7.7.1 PROFIBUS FMS With SIMATIC NET Software 05/2000 + SP2
7.7.1 PROFIBUS FMS With SIMATIC NET Software 05/2000 + SP2
Install the driver for the CP 5613 communication processor and the COM
PROFIBUS program for configuring communication via PROFIBUS
FMS.
Proceed as follows:
Place the SIMATIC NET Software (05/2000 + SP2) CD in the CD-
ROM drive of your PC and start the setup.exe file.
Click Install SIMATIC NET Software and follow the instructions of
the installation program.
Select PB FMS-5613 V2.1 in the SIMATIC NET Setup:
Components dialog box and click Next.
DIGSIKOM074a.gif
Note:
If you would like to use the communication processor CP 5613 together
with SIMATIC NET Software (05/2000 + SP2), you have to install a hotfix
from a disk. To this purpose please contact your A&D sales
representative.
Installing Drivers in During installation of the SIMATIC NET software, the drivers for the CP
the System 5613 communications processor are copied onto the hard drive of the
PC. Install this driver in the system so that you can access the CP 5613
communication processor.
Click in the Windows start menu on Settings Control Panel.
Double-click in the Control Panel Window on the PG/PC interface
icon.
The Setting the PG/PC Interface dialog box is opened.
DIGSIKOM014a.gif
Click Select.
The Install / Remove Interfaces dialog box is opened.
DIGISKOM075a.gif
Select the entry CP5613/CP5614 in the Select box and click Install.
In the subsequent dialog box, select the model name of the installed
communications processor.
Click OK.
The drivers are installed. The resources assigned by Windows are
displayed in an indication box after installation has been completed
successfully.
Click Close in the Install / Remove Interfaces dialog box.
A query appears regarding the changed settings. However, as further
settings still need to be entered, it doesn't make much sense to restart
the system at this point.
For this reason, click Cancel.
Click OK in the Setting the PG/PC interface dialog box. The dialog
box closes.
DIGSIKOM001a.gif
Specifying the Bus Select a PROFIBUS address and the station name in the FMS
Address and master parameters dialog box. Please select only even addresses
Station Name (in this case "2").
DIGSIKOM001b.gif
DIGSIKOM004a.gif
DIGSIKOM001b.gif
Note:
Make a note of the PROFIBUS address. You require it in order to set the
communication parameters in DIGSI 4 (see Chapter 7.7.1.8 and
Chapter 7.7.1.9).
DIGSIKOM010a.gif
Click New.
DIGSIKOM010b.gif
Note:
Make a note of the value for the communication reference. You require
this value in order to set the communication parameters in DIGSI 4 (see
Chapter 7.7.1.8 and Chapter 7.7.1.9).
Create the required SIPROTEC 4 FMS slaves for all the devices in the
PROFIBUS FMS network.
DIGSIKOM012a.gif
Enter a name with the extension PB5 in the File name box. Select the
drive and directory and click OK.
The settings are saved.
The configured settings must exist as an NCM database in order for the
CP 5613 communications processor to process them. You must
therefore export the settings as an NCM database.
Proceed as follows:
Use File Export NCM File to open the Save As dialog box.
DIGSIKOM013
Enter a name with the extension ldb in the File name box. Observe
the DOS conventions. Select the drive and directory and click Save.
The settings are saved as an NCM database.
Transfer the configured data of the master system to the NCM database
in the CP 5613 communications processor.
Proceed as follows:
Click in the Windows start menu on Settings Control Panel.
Double-click in the Control Panel Window on the PG/PC interface
icon.
The Setting the PG/PC Interface dialog box is opened.
DIGSIKOM014b.gif
DIGSIKOM015a.gif
Activating FMS Activate the Activate FMS check box. The Activate DP check box
may not be selected.
In the FMS/DP Database input box enter the name of the NCM file
including the complete path designation directly or search for the file
by using the Search command button in the Select Database dialog
box.
Resetting and Change to the Mode tab and click the Restart command button. This
Restarting resets the CP and restarts it.
The course of the processes is displayed in the lower section of the
dialog box.
DIGSIKOM018a.gif
Click OK. Also click OK in the Setting the PG/PC interface dialog
box.
DIGSIKOM058a.gif
DIGSIKOM019a
Add Connection Click New and change to the Parameters tab in the Properties -
PROFIBUS interface dialog box. The names and transmission rates
of all the PROFIBUS FMS subnetworks available are displayed.
DIGSIKOM020a
DIGSIKOM021a
Click OK.
Select the PROFIBUS FMS address which you specified when
configuring the master system for the device in the Address field of
the Properties - PROFIBUS Node dialog box.
