the press the EYEBALL key on the control then power the control on while keeping
the Eyeball key pressed.
When your control has powered up it should be in INITAIL CLEAR MODE. This mode allows
you to clear out all the corrupted data.
If your control has powered up in German press MACH-DATEN (forth soft key) if its in English
press MACHINE DATA.
Starting with the first soft key on the left press four soft-keys in total. You should see small ticks
appear against options on the screen.
Press the RECALL Button to go back to the screen you powered up in.
Press PLC INITIAL, this is the same in German and English (third soft key).
Press the first two soft-keys from the left. Again ticks will appear against the options.
Press the RECALL Button to go back to the screen you powered up in.
Press the RECALL Button to go back to the screen you powered up in.
You have now cleared out all the corrupted data. If the control is in German it is preferable to
change the language to English. To do this follow the steps below.
Press DIAGNOSE (if Diagnose is not present press and the option should then
appear)
Then press the RIGHT SCROLL Button so that you see NC MD and press the soft
key.
Type 250 then the search button this will highlight the Machine Data. Machine Data
250 is for either a Milling machine or a Lathe and Machine Data 199 for either a Grinder or a
Nibbling machine and is for Language Selection.
Type 1111
Press the ENTER Button
Press the RECALL Button to go back to the screen you powered up in.
Press the RECALL Button to go back to the screen you powered up in.
Press the RECALL Button to go back to the screen you powered up in.
Starting Pcin:
Pcin Settings:
When Pcin has loaded up, use the your cursor keys to
highlight V24_INI.
Once you have completed your settings press ENTER & then
press Y for SAVE INPUT. This will then set your port
settings for data transmission.
You now need to start to reload your data from your PC to the NC in order.
On you PC highlight DATA OUT and press your ENTER Button.
Press your SPACE BAR on your PC to clear the contents of the window.
Press the ENTER Button on your PC.
Now using your cursor highlight TEA1
Type 1 then ENTER on the NC. This will set the interface number.
You will see the Data transfer from the PC to the NC.
Repeat the procedure above but this time select TEA2 on the PC to transfer.
When you have transferred TEA1 & TEA2 press on the NC.
Type 1111
Press the ENTER Button
The control should now power off and back on again in INITIAL CLEAR Mode.
Press PLC INITIAL (third soft key).
Press the first two soft-keys from the left. Again ticks will appear against the options. This will
clear the PLC Program and also clear any Retentive Flags from the PLC memory.
Press the RECALL Button to go back to the screen you powered up in.
Press the RECALL Button to go back to the screen you powered up in.
Type 1 then ENTER on the NC. This will set the interface number.
You will see the Data transfer from the PC to the NC.
Repeat the procedure above but this time select PCA on the PC to transfer.
When you have transferred PCP & PCA press on the NC.
Using ALT T select any files which you have not already transferred. You will see an asterix
appear next to each file you tag. Do not tag any file with a .DIR extension and make sure that
when you have selected all your files that you leave the highlight over one of the tagged files.
Press ENTER on the PC.
The rest of the files will now be transferred.
When finished press DATA STOP on the NC.
Your NC should now be ready for operation.