Method of Statement For Duct Pressure Test
Method of Statement For Duct Pressure Test
Clean Room
Facility
METHOD STATEMENT
for
DUCT LEAK TESTING
TABLE OF CONTENTS
SECTION - 2 : CRITERIA
2.1 TEST STANDARD
2.2 TEST RIG MAXIMUM CAPACITY
2.3 TEST PRESSURE MINIMUM REQUIREMENT
SECTION 4 : ATTACHMENTS
4.1 TEST FORM
4.2 CALIBRATION CERTIFICATES
4.3 EQUIPMENT / INSTRUMENTATION
4.4 PREPARATION OF TEST RIG FOR AIR DUCT LEAK TESTING
4.5 PERFORMING DUCT LEAKAGE TEST
Rev. 0
M/s. AJB is employed as the agent for carrying out Duct Leak Testing at EIAST
Clean Room Facility.
1.1 PURPOSE
1.2 SCOPE
The method statement covers the field testing of the relevant duct system to verify
conformance with the acceptable duct leakage to ensure that seams and joints in the
ductwork do not allow excessive quantities of processed air to escape.
1.3 REFERENCES
A. HVAC drawings.
B. DW143 (Practical Guide to Duct work Leakage Testing).
1.4 DEFINITIONS
SECTION- 2 : CRITERIA
Test work shall be carried out in sections as the installation proceeds, prior to the
installation of wall panels, false ceiling, coverings and prior to connection of the
equipment.
Static Pressure
Duct Limit Maximum Air leakage
Pressure Positive Negative Air Velocity limits
2
Class Pa Pa m/s l/s/m
0.65
Low-pressure 500 500 10 0.027*pt
Class A
0.65
Medium- 1000 750 20 0.009*pt
pressure
Class B
0.65
High pressure 2000 750 40 0.003*pt
Class C
The system shall be tested at least 1.25 times its operating pressure.
Rev. 0
SECTION 4 : ATTACHMENTS
PHYSICAL DETAILS
A. Section of ductwork to be tested SRAC-TYP-02-03A (SUPPLY DUCT Section 2)
B. Drawing Number APRT-MEP-CSD-05
C. Pressure Classification ( CLASS: A, B, or C) A
D. Test Static Pressure ( Pt ) ( Pa ) 250
E. Air Leakage Limit (F = CL * Pt 0.65 ) ( LPS / m2 ) 0.977
2)
F. Surface Area of Duct Under Test (m 8.7
G. Maximum Permitted Leakage ( E * F) ( LPS ) 8.50
TEST RESULTS
H Duct Static Pressure Reading ( Pa ) 251
I Type of Flow Measuring Device FLOW GRID
J Range of Measurement of Flow Measuring Device 21.18 to 423.72
K Interpreted Leakage factor (F = CL * Pt 0.65 ) ( LPS / m2 ) 0.81
L Interpreted Air Flow Leakages Rate ( LPS ) 7.09
M Duration of Test ( normally 15 mins) 10
O Test Result PASSED
P Date and Time inspected 29-Aug-15
REMARKS:
4.2 CALIBRATION
CERTIFICATES
Rev. 0
4.3 EQUIPMENT /
INSTRUMENTATION
ENERGY AND
1
Qty Description Part Number Reference Picture
2 20-in. (500-mm) silicone AFL9020005
tubes (blue)
Fan Speed
Control
Fan Control
Switch
On/Off
Switch
110 V 230 V
Figure 1. 110V and 230V Fan Speed Controllers
Note: The control pad on the Fan Speed Controller has been
disabled.
Connect the free end of the 16-ft (5-m) silicone tube to the
pressure tap marked DUCT PRESSURE P3 (+) on the black
square box.
c. For negative pressure,
high-flow testing,
remove the low flow
nozzle if it is installed.
Then, connect the grey
cast aluminum cam
lock connector to the
inlet side of the blower
per Figure 8. Close Fan Cam Lock
both cam lock arms at Inlet Connector
the same time to ensure
proper fit. Figure 8. Negative Pressure,
High-Flow Set-Up
Connect the free end of
the 16-ft (5-m) silicone tube to pressure tap marked DUCT
PRESSURE P4 (-) on the black square box.
Refer to the Operation and Service Manuals for the Model PVM620
Micromanometer and the Model TA465-P Ventilation Meter to use
these instruments in other applications. If you do not have the
manuals, download them from TSIs website www.tsi.com.
After completing leakage testing for a section of duct, you can move
on to the next section.
Instrument Operation if SMACNA Test Protocol is Selected
1. Enter key parameters: LEAKAGE TEST
a. Surface Area of ductwork Surface Area
section to be tested. Static Pressure
Flow Device
b. Static Pressure of test, as
Leakage Class
measured by Model
Test Length
PVM620 micromanometer.
Run Test
c. Flow Device as Nozzle or
Flow Grid.
d. Leakage class as a number LEAKAGE TEST
from 1 to 48. Typical values Leakage Factor x.xx
are 3, 6, 12, 24, or 48. Leak Limit x.xx
Leak Rate x.xx
e. Test Length, or duration of Status OK
leakage test. Flow Device Flow Grid
2. Increase the blower speed Baro Pressure 20.20
until the desired static pressure Temperature 20C
is achieved. Time 9:55
Standard TestXXX
3. When the static pressure has
Sample
stabilized, select Run Test and
press . 0
(Sample Saved 1)
4. The display will show the Stop(Save) Print
readings on the right. Leakage
Factor and Leak Rate will update in real time, while other
parameters will remain constant.
If the Leak Factor and Leak Rate are sufficiently stable, press the
START soft key or the key to begin the leak test. Pressing the
ESC key will exit back to the previous screen.
5. After the leak test is complete, the Model TA465-P will prompt
you to press the SAVE or PRINT soft key. You can also press the
ESC key here to back out to the previous screen without saving
the data.
After completing leakage testing for a section of duct, you can move
on to the next section.