GET6600G Section 5 Rev 1 Bookmarks
GET6600G Section 5 Rev 1 Bookmarks
Contents5
Section 5
System and Equipment Protection
Page
INTRODUCTION ................................................................................................ 5-2
5-1
System and Equipment Protection
INTRODUCTION
This selection Guide covers some of the ba- Overcurrent relays today are available with the
sic considerations used when selecting relays for standard ANSI inverse, very inverse, or extremely
the protection of Medium Voltage Power Systems. inverse and definite time characteristics. Many
It is organized by protection packages according microprocessor-based relays also offer the IEC
to the types of equipment generally encountered time characteristics. In the absence of additional
in medium voltage systems. Feeders, Incoming system information, for a single characteristic
Lines, Bus, Transformers, Motors, Generators and device the very inverse characteristic is most likely
Metering will be addressed. to provide optimum circuit protection and selectiv-
ity with other system protective devices. This char-
Protection considerations can be provided by acteristic is intended for application where the
either single phase and multi-function three phase magnitude of fault current is determined primarily
relays that can include phase and ground direc- by the distance from the source to the fault. If
tional, non-directional relays, overcurrent, differen- selectivity with fuses or reclosers is a requirement,
tial, directional power, under-frequency and under- the extremely inverse characteristic is well suited
over voltage relaying. for applications. The inverse characteristic is useful
in those rare applications in which selectivity with
Newer multifunctional digital relays offer sev- other inverse or definite time relays is a concern.
eral benefits; expanded relay functions, digital me- It is also useful on systems that have a multiplic-
tering, diagnostics, reduction in relay costs per ity of local generators at the distribution voltage
function, reduction in wiring and increased panel and where the magnitude of fault current is deter-
space with the reduction in the quantity of relays. mined primarily by how many generators are in
GE Multilin Relay product reference guide can be service at the same time. Most microprocessor-
found at www.GEMultilin.com. based relays have all the above characteristics
field-selectable which would allow the specifier to
Instrumentation, metering, current and voltage select a relay with minimal information and select
detection considerations include selection of in- a characteristic when more complete information
strument transformer ratios, as well as scales of is available.
analog meters if used.
INCOMING LINESIncoming line phase-over-cur-
Control considerations include a discussion rent protection is typically time delay only (51),
of permissive control operation as well as supervi- furnished without instantaneous attachments (50),
sion of trip coils by indicating lamps. or on digital multi-function relays, the instanta-
neous is disabled but the functions stays avail-
Since all AC power systems are subject to tran- able. This allows the relay to be selective with
sient voltages, a discussion of surge protection is feeder relays having instantaneous attachments
also included. (50/51).
FEEDER TIES For feeder-tie (cable connected) The three most commonly used connections
circuits to downstream distribution circuit-breaker for ground-overcurrent relays are the residual con-
lineups, selectivity is enhanced by disconnecting, nection (51N), the ground-sensor (balanced-flux
disabling, or delaying the instantaneous element or zero-sequence) connection (50GS or 51GS),
(50) of the phase-overcurrent relays and setting and the neutral current transformer connection
the time-overcurrent (51) element to trip at less (51G).
than the short-circuit heating limit of the conduc-
tors. Residually connected ground-overcurrent re-
lays (51N) are wired in the ground (neutral)-return
BUS TIESBus-tie circuits, within the same lineup current transformer lead of three current transform-
of switchgear including two incoming lines, are fre- ers connected in wye. The relay detects the cur-
quently specified without overcurrent-protection. rent of a ground fault by measuring the current
When overcurrent protection is provided for this remaining in the secondary of the three phases of
type of circuit, relays are connected in what is the circuit as transformed by the current trans-
termed a current summation connection. The formers. The minimum pickup of the relay is de-
use of this connection provides the opportunity for termined by the current transformer ratio. On sys-
selectivity between main or tie breakers and feeder tems with line-to-neutral connected loads, the
breakers minimizing relay operating time delay. ground-overcurrent relay (51N) pickup must be set
(See the one-line diagram on page 2-7 for an ex- above any expected maximum single-phase un-
ample of this connection.) balanced load. If an instantaneous ground-
overcurrent element (50N) is used, it must be set
TRANSFORMERSTransformer-overcurrent pro- above any expected unbalance due to unequal
tection criteria are specified in Section 450 of the current transformer saturation on phase faults or
2005 National Electrical Code. Permissible short- transformer inrush currents. Residually connected
circuit capabilities for transformers are specified ground-overcurrent relays are usually applied on
in ANSI Standard C57.12. Selection of trans- solidly grounded systems.
