Product Catalogue H2 2013 PDF
Product Catalogue H2 2013 PDF
Product Catalogue H2 2013 PDF
Flue Gas Operated Hot Water Operated Steam Operated Direct Fired
LiBr Absorption Chiller/Heater LiBr Absorption Chiller LiBr Absorption Chiller LiBr Absorption Chiller/Heater
Content
Features of Product 2-10
11
Our Customers 12
At least till today we still only have one earth for living, but obvious In 1985 produced the first LiBr absorption chiller
climate change in recent years linked to greenhouse gas emission In 1992 drafted the Chinese national standard for LiBr absorp-
reminds human being that immediate measures should be taken to tion chiller
protect our planet well. From Kyoto Protocol, Copenhagen Agree- In 1994 set up the only one state-level enterprise technology
ment to Cancun Climate Conference the world has been working center for absorption cooling technology in China
hard to promote applications of energy saving solutions and green In 2001 the only one Postdoctoral Scientific Research Work
energy so that reduce emission of greenhouse gas. Station was set up
In 2003 became the only one public listed company in LiBr
Acting as one of effective solutions for this purpose, Lithium Bro- absorption chiller industry of China in stock exchange market.
mide Absorption Cooling technology adopts non-volatilization, In 2009 Installed the largest LiBr Absorption Heat Pump project
non-deterioration and pollution-free solution of Lithium Bromide as of the world in China
working medium, recover waste heat existed widely in industrial In 2010 developed the first unit of triple effect direct fired LiBr
and commercial area as major driving source for chilled water pro- absorption chiller in China
duction, not only helping to raise efficiency of energy consumption
but also reducing emission significantly. Green heart, Green future is slogan to represent target of Shuan-
gliang, also indicates responsibility we shall take, so we not only
Since foundation in 1982, in 31 years Shuangliang Eco-Energy develop Libr absorption technology for cooling but also spread
Systems Co., Ltd have been devoting in supplying solutions and its application to heating by heat pump, not only adopt common
products of energy saving and environmental protection based hot water and steam to drive chiller but also expand driving heat
on Lithium Bromide Absorption Chiller/Heat Pump on below mile- source to waste heat and green energy )solar and geothermal*
stones, , not only play role as leading absorption chiller manufacturer, but
also upgrade to comprehensive solution provider of energy saving,
fresh water saving and producing by absorption chiller/heat pump
and new developed air cooled condenser, seawater desalination
systems, provide economically feasible solutions to help more and
more companies to realize their responsibilities on energy saving
and emission reduction.
1
Features of Product
Pioneering technology have been used to ensure the advanced features of chiller
1. Pioneering a chiller with two pumps and without spray nozzles solves the degradation of cooling ca-
pacity forever.
Shuangliang constructed the first in China absorption chiller with two pumps and without spray nozzles, which eliminates the rapid deg-
radation of cooling capacity. In order to attain the aim, a chiller with two pumps and without nozzles is manufactured with the knowhow,
such as Left-Middle-Right arrangement of absorber-evaporator-absorber, absorber with dripping plates instead of spray nozzles, which
dont need solution spray pump. With this technology, the chiller can be operated for much longer time.
SS Dripping Plate
Spray Nozzle
Evaporator
Evaporator
Evaporator
Absorber
Absorber
Absorber
Absorber
Shuangliang Others
2. Solution heat exchanger with new construction and ow pattern improves chiller energy efciency
and reduces fuel consumption.
Heat exchangers are designed with new tubes and their supports, furthermore with new flow pattern, that leads to improve heat transfer
and reduce flow pressure drop. These measures improved chiller energy efficiency and reduced fuel consumption.
3. Distribution of refrigerant by dripping plates improves chiller energy efciency and reduces fuel con-
sumption.
The special form of distribution of refrigerant by dripping plates improves the wetting of tubes by refrigerant, fully uses the heat transfer
area, reduces the refrigerant film thickness, increases the heat transfer effects, and results in improvement of chiller energy efficiency and
reduction of fuel consumption.
4. New tubes and their arrangement in evaporator improves chiller energy efciency and reduces fuel
consumption.
Application of new tubes and their arrangement in evaporator makes more even distribution of heat transfer effect, and thus to improve
chiller energy efficiency and reduce fuel consumption.
2
5. Special construction of high pressure generator improves chiller reliability and energy efciency, and
reduces fuel consumption.
High pressure generator with solution inside tubes and wet back of combustion chamber improves chiller operation safety, and reduces
fuel consumption.
Flow Chart of H.P. Generator (Water Tube) Flow Chart of H.P. Generator (Fire Tube)
7. Evaporator tubes are protected from freezing to improve the chiller reliability.
Evapotator tubes are protected from freezing with such measure, as chiller can stop cooling very quickly. It is realized by interruptting
the operation of refrigerant pump, if failure of power or chilled water occurs, because refrigerant water from condenser is collected in the
sump of evaporator, and pumped to the dripping plate for distributing over tubes.
$SZTUBMMJ[BUJPOMJOF
Absorber
$SZTUBMMJ[BUJPO
Absorber "SFB
9. Pioneering non-condensable gas purging during heating improves the chiller reliability.
The direct fired absorption chiller can be purged during heating mode by pioneering technology to improve the chiller reliability and im-
proves chiller operation life.
All these patented technologies and other pioneering knowhow are implemened aiming at making the
chiller operation more efcient, reliable and easier.
3
DFM technology
4
5
High Air-Tightness
The Decisive Factor to Guarantee the Quality of Lithium Bromide Absorption Chiller
Lithium bromide absorption chiller is operating under high vacuum, which would be impaired by leaking of air into the chiller and
non-condensable gases generated inside of the chiller due to corrosion. Poor vacuum will reduce chiller cooling capacity and even
increase the corrosion of metal parts in chiller. So high air-tightness is the decisive factor to guarantee the quality of lithium bromide
absorption chiller, and the key parameter for evaluation of chiller characteristics.
Two special measures are adopted to improve the air tightness of Shuangliang absorption chillers:
)1* The chiller and its parts have been inspected by helium mass spectro leak tester with leakage rate of 110-10Pa m3/s, which is 4
order lower than 2.0310-6Pa m3/s specified by Japanese Industrial Standard JISB8662-1994. The rigid leak tester applied by
Shuangliang is the only equipment used in absorption chiller industry in the world. During visiting Shuangliang, a famous atomic
expert said, "Shuangliang has the same leak testing facility as used in atomic industry".
)2* A patented automatic purging unit is installed on the chiller to purge out non-condensable gases during operation ensuring the
vacuum in the chiller.
6
Intelligent Control System
Limit Control
More considerate way of control:
Running controllimit controlsafety protection control.
When chiller's normal running endangered, the self-diagnosis and self-
adjustment function will carry out to ensure stable and safe operation.
7
Reliable and Easy Centralized
Control System
Central control of units, such as automatic change-over, central control,
storage and print-out of operation data of parallel operated units, and
etc. can be realized by means of a computer with the software MMI2
for centralized control developed by the company. In such a way, the
computer automatically displays the operation data and conditions,
troubles and alarm signal and starts or stops the units, when the load
increases or decreases, and the energy consumption can be saved.
The control functions are optional for order.
8
Intelligent Control System
Shuangliang Company uses the most advanced in the world Concentration Limit Control
color touch screen as the man-machine interface. The op-
erator can start or stop the unit or learn the basic operation, The solution concentration control, specific to the company,
maintenance and acquisition of operation mode and data allows the unit to operate under high concentration safely and
merely by touching the screen in accordance with the instruc- stably by monitoring the spray concentration of the strong solu-
tion displayed. Man-machine dialogue by touch screen will tion and controlling the heating capacity, thus not only to prevent
make the operation of Shuangliang made units easier and crystallization but also to improve the operation efficiency of the
more accessible. unit.
9
Real-Time Display of Operation
and Easy to Understand and Maintenance Instructions Displaying
The control system adopts the advanced PID control tech- This function ensures that the operator can understand the unit easily
nology and touch screen LCD to display the operation con- and rapidly thus to well manage the unit and greatly improve the life of
ditions and data of the unit in a real-time manner with both the unit and guarantee the increase of efficiency for users as well.
texts and pictures, featuring direct expression of contents and
easiness for understanding, enabling the operator to know the
operation conditions anytime and to take timely measures in
emergency.
Display of Parameters
Chilled (hot) water inlet temperature Evaporating temperature Working Cooling flow chart Heating flow chart
Chilled (hot) water outlet temperature Flue gas temperature principle Working principle of chiller Working principle of heater
Cooling water inlet temperature HPG pressure
Data Display
Unit
Cooling
Maintenance
instructions
System
Routing maintenance
Unit
Heating
System
Long term shutdown
10
11
Our Customers
With about 100 sales and service branches around the world, we keep zero distance with customers.
Being sold in more than 100 countries and regions, over 20,000 absorption chillers are serving global customers well.
Lefay Resort
& Spa Lago di Garda(Italy)
12
1 Flue Gas Type Lithium Bromide
Absorption Chiller/Heater
Shuangliang is capable of serving you with our 5 main types of chillers in this category as Flue Gas type,
Flue Gas with Direct-red after burning type, Flue Gas/ Steam type, Flue Gas/Hot Water type and Flue Gas/Hot
Water with Direct-red after burning type based on diversied applications.
Trigeneration System
Trigeneration )CCHP/BCHP*, which applies the oil or gas as the
prime energy resource to meet the requirements of community
or buildings for the power, heating and/or cooling, can realize the
cascade resources applications, such as the high grade energy
is used for power generation, and less potential energy for heat-
ing and/or cooling to raise the utilization percentage of power to
85%, improve the safety of power supply by electric power net-
work, save energy considerably, protect environment and con-
tinuous develop national economy. Application of trigeneration,
which gives additional power supply to the society and reduces
the energy consumption by air conditioning installations, has the
active role to solve the power supply shortage. So, the trigenera-
tion system is the only choice of development of power supply.
