Compact NSX, Compact Ins Inv and Masterpact NW - DC - DC PV Catalogue
Compact NSX, Compact Ins Inv and Masterpact NW - DC - DC PV Catalogue
Compact NSX, Compact Ins Inv and Masterpact NW - DC - DC PV Catalogue
Compact NSX
Compact INS/INV
Masterpact NW
DC - DC PV
Power circuit breakers and switch-disconnectors
direct current from 16 to 4000 A
Compact NSX, Compact INS/INV and
Masterpact NW direct current
A complete DC offer
from 16 to 4000 A
Compact NSX, Compact INS/INV and Masterpact NW direct current (DC) circuit
breakers are used to protect and control low-voltage distribution systems.
I
A complete DC offer
Compact NSX DC from 16 to 1200 A
V
/ 750
3 6 kA 50 V
4 P F
1 0 0 kA / 7 1200
3P /
S 00 V NSX 00 A)
6 kA / 5 V 12 0 0 12
F
3
/ 500 0 NSX 00 A) (
0 kA 1 2 0 1 0
S
1 0
/ 600
V NSX A) (
5 0 kA X 1200 (800
N 00 V N S
630 630 A
)
3 6 kA / 5 V NSX 0 A) (
F / 500 63 0 60
2P 8 5 k A
00 V NSX ) (
M kA / 5 S X 400 (500 A
1 0 0 N 0A)
50 V 50 0
S
kA / 2 N SX2 A) (4
3 6 6 0 5 0
F 50 V 1
NSX 0 A) ( 2
5 0 kA / 2 100 16
N 50 V NSX 0 A) (
8 5 kA / 2 (10
M
The Compact NSX range is designed for DC - 85 kA in a 2 poles version, for systems
voltages from 24 to 750 V and offers: y 500 V
b a wide selection of models suited to many v S
applications: - 100 kA in a 2 poles version, for systems
v 1, 2, 3 and 4 poles up to 160 A y 500 V
v 3 and 4 poles from 250 to 630 A - 100 kA in a 3 or 4 poles version, for systems
v 2 poles from 630 to 1200 A y 750 V
b high breaking capacities, with four b fewer frame sizes: just two poles pitches (35
performance levels F, N, M and S: and 45 mm) for easy integration in installation
v F systems (enclosures, machines, etc.)
- 36 kA in a 1 pole version, for systems y 250 V b accessories for insulation and series or
- 36 kA in a 2 poles version, for systems parallel connection of poles, suited to the
y 500 V particularities of DC applications
- 36 kA in a 3 or 4 poles version, for systems b fixed and withdrawable versions (3 and 4
y 750 V poles, DC type).
v N Breaking capacity Icu for 250 V per pole and
- 50 kA in a 1 pole version, for systems y 250 V L/R = 15 ms (1)
- 50 kA in a 2 poles version, for systems (1P: 250 V, 2P: 500 V, 3P: 750 V)
y 600 V (1) L/R = time constant of the distribution system
v M (see page A-11).
- 85 kA in a 1 pole version, for systems y 250 V
NSX160 DC -1P. NSX160 DC - 2P. NSX250 DC - 3P. NSX630 DC - 3P. NSX1200 DC - 2P.
II
from 16 to 4000 A
Masterpact NW DC from 1000 to 4000 A
40 A)
NW 4000
0V 20 A)
(
/ 90 V NW 2000
kA 750
35 / (
H kA 0V 10 A)
50 / 50 NW 1000
H 5k
A 0V (
8 / 50
H kA
35
N
The Masterpact NW range is designed for DC voltages from 24 to 900 V and offers:
b 2 versions : C/D (3 poles)
E (4 poles)
b three current ratings: 1000, 2000 and 4000 A
b two high breaking-capacity levels N and H.
Breaking capacity Icu for L/R = 15 ms (1) for 500, 750 or 900 V system voltages:
v N
- 35 kA for systems y 500 V
v H
- 85 kA for systems y 500 V
- 50 kA for systems y 750 V
- 35kA for systems y 900 V
b two models:
v circuit breaker for the protection of power circuits and loads
v switch-disconnector for circuit control and disconnection
b fixed and drawout versions for the entire range.
(1) L/R = time constant of the distribution system (see page A-11).
III
IV
Compact NSX DC PV,
Compact INS PV and
Masterpact NW DC PV
A complete DC offer
for solar application
from 80 to 4000 A
V
Compact NSX DC PV
circuit breakers and switch-disconnectors
VI
Optimising the management of your electrical
installation
Schneider Electrics Compact NSX DC PV circuit breakers and switch-disconnectors are used to control a circuit and
achieve isolation.
With the COM option, they can be integrated into an energy management system, which provides information on:
the state of the device (O/C)
remote Opening/Closing control
number of operations.
@
Firewall
bus
Mod
Modbus
Modbus IFM
interface
iRIO RTU
The iRIO RTU (remote terminal unit) can both be used as
Ethernet coupler for the PowerLogic System devices and for
any other communicating devices operating under Modbus
RS485 protocol. Data is viewable via a standard web
FDM switchboard browser.
display unit
VII
Compact INS PV
switch-disconnectors
Photovoltaic applications
VIII
Masterpact NW HADCD-PV
switch-disconnectors
Schneider Electrics Masterpact NW HADCD-PV switch-disconnectors are used for circuit control and disconnection.
IX
Energy management
has never been simpler
Simple-to-install Smart Panels connect your building to real savings
in 3 steps
Measure
Embedded and stand-
alone metering & control
capabilities
Connect Save
> Integrated communication > Data-driven energy efficiency
interfaces actions
> Ready to connect to > Real time monitoring and control
energy management > Access to energy and site
platforms information through on-line
services
X
Measure
"Smart Panels" mean
visible information
Grouping most of the electrical protection,
command and metering components, the
switchboards are now significant sources
of data locally displayed and sent via
CLOUD communication networks.
connect
and ready to be linked
to expertise
Smart Panels use reliable, simple to install
and use displays, and Ethernet and Modbus
interfaces on the EnerlinX communication
system.
Information is safely transmitted through the
most efficient networks:
Modbus SL inside switchboards, between
components
Ethernet, on cable or WiFi, inside the
building and connecting switchboards,
computers,
Ethernet on DSL or GPRS, for access to
on-line services by Schneider Electric.
Energy experts, wherever they are, are
now able to provide advises based on
permanently updated data of the building.
Save
CLOUD
XI
TOOLS
Ecodial
Presentation 2
1
Presentation The benefits of a comprehensive
and optimised range design
DB416526.eps
Compact Compact NSX, Compact INS/INV and Masterpact DC circuit breaker ranges
NSX1250 NA DC PV comply with:
b the main international standards and in particular IEC 60947-1/2/3
Ui 1000 V Uimp 8 kV b European (EN 60947-1 and EN 60947-2) and the corresponding national
Ue (max) 1000V standards: France NF, Germany VDE, UK BS, Australia AS, Italy CEI
Icw 20kA/1s
Icm 20kA Compact b the specifications of the marine classification companies (Veritas, Lloyds Register
DB418157.eps
DB416572.eps
NW20 HADCD-PV
Ui 1000V Uimp 12kV Pollution degree
Ue 1000 V c 3P in series
Icw 85kA/1s Compact NSX and Masterpact NW DC circuit breakers are certified for operation
Icm 85kA
under pollution conditions in industrial environments, as per standard IEC 60947,
corresponding to:
IEC 60947-3
b pollution degree 3 (Compact NSX, Compact INS/INV)
Ith 2000A 55C
b pollution degree 4 (Masterpact NW).
Ue (V) Ie (A) Tropicalisation
DC22A 1000 2000
Compact NSX, Compact INS/INV and Masterpact NW DC circuit breakers have
successfully passed
the tests prescribed by the following standards for extreme atmospheric conditions:
NW20 HDC-D rating plate. NW20 HADCD-PV rating b IEC 60068-2-1 - dry cold (-40 C)
plate.
b IEC 60068-2-1 - dry heat (+85 C)
b IEC 60068-2-30 - damp heat (95 % relative humidity at +55 C)
b IEC 68-2-52 (level 2) - salt mist.
Environmental protection
Schneider Electric circuit breaker ranges benefit from Eco-design:
b use of materials not representing a danger to the environment
b non-polluting production units complying with ISO 14001 standards
b filtered breaking for high current ratings to avoid pollution in the switchboard
b low dissipated energy per pole, making energy losses insignificant
b marking of products in view of sorting recyclable materials at the end of the service
life.
2
specifically for DC - DC PV
applications
connection of poles
Series connection - controlled temperature rise and
guaranteed performance
Schneider Electric DC circuit breakers comply with product standards
IEC 60947-1 and 2.
To that end, series connection of poles meets:
b temperature-rise conditions. Connections specifically designed to dissipate heat
mean the thermal model is equivalent to that for AC applications. The devices
dissipate the temperature rise produced by relatively short series connections
b optimum safety conditions. Connections are designed for extreme operating
conditions (insulation and safety clearances, ultimate breaking capacity, high
Compact NSX DC - safety and flexibility. pollution levels, etc.).
3
Presentation Great flexibility in adapting
to DC applications
Overview of series connection of poles
for Compact NSX DC
With Compact NSX DC circuit breakers, it is easy to Compact NSX DC
create a large number of series pole arrangements
using prefabricated connections mounted on site Examples of series connection
during equipment installation. Two-pole devices
DB403286.eps
DB402976.eps
DB403287.eps
DB402977.eps
DB104468.eps
DB402606.eps
DB403289.eps
DB402978.eps
Four-pole devices
DB403290.eps
DB402979.eps
DB403291.eps
DB402980.eps
b All connections are possible for the fixed and Great flexibility for connections
withdrawable versions.
DB104475.eps
DB402981.eps
All connections are possible for the fixed and Indifferent connection of polarities.
withdrawable versions.
DB402982.eps
DB402606.eps
4
Overview of series connection of poles
for Compact INS/INV
With Compact INS/INV switch-disconnectors, it is Series connection of poles for direct current
easy to create a large number of series pole
arrangements using prefabricated connections applications
mounted on site during equipment installation.
Examples of series connection
Three-pole devices
DB104468_1.eps
DB414349.eps
DB414350.eps
One type of connection per frame size, two catalogue
numbers for all series connections.
Four-pole devices
DB414351.eps
DB414352.eps
DB414354.eps
5
Presentation Great flexibility in adapting
to DC applications
Overview of series connection of poles
for Masterpact NW DC
Masterpact NW DC circuit breakers, with high Masterpact NW DC
ratings and installed as incoming devices, offer
three coupling versions C, D and E ready for Three versions supplied ready for connection
connection. Version C
The polarities Line -, Line + indicated on the rear
DB402988.eps
DB402252_55.eps
connections of the Masterpact NW DC
circuit breakers have to be respected in order to
ensure the magnetic threshold tolerances.
DB402264_55.eps
DB402989.eps
dissipate heat.
DB104484.eps
Front view: three-pole case - three poles in Rear view with connections.
series.
Version E
DB402990.eps
DB402276_55.eps
Front view: four-pole case - four poles in Rear view with connections.
series.
6
Parallel connection of poles
DB403292.eps
DB402984.eps
technique virtually doubles, triples or quadruples
the current rating depending on the type of
circuit breaker and thus reduces the cost of
solutions.
DB104485.eps
DB402985.eps
Customer connections are made directly
to the connection plates after removing the heat
sinks.
DB104486.eps
DB402986.eps
DB402987.eps
Note: creation of the additional connection (1) is the responsibility of the panel builder or the
installer.
7
Presentation Great flexibility in adapting
to DC PV applications
Overview of series connectors
for NSX DC PV
Compact NSX TM DC PV Compact NSX NA DC PV
2 Series connections
DB416077.eps
DB416273.eps
with heatsinks
2 Series connections
(dissipators)
with heatsinks
(dissipators)
4 interphase
barriers or
terminal shields
2 terminal shields
F1-
F1+
F1-
F2-
Photovoltaic panels
F1+
F2+
F2-
F3- Photovoltaic panels
F2+
F3+
F3-
F3+
8
Connection accessories
The exceptional performance levels of Compact INS/ Parallel connection of poles for direct current
INV switch-disconnectors mean the poles can be
parallel connected. This technique virtually doubles, applications
triples or quadruples the current rating depending on
the type of circuit breaker and thus reduces the cost of Examples of parallel connection
solutions. Three-pole devices
DB414356.eps
DB104485_1.eps
Note: creation of the additional connection (1) is the responsibility of the panel builder or the
installer.
9
TOOLS
schneider-electric.com
Presentation 2
Trip-unit characteristics
Types of trip units - Trip units for Compact NSX DC A-18
Characteristics and performance of Compact NSX switch-disconnectors
from 100 to 250 NA A-20
Switch-disconnectors characteristics
Compact NSX400/630 NA DC A-22
Switch-disconnectors characteristics
Compact NSX100 NA DC PV to NSX500 NA DC PV A-50
Compact NSX630b NA DC PV to NSX1600 NA DC PV A-52
A-1
Compact NSX DC - DC PV Functions and characteristics
Compact INS/INV DC - DC PV
Masterpact NW DC - DC PV
Communication
EnerlinX communication system A-78
IFE Ethernet interface A-80
IFM Modbus communication interface A-82
COM option in Compact and Masterpact A-83
I/O application module A-84
Communications modules, IFM and IFE for Compact NSX A-86
Communication components and connections A-87
Connection of the IFE to a fixed or drawout Masterpact NW A-88
Connection of the IFM to a fixed or drawout Masterpact NW A-89
Electrical Asset Manager Configuration Engineering tool A-90
A-2
General characteristics ofMasterpact NW DC - DC PV
Operating conditions A-92
Masterpact NW DC and DC PV A-93
Masterpact NW10 to NW40 DC A-94
Trip-unit characteristics
Trip units for Masterpact NW DC A-96
Connection
Overview of solutions A-102
A-3
Functions
and characteristics
Selection guide forDC
circuit breakers
Types of DC distribution systems
There are three types of DC distribution systems (see Selection of a circuit breaker depends essentially on the distribution-system
the table). parameters presented below which are used to determine the corresponding
The operational voltage in conjunction with one of the characteristics:
three systems determines the number of poles taking b type of system - determines the type of product and the number of poles
part in current interruption. connected in series for each polarity
b rated voltage - determines the number of series poles taking part in current
interruption
b nominal current - determines the rated current of the circuit-breaker
b maximum short-circuit current at the point of installation - determines the breaking
capacity.
Types of systems
Earthed systems Isolated systems
The source has one earthed polarity (1) The source has an earthed mid-point
Diagrams and different faults
DB116982.eps
DB116983.eps
DB116984.eps
Fault analysis (neglecting resistance of earth electrodes)
Fault A b maximum Isc at U b maximum Isc at U/2 b no consequences
b only protected polarity concerned b only positive polarity concerned b the fault must be indicated by an IMD
b all poles of protected polarity must have b all poles of positive polarity must have (insulation-monitoring device) and cleared
breaking capacity u Isc max. at U breaking capacity u Isc max. at U/2 (standard IEC/EN60364)
Fault B b maximum Isc at U b maximum Isc at U b maximum Isc at U
b if only one polarity (the positive here) is b both polarities are concerned b both polarities are concerned
protected, all poles of protected polarity must b all poles of the two polarities must have b all poles of the two polarities must have
have breaking capacity u Isc max. at U breaking capacity u Isc max. at U breaking capacity u Isc max. at U
b if both polarities are protected, to enable
disconnection, all poles of the two polarities
must have breaking capacity u Isc max. at U
Fault C No consequences b same as fault A b same as fault A with the same obligations
b all poles of the
negative polarity must have breaking capacity
u Isc max. at U/2
Double fault Double fault not possible, Double fault not possible, b maximum Isc at U
A and D or C and system trips on first fault system trips on first fault b only positive polarity (cases A and D) or
E negative (C and E) concerned
b all poles of each polarity must have breaking
capacity u Isc max. at U
Most unfavourable cases
Fault A and fault B (if only one polarity is Fault B Double fault A and D or C and E
protected)
Conclusion: selection of number of poles and breaking capacity
Layout of protection poles
b on only one polarity (1) b identical for each polarity b identical for each polarity
Number of series poles
Per polarity b all on same polarity b equal b equal
Total b 1, 2 or 3 without disconnection b 2 or 4 (2) b 2 or 4 (2)
b 2, 3 or 4 with disconnection
Breaking capacity
b all poles of the protected polarity u Isc max. b all poles of both polarities u Isc max. at U b all poles of each polarity u Isc max. at U
at U b all poles of each polarity u Isc max. at U/2
Disconnection of both polarities (3)
Possible by adding a pole to the non-protected b ensured b ensured
polarity
Implementation
See the selection table opposite
(1) Positive or negative, depending on the polarity connected to the exposed conductive parts.
(2) A 3P circuit breaker can be used if a 2P version does not exist. In this case, the central pole is not connected.
(3) Disconnection made possible by multi-pole breaking.
A-4
Solutions depending on the distribution
system and the voltage
Series connection of poles
Type of distribution system
Type Earthed Isolated
Source One polarity (negative here) connected to earth Mid-point connected to earth Isolated polarities
(or exposed conductive parts)
Protected polarities 1 (disconnection of 1P) 2 (disconnection of 2P) 2 2
Diagrams
DB116985.eps
DB116986.eps
DB116987.eps
DB116988.eps
(and types of faults)
DB115851.eps
DB115851.eps
DB115850.eps
DB115851.eps
Single-pole. Two-pole (1). Two-pole (1). Two-pole (1).
NSX100-600
DB115852.eps
DB115853.eps
DB115851.eps
DB115854.eps
250 V < Un y 500 V
DB115854.eps
DB115856.eps
DB115857.eps
DB115857.eps
Version C. Version C. Version C.
Type H
24 V y Un y 500 V
DB403137.eps
DB115857.eps
DB115859.eps
DB115859.eps
DB115859.eps
DB115859.eps
DB115859.eps
DB116985.eps
DB116986.eps
DB116987.eps
DB116988.eps
(and types of faults)
DB115861.eps
DB115861.eps
DB115861.eps
DB115860.eps
DB115861.eps
DB418517.eps
DB418517.eps
DB418518.eps
DB418517.eps
(1) Compact NSX DC circuit breakers (and switch disconnectors) are designed to break the rated current or fault current at the rated operational voltage (Ue) with
all poles. To break the current at voltage > 250 V, two poles in series are required. In double earth fault situations (A + D or C + E), the circuit breaker (and switch
disconnectors) must break the current at full voltage with only half of the poles. Compact NSX DC circuit breakers (and switch disconnectors) are not designed for
this purpose and could sustain irremediable damage if used to break the current in a double earth fault situation for voltage > 250 V.
(2) Do not remove parallel connectors.
(3) Compact NSX DC circuit breakers (and switch disconnections) are designed to break the rated current or fault current at the rated operational voltage (Ue) with
all poles. To break the current at voltage > 300 V, two poles in series are required. In double earth fault situations (A + D or C + E), the circuit breaker (and switch
disconnectors) must break the current at full voltage with only half of the poles. Compact NSX DC circuit breakers (and switch disconnectors) are not designed for
this purpose and could sustain irremediable damage if used to break the current in a double earth fault situation for voltage > 300 V.
A-6
Solutions depending on the distribution
system and the voltage
Comparison of series and parallel connection in
terms of performance
Series connection of poles divides the voltage per pole Series connection of poles on a DC circuit breaker is the means to:
and optimises breaking capacity for high-voltage b divide the system voltage by the number of poles
systems. b use the rated current for each pole
b use the breaking capacity of the circuit breaker for all the poles.
For example, a Compact NSX630, 3P DC type, with the three poles connected in
series, provides:
b a maximum voltage of 750 V (250 V per pole)
b a rated current of 630 A
b a breaking capacity of 100 kA / 750 V.
Consequently, a 630 A / 250 V device can be used in a 750 V system.
Parallel connection of poles divides the current per Parallel connection of poles, on the contrary, imposes the system voltage on
pole and optimises the rated current for systems that each pole, but is the means to:
do not exceed the withstand voltage of each pole. b divide the current flowing through each pole by the number of poles
The maximum useable rating and the value of the b increase the rated current.
magnetic setting are indicated (see pages B-7, B-8 For example, the same Compact NSX630 DC 3P circuit breaker with three poles in
and B-9). parallel provides:
b a maximum voltage of 250 V (250 V per pole)
b a rated current of 1500 A (see table page B-9).
Consequently, a 630 A device used in a 250 V system can handle 1500 A.
A-7
Functions Selection guide forDC
and characteristics
circuit breakers
Examples of circuit breaker selection
DB115868.eps
b all poles of the two polarities must have breaking capacity u Isc max. at Un,
i.e. 20 kA/500 V in this case
b all poles of the each polarity must have breaking capacity u Isc max. at Un/2,
i.e. 20 kA/250 V in this case.
Selection possibilities - (see pages A-5 and A-6)
The tables indicate for 250 V < Un y 500 V and for this system:
b poles connected in series: two-pole 2P in series V selection 1
b poles connected in parallel: four-pole 2 x 2P parallel connected in series
V selection 2.
Circuit breaker selection - (see pages A-14 and B-8)
b selection 1: the 250 A rated current does not exist in 2P. It is possible to use a
Selection 1. Selection 2: Compact NSX160 DC 4P 250A 3P DC type circuit breaker with the central pole not connected V selection 3
2 x 2P parallel mounted in series. b selection 2: the 160 A rated current (DC version) is suitable with a 2 x2P
assembly connected in parallel because (see table page B-8):
v the rated current of the 2 x 2P assembly connected in parallel is In = 288 A > 250 A
DB115869.eps
Example 2
b Type of system - one polarity earthed
DB115870.eps
DB115872.eps
A-8
Connection accessories
DB108614.eps
DB108615.eps
DB108616.eps
DB108617.eps
method
DB108589.eps
DB413528.eps
DB108592.eps
Two-pole (1). Three-pole. Two-pole (1). Four-pole.
DB108591.eps
DB108592.eps
Four-pole. Four-pole. Four-pole.
(1) A 3P switch-disconnectors can be used if a 2P version does not exist. In this case, the central pole is not connected.
DB413530.eps
DB413530.eps
DB413530.eps
DB413530.eps
A-9
Functions Selection guide forDC
andcharacteristics
circuit breakers
Examples of circuit breaker selection
Selection of a Masterpact NW DC
Example 1
b Type of system - isolated polarities
DB115870.eps
Example 2
b Type of system - one polarity earthed
DB115870.eps
A-10
Calculation of DC distribution-
system characteristics
Short-circuit currents L/R time constant
Short-circuit currents
Calculation of the short-circuit current across the terminals of
DB403117.eps
a battery
During a short-circuit, the battery discharges a current equal to :
Vb
Isc =
Ri
b Vb = maximum discharge voltage (battery 100 % charged)
b Ri = internal resistance equivalent to all cells (a function of the capacity in
ampere-hours).
Example
b Consider a set of four 500 Ah batteries connected in parallel.
b Discharge voltage of one battery: 240 V (110 cells 2.2 V each).
b Discharge current of one battery: 300 A with a run-time of 30 minutes.
b Discharge current of all four batteries: 1200 A with a run-time of 30 minutes.
b Internal resistance 0.5 mW per cell, i.e. for one battery:
Ri = 110 x 0.5 x 10-3 = 55 x 10-3 W.
b Short-circuit current of one battery: Isc = 240 V / 55 x 10-3 W = 4.37 kA.
b Neglecting the resistance of the connections, for all four batteries discharging the
short-circuit current in parallel, the total short-circuit current is four times that of one
battery, i.e. Isc = 4 x 4.37 kA = 17.5 kA.
Note: if the internal resistance is not known, it is possible to use the following rough
approximation: Isc = kc where c is the capacity of the battery in ampere-hours and k is a
coefficient close to 10 and always less than 20.
from the load current (y In) to the short-circuit current Isc over a period of time that
depends on the value of the resistance R and inductance L of the short-circuited
loop.
The equation determining the current in the loop is:
U = Ri + L Di/Dt
The curve of I versus time is defined (neglecting In) by the equation:
I= Isc (1 - exp(t/t))
where t = L/R is the time constant for the rise to Isc.
DB403119.eps
To express breaking capacity, the interrupted short-circuit current with the following
time constants is used:
b L/R = 5 ms, fast short-circuit
b L/R = 15 ms, standardised value used in standard IEC 60947-2
b L/R = 30 ms, slow short-circuit.
In general, the value of the system time constant is calculated under worst-case
conditions, across the terminals of the generator.
A-11
Functions General characteristics of
andcharacteristics
Compact NSX DC and DC PV
Operating conditions
(m)
Altitude
DB111389.eps
2000
Compact NSX circuit breakers are designed to operate at their rated values at
altitudes under 2000 metres.
Above 2000 metres, the changes in the characteristics of the ambient air (electrical
resistance, cooling capacity) result in a reduction of the characteristics below.
Altitude (m) 2000 3000 4000 5000
Compact NSX DC
Impulse withstand voltage Uimp (kV) 8 7.1 6.4 5.6
Rated insulation voltage (Ui) 750 710 635 560
Maximum rated operationnal DC voltage 1 x Ue 0.88 x Ue 0.8 x Ue 0.7 x Ue
Rated current (A) 1 x In 0.96 x In 0.93 x In 0.9 x In
Compact NSX DC PV
Impulse withstand voltage Uimp (kV) 8 7.1 6.4 5.6
Rated insulation voltage (Ui) 1000 900 800 700
Maximum rated operationnal DC voltage 1000 900 800 700
Rated current (A) 1 x In 0.96 x In 0.93 x In 0.9 x In
Vibrations
Compact NSX circuit breakers are guaranteed against electromagnetic or
mechanical vibrations.
DB111390.eps
Tests are carried out in compliance with standard IEC 68-2-6 for the levels required
by merchant-marine inspection organisations (Veritas, Lloyds, etc.):
b 2 to 13.2 Hz: amplitude 1 mm
b 13.2 to 100 Hz: constant acceleration 0.7 g.
Excessive vibration may cause tripping, breaks in connections or damage to
mechanical parts.
Electromagnetic compatibility
Compact NSX circuit breakers are protected against:
DB111391.eps
Ambient temperature
Operating-temperature range
b Compact NSX circuit breakers and switches may be used between
-25 C and +70 C.
bb For temperatures higher than 40 C (65 C for circuit breakers used to protect
motor feeders), devices must be derated as indicated in the documentation.
b Circuit breakers and switches should be put into service under the normal,
ambient operating temperatures indicated above. Exceptionally, they may be put
into service when the ambient temperature is between -35 C and -25 C.
Derating
Above 40 C, it is necessary to take into account the derating values.
Storage-temperature range
b Compact NSX circuit breakers and switches may be stored in their original
packing between -50C and +85 C.
A-12
Compact NSX DC and DC PV
Degree of protection
Compact NSX DC circuit breakers offer the following protection characteristics
depending on the installation conditions:
b IP: degree of protection (standard IEC 60529)
b IK: protection against external mechanical impacts (standard EN 50102).
Compact NSX DC
Bare circuit breaker with terminal shields
With toggle IP3X IK07
DB402607.eps
standard or VDE
standard or VDE
CCM IP43 IK07
CNOMO IP54 IK07
5...8
DB403582.eps
For Compact NSX DC, installation of a rotary handle or a motor mechanism does
not alter the reliability of the position-indication system.