former-overcurrent protection is governed by these
criteria. Ground-sensor (GSCT) relaying schemes use
The NEC requirements determine the pickup an instantaneous (50GS) or time-delay (51GS)
of the time-overcurrent phase protective relays. The overcurrent relay or relay element connected to
ANSI requirements and the connection of the trans- the secondary of a window-type current transformer
former determine the time dial setting. The inrush through which all load current-carrying conductors
and short-circuit current magnitudes determine the pass. The relay detects the ground current di-
instantaneous setting of the phase-overcurrent pro- rectly from this current transformer, provided the
tective relays. equipment ground conductor and cable shielding
bypass the current transformer. Ground faults 15
GENERATORS Overcurrent relays, applied on amperes (or less) in the primary circuit can be
generator circuits, are used for feeder backup rather detected with this scheme. Ground-sensor relay-
than overload protection. These overcurrent re- ing schemes are usually applied on low resistance
lays are typically voltage-restrained overcurrent or solidly grounded systems.
relays (51V). They operate faster and are more
sensitive for faults close to the generator than for Neutral ground relaying typically uses a time-
faults remote from the generator. The GE Multilin delay overcurrent relay (51G) connected in the
SR489 relay provides complete generator protec- secondary of the current transformer, located in
tion, metering and monitoring. the neutral of a wye-connected transformer, wye-
connected generator, or the neutral of a neutral-
Ground-overcurrent Protection deriving transformer bank.
5-3
System and Equipment Protection
ters can be used to indicate the presence of a circuits with metal-enclosed conductors (non-seg
ground fault on an otherwise ungrounded system. Bus Duct) because of the impracticability of pass-
ing the phase conductors through a single current
INCOMING LINES Incoming line ground-over-cur- transformer. Ground-sensor relaying is rarely ap-
rent relay protection consists of either a residu- plied to circuits terminated with potheads because
ally connected relay (51N) or a relay (51G) con- of the special installation procedures required for
nected to a current transformer in the transformer mounting the potheads.
neutral ground connection. Ground-sensor relay-
ing (51GS) on incoming lines is not recommended Residual-ground relaying (51N or 50/51N) is
because of the size, number, and construction of suitable for feeders on solidly grounded systems
the incoming line conductors. or resistance grounded systems with available
ground-fault currents greater than about twice the
For solidly grounded systems with source maximum current transformer rating. It is also
transformers located remote from the switchgear, required for feeders, which must be selective with
residually connected ground-overcurrent relays other downstream feeders having residual-ground
(without instantaneous) are most often applied. overcurrent relaying.
Some utility users omit all incoming line ground
relays on solidly grounded systems and rely on TRANSFORMERS AND GENERATORS
three phase-overcurrent relays to provide complete Ground-overcurrent relaying for wye-connected
phase- and ground-fault protection. transformers, wye-connected generators and neu-
tral-deriving transformers usually employs neutral-
For impedance or resistance grounded sys- ground relaying, as discussed previously under In-
tems with local source transformers, a ground re- coming Lines. This provides system backup
lay (51G) connected to a current transformer in ground relaying. Settings, however, are normally
the transformer neutral connection is most appli- too high to provide good ground-fault protection for
cable. A typical current transformer ratio for the the apparatus. Ground-fault protection is better
neutral current transformer is one-half to one-quar- obtained by using a scheme of differential relay-
ter the maximum ground-fault current, e.g., a 200:5 ing, which is described later in this section.
