c2
c2
c2
2.1 Introduction
There are many devices such as three-phase ac generator, transformer etc., which
are usually used in a power station to generate and supply electrical power to a
power system network. In the power station, the three-phase ac generator generates
a three-phase alternating voltage in the range between 11 and 20 kV. The magni-
tude of the generated voltage is increased to 120 kV or more by means of a power
transformer. This higher magnitude of voltage is then transmitted to the grid sub-
station by a three-phase transmission lines. A lower line voltage of 415 V is
achieved by stepping down either from the 11 or 33 kV lines by a distribution
transformer. In these cases, a three-phase transformer is used in either to step-up or
step-down the voltage. Since a transformer plays a vital role in feeding an electrical
network with the required voltage, it becomes an important requirement of a power
system engineer to understand the fundamental details about a transformer along
with its analytical behavior in the circuit domain. This chapter is dedicated towards
this goal. On the onset of this discussion it is worth mentioning that a transformer,
irrespective of its type, contains the following characteristics (i) it has no moving
parts, (ii) no electrical connection between the primary and secondary windings,
(iii) windings are magnetically coupled, (iv) rugged and durable in construction,
(v) efciency is very high i.e., more than 95 %, and (vi) frequency is unchanged.
Figure 2.1 shows a schematic diagram of a single-phase transformer. There are two
types of windings in a single-phase transformer. These are called primary and
secondary windings or coils. The primary winding is connected to the alternating
voltage source and the secondary winding is connected to the load. The primary and
secondary winding parameters are represented by the sufx p or 1 and s or 2,
respectively. A sinusoidal current flows in the primary winding when it is con-
nected to an alternating voltage source. This current establish a flux u which moves
from the primary winding to the secondary winding through low reluctance mag-
netic core.
About 95 % of this flux moves from the primary to the secondary through the
low reluctance path of the magnetic core and this flux is linked by the both
windings and a small percent of this flux links to the primary winding. According to
the Faradays laws of electromagnetic induction, a voltage will be induced across the
secondary winding as well as in the primary winding. Due to this voltage, a current
will flow through the load if it is connected with the secondary winding. Hence, the
primary voltage is transferred to the secondary winding without a change in
frequency.
The current in the primary winding establishes a flux. The flux that moves from
primary to secondary and links both the windings is called the mutual flux and its
maximum value is represented by /m .
Flux which links only the primary winding and completes the magnetic path
through the surrounding air is known primary leakage flux. The primary leakage
flux is denoted by /1l . Similarly, secondary leakage flux is that flux which links
only the secondary winding and completes the magnetic path through the sur-
rounding air. The secondary leakage flux is denoted by /2l . Mutual and leakage
fluxes are shown in Fig. 2.2.
2.4 Ideal Transformer 51
m I2
I1
+ N2 +
N1 E2
V1 V2 ZL
E1
2l
1l
An ideal transformer is one which does not supply any energy to the load i.e., the
secondary winding is open circuited. The main points of an ideal transformer are
(i) no winding resistance, (ii) no leakage flux and leakage inductance,
(iii) self-inductance and mutual inductance are zero, (iv) no losses due to resistance,
inductance, hysteresis or eddy current and (v) coefcient of coupling is unity.
Figure 2.3a shows an ideal transformer where the secondary winding is left
open. A small magnetizing current Im will flow in the primary winding when it is
connected to the alternating voltage source, V1 . This magnetizing current lags
behind the supply voltage, V1 by 90 and produces the flux u, which induces the
primary and secondary emfs. These emfs lag behind the flux, u by 90. The
magnitude of primary induced emf E1 and supply voltage V1 is the same, but are
180 out of phase as shown in Fig. 2.3b.
(a) m
I1
+ +
V1 E1 E2 N2 V2
N1
(b) V2
V1
E2 E1 90
I m = I1
/ /m sin xt 2:1
d/
e1 N1 2:2
dt
d/
e2 N2 2:3
dt
d
e1 N1 / sin xt 2:4
dt m
e1 N1 x/m cos xt 2:5
Em1
E1 p 2:8
2
N1 2pf /m
E1 p 2:9
2
E1 4:44 f /m N1 2:10
2.5 E.M.F. Equation of Transformer 53
The primary and secondary voltages can be determined from Eqs. (2.10) and (2.11)
if other parameters are known.
I1 1
2:19
I2 a
Again, the magnetomotive force produced by the primary current will be equal to
the magnetomotive force produced by the secondary current and it can be expressed
as,
= =1 =2 0 2:20
N1 I1 N2 I2 2:21
I1 N2 1
2:22
I2 N1 a
From Eq. (2.22), it is concluded that the ratio of primary to secondary current is
inversely proportional to the turns ratio of the transformer.
