Rva47 B

Download as pdf or txt
Download as pdf or txt
You are on page 1of 166

RVA47.

320
Cascade Controller for modulating gas-fired Boilers
Basic Documentation

Ausgabe 2.2
Controller series B
CE1P2379E Siemens Building Technologies
15.07.2002 HVAC Products
2/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products 15.07.2002
Contents
1 Summary ......................................................................................................... 8
1.1 Brief description............................................................................................... 8
1.2 Features .......................................................................................................... 9
1.3 Range of products ......................................................................................... 11
1.4 Field of use .................................................................................................... 12
1.5 Product liability .............................................................................................. 12

2 Handling ........................................................................................................ 13
2.1 Installation ..................................................................................................... 13
2.1.1 Mounting location .......................................................................................... 13
2.1.2 Regulations for installation ............................................................................ 13
2.1.3 Mounting procedure....................................................................................... 13
2.1.4 Required cut-out ............................................................................................ 15
2.1.5 Orientation ..................................................................................................... 15
2.2 Electrical installation ...................................................................................... 16
2.2.1 Regulations for installation ............................................................................ 16
2.2.2 Wiring ............................................................................................................ 16
2.3 Commissioning .............................................................................................. 18
2.3.1 Functional checks.......................................................................................... 18
2.4 Parameter settings for the enduser ............................................................... 20
2.4.1 Overview of enduser parameters .................................................................. 21
2.5 Parameter settings for the heating engineer ................................................. 22
2.5.1 Overview of heating engineer parameters..................................................... 23
2.6 Parameter settings for the OEM .................................................................... 27
2.6.1 Overview of OEM parameters ....................................................................... 28
2.7 Operation....................................................................................................... 30
2.7.1 Operating elements ....................................................................................... 30
2.8 Operational faults .......................................................................................... 31

3 Description of the enduser settings ............................................................... 32

User interface ................................................................................................................ 32


3.1 Heating circuit operating modes .................................................................... 32
3.2 Operating mode of d.h.w. heating ................................................................. 33
3.3 Nominal room temperature setpoint .............................................................. 34
3.4 Manual operation........................................................................................... 35
Setting the clock ............................................................................................................ 37
3.5 Time of day.................................................................................................... 37
3.6 Weekday........................................................................................................ 37
3.7 Date (day, month).......................................................................................... 38
3.8 Year ............................................................................................................... 38
Time switch program for space heating......................................................................... 39
3.9 Preselecting the weekday.............................................................................. 39
3.10 Switching times.............................................................................................. 40
D.h.w. values ................................................................................................................. 42
3.11 Nominal d.h.w. temperature setpoint............................................................. 42
Heating circuit values .................................................................................................... 43
3.12 Reduced room temperature setpoint ............................................................. 43
3.13 Frost protection setpoint of the room temperature ........................................ 44
3.14 Summer / winter changeover temperature of the heating circuit ................... 44
3.15 Heating curve slope....................................................................................... 46

3/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Contents 15.07.2002
Actual values..................................................................................................................48
3.16 Actual value of the room temperature............................................................48
3.17 Actual value of outside temperature ..............................................................48
Maintenance ..................................................................................................................49
3.18 Standard time switch program for heating circuit and d.h.w. .........................49
Time switch program for d.h.w. heating .........................................................................50
3.19 Preselecting the weekday ..............................................................................50
3.20 Switching times ..............................................................................................50
Service . ...................................................................................................................52
3.21 Displaying the BMU error code ......................................................................52
3.22 Indication of faults ..........................................................................................53

4 Description of the heating engineer settings..................................................55

Service values................................................................................................................55
4.1 Output test .....................................................................................................55
4.2 Input test ........................................................................................................55
4.3 Display of plant type.......................................................................................56
4.4 Displaying the PPS communication ...............................................................58
Actual values..................................................................................................................60
4.5 Actual boiler temperature values of BMUs (TKx)...........................................60
4.6 Actual value of cascade flow temperature .....................................................60
4.7 Actual value of the cascade return temperature ............................................61
4.8 Actual value of buffer storage tank temperature ............................................63
4.9 Actual value of the d.h.w. temperature (TBWx) .............................................63
4.10 Attenuated outside temperature.....................................................................64
4.11 Composite outside temperature.....................................................................65
Setpoints . ..................................................................................................................66
4.12 Outside temperature source ..........................................................................66
4.13 Boiler temperature setpoint of BMUs .............................................................66
4.14 Setpoint of the cascade flow temperature......................................................67
4.15 D.h.w temperature setpoint............................................................................67
4.16 Nominal room temperature setpoint...............................................................68
4.17 Room temperature setpoint ...........................................................................69
4.18 Flow temperature setpoint .............................................................................69
Heat generation values ..................................................................................................70
4.19 Existing boilers...............................................................................................70
4.20 Display lead boiler..........................................................................................70
4.21 Remaining number of operating hours for changeover of boiler sequence ...71
4.22 Burner operating hours BMU 1 4 ................................................................72
4.23 Minimum limitation of the boiler temperature TKmin......................................72
4.24 Nominal output of BMU 1 - 4..........................................................................73
Configuration of plant .....................................................................................................74
4.25 Pump function output Q1 ...............................................................................74
4.26 Use sensor input B70/B4 ...............................................................................74
Heating circuit values .....................................................................................................76
4.27 Parallel displacement of the heating curve ....................................................76
4.28 Room influence ..............................................................................................76
4.29 Switching differential of the room temperature ..............................................77
4.30 Minimum limitation of the flow temperature setpoint......................................78
4.31 Maximum limitation of the flow temperature setpoint.....................................79
4.32 Type of building construction .........................................................................80
4.33 Adaption of the heating curve ........................................................................81

4/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Contents 15.07.2002
4.34 Maximum forward shift of optimum start control............................................ 82
4.34.1 Optimum start control .................................................................................... 83
4.34.2 Without room influence.................................................................................. 83
4.34.3 With room influence....................................................................................... 83
4.35 Maximum forward shift of optimum stop control ............................................ 84
4.35.1 Optimum stop control .................................................................................... 84
D.h.w. values ................................................................................................................. 85
4.36 Reduced setpoint of the d.h.w. temperature.................................................. 85
4.37 Release of d.h.w. heating .............................................................................. 85
4.37.1 24-hour operation - Setting 0......................................................................... 86
4.37.2 Operation according to heating program(s) with forward shift - Setting 1 ..... 86
4.37.3 Operation according to the d.h.w. time switch program - Setting 2 ............... 87
4.38 Switching program circulating pump.............................................................. 87
4.39 Assignment of d.h.w. heating ........................................................................ 88
4.40 Number of d.h.w. charging cycles ................................................................. 88
4.40.1 Once per day with a forward shift of 2.5 hours Setting 0............................... 89
4.40.2 Several times per day with a forward shift of 1 hour Setting 1 ...................... 89
4.41 Type of d.h.w. demand .................................................................................. 89
4.42 Boost of the flow temperature setpoint for d.h.w. .......................................... 90
4.43 D.h.w. priority................................................................................................. 91
4.43.1 Shifting priority............................................................................................... 92
4.44 Demand for heat with reduced d.h.w. setpoint .............................................. 94
Cascade settings ........................................................................................................... 95
4.45 Changeover of boiler sequence in a cascade ............................................... 95
4.46 Exemption from automatic changeover of the boiler sequence..................... 96
4.47 Lead boiler with a fixed changeover of the boiler sequence.......................... 97
4.48 Switch-on delay lag boilers............................................................................ 98
4.49 Restart lock of BMUs..................................................................................... 98
LPB / system ................................................................................................................. 99
4.50 LPB device address....................................................................................... 99
4.51 LPB segment address ................................................................................. 100
4.52 LPB power supply........................................................................................ 100
4.53 Displaying the LPB power supply ................................................................ 101
4.54 Displaying the LPB communication ............................................................. 101
4.55 Range of action of central changeover........................................................ 102
4.56 Automatic summer / winter changeover ...................................................... 102
4.57 Central standby switch ................................................................................ 103
4.58 Clock mode.................................................................................................. 103
4.59 Winter- / summertime changeover .............................................................. 104
4.60 Summer- / wintertime changeover............................................................... 105
Input H1 . .............................................................................................................. 106
4.61 Input H1 ....................................................................................................... 106
4.61.1 Changeover of operating mode (remote telephone switch) - Setting 0 / 1 107
4.61.2 Minimum setpoint of flow temperature contact H1 ...................................... 108
4.61.3 Heat generation lock - Setting 3 ................................................................ 108
4.61.4 Demand for heat - Setting 4 ...................................................................... 109
4.62 Minimum setpoint of flow temperature contact H1 ...................................... 110
4.63 Maximum value of heat demand signal DC 0...10 V (H1) ........................... 111
4.64 Operating action of the contact connected to H1 ........................................ 111

5 Description of the OEM settings .................................................................. 112

Heat generation values................................................................................................ 112


5.1 Minimum limitation of the boiler temperature setpoint OEM (TKminOEM)..... 112

5/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Contents 15.07.2002
5.2 Maximum limitation of the boiler temperature setpoint ................................112
5.3 Pump overrun time.......................................................................................113
5.4 Minimum limitation of the boiler return temperature.....................................113
5.5 Calibration of actual output range of BMU 1-4.............................................114
Heating circuit values ...................................................................................................115
5.6 Gain factor of room influence (KORR) .........................................................115
5.7 Constant for quick setback (KON) ...............................................................116
5.8 Boost of room temperature setpoint.............................................................117
5.9 Frost protection for the plant ........................................................................118
5.10 Overtemperature protection for the pump heating circuit.............................119
5.11 Heat gains....................................................................................................120
5.12 Adaption sensitivity 1 ...................................................................................120
5.13 Adaption sensitivity 2 ...................................................................................121
D.h.w. values ...............................................................................................................123
5.14 Maximum nominal setpoint of d.h.w. temperature .......................................123
5.15 Switching differential of the d.h.w. temperature ...........................................123
5.16 Legionella function .......................................................................................124
5.17 Setpoint of the legionella function ................................................................125
5.18 Protection against discharging of d.h.w. ......................................................125
Cascade settings .........................................................................................................127
5.19 Cascade management strategy ...................................................................127
5.19.1 Type of lead boiler operation .......................................................................128
5.19.2 Running time strategies ...............................................................................129
5.20 Lower limit of output range (Pmin) ...............................................................131
5.21 Upper limit of output range (Pmax) ..............................................................132
5.22 Mandatory time on basic stage ....................................................................132
5.23 Minimum temperature differential at the pressureless header.....................133
Configuration of plant ...................................................................................................134
5.24 Continuous display.......................................................................................134
General values .............................................................................................................135
5.25 Software version ..........................................................................................135
5.26 Device operating hours ................................................................................135

6 Functions with no settings............................................................................136


6.1 Chimney sweep ...........................................................................................136
6.2 Generating the boiler temperature setpoint .................................................136
6.3 Automatic 24-hour heating limit ...................................................................137
6.3.1 Without room influence ................................................................................137
6.3.2 With room influence .....................................................................................138
6.4 Quick setback with room sensor ..................................................................139
6.5 D.h.w. push ..................................................................................................140
6.6 Pump kick ....................................................................................................141
6.7 Protection against discharging after d.h.w. heating .....................................141
6.8 Overview of pump operation ........................................................................142
6.9 Frost protection ............................................................................................143
6.9.1 For the boiler................................................................................................143
6.9.2 For the d.h.w. ...............................................................................................143

7 Application examples ...................................................................................144


7.1 Plant types RVA47.320 - no. 27...................................................................145
7.2 Plant types RVA47.320 - no. 28...................................................................146
7.3 Plant types RVA47.320 - no. 29...................................................................147
7.4 Plant types RVA47.320 - no. 30...................................................................148

6/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Contents 15.07.2002
7.5 Plant types RVA47.320 - no. 31 .................................................................. 149
7.6 Plant types RVA47.320 - no. 32 .................................................................. 150
7.7 Plant types RVA47.320 - no. 33 .................................................................. 151
7.8 Plant types RVA47.320 - no. 34 .................................................................. 152
7.9 Plant types RVA47.320 - no. 35 .................................................................. 153
7.10 Plant types RVA47.320 - no. 36 .................................................................. 154
7.11 Plant types RVA47.320 - no. 65 .................................................................. 155
7.12 Plant types RVA47.320 - no. 66 .................................................................. 156
7.13 Plant types RVA47.320 - no. 67 .................................................................. 157
7.14 Legend......................................................................................................... 158

8 Dimensions.................................................................................................. 159

9 Technical data ............................................................................................. 160

7/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Contents 15.07.2002
1 Summary
1.1 Brief description

ALBATROS- RVA47.320 (B-series) is designed for use as a single-boiler controller or


cascade controller with up to 12 heat sources.
It is designed for integration in heat generating equipment / plants with
a modulating gas burner
a Boiler Management Unit (BMU)
d.h.w. heating with charging pump (via RVA47) or changeover valve
(via BMU)
a primary or heating circuit pump

Heating circuit control uses weather compensation while d.h.w. heating operates
depending on the storage tank temperature and the time program.

When employed in an interconnected system along with the ALBATROS controller


RVA43.222 (C-series), it is possible to operate mixed cascades (modulating / multi-
stage) with up to 15 heat sources.

Important When used in connection with gas-fired heating boilers, the availability of a BMU is
mandatory. Siemens offers different types of BMUs:
- Boiler Mangement Unit LMU5/6x
It is also possible to use BMUs of other manufacture if appropriately equipped. If you
intend to use a non-Siemens burner control in connection with the RVA47.230, please
contact your nearest Siemens representative.

Use in extensive systems The range of products comprises several units that complement one another in terms of
application and scope of functions. The controllers have communication capability and
can be combined to form heating systems that include up to 40 controllers.
For more detailed information about the generation of LPB systems, refer to "Local
Process Bus (LPB), Basic Documentation, System Engineering, document no.
CE1P2370E.

8/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Summary 15.07.2002
1.2 Features

Heating circuit Heating circuit control with a pump heating circuit


Remote operation via digital room unit
Quick setback and boost heating
Automatic 24-hour heating limit
Automatic summer / winter changeover
The building's thermal dynamics are taken into consideration
Automatic adjustment of the heating curve to the type of building construction and
the heat demand (provided a room unit is connected)
Overload detection (shifting priority)
Manual operation

Heat generation Cascading with up to 12 modulating heat sources controlled by one controller in
combination with BMUs via LPB
Cascading with up to 15 modulating heat sources and additional RVA47.320 (from
B-series) via PPS
Control of mixed cascades (modulating or multistage) with up to 12 heat sources in
combination with RVA43.222 (from C-series) with BMUs via LPB
Selectable boiler sequence and boiler strategy
Weather-compensated heating circuit control with or without room influence
Cascade flow temperature control depending on the heat demand signal from the
heating circuits connected to the system or from controllers outside the system (via
input H1)
Cascade flow temperature control depending on the temperature demand signal
(DC 010 V, input H1)
Adjustable maximum limitation of temperature demand signals delivered to the
heating boiler
Performance-related switching on / off of boilers, very accurate flow temperatures
Supervision of operating conditions at the pressureless header, low return
temperatures

Protection for the plant Protection against boiler overtemperatures (pump overrun)
Protective boiler startup (acting on the mixing valve)
Minimum limitation of the boiler return temperature (acting on the mixing valve)
Adjustable minimum and maximum limitation of boiler temperature (boiler flow
temperature)
Frost protection for the building, the plant and the boiler
Frost protection for the d.h.w. storage tank connected directly to the controller
Pump protection through periodic pump kick
Overtemperature protection for the pump heating circuit

9/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Summary 15.07.2002
Operation Temperature adjustment with the setpoint knob
7-day or 24-hour program for the heating circuit and d.h.w. heating
Automatic button for efficient operation throughout the year
D.h.w. button
Manual operation at the touch of a button
Output and input tests to aid commissioning and functional checks
Straightforward selection of operating mode via buttons
Change of operating mode via a remote switch (via contact H1)
Heat generation lock or minimum demand for heat with the remote switch (via
contact H1)
Service connection facility for local parameter settings and data logging

D.h.w. D.h.w. heating with charging pump or via BMU with diverting valve
D.h.w. control with temperature sensor or control thermostat
Selectable priority for d.h.w. heating
Selectable d.h.w. heating program
Adjustable boost of the d.h.w. charging temperature
Reduced setpoint of the d.h.w. temperature
Protection against discharging of d.h.w.
Automatic d.h.w. push
Legionella function

Use in extensive Communication via the Local Process Bus (LPB)


systems Communicating via point-to-point interface (PPS)
Controllers of other manufacture can deliver their heat demand signal by closing
potential-free contact H1
Controllers of other manufacture can deliver their analog heat demand by using DC
0...10 V signals
Input for cascade flow temperature sensor
Input for cascade return temperature sensor
Integrity of system architecture with all RVA... controllers
Can be extended to include 40 heating circuits (with central bus power supply)
Optional remote supervision
Error messages (own faults, faults of LPB devices, faults of PPS devices)

Logging Logging the individual BMU operating hours


Logging the number of device operating hours

10/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Summary 15.07.2002
1.3 Range of products

The following units and accessories are designed for use with the ALBATROS range:

Type of unit Description Documentation no.

Controllers RVA47.320 Cascade controller for modulating gas-fired heating CE1P2379E


boilers
RVA43.222 Boiler and heating circuit controller (from C-series) CE1P2390E
RVA46.531 Heating circuit controller CE1P2372E
RVA66.540 Heating circuit or primary controller CE1P2378E*

Burner controls LMU5/6x Siemens BMUs for heating circuit and d.h.w. control
............. Different types of non-Siemens burner controls for d.h.w. control (e.g.
MCBA)
OCI42 Communication interface RVA-LMU5/6x
RMCI Communication interface RVA-MCBA

Room units QAA10 Digital room sensor


QAA70 Digital, multifunctional room unit
QAA50 Digital room unit

Sensor QAC31 Outside sensor NTC 600


QAC21 Outside sensor LG-Ni 1000
QAZ21 Immersion sensor LG-Ni 1000 complete with cable
QAD21 Strap-on sensor LG-Ni 1000

Screw type terminal strips AGP2S.02M LPB (2 poles) violet


(Rast 5) AGP2S.02G Room unit (2 poles) blue
AGP2S.06A Sensor (6 poles) white
AGP3S.02D Mains (2 poles) black
AGP3S.03B Pumps (3 poles) brown

11/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Summary 15.07.2002
1.4 Field of use

Target market OEMs


Manufacturers of modulating gas-fired appliances with BMUs

Types of buildings Residential and non-residential buildings with own heating and d.h.w. heating
facility
Residential and non-residential buildings with a central heat generating plant

Types of heating systems Standard heating systems, such as:


Standard heating systems, such as radiator, convector, underfloor and ceiling
heating systems, and radiant panels
With or without d.h.w. heating

Heat generating Gas-fired heating boilers with modulating burners.


equipment Parallel cascading with lead / lag boiler changeover or fixed priority for up to 4
modulating gas-fired boilers (of identical or different capacities) with only one
controller
Parallel cascading with up to 16 modulating gas-fired boilers (of identical or
different capacities) with additional RVA47.320 (from B-series)
Mixed cascades with up to 16 modulating and multistage heat sources with
additional RVA47.320 (from B-series) and RVA43.222 (from C-series)

1.5 Product liability

The products may only be used in building services plant and applications as
described above
When using the products, all requirements specified in chapters "Handling" and
"Technical data" must be satisfied
When using the products in a system, all requirements contained in the
documentation Local Process Bus (LPB), Basic Documentation, System
Engineering (document no. CE1P2370E) must be satisfied
The local regulations for installation must be complied with

12/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Summary 15.07.2002
2 Handling

2.1 Installation
2.1.1 Mounting location

Boiler control panel


In the control panel front

2.1.2 Regulations for installation

A clearance of at least 10 mm must be provided on all sides of the controller,


enabling the unit to emit the amount of heat produced during its operation. The
space should not be accessible and no objects should be placed there.
The controller is designed for mounting in a boiler control panel. Power to the
controller may be supplied only after it is completely fitted in the cutout. If this is not
observed, there is a risk of electric shock near the terminals and through the
cooling slots.
If the controller shall be mounted directly on the wall, a housing must be used to
provide protection against electric shock hazard. The housing must have a
sufficient number of cooling slots at the bottom and the top, allowing the controller
to emit the heat it produces.
The controller has been designed based on the guidelines of safety class 2 and
must therefore be mounted in compliance with these regulations.
The controller may not be exposed to dripping water.
Permissible ambient temperature: 0...50 C

2.1.3 Mounting procedure

1. step Description Diagram


Turn off power supply
Pull the prefabricated cables
through the cut-out
Plug the connectors into the
respective sockets at the rear of the
controller
 Note:
The connectors are coded to make
certain they cannot be mixed up.

2379Z11

13/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2. step Check to ensure the fixing levers
are turned inward
Check to make certain there is
sufficient space between the front
panel and the fixing levers

2379Z12

3. step Slide the unit into the panel cut-out


without applying any force
 Note:
Do not use any tools when inserting
the unit into the cut-out. If it does not
fit, check the size of the cut-out and
the housing.

2379Z13

4. step Secure the fixing levers by


tightening the two screws on the
front of the controller.
 Note:
Tighten the screws only slightly .
When tightening the screws, the
fixing levers automatically assume
their correct positions.

2379Z14

14/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.1.4 Required cut-out

Dimensions of cut-out The controllers mounting dimensions are 91 x 91 mm.

Due to the dimensions of the front, however, the standard spacing is 96 mm.
The mechanical mounting facility allows the controller to be fitted in front panels having
a thickness of 2 to 10 mm.

2371M02
96 96

2...10

+0.8
92 -0
96
+0.8 +0.8
92 -0 92 -0
188

Use of several The mechanical mounting facility makes


controllers it possible to arrange several controllers
in a row in one cut-out. In that case, it is
merely necessary to have a wider panel
cutout.

2379Z15

2.1.5 Orientation

To avoid overtemperatures inside the


. 30
controller, the inclination may be no ma x
more than 30 and there must be a
clearance of at least 10 mm on all sides
of the unit. mm
10
This allows the controller to emit the
heat generated during operation.

mm
2371Z16 10

15/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.2 Electrical installation
2.2.1 Regulations for installation

The connections for mains and low voltage are separated


The wiring must be made in compliance with the requirements of safety class II.
This means that sensor and mains cables may not be run in the same duct

2.2.2 Wiring

When using prefabricated cables with connectors, the electrical installation is very
straightforward, owing to the coding.

Connection terminals

6 5 4 M 2 1 M M
B70/B4

B10

MD

MB
DB
H1

A6
B3

B9
M F1
Q1

N
Q3

3 2 F 4 3 2 F L N

2379A01

Rear of controller

16/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
Low voltage side Termina Terminals Connector
l
H1 input H1 AGP2S.06A (white)
B70/B4 Cascade return temperature sensor B70 or
buffer storage tank temperature sensor B4
B3 D.h.w. temperature sensor or thermostat
M Ground sensors
B10 Cascade flow temperature sensor
(common flow temperature sensor)
B9 Outside sensor
MD Ground PPS (room unit, BMU) AGP2S.02G (blue)
A6 PPS (room unit, BMU)
MB Ground bus (LPB) AGP2S.02M (violet)
DB Data bus (LPB)

Mains voltage side Termina Terminals Connector


l
Q3 D.h.w. charging pump AGP3S.03B (brown)
Q1 Heating circuit or system pump:
F1 Phase Q1 / Q3
- Not used -
- Not used
- Not used
- Not used
- Not used
L Live AC 230 V (mains connection) AGP3S.02D (black)
N Neutral conductor (mains connection)

17/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.3 Commissioning

Prerequisites To commission the controller:


1. Make certain that mounting and electrical installation are in compliance with the
relevant requirements.
2. Make all plant-specific settings as described in section "Parameter settings".
3. Reset the attenuated outside temperature (operating line 19).
4. Make the functional checks.

2.3.1 Functional checks

To facilitate commissioning and fault tracing, the controller allows output and input tests
to be made. With these tests, the controllers inputs and outputs can be checked.
Output test Buttons Explanation Line
(relays) 1
Press one of the line selection buttons.
This will take you to the programming level "Enduser.

2
Press both line selection buttons for at least 3 seconds.

This will take you to the programming level Heating


engineer and, at the same time, to the relay test (output
test).
3 Press the + or - button repeatedly, which will take you
one test step further:
Test step 0 All outputs are switched according to actual control
operation
Test step 1 All outputs are deactivated
Test step 2 D.h.w. charging pump (Q3) is activated
Test step 3 Heating circuit or system pump activated (Q1).

4
You leave the programming line "Output test by contin.
pressing either one of the line selection buttons, display

or one of the operating mode buttons

 Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating mode
selected last.
2379Z02

Display

a)
c) b)

0 4 8 12 16 20 24

a) The pointer below the symbol indicates the output activated


b) The number indicates the current test step
c) The framed number indicates the selected setting line

18/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
Input test Buttons Explanation Line
(sensors) 1
Press one of the line selection buttons.
This will take you to the programming level "Enduser.

2
Press both line selection buttons for at least 3
seconds.
This will take you to the programming level "Heating
engineer.

3
Press line selection button "Up" until you reach line
52.

This will take you to the input test.


4
Press the + or - button repeatedly, which will take you
one test step further:
Test step 0 Display of the function selected on line 97 (B70/B4)
[C].
Test step 1 Display of d.h.w. temperature (B3).
Test step 2 Display of the cascade flow temperature (B10).
Test step 3 Display of the actual outside temperature (B9)
Test step 4 Display of room temperature acquired with room
unit connected to A6
Test step 5 Display of input H1 according to the function
selected on operating line 170 [C, - - - , o o o].

5
You leave the programming line "Input test" by Contin.
pressing either one of the line selection buttons, display

or one of the operating mode or function buttons

 Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.

The selected sensor values are updated within a maximum of 5 seconds. If no sensor
is present, the connecting line interrupted, or the contact open, the display shows "---;
in the event of a short-circuit, or if the contact is closed, the LCD displays "ooo.

Display
2379Z02

a) b)

0 4 8 12 16 20 24

c)

a) The framed number indicates the selected setting line


b) Displayed value of the temperature measured
c) The number indicates the selected test step

19/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.4 Parameter settings for the enduser
Description The following settings can be made to meet the individual needs of the enduser.

Setting Buttons Explanation Line


1
Press one of the line selection buttons.
This will take you directly to the programming level
"Enduser.

2
Press the line selection buttons to select the required
line.

The parameter list on the next pages contains all
available lines.

3
Press the + or - button to set the required value.
The setting will be stored as soon as you leave the
programming mode or change to another line.
The parameter list on the next 2 pages contains all
settings that can be made.

4
By pressing any of the operating mode buttons, you Contin.
leave the programming level "Enduser. display

 Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.

