CBR Bulletin
CBR Bulletin
CBR Bulletin
1 / 25
Burner Control CBR
Depending on the power supply voltage, 4 variations, which are project customized, pre-configured and tested.
Technical Specifications:
Power Supply 230V AC 15% ... +10% 50/60Hz or
115V AC 15% ... +10% 50/60Hz
Electrical connection Phase correct connection and ground connection
according to electrical diagram
Touch protection! Must be present for thermocouples
and the UV sensor / flame rod (powerless installation
and connection)
Fuse 6,3A slow or 10A fast, integrated, replaceable
Power consumption (self) < 14VA
Power consumption (total) Max. current: 6,3A
Power consumption (safety relevant Max. 5A (for all gas valves and ignition transformer for
users) approx. 2 sec during ignition)
Max. cable lengths to burner components 10m
The burner control box has many diagnosis features for ease of
commissioning or trouble shooting:
Program sequence, device parameters, fault code history, operating hours
counter, combustion chamber temperature (measured by dual thermocouple)
or the flame signal strength can be indicated on the 7-segment display.
The functions of the buttons, button combinations, information, operating and fault codes are described on two
labels. Labels are available in different languages and are changeable.
Code label 1
Code label 2
Each CBR is configured for its specific application and tested prior to delivery.
The most important parameters can be visualized on the display (Comfort Configuration) by applying the
appropriate key combinations (refer to label 1). A Password is required to change parameters (except Profibus
address) and to activate manual operation.
You will receive your password from our sales, service or electronics department after completing registration.
P. 3 / 25
Burner Control CBR
Comfort Configuration
Depicted configurations may differ from the actual scope of delivery, procedures however, remain principally the same.
NOTE: All configured parameters are documented in the burner control certificate. This certificate is archived according the serial number.
Please notify our electrical engineering department of any changes.
All configured parameters are documented in the burner control certificate. This certificate is archived according the
serial number. Please notify our electrical engineering department of any changes.
P. 4 / 25
Burner Control CBR
Electrical Connections
Please follow all applicable safety regulations. Depicted configurations may differ from the actual scope of delivery, procedures however,
remain principally the same.
Tools:
screw driver
wrench
multi meter
Parts:
Burner controls CBR (ready for connecting and pre-
configured to customers specifications)
M8x1,25 screws or threaded studs (with washers and
nuts) 4x
Connections from the CBR to the electrical components of the burner are pre-wired and pre-assembled
according to customer specifications. Please refer to the electrical schematics.
Please note, that NiCr-Ni dual thermocouples and the UV sensor must not be attached (changed)
with power ON. Danger of electrocution if phases of power supply are not connected correctly!
Prior to commissioning, all electrical connections and signal exchange must be verified by trained
electricians in accordance to local codes and regulations.
P. 5 / 25
Burner Control CBR
A FLOX burner without the safety relevant temperature
acquisition via a NiCr-Ni dual thermocouple for release of
FLOX mode, must utilize the safety relevant inputs for
release of FLOX/Flame modes (XOR signal processing).
Input signals must are to be determined and activated by fail
safe temperature supervision. FLOX mode may only be
activated at the FLOX input terminal if the furnace temperature
is > 850C via an active signal (230V AC L1 or optional 115V
AC L1). The input of the Flame release terminal must be
deactivated. A drop in temperature below the FLOX release
threshold, the FLOX release signal must be deactivated and the
Flame release signal must be activated. Switch over must occur
within one second, otherwise a fault shut-off will occur (F 57)
Prior to activating FLOX mode, the FLOX/Flame switching logic, especially the electrical
connections, must be validated by trained personnel. Validation to be performed with the gas
supply turned off. Incorrect implementation can result in EXPLOSION!
Prior to commissioning, wire termination and controls must be verified and tested diligently by
trained professionals, in accordance to local regulations.
NOTE: all parameter settings are documented on the burner test data certificate. This certificate is
archived according to WS serial numbers. Please notify our electrical engineering department of any
changes made.
