IQ4E CPU Controller

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

Data Sheet

IQ4E/..
Controller

IQ4E Controller

Description Features
The IQ 4E controller has 10 universal inputs and 6 analogue 16 onboard I/O channels - 10 inputs and 6 outputs
voltage outputs and is expandable up to 192 points (depending I/O bus supports up to a total of 192 I/O channels (depending
on the controller variant) by adding I/O modules. This flexibility on the controller variant) using additional I/O modules
makes it suitable for a broad range of applications. I/O bus length up to 300 m (328 yards)
Ethernet 10/100 Mbps main network with TCP/IP protocol
The IQ4E controller uses Ethernet and TCP/IP networking Trend current loop LAN option
technologies with embedded XML and is fully compatible with Embedded XML Web Services as standard
other Trend IQ controllers. The IQ4E supports BACnet over IP BACnet over IP
as standard. Trend communications over a current loop LAN is Wallbus for connection of room displays
available as an option. A local PC or display (e.g. IQView4) can RS232 and USB local supervisor/engineering ports
be connected to the RS232 port. A Wallbus port is also provided Automatic time synchronisation and daylight saving via SNTP
for use with room displays. DIN rail mounting, DIN 19 size 2 standard enclosure
230 Vac, 24 Vac or 48 Vdc input power supply options

Physical
General 58.5 mm (2.3)
USB Connector Service Input Channel
(local engineering port) Indicators Button Indicators 53.5 mm (2.11)
116 mm (4.57)
110 mm (4.33)

DIN rail
clips

192.5 mm (7.55)

OK RX TX RX Output Channel
Ethernet Indicators Current Loop Indicators Indicators
(/LAN variants only)

IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.1


IQ4E/.. Data Sheet

Physical(continued)
Terminal Labels
Upper Labels
IQ4E/../230
Power Input Wallbus Universal Inputs

RS232 (local supervisor port) Auxiliary Supply Output

IQ4E/../24VAC
Power Input Wallbus Universal Inputs

1 2 3 80 81 70 71 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
!
All terminals 24V 24V
24V Class 2 (UL) 1 2 3 4 5 6 7 8 9 10
48V WMB AUX C C C C C C C C C C

RS232 (local supervisor port) Auxiliary Supply Output

Lower Label
IQ4E/../230 and IQ4E/../24VAC
Auxiliary Supply Output

Not used Ethernet Current Loop (/LAN variants only) Analogue Outputs

Functionality
The IQ4Es functionality can be divided into four sections: System, Hardware, Firmware, and Strategy.

System
The IQ4E has communication ports for Ethernet, USB (Local In addition, the IQ4E has the ability to join an internetwork
Engineering), RS232 (Local Supervisor) and Wallbus. In using its virtual INC (see Networking on page 4 for further
addition /LAN variants have a Trend current loop: details).

RS232 Wallbus Other devices connected to the Ethernet network can


communicate with the IQ4E using IP addressing. Remote
PCs can communicate through standard IT networks using IP,
enabling communication from anywhere in the world.
USB
Note:Communication with the Trend network by a supervisor,
tool or display will require the use of a virtual CNC (vCNC) in the
IQ4E or another CNC on the network (see Networking on page
4 for further details).

An integral web interface is also accessible over an Ethernet/IP


connection (see Ethernet on page 2).
Ethernet Trend Current Loop
(/LAN variants only) The IQ4E supports either static or dynamic (DHCP) IP
addressing. DHCP is enabled by default.
Ethernet
Each IQ4E has a unique MAC (Media Access Control) address
On units that do not have the current loop option (or on /LAN allocated to its Ethernet node. This can be used to help identify
variants that have the current loop disabled) the IQ4E can form the IQ4E during configuration.
a Trend LAN with other devices over the Ethernet network.

vINC

Ethernet

LAN Internetwork

2 IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.


Data Sheet IQ4E/..

Current Loop(../LAN variants only) BACnet Communications


On units that have the current loop option (which is enabled), The IQ4E controller is designed to be a BACnet Application
the IQ4E will form a Trend LAN with other devices on the Specific Controller. BACnet is an open protocol that enables
current loop. the products of a number of different manufacturers of building
automation and control equipment to communicate with
each other. It supports communication using BACnet over IP
(Ethernet) including:

Access to IQ4E parameters over BACnet,


Alarm delivery,
IC comms to a BACnet device.

A full specification of the objects, properties, and BIBBS


(BACnet Interoperability Building Blocks) supported by the IQ4E
LAN are given in the IQ4 Protocol Implementation Conformance
(on current loop) Statement (TP201248). The mapping of the BACnet properties
to the Trend parameters is covered in the IQ4 Configuration
Manual (TE201263).

INC XML Web Services


The IQ4E includes XML web services. XML is a general purpose
Internetwork specification for creating custom markup languages. It helps
developers create web pages and also provides a basic syntax
that enables information to be shared by different computers
Note: In this configuration IQ4E cannot join a Trend LAN on and applications. The IQ4E XML syntax is described in the IQ4
Ethernet. However, access by IP is still possible. Configuration Manual (TE201263).

