0% found this document useful (0 votes)
253 views9 pages

HVAC Made Easy: A Guide To Heating & Cooling Load Estimation

This document provides an overview of heating and cooling load calculations for HVAC systems. It discusses establishing design criteria, classifying climates, and methods for calculating cooling loads, focusing on the CLTD/CLF method. Key points covered include determining indoor and outdoor design conditions, factors that influence load calculations like weather, building characteristics and schedules, and using methods like Manual J and CLTD/CLF to properly size HVAC systems and their components.

Uploaded by

Jane Nixon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
253 views9 pages

HVAC Made Easy: A Guide To Heating & Cooling Load Estimation

This document provides an overview of heating and cooling load calculations for HVAC systems. It discusses establishing design criteria, classifying climates, and methods for calculating cooling loads, focusing on the CLTD/CLF method. Key points covered include determining indoor and outdoor design conditions, factors that influence load calculations like weather, building characteristics and schedules, and using methods like Manual J and CLTD/CLF to properly size HVAC systems and their components.

Uploaded by

Jane Nixon
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

www.PDHcenter.com PDH Course M196 www.PDHonline.

org

HVAC Made Easy: A Guide to Heating & Cooling Load Estimation

Course Content

AIR CONDITIONING SYSTEM OVERVIEW


Cooling & heating load calculations are normally made to size HVAC (heating, ventilating, and air-conditioning) systems
and their components. In principle, the loads are calculated to maintain the indoor design conditions. The first step in
any load calculation is to establish the design criteria for the project that involves consideration of the building concept,
construction materials, occupancy patterns, density, office equipment, lighting levels, comfort ranges, ventilations and
space specific needs. Architects and other design engineers converse at early stages of the project to produce design
basis & preliminary architectural drawings. The design basis typically includes information on:
1) Geographical site conditions (latitude, longitude, wind velocity, precipitation etc.)
2) Outdoor design conditions (temperature, humidity etc)
3) Indoor design conditions
4) Building characteristics (materials, size, and shape)
5) Configuration (location, orientation and shading)
6) Operating schedules (lighting, occupancy, and equipment)
7) Additional considerations (type of air-conditioning system, fan energy, fan location, duct heat loss and gain, duct
leakage, type and position of air return system)

Climate data requirements


One of the most important things in building HVAC design is the climate you are designing. Lets make first distinction in
terms weather and climate.
"Weather" is the set of atmospheric conditions prevailing at a given place and time. "Climate" can be defined as the
integration in time of weather conditions, characteristics of a certain geographical location. At the global level climates
are formed by the differential solar heat input and the uniform heat emission over the earth's surface.
Climate has a major effect on building performance, HVAC design and energy consumption. It is also pertinent to the
assessment of thermal comfort of the occupants. The key objectives of climatic design include:
1) To reduce energy cost of a building
2) To use "natural energy" as far as possible instead of mechanical system and power
3) To provide comfortable and healthy environment for people

Classification of climates
Many different systems of climate classification are in use for different purposes. Climatic zones such as tropical, arid,
temperature and cool are commonly found for representing climatic conditions. For the purposes of building design a
simple system based on the nature of the thermal problem in the particular location is often used.
1) Cold climates, where the main problem is the lack of heat (under heating), or excessive heat dissipation for all or
most parts of the year.
2) Temperate climates, where there is a seasonal variation between under heating and overheating, but neither is
very severe.
3) Hot-dry (arid) climates, where the main problem is overheating, but the air is dry, so the evaporative cooling
mechanism of the body is not restricted. There is usually a large diurnal (day - night) temperature variation.

Page 1 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org

4) Warm-humid climates, where the overheating is not as great as in hot-dry areas, but it is aggravated by very high
humiditys, restricting the evaporation potential. The diurnal temperature variation is small.