)The waste heat, which usually is discharged into atmosphere, now is utilized to drive the lithium bromide absorption chiller/
heater)LBAC/H*, realized the cascade application of prime energy resource.*
Electric Electric
Power Power
Flue
Gas %
Other Flue Other
% Losses
% Gas Losses
%
Jacket
Water %
Total Heat Total Heat
of Fuel #FGPSF
GMVFHBT of Fuel
BOEKBDLFUXBUFS
XFSFFYIBVTUFEJO
% WBJO
OPXUISPVHI
DPHFOFSBUJPO
TZTUFN
SFBMJ[F
%
DBTDBEFVUJMJ[BUJPO
Gas Engine PGQPXFS Gas Turbine
Trigeneration system can be widely used in places where electric power and air conditioning requirements exist simultaneously, such as
factories, hospitals, large department stores, communities and industrial parks.
13
Flue Gas Type Lithium Bromide Absorption Chiller/Heater
Flue gas type lithium bromide absorption chiller/heaters are oper- In order to meet the requirements to comfort and technological
ated by the flue gas from generators and other heat sources, fall needs of air conditioning system, lithium bromide absorption
into two categories: flue gas type and flue gas/hot water type. chiller/heaters with after-burning means can be installed, where
High temperature flue gas type absorption chiller/heaters are heat from generator flue gas )or flue gas and hot water* is not
mainly applicable to the trigeneration installations with turbo gen- enough to drive them.
erators )including micro turbine* and other places where high
temperature flue gas is available and air conditioning is neces- For trigenerator installation with internal combustion engine as
sary )such as industrial kilns*. For flue gas-hot water fired types, drive, if flue gas is enough to meet the requirements of air con-
main heat sources can find the flue gas and jacket water from ditioning, and hot water will be used for other applications, then
internal combustion engine. These types can also be used in flue gas type or such type with after-burning will be available.
other places where high temperature flue gas is available and air
conditioning is necessary.
Mode 1: Gas Turbine+Flue Gas Type Lithium Bromide Absorption Chiller
Working Principle
Fuel
Fuel is burned in the gas tur-
bine combustion chamber to
produce high pressure and Combustion chamber
Application Features
Gas turbine generator is working based on simple circle, which is beneficial to improve rate of utilizing waste heat.
Flue gas from gas turbine is used in flue gas type lithium bromide absorption chiller/heater, to simplify the installation configuration,
save equipment investment, and improve the energy integrated utilization in system.
This mode is applicable to the trigeneration system with gas turbine generator.
14
Mode 2: Gas Turbine+Flue gas type Lithium Bromide Chiller/Heater
with after burning
Working Principle
Fuel is burned in the gas turbine combustion chamber to produce high pressure and temperature gas to drive gas turbine generator,
flue gas of which is directed to lithium bromide absorption chiller/heaters with after burning to offer chilled )hot* water for air condi-
tioning. When the flue gas can not meet the cooling capacity required by air-conditioning, the after burning system is started to supply
additional portion of fuel into the combustion chamber of absorption chiller/heater.
Flue
Combustion chamber
Application Features
Gas turbine generator is working based on simple circle, which is beneficial to improve rate of utilizing waste heat.
Flue gas from gas turbine is used in flue gas type lithium bromide absorption chiller/heater with after burning, to simplify the instal-
lation configuration, save equipment investment, and improve the energy integrated utilization in system.
Installation of flue gas type lithium bromide absorption chiller with after burning allows rational configuration of generator and chiller/
heater capacity based on the air conditioning system cooling and heating load, safe equipment investment, and improve the en-
ergy integrated utilization in system.
This mode is applicable to the trigeneration system with gas turbine generator
Mode 3: Internal Combustion Engine +Flue Gas/Hot Water Type
Lithium Bromide Absorption Chiller/Heater
Working Principle
Fuel is burned in the engine combustion cham-
Internal
ber to produce mechanical power for driving Fuel combustion engine Power
generator. Engine high temperature flue gas
and jacket hot water is directed to lithium bro- Jacket
Flue gas
water
mide absorption chiller/heaters to offer chilled Flue gas
)hot* water for air conditioning. Engine circu-
lating jacket water is directed to water-water Water-water Flue gas/hot Chilled (hot) water
heat exchanger water LiBr A C/H for air conditioning
heater exchanger to supply heating when the
system is running.
For heating
Application Features
Internal combustion engine flue gas and jacket water can be used directly to operate flue gas/hot water type absorption chiller to
simplify equipment configuration, reduce equipment investment and improve the system integrated energy utilization.
This mode is applicable to the trigeneration system with internal combustion engine driven generators
15
Mode 4: Internal Combustion engine + Flue gashot water operated Absorption chillerHeater
with after burning
Working Principle
Fuel is burned in the engine combustion
Internal
chamber to produce mechanical power for combustion engine Power
driving generator. Engine high temperature
flue gas and jacket hot water is directed to Jacket Flue gas
lithium bromide absorption chiller/heaters water Flue gas
with after burning to offer chilled )hot* water Fuel
for air conditioning. Water-water Flue gas/hot Chilled (hot) water
heat exchanger water LiBr AC/H for air conditioning
Engine circulating jacket water is directed
to water-water heater exchanger to supply
heating when the system is running.
For heating
Application Features
Internal combustion engine flue gas and jacket water can be used directly to operate flue gas/hot water type absorption chiller with
after burning to simplify equipment configuration, reduce equipment investment and improve the system integrated energy utilization.
Installation of flue gas and hot water operated lithium bromide absorption chiller with after burning allows rational configuration of
generator and chiller/heater capacity based on the air conditioning system cooling and heating load, save equipment investment
and improve the system operation economy.
This mode is applicable to the trigeneration system with internal combustion engine driven generators.
High temperature flue gas, High temperature flue gas, hot High temperature flue gas, hot
Heat source High temperature flue gas gas )oil* water water, gas )oil*
Places, where high temp. Places, where high temp. Places, where high temp. Places, where high temp.
flue gas )with low content of flue gas )with low content of flue gas)with low content of flue gas )with low content of
Applications sulphur and foreign matter* is sulphur and foreign matter* is sulphur and foreign matter* sulphur and foreign matter* is
available and air conditioning available and air conditioning and hot water is available and available.
is necessary. is necessary. air conditioning is necessary.
Applied mainly for trigenera- Applied mainly for trigenera- Applied mainly for trigeneration
tion system with gas turbine tion system with gas turbine system with internal combus-
)including micro turbine*, )including micro turbine*, Applied for gas turbine
tion engine as generator drive,
internaI combustion engine, internal combustion engine, generator plant, micro-turbo
Application also can be used for cooling
fuel cell as generator drive, fuel cell as generator drive, )heating* by high temperature generators, and internalan
Features also can be used for cooling also can be used for cooling flue gas )such as flue gas of external combustion engine
)heating* by high temperature )heating* by high temperature generators
industrial kilns* and waste hot
flue gas )such as flue gas of flue gas )such as flue gas of water
industrial kilns* industrial kilns*
16
Flue gas type absorption chiller/heater
Max. design capacity: 3300USRt. Inlet temp. of ue gas
250, ue gas is required to be clean and corrosion-free while
having qualied back pressure for its clearance )induct fan shall be introduced into the system if such back pressure is
not sufcient*. Our standardized series of chillers have 430~520 and 170 for ue gas inlet/outlet temp. respectively,
chilled water inlet/outlet temp. 12/7, hot water inlet/outlet temp. 56/60, cooling water inlet/outlet temp. 32/38.
Please consult with our technical dept. for details and other applications.
Working Principle
Flue gas in
LP Generator
HP Generator Condenser
Cooling water
out
Chilled water
out
llization pipe
Auto de-crysta-
exchanger
Bypass
valve
Chilled water Sampling
valve
Oil trap
Cooling water
Refrigerant water LT heat
exchanger
HP refrigerant vapor
Weak solution
Intermediate solution Check valve Solution pump Refrigerant pump
Strong solution 3 Cooling water
Cooler
in
Refrigerant vapor Vacuum pump Cooler inlet valve
Exhaust
Chilled water inlet temp. (I) HP generator intermediate solution temp. (I,A) HP solution level(C,I)) (A)Alarm
Chilled water outlet temp. (C,I,A) Evaporation temp. (I,A) Flue gas inlet temp. (I) (I)Indication
Cooling water inlet temp. (C,I,A) Chilled water flow (A) Flue gas exhausted temp. (I) (C)Control
Auto purging unit pressure (I) De-crystallization pipe temp. (I,A)
LP generator strong solution temp. (C,I) HP generator pressure (C,I,A)
Condensation temp. (C,I,A) Strong solution spraying temp. (C,I)
17
Evaporator Chilled water from customer )about 12* enters Low Pressure generator )LP generator* Lithium bromide inter-
heat transfer tubes, and evaporates refrigerant water, which is mediate solution, which flows from the HP generator via LT heat
dripped over the tubes. Thus produced chilled water runs from the exchanger and temperature is reduced, is heated by refrigerant
evaporator at temperature about 7 into the external system. Re- vapor, produced in the HP generator, and concentrated to strong
frigerant water absorbs heat from external system, becomes water solution, which flows into the absorber through LT heat exchanger,
vapor, and flows into absorber. produced vapor flows into condenser. Refrigerant vapor, which
flows from HP generator, is condensed by heating the solution,
Absorber Strong lithium bromide solution possesses tremendous
and enters condenser also.
water vapor absorbing capacity drips over tubes, absorbs refriger-
ant vapor, produced in the evaporator, and becomes weak so- Condenser: Cooling water flows through tubes in the condenser
lution. Cooling water from cooling tower enters the heat transfer and condenses the vapor outside the tubes into refrigerant water.
tubes to cool the strong solution distributed outside tubes, and The produced refrigerant water enters the evaporator through U
carries away heat )i.e. heat from external system*. After absorbing pipe as refrigerant element for refrigeration.
water vapor, solution is diluted and sent to HP generator through
Low temperature heat exchanger )LT Heat Exchanger* Strong
heat exchangers.
solution from LP generator exchanges heat with weak solution from
Flue Gas High Pressure generator )HP generator* The flue absorber for raising the temperature of weak solution and recover-
gas is used to heat and boil the lithium bromide weak solution in the ing heat from strong solution.
