Air Circuit Breakers: CG International Division
Air Circuit Breakers: CG International Division
Air Circuit Breakers: CG International Division
current control
CG International Division
1 Next Page
RANGE
SIZE II III IV V
RATINGS ( A) 200 1600 2500 4000
400 2000 3200
630
800
1000
1250
NO. OF POLES 3P / 4P 3P / 4P 3P / 4P 3P
BREAKING
CAPACITY
50 KA 65KA 80A 80KA
lic = lcu AT 415V
AC 3 Ph
Short circuit protection is provided through an armature type direct acting magnetic release.
During short circuit fault, the armature is instantaneously attracted, in-turn tripping the ACB
through delatching of trip shaft. This design ensures faster tripping time (less than 2 cycles).
Short circuit pick up level is adjustable continuously by knobs provided on the front of the ACB.
For 4000A ACB trippping is through series trip coil & is fixed at 5 times the CT TAP set current.
To achive discrimination when used as an incomer, a time delayed S/C trip can be provided. This
consists of a S/C release fitted with microswitch and RS unit supplied separately. RS unit
provides the time delay and is available in two versions - with fixed time delay ( 0.04 sec. ) and
with adjustable time delay ( 0.04 to 0.46 sec. ) During fault, the S/C release operates the micro
switch activating the RS unit. The RS unit trips the ACB through the tripping coil after the set time
delay.
Earth Fault Protection is also offered as an optional feature. This protection is achieved through
Earth Fault ( E/F ) relay. The E/F relay senses the earth fault and gbives a trip command to the
ACB through shunt trip. The sensitivity of the E/F relay is adjustable between 10% and 40% of the
ACB rating. The E/F telay is available in both versions - 3 phase 3 wire and 3 phase 4 wire. As a
standard, LED trip indication is provided on the E/F relay.
FAULT ANALYZER :
LH series thermal magnitic ACBs upto 3200A are fitted with mechanical trip indications for
overload, phase to ground fault, two phase or two phase to ground fault and three Phase or three
Phase to ground fault. Electrical indication facility for O/L trip is also provided as standard.
Electrical indication facility for phase to ground fault, two phase or two phase to ground fault and
three phase or three phase to ground fault can be provided on request. LH 4000 ACBs are
provided with mechanical trip indications for overload, short circuit & ;facility for O/L trip
electrical indication as standard feature.
Electrical indication facility for AC under voltage trip is available on entire range of ACBs on
request.
STATIC PROTECTION
Air Circuit Breakers with static protection come with a Solid Protection Relay - The CSR. The relay
comes as an integral part of LH series ACBs from 200 Amp to 3200 Amp. and does not require any
external supply for tripping ACB during fault.
TECHNICAL SPECIFICATIONS :
Input Scaling (O/L Setting) In 0.5, 0.6, 0.7, 0.8, 0.9, & 1.0 times of rated currunt
S/C pick up level setting 2 In, 3 In, 4 In, 5 In, 6 In & 8 In
S/C time delay Inst., 0.2, 0.4, 0.6, 0.8, & 1.0 Sec
IDMT characterists' selection 4, 8, 12.5, 16, 21, & 25 seconds at 6 In.
Earth Fault ( E/F ) settings 0.2, 0.3, 0.4, 0.5, & 0.6 times In (max.)
E/F time delay Inst. 0.2 , 0.4, 0.6, 0.8 & 1.0 Sec.
Magnetic Magnetic
O / L Range S / C Setting S/C
Frame CT Taps
(A) ( Standard ) ( Optional )
( kA ) ( kA )
LH 800 400 - 630 - 800/5 200 - 400 3-6-9 i) 1.2 - 2, 4 - 3.6
315 - 630 ii) 5 - 10 -15
400 - 800
AUXILLIARY SWITCHES :
ACBs are fitted with 4 N/O + 4 N/C auxiliary contacts as standard of which 3 N/O + 3 N/C potential
free contacts are available to customer for external wiring.
SLIDING CONTACTS :
In case of drawout ACBs , two sliding contacts for each auxiliary switch are necessary. A
maximum of 30 ( single way ) sliding contacts can be provided per ACB.
STANDARD OPTIONAL
Shunt trip or U/V trip $ Shunt Trip
U/V trip
Potential free3 NO + 3 NC Aux switcheswith Closing release
sliding contact (for D/O ACB )
Closing release * RC Unit for Time delayed U/V trip ( upto 0.50 sec. )
Mech indication for ** RS relay for time delay ( 40 ms fixed ) of S/C trip ##
Service/Test/Isolated Position RS relay for time delay ( 40 - 460 ms ) of S/C trip ##
A : Available
* * * : Voltage rating of RS relay are available intwo versions. Time delay fixed at 40 ms.
(with 240 V AC Input Supply ) & Time delay variable in steps fron 40 - 460 ms.
# : Not available when fitted with RS relay. ## : Not applicable for ACBs with static release.
$ : Applicable for Thermal - Magnetic ACB. If nothing is specified then 415 VAC Shunt Trip is provided as
standard and if U/V is specified for ACB then shunt trip is optional.
Thermal Magnetic