Chiller Performance Testing
Chiller Performance Testing
testing program
Proven performance under your watchful eye
The proof is in the testing
Ensure chiller performance
Businesses around the world are being
challenged to improve energy efficiency.
According to the World Business Council for
Sustainable Development, buildings worldwide
account for 40% of global energy consumption.
Of that amount, between 45% to 65% is used
by the HVAC systems that keep building
environments comfortable and healthy. The
slightest inefficiencies in cooling and heating
equipment create a huge energy drain and the
financial impact is significant.
Performance testing to match your All Trane test stands in La Crosse and Pueblo are
specifications approved by AHRI for certification testing. Trane
Computer selection programs predict chiller Pueblo is the first chiller manufacturer to have
performance based on laboratory testing. Factory an AHRI approved air-cooled test facility. Each
performance tests confirm that the actual chiller test facility undergoes an extensive and rigorous
performance matches the predicted performance, inspection process conducted by AHRI to gain
and the results serve as a benchmark during the approval for conducting AHRI certification tests.
commissioning process.
AHRI 575 factory sound test
We are committed to the highest level of design If the sound pressure test per AHRI Standard
and manufacturing accuracy to make sure your 575 is specified, we will discuss the procedure
chiller performs as expected. with you.
3
Testing is our way of life
Measurement that counts Part load conditions per AHRI standard,
Accurate measurement is an integral part or at your specified conditions
of performance testing. All the following Large chillers are tested at full load to
instrumentation is calibrated and traceable to determine the capability and efficiency of the
NIST, the National Institute of Standards and unit at design duty. The full load performance
Technology: wattmeter, temperature sensors, often affects demand charges. For part-load
flow meters, and pressure transmitters. This measurements, AHRI 550/590 defines the
Research and ensures the instrumentation meets or exceeds entering condenser water temperatures or
development the accuracy requirements of AHRI Standard ambient air temperature for 75 percent, 50
The testing process 550/590. A copy of the latest calibration report percent, and 25 percent load. If you prefer
starts in research and is available upon request. to have your chiller tested at other part load
development. We
look at environmental conditions the measurements are taken using the
performance, acoustic A poly-phase wattmeter measures the volts same methods.
characteristics, operating
and amps per phase and the kW. Two platinum
longevity, and overall
operating efficiency. resistance temperature detectors (RTDs) measure
After the chiller goes temperature at each location (entering and
into production, we
leaving evaporator water, entering and leaving
keep looking for ways
to make it better, condenser water for water-cooled, ambient air
quieter, more reliable for air-cooled). Magnetic flow meters measure
and more efficient.
the evaporator and condenser water flow, where
applicable. For air-cooled units, the ambient
temperature system averages multiple readings
from sensors throughout the controlled test
environment. Differential pressure transmitters
measure the water pressure drop.
5
5
Proven performance and quality workmanship
Full-load vibration test available Energy that comes into our system must
Trane performs a vibration test on the assembled equal the energy that comes out
centrifugal chiller compressor at the time of the Energy comes into the system at the evaporator
100 percent load test. Advise us if you would and the motor. The energy leaves the system at
like to see the vibration test results. the condenser. For a hermetic chiller, the energy
absorbed from, or given to, the equipment room
A nickel can be balanced on the edge of the or ambient air is ignored.
main compressor-motor assembly, demonstrating
the extremely low vibrations generated by the Heat balance calculation: While it is collecting
unit while operating. We can arrange for the data for water-cooled performance tests, the
famous nickel test. computer calculates a heat balance to confirm
that the test data is valid.
7
How does the air-cooled test loop work?
The air-cooled test loop has an evaporator section
and a condenser section. Inter-connected water
and air loops create a cooling load for the chiller by
adding heat from the discharge air to the leaving-
evaporator water.
.
Air-cooled test loop Coils Coils
(water control) (ambient control)
Air flow
Upper room
Lower room
Ingersoll Rand (NYSE:IR) is a world leader in creating and sustaining safe, comfortable and efficient environments in commercial, residential and
industrial markets. Our people and our family of brandsincluding Club Car, Hussmann, Ingersoll Rand, Schlage, Thermo King and Tranework
together to enhance the quality and comfort of air in homes and buildings, transport and protect food and perishables, secure homes and commercial
properties, and increase industrial productivity and efficiency. We are a $13 billion global business committed to sustainable business practices within
our company and for our customers.
2010 Trane All rights reserved Produced on post-consumer recycled paper, using
RF-SLB003-EN June 01, 2010 environmentally friendly print practices that reduce waste. ingersollrand.com