Rva47 B
Rva47 B
Rva47 B
320
Cascade Controller for modulating gas-fired Boilers
Basic Documentation
Ausgabe 2.2
Controller series B
CE1P2379E Siemens Building Technologies
15.07.2002 HVAC Products
2/166
2 Handling ........................................................................................................ 13
2.1 Installation ..................................................................................................... 13
2.1.1 Mounting location .......................................................................................... 13
2.1.2 Regulations for installation ............................................................................ 13
2.1.3 Mounting procedure....................................................................................... 13
2.1.4 Required cut-out ............................................................................................ 15
2.1.5 Orientation ..................................................................................................... 15
2.2 Electrical installation ...................................................................................... 16
2.2.1 Regulations for installation ............................................................................ 16
2.2.2 Wiring ............................................................................................................ 16
2.3 Commissioning .............................................................................................. 18
2.3.1 Functional checks.......................................................................................... 18
2.4 Parameter settings for the enduser ............................................................... 20
2.4.1 Overview of enduser parameters .................................................................. 21
2.5 Parameter settings for the heating engineer ................................................. 22
2.5.1 Overview of heating engineer parameters..................................................... 23
2.6 Parameter settings for the OEM .................................................................... 27
2.6.1 Overview of OEM parameters ....................................................................... 28
2.7 Operation....................................................................................................... 30
2.7.1 Operating elements ....................................................................................... 30
2.8 Operational faults .......................................................................................... 31
3/166
Service values................................................................................................................55
4.1 Output test .....................................................................................................55
4.2 Input test ........................................................................................................55
4.3 Display of plant type.......................................................................................56
4.4 Displaying the PPS communication ...............................................................58
Actual values..................................................................................................................60
4.5 Actual boiler temperature values of BMUs (TKx)...........................................60
4.6 Actual value of cascade flow temperature .....................................................60
4.7 Actual value of the cascade return temperature ............................................61
4.8 Actual value of buffer storage tank temperature ............................................63
4.9 Actual value of the d.h.w. temperature (TBWx) .............................................63
4.10 Attenuated outside temperature.....................................................................64
4.11 Composite outside temperature.....................................................................65
Setpoints . ..................................................................................................................66
4.12 Outside temperature source ..........................................................................66
4.13 Boiler temperature setpoint of BMUs .............................................................66
4.14 Setpoint of the cascade flow temperature......................................................67
4.15 D.h.w temperature setpoint............................................................................67
4.16 Nominal room temperature setpoint...............................................................68
4.17 Room temperature setpoint ...........................................................................69
4.18 Flow temperature setpoint .............................................................................69
Heat generation values ..................................................................................................70
4.19 Existing boilers...............................................................................................70
4.20 Display lead boiler..........................................................................................70
4.21 Remaining number of operating hours for changeover of boiler sequence ...71
4.22 Burner operating hours BMU 1 4 ................................................................72
4.23 Minimum limitation of the boiler temperature TKmin......................................72
4.24 Nominal output of BMU 1 - 4..........................................................................73
Configuration of plant .....................................................................................................74
4.25 Pump function output Q1 ...............................................................................74
4.26 Use sensor input B70/B4 ...............................................................................74
Heating circuit values .....................................................................................................76
4.27 Parallel displacement of the heating curve ....................................................76
4.28 Room influence ..............................................................................................76
4.29 Switching differential of the room temperature ..............................................77
4.30 Minimum limitation of the flow temperature setpoint......................................78
4.31 Maximum limitation of the flow temperature setpoint.....................................79
4.32 Type of building construction .........................................................................80
4.33 Adaption of the heating curve ........................................................................81
4/166
5/166
6/166
8 Dimensions.................................................................................................. 159
7/166
Heating circuit control uses weather compensation while d.h.w. heating operates
depending on the storage tank temperature and the time program.
Important When used in connection with gas-fired heating boilers, the availability of a BMU is
mandatory. Siemens offers different types of BMUs:
- Boiler Mangement Unit LMU5/6x
It is also possible to use BMUs of other manufacture if appropriately equipped. If you
intend to use a non-Siemens burner control in connection with the RVA47.230, please
contact your nearest Siemens representative.
Use in extensive systems The range of products comprises several units that complement one another in terms of
application and scope of functions. The controllers have communication capability and
can be combined to form heating systems that include up to 40 controllers.
For more detailed information about the generation of LPB systems, refer to "Local
Process Bus (LPB), Basic Documentation, System Engineering, document no.
CE1P2370E.
8/166
Heat generation Cascading with up to 12 modulating heat sources controlled by one controller in
combination with BMUs via LPB
Cascading with up to 15 modulating heat sources and additional RVA47.320 (from
B-series) via PPS
Control of mixed cascades (modulating or multistage) with up to 12 heat sources in
combination with RVA43.222 (from C-series) with BMUs via LPB
Selectable boiler sequence and boiler strategy
Weather-compensated heating circuit control with or without room influence
Cascade flow temperature control depending on the heat demand signal from the
heating circuits connected to the system or from controllers outside the system (via
input H1)
Cascade flow temperature control depending on the temperature demand signal
(DC 010 V, input H1)
Adjustable maximum limitation of temperature demand signals delivered to the
heating boiler
Performance-related switching on / off of boilers, very accurate flow temperatures
Supervision of operating conditions at the pressureless header, low return
temperatures
Protection for the plant Protection against boiler overtemperatures (pump overrun)
Protective boiler startup (acting on the mixing valve)
Minimum limitation of the boiler return temperature (acting on the mixing valve)
Adjustable minimum and maximum limitation of boiler temperature (boiler flow
temperature)
Frost protection for the building, the plant and the boiler
Frost protection for the d.h.w. storage tank connected directly to the controller
Pump protection through periodic pump kick
Overtemperature protection for the pump heating circuit
9/166
D.h.w. D.h.w. heating with charging pump or via BMU with diverting valve
D.h.w. control with temperature sensor or control thermostat
Selectable priority for d.h.w. heating
Selectable d.h.w. heating program
Adjustable boost of the d.h.w. charging temperature
Reduced setpoint of the d.h.w. temperature
Protection against discharging of d.h.w.
Automatic d.h.w. push
Legionella function
10/166
The following units and accessories are designed for use with the ALBATROS range:
Burner controls LMU5/6x Siemens BMUs for heating circuit and d.h.w. control
............. Different types of non-Siemens burner controls for d.h.w. control (e.g.
MCBA)
OCI42 Communication interface RVA-LMU5/6x
RMCI Communication interface RVA-MCBA
11/166
Types of buildings Residential and non-residential buildings with own heating and d.h.w. heating
facility
Residential and non-residential buildings with a central heat generating plant
The products may only be used in building services plant and applications as
described above
When using the products, all requirements specified in chapters "Handling" and
"Technical data" must be satisfied
When using the products in a system, all requirements contained in the
documentation Local Process Bus (LPB), Basic Documentation, System
Engineering (document no. CE1P2370E) must be satisfied
The local regulations for installation must be complied with
12/166
2.1 Installation
2.1.1 Mounting location
2379Z11
13/166
2379Z12
2379Z13
2379Z14
14/166
Due to the dimensions of the front, however, the standard spacing is 96 mm.
The mechanical mounting facility allows the controller to be fitted in front panels having
a thickness of 2 to 10 mm.
2371M02
96 96
2...10
+0.8
92 -0
96
+0.8 +0.8
92 -0 92 -0
188
2379Z15
2.1.5 Orientation
mm
2371Z16 10
15/166
2.2.2 Wiring
When using prefabricated cables with connectors, the electrical installation is very
straightforward, owing to the coding.
Connection terminals
6 5 4 M 2 1 M M
B70/B4
B10
MD
MB
DB
H1
A6
B3
B9
M F1
Q1
N
Q3
3 2 F 4 3 2 F L N
2379A01
Rear of controller
16/166
17/166
To facilitate commissioning and fault tracing, the controller allows output and input tests
to be made. With these tests, the controllers inputs and outputs can be checked.
Output test Buttons Explanation Line
(relays) 1
Press one of the line selection buttons.
This will take you to the programming level "Enduser.
2
Press both line selection buttons for at least 3 seconds.
4
You leave the programming line "Output test by contin.
pressing either one of the line selection buttons, display
Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating mode
selected last.
2379Z02
Display
a)
c) b)
0 4 8 12 16 20 24
18/166
2
Press both line selection buttons for at least 3
seconds.
This will take you to the programming level "Heating
engineer.
3
Press line selection button "Up" until you reach line
52.
5
You leave the programming line "Input test" by Contin.
pressing either one of the line selection buttons, display
Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.
The selected sensor values are updated within a maximum of 5 seconds. If no sensor
is present, the connecting line interrupted, or the contact open, the display shows "---;
in the event of a short-circuit, or if the contact is closed, the LCD displays "ooo.
Display
2379Z02
a) b)
0 4 8 12 16 20 24
c)
19/166
2
Press the line selection buttons to select the required
line.
The parameter list on the next pages contains all
available lines.
3
Press the + or - button to set the required value.
The setting will be stored as soon as you leave the
programming mode or change to another line.
The parameter list on the next 2 pages contains all
settings that can be made.
4
By pressing any of the operating mode buttons, you Contin.
leave the programming level "Enduser. display
Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.
20/166
Actual values
18 Actual value of the room temperature (TRx) 0...50 C 0,5 -
19 Actual value of the outside temperature (TAx) -50...+50 C 0,5 -
To set the attenuated outside temperature to Tax, press the + / -
buttons simultaneously for 3 seconds.
Maintenance
23 Standard time program for heating circuit and d.h.w. 0/1 - 1 0
To activate, press the + and - buttons simultaneously for 3 seconds
Time switch program for d.h.w. heating
29 preselection of weekday 1-7 / 1...7 Weekday 1 day -
1-7 7-day block
1...7 Individual days
30 Switch-on time 1. 3rd period d.h.w. 00:00...23:59 h / min 10 min 06:00
31 Switch-off time 1. 3rd period d.h.w. 00:00...23:59 h / min 10 min 22:00
32 Switch-on time 2. 3rd period d.h.w. 00:00...23:59 h / min 10 min - -:- -
33 Switch-off time 2. 3rd period d.h.w. 00:00...23:59 h / min 10 min - -:- -
34 Switch-on time 3. 3rd period d.h.w. 00:00...23:59 h / min 10 min - -:- -
35 Switch-off time 3. 3rd period d.h.w. 00:00...23:59 h / min 10 min - -:- -
Service
49 Indication of BMU error code 1...4 / 0...255 - 1 -
1...4 = BMU number, 1...255 = error code
50 indication of faults 0..255 / 00.0114.16 - 1 -
21/166
2
Press both line selection buttons for at least 3 seconds.
4
Press the + or - button to set the required value.
The setting will be stored as soon as you leave the
programming mode or change to another line.
The parameter list on the next 2 pages contains all
settings that can be made.
5
You leave the programming level "Heating engineer" by Contin.
pressing one of the operating mode buttons. display
Note:
If no button is pressed for about 8 minutes, the
controller will automatically return to the operating
mode selected last.
22/166
23/166
Space heating
100 parallel displacement of the heating curve -4.5...+4.5 K (C) 0,5 0,0
101 room influence 0/1 - 1 1
0 Inactive
1 Active
102 Switching differential of the room temperature (SDR) - - . - / 0.5...4.0 K (C) 0,5 --.-
--.- Inactive
0,5...4,0 Active
103 Minimum limitation of the flow temperature setpoint 8...Tvmax C 1 8
(TVmin)
TVmax Line 104
108 Maximum forward shift of optimum stop control 00:00...06:00 hh:mm 10 min 00:00
0 No forward shift
D.h.w.
120 Reduced setpoint of d.h.w. temperature (TBWR) 8...TBWw C 1 40
TBWw Line 13
24/166
25/166
1)
If a BMU is connected via LPB, this setting will not be active.
The respective setting must be made directly on the BMU.
26/166
Note:
If no button is pressed for about 8 minutes, the controller
will automatically return to the operating mode selected
last.
Example
2379Z02
0 4 8 12 16 20 24
Whether correct or incorrect, each push of a button represents irrevocably a digit of the
code.
As a confirmation, the respective digit changes to 1.
27/166
28/166
1)
If a BMU is connected via LPB, this setting will not be active.
The respective setting is to be made directly on the BMU.
29/166
2379Z01
Display
2379Z02B
a)
c) b)
d)
0 4 8 12 16 20 24
a) Symbols for indicating the operational status with the black bars (level pointers)
When the ECO function is active, the current level pointer flashes.
b) Display during normal control mode or when making settings
c) Programming line when making settings.
d) Time bar for normal control mode or when making settings.
30/166
31/166
User interface
3.1 Heating circuit operating modes
Description The control provides 3 different heating circuit operating modes that can be directly
selected as required.
Setting Select the required operating mode by pressing the respective operating mode button.
It is located on the controller front for direct access by the user.
32/166
Effect of room unit Changeover of the operating mode on the room unit is active only if the controller is in
automatic mode .
The room temperature is transmitted to the controller via PPS, independent of the
selected operating mode.
Description D.h.w. heating can be switched on and off independent of the other operating modes.
Setting D.h.w. heating is selected by pressing the respective button on the controller's user
interface.
33/166
Note The d.h.w. values that can be adjusted on the controller apply to both d.h.w. heating by
the controller and d.h.w. heating by a BMU supplied by Landis & Staefa. Some BMUs
of other manufacture also support this function.
Description The heating system uses 3 different setpoints that can be adjusted:
The nominal room temperature setpoint described here
The reduced room temperature setpoint (setting on line 14)
The frost protection setpoint of the room temperature (setting on operating line 15)
Setting The nominal room temperature setpoint is preadjusted with the setpoint knob. It is
located on the controller front for direct access by the user.
8...26 C 20
2379Z17
0 2 4 6 8 10 12 14 16 18 20 22 24 26 C
Room temperature setpoint setting ranges
14 Setting "Reduced room temperature setpoint
15 Setting "Frost protection setpoint of the room temperature
Effect of temperature When the nominal room temperature setpoint is active, the rooms will be heated
setting according to the adjustment made with the setpoint knob.
Effect in the various operating modes:
34/166
Note The adjustment made with the setpoint knob has priority over the reduced room
temperature setpoint entered (line 14). Especially in a situation when the adjustment
made with the knob is lower.
Example During the heating periods, the nominal room temperature setpoint is maintained. The
heating periods are in accordance with the settings made on lines 6 to 11.
Mo
...
So
2373Z11
0 2 4 6 8 10 12 14 16 18 20 22 24 h
Room unit When using a room unit without setpoint readjustment (QAA50), the setpoint knob on
the controller acts as described above.