Confirm by clicking OK.
Click OK in the FMS / IEC setting tab of the Properties - SIPROTEC
4 device dialog box in order to accept the displayed connections.
Inserting PG/PC Now insert an object of the type PG/PC in your project in order to
integrate DIGSI 4 in the project structure.
Proceed as follows:
Select your project and click Insert Station
7 PG/PC.
Assign the name DIGSI PC to the inserted object and open the
Properties - PG/PC dialog box via the Object Properties context
menu.
Change to the Interfaces tab.
DIGSIKOM024a
Click New.
The New Interface - Select Type dialog box is opened.
DIGSIKOM027a
Select the PROFIBUS setting in the select box and click OK.
DIGSIKOM026a
Displaying the Display the current network configuration in order to check it.
Network
Double-click the PROFIBUS object.
Configuration
DIGSIKOM028
Fig. 7-57 Example of the network configuration with SICAM Station and DIGSI PC
Updating the Extend the master system by a SICAM station. To do so, start the
Master System COM PROFIBUS program and load the file (.PB5) in which you have
saved the data of your master system.
Click with the left mouse button on the icon for the CP 5613
component. The FMS Station Parameters dialog box is opened.
Select Object properties... via the context menu.
DIGSIKOM001b.gif
Saving and Save the master system under the same name and location as the
Exporting a Master original file and export it as an NCM database.
System
DIGSIKOM064a
Note:
You should normally not change the variables. The specifications for the
Length must agree with the specifications for the device.
q The values in the Write index box are addresses for write access to
the variables Variable 1, Variable 2 and Master ready.
q The values in the Read index box are addresses for read access to
the variables Variable 1 and Variable 2.
q The values in the Length box specify the length of the variables
Variable 1 and Variable 2. They must agree with the corresponding
values in the PROFIBUS FMS on the device tab.
Parameters for the Change to the PROFIBUS FMS on the device tab.
Device Interface
DIGSIKOM061
q The values in the Length variable 1 box specifies the length of the
Variable 1 variable. It must agree with the corresponding value in the
PROFIBUS FMS on the PC tab.
q The values in the Length variable 2 box specifies the length of the
Variable 2 variable. It must agree with the corresponding value in the
PROFIBUS FMS on the PC tab.
Note:
You should normally not change the variables.
digsikom049a.tif
Select the option Online via PROFIBUS FMS and click OK.
Close a SIPROTEC Select File Close in order to close the SIPROTEC device. The
4 Device connection via PROFIBUS FMS is closed automatically.
Respond to the confirmation box.
If several device windows are open, the operations described refer to the
active device window.
Terminating Device Quit the Device Editor in DIGSI 4 by means of File Exit. All the
Editing devices are closed and any existing connection via PROFIBUS FMS
is closed automatically. Respond to the confirmation boxes of the
individual devices.
7.7.2 PROFIBUS FMS V6.1 with SIMATIC NET Software 11/2002 + SP1
Caution:
Configurations which were created with an earlier program version from
SIMATIC NET are NOT compatible.
Note:
On the installation CD, you will find the following versions
V6.1 CD 11/2002 + SP1 (for Windows XP and Windows 2000)
V6.0 CD 07/2001 + SP5 + HF2 (not to be used for DIGSI 4.50).
7.7.2.2 Installing SIMATIC NET V6.1, STEP 7 (full version) and DIGSI
Note:
For STEP 7, you must install the NCM components for PROFIBUS as
well.
For SIMATIC NET V6.1, you may only install the SIMATIC NET PC
software.
DIGSI can be installed before SIMATIC NET V6.1.
Caution:
For SICAM customers: Simultaneous use of DIGSI and Recpro on a
single PC is possible, but you have to parameterize the DIGSI
connection manually.
DIGSIKOM138.tif
DIGSIKOM139.gif
DIGSIKOM140.gif
DIGSIKOM141.tif
DIGSIKOM142.gif
Adding a Add the CP card via Drag & Drop from the Hardware Catalog of the
Communication PC station.
Processor
DIGSIKOM061
Select Object properties from the context menu of the CP5613 and
set the interface type PROFIBUS in the General tab.
DIGSIKOM144.gif
Click Properties.
Set the subnet and the address of the module in the Properties -
PROFIBUS interface CP5613 dialog box.
DIGSIKOM145.gif
Click Properties.
DIGSIKOM146.gif
DIGSIKOM147.tif
DIGSIKOM147_2.tif
Adding an Add a user application via Drag & Drop from the Hardware Catalog
Application of the PC station.