HP generator. The weak solution is concentrated into intermediate
High temperature heat exchanger )HT Heat Exchanger* In-
solution, which flows into the low pressure generator through HT
termediate solution from HP generator exchanges heat with weak
heat exchanger, and produces high temperature refrigerant vapor,
solution from LT heat exchanger for raising the temperature of weak
which enters LP generator also.
solution further. Heat exchangers reduced the heat requirements of
HP generator, in the mean time, reduced the cooling water require-
ments. Performance of heat exchangers determines the operation
conditions of chiller/heaters.
Heating cycle
Flue gas exhaust
Flue gas in
LP Generator
HP Generator Condenser
Hot water
out
llization pipe
Auto de-crysta-
exchanger Bypass
valve
Sampling
valve
Oil trap
LT heat
Chilled water exchanger
Refrigerant water
HP refrigerant vapor
Weak solution Check valve Solution pump Refrigerant pump
Intermediate solution
Refrigerant vapor Vacuum pump Cooler inlet valve
Exhaust
Hot water inlet tem. (I) HP generator intermediate solution temp. (I,A) HP solution level (C,I)) (A)Alarm
Hot water outlet temp. (C,I,A) Hot water flow (A) Flue gas inlet temp. (I) ( I )Indication
(C)Control
Auto purging unit pressure (I) HP generator pressure (C,I,A) Flue gas exhausted temp. (I)
18
Technical Parameters
Type YX480- 35H2 47H2 58H2 70H2 81H2 93H2 105H2 116H2 145H2 174H2
kW 350 470 580 700 810 930 1050 1160 1450 1740
4
Cooling Capacity 10 kcal/h 30 40 50 60 70 80 90 100 125 150
USRt 99 132 165 198 231 265 298 331 413 496
Connection Diameter )DN* mm 100 100 125 125 150 150 150 150 200 200
Flow m3/h 86 114 143 172 200 229 257 286 357 429
Cooling Water
Pressure Loss mH2O 7 6.5 6.5 7 8 9 5.5 5.5 7.0 7.0
Connection Diameter )DN* mm 100 125 150 150 150 150 200 200 200 250
Flow kg/h 2745 3655 4570 5485 6400 7310 8225 9140 11425 13710
Pressure Loss mmH2O 70 110 90 120 130 140 160 160 150 160
Flue Gas
Inlet Diameter )* mm 250 300 350 350 400 400 450 450 500 600
Outlet Diameter )* mm 250 300 350 350 400 400 450 450 500 600
Electric Power Total Current A 12.6 13.7 13.7 16.8 16.8 16.8 17.4 19.2 19.8 19.8
Length 3800 3820 3808 3820 3840 3840 4340 4340 4810 4885
Overall Dimen- Width mm 2296 2406 2606 2716 2861 2871 2911 3021 3338 3615
sions
Height 2332 2351 2349 2411 2496 2544 2564 2807 2897 3034
Shipping Weight 7.2 8.3 9.8 10.5 11.4 12.5 13.8 14.2 17.1 19.6
t
Operation Weight 8.2 9.6 11.6 12.7 14.2 15.6 17.5 18.4 23 26.4
Note
)1* Values for chilled water,hot water,cooling water in the above table are for nominal operation conditions,and can be properly adjusted in actual operation.
)2* The lowest outlet temp.for chilled water is 5. Inlet temp of cooling water can be adjusted in the range of 18~34.
)3* Flow of chilled/hot water can be adjusted in the range of 60~120%.
)4* Fouling factor on chilled/hot/cooling water side is 0.086m2K/kw)0.0001m2 h /kcal*.
)5* Cooling capacity can be adjusted in the range of 20~100%.
)6* Flue gas temperature for models mentioned in the sheet is 480.
19
Type YX480- 204H2 233H2 262H2 291H2 349H2 407H2 465H2 523H2 582H2
USRt 579 661 744 827 992 1157 1323 1488 1653
Heating Capacity 104kcal/h 140 160 180 200 240 280 320 360 400
Connection Diameter )DN* mm 200 250 250 250 300 300 350 350 350
Flow m3/h 500 572 643 715 857 1000 1143 1286 1429
Cooling Water
Pressure Loss mH2O 7 9 10 9.0 11.5 11 5.5 6.5 7
Connection Diameter )DN* mm 250 250 250 300 350 350 400 400 400
Flow kg/h 15990 18280 20560 22850 27410 31980 36550 41120 45690
Pressure Loss mmH2O 160 160 180 160 170 170 160 155 160
Flue Gas
Inlet Diameter )* mm 600 700 700 700 800 900 900 1000 1000
Outlet Diameter )* mm 600 700 700 700 800 900 900 1000 1000
Electric Power Total Current A 19.8 21.7 26 26.9 31.8 33.5 36.5 36.5 42.3
Electric Power kW 5.9 6.9 7.9 7.9 9.6 10.1 11.1 11.1 12.6
Length 4885 5308 5733 5958 7230 7230 7230 7930 7960
Overall Dimen- Width mm 3825 3785 3925 4010 4437 4712 5022 5132 5559
sions
Height 3150 3280 3320 3470 3760 4060 4240 4420 4570
Shipping Weight 22.1 24.7 25.9 31.1 38.1 44.3 48.7 52.7 60.5
t
Operation Weight 29.4 33.7 36 42 52.3 60.1 66.3 72 82.4
Note
)1* Values for chilled water,hot water,cooling water in the above table are for nominal operation conditions,and can be properly adjusted in actual operation.
)2* The lowest outlet temp.for chilled water is 5. Inlet temp of cooling water can be adjusted in the range of 18~34.
)3* Flow of chilled/hot water can be adjusted in the range of 60~120%.
)4* Fouling factor on chilled/hot/cooling water side is 0.086m2K/kw)0.0001m2 h /kcal*.
)5* Cooling capacity can be adjusted in the range of 20~100%.
)6* Flue gas temperature for models mentioned in the sheet is 480.
20
-
um Bromide Absorption Chiller/Heater
Inlet temp. of ue gas
250, ue gas is required to be clean and corrosion-free while having qualied back pressure
for its clearance )induct fan shall be introduced into the system if such back pressure is not sufcient*. After burning
fuel can be oil )light diesel oil* or gas )NG, city gas etc*. Our standardized series of chillers have 430~520 and 170
for ue gas inlet/outlet temp. respectively, after burning capacity can compensate up to 100% of nominal load capacity
by using split structure, chilled water inlet/outlet temp. 12/7, hot water inlet/outlet temp. 56/60, cooling water
inlet/outlet temp. 32/38. Cooling capacity: 350-5820 kw.
Please consult with our technical dept. for details and other applications.
Cooling Cycle
flue gas out
flue gas in
LPG
Change-over
Flue Gas HPG Valve Condensor
cooling water
out
Burner HPG
Burner flame
llization Pipe
Auto-decrysta-
By-pass
Oil Trap
Refrigerant vapor
Refrigerant water
Non-return Valve Solution Pump Refrigerant Pump
Burner HPG intermediate solution Cooler cooling water
Flue gas HPG intermediate solution in
Vacuum Pump gas out
Chilled water inlet temp. (I) LPG strong solution temp. (C,I) Chilled water flow (A) Strong solution spray temp. (C,I) Gas flue out temp. (I)
Chilled water outlet temp. (C,I,A) Condensation temp. (C,I,A) Burner flue temp. (I,A) Burner HPG solution level (C,I) (I)Display
Cooling water inlet temp. (C,I,A) HPG intermediate solution temp. (I,A) Auto-decrystallization pipe temp. (I,A) Flue gas solution level (C,I) (C)Control
Auto-purge unit pressure (I) Evaporation temp.erature (I,A) HPG pressure (C,I,A) Flue gas inlet temp. (I) (A)Alarm
Heating Cycle
gas flue in
flue gas out
LPG
Burner HPG
Change-over
Valve hot water
out
llization Pipe
Auto-decrysta-
Exchanger
Flue gas By-pass
Oil Trap
Valve
Hot water Sampling
HPG refrigerant vapor Valve
LT Heat
Weak solution Exchanger
Refrigerant vapor
Refrigerant
Non-return valve Solution Pump Refrigerant Pump
Burner HPG intermediate solution
Cooler
Flue gas HPG intermediate solution
Vacuum pump gas out
Hot water inlet temp. (I) HPG intermediate solution temp. (I,A) HPG pressure (C,I,A) Flue gas inlet temp. (I) (I)Display
Hot water outlet temp. (C,I,A) Hot water flow rate (A) Burner HPG solution level (C,I) Gas flue outlet temp. (I) (C)Control
Auto-purge unit pressure (I) Burner flue gas temp. (I,A) Flue gas burner HPG solution level (C,I) (A)Alarm
21
Flue Gas/Steam Type
Lithium Bromide Absorption Chiller
Inlet temp. of ue gas
250, ue gas is required to be clean and corrosion-free while having qualied back pressure
for it's clearance )induct fan shall be introduced into the system if such back pressure is not sufcient*. Our standard-
ized series of chillers have 170 for ue gas outlet temp., steam pressure 0.4~0.8MPa, chilled water inlet/outlet temp.
12/7, cooling water inlet/outlet temp. 32/38. Cooling Capacity for single unit: 350~5820kw.
Please consult with our technical dept. for details and other applications.
Flue gas out
Flue gas in
Steam in
Chilled water
out
H.T Heat
Decrystalliza-
tion pipe
out Bypass
Oil trap
Valve
Sampling
Valve
L.T. Heat
Exchanger
Chilled water Cooling water Refrigerant water HPG. refrigerant vapor Intermediate solution in steam HPG
Weak solution Intermediate solution in flue gas HPG. Strong solution Steam condensate Steam
Chilled water inlet temp. (I) Condensation Temp. (I,A) Flue gas outlet temp. (I) Flue gas inlet temp. (I) (C)Control
Chilled water outlet temp. (C,I,A) Intermediate solution temp.(I,A) Decrystallization pipe temp. (I,A) Steam pressure (C,I,A) (A)Alarm
Cooling water inlet temp. (C,I,A) Solution level in steam HPG (C,I) Pressure in HPG (C,I,A) Steam condensate temp. (I) (I)Indication
Purging unit pressure (I) Evaporation temp. (I,A) Strong solution spraying temp (C,I)
Strong solution temp.in LPG (C,I) Chilled water flow (A) Solution level in flue gas HPG (C,I)
22
Flue Gas/Hot Water Type
Lithium Bromide Absorption Chiller/Heater
Inlet temp. of ue gas
250, ue gas is required to be clean and corrosion-free while having qualied back pres-
sure for it's clearance )induct fan shall be introduced into the system if such back pressure is not sufcient*. Hot water
returning temp.
