MODEL YK (STYLE G)
R-134a
WITH OPTIVIEWTM CONTROL CENTER
FOR ELECTRO-MECHANICAL STARTER,
SOLID STATE STARTER AND VARIABLE SPEED DRIVE
LD15222
FORM 160.75-O1 (211)
IMPORTANT!
READ BEFORE PROCEEDING!
GENERAL SAFETY GUIDELINES
This equipment is a relatively complicated apparatus. which it is situated, as well as severe personal injury or
During installation, operation maintenance or service, death to themselves and people at the site.
individuals may be exposed to certain components or
conditions including, but not limited to: refrigerants, This document is intended for use by owner-authorized
materials under pressure, rotating components, and operating/service personnel. It is expected that this in-
both high and low voltage. Each of these items has the dividual posseses independent training that will enable
potential, if misused or handled improperly, to cause them to perform their assigned tasks properly and safe-
bodily injury or death. It is the obligation and respon- ly. It is essential that, prior to performing any task on
sibility of operating/service personnel to identify and this equipment, this individual shall have read and un-
recognize these inherent hazards, protect themselves, derstood this document and any referenced materials.
and proceed safely in completing their tasks. Failure This individual shall also be familiar with and comply
to comply with any of these requirements could result with all applicable governmental standards and regula-
in serious damage to the equipment and the property in tions pertaining to the task in question.
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to specific situations:
Indicates a possible hazardous situation !"#$%&'#() *) +*,*-") .+&/+) /012") 2#*") %0)
which will result in death or serious injury damage to the machine,damage to other
if proper care is not taken. equipment and/or environmental pollu-
tion if proper care is not taken or instruc-
tions and are not followed.
2 JOHNSON CONTROLS
FORM 160.75-O1 (211)
ASSOCIATED LITERATURE
MANUAL DESCRIPTION FORM NUMBER
Vari
abl
e Speed Dri
ve Operati
on 160.00-O1
Sol
id State Starter Operati
on and Mai
ntenance 160.00-O2
Fl
oor Mounted MV SSS Operati
on 160.00-O5
Uni
tMounted MV SSS Operati
on 160.00-O7
Instal
lati
on Uni
t 160.75-N1
Opti
view ControlCenter Operati
on and Mai
ntenance 160.54-O1
Wi ri
ng Di
agram Fi
eld Connecti
ons for YK Chi
ll
er (Styl
e G) Opti
View ControlCenter wi
th Remote Low
160.75-PW 1
or Medium Vol
tage EMS or UnitMounted Low or Medi um Voltage SSS
Wiri
ng Di
agram Fi
eld Connecti
ons for YK Chi
ll
er (Styl
e G) Opti
View ControlCenter wi
th Remote
160.75-PW 2
Medium Vol
tage SSS
Wiri
ng Di
agram Fi
eld Connecti
ons for YK Chi
ll
er (Styl
e G) Opti
View ControlCenter wi
th Remote
160.75-PW 3
Medium Vol
tage VSD
!"#"$%&'"(%#()&*&+",-.&/0$1#0-&20."34(1"0$5&60#&78&/9"--,#&:;1<-,&=> 160.75-PW 4
Wi
ri
ng Di
agram YK Chi
ll
er (Styl
e G) Opti
View ControlCenter wi
th Remote Low or Medi
um Vol
tage EMS 160.75-PW 5
Wiring Diagram YK Chi
ll
er (Styl
e G) Opti
View ControlCenter wi
th Uni
tMounted Low or Medi
um
160.75-PW 6
Voltage SSS,Uni tMounted Low Voltage VSD with Modbus,or Remote Medi
um Vol tage VSD
Wiri
ng Di
agram YK Chi
ll
er (Styl
e G) Opti
View ControlCenter wi
th LTC I/O Board wi
th Remote Low or
160.75-PW 7
Medium Vol
tage EMS
Wi ri
ng Di
agram YK Chi
ll
er (Styl
e G) Opti
View ControlCenter w/LTC I/O Board wi
th UnitMounted Low
160.75-PW 8
or Medium Vol
tage SSS,Uni tMounted Low Voltage VSD with Modbus or Remote Medi um Vol
tage VSD
RenewalParts Uni
t 160.75-RP1
RenewalParts Opti
View ControlCenter 160.54-RP1
JOHNSON CONTROLS 3
FORM 160.75-O1 (211)
NOMENCLATURE
YK KC K4 H9 CY G
STYLE (Desi
gn Level
)
MOTOR CODE
POW ER SUPPLY
for 60 Hz
5 for 50 Hz
COMPRESSOR CODE*
CONDENSER CODE*
EVAPORATOR CODE*
*Refer to YK Engineering Guide for (Form 160.75-EG1)
MODEL* Shell/M otor/Compressor combinations.
