HVAC Made Easy: A Guide To Heating & Cooling Load Estimation
HVAC Made Easy: A Guide To Heating & Cooling Load Estimation
org
Course Content
Classification of climates
Many different systems of climate classification are in use for different purposes. Climatic zones such as tropical, arid,
temperature and cool are commonly found for representing climatic conditions. For the purposes of building design a
simple system based on the nature of the thermal problem in the particular location is often used.
1) Cold climates, where the main problem is the lack of heat (under heating), or excessive heat dissipation for all or
most parts of the year.
2) Temperate climates, where there is a seasonal variation between under heating and overheating, but neither is
very severe.
3) Hot-dry (arid) climates, where the main problem is overheating, but the air is dry, so the evaporative cooling
mechanism of the body is not restricted. There is usually a large diurnal (day - night) temperature variation.
Page 1 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org
4) Warm-humid climates, where the overheating is not as great as in hot-dry areas, but it is aggravated by very high
humiditys, restricting the evaporation potential. The diurnal temperature variation is small.
Page 2 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org
Preface
The term summer cooling load means much more than merely cooling the air in a building. In addition to cooling the air,
it also implies controlling:
1) The relative humidity
2) Providing proper ventilation
3) Filtering out contaminants (air cleaning) and
4) Distributing the conditioned air to the lived-in spaces in proper amounts, without appreciable drafts or objectionable
noise
This section deals with the design aspects and the equations used for summer cooling load calculations.
Design Conditions
The amount of cooling that has to be accomplished to keep buildings comfortable in hot summer depends on the
desired condition indoors and on the outdoor conditions on a given day. These conditions are, respectively, termed the
indoor design condition and the outdoor design condition.
Page 3 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org
The information provided in table 1b, 2b and 3b are for cooling and humidity control conditions that include:
1) Dry bulb temperature corresponding to 0.4%, 1.0% and 2.0% annual cumulative frequency of occurrence and the
mean coincident wet-bulb temperature (warm). These conditions appear in sets of dry bulb (DB) temperature and
the mean coincident wet bulb (MWB) temperature since both values are needed to determine the sensible and
latent (dehumidification) loads in the cooling mode.
2) Wet-bulb temperature corresponding to 0.4%, 1.0% and 2.0% annual cumulative frequency of occurrence and the
mean coincident dry-bulb temperature
3) Dew-point temperature corresponding to 0.4%, 1.0% and 2.0% annual cumulative frequency of occurrence and the
mean coincident dry-bulb temperature and humidity ratio (calculated for the dew-point temperature at the standard
atmospheric pressure at the elevation of the station).
4) Mean daily range (DR) of the dry bulb temperature, which is the mean of the temperature difference between daily
maximum and minimum temperatures for the warmest month (highest average dry-bulb temperature). These are
used to correct CLTD values.
In choosing the HVAC outdoor design conditions, it is neither economical nor practical to design equipment either for
the annual hottest temperature or annual minimum temperature, since the peak or the lowest temperatures might occur
only for a few hours over the span of several years. Economically speaking short duration peaks above the system
capacity might be tolerated at significant reductions in first cost; this is a simple risk - benefit decision for each building
design. Therefore, as a practice, the design temperature and humidity conditions are based on frequency of
occurrence. The summer design conditions have been presented for annual percentile values of 0.4, 1 and 2% and
winter month conditions are based on annual percentiles of 99.6 and 99%.
The term design condition refers to the %age of time in a year (8760 hours), the values of dry-bulb, dew-point and
wet-bulb temperature exceed by the indicated percentage. The 0.4%, 1.0%, 2.0% and 5.0% values are exceeded on
average by 35, 88, 175 and 438 hours.
The 99% and 99.6% cold values are defined in the same way but are viewed as the values for which the corresponding
weather element are less than the design condition 88 and 35 hours, respectively. 99.6% value suggests that the
outdoor temperature is equal to or lower than design data 0.4% of the time.
Design condition is used to calculate maximum heat gain and maximum heat loss of the building. For comfort cooling,
use of the 2.5% occurrence and for heating use of 99% values is recommended.
The 2.5% design condition means that the outside summer temperature and coincident air moisture content will be
exceeded only 2.5% of hours from June to September or 73 out of 2928 hours (of these summer months) or 2.5% of
the time in a year, the outdoor air temperature will be above the design condition.
Page 4 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org
In cooling load calculation, there are four related heat flow terms; 1) space heat gain, 2) space cooling load, 3) space
heat extraction rate and 4) cooling coil load.
What does these terms mean?
1) The heat gain for a building is a simultaneous summation of all external heat flows plus the heat flows generated
inside the building. The heat gain varies throughout the 24 hours of the day, as the solar intensity, occupancy;
lights, appliances etc keep varying with time.
2) The cooling load is an hourly rate at which heat must be removed from a building in order to hold the indoor air
temperature at the design value. In other words, cooling load is the capacity of equipment required to account for
such a load. Theoretically, it may seem logical to address that the space heat gain is equivalent to space cooling
load but in practice Heat gain cooling load.