20/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.4.1 Overview of enduser parameters

Line Function Range Unit Resolution Factory


setting
Setting the clock
1 Time of day 0...23:59 h / min 1 min -
2 weekday 1...7 Weekday 1 day -
3 Date (day, month) 01.01...31.12 dd.MM 1 -
4 Year 1999...2099 jjjj 1 -
Time switch program for heating circuit
5 Weekday-preselection heating circuit 1-7 / 1...7 Weekday 1 day -
1-7 7-day block
1...7 Individual days
6 Switch-on time 1. 3rd period heating circuit 00:00...23:59 h / min 10 min 06:00
7 Switch-off time 1. 3rd period heating circuit 00:00...23:59 h / min 10 min 22:00
8 Switch-on time 2. 3rd period heating circuit 00:00...23:59 h / min 10 min - -:- -
9 Switch-off time 2. 3rd period heating circuit 00:00...23:59 h / min 10 min - -:- -
10 Switch-on time 3. 3rd period heating circuit 00:00...23:59 h / min 10 min - -:- -
11 Switch-off time 3. 3rd period heating circuit 00:00...23:59 h / min 10 min - -:- -
D.h.w. values
13 Nominal setpoint of the d.h.w. temperature (TBWw) TBWR...TBWmax C 1 55
TBWR Line 120
TBWmax Line 40 (OEM)

Heating circuit values


14 Reduced room temperature setpoint (TRRw) TRF...TRN C 0,5 16
TRF Line 15
TRN Setpoint knob

15 Frost protection setpoint of the room temperature 4...TRR C 0,5 10


(TRFw)
TRR Line 14

16 summer / winter changeover temperature 8...30 C 0,5 17


17 heating curve slope -:- - / 2,5...40 - 0,5 15
-:- - Inactive
2,5...40 Active

Actual values
18 Actual value of the room temperature (TRx) 0...50 C 0,5 -
19 Actual value of the outside temperature (TAx) -50...+50 C 0,5 -
To set the attenuated outside temperature to Tax, press the + / -
buttons simultaneously for 3 seconds.
Maintenance
23 Standard time program for heating circuit and d.h.w. 0/1 - 1 0
To activate, press the + and - buttons simultaneously for 3 seconds
Time switch program for d.h.w. heating
29 preselection of weekday 1-7 / 1...7 Weekday 1 day -
1-7 7-day block
1...7 Individual days
30 Switch-on time 1. 3rd period d.h.w. 00:00...23:59 h / min 10 min 06:00
31 Switch-off time 1. 3rd period d.h.w. 00:00...23:59 h / min 10 min 22:00
32 Switch-on time 2. 3rd period d.h.w. 00:00...23:59 h / min 10 min - -:- -
33 Switch-off time 2. 3rd period d.h.w. 00:00...23:59 h / min 10 min - -:- -
34 Switch-on time 3. 3rd period d.h.w. 00:00...23:59 h / min 10 min - -:- -
35 Switch-off time 3. 3rd period d.h.w. 00:00...23:59 h / min 10 min - -:- -
Service
49 Indication of BMU error code 1...4 / 0...255 - 1 -
1...4 = BMU number, 1...255 = error code
50 indication of faults 0..255 / 00.0114.16 - 1 -

21/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.5 Parameter settings for the heating engineer
Description Configuration and parameter settings to be made by the heating engineer.

Setting Buttons Explanation Line


1
Press one of the line selection buttons.
This will take you first to the programming level
"Enduser.

2
Press both line selection buttons for at least 3 seconds.

This will take you to the programming level "Heating


engineer.
3
Press the line selection buttons to select the required
line.

The parameter list on the next 2 pages contains all
available lines.

4
Press the + or - button to set the required value.
The setting will be stored as soon as you leave the
programming mode or change to another line.
The parameter list on the next 2 pages contains all
settings that can be made.

5
You leave the programming level "Heating engineer" by Contin.
pressing one of the operating mode buttons. display

 Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.

22/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.5.1 Overview of heating engineer parameters

Line Function Range Unit Resolution Factory


setting
Service values
51 Output test (relay test) 0...3 - 1 0
0 Control mode according to the operational status
1 All outputs are deactivated
2 D.h.w. charging pump ON Q3
3 Heating circuit / system pump ON Q1
52 Input test (sensor test) 0...5 - 1 0
0 Cascade return temperature sensor B70/B4
or buffer storage tank temperature sensor
1 D.h.w. temperature sensor B3
2 Cascade flow temperature sensor B10
3 outside temperature sensor B9
4 Room temperature sensor (room unit) A6
5 input H1 H1
53 Display of plant type 27...36 / 65...67 - 1 -
54 displaying the PPS communication --- / 1..12 / 0..255 - 1 -
--- No communication
1...12 PPS device address
0...255 identification code
Actual values
1)
55 Actual value of boiler temperature of BMUs (TKx) 1...4 / 0...140 C 1 -
1...4 = BMU number, 0...140 = actual value of boiler temperature
(interrogate with + / - buttons)

56 Actual value of cascade flow temperature 0...140 C 1 -


Input B10

57 Actual value of cascade return temperature 0...140 C 1 -


Input B70

58 actual value of buffer storage tank temperature 0...140 C 1 -


Input B4
1)
59 Actual value of the d.h.w. temperature (TBWx) 0...140 C 1 -
(Input B3 or value from BMU)

60 Attenuated outside temperature (Taxged) -50.0...+50.0 C 0.5 -


61 Composite outside temperature (TAxgem) -50.0...+50.0 C 0.5 -
62 outside temperature source --.-- / 00.01...14.16 - - -
--.-- No signal
00.01 Segment / device address
Setpoints
1)
65 Setpoint of the boiler temperature of BMUs (TKx) 1...4 / 0...140 C 1 -
1...4 = BMU number, 0...140 = actual value of boiler temperature
(interrogate with + / - buttons)

66 Setpoint of the cascade flow temperature 0...140 C 1 -


69 Setpoint of d.h.w. temperature (TBWw) 0...140 C 1 -
70 Nominal room temperature setpoint 0.0...35.0 C 0,5 -
Nominal setpoint plus readjustment made on the room unit

71 Setpoint of room temperature (TRRw) 0.0...35.0 C 0,5 -


72 Flow temperature setpoint (TVw) 0...140 C 1 -
Heat generation values
75 Display of the available cascade boilers --- / 00.1...16.3 - 01.1 -
(--- = none)

76 display lead boiler --- / 00.1...16.3 - 01.1 -


77 Remaining number of operating hours for changeover 0...990 h 1 -
of boiler
sequence
Only if a value is selected on line 130, otherwise the LCD displays - -
-

23/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
Line Function Range Unit Resolution Factory
setting
1)
80 Burner hours run BMU 1 0...65535 h 1 0
1)
81 Burner hours run BMU 2 0...65535 h 1 0
1)
82 Burner hours run BMU 3 0...65535 h 1 0
1)
83 Burner hours run BMU 4 0...65535 h 1 0
1)
90 Minimum limitation of the boiler temperature (TKmin) TKminOEM...TKmax C 1 8
(max 95C)
1)
91 Nominal output BMU 1 0...255 kW 1 20
1)
92 Nominal output BMU 2 0...255 kW 1 20
1)
93 Nominal output BMU 3 0...255 kW 1 20
1)
94 Nominal output BMU 4 0...255 kW 1 20
Configuration of plant
95 pump function output Q1 1...5 - 1
1 Heating circuit pump or no pump
2 System pump for heating circuits only
3 System pump for heating circuits and d.h.w. storage tank
4 d.h.w. circulating pump
5 Pump H1
97 use sensor input B70/B4 1...2 - 1 1
1 Cascade return temperature (B70)
2 Buffer storage tank temperature sensor (B4)

Space heating
100 parallel displacement of the heating curve -4.5...+4.5 K (C) 0,5 0,0
101 room influence 0/1 - 1 1
0 Inactive
1 Active
102 Switching differential of the room temperature (SDR) - - . - / 0.5...4.0 K (C) 0,5 --.-
--.- Inactive
0,5...4,0 Active
103 Minimum limitation of the flow temperature setpoint 8...Tvmax C 1 8
(TVmin)
TVmax Line 104

104 Maximum limitation of the flow temperature setpoint TVmin...95 C 1 80


(TVmax)
Tvmin Line 103

105 type of building construction 0/1 - 1 1


0 Heavy
1 Light
106 adaption of the heating curve 0/1 - 1 1
0 Inactive
1 Active
107 Maximum forward shift of optimum start control 00:00...06:00 hh:mm 10 min 00:00
0 No forward shift

108 Maximum forward shift of optimum stop control 00:00...06:00 hh:mm 10 min 00:00
0 No forward shift

D.h.w.
120 Reduced setpoint of d.h.w. temperature (TBWR) 8...TBWw C 1 40
TBWw Line 13

121 release of d.h.w. heating 0...2 - 1 1


0 24 h/day
1 According to the heating circuit time switch program)s) with
forward shift
2 According to d.h.w. time switch program (lines 29...35)
122 switching program circulating pump 0...1 - 1 1
0 According to heating circuit time switch program
1 According to release of d.h.w. heating
123 Assignment of d.h.w. heating 0...2 - 1 2
0 For local consumer only
1 For all consumers in the same segment
2 For all consumers in the system

24/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
Line Function Range Unit Resolution Factory
setting
124 D.h.w. charging 0/1 - 1 1
0 Once per day (forward shift 2.5 h)
1 Several times per day (forward shift 1h)
125 Type of d.h.w. demand 0/1 - 1 0
0 Sensor
1 Control thermostat
126 Flow temperature boost for d.h.w. 0...30 K 1 16
127 d.h.w. priority 0...3 1 1 1
0 MK + PK absolute
1 MK + PK shifting
2 None (parallel)
3 MK shifting, PK absolute
129 demand for heat with reduced d.h.w. setpoint 0/1 - 1 1
0 No (application with buffer storage tank)
1 Yes
Boiler cascade
130 changeover of boiler sequence in cascades --- / 10...990 - / hours 10 500
--- No automatic changeover (fixed boiler sequence)
10...990 Changeover according to the selected number of hours
131 Exclusion with autom. changeover of boiler 0...3 - 1 0
sequence
0 None
1 First boiler
2 Last boiler
3 First and last boiler
132 Lead boiler with the fixed sequence 00.1...16.3 - 01.1 -
133 Switch-on delay lag boilers 2...120 min 1 5
134 Restart lock of BMUs 0...1800 s 10 300
LPB / system
140 LPB device address 0...16 - 1 1
0 Standalone
1...16 Device number
141 LPB segment address 0...14 - 1 0
0 Central segment (heat generation)
1...14 Segment (heat consumers)
142 LPB power supply 0/1 - 1 1
0 Off (central bus power supply)
1 AUTOMATIC (controller - bus power supply)
143 Displaying the LPB power supply ON / OFF - - -
144 displaying the LPB communication ON / OFF - - -
145 Range of action of central changeover 0/1 - 1 1
0 In the segment
1 In the system (if segment address = 0)
146 Automatic summer / winter changeover 0/1 - 1 0
0 Effect on local heating circuit only
1 Central changeover of all heating circuits
147 Central standby switch 0/1 - 1 0
0 OFF (Inactive)
1 ON (all units on standby)
148 clock mode 0...3 - 1 3
0 Autonomous clock
1 System time without remote adjustment
2 system time with remote adjustment
3 System clock (master)
149 Winter- / summertime changeover 01.01...31.12 tt.MM 1 25.03
150 Summer- / wintertime changeover 01.01...31.12 tt.MM 1 25.10
input H1
170 input H1 0...4 - 1 0
0 Changeover of operating mode (HC standby / d.h.w. off)
1 Changeover of operating mode (HC standby)
2 Minimum setpoint of flow temperature (setting on line 171)
3 Heat generation lock
4 Heat demand DC 0...10 V

25/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
Line Function Range Unit Resolution Factory
setting
171 minimum setpoint of flow temperature contact H1 8...TKmax C 1 70
If activated at input H1 (setting 2)

172 Maximum value of heat demand 5...130 C 1 100


If activated at input H1 (setting 4)

173 operating action of the contact H1 0/1 - 1 1


0 N.C. contact
1 N.O.

1)
If a BMU is connected via LPB, this setting will not be active.
The respective setting must be made directly on the BMU.

26/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.6 Parameter settings for the OEM
Description Boiler-specific settings and protective functions for the boiler manufacturer.

Setting Buttons Explanation Line

1 Press one of the line selection buttons.


This will take you first to the programming level
"Enduser.

2 Press both line selection buttons for at least 9 seconds.

A special display for entering the code will appear.


9s

3 CODE Press buttons and to enter the required


combination of the access code.
If the combination of buttons is correct, you reach the
programming mode OEM.
 Wrong code:
If the code has been entered incorrectly, the display will
change to the "Parameter settings for the heating
engineer.

4 Press the line selection buttons to select the required


line.

The parameter list on the next 2 pages contains all
available lines.

5 Press the + or - button to set the required value.


The setting will be stored as soon as you leave the
programming mode or change to another line.
The following parameter list contains all available lines.

6 You leave the programming level "OEM" by pressing any Contin.


of the operating mode buttons. display

 Note:
If no button is pressed for about 8 minutes, the controller
will automatically return to the operating mode selected
last.

Example
2379Z02

0 4 8 12 16 20 24

Whether correct or incorrect, each push of a button represents irrevocably a digit of the
code.
As a confirmation, the respective digit changes to 1.

27/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.6.1 Overview of OEM parameters

Line Function Range Unit Resolution Factory


setting
Heat source OEM
1)
1 Minimum limitation of the boiler temperature:OEM 8...95 C 1 8
(TKminOEM)
2 Maximum limitation of the boiler temperature (TKmax) 8...120 C 1 80
8 Pump overrun time 0...20 min 1 5
(after burner OFF)
22 Minimum limitation of boiler return temperature 8...95 C 1 8
1)
25 Calibration of actual output value BMU 1 -100...100 - 1 0
1)
26 Calibration of actual output value BMU 2 -100...100 - 1 0
1)
27 Calibration of actual output value BMU 3 -100...100 - 1 0
1)
28 Calibration of actual output value BMU 4 -100...100 - 1 0
Space heating OEM
30 Gain factor of room influence (KORR) 0...20 - 1 4
31 Constant for quick setback (KON) 0...20 - 1 2
(without room sensor)

32 Boost of room temperature setpoint 0...20 K (C) 1 5


(with boost heating)

33 Frost protection for the plant 0/1 - 1 1


0 Inactive
1 Active
34 overtemperature protection for the pump heating circuit 0/1 - 1 1
0 Inactive
1 Active
35 Heat gains (Tf) -2...+4 C 0,1 0
36 adaption sensitivity 1 1...15 - 1 15
37 adaption sensitivity 2 1...15 - 1 15
D.h.w. OEM
40 Maximum nominal setpoint of the d.h.w. temperature 8...80 C 1 60
(TBWmax)
41 Switching differential of the d.h.w. temperature 0...20 K (C) 1 5
42 Legionella function 0/1 - 1 1
0 = OFF
1 = ON

43 setpoint of the legionella function 8...95 C 1 65


44 Protection against discharging during d.h.w. heating 0...2 - 1 2
0 = no protection against discharging
1 = always protection against discharging
2 = protection against discharging only when heat generation is
locked
Cascade settings OEM
50 cascade management strategy 1...6 - 1 2
1 autonomous 1
2 autonomous 2
3 autonomous 3
4 linked 1
5 linked 2
6 linked 3
51 Lower limit of output range (Pmin) 0...Pmax % 1 40
52 Upper limit of output range (Pmax) Pmin...100 % 1 90
56 Mandatory time on basic stage when boilers are added 10...1200 s 10 60
60 Minimum temperature differential at the pressureless 0...20 K (C) 1 4
header

28/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
Line Function Range Unit Resolution Factory
setting
Configuration of plant
90 continuous display 0/1 - 1 0
0 Weekday / time of day
1 Actual value of cascade flow temperature
Service values OEM
91 software version 00.0...99.9 - 1 -
92 device operating hours 0...500000 h 1 -

1)
If a BMU is connected via LPB, this setting will not be active.
The respective setting is to be made directly on the BMU.

29/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.7 Operation
Introduction Operating instructions are inserted at the rear of the unit's front cover.

2379Z01

2.7.1 Operating elements

Operating element Function


Room temperature setpoint knob Adjustment of room temperature setpoint
Setting buttons Parameter settings
Line selection buttons Selection of parameters / switching of lines
Display Readout of actual values and settings
Operating mode buttons Operating mode changes to:
Automatic operation
continuous operation
Standby
D.h.w. heating ON / OFF
Function button with LED for Manual operation ON / OFF
manual operation
Connection facility for PC tool Diagnostics and service

Display
2379Z02B

a)

c) b)
d)
0 4 8 12 16 20 24

a) Symbols for indicating the operational status with the black bars (level pointers)
When the ECO function is active, the current level pointer flashes.
b) Display during normal control mode or when making settings
c) Programming line when making settings.
d) Time bar for normal control mode or when making settings.

30/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
2.8 Operational faults

2.8.1 No display on the controller:


Is the heating plant's main switch turned on?
Are the fuses in order?
Check the wiring

2.8.2 Controller displays the wrong time of day:


Set the correct time of day on the controller (operating line 1).
Set the correct time of day on the clock master (if present).

2.8.3 One of the BMUs does not switch on


Does the BMU really have to operate? (Check cascade lead strategy, delayed
switching on?)
Press BMU's lockout reset button.
Check the electromechanical control thermostat (TR) and the manual reset safety
limit thermostat (STB)
Check wiring and fuse of the BMU.
Check communication link to the BMU (operating line 54)
Check wiring of the cascade temperature sensors (sensor test, operating line 52).

2.8.4 One of the pumps does not run


Is the right type of plant displayed (operating line 53)?
Is the pump correctly defined? (Operating line 95)
Check wiring and fuse of the pump (relay test, operating line 51)
Check wiring of the sensors (sensor test, operating line 52)

2.8.5 D.h.w. is not being heated:


Has the button for d.h.w. heating been pressed?
Check setpoint of the d.h.w. temperature
Check if d.h.w. heating is released
Check wiring and fuse of the charging pump (relay test, operating line 51)
Check wiring of the d.h.w. temperature sensor (sensor test, operating line 52)
Check setting of the electromechanical control thermostat (TR) installed on the
boiler. It must be above the TKmax setting

2.8.6 The room temperature does not agree with the


required temperature level:
Does the room temperature setpoint agree with the required temperature level?
(Knob on the controller or on the room unit)
Is the required operating mode indicated?
Are weekday, time of day and the displayed heating program correct?
(Operating lines 1...11)
Has the heating curve slope been correctly set? (Operating line 17)
Check wiring of outside sensor (operating line 52)
Has the Setting knob for the nominal room temperature setpoint with the Parallel
displacement of the heating curve (operating line 100) been calibrated based on
the effective room temperature?

2.8.7 Error message; display shows "ER"


Select operating line 50 which gives you the error code and error address. There,
you see the error code and the address of the error. Refer to section "Indication of
errors" for a list of the possible error codes and their descriptions.

31/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Handling 15.07.2002
3 Description of the enduser settings

User interface
3.1 Heating circuit operating modes

Benefit Straightforward selection of heating circuit operating modes

Description The control provides 3 different heating circuit operating modes that can be directly
selected as required.

Setting Select the required operating mode by pressing the respective operating mode button.
It is located on the controller front for direct access by the user.

Operating Designation Effect of selected operating mode


mode

Automatic Heating according to the time program


operation (operating lines 5 to 11)
Temperature setpoints according to the heating
program
Protective functions active
Changeover on the room unit active
Automatic summer / winter changeover and
automatic 24-hour heating limit active (ECO
functions)
continuous Heating mode with no time program
operation Temperature adjustment with the setpoint knob
Protective functions active
Changeover on room unit inactive
Automatic summer / winter changeover and
automatic 24-hour heating limit inactive (ECO
functions)
Standby Heating OFF
Temperature according to frost protection
Protective functions active
Changeover on room unit inactive

32/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Illuminated buttons The selected operating mode is indicated by illuminated buttons. A number of functions
can cause the displayed selection to change. The following table shows the possible
statuses. The following table shows the possible statuses:

Settings on the controller Function Effect on button and meaning


Heat generation lock Selected HC operating mode button flashes when
Line 170 = 3 contact H1 is closed
D.h.w. operating mode button flashes when
switched on
Changeover of operating Selected HC operating mode button flashes
mode when contact H1 is closed
Line 170 = 0 D.h.w. operating mode button flashes when
switched on
Changeover of operating HC operating mode flashes
mode D.h.w. operating mode button will not be affected
Line 170 = 1
Minimum setpoint of flow Selected HC operating mode button flashes when
temperature contact H1 is closed.
Line 170 = 2 D.h.w. operating mode button will not be affected
Central standby switch HC operating mode flashes
Line 147 = 1 D.h.w. operating mode button will not be affected

Settings on the room unit Function Effect on button and meaning


Occupancy button HC operating mode flashes when occupancy
button is active.
D.h.w. operating mode button will not be affected
Holiday function HC operating mode flashes when holiday
function is active
D.h.w. operating mode button flashes when
switched on

Effect of room unit Changeover of the operating mode on the room unit is active only if the controller is in
automatic mode .
The room temperature is transmitted to the controller via PPS, independent of the
selected operating mode.

3.2 Operating mode of d.h.w. heating

Benefit Selection of d.h.w. heating mode independent of heating operation


Selection is made directly on the user interface

Description D.h.w. heating can be switched on and off independent of the other operating modes.

Setting D.h.w. heating is selected by pressing the respective button on the controller's user
interface.

33/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Effect By pressing the respective button, d.h.w. heating is switched on or off.
D.h.w. heating OFF - button dark.
D.h.w. is not being heated. Frost protection remains active, however, and prevents
the storage tank temperature from falling below a certain level
D.h.w. heating ON - button illuminated.
The d.h.w. is heated according to the settings made

Important settings The following settings affect d.h.w. heating:


Time switch program d.h.w. heating (lines 29...35)
Nominal d.h.w. temperature setpoint (line 13)
Reduced d.h.w. temperature setpoint (line 120)
Release of d.h.w. heating at the nominal setpoint (line 121)
Assignment of d.h.w. heating (line 123)
D.h.w. heating (line 124)
Type of d.h.w. demand (line 125)

 Note The d.h.w. values that can be adjusted on the controller apply to both d.h.w. heating by
the controller and d.h.w. heating by a BMU supplied by Landis & Staefa. Some BMUs
of other manufacture also support this function.

3.3 Nominal room temperature setpoint

Benefit Straightforward setting of the required nominal room temperature setpoint

Description The heating system uses 3 different setpoints that can be adjusted:
The nominal room temperature setpoint described here
The reduced room temperature setpoint (setting on line 14)
The frost protection setpoint of the room temperature (setting on operating line 15)

Setting The nominal room temperature setpoint is preadjusted with the setpoint knob. It is
located on the controller front for direct access by the user.

Setting range Unit Factory setting

8...26 C 20

2379Z17

0 2 4 6 8 10 12 14 16 18 20 22 24 26 C
Room temperature setpoint setting ranges
14 Setting "Reduced room temperature setpoint
15 Setting "Frost protection setpoint of the room temperature

Effect of temperature When the nominal room temperature setpoint is active, the rooms will be heated
setting according to the adjustment made with the setpoint knob.
Effect in the various operating modes:

34/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Operating Effect of knob adjustment
mode

Adjustment acts on the heating periods

Adjustment acts continuously

Adjustment has no effect

Note The adjustment made with the setpoint knob has priority over the reduced room
temperature setpoint entered (line 14). Especially in a situation when the adjustment
made with the knob is lower.

Example During the heating periods, the nominal room temperature setpoint is maintained. The
heating periods are in accordance with the settings made on lines 6 to 11.

Mo
...
So

2373Z11

0 2 4 6 8 10 12 14 16 18 20 22 24 h

Room unit When using a room unit without setpoint readjustment (QAA50), the setpoint knob on
the controller acts as described above.
When using a room unit featuring setpoint readjustment (QAA70), the setpoint knob on
the controller is inactive. In that case, the nominal setpoint adjusted on the room unit
applies.
A connected room unit is active only when operating mode is selected on the
controller.

3.4 Manual operation

Benefit Partly manual heating operation

Description In operating mode Manual operation, the plant components on the consumer side
must be manually adjusted and monitored. The control functions of the unit are only
used for controlling the BMUs.

Common flow temperature The BMUs are released and use their boiler temperature sensor to control the
temperature at the level of the maximum limitation of the BMU setpoint (TKmax.)
Factory setting 80 C. The actual boiler temperatures are displayed on setting line 55.

Setting Activation: Manual operation is activated by pressing this button. It is accessible


only when the cover of the controller is open

Deactivation: By pressing one of the operating mode buttons


By pressing again the manual operation button

 Note When deactivating the function, the controller will automatically return to the operating
mode previously selected.

Effect As soon as manual operation is selected, all relays will switch to the following statuses:

35/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Output Terminals Status
BMU PPS All boilers released, fixed
heat demand at TKmax
Heating circuit or system Q1 ON (uncontrolled)
pump:
D.h.w. charging pump Q3 ON (uncontrolled)

TKmax = maximum limitation of BMU setpoint (operating line 2OEM)

Display Common flow temperature (cascade flow temperature):

2379Z02
0 4 8 12 16 20 24

36/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Setting the clock
Benefit Straightforward changeover from summer- to wintertime, and vice versa
Fast and easy-to-understand time settings

Description To ensure proper operation of the heating program, the 24-hour time switch with the
time of day and weekday must be correctly set.

System time The time of day can be set from a remote location via the bus system, provided clock
operation is appropriately set. Also refer to clock operation on operating line 148.

3.5 Time of day

Setting 1. Press the operating line selection buttons to select line 1.


2. Press the + / - buttons to set the time of day.
Setting range Unit

00:00...23:59 Hour : Minute

Effect The controller's clock time is set in agreement with the correct time. This setting is
important to make certain the controllers heating program will operate correctly.

 Notes During the setting procedure, the clock continues to run


Each time the + or - button is pressed, the seconds are reset to zero

3.6 Weekday

Setting 1. Press the operating line selection buttons to select line 2.


2. Press the + / - buttons to select the weekday.
Setting range Unit

1...7 Weekday

Effect The time of day will be set to the selected weekday. This setting is important to make
certain the controllers heating program will operate correctly.

Weekday table 1 = Monday 5 = Friday


2 = Tuesday 6 = Saturday
3 = Wednesday 7 = Sunday
4 = Thursday

37/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
3.7 Date (day, month)

Setting Setting range Unit

01:01...31:12 Day month

Effect Day and month of the controller will be based on this setting. This setting of date is
important to make certain the controllers holiday program and summer- / wintertime
changeover will operate correctly.

3.8 Year

Setting Setting range Unit

1999...2099 Year

Effect The year of the controller will be based on this setting. This setting of year is important
to make certain the controllers holiday program and summer- / wintertime changeover
will operate correctly.

38/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Time switch program for space heating
Benefit The heating system operates only if there is demand for heat.
The user can set the heating periods to suit his lifestyle.
Energy can be saved by making adequate use of the heating program.

Description The time switch program for space heating consists of the switching times that can be
entered for the weekdays or the 7-day block.
The time switch program for space heating and the time switch program for d.h.w.
heating operate independently of one another.

3.9 Preselecting the weekday


Description With this setting, you select the weekdays or the 7-day block for which the switching
times of the time switch program apply.

The heating program thus set becomes active when selecting automatic mode .

Setting 1. Press the operating line selection buttons to select line 5.


2. Press the + / - buttons to preselect the 7-day block or the individual day.
Setting range Unit

1-7 7-day block


1...7 Individual days

Important This setting must be made before the switching times are entered!

For every day on which other switching times shall apply, the preselection of the
individual day with subsequent entry of the switching times must be repeated

Effect This setting is used to select either the whole week (1-7) or individual days (1...7).
Entry of 1-7 7-day block

Entry of the switching times from operating line 6 to 11 is identical for every day from
Monday through Sunday.

Example:
Mo
...
So

2373Z11

0 2 4 6 8 10 12 14 16 18 20 22 24 h
Switching time for nominal setpoint
Switching time for reduced setpoint

39/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Entry of 1...7 Individual days

The setting of the switching times from operating line 6 through 11 is entered only for
the individual day selected here.

 Tip
First, choose the 7-day block (1-7) to enter the switching times that apply to the
majority of days; then, select the individual days (1...7) to make the required
adjustments.