4 JOHNSON CONTROLS
FORM 160.75-O1 (211)
TABLE OF CONTENTS
JOHNSON CONTROLS 5
FORM 160.75-O1 (211)
LIST OF FIGURES
FIGURE 1 - ModelYK Chi
ll
er ....................................................................................................................................7
FIGURE 2 - Compressor Prerotati
on Vanes..............................................................................................................8
FIGURE 3 - Refri
gerantFl
ow-Thru Chi
ll
er (Fal
li
ng Fi
lm Evaporator) ........................................................................ 9
FIGURE 4 - Refri
gerantFl
ow-Thru Chi
ll
er (Fl
ooded Evaporator)............................................................................10
FIGURE 5 - Oi
lLevelIndi
cator ............................................................................................................................... 11
FIGURE 6 - Chi
ll
er Starti
ng Sequence And Shutdown Sequence (Em Starter And Sol
id State Starter) ................ 12
FIGURE 7 - Chi
ll
er Starti
ng Sequence And Shutdown Sequence (Vari
abl
e Speed Dri
ve) ..................................... 12
FIGURE 8 - Li
qui
d Chi
ll
er Log Sheets .....................................................................................................................14
FIGURE 9 - System Components FrontVi
ew .........................................................................................................18
FIGURE 10 - System Components Rear Vi
ew ........................................................................................................19
FIGURE 11 - Schemati
cDrawi
ng (YK) Compressor Lubri
cati
on System............................................................. 20
FIGURE 12 - Oi
lReturn System..............................................................................................................................23
FIGURE 13 - Chargi
ng Oi
lReservoi
r Wi
th Oi
l.........................................................................................................24
FIGURE 14 - Evacuati
on OfChi
ll
er .........................................................................................................................27
FIGURE 15 - Saturati
on Curve ................................................................................................................................29
FIGURE 16 - Di
agram,Meggi
ng Motor W i
ndi
ngs ...................................................................................................30
FIGURE 17 - Motor Starter Temperature And Insul
ati
on Resi
stances .................................................................... 31
LIST OF TABLES
TABLE 1 - Operati
onAnal
ysi
s Chart.......................................................................................................................25
TABLE 2 - System Pressures .................................................................................................................................28
TABLE 3 - Beari
ng Lubri
cati
on................................................................................................................................35
6 JOHNSON CONTROLS
FORM 160.75-O1 (211)
SYSTEM OPERATION DESCRIPTION nent to operation of the chiller are automatically dis-
played and read on a graphic display. Other displays
The YORK M odel YK Chiller is commonly applied
to large air conditioning systems, but may be used
can be observed by pressing the keys as labeled on the 1
Control Center. The chiller with the OptiView Control
on other applications. The chiller consists of an open
Center is compatible with an electro-mechanical start-
motor mounted to a compressor (with integral speed
er, YORK Solid State Starter (optional), or Variable
increasing gears), condenser, evaporator and variable
Speed Drive (optional).
flow control.
In operation, a liquid (water or brine to be chilled)
The chiller is controlled by a modern state of the art
flows through the evaporator, where boiling refrigerant
M icrocomputer Control Center that monitors its opera-
absorbs heat from the liquid. The chilled liquid is then
tion. The Control Center is programmed by the opera-
piped to fan coil units or other air conditioning terminal
tor to suit job specifications. Automatic timed start-ups
units, where it flows through finned coils, absorbing
and shutdowns are also programmable to suit night-
heat from the air. The warmed liquid is then returned to
time, weekends, and holidays. The operating status,
the chiller to complete the chilled liquid circuit.
temperatures, pressures, and other information perti-
COMPRESSOR
CONTROL
CENTER
MOTOR
CONDENSER
LD15222
EVAPORATOR
JOHNSON CONTROLS 7
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION FORM 160.75-O1 (211)
CAPACITY CONTROL
The major components of a chiller are selected for full
load capacities, therefore capacity must be controlled
to maintain a constant chilled liquid temperature leav-
ing the evaporator. Prerotation vanes (PRV), located at
the entrance to the compressor impeller, compensate
for variation in load (Refer to Figure 2 on Page 8).
7619A(D)
8 JOHNSON CONTROLS
FORM 160.75-O1 (211) SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION
RefrigerantFlow-Thru Chiller
YK Mod G
(Falling Fi lm Evaporator)
!"#$%&"$'()*+,-./01$2*3$-44/5"67-(*8%'&$'9
(Falling-Film Evaporator)
COMPRESSOR
SUCTION
EVAPORATOR
CONDENSER
SUCTION
BAFFLE
LIQUID LEVEL
LIQUID LEVEL
SUB-COOLER
OPTIONAL
ISOLATION LD00924A
VALVE
Rev. 2 (10-11-2010)
FIGURE 3 - REFRIGERANT FLOW -THRU CHILLER (FALLING FILM EVAPORATOR) Dan Sowers
[email protected]
(717) 771-7535
JOHNSON CONTROLS 9
SECTION 1 - DESCRIPTION OF SYSTEM AND FUNDAMENTALS OF OPERATION FORM 160.75-O1 (211)
RefrigerantFlow-Thru Chiller
(Flooded Evaporator)
YK Mod G
!"#$%&"$'()*+,-./01$2*3$-44/5"67-(*8%'&$'9
(Flooded Evaporator)
COMPRESSOR
SUCTION
OPTIONAL
ISOLATION
VALVE MESH ELIMINATORS or
SUCTION BAFFLE
EVAPORATOR
CONDENSER
LIQUID LEVEL
LIQUID LEVEL
SUB-COOLER
Rev. 2 (12-09-2010)
Dan Sowers
[email protected]
FIGURE 4 - REFRIGERANT FLOW -THRU CHILLER (FLOODED EVAPORATOR) (717) 771-7535
10 JOHNSON CONTROLS
FORM 160.75-O1 (211)
OIL HEATERS !" If the oil level during operation is in the OVER
FULL region of the oil level indicator, oil should
If the oil heater is de-energized during a shutdown pe-
be removed from the oil reservoir, This reduces
riod, it must be energized for 12hours prior to starting
the oil level to the OPERATING RANGE.
compressor, or remove all oil and recharge compres-
sor with new oil. (Refer to OilCharging Procedure on !" If the oil level during operation is in the LOW
Page 24. ) OIL region of the oil level indicator, oil should be
added to the oil reservoir. (Refer to OilCharging
OIL HEATER OPERATION Procedure on Page 24. )
The oil heater operation is controlled by the OptiV-
Comply with EPA and local regulations
iew Control Center. The heater is turned on and off
when removingor disposingof refrigera-
to maintain the oil temperature differential to a value
tion system oil!
