Improved Power Transformer Protection Using Numerical Relays
Improved Power Transformer Protection Using Numerical Relays
numerical relays
Bogdan Kasztenny* and Mladen Kezunovic
Texas A&M University, USA
Large power transformers belong to a class of very expensive and vital components in electric power
systems. If a power transformer experiences a fault, it is necessary to take the transformer out of service as
soon as possible so that the damage is minimized. The costs associated with repairing a damaged trans-
former may be very high. The unplanned outage of a power transformer can also cost electric utilities mil-
lions of dollars. Consequently, it is of a great importance to minimize the frequency and duration of un-
wanted outages. Accordingly, high demands are imposed on power transformer protective relays. The re-
quirements include dependability (no missing operations), security (no false trippings), and speed of op-
eration (short fault clearing time).
The operating conditions of power transformers do not make, however, the relaying task easy. Protec-
tion of large power transformers is perhaps the most challenging problem in the power system relaying
area.
Advanced digital signal processing techniques and recently introduced Artificial Intelligence (AI) ap-
proaches to power system protection provide the means to enhance the classical protection principles and
facilitate faster, more secure and dependable protection for power transformers. Also it is anticipated that
in the near future more measurements will be available to transformer relays owing to both substation in-
tegration and novel sensors installed on power transformers. All this will change the practice for power
transformer protection. This paper briefly reviews the state of the art, but is primarily devoted to discus-
sion of the new approaches and future directions in digital relaying for power transformers.
Global approaches
By the global approach we mean a relaying algorithm that recognizes internal faults versus all the
other phenomena in a power transformer without specifically classifying the later into magnetizing in-
rush, overexcitation and external faults.
Model methods
This family of approaches solves on-line a mathematical model of a fault-free transformer. Either cer-
tain parameters of the model are computed assuming the measured signals; or certain fraction of the ter-
minal variables are computed based on all the remaining signals, and next compared to their measured
counterparts. In the first case, the values of the calculated parameters differentiate internal faults from
other disturbances. In the second case, the difference between the calculated and measured signals enables
2
the relay to perform the classification. These approaches call for voltages and currents at all the terminals
to be measured.
Differential power method
Another relaying principle uses the differential active power to discriminate between internal faults
and other conditions. Instead of the differential currents, the differential power is computed and moni-
tored. The operating signal is a difference between the instantaneous powers at all the transformer’s ter-
minals. This approach calls for measuring the voltages at all the terminals, but pays back by enabling
avoiding the vector group (angular displacement between the current and voltages at different windings)
and ratio compensation. The dependability of this method may be further enhanced by compensating for
the internal active power losses — both in copper, and in iron.
In addition, having the active power available, the method enables one to compute the energy released
in the tank and to emulate the back-up protection — both the accumulated and sudden pressure gas re-
lays.
Multi-setting overcurrent principle
Severe internal faults may be recognized by the differential relay based only on the amplitude of the
differential current without checking any extra conditions (unrestrained tripping). If the amplitude of the
current is higher than the highest possible value under no-internal fault conditions (the inrush current, as
a rule), then the relay trips without further analysis.
The Figure 4 presents amplitudes of the differential currents under the load, overexcitation, external
fault, magnetizing inrush and internal fault conditions. The classical unrestrained differential overcurrent
element must apply the threshold D set above the maximum non-internal fault current (Figure 4). If so,
internal faults denoted as the class A are tripped by the overcurrent element while all other faults of the
classes B to D must wait to be detected by the restrained element.
However, the internal faults of the class B may be distinguished from external fault and overexcitation
phenomena by the overcurrent element working with the second lower threshold D (Figure 4). If so, the
internal faults of the category A are detected by the overcurrent principle with the threshold D. The inter-
nal faults of the category B are detected by the overcurrent element with the threshold D if the inrush hy-
pothesis is rejected by the other relaying principle such as the second harmonic restraint. The external
fault and overexcitation conditions may not be checked at all since they are ruled-out be the overcurrent
element (D). Similar reasoning applies to the faults of the categories C and D.