P. 6 / 25
Burner Control CBR
L1,N,PE
(FLOX GWS)
Bus wire
A maximum of 126 devices my be connected to a Profibus DP system (master and slaves). Each device receives an
individually defined address. The address can be entered into the CBR via the push buttons on the front panel.
The address range is from 0 to 126 (CBR delivered with invalid address 127!). All devices are connected in a bus
fashion (in line). Each individual line segment can have as many as 32 participants (masters and slaves). A bus
terminator must be placed at the beginning and end of each segment. Termination can be achieved via the switch
within each Profibus connector. To maintain fault free bus operation, each terminated device must have power
connected.
Repeaters (boosters) must be used for more than 32 devices or to extend the range of the bus network.
It is recommended to utilize shielded 2 wire cable (for example Lapp Unitronic Best.-Nr. 2170-220T or Siemens
Best.-Nr.6XV1830-OEH10) to protect the network against electromagnetic interference. The shield must be
connected on both ends, good conductivity of the shield is paramount. Do not switch the data lines A and B.
Furthermore, keep Profibus cables as far away from other highly radiating cables (for example, high voltage cables,
frequency converters, VFD, etc.)
Ascertain that the power potential level is compensated between various masters and slaves (uniform potential)
(Refer to Aufbaurichtlinien/ EMV-Manahmen im Fachbuch: Profibus-DP/DPV1 Hthig-Verlag ISBN 3-
7785-2781-9).
P. 7 / 25
Burner Control CBR
220
Variosub Profibus-
9-pin connector
1A 1B 2A 2B WS T.--Nr. 970-00-440
green red
Note: Bus connector can be removed from the CBR without interrupting the bus.
P. 8 / 25
Burner Control CBR
Cable length:
Following table valid for cable type A per EN 50170
Baud rate (kbit/s): 9,6 19,2 45,45 93,75 187,5 500 1500 3000 6000 12000
Distance (m): 1200 1200 1200 1200 1000 400 200 100 100 100
P. 9 / 25
Burner Control CBR
Profibus configuration:
When engineering a Profibus DP system, parameters and addresses must be configured for each device.
A GSD file is provided to simplify and standardize this engineering process. The GSD file format is
standardized, so it can be read and recognized by devices of all manufacturers.
Please contact our sales, service or engineering department for the GSD file applicable for your project.
The steps required to access the file should be available from your automation system manual.
The Basic I/O version (minimum configuration) for data transfer, includes only the output byte (AB0)
and the 2 input bytes (EB0 + EB1).
The Standard I/O version can transfer and analyze the four input bytes (EB0,EB1,EB2,EB3) as well the
output byte (AB0).
More information regarding the Extended I/O version can be obtained upon request.
The address of individual bus devices can be set via the CBR function keys (refer to Profibus Address
Setting). Each CBR is delivered with the invalid address 127 preselected. However, it is still possible to
operate the burner control unit in manual mode, without a valid Profibus address.
Data transfer (Bytes/Bits) from master (host) to the CBR burner control unit:
Please follow all applicable safety regulations. Depicted configurations may differ from the actual scope of delivery, procedures
however, remain principally the same. Please contact our sales or engineering department.
Following tables illustrate the data transfer between master (host) and slave (CBR).
For service adjustments, emissions testing und failure diagnosis the burner can be operated in manual
mode.
Prerequisites:
The power supply must be connected phase correct and all contacts of the process line permissives /safety
limits are closed, so that power (same potential) is present at the safety chain terminal of the CBR.
The following adjustments can be made via Comfort Configuration Step 0 or Parameter 10:
0 Automatic operation
1 Manual mode: Air purge
2 Manual mode: Heating
3 lock out control box (locked)
These selections require a password (operator password)
Air purge ON
Tools:
Screw driver
Accessories:
Digital thermometer
Salient notes:
Safety features of the thermal processing line must not circumvented or disabled.
Functionality of the safety features of every burner must be validated prior to each application
start-up, such as may occur after commissioning, maintenance work or extended down times.
How to:
Burner Faults
Please follow all applicable safety regulations. Depicted configurations may differ from the actual scope of delivery, procedures however,
remain principally the same.