92 )hot water inlet temp.
98*, chilled water outlet temp.
7, cooling water inlet/outlet temp.
28/34. Cooling capacity for single unit: 350-3490 kw.
Please consult with our technical dept. for details and other applications.
LPG
Heat source
Hot-water Flue-gas HPG Condenser
Cooling water
out
Chilled water
out
lization piping
Decrysta-
Bypass
Weak solution valve
Cooling water Sampling
valve
Intermediate solution L.T. heat
Refrigerant water exchanger
Strong solution
HPG refrigerant vapor
Non-return valve Solution pump Refrigerant pump
Hot water Cooler Cooling water
Refrigerant vapor in
Vacuum pump Discharge
Chilled water inlet temp. (I) Strong solution temp. in LPG (C,I) Chilled water flow (A) Solution level in HPG (C,I) (A)Alarm
Chilled water out temp. (C,I,A) Condensation temp. (C,I,A) Decrystalizaton piping temp. (I,A) Flue-gas inlet temp. (I) (I)Display
Cooling water inlet temp.(C,I,A) Intermediate solution temp.in HPG (I,A) Pressure in HPG (C,I,A) Flue-gas outlet temp. (I) (C)Control
Puring unit pressure(I) Evaporation temp. (I,A) Strong solution spraying temp. (C,I) Heat source hot-water outlet temp. (C,I)
LPG
Condenser
Flue-gas HPG
Hot water
out
lization piping
De-crysta-
Bypass
Oil trap
valve
Sampling
valve
Hot-water L.T. heat
Weak solution exchanger
Refrigerant water
Strong solution in HPG Solution pump Refrigerant pump
Non-return valve
Refrigerant vapor in hpg Cooler
Refrigerant vapor Vacuum pump Discharge
Hot water inlet temp. (I) Puring unit pressure(I) Hot water flow rate (A) Solution level in HPG (C,I) Flue-gas outlet temp. (I) (I)Display
Hot water out temp. (C,I,A) Strong solution temp. in HPG (I,A) Pressure in HPG (C,I,A) Flue-gas inlet temp. (I) (A)Alarm (C)Control
23
!"
Lithium Bromide Absorption Chiller/Heater
Inlet temp. of ue gas
250, ue gas is required to be clean and corrosion-free while having qualied back pressure
for its clearance )induct fan shall be introduced into the system if such back pressure is not sufcient*. After burning
fuel can be oil )light diesel oil* or gas )NG, city gas etc*. Hot water returning temp.
92 )hot water inlet temp.
98*,
chilled water outlet temp.
7, cooling water inlet/outlet temp. 28/34. Cooling capacity for single unit: 350-3490 kw.
Please consult with our technical dept. for details and other applications.
Flue out
Gas flue in
Source
hot water out
LPG
Source
hot water in Gas flue Condensor
HPG
Cooling water
out
Burner HPG
By pass
Strong solution valve
Oil trap
Refrigerant
Burner HPG intermediate solution
Non-return valve Solution pump Refrigerant pump
Gas flue HPG intermediate solution Cooling water
Cooler
Hot water in
Vacuum pump Gas out
Chilled water inlet temp. (I) Condensation temp. (C,I,A) Decrystallization pipe temp. (I,A) Gas flue inlet temp. (I) ( I )Display
Chilled water outlet temp. (C,I,A) HPG intermediate solution temp. (I,A) HPG pressure (C,I,A) Gas flue out temp. (I) (C)Control
Cooling water inlet temp. (C,I,A) Evaporation (I,A) Strong solution spray temp. (C,I) Source hot water out temp. (C,I) (A)Alarm
Purge unit pressure (I) Chilled water flow rate (A) Burner HPG solution level (C,I)
LPG strong solution temp. (C,I) Burner flue out temp. (I,A) Gas flue burner solution level (C,I)
Flue out
Gas flue in
LPG
Gas flue
HPG Condensor
Burner HPG
7
Absorber Evaporator Absorber Hot water
Burner flame HT heat in
exchanger
Auto purge unit
By pass
Oil trap
Refrigerant vapor
Refrigerant
Non-return valve Solution pump Refrigerant pump
Burner HPG strong solution
Cooler
Gas flue HPG strong solution Vacuum pump Gas out
Hot water inlet temp. (I) HPG intermediate solution temp. (I,A) HPG pressure (C,I,A) Gas flue inlet temp. (I) ( I )Display
Hot water outlet temp. (C,I,A) Hot water flow (A) Burner HPG solution level (C,I) Gas flue out temp. (I) (C)Control
Purge unit pressure (I) Burner flue out temp. (I,A) Gas flue HPG solution level (C,I) (A)Alarm
24
2 H2 Type Direct Fired Lithium Bromide
Absorption Chiller/Heater
25
Performance Parameters Working Principle
This direct-red absorption chiller/heater is operated by heat from fuel and gas burner and with LiBr solution as the ab-
sorbent. It consists of high pressure generator, low pressure generator, condenser, evaporator, absorber, high and low
temperature heat exchangers, and canned motor and vacuum pumps, is a combination of shell and tube heat exchang-
ers. It is operated under vacuum conditions by vacuum pump and auto-purging unit.
Cooling Cycle
Flue gas out
10
12 LP
generator
14
Change-over Condenser
HP generator valve 5
6
Cooling water
out
4 11
9
7
Auto decrysta
llization pipe
Chilled water inlet temp. (I) LPG strong solution temp. (C,I) Chilled water flow (A) HPG pressure (C,I,A) (I)--Indication
Chilled water outlet temp. (C,I,A) Condensation temp. (C,I,A) Flue gas exit temp. (I,A) HPG solution level (C,I) (C)--Control
Cooling water inlet temp. (C,I,A) HPG intermediate solution temp. (I,A) De-crystallization pipe temp. (I,A) (A)--Alarm
Auto-purging unit pressure (I) Evaporation temp. (I,A) HPG pressure (C,I,A)
Absorber LiBr solution, as an absorbent, possesses strong Low Pressure Generator )hereinafter LPG* The intermedi-
absorbing capacity to water vapor and is sprayed on the heat-ex- ate solution, which is cooled down and enters the LPG, is once
changing tubes of the absorber to absorb the vapor generated in again heated by vapor from HPG and vapor generated. The solu-
the evaporator and is then diluted. Heat of solution )i.e. heat from tion is further concentrated. The strong solution flows back to the
the external system* is carried away by the cooling water from the absorber after being cooled down through heat-exchanging in the
cooling tower through heat exchange tubes in the absorber, and low-temperature heat exchanger. The vapor thus generated enters
diluted solution collects under the bottom of the absorber, after the condenser. The vapor from HPG is condensed to water after
being purged by solution pump and heated in the heat exchanger, heating the solution and enters the condenser after being regu-
it enters the HPG. lated.
26
Condenser Cooling water flows through tubes in the condenser HT Heat Exchanger High temperature heat exchanger is used
and condenses the vapor outside the tubes into refrigerant water. to exchange heat between the intermediate solution from HPG
The produced refrigerant water enters the evaporator through U and the weak solution after being heated in the low temperature
pipe as refrigerant element for refrigeration. heat exchanger, to further increase the temperature of weak solu-
tion.
LT Heat Exchanger Low temperature heat exchanger is used
to exchange heat between the solution from LPG and weak solu- Heat exchangers are used to decrease the heat consumption in
tion from absorber to increase the temperature of weak solution the HPG and reduce the cooling water load required for lowering
and thus to recover the heat of strong solution. the temperature of strong solution, which is vital to the energy-
saving efficiency of the unit.