50F (27.8C) above the condenser saturation tem-
perature. This target value is maintained by the control
panel. 2
If the target value is greater than 160F (71C), the tar-
get defaults to 160F (71C). If the target value is less START-UP PROCEDURE
than 110F (43.3C), it defaults to 110F (43.3C).
Pre-Starting
To prevent overheating of the oil in the event of a con-
Prior to starting the chiller, observe the Optiview
trol center component failure, the oil heater thermostat
Cont rolCenter Operat ion and Maintenance (Form
(1HTR) is set to open at 180F (82C).
160.54-O1).M ake sure the display reads SYSTEM
CHECKING THE OIL LEVEL IN THE READY TO START.
OIL RESERVOIR Vent any air from the chiller waterboxes
Proper operating oil level During operation, the oil prior to startingthe water pumps. Failure
level should fall to the OPERATING RANGE identified %0)"0)(0).&22)-#(12%)&$)7*(()=*9C#)"*8*5#B
on the vertical oil level indicator label (Refer to Figure 5
on Page 11).
START-UP
1. If the chilled water pump is manually operated,
start the pump. The Control Center will not al-
#$%"& '(")'* ##(+"&$",&
-+&
"./#(,,")'*##(0"#*1.*0"2$%"*,"
established through the unit. If the chilled liquid
pump is wired to the M icrocomputer Control Cen-
ter the pump will automatically start, therefore,
this step is not necessary.
2. To start the chiller, press the COM PRESSOR
START switch. This switch will automatically
spring return to the RUN position. (If the unit
was previously started, press the STOP/RESET
side of the COM PRESSOR switch and then press
the START side of the switch to start the chill-
LD08647
er.) W hen the start switch is energized, the Con-
FIGURE 5 - OIL LEVEL INDICATOR trol Center is placed in an operating mode and
any malfunction will be noted by messages on a
graphic display.
JOHNSON CONTROLS 11
SECTION 2 - SYSTEM OPERATING PROCEDURES FORM 160.75-O1 (211)
LD15609
** Notfor al
lshutdowns. Refer to Di
spl
ayMessagesi
n manualOptiview Control Center Operation and Maintenance (Form 160.54-O1).
FIGURE 6 - CHILLER STARTING SEQUENCE AND SHUTDOW N SEQUENCE (EM STARTER AND SOLID
STATE STARTER)
LD15610
** Notfor al
lshutdowns. Refer to Di
spl
ayMessagesi
n manualOptiview Control Center Operation and Maintenance (Form 160.54-O1).
FIGURE 7 - CHILLER STARTING SEQUENCE AND SHUTDOW N SEQUENCE (VARIABLE SPEED DRIVE)
12 JOHNSON CONTROLS
FORM 160.75-O1 (211) SECTION 2 - SYSTEM OPERATING PROCEDURES
For display messages and information pertaining to the At start-up, the entering condenser water temperature
operation refer to Opt
iview ControlCent er Opera- may be as much as 25F (14C) colder than the stand-
tion andMaint enance (Form 160.54-O1). by return chilled water temperature. Cooling tower fan
Any malfunctions which occur during cycling will normally provide adequate control of the
STOP/RESET are also displayed. entering condenser water temperature on most instal-
lations.
Heat recovery chillers and chillers using optional head
pressure control would use a signal provided by the
microprocessor to control main condenser bundle heat
CHILLER OPERATION rejection or pressure, respectively.
The unit capacity will vary to maintain the leaving OPERATING LOG SHEET
CHILLED LIQUID TEM PERATURE setpoint by the
Pre-rotation Vanes which are modulated by an actua- A permanent daily record of system operating condi-
tor under the control of the M icroprocessor Board. The tions (temperatures and pressures) recorded at regular
vane control routine employs proportional plus deriva- intervals throughout each 24 hour operating period
tive (rate) control action. A drop in chilled liquid tem- should be kept.
2
perature will cause the actuator to close the Prerotation An optional status printer is available for this purpose
Vanes to decrease chiller capacity. W hen the chilled or Figure 8 on Page 14 shows a log sheet used by
liquid temperature rises, the actuator will open the Pre- Johnson Controls Personnel for recording test data on
rotation Vanes to increase the capacity of the chiller. chiller systems. It is available from the factory in pads
However, the current draw (amperes) by the compres- of 50 sheets each under Form 160.44-F7 and may be
sor motor is also limited to FLA setpoint by the micro- obtained through the nearest Johnson Controls office.
processor. Automatic data logging is possible by connecting the
optional printer and programming the DATA LOG-
If the load continues to decrease, after the Prerotation GER function.
Vanes are entirely closed, the chiller will be shut down
by the Leaving Chilled Liquid Low Temperature An accurate record of readings serves as a valuable ref-
Control. erence for operating the system. Readings taken when
a system is newly installed will establish normal condi-
CONDENSER WATER TEMPERATURE tions with which to compare later readings.
CONTROL For example, an increase in condenser approach tem-
The YORK chiller is designed to use less power by tak- perature (condenser temperature minus leaving con-
ing advantage of lower than design temperatures that denser water temperature) may be an indication of
are naturally produced by cooling towers throughout dirty condenser tubes.
the operating year. Exact control of condenser water
such as a cooling tower bypass, is not necessary for OPERATING INSPECTIONS
most installations. The minimum entering condenser By following a regular inspection using the display
water temperature for full and part load conditions is readings of the M icrocomputer Control Center, and
specified in the chiller engineering guide. maintenance procedure, the operator will avoid serious
where: operating difficulty. The following list of inspections
and procedures should be used as a guide.
