OE Spec MTU16V2000DS1100 3B 50Hz 1 15

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

DIESEL GENERATOR SET

MTU 16V2000 DS1100


Prime Power: 1000 KVA
380V - 415V/50 Hz/Air Charge Air Cooling

Optional equipment and finishing shown. Standard may vary.

Product Highlights
// Benefits // Performance Assurance Certification (PAC)
- Low fuel consumption - Engine-generator set tested to ISO 8528-5 for transient
- Optimized system integration ability response
- High reliability and availability of power - 75% load factor for prime power applications
- Long maintenance intervals - Verified product design, quality and performance integrity
- Optimized ratio between size and power - All engine systems are prototype and factory tested
- Wide operating range without derating
// Complete range of accessories available
// MTU Onsite Energy is a single-source supplier - Control panel
- Circuit breaker/power distribution
// Global product support - Fuel system
- Fuel connections with shut-off valve mounted to base frame
// Standards - Starting/charging system
- Engine-generator set is designed and manufactured in - Exhaust system
facilities certified to standards ISO 2008:9001 and - Mechanical radiator
ISO 2004:14001 - Container and Canopy
- Generator set complies to G3 according to ISO 8528
- Generator meets NEMA MG1, BS5000, ISO, DIN EN and // Emissions
IEC standards - Fuel consumption optimized
- NFPA 110 - TA-Luft, Tier 2 and NEA (ORDE) optimization
optionally available
// Power
Rating
- System rating: 1000 kVA // Certifications
- Accepts rated load in one step per NFPA 110 - CE certification option
- Generator set complies to G3 according to ISO 8528-5 - German Grid Code Certification (BDEW) option
- Generator set exceeds load steps according to ISO 8528-5
2 / // / MTU 16V2000 DS1100 / 3B / 50 Hz / 380V - 415V

Application data
Engine
//
Fuel consumption optimized Emission optimized
Manufacturer MTU MTU
Model 16V2000G26F 16V2000G26F
Type 4-cycle 4-cycle
Arrangement 16V 16V
Displacement: l 35.7 35.7
Bore: mm 135 135
Stroke: mm 156 156
Compression ratio 17.5 17.5
Rated speed: rpm 1500 1500
Engine governor ADEC ADEC
Speed regulation 0.25% 0.25%
Max power: kWm 890 890
Mean effective pressure: bar 19.9 19.9
Air cleaner Dry Dry

// Fuel System

Maximum fuel lift: m 5 5


Total fuel flow: l/min 30 30

//
Fuel Consumption

At 100% of power rating: l/hr 204.8 215.5
At 75% of power rating: l/hr 156.0 164.9
At 50% of power rating: l/hr 108.3 114.7

// Lube oil system

Total oil system capacity: l 102 102


Max. lube oil temperature (alarm): C 103 103
Max. lube oil temperature (shutdown) : C 105 105
Min. lube oil pressure (alarm): bar 4.5 4.5
Min. lube oil pressure (shutdown): bar 4 4

//
Combustion Air Requirements

Combustion air volume: m3/s 1.03 1.19
Max. air intake restriction: mbar 40 40

All data refers only to the engine and is based on ISO standard conditions (25C and 100m above sea level).
Emission optimized data refer to TA-Luft optimized and NEA (ORDE) optimized/Tier 2 compliant engines.
Values referenced are in accordance with ISO 3046-1. Conversion calculated with fuel density of 0.83 g/ml.
All fuel consumption values refer to rated engine power.
3 / // / MTU 16V2000 DS1100 / 3B / 50 Hz / 380V - 415V

Application data
//
Cooling/Radiator System
Fuel consumption optimized Emission optimized
Coolant flow rate (HT circuit): m3/h 41.6 41.6
Heat rejection to coolant: kW 370 350
Heat rejection to charge air: kW 145 205
Heat radiated to ambient: kW 40 40
Fan power for mech. radiator (40C): kWm 43.4 43.4
Fan power for mech. radiator (50C): kWm 43.4 43.4
Air flow required for mech. radiator (40C) cooled unit: m3/min 1462 1462
Air flow required for mech. radiator (50C) cooled unit: m3/min 1462 1462
Engine coolant capacity (without cooling equipment): l 70 70
Radiator coolant capacity (40C): l 83 83
Radiator coolant capacity (50C): l 104 104
Max. coolant temperature (warning): C 102 102
Max. coolant temperature (shutdown): C 105 105

//
Exhaust System

Exhaust gas temp. (after turbocharger): C 530 515
Exhaust gas volume: m3/s 2.78 3.07
Maximum allowable back pressure: mbar 50 50
Minimum allowable back pressure: mbar 30 30

// Generator

Protection class IP23 IP23


Insulation class H H
Voltage regulation (steady state) 0.25% 0.25%
Rado interference class N N

All data refers only to the engine and is based on ISO standard conditions (25C and 100m above sea level).
Emission optimized data refer to TA-Luft optimized and NEA (ORDE) optimized/Tier 2 compliant engines.
4 / // / MTU 16V2000 DS1100 / 3B / 50 Hz / 380V - 415V

Standard and Optional Features


// System Ratings (kW/kVA)