Six categories of climates:


1) Warm-humid - 15N and South of the equator, e.g. Lagos, Mombassa, Colombo, Jakarta etc.
2) Warm-humid Island - equatorial and trade wind zones, e.g. Caribbean, Philippines and Pacific Islands etc.
3) Hot-dry desert - 15 to 30 North and South, e.g. Baghdad, Alice Springs, Phoenix etc.
4) Hot-dry maritime desert - latitudes as (3), coastal large landmass, Kuwait, Karachi etc.
5) Composite Monsoon - Tropic Cancer/Capricorn, Lahore, Mandalay, New Delhi etc.
6) Tropical uplands - Tropic Cancer/Capricorn, 900 to 1200 meters above sea level (plateau and mountains), Addis
Ababa, Mexico City, Nairobi etc.

Load Calculations Methods


Before one can design an efficient and effective air conditioning system, the load must first be calculated using
established techniques. There are various methods in use. The most basic of these methods is a rule-of-thumb value --
for example, square feet of floor area per ton of cooling. The "square-foot-per-ton" sizing method avoids calculating the
cooling load of the building and proceeds directly from the square footage of the building. While this approach is rapid
and simple, it does not account for orientation of the walls and windows, the difference in surface area between a one-
story and a two-story home of the same floor area, the differences in insulation and air leakage between different
buildings, the number of occupants, and many other factors. Such rules-of-thumb are useful in schematic design as a
means of getting an approximate handle on equipment size and cost.
The more refined methods available in the HVAC handbooks are:
1) Total Equivalent Temperature Difference/Time Average (TETD/TA)
2) Cooling Load Temperature Difference/Cooling Load Factor (CLTD/CLF)
3) Transfer Function Method (TFM)
4) Heat Balance (HB) & Radiant Time Series (RTS)
5) Manual J Method for Residential Applications & Manual N for Commercial Buildings: These methods are simplified
versions, jointly developed by Air conditioning contractors of America (ACCA) and the Air conditioning and
Refrigeration Institute (ARI).
These different methods may yield different results for the same input data. This is primarily due to the way; each
method handles the solar effect and building dynamics. But in true sense all the above approaches attempt to consider
the fundamental principle that heat flow rates are not instantaneously converted to loads and heat addition or extraction
incident upon the building do not immediately result in a change in temperature. Thermally heavy buildings can
effectively delay the cooling or heating load for several hours.
Most designers use the TETD and CLTD methods because these methods are simple to use, give component loads
and tend to predict load on conservative side. The most recent versions of the ASHRAE Fundamentals Handbook
(2001) provide more detailed discussion on the Radiant Time Series (RTS) and Heat Balance (HB) methods. The Heat
Balance method is the most accurate but is very laborious and cumbersome and is more suitable with the use of
computer programs. The RTS is a simplified method derived from heat balance (HB) method and effectively replaces
all other simplified (non-heat balanced) methods.
For strictly manual cooling loads calculation method, the most practical to use is the CLTD/CLF method. This course
discusses CLTD/CLF method in detail in succeeding sections.
A number of handbooks provide a good source of design information and criteria to use for CLTD/CLF method;
however engineering judgment is required in the interpretation of various custom tables and applying appropriate
correction factors. It is not the intent of this course to duplicate information but rather to provide a direction regarding the
proper use or application of the available data so that the engineers and designers can make an appropriate decision.

Page 2 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org

PART 1 SUMMER COOLING LOAD

Preface
The term summer cooling load means much more than merely cooling the air in a building. In addition to cooling the air,
it also implies controlling:
1) The relative humidity
2) Providing proper ventilation
3) Filtering out contaminants (air cleaning) and
4) Distributing the conditioned air to the lived-in spaces in proper amounts, without appreciable drafts or objectionable
noise
This section deals with the design aspects and the equations used for summer cooling load calculations.

Design Conditions
The amount of cooling that has to be accomplished to keep buildings comfortable in hot summer depends on the
desired condition indoors and on the outdoor conditions on a given day. These conditions are, respectively, termed the
indoor design condition and the outdoor design condition.

