User Manual BACnet / Modbus Slave

Document code: MN67672_ENG Revision 1.001 Pagina 1 di 22


Industrial Electronic Devices

User Manual
Revision 1.001
English

BACnet / Modbus Slave - Converter


(Order Code: HD67672-A1)

for Website information:


www.adfweb.com?Product=HD67672

for Price information:


www.adfweb.com?Price=HD67672-A1

Benefits and Main Features: For others PROFINET products see also the following link:
Converter BACnet to
Very easy to configure www.adfweb.com?Product=HD67056 (M-Bus Master)
www.adfweb.com?Product=HD67671 (Modbus Master)
Electrical isolation
Other www.adfweb.com?Product=HD67672 (Modbus Slave)
Two BACnet ports Products www.adfweb.com?Product=HD67673 (Modbus TCP Master)
www.adfweb.com?Product=HD67674 (Modbus TCP Slave)
Temperature range: -40C/85C (-40F/185F) www.adfweb.com?Product=HD67675 (PROFIBUS Master)
www.adfweb.com?Product=HD67676 (PROFIBUS Slave)
www.adfweb.com?Product=HD67677 (CAN)
www.adfweb.com?Product=HD67678 (CANopen)
www.adfweb.com?Product=HD67679 (PROFINET)
www.adfweb.com?Product=HD67680 (DeviceNet Master)
www.adfweb.com?Product=HD67681 (DeviceNet Slave)
www.adfweb.com?Product=HD67682 (EtherNet/IP)
www.adfweb.com?Product=HD67683 (NMEA 2000)
www.adfweb.com?Product=HD67684 (Ethernet)

Do you have an your customer protocol?


www.adfweb.com?Product=HD67003
Do you need to choose a device? do you want help?
www.adfweb.com?Cmd=helpme

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 2 di 22
Industrial Electronic Devices

INDEX: UPDATED DOCUMENTATION:

Page Dear customer, we thank you for your attention and we remind you that
INDEX 2 you need to check that the following document is:
UPDATED DOCUMENTATION 2 Updated
REVISION LIST 2 Related to the product you own
WARNING 2
TRADEMARKS 2 To obtain the most recently updated document, note the document code
SECURITY ALERT 3 that appears at the top right-hand corner of each page of this document.
EXAMPLE OF CONNECTION 4
CONNECTION SCHEME 5 With this Document Code go to web page www.adfweb.com/download/
CHARACTERISTICS 7 and search for the corresponding code on the page. Click on the proper
CONFIGURATION 7 Document Code and download the updates.
POWER SUPPLY 8
FUNCTION MODES 9 To obtain the updated documentation for the product that you own, note
LEDS 10 the Document Code (Abbreviated written "Doc. Code" on the label on the
RS485 11 product) and download the updated from our web site
RS232 11 www.adfweb.com/download/
BACNET 12
USE OF COMPOSITOR SW67672 13
NEW PROJECT / OPEN PROJECT 13 REVISION LIST:
SET COMMUNICATION 14
SET BACNET ACCESS 15 Revision Date Author Chapter Description
OBJECTS MAP 16 1.000 15/02/2013 Fl All First Release
UPDATE DEVICE 17 1.001 01/08/2013 Fl All Revision
MECHANICAL DIMENSIONS 19
ORDERING INFORMATIONS 20
ACCESSORIES 20
DISCLAIMER 21
OTHER REGULATIONS AND STANDARDS 21 WARNING:
WARRANTIES AND TECHNICAL SUPPORT 22
RETURN POLICY 22 ADFweb.com reserves the right to change information in this manual about
our product without warning.
ADFweb.com is not responsible for any error this manual may contain.

TRADEMARKS:

All trademarks mentioned in this document belong to their respective


owners.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 3 di 22
Industrial Electronic Devices

SECURITY ALERT:

GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device are required for
each individual application, legal and safety regulation. The same applies also when using accessories.

INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e. independent limit
switches, mechanical interlocks, etc.).

QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and who
have appropriate qualifications for their job.

RESIDUAL RISKS
The device is state of the art and is safe. The instrument can represent a potential hazard if they are inappropriately installed and operated
by personnel untrained. These instructions refer to residual risks with the following symbol:

This symbol indicates that non-observance of the safety instructions is danger for people to serious injury or death and / or the
possibility of damage.