A-13
Functions Circuit breaker characteristics
andcharacteristics
Compact NSX100 DC to NSX250 DC
Electrical 250 V In
250 V In/2
500 V In
500 V In/2
750 V In
750 V In/2
Indication and control auxiliaries
Auxiliary contacts
Voltage release MX shunt release
MN undervoltage release
Installation and connections
Fixed Front connection
Rear connection
Plug-in (base) Front connection
Rear connection
Withdrawable (chassis) Front connection
Rear connection
Control Manual with toggle
with direct or extended rotary handle
Electrical with remote control
Dimensions and weight
Dimensions Fixed (mm) 1P
H x W x D (mm) connected in series 2P
3P
4P
Weight (kg) Fixed (kg) 1P
connected in series 2P
3P
4P
(1) Number of poles in series taking part in current interruption.
Example. The NSX100N DC circuit breaker exists in the following versions:
- 1 pole with an Icu of 50 kA, for systems y 250 V
- 2 poles with an Icu of 85 kA, for systems y 500 V; 1 pole can be used in a 250 V system.
A-14
NSX100 DC NSX160 DC NSX250 DC
1 2 3/4 1 2 3/4 3/4
b b b b b b - b b b b b b - -
- - - - - - b - - - - - - b b
b b b b b b b b b b b b b b b
b b b b b b b b b b b b b b b
10000
5000
10000
5000
10000
5000
10000
- b b - b b b
- b b - b b b
- b b - b b b
b
b
- - - - - - b - - - - - - b b
- - - - - - b - - - - - - b b
- - - - - - b - - - - - - b b
- - - - - - b - - - - - - b b
b
b
b
161 x 35 x 86 - - 161 x 35 x 86 - -
- 161 x 70 x 86 - - 161 x 70 x 86 -
- - 161 x 105 x 86 - - 161 x 105 x 86
- - 161 x 140 x 86 - - 161 x 140 x 86
0.7 - - 0.7 - -
- 1.2 - - 1.2 -
- - 1.6 to 1.9 - - 1.6 to 1.9
- - 2.1 to 2.3 - - 2.1 to 2.3
A-15
Functions Circuit breaker characteristics
andcharacteristics
Compact NSX400 DC to NSX1200 DC
A-16
NSX400 DC NSX630 DC NSX1200 DC
3/4 3/4 3/4 2
-
b
b
b
b
b b b b b b
b b - - - -
b b - - - -
b b - - - -
b b - - - -
b b - - - -
b b b b b b
b b b b b b
b b b b b b
-
- 350 x 185 x 110
255 x 140 x 110
255 x 185 x 110 -
-
- 9.4
8 -
8.4 -
A-17
Functions Trip-unit characteristics
andcharacteristics Types of trip units
Trip units for Compact NSX DC
breaker 160N/H DC True DC value 260 260 400 400 700 700 700 800 1000 1200 1250
Trip units for Compact NSX100 DC - NSX160 DC - NSX250 DC
Three-pole 3P-3d and four-pole 4P-4d (interchangeable trip units)
Type of trip unit TM-D TM-DC
Rating (A) In (A) at 40 C 16 25 32 40 50 63 80 100 125 160 200 250
Compact NSX100 DC b b b b b b b b - - - -
circuit NSX160 DC - - - - - - - - b b - -
breaker b b
NSX250 DC - - - - - - - - - -
Overload protection (thermal)
Tripping Ir (at 40 C) Adjustable
threshold (A) 0.7 to 1 x In
PB107547_32.eps
A-18
Types of trip units
DB418166.eps
DC DC
6000 3000
TM 1200 DC
5400 3600
840 1200A/40C
1200 960 4800 4200
1080 c
1 overload protection threshold. Up to 1200 A for Compact NSX DC, protection is provided by thermal-magnetic trip
2 short-circuit protection pick-up.
units.
b TM-D up to 160 A: fixed thermal threshold and magnetic pick-up.
b TM-D up to 63 A: adjustable thermal threshold and fixed magnetic pick-up.
b TM-DC from 80 to 250 A: fixed or adjustable (for 200 and 250 A) magnetic pick-up
and adjustable thermal threshold.
b TM-DC from 250 A to 1200 A adjustable magnetic pick-up and adjustable thermal
threshold.
b TM-G, up to 250 A: adjustable thermal threshold and fixed low magnetic pick-up to
protect long cables.
A-19
Functions Switch-disconnectors
and characteristics Characteristics and performance of
Compact NSX switch-disconnectors
from 100 to 250 NA
Installation standards require upstream protection.
However Compact NSX100 to 630 NA switch-
Common characteristics
disconnectors are self-protected by their high-set Rated voltages
magnetic release. Insulation voltage (V) Ui 750
Impulse withstand voltage (kV) Uimp 8
Operational voltage (V) Ue 750
Suitability for isolation IEC/EN 60947-3 yes
Utilisation category DC 22 A/DC 23 A
Pollution degree IEC 60664-1 3
Switch-disconnectors
Electrical characteristics as per IEC 60947-3 and EN 60947-3
PB113369_L37.eps
(1) 2P in 3P case.
(2) Suitable for 480 V NEMA.
Note: For more information, please see catalogue Compact NSX LVPED208001EN.
A-20
Common characteristics
Control
Manual With toggle b
With direct or extended rotary handle b
Electrical With remote control b
Versions
Fixed b
Withdrawable Plug-in base b
Chassis b
b
b
b
b
b
b
b
b
b
b
b
b
105 x 161 x 86
140 x 161 x 86
1.5 to 1.8
2.0 to 2.2
b
b
A-21
Functions Switch-disconnectors
andcharacteristics
characteristics
Compact NSX400/630 NA DC
Number of poles
Electrical characteristics as per IEC 60947-3
Rated current (A) In 40 C
(free air + no venting)
Altitude m 2000
Rated insulation voltage (V) Ui
Rated impulse withstand Uimp
voltage (kV)
Rated operational voltage (V) Ue DC
Type of circuit breaker
Rated short circuit withstand Icw/Icm t=1s
current (kA rms)
Compact NSX630 NA DC. Rated conditionnal short-circuit Iq kA
current with back-up fuse A gG
Rated conditionnal short-circuit Iq with NSX DC circuit breaker kA with MCCB
PB114537-L31_r.eps
current
Utilization category
Suitability for isolation
Pollution degree
Durability
Endurance (C-O cycles) mechanical
electrical (In) 750 V
Installation and connections
Control manual toggle
direct or extended rotary handle
motor mechanism
Compact NSX630 NA DC. Connections fixed front connection
long rear connection
plug-in (on base) front connection
rear connection
withdrawable (on chassis) front connection
rear connection
Additional measurement, indication and control auxiliaries
Indication contacts OF auxiliary contact
SD, SDE trip, fault-trip
Voltage releases MX, MN shunt trip/undervoltage release
Installation
Accessories crimp lugs / bare cable connector
terminal extensions and spreaders
escutcheons
terminal shields and interphase barriers
Din rail adapter
Dimensions and weight
Dimensions (mm) H x W x D (w/o series connection) 3P
4P
Weight (kg) (w/o series connection) 3P
4P
A-22
NSX400 NA DC NSX630 NA DC
3/4 3/4
400 630
b b
750 750
8 8
750 750
7.5 7.5
10 10
400 630
100 100
DC22-A DC22-A
b b
3 3
5000 5000
1000 1000
b b
b b
b b
b b
b b
b b
b b
b b
b b
b b
b b
b b
b b
b b
b b
b b
- -
A-23
Functions Accessories and auxiliaries
and characteristics Overview of Compact NSX100 to 630 DC (*)
fixed version
Insulation accessories
DB418158.eps
Interphase barriers
Sealable terminal
shields
Indication contact
A-24
Connection A-32
One-piece spreader
Cable connectors
Rear connectors
Cable connectors
Communication (1)
(1) (1)
Terminal
extensions
BSCM module
NSX cord
(1)
Modbus interface
Motor mechanism
A-25
Functions Accessories and auxiliaries
and characteristics Overview of Compact NSX1200 DC
fixed version
Insulation accessories
DB417702.eps
Sealable terminal
shields
Indication contact
Voltage release Im
6000 3000
4000
TM 25
0D
/ 40C I I
Ir 250A r m
5000
840
1200
960 A
1080
Sealable terminal
shields
A-26
Cable connectors
(1) (1)
BSCM module
NSX cord
(1)
Modbus interface
Motor mechanism
A-27
Functions Accessories and auxiliaries
and characteristics Overview of Compact NSX100 to 630 DC (*)
plug-in and withdrawable versions
Insulation accessories
DB418159.eps
Interphase barriers
Heat sink
A-28
Connection A-32
Lugs
Rear connectors
Adapter
Cable connectors
Circuit breaker
Terminal extensions
Plug-in base
Power connection
accessories
Power connections
A-29
Functions Electrical and mechanical
andcharacteristics
accessories
Compact NSX100 to 1200 DC
Compact NSX DC circuit breakers may be installed Fixed circuit breakers NSX100 to NSX1200
horizontally, vertically or flat on their back, without Fixed circuit breakers are designed for standard connection using bars or cables
derating performance levels. with lugs. Bare-cable connectors are available for connection to bare copper or
There are three installation versions: aluminium cables.
b fixed For connection of large cables, a number of solutions with spreaders may be used
b plug-in (on a base) for both cables with lugs or bare cables.
b withdrawable (on a chassis).
For the last two, components must be added (base,
DB112200.eps
DB112201.eps
DB112202.eps
chassis) to the fixed version.
Many connection components are shared by the three
versions.
DB112203.eps
DB112204.eps
L3
L2
L1
8 Nm
L2
8 Nm
L3
8 Nm
DB112208.eps
L3
L2
L1
DB112205.eps
DB112207.eps
A-30
bb Disconnected position - the power circuits are Withdrawable circuit breakers NSX100 to NSX630 (*)
disconnected, but the circuit breaker is still on the In addition to the advantages provided by the base, installation on a chassis
chassis and may still be operated (ON, OFF, facilitates handling. It offers three positions, with transfer from one to the other after
push-to-trip). mechanical unlocking:
bb The circuit breaker may be locked using bb connected: the power circuits are connected
1 to 3 padlocks (shackle diameter 5 to 8 mm), to bb disconnected: the power circuits are disconnected, the device can be operated to
prevent connection. check auxiliary operation
bb The auxiliaries can be tested (with manual auxiliary bb removed: the device is free and can be removed from the chassis.
connector).
Parts of a withdrawable configuration
A withdrawable configuration requires two side plates installed on the base and two
PB104935.eps
sides plates mounted on the circuit breaker. Similar to the plug-in version, a safety
trip causes automatic tripping if the device is ON, before engaging or withdrawing it,
and enables device operation in the disconnected position.
Accessories
Accessories are the same as for the base, with in addition:
bb auxiliary contacts for installation on the fixed part, indicating the connected and
disconnected positions
bb locking by 1 to 3 padlocks (shackle diameter 5 to 8 mm), to:
vv prevent insertion for connection
vv lock the circuit breaker in connected or disconnected position
bb toggle collar for circuit breakers with a toggle mounted through a front panel,
intended to maintain the degree of protection whatever the position of the circuit
breaker (supplied with a toggle extension)
bb telescopic shaft for extended rotary handles. The door can then be closed with the
Withdrawable Compact NSX250 DC. device in the connected and disconnected positions.
DB112209.eps
DB111369.eps
DB112219.eps
Installation positions.
Protection collar for toggle and toggle Telescopic shaft.
extension to provide IP4 in the connected and
DB112210.eps
disconnected positions.
DB112221.eps
DB112312.eps
(*) Applicable for circuit breaker up to 600 A see page A-14 to A-17.
A-31
Functions Electrical and mechanical
and characteristics
accessories
Connection of fixed devices
Fixed circuit breakers are designed for standard front Front connection
connection using bars or cables with lugs.
Cable connectors are available for bare cables. Rear Bars or cables with lugs
connection is also possible. Standard terminals
Compact NSX100 to 630 DC come with terminals comprising snap-in nuts with
screws:
DB112169.eps
DB417865.eps
certain connection accessories (in which case the interphase barriers are provided).
Bars
When the switchboard configuration has not been tested, insulated bars are
mandatory.
Maximum size of bars
Compact NSX DC circuit breaker 100 to 250 400 to 630 1200
Small lug for copper cables.
DB417866.eps
DB112173.eps
DB112174.eps
DB112176.eps
DB112177.eps
DB112180.eps
A-32
Bare cables
DB112313.eps
DB112314.eps
For bare cables (without lugs), the prefabricated bare-cable connectors may be used
for both copper and aluminium cables.
1-cable connector for Compact NSX100 to 250 DC
The connectors snap directly on to the device terminals or are secured by clips to
right-angle and straight terminal extensions as well as spreaders.
Bare cable.
1-cable connector for Compact NSX400 to 630 DC
The connectors are screwed directly to the device terminals.
2-cable connector for Compact NSX100 to 250 and 400/630/1200 DC
The connectors are screwed to device terminals or right-angle terminal extensions.
Distribution connectors for Compact NSX100 to 250 DC
These connectors are screwed directly to device terminals. Interphase barriers are
supplied with distribution connectors, but may be replaced by long terminal shields.
Each connector can receive six cables with cross-sectional areas ranging from 1.5 to
35 mm each.
DB112316.eps
DB112317.eps
DB111326.eps
DB111330.eps
For the connection of bare cables, the 1-cable connectors for Compact NSX100
to 250 DC may be secured to the rear connections using clips.
DB104730.eps
A-33
Functions Electrical and mechanical
and characteristics
accessories
Connection of electrical auxiliaries
Auxiliary circuits exit the device through a knock-out in the front cover.
Plug-in/withdrawable
Compact NSX DC.
DB403557.eps
DB403556.eps
Connector 1
Connector 1
Connector 2
Connector 2
Connector 3
DB111376.EPS
Compact
NSX100/160/250 DC.
A-34
Withdrawable Compact NSX DC
DB111379.EPS
DB403583.eps
Connector 2
Connector 1
Connector 2
Connector 3
A-35
Functions Electrical and mechanical
and characteristics
accessories
Selection of auxiliaries
for Compact NSX100/160/250 DC
Remote tripping
044313_30_SE.eps
MN undervoltage release
This release trips the circuit breaker when the control voltage drops below a tripping
threshold:
b tripping threshold between 0.35 and 0.7 times the rated voltage
b circuit breaker closing is possible if the voltage exceeds 0.85 times the rated
voltage. For a lower value, circuit breaker closing cannot be guaranteed.
Circuit breaker tripping by an MN release meets the requirements of standard
IEC 60947-2.
MX shunt release
Trips the circuit breaker when the control voltage rises above 0.7 x Un.
Control signals can be of the impulse type (u 20 ms) or maintained.
Operation
When the circuit breaker has been tripped by an MN or MX release, it must be reset
locally.
MN or MX tripping takes priority over manual closing.
In the presence of a standing trip order, closing of the contacts, even temporary,
is not possible.
Mechanical characteristics
b Endurance is equal to 50 % of the mechanical endurance of the circuit breaker.
b The releases clip in behind the front cover.
b Connection using wires up to 1.5 mm2, to integrated terminal blocks.
Electrical characteristics
b Consumption:
v pick-up (MX): < 30 VA
v seal-in (MN and MNR): < 5 VA.
b Response time: < 50 ms.
DB403012.eps
Motor mechanism /
rotary handle / toggle handle
SD SDE
OF1 OF2 OF2
SD SDE OF1
MN /
MX MN /
MX
A-36
Communication
Communication requires specific auxiliaries (see page A-42).
Communication of status indications (1)
bb 1 BSCM module.
bb 1 NSX cord (internal terminal block) for both communication and 24 V DC supply
to the BSCM.
Communication of status conditions is compatible with a toggle handle and a rotary
handle.
Communication of status indications and controls
This requires, in addition to the previous auxiliaries:
bb 1 IFM connected to the BSCM.
TMD, TMG
Communication of status indications (1)
Rotary handle / Communicating
DB403584.eps
DB403585.eps
toggle handle motor mechanism
BSCM BSCM
NSX cord
or
NSX cord
A-37
Functions Electrical and mechanical
and characteristics
accessories
Selection of auxiliaries
for Compact NSX400/630/1200 DC
Standard
All Compact NSX400/630/1200 DC circuit breakers and switch-disconnectors have
slots for the electrical auxiliaries listed below.
5 indication contacts (see page A-39)
bb 3 ON/OFF (OF1, OF2, OF3)
bb 1 trip indication (SD)
bb 1 fault-trip indication (SDE).
NA, NSX400/1200 DC
Standard
Motor mechanism /
DB403013.eps
DB403586.eps
OF1,
OF2, SD
OF1 SD OF3
SDE
OF2
OF3 SDE
MN / MN /
MX MX
A-38
Functions
and characteristics
Indication contacts for Compact NSX DC
One contact model provides circuit breaker status These common-point changeover contacts provide remote circuit breaker status
indications (OF - SD - SDE). information.
An early-make or early-break contact, in conjunction They can be used for indications, electrical locking, relaying, etc.
with a rotary handle, can be used to anticipate device They comply with the IEC 60947-5 international recommendation.
opening or closing.
A CE / CD contact indicates that the chassis is Functions
connected / disconnected. Breaker-status indications, during normal operation or after a fault
A single type of contact provides all the different indication functions:
bb OF (ON/OFF) indicates the position of the circuit breaker contacts
bb SD (trip indication) indicates that the circuit breaker has tripped due to:
vv an overload
vv a short-circuit
DB125549.eps
rotary handle.
They are used in particular for advanced opening of safety trip devices (early break)
or to energise a control device prior to circuit breaker closing (early make).
Chassis-position contacts
bb CE/CD (connected/disconnected) contacts are microswitch-type carriage
switches for withdrawable circuit breakers.
CE/CD carriage switches.
Installation
bb OF, SD, SDE functions: a single type of contact provides all these different
indication functions, depending on where it is inserted in the device. The contacts
clip into slots behind the front cover of the circuit breaker.
The SDE function on a Compact NSX100 - 250 DC equipped with a thermal-
magnetic trip unit requires the SDE actuator.
bb CAM function: the contact fits into the rotary-handle unit (direct or extended).
bb CE/CD function: the contacts clip into the fixed part of the chassis.
A-39
Functions Electrical and mechanical
and characteristics
accessories
Rotary handles
For Compact NSX DC
There are two types of rotary handle: Direct rotary handle
b direct rotary handle
b extended rotary handle. Standard handle
There are two models: Degree of protection IP40, IK07.
b standard with a black handle The direct rotary handle maintains:
b red handle and yellow front for machine-tool control. bb visibility of and access to trip-unit settings
bb suitability for isolation
bb indication of the three positions O (OFF), I (ON) and tripped
bb access to the "push to trip" button.
Device locking
PB104936.eps
A-40
Rotary handles
For Compact NSX DC
reversible.
When a number of extended rotary handles are installed on a door, this disabling
function is the means to ensure door locking by a single device.
Device and door padlocking
Padlocking locks the circuit breaker handle and disables door opening:
bb standard situation, in the OFF position, using 1 to 3 padlocks, shackle diameter 5
to 8 mm, not supplied
bb with a simple modification, in the ON and OFF positions. Locking in the ON
position does not prevent free circuit breaker tripping if a fault occurs.
In this case, the handle remains in the ON position after the circuit breaker tripping.
Unlocking is required to go to the tripped then the OFF position.
If the door controls were modified to voluntarily disable door locking, padlocking
does not lock the door, but does disable handle operation of the device.
Device locking using a keylock inside the switchboard
It is possible to install a Ronis or Profalux keylock (optional) on the base of the rotary
handle to lock the device in the OFF position or in either the ON or OFF positions.
Accessory for device operation with the door open
When the device is equipped with an extended rotary handle, a control accessory
mounted on the shaft makes it possible to operate the device with the door open.
bb The device can be padlocked in the OFF position.
bb The accessory complies with UL508.
Early-make or early-break contacts (optional)
The extended rotary handle offers the same possibilities with early-make and/or
early-break contacts as the standard rotary handle.
Parts of the extended rotary handles
bb A unit that replaces the front cover of the circuit breaker (secured by screws).
bb An assembly (handle and front plate) on the door that is always secured in the
same position, whether the circuit breaker is installed vertically or horizontally.
bb An extension shaft that must be adjusted to the distance. The min/max distance
between the back of circuit breaker and door is:
vv 185600 mm for Compact NSX100 to 250 DC
vv 209600 mm for Compact NSX400/630/1200 DC.
For withdrawable devices, the extended rotary handle is also available with a
telescopic shaft to compensate for device disconnection. In this case, the min/max
distances are:
vv 248600 mm for Compact NSX100 to 250 DC
vv 272...600 mm for Compact NSX400/630/1200 DC.
A-41
Functions Electrical and mechanical
and characteristics
accessories
Motor mechanism
For Compact NSX DC
When equipped with a motor mechanism module, Compact NSX DC circuit
PB113341.eps
breakers feature very high mechanical endurance as well as easy and sure
operation:
bb all circuit breaker indications and information remain visible and accessible,
including trip-unit settings and indications
bb suitability for isolation is maintained and padlocking remains possible
bb double insulation of the front face.
A specific motor mechanism is required for operation via the communication
function (1). This communicating motor mechanism must be connected to the
BSCM module to receive the opening and closing orders. Operation is identical to
that of a standard motor mechanism.
Compact NSX250 DC with motor mechanism.
Applications
bb Local motor-driven operation, centralised operation, automatic distribution control.
bb Normal/standby source changeover or switching to a replacement source to
ensure availability or optimise energy costs.
bb Load shedding and reconnection.
bb Synchrocoupling.
Operation
The type of operation is selected using the manual/auto mode selection switch (7).
A transparent, lead-seal cover controls access to the switch.
Automatic
When the switch is in the "auto" position, the ON/OFF (I/O) buttons and the charging
lever on the mechanism are locked.
bb Circuit breaker ON and OFF controlled by two impulse-type or maintained signals.
1 2 3
DB416307.eps
8 7 6 5 Optional accessories
bb Keylock for locking in OFF position.
1 Position indicator bb Operations counter for the Compact NSX400/630 DC, indicating the number
(positive contact indication) of ON/OFF cycles. Must be installed on the front of the motor mechanism module.
2 Spring status indicator (charged, discharged)
3 Manual spring-charging lever Characteristics
4 Keylock device (optional)
Locking device (OFF position), using 1 to 3 padlocks, Motor mechanism MT100 to MT630
shackle diameter 5 to 8 mm, not supplied Response time (ms) opening < 600
5 I (ON) pushbutton closing < 80
6 O (OFF) pushbutton Operating frequency cycles/minute max. 4
7 Manual/auto mode selection switch. The position of this Control voltage (V) DC 24/30 - 48/60 - 110/130 - 250
switch can be indicated remotely. AC 50/60 Hz 48 (50 Hz) - 110/130 -
8 Operation counter (Compact NSX400/630 DC). 220/240 - 380/440
Consumption (1) DC (W) opening y 500
closing y 500
AC (VA) opening y 500
closing y 500
(1) For NSX100 to 250 DC, the inrush current is 2 In for 10 ms.
Electrical endurance
Circuit breaker + motor
DB417749.eps
10 mechanism module, in
thousands of operations
(IEC 60947 2), at 440 V.
5 NSX100/160/250 DC
1 NSX400/630/1200 DC
(1) NSX100-250 DC only. 0.1 0.2 0.3 0.5 0.7 1 I/In
A-42
Remote tripping
For Compact NSX DC
MX or MN voltage releases are used to trip the circuit breaker. They serve primarily
044313_20_SE.eps
MN undervoltage release
The MN release opens the circuit breaker when its supply voltage drops to a value
below 35 % of its rated voltage Un.
Undervoltage tripping, combined with an emergency-off button, provides fail-safe
MX or MN voltage release. tripping. The MN release is continuously supplied, i.e. if supply is interrupted:
bb either voluntarily, by the emergency-off button,
Failsafe opening Possible opening bb or accidentally, through loss of power or faulty wiring,
DB115605.eps
Delayed A time delay unit for the MN release eliminates the risk of nuisance tripping due to a
trip order transient voltage dip lasting y 200 ms. For shorter micro-outages, a system of
capacitors provides temporary supply to the MN at U > 0.7 to ensure non tripping.
DB115631.eps
D1 MX shunt release
The MX release opens the circuit breaker via an impulse-type (u 20 ms) or
MN release with a time-delay Wiring diagram for maintained order.
unit. emergency-off function with Opening conditions
MN + time-delay unit. When the MX release is supplied, it automatically opens the circuit breaker. Opening
is ensured for a voltage U u 0.7 x Un.
Possible opening Failsafe opening Characteristics
DB115608.eps
A-43
Functions Electrical and mechanical
and characteristics
accessories
Locks
For Compact NSX DC
Locking in the OFF position guarantees isolation as per IEC 60947-2. Padlocking
DB111364.eps
DB111365.eps
systems can receive up to three padlocks with shackle diameters ranging from 5 to
8 mm (padlocks not supplied). Certain locking systems require an additional
accessory.
DB111359.eps
DB111360.eps
5...8
u auto u auto
man man
DB111361.eps
A-44
Sealing accessories
For Compact NSX DC
Outgoing-circuit identification
DB115224.eps
Compact NSX100 to 630 DC can be equipped with label holders supplied in sets of
ten (cat. no. LV429226).
They are compatible with escutcheons.
A bag contains:
bb 6 sealing accessories
bb 6 lead seals
bb 0.5 m of wire
bb 2 screws.
Sealing accessories.
DB112301.eps
DB112303.eps
Rotary handle
DB112302.eps
DB112306.eps
DB403120.eps
Motor mechanism
DB112304.eps
DB112305.eps
DB112307.eps
DB125896.eps
5...8
5...8
u auto
man
u auto
man
auto
5...8
uto
Types of seals Front-cover fixing screw Trip-unit transparent Motor mechanism Terminal-shield fixing
cover transparent cover screw
Protected operations bb front removal bb access to manual/auto bb access to power
bb access to auxiliaries bb modification of settings mode selection switch: connections (protection
bb trip-unit removal. bb access to test connector. depending on its position, against direct contact).
manual (1) or automatic
operation is not possible.
(1) In this case, local
operation is not possible.
A-45
Functions Electrical and mechanical
and characteristics
accessories
Escutcheons and protection collars
For Compact NSX DC
Escutcheons are an optional feature mounted on the IP30 or IP40 escutcheons for fixed devices
switchboard door. They increase the degree of
protection to IP40, IK07. Protection collars maintain the IP30
degree of protection, whatever the position of the The three types are glued to the cut-out in the front door of the switchboard:
device (connected, disconnected). bb escutcheon for all control types (toggle, rotary handle or motor mechanism):
vv without access to the trip unit
vv with access to the trip unit.
IP40
PB104942.eps
The four types, with a gasket, are screwed to the door cut-out:
bb three escutcheons identical to the previous, but IP40
bb a wide model for Vigi and ammeter modules that can be combined with the above.
DB112290.eps
IP30 escutcheon.
