Communication

7.7 PROFIBUS FMS

Variants We differentiate between the following variants:


q PROFIBUS FMS with SIMATIC NET software 05/2000 + SP2; see
Chapter 7.7.1
q PROFIBUS FMS with SIMATIC NET software 11/2002 + SP1; see
Chapter 7.7.2
q Procedure with SIMATIC NET NCM PC Edition; see Chapter 7.7.3

7.7.1 PROFIBUS FMS with SIMATIC NET Software 05/2000 + SP2

Operations Proceed as follows in order to establish and configure communication


between the PC and device via a PROFIBUS FMS:
Install the hardware.
Install the software for CP 5613
Create a new master system
Insert SIPROTEC 4 FMS Slave into the master system
Save the settings
Export the NCM database
Set the programming device/PC interface
Prepare Operation without a SICAM station
Prepare Operation with a SICAM station
Check and modify the variable addresses and lengths
Establish the PROFIBUS FMS connection
Close the PROFIBUS FMS connection

7.7.1.1 Installing Hardware

In order to implement communication via PROFIBUS FMS you require


the CP 5613 communications processor interface card for your
computer. For information on installing the card as well as on the physical
connection to the PROFIBUS FMS network please refer to the
documentation on the CP 5613 communication processor.

410 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.1.2 Installing the PROFIBUS FMS driver and COM PROFIBUS

Install the driver for the CP 5613 communication processor and the COM
PROFIBUS program for configuring communication via PROFIBUS
FMS.

Proceed as follows:
Place the SIMATIC NET Software (05/2000 + SP2) CD in the CD-
ROM drive of your PC and start the setup.exe file.
Click Install SIMATIC NET Software and follow the instructions of
the installation program.
Select PB FMS-5613 V2.1 in the SIMATIC NET Setup:
Components dialog box and click Next.

DIGSIKOM074a.gif

Fig. 7-36 SIMATIC NET Setup: Components dialog box

Restart the operating system after installation has been completed


successfully.

Note:
If you would like to use the communication processor CP 5613 together
with SIMATIC NET Software (05/2000 + SP2), you have to install a hotfix
from a disk. To this purpose please contact your A&D sales
representative.

SIPROTEC 4 System Description 411


E50417-H1176-C151-A5
Communication

Installing Drivers in During installation of the SIMATIC NET software, the drivers for the CP
the System 5613 communications processor are copied onto the hard drive of the
PC. Install this driver in the system so that you can access the CP 5613
communication processor.
Click in the Windows start menu on Settings Control Panel.
Double-click in the Control Panel Window on the PG/PC interface
icon.
The Setting the PG/PC Interface dialog box is opened.

DIGSIKOM014a.gif

Fig. 7-37 Setting the PG/PC interface

Click Select.
The Install / Remove Interfaces dialog box is opened.

412 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

DIGISKOM075a.gif

Fig. 7-38 Installing/removing interfaces

Select the entry CP5613/CP5614 in the Select box and click Install.
In the subsequent dialog box, select the model name of the installed
communications processor.
Click OK.
The drivers are installed. The resources assigned by Windows are
displayed in an indication box after installation has been completed
successfully.
Click Close in the Install / Remove Interfaces dialog box.
A query appears regarding the changed settings. However, as further
settings still need to be entered, it doesn't make much sense to restart
the system at this point.
For this reason, click Cancel.
Click OK in the Setting the PG/PC interface dialog box. The dialog
box closes.

SIPROTEC 4 System Description 413


E50417-H1176-C151-A5
Communication

7.7.1.3 Creating a New Master System

Configuration of the CP 5613 communications processor is carried out by


means of the COM PROFIBUS program. For details please refer to the
COM PROFIBUS manual. On the SIMATIC NET Software (05/2000 +
SP2) CD you will find the version COM PROFIBUS V5.0. However,
Windows 2000 users need the version V5.1. To this purpose please
contact your A&D sales representative.
DIGSI 4 functions in the PROFIBUS FMS network as a master. Since
DIGSI 4 is connected to the PROFIBUS FMS network via the CP 5613
communications processor, a new master system is first created for this
card.
Proceed as follows:
Start COM PROFIBUS.
Drag & drop the FMS master CP5613/CP5614 from the selection list
onto the working area (see Figure7-39 ).
Select Object properties... via the context menu:

DIGSIKOM001a.gif

Fig. 7-39 New master system

Specifying the Bus Select a PROFIBUS address and the station name in the FMS
Address and master parameters dialog box. Please select only even addresses
Station Name (in this case "2").