Heating Cycle
Flue gas out
10
12
LP
14 generator
Change-over
HP generator valve 5 Condenser 6
Change-over 2
Hot water
valve out
4 11
9
7
Auto decrysta
llization pipe
exchanger
Oil trap
Flame By-pass
valve
Hot water
Sampling
Weak solution LT heat valve
exchanger
HPG concentrated solution 8
13
Refrigerant water
HPG refrigerant vapor Check valve Solution pump Refrigerant pump
Flue gas Cooler 3
Refrigerant vapor Vacuum pump Cooler inlet valve
Exhaust
Hot water inlet temp. (I) LPG strong solution temp. (C,I) Evaporation temp. (I,A) HPG pressure (C,I,A) (I)--Indication
Hot water outlet temp. (C,I,A) Condensation temp. (C,I,A) Hot water flow (A) Strong soltuion spray temp. (C,I) (C)--Control
Cooling water inlet temp. (C,I,A) HPG intermediate solution Flue gas exit temp. (I,A) HPG solution level (C,I) (A)--Alarm
Auto-purging unit pressure (I) temp. (I,A) De-crystallization pipe temp. (I,A)
27
Table of Technical Parameters (SI)
Model DF- 99H2 132H2 165H2 198H2 231H2 265H2 298H2 331H2 413H2
kW 350 470 580 700 810 930 1050 1160 1450
Cooling Capacity 104kcal/h 30 40 50 60 70 80 90 100 125
USRt 99 132 165 198 231 265 298 331 413
Heating Capacity 104kcal/h 24 32 40 48 56 64 72 80 100
Inlet/Outlet Temp.)Chilled Water* 12 7
Inlet/Outlet Temp.)Heated Water* 56 60 )50 60*
Chilled/
Hot Flow Rate m3/h 60)24* 80)32* 100)40* 120)48* 140)56* 160)64* 180)72* 200)80* 250)100*
Water
Pressure Loss mH3O 4.4)0.7* 4.5)0.72* 4.7)0.76* 5.7)0.92* 5.6)0.9* 6.2)1.0* 8.8)1.41* 8.8)1.41* 3.8)0.61*
Connection Diameter)DN* mm 100 100 125 125 150 150 150 150 200
Inlet/Outlet Temp. 32 38
Cooling Flow Rate m3/h 85 113 141 170 198 226 255 283 353
Water Pressure Loss mH3O 6.5 6.2 6.4 6.9 7.5 7.7 5.3 5.3 7.1
Connection Diameter)DN* mm 100 125 150 150 150 150 200 200 200
Cooling 21.3 28.5 35.6 42.7 49.8 56.9 64 71.1 88.9
Light Oil Consumption kg/h
)10400kcal/ Heating 24.6 32.8 41 49.2 57.4 65.6 73.8 82 102.5
kg*
Connection Diameter)G* in 3/8"
Cooling 22.2 29.6 37 44.4 51.8 59.2 66.6 74 92.5
Heavy Oil Consumption kg/h
)10000kcal/ Heating 25.6 34.1 42.7 51.2 59.7 68.2 76.8 85.3 106.6
kg*
Connection Diameter)G* in 2"
Natural Gas Consumption Cooling 20.2 26.9 33.6 40.3 47.1 53.8 60.5 67.2 84
Nm3/h
)11000kcal/ Heating 23.3 31 38.8 46.5 54.3 62 69.8 77.5 96.9
Nm3
Den- Inlet Pressure mmH3O 150~2500 250~2500 350~2500 400~3000
sity=0.64 * Connection Diameter)G* mm)in* 1 1/2" 2" 65
Cooling 3
324 432 540 648 755 865 970 1080 1350
Air Flow for Combustion)30* m /h
Heating 372 496 620 744 868 992 1120 1240 1550
Exhaust Connection Dimension mm 170250 170250 200300 200300 250360 250360 250360 250450 250500
Power Supply 3 - 380VAC - 50Hz
Light Oil 14.7 15.4 15.4 19.6 19.6 20.2 20.8 22.6 24.9
Total Current Heavy Oil A 16.9 18.9 18.9 27.6 27.6 27.6 28.6 46.5 46.5
Electri- Gas 14.7 15.4 15.4 19.6 19.6 20.2 20.8 22.6 24.9
cal Data
Light Oil 4.4 5 4.95 6.4 6.4 6.8 7 7.3 8.5
Electric Heavy Oil kW 8.58 9.1 9.1 10.76 10.76 10.76 11 20.67 21.14
Power
Gas 4.4 5 4.95 6.4 6.4 6.8 7 7.3 8.5
Length 3780 3800 3810 3820 3840 3840 4340 4340 4810
Overall
Dimen- Width mm 1954 2113 2138 2282 2439 2449 2457 2615 2805
sions
Height 2332 2351 2349 2411 2496 2544 2564 2807 2897
Shipping Weight 6.7 7.8 8.9 9.5 10.3 11 11.8 12.2 14.3
t
Operating Weight 8.2 9.6 11.1 12.2 13.6 14.5 15.6 16.5 20.3
Note
)1* Values for chilled/heated/cooling water in above table are for nominal conditions and can be properly adjusted in actual operation.
)2* The lowest outlet temperature of chilled water is 5
)3* Chilled/Heated water can be adjusted in range of 60~120%.
)4* On the chilled/heated/cooling water side, scale factor is 0.086m2K/kW )0.0001m2h/kcal*.
)5* Cooling/Heating capacity can be adjusted in range of 30~105% for Oil-fired type, 25~105% for Gas-fired type.
)6* Nominal discharge temperature of flue gas: 170 for cooling mode, 155 for heating mode.
)7* The maximum chilled/heated/cooling water box pressure bearing capacity of normal pressure chiller is 0.8 MPa)G*.
)8* Heat values indicated in the table are low heat values.
28
496H2 579H2 661H2 744H2 827H2 992H2 1157H2 1323H2 1488H2 1653H2 1984H2 2646H2 3307H2
1740 2040 2330 2620 2910 3490 4070 4650 5230 5820 6980 9300 11630
150 175 200 225 250 300 350 400 450 500 600 800 1000
496 579 661 744 827 992 1157 1323 1488 1653 1984 2646 3307
120 140 160 180 200 240 280 320 360 400 480 640 800
12 7
56 60 )50 60*
300)120* 350)140* 400)160* 450)180* 500)200* 600)240* 700)280* 800)320* 900)360* 1000)400*1200)480*1600)640* 2000)800*
3.8)0.61* 4.1)0.66* 4.9)0.79* 6.6)1.06* 6.4)1.03* 8.4)1.35* 8.1)1.30* 8.8)1.41* 12.4)1.99*11.8)1.89* 2.6)0.42* 5.0)0.6* 7.5)1.1*
200 200 250 250 250 300 300 350 350 350 400 400 450
32 38
424 495 565 636 707 848 989 1130 1272 1413 1696 2264 2830
6.6 6.8 8.7 9.6 9.1 11.1 11 5.2 6.2 6.6 8.6 12 16
250 250 250 250 300 350 350 400 400 400 450 500 600
106.7 124.4 142.2 160 177.8 213.3 248.9 284.4 320 355.5 426.6 568.8 711
123 143.5 164 184.5 205 246 287 328 369 410 492 656 820
1" 2-1"
111 129.5 148 166.5 185 222 259 296 333 370 444 592 740
128 149.3 170.6 191.9 213.3 255.9 298.6 341.2 383.9 426.5 511.8 682.4 853
2" 2-2"
316.9 369.7 422.5 475.4 528.2 633.8 739.4 845.1 950.7 1056.3 1267.6 1690.4 2113
365.5 426.4 487.3 548.2 609.1 731 852.8 974.6 1096.5 1218.3 1462 1949.6 2437
800-3000 1100~3000 1300~3000 1500~3000
80 100 125 150 2-125 2-150
100.8 117.6 134.4 151.3 168.1 201.7 235.3 268.9 302.5 336.1 403.3 537.6 672
116.3 135.7 155.1 174.4 193.8 232.6 271.3 310.1 348.9 387.6 465.2 620 775
400~3000 550~3000 800~3000 1000~3000 1200~3000
65 80 100 125 2-80 2-100
1620 1890 2160 2430 2700 3240 3780 4320 4860 5400 6480 8850 11000
1860 2170 2480 2790 3100 3720 4340 4960 5580 6200 7440 9950 12500
300500 300500 360550 360550 400600 420700 420700 550750 550750 550750 650800 2-550750
3 - 380VAC - 50Hz
28.9 28.9 30.8 43.5 43.5 58.6 59.5 62.5 62.5 68.3 90.5 123.1 134.7
48.8 50.8 50.8 61.1 62.1 71 89.6 91.3 91.6 111.4 124.4 180.7 220.9
28.9 28.9 30.8 41 41 55.8 57.5 60.5 76.5 82.3 120.9 119.1 162.7
11.8 11.8 12.8 17.9 17.9 24.6 25.1 26.1 24.6 24.6 41.45 50.8 50.8
22.48 22.95 24.1 28.19 28.1 33.71 44 46.24 46.43 48.57 56.29 91.73 96.39
11.4 11.4 12.4 16.9 16.9 23.6 24.1 25.1 32.1 33.6 38.1 48.8 65.8
4885 4885 5308 5733 5960 7230 7230 7230 7930 7960 9190 9850 11580
2966 3050 3183 3357 3320 3851 4000 4220 4329 4607 4527 4960 5220
3034 3150 3218 3221 3320 3441 3720 3864 3864 4214 4224 5160 5160
16.7 18.2 20.8 22 26 31.8 36.2 41.2 43.9 51.1 59.3 89.6 115.2
23.4 25.1 28.9 31.1 36.3 45.1 51.5 58.4 62 71.6 84.3 113 145.2
)9* Consumption of fuel not indicated in the table can be calculated=Low heat value indicated in the table/Low heat value of adopted fuelconsumption
indicated in the table.
)10* Gas inlet pressure indicated in the table is the pressure at the outlet of ball valve then the chiller is under operation..
)11* Gas Relative Density = Gas density/Air density
)12* Overall dimensions indicated in the table include rack dimensions.
)13* The shipping weight includes the rack weight, exluding solution weight.
)14* When referring to Chilled/Heated Water sub-region, data indicated in the round brackets are parameters in heating mode with inlet/outlet tempera-
ture difference as 10.
29
3 Steam-Operated Double Effect
Lithium Bromide Absorption Chiller
H2-type steam operated double effect lithium bromide absorption chiller is a kind of large-size industrial facility with steam as the driving
energy and lithium bromide solution as the absorbent and water as refrigerant.
H2-type steam operated double effect units, using steam as the energy source, not only reduces greatly the cost for electricity and op-
eration fees in regions where there are rich steam resources, but also compensates the peak-valley load difference. When the hot sum-
mer rolls in, shortage of electric power will poses a great worry for various cities. Concentrated consumption of power by air-conditioners
is the sticking point for such a seasonal problem, for which, H2-type steam operated double effect chillers offer an attractive solution.
The most attractive feature of Shuangliang H2-type steam operated double effect chiller is its stunning performance in energy saving.
High COP of 1.33 and provenly high efficiency rank Shuangliang H2-type steam operated chiller in the leading position worldwide.
Shuangliang H2-type steam operated double effect chillers are widely applied in industries, such as precision machinery manufacturing,
instruments & meters, aviation & aerospace, textiles, electronics, electric power, metallurgy, pharmaceuticals, cigarettes, chemicals, hos-
pitals, food, etc. By utilizing dozens of patented technologies with features of extremely high energy efficiency and outstanding environ-
mental effects, in addition to her customer service experience of over 28 years, Shuangliang guarantees to reward her users with optimal
returns.
30
Working Principle
The steam operated double effect LiBr absorption chiller uses steam as the energy, LiBr solution as absorbent, and
water as refrigerant. It consists of major parts such as high pressure generator, low pressure generator, condenser,
evaporator, absorber, high and low temperature heat exchangers, condensate heat exchanger, etc., as well as auxiliary
parts such as canned motor pumps )solution pump and refrigerant pump*, vacuum pump and purging unit. It is a com-
bination of shell and tube heat exchangers. It is operated under vacuum conditions by vacuum pump and purging unit.
