100% found this document useful (1 vote)
230 views7 pages

Restrained Joint Calculations

This document provides design calculations for pipe restraint lengths for bends and tees in a water network extension project in Ajman, UAE. It includes design data such as pipe diameters, pressures, soil properties, and calculations of forces and lengths. The main results are: - For a 90 degree bend in a 600mm diameter pipe, provide a restrained length of 69.05m on both sides of the bend. - For a 600x600x250mm tee reducer, provide a restrained length of 0m on the 250mm branch and 5.225m on both sides of the 600mm run. - Key parameters calculated include unit frictional force, passive soil pressure, and maximum lateral

Uploaded by

renishkavukatt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
230 views7 pages

Restrained Joint Calculations

This document provides design calculations for pipe restraint lengths for bends and tees in a water network extension project in Ajman, UAE. It includes design data such as pipe diameters, pressures, soil properties, and calculations of forces and lengths. The main results are: - For a 90 degree bend in a 600mm diameter pipe, provide a restrained length of 69.05m on both sides of the bend. - For a 600x600x250mm tee reducer, provide a restrained length of 0m on the 250mm branch and 5.225m on both sides of the 600mm run. - Key parameters calculated include unit frictional force, passive soil pressure, and maximum lateral

Uploaded by

renishkavukatt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 7

Al Muzaki Contracting Co LLC

Water Network Extension for Al Jurf, Al


Post Box No.12444 Project :
Raqaeb& Al Helwa Areas- Ajman
Ras Al Khamiah, UAE
Tel : 0097172236815 Made Chkd Apvd
PLJ TSR ASM Date 29-Oct-17
Fax : 0097172236299 By by by

Restrained Pipe for DI Pipe Line 600 mm diameter - 90 deg. bend-16 bar pressure

DESIGN DATA

Nominal Pipe Diameter (D) = 600 mm ###

Maximum Internal Pressure (p) = 1600 kN/m###


2

Depth of earth cover (h1) = 1000 mm

Maximum density of ductile iron pipe = 78.50 kN/m

Unit Weight of Water (w) = 10 kN/m3

Unit Weight of Filled soil (s) = 16 kN/m###


3

Degree of bent () = 90.00 degrees

Type of Soil------------------- Sandy Soil with Silt

Laying Condition - Flat Bottom Trench - Backfill lightly consolidated to centreline of pipe

Value , f = 0.50

Value, Cs = 0

Value, fc = 0

Constant, Kn = 0.40

Angle of internal friction of soil, = 25 degrees

Safety Factor (Sf) = 1.5

Unit Frictional Force, Fs = D/2 C+(2We+Wp+Ww)tan

According to EN 598 :2007

Thickness of pipe = 9.6 mm ###

Hence, weight of the pipe per running metre = 1.40 kN/m###

Weight of water inside the pipe = 2.83 kN/m###


Al Muzaki Contracting Co LLC
Water Network Extension for Al Jurf, Al
Post Box No.12444 Project :
Raqaeb& Al Helwa Areas- Ajman
Ras Al Khamiah, UAE
Tel : 0097172236815 Made Chkd Apvd
PLJ TSR ASM Date 29-Oct-17
Fax : 0097172236299 By by by

Restrained Pipe for DI Pipe Line 600 mm diameter - 90 deg. bend-16 bar pressure

Total weight of water + pipe with addition of 10% (W p+Ww) = 4.65 kN/m###

Pressure from Earth Loading (as per clause D.1.2-EN 598:2007), W e = 9.60 kN/m###

= 13 degrees

Hence unit frictional force, Fs = 5.29 kN/m###

Since the pipe is enclosed in polyethylene, Ff = 3.7 kN/m###

The passive soil pressure, Pp = HcN+2CsN


N=tan(45+/2)
where , = 2.46 ###

Hc = 1300 mm ###

Hence passive soil pressure, Pp = = 51.19 kN/m###

The maximum unit lateral resistance, Rs =KnPpD = 12.29 kN/m###


(SfPAtan(/2))/
Hence length of the restrained pipe, L = (Ff+Rs/2) = 69.05 m ###

Provide restrained length of 69.05 m on both sides of the bend


Al Muzaki Contracting Co LLC
Water Network Extension for Al Jurf, Al
Post Box No.12444 Project :
Raqaeb& Al Helwa Areas- Ajman
Ras Al Khamiah, UAE
Tel : 0097172236815 Made Chkd Apvd
PLJ TSR ASM Date 29-Oct-17
Fax : 0097172236299 By by by

Restrained Pipe for DI Pipe Line 600x600x250 mm Tee Reducer -16 bar pressure

DESIGN DATA

Nominal Pipe Diameter (D) (Main) = 600 mm ###

Nominal Pipe Diameter of Branch (D') = 250 mm ###

Maximum Internal Pressure (p) = 1600 kN/m###


2

Assumed Restr. length between first joints on either side of tee on the run (L r) = 10450 mm ###

Depth of earth cover (h1) = 2100 mm

Maximum density of ductile iron pipe = 78.50 kN/m

Unit Weight of Water (w) = 10 kN/m3

Unit Weight of Filled soil (s) = 16 kN/m###


3

Type of Soil------------------- Sandy Soil

Laying Condition - Flat Bottom Trench - Backfill lightly consolidated to centreline of pipe