Generator model Voltage with mechanical radiator


kWel kVA* AMPS
Basic: Marathon 740RSL7182 380 V 800 1000 1519
Advanced: Marathon 740RSL7183 400 V 800 1000 1443
(Low voltage Marathon standard) 415 V 800 1000 1391
Basic: Marathon 742RSL7184 380 V 800 1000 1519
Advanced: Marathon 742RSL7185 400 V 800 1000 1443
(Low voltage Marathon oversized) 415 V 800 1000 1391
Leroy Somer LSA 50.2 M6 380 V 800 1000 1519
(Low voltage Leroy Somer) 400 V 800 1000 1443
415 V 800 1000 1391
Leroy Somer LSA 50.2 L7 380 V 800 1000 1519
(Low voltage Leroy Somer oversized) 400 V 800 1000 1443
415 V 800 1000 1391

* cos phi = 0,8

// Engine

4-Cycle ADEC electronic isochronous engine Fuel consumption optimized engine


Standard single stage air filter governor TA-Luft optimized engine
Oil drain extension & shut-off valve Common rail fuel injection Tier 2 optimized engine
Full flow oil filters Dry exhaust manifold NEA (ORDE) optimized engine
Closed crankcase ventilation Electric starting motor (24V)

// Generator

NEMA MG1, BS5000, ISO, DIN EN and No load to full load regulation Marathon low voltage generator
IEC standards 0.25% voltage regulation no load to Leroy Somer generator
Self-ventilated full load Oversized generator
Superior voltage waveform Brushless alternator with brushless
Solid state, volts-per-Hertz regulator pilot exciter
Ingress protection IP 23 4 pole, rotating field
3 phase voltage sensing Sustained short circuit current of up
3% maximum harmonic content to 300% of the rated Prime Power/
2/3 pitch stator windings Continuous Power current for up to
10 seconds (Marathon Generators)
Sustained short circuit current of up
to 300% of the rated current for up to
10 seconds (Leroy Somer Generators)

Represents standard features Represents optional features


5 / // / MTU 16V2000 DS1100 / 3B / 50 Hz / 380V - 415V

Standard and Optional Features, continuation


// Cooling System

Jacket water pump Mechanical radiator


Thermostat(s) Jacket water heater
Air charge air cooling

// Control Panel

Pre-wired control cabinet for easy Basler controller Different expansion modules
application of customized controller Deif controller Remote annunciator
(V1+) Complete system metering Daytank control
Island operation (V2) Digital metering Generator winding temperature
Automatic mains failure operation Engine parameters monitoring
with ATS (V3a) Generator protection functions Generator bearing temperature
Automatic mains failure operation Engine protection monitoring
incl. control of generator and mains SAE J1939 engine ECU Differential protection with
breaker (V3b) communications multi-function protection relay
Island parallel operation of multiple Parametrization software Modbus RTU-TCP gateway
gensets (V4) Multilingual capability
Automatic mains failure operation Multiple programmable contact inputs
with short (< 10s) mains parallel Multiple contact outputs
overlap synchronization (V5) Event recording
Mains parallel operation of a single IP 54 front panel rating with
genset (V6) integrated gasket
Mains parallel operation of multiple
gensets (V7)

// Circuit Breaker/Power Distribution

3-pole circuit breaker Manual-actuated circuit breaker Base frame mounted circuit breaker
4-pole circuit breaker Electrical-actuated circuit breaker Stand-alone circuit breaker in
separate switch box

// Fuel System

Flexible fuel connectors mounted to Fuel cooler


base frame
Fuel filter with water separator
Switchable fuel filter with
water separator

Represents standard features Represents optional features


6 / // / MTU 16V2000 DS1100 / 3B / 50 Hz / 380V - 415V

Standard and Optional Features, continuation


// Starting/Charging System

24V starter Battery charger


Starter batteries Redundant starter

// Mounting System

Welded base frame Resilient engine and generator Modular base frame design
mounting

// Enclosures and Containers

Canopy 20 foot container

// Exhaust System

Exhaust bellows with connection Exhaust silencer with 40 dB(A) sound


flange attenuation
Exhaust silencer with 10 dB(A) sound Y-connection-pipe
attenuation
Exhaust silencer with 30 dB(A) sound
attenuation

Represents standard features Represents optional features


7 / // / MTU 16V2000 DS1100 / 3B / 50 Hz / 380V - 415V

Weights and dimensions

Drawing above for illustration purposes only, based an standard open power 400 Volt engine-generator set. Lengths may vary with other voltages. Do not use for installation design.
See website for unit specific template drawings.

System Dimensions (LxWxH) Weight (dry/less tank)


Open Power Unit (OPU) 4830 x 1990 x 2200 mm 7100 kg
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific engine-generator set.

Sound data
// Consult your local MTU Onsite Energy distributor for sound data.

Emissions data
// Consult your local MTU Onsite Energy distributor for emissions data.

Rating Definitions and conditions


// Prime power ratings apply to installations where utility power is unavailable or unreliable. At varying load, the number
of generator set operating hours is unlimited. A 10% overload capacity is available for one hour in twelve. Ratings are in
accordance with ISO 8528-1, ISO 3046-1, BS 5514 and AS 2789. Average load factor: 75%. Operating hours/year: unlimited
// Deration factor:
Altitude: Consult your local MTU Onsite Energy Power Generation distributor for altitude derations.
Subject to change. | 3239551 | Edition 01/15 | ENC 2015-04.
Temperature: Consult your local MTU Onsite Energy Power Generation distributor for temperature derations.

Rated power is available up to 40C and 400m above sea level.

Materials and specifications subject to change without notice.

MTU Onsite Energy


A Rolls-Royce Power Systems Brand

www.mtuonsiteenergy.com