Air System Design Load Summary For CORRIDOR 4a

This document summarizes the cooling and heating load design data for Corridor 4a of the 21014 BARKA MALL R4 project. The cooling load totals 23,886 watts of sensible heat and 7,302 watts of latent heat. The heating load totals 2,538 watts of sensible heat and no latent heat. The total system cooling load is 36,870 watts of sensible heat and 7,303 watts of latent heat. The total system heating load is -52 watts of sensible heat and no latent heat.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
77 views1 page

Air System Design Load Summary For CORRIDOR 4a

This document summarizes the cooling and heating load design data for Corridor 4a of the 21014 BARKA MALL R4 project. The cooling load totals 23,886 watts of sensible heat and 7,302 watts of latent heat. The heating load totals 2,538 watts of sensible heat and no latent heat. The total system cooling load is 36,870 watts of sensible heat and 7,303 watts of latent heat. The total system heating load is -52 watts of sensible heat and no latent heat.

Uploaded by

mechmohsin4745
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Design Load Summary for CORRIDOR 4a

Project Name: 21014 BARKA MALL R4 08/01/2017


Prepared by: Amjaad 07:56AM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1800 HEATING DATA AT DES HTG
COOLING OA DB / WB 44.3 C / 29.6 C HEATING OA DB / WB 12.0 C / 10.0 C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m 0 - 0 m - -
Wall Transmission 0 m 0 - 0 m 0 -
Roof Transmission 313 m 4194 - 313 m 2538 -
Window Transmission 0 m 0 - 0 m 0 -
Skylight Transmission 0 m 0 - 0 m 0 -
Door Loads 0 m 0 - 0 m 0 -
Floor Transmission 0 m 0 - 0 m 0 -
Partitions 211 m 5194 - 211 m 0 -
Ceiling 0 m 0 - 0 m 0 -
Overhead Lighting 11738 W 8216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 52 4512 6954 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 8% / 5% 1769 348 0% 0 0
>> Total Zone Loads - 23886 7302 - 2538 0
Zone Conditioning - 23105 7302 - 141 0
Plenum Wall Load 20% 0 - 0 0 -
Plenum Roof Load 70% 9786 - 0 0 -
Plenum Lighting Load 30% 3521 - 0 0 -
Return Fan Load 2359 L/s 0 - 2359 L/s 0 -
Ventilation Load 0 L/s 0 0 0 L/s 0 0
Supply Fan Load 2359 L/s 218 - 2359 L/s -218 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 1% 239 - 1% 25 -
>> Total System Loads - 36870 7302 - -52 0
Central Cooling Coil - 36870 7303 - 0 0
>> Total Conditioning - 36870 7303 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.50 Page 1 of 1