The input and output power of an ideal transformer is,
For an ideal condition, the angle /1 is equal to the angle /2 and the output power
can be re-arranged as,
V1
Pout aI1 cos /1 2:25
a
Pout V1 I1 cos /1 Pin 2:26
From Eq. (2.26), it is seen that the input and the output power are the same in case
of an ideal transformer. Similarly, the input and output reactive powers are,
From Eqs. (2.26) and (2.27), the input and output power and reactive power can be
calculated if other parameters are given.
Example 2.1 The number of turns in the secondary coil of a 22 kVA, 2200 V/220 V
single-phase transformer is 50. Find the (i) number of primary turns, (ii) primary
full load current, and (iii) secondary full load current. Neglect all kinds of losses in
the transformer.
2.6 Turns Ratio of Transformer 55
Solution
The value of the turns ratio is,
V1 2200
a 10
V2 220
N1
a
N2
N1 aN2 10 50 500
22 103
I1 10 A
2200
22 103
I2 100 A
220
Example 2.2 A 25 kVA single-phase transformer has the primary and secondary
number of turns of 200 and 400, respectively. The transformer is connected to a
220 V, 50 Hz source. Calculate the (i) turns ratio, and (ii) mutual flux in the core.
Solution
N1 200
a 0:5
N2 400
V1 E1 4:44 f /m N1
V1 220
/m 4:95 mWb
4:44 fN1 4:44 50 200
V1
I1
V2 a2 2:31
I2
Z1
a2 2:32
Z2
Alternative approach: The impedances in the primary and secondary windings are,
V1
Z1 2:33
I1
V2
Z2 2:34
I2
Z1 V1 I2
2:36
Z2 V2 I1
Z1
aa 2:37
Z2
Z1
a2 2:38
Z2
From Eq. (2.38), it can be concluded that the impedance ratio is equal to the square
of the turns ratio. The important points for transferring parameters are (i) R1 in the
primary becomes Ra21 when referred to the secondary, (ii) R2 in the secondary
becomes a2 R2 when referred to the primary, (iii) X1 in the primary becomes Xa21 when
referred to the secondary, and (iv) X2 in the secondary becomes a2 X2 when referred
to the primary.
Example 2.3 The number of primary and secondary turns of a single-phase
transformer are 300 and 30, respectively. The secondary coil is connected with a
load impedance of 4 X. Calculate the (i) turns ratio, (ii) load impedance referred to
the primary, and (iii) primary current if the primary coil voltage is 220 V.
Solution
N1 300
a 10
N2 30
V1 220
I1 0:55 A
ZL0 400
Windings of a transformer are not connected electrically. The windings are mag-
netically coupled with each other. In this case, it is tedious to do proper analysis.
Therefore, for easy computation and visualization, the practical transformer needs
to be converted into an equivalent circuit by maintaining same properties of the
main transformer. In the equivalent circuit, the related parameters need to be
transferred either from the primary to the secondary or vice versa. A two windings
ideal transformer is shown in Fig. 2.4.
Figure 2.5 shows an exact equivalent circuit referred to the primary where all the
parameters are transferred from the secondary to the primary and these parameters
are,
I1 R1 X1 R2 X2 I2
I0 N1 N2
+
Iw +
Im V2 ZL
V1 R0 X0 E2
E1
I0
+
Iw +
Im V2 ' ZL '
V1 R0 X0
R02 a2 R2 2:39
X20 a2 X2 2:40
ZL0 a2 ZL 2:41
I2
I20 2:42
a
Figure 2.6 shows the exact equivalent circuit referred to the secondary where all the
parameters are transferred from the primary to the secondary.
These parameters are,
R1
R01 2:44
a2
X1
X10 2:45
a2
V1
V10 2:47
a
I0 '
+
Iw ' +
Im ' V2 ZL
V1 ' R0 ' X0 '
The no-load current is very small as compared to the rated primary current.
Therefore, there is a negligible voltage drop due to R1 and X1 . In this condition, it
can be assumed that the voltage drop across the no-load circuit is the same as the
applied voltage without any signicant error. The approximate equivalent circuit
can be drawn by shifting the no-load circuit across the supply voltage, V1 .
Figure 2.7 shows an approximate equivalent circuit referred to the primary. The
total resistance, reactance and impedance referred to the primary are,
V1
R0 2:54
Iw
V1
X0 2:55
Im
R1
R02 R2 R01 R2 2:56
a2
I1 I2 ' R01 X 01
I0
+
Iw +
Im V2 ' ZL '
V1 R0 X0
I1 ' I2 R02 X 02
I0 '
+
Iw ' +
Im ' V2 ZL
V1 ' R0 ' X0 '
X1
X02 X2 X10 X2 2:57
a2
Z02 R02 jX02 2:58
The no-load circuit resistance and reactance referred to the secondary are,
V10
R00 2:59
Iw0
V10
X00 2:60
Im0
Example 2.4 A 2.5 kVA, 200 V/40 V single-phase transformer has the primary
resistance and reactance of 3 and 12 , respectively. On the secondary side, these
values are 0.3 and 0.1 , respectively. Find the equivalent impedance referred to
the primary and the secondary.
