Voltaje Stability Analysis Using Static and Dynamic Approachs
Voltaje Stability Analysis Using Static and Dynamic Approachs
and,
(4)
or,
AV = E F Q
I
Fig. 1 : Test System
6
where is the i* column right eigenvector and qi the i* row left
eigenvector of JR. 3.2 Dynamic Analysis
(Ifdmaxl) but is below the high setting, the current is ramped operation and the time at which the MXL acts. Once the ULTC
down to its continuous limit after a time delay dependent on the starts to operate, voltage at the load bus will gradually be brought
level of field current and the MXL settings. The MXL parameters up toward its reference value, and load power increases, provided
are as follows : the tap ratio does not reach its upper limit. Restoration of load bus
voltage and load power may increase the reactive demand on
Ifdmaxl = 3.02 pu (or 1.05xFull Load Current) generators sufficiently to raise generator field currents above their
Ifdmaxz = 4.60 pu (or 1.6xFull Load Current) continuous limits. If field currents exceed their high set limits.
ILM = 3.85 PU K, = 0.248 currents will be ramped down without a time delay, and time
K, = 12.6 frame 3, as described below, begins. If however field currents are
below their high set limits.current ramping will be delayed for a
The physical configuration of MxLs may vary from machine to period determined by the current level and MXL setting. During
machine, depending on exciter type and manufacturer. The model this period, generator terminal voltage will remain relatively
used in this paper is based on the MXL installed at Ontario constant, and load bus voltages continue to move towards their
Hydro's Bruce 'A' nuclear units. reference values in response to ULTC actions. For the w e under
study, voltage instability does not occur during this time frame.
Time frame 3 starts when the MXL initiates the reduction of field
current. The limiting of generator field current causes the generator
terminal voltage to be reduced. This in turn causes the load bus
voltages to go down, initiating further ULTC operations. Voltage
0
'1fd instability is most likely to occur during this time frame.
Fig. 2 : MXL Model For all the three load levels, time frame 1 runs between time 0 and
about 30 seconds, and time frame 2 starts at about 30 seconds, as
can be seen from Fig. 4.
Three cases with different pre-disturbance system load levels are a. field current of machine 3 is reduced thereby reducing
considered. Total system load for each load level is : the machine terminal voltage
b. voltage at bus 11 drops below its reference value
Load Level 1 = 6655 MW and 1986 MVAR C. ULTC operates in an attempt to bring the voltage at bus
Load Level 2 = 6755 MW and 2016 WAR 11 back
Load Level 3 = 6805 M W and 2031 MVAR d. voltage and load power at bus 11 increases due to ULTC
operation
Fig. 4 to Fig. 7 show the time responses of the voltage at bus 11, e. field current of machine 3 is increased due to AVR
the field current of machine 3, the terminal voltage of machine 3, operation in response to the increase in load power at
and the tap ratio of transformer 10-11 for the cases with the three bus 11
different load levels. f. MXL reduces the field current of machine 3 and drops
the terminal voltage of machine 3
Referring to Fig. 4. three distinct time frames can be easily g. voltage at bus 11 is reduced due to the decrease in the
recognized: terminal voltage of machine 3
h. ULTC operates again
Time frame I is the period between the instant when the
disturbance occurs and the time of the first ULTC tap movement. ULTC operation continues, with bus 11 voltage being reduced,
This is the time frame normally considered in transient stability rather than increased, in response to each tap movement, indicating
simulation. At the end of this time frame, voltages at load buses the system has become voltage unstable. The voltage at bus 11
are lower than their pre-disturbance values. If load is not falls progressively until the ULTC reaches its upper limit at about
represented as constant MVA. load power also decreases because 260 seconds. After the ULTC reaches its limit, the system is
of the voltage dependency of the natural load characteristics. voltage stable as seen from Fig. 4.
