ROC800-Series IEC 62591 Interface: Scalability
ROC800-Series IEC 62591 Interface: Scalability
ROC800-Series IEC 62591 Interface: Scalability
WirelessHART Data Access After installing the IEC 62591 Interface module and the
Wireless 781 Field Link, you configure the Series 2 ROC800
The IEC62591 Function Block is pre-configured to return the with ROCLINK 800 Configuration Software to act as a gateway
Universal and Common HART parameters including; device. The ROC800 can then receive signals from and transmit
Long Tag signals to WirelessHART field devices.
User Defined Message ROCLINK 800 provides you with a list of wireless field devices
User Defined Descriptor with the correct Network ID and Join Key. You can choose
Extended Device Type which of those devices are enabled (commissioned) on the
Device ID network. You can also configure the update rate for individual
Manufacturer ID devices.
Device Serial Number You can install one IEC 62591 Interface module in a Series 2
Adapter Type THUMs Expanded Device Type ROC800. IEC 62591 Interface modules can be installed in any
Adapter ID THUMs Device ID slot. Modules can be easily installed or removed from the
PV, SV, TV and QV Variable Units module slots at any time by removing the two captive screws
Slot 0, 1, 2 and 3 Variable Units accessible from the front of the unit.
PV, SV, TV and QV Variable Value IEC 62591 Interface modules are hot-swappable, meaning the
Slot 0, 1, 2 and 3 Variable Value module can be removed and another module of the same kind
Primary Variable Loop Current can be installed under power. IEC 62591 Interface modules are
Device Status hot-pluggable, meaning they may be installed directly into
Battery Life unused module slots under power.
Note: Battery life is calculated by the transmitter. Refer to The module has a removable terminal block for convenient
the transmitters manufacturer for details. wiring and servicing. The terminal block can accommodate size
PV Loop current 16 to 24 American Wire Gauge (AWG). A USB port is provided
Burst Rate on the module to perform firmware updates and to provide
Variable Status debug information to support personnel.
Note: This discrete I/O support of the IEC 62591 module
Installation and Configuration requires a Series 2 ROC800 unit with firmware version
3.60 (or higher) and ROCLINK 800 version 2.40 (or
The IEC 62591 Interface module connects to the Emerson
higher).
Wireless 781 Field Link through a four-wire connection. This
allows the Wireless 781 Field Link to be strategically placed
away from the controller in the optimal location for best
network performance. The module provides 12 Vdc loop-
output to power the Wireless 781 Field Link.
2 www.EmersonProcess.com/Remote
October 2016 ROC800:62591
Rosemount 3051 Wireless Pressure Transmitter Rosemount 702 Wireless Discrete Transmitter
Rosemount 2051 Wireless Pressure Transmitter TopWorx 4310 Wireless Valve Position Monitor
(firmware revision 5.0 or greater)
Rosemount 708 Wireless Acoustic Transmitter Fisher 4320 Wireless Valve Position Monitor
(firmware revision 5.0 or greater)
Note: Each THUM adapter supports only one wired HART device. The maximum number of THUM devices cannot exceed the
maximum number of supported wireless devices. Refer to Emersons Wireless THUM Adapter Quick Start Guide, 00825-
0100-4075, for further information.
www.EmersonProcess.com/Remote 3
ROC800:62591 October 2016
Wireless Communications
Protocol IEC 62591 (WirelessHART)
2.42.5 GHz DSSS
Supported Device Update Rates 1 second to 60 minutes
Active Advertising support enable for 30 minutes
Range (Line of Sight) Standard Antenna 225 m (750 ft)
Extended Antenna 800 m (2600 ft)
Security AES-128 encrypted WirelessHART, including individual session keys
Unique join keys and device white listing
Output Power 10 dBm (10mW)
Wired Communications
Type 4-wire connection to the IEC 62591 Interface module
Less than 15 pF/ft capacitance
Distance 200 m (656 ft) maximum
Power
Input Supplied by the 4- wire connection to the IEC 62591 Interface module (10.5 30 Vdc)
Consumption 20 mA at 12 Vdc
Physical
Dimensions Wireless Fieldlink 140 mm H by 106.7 mm W by 133.4 mm D
(5.51 in H by 4.20 in W by 5.21 in D)
Standard Antenna 90.2 mm (3.55 in)
Extended Range 175.8 mm (6.92 in)
Antenna
Weight Aluminum Housing 1.7 kg (3.7 lb)
4 www.EmersonProcess.com/Remote
October 2016 ROC800:62591
www.EmersonProcess.com/Remote 5
ROC800:62591 October 2016
Ordinary Location Certification Special Conditions 1. The Wireless 781 Field Link housing contains aluminum and is
for FM (continued) of Certification considered a potential risk of ignition by impact or friction. Take
care during installation and use to prevent impact and friction.