In order to join an internetwork, an INC type device will be Inputs and Outputs
required elsewhere on the current loop LAN.
The IQ4E has 10 universal inputs and 6 analogue outputs, plus
The current loop may be wired in either a 2-wire or 4-wire three 24 Vdc auxiliary supply output terminals for powering
configuration. certain types of I/O devices. See Hardware on page 4 for
further details.
Network Bypass Relay:If the IQ4E loses power a set of
bypass relays will close to maintain the integrity of the current Cable Screening
loop network. If the relays close it will be recognised by a The use of screened cable for input and/or output connections
downstream device, and reported as a LAN Changed alarm. is not generally required unless the cable passes through
electrically noisy environments.
Baud Rate:By default the IQ4E auto-detects the baud rate to
use on the current loop. Where required, the rate can be set If screened cable is used the screen must be connected to the
manually using configuration software. local panel/enclosure ground and left unterminated at the far end.

RS232 (Local Supervisor Port) I/O Expansion Modules


Further I/O channels can be added to the IQ4E by the connection
An RS232 port is provided for the optional connection of local of various types of I/O expansion modules to the I/O bus.
display devices, sensors or supervisory tools. Only one device
may be connected at one time.

The connected device can be restricted to communicate only I/O bus


with the IQ4E or (if supported by the device) with the entire
Trend network (see Networking on page 4).

USB (Local Engineering Port)


I/O modules
The USB port allows connection of a PC running IQ SET
(System Engineering Tool). When connected in this way Several IQ4E variants are available to provide support for
IQSET can communicate across the entire Trend network (see differing numbers of I/O channels up to a maximum of 192 (16
Networking on page 4). onboard, 176 on I/O bus) (see Order Codes on page 10).

When not in use the connector is protected by a retained flexible The following I/O module ranges are compatible with the IQ4E:
plastic plug.
IQ4/IO see IQ4/IO Modules Data Sheet (TA201341).
Wallbus XCITE/IO see XCITE/IO Modules Data Sheet (TA201352).

The Wallbus port facilitates the connection of room display Up to 30 modules can be connected to the I/O bus, depending
devices (e.g. an RD-WMB series room display). Devices can be on the module range(s) used and the number of I/O channels
wired using either bus (daisy-chain) or star topology. supported by the controller (as described above).

These devices offer control and indication of parameters such Module Range IQ4/IO only IQ4/IO and/or XCITE/IO
as setpoint, fan speed and occupancy, as well as sensing
Number of Modules 30 15
temperature, humidity and CO2 levels.

The last module on the I/O bus must be fitted with a terminator.
A suitable terminator (compatible with IQ4/IO modules only) is
supplied with the IQ4E.

IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.3


IQ4E/.. Data Sheet

Networking Hardware
In order to connect to the Trend network the IQ4E will create its Universal Inputs(IN1 to IN10)
own internal LAN which includes the following nodes:
Each input channel will function as one of the following:
a CNC for its own controller,
a supervisor CNC (sCNC1) for its RS232 port, thermistor input,
a supervisor CNC (sCNC2) for its USB port, voltage input,
three virtual CNCs (vCNC1, vCNC2 and vCNC3), and digital input, or
a virtual INC (vINC). current input.

Supervisor Web Supervisor The input function is set automatically by the IQ4E strategy.
/Tool Browser /Tool IQSET
Thermistor input:Used for a thermistor (NTC 10 k @ 25C
(77F), -40 to 110C (-40F to 230F)), potentiometer (0 to
200k) or fan speed control. The thermistor bridge resistor is
12 k with a bridge supply 3.3 V.
Ethernet
RS232

USB
Example wiring

IQ4E
IQ4E
control
vINC vCNC1 CNC sCNC1 sCNC2
vCNC2 vCNC3 LAN

n n
Default CNC Addressing:The IQ4E device (outstation) n
address is factory-set (in the Address module) as follows:

Local LAN set to 20; Voltage input:Used with a 0 to 10 Vdc source.


Local Address set on a rolling basis in the range 11 to
119, so that in a batch of IQ4Es, each will have a different Example wiring
default address (printed on the units serial label).
+
sCNC1 Functionality:If the RS232 port address is set to 0 S
(default), sCNC1 is disabled and a connected device can only -
communicate with the IQ4E. If the address is configured to be
non-zero, sCNC1 is enabled with that address on the LAN and
allows a connected device to communicate with the entire Trend
network.
n n
sCNC2 Functionality:When a PC running IQSET is connected n
to the USB port it uses sCNC2. If the USB port address is set
to 0 (default), sCNC2 is dynamically created at address 125 for
the duration of the IQSET session. When the PC is removed Digital input:Used for a volt free contact, logic circuit (e.g.
sCNC2 times out and no longer exists on the network. If the TTL, CMOS), open collector (transistor) or open drain (FET).
address is configured to be non-zero, sCNC2 remains on the
network at all times. Example wiring
volt open logic
vCNC Functionality:Allows a supervisor tool/display to make free collector circuit
a permanent connection to the Trend network using TCP/IP. By
default all vCNCs are disabled. TTL /
CMOS
vINC Functionality:When the IQ4E joins a LAN on Ethernet, 270A
the controller with the lowest IP address assumes INC 0V
functionality (using its vINC at address 126); any vINCs in other
controllers on that LAN will automatically be disabled. The vINC
does not exist on a current loop LAN.

IC Comms:The IQ4E can communicate with other IQ n n


controllers and BACnet devices using IC Comms. Some n
controllers running earlier versions of firmware may not support
all IC Comms types. See Compatibility on page 9.
The volt free contact has a nominal wetting current of 270A.
The input is ON when the contact is closed.

