MD32-TM: Percentage Biased Transformer Differential Relay
MD32-TM: Percentage Biased Transformer Differential Relay
MD32-TM: Percentage Biased Transformer Differential Relay
DIFFERENTIAL RELAY
87
MD32-TM m Three-phase percentage biased differential relay
for two-winding transformers.
dA>
PROG/
I.R.F.
dB>
2H>
dC>
5H> BLOCK
INPUT
MULTIFUNCTION
m Programmable percentage bias curve. TRANSFORMER
DIFFERENTIAL
_
M
ENTER/RESET
LINE
Three-phase percentage biased differential protection relay for 2 winding transformers or 3 winding with
only one source of supply.
The relay measures the incoming currents and operates the CT ratio and Power Transformer vector
group compensation without the need of using interposing CTs.
MS-SCE2080-R0
1/5
MD32-TM M N80-R0
Time during which harmonic restraint level can be lowered at transformer energisation: tH = (0.05 - 90)s, step 0.01s
2nd Harmonic restraint level reduction during tH : R2H = (0.5 - 1)2H, step 0.01
5th Harmonic restraint level reduction during tH : R5H = (0.5 - 1)5H, step 0.01
Digital Inputs
B1 = Operation block input
D Id I1 + I2
R % = 100 IR =
D IR 2
Is/In 4
18 Is Id
=
In In
3
2
DlR Dld Is Id I R%
DlR
= + ( R - 0,5)
In In In 100
R
1 1 2
Dld Is Id 2R% IR
ld/In
= +
In In 100
+ ( - 2,5)
In
d> IR/In
0
0,5 1 2 2,5 3 Is
Is= Effective relays operation differential current In
@ 18
Id= Relay set differential current = [d>]
IR= Relays through current
2/5
MD32-TM M N80-R0
PROTECTION
DEGREE IP44
(IP54 on request)
164
135
134
2 195
213
PANEL CUT-OUT
115x137 (LxH) 225
3/5
MD32-TM M N80-R0
51
135
164
32 + (n x 51) 2 195
213
9 4 + (n x 51) 225
PROTECTION
DEGREE IP44
(IP54 on request)
PANEL CUT-OUT
(11+(n x 51)) x 137 (LxH)
51
133
57
7
10.5 206
75+(n+51) 232
42+(n+51)
4/5
ELECTRICAL CHARACTERISTICS MD32-TM M N80-R0
APPROVAL : CE
REFERENCE STANDARDS IEC 60255 - CE Directive - EN/IEC61000 - IEEE C37 - BSI
Dielectric test voltage IEC 60255-5 2kV, 50/60Hz, 1 min.
Impulse test voltage IEC 60255-5 5kV (c.m.), 2 kV (d.m.) - 1,2/50ms
Insulation resistance >100 M
HF disturbance test with damped oscillatory wave IEC60255-22-1 class 3 400pps, 2.5kV (m.c.), 1kV (d.m.)
(1MHz burst test)
Typical Characteristics
Accuracy at reference value of influencing factors 2% In for measurement
2% +/- 10ms for times
Rated Current In = 1 or 5A
5/5