414 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

DIGSIKOM001b.gif

Fig. 7-40 FMS master parameter

Click OK to apply your entries.

SIPROTEC 4 System Description 415


E50417-H1176-C151-A5
Communication

7.7.1.4 Inserting a SIPROTEC 4 FMS Slave in the Master System

SIPROTEC 4 devices which communicate with DIGSI 4 function in the


PROFIBUS FMS network as slaves. You must therefore add a
SIPROTEC 4 FMS Slave into the master system for each device.
Proceed as follows:
Double-click the SIPROTEC 4 device in the selection list to move it to
the working area. Select the symbol with the type of connection which
you would like to use.

DIGSIKOM004a.gif

Fig. 7-41 SIPROTEC 4 device inserted as a slave

Select Object properties... via the context menu.

DIGSIKOM001b.gif

Fig. 7-42 FMS Station parameter

416 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Select a PROFIBUS address and the station name in the FMS


station parameters dialog box. Please select only even addresses
(in this case "4").

Note:
Make a note of the PROFIBUS address. You require it in order to set the
communication parameters in DIGSI 4 (see Chapter 7.7.1.8 and
Chapter 7.7.1.9).

Click OK to apply your entries.

Establishing a Select the symbol CP5613/CP5614 in the working area.


Connection
Select Object properties... via the context menu.
Click Connections in the FMS master parameters dialog box.
The Edit FMS Connections dialog box is opened.

DIGSIKOM010a.gif

Fig. 7-43 Editing FMS connections

Click New.

SIPROTEC 4 System Description 417


E50417-H1176-C151-A5
Communication

DIGSIKOM010b.gif

Fig. 7-44 Select FMS partner station

Select the FMS partner station which you created.


Accept the values with OK. The dialog box closes.

Note:
Make a note of the value for the communication reference. You require
this value in order to set the communication parameters in DIGSI 4 (see
Chapter 7.7.1.8 and Chapter 7.7.1.9).

Create the required SIPROTEC 4 FMS slaves for all the devices in the
PROFIBUS FMS network.

418 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.1.5 Saving Settings

Save the configured settings of the master system.


Proceed as follows:
Use File Save As to open the Save As dialog box.

DIGSIKOM012a.gif

Fig. 7-45 Save As

Enter a name with the extension PB5 in the File name box. Select the
drive and directory and click OK.
The settings are saved.

SIPROTEC 4 System Description 419


E50417-H1176-C151-A5
Communication

7.7.1.6 Exporting the NCM Database

The configured settings must exist as an NCM database in order for the
CP 5613 communications processor to process them. You must
therefore export the settings as an NCM database.
Proceed as follows:
Use File Export NCM File to open the Save As dialog box.

DIGSIKOM013

Fig. 7-46 Saving file as

Enter a name with the extension ldb in the File name box. Observe
the DOS conventions. Select the drive and directory and click Save.
The settings are saved as an NCM database.

420 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.1.7 Setting the PG/PC Interface

Transfer the configured data of the master system to the NCM database
in the CP 5613 communications processor.
Proceed as follows:
Click in the Windows start menu on Settings Control Panel.
Double-click in the Control Panel Window on the PG/PC interface
icon.
The Setting the PG/PC Interface dialog box is opened.

DIGSIKOM014b.gif

Fig. 7-47 Setting the PG/PC interface

Select the CP5613_CP5614(COM PROFIBUS) entry in the Interface


parameter set used box as the active PROFIBUS FMS interface.
Select the CP_L2_1 as the Access point of application.

SIPROTEC 4 System Description 421


E50417-H1176-C151-A5
Communication

Properties Click the Properties command button


The Properties - CP5613_5614(PROFIBUS) dialog box is displayed.
Change to the FMS/DP Protocol tab.

DIGSIKOM015a.gif

Fig. 7-48 Properties - CP5613_5614(PROFIBUS),


FMS/DP-Protocol tab

Activating FMS Activate the Activate FMS check box. The Activate DP check box
may not be selected.
In the FMS/DP Database input box enter the name of the NCM file
including the complete path designation directly or search for the file
by using the Search command button in the Select Database dialog
box.

