b6 Testing Numerical Transformer Differential Relays Ieee1173
b6 Testing Numerical Transformer Differential Relays Ieee1173
b6 Testing Numerical Transformer Differential Relays Ieee1173
INTRODUCTION
Commissioning versus Maintenance Testing
INTRODUCTION
Topics:
Transformer Differential Boundary Test
(Commissioning)
Ground Differential Sensitivity Test
(Commissioning/Maintenance)
Harmonic Restraint for Transformer Inrush
(Maintenance)
Testing Numerical Transformer Differential Relays
Commissioning
Common Practice:
Test all numerical relay settings
verify settings properly entered
Easily facilitated using computer
automate test set & store results
Hundreds of tests are possible
numerical relays have many settings
Testing Numerical Transformer Differential Relays
Commissioning
Final Goal
Ensure the transformer is properly protected
for the particular application
Testing Numerical Transformer Differential Relays
46 RG
E
+
46 RG
ZT
I2
3RG
ZT
Testing Numerical Transformer Differential Relays
Y Y
Y Y
87
* Simulate Through Current
Differential Characteristic
Operating Equations
Differential Characteristic
Id
% = Y *100%
X
t ( %)
en
Perc pe
Slo Y
X
Minimum
Pickup
(per unit) Ir
Te s ting Nume ric al Trans fo rme r Diffe re ntial Re lays
Differential Characteristic
Id
ent
Perc
e
Slop
gi o n
Re
Trip g ion
Minimum R e
Blo ck
Pickup
Ir
Te s ting Nume ric al Trans fo rme r Diffe re ntial Re lays
Matrix
[]
Id
Ir
= [ ][]
1 -1 *
I1
I2
Te s ting Nume ric al Trans fo rme r Diffe re ntial Re lays
Inverted Matrix
[]
I1
I2
= [ ][]
1
- 1
* Id
Ir
Te s ting Nume ric al Trans fo rme r Diffe re ntial Re lays
Differential Characteristic
Test Current Equations
Differential Characteristic
Test Points
Minimum Pickup = 0.2 per unit
Id
Slope = 28.6%
ent
Perc
e
4 Slop
3
1 2
Minimum
Pickup
Ir
Testing Numerical Transformer Differential Relays
Differential Characteristic
Test Points (Per Unit)
Id Ir I1 I2
TABLE 1
Testing Numerical Transformer Differential Relays
DAB
I1 I2
Y
Y Y
87
* Simulate Through Current
MVA#
TAP# =
kV#LL*CTR#*SQRT(3)
Testing Numerical Transformer Differential Relays
From TABLE 1:
Id Ir I1 I2
2 0.2 0.7 0.8 0.6
IA1test = 0.8*TAP1
IA2test = 0.6*TAP2*SQRT(3)
Testing Numerical Transformer Differential Relays
Internal External
I0 IG
-90o
Operate When:
180
160
140
Fault Resistance
120
100
80
60
40
20
0
0 20 40 60 80 100 120
Source Impedance
IG
Directional Element
INTERNAL EXTERNAL
IG2
IOP
CTCF*3I0(2)
New Pickup = 1.0 Amps
Testing Numerical Transformer Differential Relays
Waveform Sources:
Events from Numerical Relays
Events from Digital Fault Recorders
Simulate using Transient Software
Testing Numerical Transformer Differential Relays
W3
delta
345 kV 230 kV
wye wye
W1 W2
Z HM + Z HL Z ML
ZH = 2 = 0.0140 per unit
Z HM + Z ML Z HL
ZM = = -0.0029 per unit
2
Z HL + Z ML Z HM
ZL = 2 = 0.0340 per unit
600 MVA
TAP2 = = 3.77
230 kV * 400 * SQRT(3)
Slope = 25%
2 2 1/2
Ieven = (I2 + I4 )
Testing Numerical Transformer Differential Relays
CONCLUSIONS
Testing Numerical Transformer Differential Relays
CONCLUSIONS
Transformer Differential Boundary Test
(Commissioning)
Ground Differential Sensitivity Test
(Commissioning/Maintenance)
Harmonic Restraint for Transformer Inrush
(Maintenance)
Testing Numerical Transformer Differential Relays
QUESTIONS