DIGSIKOM148.gif
Note:
The name of the application must be identical to the one which you
issued in the Station Configuration Editor. The names will be the same
when you perform an XDB import.
Note:
Assign this name to the CP5613 in the dialog Object
properties Operating Mode.
DIGSIKOM149.gif
Note:
From DIGSI 4.5 the VFD address is assigned via Options Configure
DIGSI 4, PROFIBUS FMS tab (see Figure 7-75). The name applies
globally and must be identical with the name assigned in Figure 7-74.
DIGSIKOM149_2.tif
Making Sure that Select the Configuration tab in Object properties of the PC station.
the Application
Name is Identical
DIGSIKOM149_3.tif
Note:
Importing an XDB file changes the operating mode of the Station
Configuration Editor to OFFLINE.
DIGSIKOM150.gif
Select the FMS / IEC setting tab in Properties and set the
communication reference.
DIGSIKOM058a.gif
DIGSIKOM061
DIGSIKOM152.gif
Fig. 7-80 NetPro with a table for configuring the SIPROTEC devices
Right-click the first empty field in the Local ID column and select
Insert new connection. The Insert New Connection dialog box
appears.
DIGSIKOM153.tif
DIGSIKOM154.gif
Record the value of the CREF number and set the value
SIPROTEC4_CR2 (LSAP24) under Conn. profile.
Click OK.
Repeat this procedure for all SIPROTEC devices which are
connected to the PROFIBUS network.
Note:
For a new project, the communication reference (CREF) always starts
with "3". This number must be identical to the number assigned to the
SIPROTEC device (see Object properties of the SIPROTEC device in
the Communication parameter tab). The communication reference is
unique for each device.
DIGSIKOM155.gif
Select the menu item Network Save and Convert to save your
changes.
Select Convert and check everything in the next dialog box and
click OK.
Caution:
This actions requires the operating mode ONLINE.
DIGSIKOM155_2.tif
Answer the following query with Yes if you want to download the new
data to your communication processor.
DIGSIKOM156.tif
You should check the following values once again to make sure that they
are set properly:
q Object properties of the devices
- CREF number
- VD name
- Access point
q Set the PG/PC interface (see Chapter 7.7.1.7)
- Access point of the application
- Interface parameterizing used
DIGSIKOM157.gif
digsikom049a.tif
Select the option Online via PROFIBUS FMS and click OK.
Closing a Select File Close in order to close the SIPROTEC device. The
SIPROTEC 4 Device connection via PROFIBUS FMS is closed automatically.
Respond to the confirmation box.
If several device windows are open, the operations described refer to the
active device window.
Terminating Device Quit the Device Editor in DIGSI 4 by means of File Exit. All the
Editing devices are closed and any existing connection via PROFIBUS FMS
is closed automatically. Respond to the confirmation boxes of the
individual devices.
Bus Connector The connector attached to the CP5613 must be actively terminated, just
like the connector of the last device on the bus.
DIGSIKOM158.tif
- Bus Node
Your CP5613 must be active; all other bus nodes may only be
marked as passive.
DIGSIKOM159.gif
DIGSIKOM160.gif
DIGSIKOM049
Note:
The configuration is almost identical to the procedure described in
Chapter 7.7.2 so that a detailed description of the software is not
necessary.
Configuration on Configure, with the help of the NCM components on PC 1, the PC station
PC 1 with the communication processor and application (see also Chapter
7.7.2):
Select SIMATIC NCM PC MANAGER from the Start menu.
Select Insert Station 1 SIMATIC PC Station to create the PC
station.
Open the Configuration.
Configure the communication processor CP5613.
Create a user application. Assign the name in Properties of the
application; note that the VFD number must be "1" in the FMS tab (see
Figure 7-74).
Assign the application in Properties of the communication processor
to the CP5613.
Select Save + Convert to close the configuration.
Select Options Configure Network to start the application
NetPro.
Assign the name of the XDB export file in Properties of the PC station
(see Figure 7-76).
Adding devices:
Select Other station in the right area under Stations and place it on
your network chart via Drag & Drop.
Assign its name (e.g. SIPROTEC + FMS number + communication
reference) in Properties of the station in the General tab.
Click New in the Interfaces tab under Properties of the station and
select PROFIBUS as the type of connection. Click OK.
Select a subnet in the Properties - PROFIBUS interface dialog box
(see Figure 7-77) and assign the device address. Click OK.
Termination You can establish the connection to your SIPROTEC devices now.
Note:
These protocols can only be used for communication between the
SIPROTEC device and a control center. Communication between
DIGSI 4 and a SIPROTEC 4 device on the basis of one of the three
aforementioned protocols is not possible.