This document provides input data for an air conditioning system called "3F-Canteen C1" in the Nahda School. It includes details on the ventilation system, zone components, sizing data, and equipment specifications. The system has one zone, uses a split DX fan coil unit, and provides cooling to an area called "Zone 1". Ventilation is provided at a rate of 71 liters per second from a common ventilation system. Equipment is sized automatically and uses air-cooled DX cooling sources.

Uploaded by

Kashif Mannan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
272 views178 pages

Air System Inputs

This document provides input data for an air conditioning system called "3F-Canteen C1" in the Nahda School. It includes details on the ventilation system, zone components, sizing data, and equipment specifications. The system has one zone, uses a split DX fan coil unit, and provides cooling to an area called "Zone 1". Ventilation is provided at a rate of 71 liters per second from a common ventilation system. Equipment is sized automatically and uses air-cooled DX cooling sources.

Uploaded by

Kashif Mannan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 178

3F-Canteen C1 Input Data

Project Name: Nahda School 08/20/2017


Prepared by: 12:54AM

1. General Details:
Air System Name ..................................................................... 3F-Canteen C1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Canteen C1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 1 of 178


3F-Canteen C1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 482.9 - - 71.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 2 of 178


3F-Canteen C2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ..................................................................... 3F-Canteen C2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Canteen C2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 3 of 178


3F-Canteen C2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 461.4 - - 68.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 4 of 178


3F-Canteen C3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ..................................................................... 3F-Canteen C3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Canteen C3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 5 of 178


3F-Canteen C3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 500.1 - - 71.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 6 of 178


3F-Canteen C4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ..................................................................... 3F-Canteen C4
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Canteen C4 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 7 of 178


3F-Canteen C4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 445.6 - - 68.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 8 of 178


3F-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ........................................................................ 3F-Corridor 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Corridor 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 9 of 178


3F-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 346.5 - - 15.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.5 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 10 of 178


3F-Corridor 2+ Stair 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name .......................................................... 3F-Corridor 2+ Stair 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Corridor 2+Stair 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 11 of 178


3F-Corridor 2+ Stair 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 659.3 - - 33.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.1 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 15.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 12 of 178


3F-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ........................................................................ 3F-Corridor 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Corridor 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 13 of 178


3F-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 366.5 - - 16.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 14 of 178


3F-Gym Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................................. 3F-Gym
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Gym x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 27.0 C
Cooling T-stat: Unocc. ................................................................................ 30.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 15 of 178


3F-Gym Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 8058.0 - - 1447.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 90.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 214.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 16 of 178


3F-Library Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ............................................................................. 3F-Library
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Library x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 17 of 178


3F-Library Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1467.6 - - 286.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 18.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 32.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 18 of 178


3F-Staff Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ...................................................................... 3F-Staff Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Staff Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 19 of 178


3F-Staff Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 249.7 - - 25.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 20 of 178


3F-Store Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................................ 3F-Store
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Store x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 27.0 C
Cooling T-stat: Unocc. ................................................................................ 35.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 21 of 178


3F-Store Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 223.7 - - 28.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 22 of 178


3F-Store 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ............................................................................. 3F-Store 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Store 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 27.0 C
Cooling T-stat: Unocc. ................................................................................ 35.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 23 of 178


3F-Store 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 324.7 - - 40.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 24 of 178


3F-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ...................................................................... 3F-Supervisor
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
3F-Supervisor x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 25 of 178


3F-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 212.3 - - 23.7

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.5 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 26 of 178


FF-Classroom 20,22 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ............................................................ FF-Classroom 20,22
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 20,22 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 27 of 178


FF-Classroom 20,22 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 710.5 - - 210.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 28 of 178


FF-Classroom 21 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................. FF-Classroom 21
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 21 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 29 of 178


FF-Classroom 21 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 568.1 - - 203.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 30 of 178


FF-Classroom 23,24,26 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................... FF-Classroom 23,24,26
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 23,24,26 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 31 of 178


FF-Classroom 23,24,26 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 563.9 - - 199.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 32 of 178


FF-Classroom 25 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................. FF-Classroom 25
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 25 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 33 of 178


FF-Classroom 25 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 585.8 - - 202.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 34 of 178