An open collector or open drain must be able to sink 270A.


The input is ON when the transistor or FET conducts. Correct
polarity must be observed.

A logic circuit must be able to sink 270 A. The input will be


ON when the voltage present on the input terminal is less than
2Vdc (minimum 0 V). A voltage greater than 3.5 Vdc (maximum
50Vdc) or open circuit will turn the input OFF. Voltage levels
between 2 and 3.5 Vdc may cause indeterminate operation.

4 IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.


Data Sheet IQ4E/..

Current input:Used for 0 to 20 mA sources which can be Enclosure


externally powered or loop powered (from the Auxiliary Supply
Output, i.e. one of the AUX terminals). The IQ4E is housed in a polycarbonate case. Integral spring
clips on the back of the case enable the unit to be clipped on to
Example wiring (and quickly released from) a standard TS35 DIN rail.

Externally powered Loop powered The /230 version must be installed in a secondary enclosure
with a minimum protective rating of IP20 (or equivalent).

External The /24VAC version must be installed in a secondary enclosure


S Power S with a minimum protective rating of IP20 (or equivalent) or
Supply mounted outside normal reach (e.g. in a plenum).

The unit may be mounted horizontally or vertically but not


upside down or on its back:

n n n n n
24V
n n IQ4E
AUX

IQ4E

IQ4E
Analogue Outputs(OUT11 to OUT16)
These provide a variable control voltage between 0 and 10Vdc.
IQ4E
The output can source up to 20 mA (see Combined Supply) DIN rail
and sink up to 3 mA. end stop

Example wiring

n
n n
Rotating clear polycarbonate covers provide access for the
power, communications and I/O connections.

Input Power Supply


The IQ4E/.. has both 230 Vac and 24 Vac input power options.
00toto 10
10 Vdc
LOAD
LOAD

Vdc
00V
V /230:This option requires a 230 Vac 10%, 50/60 Hz supply
The input power earth (ground) terminal is isolated from the
input power neutral, and must be separately earthed (grounded)
Auxiliary Supply Output locally; this ground terminal is internally connected to the IQ4E
electronics earth (ground).
This output can be used to supply I/O devices (e.g. sensors).
It provides 24 Vdc 5% from AUX terminals 70, 71 and 72, with The 230 V supply must include a dedicated 5 A fuse complying
a return through terminal 73 or any C terminal. with IEC60269 (BS1362) and a suitably rated switch in close
proximity and be clearly marked as the disconnecting device for
The maximum available current is internally limited as follows: the unit. A 5A circuit breaker with high breaking capacity may
be used as an alternative.
Auxiliary Output (AUX) Terminals E N L
70 71 72
120 mA shared 120 mA
5A
The available current also depends on other current demands
(see Combined Supply).

Combined Supply
The IQ4Es combined supply provides power for the:

Analogue outputs,
Auxiliary supply terminals,
Wallbus,
RS232 port, and
I/O Bus supply.

A maximum combined supply current of 800 mA is available.


If the total power requirement of the combined supply exceeds
this limit it will be necessary to power some of the items using
external power sources.

Note: For further details on calculating the available current


from the combined supply, see the IQ4 Configuration Manual
(TE201263).

IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.5


IQ4E/.. Data Sheet

/24VAC:This option requires a 24 Vac 10%, 50/60 Hz, 44VA Current Loop(adjacent to current loop connector - operational
max or 48 Vdc +/- 15% 0.67A, 32 W supply. on /LAN variants only):

24 Vac supply Indicator Colour Function


24 Vac transformer RX Yellow Status of connection to previous device
TX Yellow Status of connection to next device
Fused Primary
Ethernet(on end of Ethernet connector):
24
Vac
Indicator Colour Function
OK Green Status of connection (Ethernet LINK)
Panel/enclosure ground. RX Yellow Presence of data reception

Inputs/Outputs (in line with the appropriate I/O terminals and


next to the label):

Indicator Colour Function


24V
48V Input Yellow On/Off state of associated input
(digital input mode only)
The local earth terminal (1) must be earthed (grounded) at the Output Yellow Light intensity varies with output voltage
controller. The 24 V supply must include a suitably rated switch
in close proximity and be clearly marked as the disconnecting Backup
device for the unit. Do not position the equipment so that the
disconnecting device is difficult to operate. The data (firmware, strategy, parameters) is stored in flash
memory which is non-volatile in the case of power failure.
48 Vdc supply Changes to the Address module are stored immediately. Other
changes are generally stored around midnight, in addition
48 Vdc supply structural changes (e.g. module interconnections) are stored
15s after the last change, and critical data changes (e.g
strategy values), are stored on power failure or other similar
fault conditions. The tools (e.g. IQSET) will send an archive
instruction after parameter changes causing immediate storage
Panel/enclosure ground. of changes.

A supercap is used to maintain the real time clock (time and


date). In the event of power failure this will support the clock for
8 days (typically).

