7,500 sq. ft.).
K. Guest Bathroom Exhaust:
1. Type: Provide ceiling mounted American Aldes
Zone Register Terminal (ZRT-1-4-120) in the shower
compartment subducted into vertical sheet metal
exhaust risers to roof mounted exhaust fans.
a. ZRT automatically regulates the airflow at 30 l/s
(50 cfm) when the light switch is on and closes
when the light switch is off.
2. Roof Mounted Exhaust Fans: Provide with VFD sized at
50% of the total exhaust quantity. Locate static pressure
sensor in the vertical riser, set at 3.4 kPa (0.5 inch w.c.).
L. Combustion Air: Provide for gas red appliances including
boilers, pool heaters and laundry dryers.
1. Cold Climates: Provide unit heaters for general space
conditioning.
2. Fan Operation: If provided by a fan, interlock fan and
intake damper with boiler controls to ensure proper
supply of combustion air prior to boiler and equipment
ring.
M. Fans:
1. Type: Centrifugal, except parking structure fans may be
propeller fan with premium ef ciency motors.
Prefunction Area
Interstitial monitoring
Over ll protection
D. Pumps: If a skid tank is not required, provide duplex fuel
oil pump sets to transfer fuel to day tanks.
E. Fuel Storage: Size fuel oil tanks based on 24 hours fuel oil
storage capacity for backup operational power.
1. High Risk Areas: For properties in high risk areas
(hurricane regions) provide a minimum of 72 hours
storage capacity.
2. Remote Properties: On island and remote properties,
size fuel oil tanks based on 7 days storage capacity.
3. Acceptance: Obtain acceptance from MI Engineering.
15A.12 Commercial Food & Beverage (F&B) Production
A. Air Conditioning: Provide air conditioning with a
separate HVAC unit that remains negative with respect to
surrounding areas.
1. Supply Air: Locate devices so cool air is directed away
from hot food serving areas.
2. Return Air: Provide hard ducted return system. Plenum
ceilings are not permitted in food production areas.
B. Type 1 - Grease Hood: See <14> for cooking hood and
duct re suppression system at food production cooking
equipment that produces grease laden vapors, and
coordinate requirements with <10>, <15B>, <15C> and
this document. Provide the following:
1. Standard: Comply with NFPA 96 - Ventilation Control
and Fire Protection of Commercial Cooking Operations.
2. Hood Control System: Provide Melink Intelli-Hood
or Halton Marvel system for food cooking hoods to
automatically reduce the speed of the exhaust fan and
control outside and return air dampers during idle and
non-cooking periods to save fan energy and conditioned
air. The system does the following:
a. Includes the I/O (input and output) processor, key-
pad, temperature sensors, optic sensors, variable
frequency drives (VFDs) and cables.
b. Automatically turns the hoods on / off based on
temperature or a time of day schedule.
c. Varies the hood fan speeds based on both the heat
and smoke load to ensure optimal hood perfor-
mance and energy savings.
d. Automatically adjusts the temperature span to en-
sure optimal energy ef ciency.
e. Automatically recalibrates the optics at start-up to
ensure optimal energy ef ciency.
30 Mechanical
|
D. Preferred Manufacturers: Automated Logic
E. Accepted Manufacturers: Trane, Siemens, Schneider Electric, Johnson, and Honeywell
Table 1 Environmental / Ventilation Requirements
Design Temper atur es &
15A - Mechanical Systems
January 2016
3 (30) 43 (4) -
& Lobby 50% RH (70F) (7.5 cfm/person + 0.06 cfm/sf)
Provide conditioned supply air into
2A each restroom. Keep toilets under
24C (75F) 21C
Public Toilets - - - negative pressure with respect to
50% RH (70F) surrounding public areas. Exhaust
quantity 10 l/s/m2 (2 cfm/sf) minimum.
27C (80F) 27C 2.4 l/s/m2 (0.48 cfm/sf) Keep under negative pressure with
Indoor Pool 32 (3) respect to surrounding public areas.
65% RH (80F) outside air
January 2016
Provide separate HVAC unit.
24C (75F) 3.8 l/s person + 0.6 l/s/m 2 Provide individual temperature control
5 Retail 21C (70F) 4 (45) 75 (7)
50% RH (7.5 cfm/person + 0.12 cfm/sf) in each shop.
24C (75F) 3.8 l/s person + 0.6 l/s/m 2 Provide individual temperature sensor
Pre-Function 21C (70F) 1 (10) 54 (5)
50% RH (7.5 cfm/person + 0.12 cfm/sf) connected to BAS.