When using a room unit featuring setpoint readjustment (QAA70), the setpoint knob on
the controller is inactive. In that case, the nominal setpoint adjusted on the room unit
applies.
A connected room unit is active only when operating mode is selected on the
controller.
Description In operating mode Manual operation, the plant components on the consumer side
must be manually adjusted and monitored. The control functions of the unit are only
used for controlling the BMUs.
Common flow temperature The BMUs are released and use their boiler temperature sensor to control the
temperature at the level of the maximum limitation of the BMU setpoint (TKmax.)
Factory setting 80 C. The actual boiler temperatures are displayed on setting line 55.
Note When deactivating the function, the controller will automatically return to the operating
mode previously selected.
Effect As soon as manual operation is selected, all relays will switch to the following statuses:
35/166
2379Z02
0 4 8 12 16 20 24
36/166
Description To ensure proper operation of the heating program, the 24-hour time switch with the
time of day and weekday must be correctly set.
System time The time of day can be set from a remote location via the bus system, provided clock
operation is appropriately set. Also refer to clock operation on operating line 148.
Effect The controller's clock time is set in agreement with the correct time. This setting is
important to make certain the controllers heating program will operate correctly.
3.6 Weekday
1...7 Weekday
Effect The time of day will be set to the selected weekday. This setting is important to make
certain the controllers heating program will operate correctly.
37/166
Effect Day and month of the controller will be based on this setting. This setting of date is
important to make certain the controllers holiday program and summer- / wintertime
changeover will operate correctly.
3.8 Year
1999...2099 Year
Effect The year of the controller will be based on this setting. This setting of year is important
to make certain the controllers holiday program and summer- / wintertime changeover
will operate correctly.
38/166
Description The time switch program for space heating consists of the switching times that can be
entered for the weekdays or the 7-day block.
The time switch program for space heating and the time switch program for d.h.w.
heating operate independently of one another.
The heating program thus set becomes active when selecting automatic mode .
Important This setting must be made before the switching times are entered!
For every day on which other switching times shall apply, the preselection of the
individual day with subsequent entry of the switching times must be repeated
Effect This setting is used to select either the whole week (1-7) or individual days (1...7).
Entry of 1-7 7-day block
Entry of the switching times from operating line 6 to 11 is identical for every day from
Monday through Sunday.
Example:
Mo
...
So
2373Z11
0 2 4 6 8 10 12 14 16 18 20 22 24 h
Switching time for nominal setpoint
Switching time for reduced setpoint
39/166
The setting of the switching times from operating line 6 through 11 is entered only for
the individual day selected here.
Tip
First, choose the 7-day block (1-7) to enter the switching times that apply to the
majority of days; then, select the individual days (1...7) to make the required
adjustments.
Example:
237 3Z12
Mo
Di
Mi
Do
Fr
Sa
So
0 2 4 6 8 10 12 14 16 18 20 22 24 h
Description With this setting, you determine the switching times for space heating. At these
switching times, the temperature setpoints of the heating circuit change.
The heating program thus set becomes active when selecting automatic mode .
! Important First, select the weekday (operating line 5) for which the switching times shall be
entered!
Note The controller then makes a check to ensure the entries have been made in the correct
order.
Effect At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times the setpoints will be activated.
40/166
Effect of room unit When using a QAA70 room unit, the heating program will be acted upon. However, this
works only if operating mode AUTO is selected on the controller.
41/166
Setting 1. Press the operating line selection buttons to select line 13.
2. Press the + / buttons to adjust the nominal setpoint of the d.h.w. temperature.
Setting range Unit Factory setting
TBWR...TBWmax C 55
TBWR Reduced setpoint of d.h.w. temperature (setting on operating line 120)
TBWmax Maximum nominal setpoint of d.h.w. temperature (setting on line 40OEM)
2379Z16
Effect
D.h.w. temperature D.h.w. heating has 2 different setpoints that can be used:
setpoints
Nominal d.h.w. temperature setpoint: It ensures the d.h.w. temperature required
during main occupancy times
Reduced d.h.w. temperature setpoint (setting on operating line 120): it ensures the
d.h.w. temperature required during the main occupancy times.
D.h.w. charging The criteria required for releasing d.h.w. heating are defined by the settings made on
lines 121 and 123 and 124.
Note In the event of a sensor with a short-circuit (display - - - in input test, test step 1) the
d.h.w. will not be heated (protection against scalding).
42/166
Benefit Lower room temperatures during non-occupancy times, e.g. during the night
Energy savings
Description The heating system has 3 different setpoints that can be adjusted:
The reduced room temperature setpoint described here.
The nominal room temperature setpoint (to be adjusted with the setpoint knob).
The frost protection setpoint of the room temperature (setting on operating line 15)
Setting 1. Press the operating line selection buttons to select line 14.
2. Press the + / buttons to adjust the reduced room temperature setpoint.
Setting range Unit Factory setting
TRF...TRN C 16
TRF Frost protection setpoint of the room temperature (setting on line 15)
TRN Nominal room temperature setpoint (to be adjusted with the setpoint knob)
Note If the required temperature level cannot be set, the adjustment made with the setpoint
knob may be too low. It is not possible to set a value above the adjustment made with
the setpoint knob.
2379Z17
0 2 4 6 8 10 12 14 16 18 20 22 24 26 C
Effect With this setting, the reduced room temperature setpoint will change to the level called
for by reduced operation in the living rooms.
Example
Mo
...
So
2373Z11
0 2 4 6 8 10 12 14 16 18 20 22 24 h
The heating periods are in accordance with the settings made on lines 6 to 11.
43/166
Caution This function is ensured only when the heating plant operates properly!
Description This function prevents the room temperature from falling below the adjusted frost
protection setpoint.
Setting 1. Press the operating line selection buttons to select line 15.
2. Press the + / buttons to adjust the frost protection setpoint of the room
temperature.
Setting range Unit Factory setting
4...TRRw C 10
TRRw Reduced room temperature setpoint (setting on operating line 14)
Effect This setting will change the frost protection setpoint of the room temperature.
Frost protection for the In operating mode , the room temperature is prevented from falling below a certain
building level. This means that the frost protection setpoint of the room temperature will be
maintained.
2379Z17
0 2 4 6 8 10 12 14 16 18 20 22 24 26 C
Description The summer / winter changeover temperature is the criterion for automatic summer /
winter changeover of the heating plant.
44/166
8...30.0 C 17
Effect By changing the setting, the respective periods of time will be shortened or extended.
The change will only affect the heating circuit.
Entry:
Increase: Winter operation will start earlier
Summer operation will start later .
Notes The summer / winter changeover temperature can act either locally or on other devices
in the system (also refer to section "Effect of summer / winter changeover temperature")
(Also refer to "Effect of automatic summer / winter changeover" on operating line 91).
This function only acts in automatic mode and standby mode .
Level cursor flashes during summer operation.
Changeover To determine changeover, the setting of the summer / winter changeover temperature
( a fixed switching differential) is compared with the attenuated outside temperature.
Also refer to page 64.
T
C TAged
20
19
18 SoWi +1 C
17 SoWi
16 SoWi -1 C
H
2379D06
ON
OFF
0 5 10 15 t
45/166
Description The controller generates the flow temperature setpoint as a function of the selected
heating curve. For plants where the controllers cannot transmit their demand for heat
via LPB or input H1, the controller can generate a weather-compensated flow
temperature.
Setting 1. Press the operating line selection buttons to select line 17.
2. Press the + / - buttons to select the heating curve slope or - - . - einstellen.
Setting range Unit Factory setting
Effect By changing the setting, the slope of the heating curve will be increased or decreased
with the following effects:
Increase: The flow temperature will be raised when the outside temperature
drops
Decrease: The flow temperature will be raised less when the outside
temperature drops
Notes The setting of the heating curve slope (value from 2.5 to 40 or inactive - - - ) affects the
automatic generation of plant type (operating line 53).
An external demand for heat can be delivered to the controller via LPB (LPB-
compatible controllers) or input H1 (controllers of other manufacture). If several signals
are present, the controller will use the highest of them as the setpoint.
The heating curve Using the heating curve, the controller generates the flow temperature setpoint,
enabling the system to maintain a constant room temperature even without using a
room temperature sensor.
The steeper the slope of the heating curve, the higher the flow temperature setpoint at
low outside temperatures.
Note Comfort is considerably enhanced when using a room temperature sensor.
46/166
100
17,5
90
15
80
12,5
70
10
60
7,5
50
40 5
30 2,5
2000D07
20 10 0 -10 -20 -30 C
TA
TV Flow temperature
TA Composite outside temperature
47/166
Note All displays of actual values require the respective temperature detectors.
Setting 1. Press the operating line selection buttons to select line 18.
2. No setting can be made with the + / - buttons.
Display Unit
0...50 C C
Effect The temperature measured with the room unit will automatically be displayed on this
line.
Setting 1. Press the operating line selection buttons to select line 19.
2. No setting can be made with the + / - buttons.
Display Unit
- 50... + 50 C
Effect The temperature measured with the outside sensor will automatically be displayed on
this line.
Note For resetting the attenuated outside temperature to the actual room temperature, refer
to page " Attenuated outside temperature".
48/166
Benefit Straightforward resetting of all time switch programs to their standard values
Description The standard time program resets the time settings of all time switch programs. For this
purpose, the controller is supplied with non-volatile factory settings.
Setting 1. Press the operating line selection buttons to select line 23.
2. Press the + / - buttons for 3 seconds.
The standard time program is activated as soon as the display changes to 1.
Display Unit
0/1 -
Effect The time settings for the time switch programs will be overwritten with standard values.
This applies to the following settings:
Switching times of time switch program "heating circuit" ...
Switching times for d.h.w. program ...
Standard values
Switching point Setting line Standard time
Heating circuit D.h.w.
Period 1 ON 6 30 06 : 00
Period 1 OFF 7 31 22 : 00
Period 2 ON 8 32 :
Period 2 OFF 9 33 :
Period 3 ON 10 34 :
Period 3 OFF 11 35 :
49/166
Description The time switch program for d.h.w. consists of the switching times to be entered for the
weekdays or the 7-day block.
The time switch program for d.h.w. and the time switch program for space heating
operate independently of one another.
Important The time switch program is active only when, on operating line 121 (d.h.w. program),
setting 2 has been selected.
Description With this setting, you define the weekdays or the 7-day block for which the switching
times of the d.h.w. time switch program apply.
The time switch program thus set is activated by pressing the d.h.w. operating mode
button .
Setting 1. Press the operating line selection buttons to select line 29.
2. Press the + / - buttons to preselect the 7-day block or the individual day.
Setting range Unit
Important This setting must be made before the switching times are entered!
For every day on which other switching times shall apply, the preselection of the
individual day with subsequent entry of the switching times must be repeated
Effect This setting is used to select either the whole week (1-7) or individual days (1...7).
Entry:
1-7 7-day block: Entry of the switching times on lines 30 to 35 is identical for every
day from Monday through Sunday
1...7 Individual days: Entry of the switching times on lines 30 to 35 is made only for
the individual day selected here
Example: The principle is the same as that used with "Time switch program space heating" (refer
to the diagrams and tips on page 39).
Description This is the setting of the switching times for d.h.w. time switch program at which the
d.h.w. temperature setpoint will change.
The time switch program thus set is activated by pressing the d.h.w. operating mode
button .
50/166
! Important First, select the weekday for which the switching times shall be entered!
Note The controller then makes a check to ensure the entries have been made in the correct
order.
Effect At the times entered, the program will switch to the respective temperature setpoints.
The table below shows at what times the setpoints will be activated.
Entry:
51/166
Setting 1. Press the operating line selection buttons to select operating line 49.
2. Press the + / - buttons to interrogate the individual BMUs.
Display Unit
Effect The number of the lowest connected BMU number containing a fault entry will
automatically be displayed on this line.
Note Error messages cannot be acknowledged. They disappear only if the appropriate fault
has been rectified.
Display The display shows the BMU number and the associated error code. When none of the
BMUs delivers a fault status signal, or when no BMU is connected, there will be no
display.
The meaning of the different error codes depends of the make of BMU used. For this
reason, no overview of all the different error codes can be given here. For details,
please refer to the technical documentation of the relevant product.
Example:
2379Z02
0 4 8 12 16 20 24
Note If there is a BMU error code, operating line 50 also displays a general BMU error (error
code 150).
52/166
Description The controller indicates faults that may have occurred in the controller itself or in the
system.
The display shows "Er" if an error has occurred.
Setting 1. Press the operating line selection buttons to select line 50.
2. Press the + / - buttons to display the list of faults.
Display Unit
0...255 -
Effect The first entry in the error list will automatically be displayed on this operating line.
Note By pressing , it is possible to switch between error signals.
Error signals The controller can store a maximum of 2 error signals. The error signal will be cleared
only after the cause of the fault has been removed. If additional errors are present, they
will be stored as soon as storage capacity becomes available.
Device errors Errors that may occur locally on this device:
Note In the case of error code 150, operating line 49 also gives the manufacturer-specific
error code of the BMU.
53/166
Example:
2379Z02
0 4 8 12 16 20 24
54/166
Service values
4.1 Output test
Description Also termed relay test, which is used to check the wiring and the configuration.
Setting 1. Press the operating line selection buttons to select operating line 51.
2. Press the + / - buttons to run through the output test.
Setting range Unit Factory setting
0...3 Increment 0
Effect The output test will automatically become available on this operating line.
With each test step, the respective output will be activated so that it can be checked.
Test sequence The test sequence is arranged in the form of a ring counter. This means it can be run
through either forward or backward by pressing the + / - buttons.
Test step 0 All outputs are switched according to actual control operation
Description Also termed detector test, which is used to check the wiring and the configuration.
Setting 1. Press the operating line selection buttons to select operating line 52.
2. Press the + / - buttons to run through the input test.
Setting range Unit Factory setting
0...5 Increment 0
Effect The input test will automatically become available on this operating line.
With each test step, the respective input will be displayed so that it can be checked.
Test sequence The test sequence is arranged in the form of a ring counter. This means it can be run
through either forward or backward by pressing the + / - buttons.
55/166
Test step 4 Display of room temperature acquired with room unit connected to
A6
Setting 1. Press the operating line selection buttons to select operating line 53.
2. No setting can be made with the + / - buttons.
Display Unit
0, 27...36, 65...67 -
Effect The number of the current plant type will automatically be displayed on this line.
0 Invalid configuration of plant
The following factors have an impact on the generation of the type of plant:
56/166
x means that the setting has no influence on the generation of plant type.
Note If the heating curve is deactivated (setting ---), the controller requires an external heat
demand signal to release the generation of heat. An external demand for heat can be
transmitted to the controller via LPB (LPB capable controllers) or input H1. If several
signals are present, the controller will use the highest of them as the setpoint.
