Air System Sizing Summary For CORRIDOR 4a

This document provides an air system sizing summary for Corridor 4a of the 21014 BARKA MALL R4 project in Masqat, Oman. It summarizes that the cooling coil will need to handle a total load of 44.2 kW and sensible load of 36.9 kW occurring in July at 1800, with a required airflow of 2359 L/s. The supply fan is sized to provide an actual maximum airflow of 2359 L/s and will require 0.29 BHP of motor power. Outdoor ventilation for this air system is not required.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views1 page

Air System Sizing Summary For CORRIDOR 4a

This document provides an air system sizing summary for Corridor 4a of the 21014 BARKA MALL R4 project in Masqat, Oman. It summarizes that the cooling coil will need to handle a total load of 44.2 kW and sensible load of 36.9 kW occurring in July at 1800, with a required airflow of 2359 L/s. The supply fan is sized to provide an actual maximum airflow of 2359 L/s and will require 0.29 BHP of motor power. Outdoor ventilation for this air system is not required.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for CORRIDOR 4a

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:56AM

Air System Information


Air System Name ................................. CORRIDOR 4a Number of zones ............................................................. 1
Equipment Class ......................................... SPLT AHU Floor Area ................................................................. 313.0 m
Air System Type ................................................ SZCAV Location .................................................... Masqat, Oman

Sizing Calculation Information


Zone and Space Sizing Method:

Zone L/s .......................... Sum of space airflow rates Calculation Months ......................................... Jan to Dec
Space L/s ...................... Individual peak space loads Sizing Data ...................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load .......................................................... 44.2 kW Load occurs at ..................................................... Jul 1800
Sensible coil load ................................................... 36.9 kW OA DB / WB ...................................................... 44.3 / 29.6 C
Coil L/s at Jul 1800 ................................................ 2359 L/s Entering DB / WB ............................................. 26.2 / 18.2 C
Max block L/s ........................................................ 2359 L/s Leaving DB / WB .............................................. 13.3 / 12.5 C
Sum of peak zone L/s ........................................... 2359 L/s Coil ADP ..................................................................... 11.8 C
Sensible heat ratio ............................................... 0.835 Bypass Factor .......................................................... 0.100
m/kW ....................................................................... 7.1 Resulting RH ................................................................. 61 %
W/m ..................................................................... 141.1 Design supply temp. ................................................... 12.5 C
Water flow @ 5.6 K rise ......................................... N/A Zone T-stat Check .................................................... 1 of 1 OK
Max zone temperature deviation .................................. 0.0 K

Supply Fan Sizing Data

Actual max L/s ....................................................... 2359 L/s Fan motor BHP ........................................................... 0.29 BHP
Standard L/s .......................................................... 2354 L/s Fan motor kW ............................................................. 0.22 kW
Actual max L/(s-m) ................................................ 7.54 L/(s-m) Fan static ....................................................................... 50 Pa

Outdoor Ventilation Air Data


Design airflow L/s ........................................................ 0 L/s L/s/person ................................................................... 0.00 L/s/person