Frru004 Mom4
Frru004 Mom4
Frru004 Mom4
TM
FRRU004-MOM4
MONITORED OUTPUT MODULE
Features
One simple LED for status indication
NFPA Class A (Styles 6 & 7) and Class B (Style 4) for SLC
NFPA Class B (Style Y) for NAC
UL listed with Potter/Amseco, Gentex,
and Cooper Wheelock syncro-modules and devices
Electronic address setting
Downsized unit
Easy installation
Description
The Monitored Output Module (FRRU004-MOM4) provides a programmable source of power to control and operate output devices including
notification appliances and releasing devices. Additionally, it continuously supervises wiring connected to terminals A+, A- for open or short circuits
and 24+ and 24- when 24VDC is applied.
FRRU004-MOM4 employs one red LED to indicate the status. In normal condition, the LED flashes. When the output is activated, the LED will turn
on constantly. In case of trouble, the LED will turn off.
Ordering Information
Model no. FRRU004-MOM4
Specifications
No. Item Specification
1 Rated voltage range of SLC input power (S+,S-) 22.0 to 24.0V
2 Maximum SLC 24 VDC standby current(S+,S-) 250A
3 Maximum SLC 24 VDC alarm current(S+,S-) 1mA
4 Rating for connected device power ( Releasing device and NAC) 24VDC, 2A
5 Max. supervising current for external 24 VDC input power (24+,24-) 1.6mA
6 Wiring style NFPA Class B (Style Y)
7 End-of-line resistor value for notification appliance 5.1k, 1/2W
8 End-of-line device for releasing device 5.1k, 1/2W with diode
9 Maximum wiring resistance of output circuit wiring Refer to Wiring diagram
10 Maximum wiring capacitance of output circuit wiring 1F
11 Operating temperature range 0C to 49C (32F to 120F)
12 Operating humidity range 0 to 93% (non-condensing)
13 Dimensions 106mm (4.17 inches) (H) 106mm(4.17 inches) (W) 29mm (1.14 inch) (D)
North American 64mm (2-1/2 inches)deep 2-gang box
14 Applicable electrical box for installation
Standard 4 inches square box 38mm (1-1/2 inch)deep box
Wiring Diagram
Figure 2: Output Connected to a NAC
Select DC
From FACP or
previous module JP1
SLC Loop
End of line resistor
To the next S+ 5.1k ohm 1/2W
module
S- A+
24VDC(+) 24+ A- + + +
From UL1481 power limited power
supply or previous module 24VDC(-) - - -
24-
24VDC(+)
To the next module 24VDC(-) LED
Note: 1. The following synchronization modules may be used for strobe synchronization.
SM-12/24 (Wheelock)
DSM-12/24 (Wheelock)
SMD10-3A (AMSECO)
Refer to respective Sync Module manuals for the proper wire connection method and limitations.
2. when notification appliances are connected to the FRRU004-MOM4, additional FRRU004-MOM4 modules should be separated by a
short circuit isolator (SCI). If wiring Class A, Style 7, then each FRRU004-MOM4 is required to have its own listed UL 1481 power supply.
3. When notification appliances are connected to the module, the resistance values of terminals OUT+, OUT- must be less than R max below.
R max = (24V - V min) / lt
V min: Min. operating voltage of connected device
lt: Total of operating current of connected device (ampere)
Note: 1. Only one Releasing Device can be connected per FRRU004-MOM4 module.
2. When a releasing divice is connected to the module, resistance values of terminals OUT+, OUT- must be less than R max below.
R max = (24V - V min - 0.95V) / lt
V min: Min. operating voltage of connected device
lt: Total of operating current of connected device (ampere)
0.95V: Voltage to be doropped in the end-of-line device
NOTE
The information contained herein does not purport to cover all the details or variations of the equipment described, nor to provide for every
possible contingency that may be met in connection with its installation, operation or maintenance.
Specifications are subject to change without notice. Contact Nohmi before relying on the information.
Actual performance is based on proper application of the product by a qualified professional.
Should further information be required or should particular concerns arise that are not covered sufficiently for the purchasers purposes, the
matter should be referred to Nohmi or your nearest distributor.
Contact