REF PROTECTION OF Autotransformer PDF
REF PROTECTION OF Autotransformer PDF
REF PROTECTION OF Autotransformer PDF
AbstractRestricted earth fault, or zero-sequence differential 30 percent or 0.3 per unit of the transformer-rated load current
protection, is beneficial in transformer applications. Because it and is necessary to address errors at very low current
does not respond to load current, it offers a significant magnitudes, such as those due to tap changer operations.
improvement in sensitivity over traditional differential protec-
tion. Ground current in the transformer neutral is used as a
Because a CT error resulting from saturation is most likely to
reference and is compared to zero-sequence current at the be a problem at higher current levels, the slope of the
terminals to determine if a fault is internal to the transformer. characteristic provides increased security as currents increase.
The predictability of the neutral current phase angle is critical to The slope characteristic of the primary phase-differential
it being a stable reference. It is not well understood how the element causes relay sensitivity to decrease as load current
magnitude and direction of circulating zero-sequence current in increases. Therefore, at maximum transformer loading, the
a delta tertiary relates to the zero-sequence current in the auto-
transformer neutral. This technical paper derives that relation-
phase-differential element may be unable to detect ground
ship, explains restricted earth fault protection, and uses a real- faults near the neutral until the fault evolves. Because of the
world, unexpected relay operation to demonstrate these concepts primary differential elements response to phase currents and
and make relay settings recommendations. the inherent security measures of the slope characteristic,
restricted earth fault (REF), or zero-sequence differential
I. INTRODUCTION protection, can provide better detection of phase-to-ground
Transformer differential protection is simple in concept and faults near the neutral on wye-connected windings. REF
the primary means for protecting power transformers. A elements are immune to balanced load, so set these elements
transformer differential relay compares current entering the to be more sensitive for this type of fault. Ground current in
transformer to current leaving the transformer. The phasor the transformer neutral is used as a reference and is compared
sum of the currents is the operate (or difference) current. If the to zero-sequence current at the wye-connected winding
currents are not nearly equal, we assume a possible internal terminals to determine if a ground fault is internal to the
fault. transformer-wye windings [1]. Section II describes in detail
the operation of a REF element.
IOP
As with any differential or directional application, the
Unrestrained phase angle measurement stability and the predictability of
Pickup current direction are critical to successful operation. In
Operating autotransformer installations, it is not well understood how the
Region Slope 2 magnitude and direction of circulating zero-sequence current
(Multiples of TAP)
restricted to ground faults within a zone defined by neutral and asserts if any of the winding residual currents used in the REF
line CT placement. function are less than a positive-sequence current restraint
Because it employs a neutral CT at one end of the winding factor (a0) multiplied by the positive-sequence current for their
and the normal set of three CTs at the line end of the winding, respective winding. Such a winding residual current value
REF protection can detect only ground faults within that might occur with false I0 or if zero-sequence current for that
particular wye-connected winding. For REF to function, the winding exceeds 50GP. False I0 can occur in cases of CT
line-end CTs must also be connected in wye, because the saturation during heavy three-phase faults. If the blocking
technique uses zero-sequence current comparisons. Delta- logic asserts, the CTS bit asserts. To prevent 32IE assertion
connected CTs cancel out all zero-sequence components of the when CTS asserts, set the E32I logic equation setting not
currents, eliminating one of the quantities the REF element equal to CTS.
needs for comparison. The lower logic group adjusts the winding residual currents
REF implementations commonly use a directional element to a common sensitivity level with the neutral CT, calculates a
(32I) that compares the direction of an operating current, phasor sum of the appropriate currents, and compares this sum
derived from the line-end CTs, with the polarizing current to the 50GP pickup value. If the sum is greater than the pickup
obtained from the neutral CT. A zero-sequence current level, the 50GC bit asserts. This bit indicates that the winding
threshold and positive-sequence restraint supervise tripping. currents are present in sufficient magnitude.
