This document contains a cold store refrigeration load calculation. It provides specifications of the cold store dimensions and insulation. It then calculates the total refrigeration load from factors such as insulation heat leak, air changes, lighting, worker load, product load, fan load, and defrost heat. The total calculated refrigeration load is provided.

Uploaded by

EngFaisal Alrai
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
65 views

Cathodic Protection

This document contains a cold store refrigeration load calculation. It provides specifications of the cold store dimensions and insulation. It then calculates the total refrigeration load from factors such as insulation heat leak, air changes, lighting, worker load, product load, fan load, and defrost heat. The total calculated refrigeration load is provided.

Uploaded by

EngFaisal Alrai
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

COLD STORE CALCULATION

ENG. FAISAL RAI

Cold store refrigeration load

Specification L
Dimensions: LXWXH m 20
Insulation thickness : m 0.25
20.25
External store surface area m 735.375
Maximum ambient temperature C 35
Store temperature -30
Load calculation
1 Insulation heat leak through walls, roof and floor
Conductivity of polystyrene u = ( kcal/h mC ) 0.033
Temperature difference between ambient and store dT C 65
Thickness of polystyrene ( m) 0.25
Surface area of store A = ( m 2 ) 735.375
Heat leak = u A dT kcal/ 47799.4
2 Air changes
Average of 2.7 air changes in 24 h ACH / 2.7
Store volume = m 3 1000
Heat gain (35C and 60% R.H. air) kcal/m 3 40
Air change heat gain = 1000 2.7 40 24 = kcal/ 4500
3 Lights (left on during working day)
1000W = 860 kcal/h 860
4 Men working
1 man working at -30C gives off kcal/ 378
2 men working is equivalent to kcal/h 756
5 Product load
** 5.5 kcal/kg for fish load at an average temperature of -20C 5.5
Fish loaded per day kg 1000
Product load = ( kg * kcal/kg ) / 24 = kcal 229.167
6 Fan load
3 250W x 0 .860 ( 1 W = 0.860 kcal /h ) 645
7 Defrost heat
1 defrost of 8440 W for 1 h (recovered over 6 h) = kcal/ 1209.73

Total calculated refrigeration load (sum of Items 1 to 7) kcal/ 55139.3

Total refrigeration requirement with allowances (Ref.load 24 18 ) = kcal/h 73519


TR 24.3118
** PRUDUCT TYPE ( Kcal / kg ) .from tables
COLD STORE CALCULATION
ENG. FAISAL RAI

W H
10 5
0.25 0.25
10.25 5.25