FF-Classroom 27-33,35-56 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name .................................................. FF-Classroom 27-33,35-56
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Classroom 27-33,35-56 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 35 of 178


FF-Classroom 27-33,35-56 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 593.1 - - 204.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 11.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 36 of 178


FF-Classroom 34 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................. FF-Classroom 34
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Classroom 34 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 37 of 178


FF-Classroom 34 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 662.7 - - 205.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 12.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 38 of 178


FF-Classroom 57 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ................................................................. FF-Classroom 57
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Class Rooms 57 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 39 of 178


FF-Classroom 57 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 455.0 - - 155.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 9.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 40 of 178


FF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................................... FF-Corridor 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Corridor 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 41 of 178


FF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 670.8 - - 35.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 18.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 42 of 178


FF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................................... FF-Corridor 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Corridor 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 43 of 178


FF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1310.7 - - 95.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 6.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 34.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 44 of 178


FF-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................................... FF-Corridor 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Corridor 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 45 of 178


FF-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1089.9 - - 74.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 28.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 46 of 178


FF-Head of Department Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

1. General Details:
Air System Name ....................................................... FF-Head of Department
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Head of Department x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 47 of 178


FF-Head of Department Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:54AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 376.1 - - 80.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 5.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 48 of 178


FF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ................................................................... FF-Laboratories
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Split Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 49 of 178


FF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 362.9 - - 40.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 50 of 178


FF-Split Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ...................................................................... FF-Split Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Split Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 51 of 178


FF-Split Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 362.9 - - 40.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 52 of 178


FF-Staff Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ...................................................................... FF-Staff Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Staff Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 53 of 178


FF-Staff Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 188.3 - - 23.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 54 of 178


FF-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ...................................................................... FF-Supervisor
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Supervisor x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 55 of 178


FF-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 172.1 - - 21.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 3.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 56 of 178


FF-Supervisor SV7 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name .............................................................. FF-Supervisor SV7
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Supervisor SV7 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 57 of 178


FF-Supervisor SV7 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 265.8 - - 39.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 58 of 178


FF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ............................................................. FF-Teacher's Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
FF-Teacher's Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 59 of 178


FF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 339.6 - - 38.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 60 of 178


GF-Ablution Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name .......................................................................... GF-Ablution
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Ablution x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 61 of 178


GF-Ablution Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.0 - - 19.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 3.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 62 of 178


GF-Book Store Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ..................................................................... GF-Book Store
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Book Store x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 63 of 178


GF-Book Store Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 308.3 - - 66.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 64 of 178


GF-CCC Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ................................................................................ GF-CCC
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-CCC x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 65 of 178


GF-CCC Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 66 of 178


GF-Class Room 1-18 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ........................................................... GF-Class Room 1-18
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Class Rooms 1-18 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 46.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 67 of 178


GF-Class Room 1-18 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 629.2 - - 207.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 68 of 178


GF-Class Room 19 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name .............................................................. GF-Class Room 19
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Class Room 19 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 69 of 178


GF-Class Room 19 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 477.1 - - 155.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 9.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 9.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 70 of 178


GF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 71 of 178


GF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 670.8 - - 35.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 18.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 72 of 178


GF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 73 of 178


GF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 978.0 - - 63.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 25.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 74 of 178


GF-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 75 of 178


GF-Corridor 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 523.7 - - 21.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 14.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 76 of 178


GF-Corridor 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 4
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 4 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 77 of 178


GF-Corridor 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 632.4 - - 31.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 17.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 78 of 178


GF-Corridor 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 5
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 5 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 79 of 178


GF-Corridor 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 405.3 - - 10.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 80 of 178


GF-Corridor 6 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 6
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 6 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 81 of 178


GF-Corridor 6 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 405.3 - - 10.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 82 of 178


GF-Corridor 7 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ....................................................................... GF-Corridor 7
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Corridor 7 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 83 of 178


GF-Corridor 7 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 405.3 - - 10.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 84 of 178


GF-CTM Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ................................................................................ GF-CTM
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-CTM x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 85 of 178


GF-CTM Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 86 of 178


GF-Files Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ..................................................................... GF-Files Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Files Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 87 of 178