Solution
The value of the turns ratio is,
V1 200
a 5
V2 40
The total resistance, reactance and impedance referred to the primary can be
determined as,
The total resistance, reactance and impedance referred to the secondary are cal-
culated as,
R1 3
R02 R2 0:3 0:42 X
a2 25
X1 12
X02 X2 2 0:1 0:58 X
p 25
a
Z01 0:422 0:582 0:72 X
The relative directions of induced voltages between the high voltage and low
voltage terminals is known as the polarity of a transformer. The polarity of a
transformer is very important to construct three-phase transformer bank, parallel
connection of transformer, connection of current transformer (CT) and potential
transformer (PT) power with metering device. Two polarities namely additive and
subtractive are used in the transformer.
A polarity of a transformer is said to be an additive if the measured voltage
between the high voltage and the low voltage terminals is greater than the supply
voltage at the high voltage terminals. The additive polarity of a transformer is
marked by the orientation of dots as shown in Fig. 2.9. Whereas, a polarity is said to
be a subtractive if the measured voltage between the high voltage and the low
voltage terminals is lower than the supply voltage at the high voltage terminals. The
H1
X1
VH1 H 2
H2
X2
2.9 Polarity of a Transformer 63
H1
X1
VH1H 2
H2
X2
V1 220
a 2
V2 110
For safety issue, a lower voltage needs to be applied to the primary side i.e., high
voltage terminals. Suppose, a voltage of 110 V is applied to the primary side. In this
case, a voltage of 55 V (110/2) will appear at the secondary terminals. If the meter
read out the voltage of 165 V (110 + 55) then the transformer is said to be in
additive polarity. This connection is shown in Fig. 2.11.
Whereas, if the voltmeter reads the voltage of 55 V (110 55) then the trans-
former is said to be in subtractive polarity as shown in Fig. 2.12.
H2
X2
165 V
64 2 Transformer: Principles and Practices
H1
X1
VH1H 2
110 V 55 V
H2
X2
V
55 V
A1 B1 C1
N11 N 21 N 31
N12 N 22
N 32
a1 b1 c1
N11 N12 N 21 N 22
N 31 N 32
The most common congurations of a three-phase transformer are the delta and star
congurations, which are used in the power utility company. The primary and
secondary windings of a three-phase transformer are connected either in the same
(delta-delta or star-star), or different (delta-star or star-delta) conguration-pair. The
secondary voltage waveforms of a three-phase transformer are in phase with the
primary waveforms when the primary and secondary windings are connected in the
same conguration. This condition is known as no phase shift condition. If the
primary and secondary windings are connected in different conguration pair then
the secondary voltage waveforms will differ from the corresponding primary
66 2 Transformer: Principles and Practices
A A
a
N n N n
180 shift +30 lead
a
C Y/y/0
C2
c
c2
A1 A2 a1 a2
C1 c1 a
B1 A b1
b b2
B2
B
A1 A2 A a1 a2 a
B1 B2 b1 b2
N B n b
C1 C2 c1 c2
C c
C C2 D/d/0
B1
c c2
b1
C1
A c1
a
A2 a2
b2
B2 b a1
B A1
A1 A2 A a1 a2 a
B1 B2 b1 b2
B b
C1 C2 c1 c2
C c
C C2 D/z/0
c2
B1 a2
a4
c4 c1 a1
C1
A c3 b3 a3
A2 b1
B2 c4
B A1 c b2 b4
c3
b1
a2 b2
a
c2 a4
a1
b3 c1 a3
b4
b
A1 A2 A a1 a2 a3 a4 a
B1 B2 b1 b2 b3 b4
B b
n
C1 C2 c1 c2 c3 c4
C c
B2
B
A1 A2 A a1 a2 a
B1 B2 b1 b2
N B b
C1 C2 c1 c2
C c
2.11 Transformer Vector Group 69
D/y/1
C
A2 c c2
C1
A1 c1
b1
A a1 30
B2 a
b2 a2
b
C2
B B1
A1 A2 A a1 a2 a