DB402617.eps
PB104938.eps
Escutcheon for toggle without and with access to the trip unit.
A-46
Escutcheons and protection collars
For Compact NSX DC
DB112294.eps
DB112295.eps
DB112296.eps
5...8
5
5...8
...8
Toggle cover.
PB103820_35.eps
Toggle cover.
A-47
Functions Circuit breaker characteristics
andcharacteristics Compact NSX80 TM DC PV
to NSX500 TM DC PV
Number of poles
Electrical characteristics as per IEC 60947-2 and EN 60947-2
Rated current (A) In 40 C heatsink standard-IP4X
(free air + no venting)
Altitude m 2000
Rated insulation voltage (V) Ui
Rated impulse withstand Uimp
voltage (kV)
Rated operational voltage (V) Ue DC
Type of circuit breaker
Ultimate breaking capacity Icu (kA rms) DC 1000 V (4P series)
Compact NSX200 TM DC PV. (L/R 2 ms)
Service breaking capacity Ics % Icu
Suitability for isolation
PB110846.eps
A-48
NSX80 TM NSX125 TM NSX160 TM NSX200 TM NSX250 TM NSX320 TM NSX400 TM NSX500 TM
DC PV DC PV DC PV DC PV DC PV DC PV DC PV DC PV
4 4 4 4 4 4 4 4
b b b b b b b b
1000 1000 1000 1000 1000 1000 1000 1000
8 8 8 8 8 8 8 8
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
- - - - - - - -
- - - - - - - -
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b - - - -
140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 225 x 185 x 110 225 x 185 x 110 225 x 185 x 110 225 x 185 x 110
2.8 2.8 2.8 2.8 8.1 8.1 8.1 8.1
A-49
Functions Switch-disconnectors
andcharacteristics
characteristics
Compact NSX100 NA DC PV
to NSX500 NA DC PV
Compact NSX DC PV switch-disconnector
PB110838.eps
Number of poles
Electrical characteristics as per IEC 60947-3
Rated current (A) In 40 C
(free air + no venting)
Altitude m 2000
Rated insulation voltage (V) Ui
Rated impulse withstand Uimp
voltage (kV)
Rated operational voltage (V) Ue DC
Type of circuit breaker
Rated short circuit withstand Icw/Icm t=1s
current (kA rms),
Rated conditionnal short-circuit Iq kA
current with back-up fuse A gPV
Compact NSX200 NA DC PV. Rated conditionnal short-circuit Iq with circuit breaker kA with MCCB
current
Utilization category
PB110847.eps
A-50
NSX100 NA DC PV NSX160 NA DC PV NSX200 NA DC PV NSX400 NA DC PV NSX500 NA DC PV
4 4 4 4 4
10 10 10 10 10
100 160 200 400 500
10 10 10 - -
NSX125 TM DC PV NSX160-200 TM DC PV NSX200 TM DC PV
DC22-A DC22-A DC22-A DC22-A DC22-A
b b b b b
3 3 3 3 3
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
- - - - -
- - - - -
- - - - -
- - - - -
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b - -
140 x 161 x 86 140 x 161 x 86 140 x 161 x 86 185 x 255 x 110 185 x 255 x 110
2.8 2.8 2.8 8.1 8.1
A-51
Functions Switch-disconnectors
andcharacteristics
characteristics
Compact NSX630b NA DC PV
to NSX1600 NA DC PV
Compact NSX DC PV switch-disconnector
PB112180_53.eps
Number of poles
Electrical characteristics as per IEC 60947-3
Rated current (A) In 40 C
(free air + no venting)
Altitude m 2000
Rated insulation voltage (V) Ui
Rated impulse withstand Uimp
voltage (kV)
Rated operational voltage (V) Ue DC
Type of circuit breaker
Compact NSX1600 NA DC PV. Rated short circuit withstand Icw/Icm t=1s
current (kA rms)
Rated conditionnal short-circuit Iq kA
current with back-up fuse A gPV
Rated conditionnal short-circuit Iq with circuit breaker
current
Utilization category
Suitability for isolation
Pollution degree
Durability
Endurance (C-O cycles) mechanical
electrical (In) 1000 V
rear connection
A-52
NSX630b NA DC PV NSX800b NA DC PV NSX1000 NA DC PV NSX1250 NA DC PV NSX1600 NA DC PV
4 4 4 4 4
20 20 20 20 20
10 10 10 10 10
N/A N/A N/A N/A N/A
10 10 10 10 10
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
b b b b b
280 x 327 x 182 280 x 327 x 182 280 x 327x 182 280 x 327 x 182 280 x 327 x 182
18 18 18 18 18
A-53
Functions
and characteristics
Accessories and auxiliaries
Overview of Compact NSX80 TM
to NSX500 TM DC PV circuit breakers
DB417656.eps
Terminal shields
Communication (1)
(2)
(2)
Modbus interface
Cable connectors
Terminal
Terminal shields Rear connectors
extensions
A-54
Overview of Compact NSX100 NA
to NSX500 NA DC PV switch-disconnectors
DB418160.eps
Terminal shields
(1)
Heatsink
I I
n m
Modbus interface
A-55
Functions Accessories and auxiliaries
and characteristics Overview of Compact NSX630b NA
to NSX1600 NA DC PV
switch-disconnectors
DB418161.eps
Phase
barriers
Sealable terminal
shield
Heatsink
Auxiliary contact
Escutcheon
I ON
OOFF
pus h
pus h
Voltage release
ed
harg
disc
O OFF
53
012
Phase barriers
Phase
barriers
Sealable terminal
shield
A-56
Functions Compact INS DC PV
and characteristics
No matter the size or scale of the project, Schneider Electric, has a photovoltaic
DB417877.eps
solution to fit your needs. Fast ROI, high efficiency its all a part of our offer as the
INS PV-1 world leader in energy management.
600V
Ith 40A 60 The INS PV-1 is a direct current switch disconnector dedicated to array isolation and
600V DC Max 4PS control with Voc until 600 V DC.
Ue (V) Ie
DC21B 600 10A
DC21B 500 25A
DC21B 400 32A
PB111408_42.eps
Compact INS80 PV
Number of poles 4 serial pole
Electrical characteristics
Conventional thermal current (A) lth
Conventional thermal current in enclosure (A) lthe
Rated insulation level (DC V) Ui
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (DC V) Ue
Rated operational voltage DC21B (V)
Rated operational current (A) le Electrical DC
DC21B 600
DC21B 500
DC21B 400
DC21B 300
Rated duties Uninterrupted duty -
Intermittent duty Class 120 - 60 %
Short-circuit making capacity (kA peak) lcm
Short-time withstand current (A rms) lcw
Suitability for isolation Yes
Durability (O-C cycles) Mechanical 20000
Electrical DC
600 V 1500
Positive contact indication Yes
Visible break -
Emergency-off switch disconnector Yes
Degree of pollution 3
A-57
Functions and characteristics Switch-disconnector selection
Compact INS40 to 160 DC
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 C
Conventional thermal current in enclosure Ithe at 60 C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
Compact INS40 to 80 switch-disconnector.
DC
Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
PB111403_30.eps
A-58
INS40 INS63 INS80 INS100 INS125 INS160
3-4 3-4 3-4 3-4 3-4 3-4
- - - - - -
A-59
Functions and characteristics Switch-disconnector selection
Compact INS40 to 160 DC
A-60
INS40 INS63 INS80 INS100 INS125 INS160
b b b b b b
- - - b b b
b b b - - -
b b b b b b
b b b b b b
- - - b b b
- - - - - -
- - - - - -
bb bb bb b b b
- - - - - -
- - - - - -
b b b b b b
- - - - - -
- - - - - -
- - - - - -
b b b b b b
b b b b b b
b b b b b b
b b b b b b
- - - - - -
b b b b b b
- - - - - -
b b b b b b
- - - - - -
0.7 < Nm < 1.3 0.7 < Nm < 1.3 0.7 < Nm < 1.3 1.4 < Nm < 2 1.4 < Nm < 2 1.4 < Nm < 2
b b b b b b
- - - - - -
- - - - - -
- - - - - -
- - - - - -
b b b b b b
b b b b b b
b b b b b b
- - - - - -
- - - - - -
5 5 5 8 8 8
85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5
85 x 90 x 62.5 85 x 90 x 62.5 85 x 90 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5 100 x 135 x 62.5
0.5 0.5 0.5 0.8 0.8 0.8
0.6 0.6 0.6 0.9 0.9 0.9
190 x 115 x 55 190 x 115 x 55 190 x 115 x 55 260 x 160 x 55 260 x 160 x 55 260 x 160 x 55
A-61
Functions and characteristics Switch-disconnector selection
Compact INS250-100 to 630 DC
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 C
Conventional thermal current in enclosure Ithe at 60 C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Compact INS250 switch-disconnector.
Rated operational current (A) Ie Electrical DC
125 V (2P in series)
250 V (4P in series)
PB111441_47.eps
A-62
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630
3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
- - - - - - - -
A-63
Functions and characteristics Switch-disconnector selection
Compact INS250-100 to 630 DC
A-64
INS250-100 INS250-160 INS250-200 INS250 INS320 INS400 INS500 INS630
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
- - - - b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b - - - -
b b b b - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 13.5 < Nm < 16.5 13.5 < Nm < 16.5 13.5 < Nm < 16.5 13.5 < Nm < 16.5
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b - - - -
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
15 15 15 15 50 50 50 50
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
2 2 2 2 4.6 4.6 4.6 4.6
2.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9
400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200
A-65
Functions and characteristics Switch-disconnector selection
Compact INS630b to 2500 DC
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3 and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 C
Conventional thermal current in enclosure Ithe at 60 C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical DC
125 V (2P in series)
250 V (4P in series)
Compact INS1600 switch-disconnector.
Rated duties Uninterrupted duty
Intermittent duty
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)
Short-time withstand current (kA rms) Icw 0.5 s
0.8 s
PB111511_45.eps
1s
3s
20 s
30 s
Suitability for isolation
Durability (O-C cycles) Mechanical
Electrical DC
125 V (2P)
250 V (4P)
Positive contact indication
Visible break
Emergency-off switch disconnector
Degree of pollution
Compact INS1600 emergency-off switch-disconnector.
Upstream protection
See the Complementary technical information catalogue Compact INS/INV
LVPED213024EN.
(1) Suitable for 480 V NEMA.
PB111518_72.eps
(2) For vertical connection busbars only. For horizontal connection busbars, see derating charts
in Installation recommendations in catalogue Compact INS/INV LVPED213024EN.
A-66
INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500
3-4 3-4 3-4 3-4 3-4 3-4 3-4
- - - - - - -
A-67
Functions and characteristics Switch-disconnector selection
Compact INS630b to 2500 DC
A-68
INS630b INS800 INS1000 INS1250 INS1600 INS2000 INS2500
b b b b b b b
b b b b b b b
- - - - - - -
b b b b b b b
- - - - - - -
- - - - - b b
- - - - - - -
b b b b b - -
b b b b b b b
b b b b b - -
b b b b b - -
b b b b b b b
- - - - - - -
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
30 30 30 30 30 60 60
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
b b b b b b b
- - - - - - -
50 50 50 50 50 50 50
300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5
300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 440 x 462.5 x 227.5 440 x 462.5 x 227.5
14 14 14 14 14 35 35
18 18 18 18 18 45 45
- - - - - - -
A-69
Functions and characteristics Switch-disconnector selection
Compact INV100 to 630 DC
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3
and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 C
Conventional thermal current in enclosure Ithe at 60 C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Compact INV250 switch-disconnector.
Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical DC
PB111443_47.eps
250 V
Positive contact indication
Visible break
Emergency-off switch disconnector
Degree of pollution
Upstream protection
See the Complementary technical information in catalogue Compact INS/INV
LVPED213024EN.
(1) Suitable for 480 V NEMA.
(2) 550 A (DC).
A-70
INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630
3-4 3-4 3-4 3-4 3-4 3-4 3-4 3-4
- - - - - - - -
A-71
Functions and characteristics Switch-disconnector selection
Compact INV100 to 630 DC
A-72
INV100 INV160 INV200 INV250 INV320 INV400 INV500 INV630
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
- - - - b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b - - - -
b b b b - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 5 < Nm < 6.2 13.5 < Nm < 16.5 13.5 < Nm < 16.5 13.5 < Nm < 16.5 13.5 < Nm < 16.5
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
- - - - - - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
15 15 15 15 50 50 50 50
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 136 x 140 x 96 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130 205 x 185 x 130
2 2 2 2 4.6 4.6 4.6 4.6
2.2 2.2 2.2 2.2 4.9 4.9 4.9 4.9
400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 400 x 300 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200 600 x 400 x 200
A-73
Functions and characteristics Switch-disconnector selection
Compact INV630b to 2500 DC
Number of poles
Electrical characteristics as defined by IEC 60947-1 / 60947-3
and EN 60947-1 / 60947-3
Conventional thermal current (A) Ith at 60 C
Conventional thermal current in enclosure Ithe at 60 C
Rated insulation level (V) Ui AC 50/60 Hz
Impulse-withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Rated operational voltage AC20 and DC20 (V) AC 50/60 Hz
Rated operational current (A) Ie Electrical DC
125 V (2P in series)
Compact INV1600 switch-disconnector. 250 V (4P in series)
Rated duties Uninterrupted duty
Intermittent duty
Short-circuit making capacity (kA peak) Icm Min. (switch-disconnector alone)
Short-time withstand current (kA rms) Icw 0.5 s
PB111513_45.eps
0.8 s
1s
3s
20 s
30 s
Suitability for isolation
Durability (O-C cycles) Mechanical
Electrical DC
125 V (2P)
250 V (4P)
Positive contact indication
Visible break
Emergency-off switch disconnector
Compact INV1600 emergency-off switch-disconnector. Degree of pollution
Upstream protection
See the Complementary technical information in catalogue Compact INS/INV
LVPED213024EN.
PB111519_L62.eps
A-74
INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500
3-4 3-4 3-4 3-4 3-4 3-4 3-4
- - - - - - -
A-75
Functions and characteristics Switch-disconnector selection
Compact INV630b to 2500 DC
A-76
INV630b INV800 INV1000 INV1250 INV1600 INV2000 INV2500
b b b b b b b
b b b b b b b
- - - - - - -
b b b b b b b
- - - - - - -
- - - - - b b
- - - - - - -
b b b b b - -
b b b b b b b
b b b b b - -
b b b b b - -
b b b b b b b
- - - - - - -
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
30 30 30 30 30 60 60
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
- - - - - - -
- - - - - - -
b b b b b b b
b b b b b b b
b b b b b b b
- - - - - - -
50 50 50 50 50 50 50
300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 300 x 340 x 146.5 440 x 347.5 x 227.5 440 x 347.5 x 227.5
300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 300 x 410 x 146.5 440 x 462.5 x 227.5 440 x 462.5 x 227.5
14 14 14 14 14 35 35
18 18 18 18 18 45 45
- - - - - - -
A-77
Functions Communication
and characteristics
EnerlinX communication system
Products overview
Enerlin'X communication system provides access Ethernet has become the universal link between switchboards, computers and
to status, electrical values and devices control using communication devices inside the building. The large amount of information which
Ethernet and Modbus SL communication protocols. can be transferred makes the connection of Enerlin'X digital system to hosted web
services of Schneider Electric a reality. More advantages are offered to integrators
thanks to configuration web pages available remotely or on the local Ethernet network.
G G
G G
H D
(1)
(2)
F
B
Ethernet
Modbus SL ULP is a fast communication link dedicated
ULP to circuit breaker monitoring and control.
(1) Only Micrologic 1.0 (no metering/advanced functions).
(2) No Micrologic available.
A-78
Enerlin'X communication devices and displays
Name Function Port Bin. Analog. Bin. Cial. Ref.
Input Input Output
(to device) (to server)
D
gateway
E Smartlink
Ethernet
with Input/Output
functions &
Master
Gateway
(1) Gateway: transfers data from a network to another (ie.: Modbus to Ethernet).
(2) No metering/advanced function available.
(3) Interface: transfers data from an equipment to a network.(ie.: ULP to Modbus).
A-79
Functions Communication
and characteristics IFE Ethernet interface
Introduction
The IFE interface and IFE interface + gateway enable LV circuit breakers
as Masterpact NT/NW, Compact NSX or Powerpact to be connected to an Ethernet
network.
gateway
on the LAN.
bb ULP compliant for localization of the IFE interface in the switchboard.
bb Ethernet interface for Compact, Masterpact and Powerpact circuit breakers.
bb Gateway for Modbus-SL connected devices (IFE interface + gateway only).
bb Embedded set-up web pages.
bb Embedded monitoring web pages.
bb Embedded control web pages.
bb Built-in e-mail alarm notification.
Mounting
The IFE interface, IFE interface + gateway are DIN rail mounting devices. A stacking
accessory enables the user to connect several IFMs (ULP to Modbus interfaces) to
an IFE interface + gateway without additional wiring.
24 V DC power supply
IFE interface + gateway, ref.: LV434011 The IFE interface, IFE interface + gateway must always be supplied with 24 V DC.
The IFMs stacked to an IFE interface + gateway are supplied by the IFE interface +
gateway, thus it is not necessary to supply them separately. It is recommended to
use an UL listed and recognized limited voltage/limited current or a class 2 power
supply with a 24 V DC, 3 A maximum.
DB406743.eps
A-80
General characteristics
DB417466.eps
Environmental characteristics
24VDC
Conforming to standards UL 508, UL 60950, IEC 60950, 60947-6-2
Certification cUIUs, GOST, FCC, CE
Ambient temperature -20 to +70 C (-4 to +158 F)
Relative humidity 585 %
ETH1 ETH2 Level of pollution Level 3
Flame resistance ULV0
Mechanical characteristics
Shock resistance 1000 m/s2
Resistance to sinusoidal vibrations -5 Hz < f < 8.4 Hz
A B Electrical characteristics
Resistance to electromagnetic discharge Conforming to IEC/EN 61000-4-3
I J K Immunity to radiated fields 10 V/m
Immunity to surges Conforming to IEC/EN 61000-4-5
Consumption 120 mA at 24 V input
ETH1 ETH2
Physical characteristics
Dimensions 72 x 105 x 71 mm (2.83 x 4.13 x 2.79 in.)
IFE Mounting DIN rail
IFE-XX.YY.ZZ (factory set)
ETH1 LK/10-100/ACT
Weight 182.5 g (0.41 lb)
ETH2 LK/10-100/ACT
C Degree of protection of the installed IO bb On the front panel (wall mounted enclosure): IP4x
Module Status D bb Connectors: IP2x
Modbus-SL
Network Status
E bb Other parts: IP3x
T LV434011
Connections Screw type terminal blocks
F Technical characteristics - 24 V DC power supply
Power supply type Regulated switch type
R
Rated power 72 W
Input voltage 100120 V AC for single phase
200500 V AC phase-to-phase
PFC filter With IEC 61000-3-2
H G Output voltage 24 V DC
Power supply out current 3A
Note: it is recommended to use an UL listed/UL listed recognized limited voltage/Limited current
or a class 2 power supply with a 24 V DC, 3 A maximum.
A-81
Functions Communication
and characteristics IFM Modbus communication interface
Function
PB103798-50.eps
Characteristics
ULP port
2 RJ45 sockets, internal parallel wiring.
bb Connection of a single circuit breaker (eventually via its I/O application module).
IFM Modbus communication interface.
Ref.: TRV00210.
bb A ULP line terminator or an FDM121 display unit must be connected to the second
RJ45 ULP socket.
The RJ45 sockets deliver a 24 VDC supply fed from the Modbus socket.
DB417690.eps
Built-in test function, for checking the correct connection to the circuit breaker
A and FDM121 display unit.
Modbus slave port
bb Top socket for screw-clamp connector, providing terminals for:
vv 24 VDC input supply (0V, +24V)
vv Modbus line (D1, D2, Gnd).
bb Lateral socket, for Din-rail stackable connector.
Both top and lateral sockets are internally parallel wired.
6
5
B
4 7
3 8
2
1 0
5
9
6
bb Multiple IFM can be stacked, thus sharing a common power supply and Modbus
line without individual wiring.
4 7
3 8
2 9
A-82
COM option in Compact and Masterpact
All the Masterpact devices can be fitted with the For fixed and Drawout devices, the common communication option is made
communication function thanks to the COM option. up of:
Masterpact uses the Ethernet or Modbus bb a BCM ULP module, installed behind the Micrologic control unit and supplied with
communications protocol for full compatibility with the its set of sensors (OF, SDE, PF and CH micro switches) its kit for connection to XF
supervision management systems. and MX1 communicating voltage releases and its COM terminal block (inputs E1 to
Eco COM is limited to the transmission of metering E6). This module is independent of the control unit. It receives and transmits
data. It is not used to communicate status and controls. information on the communication network. An infra-red link transmits data between
the control unit and the communication module.
Consumption: 30 mA, 24 V.
bb IFM, this module required for connection to the network, contains the Modbus
address (1 to 99) declared by the user via the two dials in front. It automatically
adapts (baud rate, parity) to the Modbus network in which it is installed.
Or
bb IFE, the Ethernet interface for LV circuit breaker enables an intelligent modular
unit (IMU), for example a Masterpact NT/NW or Compact NSX circuit breaker to be
connected to an Ethernet network. Each circuit breaker has its own IFE and a
corresponding IP address.
PB106674-20.eps
BSCM module
PB103786.eps
Functions
The optional BSCM Breaker Status & Control Module is used to acquire device
status indications and control the communicating remote-control function.
It includes a memory used to manage the maintenance indicators.
Status indications
Indication of device status:
BSCM module. O/F, SD and SDE.
Maintenance indicators
The BSCM module manages the following indicators:
bb mechanical operation counter
bb electrical operation counter
bb history of status indications.
It is possible to assign an alarm to the operation counters.
Controls
The module can be used to carry out communicating remote control operations:
(open, close and reset) in different modes (manual, auto).
Mounting
The BSCM module can be installed on all CompactNSX circuit breakers and
switch-disconnectors. It simply clips into the auxiliary contact slots. It occupies the
slots of one O/F contact and one SDE contact. The BSCM is supplied with 24 V DC
power automatically via the NSX cord when the communication system is installed.
A-83
Functions Communication
and characteristics I/O application module
Description
DB416829.eps
The I/O input/output application module for LV breaker is part of an ULP system with
built-in functionalities and applications to enhance the application needs. The ULP
system architecture can be built without any restrictions using the wide range of
circuit breakers.
The I/O application is compliant with the ULP system specifications.
Two I/O application module can be connected in the same ULP network.
Pre-defined applications
Pre-defined application adds new functions to the IMU in a simple way:
bb selection by the application rotary switch on the I/O, defining the application with
pre-defined input/output assignment and wiring diagram.
bb no additional setting with the customer engineering tool required.
The resources not assigned to the pre-defined application are free for additional
user-defined applications:
bb cradle management
bb breaker operation
bb light and load control
bb custom.
User-defined applications
User-defined applications are processed by the I/O in addition to the pre-defined
application selected.
The user-defined applications are available depending on:
bb the pre-defined application selected
bb the I/O resources (inputs and outputs) not used by the application.
The resources required by user-defined applications are assigned using the
customer engineering tool:
bb protection
bb control
bb energy management
bb monitoring.
Mounting
The I/O is a DIN rail mounting device.
4 6
It has 9 positions and each position is assigned to a pre-defined application.
3 7
The factory set position of the switch is pre-defined application 1.
2 8
1 9
Setting locking pad
The setting locking pad on the front panel of the I/O enables the setting of the I/O by
the customer engineering tool.
DB416828.eps
DB416828.eps
A-84
General characteristics
DB417467.eps
Environmental characteristics
Conforming to standards UL 508, UL 60950, IED 60950, 60947-6-2
Certification cUIUs, GOST, FCC, CE
Ambient temperature -20 to +70 C (-4 to +158 F)
Relative humidity 585 %
Level of pollution Level 3
I1 C I2 I3 C I4 I5 C I6
Flame resistance ULV0
Mechanical characteristics
Shock resistance 1000 m/s2
Resistance to sinusoidal -5 Hz < f < 8.4 Hz
vibrations
Electrical characteristics
A B
Resistance to electromagnetic Conforming to IEC/EN 61000-4-3
discharge
Immunity to radiated fields 10 V/m
Immunity to surges Conforming to IEC/EN 61000-4-5
24VDC I1 C I2 I3 C I4 I5 C I6 Consumption 165 mA
Physical characteristics
Dimensions 71.7 x 116 x 70.6 mm (2.83 x 4.56 x 2.78 in.)
C
Mounting DIN rail
4 5 6
M 3 7 I1
AI D Weight 229.5 g (0.51 lb)
2 8
1
APP
9 I2
Degree of protection of the bb On the front panel (wall mounted enclosure): IP4x
I3 O1
installed IO bb IO parts: IP3x
L I4 O2 E
I5
O3
bb Connectors: IP2x
I6 F Connections Screw type terminal blocks
K T
G Technical characteristics - 24 V DC power supply
J IO LV434063 Power supply type Regulated switch type
Rated power 72 W
Input voltage 100120 V AC for single phase
200500 V AC phase-to-phase
13
O1
14 23
O2
24 33
O3
34 T1
A1
T2 PFC filter With IEC 61000-3-2
Output voltage 24 V DC
Power supply out current 3A
Note: it is recommended to use an UL listed/UL listed recognized limited voltage/Limited current
I H or a class 2 power supply with a 24 V DC, 3 A maximum.
Digital inputs
Digital input type Self powered digital input with current limitations as per
IEC 61131-2 type 2 standards (7 mA)
Input limit values at state 1 19.825.2 V DC, 6.18.8 mA
13 14 23 24 33 34 T1 T2 (close)
Input limit values at state 0 019.8 V DC, 0 mA
(open)
Maximum cable length 10 m (33 ft)
Note: for a length greater than 10 m (33 ft) and up to 300 m (1,000 ft), it is mandatory to use a
1
2
shielded twisted cable. The shield cable is connected to the IO functional ground of the IO.
Digital outputs
Digital output type Bistable relay
Rated load 5 A at 250 V AC
Rated carry current 5A
O N
Maximum switching voltage 380 V AC, 125 V DC
Maximum switch current 5A
A 24 V DC power supply terminal block. Maximum switching power 1250 VA, 150 W
B Digital input terminal block: 6 inputs, 3 commons and 1 shield. Minimum permissible load 10 mA at 5 V DC
C 6 input status LEDs. Contact resistance 30 m
D Analog input status LED. Maximum operating frequency bb 18000 operations/hr (Mechanical)
E 3 output status LEDs. bb 1800 operations/hr (Electrical)
F I/O identification labels. Digital output relay protection External fuse of 5 A or less
G Sealable transparent cover. by an external fuse
H Analog input terminal block. Maximum cable length 10 m (33 ft)
I Digital output terminal blocks. Analog inputs
J ULP status LED. The IO analog input can be connected to a Pt100 temperature sensor
K Test/reset button (accessible with cover closed). Range -30 to 200 C -22 to 392 F
L Setting locking pad. Accuracy 2 C from -30 to 20 C 3.6 F from -22 to 68 F
M Application rotary switch: 1 to 9. 1 C from 20 to 140 C 1.8 F from 68 to 284 F
N Switch for IO addressing (IO 1 or IO 2). 2 C from 140 to 200 C 3.6 F from 284 to 392 F
O ULP connectors. Refresh interval 5s 5s
A-85
Functions Communication
and characteristics Communications modules, IFM and IFE
for Compact NSX
All Compact NSX devices can be equipped with the Four functional levels
communication function via a prewired connection The Compact NSX can be integrated in a Modbus or Ethernet communication
system and a Modbus or Ethernet network interface. environment. Four functional levels can be used separately or combined.