CE CONFORMITY
The declaration is made by us. You can send an email to [email protected] or give us a call if you need it.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 4 di 22
Industrial Electronic Devices

EXAMPLE OF CONNECTION:

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 5 di 22
Industrial Electronic Devices

CONNECTION SCHEME:

Figure 1a: Connection scheme for HD67672-232-A1


ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 6 di 22
Industrial Electronic Devices

Figure 1b: Connection scheme for HD67672-485-A1

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 7 di 22
Industrial Electronic Devices

CHARACTERISTICS:

The HD67672-A1 is a BACnet / Modbus Slave Converter.

It has the following characteristics:


Up to 2048 BACnet objects (Read+Write);
Triple isolation between BACnet - Power Supply, BACnet - Modbus, Power Supply - Modbus.
Two-directional information between BACnet bus and Modbus bus;
Mountable on 35mm Rail DIN;
Wide power supply input range: 824V AC or 1235V DC;
Wide temperature range: -40C / 85C [-40F / +185F].

CONFIGURATION:

You need Compositor SW67672 software on your PC in order to perform the following:
Define the parameter of BACnet line;
Define the parameter of Modbus line;
Define BACnet objects that contains the data sent by the Master Modbus;
Define BACnet objects that contains the data to sent to the Master Modbus;
Update the device.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 8 di 22
Industrial Electronic Devices

POWER SUPPLY:

The devices can be powered at 824V AC and 1235V DC. For more details see the two tables below.

VAC VDC
Vmin Vmax Vmin Vmax
8V 24V 12V 35V

Consumption at 24V DC:

Device Consumption [W/VA]


HD67672-A1 3.5

Caution: Not reverse the polarity power

HD67672-A1

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 9 di 22
Industrial Electronic Devices

FUNCTION MODES:

The device has got two functions mode depending of the position of the Dip2 of Dip-Switch A:
The first, with Dip2 of Dip-Switch A at OFF position, is used for the normal working of the device.
The second, with Dip2 of Dip-Switch A at ON position, is used for upload the Project and/or Firmware.

For the operations to follow for the updating, see UPDATE DEVICE section.

According to the functioning mode, the LEDs will have specifics functions, see LEDS section.

Warning:
Dip1 of Dip-Switch A must be at ON position for working even if the Ethernet cable isnt inserted.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 10 di 22
Industrial Electronic Devices

LEDS:

The device has got six LEDs that are used to give information of the functioning status.
The various meanings of the LEDs are described in the table below.

LED Normal Mode Boot Mode


1: ON [supply voltage ] ON: Device powered ON: Device powered
(green) OFF: Device not powered OFF: Device not powered
Blinks quickly: Boot state
2: Modbus comm. (green) Change state when arrive Modbus requests
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
3: Device state (green) Blinks slowly (~1Hz)
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
4: Not used (green) OFF
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
5: Ethernet1 Tx (green) Blinks when is transmitting Ethernet frames
Blinks very slowly (~0.5Hz): update in progress
Blinks quickly: Boot state
6: Ethernet2 Tx (green) Blinks when is transmitting Ethernet frames
Blinks very slowly (~0.5Hz): update in progress

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 11 di 22
Industrial Electronic Devices

RS485:

For terminate the RS485 line with a 220 resistor it is necessary to put ON dip 1, like in figure.

The maximum length of the cable should be 1200m (4000 feet).

Here some codes of cables:


Belden: p/n 8132 - 2x 28AWG stranded twisted pairs conductor + foil shield + braid shield;
Belden p/n 82842 - 2x 24AWG stranded twisted pairs conductor + foil shield + braid shield;
Tasker: p/n C521 - 1x 24AWG twisted pair conductor + foil shield + braid shield;
Tasker: p/n C522 - 2x 24AWG twisted pairs conductor + foil shield + braid shield.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 12 di 22
Industrial Electronic Devices

RS232:

The connection from RS232 socket to a serial port (example one from a personal computer) must be made with a NULL MODEM cable (a
serial cable where the pins 2 and 3 are crossed).
It is recommended that the RS232 cable not exceed 15 meters.

