Axially Loaded Columns - Steel

The document summarizes the design of a UC section for use as a column in the Marymount Centre chapel building. Key details of the UC section are provided, including dimensions, material properties, and calculations of section properties. Analysis shows the section is classified as semi-compact in both the flange and web. Effective length calculations for different end conditions are presented. The compressive resistance of the section is then calculated along the two axes and found to exceed the required axial load of 65 kN, indicating the section is adequate for the application.

Uploaded by

hary9100
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
88 views2 pages

Axially Loaded Columns - Steel

The document summarizes the design of a UC section for use as a column in the Marymount Centre chapel building. Key details of the UC section are provided, including dimensions, material properties, and calculations of section properties. Analysis shows the section is classified as semi-compact in both the flange and web. Effective length calculations for different end conditions are presented. The compressive resistance of the section is then calculated along the two axes and found to exceed the required axial load of 65 kN, indicating the section is adequate for the application.

Uploaded by

hary9100
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

PROJECT MARYMOUNT CENTRE - CHAPEL BUILDING

PREPARED BY I. HARI AMUDHAN CHECKED BY Dr.K.MURUGAPPAN DATE


Section details Name = UC - 305x305x118kg/m
Depth,D = 304 mm B = 301mm
Width,B = 301 mm
Flange thk,t = 17 mm
Web thk,tw = 11 mm
b/T ratio = 7.58
d/t = 18 D = 304 mm
Section Area,A = 159 cm tw = 11 mm
Ixx = 23380 cm4
Iyy = 7733 cm4
rxx = 13.3 cm
ryy = 7.57 cm
Steel strength,Py = 275 N/mm
Section classification
Axial Load,Pu = 65 kN
Strength,py = 265 N/mm Factor r2 = 0.015427
= 1.0186932
Flange Class = SEMI-COMPACT
Web class = SEMI-COMPACT
SEMI COMPACT
Calculations END CONDITIONS INDEX
Column Length,L = 5 m FIX,FIX =
End conditions = 2 PIN,PIN =
Effective length,Le = 7.5 m PARTIALLY FIXED =
Slenderness, xx = 56.390977 @ BOTH ENDS
yy = 99.075297 CANTILEVER =
Type of col. Section = H ( "I" or "H")
Type of curve
along xx-axis = b
along yy-axis = c LINEAR INTERPOLATION TABLE
Compressive strength based on the type of the curve xx pcx yy
along xx-axis, pcx = 220.58647 N/mm 56 220 98
along yy-axis, pcy = 127.61295 N/mm 58 217 100
Compressive resistance of the column section
Along X-X axis = 3507.3248 kN
Along Y-Y axis = 2029.0458 kN

THE SECTION IS O.K SINCE SECTION CAPACITY>Pu


2/14/2014

tf = 17mm

tw = 11 mm

tf = 17mm

0
1
2

OLATION TABLE
pcy
126
123

Pu