The interface can be connected directly or via the Communication of status indications
FDM121 switchboard display unit. Four functional This level is compatible with all Compact NSX circuit breakers, whatever the trip unit,
levels can be combined to adapt to all supervision and with all switch-disconnectors. Using the BSCM module, the following information
requirements. is accessible:
bb ON/OFF position (O/F)
bb trip indication (SD)
bb fault-trip indication (SDE).
Communication of commands
Also available on all circuit breakers and switch-disconnectors, this level
(communicating remote control) can be used to:
bb open
bb close
bb reset.
Modbus principle
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating
Modbus devices (Compact NS with Modbus COM, Power Meter PM700, PM800,
Sepam, Vigilohm, Compact NSX, etc.) are installed. All types of PLCs and
microcomputers may be connected to the bus.
Addresses
The Modbus communication parameters (address, baud rate, parity) are entered
using the Electrical Asset Manager or RSU (Remote Setting Utility).
Number of devices
The maximum number of devices that may be connected to the Modbus bus
depends on the type of device (Compact with Modbus COM, PM700, PM800,
Sepam, Vigilohm, Compact NSX, etc.), the baud rate (19200 is recommended), the
volume of data exchanged and the desired response time. The RS 485 physical
layer offers up to 32 connection points on the bus (1 master, 31 slaves).
A fixed device requires only one connection point (communication module on the
device). A drawout device uses two connection points (communication modules on
the device and on the chassis).
The number must never exceed 31 fixed devices or 15 drawout devices.
Length of bus
The maximum recommended length for the Modbus bus is 1200 meters.
Bus power source
A 24 V DC power supply is required (less than 20 % ripple, insulation class II).
Ethernet principle
Ethernet is a data link and physical layer protocol defined by IEEE 802 10 and 100
Mbps specifications that connects computer or other Ethernet devices. Ethernet is
an asynchronous Carrier Sense Multiple Access with Collision detection (referred as
CSMA/CD) protocol. Carrier Sense means that the hosts can detect whether the
medium (coaxial cable) is idle or busy. Multiple Access means that multiple hosts can
be connected to the common medium. Collision Detection means a host detects
whether its transmission has collided with the transmission of another host (or
hosts). IFE Ethernet interface can be connected to a PC or a laptop over Ethernet.
The maximum length of Ethernet cable is 100 meters. IFE Ethernet interface +
gateway provides a Modbus TCP/IP gateway over Ethernet to enable Modbus TCP
communication from a Modbus TCP master to any Modbus slave devices connected
to it. The maximum active Modbus TCP client connection is twelve.
IFE Ethernet interface has an embedded web server (web page).
The Modbus RS 485 (RTU protocol) system is an open bus on which communicating
Modbus devices (Compact NS with Modbus COM, Power Meter PM700, PM800,
Sepam, Vigilohm, Compact NSX, etc.) are installed. All types of PLCs and
microcomputers may be connected to the bus.
A-86
Communication components
and connections
DB417661.eps
A
or FDM121 display unit via the internal terminal block for the
NSX cord equipped with an RJ45 connector: 24 V DC
vv cord available in three lengths: 0.35 m, 1.3 m and 3 m.
vv insulated 1.3 m version for installations > 480 V AC
vv lengths up to 10 m possible using extensions.
B
bb The FDM121 display unit and the I/O application module
are connected to:
J
vv the IFM Modbus interface by a communication cable with
RJ45 connectors on both ends I
or J
vv the IFE Ethernet interface module by a communication
cable with RJ45 connectors on both ends. H
DB416931.eps
D E
1.3 m
F
Modbus
ULP
24 V DC
24 V DC
+24V
0V
B'
Eth2
Eth1
J
I
J
R
A Modbus network
B IFM Modbus interface
B' IFE Ethernet interface module
C NSX cord
C
D Internal terminal block for communication
via NSX cord
D E
E BSCM module
F Prefabricated wiring F
G TMD trip unit
H FDM121 display G
I RJ45 cable
J Line terminator (on unused connector if applicable) Ethernet
K I/O application module ULP
24 V DC
A-87
Functions Communication
and characteristics Connection of the IFE to a fixed or drawout
Masterpact NW
Connect the IFE to a fixed electrically operated Connect the IFE to a drawout Masterpact NW or circuit breaker using the
Masterpact NW or circuit breaker using the breaker ULP cord
breaker ULP cord
Ethernet Ethernet
DB417665.eps
DB417664.eps
24 V DC 24 V DC
I6
C
I5
24VDC 24VDC C
I4
I3
I2
C
I1
ETH2 ETH2 C
I6
I5
I4
ETH2 ETH2
ETH1 ETH1
C
I3
I2
ETH1 ETH1
C
I1
+ C
24VD
set) set)
(factory (fac tory
.YY.ZZ .YY.ZZ
K
IFE_XX IFE_XX
CT CT
-100/A -100/A
LK/10 LK/10
ETH1 ETH1
IFE -100/A
CT
IFE -100/A
CT
LK/10 LK/10
ETH2 tus ETH2 tus
e Sta e Sta
Modul Modul
rk Status
Netwo
s-SL
Modbu A1
T2
O3 T1
34
33
A
O2
24
O1 23
14
13
B B
C
H
J
C
D
F
E
G
A IFE Ethernet interface for LV circuit breaker A IFE Ethernet interface for LV circuit breaker
B Breaker ULP cord B ULP cable
C Fixed terminal block C Breaker ULP cord
D BCM ULP communication module D Circuit breaker disconnected position contact (CD)
E Fixed electrically operated circuit breaker E Circuit breaker cradle
F BCM ULP communication module
G Drawout circuit breaker
H Drawout terminal block
I Circuit breaker connected position contact (CE)
J Circuit breaker test position contact (CT)
K I/O (Input/Output) application module for LV circuit breaker
A-88
Connection of the IFM to a fixed or drawout
Masterpact NW
Connect the IFM to a fixed electrically operated Connect the IFM to a drawout Masterpact NW or circuit breaker using the
Masterpact NW or circuit breaker using the breaker ULP cord
breaker ULP cord
Modbus Modbus
DB417669.eps
DB417670.eps
I6
C
I5
I4
C
I3
I2
C
I1
I6
C
I5
I4
C
I3
I2
C
I1
+ C
24VD
K
A1
T2
A
O3 T1
34
O2 33
24
O1 23
A
14
13
B
B
C
H
J
C
D
D
E
F
E
A IFM Ethernet interface for LV circuit breaker A IFM Ethernet interface for LV circuit F BCM ULP communication module
B Breaker ULP cord breaker G Drawout circuit breaker
C Fixed terminal block B ULP cable H Drawout terminal block
D BCM ULP communication module C Breaker ULP cord I Circuit breaker connected position
E Fixed electrically operated circuit breaker D Circuit breaker disconnected position contact (CE)
contact (CD) J Circuit breaker test positioncontact(CT)
E Circuit breaker cradle K I/O (Input/Output) application module
for LV circuit breaker
A-89
Functions Communication
and characteristics Electrical Asset Manager Configuration
Engineering tool
Introduction
Capture1b.eps
Electrical Asset Manager is a software application that helps the user to manage a
project as part of designing, testing, site commissioning, and maintenance of the
project life cycle.
It enables the user to prepare the settings of the devices offline (without connecting
to the device) and configure them when connected with the devices.
Also it provides lot of other value added features for the user to manage the project
such as, safe repository in cloud, attach artifacts to each device or at the project
level, organize devices in switchboard wise, manage a hierarchical structure of the
installation etc.
References:
Electrical Asset Manager software package can be downloaded from our website
www.schneider-electric.com.
Capture3b.eps
Features
Electrical Asset Manager supersedes the Schneider Electric customer engineering
tools such as Remote setting Utility (RSU) and Remote Control Utility (RCU) with
additional features.
Electrical Asset Manager supports the connection of Schneider Electric
communicable devices to:
bb create projects by device discovery, selection of devices, and import Bill of
Material (BOM)
bb monitor the status of protection and IO status
bb read information (alarms, measurements, parameters)
bb check protection discrimination between two devices
bb upload and download of configuration or settings in batch mode to multiple
Capture4b.eps
devices.
bb carry out commands and tests
bb generate and print device settings report and communication test report
bb manage multiple devices with electrical and communication hierarchy model
bb manage artifacts (project documents)
bb check consistency in settings between devices on a communication network
bb compare configuration settings between PC and device (online)
bb download latest firmware.
Electrical Asset Manager enables the user to avail the advanced features of the
software once the project is saved in Schneider Electric cloud.
A-90
Functions
Capture5b.eps
Offline Mode
A project can be built in offline mode through 2 different ways:
bb through BOM file import
bb through Device Selection.
Additionally, the user can open an existing project and modify the settings offline.
The user can do the discrimination curve check and firmware compatibility check for
devices in the project.
Online Mode
A project can be built in online mode through device discovery also other than the
methods possible through offline method.
Once the project is built, the following functions can be performed in addition to the
functions available in offline mode:
Capture6b.eps
to transfer the device settings ; to view the tripping curves; to attach device artifacts
and to download the latest firmware, to do the communication test for all the devices
and generate the test report.
bb Monitoring: this allows the user to monitor the real time values of different devices
through different sub tabs namely Monitoring, Logs and Control.
bb Reports: report tab allows you to generate and print a report of the project settings
from the report tab. The user details and project characteristics are automatically
filled with the details entered in the Project page.
Capture8b.eps
A-91
Functions
and characteristics
General characteristics
ofMasterpact NW DC - DC PV
Operating conditions
Ambient temperature
DB402051.eps
Masterpact devices have successfully passed the tests defined by the following
standards for extreme atmospheric conditions:
bb IEC 60068-2-1: dry cold at -40 C
bb IEC 60068-2-2: dry heat at +85 C
bb IEC 60068-2-30: damp heat (temperature +55 C, relative humidity 95 %)
bb IEC 60068-2-52 level 2: salt mist.
Masterpact devices can operate in the industrial environments defined by standard
IEC 60947 (pollution degree up to 4).
It is nonetheless advised to check that the devices are installed in suitably cooled
switchboards without excessive dust.
Vibrations
DB128163.eps
A-92
Masterpact NW DC and DC PV
Altitude
DB128162.eps
(m)
2000 At altitudes higher than 2000 metres, the modifications in the ambient air (electrical
resistance, cooling capacity) lower the following characteristics as follows:
Altitude (m) 2000 3000 4000 5000
NW DC
Impulse withstand voltage Uimp (kV) 12 10.6 9.5 8.4
Rated insulation voltage (Ui) 1000 900 800 700
Maximum rated operationnal NW DC y500 V 500 450 390 350
voltage 50/60 Hz Ue (V) NW DC 500-900 V 900 800 700 630
Rated current (A) at 40 C 1 x In 0.98 x In 0.96 x In 0.94 x In
NW DC PV
Impulse withstand voltage Uimp (kV) 12 10.6 9.5 8.4
Rated insulation voltage (Ui) 1000 1000 950 850
Maximum rated operationnal DC voltage 1000 1000 950 850
Rated current (A) at 40 C 1 x In 0.98 x In 0.96 x In 0.94 x In
Intermediate values may be obtained by interpolation.
Electromagnetic disturbances
DB128164.eps
Degree of protection
Masterpact NW DC circuit breakers offer the following protection characteristics
depending on the installation conditions:
b IP: degree of protection (standard IEC 60529)
b IK: protection against external mechanical impacts (standard EN 50102).
Masterpact NW DC
Circuit breaker installed in a switchboard
Bare circuit breaker IP30
DB104534.eps
A-93
Functions
and characteristics
General characteristics
ofMasterpact NW DC - DC PV
Masterpact NW10 to NW40 DC
A-94
NW10 DC NW20 DC NW40 DC
b b b
b b b
b b b b b b
- - - - - -
b b b b b b
20000
10000
8500 5000 2000
- 2000 - 2000 - 1000
b b b b b b
b b b b b b
b b b b b b
HA HA HA
- 85 - 85 - 85
- 85 - 85 - 85
b b b b - -
b b b b b b
b b b b - -
b b b b b b
A-95
Functions Trip-unit characteristics
and characteristics Trip units for Masterpact NW DC
All Masterpact NW DC devices Protection using the Micrologic 1.0 DC control unit
are equipped with a Micrologic 1.0 DC control unit.
Masterpact NW DC circuit breakers use Micrologic 1.0 DC control units. These
interchangeable units with instantaneous thresholds, operating with electromagnetic
sensors, can be adjusted on site.
The circuit breakers can be used with the three versions of sensors,
defined by their setting range.
PB101139-32R.eps
Adjustments
Settings for Masterpact NW DC circuit breakers may be accessed from the front,
with the switchboard door open.
b Settings are made for the input (+ pole) and the output (- pole).
b The setting range comprises eleven positions, plus five preferential settings
marked A, B, C, D and E.
b The setting values for the two corresponding sensors must be identical.
DB403050.eps
DB402618.eps
A-96
Setting values for magnetic pick-up Im
Settings marked A, B, C, D and E
DB104542.eps
Minimum Maximum
Sensor versions Settings Settings Settings Settings Settings
A1 and A2 B1 and B2 C1 and C2 D1 and D2 E1 and E2
1250/2500 1250 A 1500 A 1600 A 2000 A 2500 A
2500/5400 2500 A 3300 A 4000 A 5000 A 5400 A
5000/11000 5000 A 8000 A 10000 A 11000 A 11000 A
Tolerances 8 % 10 % 10 % 10 % 10 %
DB403114.eps
Intermediate settings
It is possible to set eleven other (unmarked) intermediate values.
DB403115.eps
A-97
Functions Switch-disconnectors
and characteristics
for PV application
Masterpact NW HADCD-PV
Masterpact under 1000 V DC with all the 3 poles in series and this is a mandatory condition whatever the type of fault. This comes to say that
NW40 HADCD-PV the PV systems using these switch-disconnectors must be isolated systems from the earth and that the double fault situation (A
Ui 1000V Uimp 12kV and D or C and E on the diagram below) must be absolutely avoided : insulation monitoring devices shall detect the first fault and
Ue 1000 V c 3P in series the staff shall look for this first fault and clear it with no delay. These switch-disconnectors cannot be used in grounded systems as
Icw 85kA/1s in this situation they may be expected to break the current under the full voltage (1000 V DC) with only 1 pole or 2 poles in series.
Icm 85kA These devices are not designed for that purpose and could sustain irremediable damage if used to break in these conditions.
DB116984.eps
IEC 60947-3
A-98
Connections and safety clearances
DB402268_55.eps
Safety clearances Insulated Metal parts Energised
parts parts
DB416461.eps
DB416462.eps
A 0 0 100
B 0 0 60
F : Datum.
A(*) An overhead clearance of 110 mm is required to remove the arc chutes.
An overhead clearance of 20 mm is required to remove the terminal block.
DB402311_55.eps
DB416464.eps
A 0 0 0
B 0 0 60
F : Datum.
A-99
Functions Panorama of electrical and
andcharacteristics
mechanical accessories
Masterpact NW10 to NW40 DC
PB104736.eps
exist in circuit-breaker (equipped with Micrologic DC
1.0 control unit) and switch-disconnector versions. All
auxiliaries are common from 1000 to 4000 A.
1 OFF pushbutton.
2 ON pushbutton.
3 Closing mechanism charging handle.
4 Operation counter.
5 Operating mechanism charged and ready to close
indication:
b spring charged
DB104522.eps
b spring discharged.
b OFF.
Connections
b Rear vertical connection in standard.
b Possibility of conversion to horizontal connection by turning the connectors
on the site by the customer (except for the NW40).
b Prefabricated series connections.
b Safety shutters, shutter locking blocks.
b Optional accessories:
v interphase barriers
v shutter position indication and locking.
A-100
Locking
PB104367A32.eps
PB104366A32.eps
PB100780-32R_SE.eps
b Pushbutton locking by padlockable transparent
cover.
b OFF-position locking by padlock or keylock.
b Chassis locking:
v in disconnected position by keylock
v in connected, disconnected and test positions.
b Door interlock (inhibits door opening with breaker in
connected position).
b Racking interlock (inhibits racking with door open).
b Racking interlock between crank and OFF
pushbutton.
b Automatic spring discharge before breaker removal.
b Mismatch protection. Locking in disconnected position by keylock or padlock. Door interlock (inhibits door
opening with breaker in
connected position).
Indication contacts
PB100806-19R.eps
PB100807-12R.eps
PB100820-19R.eps
PB100816-19R.eps
b Standard or low-level contacts:
v ON/OFF indication (OF)
v fault-trip indication (SDE)
v carriage switches for connected (CE), disconnected
(CD) and test (CT) positions.
Remote operation
PB104349A55.eps
PB100808-22R.eps
PB100809-11R.eps
PB100818-11R.eps
b Remote ON/OFF:
v gear motor
v XF closing or MX opening voltage releases
v PF ready-to-close contact
v options:
- RAR automatic or Res electrical remote reset
- BPFE electrical closing pushbutton.
b Remote tripping function:
v MN voltage release:
- standard
- adjustable or non-adjustable delay
v or 2nd MX voltage release.
Accessories
DB104524.eps
b Escutcheon.
b Transparent cover for escutcheon.
PB104382-27R.eps
A-101
Functions Connection
andcharacteristics Overview of solutions
Two types of connection are available: vertical Rear connection fixed device
connection is standard however the connectors can be
Masterpact NW DC
rotated for on-site conversion to horizontal connection
(except for NW40). Vertical rear connection
PB105026.eps
A-102
Connection
Overview of solutions
DB402303_59.eps
DB402323_59.eps
A-103
Functions Electrical and mechanical
andcharacteristics
accessories
Masterpact NW10 to NW40 DC
DB418162.eps
reset button.
2 OFF position locking.
3 Electrical closing
pushbutton.
4 ON pushbutton.
5 OFF pushbuton.
6 Operating mechanism
charged and ready to
close indication.
7 Pushbutton locking.
8 Main contact position
indication.
9 Operation counter.
The transparent cover blocks access to the pushbuttons used to open and close the
device.
It is possible to independently lock the opening button and the closing button.
The locking device is often combined with a remote operating mechanism.
The pushbuttons may be locked using either:
b three padlocks (not supplied)
b lead seal
Access to pushbuttons protected by transparent cover. b two screws.
The circuit breaker is locked in the OFF position by physically maintaining the
opening pushbutton pressed down:
b using padlocks (one to three padlocks, not supplied)
b using keylocks (one or two different keylocks, supplied).
Keys may be removed only when locking is effective (Profalux or Ronis type locks).
The keylocks are available in any of the following configurations:
b one keylock
b one keylock mounted on the device + one identical keylock supplied separately for
interlocking with another device
Pushbutton locking using a padlock. b two different key locks for double locking.
Profalux and Ronis keylocks are compatible with each other.
A locking kit (without locks) is available for installation of one or two keylocks (Ronis,
Profalux, Kirk or Castell).
PB100812-32R.eps
Accessory-compatibility
3 padlocks and/or 2 keylocks.
A-104
Locking on the chassis
1 Racking-handle port.
DB418163.eps
2 Connected/test/
disconnected position
indication.
3 Racking interlock.
4 Racking-handle storage.
5 Reset pushbutton.
6 Padlock locking.
7 Keylock locking.
8 Chassis front plate
(accessible with cubicle
door closed).
9 Disconnected position
door interlock.
10 Mismatch protection.
A-105
Functions Electrical and mechanical
andcharacteristics
accessories
Masterpact NW10 to NW40 DC
OF
Supplied as standard 4
Maximum number 12
Breaking capacity (A) Standard minimum load: 100 mA/24 V
p.f.: 0.3 V AC 240/380 10/6 (1)
AC12/DC12 480 10/6 (1)
690 6
V DC 24/48 10/6 (1)
125 10/6 (1)
250 3
Low-level minimum load: 2 mA/15 V
V AC 24/48 6
240 6
380 3
V DC 24/48 6
125 6
250 3
(1) Standard contacts: 10 A; optional contacts: 6 A.
V DC 24/48 3
125 0.3
250 0.15
Low-level minimum load: 2 mA/15 V
V AC 24/48 3
240 3
380 3
V DC 24/48 3
125 0.3
250 0.15
EF
Maximum number 8
Breaking capacity (A) Standard minimum load: 100 mA/24 V
p.f.: 0.3 V AC 240/380 6
AC12/DC12 480 6
690 6
V DC 24/48 2.5
125 0.8
250 0.3
Low-level minimum load: 2 mA/15 V
V AC 24/48 5
240 5
380 5
Combined contacts.
V DC 24/48 2.5
125 0.8
250 0.3
A-106
Connected, disconnected and test position carriage
PB100817-32R.eps
switches
Three series of optional auxiliary contacts are available for the chassis:
b changeover contacts to indicate the connected position CE
b changeover contacts to indicate the disconnected position CD. This position is
indicated when the required clearance for isolation of the power and auxiliary circuits
is reached.
b changeover contacts to indicate the test position CT. In this position, the power
circuits are disconnected and the auxiliary circuits are connected.
Additional actuators
A set of additional actuators may be installed on the chassis to change the functions
of the carriage switches.
CE, CD and CT connected/disconnected/test position
carriage switches. Contacts CE CD CT
Maximum number Standard with additional 3 3 3
actuators 9 0 0
6 3 0
6 0 3
3 6 0
Breaking capacity (A) Standard minimum load: 100 mA/24 V
p.f.: 0.3 V AC 240 8
AC12/DC12
380 8
480 8
690 6
V DC 24/48 2.5
125 0.8
250 0.3
Low-level minimum load: 2 mA/15 V
V AC 24/48 5
240 5
380 5
V DC 24/48 2.5
125 0.8
250 0.3
A-107
Functions Electrical and mechanical
andcharacteristics
accessories
Masterpact NW10 to NW40 DC
Two solutions are available for remote operation of Remote operation: remote ON / OFF
Masterpact devices:
The remote ON / OFF function is used to remotely open and close the circuit breaker.
b a point-to-point solution
It is made up of:
b a bus solution with the COM communication option. b an electric motor MCH equipped with a springs charged limit switch contact CH
b two voltage releases:
v a closing release XF
v an opening release MX.
Optionally, other functions may be added:
PB104349A-68R.eps
COM
A-108
Electric motor MCH
PB100808-32R.eps
The electric motor automatically charges and recharges the spring mechanism when
the circuit breaker is closed. Instantaneous reclosing of the breaker is thus possible
following opening. The spring-mechanism charging handle is used only as a backup
if auxiliary power is absent.
The electric motor (MCH) is equipped as standard with a limit switch contact (CH)
that signals the charged position of the mechanism (springs charged).
Characteristics
Power supply V AC 50/60 Hz 48/60 - 100/130 - 200/240 - 277 - 380/415 - 400/440 - 480
V DC 24/30 - 48/60 - 100/125 - 200/250
Operating threshold 0.85 to 1.1 Un
Consumption (VA or W) 180
Motor overcurrent 2 to 3 In for 0.1 s
Charging time maximum 4 seconds
Operating frequency maximum 3 cycles per minute
CH contact 10 A at 240 V
Opening release MX
200 ms The MX release instantaneously opens the circuit breaker when energised, the
min. minimum duration of the pulse operating order must be 200 ms. The MX release
for MX locks the circuit breaker in OFF position if the order is maintained (except for MX
communicating releases).
Note: whether the operating order is maintened or automatically disconnected (pulse-type), XF
or MX communicating releases (bus solution with COM communication option) always have
an impulse-type action (see diagram).
Characteristics XF MX
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480
V DC 12 - 24/30 - 48/60 - 100/130 - 200/250
Operating threshold 0.85 to 1.1 Un 0.7 to 1.1 Un
PB100809-16R.eps
Consumption (VA or W) pick-up: 200 (during 200 ms) pick-up: 200 (during 200 ms)
hold: 4.5 hold: 4.5
Circuit-breaker response time at Un 70 ms 10 (NW DC y 4000 A) 50 ms 10 (NW DC)
80 ms 10 (NW DC > 4000 A)
A-109
Functions Electrical and mechanical
andcharacteristics
accessories
Masterpact NW10 to NW40 DC
DB402622.eps
A-110
Remote operation: remote tripping
This function opens the circuit breaker via an electrical order. It is made up of:
PB104369A-68R.eps
DB402625.eps
DB402626.eps
DB402624.eps
When energised, the MX voltage release instantaneously opens the circuit breaker.
A continuous supply of power to the second MX locks the circuit breaker in the OFF
position.
Characteristics
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 277 - 380/480
V DC 24/30 - 48/60 - 100/130 - 200/250
Operating threshold 0.7 to 1.1 Un
Permanent locking function 0.85 to 1.1 Un
Consumption (VA or W) pick-up: 200 (during 80 ms) hold: 4.5
MX or MN voltage release. Circuit-breaker response time at Un 50 ms 10
Characteristics
Power supply V AC 50/60 Hz 24 - 48 - 100/130 - 200/250 - 380/480
V DC 12 - 24/30 - 48/60 - 100/130 - 200/250
Operating threshold opening 0.35 to 0.7 Un
closing 0.85 Un
Consumption (VA or W) pick-up: 200 (during 200 ms) hold: 4.5
MN consumption with delay unit pick-up: 200 (during 200 ms) hold: 4.5
Circuit-breaker response time at Un 90 ms 5
MN delay units
To eliminate circuit-breaker nuisance tripping during short voltage dips, operation of
the MN release can be delayed. This function is achieved by adding an external
delay unit in the MN voltage-release circuit. Two versions are available, adjustable
and non-adjustable.
Characteristics
Power supply non-adjustable 100/130 - 200/250
VAC 50-60 Hz/DC adjustable 48/60 - 100/130 - 200/250 - 380/480
Operating threshold opening 0.35 to 0.7 Un
closing 0.85 Un
Consumption of delay unit alone (VA or W) pick-up: 200 (during 200 ms) hold: 4.5
Circuit-breaker response non-adjustable 0.25 s
time at Un adjustable 0.5 s - 0.9 s - 1.5 s - 3 s
A-111
Functions Electrical and mechanical
andcharacteristics
accessories
Masterpact NW10 to NW40 DC
Optional equipment mounted on the chassis, the shield prevents access to the
terminal block of the electrical auxiliaries.
The operation counter sums the number of operating cycles and is visible on the front
panel. It is compatible with manual and electrical control functions.
Escutcheon CDP
DB101173.eps
Optional equipment mounted on the door of the cubicle, the escutcheon increases
the degree of protection to IP40 (circuit breaker installed free standing: IP30) .
It is available in fixed and drawout versions.
This option allows the grounding of the breaker mechanism while the front cover is
removed. The grounding is made via the chassis for the drawout version and via the
fixation side plate for the fixed version.