Apply REF protection to a single wye winding in a trans- Fig. 3 illustrates the logic of the REF directional element
former or to an entire autotransformer winding with as many 32I. At this stage, the element decides whether or not to
as three sets of line-end CT inputs. The line-end, three-phase operate.
winding inputs can additionally be used for normal percent-
Relay
age-restraint differential, overcurrent protection, or metering Word
Bits Relay
purposes. AND 1
Word
Bits
50GC
|IRW1| + 32IOP = 1,12,123 AND 2
AND 2 32IE Pos. _ 1.5 cyc
_C6 OR 1 32IF
Threshold C1 0
a0|I1W1| + +
|I0W1| _C2 IRW1 CTR1
32IOP = 1,12,123
Relay
Word IOP
|IRW2| + 32IOP = 2,12,123,23 Bits IRW2 CTR2
AND 3 OR 1 RE(lop Ipol*)
_C7 CTS
32IOP = 2,12,123,23
a0|I1W2| + _ 1.5 cyc
Zero-Sequence Reactance
Circuit Component Fig. 7. Example System for Case 1 Fault Calculation
(in Per Unit, 100 MVA Base)
ZL 0.1377
Consider the same fault on the same transformer with the
same equivalent system impedance on the HV side. However,
ZM 0.0147
in this case, we use a lower equivalent system impedance on
ZH 0.0870 the autotransformer medium-voltage (MV) side. Using the
Z0MS 0.1653 impedance values in Table II, we can perform the same
calculations to determine the current in the neutral and
Z0HS 0.1034
tertiary.
Note that ZM is less than zero. This negative impedance is TABLE II
a result of the autotransformer mathematical representation as IMPEDANCE VALUES FOR CASE 2 FAULT CALCULATION
an equivalent wye set of impedances. Impedances for Zero-Sequence Reactance
Circuit Component
autotransformers are given typically as a percentage based on (in Per Unit, 100 MVA Base)
two windings connected in delta (e.g., ZML, ZHL, and ZHM). ZL 0.1377
To perform fault calculations, we must first convert these
impedances to an equivalent wye circuit consisting of three ZM 0.0147
impedances, ZL, ZM, and ZH. This conversion often results in ZH 0.0870
negative values for one of the three impedances, ZL, ZM, or Z0MS 0.0109
ZH. This does not imply that the capacitance between two
Z0HS 0.1034
windings is being modeled, but is a result of the autotrans-
former mathematical representation. The fact that one of the K 0 = 0.5544
impedances is negative makes the autotransformer circuit j0.1377 138
interesting, as we will see in the example calculation. I N = 3 (0.5544) (500) 1
Assume there is a single-line-to-ground fault on A-phase j0.1377 + j0.0109 j0.01476 69
with a fault current of 1500 amperes at the point of the fault. = 878 A
Substituting the values for impedances and total zero- j0.0109 j0.0147 138
IT = 3 (0.5544) (500)
sequence current into (1) and (2) yields: j0.1377 + j0.0109 j0.0147 3 13.2
j0.1034 = 142 A
K0 =
j0.1377( j0.1653 j0.0147)
j0.1034 + j0.0870 + Fig. 8 shows the current distribution throughout the
j0.1377 + j0.1653 j0.0147 equivalent zero-sequence network and the autotransformer
= 0.3942 terminals when the MV system impedance was lowered. Note
j0.1377 138 that the zero-sequence currents in the neutral and tertiary have
I N = 3 (0.3942) (500) 1
j0. 1377 + j0.1653 j0. 0147 69 changed direction for a fault at the same location on the
= 26.46 A system. Also, the zero-sequence current on the MV side is
larger (when expressed as per unit) than the current on the HV
j0.1653 j0.0147 138
IT = 3 (0.3942) (500)
side.
j0.1653 + j0.1377 j0.0147 3 13.2
3I0H = 828 A
= 1864 A
H
Fig. 7 shows the current distribution throughout the
0.019 pu 3I0M = 1703 A 3I0F = 1500 A
equivalent zero-sequence network and the autotransformer
M
terminals. Z0MS ZL Z0HS
IT = 142 A
L
0.679 pu 0.660 pu
IN = 875 A
ZM ZH I0 = 1.19 pu
Even though both the neutral and tertiary currents changed IV. REAL-WORLD CASE EXAMPLE
direction, the relationship between their magnitudes is more In March 2006, a REF element on a 100 MVA
complex than applying a simple scaling factor. In Case 2, the autotransformer operated unexpectedly. The customer queried
current in the neutral was almost 6 times larger than the the REF element operation. This section analyzes the
current in the tertiary winding. In Case 1, the current in the unexpected operation and explains why the element operated.
