Spatial Separations 2010
Spatial Separations 2010
Spatial Separations 2010
rd
222-3 AVE NORTH, SASKATOON, SK S7K 0J5
The NBC defines the following commonly used terms as indicated below:
Exposing Building Face refers to that part of the exterior wall of a building which faces one direction and
is located between ground level and the ceiling of its top storey, or if a building is divided into fire
compartments, the exterior wall of a fire compartment facing in one direction.
Limiting Distance is defined as the distance from the exposing building face to a property line, lot line,
centerline of a street or public thoroughfare, or an imaginary line between two buildings on the same site.
Unprotected Opening refers to a doorway, window or opening other than one equipped with a closure
having the required fire-protection rating, or any part of a wall forming part of the exposing building face
that has a fire-resistance rating less than that required for the exposing building face.
The following options for obtaining the required fire-resistance ratings of exterior walls may be considered:
Hour Rating
Listed Assembly 1 Hour Rating
Concrete Block Listed Assembly 2 Hour Rating
Design under D-2.3
#
Concrete Block Listed Assembly
1 layer of 5/8 FR GWB Design under D-2.3
#
Concrete Block*
Equivalents** 1 layer of 5/8 FR GWB + thermal 2 layers of 5/8 FR GWB + thermal
barrier barrier
2 layers of 5/8 FR GWB 3 layers of 5/8 FR GWB
Equivalents** Equivalents**
#
Design under D-2.3
The Component Additive Method described in Appendix D can be used to design an exterior wall
assembly with the required fire-resistance rating for a maximum 90 minute rating.
Thermal Barrier
Exterior wall assemblies shall have an outer membrane consisting of sheathing and exterior cladding
with spaces between the studs filled with insulation as per D-2.3.5(2) in addition to the fire-rated
gypsum board applied to the inside face of the exterior wall. This sheathing membrane or thermal
barrier is considered to have a 15 minute fire-resistance rating based on Appendix D from the NBC
2010.
Where the building construction does not typically include sheathing (ie. pre-engineered metal
buildings), an additional layer of 5/8 Type X (or Fireguard) gypsum board applied to the inside face of
the wall is acceptable in order to achieve the required 1 or 2 hour fire-resistance rating. An extra layer
of rated drywall is not required for a hour fire-resistance rating.
This definition of a street means that only property deeded for public use as a street may be considered
as a street with respect to the requirements of Subsection 3.2.3. There are two cases where a building
can be considered to face a street, as outlined below. The first is where the building faces a true street
that in every way meets the definition of a street as shown in the figure below in Case (i). The other case
is where the building faces a public lane that is at least 6 metres wide, and has a limiting distance to the
centerline of the public lane as shown in Case (ii) below. Private access roads that are not deeded for
public use are not considered to be streets, regardless of size.
01/07/2014 Page 3