Belimo VRP-M Vav 4 1 en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

Product information System VRP-M VAV

MP BUS
TECHNOLOGY BY BELIMO

Adaptive VAV control system


for sensitive working areas

Table of contents
Overview of the system 2
System description 3
Technical data sheets
Adaptive VRP-M digital PID volumetric flow controller 5
Application 6
Functions 10
System configuration 13
Operating data settings (with VRP-M-Tool) 14
PC-Tool connection 16
Service-Tool ZTH-GEN 18
Bus operation 20
VFP-.. static pressure value sensors for neutral to slightly aggressive gases 23
VFD3 static pressure value sensor for room ventilation applications 25
Fast-running damper actuator for VRP-M system solution LMQ24A-SRV-ST 27
Fast-running damper actuator for VRP-M system solution NMQ24A-SRV-ST 29
Damper actuator for VRP-M system solution NM24A-V-ST 31
Spring-return actuator with emergency setting function
for VAV and CAV units SF24A-V-ST 33
Dimensions 35

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes  / 36


VRP-M VAV Overview of the system

Application VAV / CAV STP (pressure)


3 3
++
2 1 2 1
w w p

Supply/exhaust air systems


Extraction systems
Duct/section pressure
Actuator variants Standard actuator or fast runner
Spring-return actuator with emergency position OPEN or CLOSED
(see Damper actuators)
Sensor variants static or dynamic (see Pressure sensors)
Optimiser function for energy-
1)
efficient fan control
Stage control
Modulating control
Local override functions CLOSED / min / mid / max / CLOSED / Pmin / Pmax / Motor stop
OPEN / OPEN
Bus integration MP bus (MP partner systems), LONWORKS, KNX, Modbus, BACnet,
COU24-A-MP

1 Controller platform
VRP-M

VAV / CAV STP


Supply AC/DC 24 V
Reference variable control 0 / 2 ... 10 V, 0 / 4 ... 20 mA
Feedback, actual value Volumetric flow 0 / 2 ... 10 V p 0 / 2 ... 10 V
Tools PC-Tool VRP-M module, Service-Tool ZTH-GEN
Optimiser-compatible
Suitable gateways UK24LON, UK24EIB, UK24MOD, UK24BAC
Suitable MP-masters DDC systems from Belimo MP partners, COU24-A-MP

2 Pressure sensors

VFP-100 VFP-300 VFP-600 VFD3


Measuring principle static static static dynamic
Pressure range 0 ... 100 Pa 0 ... 300 Pa 0 ... 600 Pa selectable 0 ...
100 / 300 / 600 Pa
Comfort zone
Dusty air Dusty to very dusty 2) dusty 2)
Corrosive media Corrosive air 3) 4)

Connection Integrated cable/plug unit, suitable for VRP-M

3 Damper actuators

NM24A-V-ST LMQ24A-SRV-ST NMQ24A-SRV-ST SF24A-V-ST


Function Standard Fast runners Fast runners Spring-return
Torque 10 Nm 4 Nm 8 Nm 20 Nm
Running time 110 ... 150 s 2.5 s 4s 150 s
Emergency function OPEN or CLOSED
Connection Integrated cable/plug unit, suitable for VRP-M

1) Limitation:Optimiser function requires actuator with standard running time, fast runners are not permitted.
2) Independent of the sensor type, the pick-up device (unit component) must be tested at cyclical intervals and
be cleaned as needed.
3) The VAV unit (pick-up device, etc.) must be selected in accordance with the medium. The compatibility of
the sensor materials is to be tested (see Technical data VFP-.. and VFD3).
4) Compatible with duct cleaning agent and duct disinfecting agent.

 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


System description VRP-M VAV

Ready-to-connect system solution for


System components
Pressure-independent VAV and CAV
systems, e.g. in laboratories Controller
Fast-running VAV and CAV applications,
e.g. in digestors or generally for extracting
contaminated or slightly aggressive air in
closed rooms
Control:
DC 2 ... 10 V / 0 ... 10 V or bus
Integration in
DDC controller with MP interface
EIB-Konnex, Modbus and BACnet systems
LONWORKS systems Adaptive VRP-M digital PID volumetric flow controller for VAV applications Pages 5 ... 22
Diagnostic socket for Service and PC-Tool
Sensors

Sensors with static differential pressure measurement for all applications 1)


VFP-100, measuring range 0 ... 100 Pa
VFP-300, measuring range 0 ... 300 Pa
VFP-600, measuring range 0 ... 600 Pa Pages 23 ... 24
Sensor with dynamic differential pressure measurement for comfort applications
VFD3, adjustable measuring range 0 ... 100 / 300 / 600 Pa Pages 25 ... 26

Actuators

Standard actuator NM24A-V-ST


Fast runners LMQ24A-SRV-ST and NMQ24A-SRV-ST
Spring-return actuator with emergency setting function SF24A-V-ST Pages 27 ... 34

Brief description
Application This ready-to-connect system solution is an efficient control system for pressure-independent,
standard and fast-running volumetric flow applications.

Field of application The VAV system is used for the regulated supplying and extraction of contaminated or slightly
aggressive air 1) in enclosed spaces:
Exhaust air systems for laboratory workplaces 1)
Laboratories in chemical and pharmaceutical plants 1)
Hospital plants 1)
In conjunction with the fast running actuators LMQ24A-SRV-ST and NMQ24A-SRV-ST, the
1) Air
compatibility test essential (see Technical system is particularly suitable for laboratory applications for the suctioning off of contaminated
data for the VFP-..-sensors, page 23). air 1):
The VRP-M system with standard actuators is compatible with Fan Optimiser COU24-A-MP. The
use of VRP-M with fast running actuators is not permitted for the optimiser function!

Function The differential pressure at the static pressure sensor is converted into an actual volumetric
flow signal with a linear throughflow and serves as the actual value for the self-adaptive
PID-VAV controller.
The actual volumetric flow signal (0 ... 100% nom) can be tapped on the VRP-M as an analogue
signal.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes  / 36


VRP-M VAV System description

Brief description (continued)


The actual value x is compared with the setpoint w set on the VAV controller and the connected
damper actuator is connected according to the resulting control deviation.
The VRP-M controller can be controlled according to its application as a CAV constant
controller (min / max) or a VAV controller via the reference value input w with a modulating
0 10 / 2 10 V signal in the range from min max. Control inputs with OPEN/CLOSE/mid
functions are available for special applications.
The VRP-M can be integrated into an MP system via the MP bus connection.

Safety notes
The VRP-M system solution is not allowed to be used outside the specified field of
! application, especially in aircraft or in any other airborne means of transport.
Only components explicitly approved for this purpose by Belimo are allowed to be used for
the VRP-M system solution.
The equipment configuration and settings form part of the unit manufacturer's system
solution (OEM) and are not allowed to be modified without the OEM's prior authorisation. All
changes are liable to disrupt operation and cause damage to the system or injury to persons!
Attention must be paid to the following during the planning phase and before the VRP-M
system solution is operated:
The compatibility of the pressure sensors with the medium to be controlled must be tested,
The specifications supplied by the damper manufacturer (design, place of installation)
must be consulted and
The local technical regulations must be observed.
Applications with fast running actuator LMQ24A-SRV-ST or NMQ24A-SRV-ST: The actuator
Limitation moves first to the top, then to the bottom spindle end stops when the supply voltage is
The use of VRP-M with fast running actuators is switched on for the first time or after pressing the Adaption push-button. It then moves
not permitted for the optimiser function! into the position required by the system. The VRP-M control function is inoperative during
this procedure.
If the VRP_M solution is operated in a bus system, the cycle times of the MP bus and the
higher-level system must be taken into account.
The damper manufacturer (OEM) is responsible for ensuring that the VRP-M-system
solution is installed and set correctly as well as for overall precision. If replacement devices
are ordered, they are configured by the OEM at the factory according to the installed system.
The VRP-M system solution is sold exclusively via the OEM channel for this reason.

System characteristics
Control characteristics Adaptive, digital PID VAV controller (see System components, page 3).

Pressure measurement Belimo pressure sensors (see System components, page 3).

Damper actuators Belimo VAV damper actuators (see System components, page 3).

Optimally matched components In addition to standardised VAV and CAV applications, the VRP-M system solution is also
suitable for fast running applications such as those required in laboratories. The solution
comprises the components optimally matched with one another that are therefore only permitted
to be used in the controller-sensor-actuator combinations specified by Belimo and selected by
the unit manufacturer (see System components, page 3).