422 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Resetting and Change to the Mode tab and click the Restart command button. This
Restarting resets the CP and restarts it.
The course of the processes is displayed in the lower section of the
dialog box.

DIGSIKOM018a.gif

Fig. 7-49 Properties dialog box, Mode tab

Click OK. Also click OK in the Setting the PG/PC interface dialog
box.

SIPROTEC 4 System Description 423


E50417-H1176-C151-A5
Communication

7.7.1.8 Preparing Operation without SICAM Control Center

Proceed as follows in order to set the communication parameters in the


PROFIBUS FMS network in which you only communicate between
DIGSI 4 and SIPROTEC 4 devices:
Open your project in DIGSI 4.
Select the SIPROTEC 4 device and open the Object properties via
the context menu.
Change to the FMS / IEC setting tab in the Properties - SIPROTEC
4 device dialog box.

DIGSIKOM058a.gif

Fig. 7-50 Properties - SIPROTEC 4 device, FMS / IEC setting tab

Select the PROFIBUS FMS address and Communication


reference CR which you assigned when configuring the master
system (see Chapter 7.7.1.4).
A VFD name for DIGSI 4 is automatically assigned in the VFD name
box. Do not change this value.
The designation of the access point of the application corresponds to the
designation defined during the setting of the PG/PC interface (see
Chapter 7.7.1.7).
Confirm by clicking OK.

424 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.1.9 Preparing Operation with SICAM Control Center

If a SIPROTEC device is to be operated in conjunction with a SICAM


control center, a full version of STEP 7 must also be installed in addition
to DIGSI 4. For a detailed description of the procedure please refer to
the documentation of SICAM SAS and STEP 7.
Proceed as follows:
Start the SIMATIC Manager and open your project.
Use View Component view to select the component view of the
project.
Select the SIPROTEC 4 device and open the Properties -
SIPROTEC 4 device dialog box by means of the Object properties
context menu. Change to the PROFIBUS FMS Connections tab.

DIGSIKOM019a

Fig. 7-51 Properties - SIPROTEC 4 device, PROFIBUS FMS connections tab

Add Connection Click New and change to the Parameters tab in the Properties -
PROFIBUS interface dialog box. The names and transmission rates
of all the PROFIBUS FMS subnetworks available are displayed.

SIPROTEC 4 System Description 425


E50417-H1176-C151-A5
Communication

DIGSIKOM020a

Fig. 7-52 Properties - PROFIBUS interface, Parameters tab

Selecting a Select the subnetwork that you want to add as an additional


Subnetwork connection for the SIPROTEC 4 device.

Check the network profile. To do so click on Properties and change


in the Properties - PROFIBUS dialog box to the Network Settings
tab, where Universal (DP/FMS) has to be selected in the Profile
select box.

DIGSIKOM021a

Fig. 7-53 PROFIBUS Properties, Network Settings tab

426 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Click OK.
Select the PROFIBUS FMS address which you specified when
configuring the master system for the device in the Address field of
the Properties - PROFIBUS Node dialog box.
Confirm by clicking OK.
Click OK in the FMS / IEC setting tab of the Properties - SIPROTEC
4 device dialog box in order to accept the displayed connections.

Inserting PG/PC Now insert an object of the type PG/PC in your project in order to
integrate DIGSI 4 in the project structure.
Proceed as follows:
Select your project and click Insert Station
7 PG/PC.
Assign the name DIGSI PC to the inserted object and open the
Properties - PG/PC dialog box via the Object Properties context
menu.
Change to the Interfaces tab.

DIGSIKOM024a

Fig. 7-54 Properties - PG/PC, Interfaces tab

Click New.
The New Interface - Select Type dialog box is opened.

SIPROTEC 4 System Description 427


E50417-H1176-C151-A5
Communication

DIGSIKOM027a

Fig. 7-55 New Interface - Select Type

Select the PROFIBUS setting in the select box and click OK.

The Properties - PROFIBUS Node dialog box is opened.