% Load
Min. ECWT = LCWT C RANGE + 5F + 12 ( 100 )
% Load Daily
Min. ECWT = LCWT C RANGE + 2.8C + 6.6 ( 100 )
1. Check OptiView Control Center displays.
ECW T = Entering Condensing Water Temperature
2. If the compressor is in operation, check the bear-
LCW T = Leaving Chilled Water Temperature ing oil pressure on the SYSTEM Screen. Also
check the oil level in the oil reservoir. Operating
C Range = Condensing water temperature range at the
oil level should be operating range of oil indicator.
given load condition.
Drain or add oil if necessary.
JOHNSON CONTROLS 13
SECTION 2 - SYSTEM OPERATING PROCEDURES FORM 160.75-O1 (211)
LD00467
23889A
*NOTE:These i tems can be pri
nted byan el
ectroni
cprinter connected to the Mi
croboard
ng the PRINT keyon the Keypad,or automati
and pressi call
yusing the Data Logger feature.
14 JOHNSON CONTROLS
FORM 160.75-O1 (211) SECTION 2 - SYSTEM OPERATING PROCEDURES
Annually (m ore often ifnecessary) 1. Push the soft shutdown key on the homescreen on
1. Drain and replace the oil in the compressor oil the OptiView panel or rapid stop with the COM -
sump. (Refer to OilCharging Procedure on Page PRESSOR STOP/RESET switch. The compressor
24.
) will stop automatically. The oil pump will contin-
ue to run for coastdown period. The oil pump will
2. Evaporator and Condenser. then stop automatically.
A. Inspect and clean water strainers. 2. Stop the chilled water pump (if not wired into the
B. Inspect and clean tubes as required. M icrocomputer Control Center, in which case it
will shut off automatically simultaneously with the
C. Inspect end sheets. oil pump.) (The actual water pump contact opera-
3. Compressor Drive M otor (See motor manufactur- tion is dependent upon the position of M icroboard
ers maintenance and service instruction supplied jumper J54.)
with unit) 3. Open the switch to the cooling tower fan motors,
A. Clean air passages and windings per manu- if used.
facturers instructions.
4. The compressor sump oil heater is energized when
B. M eg motor windings Refer to Figure 16on the unit is stopped. 2
Page 30for details.
PROLONGED SHUTDOWN
C. Lubricate per motor manufacturer recom-
mendations. If the chiller is to be shut down for an extended period
of time (for example, over the winter season), the fol-
4. Inspect and service electrical components as neces- lowing paragraphs outline the procedure to be followed.
sary.
1. Test all system joints for refrigerant leaks with a
5. Perform refrigerant analysis. leak detector. If any leaks are found, they should
!9)?1*-%#-2>)&$(7#/%&0$)&$"&/*%#()0&2)&()'$#6
) be repaired before allowing the system to stand
replacingthe oil is not necessary for a long period of time.
During long idle periods, the tightness of the sys-
tem should be checked periodically.
2. If freezing temperatures are encountered while
the system is idle, carefully drain the cooling wa-
NEED FOR MAINTENANCE OR SERVICE
ter from the cooling tower, condenser, condenser
If the system is malfunctioning in any manner or the pump, and the chilled water system-chilled water
unit is stopped by one of the safety controls, consult pump and coils.
the Operation Anal ysisChart,Tabl e 1 on Page 25 of
this manual. After consulting this chart, if you are un- Open the drains on the evaporator and condenser
able to make the proper repairs or adjustments to start liquid heads to assure complete drainage. (If a
the compressor or the particular trouble continues to Variable Speed Drive, drain its cooling system.
hinder the performance of the unit, please call the near- If Solid State Starter equipped drain liquid from
est Johnson Controls District Office. Failure to report starter cooling loop.)
constant troubles could damage the unit and increase 3. If freezing temperatures are encountered for peri-
the cost of repairs. ods longer than a few days, the refrigerant should
be recovered to containers to prevent leakage from
STOPPING THE SYSTEM O-ring joints.
The Optiview Control Center can be programmed to 4. On the SETUP Screen, disable the clock. This
start and stop automatically (maximum, once each day) conserves the battery.
whenever desired. Refer to the Opt iview Control
Cent er Operation and Maintenance (Form 160. 54- 5. Open the main disconnect switches to the com-
O1). To stop the chiller, proceed as follows: pressor motor, condenser water pump and the
chilled water pump. Open the 115 volt circuit to
the Control Center.
JOHNSON CONTROLS 15
SECTION 2 - SYSTEM OPERATING PROCEDURES FORM 160.75-O1 (211)
16 JOHNSON CONTROLS
FORM 160.75-O1 (211)
JOHNSON CONTROLS 17
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION FORM 160.75-O1 (211)
OPTIVIEW CONTROL
CENTER
COMPRESSOR
SUCTION
RELIEF
VARIABLE
VALVES
SPEED
DRIVE
EVAPORATOR
LD15222
VARIABLE SPEED
SIGHT
OIL PUMP
GLASS
CONTROL BOX
FRONT VIEW
18 JOHNSON CONTROLS
FORM 160.75-O1 (211) SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
MOTOR
COMPRESSOR
DISCHARGE
LINE
LD15223
LIQUID LINE
CONDENSER OIL PUMP
HOUSING
REAR VIEW
JOHNSON CONTROLS 19
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION FORM 160.75-O1 (211)
COMPRESSOR ROTOR
SUPPORT SECTION
H.S.