Provide individual temperature sensor
24C (75F) 21C 2.5 l/s person + 0.3 l/s/m2
Ballrooms 1 (10) 54 (5) connected to BAS with local occupant
50% RH (70F) (5 cfm/person + 0.06 cfm/sf) control in each Salon.
| Mechanical
10 (100) 0.3 l/s/m 2 (0.06 cfm/sf) 32 (3) Meeting Spaces but positive with
Corridors 50% RH (70F) respect to Banquet Kitchen.
31
Mechanical Systems - 15A
Table 1 Environmental / Ventilation Requirements
Design Temper atur es &
Relative Humidity Maximum
Occupancy
Lighting Load
Space Cooling m/Per son Outside Air Remar ks
Heating Watts/m
C (F) (ft/Per son)
C (F) (watts/ft )
% RH
Hard duct 100% outside air into each
32 Mechanical
Guestrooms & 24C (75F) 23C 2.5 l/s person + 0.3 l/s/m2 guestroom. Provide supply air into
|
7A 2 persons -
Suites 50% RH (74F) (5 cfm/person + 0.06 cfm/sf) large 4 & 5 xture guest bathroom and
bathrooms with exterior exposure.
Guestroom
Corridors 24C (75F) 21C 2 air changes per hour Supply 2 air changes per hour
- 11(1) minimum.
& Elevator 50% RH (70F) 100% outside air 100% outside air
Foyers
15A - Mechanical Systems
January 2016
Provide individual temperature controls
Guest Floor 24C (75F) 21C 2 (15) or num- 3.8 l/s person + 0.9 l/s/m 2 in Lounge, Meeting Room and Pantry.
7C 32 (3)
Lounge 50% RH (70F) ber of seats (7.5 cfm/person + 0.18 cfm/sf) Provide hood exhaust in Pantry if
required.
Administrative 24C (75F) 21C 2.5 l/s person + 0.3 l/s/m2 Provide individual temperature controls
8A 10 (100) 43 (4)
Facilities 50% RH (70F) (5 cfm/person + 0.06 cfm/sf) in of ces. Provide exhaust as required.
January 2016
Cafeteria 50% RH (70F) ber of seats (7.5 cfm/person + 0.18 cfm/sf) exhaust for grease hood and dishwasher
if applicable.
24C (75F) 2.5 l/s person + 0.3 l/s/m 2 Provide individual temperature
Engineering &
21C (70F) 10 (100) 43 (4) controls in of ces. Provide exhaust for
Maintenance 50% RH (5 cfm/person + 0.06 cfm/sf) workshops as required.
| Mechanical
33
Mechanical Systems - 15A
Table 1 Environmental / Ventilation Requirements
Design Temper atur es &
Relative Humidity Maximum
Occupancy
Lighting Load
Space Cooling m/Per son Outside Air Remar ks
Heating Watts/m
C (F) (ft/Per son)
C (F) (watts/ft )
% RH
Commercial
34 Mechanical
27C (80F) 21C 3.8 l/s person + 0.9 l/s/m2 Keep under negative pressure with
Kitchens
|
5 (50) 32 (3) respect to surrounding areas.
(F&B 50% RH (70F) (7.5 cfm/person + 0.18 cfm/sf) Operate dishwasher exhaust 24 / 7
production)
15C (59F) 3.8 l/s person + 0.9 l/s/m 2 See applicable program requirements
Cold Prep &
- 5 (50) 32 (3) in <10>. Provide individual split system
Vegetable Prep 50% RH (7.5 cfm/person + 0.18 cfm/sf) connected to BAS.
15A - Mechanical Systems
21 to 24C
Provide individual temperature control
Dry Storage (70 to 75F) - - - 32 (3)
connected to BAS.
50% RH
Keep under negative pressure with
Meat / Fish / 15C (59F) 3.8 l/s person + 0.9 l/s/m 2 respect to surrounding areas. Provide
10 Poultry / Pork - 5 (50) 32 (3)
50% RH (7.5 cfm/person + 0.18 cfm/sf) individual split system connected to
Prep Area
BAS.
January 2016
Keep under negative pressure with
Pastry / 15C (59F) 3.8 l/s person + 0.9 l/s/m 2 respect to surrounding areas. Provide
Chocolate - 5 (50) 32 (3)
50% RH (7.5 cfm/person + 0.18 cfm/sf) individual temperature control
Room
connected to BAS.
IDF - -
13
Design system to maintain
Sound temperature between 10 to - 0.3 l/s/m2 (0.06 c
Equip. Room 27 C (50 to 80 F) non-
condensing.