Generally, load bus voltages will remain stable at their low values
until ULTCs operate. For the case of Load Level 3, time frame 2 runs between 30
seconds and about 50 seconds. As can be seen from Fig. 4, voltage
Time frame 2 is the period between the time of the first ULTC at bus 11 increases continuously during this time frame as the
1162
-
1.1-
MXL of generator 3 starts to reduce field current, as can be Seen
from Fig. 5. Limiting of the field current of generator 3 causes the Load Level 1
similar chain of events as in the case of Load Level 2. and the 5
voltage at bus 11 falls progressively until the tap reaches its upper
Load Level 1
I
Load Level 2
Load Level 3
m 0.85
l1.- 4
Simulation Results
Eigenvalue
I 1 1 1 1 I
Snapshots
2 I 3
1
11.4 7.9 7.7
I 151.0 141.7 140.9
456.4 424.1 4228
Snapshot 1 : Pre-disturbance
Equivalent to time = 0
Snapshot 2 : Post-disturbance. before ULTC operation.
Fig. 9 : Voltage at Bus 11 Equivalent to time frame 1
Snapshot 3 : Post-disturbance, after ULTC operation.
(Load Level 3, Tap Ratio Unlimited)
Equivalent to time frame 2
Table 2 shows the modal analysis results for the case of Load
Level 2. All the eigenvalues are positive for snapshots 1-3
(corresponding to time frame 1 and time frame 2), indicating that
the system is voltage stable for these conditions. The system
*.-I
becomes voltage unstable at snapshot 4, (corresponding to a point
in time frame 3 before the ULTC reaches its limit), as indicated by
#.a## the negative eigenvalue. The system is voltage stable at snapshot
5, (all positive eigenvalues), because the ULTC has reached its
limit. This agrees with the results obtained using the dynamic
approach.
Snapshots
Eigenvalue ' 1 1 2 1 3 1 4 1 5
I 1. I 10.1 I 6.5 I 5.8 I -10.7 I 5.6 I
146.1 136.1 133.4 70.6 69.1
li? 448.3 416.1 412.1 100.9 120.1
Snapshot 1 : Re-disturbance
Equivalent to time = 0
Fig. 10 : Speed of Machine 3 Snapshot 2 : Post-disturbance
(Load Level 3, Tap Ratio Unlimited) Before ULTC operation
Equivalent to time frame 1
Snapshot 3 : Pw-disturbance
After ULTC operation
Before MXL action
3 3 static Analysip Equivalent to time frame 2
Snapshot 4 : Post-disturbance
System Modelling After MXL action
Before ULTC reaches limit
The same models used for the time domain simulation are used to Equivalent to the start of time frame 3
Snapshot 5 : Post-disnubance
obtain different snapshots following the disturbance and to form
After MXL action
the steady state system Jacobian matrix at each snapshot for the After ULTC reaches limit
evaluation of system voltage stability. Equivalent to the end of time frame 3
1164
Table 3 shows the modal analysis results for the case of Load maintain terminal voltage control, and remote machine 2 and
Level 3. The system is voltage stable for snapshots 1 to 3. machine 1 participate more heavily than machine 3.
(corresponding to time frame 1 and time frame 2), because all the
eigenvalues are positive. The system becomes voltage unstable for Table 4 : Participation Factors
snapshot 4, (corresponding to a point in time frame 3 before the (Snapshot 3 Load Level 2)
ULTC reaches its limit), as indicated by the negative eigenvalue.
The system is voltage stable at snapshot 5, (corresponding to a
point in time frame 3 after the ULTC has reached its limit), as
indicated by all the eigenvalues being positive. Again the static
results agree with the dynamic simulation results.
Snapshots
Table 5 : Participation Factors
Eigenvalue (snapshot 4 Load Level 2)
1 2 3 4 5
Snapshot 1 : he-disturbance
Equivalent to time = 0
Snapshot 2 : Post-disturbance
Before ULTC operation
Equivalent to time frame 1
4. CONCLUSIONS
Snapshot 3 : Post-disturbance
After ULTC operation Results of dynamic analysis using time domain simulations have
Before MXL action been presented to demonstrate voltage instability and to clarify the
Equivalent to time frame 2 influence of ULTCs. generator MXLs, and voltage dependent
Snapshot 4 : Post-disturbance loads. The same system was analyzed using a static approach in
After MXL action which modal analysis is performed for system conditions, or
Before ULTC reaches limit snapshots, which approximate points along the time domain
Equivalent to the start of time frame 3 trajectory. The results obtained using the two approaches are
Snapshot 5 : Post-disturbance shown to be consistent in indicating system voltage stability.