Click the Settings tab. This tab shows the names and transmission
rates of all available PROFIBUS FMS sub-networks.
Select the subnetwork via which your DIGSI 4 PC is to be
connected.
Check the profile via the Network Settings tab in the Properties -
PROFIBUS dialog box. The Universal DP/FMS setting has to be
selected.
Click OK.
Select the PROFIBUS FMS address which you specified when
configuring the master system for the device in the Address field of
the Properties - PROFIBUS Node dialog box.
Confirm by clicking OK.
Click OK in the FMS / IEC setting tab of the Properties - SIPROTEC
4 device dialog box in order to accept the displayed connections.
Change to the Assignment tab in the Properties - PG/PC dialog box.

428 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

DIGSIKOM026a

Fig. 7-56 Properties - PG/PC, Assignment

Select the PROFIBUS interface(1) entry in the Configured


Interfaces select box and the CP5613_5614(PROFIBUS) entry in the
Interface Parameter Assignments in the PG/PC select box.
Click Assign and OK.

SIPROTEC 4 System Description 429


E50417-H1176-C151-A5
Communication

Displaying the Display the current network configuration in order to check it.
Network
Double-click the PROFIBUS object.
Configuration

DIGSIKOM028

Fig. 7-57 Example of the network configuration with SICAM Station and DIGSI PC

Updating the Extend the master system by a SICAM station. To do so, start the
Master System COM PROFIBUS program and load the file (.PB5) in which you have
saved the data of your master system.
Click with the left mouse button on the icon for the CP 5613
component. The FMS Station Parameters dialog box is opened.
Select Object properties... via the context menu.

DIGSIKOM001b.gif

Fig. 7-58 FMS Station parameter

Enter a PROFIBUS FMS address and click OK.

430 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Saving and Save the master system under the same name and location as the
Exporting a Master original file and export it as an NCM database.
System

7.7.1.10 Checking or Changing Variable Addresses and Lengths

The variables Variable 1 and Variable 2 which contain the information


are required to exchange data via a PROFIBUS FMS network. The
Master Ready variable which has a predefined value is used as soon as
the PROFIBUS FMS interface for data exchange is ready.
Proceed as follows in order to check these variables:
Open your device and double-click in the function view on Interfaces.
Change in the Interface Settings dialog box the PROFIBUS FMS on
the PC tab.

DIGSIKOM064a

Fig. 7-59 Interface Settings, PROFIBUS FMC on the PC tab

Note:
You should normally not change the variables. The specifications for the
Length must agree with the specifications for the device.

SIPROTEC 4 System Description 431


E50417-H1176-C151-A5
Communication

q The values in the Write index box are addresses for write access to
the variables Variable 1, Variable 2 and Master ready.
q The values in the Read index box are addresses for read access to
the variables Variable 1 and Variable 2.
q The values in the Length box specify the length of the variables
Variable 1 and Variable 2. They must agree with the corresponding
values in the PROFIBUS FMS on the device tab.

Parameters for the Change to the PROFIBUS FMS on the device tab.
Device Interface

DIGSIKOM061

Fig. 7-60 Interface Settings, PROFIBUS FMC on the device tab

q The values in the Length variable 1 box specifies the length of the
Variable 1 variable. It must agree with the corresponding value in the
PROFIBUS FMS on the PC tab.
q The values in the Length variable 2 box specifies the length of the
Variable 2 variable. It must agree with the corresponding value in the
PROFIBUS FMS on the PC tab.

Note:
You should normally not change the variables.

432 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.1.11 Establishing a Connection via PROFIBUS FMS

Proceed as follows in order to establish a connection via PROFIBUS


FMS:
In the DIGSI 4 project view select a SIPROTEC 4 device or a
SIPROTEC 4 variant and click on Device > Open in the context
menu.

digsikom049a.tif

Fig. 7-61 Opening a device

Select the option Online via PROFIBUS FMS and click OK.

SIPROTEC 4 System Description 433


E50417-H1176-C151-A5
Communication

7.7.1.12 Closing a Connection via PROFIBUS FMS

Existing PROFIBUS FMS connections can be closed manually or time-


controlled.

Close a SIPROTEC Select File Close in order to close the SIPROTEC device. The
4 Device connection via PROFIBUS FMS is closed automatically.
Respond to the confirmation box.
If several device windows are open, the operations described refer to the
active device window.

Terminating Device Quit the Device Editor in DIGSI 4 by means of File Exit. All the
Editing devices are closed and any existing connection via PROFIBUS FMS
is closed automatically. Respond to the confirmation boxes of the
individual devices.