B1 B2 b1 b2
B n b
C1 C2 c1 c2
C c
C
C2 Y/z/1 c
c4
c3 c2
C1
A c1 a
B1 b1
A1 A2
a1 a2 a3 a4
b2
c4 b3
B2 c
B b4
c3
b
b1
a1 a2 b2
b3
c2
b4 c1 a
a3 a4
b
A1 A2 A a1 a2 a3 a4 a
B1 B2 b1 b2 b3 b4
N B b
n
C1 C2 c1 c2 c3 c4
C c
b2
b
B2
B A1
A1 A2 A a1 a2 a
B1 B2 b1 b2
B n b
C1 C2 c1 c2
C c
B2
B
A1 A2 A a1 a2 a
B1 B2 b1 b2
N B b
C1 C2 c1 c2
C c
2.11 Transformer Vector Group 71
C
C2 Y/z/11
c4
c3 c2
C1
A c1
B1 b1
A1 A2
a1 a2 a3 a4
b2
B2 b3
B a3 a4 b4
c b1 a
c4
b2
c3 c2
a1 a2
c1
b3
b b4
A1 A2 A a1 a2 a3 a4 a
B1 B2 b1 b2 b3 b4
N B b
n
C1 C2 c1 c2 c3 c4
C c
C1 a1 a2
B1 A a b
A1 A2 c2 2
B2 c1 c
B a
A1 A2 A a1 a2
b
N B1 B2 b1 b2 n
B
c
C1 C2 c1 c2
C
72 2 Transformer: Principles and Practices
C C2 a1 b
C C2 D/d/6 b2
b B1
A1 A2 b1 a2
B1 A
C1 C1 a
a1 a2 A c1
b
a c2 2 A2
B2 b1
B c2 c
B2
c1 c A1
B
A1 A2 A a1 a2
a
B1 B2 b1 b2
B b
C1 C2 c1 c2
C c
C
C2 D/z/6
B1
c c4 a4
C1 a
c3 c2 a3
A
A2 c1 a2
b1 a1
B2 b
A1 b3 b2
B
b3
a4 c2
b4
a3 c1 a2 b4
a a1 b
b1
b2
c4
c3 c
a
A1 A2 a1 a2 a3 a4
A
B1 B2 b2
n b1 b3 b4
B b
C1 C2 c1 c2 c3 c4
C
c
Different types of loads like domestic, commercial and industrial are usually con-
nected with the secondary winding of a transformer. All these loads are operated
with a constant magnitude of voltage. The secondary voltage of a transformer under
operation changes due to voltage drop across the internal impedance and the load.
The voltage regulation of a transformer is used to identify the characteristic of the
secondary side voltage changes under different loading conditions. The voltage
regulation of a transformer is dened as the difference between the no-load terminal
voltage (V2NL ) to full load terminal voltage (V2FL ) and is expressed as a percentage
of full load terminal voltage. It is therefore can be expressed as,
V2NL V2FL E2 V2
Voltage regulation 100 % 100 % 2:61
V2FL V2
Figure 2.29b shows the phasor diagram for a lagging power factor, and from this
diagram, the following expressions can be written,
AC V2 cos /2 2:63
BC DE V2 sin /2 2:64
CD BE I2 R02 2:65
EF I2 X02 2:66
(a) E2 U (b)
E2
I 2 X 02 F
I 2 Z 02
Z
X I2 V2 Y I 2 R02 V2 I 2 X 02
(c) 2 B
Q A
I 2 R02
P I2
E2 E
R C
I 2 X 02 D
O
I2
I 2 R02
2
M V2 N
From the right angle triangle-ADF, the expression of E2 can be derived as,
AF 2 AD2 DF 2 2:67
Figure 2.29c shows the phasor diagram for a leading power factor and from this
diagram, the following expressions can be written,
MR V2 cos /2 2:71
RN OQ V2 sin /2 2:72
RQ NO I2 R02 2:73
2.12 Voltage Regulation of a Transformer 75
PO I2 X02 2:74
The expression of E2 from the right angled triangle MQP can be derived as,
Example 2.5 The primary coil resistance and reactance of a 200/400 V single-phase
transformer are 0.3 and 0:6 X, respectively. The secondary coil resistance and
reactance are 0.8 and 1:6 X, respectively. Calculate the voltage regulation if the
secondary current of the transformer is 10 A at a 0.8 pf lagging.
Solution
The value of the turns ratio is,
V1 200
a 0:5
V2 400
R1 0:3
R02 R2 0:8 2X
a2 0:25
X1 0:6
X02 X2 1:6 4X
a2 0:25
E2 V2
Voltage regulation 100 %
V2
440:5 400
Voltage regulation 100 % 10 %
400
Practice problem 2.5
A 110/220 V single-phase transformer has the resistance of 0:2 X and a reactance of
0:8 X in the primary winding. The resistance and reactance in the secondary
winding are 0.9 and 1:8 X, respectively. Calculate the voltage regulation, when the
secondary current is 6 A at a 0.85 power factor leading.