SHAFT
SEAL
EMERGENCY
OIL RESERVE
HIGH
PRESSURE
TRANSDUCER
MAIN JOURNAL
AND THRUST
BEARING
IMPELLER
REFRIG.
SIGHT
HOT GLASSES
THERMISTOR
OIL OIL
HEATER COOLER
LOW OIL
ANGLE PRESSURE
DRAIN VALVE TRANSDUCER
OIL
LD15200
20 JOHNSON CONTROLS
FORM 160.75-O1 (211) SECTION 3 - SYSTEM COMPONENTS DESCRIPTION
MOTOR DRIVELINE A 1-1/2" (38 mm) liquid level sight glass is conve-
niently located on the side of the shell to aid in deter-
The compressor motor is an open-drip-proof, squir-
mining proper refrigerant charge. The evaporator shell
rel cage, induction type constructed to YORK design
specifications. 60hertz motors operate at 3570rpm. 50
contains a dual refrigerant relief valve arrangement set 3
at 180psig (12.4barg) on H and K compressor models;
hertz motors operate at 2975rpm.
235 psig (16.2 barg) on P and Q compressor models;
The open motor is provided with a D-flange, cast iron or single-relief valve arrangement, if the chiller is sup-
adapter mounted to the compressor and supported by a plied with optional refrigerant isolation valves. A 1"
motor support. (25.4mm) refrigerant charging valve is provided. The
condenser is a shell and tube type, with a discharge
M otor drive shaft is directly connected to the compres- gas baffle to prevent direct high velocity impingement
sor shaft with a flexible disc coupling. This coupling on the tubes. The baffle is also used to distribute the
has all metal construction with no wearing parts to as- refrigerant gas flow properly for most efficient heat
sure long life, and no lubrication requirements to pro- transfer. An optional cast steel condenser inlet diffuser
vide low maintenance. may be offered, on "M "and larger condensers, in lieu
For units utilizing remote Electro-M echanical starters, of the baffle, to provide dynamic pressure recovery and
a terminal box is provided for field connected conduit. enhanced chiller efficiency. An integral sub-cooler is
M otor terminals are brought through the motor cas- located at the bottom of the condenser shell providing
ing into the terminal box. Jumpers are furnished for highly effective liquid refrigerant subcooling to pro-
three-lead type of starting. M otor terminal lugs are not vide the highest cycle efficiency. The condenser con-
furnished. Overload/over current transformers are fur- tains dual refrigerant relief valves set at 235psig (16.2
nished with all units. barg).
The removable waterboxes are fabricated of steel. The
HEAT EXCHANGERS design working pressure is 150 psig (10.3 barg) and
Evaporator and condenser shells are fabricated from the boxes are tested at 225 psig (15.5 barg). Integral
rolled carbon steel plates with fusion welded seams. steel water baffles are located and welded within the
waterbox to provide the required pass arrangements.
Heat exchanger tubes are internally enhanced type. Stub-out water nozzle connections with ANSI/AW WA
The evaporator is a shell and tube type with customer C-606 grooves are welded to the waterboxes. These
process fluid flowing inside the tubes and refriger- nozzle connections are suitable for ANSI/AW WA
ant removing heat on the shell side via evaporation. C-606 couplings, welding or flanges, and are capped
Evaporator codes A*to K*utilize a hybrid falling film for shipment. Plugged 3/4" (19 mm) drain and vent
design. It contains a balance of flooded and falling film connections are provided in each waterbox.
technology to optimize efficiency, minimize refriger-
JOHNSON CONTROLS 21
SECTION 3 - SYSTEM COMPONENTS DESCRIPTION FORM 160.75-O1 (211)
22 JOHNSON CONTROLS
FORM 160.75-O1 (211)
COMPRESSOR
SOLENOID VALVE
SOLENOID VALVE
STOP VALVE
LD08578
JOHNSON CONTROLS 23
SECTION 4 - OPERATIONAL MAINTENANCE FORM 160.75-O1 (211)
THE OIL CHARGE ing valve (A) located on the remote oil reservoir
cover plate. (Refer to Figure 13 on Page 24) Do
The nominal oil charge for all H, K, and P8-P9 YK
not tighten the connection at the charging valve
compressors is 20gallons, and for Q3-Q7YK compres-
until after the air is forced out by pumping a few
sors is 10gallons of type YORK K or YORK H oil.
,&+$<(,"$="&'("$*#"5.658 ">'*,"7#
#,"&'("#*/(,"%*&'"
New YORK Refrigeration oil must be used in the cen- oil and prevents air from being pumped into the
trifugal compressor. Since oil absorbs moisture when system.
exposed to the atmosphere, it should be kept tightly 3. Open the oil charging valve and pump oil into the
capped until used. system until oil level in the compressor oil reser-
voir is in the OVER FULL region of the oil level
OIL CHARGING PROCEDURE
indicator label. Close the charging valve and dis-
During operation the compressor oil level must be connect the hand oil pump.
maintained in the OPERATING RANGE identified
on the vertical oil level indicator. If the oil level falls 4. As soon as oil charging is complete, close the
into the lower sight glass, it is necessary to add oil to power supply to the starter to energize the oil
the compressor oil reservoir. The oil should be charged heater. This will keep the concentration of refrig-
into the oil reservoir using the YORK Oil Charging erant in the oil to a minimum.
