Advantages of NGLA For Transmission System
Advantages of NGLA For Transmission System
Advantages of NGLA For Transmission System
line surge arresters (TLSAs) offers perhaps the best opportunity for
as this may be, the value of using them transcends this one objective
the same way (see INMR Q2, 2015). If the phase to which these TLSAs
to visualize when a forward flash occurs, this is not so easy in the case
of back-flashover.
Fig. 1: Example of non-gapped transmission line arrester (NGLA).
CLICK TO ENLARGE
CLICK TO ENLARGE
Indeed, there was a time when gapped silicon carbide arresters had
reputable suppliers consistently achieve low failure rates that are close
example, recent experience with failure rates are in the 200 parts per
million (ppm) range. This rate is most likely similar for reputable
concerns.
live parts of extra high voltage power systems of 345 kV and above.
amplitudes with only a few installations along the line. For example, on
CLICK TO ENLARGE
are given for switching surge factors ranging from 1.8 to 2.7 pu for a
maximum is much less than for a 2.7 pu surge. This can make a
CONGRESS in Vancouver).
surges. Note that other constraints on line clearances could also affect
with success.
costs are far less than rebuilding the entire substation. With line
arresters and voltage uprating, substations can also use compact bus
spacing, thereby offering economic benefits where land costs are high.
Less clearance when uprating a system can also lead to lower bus
heights, which can lead to lower costs for aesthetic treatments such as
are in some cases difficult to make due to lack of space for installing
level of lines above 345 kV and lightning surges on lines below 345 kV,
change the MAD. A line arrester, due to its minimal weight, is a perfect
candidate for this application and, here, an EGLA type may be more
suited for the application since lightning and switching residual voltage
can be as much as 25% lower. In both cases, however, the MAD can
Fig. 3: Lightning activity over 1 hr period in Oct 2016 ( from www.lightningmaps.org). Lines
are drawn between strike and sensor for most recent strikes.
CLICK TO ENLARGE
Fig. 4: Overview of back-flashover process.
CLICK TO ENLARGE
is most likely due to back-flash and the most common cause is when
there is a lightning strike to the overhead shield wire and tower ground
impedance is too high. The reason for the term back-flashover is that
it is in the opposite direction of flashovers produced during a direct
transmission line: the first and more often used method is to improve
tower ground resistance and, up until 20 years ago, this was the only
lines using arresters. The first is to run a study of the system and
outage rate. This method uses fewer arresters and costs less than a
full protection scheme. The second and less used method is to install
distribution lines running through urban areas and usually features the
following:
Single-pole structures;
CLICK TO ENLARGE
line designs suitable for use in congested urban areas. There are other
voltage level on the same right-of-way may be the only feasible way to
loading and other design and construction issues. The short spans of a
compact design reduce the magnitude of high-temperature sag,
20 years. The main reason for this particular design was to reduce
visual impact and make the transmission line appear more like a
distribution system.
Open Breaker Protection
Fig. 6: TLSAs used here as line entrance arresters to protect open breaker.
CLICK TO ENLARGE
opens to clear a fault, the second or third stroke of the flash can enter
the station while the beaker is still open to clear the fault. This second
stroke can flashover the line side bushing of the breaker with high risk
of long-term damage. Of course, this is a low probability scenario but,
to assess real level of risk, a study should be conducted for the specific
Line arresters are not generally used for this application but certainly
can help overcome any such risk. Fig. 6, for example, shows a space-
ground resistance of the pole where they are installed should be the
same as at the substation. If the first tower out from the station is
used instead, it should not be located too far away or it will not
case, transmission lines with arresters in the place of OHGW cost less
initially and also going forward. The report found that construction
savings were between 1.8% and 5.8% of the total cost of the line for
phases of every tower make a line lightning proof. If only the top
phase is equipped with arresters, then the top phase serves as the
during summer. For example, if a power source is far from the major
demand center and transmission lines pass through high-lightning
this risk is to run local generators and depend less on the lower-cost
This application applies mainly for new construction but could also
work for older lines should the OHGW reach end-of-life. It is well
grounded at tower tops. Such losses are inductive in nature from load
flowing in phase conductors and become higher the closer the OHGW
shield wires and current load on the system. As seen from Table 3 for
heavily loaded lines can amount to as much as US$ 4.6 million per 100
operation of power systems. These TLSAs not only render any line