Pout Plosses
g 1 2:80
Pin Pin
It is worth nothing that the efciency of a transformer is generally higher than other
electrical machines because the transformer has no moving parts.
The iron loss of a transformer is often called as core loss, which is a result of an
alternating flux in the core of the transformer. The iron loss consists of the eddy
current loss and the hysteresis loss. In the transformer, most of the flux transferred
from the primary coil to the secondary coil through low reluctance iron path. A few
2.14 Iron and Copper Losses 77
portion of that alternating flux links with the iron parts of the transformer. As a
result, an emf is induced in the transformer core. A current will flow in that parts of
the transformer. This current does not contribute in output of the transformer but
dissipated as heat. This current is known as eddy current and the power loss due to
this current is known as eddy current loss. The eddy current loss Pe is directly
proportional to the square of the frequency (f) times the maximum magnetic flux
density Bm and the eddy current loss can be expressed as,
Pe ke f 2 B2m 2:81
Ph kh fB2:6
m 2:82
Pe / f 2 2:83
Ph / f 2:84
Practically, hysteresis loss depends on the voltage and the eddy current loss
depends on the current. Therefore, total losses of the transformer depend on the
voltage and the current not on the power factor. That is why the transformer rating
is always represented in kVA instead of kW.
In the transformer, copper losses occur due to the primary and the secondary
resistances. The full load copper losses can be determined as,
output output
g 2:90
input output losses
Substituting Eqs. (2.87), (2.88) and (2.89) into Eq. (2.90) yields,
V2 I2 cos /2
g 2:91
V2 I2 cos /2 Piron Pcu
V2 cos /2
g I22 R02
2:92
V2 cos /2 Piron
I2 I2
Piron
R02 0 2:94
I22
r
Piron
I2 2:96
R02
Multiplying both sides of Eq. (2.98) by the secondary rated voltage V2 yields,
s
Piron
V2 I2g V 2 I2 2 2:99
I2 R02
s
iron loss
VImax efficiency VIrated 2:100
full load copper loss
Example 2.6 A 30 kVA transformer has the iron loss and full load copper loss of
350 and 650 W, respectively. Determine the (i) full load efciency, (ii) output kVA
corresponding to maximum efciency, and (iii) maximum efciency. Consider that
the power factor of the load is 0.6 lagging.
Solution
Pout 30 0:6 18 kW
Pin 18 1 19 kW
80 2 Transformer: Principles and Practices
18
g 100 94:74 %
19
13:2
g 100 94:96 %
13:9
The equivalent circuit parameters are very important to characterize the perfor-
mance of transformer. The parameters of a transformer equivalent circuit can be
determined by the open circuit and the short circuit tests.
2.16 Transformer Tests 81
The main objectives of the open circuit test are to determine the no-load current and
iron loss. The components of the no-load current are used to determine the no-load
circuit resistance and reactance.
In an open circuit test, the secondary side is considered to be open circuit, and the
primary coil is connected to the source as shown in Fig. 2.30a, where all measuring
instruments are connected in the primary side. A specic alternating voltage is
applied to the primary winding. Then the wattmeter will measure the iron loss and
small amount of copper loss. The ammeter and voltmeter will measure the no-load
current and the voltage, respectively. Since, the no-load current is very small, the
copper losses can be neglected. Then the wattmeter reading can be expressed as,
P0 V1 I0 cos /0 2:101
From Eq. (2.101), the no-load power factor can be determined as,
P0
cos /0 2:102
V1 I0
The working and magnetizing components of the current can be determined as,
Iw I0 cos /0 2:103
Im I0 sin /0 2:104
Then the no-load circuit resistance and reactance can be determined as,
V1
R0 2:105
Iw
V1
X0 2:106
Im
(a) (b)
I0
A
N1 N2
Iw
+ +
Im
V1 V V1 R 0 X0
Fig. 2.30 Connection diagrams for open circuit test and no-load circuit
82 2 Transformer: Principles and Practices
P0 80
cos /0 0:67
V1 I0 200 0:6
sin /0 0:74
The values of the working and magnetizing components of the no-load current are,
V1 200
R0 500 X
Iw 0:4
V1 200
X0 454:5 X
Im 0:44
The main objectives of the short circuit test are to determine the equivalent resis-
tance, reactance, impedance and full load copper loss. In this test, the supply
voltage and the measuring instruments (e. g,. wattmeter, ammeter) are connected to
the primary side and the secondary winding is shorted out by a wire as shown in
Fig. 2.31, or connected with an ammeter. The primary voltage is adjusted until the
current in the short-circuited winding is equal to the rated primary current. Under
this condition, the wattmeter will measure the full load copper loss and it can be
written as,
From Eq. (2.107), the short circuit power factor can be calculated as,
Psc
cos /sc 2:108
Isc Vsc
2.16 Transformer Tests 83
A
N1 N2
+ +
V Isc
V1 Vsc
Vsc
Z01 Zeq 2:109
Isc
V1 40
Z01 8X
I1 5
P 150
R01 2 6X
I1 25
6
/ cos1 41:4
8
X01 Z01 sin / 8 sin 41:4 5:2 X
84 2 Transformer: Principles and Practices
V1 2200
a 10
V2 220
Z01 8
Z02 0:08 X
a2 100
R01 6
R02 2 0:06 X
a 100
X01 5:2
X02 2 0:052 X
a 100
25;000
I2 113:6 A
220
E2 V2 229 220
VR 4%
V2 220
2.17 Autotransformer
A small rating transformer with a variable voltage output is usually used in the
educational laboratory as well as in the testing laboratory. This type of small rating
transformer with a variable output is known as autotransformer. An autotransformer
has one continuous winding that is common to both the primary and the secondary.