The following settings are invalid, therefore producing fault message 58 (demand from
thermostat, but sensor used):
Plant type- Slope of heating Pump function Type of d.h.w. D.h.w. sensor
number curve (output Q1) demand connected to:
BMU RVA
x means that the setting has no influence on the generation of the type of plant.
57/166
Description PPS is a point-to-point interface for communication between controller, BMU and room
unit. The display provides information about the communication status and the types of
connected peripheral devices.
Setting 1. Press the operating line selection buttons to select operating line 54.
2. Press the + / - buttons to interrogate the various PPS users.
Display Unit
No communication
1...12 / 0...255 PPS address / identification code
ooo Short-circuit of communication line
Effect The status of the PPS communication will automatically be displayed on this line. If
communication is error-free, the controller identifies the unit connected by displaying
the identification number, in addition to the device address.
Displays The display is comprised of PPS address and a device identification code.
PPS-address Within the PPS, a fixed PPS address is assigned to some types of devices:
Room unit 1
BMU-Nummer 1 4
BMU-Nummer 2 5
BMU-Nummer 3 6
BMU-Nummer 4 7
Note These peripheral devices can only be operated under the respective PPS address. If
one of these devices is not used, the PPS address can be allocated to some other
peripheral device.
Assignment of all the other peripheral devices to the PPS addresses can be made
randomly.
Since every controller has a specific and confined PPS address space, the same PPS
addresses can be assigned to each device.
58/166
Notes When the LCD displays a PPS address with an identification code, the
communication with the respective device is error-free
When the LCD displays no PPS address and no identification code, there is no
communication or it is faulty
Incompatible devices are also displayed, but produce error code 145 (operating line
50)
59/166
Effect The lowest connected BMU number with the associated temperature will automatically
be displayed on this line. The temperatures of the other cascaded heating boilers can
be interrogated by pressing the + / - buttons. Non-existing BMUs will be skipped.
Note The cascade boilers displayed are only those connected to this controller. If there are
additional cascaded boilers, they will be displayed on the controllers to which they are
physically connected.
Special displays: In place of the temperature, the following displays can appear next to the BMU number:
Sensor with an open-circuit or no sensor connected
000 Sensor with short-circuit
Note If the LCD displays without giving an associated BMU number, there is no BMU
connected to the controller.
Description When using several cascaded heat sources, a cascade flow temperature sensor (B10)
must be installed.
Also termed "Common flow temperature sensor.
Setting 1. Press the operating line selection buttons to select operating line 56.
2. No setting can be made with the + / - buttons.
Display Unit
0...140 C
Effect The temperature measured with the cascade flow temperature sensor (B10) will
automatically be displayed on this line.
Cascade flow In a cascaded system, a common cascade flow temperature sensor (B10) is used for
temperature sensor all heat sources.
The cascade temperature sensor (B10) is connected directly to the RVA47.320.
60/166
1 2 3 4
B70
2379S27
B10 Cascade flow temperature sensor
Description When using several cascaded heat sources, we recommend to use a cascade return
temperature sensor (B70).
It is also termed "Common return temperature sensor.
Setting 1. Press the operating line selection buttons to select operating line 57.
2. No setting can be made with the + / - buttons.
Display Unit
0...140 C
Effect The temperature measured with the cascade return temperature sensor (B70) will
automatically be displayed on this line.
Cascade return In a cascaded system, a common cascade return temperature sensor (B70) should be
temperature sensor used for all heat sources. The value of this sensor is used for optimizing the controllers
functionality. In particular, it permits the detection of wrong mass flows (primary /
secondary mass flow).
The cascade return temperature sensor is connected directly to the RVA47.320.
61/166
1 2 3 4
B70
2379S27
B70 Cascade return temperature sensor
Important The meaning of the temperature measured at B70/B4 is defined by setting 1 (cascade
return temperature sensor) on operating line 97.
62/166
Description When using alternative heat sources, the buffer storage tank temperature is used as a
control criterion for the release of additional heat sources.
Setting 1. Press the operating line selection buttons to select operating line 58.
2. No setting can be made with the + / - buttons.
Display Unit
0...140 C
Effect The actual temperature in the buffer storage tank (B4) will automatically be displayed
on this line.
Important To be used as a buffer storage tank temperature sensor, input B70/B4 must be
appropriately defined (operating line 97, setting 2)
Note If input B70/B4 of the first cascade controller is already used by the optional cascade
return temperature sensor B70, buffer storage tank temperature sensor B4 can be
connected to input B70/B4 of the second controller.
Setting 1. Press the operating line selection buttons to select operating line 59.
2. No setting can be made with the + / - buttons.
Display Unit
0...140 C
Effect The temperature measured with the d.h.w. temperature sensor (B3) connected to the
controller, or the d.h.w. temperature transmitted by the BMU via PPS will automatically
be displayed on this line.
Note With the type of d.h.w. demand Thermostat (line 125), there will be no temperature
display of course. The display shows --- . The input test (line 52, test step 1)
provides information about the current switching status of the thermostat.
63/166
Description
The attenuated outside temperature is the simulated room temperature of a fictive
building that has no internal heat source. This means that it is only the outside
temperature that affects the room temperature.
Setting This operating line automatically displays the actual value [C] of the attenuated outside
temperature. No direct setting can be made.
The generation of the attenuated outside temperature cannot be influenced.
Display Unit
-50...50 C
Example TAakt
TA
C
17
16
15 TAged
14
13
2371D11
64/166
Description The composite outside temperature is a mixture of the actual outside temperature and
the attenuated outside temperature calculated by the controller.
Setting This operating line automatically displays the actual value [C] of the composite outside
temperature. No direct setting can be made.
Display Unit
-50...50 C
Process The mixture of actual and attenuated outside temperature is dependent on the type of
building construction (setting 105) and is generated as follows:
Example TAakt
TA
C TAgem1
TAgem0
17
16
TAged
15
14
13
2371D12
65/166
Description When interconnecting several controllers, only one outside sensor is required. This
sensor will be connected to any of the controllers and delivers its signal via LPB.
The controllers to which no sensor is connected adopt the outside temperature signal
via the bus system, from a controller to which a sensor is connected.
Setting 1. Press the operating line selection buttons to select operating line 62.
2. No setting can be made with the + / - buttons.
Display Unit
. No signal
00.01...14.16 Segment and device address
Effect The address of the outside detector that currently delivers the outside temperature
signal will automatically be displayed on this line.
Note If required (e.g. due to different exposure to solar radiation of the various buildings), the
different sections of the system can be equipped with their own outside sensors.
For more detailed information, refer to section Outside temperature source of Local
Process Bus (LPB), Basic Documentation, System Engineering (document no.
CE1P2370E).
Description The lowest connected BMU number with the associated temperature setpoint will
automatically be displayed on this line. The temperature setpoints of the other BMUs
used in the cascade can be interrogated by pressing the + / - buttons. Nonexisting
BMUs will be skipped.
Setting 1. Press the operating line selection buttons to select line 65.
2. Press the + / - buttons to select the setpoint of the required BMU.
Display Unit
66/166
Description The setpoint of the cascade flow temperature will automatically be displayed on this
line.
Setting 1. Press the operating line selection buttons to select line 66.
2. No setting can be made with the + / - buttons.
Display Unit
0...140 C
The setpoint can only be displayed, but not changed. The function helps better
understand the control sequences taking place in the controller.
Generation of setpoint The setpoint displayed is generated based on the different heat demand signals
received from the system. These are:
Demand for heat from the controllers internal heating circuits based on the outside
temperature
Demand for heat from the external heating circuits (system) based on the outside
temperature
Demand for heat for d.h.w. (from inside the controller or externally)
Demand for heat via contact H1
Demand for heat resulting from protective functions (e.g. frost protection for the
plant)
Demand for heat by pressing the button for manual operation
The highest of the setpoints received is shown on the display as the setpoint of the
cascade flow temperature.
Note The display shows --- if one of the following points applies:
Description The current d.h.w. temperature setpoint will automatically be displayed on this line.
Setting 1. Press the operating line selection buttons to select line 69.
2. No setting can be made with the + / - buttons.
Display Unit
0...140 C
67/166
Benefit Information about the nominal room temperature setpoint in normal operation
Description Displays the current nominal room temperature setpoint during the comfort period.
The nominal room temperature setpoint is the temperature adjusted on the controller
that shall be maintained in the rooms in normal operation (comfort).
Setting 1. Press the operating line selection buttons to select operating line 70.
2. No setting can be made with the + / - buttons.
Display Unit
0.0...35.0 C
Effect The nominal room temperature setpoint will automatically be displayed on this
operating line.
Nominal room The resulting nominal room temperature setpoint is made up of the adjusted setpoint
temperature setpoint and a readjustment that may have been made on the room unit:
68/166
Benefit Information about the room temperature setpoint in the various operating modes
Description Displays the current room temperature setpoint during the respective heating period
(normal operation / reduced operation).
Setting 1. Press the operating line selection buttons to select line 71.
2. No setting can be made with the + / - buttons.
Display Unit
0...35 C
When selecting the operating line, the current room temperature setpoint is displayed,
depending on the operating mode and the time switch program, that is, a selection /
combination of the following parameters:
Room temperature setpoint knob
Reduced setpoint of room temperature (operating line 13)
Frost protection setpoint of room temperature (operating line 15)
Readjustments made on the room unit (QAA50 / QAA70)
Benefit Displays the current flow temperature setpoint of the pump heating circuit
Description When selecting this operating line, the current flow temperature setpoint of the
controllers internal pump heating circuit is displayed.
Setting 1. Press the operating line selection buttons to select line 72.
2. No setting can be made with the + / - buttons.
Display Unit
0...140 C
The value displayed corresponds to the flow temperature of the pump heating circuit
which is required for reducing the demand for heat.
69/166
Description The function makes it possible to obtain a quick overview of the boilers used by the
system.
Setting 1. Press the operating line selection buttons to select line 75.
2. Press the + / - buttons to scroll through the list of available boilers.
Display Unit
00.1...16.3 -
Caution! Do not mix up device / device subaddress and segment / device address!
If the segment address was added, the display would read 0.00.1 ... 0.16.3.
Device address A controller that uses device address 0 (e.g. 00.1) operates autonomously ( no
communication via LPB).
The device address 1 (01.1) defines the cascade master (controller).
Device subaddress Up to four BMUs can be connected to the first RVA47.320 (B-series) of a cascade, and
up to three BMUs to each of the additional RVA47.320 (B-series).
The possible device subaddresses are therefore 1.1 ... 1.4, 2.1 ... 2.3, 3.1 ... 3.3
through 16.3 One cascade can contain a maximum of 16 boilers, however.
For more detailed information, refer to Local Process Bus (LPB), Basic
Documentation, System Engineering (document no. CE1P2370E).
Description With Automatic lead boiler changeover, this function facilitates quick identification of
the current lead boiler.
Display When selecting this operating line, the current lead boiler is displayed. No settings can
be made with the + / buttons.
Display Unit
00.1...16.3 -
70/166
Caution! Do not mix up device / device subaddress and segment / device address!
If the segment address was added, the display would read 0.00.1 ... 0.16.3.
Device address A controller that uses device address 0 (e.g. 00.1) operates autonomously ( no
communication via LPB).
The device address 1 (01.1) defines the cascade master (controller).
Device subaddress Up to four BMUs can be connected to the first RVA47.320 (B-series) of a cascade, and
up to three BMUs to each of the additional RVA47.320 (B-series).
The possible device subaddresses are therefore 1.1 ... 1.4, 2.1 ... 2.3, 3.1 ... 3.3
through 16.3 One cascade can contain a maximum of 16 boilers, however.
Note The setting for boiler sequence changeover is made on operating line 130.
For more detailed information, refer to Local Process Bus (LPB), Basic
Documentation, System Engineering (document no. CE1P2370E).
Benefit Indication of the remaining number of operating hours until the next changeover of
boiler sequence takes place.
Description Indicates the number of hours the current lead boiler still operates until the next
changeover of boiler sequence occurs.
Setting When selecting this operating line, the remaining number of operating hours for
changeover of the boiler sequence are displayed.
Display Unit
Display The number displayed represents the number of operating hours until the next
changeover of boiler sequence occurs. It is generated by subtracting the current
number of operating hours from the setting made on operating line 130 (automatic
changeover according to the number of operating hours).
Note The display appears only if, on operating line 130, a setting of 10990h has been
selected (automatic changeover according to the number of operating hours).
Otherwise, the display will show "- - -.
71/166
Benefit Overview of the number of burner operating hours of the individual BMUs
Criterion for service and maintenance work
Criterion for adjusting the cascade management strategy
Description The display shows the number of hours the respective BMU has been operating since
the controller was first commissioned.
Display Unit
0...65535 h
Note For information about the selection of the cascade management strategy, refer to
operating lines 50OEM to 52OEM.
Benefit This function prevents the boiler temperature from falling below a predefined
minimum temperature.
Description Minimum limitation of the boiler temperature setpoint is a protective function for the
boiler. In addition, minimum limitation of the setting range can be provided with the
setting 01OEM.
Setting 1. Press the operating line selection buttons to select line 90.
2. Press the + / - buttons to set the minimum limitation of the boiler temperature
TKmin.
TV
2371Z22
max
akt
min
0 10 20 30 40 50 60 70 80 90 100 120 C
72/166
Effect If the boiler temperature falls below the set minimum temperature, this setting
generates a locking signal which reduces the amount of heat supplied to the
consumers.
Description By setting this paramter, the controller knows the proportion of capacities of the
connected boilers and can take this into account with the running time strategy and the
linked lead boiler operation (refer to page 114 ff.).
Note The controller only uses the proportions of the numbers entered. When having
capacities of 100 / 150 / 70 kW, entry of the proportions of 10 / 15 / 7 or 20 / 30 / 14 will
lead to the same result as entry of the absolute figures. Hence, capacities above 255
kW can also be entered by using the respective ratios.
Effect This setting has an impact on the accuracy of the points in time the individual boilers
are switched on and off (refer to boiler management and running time strategy,
operating line 50OEM).
Autonomous lead boiler operation:
No effect
73/166
Description This parameter defines the function provided by the pump connected to terminal Q1.
Note Setting of this function has an impact on automatic generation of the type of plant.
Operating line 53.
Setting 1. Press the operating line selection buttons to select operating line 95.
2. Press the + / - buttons to select the required function of the circulating pump.
Setting range Unit Factory setting
1...5 - 1
Effect The pump provides one of the following functions, depending on the setting made:
Pump overrun is active with all settings, with the exception of setting 4.
Benefit The same sensor input can be used for different functions
Description This parameter setting defines the function adopted by the temperature sensor
connected to terminal B70/B4.