24V Note: Operation at elevated temperature or high humidity levels


48V
will reduce the lifetime of the supercap. Extended operation in
these conditions may permanently reduce the capacity of this
Note:connection to the IQ4E is polarity independent. component and result in a reduction in the number of days that
the controller can successfully backup the time and date.
The local earth terminal (1) must be earthed (grounded) at the
controller. The 48 V supply must include a suitably rated switch Labels
in close proximity and be clearly marked as the disconnecting
device for the unit. Do not position the equipment so that the A small two part label is attached to the unit which displays the
disconnecting device is difficult to operate. units serial number and MAC address (in both text and barcode
format). Space is provided on the label for recording the units
Service Button device (outstation) address, LAN number and IP address (if
DHCP is not being used). It has a tear-off self-adhesive label
The Service Button can be used to generate a network message strip that also contains the serial number and MAC address
which identifies the IQ4E using its serial number to system (text and barcode) which can be adhered to a paper record, e.g.
tools, e.g. to find the IQ4Es device address and LAN number. It a building plan or log book.
can also be used to reset the IQ4E to factory defaults; for further
details see the IQ4 Configuration Manual (TE201263). A second large adhesive label is also supplied which contains
the units serial number in text and barcode formats. This
Indicators is intended to be mounted on the outside of the equipment
cabinet or enclosure containing the IQ4E. If the unit is located
Various indicators are provided giving feedback on the in a difficult-to-reach location, this label can be scanned from a
operational status of the controller. distance using a suitable barcode scanner.

General(in centre of cover): The barcodes on both labels conform to the code 128 auto
format.
Indicator Colour Function
Power Green Condition of input power supply
Watchdog Red Presence of a firmware/strategy fault
LAN OK Green Status of the Trend LAN
(operational on /LAN variants only)
I/O Bus Green Status of connection to I/O modules
Service Yellow Service button activated. Flashes if
a powered device is connected to the
USB port when IQ4E is not powered

6 IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.


Data Sheet IQ4E/..

Firmware The quantity of each type of module may be adjusted to match


the requirements of the application subject to the following:
The firmware in the IQ4E controls its basic functionality and
provides a range of modules that can be configured to produce A maximum of 4000 modules in total,
a control strategy. A maximum for each type of module, and
The IQ4Es memory capacity (measured in brIQs).
Modules
The maximum number of modules for each type, and number of
The range of modules provided in the IQ4E firmware are listed brIQs required per module are shown in the table above.
in the table below. Full details of each module can be found in
the IQ4 Configuration Manual (TE201263). The total available memory capacity varies with the number of
supported I/O channels:
Module brIQs Max. number of Modules Note
Address 24 1 (fixed) number of I/O channels maximum brIQs available
Alarm 14 (8) 16 30,000
Destination 32 30,000
Alarm Group 9 500 64 30,000
Alarm Route 9 500 96 45,000
Alarm Log 0 1 (fixed) 128 60,000
Analog Node 16 510 160 75,000
Digital Byte 16 1012 192 90,000
Digital Input 28 1500 Plot Modules
Directory 13 500 The IQ4Es Plot modules can plot any connectable module
Display 19 1500 output (analogue or digital). There are four types of Plot module:
Driver 57 500 Synchronised, Triggered, Periodic and COV (change of value).
Although all four types are BACnet interoperable, only periodic
Function 19 1000 plots can be compliant with the BACnet standard. All Plot
IC Comms 19 IP network = 1000 modules can generate a buffer ready alarm when the number of
Maximum of 500 shared records equals a notification threshold.
between MSTP and Trend
current loop. The maximum number of records per plot is 1000. The maximum
Interface 130 500 total number of records (for all plots) depends on the available
I/O Module 14 30 plot memory (measured in log points) and the type of plots used
each Synchronised plot record requires 5 log points, while
Knob 13 1500
each Triggered, COV or Periodic plot record requires 10 log
Logic 19 1000 points:
Loop 55 500
Network 0 maximum max. number of records
number of
NTD 30 limited by max. brIQs only plot memory synchronised triggered or
I/O channels
(log points) plots periodic plots
Option 0
16 1,000,000 200,000 100,000
OSS 34 500
32 1,000,000 200,000 100,000
Page 4 500
64 1,000,000 200,000 100,000
Plot 12 500
96 1,000,000 200,000 100,000
Program 0 1 (fixed)
128 1,000,000 200,000 100,000
Schedule Offset 21 500
160 1,250,000 250,000 125,000
Sensor 76 1500
192 1,500,000 300,000 150,000
Sensor type 12 99
Sequence 106 1 (fixed)
Note: A maximum of 100 plots can be serviced in a 1s period
(see opposite for max. steps)
(e.g. 100 x 1s plots only). This is calculated on the average plots
Switch 10 1500 serviced in 1s, so a 1 minute plot would contribute a 1/60. For
Time 38 1 (fixed) example 90 x 1s plots plus 360 x 1 min would give 96 (90+6)
Time Schedule 566 100 plots per second on average. The periodic and triggered plots
User 12 500 must also be counted and its up to the engineer to make his
best estimate.
Virtual CNC 9 3
Notes: Sequence Table Module
The number of brIQs used on these modules varies with The maximum number of steps in the sequence table varies
the module type. The largest size is shown here. with the number of supported I/O channels:
Includes a maximum of 50 exceptions per module.
These modules are always present in the IQ4E. number of I/O channels maximum sequence steps
Additional 5 brIQs required per input and output. 16 600
For IP networks a maximum of 1000 IC comms can be
32 600
configured but there is a maximum transmission rate of
300 IC comms per minute. For MSTP and Trend current 64 640
loop networks a maximum of 500 IC comms can be 96 960
configured but there is a maximum transmission rate 128 1280
of 100 IC comms per minute shared between the two
160 1600
networks.
For more details see the IQ4 Configuration Manual 192 1920
(TA201263).

IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.7


IQ4E/.. Data Sheet

Firmware Upgrades Web Server


New versions of firmware may be made available from time to Information from the IQ4 can be viewed or adjusted from a web
time to change or add functionality or to provide support for new client (PC, tablet or smartphone) over any TCP/IP network (e.g.
products. company intranets) using secure HTTPS protocol. All that is
required is the IQ4s IP address or host name, and a user name
Firmware can be upgraded using a PC running the IQTool and password. Once connection to the controller has been
Firmware Upgrade Applet, and to the IQ4E connected over made, it is possible to view/adjust occupation times, view the
Ethernet (recommended for speed) or the Trend current loop. alarm log, and view/adjust/graph individual module parameters.

Timemaster
The IQ4E can act as a system Timemaster to synchronise the
time and date across the Trend system. It can use SNTP (simple
network time protocol) to obtain precision current time from an
unauthenticated NTP server on the Internet. Daylight saving
can be implemented automatically (via timezone setting) or
manually by specified dates and time adjustment.

alarms
The IQ4E will generate Network, General, and Item alarms.
Network alarms are generated by the Trend Network nodes,
General alarms are generated when the IQ4E detects a
problem within its own hardware or program, and Item alarms
are generated by the strategy, and are normally due to a faulty
plant condition.

Network alarms are sent to supervisors or tools connected to


the RS232 local supervisor port, USB local engineering port, or
to one of the controllers vCNCs.
The web interface does not allow the strategy structure to be
General and Item alarms can be sent either to a designated modified (e.g. changing module interconnections, adding or
Trend LAN address, to an IP address, or as an email. deleting modules).
Alternatively, certain Item alarms (sensor, digital input, digital
driver readback, and plot), can be sent to a BACnet device. Graphical display pages (GraphIQs), which are configured using
IQ4Es display and directory modules, can also be accessed.
Alarms sent to a Trend LAN address, or to an IP address can
either be sent in text, coded, or attribute format. Network alarms
are sent in text format only.

For coded alarms the protocol limits the item number to 255
maximum. For text alarms the maximum item label length is
20 characters (although the 963 can be set up to use labels
previously learnt).

Sending an alarm by email requires the Email Server Address


to be set up in the address module. The Email Server Address
can be an IP address, an internet domain name, or a host name;
the internet domain name or host name require a DNS server
address or a WINS server address respectively to be set up in
the network module so that the name can be resolved.

All alarms (except Network alarms) are also stored locally in the
Alarm Log. The alarm log can record up to 300 alarms. Once this
limit is reached each new alarm will overwrite the oldest record.

For further details of web pages see the IQ4 Configuration


Manual (TA201263), the IQ4 Web User Guide (TC201256), and
the Graphical Display Pages Editor Manual (TE200629).

Language
The user can specify which language the IQ4E uses for the
display of web pages and for transmitted alarms. The standard
languages are in the controller as supplied. In the controller the
Address module has a language parameter which will be set
to the default language, but can be changed to any one of the
other available languages. The IQ4E can use languages which
require 8 bit code (i.e. special or accented characters) and can
also operate with right to left languages (e.g. Chinese, Arabic).

Identication
The IQ4E will identify itself as an IQ4 to w comms.

8 IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.


Data Sheet IQ4E/..

Strategy
In order to operate as a controller, the modules provided by the This produces a strategy file (filename.IQ4) that can be
firmware must be configured to define the way the controller downloaded to the controller to define its operation. This file
is to control the connected equipment. This configuration is consists of all the strategy module instances, their parameters,
known as the strategy. Strategies are configured using the and links. When this is downloaded it is stored in the controller
System Engineering Tool (IQSET). and then run using the controller firmware.

For details of using IQSET see the System Engineering Tool


Manual (TE200147).

Field Maintenance
The IQ4E requires no routine maintenance.
WARNING: Contains no serviceable parts. Do
! not attempt to open the unit. Failure to comply
may cause damage to the unit.

DISPOSAL
COSHH (Control of Substances Hazardous to Health -
UK Government Regulations 2002) ASSESSMENT FOR WEEE Directive:
DISPOSAL OF IQ4E.
At the end of their useful life the packaging, and
RECYCLING . product should be disposed of by a suitable
All plastic and metal parts are recyclable. The printed circuit recycling centre.
board may be sent to any PCB recovery contractor to recover
some of the components for any metals such as gold and silver. Do not dispose of with normal household waste.
Do not burn.

Compatibility
Browsers: This device has been successfully tested with Controllers: IQ3/IQ4 directly and IQ1, IQ2, IQL by way of
Internet Explorer (v10 & 11), Chrome (v29.0.1547.0), Mozilla XTEND. IQ4E/../LAN communicates with IQ2, IQ1 directly.
Firefox (v23), Safari (v5.1.7) and with the default browser on the IQeco by way of IQ4NC.
following device operating systems:
Strategies: IQ1, IQ2, IQ3 can be imported into IQSET,
Apple iOS 8.1.3 converted into IQ4 strategies, and then downloaded into an
Android 5.0 Lollipop IQ4E. If the strategy file accesses I/O channels beyond those
Windows Phone 8.1 available in the IQ4E the strategy will be rejected.