Pump YORK Part No. 070-10654. To charge oil into W hen the oil reservoir is initially charged with oil, the
the oil reservoir, proceed as follows: oil pump should be started manually to fill the lines,
passages, oil cooler and oil filter. This will lower the
1. The unit must be shut down.
oil level in the reservoir. It may then be necessary to
2. Immerse the suction connection of the oil charging add oil to bring the level back into the OPERATING
pump in a clean container of new oil and connect RANGE of the oil level indicator label.
the pump discharge connection to the oil charg-
LD08648 LD08579
OIL CHARGING VALVE
24 JOHNSON CONTROLS
FORM 160.75-O1 (211)
SECTION 5 - TROUBLESHOOTING
JOHNSON CONTROLS 25
SECTION 5 - TROUBLESHOOTING FORM 160.75-O1 (211)
26 JOHNSON CONTROLS
FORM 160.75-O1 (211)
SECTION 6 - MAINTENANCE
6
EVACUATION AND DEHYDRATION OF UNIT
27385A(D)
LD00949
JOHNSON CONTROLS 27
SECTION 6 - MAINTENANCE FORM 160.75-O1 (211)
*GAUGE ABSOLUTE
BOILING
INCHES OF TEMPERATURES
MERCURY (HG) OF
MILLIMETERS OF
BELOW ONE PSIA MICRONS WATER
MERCURY (HG)
STANDARD F
ATMOSPHERE
0 14.696 760. 760,000 212
10.24" 9.629 500. 500,000 192
22.05" 3.865 200. 200,000 151
25.98" 1.935 100. 100,000 124
27.95" .968 50. 50,000 101
28.94" .481 25. 25,000 78
29.53" .192 10. 10,000 52
29.67" .122 6.3 6,300 40
29.72" .099 5. 5,000 35
29.842" .039 2. 2,000 15
29.882" .019 1.0 1,000 +1
29.901" .010 .5 500 11
29.917" .002 .1 100 38
29.919" .001 .05 50 50
29.9206" .0002 .01 10 70
29.921" 0 0 0
*One standard atmosphere = 14.696 PSIA NOTES: PSIA = Lbs. per sq. i
n. gauge pressure
= 760 mm Hg. absolute pressure at32F = Pressure above atmosphere
= 29.921 i
nches Hg. absolute at32F PSIA = Lbs. per sq. i
n. absol
ute pressure
= Sum ofgauge pl us atmosphericpressure
28 JOHNSON CONTROLS
FORM 160.75-O1 (211) SECTION 6 - MAINTENANCE
Be sure the vacuum indicator is valved off taken place the pressure and temperature will continue
while holdingthe system vacuum and be to drop until eventually a temperature of 35F (1.6C)
sure to open the valve between the vacuum or a pressure of 5mm Hg. is reached.
indicator and the system when checking
the vacuum after the 8hour period. W hen this point is reached, practically all of the air has
been evacuated from the system, but there is still a small
amount of moisture left. In order to provide a medium
VACUUM DEHYDRATION for carrying this residual moisture to the vacuum pump,
To obtain a sufficiently dry system, the following in- nitrogen should be introduced into the system to bring
structions have been assembled to provide an effective it to atmospheric pressure and the indicator temperature
method for evacuating and dehydrating a system in the will return to approximately ambient temperature. Close
field. Although there are several methods of dehydrating off the system again, and start the second evacuation.
a system, we are recommending the following, as it pro- The relatively small amount of moisture left will be
duces one of the best results, and affords a means of ob- carried out through the vacuum pump and the tem-
taining accurate readings as to the extent of dehydration. perature or pressure shown by the indicator should
The equipment required to follow this method of dehy- drop uniformly until it reaches a temperature of 35F
dration consists of a wet bulb indicator or vacuum gauge, (1.6C) or a pressure of 5mm Hg.
a chart showing the relation between dew point tempera- W hen the vacuum indicator registers this temperature
ture and pressure in inches of mercury (vacuum), (Refer or pressure, it is a positive sign that the system is evac-
to Tabl e 2 on Page 28) and a vacuum pump capable of uated and dehydrated to the recommended limit. If this
pumping a suitable vacuum on the system. level cannot be reached, it is evident that there is a leak
somewhere in the system. Any leaks must be corrected
OPERATION
before the indicator can be pulled down to 35F or 5
Dehydration of a refrigerant system can be obtained mm Hg. in the primary evacuation.
by this method because the water present in the system
reacts much as a refrigerant would. By pulling down During the primary pulldown, keep a careful watch on
the pressure in the system to a point where its satu- the wet bulb indicator temperature, and do not let it fall
ration temperature is considerably below that of room below 35F (1.6C). If the temperature is allowed to
temperature, heat will flow from the room through the fall to 32F (0C), the water in the test tube will freeze,
walls of the system and vaporize the water, allowing and the result will be a faulty temperature reading.
a large percentage of it to be removed by the vacuum 6
pump. The length of time necessary for the dehydra-
tion of a system is dependent on the size or volume of
the system, the capacity and efficiency of the vacuum
pump, the room temperature and the quantity of water
present in the system. By the use of the vacuum indi-
cator as suggested, the test tube will be evacuated to
the same pressure as the system, and the distilled water
will be maintained at the same saturation temperature
as any free water in the system, and this temperature
can be observed on the thermometer.