tertiary was 69 times larger than the current in the neutral. The autotransformer includes a tertiary winding connected
When the system impedance was changed, both the neutral in delta. The voltage levels of the autotransformer are
and tertiary currents changed direction for a fault in the same 138/69/13 kV. The MV winding supplies a dual 69 kV bus.
physical location. This scenario creates a problem for either Fig. 10 is a sketch of the autotransformer and REF element
current as a directional element polarizing quantity. Perform configuration.
fault and system studies to determine the effect of realistic
138 kV Bus
system impedance changes on neutral and tertiary current
direction before using either current to polarize a ground
directional element [3] [4] [5]. SLG
In autotransformer REF protection, the operate quantity
Iop is not the residual current in one set of CTs but rather is Polarizing
the summation of the residual currents in the high-side and Current
low-side windings. Which current, neutral or tertiary, is the
correct quantity to use as a polarizing current for REF? REF
Fig. 9 gives a one-line representation of an autotransformer Operate
Element 32IF
13 kV Bus
with a fault on the high side. The operating current and neutral Current
polarizing current should be equal in magnitude and opposite
in phase for an external fault. This is the case for both systems 69 kV Bus
shown in Figs. 7 and 8, despite the fact that the neutral current
direction changed. This is not the case if the tertiary currents
shown in Figs. 7 and 8 are used as the polarizing current.
From the equation for 32I (shown in Fig. 3), we can see that
the cosine of 180 degrees is a negative value. A negative value
for 32I indicates a reverse or out-of-zone fault.
3I0H H Fig. 10. Autotransformer and REF Element Configuration
P
3I0F Fig. 11 is an oscillographic plot of the fault currents in
3I0M
M secondary amperes. This plot shows the fault current distribu-
tion in the autotransformer during what, at first, appeared to be
IRW2
an external double-line-to-ground fault on the 138 kV
IRW1 transmission system. The double-line-to-ground fault assump-
IN L tion was made because of the phase currents observed in
IRW4
Fig. 11.
IAW1 IBW1 ICW1 IAW2 IBW2 ICW2 IAW3 IBW3 ICW3 IAW4
2.5
CTR2
To REF Logic
S = Iop 0.0
CTR1
-2.5
1
CTR4 Ipol
IAW2 IBW2 ICW2
0
REF protection must use the neutral current as the -10
polarizing quantity not the tertiary current. Equations (1) and
1 2 3 4 5 6 7 8 9 10
(2) and the fault calculations summarized in Figs. 7 and 8 Cycles
illustrate that the tertiary current and neutral current are Fig. 11. Autotransformer Fault Current Oscillographic Plot
different, and one cannot be substituted for another as a
polarizing quantity for REF protection.
6
Fig. 12 is an oscillographic plot of the currents and voltages the operation of the REF element was simulated to understand
in primary units of a nearby transmission line terminal that why the element operated.
observed the same fault. A quick observation of Fig. 12 Fig. 14 is a plot of the residual (zero-sequence) currents
indicates that the fault was a B-phase-to-ground fault (BG). present in the autotransformer HV and MV windings during
the fault. The autotransformer MV winding residual current is
IA IB IC IRMag VA VB VC VBMag
1000 simply the sum of the residual current in the two 69 kV
500 breakers.
IA IB IC IRMag
0 1000
-500
-1000
500
Amperes Primary
100
138_IG
VA VB VC VBMag
50 0
0 69_IG
500
-50
-100 1000
3 4 5 6 7 8 9 10 0 1 2 3 4 5 6 7 8 9 10
Cycles
Time (Cycles)
Fig. 12. Oscillographic Plot of Fault Currents and Voltages for a BG Fault at
a Nearby Transmission Line Terminal Fig. 14. Residual Current in Autotransformer HV and MV Windings
Analyzing the sequence currents shown in Fig. 13 for the Fig. 14 shows that the residual current in the HV winding
phase currents from the transformer relay in Fig. 11, we is approximately equal in magnitude but of opposite phase to
observe that the zero-sequence current phase angle leads the that in the MV winding. Fig. 15 is a plot of the sum of the HV
negative-sequence current by 120 degrees on all windings. and MV winding currents or the REF element operate current.