The primary explanation for this difference is the time lag or thermal storage affects of the building elements. Heat
gains that enter a building are absorbed/stored by surfaces enclosing the space (walls, floors and other interior
elements) as well as objects within the space (furniture, curtains etc.) These elements radiates into the space even
after the heat gain sources are no longer present. Therefore the time at which the space may realize the heat gain
as a cooling load is considerably offset from the time the heat started to flow. This thermal storage effect is critical
in determining the instantaneous heat gain and the cooling load of a space at a particular time. Calculating the
nature and magnitude of these re-radiated loads to estimate a more realistic cooling load is described in the
subsequent sections.
Furnishings, structure,
variable heat storage
The convective heat flows are converted to space cooling load instantaneously whereas radiant loads tend to be
partially stored in a building. The cooling load for the space is equal to the summation of all instantaneous heat
Page 5 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org
gain plus the radiant energy that has been absorbed by surfaces enclosing the space as well as objects within the
space. Thus heat gain is often not equal to cooling load.
In heating load calculations however, the instantaneous heat loss from the space can be equated to the space-
heating load and it can be use directly to size the heating equipment.
3) The space heat extraction rate is usually the same as the space-cooling load but with an assumption that the
space temperature remains constant.
4) The cooling coil load is the summation of all the cooling loads of the various spaces served by the equipment plus
any loads external to the spaces such as duct heat gain, duct leakage, fan heat, and outdoor makeup air.
Sensible Loads
Sensible heat gain is the direct addition of heat to a space,which shall result in increase in space temperatures. The
factors influencing sensible cooling load:
1) Solar heat gain through building envelope (exterior walls, glazing, skylights, roof, floors over crawl space)
2) Partitions (that separate spaces of different temperatures)
3) Ventilation air and air infiltration through cracks in the building, doors, and windows
4) People in the building
5) Equipment and appliances operated in the summer
6) Lights
Latent Loads
A latent heat gain is the heat contained in water vapor. Latent heat does not cause a temperature rise, but it constitutes
a load on the cooling equipment. Latent load is the heat that must be removed to condense the moisture out of the air.
The sources of latent heat gain are:
1) People (breathing)
2) Cooking equipment
3) Housekeeping, floor washing etc.
4) Appliances or machinery that evaporates water
5) Ventilation air and air infiltration through cracks in the building, doors, and windows
The total cooling load is the summation of sensible and latent loads.
External Loads
External cooling loads consist of the following:
Page 6 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org
Q = A * (SHGC) * (CLF)
A = area of roof, wall or glass calculated from building plans
SHGC = Solar Heat Gain Coefficient. See 1997 ASHRAE Fundamentals, Chapter 28, table 35
CLF = Solar Cooling Load Factor. See 1997 ASHRAE Fundamentals, Chapter 28, and Table 36.
3) Partitions, Ceilings & Floors
The equation used for sensible loads from the partitions, ceilings and floors:
Q = U * A * (Ta - Trc)
U = Thermal Transmittance for roof or wall or glass. See 1997 ASHRAE Fundamentals, Chapter 24 or 2001
ASHRAE Fundamentals, and Chapter 25.
A = area of partition, ceiling or floor calculated from building plans
Ta = Temperature of adjacent space (Note: If adjacent space is not conditioned and temperature is not available,
use outdoor air temperature less 5F)
Trc = Inside design temperature of conditioned space (assumed constant)
4) Ventilation & Infiltration Air
Ventilation air is the amount of outdoor air required to maintain Indoor Air Quality for the occupants (sees ASHRAE
Standard 62 for minimum ventilation requirements) and makeup for air leaving the space due to equipment
exhaust, exfiltration and pressurization.
Q sensible = 1.08 * CFM * (To Tc)
Q latent = 4840 * CFM * (W o Wc)
Q total = 4.5 * CFM * (ho hc)
CFM = Ventilation airflow rate.
To = Outside dry bulb temperature, F
Tc = Dry bulb temperature of air leaving the cooling coil, F
Page 7 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org
Internal Loads
Internal cooling loads consist of the following:
1) Sensible & latent loads due to people
2) Sensible loads due to lighting
3) Sensible loads due to power loads and motors (elevators, pumps, fans & other machinery)
4) Sensible & latent loads due to appliances
An internal load calculation is the area of engineering judgment. The internal loads are sometimes about 60% of the
load; however, these data are generally the least amount of information available to you at the design stage and
therefore the generic rules are most often employed to fix the variables. The equations used in estimating internal loads
are:
1) People
Q sensible = N * (QS) * (CLF)
Q latent = N * (QL)
N = number of people in space.
QS, QL = Sensible and Latent heat gain from occupancy is given in 1997 ASHRAE Fundamentals Chapter 28,
Table 3
CLF = Cooling Load Factor, by hour of occupancy. See 1997 ASHRAE Fundamentals, Chapter 28, table 37.Note:
CLF = 1.0, if operation is 24 hours or of cooling is off at night or during weekends.
2) Lights
The lights result in sensible heat gain.
Q = 3.41 * W * FUT * FBF * (CLF)
W = Installed lamp watts input from electrical lighting plan or lighting load data
FUT = Lighting use factor, as appropriate
FBF = Blast factor allowance, as appropriate
CLF = Cooling Load Factor, by hour of occupancy. See 1997 ASHRAE Fundamentals, Chapter 28, Table 38.
Note: CLF = 1.0, if operation is 24 hours or if cooling is off at night or during weekends.
Page 8 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org
Page 9 of 79