VAV variable volumetric flow Variable air volume applications based on a modulating reference variable, e.g. supplied by a
DDC controller, room temperature controller or bus operation,
The reference signal for the min ... max operating range can be set as follows:
DC 0 ... 10 V / DC 2 ... 10 V or bus operation

CAV constant volumetric flow Constant air volume applications with operating modes:
CLOSED / min / mid / max / OPEN (bus operation)

Bus function Up to eight Belimo MP devices (VRP-M / VAV-Compact / damper actuator / valve) can be
connected via the MP bus and integrated into the following systems:
DDC controller with integrated MP bus protocol
EIB Konnex system with Gateway UK24EIB
LONWORKS system with Gateway UK24LON
Modbus system with Gateway UK24MOD
BACnet system with Gateway UK24BAC
See Bus system, pages 20 to 22.
The VRP-M system with standard actuators is compatible with Fan Optimiser COU24-A-MP.
See System documentation COU24-A-MP.

Diagnostics tool PC-Tool VRP-M module, ZTH-GEN, can be plugged into the VRP-M or via external cable
connection.

 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


Technical data sheet VRP-M

Adaptive digital PID volumetric flow


controller for VRP-M system solutions
For pressure-independent VAV and
CAV systems
Control: 0 ... 10 / 2 ... 10 V or MP bus
Diagnostic socket for Service or PC-Tool

Technical data
Electrical data Nominal voltage AC 24 V, 50/60 Hz
DC 24 V
Nominal voltage range AC 20% / DC 10%
Power consumption Operation 1.1 W (incl. Sensor VF.., without damper actuator)
Dimensioning 2.6 VA (incl. Sensor VF.., without damper actuator)
Connection Actuator Plug, 6-pin
Pressure sensor Plug, 4-pin
Terminals 1 ... 7 7-pin screw terminals, 0.5 mm2 ... 1.5 mm2
VRP-M-Tool Plug, 3-pin
Functional data Reference signal w (terminal 3) Input impedance >200 k
Range: min ... max DC 0 ... 10 / 2 ... 10 V or
0 ... 20 / 4 ... 20 mA (with 500 resistance)
Actual value, volumetric flow U5 (terminal 5)
DC 0 ... 10 / 2 ... 10 V, max. 5 mA
Range 0 ... 100% nom
OPEN operating mode z1 (terminal 6) OPEN, input impedance >300 k
CAV operating modes z2 (terminal 7) CLOSED / min / mid / max
Contact current <1 mA
Control characteristics PID, adaptive
Control tolerance 5% of nom
Ranges nom Nominal volumetric flow (manufacturer-dependent)
max 30 ... 100% of nom
min 1) 0 ... 100% of nom
mid (intermediate position) 2) 0 ... 100% of min ... max
LED display AC/DC 24 V supply
Pressure too high/too low, zero VFP-..sensor
MP bus function (terminal 4) 3) MP 1 ... 8 (classic operation: PP)
Address in bus operation Adjustable with VRP-M-Tool and address push-
Functionality button
Slave
Operation / service VRP-M-Tool
Safety Protection class III Safety extra-low voltage
Degree of protection IP42
EMC CE according to 2004/108/EC
Principle of operation Type 1 (EN 60730-1)
Ambient temperature 0 ... +50C
Non-operating temperature 20 ... +80C
Ambient humidity 5 ... 95% r.h., non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / Weight Dimensions See Dimensions on page 35
Weight Approx. 250 g (without sensor)

1) See Creep flow limitation and minimum setting limit, page 10


2) Not available with DC 24 V supply
3) See Bus operation, pages 20 to 22

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes  / 36


VRP-M Adaptive volumetric flow controller

Safety notes
The controller is not allowed to be used outside the specified field of application, especially
! not in aircraft or in any other airborne means of transport.
The device does not contain any parts that can be replaced or repaired by the user.
The manufacturer of the unit (OEM) is responsible for ensuring that the VRP-M
controller is installed and set correctly as well as for the overall precision of the unit. If
replacement devices are ordered, they are configured by the OEM at the factory according to
the installed system. The VRP-M controller is sold exclusively via the OEM channel for this
reason.
The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.

Application
Together with a VFP-.. / VFD3 pressure sensor and a damper actuator, the VRP-M forms a
control system for pressure-independent variable (VAV) and constant (CAV) volumetric flow
controls.
For more information, see VRP-M system description, pages 3 ... 4

Electrical connections
Front panel

Connecting terminals 1 ... 7


Tab connection
Supply and control
Damper actuator

Tab connection
Pressure sensor

Service/PC-Tool diagnostic socket

~ T
Assignment of connecting terminals 1 ... 7 AC 24 V _
DC 24 V +
VAV reference signal min ... max
PP/MP communication
Volumetric flow actual value 0 ... 100% nom
OPEN operating mode
CAV CLOSED operating mode / min / mid / max

1 2 3 4 5 6 7
T + w MP U5 z1 z2
~

LED display and address push-button

PWR Green LED LED on: LED off:


Supply AC/DC 24 V OK Supply failure
Device ready for operation Device defective
Flashing With Set push-button pressed down for MP addressing
+ Red LED LED on:
Volumetric flow > setpoint = damper closes or is closed
Red LED LED on:
Volumetric flow < setpoint = damper opens or is open
p > 0 Yellow LED Zero offset pressure sensor VFP-..
(for procedure, see page 9)
Set Push-button for assigning the MP address in bus operation
(for procedure, see page 22)

 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


VRP-M Adaptive volumetric flow controller

Version overview, Release Note - VRP-M system solution


Up-to-date information about compatibility, versions and functions can be found at
www.belimo.eu

Electrical installation
Wiring diagrams: VAV operation Example 1: Example 2:
With analogue reference signal DC 0 ... 10 V with shut-off (CLOSED)
~ T
AC 24 V
~ T
AC 24 V _
+ DC 24 V
_
+ DC 24 V T
_
+ DC 24 V Reference value input w
T 0 ... 10

Reference value input w


CLOSED (shut-off)
0 ... 10 / 2 ... 10 / adjustable

PP/MP communication PP/MP communication


Actual value volumetric flow U5
Actual volumetric flow value
0 ... 10 / 2 ... 10 / adjustable
U5 0 ... 10 / 2 10 / adjustable
Control input z1/z2

1 2 3 4 5 6 7
~ T VRP-M 1 2 3 4 5 6 7
~ T VRP-M
_ w MP U5 z1 z2 _ + w MP U5 z1 z2
+
Conventional operation:
Functional description such as control priority VRP-M
Tool
VRP-M
Tool
LM.. / NM.. / SF.. VFP-.. LM.. / NM.. / SF.. VFP-..
See pages 11 ... 12

Example 3:
DC 0 ... 10 V with shut-off / parallel control
~ T
AC 24 V
_
+ DC 24 V
T
_ _
+ DC 24 V + DC 24 V

CLOSED (shut-off)

Notes
Supply via safety isolating transformer! !
We recommend routing connections 1, 2 1 2 3 4 5 6 7
~ T VRP-M 1 2 3 4 5 6 7
~ T VRP-M
(AC/DC 24 V) and 4 (MP signal) to accessible _ + w MP U5 z1 z2 _ + w MP U5 z1 z2

terminals (floor distributor, control cabinet, etc.),


in order to simplify access with the VRP-M-Tool VRP-M VRP-M
Tool Tool
for diagnostic and service work. LM.. / NM.. / SF.. VFP-.. LM.. / NM.. / SF.. VFP-..

Example 4: Example 5:
With bus control Typical application: MP with shut-off (CLOSED)
~ T ~ T
AC 24 V AC 24 V
_ + _ +
DC 24 V DC 24 V
MP MP

CLOSED (shut-off)

1 2 3 4 5 6 7
~ T VRP-M 1 2 3 4 5 6 7
~ T VRP-M
_ w MP U5 z1 z2 _ w MP U5 z1 z2
+ +

Bus operation: VRP-M


Tool
VRP-M
Tool
LM.. / NM.. / SF.. VFP-.. LM.. / NM.. / SF.. VFP-..
See pages 18 to 20 for a functional description

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes  / 36


VRP-M Adaptive volumetric flow controller

Electrical installation (continued)


Wiring diagrams: CAV operation Example 1: Example 2:
min max OPEN
~ T CLOSED
AC 24 V
_ +
DC 24 V min ~ T
AC 24 V
mid * _ + min
DC 24 V
max
max
_ _
+ DC 24 V + DC 24 V
OPEN OPEN (damper open)

Notes PP/MP communication PP/MP communication


Supply via safety isolating transformer! ! Actual value U5 Actual value U5
0 ... 10 / 2 ... 10 / adjustable 0 ... 10 / 2 ... 10 / adjustable
We recommend routing connections 1, 2
(AC/DC 24 V), 4 (MP signal) and 5 (UF signal)
to accessible terminals (floor distributor, control 1 2 3 4 5 6 7
~ T VRP-M 1 2 3 4 5 6 7
~ T VRP-M
cabinet, etc.), in order to simplify access with the _ + w MP U5 z1 z2 _
+
w MP U5 z1 z2

VRP-M-Tool for diagnostic and service work.


