Experiment 4 Heat Exchanger Control
Experiment 4 Heat Exchanger Control
Experiment 4 Heat Exchanger Control
4.1 Objective
4.2 Introduction
The Heat Exchanger Control has been designed on how a temperature loop for an exchanger
can be controlled using a microprocessor based controller. The control panel is connected to
a Distributed Control System (DCS), which can remotely control the process plant using
supervisory control mode (SCADA) or direct digital control mode (DDC). A selector located at
the control panel is used to select between SCADA or DDC mode. In SCADA mode the DCS
can monitor and control the process through the process controller and in DDC mode, the
DDC can directly control the plant through the Field Control Station.
The Heat exchanger control is a water process. A double pass shell and tube exchanger E-
221 is used for the study of process control. Hot water is circulated in the system by pump P-
213 through the tube side of the heat exchanger and returns to hot water tank T-203. Cold
water is circulated by pump P-211 from tank T-201 through the shell side and is collected as
the heated product in tank T-202. The product can also be cooled down by an air-cooled
radiator E-222 and recirculated back to the cold water tank T-201.
Various types of instrumentations are installed in the process line. An RTD Temperature
Transmitter, TT-221 monitors the product temperature and feeds the signal to a PID loop TIC-
221 in the process controller. The output from TIC-221 is fed to the control valve TCV-221
which regulate the amount of heating energy into the heat exchanger. There is another ON-
OFF temperature controller TIC-203 that controls the temperature in the hot water tank T-203
according to a preset temperature. Another ON-OFF controller LIC-202 is used as the
batching controller which controls LV-202 to batch a certain quantity of product in tank T-202.
Solenoid valves have been installed for the purpose of fault simulation in various sections of
the process line. Fault simulation switches have been installed to simulate these faults, which
will create errors in the process line.
Fill in Cold Water Tank T-201 and Hot Water Tank T-203
2
respectively.
The instrument air regulator RG1 has been set to 2.8 bar
3 (40 psi). Check that the RG1 pressure is correct and
adjust if necessary to set it at 2.8 bar.
Put the control loop into manual mode and then adjust the set
2
point to 45 C
4 Turn on the recorder then put the control loop into auto mode
4 Turn on the recorder then put the control loop into auto mode
Once the measurement stabilize turn off the recorder. Put the
10
control loop back into Manual mode
11 100
50
10
2
Table 4.5 Proportional and Integral Heat exchanger control
Put the control loop into manual mode and then adjust the set
2
point to 45 oC
4 Turn on the recorder then put the control loop into auto mode
Once the measurement stabilize turn off the recorder. Put the
10
control loop back into Manual mode
Put the control loop into manual mode and then adjust the set
2
point to 45oC
Turn on the recorder then put the control loop into auto
4
mode
Once the measurement stabilize turn off the recorder. Put the
10
control loop back into Manual mode
60 the differences.
300
Table 4.7 PID Heat exchanger control loop tuning
Put the control loop into manual mode and then adjust the
output gradually so that temperature matches the set point of
1
45oC
Turn on the recorder then put the control loop into auto
3
mode
4.6 REFERENCES
Seborg D.E., T.F. Edgar and D.A. Mellichamp, Process Dynamics and Control, John Wiley
and Sons, 2nd Ed, New York, 2004, pp 116-118.
Piping and Instrumentation Diagram