Example:

237 3Z12
Mo

Di

Mi

Do

Fr

Sa

So

0 2 4 6 8 10 12 14 16 18 20 22 24 h

3.10 Switching times

Description With this setting, you determine the switching times for space heating. At these
switching times, the temperature setpoints of the heating circuit change.
The heating program thus set becomes active when selecting automatic mode .

Setting 1. Press the line selection buttons to select line 6 to 11.


2. Press the + / buttons to set the switching time on each line.
Setting range Unit Factory setting

- -:- -...24:00 h : min See "Program overview"
below

! Important First, select the weekday (operating line 5) for which the switching times shall be
entered!

 Note The controller then makes a check to ensure the entries have been made in the correct
order.

Effect At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times the setpoints will be activated.

40/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Entry:
: Switching point inactive
00:00...24:00 At the time entered, heating to the respective temperature is ensured.

Program overview Line Switching point Temperature setpoint Standard

Switch-on time period 1 Setpoint of knob 06:00

Switch-off time period 1 Reduced setpoint 22:00

Switch-on time period 2 Setpoint of knob :

Switch-off time period 2 Reduced setpoint :

Switch-on time period 3 Setpoint of knob :

Switch-off time period 3 Reduced setpoint :

Effect of room unit When using a QAA70 room unit, the heating program will be acted upon. However, this
works only if operating mode AUTO is selected on the controller.

41/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
D.h.w. values
3.11 Nominal d.h.w. temperature setpoint

Benefit D.h.w. heating only if there is a demand for it


Possibility of using 2 different d.h.w. temperature setpoints

Setting 1. Press the operating line selection buttons to select line 13.
2. Press the + / buttons to adjust the nominal setpoint of the d.h.w. temperature.
Setting range Unit Factory setting

TBWR...TBWmax C 55
TBWR Reduced setpoint of d.h.w. temperature (setting on operating line 120)
TBWmax Maximum nominal setpoint of d.h.w. temperature (setting on line 40OEM)

2379Z16
Effect

0 10 20 30 40 50 60 70 80 90 100 120 130 140 C


The temperature setpoint during normal d.h.w. operation will be changed.

13 Setting "Nominal setpoint of the d.h.w. temperature


120 Setting "Reduced setpoint of the d.h.w. temperature
40OEM Setting "Maximum nominal setpoint of the d.h.w. temperature

D.h.w. temperature D.h.w. heating has 2 different setpoints that can be used:
setpoints
Nominal d.h.w. temperature setpoint: It ensures the d.h.w. temperature required
during main occupancy times

Reduced d.h.w. temperature setpoint (setting on operating line 120): it ensures the
d.h.w. temperature required during the main occupancy times.

D.h.w. charging The criteria required for releasing d.h.w. heating are defined by the settings made on
lines 121 and 123 and 124.

 Note In the event of a sensor with a short-circuit (display - - - in input test, test step 1) the
d.h.w. will not be heated (protection against scalding).

42/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Heating circuit values
3.12 Reduced room temperature setpoint

Benefit Lower room temperatures during non-occupancy times, e.g. during the night
Energy savings

Description The heating system has 3 different setpoints that can be adjusted:
The reduced room temperature setpoint described here.
The nominal room temperature setpoint (to be adjusted with the setpoint knob).
The frost protection setpoint of the room temperature (setting on operating line 15)

Setting 1. Press the operating line selection buttons to select line 14.
2. Press the + / buttons to adjust the reduced room temperature setpoint.
Setting range Unit Factory setting

TRF...TRN C 16

TRF Frost protection setpoint of the room temperature (setting on line 15)
TRN Nominal room temperature setpoint (to be adjusted with the setpoint knob)

 Note If the required temperature level cannot be set, the adjustment made with the setpoint
knob may be too low. It is not possible to set a value above the adjustment made with
the setpoint knob.

2379Z17

0 2 4 6 8 10 12 14 16 18 20 22 24 26 C

Room temperature setpoint setting ranges


14 Setting "Reduced room temperature setpoint
15 Setting "Frost protection setpoint of the room temperature

Effect With this setting, the reduced room temperature setpoint will change to the level called
for by reduced operation in the living rooms.

Example
Mo
...
So

2373Z11

0 2 4 6 8 10 12 14 16 18 20 22 24 h
The heating periods are in accordance with the settings made on lines 6 to 11.

43/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
3.13 Frost protection setpoint of the room
temperature

Benefit Protects the building against frost

Caution This function is ensured only when the heating plant operates properly!

Description This function prevents the room temperature from falling below the adjusted frost
protection setpoint.

Setting 1. Press the operating line selection buttons to select line 15.
2. Press the + / buttons to adjust the frost protection setpoint of the room
temperature.
Setting range Unit Factory setting

4...TRRw C 10
TRRw Reduced room temperature setpoint (setting on operating line 14)

Effect This setting will change the frost protection setpoint of the room temperature.

Frost protection for the In operating mode , the room temperature is prevented from falling below a certain
building level. This means that the frost protection setpoint of the room temperature will be
maintained.

2379Z17

0 2 4 6 8 10 12 14 16 18 20 22 24 26 C

Room temperature setpoint setting ranges


14 Setting "Reduced room temperature setpoint
15 Setting "Frost protection setpoint of the room temperature

3.14 Summer / winter changeover temperature


of the heating circuit

Benefit Fully automatic operation throughout the year


The heating will not be switched on when the outside temperature drops for short
periods of time
Additional savings function

Description The summer / winter changeover temperature is the criterion for automatic summer /
winter changeover of the heating plant.

44/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Setting 1. Press the operating line selection buttons to select line 16.
2. Press the + / buttons to select the summer / winter changeover temperature.
Setting range Unit Factory setting

8...30.0 C 17

Effect By changing the setting, the respective periods of time will be shortened or extended.
The change will only affect the heating circuit.
Entry:
Increase: Winter operation will start earlier
Summer operation will start later .

Decrease: Winter operation will start later


Summer operation will start earlier

 Notes The summer / winter changeover temperature can act either locally or on other devices
in the system (also refer to section "Effect of summer / winter changeover temperature")
(Also refer to "Effect of automatic summer / winter changeover" on operating line 91).
This function only acts in automatic mode and standby mode .
Level cursor flashes during summer operation.

Changeover To determine changeover, the setting of the summer / winter changeover temperature
( a fixed switching differential) is compared with the attenuated outside temperature.
Also refer to page 64.

Heating OFF (from winter to summer) TAged > SoWi + 1C


Heating ON (from summer to winter) TAged < SoWi - 1C

T
C TAged
20
19
18 SoWi +1 C
17 SoWi
16 SoWi -1 C

H
2379D06

ON

OFF
0 5 10 15 t

Changeover between summer and winter operation:

TAged Attenuated outside temperature


SoWi Summer / winter changeover temperature
T Temperature
t Time in days
H Heating

45/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
3.15 Heating curve slope

Benefit Constant room temperature in spite of outside temperature variations


Generation of a flow temperature with no external demand for heat

Description The controller generates the flow temperature setpoint as a function of the selected
heating curve. For plants where the controllers cannot transmit their demand for heat
via LPB or input H1, the controller can generate a weather-compensated flow
temperature.

Setting 1. Press the operating line selection buttons to select line 17.
2. Press the + / - buttons to select the heating curve slope or - - . - einstellen.
Setting range Unit Factory setting

- : - - / 2.5...40.0 Increment 15.0

Effect By changing the setting, the slope of the heating curve will be increased or decreased
with the following effects:

Increase: The flow temperature will be raised when the outside temperature
drops

Decrease: The flow temperature will be raised less when the outside
temperature drops

The following settings produce the following effects:

2.5...40.0 The controller delivers a weather-compensated flow temperature.

--:- The controller delivers no weather-compensated flow temperature.


To release heat generation, an external heat demand signal is required.
Frost protection for the plant is active, but not frost protection for the
building. The settings and the display on the room unit are also
deactivated.

 Notes The setting of the heating curve slope (value from 2.5 to 40 or inactive - - - ) affects the
automatic generation of plant type (operating line 53).

An external demand for heat can be delivered to the controller via LPB (LPB-
compatible controllers) or input H1 (controllers of other manufacture). If several signals
are present, the controller will use the highest of them as the setpoint.

The heating curve Using the heating curve, the controller generates the flow temperature setpoint,
enabling the system to maintain a constant room temperature even without using a
room temperature sensor.
The steeper the slope of the heating curve, the higher the flow temperature setpoint at
low outside temperatures.
 Note Comfort is considerably enhanced when using a room temperature sensor.

46/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
TV
40 35 30 27,5 25 22,5
C
20

100
17,5
90
15
80

12,5
70

10
60

7,5
50

40 5

30 2,5

2000D07
20 10 0 -10 -20 -30 C
TA

TV Flow temperature
TA Composite outside temperature

47/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Actual values
Benefit Display of the actual room temperature
Display of the actual outside temperature

Note All displays of actual values require the respective temperature detectors.

3.16 Actual value of the room temperature

Setting 1. Press the operating line selection buttons to select line 18.
2. No setting can be made with the + / - buttons.
Display Unit

0...50 C C

Effect The temperature measured with the room unit will automatically be displayed on this
line.

Special displays Sensor with open-circuit or no room sensor connected


000 Sensor with short-circuit

3.17 Actual value of outside temperature

Setting 1. Press the operating line selection buttons to select line 19.
2. No setting can be made with the + / - buttons.
Display Unit

- 50... + 50 C

Effect The temperature measured with the outside sensor will automatically be displayed on
this line.

Special displays Sensor with open-circuit or no sensor connected


000 Sensor with short-circuit

Note For resetting the attenuated outside temperature to the actual room temperature, refer
to page " Attenuated outside temperature".

48/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Maintenance
3.18 Standard time switch program for heating
circuit and d.h.w.

Benefit Straightforward resetting of all time switch programs to their standard values

Description The standard time program resets the time settings of all time switch programs. For this
purpose, the controller is supplied with non-volatile factory settings.

Setting 1. Press the operating line selection buttons to select line 23.
2. Press the + / - buttons for 3 seconds.
The standard time program is activated as soon as the display changes to 1.
Display Unit

0/1 -

! Caution In that case, the individual settings will be lost!

Effect The time settings for the time switch programs will be overwritten with standard values.
This applies to the following settings:
Switching times of time switch program "heating circuit" ...
Switching times for d.h.w. program ...

Standard values
Switching point Setting line Standard time
Heating circuit D.h.w.
Period 1 ON 6 30 06 : 00
Period 1 OFF 7 31 22 : 00
Period 2 ON 8 32 :
Period 2 OFF 9 33 :
Period 3 ON 10 34 :
Period 3 OFF 11 35 :

49/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Time switch program for d.h.w. heating
Benefit D.h.w. is heated only if required.
The user can set the d.h.w. heating times to suit his lifestyle.
Energy can be saved by making adequate use of the time switch program

Description The time switch program for d.h.w. consists of the switching times to be entered for the
weekdays or the 7-day block.
The time switch program for d.h.w. and the time switch program for space heating
operate independently of one another.
 Important The time switch program is active only when, on operating line 121 (d.h.w. program),
setting 2 has been selected.

3.19 Preselecting the weekday

Description With this setting, you define the weekdays or the 7-day block for which the switching
times of the d.h.w. time switch program apply.

The time switch program thus set is activated by pressing the d.h.w. operating mode
button .

Setting 1. Press the operating line selection buttons to select line 29.
2. Press the + / - buttons to preselect the 7-day block or the individual day.
Setting range Unit

1-7 7-day block


1...7 Individual days

Important This setting must be made before the switching times are entered!
For every day on which other switching times shall apply, the preselection of the
individual day with subsequent entry of the switching times must be repeated

Effect This setting is used to select either the whole week (1-7) or individual days (1...7).
Entry:
1-7 7-day block: Entry of the switching times on lines 30 to 35 is identical for every
day from Monday through Sunday

1...7 Individual days: Entry of the switching times on lines 30 to 35 is made only for
the individual day selected here

Example: The principle is the same as that used with "Time switch program space heating" (refer
to the diagrams and tips on page 39).

3.20 Switching times

Description This is the setting of the switching times for d.h.w. time switch program at which the
d.h.w. temperature setpoint will change.
The time switch program thus set is activated by pressing the d.h.w. operating mode
button .

50/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Setting 1. Press the line selection buttons to select line 30 to 35.
2. Press the + / buttons to set the switching time on each line.

Setting range Unit Factory setting

- -:- -...24:00 h : min See "Program overview"


below

! Important First, select the weekday for which the switching times shall be entered!

 Note The controller then makes a check to ensure the entries have been made in the correct
order.

Effect At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times the setpoints will be activated.
Entry:

: Switching point inactive


00:00...24:00 At the time entered, the d.h.w. will be heated to the respective
temperature.

Program overview Line Switching point D.h.w temperature setpoint Standard

Switch-on time period 1 Nominal setpoint 06:00


Switch-off time period 1 22:00
Reduced setpoint

Switch-on time period 2 Nominal setpoint :


Switch-off time period 2 :
Reduced setpoint

Switch-on time period 3 Nominal setpoint :

Switch-off time period 3 :


Reduced setpoint

51/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Service .
3.21 Displaying the BMU error code

Benefit Straightforward checking of plant.


Fault tracing is made easier.
Description For each BMU, the RVA47.320 can log and store one fault status signal with the
associated BMU number and error code. The faults are indicated on this operating line.

Setting 1. Press the operating line selection buttons to select operating line 49.
2. Press the + / - buttons to interrogate the individual BMUs.

Display Unit

1...4 / 0...255 BMU number / error code

Effect The number of the lowest connected BMU number containing a fault entry will
automatically be displayed on this line.

 Note Error messages cannot be acknowledged. They disappear only if the appropriate fault
has been rectified.

Display The display shows the BMU number and the associated error code. When none of the
BMUs delivers a fault status signal, or when no BMU is connected, there will be no
display.
The meaning of the different error codes depends of the make of BMU used. For this
reason, no overview of all the different error codes can be given here. For details,
please refer to the technical documentation of the relevant product.

Example:
2379Z02

0 4 8 12 16 20 24

BMU 1 signals error code 1.

Note If there is a BMU error code, operating line 50 also displays a general BMU error (error
code 150).

52/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
3.22 Indication of faults

Benefit Straightforward checking of plant


Fault tracing is made easier

Description The controller indicates faults that may have occurred in the controller itself or in the
system.
The display shows "Er" if an error has occurred.

Setting 1. Press the operating line selection buttons to select line 50.
2. Press the + / - buttons to display the list of faults.
Display Unit

0...255 -

Effect The first entry in the error list will automatically be displayed on this operating line.
Note By pressing , it is possible to switch between error signals.

Error signals The controller can store a maximum of 2 error signals. The error signal will be cleared
only after the cause of the fault has been removed. If additional errors are present, they
will be stored as soon as storage capacity becomes available.
Device errors Errors that may occur locally on this device:

Display Description of error


Blank No error
10 outside temperature sensor
26 Cascade flow temperature sensor
46 Cascade return temperature sensor
50 D.h.w. temperature sensor
58 D.h.w. thermostat
61 Fault room unit
70 Buffer storage tank temperature sensor
81 Short-circuit LPB
82 Address collision on LPB (same address several times)
86 Short-circuit PPS
100 2 clock masters present
145 Wrong device connected to PPS
146 Inadmissible plant configuration
147 No BMU connected
150 General BMU fault

 Note In the case of error code 150, operating line 49 also gives the manufacturer-specific
error code of the BMU.

53/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
Faulty devices Other devices that are faulty and whose faults are signaled:
Display Description of error

Example:

26.0.01 Fault with address of the faulty device

- The first digit gives the error code (26).


The second digit indicates the segment address of the faulty device (.01).
(for the segments 10-14, the letters A, b, C, d, and E are used)
The third digit indicates the device address of the faulty device (.01).

Display Example of a display after an error has occurred:

2379Z02
0 4 8 12 16 20 24

Er indicates that a fault has occurred.


Additional faults can be displayed by pressing
.

54/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the enduser settings 15.07.2002
4 Description of the heating engineer
settings

Service values
4.1 Output test

Benefit Connections can be checked prior to commissioning


Faults can be traced much faster

Description Also termed relay test, which is used to check the wiring and the configuration.

Setting 1. Press the operating line selection buttons to select operating line 51.
2. Press the + / - buttons to run through the output test.
Setting range Unit Factory setting

0...3 Increment 0

Effect The output test will automatically become available on this operating line.
With each test step, the respective output will be activated so that it can be checked.

Test sequence The test sequence is arranged in the form of a ring counter. This means it can be run
through either forward or backward by pressing the + / - buttons.

Test step 0 All outputs are switched according to actual control operation

Test step 1 All outputs are deactivated

Test step 2 D.h.w. charging pump (Q3) is activated

Test step 3 Heating circuit or system pump (Q1) is activated.

Note For additional information, refer to section "Commissioning.

4.2 Input test

Benefit Commissioning is facilitated


Faults can be traced much faster

Description Also termed detector test, which is used to check the wiring and the configuration.

Setting 1. Press the operating line selection buttons to select operating line 52.
2. Press the + / - buttons to run through the input test.
Setting range Unit Factory setting

0...5 Increment 0

Effect The input test will automatically become available on this operating line.
With each test step, the respective input will be displayed so that it can be checked.

Test sequence The test sequence is arranged in the form of a ring counter. This means it can be run
through either forward or backward by pressing the + / - buttons.

55/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Test step 0 Display of the function (B70/B4) [C] selected on operating line 97.

Test step 1 Display of the d.h.w. temperature (B3).

Test step 2 Display of the cascade flow temperature (B10).

Test step 3 Display of the actual outside temperature (B9)

Test step 4 Display of room temperature acquired with room unit connected to
A6

Test step 5 Display of input H1 according to the function selected on operating


line 170 [C, - - - , o o o].

 Note For additional information, refer to section "Commissioning.

Special displays Sensor with open-circuit or no sensor connected


000 Sensor with short-circuit

4.3 Display of plant type

Benefit Plant structure is easy to understand


Straightforward checking of configuration

Description Displays the plant type used.

Setting 1. Press the operating line selection buttons to select operating line 53.
2. No setting can be made with the + / - buttons.

Display Unit

0, 27...36, 65...67 -

Effect The number of the current plant type will automatically be displayed on this line.
0 Invalid configuration of plant

27...36, Valid configuration of plant


65...67
Plant type Based on the connected peripheral devices and parameter settings, the controller
ascertains the current plant type.
The plant type is displayed in the form of a number which corresponds to the plant
diagram.
For the graphic illustration of the various plant types, refer to chapter "Application".

The following factors have an impact on the generation of the type of plant:

- Connection of a d.h.w. temperature sensor:


The controller identifies a connected d.h.w. temperature sensor and also whether it is
connected directly to the controller or to one of the BMUs.
- Setting of operating line "Type of d.h.w. demand" (line 125)
Based on this setting, the controller knows whether the d.h.w. is heated by means of
a temperature sensor or control thermostat.
- Selection of pump connected to output Q1 (operating line 95)
- Adjustment of heating curve (operating line 17)
(- - : - or value between 2.5 and 40)

56/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
combinations The following table contains the setting combinations that lead to the required types of
plant:
Plant type- Slope of Pump function Type of d.h.w. demand D.h.w. sensor
number heating curve (output Q1) (operating line 125) connected to:
(operating (operating line (operating line 95) BMU RVA
line 53) 17)

27 --- heating circuit pump temperature No No


27 x D.h.w. circulating pump temperature No No
28 --- heating circuit pump temperature x Yes
28 --- heating circuit pump Control x No
28 x D.h.w. circulating pump temperature x Yes
28 x D.h.w. circulating pump Control x No
29 --- heating circuit pump temperature Yes No
29 x D.h.w. circulating pump temperature Yes No
30 x Primary pump for d.h.w. and temperature No No
30 x Primary pump for HCs only temperature No No
31 x Primary pump for d.h.w. and temperature x Yes
31 x Primary pump for d.h.w. and Control x No
32 x Primary pump for HCs only temperature x Yes
32 x Primary pump for HCs only Control x No
33 x Primary pump for d.h.w. and temperature Yes No
33 x Primary pump for HCs only temperature Yes No
34 2.5...40 heating circuit pump temperature No No
35 2.5...40 heating circuit pump temperature x Yes
35 2.5...40 heating circuit pump Control x No
36 2.5...40 heating circuit pump temperature Yes No
65 x Pump H1 temperature No No
66 x Pump H1 temperature x Yes
66 x Pump H1 Control x No
67 x Pump H1 temperature Yes No

x means that the setting has no influence on the generation of plant type.

 Note If the heating curve is deactivated (setting ---), the controller requires an external heat
demand signal to release the generation of heat. An external demand for heat can be
transmitted to the controller via LPB (LPB capable controllers) or input H1. If several
signals are present, the controller will use the highest of them as the setpoint.

The following settings are invalid, therefore producing fault message 58 (demand from
thermostat, but sensor used):

Plant type- Slope of heating Pump function Type of d.h.w. D.h.w. sensor
number curve (output Q1) demand connected to:
BMU RVA

28 --- heating circuit pump Control x Yes


28 x D.h.w. circulating pump Control x Yes
31 x Primary pump for d.h.w. and Control x Yes
32 x Primary pump for HCs only Control x Yes
35 2.5...40 heating circuit pump Control x Yes
66 x Pump H1 Control x Yes

x means that the setting has no influence on the generation of the type of plant.

57/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.4 Displaying the PPS communication

Benefit Interface for BMUs and digital room unit


Checking the communication with the peripheral devices (BMUs, room unit)

Description PPS is a point-to-point interface for communication between controller, BMU and room
unit. The display provides information about the communication status and the types of
connected peripheral devices.

Setting 1. Press the operating line selection buttons to select operating line 54.
2. Press the + / - buttons to interrogate the various PPS users.
Display Unit

No communication
1...12 / 0...255 PPS address / identification code
ooo Short-circuit of communication line

Effect The status of the PPS communication will automatically be displayed on this line. If
communication is error-free, the controller identifies the unit connected by displaying
the identification number, in addition to the device address.

Displays The display is comprised of PPS address and a device identification code.

PPS-address Within the PPS, a fixed PPS address is assigned to some types of devices:
Room unit  1
BMU-Nummer 1  4
BMU-Nummer 2  5
BMU-Nummer 3  6
BMU-Nummer 4  7

Note These peripheral devices can only be operated under the respective PPS address. If
one of these devices is not used, the PPS address can be allocated to some other
peripheral device.
Assignment of all the other peripheral devices to the PPS addresses can be made
randomly.
Since every controller has a specific and confined PPS address space, the same PPS
addresses can be assigned to each device.

58/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Identification code Only digital peripheral devices can be connected to the controller. Analog devices are
not permitted. The digital devices transmit the controller an identification code in
agreement with the type of device. The type of device can be identified with the help of
the list given below.

82 Room unit QAA 50 (digital)


83 Room unit QAA 70 (digital)
90 Room temperature sensor QAA10 (digital)
102 BMU

 Notes When the LCD displays a PPS address with an identification code, the
communication with the respective device is error-free
When the LCD displays no PPS address and no identification code, there is no
communication or it is faulty
Incompatible devices are also displayed, but produce error code 145 (operating line
50)

59/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Actual values
Benefit Overview of the actual temperatures of the sensors used
Better reproducibility of the control sequences thanks to visualized temperatures

4.5 Actual boiler temperature values of BMUs


(TKx)
Setting 1. Press the operating line selection buttons to select operating line 55.
2. Press the + / - buttons to interrogate the individual BMUs.
Display Unit

1...4 / 0...140 BMU number / C

Effect The lowest connected BMU number with the associated temperature will automatically
be displayed on this line. The temperatures of the other cascaded heating boilers can
be interrogated by pressing the + / - buttons. Non-existing BMUs will be skipped.
 Note The cascade boilers displayed are only those connected to this controller. If there are
additional cascaded boilers, they will be displayed on the controllers to which they are
physically connected.

Special displays: In place of the temperature, the following displays can appear next to the BMU number:
Sensor with an open-circuit or no sensor connected
000 Sensor with short-circuit

 Note If the LCD displays without giving an associated BMU number, there is no BMU
connected to the controller.

4.6 Actual value of cascade flow temperature

Description When using several cascaded heat sources, a cascade flow temperature sensor (B10)
must be installed.
Also termed "Common flow temperature sensor.

Setting 1. Press the operating line selection buttons to select operating line 56.
2. No setting can be made with the + / - buttons.
Display Unit

0...140 C

Effect The temperature measured with the cascade flow temperature sensor (B10) will
automatically be displayed on this line.
Cascade flow In a cascaded system, a common cascade flow temperature sensor (B10) is used for
temperature sensor all heat sources.
The cascade temperature sensor (B10) is connected directly to the RVA47.320.

60/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
B10

1 2 3 4

B70

2379S27
B10 Cascade flow temperature sensor

Special displays Sensor with open-circuit, no sensor connected, or sensor incorrectly


defined
000 Sensor with short-circuit

4.7 Actual value of the cascade return


temperature

Description When using several cascaded heat sources, we recommend to use a cascade return
temperature sensor (B70).
It is also termed "Common return temperature sensor.

Setting 1. Press the operating line selection buttons to select operating line 57.
2. No setting can be made with the + / - buttons.
Display Unit

0...140 C

Effect The temperature measured with the cascade return temperature sensor (B70) will
automatically be displayed on this line.
Cascade return In a cascaded system, a common cascade return temperature sensor (B70) should be
temperature sensor used for all heat sources. The value of this sensor is used for optimizing the controllers
functionality. In particular, it permits the detection of wrong mass flows (primary /
secondary mass flow).
The cascade return temperature sensor is connected directly to the RVA47.320.

61/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
B10

1 2 3 4

B70

2379S27
B70 Cascade return temperature sensor

 Important The meaning of the temperature measured at B70/B4 is defined by setting 1 (cascade
return temperature sensor) on operating line 97.

Special displays Sensor with open-circuit, no sensor connected, or sensor incorrectly


defined
000 Sensor with short-circuit

62/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.8 Actual value of buffer storage tank
temperature

Description When using alternative heat sources, the buffer storage tank temperature is used as a
control criterion for the release of additional heat sources.

Setting 1. Press the operating line selection buttons to select operating line 58.
2. No setting can be made with the + / - buttons.
Display Unit

0...140 C

Effect The actual temperature in the buffer storage tank (B4) will automatically be displayed
on this line.

Important To be used as a buffer storage tank temperature sensor, input B70/B4 must be
appropriately defined (operating line 97, setting 2)
 Note If input B70/B4 of the first cascade controller is already used by the optional cascade
return temperature sensor B70, buffer storage tank temperature sensor B4 can be
connected to input B70/B4 of the second controller.

4.9 Actual value of the d.h.w. temperature


(TBWx)

Setting 1. Press the operating line selection buttons to select operating line 59.
2. No setting can be made with the + / - buttons.
Display Unit

0...140 C

Effect The temperature measured with the d.h.w. temperature sensor (B3) connected to the
controller, or the d.h.w. temperature transmitted by the BMU via PPS will automatically
be displayed on this line.
 Note With the type of d.h.w. demand Thermostat (line 125), there will be no temperature
display of course. The display shows --- . The input test (line 52, test step 1)
provides information about the current switching status of the thermostat.

Special displays Sensor with open-circuit or no sensor connected


000 Sensor with short-circuit

63/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.10 Attenuated outside temperature

Benefit Making use of the buildings thermal storage capacity

Description
The attenuated outside temperature is the simulated room temperature of a fictive
building that has no internal heat source. This means that it is only the outside
temperature that affects the room temperature.