CT ratio is appropriate for the neutral CT in series
with a 400A, 10-second neutral grounding resis- Directional Phase-overcurrent Protection
tor. This ratio permits sensitive settings of the
ground relay and selective operation with down- Directional phase-overcurrent relays (67) op-
stream ground-sensor relays. The ground relay is erate for current flow in only one pre-determined
the system backup relay for the medium-voltage direction. Incoming lines, operating in parallel from
system. It also provides ground-fault protection separate sources, require directional phase-
for the transformer and its secondary conductors. overcurrent relay protection to provide sensitive
If a transformer primary circuit breaker is used, operation and to assure selectivity between incom-
the secondary ground-overcurrent relay (51G) in ing-line breakers for phase faults on the source
the transformer neutral connection should trip both side of one of the breakers. This directional phase-
the transformer primary and secondary circuit overcurrent protection is furnished by using relays,
breaker. polarized to operate on current flowing toward the
source. The directional- overcurrent relay without
FEEDERS Ground-sensor (zero-sequence) re- instantaneous function is appropriate for most
lay arrangements use instantaneous-overcurrent applications. The pickup of this relay should be
relays (50GS) or time-overcurrent relays (51GS) set at a value slightly below full-load current. The
and are appropriate for both resistance grounded time delay function can be set to permit selectiv-
and solidly grounded systems. These arrange- ity with upstream feeder breaker or line instanta-
ments provide sensitive ground-fault protection for neous relays.
both branch circuits and feeder-distribution circuits.
Good selectivity can be obtained for a distribution Occasionally a directional-overcurrent relay
system incorporating this type of relaying on all (67) with directional instantaneous function is ap-
branch and feeder distribution circuits; however, a plied to incoming lines fed by long dedicated
feeder breaker with ground-sensor relaying usu- service lines, the instantaneous directional unit is
ally cannot be made selective with downstream set to operate for faults located approximately 80
feeders using residual ground relaying. In addi- to 90 percent of the distance from the incoming
tion, ground-sensor relaying is not applicable to line to the source. For large local transformers,
5-4
Section 5
the instantaneous unit on a high side directional High Impedance Ground Fault Detection
overcurrent relay is set slightly above the low-volt-
age symmetrical rms amperes contributed through Many distribution system ground faults do not
the transformer to a fault on the higher voltage side generate enough current to be detected by tradi-
of the transformer. tional overcurrent protection. These faults fre-
quently result from a broken conductor falling in
Directional phase-overcurrent relays can be contact with a poor conducting surface or an ob-
voltage polarized from bus VTs connected in open- ject having relatively high impedance (tree
delta, delta-delta or wye-wye. Polarization is nec- branches, dry ground). A high percentage of arc-
essary to establish the current phase relationships ing downed conductors may be detected by new
between voltage and current to determine the di- digital relays with High Z capabilities, specifically
rection of current flow. designed for this purpose, such as the GE Multilin
F60 Feeder Protection Relay.
While earlier electromechanical directional-
overcurrent relays usually had only one time-cur- Differential Protection
rent characteristic, digital multi-function versions
are available in three-phase (and ground, if desired) Differential Protection is a method of equip-
packages with inverse, very inverse, and extremely ment protection in which an internal fault is identi-
inverse (and other) characteristics that are field- fied by comparing electrical conditions at all in-
selectable. coming and outgoing terminals of the equipment.
By virtue of the connection and settings, this pro-
Directional Ground-overcurrent Protection tection only operates for faults in the apparatus
being protected, or in the zone of protection.
Incoming lines operated in parallel from sepa- Hence differential protection does not need to co-
rate grounded sources require directional-ground- ordinate with devices protecting other downstream
overcurrent relays (67N) to assure selectivity be- conductors and equipment. Differential protection
tween incoming-line breakers for ground faults on considerations for specific equipment will be dis-
the source side of each of the incoming-line break- cussed in the later sections.