Setting 1. Press the operating line selection buttons to select operating line 97.
2. Press the + / - buttons to select the required function of the input B70/B4.
Setting range Unit Factory setting
1...2 - 1
Effect Depending on the setting made, the sensor provides the following function:
2 The sensor is used for measuring the buffer storage tank temperature (B4).
Use in cascades If, with the first controller, sensor input B70/B4 is defined for use with a return
temperature sensor (B70), for instance, it can be defined with another controller of the
74/166
Use as a buffer storage When using input B70/B4 for a buffer storage tank temperature sensor (B4), the
tank temperature sensor temperature measured at B4 is used to decide whether the consumers receive their
heat from the cascade or from the buffer storage tank.
If the temperature measured in the buffer storage tank is higher than the flow
temperature called for by the consumers, the cascade will be locked and the
consumers receive their heat from the buffer storage tank.
If the temperature measured in the buffer storage tank is lower than the flow
temperature called for by the consuemrs, the buffer storage tank will be locked and the
consumers receive their heat solely from the cascade.
Example Example of a hydraulic circuit with a buffer storage tank. The buffer storage tank can be
charged by any type of heat source (wood-fired boiler, solar collectors, heat pump, etc).
B9 V
B10 FK
B4
1 2
FK
SK
SK
B70
2379S37
V
SK = solar collectors
FK = solid fuel boiler
V = consumer
Connection of diverting The changeover valve must be connected in parallel to the pump of the first BMU. This
valve BMU must be excluded from automatic changeover of the boiler sequence (refer to
operating line 131).
75/166
Description Produces a parallel displacement of the heating curve in order to achieve a better
match of room temperature setpoints and actual room temperatures.
Setting 1. Press the operating line selection buttons to select operating line 100.
2. Press the + / buttons to set the parallel displacement..
Setting range Unit Factory setting
Effect By changing the value entered, all room temperature setpoints will be appropriately
raised or lowered. This allows the room temperature setpoints to be matched to the
effective room temperatures.
Example: If a nominal room temperature setpoint of 20 C adjusted on the controller always
produces a room temperature of 22 C (independent of the prevailing outside
temperature), displace the heating curve downward by 2 C.
Parallel displacement Each setpoint readjustment, be it by changing the setting value or the operational level,
corresponds to a parallel displacement of the heating curve.
TV
C
100
90
80
70
60
50
40
2406D02
30 30
0 TR
0 w
TV Flow temperature
TA Composite outside temperature
TRw Room temperature setpoint
Benefit More accurate room temperature control due to temperature checkback signal from
the space
Use of heat gains
Possibility of boost heating and quick setback
76/166
Setting 1. Press the operating line selection buttons to select operating line 101.
2. Press the + / buttons to select the room influence.
0/1 Increment 1
Effect The setting will activate or deactivate the effect of room temperature deviations on the
temperature control.
Entry:
1 Room temperature influence active: The measured room temperature will affect
the temperature control
To use the control variant "Weather compensation with room influence", the following
conditions must be satisfied:
An outside sensor must be connected (either to B9, the PPS or the LPB).
Setting "Room temperature influence" (101) must be active (1)
The respective room unit must be connected to terminal A6 (PPS)
There may be no controlled thermostatic radiator valves
(If such valves are present, they must be set to their fully open position).
Setting 1. Press the operating line selection buttons to select operating line 102.
2. Press the + / buttons to set the room temperature switching differential.
. - .
0.5...4.0 C
77/166
Room temperature With pump heating circuits, the amount of heat supplied is controlled by switching the
control pumps on and off. This is accomplished with two-position control by means of the room
temperature's switching differential.
2371D02
P
OFF
Switching differential
TRx Actual value of the room temperature
TRw Room
P temperature setpoint
SDR Switching
differential of room temperature
ON P Pump (ON / OFF)
w Setpoint
Switch-on point
2379Z19
Switch-off point
OFF
w
TRx [C ]
Description Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.
78/166
8...TVmax C 8
TVmax Maximum limitation of flow temperature setpoint (setting on operating line 104)
TV
2379Z09
max
TVw
akt
min
0 10 20 30 40 50 60 70 80 90 100 C
Effect The setting will make certain that the flow temperature setpoint will not fall below a
minimum level.
Limitation If the flow temperature setpoint demanded by the heating circuit reaches the minimum
limit and the outside temperature rises, the flow temperature setpoint will be maintained
at that limit, in other words, it will not be allowed to fall below it.
Description Minimum and maximum limitation define the range within which the flow temperature
setpoint may vary.
Setting 1. Press the operating line selection buttons to select operating line 104.
2. Press the + / - buttons to set the maximum limitation of the flow temperature
setpoint.
Setting range Unit Factory setting
TVmin...95 C 80
Tvmin Minimum limitation of flow temperature setpoint (setting on operating line 103)
79/166
2379Z09
max
TVw
akt
min
0 10 20 30 40 50 60 70 80 90 100 C
Effect The setting will ensure that the flow temperature setpoint will not exceed a maximum
level.
Important Maximum limitation is not to be regarded as a safety function as required with
underfloor heating systems, for example.
Limitation If the flow temperature setpoint demanded by a consumer reaches the maximum limit
and the outside temperature falls, the flow temperature setpoint will be maintained at
that limit, in other words, it will not be allowed to exceed it.
Description Enables the control system's response to be matched to the type of building
construction.
Setting 1. Press the operating line selection buttons to select operating line 105.
2. Press the + / buttons to select the type of building construction.
0/1 Increment 1
Effect When the outside temperature varies, the room temperature changes at different rates,
depending on the building's thermal storage capacity.
The above setting ensures that the generation of the composite outside temperature
will be matched to the type of building construction. Also refer to "Composite outside
temperature in section "Functions without settings".
Entry:
0 Heavy building structures: The room temperature will respond slower to outside
temperature variations
1 Light building structures: The room temperature will respond quicker to outside
temperature variations
80/166
Description The adaption facility learns from the different heating situations and matches the control
to the heating circuit at regular intervals. Also refer to section Adaption sensitivities
(lines 36 OEM + 37OEM).
Setting 1. Press the operating line selection buttons to select operating line 106.
2. Press the + / buttons to select the type of heating curve adaption.
0/1 Increment 1
Effect The setting will switch automatic adaption of the heating curve on or off.
Entry:
0 Automatic adaption inactive: The heating curve will use the setting made
Adaption The adaption facility automatically matches the heating curve to the type of building
construction and the heating requirements. Adaption gives consideration to room
temperature deviations, outside temperature characteristics and adaption sensitivity.
Note To achieve optimum adaption, the following situations should occur as rarely as
possible - especially after commissioning - since this would reset certain calculations
required for the adaption:
Manual correction of heating curve
Power failure
Heating curve set to --.-
Changes to the room temperature setpoint
Process Every day at midnight, the room temperature control differential of the previous day is
evaluated. This evaluation leads to an automatic readjustment of the heating curve.
Simple adaption (range ):
At attenuated outside temperatures below 4 C, it is only the slope of the heating
curve that is adapted.
Within this temperature range, the readjustment is weighted with the factor f2 and
adaption sensitivity 2 (line 37OEM).
81/166
No adaption (range ):
At attenuated outside temperatures above 12 C, the heating curve will not be
adapted.
f
1
f2
0,5
f1
2371D07
0
20 12 4 -4 -12
TAged
ZAF1 ZAF2
f Factor
f1 Factor for parallel displacement
f2 Factor for slope
TAged Attenuated outside temperature
ZAF1 Adaption sensitivity 1 (line 36OEM)
ZAF2 Adaption sensitivity 2 (line 37OEM)
Description Maximum forward shift is a limit function that defines the range of optimum start control.
82/166
During non-occupancy hours, the heating is maintained at the reduced level. Towards
the end of the nonoccupancy time, optimization switches the control back to the normal
level.
Optimization calculates the changeover time such that, at the start of occupancy, the
room temperature will have reached the nominal setpoint.
The composite outside temperature is used as the compensating variable. In the case
of floor heating systems, the maximum forward shift should be longer than with radiator
systems.
Using the parameter for the constant of quick setback and optimum start control (KON),
the forward shift can be matched the building dynamics.
Forward shift tE in hours and minutes with optimum start control without room
influence:
TAgem KON
0 4 8 12 16 20
- 20 0 1h20 2h40 4h00 5h20 6h00
- 10 0 0h50 1h50 2h40 3h40 4h30
0 0 0h30 1h00 1h30 2h00 2h30
+ 10 0 0 0h10 0h10 0h20 0h20
tE
The switch-on time for the heating (change to nominal level) is selected such that, at
the beginning of the occupancy time according to the heating program, the room
temperature reached will be the room temperature setpoint - 0.25 K.
The correct switch-on time is determined by adaption.
83/166
Description Maximum forward shift is a limit function that defines the range of optimum stop control.
Optimum stop control acts only when a room sensor is used and when room influence
is active.
The maximum forward shift can be set with parameter Maximum forward shift with
optimum stop control (range is 06 h). This parameter can also be used to switch
optimum stop control off (setting = 0).
During occupancy hours, the heating is maintained at the nominal level. Towards the
end of the occupancy time, the control switches to the reduced level.
Optimization calculates the changeover time such that, at the end of occupancy time,
the room temperature will be 0.5 C below the nominal setpoint (early shutdown).
Adaption takes place only with the first occupancy period per day. The switch-off point
is adapted in steps of 10 minutes. If the 0.25 K are not reached, the switch-off point is
shifted forward by 10 minutes (earlier shutdown). In the other case, the switch-off point
is shifted backward by 10 minutes (later shutdown).
84/166
Setting 1. Press the operating line selection buttons to select operating line 120.
2. Press the + / buttons to adjust the reduced setpoint of the d.h.w. temperature.
8...TBWw C 40
TBWw Nominal setpoint of d.h.w. temperature (setting on line 13)
Effect The temperature setpoint during reduced d.h.w. operation will be changed.
2379Z10a
0 10 20 30 40 50 60 70 80 90 100 120 130 140 C
D.h.w. temperature D.h.w. heating has 2 different setpoints that can be used:
setpoints
The periods of time during which these d.h.w. temperature setpoints shall be used can
be set on line 121.
Benefit Release of d.h.w. heating to the nominal setpoint as demanded by the consumers
Release of d.h.w. heating can be matched to the plant's load curve
Description Makes it possible to limit the period of time during which d.h.w. heating at the nominal
setpoint is released.
85/166
0...2 Increment 1
Effect The setting defines the period of time during which d.h.w. heating at the nominal
setpoint is released. Outside this period of time, the reduced d.h.w. setpoint applies.
There is one exception, however, function d.h.w. push (function with no setting).
Release of d.h.w. heating to the nominal setpoint takes place when using the following
settings:
0 24 hours per day
1 According to the heating circuit time switch program)s) with forward shift
Note The frost protection temperature for d.h.w. is fixed at 5 C and is always active.
2371Z18
Example:
0 6 12 18 24 h
For d.h.w. heating, the heating circuit time switch programs of the controllers in the
selected range are taken into consideration. The selection of the range (local / segment
/ system) for which the d.h.w. is produced is made on operating line 123.
The switch-on point for the release is shifted forward in time against the earliest switch-
on point of all heating circuits. The switch-off point for the release coincides with the
last switch-off point of all heating circuits.
At the switch-on point, the controller switches from the reduced d.h.w. temperature
setpoint (operating line 120) to the nominal d.h.w. temperature setpoint (operating line
13).
At the switch-off point, the controller switches from the nominal to the reduced d.h.w.
temperature setpoint.
86/166
2379Z29
Example:
0 5 6 12 16 17 24 h
For d.h.w. heating, time switch program (d.h.w.) of the local controller is taken into
account. The set switching times of that program are then used to change over
between the nominal d.h.w. setpoint (operating line 13) and the reduced d.h.w. setpoint
(operating line 120).
D.h.w. heating takes place independent of the heating circuit programs.
Heating periods With this d.h.w. heating program, it is possible to have a maximum of 3 heating periods
per day. The forward shift of the switch-on times is inactive.
2373Z24
Example:
0 6 12 18 24 h
Benefit The circulating pump runs only during the selected periods of time
No heat losses during the periods of time when there is no demand for d.h.w.
Description Defines the time switch program according to which the circulating pump is switched on
and off.
Setting 1. Press the operating line selection buttons to select operating line 122.
2. Press the + / - buttons to select the required time switch program.
Setting range Unit Factory setting
0...1 Increment 1
Effect Depending on the setting made, the circulating pump will be operated according to the
following time switch program:
0 For the switching program of the circulating pump, the switching program of the
controller internal heating circuit will be adopted.
1 Switching program according to the selected d.h.w. release (operating line 121).
87/166
Description Determines the consumers for which d.h.w. will be heated and which time switch
programs will be appropriately considered, also checking whether the relevant
controllers are in holiday mode.
Setting 1. Press the operating line selection buttons to select operating line 123.
2. Press the + / buttons to select the required assignment.
Setting range Unit Factory setting
0...2 Increment 2
Effect Depending on the selection made, the d.h.w. will be heated for the following
consumers:
0 For the local consumer only (RVA47.320)
In the case of d.h.w. heating according to the heating circuit time switch program
(operating line 121, setting 1), the time switch programs are used from the appropriate
range for the release of d.h.w. heating at the nominal temperature setpoint, based on
the consumers selected here.
With all settings (operating line 121, setting 0 - 2), it is checked whether the controllers
of the selected range are in holiday mode. Controllers in holiday mode will not be
considered for d.h.w. heating.
Important If all controllers in the selected range are in holiday mode, d.h.w. heating will not be
released. Only the frost protection function will remain active (function with no setting).
Description With this setting, d.h.w. heating can be reduced to one charging cycle per day. The
forward shift of d.h.w. heating against the range selected on operating line 123 will be
appropriately adjusted.
Note This setting is effective only if, on operating line 121, setting 1 (according to the heating
circuit time switch program(s)) has been selected.
Setting 1. Press the operating line selection buttons to select operating line 124.
2. Press the + / - buttons to select the type of d.h.w. heating.
0...1 Increment 1
88/166
The number of daily releases for d.h.w. heating at the nominal temperature setpoint is
limited to one. Also with this setting, the switch-on point is shifted forward by 2.5 hours
against the range selected on line 123.
On days where space heating at the nominal room temperature setpoint is provided for
24 hours, d.h.w. heating is released at midnight for 2.5 hours.
The number of d.h.w. charging cycles will not be limited. Also with this setting, the
switch-on point is shifted forward by one hour against the range selected on line 123.
Benefit Possibility of using a d.h.w. storage tanks equipped with a control thermostat
Description Defines the type of d.h.w. control (via d.h.w. sensor or control thermostat).