After MXL action
After ULTC reaches limit
Equivalent to the end of time frame 3 The static approach is shown to have a number of practical
advantages over the dynamic approach:
In addition to computing eigenvalues, the modal analysis program. 1) It is computationally less intensive.
using the eigenvectors of the reduced Jacobian matrix, computes 2) The sign of the eigenvalues computed in modal analysis
the participation factors of each bus, branch and generator to each clearly indicate if the system is stable or unstable at the given
mode [SI.Bus participations (PB) determine the areas most prone operating condition.
to voltage instability. Branch participations (eL)and generator 3) The participation factors clearly defme areas prone to voltage
participations (PG) indicate, for each mode, the branches and instability and indicate elements which are important in the
generators which have the largest impact on the voltage stability instability phenomenon. This provides insight into the
of that mode. The participation factors provide important mechanism of instability.
information regarding the mechanism of voltage instability.
Although time domain simulations are necessary for detailed
For the case of Load Level 2, Table 4 and Table 5 show the bus, dynamic analysis and studies requiringcoordinationof controls and
branch and generator participations for the weakest mode at protections, the above advantages make static analysis a suitable
snapshot 3 and snapshot 4, respectively (refer to Table 2 for the choice for the bulk of system studies where the examination of
descriptions of snapshot 3 and snapshot 4). From the eigenvalues system performance under a large number of conditions.
shown, we see that the system is voltage stable at snapshot 3 and
voltage unstable at snapshot 4. 5. REFERENCES
Bus participations indicate that the weak area consists of bus 11 IEEE Special Publication 90TH0358-2-PWR, "Voltage
and bus 10, which agrees with the dynamic simulation results Stability of Power Systems : Concepts, Analytical Tools. and
shown in Fig. 4. At both snapshot 3 and snapshot 4, line 9-10 is Industry Experience". Prepared by the Working Group on
the branch with the highest participation factor to the critical Voltage Stability, 1990.
mode, indicating that this branch is most critical in maitaining the
voltage stability of the critical mode. As for generator N. Flatabo, R. Ognedal. and T. Carlsen, "Voltage Stability
participations, local machine 3 participates the most at snapshot 3 Conditions in a Power Transmission System Calculated by
because its field current is not limited at this snapshot. Once the Sensitivity Methods", IEEE Trans. on Power Systems, Vol. 5 ,
field current of machine 3 is limited at snapshot 4, it is unable to No. 4. November 1990.
1165
[lo] P. Kundur, G.J. Rogers. D.Y. Wong, M.G. Lauby, "A T', = 4.10 T = 0.56
,
'
Comprehensive Power System Stability Analysis Computer
Programs Package", Proceedings of the Power Plant & Power T", = 0.033 T", = 0.062
System Training Modelling & Simulation Conference, Miami Exciters
Beach, Florida, April 17-19. 1991. Both machine 2 and machine 3 have thyristor exciter with a gain of 400
and the sensing circuit time constant of 0.02 second.
[ll] M. Stubbe, A. Bihain, T. Deuse, J.C. Baader, "STAG A New
Unified Software Program for the Study of the Dynamic
Behaviour of Electrical Power Systems", IEEE Trans. on
Power Systems, Vol. 4, No. 1, February 1989.
(121 C.W. Taylor, "Voltage Stability : Load Characteristics and Kip Morison joined the Power System Planning Division of
R&D Needs", Paper Presented at EPRVCRIEPI Joint Ontario Hydro in 1981 and received his M.A.Sc. degree from the
Symposium on Power System Dynamics and Stability, University of Toronto in 1985. He currently works as a system
Monterey, California, May8-10, 1990. studies engineer in the Analytical Methods & Specialized System
Studies Department, and is involved io special system stability and
[13] C. Concordia. Comments on Above Reference [SI, Private conhol studies.
Communication.
Baofu Gao received his M.A.Sc. degree from the University of
APPENDIX Toronto in 1986. In 1990 he joined Ontario Hydro where he now
TEST mSTEM DATA works in the Analytical Methods & Specialized Studies
Department in the Power System Planning Division. He is also
Trausmissim Lmes (R, X & B in pu on 100 MVA Base) studying part-time at the Department of Electrical Engineering,
R X B University of Toronto for his Ph.D. degree.