A-112
Compact NSX DC - DC PV Installation recommendations
Masterpact NW DC - DC PV
Presentation 2
Functions and characteristics A-1
Compact NSX DC PV
Safety clearances and minimum distances B-10
Temperature derating B-12
Temperature derating - Power dissipation / Resistance B-13
B-1
Installation Compact NSX100 to NSX1200 DC
recommendations
Installation in switchboards
DB413249.eps
DB413250.eps
Fig. C Fig. D
DB413251.eps
DB413252.eps
Fig. E
DB413253.eps
Possible supports
For fixed or withdrawable circuit breakers
On a plain mounting plate On a slotted mounting plate
DB413249.eps
DB413254.eps
On rails
DB413255.eps
B-2
Power connections
The circuit breakers can be connected with copper, tinned copper or tinned
aluminum conductors (rigid or flexible bars, cables).
In the event of a short-circuit, electrodynamic forces will be exerted on the
conductors.
They must therefore be correctly sized and maintained in place using supports.
Electrical connection points on all types of devices (contactors, circuit breakers, etc.)
should not be used for mechanical support.
Weights
Type Circuit Plug-in Chassis Motor
breaker base mechanism
NSX100N/H DC 1P/1D 0.5 - - -
2P/2D 1.45 - - -
NSX100 DC 3P/3D 1.79 0.8 2.2 1.2
4P/4D 2.57 1.05 2.2 1.2
NSX160N/H DC 1P/1D 0.5 - - -
2P/2D 1.45 - - -
NSX160N DC 3P/3D 1.85 0.8 2.2 1.2
4P/4D 2.58 1.05 2.2 1.2
NSX250 DC 3P/3D 2.2 0.8 2.2 1.2
4P/4D 2.78 1.05 2.2 1.2
NSX400/630 DC 3P/3D 6.19 2.4 2.2 2.8
4P/4D 8.13 2.8 2.2 2.8
NSX1200 DC 2P/2D 8.9 - - 2.8
B-3
Installation Compact NSX100 to NSX1200 DC
recommendations
Power connections
NSX100/160/250 NSX400/630/1200
DC DC
Bars L (mm) y 25 y 32
DB115656.eps
I (mm) d + 10 d + 15
d (mm) y 10 y 15
400
e (mm) y6 3 y e y 10
d (mm) 8.5 10.5
I
L Lugs L (mm) y 25 y 32
L
(mm) 8.5 10.5
e Tightening torque (Nm) (1) 15 50
Tightening torque (Nm) (2) 5 20
(1) Tightening torque for lugs or bars on the circuit breaker.
(2) Tightening torque for rear connections or terminal extensions on plug-in base.
DB115660.eps
NSX100 to 250 DC
DB111327.eps
DB112315.eps
NSX400 to 630 DC
DB111326.eps
DB112316.eps
NSX1200 DC
2-cable connector
L (mm) 30 or 60
DB111326.eps
B-4
Safety clearances, minimum distances
and insulation of live parts
Minimal distance between two adjacent circuit When installing a Compact NSX100 to 1200 DC circuit breaker, minimum distances
breakers (safety clearances) must be maintained between the device and panels, bars and
A1 other protection devices installed nearby. These distances, which depend on the
DB402628.eps
A2 ultimate breaking capacity, are defined by tests carried out in accordance with
standard IEC 60947-2.
If installation conformity is not checked by type tests, it is also necessary to:
b use insulated bars for circuit breaker connections
b block off the busbars using insulating screens.
Terminal shields, interphase barriers and the insulation kit are recommended and
may be mandatory depending on the utilisation voltage and the type of installation
(fixed, withdrawable).
Minimal distance between the circuit breaker and Minimal distance between the circuit breaker and top, bottom or side panels
front or rear panels
DB402630.eps
DB402629.eps
DB413245.eps
D1
NSX100-250 DC U y 250 V 0 30 30 5 35 35 0 10 0
U y 500 V 0 30 30 10 (1) 35 35 0 20 0
U y 750 V 0 30 (4) 30 (4) 20 (4) 35 (4) 35 (4) 0 - 0
NSX400-630 DC U y 250 V 0 30 30 5 60 60 0 10 0
U y 500 V 0 30 30 10 (1) 60 60 0 20 0
U y 750 V 0 30 (4) 30 (4) 20 (4) 100 (4) 100 (4) 0 - 0
NSX1200 DC (5) U y 300 V 0 30 30 10 60 60 0 - 0
U y 600 V 0 30 30 20 100 100 0 - 0
(1) Distance must be doubled with interphase barriers.
(2) For Compact NSX DC with long or short terminal shields.
(3) For Compact NSX DC without terminal shields.
(4) For voltage > 500 V, terminal shields are mandatory. The length of terminal shields (long or short terminal shields) should be considered.
(5) For Compact NSX1200 DC, terminal shields are required and are supplied with the circuit breaker.
The mandatory distances when installing Compact NSX DC circuit breakers are calculated from the device case, not taking into account the terminal shields or the
interphase barriers.
DB403290.eps
DB403288.eps
DB403291.eps
DB115861.eps
DB418517.eps
DB417745.eps
DB115854.eps
DB115855.eps
DB115853.eps
B-5
Installation Compact NSX100 to NSX1200 DC
recommendations
Temperature derating
These values are valid for fixed and withdrawable When the ambient temperature is greater than 40 C, overload-protection
circuit breakers with or without terminal shields. characteristics are slightly modified.
To determine tripping times using time/current curves, use the values of the current
indicated in the table below, corrected to take into account the ambient temperature.
Example: Compact NSX100 DC equipped with a TM80DC trip unit has a rating of:
b 84 A at 40 C
b 78 A at 55 C.
B-6
Characteristics of circuit breakers with
parallel connection of poles
When poles are connected in parallel,the trip unit Type of Pole Type of Equivalent Magnetic Breaking
corresponding to the maximum circuit breaker rating is circuit connections trip unit rated threshold capacity
never used, for safety reasons related to temperature breaker current (1) Im (A) Icu (kA)
rise.The heating conditions are modified.The table In (A) 20 %
opposite indicates the new thermal ratings that should at 40 C
be used for 2P, 3P and 4P circuit breakers. NSX100F DC 250 V 500 V
NSX100F DC 2P in parallel TM16D 40 520 36 -
2-pole TM25D 63 800
TM30D 80 800
TM40D 100 1400
TM50D 125 1400
TM63D 158 1400
See TM80D 200 1600
example 2
(see page
A-8)
NSX100F DC 3P in parallel TM16D 58 780 Please -
3-pole TM25D 90 1200 consult
us
TM32D 115 1650
TM40D 144 2100
TM50D 180 2100
TM63D 227 2100
TM80DC 288 2400
TM16G 58 240
TM25G 90 300
TM40G 144 300
TM63G 227 450
TM80G 288 750
TM100G 360 1200
NSX100F DC 4P in parallel TM16D 74 1040 Please -
4-pole TM25D 115 1600 consult
us
TM32D 147 2200
TM40D 184 2800
TM50D 230 2800
TM63D 290 2800
TM80DC 368 3200
TM16G 74 320
TM25G 115 400
TM40G 184 400
TM63G 290 600
TM80G 368 1000
TM100G 460 1600
2 x 2P (in TM16D 37 520 36 36
parallel) TM25D 58 800
in series
TM32D 74 1100
TM40D 46 1400
TM50D 115 1400
TM63D 145 1400
TM80DC 184 1600
TM16G 37 160
TM25G 58 200
TM40G 46 200
TM63G 145 300
TM80G 184 500
TM100G 230 800
(1) Rated current of the assembly with the indicated pole connections.
B-7
Installation Compact NSX100 to NSX1200 DC
recommendations
Characteristics of circuit breakers with
parallel connection of poles
When poles are connected in parallel,the trip unit Type of Pole Type of Equivalent Magnetic Breaking
corresponding to the maximum circuit breaker rating is circuit connections trip unit rated threshold capacity
never used, for safety reasons related to temperature breaker current (1) Im (A) 20 % Icu (kA)
rise.The heating conditions are modified.The table In (A) at
opposite indicates the new thermal ratings that should 40 C
be used for 2P, 3P and 4P circuit breakers. NSX160F DC 250 V 500 V
NSX160F DC 2P in parallel TM125D 313 2400 36 -
2-pole
NSX160F DC 3P in parallel TM100DC 360 2400 Please -
3-pole TM125DC 450 3750 consult
us
TM125G 450 1560
TM160G 576 1560
NSX160F DC 4P in parallel TM100DC 460 3200
4-pole TM125DC 575 5000
TM125G 575 2080
TM160G 736 2080
2x2P (in TM100DC 230 1600 36 36
See parallel) in TM125DC 288 2500
series
example 1 TM125G 288 1040
(see page TM160G 368 1040
A-8)
NSX250F DC
NSX250F DC 2P in parallel TM160DC 400 2500 36 -
3-pole TM200DC 500 2000 to 4000
NSX250F DC 3P in parallel TM160DC 576 3750 Please -
3-pole TM200DC 720 3000 to 6000 consult
us
TM200G 720 1560
TM250G 900 1875
NSX250F DC 4P in parallel TM160DC 736 5000
4-pole TM200DC 920 4000 to 8000
TM200G 920 2080
TM250G 1150 2500
2x2P (in TM160DC 368 2500 36 36
parallel) TM200DC 460 2000 to 4000
in series
TM200G 460 1040
TM250G 575 1250
B-8
Characteristics of circuit breakers with
parallel connection of poles
When poles are connected in parallel,the trip unit Type of Pole Type of Equivalent Magnetic Breaking
corresponding to the maximum circuit breaker rating is circuit connections trip unit rated threshold capacity
never used, for safety reasons related to temperature breaker current (1) Im (A) 20 % Icu (kA)
rise.The heating conditions are modified.The table In (A) at
opposite indicates the new thermal ratings that should 40 C
be used for 2P, 3P and 4P circuit breakers. NSX400F DC 250 V 500 V
NSX400F DC 2P in parallel TM250DC 500 1250 to 2000 36 -
3-pole TM320DC 640 1600 to 3200
3P in parallel TM250DC 750 1875 to 3000 36 -
TM320DC 960 2400 to 4800
NSX400F DC 4P in parallel TM250DC 1000 2500 to 4000
4-pole TM320DC 1280 3200 to 6400
2x2P (in TM250DC 500 1250 to 2000 36 36
parallel) TM320DC 640 1600 to 3200
in series
NSX630F DC
NSX630F DC 2P in parallel TM500DC 1000 2500 to 5000 36 -
3-pole TM600DC 1065 3000 to 6000
NSX630F DC 3P in parallel TM500DC 1485 3750 to 7500 36 -
3-pole TM600DC 1500 4500 to 9000
NSX630F DC 4P in parallel TM500DC 1650 5000 to 10000
4-pole TM600DC 1985 6000 to 12000
B-9
Installation Compact NSX DC PV
recommendations Safety clearances and minimum distances
DB413830.eps
DB415722.eps
D1
D3
C1
0.8 min.
DB416421.eps
D1
Fiber
insulating
plate
Fiber
insulating
plate
D2
Dimensions (mm) C1 C2 D1 D2
NSX80 to 200 DC PV 13 13 13 13
NSX250 to 500 DC PV 25.4 25.4 25.4 25.4
Note: the thermal behaviour of switchgear and enclosures warrants careful monitoring. PV generator boxes and array boxes are usually installed outdoors
and exposed to the elements. In the event of high ambient temperatures, high IP levels could reduce air flow and thermal power dissipation.
In addition, the way switchgear devices achieve high voltage operation - i.e. through the use of poles in series - increases their temperature. Special attention
should therefore be paid to the temperature of switchgear inside outdoor enclosures on the DC side.
Schneider Electric recommend to check the installation as per IEC 61439 or any other equivalent standard.
B-10
Safety clearance with interphase barriers
PB110838_71.eps
DB413832.eps
DB413833.eps
DB413834.eps
panel
D1/D2
Compact NSX200 NA DC PV
with short heatsinks and
interphase barriers.
D3 Insulating
C1 screen is
PB110839_69.eps
(1)
mandatory
(1) Dimensions of the insulating screen are identical as for the circuit breaker (see page B-10).
Compact NSX200 NA DC PV
with long heatsinks and
interphase barriers.
Note: the thermal behaviour of switchgear and enclosures warrants careful monitoring. PV generator boxes and array boxes are usually installed outdoors
and exposed to the elements. In the event of high ambient temperatures, high IP levels could reduce air flow and thermal power dissipation.
In addition, the way switchgear devices achieve high voltage operation - i.e. through the use of poles in series - increases their temperature. Special attention
should therefore be paid to the temperature of switchgear inside outdoor enclosures on the DC side.
Schneider Electric recommend to check the installation as per IEC 61439 or any other equivalent standard.
B-11
Installation
recommendations
Compact NSX DC PV
Temperature derating
DC PV overcurrent protection
Compact NSX TM DC PV
Maximum current (A): Ith Cooper
For Compact NSX the overload protection is calibrated cable
20 C 25 C 30 C 35 C 40 C 45 C 50 C 55 C 60 C 65 C 70 C
section (1)
at 40 C and for C60 DC PV at 20 C. This means that
when the ambient temperature is less or greater than NSX80 TM DC PV
these temperatures, the Ir protection pickup is slightly 88 86 84 82 80 77 75 72 69 66 63 Cu 25 mm2
modified. NSX125 TM DC PV
b Temperature rise for Compact range have been 137.5 135 131 128 125 121 116 112 108 103 98 Cu 50 mm2
checked with terminal shields (mandatory) heatsink on NSX160 TM DC PV
top, four cables on bottom connections with section 176 172 168 164 160 153 147 142 136 130 124 Cu 70 mm2
and length according to IEC60947-1 Table 9 and 10. NSX200 TM DC PV
b Values in the tables are provided for vertical 194 189 183 178 172 167 161 155 149 142 136 Cu 95 mm2
mounting only. In case of horizontal mounting consult 200 200 200 200 200 188 182 175 168 160 153 Cu 95 mm2 (*)
us. To obtain the tripping time for a given temperature: NSX250 TM DC PV
v see the tripping curves for 20 or 40 C 302 295 288 280 250 243 235 228 220 210 197 Cu 120 mm2
v determine tripping times corresponding to the Ir NSX320 TM DC PV
value (thermal setting on the device), corrected for the 371 362 352 342 320 309 297 286 273 261 248 Cu 185 mm2
breaker ambient temperature as indicated in the tables NSX400 TM DC PV
below. 455 444 433 421 400 386 372 358 343 327 311 Cu 240 mm2
NSX500 TM DC PV
557 542 526 511 495 478 461 444 426 405 384 Cu 2x150 mm2
(1) Temperature rise have been checked with four cables on bottom connections with section and length according to IEC60947-1 Table 9
a. When used in array boxes, with short connection to string protections the cross section of the bars or cables shall have a higher cross section.
b. When cables have a cross section lower than the value indicated an additional 0.9 derating coefficient shall be applied.
Values in the tables are provided for vertical mounting only.
(*) Take into account this derating line for products with date code over --15011.
B-12
Temperature derating -
Power dissipation / Resistance
B-13
Installation Masterpact NW10 to NW40
recommendations
DC - DC PV
Installation in switchboard
Possible positions
DB402631.eps
DB402632.eps
DB402633.eps
Power supply
The plus and minus polarities (LINE + and LINE -) of the power supply must be
connected as indicated in the Dimensions and connection chapter.
DB402634.eps
DB402636.eps
Mounting on rails.
DB402637.eps
B-14
Door interlock
Mounted on the right or left-hand side of the craddle, Door interlock catch VPEC
this device inhibits opening of the cubicle door when
the circuit breaker is in connected or test position. Y
DB402638.eps
It the breaker is put in the connected position with the
door open, the door may be closed without having to
disconnect the circuit breaker.
Dimensions (mm)
Type DC (1) (2)
NW10-40 DC (versions C-D) 215 215
NW10-40 DC (version E) 330 215
Type DC PV (1) (2)
NW10-40 DC PV (version D) 215 215
Note:
The door interlock can either be mounted on the right side or
the left side of the breaker.
F : Datum.
B-15
Installation Masterpact NW10 to NW40
recommendations
DC - DC PV
Cable-type door interlock - Connection of
MN, MX and XF voltage releases
Cable-type door interlock IPA
This option prevents door opening when the circuit breaker is closed and prevents
circuit breaker closing when the door is open.
For this, a special plate associated with a lock and a cable is mounted on the right
side of the circuit breaker.
With this interlock installed, the source changeover function cannot be implemented.
DB402737.eps
DB402738.eps
DB402739.eps
B-16
Power connection
Cable connections
DB402740.eps
DB402741.eps
If cables are used for the power connections, make
sure that they do not apply excessive mechanical
forces to the circuit breaker terminals.
For this, make the connections as follows:
bb extend the circuit breaker terminals using short bars
designed and installed according to the
recommendations for bar-type power connections:
vv for a single cable, use solution B opposite
vv for multiple cables, use solution C opposite.
bb in all cases, follow the general rules for connections
to busbars:
vv position the cable lugs before inserting the bolts
v the cables should firmly secured to the framework of
the switchboard E.
DB402742.eps
Busbar connections
DB402743.eps
DB402744.eps
Electrodynamic stresses
The first busbar support or spacer shall be situated within a maximum distance from
the connection point of the breaker (see table below). This distance must be
respected so that the connection can withstand the electrodynamic stresses between
phases in the event of a short circuit.
Maximum distance A between busbar to circuit breaker connection and the first busbar
support or spacer with respect to the value of the prospective short-circuit current.
Isc (kA) 30 50 65 80 100
distance A (mm) 350 300 250 150 150
B-17
Installation Masterpact NW10 to NW40
recommendations
DC - DC PV
Power connection
Clamping
DB402746.eps
DB402747.eps
DB402748.eps
DB402749.eps
1 Terminal screw factory-tightened to 16 Nm.
2 Breaker terminal. Tightening torques
3 Busbar. Tightening torque (Nm) Tightening torque
4 Bolt. with flat washers or (Nm) with contact
Nominal (mm) Drilling (mm)
5 Washer. split lockwashers or serrated washers
6 Nut.
10 11 37.5 50
Busbar drilling
Examples
DB402750.eps
DB402751.eps
DB402752.eps
Isolation distance
DB402753.eps
Dimensions (mm)
Ui X mini
500 V DC 8 mm
900 V DC 14 mm
Busbar bending
When bending busbars maintain the radius indicated below
(a smaller radius would cause cracks).
DB402754.eps
Dimensions (mm)
e Radius of curvature r
Min. Recommended
5 5 7.5
10 15 18 to 20
B-18
DB402767.eps DB402766.eps DB402765.eps DB402761.eps DB402760.eps DB402755.eps
DB402762.eps DB402756.eps
DB402763.eps DB402757.eps
DB402764.eps DB402758.eps
DB402759.eps
B-19
Installation Masterpact NW10 to NW40
recommendations
DC - DC PV
Busbar sizing
Basis of tables
b maximum permissible busbar temperature: 100 C
b Ti: temperature around the circuit breaker and its connections
b busbar material is unpainted copper.
Example
Conditions:
b drawout version
b horizontal busbars
b Ti:50 C
b service current:2000 A.
Solution
For Ti = 50 C, use an NW20 DC - DC PV which can be connected
with three 100 x 5 mm bars or two 80 x 10 mm bars.
Basis of tables
b maximum permissible busbar temperature: 100 C
b Ti: temperature around the circuit breaker and its connections
b busbar material is unpainted copper.
Example
Conditions:
b fixed version
b vertical busbars
b Ti:40 C
b service current:1000 A.
Solution
For Ti = 40 C, use an NW10 DC - DC PV which can be connected
with two 50 x 5 mm bars or one 50 x 10 mm bar.
B-20
Temperature derating - Power dissipation
and input/output resistance
Temperature derating
The table below indicates the maximum current rating, for each connection type, as
a function of the ambient temperature around the circuit breaker and the busbars.
For ambient temperatures greater than 60 C, consult us.
Ti: temperature around the circuit breaker and its connections.
B-21
TOOLS
schneider-electric.com
C-1
Dimensions Compact (fixed version) 1P-2P
andconnection
NSX100-NSX160 DC
Dimensions, mounting, cutout
Dimensions
1 pole 2 poles
DB402532.eps
DB402533.eps
DB402534.eps
X X X
Y Y
Mounting
On backplate
1 pole 2 poles
DB416364.eps
DB416365.eps
X X
Y Y
(c) For rear connection only.
On rails
1 pole 2 poles
DB402537.eps
DB402538.eps
X X
Y Y
C-2
Front-panel cutout
On backplate
DB402539.eps
DB416366.eps
DB416367.eps
DB416368.eps
X X X X
Y Y
Y
With escutcheon
DB416369.eps
DB402543.eps
X X
Dimensions (mm)
Type C C1 C2 C3 C6 C7 G G1 G4 G5 H
NSX100/160 DC 29 76 54 108 43 104 62.5 125 70 140 80.5
Type H1 H2 H3 H4 H6 H7 K K1 L3 L4 L5
NSX100/160 DC 161 94 188 160.5 178.5 357 17.5 35 17.5 70 35
Type P1 P2 P4 P5 P6 R R1 R2 R4 R5 R6
NSX100/160 DC 81 86 111 83 88 14.5 29 19 38 73 29
Type R7 T T4 U
NSX100/160 DC 58 6 22 y 32
C-3
Dimensions and Dimensions and mounting
connection Compact NSX100 to 1200 DC
fixed version
DB112062.eps
DB112063.eps
DB112064.eps
A4
A3
A A2
A1
X X X
A A2
A3
A4
C1 B B
C2 B1 B2
C3
Z Y Y
Interphase barriers. Long terminal shields (also available for NSX400/630 DC spreaders with 52.5 mm pitch:
Short terminal shields. B1 = 157.5 mm, B2 = 210 mm).
F1 F1 F1 F1 F1 F1 F1
DB112065.eps
DB111411.eps
DB112067.eps
DB112066.eps
F2 F2 F2
F1 F1 F3
E4
X X X
E2
E1 E3
2 6 Y T(1) Y 4 6 Y 4 6
F1 F1 F3
DB112068.eps
DB111412.eps
DB112069.eps
DB112070.eps
F2 F2 F2
X X X
E2
E1
2 6 Y Y 4 6 Y 4 6
C-4
On DIN rail with adapter plate (NSX100 to 250 DC)
G4
DB112071.eps
DB112072.eps
G5
G3 X
G2
G1
Dimensions (mm)
Type A A1 A2 A3 A4 B B1 B2 C1 C2 C3
NSX100/160/250 DC 80.5 161 94 145 178.5 52.5 105 140 81 86 126
NSX400/630 DC 127.5 255 142.5 200 237 70 140 185 95.5 110 168
NSX1200 DC - - - 240 - 70 - 185 95.5 110 168
Type E1 E2 F1 F2 F3 G1 G2 G3 G4 G5
NSX100/160/250 DC 62.5 125 35 17.5 70 95 75 13.5 23 17.5
NSX400/630 DC 100 200 45 22.5 90 - - - - -
NSX1200 DC 100 200 - 22.5 90 - - - - -
C-5
Dimensions Dimensions and mounting
andconnection Compact NSX100 to 630 DC
plug-in version
Dimensions 3P 4P
M
DB112640.eps
DB112641.eps
DB112642.eps
DB112643.eps
N
A11
M A10
A A2
N A1
X X X
A A2
A10
A11
B B
27 B1 B2
45
D1 C3
Z Y Y
Interphase barriers for base. Long terminal shields (also available for NSX400/630 DC spreaders with 52.5 mm pitch:
Short terminal shields on circuit breaker. B1 = 157.5 mm, B2 = 210 mm)
Adapter for base, required to mount long terminal shields or interphase barriers.
Mounting
Through front panel (N) 3P 3P 4P
NSX100 to 250 DC NSX400/630 DC NSX100 to 630 DC
F1 F1 F3
DB112648.eps
DB112649.eps
DB115637.eps
DB112650.eps
N F2 F2 F2
E10 E12 X X Y
X
E9 E11
F4 F4 F4 4 6
2 6 4 6
F5 F5 F6
Y Y Y
C-6
On backplate (M) 3P 4P
Front connection (an insulating screen is supplied with the base and must be fitted between the base and the backplate)
F1 F3
DB112654.eps
DB112655.eps
DB112656.eps
F2 F2
E14 X X
E13
2 6 4 6
Y Y
F1 F1 F1 F1 F1
DB112657.eps
DB112658.eps
DB112659.eps
F1 F2
F2 F3
E14 E16 X X
E13 E15
2 6 T1(1) 4 6
Y Y
(1) The T1 holes are required for rear connection only.
F1 F1 F1 F1 F1
DB112660.eps
DB112661.eps
DB112662.eps
F1 F2
F2 F3
E14
E18 X
X
E13 E17
2 6 T1(1) 4 6
Y Y
(1) The T1 holes are required for rear connection only.
On rails 3P 4P
F7 F8
DB112663.eps
DB112664.eps
DB112665.eps
F9 F9
U
X X
E20
E19
2 6 4 6
Y Y
C-7
Dimensions and Dimensions and mounting
connection Compact NSX100 to 630 DC
withdrawable version
Dimensions 3P 4P
M
DB112644.eps
DB112645.eps
DB112646.eps
DB112647.eps
N
A10
M A12 A11
N
X X X
A13 A11
A10
B3 B3
27 B4 B6
45 B5 B7
D1 C3 Y Y
Z
M
DB112681.eps
C3 32
Z
Interphase barriers for base. Long terminal shields.
Short terminal shields on circuit breaker. Adapter for base, required to mount long terminal shields or interphase barriers.
Mounting
Through front panel (N) 3P 3P 4P
NSX100 to 250 DC NSX400/630 DC NSX100 to 630 DC
N F1 F1 F3
DB112651.eps
DB112652.eps
DB115638.eps
DB112653.eps
F2 F2 F2
3 E10 E12 X X X
E9 E11
C-8
On backplate (M) 3P 4P
Front connection (an insulating screen is supplied with the base and must be fitted between the base and the backplate)
F1 F3
DB112682.eps
DB112655.eps
DB112656.eps
F2 F2
E14 X X
E13
2 6 4 6
Y Y
F1 F1 F1 F1 F1
DB112683.eps
DB112658.eps
DB112659.eps
F1 F2
F2 F3
E14 E16 X X
E13 E15
2 6 T1(1) 4 6
Y Y
(1) The T1 holes are required for rear connection only.