Dimmer
-
Equip. Room
Mechanical,
Electrical, 24C (75F) 21C
15 Telephone - 0.3 l/s/m2 (0.06 c
Rooms & 50% RH (70F)
Closets
Hotel
Technical Standards
January 2016
15B - Plumbing Systems
Contents
15B.1 General Requirements 1
15B.7 Laundry 15
Module Or ganization
This Module is a part of an integrated series of 17 Modules.
Coordination with information from other Modules is required.
The reference symbol <XX> is used to indicate a Module reference that includes related
information.
Plumbing Systems
15B.1 General Requirements
A. Design Criteria: This document establishes minimum
Marriott International (MI) requirements and is not
intended to provide complete design solutions to project
speci c situations.
B. Codes & Standards:
1. Deviations: Submit in writing, proposed deviations from
systems, equipment or manufacturer to MI Engineering for
approval. For deviations that alter operating costs, submit
a complete computer simulated life cycle cost analysis
so that negative impacts are reected in the operating
Pro-Forma.
2. Governing Regulations: If governing regulations conict
with MIs Design Standards, contact MI Engineering for
resolution.
3. Documentation: Clearly identify on the design drawings,
systems and equipment required by this document and
provided by the contractor.
4. Sanitation: Comply with sanitation standards to safeguard
the water supply, drainage and food service equipment
<10>.
C. System Design: Design systems in compliance with
American Society of Plumbing Engineers (ASPE) standards.
D. Dimensions, Sizes & Measurements: In this Standard,
conversions from English to metric (SI) units are approximate.
E. Energy E ciency: MI has adopted a signi cantly aggressive
environmental policy. At a minimum, design plumbing systems
in compliance with ASHRAE Standard 90.1 2013, Energy
Ef ciency in Buildings.
1. Provide a complete computer simulated life cycle cost
analysis for alternate plumbing systems and equipment
considered for implementation.
2. Investigate the use of alternate or renewable energy options,
including solar hot water and swimming pool heat.
Toilets (Water Closet) Provide ush toilets that exceed 800 MaP test.
Sink
Fixture: 61 x 51 cm (24 x 20 inch) enameled cast iron,
with wall hanger and stainless steel rim guard, white
with 75 mm (3 inch) acid resistant enameled cast iron
Sink, Service P trap with grid strainer
Faucet: Wall mounted service faucet, vacuum
breaker, integral stops, adjustable wall brace, pail
hook, chrome plated
Fixture: 61 x 61 x 25 cm (24 x 24 x 10 inch) molded
stone, 75 mm (3 inch) stainless steel combination
dome strainer and lint basket
Sink, Mop (Floor Mounted)
Fitting: Wall mounted service faucet, vacuum
breaker, integral stops, adjustable wall brace, pail
hook, chrome plated
Fixture: Undercounter, 18 gauge 302 stainless steel,
fully under coated
Sink, Bar (Guestrooms) Fitting: 5.70 l/min (1.5 gpm) ow restrictor, aerator,
lever handles
Strainer: Perforated grid chrome strainer with 302
stainless steel chrome plated tailpiece
Shower Fixtur es
Fixture: As accepted by EDITION
Shower Valve: Pressure balanced valve with
screwdriver stops
Whirl Pool Bath Faucet: Cast brass body and spout, lever handles,
polished chrome nish
Tub Waste and Overow: 17 gauge drain with
tailpiece, lift and turn stopper, polished chrome nish
Fixture: Monolithic, enameled cast iron or as
accepted by EDITION. Slip resistant surface.
Bathtub, Suite Faucet: Cast brass body and spout, lever handles,
polished chrome nish
Tub Waste and Overow: Solid brass 40 mm
(1 inch), 17 gauge drain with tailpiece, lift and turn
stopper, chrome nish
Hotel
Technical Standards
January 2016
15C - Electrical Systems
Contents
15C.1 General 1
15C.4 Devices 4
15C.9 Lighting 13
Module Or ganization
This Module is a part of an integrated series of 17 Modules.
Coordination with information from other Modules is required.
The reference symbol <XX> is used to indicate a Module reference that includes related
information.
Electrical Systems
15C.1 General
A. Design Criteria: This document establishes minimum
MI requirements and is not intended to provide complete
design solutions to project speci c situations.
B. Codes & Standards:
1. Deviations: Submit in writing, proposed deviations
from systems, equipment or manufacturers to MI
Engineering for approval. For deviations that alter
operating costs, submit a complete computer simulated
life cycle cost analysis so that negative impacts are
reflected in the operating Pro-Forma.
2. Governing Regulations: Comply with governing codes,
and the current editions of NFPA 70 (NEC), NFPA
72, NFPA 101. If governing regulations conflict with
MIs Design Standards, contact MI Engineering for
resolution.
3. Documentation: Clearly identify on the design
drawings, systems and equipment required by this
document and provided by the contractor.