5-6 o.oo00 o.Oo40 o.oo00
6-7 0.0015 0.0288 1.1730 Prabhashankar Kundur received the M.A.Sc.and Ph.D. degrees
9-10 0.0010 0.0030 O.oo00 from the University of Toronto, Canada io 1965 and 1967
Trausfonnels (R & X in pu on 100 MVA Base) respectively. He taught at Mysore and Bangalore Universities
R x Ratio during 1967-1969. In 1969, he joined Ontario Hydro where he is
1-5 O.oo00 0.0020 0.8857 cunently Manager of the Analytical Methods & Specialized
26 O.oo00 0.0045 0.8857
3-7 O.oo00 0.0125 0.9024 Studies Department in the Power System Planning Division. He
7-8 O.oo00 0.0030 1.0664 also holds the position of adjunct Professor at the University of
7-9 O.oo00 0.0026 1.0800 Toronto. Dr. Kundur was elected a Fellow of the IEEE in 1985
10-11 O.oo00 0.0010 0.9750 (Load Level 1) and is a member of several IEEE working groups and task forces.
0.9938 (Load Level 2) He is also a member of C i p Task Force 38-02-10 on Modelling
1.oo00 (Load Level 3) of Voltage Collapse Including Dynamic Phenomena.
1166
thus clear that AV is proportional to i,,as stated. This is the direction Herminio J.C.P. Pinto & Nelson
I Martins (CEPEL - Centro de
of the modal output. Pesquisas de Energia Eletrica, Rio de Janeiro, FU, Brazil): The
The direction of the modal input AQ is uniquely defined if it is to authors are to be congratulated on this fine paper, which reflects their
maximize the input scalar k for a constant magnitude of I AQl . The large experience in this field. We share the authors' views on the
corresponding direction is then up along the steepest slope, or benefits gained from the coordinated use of both linearized and non-
gradient, in the parlance of the paper. This means that AQ should have linear system analysis to the voltage stability problem.
the direction q l T which, consequently, is the direction of the modal
input. It can be checked that the direcrion Il for AQ, while it has the Our voltage stability work is presently very much related to that of [8].
merit that it does not excite another mode, gives a smaller output IAVI We have produced a simple, though mathematically rigorous, dynamic
- often significantly smaller (the strongly unsymmetrical matrix [ y system model for the voltage stability methodology proposed by the
authors in [8] This dynamic model provides an answer to the
may serve as an example) - for the same magnitude of 1 AQl . The criticisms made in [9] and [13] on the methodology of [8], regarding
direction q l r is therefore the best choice for identifying the most the dynamic nature of a stability problem.
efficient controls to prevent voltage instability.
Of course, this definition of a modal input is at variance with the We will be soon reporting on our work, but feel that a discussion to
fundamental concept of an eigenvector which, as an input to a matrix, this paper is appropriated at this time.
gives an output of the same direction. This is also the approach
adopted in the paper. It seems that the requirement of optimal input The authors carry out modal analysis on the system equations:
conflicts with that of the independence of the individual modes! The
clarification of this problem by the authors would be most welcome. SI + a-'= 0 (A)
It would appear that conceptually more satisfactory results could be
obtained by using Singular Value Decomposition (SVD) for the where JR is the reduced Jacobian matrix defined in section 2 of the
analysis of input-output type of problems as the one examined in the paper. Equation (A) describes the dynamics of the system model
paper in question. With conventional notations, we have represented in the block diagram below:
y=AX (b)
where
A = UZVT (C)
Accordingly (see my discussion to Ref. [A]), the output modes are
given by the columns of the ortho-normal matrix U while the input
modes are defined by the columns of the ortho-normal matrix V. The
individual modes are orthogonal to each other and thus completely
independent. Moreover, since multiplications with ortho-normal
matrices preserve the Euclidean norm, the magnitude of the output
vector y is directly related to the magnitude of the input vector x of
mode i by the correspondent singular value ai. It may be useful to note
that U, V, and E are related to the eigenset of the matrix ArA as Figure A. Simple Dynamic Model Structure foI
follows: U and V are the matrices of its left and right eigenvectors, and Voltage Stability Analysis
E is the matrix of the square roots of its eigenvalues which are all
positive. If A is symmetrical, then its singular values U are equal to its Please note some analogy to the classical multimachine electro-
eigenvalues A. mechanical stability problem, described by equations.
