Interpolation

This document summarizes the wind load analysis for the First Baptist Church located in Mabuhay City, Philippines. It provides key details about the building dimensions and geometry. It then outlines the steps to calculate the design wind load on the building using the specified reference standard, including determining basic wind speed, pressure coefficients, and velocity pressures. The calculations show the windward design load is -1.064 kPa and the leeward design load is 0.030 kPa.

Uploaded by

Crest
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
105 views

Interpolation

This document summarizes the wind load analysis for the First Baptist Church located in Mabuhay City, Philippines. It provides key details about the building dimensions and geometry. It then outlines the steps to calculate the design wind load on the building using the specified reference standard, including determining basic wind speed, pressure coefficients, and velocity pressures. The calculations show the windward design load is -1.064 kPa and the leeward design load is 0.030 kPa.

Uploaded by

Crest
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 10

WIND LOAD ANALYSIS

Reference : NSCP. 2010 Volume 1, Building, Towers,


and Other Vertical Structure, Sixth Edition

Building Name : First Baptist Church

Location : Mabuhay City, Dasmarinas, Cavite, Philippines

Enclosure: Enclosed Building

Bay Distances: 3 ; 2.2 m

No. of Bays: 4 bays

Hor. Distance of building (Normal to wind direction)


11.2 m

Hor. Distance of building (Parallel to wind direction)


4.7 m

Number of floor above ground (including mean heigth)


3

Story Height:

1st Floor 2.4 m


2nd Floor 3m
5.4 m

Calculation of Mean Roof Height

Roof slope: 6.34


Roof Height: 0.5 m
Mean Roof Height,h: 5.65 m

Determining if the Building is High Rise or Low Rise

5.65 < 18 It is a LOW RISE BUILDING

Thus for Low Rise Building:

207.5.12.2.2 =_ [(_ )(_


Design Parameter :

207.5.4.4 Basic Wind Speed,V: 200 kph Table. 207-1 (Zone 2)


207.5.4.4 Wind Directionally Factor,Kd: 0.85 Table. 207-2
207.5.6 Importance Factor,Iw: 1.00 Table.207-3 (Standard)

Velocity Pressure Exposure Coefficient, Kz, Kh

Heigh above ground level,z : 5.40 m


Mean Roof Height,h: 5.65 m

for interpolation, Kz for interpolation, Kh

207.5.6.6 4.50 0.70 4.50 0.70 Table.207-4


5.40 Kz 5.65 Kh
207.5.6.6 6.00 0.70 6.00 0.70 Table.207-4

Kz = 0.7 Kh = 0.7

Topographic Factor,Kzt

207.5.7.2 Kzt = 1.00

Gust Effect Factor, G

207.5.8.1 G= 0.85

External Pressure Coefficient, Cp

Wind Direction: Normal to ridge 15 10

h/L = 1.20

207.5.12.2.1 Cp = -0.90 -0.18 Figure 207-6 (cont'd)

Internal Pressure Coefficient, GCpi

Enclosure Classification: Enclosed Building

207.5.12.2.1 Gcpi = 0.18 -0.18 Figure 207-5

Calculation of Velocity Pressure @ windward, qz


207.5.10 qz = 0.0000473*Kz*Kzt*Kd*V2*Iw 1.126 Kpa

Calculation of Velocity Pressure @ leeward, qh

207.5.10 qh = 0.0000473*Kh*Kzt*Kd*V2*Iw 1.126 Kpa

Design Wind Load

for Cp = -0.90 ; Gcpi = +0.18


207.5.12.2.1 p =qz*G*Cp - qh*(GCpi) -1.064 Kpa

for Cp = -0.18 ; Gcpi = -0.18


207.5.12.2.1 p =qz*G*Cp - qh*(GCpi) 0.030 Kpa
=_ [(_ )(_ )]
76.92 1.22
80 X
84.62 0.87

X= 1.08