Setting This operating line automatically displays the actual value [C] of the attenuated outside
temperature. No direct setting can be made.
The generation of the attenuated outside temperature cannot be influenced.
Display Unit

-50...50 C

Resetting It is possible, however, to reset the attenuated outside temperature:


1. Press the operating line selection buttons to select line 19.
2. Press the + / - buttons for 3 seconds.
As soon as the display stops flashing, the attenuated outside temperature is reset to
the actual outside temperature.

Process The attenuated outside temperature is generated by the controller. It is continually


calculated based on the prevailing outside temperature. The factory setting is 0 C.
Effect The attenuated outside temperature affects directly only the summer / winter
changeover (setting 16).
The attenuated outside temperature acts indirectly, via the composite outside
temperature, on flow temperature control.

Example TAakt
TA
C
17

16

15 TAged

14

13
2371D11

18:00 06:00 18:00 06:00 18:00 h

TAakt Actual outside temperature


TAged Attenuated outside temperature

64/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.11 Composite outside temperature

Benefit Compensating variable for the flow temperature control

Description The composite outside temperature is a mixture of the actual outside temperature and
the attenuated outside temperature calculated by the controller.

Setting This operating line automatically displays the actual value [C] of the composite outside
temperature. No direct setting can be made.
Display Unit

-50...50 C

Process The mixture of actual and attenuated outside temperature is dependent on the type of
building construction (setting 105) and is generated as follows:

Selected type of construction Composite outside temperature


Heavy (setting 105 = 0) Tagem = TAakt + TAged
Light (setting 105 = 1) Tagem = TAakt + TAged

Effect The composite outside temperature as a compensating variable acts on flow


temperature control, that is thus matched to the prevailing weather conditions.
It also acts on the 24-hour heating limit to shut down the heating.

Example TAakt
TA
C TAgem1
TAgem0
17

16

TAged
15

14

13
2371D12

18:00 06:00 18:00 06:00 18:00 t

TAakt Actual outside temperature


TAged Attenuated outside temperature
TAgem1 Composite outside temperature for light building structures
TAgem0 Composite outside temperature for heavy building structures

65/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Setpoints .
4.12 Outside temperature source

Benefit Display and location of actual outside temperature measurement

Description When interconnecting several controllers, only one outside sensor is required. This
sensor will be connected to any of the controllers and delivers its signal via LPB.
The controllers to which no sensor is connected adopt the outside temperature signal
via the bus system, from a controller to which a sensor is connected.

Setting 1. Press the operating line selection buttons to select operating line 62.
2. No setting can be made with the + / - buttons.
Display Unit

. No signal
00.01...14.16 Segment and device address

Effect The address of the outside detector that currently delivers the outside temperature
signal will automatically be displayed on this line.

Display . No outside sensor signal

01.02 Address of outside sensor


The first 2 digits represent the segment number (01.)
The second digit corresponds to the device number (.02)

 Note If required (e.g. due to different exposure to solar radiation of the various buildings), the
different sections of the system can be equipped with their own outside sensors.
For more detailed information, refer to section Outside temperature source of Local
Process Bus (LPB), Basic Documentation, System Engineering (document no.
CE1P2370E).

4.13 Boiler temperature setpoint of BMUs

Benefit Indication of BMU temperature setpoints


Better overview of the plants operational status

Description The lowest connected BMU number with the associated temperature setpoint will
automatically be displayed on this line. The temperature setpoints of the other BMUs
used in the cascade can be interrogated by pressing the + / - buttons. Nonexisting
BMUs will be skipped.
Setting 1. Press the operating line selection buttons to select line 65.
2. Press the + / - buttons to select the setpoint of the required BMU.

Display Unit

1...4 / 0...140 BMU number / C


 Note The setpoints can only be displayed but not changed. The function helps better
understand the control sequences taking place in the controller.
No setpoint is displayed (---), when

there is no heat demand from the consumers


no BMU is connected to the controller

66/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.14 Setpoint of the cascade flow temperature

Benefit Indication of setpoint of the cascade flow temperature


Better overview of the plants operating state

Description The setpoint of the cascade flow temperature will automatically be displayed on this
line.

Setting 1. Press the operating line selection buttons to select line 66.
2. No setting can be made with the + / - buttons.

Display Unit

0...140 C

The setpoint can only be displayed, but not changed. The function helps better
understand the control sequences taking place in the controller.

Generation of setpoint The setpoint displayed is generated based on the different heat demand signals
received from the system. These are:
Demand for heat from the controllers internal heating circuits based on the outside
temperature
Demand for heat from the external heating circuits (system) based on the outside
temperature
Demand for heat for d.h.w. (from inside the controller or externally)
Demand for heat via contact H1
Demand for heat resulting from protective functions (e.g. frost protection for the
plant)
Demand for heat by pressing the button for manual operation
The highest of the setpoints received is shown on the display as the setpoint of the
cascade flow temperature.

 Note The display shows --- if one of the following points applies:

There is no demand for heat


The controller has been defined as a cascade controller (device address > 1)
Sensor B10 has not been detected or connected

4.15 D.h.w temperature setpoint

Benefit Visualization of the d.h.w. temperature setpoint


Better overview of the plants operating state

Description The current d.h.w. temperature setpoint will automatically be displayed on this line.

Setting 1. Press the operating line selection buttons to select line 69.
2. No setting can be made with the + / - buttons.

Display Unit

0...140 C

The setpoint can only be displayed, but not changed.

Generation of setpoint The value displayed depends on the following parameters:

67/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Current time of day (operating line 1)
Time switch program d.h.w. heating (lines 29...35)
Nominal setpoint of the d.h.w. temperature
(operating line 13)
Reduced setpoint of the d.h.w. temperature
(operating line 120)
Release of d.h.w. heating
(operating line 121)
Assignment of d.h.w.
(operating line 123)
d.h.w.frost protection (5C)
Number of the d.h.w. heating cycles per day (operating line 124)
Legionella function ON / OFF (operating line 42OEM)
Legionella setpoint (operating line 43OEM)

 Note No value (---) is displayed in the following situations:

No d.h.w. heating available


D.h.w. heating is switched off (button for d.h.w. heating OFF)

4.16 Nominal room temperature setpoint

Benefit Information about the nominal room temperature setpoint in normal operation

Description Displays the current nominal room temperature setpoint during the comfort period.
The nominal room temperature setpoint is the temperature adjusted on the controller
that shall be maintained in the rooms in normal operation (comfort).

Setting 1. Press the operating line selection buttons to select operating line 70.
2. No setting can be made with the + / - buttons.
Display Unit

0.0...35.0 C

Effect The nominal room temperature setpoint will automatically be displayed on this
operating line.

Nominal room The resulting nominal room temperature setpoint is made up of the adjusted setpoint
temperature setpoint and a readjustment that may have been made on the room unit:

Without room unit


Adjustment made with the controllers setpoint knob
= controller's nominal room temperature setpoint

When using a room unit with no programming facility (e.g. QAA50)


Adjustment made with the controllers setpoint knob
1)
+ readjustment made on the room unit ( 3 C)
= controller's nominal room temperature setpoint

When using a room unit with a programming facility (e.g. QAA70)


1)
Setpoint programmed with the room unit
1)
+ readjustment made on the room unit ( 3 C)
= controller's nominal room temperature setpoint
 In that case, the controller's setpoint knob is inactive.

68/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
 Important 1) Setpoints and readjustments made on room units are considered only in automatic
mode .

4.17 Room temperature setpoint

Benefit Information about the room temperature setpoint in the various operating modes

Description Displays the current room temperature setpoint during the respective heating period
(normal operation / reduced operation).

Setting 1. Press the operating line selection buttons to select line 71.
2. No setting can be made with the + / - buttons.

Display Unit

0...35 C

When selecting the operating line, the current room temperature setpoint is displayed,
depending on the operating mode and the time switch program, that is, a selection /
combination of the following parameters:
Room temperature setpoint knob
Reduced setpoint of room temperature (operating line 13)
Frost protection setpoint of room temperature (operating line 15)
Readjustments made on the room unit (QAA50 / QAA70)

 Note If there is no heating circuit, the display shows ---.

4.18 Flow temperature setpoint

Benefit Displays the current flow temperature setpoint of the pump heating circuit

Description When selecting this operating line, the current flow temperature setpoint of the
controllers internal pump heating circuit is displayed.

Setting 1. Press the operating line selection buttons to select line 72.
2. No setting can be made with the + / - buttons.

Display Unit

0...140 C

The value displayed corresponds to the flow temperature of the pump heating circuit
which is required for reducing the demand for heat.

 Note The display shows --- in the following situations:

No heating circuit available


ECO function active (summer / winter changeover, automatic 24-hour heating limit)
Quick setback active
Room temperature limitation active

69/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Heat generation values
4.19 Existing boilers

Benefit Overview of the boilers used by the system

Description The function makes it possible to obtain a quick overview of the boilers used by the
system.

Setting 1. Press the operating line selection buttons to select line 75.
2. Press the + / - buttons to scroll through the list of available boilers.

Display Unit

00.1...16.3 -

The numbers have the following meaning:

00.1...16.3 Device address and device subaddress (boiler number in a controller) of


the boilers assigned to the system (max. 16).
All boilers must be contained in segment 0 to ensure the demand for
heat from all segments will be considered.

 Caution! Do not mix up device / device subaddress and segment / device address!
If the segment address was added, the display would read 0.00.1 ... 0.16.3.

Device address A controller that uses device address 0 (e.g. 00.1) operates autonomously ( no
communication via LPB).
The device address 1 (01.1) defines the cascade master (controller).

Device subaddress Up to four BMUs can be connected to the first RVA47.320 (B-series) of a cascade, and
up to three BMUs to each of the additional RVA47.320 (B-series).
The possible device subaddresses are therefore 1.1 ... 1.4, 2.1 ... 2.3, 3.1 ... 3.3
through 16.3 One cascade can contain a maximum of 16 boilers, however.

For more detailed information, refer to Local Process Bus (LPB), Basic
Documentation, System Engineering (document no. CE1P2370E).

4.20 Display lead boiler

Benefit Quick overview of current lead boiler

Description With Automatic lead boiler changeover, this function facilitates quick identification of
the current lead boiler.

Display When selecting this operating line, the current lead boiler is displayed. No settings can
be made with the + / buttons.

Display Unit

00.1...16.3 -

The numbers have the following meaning:

70/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
00.1...16.3 Device address and device subaddress (boiler number in a controller) of
the boilers assigned to the system (max. 16).
All boilers must be contained in segment 0 to ensure the demand for
heat from all segments will be considered.

 Caution! Do not mix up device / device subaddress and segment / device address!
If the segment address was added, the display would read 0.00.1 ... 0.16.3.

Device address A controller that uses device address 0 (e.g. 00.1) operates autonomously ( no
communication via LPB).
The device address 1 (01.1) defines the cascade master (controller).

Device subaddress Up to four BMUs can be connected to the first RVA47.320 (B-series) of a cascade, and
up to three BMUs to each of the additional RVA47.320 (B-series).
The possible device subaddresses are therefore 1.1 ... 1.4, 2.1 ... 2.3, 3.1 ... 3.3
through 16.3 One cascade can contain a maximum of 16 boilers, however.

 Note The setting for boiler sequence changeover is made on operating line 130.
For more detailed information, refer to Local Process Bus (LPB), Basic
Documentation, System Engineering (document no. CE1P2370E).

4.21 Remaining number of operating hours for


changeover of boiler sequence

Benefit Indication of the remaining number of operating hours until the next changeover of
boiler sequence takes place.

Description Indicates the number of hours the current lead boiler still operates until the next
changeover of boiler sequence occurs.

Setting When selecting this operating line, the remaining number of operating hours for
changeover of the boiler sequence are displayed.
Display Unit

0...990 / --- h/-

Display The number displayed represents the number of operating hours until the next
changeover of boiler sequence occurs. It is generated by subtracting the current
number of operating hours from the setting made on operating line 130 (automatic
changeover according to the number of operating hours).
 Note The display appears only if, on operating line 130, a setting of 10990h has been
selected (automatic changeover according to the number of operating hours).
Otherwise, the display will show "- - -.

71/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.22 Burner operating hours BMU 1 4

Benefit Overview of the number of burner operating hours of the individual BMUs
Criterion for service and maintenance work
Criterion for adjusting the cascade management strategy

Description The display shows the number of hours the respective BMU has been operating since
the controller was first commissioned.

Setting 1. Press the line selection buttons to select lines 80 -83.


2. No setting can be made with the + / - buttons.

Display Unit

0...65535 h

The numbers have the following meaning:


Line 80 Number of burner operating hours of BMU 1
Line 81 Number of burner operating hours of BMU 2
Line 82 Number of burner operating hours of BMU 3
Line 83 Number of burner operating hours of BMU 4

 Note For information about the selection of the cascade management strategy, refer to
operating lines 50OEM to 52OEM.

4.23 Minimum limitation of the boiler


temperature TKmin

Benefit This function prevents the boiler temperature from falling below a predefined
minimum temperature.

Description Minimum limitation of the boiler temperature setpoint is a protective function for the
boiler. In addition, minimum limitation of the setting range can be provided with the
setting 01OEM.

Setting 1. Press the operating line selection buttons to select line 90.
2. Press the + / - buttons to set the minimum limitation of the boiler temperature
TKmin.

Setting range Unit Factory setting

TKminOEM...TKmax (max 95C) C 8


TkminOEM Minimum limitation of the boiler temperature setpoint (setting on line 01OEM)
Tkmax Maximum limitation of the boiler temperature setpoint (setting on line 02OEM)

TV
2371Z22

max

akt

min

0 10 20 30 40 50 60 70 80 90 100 120 C

72/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
55 Actual value of the boiler temperature
90 Minimum limitation of the boiler temperature setpoint
2OEM Maximum limitation of the boiler temperature setpoint
1OEM Lowest minimum limitation of the boiler temperature setpoint

Effect If the boiler temperature falls below the set minimum temperature, this setting
generates a locking signal which reduces the amount of heat supplied to the
consumers.

4.24 Nominal output of BMU 1 - 4

Benefit Consideration is given to the different heat source capacities

Description By setting this paramter, the controller knows the proportion of capacities of the
connected boilers and can take this into account with the running time strategy and the
linked lead boiler operation (refer to page 114 ff.).

Settings 1. Press the line selection buttons to select lines 91 -94.


2. Press the + / - buttons to set the nominal capacities of BMUs 1 - 4.

Line BMU-Nr. Setting range Unit Factory setting


BMU1 0...255 kW 20
BMU2 0...255 kW 20
BMU3 0...255 kW 20
BMU4 0...255 kW 20

 Note The controller only uses the proportions of the numbers entered. When having
capacities of 100 / 150 / 70 kW, entry of the proportions of 10 / 15 / 7 or 20 / 30 / 14 will
lead to the same result as entry of the absolute figures. Hence, capacities above 255
kW can also be entered by using the respective ratios.

Effect This setting has an impact on the accuracy of the points in time the individual boilers
are switched on and off (refer to boiler management and running time strategy,
operating line 50OEM).
Autonomous lead boiler operation:
No effect

Linked lead boiler operation:


The lag boilers follow the lead boiler's output at different speeds, depending on the
proportion of capacities of lead boiler and lag boilers.

Running time strategy 1 - 3:


Additional boilers are switched on or off earlier or later, depending on the capcities of
the individual boilers in sequence.

73/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Configuration of plant
4.25 Pump function output Q1

Benefit Use of pump for different types of plant

Description This parameter defines the function provided by the pump connected to terminal Q1.

 Note Setting of this function has an impact on automatic generation of the type of plant.
Operating line 53.

Setting 1. Press the operating line selection buttons to select operating line 95.
2. Press the + / - buttons to select the required function of the circulating pump.
Setting range Unit Factory setting

1...5 - 1

Effect The pump provides one of the following functions, depending on the setting made:

1 Circulating pump operates as a heating circuit pump of the controller-internal


pump heating circuit or no pump is available.
2 Circulating pump works as a system pump for the heating circuits only
(located after the d.h.w. storage tank).
3 Circulating pump works as a system pump for the heating circuits and for the
d.h.w. (located before the d.h.w. storage tank).
4 Circulating pump operates as a d.h.w. circulating pump
5 Circulating pump operates as an H1 pump

Pump overrun is active with all settings, with the exception of setting 4.

4.26 Use sensor input B70/B4

Benefit The same sensor input can be used for different functions

Description This parameter setting defines the function adopted by the temperature sensor
connected to terminal B70/B4.

Setting 1. Press the operating line selection buttons to select operating line 97.
2. Press the + / - buttons to select the required function of the input B70/B4.
Setting range Unit Factory setting

1...2 - 1

Effect Depending on the setting made, the sensor provides the following function:

1 The sensor is used for measuring the return temperature (B70).

2 The sensor is used for measuring the buffer storage tank temperature (B4).

Use in cascades If, with the first controller, sensor input B70/B4 is defined for use with a return
temperature sensor (B70), for instance, it can be defined with another controller of the

74/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
cascade for use with a buffer storage tank temperature sensor (B4). The sensor values
are automatically transmitted to the cascade master. Within a cascade, each type of
sensor may occur only once (with the exception of the outside sensor).

Use as a buffer storage When using input B70/B4 for a buffer storage tank temperature sensor (B4), the
tank temperature sensor temperature measured at B4 is used to decide whether the consumers receive their
heat from the cascade or from the buffer storage tank.
If the temperature measured in the buffer storage tank is higher than the flow
temperature called for by the consumers, the cascade will be locked and the
consumers receive their heat from the buffer storage tank.
If the temperature measured in the buffer storage tank is lower than the flow
temperature called for by the consuemrs, the buffer storage tank will be locked and the
consumers receive their heat solely from the cascade.

Example Example of a hydraulic circuit with a buffer storage tank. The buffer storage tank can be
charged by any type of heat source (wood-fired boiler, solar collectors, heat pump, etc).

B9 V

B10 FK

B4

1 2

FK
SK

SK

B70

2379S37
V

SK = solar collectors
FK = solid fuel boiler
V = consumer

Connection of diverting The changeover valve must be connected in parallel to the pump of the first BMU. This
valve BMU must be excluded from automatic changeover of the boiler sequence (refer to
operating line 131).

75/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Heating circuit values
4.27 Parallel displacement of the heating curve

Benefit Adjustment of controller's temperature scale to the actual plant conditions.

Description Produces a parallel displacement of the heating curve in order to achieve a better
match of room temperature setpoints and actual room temperatures.

Setting 1. Press the operating line selection buttons to select operating line 100.
2. Press the + / buttons to set the parallel displacement..
Setting range Unit Factory setting

-4.5...+4.5 C (K) 0.0

Effect By changing the value entered, all room temperature setpoints will be appropriately
raised or lowered. This allows the room temperature setpoints to be matched to the
effective room temperatures.
Example: If a nominal room temperature setpoint of 20 C adjusted on the controller always
produces a room temperature of 22 C (independent of the prevailing outside
temperature), displace the heating curve downward by 2 C.

Parallel displacement Each setpoint readjustment, be it by changing the setting value or the operational level,
corresponds to a parallel displacement of the heating curve.

TV
C
100

90

80

70

60

50

40
2406D02

30 30

20 10 0 -10 -20 -30 C


TA
10
10

0 TR
0 w

TV Flow temperature
TA Composite outside temperature
TRw Room temperature setpoint

4.28 Room influence

Benefit More accurate room temperature control due to temperature checkback signal from
the space
Use of heat gains
Possibility of boost heating and quick setback

76/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Description Defines the impact of room temperature deviations on the controlled system.
Room temperature deviation is the temperature differential between actual room
temperature and room temperature setpoint.

Setting 1. Press the operating line selection buttons to select operating line 101.
2. Press the + / buttons to select the room influence.

Setting range Unit Factory setting

0/1 Increment 1

Effect The setting will activate or deactivate the effect of room temperature deviations on the
temperature control.
Entry:

0 Room influence inactive:


The measured room temperature will not affect temperature control

1 Room temperature influence active: The measured room temperature will affect
the temperature control

Room influence Room influence means:


Deviations of the actual room temperature from the setpoint are acquired and taken into
account by temperature control.

To use the control variant "Weather compensation with room influence", the following
conditions must be satisfied:
An outside sensor must be connected (either to B9, the PPS or the LPB).
Setting "Room temperature influence" (101) must be active (1)
The respective room unit must be connected to terminal A6 (PPS)
There may be no controlled thermostatic radiator valves
(If such valves are present, they must be set to their fully open position).

4.29 Switching differential of the room


temperature

Benefits Temperature control with pump heating circuit


Prevents overtemperatures in the room in the case of pump heating circuits
Description Serves as a room temperature limitation with pump heating circuits

Setting 1. Press the operating line selection buttons to select operating line 102.
2. Press the + / buttons to set the room temperature switching differential.

Setting range Unit Factory setting

. - .
0.5...4.0 C

Effect The switching differential for two-position control will be changed.


Entry:
--.- Switching differential is inactive
The pump always remains activated

77/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Decrease: Switching differential will become smaller
Pumps are switched on and off more often
Room temperature varies within a narrower band

Increase: Switching differential will become greater


Pumps are switched on and off less often
Room temperature varies within a wider band

Room temperature With pump heating circuits, the amount of heat supplied is controlled by switching the
control pumps on and off. This is accomplished with two-position control by means of the room
temperature's switching differential.

 Note Room temperature acquisition requires a room unit.


Legend
C
Functioning: TRx
TRx Actual value of the room temperature
TRw Room temperature setpoint
TRw+SDR
SDR Switching differential of room
TRw
temperature
ON Switch-on point
OFF Switch-off point
t t Time
P Pump
ON

2371D02
P
OFF

Switching differential
TRx Actual value of the room temperature
TRw Room
P temperature setpoint
SDR Switching
differential of room temperature
ON P Pump (ON / OFF)
w Setpoint

Switch-on point
2379Z19

Switch-off point

OFF

w
TRx [C ]

Pump ON TRx = TRw


Pump OFF TRx = TRw + SDR

4.30 Minimum limitation of the flow temperature


setpoint

Benefit Prevents too low flow temperatures

Description Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.

78/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Setting 1. Press the operating line selection buttons to select operating line 103.
2. Press the + / - buttons to set the minimum limitation of the flow temperature
setpoint.
Einst ellbereich Unit Factory setting

8...TVmax C 8
TVmax Maximum limitation of flow temperature setpoint (setting on operating line 104)

TV

2379Z09
max
TVw
akt

min

0 10 20 30 40 50 60 70 80 90 100 C

TVw Current flow temperature setpoint


103 Minimum limitation of flow temperature setpoint
104 Maximum limitation of the flow temperature setpoint

Effect The setting will make certain that the flow temperature setpoint will not fall below a
minimum level.

Limitation If the flow temperature setpoint demanded by the heating circuit reaches the minimum
limit and the outside temperature rises, the flow temperature setpoint will be maintained
at that limit, in other words, it will not be allowed to fall below it.

4.31 Maximum limitation of the flow temperature


setpoint

Benefit Prevents too high flow temperatures

Description Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.

Setting 1. Press the operating line selection buttons to select operating line 104.
2. Press the + / - buttons to set the maximum limitation of the flow temperature
setpoint.
Setting range Unit Factory setting

TVmin...95 C 80
Tvmin Minimum limitation of flow temperature setpoint (setting on operating line 103)

79/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
TV

2379Z09
max
TVw
akt

min

0 10 20 30 40 50 60 70 80 90 100 C

TVw Current flow temperature setpoint


103 Minimum limitation of the flow temperature setpoint
104 Maximum limitation of the flow temperature setpoint

Effect The setting will ensure that the flow temperature setpoint will not exceed a maximum
level.
 Important Maximum limitation is not to be regarded as a safety function as required with
underfloor heating systems, for example.

Limitation If the flow temperature setpoint demanded by a consumer reaches the maximum limit
and the outside temperature falls, the flow temperature setpoint will be maintained at
that limit, in other words, it will not be allowed to exceed it.

4.32 Type of building construction

Benefit Consideration is given to the building's thermal dynamics

Description Enables the control system's response to be matched to the type of building
construction.

Setting 1. Press the operating line selection buttons to select operating line 105.
2. Press the + / buttons to select the type of building construction.

Setting range Unit Factory setting

0/1 Increment 1

Effect When the outside temperature varies, the room temperature changes at different rates,
depending on the building's thermal storage capacity.
The above setting ensures that the generation of the composite outside temperature
will be matched to the type of building construction. Also refer to "Composite outside
temperature in section "Functions without settings".
Entry:
0 Heavy building structures: The room temperature will respond slower to outside
temperature variations

1 Light building structures: The room temperature will respond quicker to outside
temperature variations

Building construction Heavy building structures:


Buildings with thick walls or with external insulation
Light building structures:
Buildings with a light envelope

80/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.33 Adaption of the heating curve

Benefit No heating curve adjustments required


Automatic adaption of heating curve

Description The adaption facility learns from the different heating situations and matches the control
to the heating circuit at regular intervals. Also refer to section Adaption sensitivities
(lines 36 OEM + 37OEM).

Setting 1. Press the operating line selection buttons to select operating line 106.
2. Press the + / buttons to select the type of heating curve adaption.

Setting range Unit Factory setting

0/1 Increment 1

Effect The setting will switch automatic adaption of the heating curve on or off.
Entry:
0 Automatic adaption inactive: The heating curve will use the setting made

1 Automatic adaption active: In automatic mode (nominal room temperature


setpoint ), the heating curve will automatically and continuously be adapted

 Note Prerequisite is the presence of a room temperature sensor.

Adaption The adaption facility automatically matches the heating curve to the type of building
construction and the heating requirements. Adaption gives consideration to room
temperature deviations, outside temperature characteristics and adaption sensitivity.
 Note To achieve optimum adaption, the following situations should occur as rarely as
possible - especially after commissioning - since this would reset certain calculations
required for the adaption:
Manual correction of heating curve
Power failure
Heating curve set to --.-
Changes to the room temperature setpoint

Process Every day at midnight, the room temperature control differential of the previous day is
evaluated. This evaluation leads to an automatic readjustment of the heating curve.
Simple adaption (range ):
At attenuated outside temperatures below 4 C, it is only the slope of the heating
curve that is adapted.

Within this temperature range, the readjustment is weighted with the factor f2 and
adaption sensitivity 2 (line 37OEM).

Combined adaption (range ):


At attenuated outside temperatures of between 4 and 12 C, it is partly the slope
and partly the parallel displacement that are adapted.

Within this temperature range, the readjustment of the parallel displacement is


weighted with the factor f1 and adaption sensitivity 1 (line 36OEM).

81/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
The readjustment of the slope in this temperature range is weighed with factor f2
and adaption sensitivity 2 (line 37OEM).

No adaption (range ):
At attenuated outside temperatures above 12 C, the heating curve will not be
adapted.

Diagram Example using a nominal room temperature setpoint of 20 C.

f
1

f2
0,5
f1

2371D07
0
20 12 4 -4 -12
TAged
ZAF1 ZAF2

f Factor
f1 Factor for parallel displacement
f2 Factor for slope
TAged Attenuated outside temperature
ZAF1 Adaption sensitivity 1 (line 36OEM)
ZAF2 Adaption sensitivity 2 (line 37OEM)

4.34 Maximum forward shift of optimum start


control

Benefit Maximum forward shift of optimum start control.

Description Maximum forward shift is a limit function that defines the range of optimum start control.

Setting Setting range Unit Factory setting


00:00...06:00 hh:mm 00:00

Effect 00:00 Optimum start control switched off

00:10...06:00 Optimum start control switched on

82/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.34.1 Optimum start control

Optimum start control acts with or without room influence.


The maximum forward shift can be set with parameter Maximum forward shift with
optimum start control (range 06 h). This parameter can also be used to switch
optimum start control off (setting 0).