The use of SVD has the following advantages:
It gives full modal information for outputs, inputs, and their ratio. s21 + K s = 0
The singular values represent precisely the ratio of the magnitudes where K S is the matrix of synchronizing torque coefficients
of output to input for any given mode.
The modes can be ranked by the associated singular values and are Let us now describe the dynamic behavior of our simple load model,
fully decoupled. considering the case of a single load bus:
The transfer matrix A does not have to be square, so that the effect
of a reduced number of input variables can be investigated.
The largest singular values and their associated singular vectors
can be directly calculated by simple iterative procedures.
If the largest singular values are exactly or nearly equal, an
invariant subspace for best control vectors can be determined. I 1
Inputs and outputs can be easily interchanged since U and V are I I
orthogonal matrices.
L
Because of the above listed features of the SVD, the reduction of the
original Jacobian matrix in eqn.(l) to the reduced Jacobian of eqn.(2) I
The closed loop transfer function of the system of Figure B is: Quasi-dynamicmethods without modeling of fast dynamics
is often effective--full dynamic simulation can be used to
confirm results.
The authors model about half of the load (both real and re-
active parts) a s static, constant power. This is often consid-
The closed loop system pole is therefore equal to - 1 / k , and the closed ered a poor approximation of induction motor load in
loop transfer hnction has zero gain at steady state (washout block) dynamic simulation. (Adjustable speed drives and power
Our linear dynamic load model has therefore the characteristc of electronic loads may, however, approach this model.) Could
automatically bringing the bus voltage deviation back to zero following t h e authors discuss t h e effect of realistic dynamic loads in
a step change in the load MVAr demand This is therefore a simplified both the time domain simulation and t h e modal analysis?
model of an OLTC action Note also that a system which is voltage
Figure 3 show a linear decrease in field current. I think this
stable will have eigenvalues in the left half plane, which is coherent
is only true for step changes into the integrator of Figure 2.
with modal analysis
As a side issue, can the authors confirm that, for load level
Many other first order dynamic models may also be proposed for the 2 or 3, and with tap changer a t limit, adding load will de-
load, all of which have different dynamic performances but provide crease load power, and inserting a capacitor bank will raise
equivalent information regarding the voltage stability condition of the voltage and load power? For a similar system (but with in-
system. duction motor rather t h a n static constant power loads), ref-
erence A demonstrates these effects.
Another point worth mentioning is the benefit of using transfer The interpretation of voltage stability for discontinuous tap
function residues or controllability factors [A] rather than participation changing with limits requires discussion. Modal analysis
factors to produce the various ranking lists needed (critical generators, applied a t a point in time between t a p changes (e.g., snap-
critical lines, critical loads, etc.). shot 4 for load level 2 ) should, mathematically, be stable
just as snapshot 5 is stable. How does modal analysis treat
We suggest that the terminology used by the authors (static approach the discontinuous tap changing? Regarding t a p changer
to voltage stability) be changed to miall signal voltage stability The limits, can we say that modal analysis shows periods of
suggested terminology will then be in harmony with modal analysis and voltage decay (along with generatiodnetwork participa-
with the well established small signal electromechanical stability tions) of a stable nonlinear dynamic system?
analysis [B]
Reference:
Martins, N. and Lima, L.T.G., Determination of Suitable A. C. W. Taylor, A Conceptual Analysis of Voltage Stability as
Locations for Power System Stabilizers and Static VAr Related to Load Characteristics, published by the North
Compensators for Damping Electromechanical Oscillations in American Electric Reliability Council in Survey of the Volt-
Large Scale Power Systems, IEEE Trans. on Power Systems,, age Collapse Phenomenon, August 1991.
Vol. PWRS-5, pp 1455-1469, November 1990.
Manuscript received August 10, 1992.
Martins, N. and Lima, L.T.G., Eigenvalue and Frequency
Domain Analysis of Small-Signal Electromechanical Stability
Problems, IEEE Symposium on Application of Eigenanalysis
and Frequency Domain Methods for System Dynamic M. Y. Vaiman and V. A. Faybisovich ( V & R Energy System
Performance, publication 90 TH 0292-3 PWR, pp 17-33, 1989 Research, Los Angeles, CA): We have some remarks to a very
interesting article by G. K. Morison, B. Gao, P. Kundur.