If the system has been pressure tested and found to be
tight prior to evacuation, then the saturation tempera- LD00474
ture recordings should follow a curve similar to the typ-
ical saturation curve shown as Figure 15on Page 29. FIGURE 15 - SATURATION CURVE
JOHNSON CONTROLS 29
SECTION 6 - MAINTENANCE FORM 160.75-O1 (211)
inder must be admitted to the system pressure until the The refrigerant charge level must be checked after the
system pressure is raised above the point correspond- pressure and temperature have equalized between the
ing to the freezing point of the evaporator liquid. For condenser and evaporator. This would be expected to be
water, the pressure corresponding to the freezing point 4hours or more after the compressor and water pumps
is 8.54PSIG (58.9kPa) for R-134a (at sea level). are stopped. The level should visible in the sight glass.
W hile charging, every precaution must be taken to pre- Charge the refrigerant in accordance with the meth-
vent moisture laden air from entering the system. M ake od shown under the REFRIGERANT CHARGING,
up a suitable charging connection from new copper tub- above. The refrigerant level should be observed and
ing to fit between the system charging valve and the fit- the level recorded after initial charging.
ting on the charging drum. This connection should be
HANDLING REFRIGERANT FOR DISMANTLING
as short as possible but long enough to permit sufficient
AND REPAIRS
flexibility for changing drums. The charging connection
should be purged each time a full container of refrigerant If it becomes necessary to open any part of the refriger-
is connected and changing containers should be done as ant system for repairs, it will be necessary to remove
quickly as possible to minimize the loss of refrigerant. the charge before opening any part of the unit. If the
chiller is equipped with optional valves, the refrigerant
Refrigerant may be furnished in cylinders containing can be isolated in either the condenser or evaporator /
either 30, 50, 125, 1,025or 1750lbs. (13.6, 22.6, 56.6, compressor while making any necessary repairs.
464or 794kg) of refrigerant.
MEGGING THE MOTOR
The nameplate on the chiller contains the
correct refrigerant charge information W hile the main disconnect switch and compressor mo-
for the chiller. tor starter are open, meg the motor as follows:
1. Using a megohm meter (megger), meg between
phases and each phase to ground (Refer to Figure 16
on Page 30);these readings are to be interpreted
CHECKING THE REFRIGERANT CHARGE using the graph shown in Figure 17on Page 31.
DURING UNIT SHUTDOWN 2. If readings fall below shaded area, remove exter-
The refrigerant charge is specified for each chiller model. nal leads from motor and repeat test.
Charge the correct amount of refrigerant and record the M otor is to be megged with the starter at
level in the evaporator sight glass. ambient temperature after 24 hours of
idle standby.
The refrigerant charge should always be checked and
trimmed when the system is shut down.
LD00475
30 JOHNSON CONTROLS
FORM 160.75-O1 (211) SECTION 6 - MAINTENANCE
MEGOHMS
6
LD00476
TEMPERATURE F
FIGURE 17 - MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES
JOHNSON CONTROLS 31
SECTION 6 - MAINTENANCE FORM 160.75-O1 (211)
32 JOHNSON CONTROLS
FORM 160.75-O1 (211) SECTION 6 - MAINTENANCE
Acid cleaningshould only be performed 3. W ith nitrogen or dry air, blow out the tubes to
by an expert. Please consult your local clear them of traces of refrigerant laden moisture
water treatment representative for as- from the circulation water. As soon as the tubes
sistance in removing scale buildup and are clear, a cork should be driven into each end
preventative maintenance programs to of the tube. Pressurize the dry system with 50 to
eliminate future problems. COM M ER- 100 PSIG (345 to 690 kPa) of nitrogen. Repeat
CIALACID CLEANING this with all of the other tubes in the suspected
section or, if necessary, with all the tubes in the
In many major cities, commercial organizations now evaporator or condenser. Allow the evaporator or
offer a specialized service of acid cleaning evaporators condenser to remain corked up to 12to 24hours
and condensers. If acid cleaning is required, YORK before proceeding. Depending upon the amount
recommends the use of this type of organization. The of leakage, the corks may blow from the end of a
Dow Industries Service Division of the Dow Chemical tube, indicating the location of the leakage. If not,
Company, Tulsa, Oklahoma, with branches in principal if will be necessary to make a very thorough test
cities is one of the most reliable of these companies. with the leak detector.
Testing ForEvaporatorAnd CondenserTube 4. After the tubes have been corked for 12 to 24
Leaks hours, it is recommended that two men working
at both ends of the evaporator carefully test each
Evaporator and condenser tube leaks in R-134a sys-
tube one man removing corks at one end and
tems may result in refrigerant leaking into the water
the other at the opposite end to remove corks and
circuit, or water leaking into the shell depending on the
handle the leak detector. Start with the top row of
pressure levels. If refrigerant is leaking into the water,
tubes in the section being investigated. Remove
it can be detected at the liquid head vents after a period
the corks at the ends of one tube simultaneously
of shutdown. If water is leaking into the refrigerant,
and insert the exploring tube for 5seconds this
system capacity and efficiency will drop off sharply. If
should be long enough to draw into the detec-
a tube is leaking and water has entered the system, the
tor any refrigerant gas that might have leaked
evaporator and condenser should be valved off from
through the tube walls. A fan placed at the end of
the rest of the water circuit and drained immediately to
the evaporator opposite the detector will assure
prevent severe rusting and corrosion. The refrigerant
that any leakage will travel through the tube to
system should then be drained and purged with dry ni-
the detector.
trogen to prevent severe rusting and corrosion. If a tube
leak is indicated, the exact location of the leak may be 5. D -+<"-/C"#(-<*
/4"&
.:(,"=$+"#-&(+"*0(/&*7)-&*$/8 6
determined as follows:
6. If any of the tube sheet joints are leaking, the leak
1. Remove the heads and listen at each section of should be indicated by the detector. If a tube sheet
tubes for a hissing sound that would indicate gas leak is suspected, its exact location may be found
leakage. This will assist in locating the section of by using a soap solution. A continuous buildup of
tubes to be further investigated. If the probable bubbles around a tube indicates a tube sheet leak.