GF-Files Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 195.5 - - 16.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 88 of 178


GF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name .................................................................. GF-Laboratories
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Laboratories x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 89 of 178


GF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 626.7 - - 218.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 90 of 178


GF-Library Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

1. General Details:
Air System Name ............................................................................ GF-Library
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Library x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 91 of 178


GF-Library Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:55AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1334.3 - - 275.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 17.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 29.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 92 of 178


GF-Manager Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ......................................................................... GF-Manager
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Manager x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 93 of 178


GF-Manager Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 361.6 - - 35.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 94 of 178


GF-Manager Waiting Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ........................................................... GF-Manager Waiting
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Manager Waiting x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 95 of 178


GF-Manager Waiting Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 96 of 178


GF-Meeting RHS Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name .................................................................. GF-Meeting RHS
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Meeting RHS x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 97 of 178


GF-Meeting RHS Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 223.0 - - 20.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 98 of 178


GF-Mosque Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ........................................................................... GF-Mosque
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Mosque x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 99 of 178 99


GF-Mosque Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1363.0 - - 289.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 18.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 30.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 100 of 178 100


GF-Music Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ................................................................... GF-Music Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Music Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 101 of 178


GF-Music Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 732.7 - - 196.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 16.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 102 of 178


GF-Office RHS NE Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ............................................................... GF-Office RHS NE
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Office-RHS NE x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 103 of 178


GF-Office RHS NE Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 385.1 - - 48.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 3.1 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 104 of 178


GF-Office Small RHS Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ........................................................... GF-Office Small RHS
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Office Small RHS x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 105 of 178


GF-Office Small RHS Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 69.4 - - 7.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 1.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 106 of 178


GF-Pantry Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ............................................................................. GF-Pantry
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Pantry x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 107 of 178


GF-Pantry Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 82.0 - - 6.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 1.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 108 of 178


GF-PM Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ................................................................................... GF-PM
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-PM x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 109 of 178


GF-PM Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 110 of 178


GF-PTC Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ................................................................................. GF-PTC
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-PTC x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 111 of 178


GF-PTC Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 235.2 - - 27.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.0 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 112 of 178


GF-Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ....................................................................... GF-Reception
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Reception x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 113 of 178


GF-Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 674.6 - - 88.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 5.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 16.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 114 of 178


GF-Reception Lower Right Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name ................................................. GF-Reception Lower Right
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Reception Lower RHS x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 115 of 178


GF-Reception Lower Right Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 400.0 - - 69.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 116 of 178


GF-Room Across Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name .............................................. GF-Room Across Reception
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Room Across Reception x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 117 of 178


GF-Room Across Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 266.9 - - 43.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 118 of 178


GF-Security Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

1. General Details:
Air System Name .......................................................................... GF-Security
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Security x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 119 of 178


GF-Security Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:56AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 227.1 - - 16.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 120 of 178


GF-Sm. Room Across Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ....................................... GF-Sm. Room Across Reception
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Sm. Room Across Rec. x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 121 of 178


GF-Sm. Room Across Reception Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 130.8 - - 20.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 122 of 178


GF-Social Councillor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ........................................................... GF-Social Councillor
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Social Councillor x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 123 of 178


GF-Social Councillor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 124 of 178


GF-Split Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Split Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Split Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 125 of 178


GF-Split Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 362.9 - - 40.3

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 126 of 178


GF-Staircase 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 127 of 178


GF-Staircase 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 256.7 - - 10.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 128 of 178


GF-Staircase 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 129 of 178


GF-Staircase 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 328.1 - - 16.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 130 of 178


GF-Staircase 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 131 of 178


GF-Staircase 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 223.0 - - 12.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 132 of 178


GF-Staircase 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 4
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 4 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 133 of 178


GF-Staircase 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 281.7 - - 11.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 134 of 178


GF-Staircase 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Staircase 5
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Staircase 5 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 135 of 178


GF-Staircase 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 342.3 - - 14.7

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.8 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 136 of 178


GF-Student Affairs Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name .............................................................. GF-Student Affairs
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Student Affairs x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 137 of 178


GF-Student Affairs Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 131.7 - - 20.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.3 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 138 of 178


GF-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name ..................................................................... GF-Supervisor
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Supervisor SV1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 139 of 178