Therefore, in an autotransformer, the primary and secondary windings are con-
nected electrically. The advantages of an autotransformer over a two-winding
transformer include lower initial investment, lower leakage reactance, lower losses
compared to conventional transformer and lower excitation current.
An autotransformer with primary and secondary windings is shown in Fig. 2.32.
In this connection, the sufx c indicates the common winding and the sufx
s indicates the series winding. From Fig. 2.32, the following equations can be
written as,
Ns Ic
a 2:112
Nc Is
Vs Ns
a 2:113
Vc Nc
V1
1 a 2:115
Vc
VL 1
2:116
V1 1 a
Where the voltage at the load is equal to the voltage at the common terminals i.e.,
VL Vc .
The expression of the load current can be written as,
IL Is Ic aIs Is 2:117
IL 1 aIs 2:118
IL
1 a 2:119
Is
120;000
Ipq 545:5 A
220
120;000
Iqr 54:5 A
2200
Fig. 2.33 An p
autotransformer with a
specic voltage I pq +
I1
2420 V
q
+
-
2200 V
Iqr
- r
2.17 Autotransformer 87
Fig. 2.34 An p
autotransformer with a
specic voltage I pq
+
I1
q 1320 V
+
1100 V -
Iqr
- r
600 2200
kVA1 1320 kVA
1000
545:5 2420
kVA2 1320 kVA
1000
Practice problem 2.9
A single-phase 100 kVA, 1100/220 V, 50 Hz transformer is connected as an
autotransformer as shown in Fig. 2.34. The voltages of the upper and lower parts of
the coil are 220 and 1100 V, respectively. Determine the kVA rating of the
autotransformer.
Nowadays, the demand of load is increasing with the increase in population and
industrial sector. Sometimes, it is difcult to meet the excess demand of power by
the existing single unit transformer. Therefore, an additional transformer is required
to connect in parallel with the existing one. The following points should be con-
sidered for making parallel connections of transformers:
Terminal voltage of both transformers must be the same.
Polarity must be same for both transformers.
For both transformers, the percentage impedances should be equal in magnitude.
Ratio of R to X must be the same for both transformers.
Phase sequences and phase shifts must be the same (for three-phase
transformer).
88 2 Transformer: Principles and Practices
The primary and secondary windings of the transformer may be connected in either
by wye (Y) or delta (D). Three-phase transformer connections are classied into
four possible types; namely, Y-Y(wye-wye), Y-D (wye-delta), D-Y(delta-wye) and
D-D (delta-delta).
Figure 2.35 shows the Y-Y connection diagram. This type of connection of a
three-phase transformer is rarely used for large amount of power transmission.
Neutral point is necessary for both primary and secondary sides in some cases. In
balanced loads, this type of connection works satisfactorily and provides neutral to
each side for grounding. At the primary side, the phase voltage can be written as,
VL1
VP1 p 2:120
3
VL2
VP2 p 2:121
3
The ratio of the primary line voltage to the secondary line voltage of this connection
is,
VL1
a 2:122
VL2
p
3VP1 VP1
a p 2:123
3VP2 VP2
b
a
c a Secondary b c n
2.19 Three-Phase Transformer Connections 89
The wye-delta connection is mainly used at the substation where the voltage is
stepped down. In this connection, the current in the secondary coil is 57.7 % of the
load current. At the primary side of this connection, a proper copper wire is used to
ground the neutral point. Figure 2.36 shows the connection diagram of the
wye-delta transformer. In this connection, the expression of the primary line voltage
is,
p
VL1 3VP1 2:124
VP1
a 2:126
VP2
IP2
a 2:129
IP1
A
C
b
a c
Secondary a c
b
90 2 Transformer: Principles and Practices
The delta-wye connection is generally used at the power generating station to step
the voltage. Figure 2.37 shows the connection diagram of a delta-wye transformer.