It should work with all modern browsers, smart phones, and Ethernet Nodes:XTEND, NXIP, or EINC.
tablets (with JavaScript enabled) available at the date of release
of this product. Note: NXIP or EINC must not be used in an automatic IP
addressing (DHCP) environment.
Owing to the rapidly changing nature of web devices, new
devices and browsers will become available after the release of BACnet Devices:IQ4E Compatibility is defined in IQ4 Product
this product. If you would like to check the compatibility of IQ4E Implementation Conformance Statement (TP201248).
with your device, please connect to: iq4demo.trendcontrols.
com. Log in with username: mobile and password: trend.

Supervisors and Displays:963 v3.5 or greater, 916, IQView,


IQView4, IQView8, RD-IQ, SDU-xcite.

Note: The NDP is not compatible with IQ4E; it will not recognise
an IQ4E connected to its network.

Wallbus:RD-WMB, RS-WMB, RV-WMB.

Utility Software:IQSET v7.06 or greater

I/O Modules:IQ4/IO range, XCITE/IO (IQ3) range.

IC Comms:IQ4, IQ3, IQ2, IQeco, IQL, and IQ1 (v3 onwards).

Note: Some controllers running earlier versions of firmware may


not support all IC Comms types. Refer to the IQ4 Configuration
Manual (TE201263) for full compatibility details. For details
on using IC Comms with IQL controllers refer to the Trend
LonWorks Products Engineering Manual (TE200292).

IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.9


IQ4E/.. Data Sheet

Installation
The IQ4E is designed to be clipped on to a standard TS35 DIN rail. The IQ4E must be installed in a secondary enclosure with a
minimum protective rating of IP20 (or equivalent). The /24VAC version can also be mounted outside normal reach (e.g. in a plenum).

The installation procedure involves:


Mounting the controller in position
Connecting power
Connecting Ethernet (if required) Checking network
Connecting RS232 (if required) Configuring the strategy
Connecting Current Loop (../LAN only) Testing strategy using Controller Simulation in IQSET
Connecting the I/O channels (as required) Downloading strategy and other configuration files
Connecting Wallbus (if required) Check BACnet communications
Mounting and connecting I/O modules (if required) Connecting inputs and checking operation
Powering up Connecting outputs and checking operation
Setting up IP address parameters (if using Ethernet)
Setting up LAN number and device address,

A full description of installing the unit is given in the IQ4E/.., IQ4NC/16/.., IQ4NC/32/.. Installation Instructions - Mounting (TG201338)
and IQ4E/.. IQ4NC/16/..., IQ4NC/32/... Installation Instructions - Configuring (TG201339).

Order Codes
IQ4E/[CHAN]/[LAN]/BAC/[Power]

[CHAN] Number of supported I/O channels: 16, 32, 64, 96, 128, 160, 192
[LAN] Blank No Trend current loop
LAN Trend current loop option fitted
[Power] 230 230 Vac input power supply
24VAC 24 Vac/48 Vdc input power supply

Note: XML web services are included as standard in the IQ4E.

IQ4E/16/BAC/230 IQ4E with 16 I/O channels and 230 Vac supply


IQ4E/32/BAC/230 IQ4E expandable to 32 I/O channels and 230 Vac supply
IQ4E/64/BAC/230 IQ4E expandable to 64 I/O channels and 230 Vac supply
IQ4E/96/BAC/230 IQ4E expandable to 96 I/O channels and 230 Vac supply
IQ4E/128/BAC/230 IQ4E expandable to 128 I/O channels and 230 Vac supply
IQ4E/160/BAC/230 IQ4E expandable to 160 I/O channels and 230 Vac supply
IQ4E/192/BAC/230 IQ4E expandable to 192 I/O channels and 230 Vac supply
IQ4E/16/BAC/24VAC IQ4E with 16 I/O channels and 24 Vac/48V dc/48V dc supply
IQ4E/32/BAC/24VAC IQ4E expandable to 32 I/O channels and 24 Vac/48V dc supply
IQ4E/64/BAC/24VAC IQ4E expandable to 64 I/O channels and 24 Vac/48V dc supply
IQ4E/96/BAC/24VAC IQ4E expandable to 96 I/O channels and 24 Vac/48V dc supply
IQ4E/128/BAC/24VAC IQ4E expandable to 128 I/O channels and 24 Vac/48V dc supply
IQ4E/160/BAC/24VAC IQ4E expandable to 160 I/O channels and 24 Vac/48V dc supply
IQ4E/192/BAC/24VAC IQ4E expandable to 192 I/O channels and 24 Vac/48V dc supply
IQ4E/16/LAN/BAC/230 IQ4E with 16 I/O channels, Trend current loop and 230 Vac supply
IQ4E/32/LAN/BAC/230 IQ4E expandable to 32 I/O channels, Trend current loop and 230 Vac supply
IQ4E/64/LAN/BAC/230 IQ4E expandable to 64 I/O channels, Trend current loop and 230 Vac supply
IQ4E/96/LAN/BAC/230 IQ4E expandable to 96 I/O channels, Trend current loop and 230 Vac supply
IQ4E/128/LAN/BAC/230 IQ4E expandable to 128 I/O channels, Trend current loop and 230 Vac supply
IQ4E/160/LAN/BAC/230 IQ4E expandable to 160 I/O channels, Trend current loop and 230 Vac supply
IQ4E/192/LAN/BAC/230 IQ4E expandable to 192 I/O channels, Trend current loop and 230 Vac supply
IQ4E/16/LAN/BAC/24VAC IQ4E with 16 I/O channels, Trend current loop and 24 Vac/48V dc supply
IQ4E/32/LAN/BAC/24VAC IQ4E expandable to 32 I/O channels, Trend current loop and 24 Vac/48V dc supply
IQ4E/64/LAN/BAC/24VAC IQ4E expandable to 64 I/O channels, Trend current loop and 24 Vac/48V dc supply
IQ4E/96/LAN/BAC/24VAC IQ4E expandable to 96 I/O channels, Trend current loop and 24 Vac/48V dc supply
IQ4E/128/LAN/BAC/24VAC IQ4E expandable to 128 I/O channels, Trend current loop and 24 Vac/48V dc supply
IQ4E/160/LAN/BAC/24VAC IQ4E expandable to 160 I/O channels, Trend current loop and 24 Vac/48V dc supply
IQ4E/192/LAN/BAC/24VAC IQ4E expandable to 192 I/O channels, Trend current loop and 24 Vac/48V dc supply