434 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.2 PROFIBUS FMS V6.1 with SIMATIC NET Software 11/2002 + SP1

Caution:
Configurations which were created with an earlier program version from
SIMATIC NET are NOT compatible.

Operations Proceed as follows in order to establish and configure communication


between the PC and device via a PROFIBUS FMS:
Install the hardware.
Install the software (SIMATIC NET software 11/2002 or 07/2001,
STEP 7 (full version), DIGSI)

Note:
On the installation CD, you will find the following versions
V6.1 CD 11/2002 + SP1 (for Windows XP and Windows 2000)
V6.0 CD 07/2001 + SP5 + HF2 (not to be used for DIGSI 4.50).

Configure the PC station.


Create a project.
Insert SIPROTEC devices.
Configure the PROFIBUS network.
Load the configuration data to the CP5613.
Establish a connection via PROFIBUS FMS.
Close the connection via PROFIBUS FMS.
Diagnosis options for problems with the connection establishment

7.7.2.1 Installing Hardware

In order to implement communication via PROFIBUS FMS you require


the CP 5613 communications processor interface card for your
computer. For information on installing the card as well as on the physical
connection to the PROFIBUS FMS network please refer to the
documentation on the CP 5613 communication processor.

SIPROTEC 4 System Description 435


E50417-H1176-C151-A5
Communication

7.7.2.2 Installing SIMATIC NET V6.1, STEP 7 (full version) and DIGSI

Install the software components. Please refer to the installation


information in the documentation of the respective software package and
Chapter 7.7.1.2.
Observe the following notes:

Note:
For STEP 7, you must install the NCM components for PROFIBUS as
well.
For SIMATIC NET V6.1, you may only install the SIMATIC NET PC
software.
DIGSI can be installed before SIMATIC NET V6.1.

Caution:
For SICAM customers: Simultaneous use of DIGSI and Recpro on a
single PC is possible, but you have to parameterize the DIGSI
connection manually.

436 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.2.3 Configuring the PC Station

To configure the PC station, proceed as follows:


Select SIMATIC NET Settings Set PC Station. The
Configuration Console is started.
Select in the Tree tab theCP5613/CP5614 module, and then select
General.

DIGSIKOM138.tif

Fig. 7-62 Configuration Console "Set PC Station"

Select the Configured Mode entry under Mode of the module.


Click Apply.

SIPROTEC 4 System Description 437


E50417-H1176-C151-A5
Communication

Start the Station Configuration Editor. The CP5613 communication


processor is already entered.

DIGSIKOM139.gif

Fig. 7-63 Station Configuration Editor

Click Station Name... to issue a name to the station:

DIGSIKOM140.gif

Fig. 7-64 Issuing a station name

Click OK to save the name.

438 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Click Add... in the Station Configuration Editor to configure DIGSI


as an application.

DIGSIKOM141.tif

Fig. 7-65 Adding a component

Click OK and then exit the Station Configuration Editor with OK as


well.

SIPROTEC 4 System Description 439


E50417-H1176-C151-A5
Communication

7.7.2.4 Creating a Project

To create a project in SIMATIC Manager, proceed as follows:


Start the SIMATIC Manager.
Select the menu item File New and issue a name for the new
project.

Inserting a PC Select the menu item Insert Station SIMATIC PC Station to


Station insert a PC station in the project.
Select Object properties from the conext menu and issue the same
name for the PC station as in the Station Configuration Editor.

DIGSIKOM142.gif

Fig. 7-66 Properties - SIMATIC PC Station

Close the Properties - SIMATIC PC Station dialog box with OK.


Open the PC station by double-clicking the object.
Open the Configuration entry by double-clicking the object.

440 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Adding a Add the CP card via Drag & Drop from the Hardware Catalog of the
Communication PC station.
Processor

DIGSIKOM061

Fig. 7-67 SIMATIC Manager, HW Config - SIMATIC_PC_Station

Select Object properties from the context menu of the CP5613 and
set the interface type PROFIBUS in the General tab.

SIPROTEC 4 System Description 441


E50417-H1176-C151-A5
Communication

DIGSIKOM144.gif

Fig. 7-68 Properties - CP 5613

Click Properties.
Set the subnet and the address of the module in the Properties -
PROFIBUS interface CP5613 dialog box.

