1.converter Transformer
1.converter Transformer
1.converter Transformer
Design
active part
Valve Winding (Y) Tap Winding Valve Winding (D)
Line Winding
HV-Terminal
Neutral-Terminal
Simplified connection of
line windings and tap windings
Winding and core arrangement
Converter Xmer & Normal AC Xmer..
Polarity Reversal
Voltage Distribution in Oil Barrier System
Impedance variation influence
On load Tap Changer
Harmonic Currents
Losses
DC Magnetisation
Short Circuit Forces
DC Bushings
Under Polarity Reversal..
- Transient DC voltages:
AC DC
Insulation Design
When changing over from one tap to next, the current in the leaving
tap has to be broken during the normal current zero passage.
Yoke shunts are used to contain and direct the above leakage
flux to core
results in -
high levels of vibration
increased sound level in transformers
marginal increase in no-load loss.
Short Circuit Forces.
To avoid chances of phase to ground short circuits, valve side bushings are
located inside the valve hall. This also reduces the pollution related
flashovers and consequent short circuit.
Inverter mode
3
U d = (1.35 U cos L I d )
Overlap
2 L I d
cos( + ) = cos
U
+ + =
Converter Transformer
Tests
required acc. to IEC 60076-1, ~-3, IEC61378-2
routine
tests
meas of DC wind. res. IEC 60076-1, 10.2
meas. of voltage ratio and check of phase IEC 60076-1, 10.3
displacement
meas. of s/c imp. and load loss IEC 60076-1, 10.4
meas. of no load loss and current at fr and Ur IEC 60076-1, 10.5
dielectric routine tests (for IEC 60076-3
Um>300kV)
LI (for line & neutral, principal and extr. neg. Ut IEC 60076-3, cl.13 & 14
taps)
SI IEC 60076-3, cl.15
ACLD (AC long duration), sine wave>>fr, IEC 60076-3, cl.12.4
100%Utrms(60s)
seperate source AC (applied potential IEC 60076-3, cl.11
test)
seperate source DC volt. withstand incl IEC 601378-2, cl.10
PD meas.
polarity reversal test IEC 601378-2, cl.10
Tests
type
tests
temp.rise IEC 60076-2, also 5.2.3
test
dielectric type tests n.a., all tests are routine IEC 60076-3
tests
sound IEC 60076-10
power level
sound power level of cooling IEC 60076-10
equipment
special
tests
dielectric special tests (for Um>300kV) (to be agreed see routine tests IEC 60076-3
about)
ACSD (AC short duration), 1ph transformer: ph- gr only, 1-ph.: IEC 60076-3, cl.12.2 &
100%Utest for 60s U2=1.5*U 12.3
m/Wurzel
(3)