Indoor Design Conditions


The indoor design conditions are directly related to human comfort. Current comfort standards, ASHRAE Standard 55-
1992 [4] and ISO Standard 7730 [5], specify a comfort zone, representing the optimal range and combinations of
thermal factors (air temperature, radiant temperature, air velocity, humidity) and personal factors (clothing and activity
level) with which at least 80% of the building occupants are expected to express satisfaction. As a general guideline for
summer air-conditioning design, the thermal comfort chapter of the ASHRAE fundamentals handbook (Chapter 8, 2001)
provides a snapshot of the psychrometric chart for the summer and winter comfort zones.
For most of the comfort systems, the recommended indoor temperature and relative humidity are:
1) Summer: 73 to 79F; The load calculations are usually based at 75F dry bulb temperatures & 50% relative
humidity
2) Winter: 70 to 72F dry bulb temperatures, 20 - 30 % relative humidity
The standards were developed for mechanically conditioned buildings typically having overhead air distribution systems
designed to maintain uniform temperature and ventilation conditions throughout the occupied space. The Psychrometric
chapter of the Fundamentals Handbook (Chapter 6, 2001) provides more details on this aspect.

Outdoor Design Conditions


Outdoor design conditions are determined from published data for the specific location, based on weather bureau or
airport records. Basic climatic and HVAC design condition data can be obtained from ASHRAE handbook, which
provides climatic conditions for 1459 locations in the United States, Canada and around the world. The information
includes values of dry-bulb, wet-bulb and dew-point temperature and wind speed with direction on percentage
occurrence basis.
Design conditions for the United States appear in Table 1a and 1b, for Canada in Tables 2a and 2b, and the
international locations in Tables 3a and 3b of 1997, ASHRAE fundamentals handbook chapter 26.
The information provided in table 1a, 2a and 3a are for heating design conditions that include:
1) Dry bulb temperatures corresponding to 99.6% and 99% annual cumulative frequency of occurrence,
2) Wind speeds corresponding to 1%, 2.5% and 5% annual cumulative frequency of occurrence,
3) Wind direction most frequently occurring with 99.6% and 0.4% dry-bulb temperatures and
4) Average of annual extreme maximum and minimum dry-bulb temperatures and standard deviations.

Page 3 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org

The information provided in table 1b, 2b and 3b are for cooling and humidity control conditions that include:
1) Dry bulb temperature corresponding to 0.4%, 1.0% and 2.0% annual cumulative frequency of occurrence and the
mean coincident wet-bulb temperature (warm). These conditions appear in sets of dry bulb (DB) temperature and
the mean coincident wet bulb (MWB) temperature since both values are needed to determine the sensible and
latent (dehumidification) loads in the cooling mode.
2) Wet-bulb temperature corresponding to 0.4%, 1.0% and 2.0% annual cumulative frequency of occurrence and the
mean coincident dry-bulb temperature
3) Dew-point temperature corresponding to 0.4%, 1.0% and 2.0% annual cumulative frequency of occurrence and the
mean coincident dry-bulb temperature and humidity ratio (calculated for the dew-point temperature at the standard
atmospheric pressure at the elevation of the station).
4) Mean daily range (DR) of the dry bulb temperature, which is the mean of the temperature difference between daily
maximum and minimum temperatures for the warmest month (highest average dry-bulb temperature). These are
used to correct CLTD values.
In choosing the HVAC outdoor design conditions, it is neither economical nor practical to design equipment either for
the annual hottest temperature or annual minimum temperature, since the peak or the lowest temperatures might occur
only for a few hours over the span of several years. Economically speaking short duration peaks above the system
capacity might be tolerated at significant reductions in first cost; this is a simple risk - benefit decision for each building
design. Therefore, as a practice, the design temperature and humidity conditions are based on frequency of
occurrence. The summer design conditions have been presented for annual percentile values of 0.4, 1 and 2% and
winter month conditions are based on annual percentiles of 99.6 and 99%.
The term design condition refers to the %age of time in a year (8760 hours), the values of dry-bulb, dew-point and
wet-bulb temperature exceed by the indicated percentage. The 0.4%, 1.0%, 2.0% and 5.0% values are exceeded on
average by 35, 88, 175 and 438 hours.
The 99% and 99.6% cold values are defined in the same way but are viewed as the values for which the corresponding
weather element are less than the design condition 88 and 35 hours, respectively. 99.6% value suggests that the
outdoor temperature is equal to or lower than design data 0.4% of the time.
Design condition is used to calculate maximum heat gain and maximum heat loss of the building. For comfort cooling,
use of the 2.5% occurrence and for heating use of 99% values is recommended.
The 2.5% design condition means that the outside summer temperature and coincident air moisture content will be
exceeded only 2.5% of hours from June to September or 73 out of 2928 hours (of these summer months) or 2.5% of
the time in a year, the outdoor air temperature will be above the design condition.