GF-Supervisor Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 104.7 - - 17.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.1 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 140 of 178


GF-Supervisor SV1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

1. General Details:
Air System Name .............................................................. GF-Supervisor SV1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Supervisor SV1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 141 of 178


GF-Supervisor SV1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:57AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 104.7 - - 17.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.1 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 2.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 142 of 178


GF-Supervisor SV2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name .............................................................. GF-Supervisor SV2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Supervisor SV2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 143 of 178


GF-Supervisor SV2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 265.8 - - 39.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 5.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 144 of 178


GF-SW Entrance Low Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name .......................................................... GF-SW Entrance Low
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-SW Entrance Lower x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 145 of 178


GF-SW Entrance Low Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 862.4 - - 123.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 7.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 21.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 146 of 178


GF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ............................................................ GF-Teacher's Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Teacher's Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 147 of 178


GF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 339.6 - - 38.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.4 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 7.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 148 of 178


GF-Uniform Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name .......................................................................... GF-Uniform
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
GF-Uniform x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 149 of 178


GF-Uniform Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 194.9 - - 57.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 3.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 4.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 150 of 178


RF-Staircase 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 151 of 178


RF-Staircase 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 285.3 - - 10.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 152 of 178


RF-Staircase 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 153 of 178


RF-Staircase 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 368.6 - - 16.5

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 1.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.5 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 154 of 178


RF-Staircase 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 3
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 3 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 155 of 178


RF-Staircase 3 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 256.7 - - 12.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 156 of 178


RF-Staircase 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 4
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 4 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 157 of 178


RF-Staircase 4 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 308.5 - - 11.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 6.9 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 158 of 178


RF-Staircase 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

1. General Details:
Air System Name ..................................................................... RF-Staircase 5
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
RF-Staircase 5 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 159 of 178


RF-Staircase 5 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:58AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 380.3 - - 14.7

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 0.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.3 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 160 of 178


SF-Classroom 71 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ................................................................. SF-Classroom 71
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Classroom 71 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 161 of 178


SF-Classroom 71 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 662.7 - - 205.8

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.9 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 12.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 162 of 178


SF-Classrooms 58,60 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name .......................................................... SF-Classrooms 58,60
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Class Rooms 58,60 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 163 of 178


SF-Classrooms 58,60 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 710.5 - - 210.6

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.2 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 164 of 178


SF-Classrooms 59 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ............................................................... SF-Classrooms 59
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Class Rooms 59 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 165 of 178


SF-Classrooms 59 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 568.1 - - 203.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.7 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 166 of 178


SF-Classrooms 61,62 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name .......................................................... SF-Classrooms 61,62
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Class Rooms 61,62 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 167 of 178


SF-Classrooms 61,62 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 563.9 - - 199.2

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.5 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 10.4 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 168 of 178


SF-Classrooms 63-70, 72-84 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ............................................... SF-Classrooms 63-70, 72-84
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Classroom 63-70,72-84 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 169 of 178


SF-Classrooms 63-70, 72-84 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 593.1 - - 204.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 12.8 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 11.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 170 of 178


SF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ....................................................................... SF-Corridor 1
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Corridor 1 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 171 of 178


SF-Corridor 1 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1310.7 - - 95.1

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 6.0 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 34.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 172 of 178


SF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ....................................................................... SF-Corridor 2
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Corridor 2 x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 173 of 178


SF-Corridor 2 Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 1089.9 - - 74.4

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 4.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 28.6 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 174 of 178


SF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

1. General Details:
Air System Name ................................................................... SF-Laboratories
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Laboratories x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 175 of 178


SF-Laboratories Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 12:59AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 626.7 - - 218.0

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load .......................................................................... 13.7 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 13.2 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 176 of 178


SF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 01:00AM

1. General Details:
Air System Name ............................................................. SF-Teacher's Room
Equipment Type ....................................................................... Terminal Units
Air System Type ................................................................... Split DX Fan Coil
Number of zones ............................................................................................. 1
Ventilation ......................................................... Common Ventilation System

