System Sensor Pressure Switch Model EPS40-2

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

EPS40-1 AND EPS40-2

Supervisory Pressure
Switches

System Sensor EPS40 Series switches are designed for

use in dry pipe systems or pressure tanks and water

pressure supplies of automatic water control valves.

Features The EPS40-1 has a single SPDT switch while the EPS40-2 model
Sensitivity adjustment wheel, no special tools required contains two SPDT switches. The EPS40 Series features field
adjustable pressure sensitivity to provide an alarm response between
Reinforced diaphragm resists pressure spikes 10 and 100 psi. All models are factory set for use in a nominal 40 psi
Two conduit entrances system. The EPS40-1 is factory set to respond at 30 psi at decreasing
Both one- and two-switch models available pressure while the EPS40-2 is factory set to respond at 50 psi on
rising pressure and 30 psi at decreasing pressure. The pressure
adjustment wheel requires no special tools and does not affect
Agency Listings switch synchronization on the EPS40-2. The EPS40-1 and EPS40-2
supervisory pressure switches are NEMA 4 rated.

118f/01 0X0A7.AY CS169


S739

VdS
G4020028 7770-1209:147 167-93-E

Specifications, EPS40-1 and EPS40-2


Architectural/Engineering Specifications EPS40-1 (SPDT), EPS40-2 (2/SPDT)
Model shall be an EPS40-1 or EPS40-2 pressure type waterflow switch as manufactured by System Sensor of St. Charles, IL. They shall be installed on the sprinkler
system with connection as shown on the drawings and/or as specified herein. Pressure switches shall be of the bellows-activated type. Switches shall have
a maximum service pressure rating of 250 psi and shall be adjustable from 10 100 psi. There shall be one (1) or two (2) SPDT contacts rated at 10.0 Amp @
125/250 VAC and 2.5 Amp @ 6/12/24 VDC. The contractor shall furnish and install, where indicated on the plans, pressure switches according to appropriate
NFPA standards. Switches shall be provided with a NPT male pressure connection to be connected into the air supply line on the system side of any shut-off
valve. Switches shall provide 1 knockout type and 1 open hole for conduit fitting attachment and a ground screw provision for electrical grounding.
The switch enclosure shall be weatherproof and carry a UL 4x/NEMA 4 rating when used with proper electrical fittings and conduit. The cover shall incorporate
tamper-resistant screws. The unit shall be listed by Underwriters Laboratories, Inc., the California State Fire Marshal, MEA, CSFM, LPCB, VdS and approved by
Factory Mutual.
Specifications, EPS40-1 and EPS40-2 (continued)
Physical/Operating Specifications
Maximum Operating 250 psi Operating Temperature Indoor or outdoor use:
Pressure Range 40F to 160F (40C to 71C)
Maximum Adjustment 10 to 100 psi Cover Tamper Switch UL Models: Optional P/N 546-8000
Pressure Range ULC Models: Factory Installed
Differential Approximately 3 psi @ 10 psi, 6 psi @ 100 psi Enclosure Rated UL 4x, NEMA 4 for indoor or outdoor use
Factory Setting EPS40-1 operates at decreasing pressure at 30 psi Shipping Weight 1.2 lbs. (.54 Kg)
EPS40-2 operates at increasing pressure at 50 psi
and decreasing pressure at 30 psi
Switch Contact Ratings EPS10-1: One set SPDT (Form C) Service Use Automatic Sprinkler: NFPA 13
EPS10-2: Two sets SPDT (Form C) One or Two Family Dwelling: NFPA 13D
10.0 A, HP @ 125/250 VAC Residential Occupancies up to 4 Stories: NFPA 13R
2.5 A @ 6/12/24 VDC National Fire Alarm Code: NFPA 72
Pressure Connection NPT male Warranty 3 years
Dimensions 5.12 H 3.325 W 4.250 L
(13.0 cm 8.4 cm 10.8 cm)

Typical Sprinkler Applications


WIRE TO SUPERVISORY WIRE TO ALARM
CIRCUIT OF FIRE ALARM INDICATING CIRCUIT
EPS40 CONTROL PANEL EPS40 OF FIRE ALARM
CONTROL PANEL
TO
SPRINKLER
SYSTEM

INSTALL CHECK
BLEEDER DRY VALVE
CHECK VALVE FOR PIPE WATER
VALVE TESTING VALVE MOTOR
GONG
AIR LINE
SHUT-OFF
VALVE WATER LOCAL ALARM
OS & Y BY-PASS SHUT OFF
VALVE TEST VALVE
VALVE

DRY SYSTEM

Electrical Connections Pressure Switch Basic Dimensions


MODELS EPS40-1 MODELS EPS40-2 41/4

SWITCH AT 40 P.S.I. (NORMAL)


SWITCHES AT 30 P.S.I. (LOW TRIP PT.) GROUND
B B SCREW
CO
M

B COM COM
A

COM A A (GREEN) SWITCH #2 HEX


A
SW1 SW2 ADJUSTMENT
B

SWITCH AT 30 P.S.I. (LOW TRIP PT.)


SWITCHES AT 40 P.S.I. (NORMAL) SCREW
B
COM B B
A COM COM
A A 51/8
SW1 SW2 MAIN ADJUSTMENT
WHEEL
SWITCH 1 SWITCHES AT 50 P.S.I. (HIGH TRIP PT.)
LOCKING
B B SCREW
COM COM 1/2 NPT
A A
SW1 SW2

Ordering Information
Part No. Description
EPS40-1 Low Pressure Supervisory Switch, One SPDT, 10100 PSI
EPS40-2 High/Low Pressure Supervisory Switch, Two SPDT, 10100 PSI
EPSA40-1 Low Pressure Supervisory Switch, One SPDT, 10100 PSI (ULC Model)
EPSA40-2 High/Low Pressure Supervisory Switch, Two SPDT, 10100 PSI (ULC Model)
Replacement Parts
S07-66-XX Replacement Tamper Screws for Cover of EPS
WFDW Replacement Tamper Proof Wrench for Cover of EPS
546-8000 Cover Tamper Switch for EPS Series

2006 System Sensor.


3825 Ohio Avenue St. Charles, IL 60174 Product specifications subject to change without notice. Visit systemsensor.com for
current product information, including the latest version of this data sheet.
Phone: 800-SENSOR2 Fax: 630-377-6495 A05-0177-010 9/06 #1676