VRP-M VRP-M
Tool Tool
LM.. / NM.. / SF.. VFP-.. LM.. / NM.. / SF.. VFP-..
See pages 10 and 11 for a functional description
* Function not available with DC 24 V supply.

 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


VRP-M Adaptive volumetric flow controller

Commissioning
Prerequisites The following has been accomplished by the unit manufacturer for the system solution:
The system solution is mounted on the VAV unit
The static pressure sensor has been balanced to the zero point offset or the pressure range of
the dynamic pressure sensor has been adjusted, respectively
The VRP-M has been correctly calibrated and parameterised to the p @ nom value of the
VAV unit
The electrical connection has been made and checked
24 V supply and control have been made ready for operation
The ventilators have been put into operation

Procedure Test the electrical connection


Check the zero offset with static pressure sensor or the pressure range setting with dynamic
pressure sensor, respectively
Check the damper mobility
Test the damper angle of rotation setting, correcting it if necessary, and carry out an angle of
rotation adaptation
Check the min / max setting, correcting it if necessary
Test the supply pressure (supply/exhaust air ventilator in operation and balanced)
Test the control signal setting, adjusting it if necessary

Damper actuator angle of rotation adaptation An angle of rotation adaptation is to be performed after each adjustment of the damper angle of
rotation limitation, particularly in plants which are operated with a fan optimiser function.
Note In the case of fast runner damper actuators LMQ24A-SRV-ST and NMQ24A-SRV-ST, it is
Fast runner damper actuators mandatory that a angle of rotation adaptation be carried out after every adjustment of the angle
LMQ24A-SRV-ST and NMQ24A-SRV-ST of rotation limitation
Once the push button gear disengagement key
is pressed, a synchronisation is carried out, i.e. Procedure:
the actuator moves CLOSED and returns to the Switch on the 24 V supply
setpoint position. Press the Adaption push-button (actuator travels CLOSED OPEN setpoint position)

Static pressure sensor VFP-.. Disconnect both (!) hose connections from the sensor
Zero offset Remove the cover of the sensor housing
Rotate the zero potentiometer inside the VFP-.. until the LED in the VRP-M [p > 0] lights up ..

Rotate it back until the LED just gets off or ..


..
..
rotate it back until the voltage U5 is <0.04 V / 2.04 V (Mode = 0 ... 10 V / 2 ... 10 V) ..
.

Connect the hose connections to the sensor: observe + / setting!

Note
Static pressure sensors VFP-..
In the event of a mounting orientation that deviates U5
from the perpendicular position, it is mandatory 1 5
that a zero offset be carried out.
VFP-100 Zero potentiometer VFP-300 Zero potentiometer VRP-M LED p > 0
VFP-600

Dynamic pressure sensor VFD3 The DIP switches for adjusting the pressure range are located under the VFD3 housing cover.
Pressure range setting
DIP switch Pressure
Remarks
Position range

0 ... 100 Pa

DIP 0 ... 300 Pa Default setting

Note 0 ... 600 Pa


Dynamic pressure sensor VFD3
The pressure range of the VFD3 is set in the Cannot be used
factory by the manufacturer of the VAV unit 20 ... 100 Pa
with the VRP-M
and configured accordingly in the VRP-M. It is
mandatory that an adjustment of the pressure
range requires an adaptation in the VRP-M If necessary, the setting of the DIP switches can be sealed with a compatible lacquer. It is
configuration. recommended for purposes of documenting the setting that the selected pressure range be
The pressure range 20 ... 100 Pa cannot be used marked on the housing cover with a waterproof felt-tip pen.
with the VRP-M. The VFD3 is not equipped with an external zero adjustment.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes  / 36


VRP-M Adaptive volumetric flow controller

Functions
Nominal volumetric flow nom nom corresponds to the maximum volumetric flow of the VAV unit at which the pressure drop
and noise are still within the permissible operating conditions. The nom values are specified and
programmed permanently by the unit manufacturer.
The volumetric flow actual value signal U5 is always in reference to the nom. For this reason,
changes in the operating volumetric flow setting min and max have no influence on the U5 V
signal
Start point nom

V]
U5[
al
ign
es
0 ... 10 V alu
lv
2 ... 10 V tua
adjustable ac
w
flo
ic
m etr
lu
Vo

Volumetric flow [nom]


End point

Creep flow limitation Creep flow limitation (1)


Minimum setting limit min This function suppresses differential pressure signals in the zero region. Thanks to this limitation,
undefined actuator movements in the effective pressure range of 1 ... 6 Pa are prevented. The
operating range is physically limited owing to the dynamic behaviour of the differential pressure
sensor in this area and the flow pattern of the fluid being pumped.

Sensor Pressure range Limitation


VFP-100 0 ... 100 Pa 1 Pa
VFP-300 0 ... 300 Pa 3 Pa
VFP-600 0 ... 600 Pa 6 Pa
VFD3 0 ... 100 Pa 1 Pa
0 ... 300 Pa 3 Pa
0 ... 600 Pa 6 Pa

Unit manufacturer's minimum setting limit (2)


Oversized VAV units can make it harder to regulate the lowermost pressure value range.
The manufacturer will specify the lowest permissible volumetric flow for the units, usually
corresponding to a pressure value of approximately 5 ... 12 Pa. Functional restrictions in this
range can be avoided by complying with the unit manufacturer's volumetric flow adjustment.

Setting Setting
[min] [max]

100% 100%
a Optimum range
b Setting with restriction
c Setting with greatest
restriction

a
b
30%
c
2
1
0% Reference signal w
0/2 10 [V]
1 Creep flow limitation <2 Pa
2 Unit manufacturer's minimum setting limit

10 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


VRP-M Adaptive volumetric flow controller

Functions (continued)
Control tolerance The maximum permissible control tolerance is defined as a percentage of the nominal volumetric
flow nom. If the control deviation exceeds or undershoots this tolerance, the actuator is adjusted
so that the actual volumetric flow corresponds to the required setpoint.
Control tolerance: 5% of nom
The two LEDs [+p] and [-p] will show the following when the maximum control tolerance is
exceeded or undershot or when the actuator in movement must be corrected by the deviation:
LED [+p]: actual value > (setpoint + control tolerance) = damper closes
LED [-p]: actual value < (setpoint + control tolerance) = damper opens
VAV operating volumetric flow In variable operation, the pressure is specified by means of the reference signal in the range
Setting min ... max min ... max.
max forms the upper limit value as a function of the nominal volumetric flow.
Adjustment range 30 ... 100% of nom.
min forms the lower limit value as a function of nom.
Adjustment range 0 ... 100% of nom.

[max]
Reference signal w
[V]

Volumetric flow actual value signal U5 [V]


max nom
Example with Mode 0 10 V

Variable operation

Volumetric flow [% nom]

[min]

Voltage level Start point End point

0,0 10
Mode:
min < Modulating operation > max 010 V

Shut-off

0,0 0,1 2,0 10


CLOSED min < Modulating operation > max 210 V

In 2 10 V mode, it is possible to achieve shut-off operation (damper CLOSED) by lowering the


reference signal to 0.0 V.

For override control in VAV operation, e.g. CLOSED or OPEN, the reference signal w (Input 3)
can be overridden by wiring the control inputs 6 (z1) and 7 (z2).
CAV operating modes Five operating modes are available for step mode:
CLOSED / min / mid / max / OPEN Shut-off operation Damper CLOSED: The damper is moved into the CLOSED position in a
defined manner.
Operating modes min / mid / max: The VRP-M permanently regulates the selected
volumetric flow.
Flushing operation damper OPEN: The damper can be opened for maximum ventilation, in
which case volumetric flow control is deactivated!
The operating mode control signals are connected to inputs 6 (z1) and 7 (z2). If signals appear
at these two inputs simultaneously, input 6 (z1) for the OPEN function takes priority.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 11 / 36


VRP-M Adaptive volumetric flow controller

Functions (continued)
30 40 50 60 70 80 90 100% [max]

CAV operating mode


nom
max
OPEN
(depending on supply
pressure)
Constant operation

mid

min

CLOSED

Note
mid is not available with DC 24 V supply.
Volumetric flow [% nom]
0 10 20 30 40 50 60 70 80 90 100

[min]
43%
VAV operation with override If necessary, the VAV min ... max range can be overridden by fixed operating modes in VAV
CLOSED / min / mid / max / OPEN applications.
The following operating modes are available:
Shut-off operation Damper CLOSED: The damper is moved into the CLOSED position in a
defined manner.
Operating modes min / mid / max: The VRP-M permanently regulates the selected
volumetric flow.
Flushing operation damper OPEN: The damper can be opened for maximum ventilation, in
which case volumetric flow control is deactivated!
30 40 50 60 70 80 90 100% [max]

