Architectural design and detail engineering
1 1013 7.10 FFL
SBR(INFLUENT)
10 1127
SBR(INFLUENT)
10 1127
SBR(EFFLUENT)
SBR(DESIGN CRITERIA)
21 1244 centrifuge
tread>=260mm
riser<=175mm
slope of ramp<= 1:6
ratio of tread and riser=(2tread+1riser)=600-650mm
no. of risers per flight<=15
blast proof & rain water shaft wall>=230mm thick RCC wall
external walls>=230mm thick brick wall
internal partition wall=230/115 mm thick brick wall
fire wall>=345mm thick brick wall
entrance door size>=1500x2100mm
bath cubicle door=800x2100mm
other doors>=1000x2100mm
total openable area of windows>=15% of floor area
size of overhang>=900mm
non approachable ht.of wall>=300mm
approachable ht. of wall>=900mm
ht. of ceiling=2500-3000mm
min width of 1000mm around building
d equipment
load=0.5MT-5MT & lift<5m
if two in no. each of 75% capacity of total weight shall be provided
load>=5MT & lift>5m
CTRICAL
mentation
A SYSTEM
sewage water
chnical data
designed GWL=existing ground level(egl)
width>=1m
under wind & seismic forces increase net.safe bearing capacity in shear by 25%
E=120Kg/cm2
density of moist soil=1800Kg/m3
K=0.19
layer thickness<=150mm
otective coating system for STP
ion(Architecture)
rial specification
tion ELECTRICAL
max ambient temperature=50C
min ambient temperature=3C
design ambient temperature=40C
altitude above MSL<1000M
11KV shall be three cored
on instrumentation
buried trenches shall have min width of 600mm and depth of 1000mm