During non-occupancy hours, the heating is maintained at the reduced level. Towards
the end of the nonoccupancy time, optimization switches the control back to the normal
level.
Optimization calculates the changeover time such that, at the start of occupancy, the
room temperature will have reached the nominal setpoint.

4.34.2 Without room influence

The composite outside temperature is used as the compensating variable. In the case
of floor heating systems, the maximum forward shift should be longer than with radiator
systems.
Using the parameter for the constant of quick setback and optimum start control (KON),
the forward shift can be matched the building dynamics.

Forward shift tE in hours and minutes with optimum start control without room
influence:

TAgem KON
0 4 8 12 16 20
- 20 0 1h20 2h40 4h00 5h20 6h00
- 10 0 0h50 1h50 2h40 3h40 4h30
0 0 0h30 1h00 1h30 2h00 2h30
+ 10 0 0 0h10 0h10 0h20 0h20
tE

TAgem Composite outside temperature


tE Forward shift
KON Parameter for quick setback and optimum start control without room influence

Parameter KON: KON = 0: Function deactivated


note: KON also acts on quick setback
Small KON: for high building structures can be heated up fairly quickly
Large KON: for heavy, well insulated building structures whose heating
up time is fairly long

4.34.3 With room influence

Optimum start control acts only when room influence is active.

The switch-on time for the heating (change to nominal level) is selected such that, at
the beginning of the occupancy time according to the heating program, the room
temperature reached will be the room temperature setpoint - 0.25 K.
The correct switch-on time is determined by adaption.

83/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.35 Maximum forward shift of optimum stop
control

Benefit Maximum forward shift of optimum stop control.

Description Maximum forward shift is a limit function that defines the range of optimum stop control.

Setting Setting range Unit Factory setting

00:00...06:00 hh:mm 00:00

Effect 00:00 Optimum stop control deactivated

00:10...06:00 Optimum stop control activated

4.35.1 Optimum stop control

Optimum stop control acts only when a room sensor is used and when room influence
is active.
The maximum forward shift can be set with parameter Maximum forward shift with
optimum stop control (range is 06 h). This parameter can also be used to switch
optimum stop control off (setting = 0).

During occupancy hours, the heating is maintained at the nominal level. Towards the
end of the occupancy time, the control switches to the reduced level.
Optimization calculates the changeover time such that, at the end of occupancy time,
the room temperature will be 0.5 C below the nominal setpoint (early shutdown).

Adaption takes place only with the first occupancy period per day. The switch-off point
is adapted in steps of 10 minutes. If the 0.25 K are not reached, the switch-off point is
shifted forward by 10 minutes (earlier shutdown). In the other case, the switch-off point
is shifted backward by 10 minutes (later shutdown).

84/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
D.h.w. values
4.36 Reduced setpoint of the d.h.w. temperature

Benefit High d.h.w. temperatures only if required


Energy savings due to lower temperatures in the remaining time

Description Reduction of the d.h.w. temperatures outside main occupancy times.


The time switch integrated in the controller automatically switches between main and
secondary occupancy times. For more detailed information, refer to "D.h.w. heating
program", operating lines 29...35
 Note If the d.h.w. is heated by means of a control thermostat connected to terminal B3,
reduced setpoint operation will not be possible.

Setting 1. Press the operating line selection buttons to select operating line 120.
2. Press the + / buttons to adjust the reduced setpoint of the d.h.w. temperature.

Setting range Unit Factory setting

8...TBWw C 40
TBWw Nominal setpoint of d.h.w. temperature (setting on line 13)

Effect The temperature setpoint during reduced d.h.w. operation will be changed.

2379Z10a
0 10 20 30 40 50 60 70 80 90 100 120 130 140 C

13 Setting "Nominal setpoint of d.h.w. temperature


120 Setting "Reduced setpoint of the d.h.w. temperature
40OEM Setting "Maximum nominal setpoint of the d.h.w. temperature

D.h.w. temperature D.h.w. heating has 2 different setpoints that can be used:
setpoints

Nominal setpoint of the d.h.w. temperature (setting on line 13)


Produces the d.h.w. temperature required during main occupancy times
Reduced setpoint of the d.h.w. temperature (setting on line 120)
Produces the d.h.w. temperature required outside the main occupancy times

The periods of time during which these d.h.w. temperature setpoints shall be used can
be set on line 121.

4.37 Release of d.h.w. heating

Benefit Release of d.h.w. heating to the nominal setpoint as demanded by the consumers
Release of d.h.w. heating can be matched to the plant's load curve

Description Makes it possible to limit the period of time during which d.h.w. heating at the nominal
setpoint is released.

85/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Setting 1. Press the operating line selection buttons to select operating line 121.
2. Press the + / buttons to enter the required period of time during which d.h.w.
heating at the nominal setpoint shall be released.

Setting range Unit Factory setting

0...2 Increment 1

Effect The setting defines the period of time during which d.h.w. heating at the nominal
setpoint is released. Outside this period of time, the reduced d.h.w. setpoint applies.
There is one exception, however, function d.h.w. push (function with no setting).
Release of d.h.w. heating to the nominal setpoint takes place when using the following
settings:
0 24 hours per day

1 According to the heating circuit time switch program)s) with forward shift

2 According to the d.h.w. time switch program of the RVA47.320

 Note The frost protection temperature for d.h.w. is fixed at 5 C and is always active.

4.37.1 24-hour operation - Setting 0

The d.h.w. temperature is always maintained at the nominal d.h.w. temperature


setpoint, independent of any time switch programs (setting line 13).

2371Z18
Example:

0 6 12 18 24 h

4.37.2 Operation according to heating program(s) with


forward shift - Setting 1

For d.h.w. heating, the heating circuit time switch programs of the controllers in the
selected range are taken into consideration. The selection of the range (local / segment
/ system) for which the d.h.w. is produced is made on operating line 123.
The switch-on point for the release is shifted forward in time against the earliest switch-
on point of all heating circuits. The switch-off point for the release coincides with the
last switch-off point of all heating circuits.

At the switch-on point, the controller switches from the reduced d.h.w. temperature
setpoint (operating line 120) to the nominal d.h.w. temperature setpoint (operating line
13).
At the switch-off point, the controller switches from the nominal to the reduced d.h.w.
temperature setpoint.

86/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
 Note The extent to which the switch-on point is shifted forward in time depends on the
number of d.h.w. heating cycles permitted in a 24-hour period (operating line 124):

2379Z29
Example:

0 5 6 12 16 17 24 h

4.37.3 Operation according to the d.h.w. time switch program


- Setting 2

For d.h.w. heating, time switch program (d.h.w.) of the local controller is taken into
account. The set switching times of that program are then used to change over
between the nominal d.h.w. setpoint (operating line 13) and the reduced d.h.w. setpoint
(operating line 120).
D.h.w. heating takes place independent of the heating circuit programs.

Heating periods With this d.h.w. heating program, it is possible to have a maximum of 3 heating periods
per day. The forward shift of the switch-on times is inactive.

2373Z24
Example:

0 6 12 18 24 h

4.38 Switching program circulating pump

Benefit The circulating pump runs only during the selected periods of time
No heat losses during the periods of time when there is no demand for d.h.w.

Description Defines the time switch program according to which the circulating pump is switched on
and off.

Setting 1. Press the operating line selection buttons to select operating line 122.
2. Press the + / - buttons to select the required time switch program.
Setting range Unit Factory setting

0...1 Increment 1

Effect Depending on the setting made, the circulating pump will be operated according to the
following time switch program:

0 For the switching program of the circulating pump, the switching program of the
controller internal heating circuit will be adopted.
1 Switching program according to the selected d.h.w. release (operating line 121).

87/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.39 Assignment of d.h.w. heating

Benefit Assignment of d.h.w. heating to the respective consumers


All relevant time switch programs are taken into consideration
Controllers in holiday mode are taken into consideration

Description Determines the consumers for which d.h.w. will be heated and which time switch
programs will be appropriately considered, also checking whether the relevant
controllers are in holiday mode.

Setting 1. Press the operating line selection buttons to select operating line 123.
2. Press the + / buttons to select the required assignment.
Setting range Unit Factory setting

0...2 Increment 2

Effect Depending on the selection made, the d.h.w. will be heated for the following
consumers:
0 For the local consumer only (RVA47.320)

1 For all consumers (controllers) in the same segment

2 For all consumers (controllers) in the LPB system

In the case of d.h.w. heating according to the heating circuit time switch program
(operating line 121, setting 1), the time switch programs are used from the appropriate
range for the release of d.h.w. heating at the nominal temperature setpoint, based on
the consumers selected here.
With all settings (operating line 121, setting 0 - 2), it is checked whether the controllers
of the selected range are in holiday mode. Controllers in holiday mode will not be
considered for d.h.w. heating.

 Important If all controllers in the selected range are in holiday mode, d.h.w. heating will not be
released. Only the frost protection function will remain active (function with no setting).

4.40 Number of d.h.w. charging cycles

Benefit Choice of one or several d.h.w. charging cycles


Forward shift of release matched to the number of d.h.w. charging cycles

Description With this setting, d.h.w. heating can be reduced to one charging cycle per day. The
forward shift of d.h.w. heating against the range selected on operating line 123 will be
appropriately adjusted.

Note This setting is effective only if, on operating line 121, setting 1 (according to the heating
circuit time switch program(s)) has been selected.

Setting 1. Press the operating line selection buttons to select operating line 124.
2. Press the + / - buttons to select the type of d.h.w. heating.

Setting range Unit Factory setting

0...1 Increment 1

88/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Effect According to the selection made, the controller releases d.h.w. heating either once or
several times per day and adjusts the forward shift accordingly.

Setting Charging / day Forward shift


0 One 2.5 hours
1 Several 1 hourStunde

4.40.1 Once per day with a forward shift of 2.5 hours


Setting 0

The number of daily releases for d.h.w. heating at the nominal temperature setpoint is
limited to one. Also with this setting, the switch-on point is shifted forward by 2.5 hours
against the range selected on line 123.

On days where space heating at the nominal room temperature setpoint is provided for
24 hours, d.h.w. heating is released at midnight for 2.5 hours.

4.40.2 Several times per day with a forward shift of 1 hour


Setting 1

The number of d.h.w. charging cycles will not be limited. Also with this setting, the
switch-on point is shifted forward by one hour against the range selected on line 123.

4.41 Type of d.h.w. demand

Benefit Possibility of using a d.h.w. storage tanks equipped with a control thermostat

Description Defines the type of d.h.w. control (via d.h.w. sensor or control thermostat).

 Note Setting of this function has an impact on automatic generation of the type of plant.
Operating line 53.

Setting 1. Press the operating line selection buttons to select operating line 125.
2. Press the + / - buttons to select the type of d.h.w. demand.

Setting range Unit Factory setting

0/1 Increment 0

Effect By making this setting, the controller takes into account the signal fed to it by the d.h.w.
sensor connected to terminal B3.
Entry:
0: Sensor: the temperature measured with the sensor connected to terminal B3 is
used for the control of the d.h.w. temperature.
1: Control thermostat: the switching status of the control thermostat connected to
terminal B3 is used for the control of the d.h.w. temperature.

89/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
 Important The contacts of the control thermostat must be suited for extra low voltage (gold-
plated)!

Difference When using a d.h.w. sensor:


The controller calculates the switching points with the respective switching differential
as a function of the d.h.w. temperature setpoint entered.

Sensor / line with a short- = fault message


Sensor value available = d.h.w. according to the current setpoint
Sensor / line with a short- = no d.h.w.

When using a d.h.w. control thermostat:


The controller takes into consideration the switching statuses of the control thermostat.

Line / terminal with short-circuit = d.h.w. charging ON


Line / terminal with open-circuit = d.h.w charging OFF
Contact resistance too high = error message from the thermostat

 Note When using a d.h.w. control thermostat, reduced operation is not possible.

Important when using a The nominal d.h.w. temperature setpoint (operating line 13) must be equal to or
d.h.w. thermostat higher than the setpoint adjusted on the control thermostat (thermostat is calibrated
at switch-off point)
Boost of the flow temperature setpoint (setting on operating line 126) must be
minimum of 10 C (has an impact on the charging time)
In that case, frost protection for d.h.w. is not ensured

D.h.w. control thermostat


(example) 70 C TBWw + UEBW

UEBW >= 10 C
60 C TBWw
T > 0 C
56 C
TRw
2371Z36

SD = 6 C
50 C TRw - SD

UEBW = Boost of the temperature setpoint (setting 126)


TBWw = Nominal setpoint of the d.h.w. temperature (setting on operating line 13)
TRW - SD = setpoint of the thermostat minus the switching differential
TRw = setpoint of the thermostat (point of calibration)

4.42 Boost of the flow temperature setpoint for


d.h.w.

Benefit Efficient d.h.w. heating

Description To allow the d.h.w. to be heated up, the boiler temperature must be higher than the
d.h.w. setpoint.

90/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Setting 1. Press the operating line selection buttons to select line 126.
2. Press the + / - buttons to adjust the setpoint boost.

Setting range Unit Factory setting

0...30 C (K) 16

Effect The setting will raise the boiler temperature setpoint when there is demand for d.h.w.
Increase: Heating up time will become shorter
More overshoot

Decrease: Heating up time will become longer


Less overshoot

boiler boost Using the two settings, the controller generates the boiler temperature setpoint for
d.h.w. heating.

Setting on operating line Nominal d.h.w. temperature setpoint


13
Setting on operating line Boost
126
Total Boiler temperature setpoint

 Note For d.h.w. control, refer to section "Switching differential of d.h.w. temperature (line 41
OEM).

4.43 D.h.w. priority

Benefit Optimum allocation of boilers' heat output

Description Defines the priority of d.h.w. heating over space heating.

Setting 1. Press the operating line selection buttons to select line 127.
2. Press the + / - buttons to select the type of d.h.w. priority.

Setting range Unit Factory setting

0...3 Increment 1

Effect During d.h.w. heating, space heating will be restricted, depending on the setting made.
Entry:
0 Absolute priority
The controller-internal heating circuit and the heating circuits of other controllers
connected to the LPB will be locked until the d.h.w. is heated up. The system
pump remains in operation.

1 Shifting priority If the capacity of the heat generating equipment is no longer


sufficient, the amount of heat supplied to the heating circuits will be restricted
until d.h.w. heating is terminated.

2 No priority: D.h.w. heating and space heating at the same time.

91/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
In the case of tightly sized boilers and mixing heating circuits, the setpoint may
not be reached if the heating load is great, since too much heat is required for
space heating.

3 Shifting / absolute priority


If the capacity of the heat source is no longer sufficient, the mixing heating
circuits will be restricted until d.h.w. heating is terminated. The pump heating
circuits will be locked until d,h.w. is heated up.

Frost protection for the Frost protection for the plant is fully active only in the case of setting 2. With setting 0 or
plant 1, it will be partly or fully restricted. If the boiler is correctly sized, frost protection for the
plant is also ensured when using setting 1. In the case of plants where there is a
considerable risk of frost (e.g. plants with outdoor heating), setting 0 should not be
used.

4.43.1 Shifting priority

The purpose of the function "Shifting priority" is to achieve optimum d.h.w. heating. This
means that during d.h.w. heating, the actual boiler temperature should be as close as
possible to the boiler temperature setpoint without shutting down the burner. To
achieve this, it may be necessary to restrict the heating circuits by means of a locking
signal. The signal is generated by a temperature-time integral.
Depending on the consumer, the locking signal will lead to switching on / off or a
setpoint reduction.

Impact on 2-position Cycling or deactivation of the pumps will reduce the amount of heat drawn from the
loads heat source. This will considerably shorten the time required for heating up the d.h.w.
Heating circuit pump:
Status Effect
Locking signal < 20 % Normal pump operation
Locking signal > 20 % Heating circuit pump cycles
Locking signal > 93 % Heating circuit pump OFF

D.h.w. pump or boiler pump:


No effect

Switching point Through the generation of the temperature-time integral it is not only the period of time
that is considered, but also the extent of the undershoot. This means that when the
crossing is significant, the pumps will be deactivated earlier.

Impact on modulating The consumption of heat is considerably reduced through the reduction of the flow
loads temperature setpoints. This reduces considerably the heating up time for d.h.w., with a
minimum impact on the heating circuits.
Mixing valve:

Status Effect
Locking signal > 0 % Flow temperature setpoints will be lowered.
The extent of lowering is dependent on the magnitude and the period of
time of the undershoot.

Locking signal reduced to Setpoints according to the normal control condition


0%

setpoint reduction Through the generation of the temperature-time integral it is not only the period of time
that is considered, but also the extent of the undershoot. This means that when the
undershoot is significant, the setpoint reduction will be greater.

92/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Temperature-time This temperature-time integral generates the locking signal for restricting the heating
integral circuits.
When generating the locking signal, one of four different procedures is used:

Diagram Procedure
a to b Within a foreseeable period of time, the actual value of the boiler
temperature (TKx) will no longer be within the switching differential of
the boiler temperature setpoint.
 Locking signal will be increased
b to c and Within a foreseeable period of time, the actual boiler temperature (TKx)
d to e will lie within the switching differential of the boiler temperature setpoint.
 Locking signal will remain at a constant level
c to d and Within a foreseeable period of time, the actual boiler temperature (TKx)
e to f will lie above TKw.
 Locking signal will be decreased
f The actual boiler temperature (TKx) exceeds the boiler temperature
setpoint.
 Locking signal will be set to 0 %.

Example:
TK SDK

TKw

2378Z11
TKx

x%

0% t
a b c d e f

a Start of d.h.w. heating


TK Boiler temperature
TKw Boiler temperature setpoint
TKx Actual value of the boiler temperature
SDK Boilers switching differential (factory setting 8K)
t Time
Y Locking signal

93/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.44 Demand for heat with reduced d.h.w.
setpoint

Benefit Selectable type of heat demand with reduced d.h.w. setpoint

Description In connection with alternative sources of energy, an early release of heat generation
(BMUs) for d.h.w. heating outside the main occupancy times is often undesirable. A
choice of two different procedures is available releasing the cascade earlier or later.

Setting 1. Press the operating line selection buttons to select operating line 129.
2. Press the + / - buttons to select the required assignment.

Setting range Unit Factory setting

0/1 - 1

Effect The setting determines whether or not heat generation will be released for maintaining
the reduced d.h.w. setpoint:

No (use with buffer storage tank and alternative heat source).


Outside the main occupancy hours, the attempt is made to bring the d.h.w.
temperature to the reduced setpoint level using energy from the buffer storage
tank. This means that the d.h.w. charging pump runs but the demand for heat
will be suppressed. Heat generation for d.h.w. charging will be released only
(d.h.w. push) when the d.h.w. temperature has dropped below the reduced
setpoint by twice the d.h.w. switching differential (41OEM).

Yes (standard procedure).


Outside the main occupancy hours, the d.h.w. temperature is raised to the level
of the reduced setpoint. This is accomplished by sensing a heat demand signal
to the heat source (individual boiler or cascade).

94/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Cascade settings
4.45 Changeover of boiler sequence in a
cascade

Benefit Even wear and tear of the boilers in a cascade, or


Selectable fixed switching on / off sequence
Different time intervals for changeover of boiler sequence can be set
Description The parameter determines whether or not the switching on / off sequence of the boilers
shall be changed after an adjustable period of time.

Setting 1. Press the operating line selection buttons to select operating line 130.
2. Press the + / buttons to select --- or enter the number of operating hours after
which changeover of boiler sequence shall take place.
Setting range Unit Factory setting

--- / 10...990 - / hours 500

Effect --- Fixed switching on / off sequence of the boilers in the cascade. The lead
boiler can be freely selected (refer to operating line 132); the other boilers
are switched on and off in the order of the device addresses /
subaddresses.

10...990 On completion of the number of operating hours set here, the switching
sequence of the boilers in the cascade will change. This means that the
boiler with the next higher device address will become the lead boiler.

Example: Example of four boilers with a set differential of 100 operating hours.

1st changeover 2nd changeover 3rd changeover 4th changeover


P [kW]

BMU 4 BMU 1 BMU 2 BMU 3

BMU 3 BMU 4 BMU 1 BMU 2 Lag boiler

BMU 2 BMU 3 BMU 4 BMU 1

BMU 1 BMU 2 BMU 3 BMU 4 lead boiler


2379Z07

100 200 300 400 t [h]

t = Total number of operating hours of all lead boilers [h]


P= Total output of cascade [kW]

95/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.46 Exemption from automatic changeover of
the boiler sequence

Benefit Individual boilers can be exempted from automatic changeover

Description Use this function if you want to operate a certain boiler as the first and / or last boiler of
the switching on sequence.

Setting 1. Press the operating line selection buttons to select line 131.
2. Press the + / button to enter the boiler(s) to be exempted from automatic
changeover.

Setting range Unit Factory setting

0...3 - 0

 Important Setting this parameter has an effect only if, on operating line Changeover of boiler
sequence in a cascade (line 130), setting Automatic changeover according to the
number of operating hours (10...990 h) has been selected.

Effect Depending on the selected setting, the respective boiler will be exempted from
automatic changeover of the boiler sequence.
Entry:

0 No exemption.
The switching on sequence of the boilers will change on completion of the number
of operating hours set (line 130).
1 The first boiler is exempted.
The first boiler in the addressing scheme always remains the lead boiler. With the
other boilers, the switching on sequence changes when the set number of
operating hours have elapsed (line 130).
2 The last boiler is exempted.
The last boiler in the addressing scheme always remains the last boiler. The other
boilers will be switched over on completion of the number of operating hours set
(line 130).
3 The first and the last boiler are exempted.
The first boiler in the addressing scheme always remains the lead boiler. the last
boiler in the addressing scheme always remains the last boiler. The boilers in
between will be switched over on completion of the number of operating hours set
(line 130).

 Note The boiler sequence is to be determined on operating lines Device address (line 140)
and Segment address (line 141).

96/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.47 Lead boiler with a fixed changeover of the
boiler sequence

Benefit Lead boiler of the cascade with a fixed changeover of the boiler sequence can be
freely selected
Better adjustment to the plants demand profile by selecting a suitable type of boiler
as the lead boiler
Description With a fixed changeover of the boiler sequence (refer to operating line 130), the lead
boiler can be freely selected.

Setting 1. Press the operating line selection buttons to select operating line 132.
2. Press the + / - buttons to select the required lead boiler.
Setting range Unit Factory setting

00.1...16.3 - -

Effect The boiler defined as the lead boiler is always the first boiler to be switched on and the
last to be switched off. The other boilers are switched on and off in accordance with the
order of the device addresses / device subaddresses.
For example, display 1.1 means that device 1 (in segment 0), device subaddress 1
(BMU 1), is the selected lead boiler.

 Note All cascade boilers must be in segment 0 so that the heat demand signals from all
segments can be acquired. For more detailed information about the device address /
device subaddress, refer to Local Process Bus (LPB), Basic Documentation, System
Engineering (document no. CE1P2370E).

 Important This setting has an effect only if function "Changeover of boiler sequence in cascades"
(operating line 130) is set to --- = fixed switching on / off sequence.

97/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.48 Switch-on delay lag boilers

Benefit Smooth operation due to stable operating conditions


Adjustable rate of release of total capacity

Description After a BMU has switched on, an adjustable period of time must elapse until another
BMU can be switched on.

Setting 1. Press the operating line selection buttons to select operating line 133.
2. Press the + / - buttons to enter the number of minutes on completion of which
another BMU can be switched on.
Setting range Unit Factory setting

1...120 Minutes 5

Effect For stability reasons, each BMU added to the cascade will first run in its basic stage for
about one minute. This minute is already contained in the adjusted switch-on delay.
Correct adjustment of the switch-on delay ensures that plant operating conditions will
be stable. This prevents frequent cycling of the BMUs.

Note The function is only active with "Serial 2" (setting on line OEM 61 = 0)

4.49 Restart lock of BMUs

Benefit Too frequent switching on / off cycles of the BMUs will be avoided

Description A BMU that has just been switched off can be switched on again only after an
adjustable period of time has elapsed.

Setting 1. Press the operating line selection buttons to select operating line 134.
2. Press the + / - buttons to enter the number of minutes on completion of which a
switched off BMU can be switched on again.
Setting range Unit Factory setting

0...1800 Seconds 300

Effect The restart lock ensures that a BMU that has just been switched off will not be switched
on again a short time later. The BMU will be released again only after the adjusted
period of time has elapsed. This prevents frequent cycling of the BMUs and ensures
that plant conditions will be more stable.

98/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
LPB / system
Benefit Creation of systems
Wide field of use with a smaller number of unit versions
Plants can be extended in a straightforward manner

Description The LPB is used as a communication basis for generating a system with additional
ALBATROS controllers or controllers of other manufacture.

4.50 LPB device address


Description The device address and the segment address are used as destinations in the bus
system (similar to a postal address). To ensure communication, each device must be
correctly addressed.

Setting 1. Press the operating line selection buttons to select operating line 140.
2. Press the + / - buttons to enter the device number.

Setting range Unit Factory setting

0...16 Increment 1

Effect Entry of the device address is especially important when using combinations of units, or
in a system. The addresses classify the controllers within a segment.
Entry:

Address Effect Example


0 Standalone Single controllers

1 Master (LPB) Controllers with master function


Cascade master
Heat generation master
Consumer master in the respective segment

2...16 Slave (LPB) Controllers with slave function


Other heat generation controller
Heating circuit controller
D.h.w. controller

Device address The device addresses should be assigned in consecutive order in accordance with the
controllers connected. It is not permitted to assign an address several times within a
bus segment, since this would lead to communication errors. Each segment must have
a device as a master (address 1).

 Note For more detailed information about the addressing of devices in a system, refer to
Local Process Bus (LPB), Basic Documentation, System Engineering (document no.
CE1P2370E).

99/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.51 LPB segment address
Description The segment address and the device address are used as destinations in the bus
system (similar to a postal address). To ensure communication, each device must be
correctly addressed.

Setting 1. Press the operating line selection buttons to select operating line 141.
2. Press the + / - buttons to enter the segment address.
Setting range Unit Factory setting

0...14 Increment 0

Effect Entry of the segment address is especially important when used in a system. With this
setting, the system can be subdivided into a number of segments.
Entry:
0 Heat generation segment

1...14 Heat consumer segment

Segment number A bus segment is comprised of a number of devices that are used in the same place of
application. All devices in a segment must carry the same segment address.

 Note For more detailed information about the addressing of devices in a system, refer to
Local Process Bus (LPB), Basic Documentation, System Engineering (document no.
CE1P2370E).

4.52 LPB power supply


Benefit A central bus power supply is not required in systems with up to 16 devices
Straightforward extension of systems

Description The bus power supply via the controllers enables the bus system to be powered directly
by the individual controllers (no central bus power supply).

Setting 1. Press the operating line selection buttons to select operating line 142.
2. Press the + / - buttons to select the type of bus power supply.
Setting range Unit Factory setting

0/1 Increment 1

Effect Entry:
0 Off
No bus power supply via the controller.

1 Automatically
The bus power supply (LPB) via the controller is automatically switched on and
off depending on the requirements of the LPB.

 Note The actual status of the power supply is shown on operating line 143.

Bus power supply The bus system (LPB) can be powered either via the individual controller bus power
supplies or via a central bus power supply.

100/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
 Note For more detailed information about the bus power supply and its engineering, refer to
Local Process Bus (LPB), Basic Documentation, System Engineering (document no.
CE1P2370E).

4.53 Displaying the LPB power supply

Benefit Overview of operational status of the bus power supply via controllers

Description The display shows whether the controller currently powers the bus (LPB).