F1 F1 F1 F1 F1
DB112684.eps
DB112661.eps
DB112662.eps
F1 F2
F2 F3
E14
E18 X
X
E13 E17
2 6 T1(1) 4 6
Y Y
On rails 3P 4P
F7 F8
DB112685.eps
DB112664.eps
DB112665.eps
F9 F9
U
X X
E20
E19
2 6 4 6
Y Y
Type A10 A11 A12 A13 B3 B4 B5 B6 B7 C3 D1 E9 E10 E11 E12 E13 E14
NSX100/160/250 DC 175 210 106.5 103.5 92.5 185 216 220 251 126 75 95 190 87 174 77.5 155
NSX400/630 DC 244 281 140 140 110 220 250 265 295 168 100 150 300 137 274 125 250
Type E15 E16 E17 E18 E19 E20 F1 F2 F3 F7 F8 F9 F10 F11 F12 T1 U
NSX100/160/250 DC 79 158 61 122 37.5 75 35 17.5 70 70 105 35 74 148 183 24 y 32
NSX400/630 DC 126 252 101 202 75 150 45 22.5 90 100 145 50 91.5 183 228 33 y 35
C-9
Dimensions and Dimensions and mounting
connection Motor mechanism module
for Compact NSX100 to 1200 DC
DB112694.eps
DB112695.eps
DB112696.eps
A17
A15 X X X
A14 A16
5...8
B8 B8
C4
B9 B9
C5/C6
B B
B1 B2
Y Y
Z
C5: without keylock
C6: with keylock
Plug-in circuit breaker
M M
DB112697.eps
DB112698.eps
N N
5...8
27
45
D1 C5
Z
Withdrawable circuit breaker
M M
DB112699.eps
DB112700.eps
N N
X
5...8
27
45
D1 C5 32
Z
C-10
Direct rotary handle
for Compact NSX100 to 1200 DC
DB112702.eps
DB112703.eps
DB112704.eps
I
60
A15 X X X
60
A14 O
A18
B8 B8
B9 B9
C7
B B
C8/C9 B1 B2
Z Y Y
DB112706.eps
N N
27
45
D1 C8
Z
N N
27
45
D1 C8 32
C-11
Dimensions and Dimensions and mounting
connection MCC and CNOMO type direct rotary
handles for Compact NSX100 to 1200 DC
fixed version
Dimensions
MCC type direct rotary handle
DB112712.eps
DB112713.eps
DB112714.eps
A18
A20
5...
8
X X
A19
1...3 max.
P1 B10
B11
Z B12
Y
CNOMO type direct rotary handle
DB112715.eps
DB112716.eps
DB112717.eps
LIN GERI
MER t NS
compac
N
A18 A22
X X
8
5...
push
to
trip
A21
1...3 max.
P2 B10
B13
B14
Z Y
DB111413.eps
DB111414.eps
100 145
5...
8
X X
41 51
50
75
100
145
Y
Y
CNOMO type direct rotary handle
DB112715.eps
DB111415.eps
DB111416.eps
N
LIN GERI
MER t NS
compac
150
119
8
5...
push
to
trip
X X
50.5 50.4
C-12
Extended rotary handle
for Compact NSX100 to1200 DC
Dimensions
Fixed and plug-in circuit breakers
M M
DB112709.eps
DB112710.eps
N N
10
X
DB112711.eps
N N
DB111419.eps
60 45 50
A18 A18
75 X X
37.5
60 2 4.2
36
72
B10
Type A18 B10 D1 B10
37.5
Y
NSX100/160/250 DC 9 9.25 75 75
NSX400/630/1200 DC 24.6 5 100 Y
C-13
Dimensions and Front-panel accessories
connection Compact NSX100 to 1200 DC
DB114998.eps
DB114999.eps
DB115000.eps
DB416370.eps
X X
A
B 4
Y
DB115002.eps
DB115003.eps
DB115004.eps
X X
A1
B 4
Y
DB115010.eps
DB115011.eps
DB115012.eps
X A3 X
A2
B1 3.5 6.5
Y
DB115022.eps
DB115024.eps
DB115023.eps
X X
A4
B2 35
Y
C-14
IP43 toggle cover
DB115030.eps
DB115031.eps
DB115032.eps
DB115120.eps
X
A5
B3 C
Y
Type A A1 A2 A3 A4 A5 B B1 B2 B3 C
NSX100/160/250 DC 113 138 114 101 73 85 113 157 91 103 40
NSX400/630/1200 DC 163 211 164 151 122.5 138 163 189 122.5 138 60
C-15
Dimensions and Power connections
connection Compact NSX100 to 1200 DC
fixed version
DB115445.eps
DB115446.eps
DB417705.eps
10.5 14
14
Z
70 113.5
X X
Cables with lugs/bars Bars/cables with lugs
159.5
DB416576.eps
43 for short RC
88 for long RC
10 8.6
13
18
70
6 20
X
NSX400/630 DC
Z
DB416577.eps
50 for short RC
115 for long RC
15 13 23.2
14
30
113.5
8
X
Bare-cable connectors
NSX100 to 250 DC
DB115450.eps
DB416579.eps
Z
DB416578.eps
Z 63
22
70
X
70
C-16
Connection with accessories (cont.)
Bare-cable connectors
NSX400/1200 DC
DB115453.eps
DB416581.eps
Z Z
DB416580.eps
46.5
14
113.5 113.5
X X
DB417704.eps
DB417703.eps
46.5
Z
159.5
DB416582.eps
70
41
64.5
66.5 (a)
(a) NSX250 DC. Z
Right-angle terminal extensions (upstream only)
NSX100 to 250 DC NSX400/630 DC
Z
DB115458.eps
DB403551.eps
DB403552.eps
Z
37.5 61 8
39.5 (b) 4
20.5 34
70 113.5
X X
(b) NSX250 DC.
C-17
Dimensions and Power connections
connection Compact NSX100 to 630 DC
fixed version
DB403553.eps
Z
41
30
70
DB115464.eps
DB115465.eps
30
Z
23.5
58
53
42 8 42
70 113.5
4
X X
DB115467.eps
DB115468.eps
Z 10
13.5
61.5
40 48
31 8
4
70 113.5
X X
DB115470.eps
45
4
46
35
70
C-18
Connection with accessories (cont.)
Spreaders 3P 4P
NSX100 to 250 DC
E1 E3
DB115471.eps
DB115472.eps
DB115473.eps
DB115474.eps
E2 E2 F2 E2 E2 E2 C3
F1
X X X
NSX400/630 DC
Y Y
C4
Type C3 C4 E1 E2 E3 F1 F2
NSX100/160 DC 23.5 - 114 45 159 100 11
NSX250 DC 25.5 - 114 45 159 100 11
NSX400/630 DC - 44 135 52.5 187.5 152.5 15
170 70 240 166 15
DB115477.eps
180.5
DB115476.eps
26
140
45 45 45
130
113.5
X
X
Y
Z
C-19
Dimensions and Power connections
connection Connection of insulated bars or cables
with lugs to Compact NSX100 to 1200 DC
DB115653.eps
Dimensions NSX100 DC NSX160/250 DC NSX400/630/1200 DC
400 Bars L (mm) y 25 y 25 y 32
d I (mm) d + 10 d + 10 d + 15
I
d (mm) y 10 y 10 y 15
L
e (mm) y6 y6 3 y e y 10
e
(mm) 6.5 8.5 10.5
Bar. Lugs L (mm) y 25 y 25 y 32
DB417866.eps
l (mm) 20 y I y 25 20 y I y 25
DB112172.eps
DB112176.eps
d (mm) y 10 y 10
400
e (mm) y6 y6
Tinned copper Tinned copper d (mm) 6.5 8.5
I
Spreaders: L Lugs L (mm) y 25 y 25
L
separate parts One-piece spreader (mm) 6.5 8.5
e Torque (Nm) (1) 10 15
DB112177.eps
DB416402.eps
Tinned copper
Spreaders and straight, right-angle, 45, double-L and edgewise terminal extensions
are supplied with flexible interphase barriers.
For U > 600 V, the mandatory insulation kit is not
compatible with spreaders made up of separate parts.
Connection with accessories to NSX400 DC and 630 DC
Accessories for NSX400 and 630 DC (IEC 228)
Spreaders made up of separate parts for 52.5 and Pole pitch
70 mm pitch Without spreaders 45 mm
With spreaders 52.5 or 70 mm
DB115657.eps
l (mm) d + 15 30 y I y 34
Tinned copper d (mm) y 20 y 15
400
For U > 600 V, use of the 52.5 mm pitch spreaders e (mm) 3 y e y 10 3 y e y 10
requires a specific insulation kit. d (mm) 12.5 10.5
I
The 70 mm pitch spreaders may not be used. L Lugs L (mm) y 40 y 32
L
(mm) 12.5 10.5
Accessories for NSX100 to 630 DC e Torque (Nm) (1) 50 50
Right-angle terminal Edgewise terminal
Torque (Nm) (2) 20 20
extensions extensions
(1) Tightening torque on the circuit breaker for spreaders or terminal extensions.
(2) Tightening torque on the plug-in base for spreaders or terminal extensions.
DB112175.eps
DB112173.eps
Spreaders and right-angle, 45 and edgewise terminal extensions are supplied with
flexible interphase barriers.
Tinned copper Tinned copper
DB115658.eps
To be mounted on upstream
side.
45 terminal extensions
DB112174.eps
C-20
Connection of bare cables
to Compact NSX100 to 1200 DC
DB115660.eps
DB112315.eps
DB112317.eps
DB111327.eps
1-cable 2-cable Distribution connector
connector connector
DB115663.eps
S (mm) Cu / Al 1.5 to 95 (1) 25 to 50 70 to 95 120 to 185
150 max. flex.
L Torque (Nm) 12 20 26 26
2-cable connector
S
L (mm) 25 or 50
S (mm) Cu / Al 2 x 50 to 2 x 120
Torque (Nm) 22
6-cable distribution connector (copper or aluminium)
L (mm) 15 or 30
S (mm) Cu / Al 1.5 to 6 (1) 8 to 35
Torque (Nm) 4 6
(1) For flexible cables from 1.5 to 4 mm, connection with crimped or self-crimping ferrules.
DB111326.eps
2-cable connector
2-cable connector
L (mm) 30 or 60
DB115663.eps
C-21
Dimensions Compact (fixed version)
andconnection
2P-3P-4P Parallel and series
connection ofpoles
Compact NSX100 to NSX250 DC
2P fixed version (Compact NSX100-160 N/H DC) - 3P fixed version (Compact NSX100-250 DC)
With series connections
2 poles 3 poles
DB402545.eps
X X X X X X X X X
Y Y Y
Z Y Y Y Y Y
DB402547.eps
X X X
Z
Y Y
X X X X X
Y
Y
Z Y Y
DB402549.eps
DB402550.eps
DB402551.eps
X X
X
Y
Y
Z
C-22
Compact NSX400 to NSX630 DC
3P fixed version (Compact NSX400-630 DC)
With series connections
DB402552.eps
X X X X X X X
Y Y
Z Y Y Y Y
DB402554.eps
DB402555.eps
X X
Y
Z
X
X X X X
Y
Z Y Y
DB402558.eps
DB402560.eps
X X X
Y Y
Z
C-23
Dimensions Compact (fixed version)
andconnection
4P Parallel and series connection
of poles
Compact NSX630 to NSX1200 DC
4P fixed version (Compact NSX630 to NSX1200DC)
With parallel connections
45
DB417867.eps
DB417868.eps
45 45
347
X
X 319
173.5 159.5
17
Y
Z
C-24
Compact (withdraw. version)
3P-4P Parallel and series
connection ofpoles
Compact NSX100 to NSX250 DC
3P withdrawable version
Connections mounted with heat sink directed outwards
DB402561.eps
DB402562.eps
DB402563.eps
Z
Y
X X
X X
Z
Y
DB402565.eps
DB402566.eps
Y Z
X X
X X
Y Z
4P withdrawable version
Connections mounted with heat sink directed outwards
DB402568.eps
DB402569.eps
DB402567.eps
Y Z
X X
X X
Z
Y
DB402571.eps
DB402572.eps
Y Z
X X
X X
Y Z
C-25
Dimensions Compact (withdraw. version) 3P-
andconnection
4P Parallel and series connection
ofpoles
Compact NSX400 to NSX630 DC
3P withdrawable version
Connections mounted with heat sink directed outwards
DB402573.eps
DB402574.eps
DB402575.eps
Y Z
X X
X X
Z
Y
DB402577.eps
DB402578.eps
Y Z
X X
X X
Y Z
4P withdrawable version
Connections mounted with heat sink directed outwards
DB402579.eps
DB402580.eps
DB402581.eps
Y Z
X X
X X
Y Z
DB402583.eps
DB402584.eps
Y Z
X X
X X
Y
Z
C-26
Dimensions Compact (fixed version)
andconnection
4P connection ofpoles,
dimensions and mounting
Compact NSX100 to NSX630 DC PV
4P fixed version (Compact NSX100-250 DC PV)
With series connections
12.5 47.5
DB413515.eps
DB416371.eps
55 60
DB415913.eps
6
190.5
X X 125 X
70 625
Y
22
17.5
Z 70
35 35 35
Y
67
DB416372.eps
75
DB415914.eps
356 6
X X X
200
113.5
100
32 22.5
Y
90
45 45 45
Z Y
Dimensions
DB112061R.eps
DB416373.eps
DB112064R.eps
A4
A3
A
A1
X X
A A2
A3
A4
C1 B
C2
B2
C3
Z Y
Interphase barriers. Long terminal shields (also available for NSX400/630 DC spreaders with 52.5 mm
Long terminal shields. pitch: B2 = 210 mm).
Type A A1 A2 A3 A4 B B2 C1 C2 C3
NSX100/160/250 DC PV 80.5 161 94 145 178.5 52.5 140 81 86 126
NSX400/630 DC PV 127.5 255 142.5 240 237 70 185 95.5 110 168
C-27
Dimensions Compact (fixed version)
and connection
4P connection ofpoles,
dimensions
Compact NSX630b to 1600 DC PV
Electrical control
Front connection
DB415915.eps
DB415753.eps
(1)
(2)
254
248.5
163.5 240
X 210 327
200
X
100
254
Z
107.5 169.5 99.5
175.5 Y
182
(1) With terminal shield.
(2) With phase separator.
Rear connection
DB417789.eps
X X
DB415754.eps
100
123
107.5 35
175.5 70
182 169.5 99.5
F
Z
Front-panel cutouts
Door cutout
A
DB415756.eps
150 mini
DB415916.eps
(A)
(1) (2)
Y
264 mini 194 mini
X X 216 (1)
266 (2)
108 (1)
133 (2)
F : Datum.
(1) Without escutcheon.
(2) With escutcheon.
C-28
Compact (fixed version)
4P front connection ofpoles,
mounting
Compact NSX630b to 1600 DC PV
On backplate
Y
DB415758.eps
4 6.5
X
200
100
169.5 99.5
On rails
DB415759.eps
4 6.5
X
200
100
169.5 99.5
Note: mounting parameters for electrically operated devices are identical to those for manually
operated devices.
X and Y are the symmetry planes for a 4-pole device.
Z is the back plane of the device.
C-29
Dimensions Compact (fixed version)
and connection
4P rear connection ofpoles,
mounting
Compact NSX630b to 1600 DC PV
On backplate
Y
DB415760.eps
4 6.5
X
200
75
60 100
4 R30
169.5 99.5
270
On rails
DB415761.eps
169.5 99.5
2 6.5
100
107
117
3 6.5
35
Y
70 70
Note: mounting parameters for electrically operated devices are identical to those for manually
operated devices.
X and Y are the symmetry planes for a 4-pole device.
Z is the back plane of the device.
C-30
Dimensions Masterpact (fixed device)
andconnection
NW10 to 40 DC version C/D (3P),
version E (4P)
NW10 to 40 DC PV version D (3P)
Device
DB402242.eps
DB402241.eps
X X
Y
DB402244.eps
X
DB402243.eps
DB402246.eps
DB402247.eps
C-31
Dimensions Masterpact
DB104832.eps
andconnection
(fixed device)
NW10 to 40 DC
Version C
Connections
Horizontal rear connection (NW10 - NW20 DC) Detail
DB104808.eps
DB416092.eps
DB416093.eps
Y
X
Db101278.eps
Vertical rear connection (NW10 - NW20 DC) Detail
DB402252_55.eps
DB416094.eps
DB416095.eps
X DB101282.eps
Y
View A detail.
DB416096.eps
DB416097.eps
X Y
Db101314.eps
C-32
Masterpact
DB104833.eps
(fixed device)
NW10 to 40 DC - DC PV
Version D
Connections
Horizontal rear connection (NW10 - NW20 DC - DC PV) Detail
DB104818.eps
DB416098.eps
DB416099.eps
X
Db101278.eps
Vertical rear connection (NW10 - NW20 DC - DC PV) Detail
DB402264_55.eps
DB416100.eps
DB416101.eps
X
DB101282.eps
Y
View A detail.
Vertical rear connection (NW40 DC - DC PV) Detail
DB402268_55.eps
DB416102.eps
DB416103.eps
Y
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8.
View A detail.
Tightening torque: 50 Nm with contact washer.
C-33
Dimensions Masterpact
DB104835.eps
andconnection
(fixed device)
NW10 to 40 DC
Version E
Connections
Horizontal rear connection (NW10 - NW20 DC) Detail
DB416105.eps
DB402272_55.eps
DB416104.eps
X Y
Db101278.eps
Vertical rear connection (NW10 - NW20 DC) Detail
DB402276_55.eps
DB416107.eps
DB416106.eps
X Y
DB101282.eps
View A detail.
DB416108.eps
DB416109.eps
Y
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer. View A detail.
C-34
Masterpact (drawout device)
NW10 to 40 DC version C/D (3P)
version E (4P)
NW10 to 40 DC PV version D (3P)
Device
DB416110.eps
DB416111.eps
Y
X X
X Y
DB416112.eps
DB416113.eps
Db101294.eps
DB416114.eps
C-35
Dimensions Masterpact
DB104879.eps
andconnection
(drawout device)
NW10 to 40 DC
Version C
Connections
Horizontal rear connection (NW10 - NW20 DC) Detail
DB402291_55.eps
DB416115.eps
DB416116.eps
Y
Db101278.eps
X
DB416117.eps
DB416118.eps
Y
X
DB101282.eps
View A detail.
DB416119.eps
DB416120.eps
Y
X
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer. View A detail.
C-36
Masterpact
DB104880.eps
(drawout device)
NW10 to 40 DC - DC PV
Version D
Connections
Horizontal rear connection (NW10 - NW20 DC - DC PV) Detail
DB402303_55.eps
DB416121.eps
DB416122.eps
Y
Db101278.eps
Vertical rear connection (NW10 - NW20 DC - DC PV) Detail
DB104859.eps
DB416123.eps
DB416124.eps
X
Y
DB101282.eps
View A detail.
Vertical rear connection (NW40 DC - DC PV) Detail
DB402311_55.eps
DB416125.eps
DB416126.eps
Y
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8.
Tightening torque: 50 Nm with contact washer. View A detail.
C-37
Dimensions Masterpact
DB104881.eps
andconnection
(drawout device)
NW10 to 40 DC
Version E
Connections
Horizontal rear connection (NW10 - NW20 DC) Detail
DB402315_55.eps
DB416127.eps
DB416128.eps
X Y
Db101278.eps
Vertical rear connection (NW10 - NW20 DC) Detail
DB104871.eps
DB416129.eps
DB416130.eps
X Y
DB101282.eps
View A detail.
Vertical rear connection (NW40 DC) Detail
DB416131.eps
DB402323_55.eps
DB416132.eps
Y
Db101314.eps
Note:
Recommended connection screws: M10 class 8.8. View A detail.
Tightening torque: 50 Nm with contact washer.
C-38
Masterpact NW10 to 40
DC - DC PV
Accessories
DB416134.eps
Y
X
X
F : Datum.
Escutcheon
Fixed device Drawout device
Y Y
DB416135.eps
DB416136.eps
X X
Db101368.eps
C-39
Dimensions Masterpact NW10 to 40
and connections
DC - DC PV
Accessories
DB115891.eps
6
3 4 5
S
3 6
MN
UVR
30 V
100/1C
AC/D
C-40
Dimensions and mounting
External modules for Compact and
Masterpact
DB416700.eps
24VDC I1 C I2 I3 C I4 I5 C I6
I1 A1
I2
I3 O1
I4 O2
I5 O3 45 92
I6
84.8 115
IO LV434063
O1 O2 O3 A1
13 14 23 24 33 34 T1 T2
72 63.6
71
IFM - Modbus-SL interface
DB416701.eps
DB416702.eps
45 92
85 105
18 66
73
DB416698.eps
ETH1 ETH2
IFE
IFE-XX.YY.ZZ (factory set)
ETH1 LK/10-100/ACT
45 92
ETH2 LK/10-100/ACT
Module Status
84.8 105
Modbus-SL
Network Status
T LV434011
72 63.6
71
ComX 200
DB417076.eps
DB417077.eps
90 45 85 106
144 63
69
C-41
Dimensions and Dimensions and mounting
connection FDM121 switchboard display
Dimensions
DB114991.eps
DB114992.eps
96
X
96
Y
Mounting
Through panel
DB114993.eps
DB416963.eps
DB118545.eps
+ 0.8
X 92 0
X
+ 0.8
10.6 92 0
20.7 23
Y
Z
On panel
DB114996.eps
DB115121.eps
DB115122.eps
DB115270.eps
2 22.5
16.5
X 99.3
+ X
- 0.5
32
19
+0.3
15 37 20 13 2 22.5
-
+
- 1.5
33
Z
17
99.3
Y
Connector (optional).
C-42
FDM128 switchboard display
Dimensions
DB416703.eps
DB416736.eps
129
X
163
Mounting
On panel
1.5...6
DB416704.eps
DB416737.eps
DB416738.eps
100
X
30.6
17.5
39
+0
DB416739.eps
DB416740.eps
22,5 -0,30
100
100 100
100
+0
30 -0,20
C-43
TOOLS
Ecodial
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
Dimensions and connection C-1
Masterpact NW DC - DC PV
Communication D-14
Withdrawable Masterpact NW DC - DC PV
Connection to the I/O and communication interface module D-16
D-1
Wiring diagrams Compact NSX100 to 1200 DC
Fixed circuit breakers
C2
A4
A2
B4
B2
C1
a (-)
manu SDE
a (-)
NSX cord
a (220/240 V)
+ -
BSCM
HL
B4
auto 0 I
manu
A1
Communicating motor
mechanism (MTc) (1)
D-2
Wiring diagrams Compact NSX100 to 1200 DC
Fixed circuit breakers
Indication contacts
DB403696.eps
102
104
134
124
42
32
22
12
82
84
92
94
44
34
24
14
WH
RD
YE
VT
OF4 OF3 OF2 OF1 SDE SD CAF2 CAF1 CAO1
WH
RD
GY
131
41
31
21
121
101
81
91
11
D-3
Wiring diagrams Compact NSX100 to 630 DC
Plug-in / withdrawable circuit breakers
Remote operation
a (+)
a (+)
DB413077.eps
SDE 81
BPO BPF
82 84
C2
D2
B4
A4
A2
84
RD
A2 WH
BL
C2 OR
A4 OR
BL
D2
B4
B2
MN MX
auto
0 I
or manu
A1
L1
D1
C1
GN
WH
BK
A1
D1/C1
L1
NSX cord
a (220/240 V)
+ -
HL
BSCM
B4
B4 GN
auto
0 I
manu
OR A1
A4
Communicating motor
mechanism (MTc) (1)
D-4
Wiring diagrams Compact NSX100 to 630 DC
Plug-in / withdrawable circuit breakers
32
22
12
82
84
92
94
44
34
24
14
42 GN
82 GN
92 GN
44 RD
84 RD
94 RD
32 YE
22 YE
12 YE
34 VT
24 VT
14 VT
314
312
352
354
102
104
134
124
WH
GY
GY
RD
VT
VT
YE
VT
OF4 OF3 OF2 OF1 SDE SD CAF2 CAF1 WH CAO1 CE CD
YE
YE
GY
RD
131
121
101
BK 41
GY 31
GY 21
311
351
BK 81
BK 91
GY 11
41
31
21
81
91
11
D-5
Wiring diagrams Compact NSX100 to 630
DC - DC PV
Motor mechanism
The diagram is shown with circuits Motor mechanism (MT) with automatic reset
de-energised, all devices open, connected and a (+)
charged and relays in normal position.
DB114666.eps
SDE 81
BPO BPF
After tripping initiated by the "Push to trip" button or
by the undervoltage (MN) release or the shunt (MX)
release, device reset can be automatic, remote or 82 84
manual.
A4
A2
B4
B2
Following tripping due to an electrical fault (with an
SDE contact), reset must be carried out manually.
Q
auto
0 I
manu
A1
L1
manu SDE
a (-)
SDE 81
BPO BPF Reset
82 84
A4
A2
B4
B2
Q
auto
0 I
manu
A1
L1
manu SDE
a (-)
SDE 81
BPO BPF
82 84
A4
A2
Symbols
B4
B2
Q: circuit breaker
A4 : opening order
A2: closing order
B4, A1: motor mechanism power supply Q
L1: manual position (manu) auto
0 I
manu
B2: SDE interlocking (mandatory for correct
operation)
A1
L1
D-6
Wiring diagrams Compact NSX100 to 630
DC - DC PV
Motor mechanism
NSX cord
DB114669.eps
a (220/240 V)
+ -
BSCM
HL
B4
Q
auto 0 I
manu
A1
a
DB114670R.eps
Symbols
Q: circuit breaker
B4, A1: motor mechanism power supply
BSCM: breaker status and control module
Terminals shown in red O must be connected by the customer.
D-7
Wiring diagrams Compact NSX100 to 630
DC - DC PV
Communication
Ethernet
I
24 V DC
Modbus
A M A
24 V DC B
+24V
0V
H H
Eth2
Eth1
C
D
J +24V
0V
Eth2
Eth1
-100/A
ct/Eth1
H
H
LK/10
ct/Eth2
-100/A
H
LK/10
atus
atus
I6
C
I5
I4
C
I3
I2
C
I1
I6
C
I5
I4
C
I3
I2
C
I1
+
DC
24V
A1
O1
J
O2
O3
J dule
IO Mo
E
E
A1
T2
O3 T1
34
I6 O2 33
C
I
I5 24
I4 O1 23
C 14
I3 13
I2
C
I1
I6
C
I5
I3
I2
C
I1
+
DC
24V
A1
T2
T1
L
O2
24
O1 23
14
13
F
K L
G G
A FDM121 (TRV00121) E I/O application module (LV434063) I FDM128 (LV434128) J ULP cable
M Modbus Termination
(1)
B IFE master (LV434011) F Masterpact NW K Breaker ULP cord
(VW3A8306DRC)
C IFE (LV434010) G Compact NSX L NSX cord
D IFM (TRV00210) H ULP termination (TRV00880) Ethernet
Modbus
(1) Modbus termination is mandatory, see ULP system user guide TRV99101.