Reference signal w OPEN


[V]
2 4 6 8 10 Volumetric flow actual value signal U5 [V]
10
Example with Mode 2 10 V

max nom

6
Variable operation
mid
4

min
2
Notes
min: All inputs (3 / 6 / 7) open. CLOSED Constant operation
mid not available with DC 24 V supply. 0
Volumetric flow [% nom]
0 10 20 30 40 50 60 70 80 90 100

[min]
41%

Priorities for reference value input 3 (w) If several signals appear simultaneously, they are processed according to the following priorities.
and control inputs 6 (z1) / 7 (z2)
Terminal Priority Function
6 z1 1 OPEN
7 z2 2 CLOSED / min / mid / max
3 w 3 min max

12 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


VRP-M Adaptive volumetric flow controller

System configuration
Unit manufacturer's settings The system solution selected by the unit manufacturer is mounted by the latter on the VAV unit
and configured according to the system requirements (as stated in the order). This configuration
comprises the following settings:
VRP-M-Tool
Expert tab
System information

Function Volumetric flow


Sensor The pressure sensor type is specified to enable the pressure range to be adapted.
Actuator The actuator type is specified for the adaptation of the running time characteristics.
Density Density adjustment to the environment.
Height Height above sea level for density calculation.
Control reference signal w, The reference signal w and the volumetric flow actual value signal U5 are adapted to the MCR
actual volumetric flow signal U5 system.
Selection DC 0...10 V / DC 2...10 V / adjustable (sequence matching in the 0...10 V range)
Calibration nom The nom values are specified and permanently programmed by the unit manufacturer.
With the setting of the nom, every VRP-M system solution is optimally adapted to the VAV unit
used. nom corresponds to the maximum volumetric flow of the VAV unit at which the pressure
drop and noise are still within the permissible operating conditions. The nom setting is specified
by the unit manufacturer.
Volumetric flow
Actual value signal U5
[V]
NW... NW... NW...
NW100
10 nom

0 Volumetric flow [nom]

Smallest Largest
Nominal diameter Nominal diameter
OEM unit product range

Replacement orders If replacement devices are ordered, they must be parameterised beforehand by the OEM at the
factory according to the installed system. The VRP-M is sold exclusively via the OEM channel for
this reason.

Note
The equipment configuration and settings form
part of the unit manufacturer's system solution
(OEM) and are not allowed to be modified without
the OEM's prior authorisation. All changes are
liable to disrupt operation and cause damage to
the system or injury to persons!

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 13 / 36


VRP-M Adaptive volumetric flow controller

PC-Tool VRP-M module operating data setting


Adjustments on the system with PC-Tool The VRP-M module enables, if needed, the adjustment of the operating data (min, mid, max
settings) and of the reference signals (Setting mode Voltage range) to the requirements at the
plant. The PC-Tool adapter must be connected to the diagnostics socket on the VRP-M or to the
MP connection routed to the terminals for this purpose
(see pages 16 ... 17).
VRP-M module
Service tab

1 2

1 Identification 5 Checking Operation:


2 Operating volumetric flow settings Reference signal display
3 System designation entry Pressure value [Pascal]
4 Volumetric flow Setpoint / actual value display [m3/h, l/s]
Operating mode selection:
AUTO / CLOSED / OPEN
min / mid / max / nom
Variable setpoint (min ... max)

Operating volumetric flow settings These parameters are used to set the VAV unit to the air volumes required for the respective
application.
The settings are based on the air volumes calculated by the planning engineer and can either be
preset by the VAV unit manufacturer or adjusted on the system using the VRP-M module.

max Adjustment range 30 ... 100% of nom


Upper volumetric flow limit
min Adjustment range 0 ... 100% of nom
Control range x * ...100% of nom
Lower volumetric flow limit
Shut-off operation (CLOSED) via min setting
If a shut-off function is required in VAV operation, it can be achieved with the setting min 0%
mid Range 0 ...100% of the range min ... max
An intermediate position mid is available for constant volume applications (CAV) to facilitate finer
steps.

* min settings below the control range


min values below the start value displayed in the range can be set, e.g. for VAV units with shut-off function

System designation entry Input field (16 characters) for specific system designations, e.g. MCR address, system name,
item number in diagram, etc.

14 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


VRP-M Adaptive volumetric flow controller

PC-Tool VRP-M module Operating data settings (continued)


VRP-M module
Expert tab

1
4

1 Mode setting: 3 VRP-M system information


Standard 0 ... 10 / 2 ... 10 V VRP-M version and calibration value setting
2 Control Volumetric flow function
Individual setting Sensor type
Reference signal w Actuator type
Volumetric flow actual value signal U5 4 Ambient conditions
Height above sea level
Density

Mode setting Options: 0... 10 V / 2...10 V / individual setting


The mode setting acts on the reference signal w and the volumetric flow actual value signal U5.
Variable settings are displayed here and can also be reset by selecting 2 ... 10 / 0 ... 10 V.
Variable settings are entered in the Control field above.
Control It is sometimes essential to adapt the reference signal w or the volumetric flow actual value
Variable setting signal U5 to the MCR system directly on the control system.
The reference signal w and the volumetric flow actual value signal U5 can be set to different
values (e.g. reference signal w: 2 ... 10 V / actual value signal U5: 0 ... 10 V).
Reference signal [w] / operating range min ... max
Start point: DC 0.0 ... 8 V
Stop point: DC 2.0 ... 10 V
Actual value signal [U5] / display range 0 ... 100% nom
Start point: DC 0.0 ... 8 V
Stop point: DC 2.0 ... 10 V
Ambient conditions With this function, the VRP-M solution and the VFD3 sensor can be adjusted to the geographical
environment of the plant.
Plant
785 m

550 m

Sea level
0m

All relevant parameters can be entered through the Ambient conditions adjustment marker in
the Expert tab. the following values are required for calculating the density and the correction
value for the VFD3 signal:
Correction
Typical setting value
influence
Height above e.g. 1822 m, for St. Moritz,
large
sea level Switzerland
Temperature of
medium Mean value, e.g. 19C
medium
Humid medium negligible Average, e.g. 45% r.h.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 15 / 36


VRP-M Adaptive volumetric flow controller

PC-Tool VRP-M module Availability


The current version of the PC-Tool or the VRP-M module, respectively, and the associated
documentation can be downloaded from www.belimo.eu.

PC-Tool connection
The PC-Tool required for settings and servicing can be connected either directly to the 3-pin
service socket on the VRP-M controller or via the MP connection (terminal 4). A level converter
ZIP-USB-MP or ZIP-RS232 is required for communication.

Conventional operation (PP) Connection via service socket

VRP-M VRP-M
Modul Modul
AC 230 V

ZN230-24
ZIP-RS232 ZIP-USB-MP
Actuator
ON
T ~ U
PP
USB USB

RS232
OFF 1 2 5

AC 24 V

ZKS-MP

VRP-M

AC/DC 24 V

Connection in control cabinet


VRP-M
Modul

ZIP-USB-MP
USB

ZK2-GEN

PP/MP GND

VRP-M

1 2 4

AC/DC 24 V
white = GND (1)
green = MP (4)
blue = do not connect

16 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


VRP-M Adaptive volumetric flow controller

PC-Tool connection
MP bus mode The PC-Tool can only be connected via the bus master during MP bus operation because
otherwise two MP masters would be connected on the same MP bus. This means the local
connection to the VRP-M is not permitted to be operating at the same time as the MP master.

VRP-M
Modul

ZIP-USB-MP
USB

MP 1 MP ..

UK24LON
Notes ZKS-MP 2
The service plug integrated in the VRP-M is not + -
available with bus operation.
The MP bus cannot be used to transmit open
and closed-loop control functions if it is also MP .. MP 8
used to connect the PC-Tool. MP-Bus
Workaround: Undo MP bus (terminal 4) and use
local MP plug or tool connection on the UK24... + -

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 17 / 36


VRP-M Adaptive volumetric flow controller

Service-Tool ZTH-GEN
Service-Tool for parameterisable and communicative Belimo actuators and VAV controllers.
Local connection via service socket on the device or remote control via MP/PP connection.

Connection and supply The ZTH-GEN is supplied via the actuator/VAV controller. The connection is set up
directly at the Service socket of the actuator/VAV controller or
via the PP/MP connection, e.g. connection socket, in the control cabinet, room controller CR24

Local connection via service socket Connection to Cable type Connection


ZK4-GEN 1 GND
2 ~/+ ZTH-GEN connection in MP bus system:
VRP-M ZK4-GEN The MP connection should be separated
3
blue from the MP bus while the ZTH-GEN is
4 PP
operating.

Direction connection to terminals Connection to Cable type Connection


VAV-Universal actuators:
white 1 GND The V actuators NM24A-S-ST,
blue 2 ~/+ LMQ24A-SRV-ST and NMQ24A-SRV-ST,
VRP-M ZK2-GEN suitable for the VAV universal controller
3
turquoise 4 PP VRP-M (STP), have a tool connection, but
are not tool-capable.