location of the leaky tubes has been determined,
treat that section in the following manner (if the COMPRESSOR
#$)-&*$/"* ,"/$&"0(7/* &
(B"-##"&
'("&.:(,"%* #
#"+(1.*+(" M aintenance for the compressor assembly consists
investigations). of checking the operation of the oil return system and
2. Wash off both tube heads and the ends of all tubes changing the dehydrator, checking and changing the oil,
with water. checking and changing the oil filters, checking the op-
eration of the oil heater, checking the operation of the oil
Do not use carbon tetrachloride for this pump, and observing the operation of the compressor.
purpose since its fumes give the same
C*8#) "&(/020-*%&0$) %+*%) %+#) -#9-&5#-*$%)
does.
JOHNSON CONTROLS 33
SECTION 6 - MAINTENANCE FORM 160.75-O1 (211)
Internal wearing of compressor parts could be a seri- of operation. However, if aluminum particles continue
ous problem caused by improper lubrication, brought to accumulate and the same conditions continue to stop
about by restricted oil lines, passages, or dirty oil fil- the unit operation after a new filter is installed, notify
ters. If the unit is shutting down on (HOT) High Oil the nearest Johnson Controls office to request the pres-
Temperature or Low Oil Pressure (OP), change the oil ence of a Johnson Controls Service Technician.
filter element. Examine the oil filter element for the
presence of aluminum particles. Aluminum gas seal ELECTRICAL CONTROLS
rings can contact the impeller and account for some For information covering the OptiView Control Cen-
aluminum particles to accumulate in the oil filter, espe- ter operation, refer to the Optiview ControlCenter
cially during the initial start up and first several months Operat ion andMaint enance (Form 160.54-O1).
34 JOHNSON CONTROLS
FORM 160.75-O1 (211)
JOHNSON CONTROLS 35
SECTION 7 - PREVENTIVE MAINTENANCE FORM 160.75-O1 (211)
Additional information on motor lubrica- a new unit, it is a good indication that the con-
tion and other service issues can be found denser tubes require cleaning. Refer to SECTION
in the A-C M otors Instruction M anual. 6- MAINTENANCE of this manual for condenser
tube cleaning instructions.
2. The evaporator tubes under normal circumstances
will not require cleaning. If the temperature dif-
LEAK TESTING ference between the refrigerant and the chilled
water increases slowly over the operating season,
The unit should be leak tested monthly. Any leaks
it is an indication that the evaporator tubes may be
found must be repaired immediately.
fouling or that there may be a water bypass in the
EVAPORATOR AND CONDENSER waterbox requiring gasket replacement or refrig-
erant may have leaked from the chiller.
The major portion of maintenance on the condenser
and evaporator will deal with the maintaining the wa- 3. Heat recovery condenser tubes should be evalu-
ter side of the condenser and evaporator in a clean ated similiar to evaporator tubes when the heating
condition. circuit is a treated, closed loop. Fouling could be
detected as ability to meet heat load requirements
The use of untreated water in cooling towers, closed decreases.
water systems, etc. frequently results in one or more of
the following: OIL RETURN SYSTEM
1. The condenser tubes should be cleaned annually 2. It is important that the factory settings of controls
or earlier if conditions warrant. If the temperature (operation and safety) not be changed. If the set-
difference between the water off the condenser tings are changed without Johnson Controls ap-
and the condenser liquid temperature is more than proval, the warranty will be jeopardized.
4F (2C) greater than the difference recorded on
36 JOHNSON CONTROLS
JOHNSON CONTROLS
P R OC E DUR E DA IL Y WE E K L Y MONT HL Y YE AR LY OT HE R
For operating and maintenance requirements listed above, refer to appropriate service literature, or contact your local YORK Service Office.
1
This procedure must be performed at the specified time interval by an Industry Certified Technician who has been trained and qualified to work on this type of YORK
equipment. A record of this procedure being successfully carried out must be maintained on file by the equipment owner should proof of adequate maintenance be required
at a later date for warranty validation purposes.
2
More frequent service may be required depending on local operating conditions.
Form 160.54-MR1 (801)
37
LD13598
FORM 160.75-O1 (111)
NOTES
38 JOHNSON CONTROLS
FORM 160.75-O1 (211)
Capaci
ty Tons Refri
gerantEffect(ton) 3.516 Ki
lowatts (kW )
Fl
ow Rate Gal
lons /Mi
nute (gpm) 0.0631 Li
ters /Second (l
/s)
W ei
ght Pounds (l
bs) 0.4538 Ki
lograms (kg)
Vel
oci
ty Feet/Second (fps) 0.3048 Meters /Second (m/s)
TEMPERATURE
To convert degrees Fahrenheit (F) to degrees Celsius
(C), subtract 32and multiply by 5/9or 0.5556.
Example: (45.0F - 32) x 0.5556= 27.2C
To convert a temperature range (i.e., a range of 10F)
from Fahrenheit to Celsius, multiply by 5/9or 0.5556.
Example: 10.0F range x 0.5556= 5.6C range
JOHNSON CONTROLS 39
OCHC&P0Q&RSTUN&70#VN&O,$$5<-M($"(&W;X&RYZ[SJRSTU& Tel
e. 800-861-1001 ;@EL
,41&10&49($%,&A"190@1&$01"4,C&O#"$1,.&"$&W;X
Copyright byJohnson Control s 2011 www.york.com ALL RIGHTS RESERVED