UPGRADES
If the number of supported I/O channels needs to be increased, the following controller upgrades are available:

IQ4E/16-32/UP Upgrade from 16 to 32 channels


IQ4E/32-64/UP Upgrade from 32 to 64 channels
IQ4E/64-96/UP Upgrade from 64 to 96 channels
IQ4E/96-128/UP Upgrade from 96 to 128 channels
IQ4E/128-160/UP Upgrade from 128 to 160 channels
IQ4E/160-192/UP Upgrade from 160 to 192 channels

Note: An upgrade will only increase the number of I/O channels that are supported in the firmware; an upgrade does not change the
hardware. Additional I/O modules will be required to make use of the extra channels.

10 IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.


Data Sheet IQ4E/..

Accessories
IQ4/IO/.. Range of IQ4/IO modules - see IQ4/IO Modules Data Sheet (TA201341)
XCITE/IO/.. Range of XCITE/IO modules - see XCITE/IO Modules Data Sheet (TA201352)

Specifications
Electrical Supply Current :50 mA maximum*.
Number of Devices :up to 14 (subject to power loading)
Power Input
/230 :230 Vac 10% 50/60 Hz, 70 VA max. USB Local Engineering Port
/24VAC :24 Vac 10% 50/60Hz, 44 VA max or Transmission :USB 2.0.
:48 Vdc 15% 0.67A, 32 W Data Rate :480 Mbits/s (Hi-Speed).
Fusing :No replaceable fuses required. Distance :5 m (5 yards) maximum.
Power Failure Protection Address (sCNC2) :1 to 119, (2, 3 and 10 not permitted)
Strategy & data :non-volatile flash memory. settable in software.
Real time clock :supercap, maintained for up to 8 days
(typical). I/O Bus
Clock Accuracy :10 s per month (typical). Maximum Total Length :300 m (328 yds), using IQ4/IO modules
Cycle Time :Sequence table 1s. only;
30 m (33 yds), using IQ4/IO and/or
Ethernet Network XCITE/IO modules.
Transmission :10/100 BASE-T (IEEE 802.3). Maximum Modules :30 (IQ4/IO modules only);
Connection :RJ45, auto MDI-X. 15 (IQ4/IO and/or XCITE/IO modules).
Cable Type :Cat 5e, UTP (unshielded twisted pair). Maximum Channels :192 (including 16 onboard).
Distance (to hub) :100 m (109 yds) maximum. Bus Supply 24 Vdc 5%; 800 mA maximum*.
Virtual CNCs :3. Cable Type :Belden 3084A (up to 100 m);
Addresses :Not set by default set to desired value Belden 7895A (up to 300 m).
in range 1 to 119 (excluding 2, 3, & 10) For further details see:
using configuration mode. Address IQ4/IO Modules Data Sheet (TA201341);
must be unique on LAN. XCITE/IO Modules Data Sheet (TA201352).