Manuscript received August 10, 1992. Remark 1. This paper compares voltage stability analysis of
power system using static and dynamic technique. For small
example authors show that the results of comparison are consis-
Carson W.Taylor, Bonneville Power Administration, Port- tent. However, the authors dont describe the conditions when
land Oregon: The authors demonstrate some important as- results obtained by using the dynamic and static methods are
pects of voltage stability. similar. Also the authors dont describe the conditions when the
A power system is a dynamic system with many complexi- results, that were obtained by using these approaches are not
ties (e.g., nonlinearities including discontinuous equip- consistent.
Only in the cases when violation of stability is a periodic one,
ment). Simulation, particularly static voltage stability
simulation, requires significant approximations. The au- the results obtained by the dynamic and static methods are
consistent. Indeed, all eigen-values of the matrix of the lin-
thors demonstrate that linearized sensitivity type static
earized steady state system power voltage equations are real
methods can, however, be useful in voltage stability analy-
ones (not complex) and change of their signs indicates the
sis. Weak points in the generatiodtransmission system are
stability violation. If the stability violation is oscillatory one we
identified.
must use only dynamic approach [l].
The authors give several reasons for more accurate time Remark 2. To use steady state system power voltage equations
domain simulation. Since effective (i.e., cost-effective) volt- for voltage stability analysis is better to utilize another tech-
age stability solutions often involve various control meth- nique. In monographs [2, 31 is shown an interesting property of
ods, longer-term dynamic simulation is no doubt the most stressed power system comprising the fact that the surface of
important tool for system design and demonstration. We potential function of its conservative model has not a conven-
are using the ETMSP 3.0 program for design of undervolt- tional shape of potential well but of a trough(groove) - shaped
age load shedding and automatic capacitor bank switching. one. Such a trough goes from the minimum of potential energy
1169
indicated using modal analysis by high Q / V sensitivities. Provid- pute using a particular analytical technique reflect actual system
ing the snapshots, on which modal analysis is performed, are problems and the solutions we come up with are meaningful.
obtained frequently enough so that these sensitivities are re- Dr. Pals last comment is that exact limits obtained based on a
flected in subsequent operating points, then the method will assumed load distribution is not very meaningful. Dr. Pal clearly
indeed capture fast dynamics. overlooks the fact that virtually all power system transmission
Regarding the comment on the generalization of the findings, and generation planning, as well as operating, is performed
there is no reason to believe that the results will not be consis- using assumed load distributions and growth rates based on load
tent for different types of load, providing the correct load forecasts. In this regard, a stability margin obtained using load
dynamic characteristics are used in obtaining the snapshots (as forecast information may in fact be the most practical measure
in dynamic simulation) and incorporated into the Jacobian used available to planners and operators.
for modal analysis. Dr. Pal again raises the comment that he
believes the singularity of the Jacobian is not a suitable indicator References
of voltage instability, particularly when different load character-
istics are present. This issue has been addressed many times [l] I. Dobson and Liming Lu, Using an Iterative Methods to
Compute a Closest Saddle Node Bifurcation in the Load
before, including in the closure of [2]. It is essential to under-
Parameter Space of an Electric Power system, Paper pre-
stand that, unlike the conventional powerflow Jacobian, lin-
sented at Voltage Stability and Security NSF Workshop,
earized load characteristics are included in the reduced Jacobian
used for modal analysis. Indeed if this were not the case, the Deep Creek Lake, MD, August, 1991.
singularity would not correctly correspond to instability. Inclu- [2] B. Gao, G. K. Morison, P. Kundur, Voltage Stability
Evaluation Using Modal Analysis, Paper 91 SM 420-0
sion of linearized dynamic characteristic in the Jacobian is
PWRS presented at the 1991 IEEE/PES 1991 Summer
provided to ensure that singularity corresponds to instability, for
that particular load type. It is important to keep in mind the Meeting, San Diego, California, July 28, 1991.
practical aspects of the problem; whether the results we com- Manuscript received October 1, 1992.