2. Ventilation System Components:


Ventilation Air Data:
Airflow Control ................................................... Constant Ventilation Airflow
Ventilation Sizing Method ..................................... Sum of Space OA Airflows
Unocc. Damper Position ....................................................................... Closed
Damper Leak Rate .......................................................................................... 0 %
Outdoor Air CO2 Level ................................................................................ 400 ppm

Cooling Coil Data:


Setpoint ...................................................................................................... 16.0 C
Coil Bypass Factor ................................................................................... 0.180
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Ventilation Fan Data:


Fan Type ................................................................................ Forward Curved
Configuration .................................................................................... Draw-thru
Fan Performance ............................................................................................ 0 Pa
Overall Efficiency .......................................................................................... 54 %

% Airflow 100 90 80 70 60 50
% kW 100 91 81 72 61 54

% Airflow 40 30 20 10 0
% kW 46 40 33 27 21

Duct System Data:


Return Duct or Plenum Data:
Return Air Via ............................................................................ Ducted Return

3. Zone Components:
Space Assignments:

Zone 1: Zone 1
SF-Teacher's Room x1

Thermostats and Zone Data:


Zone .............................................................................................................. All
Cooling T-stat: Occ. ................................................................................... 23.0 C
Cooling T-stat: Unocc. ................................................................................ 40.0 C
Heating T-stat: Occ. ................................................................................... 21.1 C
Heating T-stat: Unocc. ............................................................................... 18.3 C
T-stat Throttling Range .............................................................................. 0.83 K

Thermostat Schedule ..................................................................... Thermostat


Unoccupied Cooling is ....................................................................... Available

Common Terminal Unit Data:


Cooling Coil:
Design Supply Temperature ...................................................................... 13.0 C
Coil Bypass Factor ................................................................................... 0.100
Cooling Source .......................................................................... Air-Cooled DX
Schedule .............................................................................. JFMAMJJASOND

Fan Control ........................................................................................... Fan On

Terminal Units Data:


Zone .............................................................................................................. All
Terminal Type ..................................................................................... Fan Coil
Minimum Airflow ......................................................................................... 0.00 L/s/person
Fan Performance ............................................................................................ 0 Pa
Fan Overall Efficiency ................................................................................... 50 %

Hourly Analysis Program v4.90 Page 177 of 178


SF-Teacher's Room Input Data
Project Name: Nahda School 08/20/2017
Prepared by: 01:00AM

4. Sizing Data (Computer-Generated):


System Sizing Data:
Sizing Data:
Cooling Supply Temperature ..................................................................... 13.0 C

Hydronic Sizing Specifications:


Chilled Water Delta-T ................................................................................... 5.6 K
Hot Water Delta-T ...................................................................................... 11.1 K

Safety Factors:
Cooling Sensible ........................................................................................... 10 %
Cooling Latent ............................................................................................... 10 %
Heating ............................................................................................................ 0 %

Zone Sizing Data:


Zone Airflow Sizing Method ................................. Sum of space airflow rates
Space Airflow Sizing Method ............................. Individual peak space loads

Zone Supply Airflow Zone Htg Unit Reheat Coil Ventilation


(L/s) (kW) (kW) (L/s)

1 368.9 - - 40.9

5. Equipment Data
Vent. Cooling Unit - Air-Cooled DX
Estimated Maximum Load ............................................................................ 2.6 kW
Design OAT ................................................................................................ 35.0 C
Equipment Sizing ............................................................................ Auto-Sized
Capacity Oversizing Factor ............................................................................. 0 %
ARI Performance Rating .......................................................................... 3.224 EER
Conventional Cutoff OAT ........................................................................... 12.8 C
Low Temperature Operation ..................................................................... Used
Low Temperature Cutoff OAT ................................................................... -17.8 C

Terminal Cooling Units - Air-Cooled DX

Estimated Gross Capacity Compressor


Maximum Design Cooling Oversizing + OD Fan ARI Conventional
Load OAT Equipment Capacity Factor Power Performance Cutoff OAT
Zone (kW) (C) Sizing (kW) (%) (kW) Rating Units (C)
1 8.1 35.0 Auto-Sized - 0 - 3.224 EER -17.8

Hourly Analysis Program v4.90 Page 178 of 178