Cooling Loads Classified by Source


Cooling loads fall into the following categories, based on their sources:
1) Heat transfer (gain) through the building skin by conduction, as a result of the outdoor-indoor temperature
difference.
2) Solar heat gains (radiation) through glass or other transparent materials.
3) Heat gains from ventilation air and/or infiltration of outside air.
4) Internal heat gains generated by occupants, lights, appliances, and machinery.

Page 4 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org

In cooling load calculation, there are four related heat flow terms; 1) space heat gain, 2) space cooling load, 3) space
heat extraction rate and 4) cooling coil load.
What does these terms mean?
1) The heat gain for a building is a simultaneous summation of all external heat flows plus the heat flows generated
inside the building. The heat gain varies throughout the 24 hours of the day, as the solar intensity, occupancy;
lights, appliances etc keep varying with time.
2) The cooling load is an hourly rate at which heat must be removed from a building in order to hold the indoor air
temperature at the design value. In other words, cooling load is the capacity of equipment required to account for
such a load. Theoretically, it may seem logical to address that the space heat gain is equivalent to space cooling
load but in practice Heat gain cooling load.
The primary explanation for this difference is the time lag or thermal storage affects of the building elements. Heat
gains that enter a building are absorbed/stored by surfaces enclosing the space (walls, floors and other interior
elements) as well as objects within the space (furniture, curtains etc.) These elements radiates into the space even
after the heat gain sources are no longer present. Therefore the time at which the space may realize the heat gain
as a cooling load is considerably offset from the time the heat started to flow. This thermal storage effect is critical
in determining the instantaneous heat gain and the cooling load of a space at a particular time. Calculating the
nature and magnitude of these re-radiated loads to estimate a more realistic cooling load is described in the
subsequent sections.

Convective Component Heat Extraction by


Instantaneous Instantaneous
Heat Gain Equipment
Cooling Load

Radiative Component Convection (with time delay)

Furnishings, structure,
variable heat storage

Schematic Relation of Heat Gain to Cooling Load

The convective heat flows are converted to space cooling load instantaneously whereas radiant loads tend to be
partially stored in a building. The cooling load for the space is equal to the summation of all instantaneous heat

Page 5 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org

gain plus the radiant energy that has been absorbed by surfaces enclosing the space as well as objects within the
space. Thus heat gain is often not equal to cooling load.
In heating load calculations however, the instantaneous heat loss from the space can be equated to the space-
heating load and it can be use directly to size the heating equipment.
3) The space heat extraction rate is usually the same as the space-cooling load but with an assumption that the
space temperature remains constant.
4) The cooling coil load is the summation of all the cooling loads of the various spaces served by the equipment plus
any loads external to the spaces such as duct heat gain, duct leakage, fan heat, and outdoor makeup air.

Cooling Loads Classified by Kinds of Heat


There are two distinct components of the air conditioning load; (1) the sensible load (heat gain) and (2) the latent load
(water vapor gain).

Sensible Loads
Sensible heat gain is the direct addition of heat to a space,which shall result in increase in space temperatures. The
factors influencing sensible cooling load:
1) Solar heat gain through building envelope (exterior walls, glazing, skylights, roof, floors over crawl space)
2) Partitions (that separate spaces of different temperatures)
3) Ventilation air and air infiltration through cracks in the building, doors, and windows
4) People in the building
5) Equipment and appliances operated in the summer
6) Lights

Latent Loads
A latent heat gain is the heat contained in water vapor. Latent heat does not cause a temperature rise, but it constitutes
a load on the cooling equipment. Latent load is the heat that must be removed to condense the moisture out of the air.
The sources of latent heat gain are:
1) People (breathing)
2) Cooking equipment
3) Housekeeping, floor washing etc.
4) Appliances or machinery that evaporates water
5) Ventilation air and air infiltration through cracks in the building, doors, and windows
The total cooling load is the summation of sensible and latent loads.