Connection in the MP bus system Right ZTH-VAV Wrong ZTH-VAV

+ OK + OK

MP6 MP6

MP7 MP7
MP1 MP1

MP8 MP8
MP4 MP4
MP5 MP5

MP2 MP3 MP2 MP3

Direct connection to the MP bus or MP master is not possible with the ZTH-GEN.
Solution: Use the service socket on the VAV controller or temporarily disconnect the MP
connection of the MP device from the MP bus and connect the ZTH-GEN to the MP connection.

Menu structure, handling The operating menu can be run through from both sides .
Device identification
Starting / ending
z1 Type
RJ plugs
z2 Position
Type - Type + Type
OK

z2 Designation Firmware Serial number

Data, settings Option, range


Option 1 - + x ... y

OK

Option 2 - + x ... y OK

Starting / ending The connection to the actuator/VAV controller is started by plugging in the RJ plug and
terminated by unplugging it.

18 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


VRP-M Adaptive volumetric flow controller

Configuration
Start Configuration 1. Press the key (OK) while simultaneously plugging in the connecting cable

2. Configuration menu display appears

Configuration menu Option / Display Setting Product range Explanation


HW Version Vx.x Display of the current hardware and
FW Version Vx.x firmware version of the ZTH-GEN
Text German / English -
VAV unit m3/h / l/s / cfm VAV
EPIV unit m3/h / l/min / gpm Valves
Supply. ... Display of the current AC 24
AC V VHW: % V supply voltage, with direct
connection to terminals (ZK2-GEN)
Start MP tester OK - MP bus diagnostics tool for system
integrators.
The MP tester is not a component
part of this documentation.
PICCV function 0/1 Valves Belimo US
Enable PICCV Wizard function
Expert Mode 1) 0/1 VAV 3) Enable VAV settings:
Switching mode,
set min / max to original values
(call up OEM setting)
Advanced Mode 2) 0/1 VAV 3) Enable settings:
Fire protection VAV: Direction of rotation,
BF-Top: Adaption
Exit Configuration OK
1) 2)
Activate options and only as needed and with the respective know-how; the adjustment of the respective
parameters requires special expertise.
3) only for VAV-Compact

Functions for VAV product range


Menu tree Device identification

z1 Type Start
Position
z2
Type - Type + Type
OK

z2 Designation Firmware Serial number


Data, settings
Volume 125 m3/h z1


Setpoint 124 m3/h z2



p 164 Pa z2

Position 65% z2 Option, range

Step >Auto< z2 - + Auto / Open / Closed / max / min / Stop OK
Mode 2 ... 10 V z1
Expert



new 0 ... 10 V z2 - + 0 ... 10 / 2 ... 10 V OK

min 10 m3/h z1


new 25 m3/h z2 - + 0 ... max OK
max 250 m3/h z1

- +

new 200 m3/h z2 min ... max OK

nom 250 m3/h z1

Address PP z1


new MP4 z2 - + PP / MP1 / MP2 / MP3 ... MP8 OK

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 19 / 36


VRP-M Adaptive volumetric flow controller

Bus operation
The VRP-M system solution can be interconnected with other Belimo MP actuators (damper
actuators, valve actuators, VAV-Compact controllers, VRP-M system solutions) thanks to the
integrated communication principle over the Belimo MP bus. The maximum of eight Belimo MP
devices are supplied with a digital control signal by the higher-level bus master and then opened
to the position dictated by this signal.
The switching from conventional to bus mode takes place automatically, as soon as an MP
address (1...8) is assigned to the MP actuator.
The Belimo MP devices can be integrated in the following systems:
LONWORKS: The variables of Functional Profile 8110 can be used in conjunction with the
Belimo UK24LON interface.
EIB-Konnex: In connection with the Belimo UK24EIB interface
DDC controller with an integrated MP bus protocol: Available from several manufacturers
Damper position (starting with VRP-M Version V3.x)
(nvoAbsAngle absolute actuator position in angular degrees ())
The feedback signal, i.e. the network variable nvoAbsAngle, is not available for applications with
NM24-V-ST actuators (old actuator generation).
MP bus cycle time
The cycle time of the MP bus must be noted when integrating setpoints and actual values. It is
typically 28 s, depending on the number of connected bus users and integrated sensors.
The local VRP-M control function is not affected by the cycle time. The cycle time of the MP bus
must always be taken into account, however, when selecting setpoints via the MP bus.
Principle of operation Sensor integration (starting with VRP-M version V3.x)
The VRP-M can be connected to an additional active 0 ... 10 V signal in MP bus mode
independently of the VAV control loop. The sensor signal is connected to the reference value
input that is not used in MP bus mode (connection 3).
The VRP-M acts in this capacity as an analogue/digital converter for the transmission of the
sensor signal to the higher-level system. This must know the physical address (which sensor at
which MP device) and be able to interpret the respective sensor signal.
~ T
Active sensor connection
DC 24 V _ +
MP

0 10 V
Sensor T

1 2 3 4 5 6 7
~ T VRP-M
_ + w PP U5 y z

Active 0 ... 10 V sensors for open and closed-loop control functions in the higher-level
system, such as moisture or CO2 sensors. The cycle time must be taken into account in the
implementation!
Reference signal w setting if an active sensor is connected: 0 10 V
Integration of switches, passive The VRP-M only supports active sensors with a 0 10 V output; i.e. no switches or passive
resistance sensors sensors (resistance elements) can be integrated.
Principle of VRP-M in bus operation In bus operation, the VRP-M controller receives its reference signal from the higher-level control
system and adjusts the volumetric flow to the fixed selected value in the range min ... max.
If needed, the VAV range min ... max can be overridden in bus operation by fixed operating
modes (control inputs z1 and z2).
The following operating modes are available:
Shut-off operation Damper CLOSED: The damper is moved into the CLOSED position in a
defined manner.
Operating modes mid / max: The VRP-M permanently moves the selected volumetric flow.
Flushing operation damper OPEN: The damper can be opened for maximum ventilation, in
which case the volumetric flow control is deactivated.

20 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


VRP-M Adaptive volumetric flow controller

Bus operation (continued)


[max]

Reference signal OPEN


[%]
Volumetric flow actual value signal
(e.g. UK24LON nvcActualValve)
max nom
Reference signal
(e.g. UK24LON nviRelStpt)

mid

Note CLOSED
mid is not available with DC 24 V supply. min
Volumetric flow [% nom]

[min]

Operating volumetric flow setting min / max The setpoint selected over the MP bus is resolved by means of the min and max settings on
the VRP-M.
Function Volumetric flow Range
nom Nominal OEM-specific value, depending on the application and the VAV unit type
max Maximum 30 ... 100% of nom
min Minimum 0 * ... 100% of nom
* The minimum volumetric flow adjustment min is dependent on the VAV unit used, or is influenced by the
creep flow limitation, respectively (see the function: Creep flow limitation / Minimum setting limit).

Open operating volumetric flow setting The min / max setting can be open if necessary, i.e. with a setting of min 0% / max 100%. In
this case, the volumetric flow must be limited in the higher-level system.
This operating setting allows the limitation of the volumetric flow to be adjusted without altering
the parameters on the VAV controller.
Responsibility for the limiting function passes from the unit manufacturer to the system supplier
or integrator.
Bus signal priorities (MP setpoint) If several signals appear simultaneously, they are processed according to the following table of
and control inputs 6 (z1) / 7 (z2) priorities.
Terminal Priority Function
6 z1 1 OPEN
7 z2 2 CLOSED / mid / max
3 MP override function
1 OPEN
2 CLOSED
3 max
4 min
5 mid
6
Note 7 nom
Note the speed of the MP bus! 4 MP setpoint 0 ... 100% = min ... max

Bus fail function


The VRP-M saves the current setpoint, i.e. the last setpoint to have been received from a bus
master (VRP-M-Tool, UK24LON). If the MP network fails, the connected VRP-M detects this and
Last setpoint retains this setpoint until it receives a new one from the MP master.
Initial setpoint after power failure The VRP-M starts with its MP initial status (setpoint 0%, corresponding to the min setting) if a
power failure occurs in the intervening period.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 21 / 36


VRP-M Adaptive volumetric flow controller

MP bus
Topology The cables of up to eight actuators can be laid in a freely definable topology. The following
topologies are permitted: star, ring, tree or mixed forms.

Up to 8 MP bus users

Connection The network consists of a 3-pin connection (MP communication and 24 V supply). Neither
special cables nor terminating resistors are required. Power can be supplied either through the
bus cable or from a local power supply.
~ T
AC 24 V
DC 24 V _ +
MP

Additional MP bus users

1 2 3 4 5 6 7
~ T VRP-M 1 2 3 4 5 6 7
~ T VRP-M
_ + w MP U5 z1 z2 _ + w MP U5 z1 z2

Network Up to eight MP actuators can be connected in a network (VAV-Compact, VRP-M etc.).