Remove power (lockout and tag out) prior to working on electrical components.
Fault trouble shooting by authorized trained professionals! Repair attempts on the CBR will void
the warranty!
Improper attempts at repairs and incorrect electrical connections, for example providing power to
output terminals can cause gas valves to pen and destroy the CBR fail safe operation can no
longer be guaranteed!
Please contact the WS service department if a fault persists and can not be reset.
Power down the burner control box and close the manual gas shut-off valve. Isolate the burner from the
exhaust system (i.e. Shut-off valve or blind flange). The faulting burner should be locked out and tagged
out to prevent unintended activation.
P. 18 / 25
Burner Control CBR
a) Status Display
These faults do not cause a burner shut-off and will auto reset once conditions are within normal
operating limits.
P. 19 / 25
Burner Control CBR
b) Burner faults
Fault displayed on CBR by flashing red LED and following fault Code:
False flame signal detected by Unusually long residual flare after burner
ionization electrode or the UV-probe has turned off e.g. gas valve leakage;
UV-probe defective or aged;
Ground connection of ionization
electrode?
Flame loss during STS Check the gas and air flow volumes;
(no flame established during start-up) Check spark plug connection;
Is a spark generated, transformer OK?
Is the spark visible through the sight
glass?
F A8 defective
With start/flame burners, switching
temperature for next mode in order?
P. 20 / 25
Burner Control CBR
Fault displayed on CBR by flashing red LED and following fault Code:
Fault displayed on CBR by flashing red LED and following fault Code:
False flame signal detected by the UV- Unusually long residual flare after burner
probe during start-up has turned off e.g. gas valve leakage; UV-
(similar to F A6) probe defective or aged
Burner internals defective?
Ground connection of Ionization
F a electrode?
Air purge orifices in the gas head plugged
clean
F
P. 22 / 25
Burner Control CBR
flashing
Display fault (internal) The connected display is invalid
F2
flashing
Password fault Incorrect password entered or password
not confirmed by pressing reset button.
F3
Note: Access to device configuration
flashing
levels protected by dedicated passwords
Reset fault Prolonged reset signal present (> 10
seconds) or signal is already present when
F4 connecting power
F5 changeable parameter.
Button combination locked
flashing
Burner (CBR) locked out The CBR is locked out
Comfort Configuration 0 or parameter
(A burner may be turned off in this 10 (manual mode) is set to 3
F7 fashion) For example after long operation in
manual mode.
Comfort Configuration 0 or parameter
flashing 10 must be set to 0 (automatic mode) or
to manual mode (1 or 2)
Configuration error Parameters 65 and 90 have colliding
F8 settings.
flashing
Profibus fault The connection with the Profibus master
interrupted; Profibus IC defective or
F9 missing
flashing
P. 23 / 25
Burner Control CBR
Fault displayed on CBR by flashing red LED and following fault Code:
Fault Display Fault / Cause Check / Resolution
Hardware fault Ambient temperature too high;
Excess power supply level in main power
supply
F 03
Reset fault Wait until new reset is permitted
(Too many reset attempts. Maximum 5
resets per 15 minute interval permitted)
F 04
Configuration error Switching intervals are smaller than the
test intervals of the pressure switch or the
thermocouple configuration or
F 0C post air purge / post combustion < 0.5s
F 18
Processor fault Strong EMV interference
P
F1
P. 24 / 25
Burner Control CBR
Fault displayed on CBR by flashing red LED and following fault Code:
Fault Display Fault / Cause Check / Resolution
External FLOX/Flame switching fault XOR signals not present at FLOX and
flame terminals with external
FLOX/flame release (without
F 57 thermocouple
Fault displayed on CBR by flashing red LED and following fault Code:
Fault Display Fault / Cause Check / Resolution
Ambient temperature fault The ambient temperature surrounding the
CBR is too high
F 5E
Combustion chamber temperature Shut down to protect the burner against
fault excessive ambient temperatures;
(Over temperature burner) Fault does not auto reset after temperature
F 5F has dropped
Thermocouple fault
d) Internal faults