D-8
Wiring diagrams Compact NSX100 to 630
DC - DC PV
Communication
121
FDM
DB417667.eps
24VDC
I/O
application
module
ULP cable
NSX cord
Modbus-SL Ethernet
24 V DC 24 V DC
24VDC
ETH1 ETH2
IFM IFE
D-9
Electrical diagrams Compact NSX630b
to NSX1600 DC PV
Fixed switch-disconnectors
Remote operation
MN : undervoltage release
DB128373.eps
or
MX : shunt release
AT BPO BPF
Motor-mechanism module (1)
A4 : electrical opening order
A2 : electrical closing order
D2
C2
B4
A4
A2
CN1 a - 440/480 V
DB128380.eps
9 11
MN MX Motor-mechanism R
module A4 A2 B4
or
Motor-mechanism
module
D1
A1
C1
A1
CN2 a - 440/480 V
D-10
Indication contacts Terminal-block marking (electrical operation)
OF3 / OF2 / OF1 : indication contacts
DB128377R.eps
MN/MX
D1/C1
D2/C2
31 21 11
32 22 12
34 24 14
B4 A4 A2 A1
D-11
Electrical diagrams Masterpact NW10 to NW40
DC - DC PV
Fixed and drawout devices
DB404307.eps
DB105058.eps
Micrologic DC Micrologic DC
Version E - DC Version D - DC PV
DB416406.eps
DB404308.eps
Micrologic DC
E3 E4 182 82 C3 A3 252 B3
D-12
Electrical diagrams Masterpact NW10 to NW40
DC - DC PV
Fixed and drawout devices
44 34 24 14 244 234 224 214 144 134 124 114 834 824 814 334 324 314 934 924 914
42 32 22 12 242 232 222 212 142 132 122 112 832 822 812 332 322 312 932 922 912
41 31 21 11 241 231 221 211 141 131 121 111 831 821 811 331 321 311 931 921 911
or or or or or or or or or or
EF24 EF23 EF22 EF21 EF14 EF13 EF12 EF11 CE6 CE5 CE4 CE9 CE8 CE7
248 238 228 218 148 138 128 118 364 354 344 394 384 374
246 236 226 216 146 136 126 116 362 352 342 392 382 372
245 235 225 215 145 135 125 115 361 351 341 391 381 371
OF14 or or
EF14
CD6 Disconnected
OF13 or CD5 position
EF13 CD4 contacts
OF12 or
EF12
OF11 or
EF11
Legend:
Interconnected connections
(only one wire per connection point).
D-13
Electrical diagrams Masterpact NW DC - DC PV
Communication
Communication architecture
DB417944.eps
Ethernet
I
24 V DC
Modbus
A M A
24 V DC B
+24V
0V
H H
Eth2
Eth1
C
-100/A
ct/Eth1
D
LK/10
ct/Eth2
-100/A
LK/10
tus
J
s Sta
Modbu
+24V tus
0V rk Sta
s Netwo
Modbu
Com
Eth2
Eth1
R
-100/A
ct/Eth1
H
H
LK/10
ct/Eth2
-100/A
H
LK/10
tus
s Sta
Modbu
tus
rk Sta
s Netwo
Modbu I6
Com I5
C
I4
C
I3
I2
C
I1
I6
C
I5
I4
C
I3
I2
R I1
C
+
DC
24V
A1
O1
J
I1
O2
I2
O3
I3
APP I4
J
I5
I6
dule
IO Mo
E
C
I6
E O2 33
O3
34
T1
A1
T2
I
I5 24
I4 O1 23
C 14
I3 13
I2
C
I1
I6
C
I5
I4
C
I3
I2
C
I1
+
DC
24V
A1
O1
1
I1
O2
2
I2
O3
3
I3
APP 4
I4
5
I5
6
I6
dule
IO Mo
A1
T2
O3 T1
34
O2 33
L
24
O1 23
14
13
F
K L
G G
A FDM121 (TRV00121) E I/O application module (LV434063) I FDM128 (LV434128) J ULP cable
M Modbus Termination
(1)
B IFE master (LV434011) F Masterpact NW K Breaker ULP cord
(VW3A8306DRC)
C IFE (LV434010) G Compact NSX L NSX cord
D IFM (TRV00210) H ULP termination (TRV00880) Ethernet
Modbus
(1) Modbus termination is mandatory, see ULP system user guide TRV99101.
D-14
Electrical diagrams Fixed, electrically operated
Masterpact NW DC - DC PV
Connection to the communication
interface module
DB416707.eps
121
FDM
Color
Red E1 24 V
Black E2 0V
White E5 H
Blue E6 L
Breaker ULP
cord
E1 E2 E3 E4 E5 E6
A / Tx- D0
B / Tx+ D1
A / Rx- D0
B / Rx+ D1
24 V
0V
D0 = A / Rx-, A / Tx-
ULP cable D1 = B / Rx+, B / Tx+
24VDC
ETH1 ETH2
IFE IFM
OR
D-15
Electrical diagrams Withdrawable Masterpact NW
DC - DC PV
Connection to the I/O and communication
interface module
DB416708.eps
121
FDM
24VDC
I/O
application
Color module
Red E1 24 V
Black E2 0V
White E5 H
Blue E6 L
Breaker ULP ULP cable
cord
Red Black White Blue
E1 E2 E3 E4 E5 E6
A / Tx- D0
B / Tx+ D1
A / Rx- D0
B / Rx+ D1
24 V
0V
Modbus-SL Ethernet
24 V DC 24 V DC
24VDC
ETH1 ETH2
IFM IFE
D-16
Compact NSX DC - DC PV Additional characteristics
Masterpact NW DC - DC PV
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
Dimensions and connection C-1
Electrical diagrams D-1
E-1
Additional Compact NSX100 to 250 DC
characteristics TMD magnetic trip units, tripping curves
TM16D TM25D
DB413316.eps
DB413317.eps
Reflex tripping.
TM30D/TM32D TM40D
DB417919.eps
DB413319.eps
Reflex tripping.
E-2
Additional Compact NSX100 to 250 DC
characteristics TMD magnetic trip units, tripping curves
TM50D TM63D
DB413320.eps
DB413321.eps
TM63D : Im = 11 x In
TM80D TM100D
DB416611.eps
DB416610.eps
E-3
Additional Compact NSX100 to 250 DC
characteristics
TMD magnetic trip units, tripping curves
TM125D TM160D
DB416310.eps
DB416311.eps
TM200D TM250D
DB416312.eps
DB416313.eps
E-4
Additional Compact NSX100 to 250 DC
characteristics
TMG magnetic trip units, tripping curves
TM16G TM25G
DB416352.eps
DB416353.eps
TM25G DC : Im 4.3 x In
TM40G TM63G
DB416354.eps
DB416355.eps
E-5
Additional Compact NSX100 to 250 DC
characteristics TMG magnetic trip units, tripping curves
TM80G TM100G
DB416583.eps
DB416584.eps
TM80G TM100G
Im = 3.1 x In Im = 4 x In
t < 10 ms t < 10 ms
TM125G TM160G
DB416586.eps
DB416585.eps
TM160G
TM125G
Im = 3.3 x In
Im = 2.7 x In
t < 10 ms t < 10 ms
E-6
Additional Compact NSX100 to 250 DC
characteristics
TMG magnetic trip units, tripping curves
TM200G TM250G
DB416587.eps
DB416588.eps
TM200G TM250G
Im = 2.6 x In Im = 2.5 x In
t < 10 ms t < 10 ms
E-7
Additional Compact NSX400 to 630 DC
characteristics
TM-DC trip units, tripping curves
DB417747 .eps
TM250D UPS : TM320D UPS :
Im = 625 A ... 1000 A/DC Im = 800 A ... 1600 A/DC
DB417706.eps
E-8
Additional Compact NSX400 to 630 DC
characteristics
TM-DC trip units, tripping curves
TM-DC 600
DB417707.eps
TM600D UPS :
Im = 1500 A ... 3000 A/DC
E-9
Additional Compact NSX630 to 1200 DC
characteristics
TM-DC trip units, tripping curves
DB417709.eps
TM630D UPS : TM800D UPS :
Im = 1600 A ... 3200 A/DC Im = 2000 A ... 4000 A/DC
DB417711.eps
E-10
Additional Current and energy limiting
characteristics
curves
The limiting capacity of a circuit breaker is its aptitude Ics = 100 % Icu
to let through a current, during a short-circuit, that is The exceptional limiting capacity of the Compact NSX DC range greatly reduces the
less than the prospective short-circuit current. forces created by fault currents in devices.
The result is a major increase in breaking performance.
In particular, the service breaking capacity Ics is equal to 100 % of Icu.
The Ics value, defined by IEC standard 60947-2, is guaranteed by tests comprising
(Isc) the following steps:
DB416363.eps
Prospective b break three times consecutively a fault current equal to 100 % of Icu
Isc peak
b check that the device continues to function normally, that is:
v it conducts the rated current without abnormal temperature rise
v protection functions perform within the limits specified by the standard
Prospective v suitability for isolation is not impaired.
current
Longer service life of electrical installations
Limited Isc Current-limiting circuit breakers greatly reduce the negative effects of short-circuits
peak on installations.
Actual
current Thermal effects
Limited Less temperature rise in conductors, therefore longer service life for cables.
Isc
Mechanical effects
(t) Reduced electrodynamic forces, therefore less risk of electrical contacts or busbars
The exceptional limiting capacity of the Compact NSX DC being deformed or broken.
range is due to the rotating double-break technique (very rapid Electromagnetic effects
natural repulsion of contacts and the appearance of two arc Fewer disturbances for measuring devices located near electrical circuits.
voltages in-series with a very steep wave front).
Current and energy limiting curves
The limiting capacity of a circuit breaker is expressed by two curves which are a
function of the prospective short-circuit current (the current which would flow if no
protection devices were installed):
b the actual peak current (limited current)
b thermal stress (A2s), i.e. the energy dissipated by the short-circuit in a conductor
with a resistance of 1 .
Example
What is the real value of a 150 kA rms prospective short-circuit (i.e. 330 kA peak)
limited by an NSX250L DC upstream ?
The answer is 30 kA peak (curve page E-12).
Example
Is a Cu/PVC cable with a CSA of 10 mm adequately protected by an NSX160F?
The table above indicates that the permissible stress is 1.32x106 A2s.
All short-circuit currents at the point where an NSX160F (Icu = 35 kA) is installed are
limited with a thermal stress less than 6x105 A2s (curve page E-12).
Cable protection is therefore ensured up to the limit of the breaking capacity of the
circuit breaker.
E-11
Additional Current and energy limiting
characteristics
curves
Compact NSX DC
DB417921.eps
DB417920.eps
NSX400 DC
DC NSX250 DC
DC NSX160 DC
DC NSX100 DC
NSX400 DC
DC
NSX250 DC DC
NSX100 DC
NSX160 DC
E-12
Additional Current and energy limiting
characteristics
curves
Compact NSX DC
DB418139.eps
NSX1200 DC
NSX1200 DC
NSX630 DC
5000
I peak i2t NSX630 DC
(k) (kAs)
500
DB418140.eps
NSX1200 DC
NSX1200 DC
NSX630 DC 5000
I peak i2t
(k) (kAs)
NSX630 DC
500
E-13
Additional Compact NSX80 to 500 DC PV
characteristics
TMD magnetic trip units, tripping curves
TM80D TM125D
DB416348.eps
DB416349.eps
TM160D TM200D
DB416350.eps
DB416351.eps
E-14
Additional Compact NSX80 to 500 DC PV
characteristics
TMD magnetic trip units, tripping curves
TM250D TM320D/400D
DB415723.eps
DB415724.eps
IEC PV TM250D IEC PV TM320D/400D
Im = 5... 10 x In Im = 5... 10 x In
TM500D
DB415725.eps
IEC PV TM500D
Im = 5... 10 x In
E-15
Additional Masterpact NW10 to NW40 DC
characteristics Tripping curves
U = 500 V DC, L/R = 5 ms
DB104941.eps
E-16
Additional Masterpact NW10 to NW40 DC
characteristics Tripping curves
U = 750/900 V DC, L/R = 5 ms
DB104944.eps
E-17
Additional Masterpact NW10 to NW40 DC
characteristics Tripping curves
U = 500 V DC, L/R = 15 ms
DB104947.eps
E-18
Additional Masterpact NW10 to NW40 DC
characteristics Tripping curves
U = 750/900 V DC, L/R = 15 ms
DB104950.eps
E-19
Additional Masterpact NW10 to NW40 DC
characteristics Tripping curves
U = 500/750 V DC, L/R = 30 ms
DB104953.eps
E-20
Additional Masterpact NW10 to NW40 DC
characteristics Tripping curves
U = 900 V DC, L/R = 30 ms
DB104956.eps
E-21
TOOLS
schneider-electric.com
Presentation 2
Functions and characteristics A-1
Installation recommendations B-1
Dimensions and connection C-1
Electrical diagrams D-1
Additional characteristics E-1
Spare parts:
Compact NSX100 DC to 1200 DC,
NSX400 NA DC to NSX630 NA DC F-13
Compact INS DC PV
Compact NSX80/500 TM DC PV to NSX100/500 NA DC PV
Connection accessories F-15
Electrical auxiliaries F-17
Operation and locking/Interlocking F-19
Installation F-20
F-1
Compact NSX DC - DC PV Catalogue numbers
Compact INS/INV DC - DC PV
Masterpact NW DC - DC PV
andorderform
F-2
Spare parts: Masterpact NW DC - DCPV
Connection F-37
Remote operation F-38
Chassis locking and accessories F-39
Clusters F-40
Circuit breaker locking and accessories F-41
Mechanical interlocking for source changeover F-42
Indication contacts F-43
Instructions F-44
Order form
Compact NSX100DC to NSX250DC circuit breakers F-46
Masterpact NW DC F-51
F-3
Catalogue numbers Compact NSX100 DC to
NSX630DC
Choice of device
F-4
Catalogue numbers Compact NSX100 DC to 1200 DC,
NSX400 NA DC to NSX630 NA DC
Choice of device
Compact NSX100/160/250 DC
Basic frame
3P 4P
DB115910.eps
+ Trip unit
Standard protection: trip unit TM-D/DC
DB404345.eps
Rating 3P 3d 4P 4d
TM16D LV429037 LV429057
TM25D LV429036 LV429056
TM32D LV429035 LV429055
TM40D LV429034 LV429054
TM50D LV429033 LV429053
TM63D LV429032 LV429052
TM80DC LV438029 LV438049
TM100DC LV438028 LV438048
TM125DC LV438136 LV438146
TM160DC LV438135 LV438145
TM200DC LV438246 LV438256
TM250DC LV438245 LV438255
Type G protection: trip unit TM-G
Rating 3P 3d 4P 4d
TM16G LV429155 LV429165
TM25G LV429154 LV429164
TM40G LV429153 LV429163
TM63G LV429152 LV429162
TM80G LV430080 LV430092
TM100G LV430081 LV430093
TM125G LV430082 LV430094
TM160G LV430083 LV430095
TM200G LV430084 LV430096
TM250G LV430085 LV430097
Compact NSX400/630 DC
3P 4P
DB404342.eps
Rating 2P 3P 4P
100 LV429619 LV429629 LV429639
Compact NSX160NA
Rating 2P 3P 4P
160 LV430619 LV430629 LV430639
Compact NSX250NA
Rating 2P 3P 4P
250 LV431619 LV431629 LV431639
Compact NSX400/630 NA DC
3P 4P
Compact NSX400 NA DC LV438153 LV438151
Compact NSX630 NA DC LV438154 LV438152
(1) See catalogue Compact NSX LVPED208001EN for order form and configurated product.
F-5
Catalogue numbers Compact NSX100 DC to 1200 DC,
NSX400 NA DC to NSX630 NA DC
Connection accessories
Special connection accessories for parallel or series connection NSX100- NSX400- NSX1200
250 DC 630 DC DC
Connection accessories
DB104731.eps
plates
Connection plates for parallel connection of 4 poles (3) (3)
4P LV429518
Set of 3 LV429242
Set of 4 LV429243
Aluminium connectors 25 to 95 mm2 ; y 250 A Set of 2 LV429255
Set of 3 LV429227
DB112725.eps
Set of 4 LV429228
120 to 185 mm2 ; y 250 A Set of 2 LV429247
Set of 3 LV429259
Set of 4 LV429260
Clips for connectors Set of 10 LV429241
DB112726.eps
DB112227.eps
Aluminium connectors for 2 cables (4) 2 x (50 to 120 mm) ; y 250 A Set of 3 LV429218
(3P)
Set of 4 LV429219
(4P)
Aluminium connectors 1x (35 to 300 mm) Set of 3 LV432479
(3P)
Set of 4 LV432480
(4P)
DB112228.eps
Aluminium connectors (4) for 6 cables 6 x (1.5 to 35 mm) ; y 250 A Set of 3 LV429248
(3P)
Set of 4 LV429249
(4P)
Aluminium connectors for 2 cables 2 x (35 to 300 mm) Set of 3 LV432481
(3P)
Set of 4 LV432482
(4P)
6.35 mm voltage tap for steel or aluminium connectors Set of 10 LV429348
DB112724.eps
F-6
Catalogue numbers Compact NSX100 DC to 1200 DC,
NSX400 NA DC to NSX630 NA DC
Connection accessories (cont.)
Set of 3 LV429263
Set of 4 LV429264
Set of 4 LV429224
Set of 4 LV429222
4P LV431564
4P LV431061
Front alignment base (for one-piece spreader) 3P/4P LV431064
Set of 4 LV429256
For cable 150 mm2 Set of 3 LV429253
Set of 4 LV429257
For cable 185 mm2 Set of 3 LV429254 LV429254 LV429254
Set of 4 LV429258 LV429258 LV429258
For cable 240 mm 2
Set of 3 LV432500 LV432500
Set of 4 LV432501 LV432501
For cable 300 mm2 Set of 3 LV432502 LV432502
Set of 4 LV432503 LV432503
Crimp lugs for aluminium cable (supplied with 2 or 3 interphase barriers)
For cable 150 mm2 Set of 3 LV429504
DB404351.eps
Set of 4 LV429505
For cable 185 mm2 Set of 3 LV429506 LV429506 LV429506
Set of 4 LV429507 LV429507 LV429507
For cable 240 mm2 Set of 3 LV432504 LV432504
Set of 4 LV432505 LV432505
For cable 300 mm2 Set of 3 LV432506 LV432506
Set of 4 LV432507 LV432507
Barriers
Interphase barriers Set of 6 LV429329 LV432570
DB115920.eps
Insulation screen
2 insulating screens for breaker (45 mm pitch) 3P LV429330
DB112242.eps
4P LV429331
2 insulating screens for breaker (70 mm pitch) 3P LV432578
push
to
trip
4P LV432579
F-7
Catalogue numbers Compact NSX100 DC to 1200 DC,
NSX400 NA DC to NSX630 NA DC
Electrical auxiliaries
Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV 29450
DB404352.eps
Voltage releases MX MN
AC 24 V 50/60 Hz LV429384 LV429404
DB404353.eps
F-8
Catalogue numbers Compact NSX100 DC to 1200 DC,
NSX400 NA DC to NSX630 NA DC
Electrical auxiliaries (cont.)
Communication option
IFE Ethernet interface for LV breaker LV434010
DB417415.eps
24-30 V DC 54440
48-60 V DC 54441
100-125 V AC 54442
110-130 V AC 54443
200-240 V AC 54444
380-415 V AC 54445
(1) SDE adapter mandatory for trip unit TM,TMG.
(2) See Telemecanique catalogue.
F-9
Catalogue numbers Compact NSX100 DC to 1200 DC,
NSX400 NA DC to NSX630 NA DC
Operation and locking/Interlocking
ON
I
With red handle on yellow front LV429339 LV432599
MCC conversion accessory LV429341 LV432606
CNOMO conversion accessory LV429342 LV432602
O
OFF
O
OFF ON
I
With telescopic handle for withdrawable device LV429343 LV432603
OFF
Accessories
Indication auxiliary 1 early-break contact LV429345 LV432605
2 early-break contacts LV429346 LV429346
Locks NSX100-250 DC NSX400-1200 DC
Toggle locking device for 1 to 3 padlocks
By removable device 29370 29370
DB115913.eps
push
to
trip
ON
I
Keylock (keylock adapter not included) Ronis 1351B.500 41940 41940
Profalux KS5 B24 D4Z 42888 42888
O
OFF
2
Keylock (keylock adapter not included) Ronis 1351B.500 41940
/auto
I
1
Profalux KS5 B24 D4Z 42888
manu O push
ON
OFF
push
ON
I
ON
I
O
OFF
O
OFF
F-10
Catalogue numbers Compact NSX100 DC to 1200 DC,
NSX400 NA DC to NSX630 NA DC
Installation
IP30
IP40
IP43 rubber toggle cover
1 toggle cover LV429319 LV432560
DB112738.eps
Lead-sealing accessories
Bag of accessories LV429375 LV429375
DB115615.eps
F-11
Catalogue numbers Compact NSX100 DC to
NSX630DC
Plug-in/withdrawable accessories
4P LV429307 LV432585
Auxiliary connections
1 9-wire fixed connector (for base) LV429273 LV429273
DB117160.eps
Base 2P LV429265
DB117180.eps
3P LV429266 LV432516
F-12
Catalogue numbers: Spare parts:
spare parts
Compact NSX100 DC to 1200 DC,
NSX400 NA DC to NSX630 NA DC
Torque limiting screws (set of 12) 3P/4P Compact NSX100-630 LV429513 LV432513
DB111434.eps
DB111436.eps
F-13
Catalogue numbers Compact INS DC PV
Compact NSX80/500 TM DC PV
to NSX100/500 NA DC PV
.1
.2
.4
PV - 1
(1) For accessories, see catalogue INS/INV page dedicated to INS40 to 160 A.
F-14
Catalogue numbers Compact NSX80/500 TM DC PV
to NSX100/500 NA DC PV
Connection accessories
Terminal shield
1 short terminal shield for breaker or plug-in base 4P LV429516 LV432592
DB416407.eps
Set of 3 LV429242
Set of 4 LV429243
Aluminium connectors 25 to 95 mm2 ; y 250 A Set of 2 LV429255
Set of 3 LV429227
DB112725.eps
Set of 4 LV429228
120 to 185 mm2 ; y 250 A Set of 2 LV429247
Set of 3 LV429259
Set of 4 LV429260
Clips for connectors Set of 10 LV429241
DB112726.eps
DB112227.eps
Aluminium connectors for 2 cables (1) 2 x (50 to 120 mm) ; y 250 A Set of 3 LV429218
(3P)
Set of 4 LV429219
(4P)
Aluminium connectors 1 x (35 to 300 mm) Set of 3 LV432479
(3P)
Set of 4 LV432480
(4P)
DB112228.eps
Aluminium connectors (1) for 6 cables 6 x (1.5 to 35 mm) ; y 250 A Set of 3 LV429248
(3P)
Set of 4 LV429249
(4P)
Aluminium connectors for 2 cables 2 x (35 to 300 mm) Set of 3 LV432481
(3P)
Set of 4 LV432482
(4P)
6.35 mm voltage tap for steel or aluminium connectors Set of 10 LV429348
DB112724.eps
F-15
Catalogue numbers Compact NSX80/500 TM DC PV
to NSX100/500 NA DC PV
Connection accessories (cont.)
Set of 3 LV429263
Set of 4 LV429264
Set of 4 LV429224
Set of 4 LV429222
4P LV431564
Set of 4 LV429256
For cable 150 mm2 Set of 3 LV429253
Set of 4 LV429257
For cable 185 mm2 Set of 3 LV429254
Set of 4 LV429258
For cable 240 mm2 Set of 3 LV432500
Set of 4 LV432501
For cable 300 mm2 Set of 3 LV432502
Set of 4 LV432503
Crimp lugs for aluminium cable (supplied with 2 or 3 interphase barriers)
For cable 150 mm2 Set of 3 LV429504
DB404351.eps
Set of 4 LV429505
For cable 185 mm2 Set of 3 LV429506
Set of 4 LV429507
For cable 240 mm2 Set of 3 LV432504
Set of 4 LV432505
For cable 300 mm 2
Set of 3 LV432506
Set of 4 LV432507
Barriers
Interphase barriers Set of 6 LV429329 LV432570
DB115920.eps
Insulation screen
2 insulating screens for breaker (45 mm pitch) 3P LV429330
DB112242.eps
4P LV429331
2 insulating screens for breaker (70 mm pitch) 3P LV432578
push
to
trip
4P LV432579
Note: circuit breakers or switch-disconnectors must be in "off" position when fitting the mechanical or electrical accessories.
F-16
Catalogue numbers Compact NSX80/500 TM DC PV
to NSX100/500 NA DC PV
Electrical auxiliaries
Electrical auxiliaries
Auxiliary contacts (changeover)
OF or SD or SDE or SDV 29450
DB404352.eps
Voltage releases MX MN
AC 24 V 50/60 Hz LV429384 LV429404
DB404353.eps
F-17
Catalogue numbers Compact NSX80/500 TM DC PV
to NSX100/500 NA DC PV
Electrical auxiliaries (cont.)
24-30 V DC 54440
48-60 V DC 54441
100-125 V AC 54442
110-130 V AC 54443
200-240 V AC 54444
380-415 V AC 54445
(1) NSX80-250 DC PV TM/NA only.
(2) SDE adapter mandatory for trip unit TM,TMG.
F-18
Catalogue numbers Compact NSX80/500 TM DC PV
to NSX100/500 NA DC PV
Operation and locking/Interlocking
ON
I
With red handle on yellow front LV429339 LV432599
MCC conversion accessory LV429341 LV432606
CNOMO conversion accessory LV429342 LV432602
O
OFF
O
OFF ON
I
With telescopic handle for withdrawable device LV429343 LV432603
OFF
Accessories
Indication auxiliary 1 early-break contact LV429345 LV432605
2 early-break contacts LV429346 LV429346
Locks NSX100-250 NSX400-630
DCPV DCPV
Toggle locking device for 1 to 3 padlocks
By removable device 29370 29370
DB115913.eps
push
to
trip
ON
I
Keylock (keylock adapter not included) Ronis 1351B.500 41940 41940
Profalux KS5 B24 D4Z 42888 42888
O
OFF
2
Keylock (keylock adapter not included) Ronis 1351B.500 41940
/auto
I
1
Profalux KS5 B24 D4Z 42888
manu O push
ON
OFF
push
F-19
Catalogue numbers Compact NSX80/500 TM DCPV
to NSX100/500 NA DC PV
Installation
IP30
IP40
IP43 rubber toggle cover
1 toggle cover LV429319 LV432560
DB112738.eps
Lead-sealing accessories
Bag of accessories LV429375 LV429375
DB115615.eps
F-20
Catalogue numbers Compact NSX630b to 1600 NA
DCPV fixed electricallyoperated
Complete device without motor
mechanism module
Complete molded case switch-disconnector (without motor mechanism module)
Molded case switch disconnector Compact NSX630b NA DC PV 630 A 4P LV438969
DB416408.eps
Basic frame
Bottom (33613)
F-21
Catalogue numbers Compact NSX630b to 1600 NA
DCPV fixed electricallyoperated
Device based on separate components
with or without motor mechanism module
Basic frame molded case switch-disconnector
Compact NSX type NA
DB416414.eps
4P
NSX630b NA DC PV LV453421
NSX800 NA DC PV LV453423
NSX1000 NA DC PV LV453425
NSX1250 NA DC PV LV453427
NSX1600 NA DC PV LV453429
I ON
push
OOFF
push
Note: the characteristics of the motor mechanism module for electrical operation are specified
d
discharge
O OFF
separately by selecting a part number from the table at the bottom of this page.