Supply with AC or DC voltage
Nominal voltage AC 24 V, 50/60 Hz, DC 24 V
Power supply range AC 19.2...28.8 V, DC 21.6...26.4 V
Dimensioning See Technical data, page 7
MP bus signal cable length
The cable lengths are limited:
By the sum of the performance data of the connected devices, e.g. VAV controllers, actuators
By the type of supply (AC 24 V or DC 24 V)
By the cable cross-section.
For more information about planning and installation, see www.belimo.com
VAV-Compact NMV-D2-MP products information
Bus and communication systems section
Addressing If the VRP-M system solution is integrated in a bus system, each connected VRP-M must be
assigned an MP address in the range 1 ... 8.
Procedure
Start the addressing procedure on the MP bus master VRP-M-Tool, UK24LON etc.
For the procedure, see the documentation of the bus master used
Procedure with VRP-M-Tool:
a) Select Addressing via serial number
Enter the serial number of the VRP-M (sticker on the VRP-M, display in the VRP-M-Tool)
b) Select addressing with acknowledgement on the VRP-M
Acknowledge the selected address by pressing the Set key on the desired VRP-M. If the Set
key is pressed, then the Power LED will flash (green)

22 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


Technical data sheet VFP-..

Static differential pressure sensors


for neutral to slightly aggressive gases
Measuring range, type-dependent,
0 ... 100 / 300 / 600 Pa
Cable connection with plug suitable for
VAV-Universal VRP-M

VFP-300
VFP-100 VFP-600

Type overview

Temperature sensitivity
Type Measuring ranges Overload protection Weight
of zero
VFP-100 0 ... 100 Pa max. 500 Pa 0.1% / K Approx. 500 g
VFP-300 0 ... 300 Pa Max. 1500 Pa 0.05% / K Approx. 280 g
VFP-600 0 ... 600 Pa Max. 3000 Pa 0.05% / K Approx. 280 g

Technical data
Electrical data Supply DC 15V (from VRP-M controller)
Connection 1 m cable with 4-pin plug
(suitable for VRP-M)
Functional data Type, principle of operation Pressure measurement by means of diaphragm
(static, inductive)
Measuring range See Type overview
Overload protection See Type overview
Measuring medium Neutral to slightly aggressive gases
Parts in contact with medium Ni, Al, CuBe, PU
Linearity 1% of final value (FS)
Switching differential Max. 0.1% of final value
Temperature sensitivity Zero See Type overview
Measuring range t = +10 ... 40C (reference temperature t0 = 25C)
Mounting orientation Upright (nipple on bottom or side)
Position dependency Max. 4.5 Pa
With 90 rotation around horizontal spindle
Connection for pressure hoses Hose nipple
for hose with 4 ... 6 mm interior diameter
Safety Protection class III Safety extra-low voltage
Degree of protection IP42
EMC CE according to 2004/108/EC
Principle of operation Type 1 (EN 60730-1)
Ambient temperature 0 ... +50C
Non-operating temperature 10 ... +70C
Ambient humidity 5 ... 95% r.h., non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / Weight Dimensions See Dimensions on page 35
Weight See Type overview

Safety notes
The pressure sensors must not be used outside the specified field of application,
! especially in aircraft or in any other airborne means of transport.
It may only be installed by suitably trained personnel.
Legal regulations and regulations issued by authorities must be observed during installation.
The devices do not contain any parts that can be replaced or repaired by the user.
The devices contain electrical and electronic components and are not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 23 / 36


VFP-.. Static pressure value sensors

Product features
Application Together with a VRP-M controller and a Belimo damper actuator, the VFP-.. static pressure
sensors form a control system for pressure-independent variable (VAV) and constant (CAV)
volumetric flow controls.
The pressure sensors are used for static differential pressure measurement with pick-up devices
installed in air ducts. They can also be used with contaminated or mildly aggressive air 1). Their
robust design makes them ideal for installation in laboratories, clean room systems and industrial
applications.

Principle of operation A high-quality metal diaphragm is used in the sensor. The measured pressure produces a
corresponding diaphragm stroke, which is detected inductively and converted to a pressure-
linearised output signal.
The measuring signal is influenced by the mounting position due to the dead weight of the
diaphragm. The sensor is calibrated in vertical position at the factory, although it can, if
necessary, e.g. if installed in another position, be readjusted at the utilisation site.
The temperature is compensated to reduce drift to a minimum. The wear-free, inductive
measurement method guarantees maintenance-free operation.
1)See Technical data, page 23
For zero offset and more information, see System description, page 9

Electrical installation
The ready-to-connect sensor unit is connected to the VRP-M controller
with the 4-pin plug.

24 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


Technical data sheet VFD3

Dynamic pressure value sensor for room


ventilation applications in the comfort zone
Measuring range:
adjustable with DIP switch in the range
between 0 ... 100 / 300 / 600 Pa
Cable connection with plug, suitable for
VAV-Universal VRP-M

Technical data
Electrical data Nominal voltage AC 24 V, 50/60 Hz / DC 1524 V
Nominal voltage range AC 19.2 28.8 V / DC 13.5 28.8 V
Power consumption Operation 0.35 W
Dimensioning 0.75 VA
Connection Pre-mounted 1 m cable with 4-pin plug,
compatible with VRP-M
Functional data Type, principle of operation p sensor with dynamic measurement principle
Range of use, measuring medium Outside air/exhaust air in the comfort zone with
sensor-compatible media
Medium temperature 0 ... 50C
Humidity of the medium 5 ... 95% r.h., non-condensating
Materials in contact with medium Glass, epoxy resin, PA, TPE
Connection for pressure hoses Hose nipple 6 mm,
with + and connection designation
Nominal voltage range Can be selected with DIP switch:
0 100 Pa
0 300 Pa (default setting)
0 600 Pa
20 100 Pa (cannot be used with the VRP-M)
Accuracy 1 Pa in the pressure range 20 20 Pa
5% in the pressure range 20 500 Pa
6.5% in the pressure range 500 600 Pa
Zero <1%, no balancing required
Loading capacity 5000 Pa
Installation position Any, no reset necessary
Response time <50 ms (<100 ms after Power-Up)
Output signal 0 ... 10 V, max. load 1 mA
Safety Protection class III Safety extra-low voltage
Degree of protection IP40
EMC CE according to 2004/108/EC
Principle of operation Type 1
Rated current voltage 0.8 kV
Control pollution degree 3
Ambient temperature 0 ... +50C
Non-operating temperature 20 ... +60C
Ambient humidity 0 ... 95% r.h., non-condensating
Dimensions / Weight Dimensions (H x W x D) See Dimensions on page 35
Weight Approx. 170 g

Safety notes
The pressure sensors must not be used outside the specified field of application,
! especially in aircraft or in any other airborne means of transport.
It may only be installed by suitably trained personnel.
Legal regulations and regulations issued by authorities must be observed during installation.
The devices contain electrical and electronic components and are not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 25 / 36


VFD3 Dynamic pressure value sensor

Product features
Application Recording of p values in conventional heating, ventilation and air conditioning room ventilation
comfort applications, e.g.:
Negative and positive pressure in the duct system with reference to the ambient pressure
Volumetric flow of supply air/exhaust air in combination with Belimo VAV universal controller
VRP-M

Principle of operation The integrated maintenance-free D3 pressure value sensor functions in accordance with the
dynamic measurement principle. The differential pressure p present at the sensor is available
at the analogue output as 0 ... 10 V value.

Note
Dynamic pressure sensor VFD3
The pressure range of the VFD3 is set in the
factory by the manufacturer of the VAV unit
and configured accordingly in the VRP-M. It is
mandatory that an adjustment of the pressure
range requires an adaptation in the VRP-M
configuration.
The pressure range 20 ... 100 Pa cannot be used
with the VRP-M.

26 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


Technical data sheet LMQ24A-SRV-ST

Fast-running damper actuator for VRP-M


system solution
Torque 4 Nm
Running time 2.5 s

Limitation
The use of VRP-M with fast running actuators is
not permitted for the optimiser function!