ers. For solidly grounded systems and many im-
pedance-grounded systems, a multi-functional BUS PROTECTIONBus-differential relays should
digital relay usually is appropriate. This relay is be applied to generator buses, buses with high
set at a low pickup to permit selectivity with the available short-circuit current, and buses which, if
other incoming-line non-directional ground- faulted, create system disturbances which could
overcurrent relaying. lead to system instability in other portions of the
system if the fault is not rapidly isolated. High-
All directional-ground relays must be polar- speed bus differential can also reduce the level of
ized. For systems with local, grounded supply incident energy released during an internal arcing
transformers, the current transformer located in fault, increasing operator safety and reducing
the transformer neutral-ground connection may be equipment damage. This type of relaying uses
used for polarizing. For systems with remote-sup- equally rated phase-current transformers of like
ply transformers, a set of local wye-broken delta characteristics in each circuit connected to or from
connected voltage transformers (or wye-wye VTs the bus to be protected. Bus-differential relays
with wye-broken delta auxiliary transformers) may (87B) are available in both single phase, or three
be used for polarization. On occasion, dual polar- phase designs, such as the GE Multilin PVD
ization may be desirable. (single phase) or MIB (three phase) relay.
5-5
System and Equipment Protection
Open-phase Protection (Negative-sequence
Differential relays protect the internal trans-
Voltage)
former circuit, including conductors, bushings and
windings. Fault-pressure relays provide excellent
Incoming line open-phase operation occurs
internal tank-fault protection for liquid-filled trans-
when one conductor is opened due to either a
formers, but do not include the entire circuit in the
single upstream fuse melting or a single-line con-
protected zone.
ductor or circuit breaker pole opening. System
protection for either of these events for systems
Transformers connected delta-wye, with the
without local generation consists of a negative-
secondary neutral grounded through resistance,
sequence voltage unbalanced relay (60). To avoid
frequently require ground-fault as well as phase-
tripping on system transient disturbances, this
fault differential protection because the pickup of
relay should operate through a time delay usually
phase-differential relays may not be low enough
set from 2 to 4 seconds. For systems subject to
to detect secondary ground faults. This results
harmonics, a harmonic filter applied to the input
from the large CTs necessary to carry transformer
to this relay may be required. The negative-se-
load currents at forced air ratings. For such sys-
quence voltage function (60) may also be incorpo-
tems, the GE Multilin SR745 Transformer Protec-
rated in a multi-function motor protection relay.
tion relay can be used for complete protection.
Automatic Reclosing
MOTORS Motor differential relays are usually
Radial feeders supplying overhead lines, with or
applied to motors 1500 hp and larger. Three-phase
without line sectionalizing, sometimes employ
motor-differential relays (87M) used for this appli-
automatic reclosing for better service continuity.
cation employ the balanced-current principle. This
Relaying for this type of application is used for
type of protection provides for detecting motor-fault
open-wire overhead circuits, which are prone to
currents as small as 15 amperes. An example for
develop non-persistent faults. A series of three or
a typical application is shown in the one-line dia-
four attempts to close a breaker at variable times
gram in Section 2. In some applications, differen-
may either be programmed with an immediate ini-
tial relay schemes are used to protect both the
tial reclosure or an initial time-delay reclosure. A
motor and its feeder cable. These schemes use
multi-shot automatic reclosure option is utilized
three CTs on each side of the motor.
for this function. The use of the immediate initial
reclosure option is not recommended on feeders
LINES Line-differential protection (87L) for short
serving large motors or on feeders originating on a
lines and important tie lines between medium-volt-
generator bus. Frequently, the automatic reclosing
age switchgear lineups is obtained by using pilot-
relay is programmed to block an instantaneous
wire relays. These relays compare the currents
overcurrent relay (50 or 50N) after the initial trip,
at each end of a two-terminal line. These high-
for part of or all of the reclosing schedule. This
speed relays are sensitive to both phase and
function may also be incorporated as part of a multi-
ground faults. Pilot wire supervision and transfer
function microprocessor-based protection relay,
tripping relays are used in conjunction with the
which is directional or non-directional.
pilot-wire relays.