Fault identification and selection (FIDS) logic found in
100
commonly used microprocessor-based distance and directional
relays indicated that the fault was either a BG fault or a CAG
Amperes Primary
50
fault [6]. From this and the large B-phase fault current IRST_REF
observed in Fig. 12, we conclude that this was a 138 kV BG 0
fault.
200 50
0 1 2 3 4 5 6 7 8 9 10
Time (Cycles)
100
Angle (Degrees)
magnitude and of opposite phase angles. The REF element VI. APPENDIX: AUTOTRANSFORMER NEUTRAL AND TERTIARY
would have remained secure for the out-of-zone fault [7]. CURRENT DERIVATION EQUATION
120 A. Typical Datasheet
65
Amperes Primary
IRST_REF 10
IOP_REF 45
(IN)
100
0 1 2 3 4 5 6 7 8 9 10
Time (Cycles)
(a)
Fig. A.1. Typical Autotransformer Transformer Datasheet
120
50GP
From the example transformer datasheet in Figure A.1, the
90
Amperes Primary
We now recall that ZHL was the measured impedance when Vtest = (n 1)2 (ZS + ZC + 3 Z N ) I test (A.10)
a voltage (Vtest) is applied to the H terminals with the L
Vtest
= (n 1) (ZS + Z C + 3 Z N )
2
terminals short-circuited and the M terminals open-circuited, ZHM , act = (A.11)
as shown in Fig. A.4. I test
2
ZHM ,act n 1
(ZS + ZC + 3 Z N )
Itest
ZHM, baseC = = (A.12)
n2 n
Vtest Finally, it should be evident that:
Open 3ZN Z ML , baseC = ZC + Z T (A.13)
Fig. A.4. Test for Measuring ZHL We now have calculated the impedances ZHL,baseC, ZHM,baseC,
and ZML,baseC in equivalent ohms using a voltage base of VC.
It is important to note that ZHM, ZHL, and ZML are expressed
in per unit, whereas our circuit above is expressed in terms of However, a typical nameplate gives these values in terms of
volts and amperes. We will account for this by performing our per unit, not in ohms or equivalent ohms. So we can convert
by simply taking each impedance in equivalent ohms and
calculation in a common base. We will also assume that ZC,
ZS, and ZT are given as equivalent ohms or ohms at the dividing by the Zbase,C, yielding:
common base. This process is very similar to per unit. It ZC ZN
2 + 3
involves selecting a common MVA base just as per unit ZHL , baseC ZT n 1 ZS Z baseC ZbaseC
Z HL = = + +
calculations do; however, we will also select one voltage base ZbaseC ZbaseC n Z baseC n2
(A.14)
and convert all impedances to that voltage base regardless of
2
which transformer winding they are on. In order for our n 1 ZC, pu + 3 ZnH
= ZT , pu + ZS, pu +
common base model to avoid violating the laws of physics, n n2
we have to account for the turns ratio, just as if we had left the 2
quantities in terms of actual ohms. So we can define: Z HM , baseC n 1 ZS + ZC + 3 Z N
Z HM = =
VH VS + VC
Z baseC n Z baseC
n= = (A.15)
2
VM VC n 1
= (
ZS, pu + ZC, pu + 3 Z nH )
So: n
VS ZML, baseC ZC + ZT
= n 1 ZML = =
VC ZbaseC ZbaseC (A.16)
= ZC , pu + ZT , pu
Vtest is then calculated as:
Vtest = n 2 ZT I test + (n 1)2 ZS I test + (ZC + 3 Z N ) I test (A.7) where:
ZN
We can calculate ZHL,act: ZnH =
ZbaseC
Vtest
= n 2 ZT + (n 1) ZS + (ZC + 3 Z N )
2
Z HL,act = (A.8) We can take (A.14), (A.15), and (A.16) and substitute into
I test
(A.4), (A.5), and (A.6) to calculate ZH, ZM, and ZL.