Current Loop (/LAN variants only) Inputs/Outputs


Transmission :20 mA, two wire current loop, opto-
isolated, polarity independent receiver, Universal Inputs
balanced transmitter. Number of Channels :10.
Baud Rate :1k2, 4k8, 9k6, 19k2, or 38k4; Function :Measuring voltage, current, thermistor
auto-detected (default) or settable in or digital input (function set by strategy).
software. Input Noise Rejection :Minimum 60 dB series mode rejection
Device Address :1 to 119, (2, 3 and 10 not permitted) at input power supply frequency.
settable in software. Input Resolution :12 bit (4096 steps).
LAN Number :1 to 119, (2, 3 and 10 not permitted) Voltage Input
settable in software. Input range :0 to 10 V.
Distance (node to node) :dependent on cable type and baud rate Input resistance :9.4 k.
(see table below): Accuracy :0.5% of span (50 mV).
Current Input
Baud Rate Input range :0 to 20 mA.
Cable Type
1k2 4k8 9k6 19k2 38k4 Input resistance :120 .
Trend Shielded Accuracy :0.5% of span (100A).
TP/2/2/22/ twisted pair Thermistor Input
HF/200 2 pairs (4 Temperature (NTC 10 k @ 25C (77F))
Belden 8723 conductors) Input range :-40 to 110C (-40F to 230F)
Accuracy :0.3C (-20C to 90C (-4F to 194F));
Trend Shielded 1000 m 700 m 350 m 0.4C (<-20C (-4F) or >90C (194F))
TP/1/1/22/ twisted pair (1090 yds) (765 yds) (380 yds) Resistance
HF/200 1 pair (2 Input range :0 to 200 k
Belden 8761 conductors) Accuracy :1% of measured value or 10 ,
Belden 9182 Twinaxial (2 whichever is the greater
Belden 9207 conductors) Bridge resistor :12.2 k.
Bridge supply :3.3V.
Note: Adjacent devices may specify different maximum cable Digital Input
lengths and baud rates. The shortest cable length (for the chosen Input voltage :0 to 5 Vdc typical (50 Vdc maximum).
baud rate) applies when connecting to the IQ4E current loop. ON state :<2.5 V @ 270 A (sink).
OFF state :>3.5 V (or open circuit).
RS232 Local Supervisor Port Count rate :30 Hz max. (pulse width 16.6 ms).
Transmission :RS232, EIA/TIA/232E, V28 supports
Trend System comms.
Distance :15 m (16 yards) maximum.
Supply 24 Vdc 5%; 60 mA maximum.
Baud Rate :9k6.
Address (sCNC1) :1 to 119, (2, 3 and 10 not permitted)
settable in software.

Wallbus
Cable Type :Unscreened twisted pair.
Distance :60 m (200 ft) maximum.

IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.11


IQ4E/.. Data Sheet

Analogue Outputs I/O Bus :PCB edge connector for use with
Number of Channels :6. IQ4/IC/LINK rigid interconnector,
Function :Variable control from strategy of valve/ IQ4/IC/ADPT cable adapter, or IQ4/
damper actuators, voltage to current/ IC/TERM terminator.
pressure converters, relay modules, RS232 Supervisor Port :RJ11 (FCC68).
lighting dimmers, etc. Ethernet Port :RJ45 connector.
Voltage Range :0 to 10Vdc. USB Engineering Port :Micro B connector.
Current (maximum*) :up to 20 mA (source) or 3 mA (sink). USB Expansion Port :USB Type A (for future use)
Accuracy :0.5% of span.
Resolution :11 bit (2048 steps). Environmental
Auxiliary Supply Output EMC :EN61326-1:2013.
Voltage :24 Vdc 5%. Immunity :Table 2 - for equipment intended for
Current (maximum*) :120 mA shared between terminals 70 and use in industrial locations.
71, plus 120 mA from terminal 72. Emissions :Class B.
Safety :EN61010-1:2010.
*Available current may be affected by demands on other CB certificate
outputs - see Combined Supply on page 5. IQ4E/LAN/230 :NO90303
IQ4E/230 :NO90304
Indicators IQ4E/LAN/24VAC :TBD
IQ4E/24VAC :TBD
Power ( ) :Green LED Ambient limits
Watchdog ( ) :Red LED Storage :-25C (-13F) to +60C (+140F).
LAN OK ( ) :Green LED Operating :-25C (-13F) to +55C (+131F).
I/O Bus ( ) :Green/Red LED
Service Button ( ) :Yellow LED Note: For temperatures below 0C (32F) special care must
RX (current loop) :Yellow LED be taken that there is no condensation on or within the unit.
TX (current loop) :Yellow LED
OK (Ethernet) :Green LED Humidity :0 to 90%RH non-condensing.
RX (Ethernet) :Yellow LED Altitude :<4000 m (13124).
IN1 to IN10 :Yellow LED Pollution Degree :2 (Only non-conducting pollution
OUT11 to OUT16 :Yellow LED occurs).
Protection :IP20 if mounted in an enclosure rated
Mechanical at IP20 or equivalent.

Dimensions (WxHxD) :192.5 mm (7.55) x 116 mm (4.57)


x 58.5 mm (2.3).
Material
Main body :Flame Retardant Polycarbonate (white)
Terminal covers :Flame Retardant Polycarbonate
(translucent orange).
Weight
/24VAC :0.51 kg (1.14 lb)
/230 :0.52 kg (1.15 lb)
Mounting :TS35 DIN Rail (EN500022).

Connectors
Power
Connector type :2 part connector with rising cage clamp
screw terminals.
Cable size :0.14 to 2.5 mm2 (22 to 12 AWG).
Inputs/Outputs, Current Loop, Wallbus & AUX (power out).
Connector type: :2 part connector (0.2 pitch) with rising
cage clamp screw terminals.
Cable size :0.14 to 2.5mm2 (22 to 12 AWG)

iPad and iPhone are trademarks of Apple Inc., registered in the U.S. and other countries. Android is a trademark of Google Inc.
Windows is either a registered trademark or trademark of Microsoft Corporation in the United States and/or other countries

Please send any comments about this or any other Trend technical
publication to [email protected]

2016 Honeywell Technologies Srl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls
Division of Honeywell Technologies Srl, Z.A. La Pice, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation
to notify any person of such revisions or changes.
Trend Control Systems Limited
Albery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

12 IQ4E/.. Controller Data Sheet TA201340 Issue 5, 13-Sep-2016. Applies to v3.41.