Cooling Cycle
LP generator
HP genertor
Motor regulating valve Condenser
Steam
Cooling water
out
Supplied by customer
Chilled water
out
Auto Decrystallization pipe
High temperature
heat exchanger
Absorber Evaporator Absorber
Steam Chilled water
Condensate in
Condensate
Auto purging unit
out By-pass
Oil trap
Chilled water inlet temp. (I) Low pressure generator Strong solution temp. (C,I) Chilled water flow (A) Strong solution spray temp. (C,I) ( C ) Control
Chilled water outlet temp. (C,I,A) Condensation temp. (C,I,A) Steam condensate temp. (I) High pressure generator solution level(C,I) ( A ) Alarm
Cooling water inlet temp. (C,I,A) High pressure generator intermediate solution temp. (I,A) De-crystallization pipe temp. (I,A) Steam pressure (C,I,A) ( I ) Indication
Auto-purging unit pressure (I) Evaporation temp. (I,A) High pressure generator pressure(C,I,A)
31
# !
Model ST- 99H2H 132H2H 165H2H 198H2H 231H2H 265H2H 298H2H 331H2H 413H2H 496H2H
kW 350 470 580 700 810 930 1050 1160 1450 1740
4
Cooling Capacity 10 kcal/h 30 40 50 60 70 80 90 100 125 150
USRt 99 132 165 198 231 265 298 331 413 496
Inlet/outlet Temp. 12 7
Chilled Water
Flow Rate m3/h 60 80 100 120 140 160 180 200 250 300
Pressure Loss mH2HO 5.5 5.5 5.7 5.8 7.8 7.3 7.9 10.9 11 5.5
Connection Diameter)DN* mm 100 100 125 125 150 150 150 150 200 200
Inlet/outlet Temp. 32 38
Cooling Water
Flow Rate m3/h 85 113 142 170 198 227 255 283 354 425
Pressure Loss mH2HO 7.2 6.9 7 7.4 9 8.9 8.5 6 6.6 8.4
Connection Diameter)DN* mm 100 125 150 150 150 150 200 200 200 250
Consumption kg/h 372 496 620 744 868 992 1116 1240 1550 1860
Total Current A 12.6 13.7 13.7 13.7 16.8 16.8 16.8 17.4 19.2 19.8
Electric Power kW 3.8 4.2 4.2 4.2 5.0 5.0 5.0 5.2 5.5 5.9
Dimensions
Length 3810 3810 3790 3790 3820 3840 3890 4357 4357 4895
Overall
Width mm 1942 2027 2060 2060 2183 2308 2355 2332 2450 2558
Height 2152 2170 2169 2217 2231 2316 2364 2384 2702 2717
Shipping Weight 6.4 6.9 7.3 7.9 8.3 9 9.6 10.1 11 13.1
t
Operating Weight 7.7 8.5 9.1 9.8 10.3 11.4 12.1 13.4 14.6 17.4
Notes
)1* Values for steam,chilled water and cooling water in above table are for nominal conditions and can be properly adjusted in actual operation.
With the inlet/outlet temperature of cooling water as 30/36, the steam consumption is only 12.2kg/)104kcal/h*, and the COP value is 1.43.
)2* Steam pressure 0.8 Mpa)G* refers to the inlet pressure without any valve pressure loss. The lowest outlet temperature of chilled water is 5
)3* Cooling capacity can be adjusted in range of 20~100% , and chilled water can be adjusted in range of 60~120%.
32
Model ST- 579H2H 661H2H 744H2H 827H2H 992H2H 1157H2H 1323H2H 1488H2H 1653H2H 1984H2H
kW 2040 2330 2620 2910 3490 4070 4650 5230 5820 6980
4
Cooling Capacity 10 kcal/h 175 200 225 250 300 350 400 450 500 600
USRt 579 661 744 827 992 1157 1323 1488 1653 1984
Inlet/outlet Temp. 12 7
Chilled Water
Flow Rate m3/h 350 400 450 500 600 700 800 900 1000 1200
Pressure Loss mH2HO 5.2 5.3 6.1 8.2 8.1 11.5 10.5 11.1 15.3 14.1
Connection Diameter)DN* mm 200 250 250 250 300 300 350 350 350 400
Inlet/outlet Temp. 32 38
Cooling Water
Flow Rate m3/h 496 567 638 709 850 992 1134 1275 1417 1700
Pressure Loss mH2HO 8.1 8.7 10.2 10.8 11.2 14.3 14.1 5.9 7.6 6.9
Connection Diameter)DN* mm 250 250 250 300 300 350 350 400 400 450
Consumption kg/h 2170 2480 2790 3100 3720 4340 4960 5580 6200 7440
Steam Pipe Diameter)DN* mm 80 80 100 100 100 125 125 150 150 150
Electric Modulating Valve mm 65 80 80 80 80 100 100 100 125 125
Dia.)DN*
Steam Condensate Pipe mm 40 40 40 40 50 50 50 65 65 65
Diameter)DN*
Power Supply 3 - 380VAC - 50Hz
Electrical
Data
Total Current A 19.8 20.8 21.7 26 28.5 31.8 33.5 36.5 42.3 44.9
Electric Power kW 5.9 6.5 6.9 7.9 8.9 9.6 10.1 11.1 12.6 14.1
Dimensions
Length 4918 4918 5335 5805 5795 6525 6525 6813 7513 7570
Overall
Width mm 2740 2760 2815 2800 2930 3209 3334 3354 3354 3756
Height 2854 2970 3038 3041 3335 3381 3669 3804 3804 4254
)4* On the chilled water/cooling water side, scale factor is 0.086m2K/kW )0.0001m2h/kcal*.
)5* The maximum chilled/cooling water box pressure bearing capacity of normal pressure chiller is 0.8 MPa)G*.
)6* The unit is transported with rack of 180mm in height, and for the units ST-992H2H and above, submerged type rack will be adopted, extra 60mm
shall be included.
)7* The shipping weight includes the rack weight, exluding solution weight.
33
Table of Technical Parameters (0.6MPa) (SI)
Model ST- 99H2 132H2 165H2 198H2 231H2 265H2 298H2 331H2 413H2 496H2 579H2
kW 350 470 580 700 810 930 1050 1160 1450 1740 2040
4
Cooling Capacity 10 kcal/h 30 40 50 60 70 80 90 100 125 150 175
USRt 99 132 165 198 231 265 298 331 413 496 579
Inlet/outlet Temp. 12 7
Chilled Water
Flow Rate m3/h 60 80 100 120 140 160 180 200 250 300 350
Pressure Loss mH2O 4.4 4.5 4.7 5.7 5.6 6.2 8.8 8.8 3.8 3.8 4.1
Connection Diameter)DN* mm 100 100 125 125 150 150 150 150 200 200 200
Inlet/outlet Temp. 32 38
Cooling Water
Flow Rate m3/h 86 114 143 172 200 229 257 286 357 429 500
Pressure Loss mH2O 6.6 6.3 6.5 7 7.6 7.8 5.4 5.4 7.2 6.6 6.9
Connection Diameter)DN* mm 100 125 150 150 150 150 200 200 200 250 250
Consumption kg/h 376 501 627 752 877 1003 1128 1253 1566 1880 2193
Pressure)G*
Steam Pipe Diameter)DN* mm 40 50 50 65 65 65 65 80 80 80 80
Electric Modulating Valve mm 40 40 40 50 50 50 50 65 65 65 80
Dia.)DN*
Steam Condensate Pipe mm 25 25 25 25 32 32 32 32 40 40 40
Diameter)DN*
Power Supply 3 - 380VAC - 50Hz
Electrical
Data
Total Current A 12.6 13.7 13.7 16.8 16.8 16.8 17.4 19.2 19.8 19.8 19.8
Electric Power kW 3.8 4.2 4.2 5.0 5.0 5.0 5.2 5.5 5.9 5.9 5.9
Dimensions
Length 3810 3810 3790 3820 3840 3840 4357 4357 4885 4918 4918
Overall
Width mm 1942 2027 2060 2183 2308 2355 2332 2450 2558 2740 2760
Height 2152 2170 2169 2231 2316 2364 2384 2627 2717 2854 2970
Shipping Weight 6.5 7.1 7.5 8.1 9 9.4 10.1 10.5 12.8 14.5 15.6
t
Operating Weight 7.8 8.7 9.3 10.1 11.4 11.9 13.4 14 17.1 20 21.3
Notes
)1* Values for steam,chilled water and cooling water in above table are for nominal conditions and can be properly adjusted in actual operation.
With the inlet/outlet temperature of cooling water as 30/36, the steam consumption is only 12.35kg/)104kcal/h*, and the COP value is 1.41.
)2* Steam pressure 0.6 Mpa)G* refers to the inlet pressure without any valve pressure loss. The lowest outlet temperature of chilled water is 5
)3* Cooling capacity can be adjusted in range of 20~100% , and chilled water can be adjusted in range of 60~120%.
)4* On the chilled water/cooling water side, scale factor is 0.086m2K/kW )0.0001m2h/kcal*.