Note Setting of this function has an impact on automatic generation of the type of plant.
Operating line 53.
Setting 1. Press the operating line selection buttons to select operating line 125.
2. Press the + / - buttons to select the type of d.h.w. demand.
0/1 Increment 0
Effect By making this setting, the controller takes into account the signal fed to it by the d.h.w.
sensor connected to terminal B3.
Entry:
0: Sensor: the temperature measured with the sensor connected to terminal B3 is
used for the control of the d.h.w. temperature.
1: Control thermostat: the switching status of the control thermostat connected to
terminal B3 is used for the control of the d.h.w. temperature.
89/166
Note When using a d.h.w. control thermostat, reduced operation is not possible.
Important when using a The nominal d.h.w. temperature setpoint (operating line 13) must be equal to or
d.h.w. thermostat higher than the setpoint adjusted on the control thermostat (thermostat is calibrated
at switch-off point)
Boost of the flow temperature setpoint (setting on operating line 126) must be
minimum of 10 C (has an impact on the charging time)
In that case, frost protection for d.h.w. is not ensured
UEBW >= 10 C
60 C TBWw
T > 0 C
56 C
TRw
2371Z36
SD = 6 C
50 C TRw - SD
Description To allow the d.h.w. to be heated up, the boiler temperature must be higher than the
d.h.w. setpoint.
90/166
0...30 C (K) 16
Effect The setting will raise the boiler temperature setpoint when there is demand for d.h.w.
Increase: Heating up time will become shorter
More overshoot
boiler boost Using the two settings, the controller generates the boiler temperature setpoint for
d.h.w. heating.
Note For d.h.w. control, refer to section "Switching differential of d.h.w. temperature (line 41
OEM).
Setting 1. Press the operating line selection buttons to select line 127.
2. Press the + / - buttons to select the type of d.h.w. priority.
0...3 Increment 1
Effect During d.h.w. heating, space heating will be restricted, depending on the setting made.
Entry:
0 Absolute priority
The controller-internal heating circuit and the heating circuits of other controllers
connected to the LPB will be locked until the d.h.w. is heated up. The system
pump remains in operation.
91/166
Frost protection for the Frost protection for the plant is fully active only in the case of setting 2. With setting 0 or
plant 1, it will be partly or fully restricted. If the boiler is correctly sized, frost protection for the
plant is also ensured when using setting 1. In the case of plants where there is a
considerable risk of frost (e.g. plants with outdoor heating), setting 0 should not be
used.
The purpose of the function "Shifting priority" is to achieve optimum d.h.w. heating. This
means that during d.h.w. heating, the actual boiler temperature should be as close as
possible to the boiler temperature setpoint without shutting down the burner. To
achieve this, it may be necessary to restrict the heating circuits by means of a locking
signal. The signal is generated by a temperature-time integral.
Depending on the consumer, the locking signal will lead to switching on / off or a
setpoint reduction.
Impact on 2-position Cycling or deactivation of the pumps will reduce the amount of heat drawn from the
loads heat source. This will considerably shorten the time required for heating up the d.h.w.
Heating circuit pump:
Status Effect
Locking signal < 20 % Normal pump operation
Locking signal > 20 % Heating circuit pump cycles
Locking signal > 93 % Heating circuit pump OFF
Switching point Through the generation of the temperature-time integral it is not only the period of time
that is considered, but also the extent of the undershoot. This means that when the
crossing is significant, the pumps will be deactivated earlier.
Impact on modulating The consumption of heat is considerably reduced through the reduction of the flow
loads temperature setpoints. This reduces considerably the heating up time for d.h.w., with a
minimum impact on the heating circuits.
Mixing valve:
Status Effect
Locking signal > 0 % Flow temperature setpoints will be lowered.
The extent of lowering is dependent on the magnitude and the period of
time of the undershoot.
setpoint reduction Through the generation of the temperature-time integral it is not only the period of time
that is considered, but also the extent of the undershoot. This means that when the
undershoot is significant, the setpoint reduction will be greater.
92/166
Diagram Procedure
a to b Within a foreseeable period of time, the actual value of the boiler
temperature (TKx) will no longer be within the switching differential of
the boiler temperature setpoint.
Locking signal will be increased
b to c and Within a foreseeable period of time, the actual boiler temperature (TKx)
d to e will lie within the switching differential of the boiler temperature setpoint.
Locking signal will remain at a constant level
c to d and Within a foreseeable period of time, the actual boiler temperature (TKx)
e to f will lie above TKw.
Locking signal will be decreased
f The actual boiler temperature (TKx) exceeds the boiler temperature
setpoint.
Locking signal will be set to 0 %.
Example:
TK SDK
TKw
2378Z11
TKx
x%
0% t
a b c d e f
93/166
Description In connection with alternative sources of energy, an early release of heat generation
(BMUs) for d.h.w. heating outside the main occupancy times is often undesirable. A
choice of two different procedures is available releasing the cascade earlier or later.
Setting 1. Press the operating line selection buttons to select operating line 129.
2. Press the + / - buttons to select the required assignment.
0/1 - 1
Effect The setting determines whether or not heat generation will be released for maintaining
the reduced d.h.w. setpoint:
94/166
Setting 1. Press the operating line selection buttons to select operating line 130.
2. Press the + / buttons to select --- or enter the number of operating hours after
which changeover of boiler sequence shall take place.
Setting range Unit Factory setting
Effect --- Fixed switching on / off sequence of the boilers in the cascade. The lead
boiler can be freely selected (refer to operating line 132); the other boilers
are switched on and off in the order of the device addresses /
subaddresses.
10...990 On completion of the number of operating hours set here, the switching
sequence of the boilers in the cascade will change. This means that the
boiler with the next higher device address will become the lead boiler.
Example: Example of four boilers with a set differential of 100 operating hours.
95/166
Description Use this function if you want to operate a certain boiler as the first and / or last boiler of
the switching on sequence.
Setting 1. Press the operating line selection buttons to select line 131.
2. Press the + / button to enter the boiler(s) to be exempted from automatic
changeover.
0...3 - 0
Important Setting this parameter has an effect only if, on operating line Changeover of boiler
sequence in a cascade (line 130), setting Automatic changeover according to the
number of operating hours (10...990 h) has been selected.
Effect Depending on the selected setting, the respective boiler will be exempted from
automatic changeover of the boiler sequence.
Entry:
0 No exemption.
The switching on sequence of the boilers will change on completion of the number
of operating hours set (line 130).
1 The first boiler is exempted.
The first boiler in the addressing scheme always remains the lead boiler. With the
other boilers, the switching on sequence changes when the set number of
operating hours have elapsed (line 130).
2 The last boiler is exempted.
The last boiler in the addressing scheme always remains the last boiler. The other
boilers will be switched over on completion of the number of operating hours set
(line 130).
3 The first and the last boiler are exempted.
The first boiler in the addressing scheme always remains the lead boiler. the last
boiler in the addressing scheme always remains the last boiler. The boilers in
between will be switched over on completion of the number of operating hours set
(line 130).
Note The boiler sequence is to be determined on operating lines Device address (line 140)
and Segment address (line 141).
96/166
Benefit Lead boiler of the cascade with a fixed changeover of the boiler sequence can be
freely selected
Better adjustment to the plants demand profile by selecting a suitable type of boiler
as the lead boiler
Description With a fixed changeover of the boiler sequence (refer to operating line 130), the lead
boiler can be freely selected.
Setting 1. Press the operating line selection buttons to select operating line 132.
2. Press the + / - buttons to select the required lead boiler.
Setting range Unit Factory setting
00.1...16.3 - -
Effect The boiler defined as the lead boiler is always the first boiler to be switched on and the
last to be switched off. The other boilers are switched on and off in accordance with the
order of the device addresses / device subaddresses.
For example, display 1.1 means that device 1 (in segment 0), device subaddress 1
(BMU 1), is the selected lead boiler.
Note All cascade boilers must be in segment 0 so that the heat demand signals from all
segments can be acquired. For more detailed information about the device address /
device subaddress, refer to Local Process Bus (LPB), Basic Documentation, System
Engineering (document no. CE1P2370E).
Important This setting has an effect only if function "Changeover of boiler sequence in cascades"
(operating line 130) is set to --- = fixed switching on / off sequence.
97/166
Description After a BMU has switched on, an adjustable period of time must elapse until another
BMU can be switched on.
Setting 1. Press the operating line selection buttons to select operating line 133.
2. Press the + / - buttons to enter the number of minutes on completion of which
another BMU can be switched on.
Setting range Unit Factory setting
1...120 Minutes 5
Effect For stability reasons, each BMU added to the cascade will first run in its basic stage for
about one minute. This minute is already contained in the adjusted switch-on delay.
Correct adjustment of the switch-on delay ensures that plant operating conditions will
be stable. This prevents frequent cycling of the BMUs.
Note The function is only active with "Serial 2" (setting on line OEM 61 = 0)
Benefit Too frequent switching on / off cycles of the BMUs will be avoided
Description A BMU that has just been switched off can be switched on again only after an
adjustable period of time has elapsed.
Setting 1. Press the operating line selection buttons to select operating line 134.
2. Press the + / - buttons to enter the number of minutes on completion of which a
switched off BMU can be switched on again.
Setting range Unit Factory setting
Effect The restart lock ensures that a BMU that has just been switched off will not be switched
on again a short time later. The BMU will be released again only after the adjusted
period of time has elapsed. This prevents frequent cycling of the BMUs and ensures
that plant conditions will be more stable.
98/166
Description The LPB is used as a communication basis for generating a system with additional
ALBATROS controllers or controllers of other manufacture.
Setting 1. Press the operating line selection buttons to select operating line 140.
2. Press the + / - buttons to enter the device number.
0...16 Increment 1
Effect Entry of the device address is especially important when using combinations of units, or
in a system. The addresses classify the controllers within a segment.
Entry:
Device address The device addresses should be assigned in consecutive order in accordance with the
controllers connected. It is not permitted to assign an address several times within a
bus segment, since this would lead to communication errors. Each segment must have
a device as a master (address 1).
Note For more detailed information about the addressing of devices in a system, refer to
Local Process Bus (LPB), Basic Documentation, System Engineering (document no.
CE1P2370E).
99/166
Setting 1. Press the operating line selection buttons to select operating line 141.
2. Press the + / - buttons to enter the segment address.
Setting range Unit Factory setting
0...14 Increment 0
Effect Entry of the segment address is especially important when used in a system. With this
setting, the system can be subdivided into a number of segments.
Entry:
0 Heat generation segment
Segment number A bus segment is comprised of a number of devices that are used in the same place of
application. All devices in a segment must carry the same segment address.
Note For more detailed information about the addressing of devices in a system, refer to
Local Process Bus (LPB), Basic Documentation, System Engineering (document no.
CE1P2370E).
Description The bus power supply via the controllers enables the bus system to be powered directly
by the individual controllers (no central bus power supply).
Setting 1. Press the operating line selection buttons to select operating line 142.
2. Press the + / - buttons to select the type of bus power supply.
Setting range Unit Factory setting
0/1 Increment 1
Effect Entry:
0 Off
No bus power supply via the controller.
1 Automatically
The bus power supply (LPB) via the controller is automatically switched on and
off depending on the requirements of the LPB.
Note The actual status of the power supply is shown on operating line 143.
Bus power supply The bus system (LPB) can be powered either via the individual controller bus power
supplies or via a central bus power supply.
100/166
Benefit Overview of operational status of the bus power supply via controllers
Description The display shows whether the controller currently powers the bus (LPB).
Setting 1. Press the operating line selection buttons to select operating line 143.
2. No setting can be made with the + / - buttons.
Display Unit
ON / OFF -
Effect The status of the bus power supply via controllers will automatically be displayed on
this operating line.
Display:
ON The bus power supply via controllers is currently active.
At the moment, the controller supplies some of the power required by the bus.
Bus power supply Power supply to the bus can be accomplished in different ways. The respective setting
is made on operating line 142.
Setting 1. Press the operating line selection buttons to select operating line 144.
2. No setting can be made with the + / - buttons.
Display Unit
ON / OFF -
Effect The status of the BUS communication will automatically be displayed on this line.
Display ON Communication active
The controller communicates with another controller via the LPB.
101/166
Benefit The range of action of the central changeover actions can be defined
Setting 1. Press the operating line selection buttons to select operating line 145.
2. Press the + / - buttons to select the required range of action of changeover.
Setting range Unit Factory setting
0/1 Increment 1
Effect The range of action can be defined for the central changeover actions Changeover of
operating mode, Summer / winter changeover and Standby. The range of action
can be defined by making the following settings:
1 Changeover takes place with all controllers in the entire system (LPB).
Note The setting is of importance only if the controller is defined as the master and located in
segment 0 (address 0/1). With any other addressing, it has no effect.
Benefit Makes possible a uniform changeover of all heating circuits in the selected range of
action
Description Summer / winter changeover of the selected range of action takes place when the
changeover temperature set on operating line 16 is reached.
Setting 1. Press the operating line selection buttons to select operating line 146.
2. Press the + / - buttons to select the effect of automatic summer / winter changeover.
Setting range Unit Factory setting
0/1 Increment 0
Effect The setting will change the effect of summer / winter changeover:
Entry:
0 Local effect
Automatic summer / winter changeover switches the local heating circuit on and
off.
1 Central effect
Either the heating circuits of the segment or those of the entire system are
switched on and off by automatic summer / winter changeover, depending on the
setting made on operating line Range of action of central changeover.
Important Setting 1 (central effect) is active only if the controller has been defined as a master
controller (setting on line 140 = 1).
102/166
Description From the master controller, the entire heating system can be switched to standby.
Setting 1. Press the operating line selection buttons to select operating line 147.
2. Press the + / - buttons to select central standby switching.
Setting range Unit Factory setting
0/1 Increment 0
Important Setting 1 (central effect) is active only if the controller has been defined as a master
controller (setting on line 140 = 1).
Effect Entry:
0 Central standby switching is deactivated
Important If central standby on the master controller is switched on, it can only be switched off
again from that controller!
D.h.w. The central standby circuit does not affect d.h.w. heating. This means that the d.h.w. is
heated according to the settings made.
Display If the function is activated from the master controller, the operating mode buttons of
all affected controllers in the segment or system will flash.
Description Clock operation is an important setting for time synchronization if several controllers are
interconnected to form one system.
Setting 1. Press the operating line selection buttons to select operating line 148.
2. Press the + / - buttons to select clock mode.
Setting range Unit Factory setting
0...3 Increment 3
Important For time adjustment of the controllers connected to the system, one device per system
must be set as a system lock (setting 3).
Effect The setting will change the effect of the system time on the controller's time setting
(settings on operating lines 1 to 2).