Setting 1. Press the operating line selection buttons to select operating line 143.
2. No setting can be made with the + / - buttons.
Display Unit

ON / OFF -

Effect The status of the bus power supply via controllers will automatically be displayed on
this operating line.
Display:
ON The bus power supply via controllers is currently active.
At the moment, the controller supplies some of the power required by the bus.

OFF The bus power supply via controllers is currently inactive.

Bus power supply Power supply to the bus can be accomplished in different ways. The respective setting
is made on operating line 142.

4.54 Displaying the LPB communication

Benefit Overview of communication status of bus (LPB)

Description Indicates whether communication on the LPB is currently active.

Setting 1. Press the operating line selection buttons to select operating line 144.
2. No setting can be made with the + / - buttons.
Display Unit

ON / OFF -

Effect The status of the BUS communication will automatically be displayed on this line.
Display ON Communication active
The controller communicates with another controller via the LPB.

OFF Communication inactive

101/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.55 Range of action of central changeover

Benefit The range of action of the central changeover actions can be defined

Description Function for defining the range of action of central changeover.

Setting 1. Press the operating line selection buttons to select operating line 145.
2. Press the + / - buttons to select the required range of action of changeover.
Setting range Unit Factory setting

0/1 Increment 1

Effect The range of action can be defined for the central changeover actions Changeover of
operating mode, Summer / winter changeover and Standby. The range of action
can be defined by making the following settings:

0 Changeover takes place with all controllers in the same segment.

1 Changeover takes place with all controllers in the entire system (LPB).

 Note The setting is of importance only if the controller is defined as the master and located in
segment 0 (address 0/1). With any other addressing, it has no effect.

4.56 Automatic summer / winter changeover

Benefit Makes possible a uniform changeover of all heating circuits in the selected range of
action

Description Summer / winter changeover of the selected range of action takes place when the
changeover temperature set on operating line 16 is reached.

Setting 1. Press the operating line selection buttons to select operating line 146.
2. Press the + / - buttons to select the effect of automatic summer / winter changeover.
Setting range Unit Factory setting

0/1 Increment 0

Effect The setting will change the effect of summer / winter changeover:
Entry:
0 Local effect
Automatic summer / winter changeover switches the local heating circuit on and
off.

1 Central effect
Either the heating circuits of the segment or those of the entire system are
switched on and off by automatic summer / winter changeover, depending on the
setting made on operating line Range of action of central changeover.

 Important Setting 1 (central effect) is active only if the controller has been defined as a master
controller (setting on line 140 = 1).

102/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.57 Central standby switch

Benefit Central operation of the interconnected system

Description From the master controller, the entire heating system can be switched to standby.

Setting 1. Press the operating line selection buttons to select operating line 147.
2. Press the + / - buttons to select central standby switching.
Setting range Unit Factory setting

0/1 Increment 0

 Important Setting 1 (central effect) is active only if the controller has been defined as a master
controller (setting on line 140 = 1).

Effect Entry:
0 Central standby switching is deactivated

1 Central standby switching is activated

 Important If central standby on the master controller is switched on, it can only be switched off
again from that controller!

D.h.w. The central standby circuit does not affect d.h.w. heating. This means that the d.h.w. is
heated according to the settings made.

Display If the function is activated from the master controller, the operating mode buttons of
all affected controllers in the segment or system will flash.

4.58 Clock mode

Benefit Straightforward time synchronization of the controllers in the system

Description Clock operation is an important setting for time synchronization if several controllers are
interconnected to form one system.

Setting 1. Press the operating line selection buttons to select operating line 148.
2. Press the + / - buttons to select clock mode.
Setting range Unit Factory setting

0...3 Increment 3

 Important For time adjustment of the controllers connected to the system, one device per system
must be set as a system lock (setting 3).

Effect The setting will change the effect of the system time on the controller's time setting
(settings on operating lines 1 to 2).
Entry:

103/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
0 Autonomous clock
The clock time on the unit can be adjusted Adjustment

The controller's clock time will not be matched to the


Controller time System time
system time

1 System time
The clock time on the unit cannot be adjusted Adjustment

The controller's clock time will automatically and


Controller time System time
continuously be matched to the system time

2 System time with adjustment


The clock time on the unit can be adjusted and, at Adjustment
the same time, adjusts the system time since the
change will be adopted by the master Controller time System time

The controller's clock time is still automatically and


continuously matched to the system time

3 System clock (master)


The clock time on the unit can be adjusted and, at Adjustment
the same time, adjusts the system time
Controller time System time
The controller's time is used for the system

4.59 Winter- / summertime changeover

Benefit Automatic changeover of the yearly clock to summertime.

International standards In accordance with present international standards, the change from wintertime to
summertime takes place on the last Sunday in March. The standard setting of the
controller complies with this rule since that Sunday lies between the standard setting
and the last day of the relevant month. With this setting, the day of changeover can be
matched to changing standards.

Description On the Sunday following that date, the controllers time of day will switch over to
summertime.
For that purpose, the time of day is shifted forward by one hour.

Setting Setting range Unit Factory setting

01.01...31.12. tt.MM 25.03.

104/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.60 Summer- / wintertime changeover

Benefit Automatic changeover of the yearly clock to wintertime.

International standards In accordance with present international standards, the change from summertime to
wintertime takes place on the last Sunday in October. The standard setting of the
controller complies with this rule since that Sunday lies between the standard setting
and the last day of the relevant month. With this setting, the day of changeover can be
matched to changing standards.

Description On the Sunday following that date, the controllers time of day will switch over to
wintertime.
For that purpose, the time of day is shifted backward by one hour.

Setting Setting range Unit Factory setting

01.01...31.12. tt.MM 25.10.

105/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Input H1 .
4.61 Input H1

Benefit Changeover of operating mode via telephone (e.g. in a holiday house)


Minimum demand for heat
Heat generation lock
Demand for heat

Description Terminal H1 is an input that provides different functions, depending on the selected
setting.

Setting 1. Press the operating line selection buttons to select operating line 170.
2. Press the + / - buttons to select the required function.
Setting range Unit Factory setting

0...4 Increment 0

Effect With this setting, the function of terminal H1 can be changed. The selected function will
be activated when the potential-free contact connected to terminal H1 closes or when
an analog voltage signal of DC 0...10 V is transmitted.
Entry:
0 Changeover of operating mode (remote telephone switch) for heating circuit
and d.h.w.: The operating mode is changed when the contact closes

1 Changeover of operating mode (remote telephone switch) for heating circuit


only: The operating mode is changed when the contact closes

2 Minimum setpoint of flow temperature, contact H1


The "Minimum setpoint of flow temperature contact H1" set on operating line 171
will be activated when the contact closes.
3 Heat generation lock
The heat sources will be locked when the contact closes.

4 Demand for heat


The demand for heat (between 0 and 130 C) is delivered to the heat sources in
the form of a voltage signal.

 Note When using terminal H1 as a contact (settings 0 -3), several switches can be
connected in parallel. The function will be activated when one or several contacts
close(s), depending on the selected setting.
When using terminal H1 as a voltage input (setting 4), it is not possible to connect
several signals in parallel.
When 2 heat demand signals are received at the same time, one via contact H1
(settings 2 + 4) and another (LPB, d.h.w. or controller internally), the highest of them
will be selected. Exception D.h.w. cannot be boosted by another heat requisition.

 Important The relay contacts must be suited for use with extra low voltage (gold-plated).

106/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.61.1 Changeover of operating mode (remote telephone
switch) - Setting 0 / 1

Description A remote telephone switch is a potential-free relay contact, e.g. in the form of a modem,
which can be switched by making a phone call plus dialing a code.

The operating mode is changed when the contact connected to terminal H1 (e.g. a
remote telephone switch) closes. In that case, the LEDs in the operating mode buttons
and will flash.
D.h.w. Whether or not d.h.w. heating takes place when the remote telephone switch is
activated depends on the setting made:

Setting 0: D.h.w. heating is locked when changeover is activated.


Setting 1: D.h.w. heating remains released when changeover is activated.

Effect Activation of this function will produce different actions, depending on the function of
the controller within the LPB system (also refer to Local Process Bus (LPB), Basic
Documentation, System Engineering, document no. CE1P2370E).

The effect depends on the setting made on operating line 145.

Changeover of system Changeover of all controllers in the entire LPB system

Prerequisite: Operating line 145 must be set to 1 (range of action = entire


system)
The contact must be connected to the master controller in
segment 0
Possible address: Device address 1 (line 140)
Segment address 0 (operating line 141)

Effect: All controllers in the system switch to operating mode


With setting 0, d.h.w. heating is switched off in the entire system;
with setting 1, it is released in the entire system
With all controllers, operating mode changeover with the buttons is
no longer possible
When the contact of the remote telephone switch opens, all
controllers will return to the operating mode selected last

Check: Buttons or + flash on all controllers in the system 1)

1)
With setting 0 as selected above (d.h.w. heating locked), the two buttons and
will flash.
With setting 1 as selected above (d.h.w. heating remains released), only operating
mode button will flash.

107/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
Changeover of segment Changeover of all controllers in the same segment

Prerequisite: With segment 0, setting 0 must be made on operating line 145


(range of action of segment); with the other segments, the setting
on operating line 145 has no impact.
The contact must be connected to the master controller in
segments 0 to 14
Possible addresses: Device address 1 (line 140)
Segment address 0...14 (operating line 141)

Effect: All controllers in the same segment switch to operating mode


With setting 0, d.h.w. heating is switched off in the entire segment;
with setting 1, it is released in the entire segment
With all controllers in the same segment, operating mode
changeover with the buttons is no longer possible
When the contact of the remote telephone switch opens, all
controllers will return to the operating mode selected last

Check: Buttons or + flash on all controllers in the same segment


1)

1)
With setting 0 as selected above (d.h.w. heating locked), the two buttons and
will flash.
With setting 1 as selected above (d.h.w. heating remains released), only operating
mode button will flash.

4.61.2 Minimum setpoint of flow temperature contact H1


see operating line 171 - Setting 2

4.61.3 Heat generation lock - Setting 3

BMU on PPS The heat sources connected to the PPS will be locked when contact H1 closes (e.g. via
ripple control).
All heat demand signals from the heating circuits connected to LPB and from the d.h.w.
storage tank connected to the RVA47.320 will be ignored while frost protection for the
boiler will remain ensured.
However, a local d.h.w. storage tank connected directly to the BMU can still trigger
d.h.w. heating.
Chimney sweep function The chimney sweep function can be activated directly on the BMU although the heat
generation lock is switched on.

BMU on LPB All at LPB connected heat generations are not applied from the heat generation lock.
The setting for this function must be made at the BMU.

108/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.61.4 Demand for heat - Setting 4

External consumers can transmit a demand for heat in the form of an analog signal of
DC 0...10 V. The RVA47.320 converts this voltage signal to a temperature setpoint of
0...130 C and considers this value when generating the setpoint of the cascade.

T = 110C

T = 130C
T = 50C

T = 70C

T = 90C
S = 5C
[v]

10

2379Z26
8

0
10 20 30 40 50 60 70 80 90 100 110 120 130 [c]

T = maximum value of heat demand


S = minimum limitation of heat demand = 5 C

The setpoint for 10 V can be set with parameter Maximum value of heat demand
(operating line 172, setting range 5...130 C). The voltage corresponding to the
displayed temperature can then be calculated as follows:

10 [V] * " actual temperatur e" [C]


[V] =
" Maximum value of heat demand" [C]

109/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.62 Minimum setpoint of flow temperature
contact H1

Benefit Handling of heat demand signals from units incompatible with LPB
Temporary startup of boiler via switching contact

Description Function for setting the temperature at which the cascade or the boiler is maintained
when contact H1 is closed.

 Important This setting has an effect only if on operating line 170 Input H1 setting 1 "Minimum
setpoint of flow temperature contact H1" has been selected.

Setting 1. Press the operating line selection buttons to select operating line 171.
2. Press the + / buttons to set the required value of the "Minimum setpoint of flow
temperature contact H1".
Setting range Unit Factory setting

8...TKmax C 70

...TKmax Maximum limitation of BMU setpoint, operating line 2 OEM.

Effect Function "Minimum setpoint of flow temperature contact H1" selected on operating line
170 will be activated when contact H1 closes. The heat source or the cascade will
maintain the temperature level set here until either contact H1 reopens or more heat is
demanded.

 Notes If several heat demand signals are received at the same time (LPB, contact H1, d.h.w.,
or from the controller itself), the highest of them will automatically be selected.

If the demand for heat is so small that a single BMU running on its basic stage still
produces too much heat, it will start cycling within the switching differential set on it.
Otherwise, the required output will be provided through modulation of the burner.

TK
C
80 TKw

70

60
TVHw
50
2379Z20

40

0
30
30 20 10 0 -10 C TA gem

TVHw Minimum setpoint of the flow temperature, contact H1

TKw Boiler temperature setpoint

110/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
4.63 Maximum value of heat demand signal DC
0...10 V (H1)

Benefit Adjustable temperature range for heat demand signal via input H1
Can be matched to the voltage outputs of devices of other manufacture

Description The parameter determines which temperature the maximum voltage of the setting
Heat demand via H1 (operating line 170, setting 4) corresponds to.

 Important This setting is active only if on operating line 170 (input H1) setting 4 Heat demand DC
010 V has been selected.

Setting 1. Press the operating line selection buttons to select operating line 172.
2. Press the + / buttons to set the required Maximum value of the heat demand
signal.
Setting range Unit Factory setting

5...130 C 100

Effect This setting defines the temperature corresponding to 10 V of the setting Heat demand
via H1 (operating line 170, setting 4).
Based on this temperature, the controller converts the heat demand voltage signal to a
temperature.

4.64 Operating action of the contact connected


to H1

Benefit The operating action of the contact can be matched to the type of output signal
delivered by a device of other manufacture
More flexibility when selecting non-Landis & Staefa products (both operating
actions can be considered)

Description This function enables the operating action of contact H1 to be matched to the operating
action of a device of other manufacture.

Setting 1. Press the operating line selection buttons to select operating line 173.
2. Press the + / - buttons to select the operating action of contact H1.
Setting range Unit Factory setting

0...1 - 1

Entry:
0 The contact is a N.C. contact, which means that it is normally closed and opened
only when the third party device delivers a signal.
1 The contact is a N.O. contact, which means that it is normally open and closed
only when the third party device delivers a signal.

 Note If input H1 is used for a heat demand signal (line 170, setting 4), this setting will have
no effect.

111/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the heating engineer settings 15.07.2002
5 Description of the OEM settings

Heat generation values

5.1 Minimum limitation of the boiler


temperature setpoint OEM (TKminOEM)

Benefit Minimum limitation of the boiler temperature setpoint

Description This function provides minimum limitation of the boiler temperature setpoint.

Setting 1. Press the line selection buttons to select operating line 1OEM.
2. Press the + / - buttons to set the minimum limitation of the boiler temperature.

Setting range Unit Factory setting

8...95 C 8

Effect The setting ensures minimum limitation of the boiler temperature setpoint which can be
adjusted on line 90 (TKmin).

5.2 Maximum limitation of the boiler


temperature setpoint

Benefit Maximum limitation of the boiler temperature setpoint.


Preset temperature for manual operation.

Description Maximum limitation of the boiler temperature setpoint and delivery of the flow
temperature setpoint for the cascade in manual operation.

Setting 1. Press the line selection buttons to select line 2OEM.


2. Press the + / - buttons to set the maximum limitation of the boiler temperature
setpoint.

Setting range Unit Factory setting

8...120 C 80

Effect This setting provides maximum limitation of the boiler and cascade flow temperature
setpoint. The boilers controlled by the BMUs are operated at a temperature no higher
than the adjusted temperature, even if the consumers call for more heat.
In manual operation, the value set is used directly as the flow temperature setpoint.
The boilers controlled by the BMUs are operated at this temperature.

112/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
5.3 Pump overrun time

Benefit Protects the boiler against overtemperatures


Use of residual heat in the boiler.

Description Overrun of the primary, heating circuit and d.h.w. charging pump ensures that residual
heat will be carried away from the pressureless header. This makes certain that the
boiler pump controlled by the BMU will be able to draw the residual heat from the boiler,
thus avoiding boiler overtemperatures and preventing the manual reset safety limit
thermostat from cutting out.

Setting 1. Press the line selection buttons to select line 8OEM.


2. Press the + / - buttons to set the pump overrun time.

Setting range Unit Factory setting

0...20 min 5

Effect All pumps that, at the time of burner shutdown of the last boiler, were operating,
continue to run for the period of time set here. At the same time, the previous flow
temperature setpoint remains valid, allowing the mixing valves of the controllers
connected to LPB to stay open.
Example HK

t
Q

ON

OFF
t
tPN
Y

TVNw
2373Z28

TVRw
t

HK Operating mode
Nominal operation
Q Pumps
Y External mixing valve (via LPB) Reduced operation
TVNw Nominal flow temperature setpoint
TVRw Reduced flow temperature setpoint tPN Pump overrun time

 Note With no burner shutdown, the general pump overrun time is one minute.

5.4 Minimum limitation of the boiler return


temperature

Benefit The minimum boiler return temperature can be adjusted


The effect on the consumers can be adjusted

Description The setting defines the permitted minimum boiler return temperature.

113/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
Setting 1. Press the line selection buttons to select line 22OEM.
2. Press the + / - buttons to set the required minimum limitation of the boiler return
temperature.

Setting range Unit Factory setting

8...95 C 8

Effect If the boiler return temperature drops below the minimum limit set here, the consumers
heat c7onsumption will be restricted.

5.5 Calibration of actual output range of BMU 1-4

Benefit More accurate control through optimized signal transmission.


Calibration of the output signals delivered by the BMUs to match the actual values.

Description The output signals delivered by the BMUs can be calibrated to match the actual load.
This enhances the control performance.

Setting 1. Press the line selection buttons to select line 25OEM - 28OEM.
2. Press the + / - buttons to adjust the calibration factors.

Setting range Unit Factory setting

-100...100 - 0

In that case:
- Operating line 25 = BMU 1
- Operating line 26 = BMU 2
- Operating line 27 = BMU 3
- Operating line 28 = BMU 4

Effect The output signal delivered by the respective BMU is corrected by the adjusted factor
and then used for controller-internal calculations.
In principle, operation without the adjusted calibration factor is possible, but to achieve
the greatest possible accuracy the adjustment should be made.

Calculation Calculation of the calibration factor for the respective BMU is made based on the
following formula:

PGs
P%GS 100
PN
K% =
P%GS
1
100

Legend
K% Calibration factor [%]
P%GS Output provided on the basic stage [%]
PGS Output on the basic stage [W]
PN Nominal output [W]

 Note The value of P%GS is obtained by making a readout with the ACS69 service tool.
On the ACS69, the value is displayed on page Heat source state under the name
Actual capacity value BMU X.
The values of PGS and PN are given on the type field of the BMUs.

114/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
Heating circuit values
5.6 Gain factor of room influence (KORR)

Benefit The influence of room temperature deviations on the controlled system can be
adjusted

Note Defines the influence of room temperature setpoint deviations on the controlled system.
The room influence can be activated and deactivated (operating line 101).

Setting 1. Press the line selection buttons to select operating line 30OEM.
2. Press the + / buttons to set the gain factor.

Setting range Unit Factory setting

0...20 - 4

Effect Changing this setting has the following impact:


Entry:

Increase: Authority of room influence will increase

Decrease: Authority of room influence will decrease

Correction The value of setting 30OEM is divided by 2 and multiplied by the differential (room
temperature setpoint actual room temperature).
The result is then added to the room temperature setpoint.

30OEM
TRwk = TRw + (TRw - TRx)
2

TRw Room temperature setpoint


TRx Actual value of the room temperature
TRwk Corrected room temperature setpoint

 Note The gain factor of the room influence is only active when a room unit is connected.

115/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
5.7 Constant for quick setback (KON)

Benefit Making use of the buildings thermal storage capacity.

Description Quick setback is dependent on whether or not a room temperature sensor is used. A
differentiation is made between quick setback with and without room temperature
sensor.
 Important This setting is active only if no room sensor is used.

Setting 1. Press the line selection buttons to select line 31OEM.


2. Press the + / buttons to set the constant.

Setting range Unit Factory setting

0...20 - 2

Effect The duration of quick setback will be changed.


Entry:

Increase: Setback time will become longer


For well insulated buildings that cool down slowly

Decrease: Setback time will become shorter


For poorly insulated buildings that cool down rather quickly

Quick setback without Quick setback is started as soon as a change to a lower room temperature setpoint
room temperature takes place (e.g. switching times in automatic mode).
sensor During quick setback, the heating circuit pump will be deactivated and no heat demand
signal delivered.
Exception Due to frost protection for the plant, the heating circuit pump can be
activated however in spite of quick setback.

The quick setback time is generated based on setting 31OEM , the composite outside
temperature in the room temperature setpoint step. It is limited to a maximum of 15
hours.

Example The example applies to a setpoint step change of 4 C (e.g. TRw from 20 to 16 C):

TAgem Setting 31OEM


0 4 8 12 15 20
- 20 0 0 0 0 0 0
- 10 0 0.5 1 1.5 2 2.5
0 0 3 6 9 11 15
+10 0 5 11 15 (16.5) 15 (21) 15 (27)
Values in hours

 Note If a room sensor is connected, the quick setback time will not be generated from this
setting. For details, refer to section "Quick setback with room temperature sensor
(Chapter 6, Functions with no settings).

116/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
5.8 Boost of room temperature setpoint

Benefit Reduction of the rooms heating up time

 Note Boosts the room temperature setpoint temporarily, aimed at achieving shorter heating
up times for the room. This setting is active only if a room temperature sensor is used.

Setting 1. Press the line selection buttons to select line 32OEM.


2. Press the + / buttons to adjust the room temperature setpoint boost.

Setting range Unit Factory setting

0...20 C (K) 5

Effect The duration of boost heating will be changed.


Entry:

Increase: More setpoint boost


Heating up time will become shorter

Decrease: Less setpoint boost


Heating up time will become longer

Boost heating Boost heating is started as soon as switching to a higher room temperature setpoint
occurs (e.g. switching times in automatic mode).
The room temperature setpoint will be raised by the setting made on line 32OEM until the
room is heated up (TRw - C).
The boost produces an increase in the flow temperature setpoint.

C
TR w
20

2371D03a
15 TR x

a b
t

TRx Actual value of the room temperature 32OEM Setpoint boost


TRw Room temperature setpoint t Time

117/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
5.9 Frost protection for the plant

Benefit Protects the plant against freezing

Description When this function is activated and there is a risk of frost, the heating will automatically
switch on, thus preventing the heating plant from freezing.

 Important This function is ensured only if the plant works properly and is fully operational!

Setting 1. Press the line selection buttons to select line 33OEM.


2. Press the + / - buttons to activate or deactivate the frost protection for the plant.

Setting range Unit Factory setting

0/1 - 1

Effect Depending on the selection made, the plant will be protected by activating the pumps.
Entry:
0 Frost protection for the plant OFF
Function deactivated

1 Frost protection for the plant ON


Function activated

frost protection for the The heating circuit pump will be switched on in function of the actual outside
plant temperature, even if there is no demand for heat.

Outside temperature Pump Diagram


... -4C Continuously ON ON
-5...1.5 C ON for 10 minutes at 6-hour intervals takt
1.5 C... Continuously OFF OFF

Exception Between -4...-5C, different statuses can occur. In this temperature range, it is decisive
which situation prevailed:
If the temperature was previously higher (in the range of "takt), the pump is
switched on / off also in the range -4 to -5 C and is continuously running only when
the outside temperature is lower
If the temperature was previously lower (in the range of "ON),the pump is
continuously activated also in the range up to -4 C and is switched on / off when
the outside temperature is higher

ON

takt

OFF
2371Z30

-6 -5 -4 -3 -2 -1 0 1 2 3 4
TA C

118/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
5.10 Overtemperature protection for the pump
heating circuit

Benefit Prevents overtemperatures in the pump heating circuit


Enhances the control performance of a pump heating circuit

Description The flow temperature can be higher than that called for by the pump heating circuit
(e.g. in the case of a higher setpoint demand by another consumer). The controller
offsets the surplus energy by letting the pump cycle, thus preventing the pump heating
circuit from overheating.

Setting 1. Press the line selection buttons to select operating line 34OEM.
2. Press the + / - buttons to activate or deactivate the overtemperature protection.

Setting range Unit Factory setting

0/1 - 1

Effect The pump of the pump heating circuit will cycle in a way that the effect of too high flow
temperatures will be offset.

0 Overtemperature protection deactivated


1 Overtemperature protection activated

The cycling period is fixed at 10 min. This period of time will be broken down according
to the following on time ratio:

TVwGef TRw
On time ratio
=
TVxGed TRw

On time ratio
TVwGef Demanded flow temperature setpoint
TRw Current room temperature setpoint
TVxGed Actual value of the attenuated flow temperature
TVKx Actual value of cascade flow temperature (B10)

 Note In the case of a single boiler plant without a cascade flow temperature sensor (B10),
the boiler temperature is used in place of the actual value of the cascade flow
temperature (TVKx).

Running time Multiplication of the on time ratio by the cycling period (10 minutes) gives the number of
minutes for which the pump runs.
This means that with an on time ratio of 0.6, the pump runs for 6 minutes and is then
switched off for the remaining 4 minutes of the cycling period.

119/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
Limitations The pumps running time is set to a minimum of 3 minutes.
The pumps off time is set to a minimum of 2 minutes.
Also, the pump will be activated and deactivated at the following switching points:
Pump continuously ON TVxGed TVwGef ( 1)
Pump continuously TVwGef TRw < TVxGed
OFF

 Important The function of a room temperature sensor - if present - overrides that of the
overtemperature protection.

5.11 Heat gains

Benefit To save energy, heat gains are taken into consideration

Description This setting takes into account potential heat gains from machines, pieces of
equipment, or other constant heat sources, that might adversely affect accurate control.
The value will change when the heating curve adaption is activated.

Setting 1. Press the line selection buttons to select line 35OEM.


2. Press the + / - buttons to set the effect of heat gains.

Setting range Unit Factory setting

-2...+4 C 0

Effect The setting compensates the sum of all constant heat gains as follows:
Increase: For more compensation
In the case of significant heat sources

Decrease: For less compensation


In the case of less significant heat sources

The setting in C corresponds to the temperature differential that would result if the
room was solely heated by the heat gains.

5.12 Adaption sensitivity 1

Benefit Adaption of the heating curve as a function of the outside temperature

Description Adaption sensitivity 1 serves for calculating the adaption of the heating curve in the
temperature range 4 to 12 C (also refer to section "Adaption of heating curve, line
106).

Setting 1. Press the line selection buttons to select line 36OEM.


2. Press the + / - buttons to adjust adaption sensitivity 1.

Display Factory setting

1...15 15

120/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
The level of adaption sensitivity is automatically adapted by the controller and,
therefore, need not be manually adjusted.

Effect The heating curve in the temperature range 4 to 12 C will be differently adapted,
depending on the level of adaption sensitivity 1.
Increase: More adaption
Decrease: Less adaption

Reduction Each time a significant adaption of the heating curve between 4 and 12 C (ZAF1) has
taken place, adaption sensitivity 1 will automatically be reduced by one step. This
means that the extent of adaption and thus the readjustment of the slope and the
heating curves parallel displacement will gradually be reduced .
 Note When readjusting the slope of the heating curve (line 17), the adaption sensitivity will
automatically be reset to the factory-set value.

Diagram Refer to the next section "Adaption sensitivity 2.

 Note For more detailed information about the effects, refer to operating line Adaption of
heating curve (line 106).