34
Model ST- 661H2 744H2 827H2 992H2 1157H2 1323H2 1488H2 1653H2 1984H2 2646H2 3307H2
kW 2330 2620 2910 3490 4070 4650 5230 5820 6980 9300 11630
4
Cooling Capacity 10 kcal/h 200 225 250 300 350 400 450 500 600 800 1000
USRt 661 744 827 992 1157 1323 1488 1653 1984 2646 3307
Inlet/outlet Temp. 12 7
Chilled Water
Flow Rate m3/h 400 450 500 600 700 800 900 1000 1200 1600 2000
Pressure Loss mH2O 4.9 6.6 6.4 8.4 8.1 8.8 12.4 11.8 2.6 5 7.5
Connection Diameter)DN* mm 250 250 250 300 300 350 350 350 400 400 450
Inlet/outlet Temp. 32 38
Cooling Water
Flow Rate m3/h 572 643 715 858 1001 1144 1287 1430 1716 2288 2860
Pressure Loss mH2O 8.8 9.8 9.2 11.3 11.2 5.2 6.3 6.7 8.7 12 16
Connection Diameter)DN* mm 250 250 300 350 350 400 400 400 450 500 600
Consumption kg/h 2506 2819 3133 3759 4386 5012 5639 6265 7518 10024 12530
Pressure)G*
Steam Pipe Diameter)DN* mm 100 100 100 125 125 150 150 150 150 200 200
Electric Modulating Valve mm 80 80 100 100 100 125 125 125 150 150 200
Dia.)DN*
Steam Condensate Pipe mm 40 40 50 50 50 65 65 65 65 80 100
Diameter)DN*
Power Supply 3 - 380VAC - 50Hz
Electrical
Data
Total Current A 21.7 26 26.9 31.8 33.5 36.5 36.5 42.3 44.9 71.8 95.4
Electric Power kW 6.9 7.9 7.9 9.6 10.1 11.1 11.1 12.6 14.1 23.6 26.4
Dimensions
Length 5335 5733 5795 6525 6525 6813 7513 7513 9118 9500 11580
Overall
Width mm 2815 2800 2930 3209 3334 3354 3354 3756 3766 4400 4400
Height 3038 3041 3260 3381 3669 3804 3804 4154 4164 5100 5100
)5* The maximum chilled/cooling water box pressure bearing capacity of normal pressure chiller is 0.8 MPa)G*.
)6* The unit is transported with rack of 180mm in height, and for the units ST-827H2 and above, submerged type rack will be adopted, extra 60mm
shall be included.
)7* The shipping weight includes the rack weight, exluding solution weight.
35
Table of Technical Parameters (0.4MPa) (SI)
231DH2L
1157H2L
1323H2L
132H2L
165H2L
198H2L
265H2L
331H2L
413H2L
496H2L
579H2L
661H2L
827H2L
992H2L
83H2L
99H2L
Model SXZ4-
kW 290 350 470 580 700 810 930 1160 1450 1740 2040 2330 2910 3490 4070 4650
4
Cooling Capacity 10 kcal/h 25 30 40 50 60 70 80 100 125 150 175 200 250 300 350 400
USRt 83 99 132 165 198 231 265 331 413 496 579 661 827 992 1157 1323
Chilled
Inlet/Outlet Temp. 12 7
Water
Flow Rate m3/h 50 60 80 100 120 140 160 200 250 300 350 400 500 600 700 800
Cooling
Inlet/Outlet Temp. 32 38
Water
3
Flow Rate m /h 72 86 115 144 173 202 230 288 360 432 504 576 720 864 1008 1152
Consumption kg/h 319 383 510 638 765 893 1020 1275 1594 1913 2231 2550 3188 3825 4463 5100
Steam
Notes
)1* Values for steam,chilled water and cooling water in above table are for nominal conditions and can be adjusted in proper actual operation.
With the inlet/outlet temperature of cooling water as 30/36, the steam consumption is only 12.6kg/)104kcal/h*, and the COP value is 1.38.
)2* Steam pressure 0.4 Mpa)G* refers to the inlet pressure without any valve pressure loss. The lowest outlet temperature of chilled water is 5
)3* Cooling capacity can be adjusted in range of 20~100% , and chilled water can be adjusted in range of 60~120%.
)4* On the chilled water/cooling water side, scale factor is 0.086m2K/kW )0.0001m2h/kcal*.
)5* The maximum chilled/cooling water box pressure bearing capacity of normal pressure chiller is 0.8 MPa)G*.
36
4 Steam-Operated Single Effect
Lithium Bromide Absorption Chiller
Steam-operated single effect lithium bromide absorption chiller is a kind of large-size refrig-
eration facility with low pressure steam as the driving energy and lithium bromide solution
as the absorbent and water as refrigerant. Steam single effect chiller, using steam or waste
steam as the energy source, not only reduces greatly the cost for electricity but also pos-
sess great economic potential in applications where this source of energy is available.
37
Working Principle
Cooling Cycle
Motor regulating valve
Steam in
Generator
Condenser
Supplied by customer
Condensate out
Cooling water
Condensate heat exchanger out
Heat exchanger
Chilled water
out
Check valve
llization pipe
Auto decrysta-
By-pass
Auto purging unit
valve
Oil trap
Sampling
Steam valve
Condensate
Cooling water Discharge
Chilled water inlet temperature (I) Condensate temperature (I) Condensation temperature (I,C,A) Chilled water flow (A) ( I )Indication
Chilled water outlet temperature (I,C,A) Solution spray temperature (I,C) Evaporation temperature (I,A) Vacuum pressure (I) ( C )Control
Cooling water inlet temperature (I,C,A) Strong solution outlet temperature (I,C,A) De-crystallization temperature (I,A) Steam pressure (I,C,A) ( A )Alarm
38
# !
Model SS- 99H2 165H2 265H2 331H2 413H2 496H2 579H2 661H2 744H2 827H2 992H2 1157H2 1323H2
kW 350 580 930 1160 1450 1740 2040 2330 2620 2910 3490 4070 4650
4
Cooling Capacity 10 kcal/h 30 50 80 100 125 150 175 200 225 250 300 350 400
USRt 99 165 265 331 413 496 579 661 744 827 992 1157 1323
Inlet/outlet Temp. 12 7
Chilled Water
Flow Rate m3/h 60 100 160 200 250 300 350 400 450 500 600 700 800
Pressure Loss mH2O 4.4 5.2 5.3 8.2 3.5 3.5 3.5 4.6 5.8 5.8 7.9 8.1 7.3
Connection Diameter)DN* mm 100 125 150 150 200 200 200 250 250 250 300 300 350
Inlet/outlet Temp. 32 40
Cooling Water
Flow Rate m3/h 85 142 226 283 354 425 495 566 637 708 849 991 1132
Pressure Loss mH2O 7.3 7.9 8 10.2 9.0 8.4 8.4 10.5 6.5 6.5 7.9 8.1 7.5
Connection Diameter)DN* mm 100 150 200 200 200 250 250 250 300 300 350 350 400
Consumption kg/h 684 1140 1824 2280 2850 3420 3990 4560 5130 5700 6840 7980 9120
Total Current A 13.6 14.7 17.8 20.2 20.8 20.8 20.8 22.7 27.0 27.9 32.8 34.5 37.5
Electric Power kW 4.15 4.55 5.35 5.85 6.25 6.25 6.25 6.85 8.25 8.25 9.95 10.45 11.45
Dimensions
Length 3950 3890 3955 4475 5080 5138 5150 5590 5960 5985 6695 6715 6855
Overall
Width mm 1592 1698 2010 2132 2194 2380 2475 2476 2521 2555 2700 2855 3215
Height 2346 2406 2773 2804 2985 3210 3318 3381 3425 3643 3759 4100 4495
Operating Weight 7.2 8.0 10.6 12.8 15.2 17.4 2.0 22.4 24.2 26.6 31.6 36.2 40.0
t
Shipping Weight 5.9 6.3 8.2 9.7 11.6 13.0 14.6 16.8 17.8 19.6 22.8 26.1 28.8
Notes
)1* Values for steam,chilled water and cooling water in above table are for nominal conditions and can be properly adjusted in actual operation.
)2* The lowest outlet temprature of chilled water is 5.
)3* Cooling capacity can be adjusted in range of 20~100% , and chilled water can be adjusted in range of 60~120%.
)4* On the chilled water/cooling water side, scale factor is 0.086m2K/kW )0.0001m2h/kcal*.
)5* The maximum chilled/cooling water box pressure bearing capacity of normal pressure chiller is 0.8 MPa)G*.
)6* The unit is transported with rack of 180mm in height, and for the units SS-661H2 and above, submerged type rack will be adopted, extra 60mm
shall be included.
)7* The shipping weight includes the rack weight, exluding solution weight.
39
5 Hot Water Operated Two Stage
Lithium Bromide Absorption Chiller
Hot water operated two stage lithium bromide absorption chiller is a kind of large-size industrial facility with hot water as the driving energy
and lithium bromide solution as the absorbent and water as refrigerant.
Hot water two stage units, using hot water as the energy source, not only reduces greatly the cost for electricity and operation fees in
regions where there are rich hot water resources, but also compensates the peak-valley load difference. When the hot summer rolls in,
shortage of electric power will poses a great worry for various cities. Concentrated consumption of power by air-conditioners is the sticking
point for such a seasonal problem, for which, hot water operated two stage chillers offer an attractive solution.
Shuangliang hot water operated two stage chillers are widely applied in industries, such as precision machinery manufacturing, instruments
& meters, aviation & aerospace, textiles, electronics, electric power, metallurgy, pharmaceuticals, cigarettes, chemicals, hospitals, food,
etc. By utilizing dozens of patented technologies with features of extremely high energy efficiency and outstanding environmental effects, in
addition to her customerservice experience of over 28 years, Shuangliang guarantees to reward her users with optimal returns.