In this connection, the expression of the primary line voltage is,
VL1 VP1 a
p p 2:134
VL2 3VP2 3
1
IP1 p IL1 2:135
3
a
c
Secondary a b c
n
2.19 Three-Phase Transformer Connections 91
IP2
a 2:136
IP1
The delta-delta connection is generally used for both high voltage and low voltage
rating transformers where insulation is not an important issue. The connection
diagram for delta-delta transformer is shown in Fig. 2.38. In this case, the primary
line voltage is,
VL1 VP1 2:139
VL1 VP1
a 2:141
VL2 VP2
A
C
Primary
a c
Secondary
a b c
92 2 Transformer: Principles and Practices
The remaining two transformers are able to supply three-phase power to the load
terminal if one of the transformer is removed from the connection. This type of
three-phase power supply by two transformers is known as open delta or V-V
connection. This open delta connection is able to supply three-phase power at a
reduced rate of 57.7 %. The connection diagram for open delta connection is shown
in Fig. 2.39.
In the V-V connection, the secondary line current is,
The ratio of delta-delta output capacity to the V-V output capacity is,
p
P0VV 3VL2 IP2
0:577 2:147
P0DD 3VL2 IP2
A
C
Primary
b
a c
Secondary
a b c
2.19 Three-Phase Transformer Connections 93
VP1 VL1 11 kV
VP1 11;000
VP2 1000 V
a 11
IL1 11
IP1 p p 6:35 A
3 3
Wye-delta connection:
The line voltage at the primary side is,
VL1 11 kV
VL1 11;000
VP1 p p 6350:85 V
3 3
94 2 Transformer: Principles and Practices
VP1 6350:85
VP2 577:35 V
a 11
IP2 aIP1 11 6 66 A
The magnitude of the voltage and the current are normally high in the power system
networks. To reduce the magnitude of the voltage and current, instrument trans-
formers are used. There are two types of instrument transformers; namely, current
transformer (CT) and potential transformer (PT) . If a power system carries an
alternating current greater than 100 A, then it is difcult to connect measuring
instruments like low range ammeter, wattmeter, energy meter and relay.
The current transformer is then connected in series with the line to step down the
high magnitude of the current to a rated value of about 5 A for the ammeter and the
current coil of the wattmeter. The diagram of a current transformer is shown in
Fig. 2.40. If the system voltage exceeds 500 V, then it is difcult to connect
measuring instruments directly to the high voltage. The potential transformer is then
used to step down to a suitable value of the voltage at the secondary for supplying
the voltmeter and the voltage coil of the wattmeter. The secondary of the instrument
transformer is normally grounded for safety reason. The connection diagram of a
potential transformer is shown in Fig. 2.41.
2.20 Instrument Transformers 95
Exercise Problems
2:9 The number of turns at the primary and secondary coils of a single-phase
transformer are found to be 480 and 60, respectively. The transformer draws
a current of 0.6 A when connected to 120 V supply. Determine the current
and the voltage at the secondary coil.
2:10 The turns ratio of a 5 kVA single-phase transformer is found to be 2. The
transformer is connected to a 230 V, 50 Hz supply. If the secondary current
of a transformer is 6 A, then nd the primary current and secondary voltage.
2:11 The secondary number of turns of a 30 kVA, 4400/440 V single-phase
transformer is found to be 100. Find the number of primary turns, full load
primary and secondary currents.
2:12 A 5 kVA, 1100/230 V, 50 Hz single-phase transformer is installed near the
domestic area of a country. Find the turns ratio, primary and secondary full
load currents.
2:13 The number of turns of the primary winding of a single-phase 50 Hz
transformer is found to be 50. Find the value of the core flux, if the induced
voltage at this winding is 220 V.
2:14 The number of primary turns of a 60 Hz single-phase transformer is found to
be 500. Calculate the induced voltage in this winding, if the value of the core
flux is 0.05 Wb.
2:15 The maximum flux of a 3300/330 V, 50 Hz step-down single-phase trans-
former is found to be 0.45 Wb. Calculate the number of primary and sec-
ondary turns.
2:16 The cross sectional area of a 5 kVA, 2200/220 V, 50 Hz single-phase
step-down transformer is found to be 25 cm2 and a maximum flux density is
4 Wb/m2. Calculate the primary and secondary turns.
2:17 The number of turns at the primary and secondary of an ideal single-phase
transformer are found to be 500 and 250, respectively. The primary of the
transformer is connected to a 220 V, 50 Hz source. The secondary coil
supplies a current of 5 A to the load. Determine the (i) turns ratio, (ii) current
in the primary and (iii) maximum flux in the core.