BACNET:

The BACnet connection must be made using Connector3 and/or Connector4 of HD67672-232-A1 or HD67672-485-A1 with at least a
Category 5E cable. The maximum length of the cable should not exceed 100m. The cable has to conform to the T568 norms relative to
connections in cat.5 up to 100 Mbps. To connect the device to an Hub/Switch is recommended the use of a straight cable, to connect the
device to a PC/PLC/other is recommended the use of a cross cable.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 13 di 22
Industrial Electronic Devices

USE OF COMPOSITOR SW67672:

To configure the Converter, use the available software that runs with
Windows, called SW67605. It is downloadable on the site
www.adfweb.com and its operation is described in this document.
(This manual is referenced to the last version of the software present
on our web site). The software works with MSWindows (MS 2000, XP,
Vista, Seven, 8; 32/64bit).

When launching the SW67672 the right window appears (Fig. 2).

Note:
It is necessary to have installed .Net Framework 4.

Figure 2: Main window for SW67672

NEW PROJECT / OPEN PROJECT:

The New Project button creates the folder which contains the entire device configuration.

A device configuration can also be imported or exported:


To clone the configurations of a programmable BACnet / Modbus Slave Converter in
order to configure another device in the same manner, it is necessary to maintain the folder
and all its contents;
To clone a project in order to obtain a different version of the project, it is sufficient to
duplicate the project folder with another name and open the new folder with the button
Open Project.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 14 di 22
Industrial Electronic Devices

SET COMMUNICATION:

This section define the fundamental communication parameters of two buses, BACnet and Modbus
Slave.

By Pressing the Set Communication button from the main window for SW67672 (Fig. 2) the
window Set Communication appears (Fig. 3).
The window is divided in two sections, one for the BACnet and the other for the Modbus Slave.

The means of the fields for BACnet are:


In the fields IP ADDRESS insert the IP address that you want to give to the Converter;
In the fields SUBNET Mask insert the SubNet Mask;
In the fields GATEWAY insert the default gateway that you want to use. This feature can
be enabled or disabled pressing the Check Box field. This feature is used for going out of the
net;
In the field Port the port used for BACnet communication is defined. The port has a fixed
value of 47808;
In the field "BACnet Device Name" is possible to assign a name to the BACnet node;
In the field Device Identifier is possible to assign a number to the BACnet node (Used for
the Device Identifier).

The means of the fields for the Modbus Slave section are:
In the field Serial is possible to select the serial (between RS232 and RS485) used for the
Modbus Communication;
In the field Baudrate it is possible to select the baudrate of the Modbus line;
In the field Parity it is possible to select the parity of the Modbus line;
In the ID Device field the Modbus Slave ID is defined.

Figure 3: Set Communication window

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 15 di 22
Industrial Electronic Devices

SET BACNET ACCESS:

By Pressing the Set BACnet Access


button from the main window for SW67672
(Fig. 2) the window Set Communication
appears (Fig. 4).

The window is divided in two parts, the


BACnet in Read that contains the BACnet
objects readable by a BACnet Master (the
Modbus registers associated to these
objects are writeable by a Modbus master);
and BACnet in Write that contains the
BACnet objects writeable by a BACnet
Master (the Modbus registers associated to
these objects are readable by a Modbus
Master).

The meaning of the fields in the window are


the follows:
In the field Data Type is possible
to select the BACnet object data Figure 4: BACnet Set Access window
type;
In the field Eng. Unit, with double click the window Select the BACnet Engineering Unit appears (Fig. 5);
In the field Position is possible to select the position where take/save the data from a 1400 bytes array;
The field Start Bit is used for the Binary In and Binary Out BACnet objects;
The field Length is used for all the others BACnet objects.

At Modbus side when using Holding Register and Input Register, byte 0 and 1 of the 1400 elements array (Position field) is the Modbus
Address 0, byte 2 and 3 are Modbus Address 1 and so on.
For Coil Status and Input Status the byte 0 is the Modbus Address 0m byte 1 is the Modbus Address 0 and so on.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 16 di 22
Industrial Electronic Devices

Is possible to insert directly the Unit (using its unique number) by compiling the
Selected BACnet Engineering Unit field; or by selecting with the fields
Select the Type and Select unit the Type/Unit desired. If the second way is
used, is necessary to press the Select Engineering Unit button for confirm the
choice.