Cooling Loads Classified by Inside-Outside Environment


Buildings can be classified as envelope-load-dominated and interior-load-dominated. The envelope heat flows are
termed external loads, in that they originate with the external environment. The other loads are termed internal loads,
in that they are generated from within the building itself. The percentage of external versus internal load varies with
building type, site climate, and building design decisions. It is useful to identify whether internal or external loads will
dominate a building, as this information should substantially change the focus of design efforts related to control and
energy efficiency.

External Loads
External cooling loads consist of the following:

Page 6 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org

1) Sensible loads through opaque envelope assemblies (roofs, walls, floors)


2) Sensible loads through transparent or translucent envelope assemblies (skylights, windows, glazed openings)
3) Sensible loads through ventilation and infiltration (air leakage)
4) Latent loads through ventilation and infiltration.
Because of the inherent differences in these types of heat flows, they are calculated (estimated) using four different
equations:
1) Roofs, External Walls & Conduction through Glass
The equation used for sensible loads from the opaque elements such as walls, roof, partitions and the conduction
through glass is:
Q = U * A * (CLTD)
U = Thermal Transmittance for roof or wall or glass. See 1997 ASHRAE Fundamentals, Chapter 24 or 2001
ASHRAE Fundamentals, chapter 25.
A = area of roof, wall or glass calculated from building plans
CLTD = Cooling Load Temperature Difference for roof, wall or glass. Refer 1997 ASHRAE Fundamentals, Chapter
28, tables 30, 31, 32, 33 and 34.
2) Solar Load through Glass
The equation used for radiant sensible loads from the transparent/translucent elements such as window glass,
skylights and plastic sheets is:

Q = A * (SHGC) * (CLF)
A = area of roof, wall or glass calculated from building plans
SHGC = Solar Heat Gain Coefficient. See 1997 ASHRAE Fundamentals, Chapter 28, table 35
CLF = Solar Cooling Load Factor. See 1997 ASHRAE Fundamentals, Chapter 28, and Table 36.
3) Partitions, Ceilings & Floors
The equation used for sensible loads from the partitions, ceilings and floors:

Q = U * A * (Ta - Trc)
U = Thermal Transmittance for roof or wall or glass. See 1997 ASHRAE Fundamentals, Chapter 24 or 2001
ASHRAE Fundamentals, and Chapter 25.
A = area of partition, ceiling or floor calculated from building plans
Ta = Temperature of adjacent space (Note: If adjacent space is not conditioned and temperature is not available,
use outdoor air temperature less 5F)
Trc = Inside design temperature of conditioned space (assumed constant)
4) Ventilation & Infiltration Air
Ventilation air is the amount of outdoor air required to maintain Indoor Air Quality for the occupants (sees ASHRAE
Standard 62 for minimum ventilation requirements) and makeup for air leaving the space due to equipment
exhaust, exfiltration and pressurization.
Q sensible = 1.08 * CFM * (To Tc)
Q latent = 4840 * CFM * (W o Wc)
Q total = 4.5 * CFM * (ho hc)
CFM = Ventilation airflow rate.
To = Outside dry bulb temperature, F
Tc = Dry bulb temperature of air leaving the cooling coil, F

Page 7 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org

Wo = Outside humidity ratio, lb (water) per lb (dry air)


Wc = Humidity ratio of air leaving the cooling coil, lb (water) per lb (dry air)
ho = Outside/Inside air enthalpy, Btu per lb (dry air)
hc = Enthalpy of air leaving the cooling coil Btu per lb (dry air)
Refer to 1997 ASHRAE Fundamentals, Chapter 25, for determining infiltration