Entry:
103/166
1 System time
The clock time on the unit cannot be adjusted Adjustment
International standards In accordance with present international standards, the change from wintertime to
summertime takes place on the last Sunday in March. The standard setting of the
controller complies with this rule since that Sunday lies between the standard setting
and the last day of the relevant month. With this setting, the day of changeover can be
matched to changing standards.
Description On the Sunday following that date, the controllers time of day will switch over to
summertime.
For that purpose, the time of day is shifted forward by one hour.
104/166
International standards In accordance with present international standards, the change from summertime to
wintertime takes place on the last Sunday in October. The standard setting of the
controller complies with this rule since that Sunday lies between the standard setting
and the last day of the relevant month. With this setting, the day of changeover can be
matched to changing standards.
Description On the Sunday following that date, the controllers time of day will switch over to
wintertime.
For that purpose, the time of day is shifted backward by one hour.
105/166
Description Terminal H1 is an input that provides different functions, depending on the selected
setting.
Setting 1. Press the operating line selection buttons to select operating line 170.
2. Press the + / - buttons to select the required function.
Setting range Unit Factory setting
0...4 Increment 0
Effect With this setting, the function of terminal H1 can be changed. The selected function will
be activated when the potential-free contact connected to terminal H1 closes or when
an analog voltage signal of DC 0...10 V is transmitted.
Entry:
0 Changeover of operating mode (remote telephone switch) for heating circuit
and d.h.w.: The operating mode is changed when the contact closes
Note When using terminal H1 as a contact (settings 0 -3), several switches can be
connected in parallel. The function will be activated when one or several contacts
close(s), depending on the selected setting.
When using terminal H1 as a voltage input (setting 4), it is not possible to connect
several signals in parallel.
When 2 heat demand signals are received at the same time, one via contact H1
(settings 2 + 4) and another (LPB, d.h.w. or controller internally), the highest of them
will be selected. Exception D.h.w. cannot be boosted by another heat requisition.
Important The relay contacts must be suited for use with extra low voltage (gold-plated).
106/166
Description A remote telephone switch is a potential-free relay contact, e.g. in the form of a modem,
which can be switched by making a phone call plus dialing a code.
The operating mode is changed when the contact connected to terminal H1 (e.g. a
remote telephone switch) closes. In that case, the LEDs in the operating mode buttons
and will flash.
D.h.w. Whether or not d.h.w. heating takes place when the remote telephone switch is
activated depends on the setting made:
Effect Activation of this function will produce different actions, depending on the function of
the controller within the LPB system (also refer to Local Process Bus (LPB), Basic
Documentation, System Engineering, document no. CE1P2370E).
1)
With setting 0 as selected above (d.h.w. heating locked), the two buttons and
will flash.
With setting 1 as selected above (d.h.w. heating remains released), only operating
mode button will flash.
107/166
1)
With setting 0 as selected above (d.h.w. heating locked), the two buttons and
will flash.
With setting 1 as selected above (d.h.w. heating remains released), only operating
mode button will flash.
BMU on PPS The heat sources connected to the PPS will be locked when contact H1 closes (e.g. via
ripple control).
All heat demand signals from the heating circuits connected to LPB and from the d.h.w.
storage tank connected to the RVA47.320 will be ignored while frost protection for the
boiler will remain ensured.
However, a local d.h.w. storage tank connected directly to the BMU can still trigger
d.h.w. heating.
Chimney sweep function The chimney sweep function can be activated directly on the BMU although the heat
generation lock is switched on.
BMU on LPB All at LPB connected heat generations are not applied from the heat generation lock.
The setting for this function must be made at the BMU.
108/166
External consumers can transmit a demand for heat in the form of an analog signal of
DC 0...10 V. The RVA47.320 converts this voltage signal to a temperature setpoint of
0...130 C and considers this value when generating the setpoint of the cascade.
T = 110C
T = 130C
T = 50C
T = 70C
T = 90C
S = 5C
[v]
10
2379Z26
8
0
10 20 30 40 50 60 70 80 90 100 110 120 130 [c]
The setpoint for 10 V can be set with parameter Maximum value of heat demand
(operating line 172, setting range 5...130 C). The voltage corresponding to the
displayed temperature can then be calculated as follows:
109/166
Benefit Handling of heat demand signals from units incompatible with LPB
Temporary startup of boiler via switching contact
Description Function for setting the temperature at which the cascade or the boiler is maintained
when contact H1 is closed.
Important This setting has an effect only if on operating line 170 Input H1 setting 1 "Minimum
setpoint of flow temperature contact H1" has been selected.
Setting 1. Press the operating line selection buttons to select operating line 171.
2. Press the + / buttons to set the required value of the "Minimum setpoint of flow
temperature contact H1".
Setting range Unit Factory setting
8...TKmax C 70
Effect Function "Minimum setpoint of flow temperature contact H1" selected on operating line
170 will be activated when contact H1 closes. The heat source or the cascade will
maintain the temperature level set here until either contact H1 reopens or more heat is
demanded.
Notes If several heat demand signals are received at the same time (LPB, contact H1, d.h.w.,
or from the controller itself), the highest of them will automatically be selected.
If the demand for heat is so small that a single BMU running on its basic stage still
produces too much heat, it will start cycling within the switching differential set on it.
Otherwise, the required output will be provided through modulation of the burner.
TK
C
80 TKw
70
60
TVHw
50
2379Z20
40
0
30
30 20 10 0 -10 C TA gem
110/166
Benefit Adjustable temperature range for heat demand signal via input H1
Can be matched to the voltage outputs of devices of other manufacture
Description The parameter determines which temperature the maximum voltage of the setting
Heat demand via H1 (operating line 170, setting 4) corresponds to.
Important This setting is active only if on operating line 170 (input H1) setting 4 Heat demand DC
010 V has been selected.
Setting 1. Press the operating line selection buttons to select operating line 172.
2. Press the + / buttons to set the required Maximum value of the heat demand
signal.
Setting range Unit Factory setting
5...130 C 100
Effect This setting defines the temperature corresponding to 10 V of the setting Heat demand
via H1 (operating line 170, setting 4).
Based on this temperature, the controller converts the heat demand voltage signal to a
temperature.
Benefit The operating action of the contact can be matched to the type of output signal
delivered by a device of other manufacture
More flexibility when selecting non-Landis & Staefa products (both operating
actions can be considered)
Description This function enables the operating action of contact H1 to be matched to the operating
action of a device of other manufacture.
Setting 1. Press the operating line selection buttons to select operating line 173.
2. Press the + / - buttons to select the operating action of contact H1.
Setting range Unit Factory setting
0...1 - 1
Entry:
0 The contact is a N.C. contact, which means that it is normally closed and opened
only when the third party device delivers a signal.
1 The contact is a N.O. contact, which means that it is normally open and closed
only when the third party device delivers a signal.
Note If input H1 is used for a heat demand signal (line 170, setting 4), this setting will have
no effect.
111/166
Description This function provides minimum limitation of the boiler temperature setpoint.
Setting 1. Press the line selection buttons to select operating line 1OEM.
2. Press the + / - buttons to set the minimum limitation of the boiler temperature.
8...95 C 8
Effect The setting ensures minimum limitation of the boiler temperature setpoint which can be
adjusted on line 90 (TKmin).
Description Maximum limitation of the boiler temperature setpoint and delivery of the flow
temperature setpoint for the cascade in manual operation.
8...120 C 80
Effect This setting provides maximum limitation of the boiler and cascade flow temperature
setpoint. The boilers controlled by the BMUs are operated at a temperature no higher
than the adjusted temperature, even if the consumers call for more heat.
In manual operation, the value set is used directly as the flow temperature setpoint.
The boilers controlled by the BMUs are operated at this temperature.
112/166
Description Overrun of the primary, heating circuit and d.h.w. charging pump ensures that residual
heat will be carried away from the pressureless header. This makes certain that the
boiler pump controlled by the BMU will be able to draw the residual heat from the boiler,
thus avoiding boiler overtemperatures and preventing the manual reset safety limit
thermostat from cutting out.
0...20 min 5
Effect All pumps that, at the time of burner shutdown of the last boiler, were operating,
continue to run for the period of time set here. At the same time, the previous flow
temperature setpoint remains valid, allowing the mixing valves of the controllers
connected to LPB to stay open.
Example HK
t
Q
ON
OFF
t
tPN
Y
TVNw
2373Z28
TVRw
t
HK Operating mode
Nominal operation
Q Pumps
Y External mixing valve (via LPB) Reduced operation
TVNw Nominal flow temperature setpoint
TVRw Reduced flow temperature setpoint tPN Pump overrun time
Note With no burner shutdown, the general pump overrun time is one minute.
Description The setting defines the permitted minimum boiler return temperature.
113/166
8...95 C 8
Effect If the boiler return temperature drops below the minimum limit set here, the consumers
heat c7onsumption will be restricted.
Description The output signals delivered by the BMUs can be calibrated to match the actual load.
This enhances the control performance.
Setting 1. Press the line selection buttons to select line 25OEM - 28OEM.
2. Press the + / - buttons to adjust the calibration factors.
-100...100 - 0
In that case:
- Operating line 25 = BMU 1
- Operating line 26 = BMU 2
- Operating line 27 = BMU 3
- Operating line 28 = BMU 4
Effect The output signal delivered by the respective BMU is corrected by the adjusted factor
and then used for controller-internal calculations.
In principle, operation without the adjusted calibration factor is possible, but to achieve
the greatest possible accuracy the adjustment should be made.
Calculation Calculation of the calibration factor for the respective BMU is made based on the
following formula:
PGs
P%GS 100
PN
K% =
P%GS
1
100
Legend
K% Calibration factor [%]
P%GS Output provided on the basic stage [%]
PGS Output on the basic stage [W]
PN Nominal output [W]
Note The value of P%GS is obtained by making a readout with the ACS69 service tool.
On the ACS69, the value is displayed on page Heat source state under the name
Actual capacity value BMU X.
The values of PGS and PN are given on the type field of the BMUs.
114/166
Benefit The influence of room temperature deviations on the controlled system can be
adjusted
Note Defines the influence of room temperature setpoint deviations on the controlled system.
The room influence can be activated and deactivated (operating line 101).
Setting 1. Press the line selection buttons to select operating line 30OEM.
2. Press the + / buttons to set the gain factor.
0...20 - 4
Correction The value of setting 30OEM is divided by 2 and multiplied by the differential (room
temperature setpoint actual room temperature).
The result is then added to the room temperature setpoint.
30OEM
TRwk = TRw + (TRw - TRx)
2
Note The gain factor of the room influence is only active when a room unit is connected.
115/166
Description Quick setback is dependent on whether or not a room temperature sensor is used. A
differentiation is made between quick setback with and without room temperature
sensor.
Important This setting is active only if no room sensor is used.
0...20 - 2
Quick setback without Quick setback is started as soon as a change to a lower room temperature setpoint
room temperature takes place (e.g. switching times in automatic mode).
sensor During quick setback, the heating circuit pump will be deactivated and no heat demand
signal delivered.
Exception Due to frost protection for the plant, the heating circuit pump can be
activated however in spite of quick setback.
The quick setback time is generated based on setting 31OEM , the composite outside
temperature in the room temperature setpoint step. It is limited to a maximum of 15
hours.
Example The example applies to a setpoint step change of 4 C (e.g. TRw from 20 to 16 C):
Note If a room sensor is connected, the quick setback time will not be generated from this
setting. For details, refer to section "Quick setback with room temperature sensor
(Chapter 6, Functions with no settings).
116/166
Note Boosts the room temperature setpoint temporarily, aimed at achieving shorter heating
up times for the room. This setting is active only if a room temperature sensor is used.
0...20 C (K) 5
Boost heating Boost heating is started as soon as switching to a higher room temperature setpoint
occurs (e.g. switching times in automatic mode).
The room temperature setpoint will be raised by the setting made on line 32OEM until the
room is heated up (TRw - C).
The boost produces an increase in the flow temperature setpoint.
C
TR w
20
2371D03a
15 TR x
a b
t
117/166
Description When this function is activated and there is a risk of frost, the heating will automatically
switch on, thus preventing the heating plant from freezing.
Important This function is ensured only if the plant works properly and is fully operational!
0/1 - 1
Effect Depending on the selection made, the plant will be protected by activating the pumps.
Entry:
0 Frost protection for the plant OFF
Function deactivated
frost protection for the The heating circuit pump will be switched on in function of the actual outside
plant temperature, even if there is no demand for heat.
Exception Between -4...-5C, different statuses can occur. In this temperature range, it is decisive
which situation prevailed:
If the temperature was previously higher (in the range of "takt), the pump is
switched on / off also in the range -4 to -5 C and is continuously running only when
the outside temperature is lower
If the temperature was previously lower (in the range of "ON),the pump is
continuously activated also in the range up to -4 C and is switched on / off when
the outside temperature is higher
ON
takt
OFF
2371Z30
-6 -5 -4 -3 -2 -1 0 1 2 3 4
TA C
118/166
Description The flow temperature can be higher than that called for by the pump heating circuit
(e.g. in the case of a higher setpoint demand by another consumer). The controller
offsets the surplus energy by letting the pump cycle, thus preventing the pump heating
circuit from overheating.
Setting 1. Press the line selection buttons to select operating line 34OEM.
2. Press the + / - buttons to activate or deactivate the overtemperature protection.
0/1 - 1
Effect The pump of the pump heating circuit will cycle in a way that the effect of too high flow
temperatures will be offset.
The cycling period is fixed at 10 min. This period of time will be broken down according
to the following on time ratio:
TVwGef TRw
On time ratio
=
TVxGed TRw
On time ratio
TVwGef Demanded flow temperature setpoint
TRw Current room temperature setpoint
TVxGed Actual value of the attenuated flow temperature
TVKx Actual value of cascade flow temperature (B10)
Note In the case of a single boiler plant without a cascade flow temperature sensor (B10),
the boiler temperature is used in place of the actual value of the cascade flow
temperature (TVKx).
Running time Multiplication of the on time ratio by the cycling period (10 minutes) gives the number of
minutes for which the pump runs.
This means that with an on time ratio of 0.6, the pump runs for 6 minutes and is then
switched off for the remaining 4 minutes of the cycling period.
119/166
Important The function of a room temperature sensor - if present - overrides that of the
overtemperature protection.
Description This setting takes into account potential heat gains from machines, pieces of
equipment, or other constant heat sources, that might adversely affect accurate control.
The value will change when the heating curve adaption is activated.
-2...+4 C 0
Effect The setting compensates the sum of all constant heat gains as follows:
Increase: For more compensation
In the case of significant heat sources
The setting in C corresponds to the temperature differential that would result if the
room was solely heated by the heat gains.