Value , f = 0.50

Value, Cs = 0

Value, fc = 0

Constant, Kn = 0.40

Angle of internal friction of soil, = 25 degrees

Safety Factor (Sf) = 1.5

Unit Frictional Force, Fs = D/2 C+(2We+Wp+Ww)tan

According to EN 598 :2007

Thickness of pipe = 9.6 mm ###


Al Muzaki Contracting Co LLC
Water Network Extension for Al Jurf, Al
Post Box No.12444 Project :
Raqaeb& Al Helwa Areas- Ajman
Ras Al Khamiah, UAE
Tel : 0097172236815 Made Chkd Apvd
PLJ TSR ASM Date 29-Oct-17
Fax : 0097172236299 By by by

Restrained Pipe for DI Pipe Line 600x600x250 mm Tee Reducer -16 bar pressure

Hence, weight of the pipe per running metre = 1.40 kN/m###

Weight of water inside the pipe = 2.83 kN/m###

Total weight of water + pipe with addition of 10% (W p+Ww) = 4.65 kN/m###

Pressure from Earth Loading (as per clause D.1.2-EN 598:2007), W e = 20.16 kN/m###

= 13 degrees

Hence unit frictional force, Fs = 9.97 kN/m###

Since the pipe is enclosed in polyethylene, Ff = 6.98 kN/m###

The passive soil pressure, Pp = HcN+2CsN


N=tan(45+/2)
where , = 2.46 ###

Hc = 2400 mm ###

Hence passive soil pressure, Pp = = 94.51 kN/m###

The maximum unit lateral resistance, Rs =KnPpD = 22.68 kN/m###


(SfPAb-RsLr/2)/Ff
Hence length of the restrained pipe, L = = -0.07 m ###

Hence

Provide restrained length of 0 m on the branch of 250 mm side

Provide restrained length of 5.225 m on the run of 600 mm side

Provide restrained length of 5.225 m on the run of 600 mm side


Al Muzaki Contracting Co LLC
Water Network Extension for Al Jurf, Al
Post Box No.12444 Project :
Raqaeb& Al Helwa Areas- Ajman
Ras Al Khamiah, UAE
Tel : 0097172236815 Made Chkd Apvd
PLJ TSR ASM Date 29-Oct-17
Fax : 0097172236299 By by by

Restrained Pipe for DI Pipe Line 600x400 mm taper -16 bar pressure

DESIGN DATA

Nominal Pipe Diameter (D) (Larger) = 600 mm ###

Nominal Pipe Diameter of Branch (D') (Smaller) = 400 mm ###

Maximum Internal Pressure (p) = 1600 kN/m###


2

Depth of earth cover (h1) = 1200 mm

Maximum density of ductile iron pipe = 78.50 kN/m

Unit Weight of Water (w) = 10 kN/m3

Unit Weight of Filled soil (s) = 18 kN/m###


3

Unit Weight of concrete (c) = 25 kN/m3

Type of Soil------------------- Sandy Soil

Laying Condition - Flat Bottom Trench - Backfill lightly consolidated to centreline of pipe

Value , f = 0.75

Value, Cs = 0

Value, fc = 0

Constant, Kn = 0.40

Angle of internal friction of soil, = 36 degrees

Depth of Water table from ground level = 0 mm

Safety Factor (Sf) = 1.5

Unit Frictional Force, Fs = D/2 C+(2We+Wp+Ww)tan

According to EN 598 :2007

Thickness of pipe (type 1) = 9.6 mm ###


Al Muzaki Contracting Co LLC
Water Network Extension for Al Jurf, Al
Post Box No.12444 Project :
Raqaeb& Al Helwa Areas- Ajman
Ras Al Khamiah, UAE
Tel : 0097172236815 Made Chkd Apvd
PLJ TSR ASM Date 29-Oct-17
Fax : 0097172236299 By by by

Restrained Pipe for DI Pipe Line 600x400 mm taper -16 bar pressure

Hence, weight of the pipe per running metre = 1.40 kN/m###

Weight of water inside the pipe = 2.83 kN/m###

Total weight of water + pipe with addition of 10% (W p+Ww) = 4.65 kN/m###

Pressure from Earth Loading (as per clause D.1.2-EN 598:2007), W e = 12.96 kN/m###

= 27 degrees

Hence unit frictional force, Fs = 15.58 kN/m###

Since the pipe is enclosed in polyethylene, Ff1 = 10.91 kN/m###

Thickness of pipe (type 1) = 8 mm ###

Hence, weight of the pipe per running metre = 0.77 kN/m###

Weight of water inside the pipe = 1.26 kN/m###

Total weight of water + pipe with addition of 10% (W p+Ww) = 2.23 kN/m###

Pressure from Earth Loading (as per clause D.1.2-EN 598:2007), W e = 8.64 kN/m###

= 27 degrees

Hence unit frictional force, Fs = 9.94 kN/m###

Since the pipe is enclosed in polyethylene, Ff2 = 6.96 kN/m###

Hence length of the restrained pipe, L1 = (SfP(A1-A2))/Ff1 = 34.6 m ###

###

Hence length of the restrained pipe, L2 = (SfP(A1-A2))/Ff2 = 54.24 m

Provide restrained length of 34.6 m on the 600 mm side


Al Muzaki Contracting Co LLC
Water Network Extension for Al Jurf, Al
Post Box No.12444 Project :
Raqaeb& Al Helwa Areas- Ajman
Ras Al Khamiah, UAE
Tel : 0097172236815 Made Chkd Apvd
PLJ TSR ASM Date 29-Oct-17
Fax : 0097172236299 By by by

Restrained Pipe for DI Pipe Line 600x400 mm taper -16 bar pressure

Provide restrained length of 54.24 m on the run of 400 mm side

You might also like