2:18 The primary number of turns of a 4 kVA, 1100/230 V, 50 Hz single-phase
transformer is 500. The cross sectional area of the transformer core is 85 cm2.
Find the (i) turns ratio, (ii) number of turns in the secondary and (iii) maxi-
mum flux density in the core.
2:19 The primary and secondary turns of a single-phase transformer are 50 and
500, respectively. The primary winding is connected to a 220 V, 50 Hz
supply. Find the (i) flux density in the core if the cross sectional area is
250 cm2 and (ii) induced voltage at the secondary winding.
2:20 The primary coil number of turns of a single-phase 2200/220 V, 50 Hz
transformer is found to be 1000. Find the area of the core if the maximum
flux density of the core is 1.5 Wb/m2.
2:21 The maximum flux of a single-phase 1100/220 V, 50 Hz transformer is found
to be 5 mWb. The number of turns and the voltage at the primary winding
are found to be 900 and 1100 V, respectively. Determine the frequency of the
supply system.
Exercise Problems 97
2:35 The iron loss and full load copper loss of a 40 kVA transformer are found to
be 450 and 750 W, respectively. Calculate the (i) full load efciency,
(ii) output kVA corresponding to maximum efciency, and (iii) maximum
efciency. Consider the power factor of the load is 0.95 lagging.
2:36 The iron loss of a 40 kVA transformer is 50 % of the full load copper loss.
The full load copper loss is found to be 850 W. Calculate the (i) full load
efciency, (ii) output kVA corresponding to maximum efciency, and
(iii) maximum efciency. Assume the power factor of the load is 0.9 lagging.
2:37 The iron loss and full load copper loss of a 25 kVA transformer are found to
be 300 and 550 W, respectively. Find the (i) full load efciency, (ii) output
kVA corresponding to maximum efciency, and (iii) maximum efciency.
Assume the power factor of the load is 0.6 lagging.
2:38 The primary and secondary windings parameters of a 100 kVA, 2200/220 V
transformer are R1 0:6 X, X1 0:9 X, R2 0:007 X, X2 0:008 X. The
transformer is operating at a maximum efciency of 75 % of its rated load
with 0.9 lagging power factor. Calculate the (i) efciency of transformer at
full load, and (ii) maximum efciency, if the iron loss is 350 W.
2:39 A 200 kVA, 2400/240 V transformer has the primary and windings
parameters R1 20 X, X1 27 X, R2 0:18 X, X2 0:26 X. The trans-
former is operating at a maximum efciency of 80 % of its rated load with
0.8 pf lagging. Calculate the (i) efciency of the transformer at full load, and
(ii) maximum efciency if the iron loss is 400 W.
2:40 The low voltage side of a 30 kVA, 2400/220 V, 50 Hz single-phase trans-
former is short circuited. The test data recorded from the high voltage side
are 200 W, 6 A and 45 V. Find the (i) equivalent resistance, reactance and
impedance referred to the primary, (ii) equivalent resistance, reactance and
impedance referred to the secondary, and (iii) voltage regulation at 0.6 power
factor lagging.
2:41 The low voltage winding of a 25 kVA, 1100/220 V, 50 Hz single-phase
transformer is short circuited. The test data recorded from the high voltage
side are 156 W, 4 A and 50 V. Calculate the (i) equivalent resistance,
reactance and impedance referred to the primary, (ii) equivalent resistance,
reactance and impedance referred to the secondary, and (iii) voltage regu-
lation at 0.85 power factor leading.
2:42 The test data of a 10 kVA, 440/220 V, 50 Hz single-phase transformer are as
follows:
Open circuit test: 220 V, 1.4 A, 155 W;
Short circuit test: 20.5 V, 15 A, 145 W;
Calculate the approximate equivalent circuit parameters.
2:43 The open circuit test data of a single-phase transformer are recorded as the
220 V, 1.2 A and 145 W. Find the no-load circuit parameters.
Exercise Problems 99
Fig. P2.1 An p
autotransformer with a I pq
specic voltage +
I1
q 1320 V
+
1100 V
I qr
r
References
1. T. Wildi, Electrical Machines, Drives and Power Systems, 6th edn. (Pearson Education
International, Upper Saddle River, 2006)
2. M.A. Salam, Fundamentals of Electrical Machines, 2nd edn. (Alpha Science, International Ltd.,
Oxford, 2012)
3. S.J. Chapman, Electric Machinery and Power System Fundamentals (McGraw-Hill Higher
Education, New York, 2002)
4. A.E. Fitzgerald, C. Kingsley Jr., S.D. Umans, Electric Machinery, 6th edn (McGraw-Hill
Higher Education, New York, 2003)
http://www.springer.com/978-981-10-0444-5