5.13 Adaption sensitivity 2

Benefit Adaption of the heating curve as a function of the outside temperature

Description Adaption sensitivity 2 serves for adapting the heating curve in the temperature range
below 4 C (also refer to section "Adaption of heating curve, line 106).

Setting 1. Press the line selection buttons to select line 37OEM.


2. Press the + / buttons to adjust the adaption sensitivity.

Setting range Unit Factory setting

1...15 - 15

The level of adaption sensitivity is automatically adapted by the controller and,


therefore, need not be manually adjusted.
Effect The heating curve in the temperature range below 4 C will be adapted differently,
depending on the level of adaption sensitivity 2.
Increase: More adaption
Decrease: Less adaption
Reduction Each time a significant adaption of the heating curve below 4 C (ZAF2) has taken
place, adaption sensitivity 2 will automatically be reduced by one step. This means that
the extent of adaption and thus the readjustment of the heating curves slope will
gradually be reduced.
 Note When readjusting the slope of the heating curve (line 17), the adaption sensitivity will
automatically be reset to the factory-set value.

Diagram Example using a nominal room temperature setpoint of 20 C:

121/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
f
1

f2
0,5
f1

237 1D07
0
20 12 4 -4 -12
TAged
ZAF1 ZAF2

f Factor
f1 Factor for parallel displacement
f2 Factor for slope
TAged Attenuated outside temperature
ZAF1 Adaption sensitivity 1 (line 36OEM)
ZAF 2 Adaption sensitivity 2 (line 37OEM)

 Note For more detailed information about the effects, refer to operating line Adaption of
heating curve (line 106).

122/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
D.h.w. values
5.14 Maximum nominal setpoint of d.h.w.
temperature

Benefit Setting can be limited by the enduser


Reduced risk of scalding
Minimized proneness to lime buildup

Description Function for limiting the nominal setpoint of the d.h.w. temperature.

Setting 1. Press the line selection buttons to select line 40OEM.


2. Press the + / - buttons to adjust the nominal setpoint of the d.h.w. temperature.
Setting range Unit Factory setting

8...80 C 60

Effect The setting will ensure maximum limitation of the nominal d.h.w. temperature setpoint
(setting on line 13).

2379Z10a
0 10 20 30 40 50 60 70 80 90 100 120 130 140 C
13 Setting "Nominal setpoint of d.h.w. temperature
120 Setting "Reduced setpoint of d.h.w. temperature
40OEM Setting "Maximum nominal setpoint of d.h.w. temperature

5.15 Switching differential of the d.h.w.


temperature

Benefit Optimum frequency of d.h.w. heating

Description D.h.w. control is in the form of a two-position controller with an adjustable switching
differential.

 Note The switching differential for d.h.w. control has no impact on d.h.w. with a control
thermostat or changeover valve (via BMU).

Setting 1. Press the line selection buttons to select line 41OEM.


2. Press the + / - buttons to adjust the switching differential for d.h.w.

Setting range Unit Factory setting

0...20 C (K) 5

Effect The setting will change the switching differential of the d.h.w. temperature control.
Entry:
Increase: Switching differential will become larger
Fewer and longer heating up times, larger temperature variations

123/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
Decrease: Switching differential will become smaller
More frequent and shorter heating up times, smaller temperature
variations

6 D.h.w. temperature control

2-position control heats the d.h.w. at certain intervals. The duration of d.h.w. heating
depends mainly on the storage tanks capacity and water volume and the amount of
d.h.w. currently required.
Legend
C
TBWx TBWx Actual value of d.h.w.
TBWw temperature
TBWw D.h.w temperature setpoint
TBWw-SDBW
SDBW Switching differential of d.h.w.
ON Switch-on point
t OFF Switch-off point
t Time
P Pump

2371D05
ON
P
OFF

Switching differential D.h.w. ON: TBWx = TBWw - SDBW


D.h.w. OFF: TBWx = TBWw

P TBWx Actual value of d.h.w. temperature


TBWw D.h.w temperature setpoint
ON SDBW Switching differential of d.h.w. (41)
P Pump (ON / OFF)
w Setpoint
2379Z24a

Switch-on point
OFF

Switch-off point
w
TBWx [C ]

6.1 Legionella function

Benefit Potential legionella viruses in the d.h.w. storage tank will be killed at regular
intervals.

Description The legionella function ensures that the d.h.w. in the storage tank will periodically be
raised to a temperature of at least 60 C, thus making certain that potential legionella
viruses will be killed.

Setting 1. Press the line selection buttons to select line 42OEM.


2. Press the + / buttons to activate or deactivate the legionella function.

Setting range Unit Factory setting

0/1 Increment 1

Effect The setting activates or deactivates the legionella function.


Entry:
0 OFF: Function not active.

124/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
1 ON: The function will be activated every Monday morning when d.h.w. is heated
up for the first time and lasts a maximum of 2.5 hours. The d.h.w. is heated up to
the adjusted legionella setpoint. Also refer to line 43OEM.

 Notes This function is possible only when d.h.w. heating is released by the d.h.w. heating
program.
If the legionella function is aborted during the usual time (on Mondays), it will be
repeated the next time the d.h.w. setpoint is changed

6.2 Setpoint of the legionella function

Benefit Adjustable temperature level to kill legionella viruses

Description The setpoint of the legionella function is an adjustable temperature level to which the
d.h.w. temperature is raised when the legionella function is activated (also refer to
section "Legionella function). For details, also refer to "Legionella function", line 42OEM.

Setting 1. Press the line selection buttons to select line 43OEM.


2. Press the + / buttons to adjust the required setpoint.

Setting range Unit Factory setting

8...95 C 65

Effect The setting changes the d.h.w. setpoint during the period of time the d.h.w. is heated
up as a result of the legionella function.

6.3 Protection against discharging of d.h.w.

Benefit Prevents inadvertent discharging of the d.h.w. storage tank via the heating system

Description Prevents inadvertent discharging of the d.h.w. storage tank by cold water from the
heating circuit.

Setting 1. Press the line selection buttons to select line 44OEM.


2. Press the + / - buttons to activate or deactivate the protection against discharging.

Setting range Unit Factory setting

0...2 - 2

Effect The setting activates or deactivates the protection against discharging:


0 Protection against discharging is not active

1 Protection against discharging is active


Continuous protection with released or logged heat generation based on the
actual value of flow sensor B10, boiler sensor B2 or of the buffer storage tank.
2 Protection against discharging is active only when heat generation is locked
Protection only either when heat generation is logged based on comparison
between flow sensor B2 and buffer storage tank or

125/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
in the case of heat generation lock via contact H and when there is no buffer
storage tank sensor based on B10 or B2.

When protection against discharging of the d.h.w. is active, the boost of the flow
temperature (operating line 126) is checked during the heating cycle:

If at least half the boost value is reached, d.h.w. heating will be released
If the boost value is less than 1/8 of the value set, d.h.w. heating will not be
released

 Note Setting 1 may be used only if the cascade return temperature sensor is connected.

126/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
Cascade settings
6.4 Cascade management strategy

Benefit Selection of required type of lead boiler operation.

Combination with optimum running time strategy.

Description For the plant configuration used, this setting represents an optimum combination of
lead boiler operation and running time strategy.
Setting
1. Press the line selection buttons to select line 50OEM.
2. Press the + / - buttons to select the required combination of lead boiler operation
and running time strategy.

Setting range Unit Factory setting

1...6 1 2

There is a total of 2 types of lead boiler operation and three running time strategies
available. The 6 combinations are assigned as follows:
Einstellung (Kombination) type of lead boiler operation running time trategyrunning

1 autonomous 1
2 autonomous 2
3 autonomous 3
4 linked 1
5 (Standard setting) linked 2
6 linked 3

 Note Proceed as follows to make the required setting:


- First, determine the required type of lead boiler operation
- Determine the required running time strategy
- Use the above table to choose the setting required for your application

127/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
6.4.1 Type of lead boiler operation

General The type of lead boiler operation describes the way the individual boilers in the cascade
are controlled.

Autonomous: The RVA47.320 delivers a boiler temperature setpoint to the BMUs.


The released BMUs then control their output autonomously between 0 and 100 % in
order to reach the preset boiler temperature setpoint.

wt = 70C wt = 70C wt = 70C wt = 70C


Example:

2379z04
1 2 3 4

P = 50 % P = 51 % P = 53 % P = 48 %

wt = Boiler temperature setpoint = Actual output

It is thus possible that individual boilers will be operated outside their output range. The
average actual output is within the defined output range, however (for exceptions, refer
to lines 51 and 52).

linked: A differentiation is made between lead boiler and lag boilers. The RVA47.320 delivers a
temperature setpoint to the lead boiler, which translates it into output. The lag boilers
take this output as maximum limitation of output, thus following the lead boiler.

wt = 70C
Example:
1 2 4 2379z04
3

T = 69C T = 68C T = 73C

P = 50 % wp = 50 % wp = 50 % wp = 50 %

wt = Boiler temperature setpoint for lead boiler


wp = Nominal output setpoint for BMUs 1 - 4
P = Actual output
T = Actual temperature

This means that all boilers will be operated within the defined output range (for
exceptions, refer to pages 14 and 132).

 Note In the case of linked lead boiler operation, the controller considers the ratio of the
nominal BMU outputs and matches the speed of lag boiler operation accordingly.

128/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
6.4.2 Running time strategies

General The running time strategy defines the criteria for the switching on / off of the lag boilers.
It is determined by the following parameters:
- Nominal output of BMU 1 - 4 See line 91 -94
- Entry of minimum limit of output range (Pmin) See line 10OEM
- Entry of maximum limit of output range (Pmax) See line 52OEM
The RVA47.320 initiates changeover only when it leads to a valid operational status
while taking the above parameters into consideration.

 Notes The following parameters also have an impact on the function:


- Delayed switching on of BMU see line 133
- Restart lock for BMU see line 134
For stability reasons, each BMU added to the cascade first runs on the basic stage for
about one minute on completion of which it will be released for modulating control to
deliver the output required.

 Important The running time strategies described below become active only when the flow
temperature setpoint is reached. During the heating up time (e.g. after night setback),
the boilers required are run up to the maximum released output as quickly as possible
(short heating up time).

Strategy 1: Additional boilers are switched on as late as possible and switched off again as early as
possible. Hence, the aim is to have the smallest possible number of boilers in
operation, or to obtain short running times for additional boilers.

2379Z05a
80% ON
Example of three boilers
with an output range of 20
- 80 %: 80% 80% ON

40% 40%

80% 80% 80%


53% 53% 53%
100% 100% 100%

80% 80% 80%


53% 53% 53%

80% 80%

40% 40%
OFF

80%

OFF

= increase in output = Switching onZuschaltung


= decrease in output = Switching offWegschaltung
P = OutputLeistung

129/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
Strategy 2: Additional boilers are switched on as late as possible and switched off again as late as
possible. Hence, the aim is to obtain the smallest possible number of switching on /
off cycles for the boilers.

80% ON 2379Z05
Example of three boilers
with an output range of 20
- 80 %: 80% 80% ON

40% 40%

80% 80% 80%


53% 53% 53%
100% 100% 100%

80% 80% 80%

20% 20% 20%

20% 30% 30% OFF


20%

40% OFF

Strategy 3: Additional boilers are switched on as early as possible and switched off as late as
possible. Hence, the aim is to have the highest possible number of boilers in
operation, or to obtain long running times for additional boilers.

2379Z05a
Example of three boilers
40% ON
with an output range of 20
- 80 %:
20% 20% 30% 30% ON

27% 27% 27% 100% 100% 100%


20% 20% 20%

20% 20% 20% 27% 27% 27%

20% 20% 30% 30% OFF

40%
OFF

= increase in output = Switching on


= decrease in output = Switching off
P = Output

130/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
6.5 Lower limit of output range (Pmin)

Benefit The minimum output of the boilers controlled by the BMUs can be defined.

Description Defines the minimum limit of the optimum output range used by the BMUs.

Setting 1. Press the line selection buttons to select line 51OEM.


2. Press the + / - buttons to set the minimum limitation of the output.

Setting range Unit Factory setting

5...Pmax % 40
Pmax. = upper limit of output range (operating line 52)

 Note Typically, the set minimum limitation of the output lies above the lowest basic stage of
all BMUs. A lower setting causes several BMUs to cycle Do not use lower settings
without having tested them in practical operation.

Effect The setting defines the minimum limit of the output range within which the BMUs are
controlled. The value is used as the switch-on or switch-off criterion according to the
selected running time strategy (refer to page 129).

Pmax
Output range of BMUs
Pmin
2379Z06

The minimum limit of the output range is crossed only in exceptional cases, e.g. when
the setting of the value is too high, or when, due tot he BMUs' output ratio, an invalid
operational status would result after changeover.

131/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
6.6 Upper limit of output range (Pmax)

Benefit The maximum output of the BMUs can be defined.

Description Defines the maximum limit of the optimum output range used by the BMUs.

Setting 1. Press the line selection buttons to select operating line 52OEM.
2. Press the + / - buttons to set the maximum limitation of the output.

Setting range Unit Factory setting

Pmin...100 % 90
Pmin. = minimum limit of output range (operating line 51)

Effect The setting defines the maximum limit of the output range within which the BMUs are
controlled. The value is used as the switch-on or switch-off criterion according to the
selected running time strategy (refer to page 129).

Pmax

Output range of BMUs


Pmin
2379Z06

The maximum limit of the output range (when <100 %) is crossed only when all
available BMUs run at Pmax and there is still demand for heat.
Otherwise, crossing only takes place in exceptional cases, e.g. when the setting of the
value is too low, or when, due to the BMUs output ratio, an invalid operational status
would result after changeover.
When using a setting of 100 %, the value will of course never be exceeded.

6.7 Mandatory time on basic stage

Benefit The minimum running time on the basic stage can be defined

Description This function allows the minimum running time on the basic stage to be set. This
enables the controller to operate smoothly even if BMUs of very high capacity are used.

Setting 1. Press the line selection buttons to select operating line 56OEM.
2. Press the + / - buttons to adjust the mandatory time on the basic stage.

Setting range Unit Factory setting

10...1200 s 60

Effect When started up, each BMU is operated on the basic stage for the period of time
adjusted here. The BMU will be released for modulation only when this time has
elapsed. This period of time enables the controller to analyse the current operational
status and then plan the next steps.
 Note When using heat generating equipment of very high capacity, the longer time leads to a
more stable (slower) operating performance.

132/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
6.8 Minimum temperature differential at the
pressureless header

Benefit Detection of a too high flow rate on the heat generation side.
Avoiding excessive return temperatures.

Description An excessive flow rate on the heat generation side and the resulting increase of the
return temperature is quickly detected and, if necessary, offset by shutting down one of
the BMUs.

Setting 1. Press the line selection buttons to select line 60OEM.


2. Press the + / - buttons to set the minimum temperature differential.

Setting range Unit Factory setting

0...20 K (C) 4

Effect The minimum temperature differential at the pressureless header prevents the return
temperature from exceeding a certain level.
The setting is only active when running time strategy 2 or 3 is selected (see page 35).
With running time strategy 1, the function is inactive.
When the return temperature rises to a level which is half a switching differential (
MTS/2) below the flow temperature (point a), the selected running time strategy 2 or 3
is switched over to running time strategy 1. This means that one of the BMUs is shut
down as soon as possible.
If the return temperature moves away from the flow temperature by one full switching
differential MTS (point b), changeover is cancelled again. This means that running time
strategy 1 switches back to the previous running time strategy 2 or 3.

[C]
tVL
=
MTS
=

tRL
LZS2/3

LZS1
2379Z27
a b t
tVL Cascade flow temperature (B10)
tRL Cascade return temperature (B70)
MTS Minimum temperature differential at the pressureless header
LZS1-3 Running time strategy 1 - 3
a/b Changeover points of running time strategy

133/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
Configuration of plant
6.9 Continuous display

Benefit Selection of value for the continuous display.

Description Determines to kind of information to appear on the continuous display.

Setting 1. Press the line selection buttons to select operating line 90OEM.
2. Press the + / - buttons to select the required continuous display.
Setting range Unit Factory setting

0/1 - 0

Effect This setting changes the continuous display of the device. It appears when no
operating line is selected.
0 Day / time of day
The continuous display shows the weekday (1...7 = Mo...Su) and the time of
day.
1 Cascade flow temperature sensor (common flow temperature sensor)
The continuous display shows the temperature measured with the cascade flow
temperature sensor (B10)

 Caution! When connecting several BMUs to the controller, the continuous display always shows
the cascade flow temperature. In that case, setting 0 can be no longer selected.

0 4 8 12 16 20 24

134/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
General values
6.10 Software version

Benefit Straightforward display of software version used, without removing the controller

Description The software version installed represents the state of the software available at the time
the controller was produced.

Setting 1. Press the line selection buttons to select line 91OEM.


2. No setting can be made with the + / - buttons.
Display Unit

00.0 ... 99.9 Digits

Effect The software version will automatically be displayed on this line.


Example: 01.0
The first 2 digits give the software version (01.)
The third digit gives the software revision (.0)

6.11 Device operating hours

Benefit Display of the number of device operating hours

Description Here, you can read the number of hours the controller has been in operation

Setting 1. Press the line selection buttons to select operating line 92OEM.
2. No setting can be made with the + / - buttons.
Display Unit

0... 500000 h

Effect The number of operating hours since the controller was first commissioned will
automatically be displayed on this line.
The hours considered as operating hours are those during which power was supplied to
the controller, that is, including the periods of time with no effective heating operation.
The number of operating hours cannot be reset.

135/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Description of the OEM settings 15.07.2002
7 Functions with no settings
Introduction The functions described below require no settings. They are performed automatically
but have an impact on the plant.
For the rectification of faults, planning and plant maintenance, it may therefore be very
advantageous to know about their impact on plant operation.

7.1 Chimney sweep

Benefit Produces the operational status required for flue gas measurements.

Description No chimney sweep function can be triggered on the controller itself. the chimney sweep
function is activated directly on the respective BMU.

Effect As soon as the chimney sweep function is triggered on one of the BMUs of the
cascade, the BMU transmits the signal to the controller, which shuts down all other
BMUs. The controller allows the boiler temperature to rise to a level of 64 C, which is
required to make flue gas measurements, then maintaining that temperature level by
enforcing heat consumption of both the heating circuits and d.h.w.
This action is independent of whether a lead or lag boiler is involved.
By deactivating the chimney sweep function on the BMU, or on completion of a period
of time to be adjusted on the BMU, the controller returns to its initial operational status.

 Note For information about the activation of the chimney sweep function and other
information, refer to the technical documentation of the type of BMU used.

7.2 Generating the boiler temperature setpoint

Benefit Demand-dependent control of the burner

Description The various heating circuits require different flow temperature setpoints depending on
the demand for heat. However, since boiler temperature control can consider only one
setpoint, a selection is made.

Process Generally, the demand for the highest setpoint required by a consumer (e.g. by a
heating circuit) generates the current boiler temperature setpoint.
The setpoint requirements considered stem from both controller-internal setpoints
(heating circuit or input H1) and setpoints transmitted via LPB.
Auxiliary functions, such as setpoint boosts and the like, are included in the setpoints
actually demanded at the time.
Exception A demand for d.h.w. has priority over all other setpoint requirements, which means that
the required d.h.w. setpoint will be maintained, even if it is lower than that called for by
a heating circuit.

Effect The boiler temperature is maintained at the highest setpoint currently demanded -
unless d.h.w. is required.

136/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Functions with no settings 15.07.2002
Example T
C
90

80 TKw

70 TV w2

60

50

40 TVw1

2371D09
30

20
20 10 0 -10 -20 -30
TAgem

TKw Boiler temperature setpoint


TVw1 Flow temperature setpoint of the controller-internal heating circuit (incl. setpoint boost if any)
TVw2 Flow temperature setpoint of a controller-external heating circuit (incl. setpoint boost if any)

7.3 Automatic 24-hour heating limit

Benefit Automatic shutdown of heating.


Saving energy without sacrificing comfort.

Description This is a fast-acting savings function since the heating is switched off when there is no
more demand for heat. Economical operation is ensured throughout the year,
especially during intermediate seasons. Manual switching off is no longer required.

Notes The automatic 24-hour heating limit does not function in continuous operation
The display shows the automatic 24-hour heating limit as ECO

7.3.1 Without room influence

Introduction If no room unit is connected, the room temperature setpoint will not be readjusted by
the room influence. In that case, the automatic 24-hour heating limit operates according
to the selected setpoint of or .

Process The temperature basis used for this process are the values of the flow temperature
setpoint and the current room temperature setpoint.

Switching off If the flow temperature setpoint falls below the room temperature setpoint plus a
correction value, the heating will be switched off.

Heating OFF:

TVw = TRw +2 S/10

Switching on If the flow temperature setpoint exceeds the room temperature setpoint plus a
correction value, the heating will be switched on.

137/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Functions with no settings 15.07.2002
Heatings switch-on point:

TVw = TRw + 4 S/10

TVw Flow temperature setpoint


TRw Room temperature setpoint
s Slope of the heating curve

7.3.2 With room influence

Introduction The automatic 24-hour heating limit operates depending on the current flow
temperature setpoint. If a room unit is connected, the room influence continuously
readjusts the flow temperature setpoint.
This means that the automatic 24-hour heating limit differs when room influence is
used.

Process The temperature basis used for this process are the values of the flow temperature
setpoint and the current room temperature setpoint.

Switching off If the flow temperature setpoint corrected by the room influence falls below the room
temperature setpoint plus a correction value, the heating will be switched off.

Heatings switch-off point:

S 31OEM
TVwk TRw + 2
10 16

Switching on If the flow temperature setpoint corrected by the room influence exceeds the room
temperature setpoint plus a correction factor, the heating will be switched on.

Heatings switch-on point:

S 31OEM
TVwk TRw + 4
10 16

TVwk Flow temperature setpoint corrected by the room temperature


TRw Room temperature setpoint
s Slope of the heating curve

138/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Functions with no settings 15.07.2002
7.4 Quick setback with room sensor

Benefit Making use of the buildings thermal storage capacity.

Description Quick setback is dependent on whether or not a room temperature sensor is used. A
differentiation must therefore be made between quick setback with or without room
sensor.
 Important This process has an impact only when a room temperature sensor is used.

Process Quick setback is started as soon as a change to a lower room temperature setpoint
takes place (e.g. switching times in automatic mode).
Quick setback is terminated as soon as the actual room temperature reaches the level
of the respective room temperature setpoint (TRx = TRw).

2371D08
C

20
TRx
15

TRw
t

H
ON

OFF
t

TRx Actual value of the room temperature


TRw Room temperature setpoint
H Quick setback

Effect During quick setback, the heating circuit pump will be deactivated and there will be no
demand for heat. This means that the room temperature falls quicker since the supply
of heat from the flow or boiler is cut off.
Exception Due to frost protection for the plant, the heating circuit pump can be
activated however in spite of quick setback.

 Note If no room sensor is connected, quick setback will not be accomplished through this
process. For details, refer to section "Quick setback constant", operating line 31OEM.

139/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Functions with no settings 15.07.2002
7.5 D.h.w. push

Benefit Availability of d.h.w. is also ensured during non-occupancy times.

Description If, due to unexpected demand, the d.h.w. storage tank is emptied, the d.h.w. push
provides one-time charging of the storage tank until the nominal d.h.w. temperature
setpoint is reached.

Process The d.h.w. push is triggered as soon as the actual d.h.w. temperature falls below the
reduced d.h.w. setpoint (line 120) by more than twice the switching differential (line
41OEM).
TBWx < TBWR - 2 SDBW

Effect When the d.h.w. push is triggered, the storage tank is charged once until the nominal
d.h.w. temperature setpoint (operating line 13) is reached.
Then, normal operation according to the d.h.w. heating program is resumed.

Example
SDBW
TBWw

TBWx
SDBW
TBWR

2SDBW

2379D10
TBWw

TBWR

Push
t

SDBW Switching differential d.h.w.


TBWw Nominal d.h.w. temperature setpoint
TBWR Reduced setpoint of the d.h.w. temperature

140/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Functions with no settings 15.07.2002
7.6 Pump kick

Benefit No seizing of pumps

Description The pump kick is a protective function aimed at preventing the pumps from seizing.

Process Every Friday at 10:00 h, the pumps connected directly to the RVA47.320 are activated
for 30 seconds, one by one at an interval of one minute.

The pump kick is activated without giving consideration to any of the other functions.

Effect During the periods of time pump kick is activated, the water circulates. The mechanical
parts of the pumps will be purged, thus preventing the pumps from seizing.

 Note The kick of the d.h.w. pump is the last pump kick made in order to prevent the transfer
of heat from the d.h.w. storage tank to the heating system.

7.7 Protection against discharging after d.h.w.


heating

Benefit Inadvertent discharging of the d.h.w. storage tank will be prevented

Description The Protection against discharging after d.h.w. heating prevents inadvertent
discharging of the d.h.w. storage tank resulting from the pump overrun. Together with
Protection against discharging during d.h.w. heating (operating line 44OEM), efficient
protection against discharging is thus ensured.

Process The controller compares the storage tank temperature with the cascade flow
temperature (common flow temperature) or, in certain situations, with the boiler
temperature.
If the cascade temperature (or the boiler temperature) is lower than the storage tank
temperature, pump overrun will be stopped prematurely.

141/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Functions with no settings 15.07.2002
7.8 Overview of pump operation

Benefit Straightforward checking of proper functioning of the various pumps.

Description Operation of the various pumps depends on a number of factors. To enable you to
quickly understand the different interrelationships when commissioning and checking
the plant, please make use of the list below. It provides information about the setting
combinations (pump settings / demand for heat) at which a pump runs (the meaning of
the different pump settings is defined on operating line 95).

Pumps Demand for heat


Settings via HC: Input H1 via d.h.w.:
Pump runs when
Q1
there is demand for Pump does not run Pump does not run
Setting 1
heat

* Pump runs when Pump runs when


Q1
there is demand for there is demand for Pump does not run
Setting 2
heat heat
* Pump runs when Pump runs when * Pump runs when
Q1
there is demand for there is demand for there is demand for
Setting 3
heat heat heat

Q1 No influence from type of heat demand. Pump runs according to


Setting 4 the settings made on operating line 122.
Pump runs when
Q1
Pump does not run there is demand for Pump does not run
Setting 5
heat
Pump runs when
Q3
Pump does not run Pump does not run there is demand for
Setting 1
heat

* = the pump also runs when the demand for heat comes from another controller integrated via LPB

When there is no more demand for heat, the pumps in operation overrun for the period
of time set on line Pump overrun time (8OEM), with the exception of the d.h.w.
circulating pump, Q1 setting 4.
There are situations, however, where the pumps (with the exception of pump H1, Q1
setting 5) do not run, for example with:

Summer / winter changeover


24-hour heating limit
Quick setback
Room temperature limitation by room sensor

142/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Functions with no settings 15.07.2002
7.9 Frost protection

Benefit Ensures that the boiler and d.h.w. temperature will not fall below a certain level

 Note In addition to the frost protection modes described here, frost protection for the building
and frost protection for the plant, whose parameters can be set, are also active. For
details, refer to the description given on lines 15 and 33 OEM.

7.9.1 For the boiler

The frost protection function for the boilers is integrated in the BMUs. For detailed
information, refer to the technical documentation of the product used.
For details, refer to the documentation of the relevant product.

7.9.2 For the d.h.w.

Description Frost protection for the d.h.w. prevents freeze-ups of the d.h.w. storage tank that is
connected directly to the RVA47.320. Whenever the d.h.w. temperature drops
excessively, forced charging will be initiated.