The principle of the multi-setting overcurrent element is implemented as shown in Figure 5 and repre-
sents a solution that can be placed between the traditional restrained and unrestrained differential func-
tions. This approach enables reduction of the operating time particularly for the internal faults with me-
dium levels of the fault current (the classes B and D in Figure 4). This approach enhances dependability by
speeding-up the operation and covering the low-current internal faults.
3
Phenomena specific approaches
By the phenomenon specific approach we mean a relaying algorithm that restraints the relay from
tripping only in one particular non-internal fault related situation (such as inrush) although some of the
restraining algorithms occasionally deliver an extra blocking during other conditions as well.
Flux based inrush restraint
This relaying algorithm differentiates internal faults from the inrush and overexcitation conditions
based on the calculated flux in the core. As its advantage, this approach tides together the cause of the
problem (saturation of the core as a source of the current unbalance) with the phenomenon used for rec-
ognition (flux in the core).
When invented more than fifteen years ago, the method displayed a disadvantage due to the lack of
ability to measure the voltage signals. Nowadays, the voltages are easily available for digital transformer
protection terminals which makes this kind of relaying principles attractive.
Detection of external faults
In order to overcome dependability limitations inherent in the biased characteristic and enhance the
performance of the differential relay, three approaches that modify the standard principle may be applied.
They are:
· The DELTA-differential criterion which compares the increase of the differential current (with respect
to its pre-fault value) with the adequate increase of the restraining current. The modified single slope
bias characteristic is applied for such incremental signals.
· The sequence of events principle that enables distinguishing between internal and external fault cur-
rents under saturation of the CTs. This criterion acts as the trip suppressor and blocks the relay when
the external fault hypothesis gets confirmed.
· The saturation detector that detects considerable saturation of the CTs. The result of detection is used
to control on-the-fly the slope of the biased characteristic, which is increasing dependability of the dif-
ferential relay.
4
The multi-criteria differential relay is a good example of the fuzzy logic approach to protective relay-
ing. In this technique (Figure 6):
· The criteria signals such as amplitudes, harmonic contents, etc. are fuzzified in order to account for
dynamic errors of the measuring algorithms. Thus, instead of real numbers, the signals are repre-
sented by fuzzy numbers. Since the fuzzification process provides a special kind of flexible filtering,
faster measuring algorithms that speed up the operation of protective relays may be used.
· The thresholds for the criteria signals are also represented by fuzzy numbers to account for the lack of
precision in dividing the space of the criteria signals between the tripping and blocking regions.
· The fuzzy signals are compared with the fuzzy settings. The comparison result is a fuzzy logic vari-
able between the Boolean absolute levels of truth and false.
· Several relaying criteria are used in parallel. The criteria are aggregated by means of formal multi-
criteria decision-making algorithms that allow the criteria to be assigned a weight according to the
reasoning ability.
· The tripping decision depends on the multi-criteria evaluation of the status of a protected element
(sound vs. faulty). Additional decision factors may include the amount of available information, or the
expected costs of relay misoperation.
This relaying frame may be self-organizing, i.e. it may be automatically tuned prior to its installation
using a large number of training cases, therefore resembling the Artificial Neural Network (ANN) based
approach. The prior tuning results in an algorithm that is simple and traceable.
The Figure 7 presents a simplified block diagram of a fuzzy logic based differential relay for power
transformers. The relay employs 12 protection criteria to restraint itself from tripping during inrush, over-
excitation and external fault conditions. The operation of this scheme is illustrated using two cases par-
ticularly difficult from the standpoint of protective relaying.
The Figure 8 presents the differential and restraining currents for an internal turn-to-turn fault involv-
ing 16% of turns of the HV winding of the Yd11 140/10.4 kV two winding transformer. The fault occurs
50ms after switching-on of the transformer. Since the fault pattern is affected by the dominating inrush
current, this case is very difficult and causes the traditional protection techniques to fail. The fuzzy logic
scheme restraints itself from tripping during the inrush conditions and clears the fault 16ms after its in-
ception regardless of the inrush pattern still present in the differential current.