2. The surface resistivity of the unit is greater than one gigaohm
(G). To avoid electrostatic charge build-up, do not rub or clean
the unit with solvents or a dry cloth.
3. The 781 Field Link will not pass the 500 Vrms dielectric strength
test and this must be taken into account during installation.
CSA Intrinsically Certificate Number: 2330424
Safe
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D.
Temp Code T3C
Enclosure Type 4X, IP66/67
When installed per Rosemount Drawing 00781-1010
European Union Directive The EC declaration of conformity for all applicable European directives for this product can
Information be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained
by contacting your local sales representative.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
Electro Magnetic Compatibility (EMC) (2004/108/EC)
Emerson Process Management complies with the EMC Directive.
Radio and Telecommunications Terminal Equipment Directive (R&TTE)(1999/5/EC)
Emerson Process Management complies with the R&TTE Directive
European I1 ATEX Intrinsic Safety
Certification
Certificate Number: Baseefa11ATEX0059X
II 1G Ex ia IIC T4 Ga (Tamb = -40 C to 70 C)
Enclosure Type IP66/67
When installed per Rosemount Drawing 00781-1024
CE 1180
Input/Output Input / Power Input / RS485 Output / RS485
Parameters Ui = 30 V Ui = 11 V UO = 7.14 V
Ii = 200 mA Ii = 300 mA IO = 112 mA
Pi = 1.0 W Pi = 1.0 W PO = 1.0 W
Ci = 0 Ci = 5.1 nF Ci = 0
Li = 0 Li = 0 Li = 0
CO = 13.9 F
LO = 0
6 www.EmersonProcess.com/Remote
October 2016 ROC800:62591
European Union Directive European Special 1. The plastic antenna may present a potential
Information (continued) Certification Conditions for electrostatic ignition hazard and must not be
(continued) Safe Use (X) rubbed or cleaned with a dry cloth.
2. The Wireless 781 Field Link enclosure is made
of aluminum alloy and is given a protective
polyurethane paint finish; however, care should
be taken to protect it from impact or abrasion if
located in a zone 0 environment.
3. The device is not capable of withstanding the
500V isolation test required by EN60079-
11:2007 Clause 6.3.12. This must be taken into
account when installing the device.
IECEx Intrinsic Certificate Number: IECEx BAS 11.0028X
Safety
Ex ia IIC T4 Ga (Tamb = -40 C to 70 C)
Enclosure Type IP66/67
When installed per Rosemount Drawing 00781-1024
Input/Output Input / Power Input / RS485 Output / RS485
Parameters Ui = 30 V Ui = 11 V UO = 7.14 V
Ii = 200 mA Ii = 300 mA IO = 112 mA
Pi = 1.0 W Pi = 1.0 W PO = 1.0 W
Ci = 0 Ci = 5.1 nF Ci = 0
Li = 0 Li = 0 Li = 0
CO = 13.9 F
LO = 0
Special 1. The plastic antenna may present a potential
Conditions for electrostatic ignition hazard and must not be
Safe Use (X) rubbed or cleaned with a dry cloth.
2. The Wireless 781 Field Link enclosure is made
of aluminum alloy and is given a protective
polyurethane paint finish; however, care should
be taken to protect it from impact o rabrasion if
located in a zone 0 environment.
3. The device is not capable of withstanding the
500V isolation test required by EN60079-
11:2006 Clause 6.3.12. This must be taken into
account when installing the device.
Combination Certification KL Combination of I1, I5, I6, and I7
www.EmersonProcess.com/Remote 7
ROC800:62591 October 2016
1 A RS-485 (+)
2 B RS-485 ()
3 TA Termination A
4 TB Termination B
5 PWR+ Output Power (+)
6 PWR Output Power ()
Communications
Quantity 1
Type 4-wire connection to the Emerson Wireless 781 Field Link
Max. Number of Wireless Field 60
Devices per Module
Max. Number of Modules per 1
ROC800
USB Port
Quantity 1
Type USB 2.0 specification
Use Firmware upgrades and troubleshooting report
Warning Do not use USB connector unless the area is known to be non-hazardous.
Power
Loop Output Power 12 Vdc
Consumption Main power supply Typical 31 mA at 24 Vdc
loading at the
Battery Terminals
(at 24.0 Vdc)
Additional loading USB Connection 13 mA at 24 Vdc
that may apply
Physical
Dimensions 26 mm W by 75 mm H by 133 mm D (1.03 in. W by 2.96 in. H by 5.24 in. D)
Weight 62.4 g (2.2 oz)
Wiring 16 24 AWG twisted shielded pair
LEDs RS-485 transmit and recieve
8 www.EmersonProcess.com/Remote
October 2016 ROC800:62591
Environmental
Same as the Series 2 ROC800 in which it is installed.
Approvals
Same as the Series 2 ROC800 in which it is installed (with the exception of ATEX certification).
www.EmersonProcess.com/Remote 9
ROC800:62591 October 2016