Figure 5: Select the BACnet Engineering Unit window

OBJECTS MAP:

By Pressing the Objects Map button from the main window for SW67762 (Fig. 2) is possible to create a .csv document with the map of
BACnet Objects.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 17 di 22
Industrial Electronic Devices

UPDATE DEVICE:

By pressing the Update Device button it is possible to load the created Configuration into the
device; and also the Firmware, if is necessary.

If you dont know the actual IP address of the device you have to use this procedure:
Turn off the Device;
Put Dip2 of Dip-Switch A at ON position;
Turn on the device
Connect the Ethernet cable;
Insert the IP 192.168.2.205;
Press the Ping button, must appear Device Found!;
Press the Next button;
Select which operations you want to do;
Press the Execute update firmware button to start the upload;
When all the operations are OK turn off the Device;
Put Dip2 of Dip-Switch A at OFF position;
Turn on the device.

At this point the configuration/firmware on the device is correctly updated.

Figure 6: Update device windows

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 18 di 22
Industrial Electronic Devices

If you know the actual IP address of the device you have to use this procedure:
Turn on the Device with the Ethernet cable inserted;
Insert the actual IP of the Converter;
Press the Ping button, must appear Device Found!;
Press the Next button;
Select which operations you want to do;
Press the Execute update firmware button to start the upload;
When all the operations are OK the device automatically goes at
Normal Mode.

At this point the configuration/firmware on the device is correctly update.

Note:
When you install a new version of the software it is better if the first time you do the update of the Firmware in the HD67672-A1
device.

Note:
When you receive the device, for the first time, you have to update also the Firmware in the HD67672-A1 device.

Warning:
If the Fig. 7 appears when you try to do the Update before require assistance try these points:
Try to repeat the operations for the updating;
Try with another PC;
Try to restart the PC;
If you are using the program inside a Virtual Machine, try to use in the main
Operating System;
If you are using Windows Seven or Vista or 8, make sure that you have the
administrator privileges;
Take attention at Firewall lock;
Check the LAN settings. Figure 7: Protection window

In the case of HD67672-A1 you have to use the software SW67672: www.adfweb.com\download\filefold\SW67672.zip.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 19 di 22
Industrial Electronic Devices

MECHANICAL DIMENSIONS:

Figure 8: Mechanical dimensions scheme for HD67672-232-A1 Figure 9: Mechanical dimensions scheme for HD67672-485-A1

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 20 di 22
Industrial Electronic Devices

ORDERING INFORMATIONS:

The ordering part number is formed by a valid combination of the following:


HD67672 232 A 1

Connectors Type
1: Removable 5mm Screw Terminal

Enclosure Type
A: 1M, 35mm DIN Rail mounting

Modbus port
232: RS232
485: RS485

Device Family
HD67672: BACnet / Modbus Slave - Converter

Order Code: HD67672-232-A1 - BACnet / Modbus Slave - Converter


Order Code: HD67672-485-A1 - BACnet / Modbus Slave - Converter

ACCESSORIES:

Order Code: AC34001 - 35mm Rail DIN - Power Supply 220/240V AC 50/60Hz 12 V AC
Order Code: AC34002 - 35mm Rail DIN - Power Supply 110V AC 50/60Hz 12 V AC

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 21 di 22
Industrial Electronic Devices

DISCLAIMER

All technical content within this document can be modified without notice. The content of the document content is a recurring audit.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.

OTHER REGULATIONS AND STANDARDS

WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and human health, which could otherwise be caused by
inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about recycling this
product, please contact your local city office, your household waste disposal service or the shop where you purchased the product.

RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE


The device respects the 2002/95/EC Directive on the restriction of the use of certain hazardous substances in electrical
and electronic equipment (commonly referred to as Restriction of Hazardous Substances Directive or RoHS).

CE MARKING
The product conforms with the essential requirements of the applicable EC directives.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual BACnet / Modbus Slave
Document code: MN67672_ENG Revision 1.001 Pagina 22 di 22
Industrial Electronic Devices

WARRANTIES AND TECHNICAL SUPPORT:

For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]

RETURN POLICY:

If while using your product you have any problem and you wish to exchange or repair it, please do the following:
1) Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to
provide detailed information about the problem.
2) Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be