The Figure 9 presents the differential and restraining currents for an internal fault at the terminals ac-
companied by extremely severe saturation of the CTs. The fuzzy logic relay clears the fault in 5ms.
5
· The ANN is fed by all the currents either in the phase, or in the differential-restraining coordinates. The
sliding data widow, consisting of the recent and a few historical samples of the signals, is fed to the
ANN.
· The output from the ANN encodes the tripping decision.
· The training patterns exposed to the ANN cover usually inrush conditions, internal and external faults.
Only the selected data window positions are typically used for training.
· Additional pre- and post-processing may be applied.
The ANN approach can also be of either a global type or phenomena specific type. In the first case, the
net is trained to differentiate internal faults from all the other phenomena. In the second case, it is trained
to distinguish between internal faults and a specific non-internal fault pattern (inrush, for example). Also,
the ANNs are proposed for certain auxiliary functions such as reconstruction of the secondary current
waveforms distorted by saturation of the CTs.
The ANN based relays for power transformer show promising security and dependability.
The Figures 8 and 9 present the output from an ANN trained to protect the same transformer as in the
example for the fuzzy logic scheme. The ANN is fed by half a cycle data window of the differential and
restraining currents from all three phases. The net has 30 input neurons, 15 neurons in the hidden layer
and 1 output neuron. The case from Figure 8 is tripped in 18ms and the case from Figure 9 is tripped in
12ms.
6
measured by sensing the radial component of the electric field in a well-defined region around the high-
voltage conductor.
Advances in the area of measuring sensors will certainly contribute to the quality of power system
protection.
H.Ungrad, W.Winkler and A.Wiszniewski, Protection techniques in electrical energy systems, Marcel Dekker,
New York, 1995.
IEEE Tutorial Course, Advancements in microprocessor based protection and communication, IEEE Catalog
No.97 TP 120-0, July 1997.
M.M.Saha, B.Hillstrom, B.Kasztenny and E.Rosolowski, „A fuzzy logic based relay for power trans-
former protection", ABB Review, No.1/98, January 1998, pp.41-48.
7
M.Kezunovic, „A survey of neural net applications to protective relaying and fault analysis”, Engineering
Intelligent Systems, Vol.5, No.4, December 1997, pp.185-192.
L. Kojovic, „Rogowski’s coil suit relay protection and measurement of power systems”, IEEE Computer
Applications in Power, Vol.10, No.3, July 1997, pp.47-52.
Biographies
Bogdan Kasztenny (M'95, SM’98) received his M.Sc. (1989) and Ph.D. (1992) degrees, both with hon-
ors, from the Wroclaw University of Technology, Poland, where he is a faculty member of the Department
of Electrical Engineering. In 1994 he was with the Southern Illinois University at Carbondale as a Visiting
Professor. In the academic year 1997-98 Dr.Kasztenny was a Senior Fulbright Fellow at Texas A&M Uni-
versity, where currently he is an Associate Research Scientist. His research interests include power system
protection, digital signal processing and real-time computer applications in power systems.
Mladen Kezunovic (S’77, M’80, SM’85) received his Dipl. Ing. degree from the University of Sarajevo,
the M.S. and Ph.D. degrees from the University of Kansas, all in electrical engineering, in 1974, 1977 and
1980, respectively. Dr.Kezunovic’s industrial experience is with Westinghouse Electric Corporation in the
USA, and the Energoinvest Company in Sarajevo. He also worked at the University of Sarajevo. He was a
Visiting Associate Professor at Washington State University in 1986-1987. He has been with Texas A&M
University since 1987 where he is a Professor and Director of Electric Power and Power Electronics Insti-
tute. His main research interests are digital simulators and simulation methods for relay testing as well as
application of intelligent methods to power system monitoring, control and protection. Dr.Kezunovic is a
registered professional engineer in Texas.
8
Tables and Figures
9
CB CT CT CB
VT
CT
CB
ANTI-ALIASING FILTERS
A/D CONVERTER
BINARY OUTPUTS
TRIP
ALARM
AI
Advanced methods
principles
Today's
products
10
A/D CONVERTER
MEASUREMENTS
RELAY
NO
ACTIVATED?