DIGSIKOM145.gif

Fig. 7-69 Properties - PROFIBUS interface CP5613

Click Properties.

442 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Set the transmission rate and profile in the Properties - PROFIBUS


dialog box, on the Network Settings tab.

DIGSIKOM146.gif

Fig. 7-70 Properties - PROFIBUS, Network Settings tab

Close the Properties - PROFIBUS dialog box with OK.


Close the Properties - PROFIBUS interface CP5613 dialog box with
OK.
Change to the Operating Mode tab in the Properties - CP5613
dialog box.

SIPROTEC 4 System Description 443


E50417-H1176-C151-A5
Communication

DIGSIKOM147.tif

Fig. 7-71 Properties - CP5613, Operating Mode tab


Change to the Options tab in the Properties - CP5613 dialog box.

DIGSIKOM147_2.tif

Fig. 7-72 Properties - CP5613, Options tab


Select the Time-of-Day Synchronization, Master option, if you want
to use the PC time to synchronize the devices connected to the
PROFIBUS net. Click OK to close the dialog.

444 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Adding an Add a user application via Drag & Drop from the Hardware Catalog
Application of the PC station.

DIGSIKOM148.gif

Fig. 7-73 SIMATIC Manager, HW Config - SIMATIC_PC_Station: Adding a user application

Note:
The name of the application must be identical to the one which you
issued in the Station Configuration Editor. The names will be the same
when you perform an XDB import.

Note:
Assign this name to the CP5613 in the dialog Object
properties Operating Mode.

Select Object properties from the context menu of the application


and click Edit VFDs in the FMS tab.
Click New to set up a new VFD (Virtual Field Device).

SIPROTEC 4 System Description 445


E50417-H1176-C151-A5
Communication

DIGSIKOM149.gif

Fig. 7-74 Edit VFD

Note:
From DIGSI 4.5 the VFD address is assigned via Options Configure
DIGSI 4, PROFIBUS FMS tab (see Figure 7-75). The name applies
globally and must be identical with the name assigned in Figure 7-74.

DIGSIKOM149_2.tif

Fig. 7-75 Configuring DIGSI 4

446 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Close the Edit VFD dialog box with OK.


Close the object properties with OK.
Select the menu item Station Save and Convert to save your
changes.
Close the hardware configuration.

Making Sure that Select the Configuration tab in Object properties of the PC station.
the Application
Name is Identical

DIGSIKOM149_3.tif

Fig. 7-76 Properties - SIMATIC PC Station, Configuration tab

Save your configuration file in the XDBs directory of your project by


clicking OK.
Open the PC station in the Station Configuration Editor (see Figure
7-63) and click Import XDB to adjust the settings.

Note:
Importing an XDB file changes the operating mode of the Station
Configuration Editor to OFFLINE.

SIPROTEC 4 System Description 447


E50417-H1176-C151-A5
Communication

7.7.2.5 Inserting SIPROTEC Devices

To insert your SIPROTEC devices, proceed as follows:


Select the menu item Insert New Object SIPROTEC Device and
insert the desired device into your project via Drag & Drop from the
device catalog.
Select Object properties from the context menu of the device and
click New in the PROFIBUS FMS tab.
Select a subnet in the Properties - PROFIBUS interface dialog box.
The next available address on this network is entered in the Address
field.

DIGSIKOM150.gif

Fig. 7-77 Properties - PROFIBUS interface

Close the Properties - PROFIBUS interface dialog box with OK.

448 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

Select the FMS / IEC setting tab in Properties and set the
communication reference.

DIGSIKOM058a.gif

Fig. 7-78 Properties - SIPROTEC 4 device, FMS / IEC setting tab

SIPROTEC 4 System Description 449


E50417-H1176-C151-A5
Communication

7.7.2.6 Configuring PROFIBUS Network

To configure your PROFIBUS network, proceed as follows:


Select the menu item Options Configure Network. The NetPro
application is started. It contains the configured PC station and the
SIPROTEC devices.

DIGSIKOM061

Fig. 7-79 NetPro with configured components

Click Application in the SIMATIC_PC_STATION. A table for


configuring the SIPROTEC devices is inserted.

450 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

DIGSIKOM152.gif

Fig. 7-80 NetPro with a table for configuring the SIPROTEC devices

Right-click the first empty field in the Local ID column and select
Insert new connection. The Insert New Connection dialog box
appears.