Technical data
Electrical data Supply AC/DC 24 V (from VRP-M controller)
Power consumption Operation 13 W @ nominal torque
Rest position 1.5 W
Dimensioning 23 VA
Connection 0.5 m cable with 6-pin plug
(suitable for VRP-M)
Functional data Torque (nominal torque) Min. 4 Nm @ nominal voltage
Direction of rotation As an option with switch 0 / 1
Direction of motion at Y = 0V In switch position 0 or 1
Angle of rotation max. 95 , mechanical end stops adjustable
Running time 2.5 s / 90
Sound power level 52 dB (A)
Position indication Mechanical, plug-in
Safety Protection class III Safety extra-low voltage
Degree of protection IP54 in all mounting positions
EMC CE according to 2004/108/EC
Principle of operation Type 1 (EN 60730-1)
Ambient temperature 30 ... +50C
Non-operating temperature 40 ... +80C
Ambient humidity 95% r.h., non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / Weight Dimensions See Dimensions on page 35
Weight Approx. 810 g

Safety notes
The actuator is not allowed to be used outside the specified field of application, especially in
! aircraft or in any other airborne means of transport.
It may only be installed by suitably trained personnel.
Legal regulations and regulations issued by authorities must be observed during installation.
The device may only be opened at the manufacturer's site. It does not contain any parts that
can be replaced or repaired by the user.
The cable must not be removed from the device.
Self adaptation is necessary when the system is commissioned and after each adjustment of
the angle of rotation (press the adaptation push-button).
When calculating the torque required, the specifications supplied by the damper
manufacturers (cross-section, construction, place of installation), and the ventilation
conditions must be observed.
The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 27 / 36


LMQ24A-SRV-ST Fast-running damper actuator for VRP-M system solution

Product features
Simple direct mounting Simple direct mounting on the damper spindle with a universal spindle clamp; a universal
mounting bracket is enclosed to prevent the actuator from rotating.

Manual override Manual override with self-resetting push-button.


The position calculation is synchronised in order to prevent deviations as a result of manual
override. This synchronisation acts at the same time as a simple functional check (see below
Synchronisation).

Adjustable angle of rotation The angle of rotation is adapted to the available setting range by the manufacturer of the damper
by means of integrated, mechanical end stops.
Permissible range: 63 ... 100%.
Adaption Adaptation to the available angle of rotation
Caution! This function detects the upper and lower spindle end stops and stores them in the actuator. The
An adaption must be carried out when the ! running time and the operating range are adapted to the available angle of rotation. Detection
system is commissioned or whenever the of the mechanical end stops enables a gentle approach to the end position and protects the
end stops for angle of rotation limiting are actuator and damper mechanisms. The actuator moves first to the top, then to the bottom
adjusted (press the Adaption push-button spindle end stops when the supply voltage is switched on for the first time, i.e. at the time of
once). commissioning or after pressing the Adaption key.

Home position Actuation of the Gear disengagement key causes the actuator to move to home position. This
function is performed by the actuator, even when the supply voltage is restored, if the Gear
disengagement key was pressed during the electricity interruption.

Pos. direction of rotation switch Home position


0
Y = 0 ccw Left end stop
1 Y = 0 cw Right end stop

After this procedure, the actuator then moves into the position defined by the system.

Functional check An extremely simple functional check of the dampers is possible: The gearbox can be
disengaged simply by pressing the gear disengagement key on the housing. As long as the
key remains pressed, the damper can be operated manually.

High functional reliability The actuators are overload-proof, require no limit switches and automatically stop when the end
stop is reached.

Electrical installation
The ready-to-connect actuator unit is connected to the VRP-M controller
with the 6-pin plug.

Display and operating elements

1 Direction of rotation switch


1 Switching over: Direction of rotation changes

2 2 Push-button and LED display green


Off: No power supply or fault
3 Illuminated: Operation
Press key: Initiates angle of rotation adaptation, followed by standard mode
4
3 Push-button and LED display yellow
Off: Standard mode
5 Illuminated: Adaption or synchronisation process active
Press key: No function
4 Gear disengagement key
Press key: Gearbox disengaged, motor stops, manual override possible
Release key: Gearbox engaged, synchronisation starts, followed by standard mode
5 Communication (PC-Tool, ZTH-GEN) is blocked for this actuator type

28 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


Technical data sheet NMQ24A-SRV-ST

Fast-running damper actuator for VRP-M


system solution
Torque 8 Nm
Running time 4 s

Technical data
Electrical data Supply AC/DC 24 V (from VRP-M controller)
Power consumption Operation 12 W @ nominal torque
Rest position 1.5 W
Dimensioning 18 VA
Connection 0.5 m cable with 6-pin plug
(suitable for VRP-M)
Functional data Torque (nominal torque) Min. 8 Nm @ nominal voltage
Direction of rotation As an option with switch 0 / 1
Direction of motion for Y = 0 V In switch position 0 or 1
Angle of rotation max. 95 , mechanical end stops adjustable
Running time 4 s / 90
Sound power level 52 dB (A)
Position indication mechanical, plug-in
Safety Protection class III Safety extra-low voltage
Degree of protection IP54 in all mounting positions
EMC CE according to 2004/108/EC
Principle of operation Type 1 (EN 60730-1)
Ambient temperature 30 ... +50C
Non-operating temperature 40 ... +80C
Ambient humidity 95% r.h., non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / Weight Dimensions See Dimensions on page 35
Weight Approx. 930 g

Safety notes
The actuator is not allowed to be used outside the specified field of application, especially in
! aircraft or in any other airborne means of transport.
It may only be installed by suitably trained personnel.
Legal regulations and regulations issued by authorities must be observed during installation.
The device may only be opened at the manufacturer's site. It does not contain any parts that
can be replaced or repaired by the user.
The cable must not be removed from the device.
Self adaption is necessary when the system is commissioned and after each adjustment of
the angle of rotation (press the Adaption push-button once).
When calculating the torque required, the specifications supplied by the damper
manufacturers (cross-section, construction, place of installation), and the ventilation
conditions must be observed.
The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 29 / 36


NMQ24A-SRV-ST Fast-running damper actuator for VRP-M system solution

Product features
Simple direct mounting Simple direct mounting on the damper spindle with a universal spindle clamp; a universal
mounting bracket is enclosed to prevent the actuator from rotating.

Manual override Manual override with self-resetting push-button.


The position calculation is synchronised in order to prevent deviations as a result of manual
override. This synchronisation acts at the same time as a simple functional check (see below
Synchronisation).

Adjustable angle of rotation The angle of rotation is adapted to the available setting range by the manufacturer of the damper
by means of integrated, mechanical end stops.
Permissible range: 63 ... 100%.
Adaption Adaptation to the available angle of rotation
Caution! This function detects the upper and lower spindle end stops and stores them in the actuator. The
An adaption must be carried out when the ! running time and the operating range are adapted to the available angle of rotation. Detection
system is commissioned or whenever the of the mechanical end stops enables a gentle approach to the end position and protects the
end stops for angle of rotation limiting are actuator and damper mechanisms. The actuator moves first to the top, then to the bottom
adjusted (press the Adaption push-button spindle end stops when the supply voltage is switched on for the first time, i.e. at the time of
once). commissioning or after pressing the Adaption key.

Home position Actuation of the Gear disengagement key causes the actuator to move to home position. This
function is performed by the actuator, even when the supply voltage is restored, if the Gear
disengagement key was pressed during the electricity interruption.
Pos. direction of rotation switch Home position
0
Y = 0 ccw Left end stop
1 Y = 0 cw Right end stop

After this procedure, the actuator then moves into the position defined by the system.

Functional check An extremely simple functional check of the dampers is possible: The gearbox can be
disengaged simply by pressing the gear disengagement key on the housing. As long as the
key remains pressed, the damper can be operated manually.

High functional reliability The actuators are overload-proof, require no limit switches and automatically stop when the end
stop is reached.

Electrical installation
The ready-to-connect actuator unit is connected to the VRP-M controller with the 6-pin plug.

Display and operating elements

1 Direction of rotation switch


1 Switching over: Direction of rotation changes

2 2 Push-button and LED display green


Off: No power supply or fault
3 Illuminated: Operation
Press key: Initiates angle of rotation adaptation, followed by standard mode
4
3 Push-button and LED display yellow
Off: Standard mode
5 Illuminated: Adaption or synchronisation process active
Press key: No function
4 Gear disengagement key
Press key: Gearbox disengaged, motor stops, manual override possible
Release key: Gearbox engaged, synchronisation starts, followed by standard mode
5 Communication (PC-Tool, ZTH-GEN) is blocked for this actuator type

30 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


Technical data sheet NM24A-V-ST

Damper actuator for VRP-M system


solution
Torque 10 Nm
Running time 150 s

Technical data
Electrical data Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
(from VRP-M)
Power consumption Operation 3.5 W @ nominal torque
Rest position 1.25 W
Dimensioning 6 VA
Connection 0.5 m cable with 6-pin plug
(suitable for VRP-M)
Functional data Torque (nominal torque) Min. 10 Nm @ nominal voltage
Position accuracy 5%
Direction of rotation As an option with switch 0 / 1
Direction of motion at Y = 2V In switch position 0 or 1
Angle of rotation max. 95
Mechanical end stops adjustable
Running time 150 s
Sound power level max. 35 dB (A)
Position indication mechanical, plug-in
Safety Protection class III Safety extra-low voltage
Degree of protection IP54 in all mounting positions
EMC CE according to 2004/108/EC
Principle of operation Type 1 (EN 60730-1)
Ambient temperature 30 ... +50C
Non-operating temperature 40 ... +80C
Ambient humidity 95% r.h., non-condensing (EN 60730-1)
Maintenance Maintenance-free
Dimensions / Weight Dimensions See Dimensions on page 35
Weight Approx. 710 g

Safety notes
The actuator is not allowed to be used outside the specified field of application, especially in
! aircraft or in any other airborne means of transport.
It may only be installed by suitably trained personnel.
Legal regulations and regulations issued by authorities must be observed during installation.
The device may only be opened at the manufacturer's site. It does not contain any parts that
can be replaced or repaired by the user.
The cable must not be removed from the device.
When the required torque is calculated, the cross section, design and installation site as well
as the air flow conditions must be observed.
The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 31 / 36


NM24A-V-ST Damper actuator for VRP-M system solution

Product features
Simple direct mounting Simple direct mounting on the damper spindle with a universal spindle clamp, supplied with
a universal mounting bracket to prevent the actuator from rotating.