DB415193.eps
4P
Top 630-1000 A - NA 33612
Heatsink mandatory Kit of 2 LV438966
Bottom interphase barriers* Kit of 3 33646
DB416413.eps
Electrical auxiliaries
Indication contacts
6 A - 240 V Low level
DB128428.eps
F-22
Catalogue numbers Compact INS40 to 160 DC
Complete fixed/FC device and
accessories
.1
.2
.4
3P 4P
DB125622.eps
.1
.2
.4
3P 4P
DB125622.eps
F-23
Catalogue numbers Compact INS40 to 160 DC
Accessories
Set of 4 28948
Terminal shrouds
INS40 to 80 3P/4P Set of 2 28955
DB117592.eps
Terminal shields
INS40 to 80 3P/4P Set of 2 28957
DB117593.eps
Interphase barriers
INS100 to 160 3P/4P Set of 6 28959
DB404166.eps
Electrical auxiliaries
Auxiliary contacts
1 CAF / CAO standard (early make or break) INS40 to 160 29450
DB117563.eps
1 CAF / CAO low level (early make or break) INS40 to 160 29452
Rotary handles
Direct front control or lateral control Built-in
Accessories for conversion to extended rotary handles
Front control Black handle INS40 to 160 LV428941
DB414127.eps
F-24
Catalogue numbers Compact INS40 to 160 DC
Accessories
.2
.4
F-25
Catalogue numbers Compact INS250-100 to 630 DC
Complete fixed/FC device and
accessories
3P 4P
DB404169.eps
3P 4P
DB404169.eps
F-26
Catalogue numbers Compact INV100 to 630 DC
Complete fixed/FC device and specific
accessories
3P 4P
DB413546.eps
3P 4P
DB413546.eps
F-27
Catalogue numbers Compact INS250-100 to 250 DC
and Compact INV100 to 250 DC
Accessories
Connection accessories
Rear connections
Short (1 pair) LV429235
DB117567.eps
Cable connectors
Snap-on, for cables: Steel: 1.5 to 95 mm ; y 160 A Set of 3 LV429242
DB112226.eps
Set of 4 LV429243
Set of 4 LV429228
Aluminium: 120 to 185 mm ; y 250 A Set of 3 LV429259
Set of 4 LV429260
Tab connector for voltage tap on 185 mm cable connector Set of 10 LV429348
DB112726.eps DB112724.eps
Distribution connector for six 1.5 to 35 mm cables with interphase barriers Set of 3 LV429248
DB112228.eps
Set of 4 LV429249
Aluminium connectors for 2 cables: 2 x (50 to 120 mm2); y 250 A Set of 3 LV429218
DB112227.eps
Set of 4 LV429219
DB107443.eps
+ 4 x 6 mm + 8 x 7.5 mm)
Set of 4 LV429262
4P LV431564
Set of 4 LV429256
For 150 mm cables Set of 3 LV429253
Set of 4 LV429257
For cable 185 mm cables Set of 3 LV429254
Set of 4 LV429258
Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers)
For 150 mm cables Set of 3 LV429504
DB417620.eps
Set of 4 LV429505
For 185 mm cables Set of 3 LV429506
Set of 4 LV429507
F-28
Catalogue numbers Compact INS250-100 to 250 DC
and Compact INV100 to 250 DC
Accessories
Connection accessories
Terminal shields
1 Short 3/4 P LV429516
DB414360.eps
Interphase barriers
Set of 6 LV429329
DB101942.eps
Electrical auxiliaries
Auxiliary contacts (changeover type)
CAM (early make or break) 29450
DB117563.eps
Rotary handles
Front control
Direct for INS/INV250 Built-in
Extended
For INS/INV250 with standard rotary handle LV431050
DB414127.eps
Lateral control
Direct lateral control for INS/INV250
DB125624.eps
F-29
Catalogue numbers Compact INS250-100 to 250 DC
and Compact INV100 to 250 DC
Accessories
By keylock Keylocking device 2 x 31087
+ Ronis 1351B.500 keylock 41940
or + Profalux KS5 B24 D4Z keylock 42888
F-30
Catalogue numbers Compact INS320 to 630 DC
and Compact INV320 to 630 DC
Accessories
Connection accessories
Rear connections
Short (1 pair) LV432475
DB117567.eps
Cable connectors
For 1 cable, 35 mm to 300 mm Set of 3 LV432479 (1)
DB117587.eps
(1) Kit comprising 2 interphase barriers. (2) Kit comprising 3 interphase barriers.
Set of 4 LV432485
Set of 4 LV432487
4P LV432491
70 mm 3P LV432492
4P LV432493
Crimp lugs for copper cables (supplied with 2 or 3 interphase barriers)
For 240 mm cables Set of 3 LV432500
DB417619.eps
Set of 4 LV432501
For 300 mm cables Set of 3 LV432502
Set of 4 LV432503
Crimp lugs for aluminium cables (supplied with 2 or 3 interphase barriers)
For 240 mm cables Set of 3 LV432504
DB417620.eps
Set of 4 LV432505
For 300 mm cables Set of 3 LV432506
Set of 4 LV432507
Terminal shields
1 Short 3/4P LV432592
DB414359.eps
Interphase barriers
Set of 6 LV432570
DB404182.eps
plate equipped
with heat sink +
1 interphase
barrier
(*) Series connection of: 2 poles = 1 terminal extension Parallel connection of: 2 poles = 2 terminal extensions
3 poles = 2 terminal extensions 4 poles = 4 terminal extensions
DB416824.eps
F-31
Catalogue numbers Compact INS320 to 630 DC
and Compact INV320 to 630 DC
Accessories
Electrical auxiliaries
Auxiliary contacts (changeover type)
1 OF/CAF/CAO (early make or break) 29450
DB117563.eps
Rotary handles
Extended front control
For INS320/400/630 with standard rotary handle 31052
DB404185.eps
5...8
F-32
Catalogue numbers Compact INS630b to 2500 DC
Complete fixed/FC device and
accessories
F-33
Catalogue numbers Compact INV630b to 2500 DC
Complete fixed/FC device and specific
accessories
F-34
Catalogue numbers Compact INS630b to 2500 DC
and Compact INV630b to 2500 DC
Accessories
Connection accessories
Vertical connection adapters
INS/INV630b-1600 3P Set of 3 31301
DB404192.eps
4P Set of 4 31302
4P Set of 4 33645
4P Set of 4 31306
Insulation accessories
Base for terminal shield (not compatible with interphase barriers)
INS/INV630b-1600 3P 31307
DB404195.eps
4P 31308
Terminal shield
INS/INV630b-1600 3P LV433638
DB404196.eps
4P LV433639
Electrical auxiliaries
Auxiliary contacts (changeover type) INS/INV630b-2500
1 OF/CAF/CAO standard (early make or break) 29450
DB117563.eps
F-35
Catalogue numbers Compact INS630b to 2500 DC
and Compact INV630b to 2500 DC
Accessories
F-36
Catalogue numbers: Spare parts:
spare parts
Masterpact NW DC - DCPV
Connection
Connection
C or D type E type
Fixed or drawout circuit breakers or switches
Rear connection (vertical or horizontal mounting) / Replacement kit (3 or 4 parts)
1000/2000 A Vertical or horizontal 47966 47967
DB404366.eps
Top or bottom
Vertical mounting
Connection accessories
Additional support brackets for mounting on a backplate
For fixed rear-connected circuit breaker (2 parts) 47829
DB404369.eps
F-37
Catalogue numbers: Spare parts:
spare parts
Masterpact NW DC - DCPV
Remote operation
Remote operation
Gear motor
MCH (1 part)
DB404410.eps
AC 50/60 Hz 48 V 47889
100/130 V 47893
200/240 V 47894
250/277 V 47895
380/415 V 47896
440/480 V 47897
DC 24/30 V 47888
48/60 V 47889
100/125 V 47890
DB404322.eps
200/250 V 47891
Terminal block (1 part) For fixed circuit breaker 47074
For drawout circuit breaker 47849
DB416231.eps
AC 50/60 Hz 12 V DC 33658
DC 24/30 V DC, 24 V AC 33659
48/60 V DC, 48 V AC 33660
100/130 V AC/DC 33661
200/250 V AC/DC 33662
277 V AC 33663
380/480 V AC 33664
Communicating coil (1 part)
AC 50/60 Hz 12 V DC 33032
DC 24/30 V DC, 24 V AC 33033
48/60 V DC, 48 V AC 33034
100/130 V AC/DC 33035
200/250 V AC/DC 33036
277 V AC 33037
DB404322.eps
380/480 V AC 33038
Terminal block (1 part) For fixed circuit breaker 47074
For drawout circuit breaker 47849
DB416231.eps
R (non-adjustable) Rr (adjustable)
AC 50/60 Hz 48/60 V AC/DC 33680
DC 100/130 V AC/DC 33684 33681
200/250 V AC/DC 33685 33682
380/480 V AC/DC 33683
Installation manual 47951
F-38
Catalogue numbers: Spare parts:
spare parts
Masterpact NW DC - DCPV
Chassis locking and accessories
Chassis locking
Disconnected position locking / 1 part
By padlocks
DB404325.eps
VCPO Standard
By Profalux keylocks
Profalux 1 lock with 1 key + adaptation kit 64934
2 locks 1 key + adaptation kit 64935
2 locks 2 different keys + adaptation kit 64936
1 keylock Profalux identical key not identified combination 33173
(without adaptation kit): identical key identified 215470 combination 33174
identical key identified 215471 combination 33175
By Ronis keylocks
Ronis 1 lock with 1 key + adaptation kit 64937
2 locks 1 key + adaptation kit 64938
2 locks 2 different keys + adaptation kit 64939
1 keylock Ronis identical key not identified combination 33189
(without adaptation kit): identical key identified EL24135 combination 33190
identical key identified EL24153 combination 33191
identical key identified EL24315 combination 33192
Adaptation kit adaptation kit Profalux / Ronis 48564
(without keylock): adaptation kit Kirk 48565
adaptation kit Castell 48566
Installation manual 47952
Door interlock / 1 part
Right and left-hand side of chassis (VPECD or VPECG) 47914
DB404326.eps
4P 48596
4000b/6300 A 3P 48597
4P 48598
4P 48723
4000b/6300 A 3P 48722
4P 48724
Installation manual 47952
Shutter locking block (for replacement) / 1 part
2 parts for 800/4000 A 48591
DB404333.eps
F-39
Catalogue numbers: Spare parts:
spare parts
Masterpact NW DC - DCPV
Clusters
Clusters
1 disconnecting contact cluster for chassis (see table below) (part 1) 64906
DB403280.eps
Racking handle
Racking handle 47944
DB403281.eps
DC rear connection
Serial connection kit
For NW10/20 DC 48642
DB416603.eps
F-40
Catalogue numbers: Spare parts:
spare parts
Masterpact NW DC - DCPV
Circuit breaker locking and accessories
48539
By Profalux keylocks
Profalux 1 lock with 1 key + adaptation kit 64928
2 locks 1 key + adaptation kit 64929
2 locks 2 different keys + adaptation kit 64930
1 keylock Profalux identical key not identified combination 33173
(without adaptation kit): identical key identified 215470 combination 33174
identical key identified 215471 combination 33175
By Ronis keylocks
Ronis 1 lock with 1 key + adaptation kit 64931
2 locks 1 key + adaptation kit 64932
2 locks 2 different keys + adaptation kit 64933
1 keylock Ronis identical key not identified combination 33189
(without adaptation kit): identical key identified EL24135 combination 33190
identical key identified EL24153 combination 33191
identical key identified EL24315 combination 33192
Adaptation kit adaptation kit Profalux / Ronis 64925
(without keylock): adaptation kit Kirk 64927
adaptation kit Castell 64926
Installation manual 47951
Other circuit breaker accessories
Mechanical operation counter / 1 part
Operation counter CDM 48535
DB125617.eps
DB403098.eps
DB403099.eps
Escutcheon Cover
Blanking plate Installation manual 47951
Spring charging handle / 1 part
Spring charging handle 47940
DB404413.eps
F-41
Catalogue numbers: Spare parts:
spare parts
Masterpact NW DC - DCPV
Mechanical interlocking
for source changeover
Cable-type door interlock
1 complete assembly for Masterpact NW fixed or drawout device 48614
Note: the installation manual is enclosed.
F-42
Catalogue numbers: Spare parts:
spare parts
Masterpact NW DC - DCPV
Indication contacts
Indication contacts
ON/OFF indication contacts (OF) / 12 parts
1 additional block of 4 contacts 64922
DB404321.eps
Low-level 47916
Wiring For fixed circuit breaker 47074
For drawout circuit breaker 47849
Combined closed / connected contacts for use with 1 auxiliary contact / 1 part
1 contact (5 A - 240 V) 48477
DB404322.eps
1 pushbutton 48534
F-43
Catalogue numbers: Spare parts:
spare parts
Masterpact NW DC - DCPV
Instructions
Instructions
Chassis accessories 47952
Circuit breaker accessories 47951
Fixed and drawout circuit breaker 47950
User manual NW DC (French) 64923
NW DC (English) 64924
Modbus communication notice for manual 33088
F-44
Catalogue numbers: Spare parts:
spare parts
Masterpact NW DC - DCPV
Monitoring and control converter
F-45
Order form Compact NSX100DC
to NSX250DC circuit breakers
Check the applicable and enter the appropriate Indication and measurements
square boxes information in the rectangles Auxiliary contact OF SD SDE Standard Low level
Circuit breaker Quantity SDE adapter (TM trip unit)
Compact type NSX100/160/250 Remote operation
Electrical operation Motor mechanism AC DC V
Voltage releases Instantaneous MX AC DC V
Rating A
MN AC DC V
Circuit breaker F, N, M, S
Fixed time delay MN AC DC V
Number of poles 1 or 2
Adjust. time delay MN AC DC V
Circuit breaker DC
Rotary handles
Number of poles 3 or 4
Direct Black Red on yellow front
Number of poles tripped 3d or 4d MCC conversion access. CNOMO conversion access.
Fixed device Front conn. Long rear conn. Extended Black Red on yellow front
Short rear conn. Telescopic handle for withdrawable device
Plug-in/withdr. Plug-in Withdrawable Indication auxiliary 1 early-break switch 2 early-break switches
Thermal-magnetic trip unit Wiring accessory for early-make switches
Thermal-magnetic TMD rating (1663 A)
NSX100 to 250 Locking
TMG rating (16250 A)
Toggle (1 to 3 padlocks) Removable Fixed Open/Close
TMDC rating (80250 A)
Fixed Open
Special connection accessories for parallel or Rotary handle Keylock adapter (keylock not included)
series connection
Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
Series 2 poles (1 connection plate)
connection Motor mechanism Keylock adapter + Keylock Ronis (special) NSX100/250
3 poles (2 connection plates)
Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
4 poles (3 connection plates)
Interlocking
Parallel 2 poles (2 connection plates)
Mechanical Toggle Rotary handle
connection 3 poles (NSX100 to 250,
By key (2 Keylocks, 1 key) Keylock adapter (keylock not included)
1 set of 2 connection plates)
For rotary handle Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
2 x 2 poles (4 connection plates)
Installation accessories
Special terminal shields for parallel or series Front-panel escutcheon Toggle
connection Rotary handle, motor mechanism, escutcheon collar; IP40
1P short 1 pair
Toggle cover
2P short 2 x 1 pair (1P)
Sealing accessories
3P short for series connection of poles 1 set
DIN rail adapter NSX100/250
4P short for series connection of poles 1 set
Plug-in / Drawout configuration accessories
4P short for parallel connection 1 set Auxiliary connections 1 automatic connector fixed part with 9 wires (for base)
of poles (2P/4P)
1 auto. conn. moving part with 9 wires (for circuit breaker )
Connection 1 support for 3 automatic connector moving parts
NSX100/250 Steel 1.5v to 95v (< 160 A)
connectors 9-wire manual auxiliary connector (fixed + moving)
Aluminium 25v to 95v (< 250 A)
Plug-in base accessories Long insulated terminals Set of 3 Set of 4
Aluminium 120v to 185v (< 250 A)
2 IP4 shutters for base
Voltage measurement For bare cable NSX100/250
input connector y 185v Chassis accessories Escutcheon collar Toggle
Right-angle terminal extensions Locking kit (keylock not included)
Straight extensions NSX100/250 2 carriage switches (conn./disconnected position indication)
Double L terminal extension 3P 4P Parts of plug-in Plug-in base FC/RC 2P 3P 4P
Spreader from 35 to 45 mm 3P 4P Set of 2 power connections Standard
One piece spreader Safety trip for advanced opening
Front alignment For 3P/4P chassis Moving part
Cu cable lugs NSX100/250 120v 150v 185v Fixed part
240v 300v Communication
NSX Cord L = 0.35 m NSX Cord L = 1.3 m
Al cable lugs NSX100/250 150v 185v
NSX Cord U > 480 V AC L = 0.35 m NSX Cord L = 3 m
240v 300v
BSCM
Insulation screen 45 mm 3P 4P
Communicating motor mechanism 220-240 V
70 mm 3P 4P
Switchboard front display module FDM121
Interphase barriers Set of 6
FDM mounting accessory
Ethernet interface + gateway
Ethernet interface
Modbus interface
I/O application module Qty 1 Qty 2
Stacking accessory
ULP line termination
RJ45 connectors female/female Wire length RJ45 Wire length RJ45
L = 0.3 m L = 0.6 m
Wire length RJ45 Wire length RJ45
L=1m L=2m
Wire length RJ45 Wire length RJ45
L=3m L=5m
F-46
Order form Compact NSX400DC
to NSX630DC
Circuit breakers and switch-disconnectors
Check the applicable and enter the appropriate Indication and measurements
square boxes information in the rectangles Auxiliary contact OF SD SDE Standard Low level
Circuit breaker / Quantity SDE adapter (TM trip unit)
Switch-disconnector Remote operation
Compact type NSX400/630 Electrical operation Motor mechanism AC DC V
switch-disconnector circuit breaker Voltage releases Instantaneous MX AC DC V
Rating A MN AC DC V
Circuit breaker F, S Fixed time delay MN AC DC V
DC Adjust. time delay MN AC DC V
Number of poles 3 or 4 Rotary handles
Fixed device Front conn. Long rear conn. Direct Black Red on yellow front
MCC conversion access. CNOMO conversion access.
Short rear conn.
Extended Black Red on yellow front
Plug-in/withdr. Plug-in Withdrawable
Telescopic handle for withdrawable device
Circuit breaker thermal-magnetic trip unit
Thermal-magnetic TM-DC rating (250600 A) Indication auxiliary 1 early-break switch 2 early-break switches
Wiring accessory for early-make switches
Special connection accessories for parallel or Locking
series connection Toggle (1 to 3 padlocks) Removable Fixed Open/Close
Series 2 poles (1 connection plate) Fixed Open
connection 3 poles (2 connection plates) Rotary handle Keylock adapter (keylock not included)
4 poles (3 connection plates) Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
Parallel 2 poles (2 connection plates) Motor mechanism Keylock adapter (keylock not included) NSX400/630
connection 2 x 2 poles (4 connection plates) Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
Special terminal shields for parallel or series Interlocking
connection Mechanical Toggle Rotary handle
Terminal shield for front connection By key (2 Keylocks, 1 key) Keylock adapter (keylock not included)
Terminal shield for rear connection For rotary handle Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
Standard Short Installation accessories
Connection Front-panel escutcheon Toggle
NSX400/630 1 cable 35v to 300v Rotary handle, motor mechanism, escutcheon collar; IP40
connectors 2 cables 35v to 240v Toggle cover
Voltage measurement input For bare cable connector Sealing accessories
Right-angle terminal extensions Plug-in / Drawout configuration accessories
Edgewise extensions Auxiliary connections 1 automatic connector fixed part with 9 wires (for base)
Double L terminal extension 3P 4P 1 auto. conn. moving part with 9 wires (for circuit breaker )
Spreader from 35 to 45 mm 3P 4P 1 support for 3 automatic connector moving parts
One piece spreader 9-wire manual auxiliary connector (fixed + moving)
Front alignment Plug-in base accessories Long insulated terminals Set of 3 Set of 4
Cu cable lugs NSX400/630 120v 150v 185v 2 IP4 shutters for base
240v 300v Chassis accessories Escutcheon collar Toggle
Al cable lugs NSX400/630 150v 185v Locking kit (keylock not included)
240v 300v 2 carriage switches (conn./disconnected position indication)
Insulation screen 45 mm 3P 4P Parts of plug-in Plug-in base FC/RC 2P 3P 4P
70 mm 3P 4P Set of 2 power connections Standard
Interphase barriers Set of 6 Safety trip for advanced opening
For 3P/4P chassis Moving part
Fixed part
Communication
NSX Cord L = 0.35 m NSX Cord L = 1.3 m
NSX Cord U > 480 V AC L = 0.35 m NSX Cord L = 3 m
BSCM
Communicating motor mechanism 220-240 V
Switchboard front display module FDM121
FDM mounting accessory
Ethernet interface + gateway
Ethernet interface
Modbus interface
I/O application module Qty 1 Qty 2
Stacking accessory
ULP line termination
RJ45 connectors female/female Wire length RJ45 Wire length RJ45
L = 0.3 m L = 0.6 m
Wire length RJ45 Wire length RJ45
L=1m L=2m
Wire length RJ45 Wire length RJ45
L=3m L=5m
F-47
Order form Compact NSX1200DC
circuit breakers
F-48
Order form Compact NSX80/500 TM DC PV
to NSX100/500 NA DC PV
Circuit breakers and
switch-disconnectors
Check the applicable and enter the appropriate Indication auxiliaries
square boxes information in the rectangles Auxiliary contact OF SD SDE Standard Low level
Circuit breaker Quantity SDE adapter (TM trip unit)
Compact type NSX80 TM DC PV Remote operation
NSX125 TM DC PV Electrical operation Motor mechanism AC DC V
NSX160 TM DC PV Voltage releases Instantaneous MX AC DC V
NSX200 TM DC PV MN AC DC V
NSX250 TM DC PV Fixed time delay MN AC DC V
NSX320 TM DC PV Adjust. time delay MN AC DC V
NSX400 TM DC PV Rotary handles
NSX500 TM DC PV Direct Black Red on yellow front
Special connection and insulation accessories MCC conversion access. CNOMO conversion access.
for circuit breakers (mandatory) Extended Black Red on yellow front
Upstream connection plates with heatsink (x2) Telescopic handle for withdrawable device
special terminal shields Indication auxiliary 1 early-break switch 2 early-break switches
Downstream standard long terminal shields Wiring accessory for early-make switches
or rear connections short Locking
long Toggle (1 to 3 padlocks) Removable Fixed Open/Close
+ short terminal shields
Fixed Open
Switch-disconnector Quantity
Rotary handle Keylock adapter (keylock not included)
Compact type NSX100 NA DC PV
Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
NSX160 NA DC PV Motor mechanism Keylock adapter + Keylock Ronis (special) NSX100/250
NSX200 NA DC PV (160 A) Keylock adapter (keylock not included) NSX400/630
NSX200 NA DC PV (200 A) Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
NSX400 NA DC PV
Interlocking
NSX500 NA DC PV Mechanical Toggle Rotary handle
Special connection and insulation accessories By key (2 keylocks, 1 key) Keylock adapter (keylock not included)
for switch-disconnectors (mandatory) For rotary handle Keylock Ronis 1351B.500 Profalux KS5 B24 D4Z
Upstream connection plates with heatsink (x2)
y 200 A at 40 C special terminal shields
Installation accessories
Front-panel escutcheon Toggle
or interphase barriers Rotary handle, motor mechanism, escutcheon collar; IP40
Upstream connection plates with heatsink (x2) Toggle cover
= 200 A at 55 C (long)
Sealing accessories
interphase barriers
DIN rail adapter NSX100/250
Upstream connection plates with heatsink (x2)
u 400 A Communication
special terminal shields
NSX Cord L = 0.35 m NSX Cord L = 1.3 m
or interphase barriers NSX Cord U > 480 V AC L = 0.35 m NSX Cord L = 3 m
Downstream standard long terminal shields BSCM
or rear connections short Communicating motor mechanism 220-240 V
long Switchboard front display module FDM121
+ short terminal shields FDM mounting accessory
or interphase barriers Ethernet interface + gateway
Ethernet interface
Connection
Modbus interface
NSX100/250 Steel 1.5v to 95v (< 160 A)
connectors I/O application module Qty 1 Qty 2
Aluminium 25v to 95v (< 250 A)
Stacking accessory
Aluminium 120v to 185v (< 250 A)
ULP line termination
NSX400/630 1 cable 35v to 300v
connectors RJ45 connectors female/female Wire length RJ45 Wire length RJ45
2 cables 35v to 240v
L = 0.3 m L = 0.6 m
Voltage measurement For bare cable NSX100/250
input connector y 185v Wire length RJ45 Wire length RJ45
L=1m L=2m
For bare cable NSX400/630
connector Wire length RJ45 Wire length RJ45
L=3m L=5m
Right-angle terminal extensions
Straight extensions NSX100/250
Edgewise extensions NSX400/630
Double L terminal extension 3P 4P
Spreader from 35 to 45 mm 3P 4P
Cu cable lugs NSX100/250 120v 150v 185v
NSX400/630 240v 300v
Al cable lugs NSX100/250 150v 185v
NSX400/630 240v 300v
Insulation screen 45 mm 3P 4P
70 mm 3P 4P
Interphase barriers Set of 6
F-49
Order form Compact NSX630/1600 NA
DCPV 4P, fixed version
Upside: front connection, 2 kit heatsink,
phase separator are included
Name of customer: ................................................................... Indication contacts
Adress for delivery: .................................................................. OF - ON/OFF indication contacts (maixmum 3)
Requested delivery date: ......................................................... 6 A-240 V AC qty Low level qty
Customer order no: .................................................................. Remote operation
To indicate your choices, Electrical operation Standard Communicating
Check the and enter the appropriate (NSX 630b/1600 DC PV) Power supply AC DC V
applicable square information in the Voltage releases MX AC DC V
boxes rectangles
MN AC DC V
Switch-disconnector Quantity
Rating A MN delay unit Adjustable Non-adjustable
Communication Locking
COM module Device with Ethernet For electrically VBP - ON/OFF pushbutton locking
(BCM-ULP) interface operated devices (by transparent cover + padlocks)
(NSX630b/1600 DC PV)
with Ethernet OFF position locking:
interface + gateway
VCPO - by padlocks
with Modbus VSPO - by keylocks:
interface
Keylock kit (w/o keylock) Profalux Ronis
Front Display Module (FDM121) Mounting accessory
1 keylock Profalux Ronis
Breaker ULP Cord L = 0.35 m
2 identical keylocks, 1 key Profalux Ronis
L = 1.3 m
Accessories
L=3m
CDM - mechanical operation counter
AD - external power-supply module V
CDP - escutcheon
NSX630b/1600 DC PV connection
CP - transparent cover for escutcheon
Horizontal rear connections Bottom
OP - blanking plate for escutcheon
Vertical rear connections Bottom
Front connections Bottom
4 x 240 + bare cable connectors + shields Bottom
Vertical-connection adapters Bottom
Cable-lug adapters Bottom
Long connection shields (1) Top Bottom
or interphase barriers Bottom
(1) B
ottom long connection shield or Bottom interphase
barriers kit is mandatory.
F-50
Order form Masterpact NW DC
F-51
Notes
F-52
Notes
F-53
Notes
F-54
ART960272 2015 - Schneider Electric - All rights reserved.
LVPED208006EN 06-2015