SIPROTEC 4 System Description 451


E50417-H1176-C151-A5
Communication

DIGSIKOM153.tif

Fig. 7-81 Inserting a new connection

Select the SIPROTEC device under Connection Partner, select the


entry FMS connection under Connection and activate the option
Display properties dialog.
Click Apply. The Properties - FMS Connection dialog box appears.

452 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

DIGSIKOM154.gif

Fig. 7-82 Properties - FMS connection

Record the value of the CREF number and set the value
SIPROTEC4_CR2 (LSAP24) under Conn. profile.
Click OK.
Repeat this procedure for all SIPROTEC devices which are
connected to the PROFIBUS network.

Note:
For a new project, the communication reference (CREF) always starts
with "3". This number must be identical to the number assigned to the
SIPROTEC device (see Object properties of the SIPROTEC device in
the Communication parameter tab). The communication reference is
unique for each device.

SIPROTEC 4 System Description 453


E50417-H1176-C151-A5
Communication

DIGSIKOM155.gif

Fig. 7-83 NetPro with configured SIPROTEC devices

Select the menu item Network Save and Convert to save your
changes.
Select Convert and check everything in the next dialog box and
click OK.

454 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.2.7 Loading Configuration Data

To load the configuration data to the PLC CP5613, proceed as follows:

Caution:
This actions requires the operating mode ONLINE.

Start the Station Configuration Editor.


Click the button Change Operating Mode (only available in the
OFFLINE operating mode) and answer the following query with Yes.
The operating mode changes to ONLINE.

DIGSIKOM155_2.tif

Fig. 7-84 Station Configuration Editor - Operating mode ONLINE

Change to the NetPro application.


Click on the icon of the SIMATIC PC station.
Select the menu item PLC Download to current
project Selected stations.

SIPROTEC 4 System Description 455


E50417-H1176-C151-A5
Communication

Answer the following query with Yes if you want to download the new
data to your communication processor.

DIGSIKOM156.tif

Fig. 7-85 Confirmation query which appears when loading


the configuration data

Close the NetPro application.

7.7.2.8 Check Settings

You should check the following values once again to make sure that they
are set properly:
q Object properties of the devices
- CREF number
- VD name
- Access point
q Set the PG/PC interface (see Chapter 7.7.1.7)
- Access point of the application
- Interface parameterizing used

456 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

DIGSIKOM157.gif

Fig. 7-86 Properties - FMS connection

SIPROTEC 4 System Description 457


E50417-H1176-C151-A5
Communication

7.7.2.9 Establishing a Connection via PROFIBUS FMS

Proceed as follows in order to establish a connection via PROFIBUS


FMS:
In the DIGSI 4 project view select a SIPROTEC 4 device or a
SIPROTEC 4 variant and click on Device > Open in the context
menu.

digsikom049a.tif

Fig. 7-87 Opening a device

Select the option Online via PROFIBUS FMS and click OK.

458 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.2.10 Closing a Connection via PROFIBUS FMS

Existing PROFIBUS FMS connections can be closed manually or time-


controlled.

Closing a Select File Close in order to close the SIPROTEC device. The
SIPROTEC 4 Device connection via PROFIBUS FMS is closed automatically.
Respond to the confirmation box.
If several device windows are open, the operations described refer to the
active device window.

Terminating Device Quit the Device Editor in DIGSI 4 by means of File Exit. All the
Editing devices are closed and any existing connection via PROFIBUS FMS
is closed automatically. Respond to the confirmation boxes of the
individual devices.

SIPROTEC 4 System Description 459


E50417-H1176-C151-A5
Communication

7.7.2.11 Diagnosis Options

Check the following points if problems occur with the connection


establishment:

Bus Connector The connector attached to the CP5613 must be actively terminated, just
like the connector of the last device on the bus.

Configuration Information on the possible error sources is available in the Configuration


Console Console:
- Bus Statistics
Here you can see whether your CP5613 is connected to the ring and
whether certain errors have occurred.

DIGSIKOM158.tif

Fig. 7-88 Configuration Console, Bus Statistics

460 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

- Bus Node
Your CP5613 must be active; all other bus nodes may only be
marked as passive.