Description Adaption sensitivity 1 serves for calculating the adaption of the heating curve in the
temperature range 4 to 12 C (also refer to section "Adaption of heating curve, line
106).
1...15 15
120/166
Effect The heating curve in the temperature range 4 to 12 C will be differently adapted,
depending on the level of adaption sensitivity 1.
Increase: More adaption
Decrease: Less adaption
Reduction Each time a significant adaption of the heating curve between 4 and 12 C (ZAF1) has
taken place, adaption sensitivity 1 will automatically be reduced by one step. This
means that the extent of adaption and thus the readjustment of the slope and the
heating curves parallel displacement will gradually be reduced .
Note When readjusting the slope of the heating curve (line 17), the adaption sensitivity will
automatically be reset to the factory-set value.
Note For more detailed information about the effects, refer to operating line Adaption of
heating curve (line 106).
Description Adaption sensitivity 2 serves for adapting the heating curve in the temperature range
below 4 C (also refer to section "Adaption of heating curve, line 106).
1...15 - 15
121/166
f2
0,5
f1
237 1D07
0
20 12 4 -4 -12
TAged
ZAF1 ZAF2
f Factor
f1 Factor for parallel displacement
f2 Factor for slope
TAged Attenuated outside temperature
ZAF1 Adaption sensitivity 1 (line 36OEM)
ZAF 2 Adaption sensitivity 2 (line 37OEM)
Note For more detailed information about the effects, refer to operating line Adaption of
heating curve (line 106).
122/166
Description Function for limiting the nominal setpoint of the d.h.w. temperature.
8...80 C 60
Effect The setting will ensure maximum limitation of the nominal d.h.w. temperature setpoint
(setting on line 13).
2379Z10a
0 10 20 30 40 50 60 70 80 90 100 120 130 140 C
13 Setting "Nominal setpoint of d.h.w. temperature
120 Setting "Reduced setpoint of d.h.w. temperature
40OEM Setting "Maximum nominal setpoint of d.h.w. temperature
Description D.h.w. control is in the form of a two-position controller with an adjustable switching
differential.
Note The switching differential for d.h.w. control has no impact on d.h.w. with a control
thermostat or changeover valve (via BMU).
0...20 C (K) 5
Effect The setting will change the switching differential of the d.h.w. temperature control.
Entry:
Increase: Switching differential will become larger
Fewer and longer heating up times, larger temperature variations
123/166
2-position control heats the d.h.w. at certain intervals. The duration of d.h.w. heating
depends mainly on the storage tanks capacity and water volume and the amount of
d.h.w. currently required.
Legend
C
TBWx TBWx Actual value of d.h.w.
TBWw temperature
TBWw D.h.w temperature setpoint
TBWw-SDBW
SDBW Switching differential of d.h.w.
ON Switch-on point
t OFF Switch-off point
t Time
P Pump
2371D05
ON
P
OFF
Switch-on point
OFF
Switch-off point
w
TBWx [C ]
Benefit Potential legionella viruses in the d.h.w. storage tank will be killed at regular
intervals.
Description The legionella function ensures that the d.h.w. in the storage tank will periodically be
raised to a temperature of at least 60 C, thus making certain that potential legionella
viruses will be killed.
0/1 Increment 1
124/166
Notes This function is possible only when d.h.w. heating is released by the d.h.w. heating
program.
If the legionella function is aborted during the usual time (on Mondays), it will be
repeated the next time the d.h.w. setpoint is changed
Description The setpoint of the legionella function is an adjustable temperature level to which the
d.h.w. temperature is raised when the legionella function is activated (also refer to
section "Legionella function). For details, also refer to "Legionella function", line 42OEM.
8...95 C 65
Effect The setting changes the d.h.w. setpoint during the period of time the d.h.w. is heated
up as a result of the legionella function.
Benefit Prevents inadvertent discharging of the d.h.w. storage tank via the heating system
Description Prevents inadvertent discharging of the d.h.w. storage tank by cold water from the
heating circuit.
0...2 - 2
125/166
When protection against discharging of the d.h.w. is active, the boost of the flow
temperature (operating line 126) is checked during the heating cycle:
If at least half the boost value is reached, d.h.w. heating will be released
If the boost value is less than 1/8 of the value set, d.h.w. heating will not be
released
Note Setting 1 may be used only if the cascade return temperature sensor is connected.
126/166
Description For the plant configuration used, this setting represents an optimum combination of
lead boiler operation and running time strategy.
Setting
1. Press the line selection buttons to select line 50OEM.
2. Press the + / - buttons to select the required combination of lead boiler operation
and running time strategy.
1...6 1 2
There is a total of 2 types of lead boiler operation and three running time strategies
available. The 6 combinations are assigned as follows:
Einstellung (Kombination) type of lead boiler operation running time trategyrunning
1 autonomous 1
2 autonomous 2
3 autonomous 3
4 linked 1
5 (Standard setting) linked 2
6 linked 3
127/166
General The type of lead boiler operation describes the way the individual boilers in the cascade
are controlled.
2379z04
1 2 3 4
P = 50 % P = 51 % P = 53 % P = 48 %
It is thus possible that individual boilers will be operated outside their output range. The
average actual output is within the defined output range, however (for exceptions, refer
to lines 51 and 52).
linked: A differentiation is made between lead boiler and lag boilers. The RVA47.320 delivers a
temperature setpoint to the lead boiler, which translates it into output. The lag boilers
take this output as maximum limitation of output, thus following the lead boiler.
wt = 70C
Example:
1 2 4 2379z04
3
P = 50 % wp = 50 % wp = 50 % wp = 50 %
This means that all boilers will be operated within the defined output range (for
exceptions, refer to pages 14 and 132).
Note In the case of linked lead boiler operation, the controller considers the ratio of the
nominal BMU outputs and matches the speed of lag boiler operation accordingly.
128/166
General The running time strategy defines the criteria for the switching on / off of the lag boilers.
It is determined by the following parameters:
- Nominal output of BMU 1 - 4 See line 91 -94
- Entry of minimum limit of output range (Pmin) See line 10OEM
- Entry of maximum limit of output range (Pmax) See line 52OEM
The RVA47.320 initiates changeover only when it leads to a valid operational status
while taking the above parameters into consideration.
Important The running time strategies described below become active only when the flow
temperature setpoint is reached. During the heating up time (e.g. after night setback),
the boilers required are run up to the maximum released output as quickly as possible
(short heating up time).
Strategy 1: Additional boilers are switched on as late as possible and switched off again as early as
possible. Hence, the aim is to have the smallest possible number of boilers in
operation, or to obtain short running times for additional boilers.
2379Z05a
80% ON
Example of three boilers
with an output range of 20
- 80 %: 80% 80% ON
40% 40%
80% 80%
40% 40%
OFF
80%
OFF
129/166
80% ON 2379Z05
Example of three boilers
with an output range of 20
- 80 %: 80% 80% ON
40% 40%
40% OFF
Strategy 3: Additional boilers are switched on as early as possible and switched off as late as
possible. Hence, the aim is to have the highest possible number of boilers in
operation, or to obtain long running times for additional boilers.
2379Z05a
Example of three boilers
40% ON
with an output range of 20
- 80 %:
20% 20% 30% 30% ON
40%
OFF
130/166
Benefit The minimum output of the boilers controlled by the BMUs can be defined.
Description Defines the minimum limit of the optimum output range used by the BMUs.
5...Pmax % 40
Pmax. = upper limit of output range (operating line 52)
Note Typically, the set minimum limitation of the output lies above the lowest basic stage of
all BMUs. A lower setting causes several BMUs to cycle Do not use lower settings
without having tested them in practical operation.
Effect The setting defines the minimum limit of the output range within which the BMUs are
controlled. The value is used as the switch-on or switch-off criterion according to the
selected running time strategy (refer to page 129).
Pmax
Output range of BMUs
Pmin
2379Z06
The minimum limit of the output range is crossed only in exceptional cases, e.g. when
the setting of the value is too high, or when, due tot he BMUs' output ratio, an invalid
operational status would result after changeover.
131/166
Description Defines the maximum limit of the optimum output range used by the BMUs.
Setting 1. Press the line selection buttons to select operating line 52OEM.
2. Press the + / - buttons to set the maximum limitation of the output.
Pmin...100 % 90
Pmin. = minimum limit of output range (operating line 51)
Effect The setting defines the maximum limit of the output range within which the BMUs are
controlled. The value is used as the switch-on or switch-off criterion according to the
selected running time strategy (refer to page 129).
Pmax
The maximum limit of the output range (when <100 %) is crossed only when all
available BMUs run at Pmax and there is still demand for heat.
Otherwise, crossing only takes place in exceptional cases, e.g. when the setting of the
value is too low, or when, due to the BMUs output ratio, an invalid operational status
would result after changeover.
When using a setting of 100 %, the value will of course never be exceeded.
Benefit The minimum running time on the basic stage can be defined
Description This function allows the minimum running time on the basic stage to be set. This
enables the controller to operate smoothly even if BMUs of very high capacity are used.
Setting 1. Press the line selection buttons to select operating line 56OEM.
2. Press the + / - buttons to adjust the mandatory time on the basic stage.
10...1200 s 60
Effect When started up, each BMU is operated on the basic stage for the period of time
adjusted here. The BMU will be released for modulation only when this time has
elapsed. This period of time enables the controller to analyse the current operational
status and then plan the next steps.
Note When using heat generating equipment of very high capacity, the longer time leads to a
more stable (slower) operating performance.
132/166
Benefit Detection of a too high flow rate on the heat generation side.
Avoiding excessive return temperatures.
Description An excessive flow rate on the heat generation side and the resulting increase of the
return temperature is quickly detected and, if necessary, offset by shutting down one of
the BMUs.
0...20 K (C) 4
Effect The minimum temperature differential at the pressureless header prevents the return
temperature from exceeding a certain level.
The setting is only active when running time strategy 2 or 3 is selected (see page 35).
With running time strategy 1, the function is inactive.
When the return temperature rises to a level which is half a switching differential (
MTS/2) below the flow temperature (point a), the selected running time strategy 2 or 3
is switched over to running time strategy 1. This means that one of the BMUs is shut
down as soon as possible.
If the return temperature moves away from the flow temperature by one full switching
differential MTS (point b), changeover is cancelled again. This means that running time
strategy 1 switches back to the previous running time strategy 2 or 3.
[C]
tVL
=
MTS
=
tRL
LZS2/3
LZS1
2379Z27
a b t
tVL Cascade flow temperature (B10)
tRL Cascade return temperature (B70)
MTS Minimum temperature differential at the pressureless header
LZS1-3 Running time strategy 1 - 3
a/b Changeover points of running time strategy
133/166
Setting 1. Press the line selection buttons to select operating line 90OEM.
2. Press the + / - buttons to select the required continuous display.
Setting range Unit Factory setting
0/1 - 0
Effect This setting changes the continuous display of the device. It appears when no
operating line is selected.
0 Day / time of day
The continuous display shows the weekday (1...7 = Mo...Su) and the time of
day.
1 Cascade flow temperature sensor (common flow temperature sensor)
The continuous display shows the temperature measured with the cascade flow
temperature sensor (B10)
Caution! When connecting several BMUs to the controller, the continuous display always shows
the cascade flow temperature. In that case, setting 0 can be no longer selected.
0 4 8 12 16 20 24
134/166
Benefit Straightforward display of software version used, without removing the controller
Description The software version installed represents the state of the software available at the time
the controller was produced.
Description Here, you can read the number of hours the controller has been in operation
Setting 1. Press the line selection buttons to select operating line 92OEM.
2. No setting can be made with the + / - buttons.
Display Unit
0... 500000 h
Effect The number of operating hours since the controller was first commissioned will
automatically be displayed on this line.
The hours considered as operating hours are those during which power was supplied to
the controller, that is, including the periods of time with no effective heating operation.
The number of operating hours cannot be reset.
135/166
Benefit Produces the operational status required for flue gas measurements.
Description No chimney sweep function can be triggered on the controller itself. the chimney sweep
function is activated directly on the respective BMU.
Effect As soon as the chimney sweep function is triggered on one of the BMUs of the
cascade, the BMU transmits the signal to the controller, which shuts down all other
BMUs. The controller allows the boiler temperature to rise to a level of 64 C, which is
required to make flue gas measurements, then maintaining that temperature level by
enforcing heat consumption of both the heating circuits and d.h.w.
This action is independent of whether a lead or lag boiler is involved.
By deactivating the chimney sweep function on the BMU, or on completion of a period
of time to be adjusted on the BMU, the controller returns to its initial operational status.
Note For information about the activation of the chimney sweep function and other
information, refer to the technical documentation of the type of BMU used.
Description The various heating circuits require different flow temperature setpoints depending on
the demand for heat. However, since boiler temperature control can consider only one
setpoint, a selection is made.
Process Generally, the demand for the highest setpoint required by a consumer (e.g. by a
heating circuit) generates the current boiler temperature setpoint.
The setpoint requirements considered stem from both controller-internal setpoints
(heating circuit or input H1) and setpoints transmitted via LPB.
Auxiliary functions, such as setpoint boosts and the like, are included in the setpoints
actually demanded at the time.
Exception A demand for d.h.w. has priority over all other setpoint requirements, which means that
the required d.h.w. setpoint will be maintained, even if it is lower than that called for by
a heating circuit.
Effect The boiler temperature is maintained at the highest setpoint currently demanded -
unless d.h.w. is required.
136/166
80 TKw
70 TV w2
60
50
40 TVw1
2371D09
30
20
20 10 0 -10 -20 -30
TAgem
Description This is a fast-acting savings function since the heating is switched off when there is no
more demand for heat. Economical operation is ensured throughout the year,
especially during intermediate seasons. Manual switching off is no longer required.
Notes The automatic 24-hour heating limit does not function in continuous operation
The display shows the automatic 24-hour heating limit as ECO
Introduction If no room unit is connected, the room temperature setpoint will not be readjusted by
the room influence. In that case, the automatic 24-hour heating limit operates according
to the selected setpoint of or .
Process The temperature basis used for this process are the values of the flow temperature
setpoint and the current room temperature setpoint.
Switching off If the flow temperature setpoint falls below the room temperature setpoint plus a
correction value, the heating will be switched off.
Heating OFF:
Switching on If the flow temperature setpoint exceeds the room temperature setpoint plus a
correction value, the heating will be switched on.
137/166
Introduction The automatic 24-hour heating limit operates depending on the current flow
temperature setpoint. If a room unit is connected, the room influence continuously
readjusts the flow temperature setpoint.
This means that the automatic 24-hour heating limit differs when room influence is
used.
Process The temperature basis used for this process are the values of the flow temperature
setpoint and the current room temperature setpoint.