YES
UNRESTRAINED
TRIP?
NO
DETECTION OF INRUSH
YES
DETECTION OF
OVEREXCITATION
DETECTION OF EXTERNAL
FAULTS
TRIPPING LOGIC
TRIP
NO
REQUESTED?
YES
Figure 3. Simplified flow chart of the logic for digital differential relay for power transformers.
11
A
,
differential current B
,
C
magnetizing inrush
internal faults
load
external faults
overexcitation
Overcurrent
Element
Threshold ,
Inrush Excluded
Inrush
detection
Overcurrent
Element
Threshold ,1
External Fault
Excluded TRIP
External fault
detection
Overcurrent
Element
Threshold ,2 Overexcitation
Excluded
Overexcitation
detection
12
Criteria
Signals
Fuzzification
Signal-Setting
Fuzzy Settings
Comparison
Multi-Criteria
Weighting Factors
Decision-Making
Thresholding
Threshold
(defuzzification)
TRIP
w1
M
E
w2
A
S
w3
U
R
I Ruling-out the hypothesis of
MIN
N stationary overexcitation
G
Ruling-out the hypothesis of an
external fault combined with
d>D
U
saturation of CTs
N
I Ruling-out the hypothesis of an
T external fault combined with ratio D
mismatch
Figure 7. Simplified block diagram of the Fuzzy Logic differential relay for power transformers.
13
Differential current
Restraining current
TRIP, FUZZY
TRIP, ANN
time, cycles
Figure 8. The differential and restraining currents during internal fault occurring in the course of trans-
former energization, and the trip signals of the fuzzy and ANN based transformer relays.
14
Differential current
Restraining current
TRIP, FUZZY
TRIP, ANN
time, cycles
Figure 9. The differential and restraining currents during an internal fault with deep saturation of the CTs,
and the trip signals of the fuzzy and ANN based transformers relays.
15
Input
Signals
Pre-Processing
Post-Processing
TRIP
16
Table II. Improvements area resulting from new protection techniques for power transformers
Inrush Overexcitation External faults Saturation of CTs
Advanced Considerable improvement in relay security espe- Considerable improve- Saturation detectors
numerical cially if the voltage signals are available. The ment in dependability can enhance both the
speed of operation during internal faults is, how- owing to the principles dependability and secu-
methods ever, difficult to improve. such as the DELTA- rity. They have, how-
differential criterion for ever, difficulties during
external faults. inrush currents both
with and without satu-
ration of the CTs.
Artificial The pattern recognition property of ANNs enables distinguishing the internal ANNs may be used as
Neural fault waves from all the other disturbances with high accuracy. This includes stand alone tools to
correct treatment of the cases with saturation of the CTs. mitigate the problem of
Networks saturation of the CTs -
either as saturation
detectors or algorithms
reconstructing the pri-
mary waves.
Fuzzy The multi-criteria decision making approach allows employing many different The fuzzy filtering may
Sets and protection principle for inrush, overexcitation and external faults in parallel. It be a partial remedy for
enables one to improve both security and dependability of the relay. measuring errors
Logic caused by the satu-
rated CTs.
Optical CTs The optical CTs allow No improvement Significant improvement by avoiding CT saturation
avoiding problems as- (a source of a false differential signal). The optical
sociated with CT satu- CTs may improve both dependability and security
ration during inrush. of the relay.
They are not, however,
helping detecting the
magnetizing inrush.
Extra External measurements helping tide an unknown Communicating with
External transient that triggered the relay with the source in other relays may help
the substation. This helps preventing false trip- the transformer relay to
Measurements pings during both magnetizing inrush and station- distinguish between
ary overexcitation conditions. internal and external Detecting internal faults
faults. based on more
Extra Direct detecting of core saturation may signifi- Directly detecting inter- information than just
Internal cantly enhance the relay security. nal faults (such as dis- the differential signal
charges) may enhance can enhance depend-
Measurements relay dependability. ability.
17