DIGSIKOM159.gif

Fig. 7-89 Configuration Console, Bus Node

Wrong Access If your configuration data cannot be downloaded to the communication


Point for S7ONLINE processor, check the access point S7ONLINE in the Configuration
Console:

DIGSIKOM160.gif

Fig. 7-90 Configuration Console, Access Points

If this entry is not set to PC internal (local), double-click the entry.


Set the access point to this value in the Properties of S7Online and
close the dialog with OK.

SIPROTEC 4 System Description 461


E50417-H1176-C151-A5
Communication

DIGSIKOM049

Fig. 7-91 Properties of S7Online

462 SIPROTEC 4 System Description


E50417-H1176-C151-A5
PROFIBUS FMS

7.7.3 Procedure with SIMATIC NET NCM PC Edition

If you do not have a SIMATIC STEP 7 full version, proceed as follows:

Note:
The configuration is almost identical to the procedure described in
Chapter 7.7.2 so that a detailed description of the software is not
necessary.

Prerequisites You need two PCs.

Installation Install only the NCM component (SIMATIC NCM PC V5.2) of


SIMATIC NET on PC 1.
Install DIGSI and the PROFIBUS card (and its drivers) on PC 2.

Configuration on Configure, with the help of the NCM components on PC 1, the PC station
PC 1 with the communication processor and application (see also Chapter
7.7.2):
Select SIMATIC NCM PC MANAGER from the Start menu.
Select Insert Station 1 SIMATIC PC Station to create the PC
station.
Open the Configuration.
Configure the communication processor CP5613.
Create a user application. Assign the name in Properties of the
application; note that the VFD number must be "1" in the FMS tab (see
Figure 7-74).
Assign the application in Properties of the communication processor
to the CP5613.
Select Save + Convert to close the configuration.
Select Options Configure Network to start the application
NetPro.
Assign the name of the XDB export file in Properties of the PC station
(see Figure 7-76).
Adding devices:
Select Other station in the right area under Stations and place it on
your network chart via Drag & Drop.
Assign its name (e.g. SIPROTEC + FMS number + communication
reference) in Properties of the station in the General tab.
Click New in the Interfaces tab under Properties of the station and
select PROFIBUS as the type of connection. Click OK.
Select a subnet in the Properties - PROFIBUS interface dialog box
(see Figure 7-77) and assign the device address. Click OK.

SIPROTEC 4 System Description 463


E50417-H1176-C151-A5
Communication

Click on the area Application in the object of the PC Station.


Insert a new connection. To this purpose select the device and FMS
Connection as the type of connection. Click Apply.
Change to the properties of the FMS Connection and select the
station and connection profile (see Figure 7-82). Click OK.
Repeat this procedure for all SIPROTEC devices which are to be
connected to the PROFIBUS FMS network.
Select Network Save and Convert and confirm the confirmation
query with OK.
Start the Windows Explorer and change to the XDBs directory of your
project (e.g. Programs\Siemens\
SIMATIC.NCM\S7PROJ\Project\XDBs) and copy the XDB file to a
disk.

Configuration on Create a project in DIGSI 4 and add the necessary SIPROTEC


PC 2 devices.
Check under Options Configure DIGSI 4 the data in the
PROFIBUS FMS tab (see Figure 7-77).
Check the PROFIBUS address and communication reference (CR)
from the properties of the devices (see Figure 7-50).
Import the XDB configuration file on PC 2 in the Station
Configuration Editor (see Page 447).

Termination You can establish the connection to your SIPROTEC devices now.

464 SIPROTEC 4 System Description


E50417-H1176-C151-A5
Supplementary Protocols

7.8 Supplementary Protocols

SIPROTEC 4 devices as from system firmware Version 4.2 also allow


communication on the basis of
q PROFIBUS DP,
q DNP 3.0 and
q MODBUS.
In DIGSI 4 these protocols are called Other protocols.

Note:
These protocols can only be used for communication between the
SIPROTEC device and a control center. Communication between
DIGSI 4 and a SIPROTEC 4 device on the basis of one of the three
aforementioned protocols is not possible.

Operations Proceed as follows in order to establish and configure the communication


via these Other protocols:
Specify the interface in DIGSI 4.
Select the mapping file and edit it.
Configure the information.
Initialize your SIPROTEC 4 device.

SIPROTEC 4 System Description 465


E50417-H1176-C151-A5