Directional Power, Underfrequency, and
GENERATORS All generators should be pro-
Undervoltage Protection
tected with differential relaying. Generator-differ-
ential relays (87G) are high-speed relays sensi-
Systems with local generation or large mo-
tive to phase faults and many ground faults. These
tors require relaying to detect fault conditions on
relays compare the currents in and out of genera-
the utility tie circuit or to detect loss of the utility
tors using three CTs on each side of the genera-
source. Relays used to detect these circum-
tor. For small generators, balanced-current-differ-
stances should be high-speed to trip the utility tie
ential relaying may be used. This type of relaying
prior to any automatic reclosing operations and to
is described under Differential Protection Motors.
promptly initiate any programmed load shedding.
Complete protection for these circumstances is
provided by a combination of functions including
under frequency (81); a sensitive directional-power
(32); and undervoltage (27). For some applica-
tions where the (32) and (27) functions are only
5-6
Section 5
instantaneous, a timer is used which is set at are two indicating lamps, one red and one green.
about 0.2 second. The directional-power element The red lamp indicates a closed breaker and su-
may be connected to current transformers either pervises the trip coil integrity. The green lamp in-
in the incoming line circuit or in a large motor cir- dicates an open breaker. This lamp is connected
cuit depending on the application. A study of the through a breaker b contact.
specific system is required to select the appropri- For switchgear applications requiring remote
ate relays and connections for this type of protec- control, a permissive control (69CS) function is
tion. available. This function provides local or remote
control of a circuit breaker under certain defined
GE Multilin multi-function relays, such as the conditions, and is available in three schemes as
SR489G or G60 use a combination of relay func- shown in Table 5-1. Scheme C is recommended
tions including under frequency (81), sensitive di- for remote control, since it provides maximum op-
rectional-power (32), undervoltage relay (27), and erating flexibility. When a local trip operation is
timing functions to provide complete protection. initiated, the breaker cannot be closed remotely
until the local switch handle is returned to the
BASIC EQUIPMENT PROTECTION NORMAL AFTER CLOSE position. When the
breaker is in the TEST position, closing and trip-
Circuit Breaker Control and Control Power ping can only be done locally.
Protection
5-7
System and Equipment Protection
An optional white breaker disagreement lamp CURRENT TRANSFORMERS AND VOLTAGE
is also available. This lamp is by-passed by a slip TRANSFORMERSStandard window-type current
contact of the control switch and connected to a transformers are available in ratios ranging from
b contact of the breaker and provides indication 50:5 to 4000:5 amperes. The basic ground-sen-
of a breaker opening not initiated by the control sor window-type CT (GSCT) ratio is 50:5 amperes,
switch. An alternate option for this white lamp is with a 7.25" window, and an optional GSCT with a
to provide indication of the circuit breaker spring- 12" window is available for circuits with a large
charged condition. number of conductors. Relay accuracy class is
per IEEE C37.20.2-1999, Table 4. Higher accu-
Each breaker trip and close circuit is individu- racy classes may be available, however space for
ally protected by a two-pole fuse-block with prop- mounting is limited.
erly selected fuses, or molded case breaker.
5-8
Section 5
Metering and Test Blocks
do not hold the narrow protective level required by The surge suppressor 200 ampere rating and
the IEEE C62.11 standard for surge arresters. The characteristics are shown in Table 5-4 for
goal is to provide a bank of protective levels which machine voltages in these voltage classifications,
are below the BIL levels of rotating machines and to illustrate the margin of protection. The BIL
ventilated dry-type transformers. See Table 5-5. ratings of ventilated dry-type transformers are
above the machine characteristics shown and are
The discs used in the surge suppressor are relatively insensitive to front time in contrast to
approximately two inches in diameter and one and the motor characteristic. Note that steep front
one-quarter inches thick. Mechanically and ther- transient may be above the machine characteris-
mally they are very strong. The material is not sub- tics at fast front times.
ject to deterioration by repeated surges. Its cur-
rent when energized line-to-ground is a few micro-
amperes.
Tests on surge suppressors indicated that
switching surges rarely produced a 200 ampere
surge through the surge suppressor. For this rea-
son the surge suppressor is rated at a protective
level at 200 amperes.
4.16 60 11
7.2 9.5 23
13.6 9.5 36
5-10