Cathodic Protection
Cathodic Protection
Specification L
Dimensions: LXWXH m 20
Insulation thickness : m 0.25
20.25
External store surface area m 735.375
Maximum ambient temperature C 35
Store temperature -30
Load calculation
1 Insulation heat leak through walls, roof and floor
Conductivity of polystyrene u = ( kcal/h mC ) 0.033
Temperature difference between ambient and store dT C 65
Thickness of polystyrene ( m) 0.25
Surface area of store A = ( m 2 ) 735.375
Heat leak = u A dT kcal/ 47799.4
2 Air changes
Average of 2.7 air changes in 24 h ACH / 2.7
Store volume = m 3 1000
Heat gain (35C and 60% R.H. air) kcal/m 3 40
Air change heat gain = 1000 2.7 40 24 = kcal/ 4500
3 Lights (left on during working day)
1000W = 860 kcal/h 860
4 Men working
1 man working at -30C gives off kcal/ 378
2 men working is equivalent to kcal/h 756
5 Product load
** 5.5 kcal/kg for fish load at an average temperature of -20C 5.5
Fish loaded per day kg 1000
Product load = ( kg * kcal/kg ) / 24 = kcal 229.167
6 Fan load
3 250W x 0 .860 ( 1 W = 0.860 kcal /h ) 645
7 Defrost heat
1 defrost of 8440 W for 1 h (recovered over 6 h) = kcal/ 1209.73
W H
10 5
0.25 0.25
10.25 5.25