Internal Loads
Internal cooling loads consist of the following:
1) Sensible & latent loads due to people
2) Sensible loads due to lighting
3) Sensible loads due to power loads and motors (elevators, pumps, fans & other machinery)
4) Sensible & latent loads due to appliances
An internal load calculation is the area of engineering judgment. The internal loads are sometimes about 60% of the
load; however, these data are generally the least amount of information available to you at the design stage and
therefore the generic rules are most often employed to fix the variables. The equations used in estimating internal loads
are:
1) People
Q sensible = N * (QS) * (CLF)
Q latent = N * (QL)
N = number of people in space.
QS, QL = Sensible and Latent heat gain from occupancy is given in 1997 ASHRAE Fundamentals Chapter 28,
Table 3
CLF = Cooling Load Factor, by hour of occupancy. See 1997 ASHRAE Fundamentals, Chapter 28, table 37.Note:
CLF = 1.0, if operation is 24 hours or of cooling is off at night or during weekends.
2) Lights
The lights result in sensible heat gain.
Q = 3.41 * W * FUT * FBF * (CLF)
W = Installed lamp watts input from electrical lighting plan or lighting load data
FUT = Lighting use factor, as appropriate
FBF = Blast factor allowance, as appropriate
CLF = Cooling Load Factor, by hour of occupancy. See 1997 ASHRAE Fundamentals, Chapter 28, Table 38.
Note: CLF = 1.0, if operation is 24 hours or if cooling is off at night or during weekends.

3) Power Loads & Motors


Three different equations are used under different scenarios:
a. Heat gain of power driven equipment and motor when both are located inside the space to be conditioned
Q = 2545 * (P / Eff) * FUM * FLM
P = Horsepower rating from electrical power plans or manufacturers data
Eff = Equipment motor efficiency, as decimal fraction
FUM = Motor use factor (normally = 1.0)
FLM = Motor load factor (normally = 1.0)

Page 8 of 79
www.PDHcenter.com PDH Course M196 www.PDHonline.org

Note: FUM = 1.0, if operation is 24 hours


b. Heat gain of when driven equipment is located inside the space to be conditioned space and the motor is
outside the space or air stream
Q = 2545 * P * FUM * FLM
P = Horsepower rating from electrical power plans or manufacturers data
Eff = Equipment motor efficiency, as decimal fraction
FUM = Motor use factor
FLM = Motor load factor
Note: FUM = 1.0, if operation is 24 hours
c. Heat gain of when driven equipment is located outside the space to be conditioned space and the motor is
inside the space or air stream
Q = 2545 * P * [(1.0-Eff)/Eff] * FUM * FLM
P = Horsepower rating from electrical power plans or manufacturers data
Eff = Equipment motor efficiency, as decimal fraction
FUM = Motor use factor
FLM = Motor load factor
Note: FUM = 1.0, if operation is 24 hours
4) Appliances
Q = 3.41 * W * Fu * Fr * (CLF)
W = Installed rating of appliances in watts. See 1997 ASHRAE Fundamentals, Chapter 28; Table 5 thru 9 or use
manufacturers data. For computers, monitors, printers and miscellaneous office equipment, see 2001 ASHRAE
Fundamentals, Chapter 29, Tables 8, 9, & 10.
Fu = Usage factor. See 1997 ASHRAE Fundamentals, Chapter 28, Table 6 and 7
Fr = Radiation factor. See 1997 ASHRAE Fundamentals, Chapter 28, Table 6 and 7
CLF = Cooling Load Factor, by hour of occupancy. See 1997 ASHRAE Fundamentals, Chapter 28, Table 37 and
39. Note: CLF = 1.0, if operation is 24 hours or of cooling is off at night or during weekends.
Heat Gain from HVAC System
a. Supply Fan Heat Load
Supply and/or return fans that circulate or supply air to the space add heat to the space or system depending
on the location relative to the conditioned space. The heat added may take one or all of the following forms:
Instantaneous temperature rise in the air stream due to fan drive inefficiency.
Temperature rise in the air stream when the air is brought to static equilibrium and the static and kinetic energy
is transformed into heat energy.
The location of the fan and motor relative to the cooling coil and space being conditioned determines how the
heat is added to the system. If the fan is downstream of the cooling coil (draw-thru) then the fan heat load is
added to the space-cooling load. If the fan is upstream of the cooling coil, then the fan heat load is added to
the system cooling coil load.
The heat energy is calculated as follows:
Q = 2545 * [P / (Eff1 * Eff2)]
P = Horsepower rating from electrical power plans or manufacturers data
2545 = conversion factor for converting horsepower to Btu per hour
Eff1 = Full load motor and drive efficiency
Eff2 = Fan static efficiency

Page 9 of 79

You might also like