40
Working Principle
Cooling Cycle 5
Hot Water out
Condenser (2)
Condenser (1)
Cooling water inlet temp. (C,I,A)
Regulating
Hot water inlet temp. (C.I,A) Valve
4 M
Hot water outlet temp. (I) Hot Water in
Strong solution spray temp. (C.I) Generator Generator
8
Strong solution outlet temp. (C.I)
Supplied by Customer
Condensation temp. (C.I.A) 7
Evaporation temp. (I.A) 6
Cooling Water in Cooling Water out
De-crystallization pipe temp. (I.A)
3
Chilled water flow switch (A)
(C)-Control 1 2
Chilled Water in Chilled Water out
(A)-Alarm
10 12 11
Evaporator (2)
Evaporator (1)
Absorber (2)
Absorber (1)
(I)-Indication
Pipeline
Valve
stallization Pipe
Automatic Decry-
stallization Pipe
Automatic Decry-
Valve Valve
Hot water (Low temperature)
Oil Trap
Strong solution
41
# !
1157H2
1323H2
1488H2
165H2
198H2
265H2
331H2
413H2
496H2
579H2
661H2
744H2
827H2
992H2
HSC)130/68*-
99H2
Model
HSB)120/68*-
kW 350 580 700 930 1160 1450 1740 2040 2330 2620 2910 3490 4070 4650 5230
4
Cooling Capacity 10 kcal/h 30 50 60 80 100 125 150 175 200 225 250 300 350 400 450
USRt 99 165 198 265 331 413 496 579 661 744 827 992 1157 1323 1488
Inlet/Outlet Temp. 12 7
Chilled Water
Flow Rate m3/h 60 100 120 160 200 250 300 350 400 450 500 600 700 800 900
Pressure Loss mH2O 14.9 14.9 14.5 11.8 7.0 6.9 9.2 9.2 11.7 11.7 16.2 16.2 18.3 13.2 15.3
Connection Diameter )DN* mm 100 125 125 150 150 200 200 200 250 250 250 300 300 350 350
Inlet/Outlet Temp. 32 38
Cooling Water
Flow Rate m3/h 114 189 227 303 378 473 567 662 756 851 945 1134 1323 1512 1701
Pressure Loss mH2O 9.0 9.1 9.2 7.1 9.3 9.2 11.2 11.2 14.0 13.6 10.7 10.7 11.0 13.9 17.4
Connection Diameter )DN* mm 125 150 200 200 250 250 300 300 300 350 350 400 450 450 450
Inlet/Outlet Temp. 68
Consumption)130/68* 6.1 10.2 12.2 16.3 20.4 25.5 30.6 35.7 40.8 45.9 51.0 61.2 71.4 81.6 91.8
Hot Water
t/h
Consumption)120/68* 7.3 12.2 14.6 19.4 24.3 30.4 36.5 42.5 48.6 54.7 60.8 76.9 85.1 97.2 109.4
Pressure Loss mH2O 9.3 9.8 8.8 9.3 9.1 9.0 11.9 11.9 9.6 10.0 13.3 13.3 11.4 15.6 11.1
Piping Diameter )DN* mm 40 50 50 65 80 80 80 80 100 100 100 125 125 150 150
Total Current A 20.4 23.3 23.3 25.5 25.5 28.1 28.7 30.9 30.9 33.4 37.7 41.6 44.0 45.0 45.9
Electric Power kW 6.55 7.25 7.25 7.65 7.65 8.65 9.05 9.45 9.45 10.25 11.25 12.35 13.35 13.95 14.45
Dimensions
Length 4118 4216 4344 4610 5095 5190 5593 5760 6217 6270 7110 7160 7860 8742 9542
Overall
Width mm 1803 2023 2073 2130 2280 2451 2475 2576 2590 2777 2854 2949 2978 3072 3072
Height 2489 2687 2841 2900 2857 3151 3234 3480 3654 3852 3816 4090 4225 4350 4350
Shipping Weight 8.2 10.2 14.4 13.4 15.9 18.0 20.6 23.6 25.9 27.7 30.2 34.3 41.5 47.8 53.7
t
Operating Weight 10.0 12.9 11.2 17.1 20.4 23.7 27.5 31.8 34.9 38.7 41.6 47.8 57.1 65.2 73.7
Notes
)1* The lowest outlet temprature of chilled water is 5.
)2* Cooling capacity can be adjusted in range of 20~100% , and chilled water can be adjusted in range of 60~120%.
)3* On the chilled water/cooling water/hot water side, scale factor is 0.086m2K/kW )0.0001m2h/kcal*.
)4* Chilled/cooling/hot water boxes have the maximum pressure bearing capacity of 0.8 Mpa)G* for standard type and 1.6 Mpa)G* for High pres-
sure type.
)5* The chiller is transported with rack of 180mm in height for chiller less than unit HSB-413H2, and additional height of rack of 60mm for the unit
HSB-496H2 and move.
)6* The shipping weight includes the rack weight, exluding solution weight.balanced during handling.
For variable gensets' jacket water with different temp., there are options for customized design to recover its waste heat for chilled water production
from 7 to max 30, for example, for 90/70 jacket water condition, there are series of special hot water chillers to consume it straight with vari-
able cooling capacity.
For high temperature150 hot water with pressure, there are also customized design for double effect hot water chiller.
42
6 Hot Water Operated Single Stage
Lithium Bromide Absorption Chiller
Hot water operated single effect lithium bromide absorption chiller is a kind of large-size refrigeration facility with low
temperature hot water as the driving energy and lithium bromide solution as the absorbent and water as refrigerant.
Hot water single effect chiller, using hot water or waste hot water as the energy source, not only reduces greatly the
cost for electricity but also possess great economic potential in applications where this source of energy is available.
By using the chiller, waste hot water can be recovered, which used to be discharged or regarded as no use. In addi-
tion, hot water single effect chiller uses water as refrigerant instead of CFCs and therefore has no harm to ozone layer,
therefore, compared with electric chiller, the machine has an signicant advantage of environment preservation.
43
Working Principle
Cooling Cycle
Hot Water
Out
Cooling Water
Supplied By Customer Out
Heat Exchanger
Chilled Water
Out
Check Valve
Chilled Water
In
By-pass
Valve
Auto Purging Unit
Sampling
Oil Trap
Valve
Hot water (High temperature)
Hot water (Low temperature)
Discharge
Cooling water
Vacuum
Chilled water Pump Solution
Pump
Strong solution Refrigerant
Pump
Weak solution Cooler
Cooling Water
In
Refrigerant water
Refrigerant vapor
Chilled water inlet temp. (I) Hot water inlet temp. (I,C,A) Strong solution outlet temp. (I,C,A) De-crystallization temp. (I,A) (C)Control
Chilled water outlet temp. (I,C,A) Hot water outlet temp. (I) Condensation temp. (I,C,A) Chilled water flow (A) (A)Alarm
Cooling water inlet temp. (I,C,A) Solution spray temp. (I,C) Evaporation temp. (I,A) Vacuum pressure (I) (I)Indication
In hot water operated single effect chiller, weak solution in absorber Heat exchanger is a sort of heat-exchanging equipment between
is pumped into generator via heat exchangers by solution pump high and low temperature solution. In hot water single effect chiller,
and then concentrated into strong solution when heating by hot there is still a heat exchanger, in which heat is exchanged be-
water. tween high temperature strong solution and low temperature weak
solution, therefore, increasing the heat efficiency of chiller.
Refrigerant vapor generated at the same time is condensed into
water in condenser. Resulting latent heat is carried out of chiller by
cooling water.
44
# !
Model HSA)95/85*- 99H2 165H2 265H2 331H2 413H2 496H2 579H2 661H2 744H2 827H2 992H2 1157H2 1323H2
kW 350 580 930 1160 1450 1740 2040 2330 2620 2910 3490 4070 4650
4
Cooling Capacity 10 kcal/h 30 50 80 100 125 150 175 200 225 250 300 350 400
USRt 99 165 265 331 413 496 579 661 744 827 992 1157 1323
Inlet/Outlet Temp. 15 10
Chilled Water
Flow Rate m3/h 60 100 160 200 250 300 350 400 450 500 600 700 800
Pressure Loss mH2O 6.2 5.9 9.5 9.4 13.5 13.2 5.0 6.9 6.7 9.2 9.2 9.1 13.3
Connection Diameter)DN* mm 100 125 150 150 200 200 200 250 250 250 300 300 350
Inlet/Outlet Temp. 32 38
Cooling Water
Flow Rate m3/h 112 186 298 372 465 558 651 744 837 930 1116 1302 1488
Pressure Loss mH2O 6.8 7.0 5.3 5.2 6.4 7.0 7.7 8.7 9.3 11.0 11.1 10.8 14.9
Connection Diameter)DN* mm 125 150 200 250 250 250 300 300 300 350 400 400 400
Inlet/Outlet Temp. 95 85
Consumption t/h 36.9 61.5 98.4 123 153.8 184.5 215.3 246 276.8 307.5 369 430.5 492
Hot Water
Pressure Loss mH2O 4.3 4.3 3.2 3.2 4.6 4.6 2.5 3.1 3.1 4.2 4.2 4.2 5.9
Piping Diameter)DN* mm 80 100 125 150 150 200 200 200 200 200 250 250 250
Electric Modulating Valve mm 65 100 125 125 150 150 150 200 200 200 250 250 250
Dia.)DN*
Power Supply 3 - 380VAC - 50Hz
Electrical
Data
Total Current A 13.6 14.7 17.8 20.2 20.8 20.8 20.8 22.7 27.0 27.9 32.8 34.5 37.5
Electric Power kW 4.15 4.55 5.35 5.85 6.25 6.25 6.25 7.25 8.25 8.25 9.95 10.45 11.45
Dimensions
Length 3870 3860 4420 4535 5038 5080 5535 5935 5935 6635 6735 6745 7445
Overall
Width mm 1526 1646 1786 1967 2081 2200 2239 2402 2408 2446 2635 2850 2869
Height 2239 2541 2714 2860 2940 3080 3195 3315 3460 3460 3770 4170 4170
Operating Weight 7.3 9.3 13.0 15.2 18.1 21.5 25.0 28.0 30.2 33.6 39.9 45.9 51.3
t
Shipping Weight 5.8 7.1 9.5 10.8 12.9 15.2 17.9 20.1 21.5 23.3 27.7 31.7 35.1
Notes:
)1* The lowest outlet temprature of chilled water is 5.
)2* Cooling capacity can be adjusted in range of 20~100% , and chilled water can be adjusted in range of 60~120%.
)3* On the chilled water/cooling water/hot water side, scale factor is 0.086m2K/kW )0.0001m2h/kcal*.
)4* Chilled/cooling/hot water boxes have the maximum pressure bearing capacity of 0.8 MPa)G* for standard type and 1.6 MPa)G* for High pressure type.
)5* The chiller is transported with rack of 180mm in height for chiller less than unit HSA-496H2, and additional height of rack of 60mm for the unit HSA-
579H2 and move.
)6* The shipping weight includes the rack weight, exluding solution weight.
45
SHUANGLIANG ECO-ENERGY SYSTEMS CO., LTD
Add: Shuangliang Industry Park in Ligang, Jiangyin City, Jiangsu Provine, China
Tel: +86-510-86638824 86632095
Fax: +86-510-86634678
Post Code: 214444
Email: [email protected]
www.shuangliang.com
Cat. No.: SL-IT-C1303(E) New Release
2013 Copyright Reserved. Information subject to change without prior notice.