Switching off If the flow temperature setpoint corrected by the room influence falls below the room
temperature setpoint plus a correction value, the heating will be switched off.
S 31OEM
TVwk TRw + 2
10 16
Switching on If the flow temperature setpoint corrected by the room influence exceeds the room
temperature setpoint plus a correction factor, the heating will be switched on.
S 31OEM
TVwk TRw + 4
10 16
138/166
Description Quick setback is dependent on whether or not a room temperature sensor is used. A
differentiation must therefore be made between quick setback with or without room
sensor.
Important This process has an impact only when a room temperature sensor is used.
Process Quick setback is started as soon as a change to a lower room temperature setpoint
takes place (e.g. switching times in automatic mode).
Quick setback is terminated as soon as the actual room temperature reaches the level
of the respective room temperature setpoint (TRx = TRw).
2371D08
C
20
TRx
15
TRw
t
H
ON
OFF
t
Effect During quick setback, the heating circuit pump will be deactivated and there will be no
demand for heat. This means that the room temperature falls quicker since the supply
of heat from the flow or boiler is cut off.
Exception Due to frost protection for the plant, the heating circuit pump can be
activated however in spite of quick setback.
Note If no room sensor is connected, quick setback will not be accomplished through this
process. For details, refer to section "Quick setback constant", operating line 31OEM.
139/166
Description If, due to unexpected demand, the d.h.w. storage tank is emptied, the d.h.w. push
provides one-time charging of the storage tank until the nominal d.h.w. temperature
setpoint is reached.
Process The d.h.w. push is triggered as soon as the actual d.h.w. temperature falls below the
reduced d.h.w. setpoint (line 120) by more than twice the switching differential (line
41OEM).
TBWx < TBWR - 2 SDBW
Effect When the d.h.w. push is triggered, the storage tank is charged once until the nominal
d.h.w. temperature setpoint (operating line 13) is reached.
Then, normal operation according to the d.h.w. heating program is resumed.
Example
SDBW
TBWw
TBWx
SDBW
TBWR
2SDBW
2379D10
TBWw
TBWR
Push
t
140/166
Description The pump kick is a protective function aimed at preventing the pumps from seizing.
Process Every Friday at 10:00 h, the pumps connected directly to the RVA47.320 are activated
for 30 seconds, one by one at an interval of one minute.
The pump kick is activated without giving consideration to any of the other functions.
Effect During the periods of time pump kick is activated, the water circulates. The mechanical
parts of the pumps will be purged, thus preventing the pumps from seizing.
Note The kick of the d.h.w. pump is the last pump kick made in order to prevent the transfer
of heat from the d.h.w. storage tank to the heating system.
Description The Protection against discharging after d.h.w. heating prevents inadvertent
discharging of the d.h.w. storage tank resulting from the pump overrun. Together with
Protection against discharging during d.h.w. heating (operating line 44OEM), efficient
protection against discharging is thus ensured.
Process The controller compares the storage tank temperature with the cascade flow
temperature (common flow temperature) or, in certain situations, with the boiler
temperature.
If the cascade temperature (or the boiler temperature) is lower than the storage tank
temperature, pump overrun will be stopped prematurely.
141/166
Description Operation of the various pumps depends on a number of factors. To enable you to
quickly understand the different interrelationships when commissioning and checking
the plant, please make use of the list below. It provides information about the setting
combinations (pump settings / demand for heat) at which a pump runs (the meaning of
the different pump settings is defined on operating line 95).
* = the pump also runs when the demand for heat comes from another controller integrated via LPB
When there is no more demand for heat, the pumps in operation overrun for the period
of time set on line Pump overrun time (8OEM), with the exception of the d.h.w.
circulating pump, Q1 setting 4.
There are situations, however, where the pumps (with the exception of pump H1, Q1
setting 5) do not run, for example with:
142/166
Benefit Ensures that the boiler and d.h.w. temperature will not fall below a certain level
Note In addition to the frost protection modes described here, frost protection for the building
and frost protection for the plant, whose parameters can be set, are also active. For
details, refer to the description given on lines 15 and 33 OEM.
The frost protection function for the boilers is integrated in the BMUs. For detailed
information, refer to the technical documentation of the product used.
For details, refer to the documentation of the relevant product.
Description Frost protection for the d.h.w. prevents freeze-ups of the d.h.w. storage tank that is
connected directly to the RVA47.320. Whenever the d.h.w. temperature drops
excessively, forced charging will be initiated.
the actual value of the d.h.w. temperature exceeds 5 C ... the frost protection
by more than one d.h.w. switching differential (line function for d.h.w. will be
41OEM)... terminated
(TBWx > 5 C + SDBW)
Notes The frost protection setpoint for the d.h.w. is factory-set at 5 C and cannot be
changed
Pump overrun will be activated when d.h.w. heating is terminated.
Important The frost protection function only acts on a d.h.w. storage tank connected directly
to the RVA47.320. In the case of plant types with d.h.w. heating via BMU, this
function must be provided by the BMU.
The frost protection function is only active when using a temperature sensor. If the
d.h.w. is heated with the help of a control thermostat, no frost protection function is
possible because there is no actual value of the storage tank temperature.
143/166
Furthermore, the controller can ensure the coordination of additional boiler controllers
of a cascade (cascade master function).
D.h.w. heating is provided either directly by the RVA47.320 or by one of the BMUs
based on the values adjusted on the RVA47.320.
The RVA47.320 accepts and handles heat demand signals of additional controllers
connected to the LPB, and of controllers delivering their signals via input H1.
Note On the consumer side, the plant can be extended to include up to 16 controllers without
an additional bus power supply, and up to 40 controllers when using a central bus
power supply (also refer to Basic Documentation LPB System Engineering, reference
number CE1P2370E).
On the heat generation side, additional RVA47.320 or RVA43.222 can be used to build
up a cascade of up to 16 heat sources (modulating, multi-stage or mixed).
Hydraulic circuit Where shown, the applications require proper hydraulic decoupling between heat
generation and heat consumption since the volumetric flows on both sides vary and are
different from one another. The simplest hydraulic decoupling method is the use of a
sufficiently large pressureless header (bypass, hydraulic decoupler; about two to three
nominal sizes larger than the header of the boiler circuit).
With plant types using no boiler pump, a flow switch is required to ensure the flow of
water through the boiler.
When using heating boilers with a speed controlled pump, the pump must be set to a
fixed speed.
Important When designing the plant, it should be made certain that the volumetric flows on the
heat generation and heat consumption side at nominal output are about the same.
outside temperature The outside sensor can be connected either directly to the RVA47.320 or to one of the
sensor BMUs to transmit its value to the controller via the PPS, but it can also be connected to
some other LPB capable controller to transmit its value to the other LPB capable
controllers via the LPB. But it can be connected to some other LPB-compatible
controller to transmit its value via LPB to the other LPB-compatible controllers.
We recommend to connecte it directly to the RVA47.320.
D.h.w. priority When using d.h.w. heating with a charging pump, d.h.w. priority is possible only in
connection with LPB-compatible controllers. Controllers not suited for use with the LPB
cannot be acted upon.
144/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. No d.h.w. heating via
the RVA47.320.
B10
1 2 3 4
B70
2379S27
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 27
Heating curve (line 17) --- (inactive)
Pump function Q1 (line 95) 1 (heating circuit pump or no pump)
Important This application requires the heat demand signal from a consumer to release heat
generation:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
Electrical connections
H1 B70 B10 B9 A6 / BMU
M B M B M B M B PPS LPB
H1 B70 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A27
L
N
145/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating with
charging pump through the RVA47.320.
B10
B3
1 2 3 4
B70
2379S28
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 28
Heating curve (line 17) --- (inactive)
Pump function Q1 (line 95) 1 (heating circuit pump or no
Important This application requires the heat demand signal from a consumer (or d.h.w. heating)
to release heat generation:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
Electrical connections
H1 B70 B3 B10 B9 A6 / BMU
M B M B M B M B M B PPS LPB
H1 B70 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A28
N
L
146/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve.
B10
1 2 3 4
B70
2379S29
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 29
Heating curve (line 17) --- (inactive)
Pump function Q1 (line 95) 1 (heating circuit
pump or no pump)
Important This application requires the heat demand signal from a consumer to release heat
generation:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
Note A heat demand signal from the d.h.w. storage tank releases only that boiler to which
the storage tank is hydraulically connected. The other boilers of the cascade will not be
released.
Electrical connections
H1 B70 B10 B9 A6 / BMU
M B M B M B M B PPS LPB
H1 B70 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A27
L
N
147/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. System pump for
heating circuits connected to the RVA47.320.
No d.h.w. heating via the RVA47.320.
B10
1 2 3 4
B70
2379S30
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 30
Heating curve (line 17) --- (inactiv) or 2.5...40
Pump function Q1 (line 95) 2 (primary pump for HC only) or
3 (primary pump for HC and d.h.w.)
Important Heat generation is released by the heat demand signal from a consumer:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).
H1 B70 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A30
N
L
148/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating with
charging pump through the RVA47.320.
System pump for heating circuits and d.h.w. heating connected to RVA47.320.
B10
B3
1 2 3 4
B70
2379S31
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 31
Heating curve (line 17) --- (inactiv) or 2.5...40
Pump function Q1 (line 95) 3 (primary pump for HC and d.h.w.)
Important Heat generation is released by the heat demand signal from a consumer (or d.h.w.
heating):
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).
H1 B7 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A31
N
L
149/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating with
charging pump through the RVA47.320.
Primary pump for heating circuits connected to the RVA47.320.
B10
B3
1 2 3 4
B70
2379S32
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 32
Heating curve (line 17) --- (inactiv) or 2.5...40
Pump function Q1 (line 95) 2 (primary pump for HCs only)
Important Heat generation is released by the heat demand signal from a consumer (or d.h.w.
heating):
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).
H1 B7 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A31
N
L
150/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve. System pump for heating circuits connected to the
RVA47.320.
B10
1 2 3 4
B70
2379S33
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 33
Heating curve (line 17) --- (inactiv) or 2.5...40
Pump function Q1 (line 95) 2 (primary pump for HC
only)
Important Heat generation is released by the heat demand signal from a consumer:
LPB capable controllers signal the RVA47.320 their current heat demand directly
via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
When there is no heat demand signal from the consumers (no LPB capable controllers
connected and no possibility to use input H1), the controller itself can generate a
weather-compensated flow temperature (adjustment of heating curve with a valid
value).
Notes A heat demand signal from the d.h.w. storage tank releases only that boiler to which
the storage tank is hydraulically connected. The other boilers of the cascade
will not be released.
H1 B70 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
23 79A3 3
N
L
151/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. Control of pump
heating circuit by the RVA47.320.
No d.h.w. heating via the RVA47.320.
B10
1 2 3 4
B70
2379S34
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 34
Heating curve (line 17) 2.5...40
Pump function Q1 (line 95) 1 (heating circuit pump)
Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
H1 B70 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A33
N
L
152/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. Control of the pump
heating circuit by the RVA47.320. D.h.w. heating with charging pump by the
RVA47.320.
B10
B3
1 2 3 4
B70
2379S35
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 35
Heating curve (line 17) 2.5...40
Pump function Q1 (line 95) 1 (heating circuit pump)
Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
H1 B7 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A31
N
L
153/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve. Control of pump heating circuit by RVA47.320.
B10
1 2 3 4
B70
2379S36
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 36
Heating curve (line 17) 2.5...40
Pump function Q1 (line 95) 1 (heating circuit pump)
Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
Controllers not suited for use with the LPB can deliver their heat demand signal via
input H1.
Notes When there is only a heat demand signal from the d.h.w. storage tank (heating circuits
do not currently call for heat), the boiler put into operation is only that to
which the storage tank is hydraulically connected. The other boilers of the
cascade will not be released.
H1 B70 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A33
N
L
154/166
Note The plant type no. is identical with the number displayed on line 53.
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. Control of the pump
heating circuit by the RVA47.320 based on the heat demand signal received via input
H1.
B10
1 2 3 4
B70
2379S34
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 65
Heating curve (line 17) --- (inactive) or 2.5...40
Pump function Q1 (line 95) 5 (pump H1)
Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
The heat demand signal for the pump heating circuit is generated via input H1.
H1 B70 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A33
N
L
155/166
B10
B3
1 2 3 4
B70
2379S35
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 66
Heating curve (line 17) --- (inactive or 2.5...40
Pump function Q1 (line 95) 5 (pump H1)
Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
The heat demand signal for the pump heating circuit is generated via input H1.
H1 B7 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A31
N
L
156/166
Hydraulic circuit Control of a single BMU or cascade control of up to four BMUs. D.h.w. heating by one
BMU, with changeover valve.
Control of the pump heating circuit by the RVA47.320 based on the heat demand signal
received via input H1.
B10
1 2 3 4
B70
2379S36
Type of unit BMU 1 BMU 2 BMU 3 BMU 4 RVA47.320
Display of plant type 67
Heating curve (line 17) --- (inactive) or 2.5...40
Pump function Q1 (line 95) 5 (pump H1)
Important Other LPB capable controllers on the consumer side signal the RVA47.320 their current
heat demand directly via LPB.
The heat demand signal for the pump heating circuit is generated via input H1.
Notes When there is only a heat demand signal from the d.h.w. storage tank (heating circuits
do not currently call for heat), the boiler put into operation is only that to which the
storage tank is hydraulically connected. The other boilers of the cascade will not be
released.
H1 B70 B3 M B10 B9 MD A6 MB DB
N1
Q3 Q1 F1 L N
2379A33
N
L
157/166
For application examples with a cascade integrated in systems with alternative heat
generation, refer to Basic Documentation LPB System Engineering (document no.
CE1P2379E).
158/166
Room unit 11
6
96
9,3
91 x 91
96
2379M100
17,4
81
2371M02
Panel cutout
96 96
2...10 +0.8
92 -0
96
+0.8 +0.8
92 -0 92 -0
188
159/166
160/166
161/166
162/166
163/166
164/166
Seite: nderung:
1 Old version: V2.0 from 22.09.1999 new version: V2.2 from 15.07.2002
8 Short description: Text changed
9 Features Group formed to heating circuit and heat generation
12 Range Burner controls: LGM... and OCI12 deleted, LMU and OCI42 inserted
22 Line No. 3 and 4 inserted
25 Footnote for lines 90-94
Lines 107 and 108 inserted
27 Footnote 1) inserted
29 Footnote for lines 1, 25-28
30 Footnote 1) inserted
39 Lines 3 and 4 description inserted
55 Example: Graphic and Note changed
83-85 Description for line 107 and 108 inserted
92 Effect for entry 3: Shifting/absolute priority description changed
130- Chapter "Automatic 24-hour heating limit" changed
134
161 Output relays Text deleted
165/166
166/166