Process If... then...


the actual value of the d.h.w. temperature falls below 5 ... the frost protection
C... function for the d.h.w.
(TBWx < 5 C) becomes active

the actual value of the d.h.w. temperature exceeds 5 C ... the frost protection
by more than one d.h.w. switching differential (line function for d.h.w. will be
41OEM)... terminated
(TBWx > 5 C + SDBW)

 Notes The frost protection setpoint for the d.h.w. is factory-set at 5 C and cannot be
changed
Pump overrun will be activated when d.h.w. heating is terminated.

 Important The frost protection function only acts on a d.h.w. storage tank connected directly
to the RVA47.320. In the case of plant types with d.h.w. heating via BMU, this
function must be provided by the BMU.

The frost protection function is only active when using a temperature sensor. If the
d.h.w. is heated with the help of a control thermostat, no frost protection function is
possible because there is no actual value of the storage tank temperature.

143/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Functions with no settings 15.07.2002
8 Application examples
General The RVA47.320 can control up to four modulating gas-fired heating boilers. For this
purpose, the boilers must be equipped with an appropriate BMU which controls the
boiler temperature.
In the controllers internal cascade circuit, the RVA47.320 determines the order the
individual BMUs are switched on and off based on the output balance. The boilers are
thus switched on and off temperature over- or undershoot. The individual boilers are
controlled by the respective BMUs.

Furthermore, the controller can ensure the coordination of additional boiler controllers
of a cascade (cascade master function).
D.h.w. heating is provided either directly by the RVA47.320 or by one of the BMUs
based on the values adjusted on the RVA47.320.
The RVA47.320 accepts and handles heat demand signals of additional controllers
connected to the LPB, and of controllers delivering their signals via input H1.

 Note On the consumer side, the plant can be extended to include up to 16 controllers without
an additional bus power supply, and up to 40 controllers when using a central bus
power supply (also refer to Basic Documentation LPB System Engineering, reference
number CE1P2370E).
On the heat generation side, additional RVA47.320 or RVA43.222 can be used to build
up a cascade of up to 16 heat sources (modulating, multi-stage or mixed).

Hydraulic circuit Where shown, the applications require proper hydraulic decoupling between heat
generation and heat consumption since the volumetric flows on both sides vary and are
different from one another. The simplest hydraulic decoupling method is the use of a
sufficiently large pressureless header (bypass, hydraulic decoupler; about two to three
nominal sizes larger than the header of the boiler circuit).
With plant types using no boiler pump, a flow switch is required to ensure the flow of
water through the boiler.
When using heating boilers with a speed controlled pump, the pump must be set to a
fixed speed.
 Important When designing the plant, it should be made certain that the volumetric flows on the
heat generation and heat consumption side at nominal output are about the same.

outside temperature The outside sensor can be connected either directly to the RVA47.320 or to one of the
sensor BMUs to transmit its value to the controller via the PPS, but it can also be connected to
some other LPB capable controller to transmit its value to the other LPB capable
controllers via the LPB. But it can be connected to some other LPB-compatible
controller to transmit its value via LPB to the other LPB-compatible controllers.
We recommend to connecte it directly to the RVA47.320.

D.h.w. priority When using d.h.w. heating with a charging pump, d.h.w. priority is possible only in
connection with LPB-compatible controllers. Controllers not suited for use with the LPB
cannot be acted upon.

144/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.1 Plant types RVA47.320 - no. 27

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. No d.h.w. heating via
the RVA47.320.

B10

1 2 3 4

B70

2379S27
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 27
Heating curve (line 17) --- (inactive)
Pump function Q1 (line 95) 1 (heating circuit pump or no pump)

 Important This application requires the heat demand signal from a consumer to release heat
generation:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.

Electrical connections
H1 B70 B10 B9 A6 / BMU

M B M B M B M B PPS LPB

H1 B70 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A27

L
N

Legend For a detailed legend, refer to page 158.

145/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.2 Plant types RVA47.320 - no. 28

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating with
charging pump through the RVA47.320.

B10

B3
1 2 3 4

B70

2379S28
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 28
Heating curve (line 17) --- (inactive)
Pump function Q1 (line 95) 1 (heating circuit pump or no

 Important This application requires the heat demand signal from a consumer (or d.h.w. heating)
to release heat generation:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.

Electrical connections
H1 B70 B3 B10 B9 A6 / BMU

M B M B M B M B M B PPS LPB

H1 B70 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A28

N
L

Legend For a detailed legend, refer to page 158.

146/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.3 Plant types RVA47.320 - no. 29

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve.

B10

1 2 3 4

B70

2379S29
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 29
Heating curve (line 17) --- (inactive)
Pump function Q1 (line 95) 1 (heating circuit
pump or no pump)

 Important This application requires the heat demand signal from a consumer to release heat
generation:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.

 Note A heat demand signal from the d.h.w. storage tank releases only that boiler to which
the storage tank is hydraulically connected. The other boilers of the cascade will not be
released.

Electrical connections
H1 B70 B10 B9 A6 / BMU

M B M B M B M B PPS LPB

H1 B70 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A27

L
N

 Note The d.h.w. sensor (B3) is connected directly to BMU 1.

Legend For a detailed legend, refer to page 158.

147/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.4 Plant types RVA47.320 - no. 30

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. System pump for
heating circuits connected to the RVA47.320.
No d.h.w. heating via the RVA47.320.

B10

1 2 3 4

B70

2379S30
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 30
Heating curve (line 17) --- (inactiv) or 2.5...40
Pump function Q1 (line 95) 2 (primary pump for HC only) or
3 (primary pump for HC and d.h.w.)

 Important Heat generation is released by the heat demand signal from a consumer:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.

When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).

H1 B70 B10 B9 A6 / BMU

Electrical connections M B M B M B M B PPS LPB

H1 B70 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A30

N
L

Legend For a detailed legend, refer to page 158.

148/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.5 Plant types RVA47.320 - no. 31

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating with
charging pump through the RVA47.320.
System pump for heating circuits and d.h.w. heating connected to RVA47.320.

B10

B3
1 2 3 4

B70

2379S31
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 31
Heating curve (line 17) --- (inactiv) or 2.5...40
Pump function Q1 (line 95) 3 (primary pump for HC and d.h.w.)

 Important Heat generation is released by the heat demand signal from a consumer (or d.h.w.
heating):
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).

H1 B70 B3 B10 B9 A6 / BMU


Electrical connections M B M B M B M B M B PPS LPB

H1 B7 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A31

N
L

Legend For a detailed legend, refer to page 158.

149/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.6 Plant types RVA47.320 - no. 32

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating with
charging pump through the RVA47.320.
Primary pump for heating circuits connected to the RVA47.320.

B10

B3
1 2 3 4

B70

2379S32
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 32
Heating curve (line 17) --- (inactiv) or 2.5...40
Pump function Q1 (line 95) 2 (primary pump for HCs only)

 Important Heat generation is released by the heat demand signal from a consumer (or d.h.w.
heating):
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).

H1 B70 B3 B10 B9 A6 / BMU


Electrical connections M B M B M B M B M B PPS LPB

H1 B7 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A31

N
L

Legend For a detailed legend, refer to page 158.

150/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.7 Plant types RVA47.320 - no. 33

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve. System pump for heating circuits connected to the
RVA47.320.

B10

1 2 3 4

B70

2379S33
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 33
Heating curve (line 17) --- (inactiv) or 2.5...40
Pump function Q1 (line 95) 2 (primary pump for HC
only)

 Important Heat generation is released by the heat demand signal from a consumer:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).
 Notes A heat demand signal from the d.h.w. storage tank releases only that boiler to which
the storage tank is hydraulically connected. The other boilers of the cascade
will not be released.

H1 B70 B10 B9 A6 / BMU


Electrical connections LPB
M B M B M B M B PPS

H1 B70 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
23 79A3 3

N
L

 Note The d.h.w. sensor (B3) is connected directly to BMU 1.

Legend For a detailed legend, refer to page 158.

151/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.8 Plant types RVA47.320 - no. 34

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. Control of pump
heating circuit by the RVA47.320.
No d.h.w. heating via the RVA47.320.

B10

1 2 3 4

B70

2379S34
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 34
Heating curve (line 17) 2.5...40
Pump function Q1 (line 95) 1 (heating circuit pump)

 Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.

H1 B70 B10 B9 A6 / BMU


Electrical connections M B M B M B M B PPS LPB

H1 B70 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A33

N
L

Legend For a detailed legend, refer to page 158.

152/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.9 Plant types RVA47.320 - no. 35

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. Control of the pump
heating circuit by the RVA47.320. D.h.w. heating with charging pump by the
RVA47.320.

B10

B3
1 2 3 4

B70

2379S35
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 35
Heating curve (line 17) 2.5...40
Pump function Q1 (line 95) 1 (heating circuit pump)

 Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.

H1 B70 B3 B10 B9 A6 / BMU

Electrical connections M B M B M B M B M B PPS LPB

H1 B7 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A31

N
L

Legend For a detailed legend, refer to page 158.

153/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.10 Plant types RVA47.320 - no. 36

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve. Control of pump heating circuit by RVA47.320.

B10

1 2 3 4

B70

2379S36
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 36
Heating curve (line 17) 2.5...40
Pump function Q1 (line 95) 1 (heating circuit pump)

 Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
 Notes When there is only a heat demand signal from the d.h.w. storage tank (heating circuits
do not currently call for heat), the boiler put into operation is only that to
which the storage tank is hydraulically connected. The other boilers of the
cascade will not be released.

H1 B70 B10 B9 A6 / BMU


Electrical connections LPB
M B M B M B M B PPS

H1 B70 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A33

N
L

 Note The d.h.w. sensor (B3) is connected directly to BMU 1.

Legend For a detailed legend, refer to page 158.

154/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.11 Plant types RVA47.320 - no. 65

 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. Control of the pump
heating circuit by the RVA47.320 based on the heat demand signal received via input
H1.

B10

1 2 3 4

B70

2379S34
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 65
Heating curve (line 17) --- (inactive) or 2.5...40
Pump function Q1 (line 95) 5 (pump H1)

 Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.

The heat demand signal for the pump heating circuit is generated via input H1.

In addition, the controller itself can generate a weather-compensated flow temperature


(setting the heating curve to a valid value).

H1 B70 B10 B9 A6 / BMU


Electrical connections LPB
M B M B M B M B PPS

H1 B70 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A33

N
L

Legend For a detailed legend, refer to page 158.

155/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.12 Plant types RVA47.320 - no. 66
 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs.


D.h.w. heating with charging pump through the RVA47.320.
Control of the pump heating circuit by the RVA47.320 based on the heat demand signal
received via input H1.

B10

B3
1 2 3 4

B70

2379S35
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 66
Heating curve (line 17) --- (inactive or 2.5...40
Pump function Q1 (line 95) 5 (pump H1)

 Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.

The heat demand signal for the pump heating circuit is generated via input H1.

In addition, the controller itself can generate a weather-compensated flow temperature


(setting the heating curve to a valid value).

H1 B70 B3 B10 B9 A6 / BMU


Electrical connections LPB
M B M B M B M B M B PPS

H1 B7 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A31

N
L

Legend For a detailed legend, refer to page 158.

156/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.13 Plant types RVA47.320 - no. 67
 Note The plant type no. is identical with the number displayed on line 53.

Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve.
Control of the pump heating circuit by the RVA47.320 based on the heat demand signal
received via input H1.

B10

1 2 3 4

B70

2379S36
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 67
Heating curve (line 17) --- (inactive) or 2.5...40
Pump function Q1 (line 95) 5 (pump H1)

 Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.

The heat demand signal for the pump heating circuit is generated via input H1.

In addition, the controller itself can generate a weather-compensated flow temperature


(setting the heating curve to a valid value).

 Notes When there is only a heat demand signal from the d.h.w. storage tank (heating circuits
do not currently call for heat), the boiler put into operation is only that to which the
storage tank is hydraulically connected. The other boilers of the cascade will not be
released.

H1 B70 B10 B9 A6 / BMU


Electrical connections LPB
M B M B M B M B PPS

H1 B70 B3 M B10 B9 MD A6 MB DB

N1

Q3 Q1 F1 L N
2379A33

N
L

 Note The d.h.w. sensor (B3) is connected directly to BMU 1.

Legend For a detailed legend, refer to page 158.

157/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
8.14 Legend
Low voltage side Mains voltage side

DB Data bus (LPB) N Neutral conductor (mains connection)


MB Ground bus (LPB) L Live AC 230 V (mains connection)
A6 PPS (room unit, BMU...)
MD Ground PPS
B9 outside temperature sensor F1 Line control contact relay Q1/Q3
B10 Cascade flow temperature sensor Q1 Heating circuit pump / primary pump
B70 Cascade return temperature sensor
M Ground sensors Q3 D.h.w. charging pump
B3 D.h.w. temperature sensor / control
thermostat
H1 input H1

LPB Local Process Bus N1 ALBATROScontroller RVA47.320


(ALBATROS-process bus)
PPS Point-to-point interface BMU Boiler Management Unit (burner control
(ALBATROS peripheral bus) with additional management functions)

The connection diagrams show optional components with broken lines.

For application examples with a cascade integrated in systems with alternative heat
generation, refer to Basic Documentation LPB System Engineering (document no.
CE1P2379E).

158/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Application examples 15.07.2002
9 Dimensions

Room unit 11
6
96

9,3

91 x 91
96
2379M100

17,4

81

2371M02
Panel cutout
96 96

2...10 +0.8
92 -0
96

+0.8 +0.8
92 -0 92 -0
188

159/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Dimensions 15.07.2002
10 Technical data

Power supply Nominal voltage AC 230 V (10 %)


Nominal frequency 50 Hz (6 %)
Power consumption max. 7 VA

Requirements Safety class II, to EN 60 730


(when mounted properly)
Degree of protection IP 40 to EN 60 529
(when mounted correctly)
Electromagnetic immunity conforming to the requirements of
EN 50 082-2
Electromagnetic emissions conforming to the requirements of
EN 50 081-1
Climatic conditions Operation to IEC 721-3-3 lass 3K5 (noncondensing)
Temperature 0...50 C
Storage to IEC 721-3-1 class 1K3 -2570 C
Transport to IEC 721-3-2 class 2K3 -2570 C

Contamination To EN 60 730 usual environment

Mechanical conditions Operation to IEC 721-3-3 class 3M2


Storage to IEC 721-3-1 class 1M2
Transport to IEC 721-3-2 class 2M2

Mode of operation To EN 60730 par. 11.4 11.4 1b

Output relays Voltage range AC 24...230 V


Nominal current AC 0.022 (2) A
Switch-on peak max. 10 A for max. 1 s
Fusing max. 10 A

Bus extension Perm. cable length for PPS:


(Telephone wire 0.8 mm dia., 2-wire
interchangeable)
Max. cable length central unit / peripheral unit 75 m
Max. total cable length (sum of all branches) 250 m

Perm. cable length for LPB:


(copper cable 1.5 mm2, 2-wire not
interchangeable)
With controller bus power supply (per controller) 250 m
With central bus power supply (bus power supply
/ controller) 460 m

Bus loading number E=3

Perm. sensor cable 0.6 mm dia. max. 20 m


2
lengths 1.0 mm max. 80 m
2
1.5 mm max. 120 m

160/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Technical data 15.07.2002
Inputs outside temperature sensor NTC (QAC31) or
Ni 1000 (QAC21)
D.h.w. sensor Ni 1000 at 0 C (QAZ21)
Cascade flow temperature sensor Ni 1000 at 0 C (QAD21)
Cascade return temperature sensor Ni 1000 at 0 C (QAD21)
buffer storage tank sensor Ni 1000 at 0 C (QAZ21)

H1 as an analog input with


safety extra low voltage (SELV) UH1 = (12...24) V
(contact open)
IH1 = (2...5) mA
(contact closed)

H1 as an analog input with


safety extra low voltage (SELV) Uin = (0...10 V) fr 0...130 C
Rin = 100 k
max. ratings 20 V; 20 mA

Miscellaneous Backup of time switch > 12 hours


Weight approx. 0.5 kg
Software class to EN 60 730 class A

161/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Technical data 15.07.2002
Index
contact H1 .............................................. 106, 110, 111
A
continuous display .................................................. 134
actual value of buffer storage tank temperature........63
control of the burner ............................................... 136
actual value of cascade flow temperature .................60
actual value of cascade return temperature ..............61 D
Actual value of d.h.w. temperature............................63 D.h.w temperature setpoint ...................................... 67
actual value of outside temperature ..........................48 d.h.w.
Actual value of the boiler temperature.......................60 switching times.................................................... 50
Actual value of the room temperature .......................48 D.h.w. operating mode ............................................. 33
adaption heating curve ..............................................81 d.h.w. priority ............................................................ 91
adaption of the heating curve ....................................81 d.h.w. push ............................................................. 140
sensitivity 2 ........................................................121 d.h.w. sensor ............................................................ 89
adaption sensitivity 1 ...............................................120 D.h.w. temperature control ..................................... 124
adaption sensitivity 2 ...............................................121 d.h.w. time switch program....................................... 50
assignment of d.h.w. heating.....................................88 demand for heat ..................................................... 106
Attenuated outside temperature ................................64 demand for heat with reduced d.h.w. setpoint.......... 94
automatic 24-hour heating limit ...............................137 Device address............................................. 70, 71, 99
with room influence ............................................138 device operating hours ........................................... 135
without room influence .......................................137 Device subaddress ............................................. 70, 71
automatic adaption ....................................................81 Dimensions............................................................. 159
automatic summer / winter changeover ..................102 dimensions of cutout................................................. 15
discharge protection d.h.w...................................... 125
B
Display _ER_............................................................ 53
BMU boiler temperature setpoint...............................66
display boilers........................................................... 70
boiler temperature setpoint of BMUs.........................66
display cascade flow temperature ............................ 67
Boost heating ..........................................................117
display lead boiler..................................................... 70
boost of room temperature setpoint ........................117
Display of actual values............................................ 48
Boost of room temperature setpoint ........................117
display of flow temperature setpoint ......................... 69
boost of the flow temperature setpoint ......................90
display of LPB communication ............................... 101
Brief description...........................................................8
display of LPB power supply .................................. 101
buffer storage tank temperature ................................74
display of plant type.................................................. 56
building's thermal dynamics ......................................80
Display of plant type ................................................. 56
Burner controls ..........................................................11
display of room temperature setpoint ....................... 69
Burner operating hours BMU 1 4............................72
display of the nominal room temperature setpoint.... 68
bus power supply ....................................................100
displaying the BMU error code ................................. 52
bus power supply via controllers .............................100
Displaying the boiler temperature setpoint ............... 66
C Displaying the d.h.w temperature setpoint ............... 67
Calibration of actual output range of BMU 1 -4 .......114 displaying the LPB communication......................... 101
cascade management strategy ...............................127 Displaying the LPB power supply ........................... 101
central bus power supply........................................100 Displaying the nominal room temperature setpoint .. 68
central changeover..................................................102 displaying the PPS communication .......................... 58
central stand-by switch............................................103
E
changeover of boiler sequence ................................96
Effect of room unit .................................................... 33
changeover of boiler sequence in a cascade ............95
ER display ................................................................ 53
changeover of operating mode................................107
exemption of boilers ................................................. 96
changeover temperature heating circuit ....................44
exemption with changeover of the boiler sequence . 96
chimney sweep................................................108, 136
existing boilers.......................................................... 70
clock mode ..............................................................103
Clock setting......................................................37, 103 F
communication status..............................................101 Features ..................................................................... 9
communication via BUS ..........................................101 field of use ................................................................ 12
communication via LPB.............................................99 fixed changeover of boiler sequence........................ 97
Composite outside temperature ................................65 Flow temperature setpoint ........................................ 69
constant for quick setback.......................................116 frost protection........................................................ 143

162/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Index 15.07.2002
boiler.................................................................. 143 master .............................................................103, 104
d.h.w. ................................................................. 143 Maximum limitation of flow temperature setpoint ......79
frost protection for d.h.w. ........................................ 143 Maximum limitation of the boiler temperature setpoint
frost protection for the boiler ................................... 143 ................................................................................112
Frost protection for the building ................................ 44 Maximum limitation of the flow temperature setpoint 79
frost protection for the plant .................................... 118 maximum nominal setpoint of d.h.w. temperature ..123
with weather compensation ............................... 118 maximum value of the heat demand signal DC 0...10
Frost protection for the plant ............................. 92, 118 V ..............................................................................111
frost protection setpoint of the room temperature ..... 44 minimum demand for heat ......................................106
Frostschutz Raumheizung ........................................ 44 minimum limit of output range .................................131
minimum limitation
G
boiler return temperature ...................................113
generating the boiler temperature setpoint ............. 136
minimum limitation of flow temperature setpoint .......79
H Minimum limitation of the boiler temperature ............72
heat demand ........................................................... 109 Minimum limitation of the boiler temperature setpoint
heat gains ............................................................... 120 ................................................................................112
heat generation lock................................................ 108 Minimum limitation of the flow temperature setpoint .79
heating circuit operating modes ................................ 32 minimum setpoint of flow temperature contact H1 ..110
Heating circuit operating modes ............................... 32 minimum temperature differential at the pressureless
heating curve adaption sensitivity 1 ........................ 120 header .....................................................................133
heating curve slope................................................... 46 modem ....................................................................107
heavy building structures .......................................... 81 Mounting location ......................................................13
hours run counter for changeover of boiler sequence mounting procedure ..................................................13
.................................................................................. 71 mounting the controller..............................................13
I N
indication of faults ..................................................... 53 Nominal d.h.w. temperature setpoint ........................42
input B70/B4 ............................................................. 74 nominal output of BMU 1 - 4 .....................................73
input H1................................................................... 106 nominal room temperature setpoint ..........................34
input test ................................................................... 55 Nominal room temperature setpoint ..........................34
Number of d.h.w. charging cycles .............................88
K
KON ........................................................................ 116 O
KORR...................................................................... 115 operating action of the contact H1 ..........................111
Operating elements...................................................30
L
operating hours of device ........................................135
lag boiler
operating mode of d.h.w. heating..............................33
switch-on delay.................................................... 98
Operational faults ......................................................31
Lag boiler .................................................................. 95
optimum start control.................................................83
lead boiler ........................................................... 95, 97
with room influence ..............................................84
lead boiler display ..................................................... 70
without room influence .........................................83
Legionella function .................................................. 124
optimum stop control .................................................84
Leistungsband
output calibration.....................................................114
obere Grenze..................................................... 132
output Q1 ..................................................................74
light building structures ............................................. 81
output test .................................................................55
locking signal ............................................................ 92
Output test.................................................................18
Lower limit of output range (Pmin) .......................... 131
outside temperature source ......................................66
LPB device address .................................................. 99
overtemperature protection for the pump heating
LPB power supply ................................................... 100
circuit .......................................................................119
LPB segment address............................................. 100
overview of pump operation ....................................142
LPB supply.............................................................. 100
P
M
parallel displacement of heating curve ......................76
management strategy cascade............................... 127
parallel displacement of the heating curve ................76
mandatory time on basic stage ............................... 132
parameter settings for OEM ......................................27
mandatory time on basic stage ............................... 132
parameter settings for the enduser ...........................20
manual operation .............................................. 35, 112
parameter settings for the heating engineer .............22

163/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Index 15.07.2002
parameters setpoint boost for d.h.w. heating............................... 90
heating engineer ......................................21, 23, 28 setpoint of the cascade flow temperature................. 67
Plant types...............................................................145 setpoint of the legionella function ........................... 125
PPS communication ..................................................58 Setting the clock ....................................................... 37
Preselecting the weekday .........................................39 Shifting priority.......................................................... 92
preselection of weekday............................................50 shortened heating up time ...................................... 117
pressureless header................................................133 slope of the heating curve ........................................ 46
Product liability ..........................................................12 software version ..................................................... 135
proneness to lime build-up ......................................123 standard time programs............................................ 49
protection against boiler overtemperatures .............113 Standard values........................................................ 49
protection against discharging after d.h.w. heating .141 standby switch ........................................................ 103
Protection against discharging of d.h.w...................125 summer / winter changeover temperature................ 44
protection against legionella viruses .......................124 summer- / wintertime .............................................. 105
protection against scalding......................................123 summer operation..................................................... 45
pump function output Q1 ...........................................74 Switching differential d.h.w. .................................... 123
Pump heating circuit................................................119 switching differential of room temperature................ 77
pump kick ................................................................141 Switching differential of the d.h.w. temperature...... 123
pump overrun time ..................................................113 Switching differential of the room temperature ......... 77
Pump overrun time ..................................................113 switching program circulating pump ......................... 87
switching times ......................................................... 40
Q
switching times d.h.w................................................ 50
quick setback constant ............................................116
switch-on delay of BMUs ......................................... 98
quick setback with room sensor ..............................139
system standby....................................................... 103
Quick setback without room temperature sensor ....116
System time............................................................ 103
R
T
range of action.........................................................102
Technical data ........................................................ 160
range of action of central changeover .....................102
temperature-time integral
range of controllers....................................................11
d.h.w. priority ....................................................... 93
Range of products .....................................................11
terminal H1 ............................................................. 106
range of room units ...................................................11
test sequence ........................................................... 55
range of sensors........................................................11
Time of day............................................................... 37
rectification of faults...................................................31
Time switch program for d.h.w. heating.................... 50
Reduced room temperature setpoint.........................43
Time switch program for space heating.................... 39
Reduced setpoint of the d.h.w. temperature .............85
time synchronization............................................... 103
Regulations for installation ..................................13, 16
Tkmin........................................................................ 72
release of d.h.w. heating ...........................................85
type of building construction ..................................... 80
remote telephone switch .........................................107
Type of d.h.w. demand ............................................. 89
Restart lock of BMUs.................................................98
type of lead boiler operation ........................... 127, 128
Return temperature ...................................................74
room influence...................................................76, 115 U
room temperature limitation......................................77 Upper limit of output range (Pmax)......................... 132
Room temperature setpoint.......................................69 use of several controllers.......................................... 15
Room unit ..................................................................58 use sensor input B70/B4 .......................................... 74
Rcksetzen der Zeitprogramme ................................49
W
running time stragety.......................................127, 129
weekday ................................................................... 37
S Weekday................................................................... 37
screw / plug-in strips..................................................11 winter- / summertime .............................................. 104
segment address.....................................................100 winter operation ........................................................ 45
segment controller.....................................................99 wiring ........................................................................ 16
with master function .............................................99

164/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Index 15.07.2002
Proof of change
The following changes have been made in this document compared to the last edition.
The page numbers are those of the present edition. The pages numbers are those of
the present edition.

Seite: nderung:
1 Old version: V2.0 from 22.09.1999 new version: V2.2 from 15.07.2002
8 Short description: Text changed
9 Features Group formed to heating circuit and heat generation
12 Range Burner controls: LGM... and OCI12 deleted, LMU and OCI42 inserted
22 Line No. 3 and 4 inserted
25 Footnote for lines 90-94
Lines 107 and 108 inserted
27 Footnote 1) inserted
29 Footnote for lines 1, 25-28
30 Footnote 1) inserted
39 Lines 3 and 4 description inserted
55 Example: Graphic and Note changed
83-85 Description for line 107 and 108 inserted
92 Effect for entry 3: Shifting/absolute priority description changed
130- Chapter "Automatic 24-hour heating limit" changed
134
161 Output relays Text deleted

165/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


HVAC Products Proof of change 15.07.2002
Siemens Building Technologies AG 1999 Siemens Building Technologies AG
HVAC Products nderungen vorbehalten
Gubelstrasse 22
CH 6301 Zug
Tel. 41 41-724 24 24
Fax 41 41-724 35 22
www.landisstaefa.com

166/166

Siemens Building Technologies Basic Documentation RVA47.320 CE1P2379E


Landis & Staefa Division 15.07.2002

You might also like