C. Design Considerations:
1. General: Provide an energy ef cient electrical system
requiring minimum maintenance and a high level of
safety.
2. Reliability: Provide a system design, equipment
selection, and a property operating environment that
permits maintenance with little or no down time and a
high degree of reliability.
3. Equipment: Locate to provide a minimum impact to
architecture and interior nishes.
4. Interior: Locate equipment in an interior weather
protected space unless an exterior location is absolutely
necessary. Do not provide equipment designed for
interior use at exterior locations.
D. Fire Protection & Life Safety: See <14>.
MAIN
SWITCHBOARD
AUTOMATIC
TRANSFER
SWITCH
AUTOMATIC
TRANSFER
SWITCH
STANDBY
POWER
SOURCE
STANDBY BACKUP
POWER (OPERATIONAL)
POWER
LOAD LOAD
Elevators: Minimum one service and one guest Sewage plant, ejectors and sump pumps
elevator serving all floors with power transferable to
selected elevators
Elevator emergency return and remens service and Central fuel red heating plant
elevator machine room air conditioning
15C.9 Lighting
A. Design Considerations:
1. Service and Access:
a. Locate lighting xtures to enable reasonable access
for service and re-lamping.
b. Locate ground mounted exterior xtures to en-
able reasonable access for service and re-lamping.
c. Locate master dimmer control in air conditioned,
protected, non-public areas.
2. Circuiting: Provide separate zones for wall washers,
down lights and decorative xtures.
3. Lighting Levels: Design lighting systems to provide
foot-candle (lux) levels in compliance with Table 3 -
Lighting Requirements at the end of this document.
B. Types:
1. Lobby Areas: Lighting in restaurant areas, guest
corridors, stairwells and public toilets is generally LED
or compact fluorescent downlights, wall sconces and
halogen decorative light xtures.
2. Function Areas: See lighting xture types below in this
document for criteria.
3. Guestroom Lighting: 2700 degree Kelvin LED or
compact fluorescent spiral type lamps with color
rendering index (CRI) of 85 and instant on, no flicker
ballasts and lamps. Downlights are CFL or LED.
4. Suite Lighting: Obtain MI review and acceptance.
5. Guestroom Bathroom Lighting: Damp location
rated downlights over tub and shower, CFL or LED
downlights over vanity sink, and paired wall sconces
flanking the vanity. If room size dictates, provide a
decorative downlight xture at center of room. Provide
two level lighting control in the bathroom.
6. Back-of-House Lighting: Generally fluorescent lighting
is designed by the electrical engineer.
7. Food & Beverage: Provide the following:
a. Recessed mounted xture and lens flush with
ceiling
b. Shatterproof sheaths
c. Fluorescent lamp (Back of House)
d. Removable, washable plastic lens
Compact
Boardroom & Meeting Room Fluorescent / LED
Downlight
Lighting Controls
Fluorescent Cove
2 button wall
control Wall Sconce
4 button wall
control Chandelier
1 Lighting Cove
1 2 Service Corridor
Main dimmer
Dimmer wall
Compact Fluorescent
Fluorescent Cove
Wall Sconce
Chandelier
Infrared handheld control Handheld control empowers the clients to have full
4 scene (min.) recall with raise, lower and o control of their environment.
Communicate to infrared ceiling sensors.
Partitioning capability using wall station or ceiling Partition controls allow the individual and combined
mounted sensors. rooms to function appropriately.
Override zone control from back of the house When A/ V person is available, they may want to have the
In room programming jacks and handheld ability to alter scene or zone settings, or to look at the
programmer when processor based systems are
Grand Ballroom facility remotely.
used.
salons &
Jr. Ballroom When additional stage lighting is used in Ballroom for
speci c events, the audio / visual technician requires the
salons DMX control capability by theatrical stage board
ability to patch architectural lighting to the stage board
for all architectural lighting when required.
for large events. When the stage board is disconnected,
architectural lighting returns to its last selected scene.
The locations of the head table and food displays and
other table presentations move from one event to the
Circuit and zone lighting in Ballroom areas to ac- next.
commodate maximum exibility of space. Property requires the ability to turn individual light
zones on and o in the appropriate parts of the Ballroom
without a ecting the entire Ballroom.
Provide occupancy sensors to communicate directly with
Occupancy sensors the lighting control system to ensure that lights are turned
o or to a pre-programmed night light.
Wall box-mounted manual dimmers or include
as a de ned area within the Ballroom dimming This area requires exibility of lighting for multiple events
system. Provide astronomic time clock control for and functions.
Prefunction after hours light level settings.
Exit Stairs 215 (20) PS X Single 32 W, 1.2 m (4 ft.) vandal proof tube