Input Details: - (Assumed The Topography Is Plain) Units (M) 26.9 (M) 17.45 (M) 14.2 4

This document provides calculations for wind load on a building with a pitched roof. It includes inputs like building dimensions, wind speed data, pressure coefficients. The calculations determine pressure values for different angles of the wind on the roof and walls based on coefficients and internal pressure assumptions. The results are wind pressures on various surfaces of the building for design.

Uploaded by

gvgbabu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
112 views5 pages

Input Details: - (Assumed The Topography Is Plain) Units (M) 26.9 (M) 17.45 (M) 14.2 4

This document provides calculations for wind load on a building with a pitched roof. It includes inputs like building dimensions, wind speed data, pressure coefficients. The calculations determine pressure values for different angles of the wind on the roof and walls based on coefficients and internal pressure assumptions. The results are wind pressures on various surfaces of the building for design.

Uploaded by

gvgbabu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 5

Sheet1

Wind load calculation


Input details:- (Assumed the topography is Plain)

1.Details of the Building Units


Length of the building (M) 26.9
Bredth of the building (M) 17.45
Height of the building (M) 14.2
Importance of structure 4
(See table NO:-1)

Basic wind speed (Vb) (m/s) 44

Terrain Category 2

(See table NO:-2)

Class of structure B
(See table NO:-3)

Coefficients
K1 1.07

K2 1.0136
K3 1 (Fixed)

Design wind speed (m/s) 47.720288

Design wind pressure (N/m2) 1366.3355321


1.366 (kN/m2)

Page 1
Sheet2

Wind load calculations for Pitched roofs


c/c distance between columns
(along width) 10.5 (mtrs)
(along length) 26.9 (mtrs)
Height of the truss 1.9 (mtrs)
Slope of the truss 19.895 (degrees)

Building height ratio (h/w) 0.7048710602

Coefficients for cpe


For wind angle 0 deg
wind angle(0 deg)
EF GH
-0.704182747 -0.501045687

For wind angle 90 deg


WInd angle(90 deg)
EG FH
-0.8 -0.6

Assume the percentage of openings as > 20.00%


internal pressure coefficients 0.5 -0.5

Page 2
Sheet2

1) Pressure coefficient for internal pressure +0. 0.5

Page 3
Sheet2

wind angle(0 deg) pressure on roof


EF GH EF GH
-0.204182747 -0.001045687 -0.278982142 -0.001428759

WInd angle(90 deg) EG FH


EG FH -0.40990066 -0.136633553
-0.3 -0.1

2)Pressure coefficient for internal pressure -0.7 -0.5

wind angle(0 deg) pressure on roof


EF GH EF GH
-1.204182747 -1.001045687 -1.645317674 -1.367764291

WInd angle(90 deg) EG FH


EG FH -1.776236192 -1.502969085
-1.30 -1.1

Page 4
Sheet3

Wind calculations for walls of rectangular clad buildings


Building height ratio 0.70487106
Building plan ratio 1.54154728

Wind pressure coefficients

Building Building cpe for Local


Wind angle
height ratio plan ratio A B C D cpe
1.5 4 0 0.7 -0.3 -0.7 -0.7 -1.1
1.5 4 90 -0.5 -0.5 0.7 -0.1 -1.1

internal pressure coefficient

Assume the percentage of openings as > 20%


internal pressure coefficient 0.5 -0.5

1)Pressure coefficient for internal pressure coefficient 0.5

Wind angle
0 1.2
0.2 -0.2 -0.2 -0.6
90 0
0 1.2 0.4 -0.6
PRESSURE A B C D
0 1.63960264 0.273 -0.2733 -0.3
90 0 0 1.6396 0.55

2)Pressure coefficient for internal pressure coefficient -0.5

Wind angle A C B D Local cpe


0 0.2
-0.8 -1.2 -1.2 -1.6
90 -1
-1 0.2 -0.6 -1.6
PRESSURE A B C D
0 0.27326711 -1.09 -1.6396 -1.6
90 -1.36633553 -1.37 0.2733 -0.8

Page 5