Manual override Manual override with self-resetting push-button possible (gear disengagement for as long as the
button is pressed).

Adjustable angle of rotation Adjustable angle of rotation with mechanical end stops.

Adaption Angle-of-rotation sensing and adaptation of the control range. Triggered by pressing a button on
the actuator, with LEDs for status display.

High functional reliability The actuator is overload protected, requires no limit switches and automatically stops when the
end stop is reached.

Accessories
Description Data sheet
Electrical accessories Auxiliary switch S..A.. T2 - S..A..
Feedback potentiometer P..A.. T2 - P..A..
Mechanical accessories Shaft extension AV6-20 T2 - Z-NM..A..

Electrical installation
The ready-to-connect actuator unit is connected to the VRP-M controller with the 6-pin plug.

Display and operating elements

1 Direction of rotation switch


1 Switching over: Direction of rotation changes

2 2 Push-button and LED display green


Off: No power supply or fault
3 Illuminated: Operation
Press key: Initiates angle of rotation adaptation, followed by standard mode
4
3 Push-button and LED display yellow
Off: Standard mode
5 Illuminated: Adaption or synchronisation process active
Press key: No function
4 Gear disengagement key
Press key: Gearbox disengaged, motor stops, manual override possible
Release key: Gearbox engaged, synchronisation starts, followed by standard mode
5 Communication (PC-Tool, ZTH-GEN) is blocked for this actuator type

32 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


Technical data sheet SF24A-V-ST

Spring-return actuator with emergency


setting function for VAV and CAV units in
ventilation and air conditioning systems
for building services installations

Torque
20 Nm
Running time 150 s

Technical data
Electrical data Nominal voltage AC 24 V, 50/60 Hz / DC 24 V
(from VRP-M)
Power consumption Operation 8.5 W @ nominal torque
Rest position 3.5 W
Dimensioning 11 VA
Connection 1 m cable with 6-pin plug (compatible with VRP-M)
Functional data Torque Motor Min. 20 Nm @ nominal voltage
Spring-return Min. 20 Nm
Position accuracy 5%
Direction of rotation Motor as an option with switch /
Spring-return As an option by installation L / R
Direction of rotation for Y = 0 V in switch position 1 or 0
Manual override With hand crank and interlocking switch
Angle of rotation max. 95 (can be limited by
adjustable mechanical stop)
Running time Motor 150 s / 90
Spring-return 20 s @ 20 ... 50C / max. 60 s @ 30C
Sound power level Motor 40 dB (A) @ 150 s running time
Spring-return 62 dB (A)
Service life Min. 60,000 emergency settings
Safety Protection class III Safety extra-low voltage
Degree of protection IP54
EMC CE according to 2004/108/EC
Certification Certified in accordance with IEC/EN 60730-1 and IEC/
EN 60730-2-14
Principle of operation Type 1.AA
Rated current voltage 0.8 kV
Control pollution degree 3
Ambient temperature 30 ... +50C
Non-operating temperature 40 ... +80C
Ambient humidity 95% r.h., non-condensing
Maintenance Maintenance-free
Dimensions / Weight Dimensions See Dimensions on page 35
Weight Approx. 2.3 kg

www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 33 / 36


SF24A-V-ST Spring-return actuator for VRP-M system solution

Safety notes
The actuator is not allowed to be used outside the specified field of application, especially in
! aircraft or in any other airborne means of transport.
It may only be installed by suitably trained personnel.
Legal regulations and regulations issued by authorities must be observed during installation.
The device may only be opened at the manufacturer's site. It does not contain any parts that
can be replaced or repaired by the user.
The cable must not be removed from the device.
The device contains electrical and electronic components and is not allowed to be disposed
of as household refuse. All locally valid regulations and requirements must be observed.

Product features
Principle of operation The actuator is controlled by the Belimo VRP-M controller and travels to the position defined by
the control signal.

Simple direct mounting Simple direct mounting on the damper spindle with a universal spindle clamp; a universal
mounting bracket is enclosed to prevent the actuator from rotating.

Adjustable angle of rotation Adjustable angle of rotation with mechanical end stop.

Adaption Angle-of-rotation sensing and adaptation of the control range. Triggered by pressing a button on
the actuator, with LEDs for status display.

High functional reliability The actuator is overload protected, requires no limit switches and automatically stops when the
end stop is reached.

Accessories
Description Data sheet
Electrical accessories Auxiliary switch S2A-F
Mechanical accessories Various accessories (spindle clamps, shaft extensions, etc.) T2 - Z-SM..A..

Electrical installation
The ready-to-connect actuator unit is connected to the VRP-M controller with the 6-pin plug.

Display and operating elements

1 Membrane key and LED display green


Off: No power supply or fault
Illuminated: Operation
3 Press key: Initiates angle of rotation adaptation, followed by standard mode
2 Membrane key and LED display yellow
Off: Standard mode
Illuminated: Adaption or synchronisation process active
Press key: No function
1 2
3 Communication (PC-Tool, ZTH-GEN) is blocked for this actuator type

Operating elements The elements manual override, locking switch and direction of rotation switch are available on
both sides.

34 / 36 S4-VRP-M VAV en v4.1 08.2012 Subject to changes www.belimo.eu


Dimensions

Dimensional drawings of VRP-M controller 153


140
130

45
54
5

4.5

88
43
Dimensional drawings of VFP-100 sensor 135

58

80
40
5

15 120
150

Dimensional drawings of VFP-300 and VFP- 81


600 sensors

49

51
25.5
4.5

12 66
90

Dimensional drawings of VFD3 90


39

51
99
110
Dimensional drawings LMQ24A-SRV-ST

Damper spindle Length


75

80
50

40 8 ... 26.7 8 26.7


* 20 8 ... 20 8 20
* Option (Accessory K-NA) 124 25 121 41

Dimensional drawings NMQ24A-SRV-ST


77

Damper spindle Length


88
52

42 8 ... 26.7 8 26.7


* 20 8 ... 20 8 20
* Option (Accessory K-SA) 139 41
30 131

Dimensional drawings NM24A-V-ST

Damper spindle Length


75

80
50

40 8 ... 26.7 8 26.7


* 20 8 ... 20 8 20
* Option (Accessory K-NA) 124 25 121 41

Dimensional drawings SF24A-V-ST


20.5

2-FRONT

Variant 1a:
-spindle clamp (with insertion part) EU Standard
93

60

98
80

Damper spindle Length


85
10 ... 22 10 14 ... 25.4
15
12.5

32 27
Variant 1b: 162

1-spindle clamp (without insertion part) EU Standard 172


182
Damper spindle Length 236

85 19 ... 25.4
12 ... 18
15 (26.7)
www.belimo.eu S4-VRP-M VAV en v4.1 08.2012 Subject to changes 35 / 36
All inclusive.

5 years
Guarantee

Worldwide
present

Complete
assortment from
a single source

Examined
Quality

Short
delivery time

Comprehensive
support

Headquarters Subsidiaries, Representatives and Agencies

BELIMO Holding AG Agentina Denmark Lebanon Rumania


Brunnenbachstrasse 1 Australia Egypt Liechtenstein Russia
CH-8340 Hinwil Bahrain Estonia Lithuania Saudi Arabia
Tel. +41 (0)43 843 61 11 Belgium Finland Luxembourg Singapore
Fax +41 (0)43 843 62 68 Bosnia-Herzegovina France Malaysia Slovakia
[email protected] Brazil Great Britain Mexico Slovenia
www.belimo.com Bulgaria Germany Morocco South Africa
Canada Greece Netherlands Spain
Chile Hong Kong New Zealand Sweden
Croatia Hungary Norway Switzerland
Cyprus Iceland Oman Taiwan
Czech Republic India Pakistan Turkey
Indonesia Peoples Republic of China Ukraine
Ireland Philippines United Arab Emirates
Israel Poland United States of America
Italy Portugal
Japan Qatar
Jordan Republic of Korea (South Korea)
Kuwait
Latvia

Belimo worldwide: www.belimo.com