If we choose the MV Winding M (or C) as our voltage base 2
and consider the transformer rating as a common MVA base n 1
ZH =
n 1 n 1
ZS, pu 2 ZC, pu 2 3 ZnH ( )
for all of our quantities, we can then convert ZHL from actual n n n (A.17)
ohms to equivalent ohms or ohms on voltage base M: n 1
= ZH 2 3 ZnH
2 n
ZHL,act n 1 Z + 3 Z
ZHL, baseC = = ZT + ZS + C 2 N (A.9)
n 2
n n n 1
ZM =
n
ZC, pu +
n
(
n 1
)
3 ZnH
Similarly, we can perform the same calculation for ZHL. (A.18)
n 1
= ZM + 3 ZnH
Itest n
0
Open
1 1
(
ZL = ZT, pu + ZC, pu + 3 ZnH
n n
)
Vtest (A.19)
3ZN 1
= ZL + 3 ZnH
n
Itest
Notice that (A.17), (A.18), and (A.19) match the equivalent
Fig. A.5. Test for Measuring ZHM wye network shown in Figure A.3.c.
11
Alternatively, we can write (A.17), (A.18), (A.19) in a Fig. A.6.b, we can use a current divider to calculate the zero-
matrix form: sequence current on the autotransformer high side as follows:
1 Z0 HS
I 0 Hpu = I (A.21)
Z 1 1 1
n ZML Z (Z M + Z0 MS ) 0 HFpu
Z0 HS + Z H + L
L Z L + Z M + Z0 MS
Z = 1 1 1 n 1 ZHL
1 (A.20)
2
M
n ZHM Similarly, we can apply a current divider to obtain the
ZH
n 1
1 1 1 2 6ZnH current in the tertiary winding
n ZM + Z0 MS
I0 Lpu = I0 Hpu
D. Zero-Sequence Network Representation ZL + ZM + Z0 MS
We can then express the tertiary current as: Substituting for P0 from (A.31):
ZM + Z0 MS ZL kV
I0 Lpu = K 0 I0 HFpu
(A.32) I N = 3 K 0 I 0 HF 3 K 0 I0 HF H (A.38)
ZL + ZM + Z0 MS Z
L + Z M + Z 0 MS kVM
This is given in per unit. It may be useful to consider the Finally, we can factor out the common terms and are left
values in actual amperes. If we use the total zero-sequence with:
current in amperes (I0HF) rather than in per unit (I0Hfpu) and ZL kVH
substitute into (A.32) we get: I N = 3 K 0 I0 HF 1
kV
(A.39)
Z + Z + Z
L M 0 MS M
ZM + Z0 MS I
I0 L = K 0 I0 HF base, LOW
(A.33) Thus the current in the neutral and tertiary for the high-side
Z
L + Z M + Z 0 MS I base, HIGH
fault are given in (A.39) and (A.35), respectively.
but For brevity, the current in the neutral and tertiary windings
I base, LOW kVH for the low-side fault are not included; however, the process is
= (A.34) similar. The equations for both cases are summarized in
I base, HIGH kVL
Table A-I.
Now consider that the zero-sequence current in the tertiary Fig. A.8 shows the zero-sequence diagrams for both cases
is trapped inside the delta. The base quantities for per-unit with the current distribution factors included.
calculation are line currents not delta currents. Taking this into
consideration and substituting into (A.33) we arrive at: Neutral Bus
ZM + Z0 MS kVH (S0 R0)I0LF
I0 L = K 0 I0 HF
(A.35) (1 S0)I0LF
Z
L + Z M + Z 0 MS kVL 3
Because the neutral current does not appear on the zero- Z0MS ZL Z0HS
sequence network diagram, we consider Fig. A.7 and apply
Kirchoffs Law to obtain the neutral current from 3I0H and S0I0LF R0I0LF
kVH
I N = 3 K 0 I0 HF 3 P0 I 0 HF (A.37)
kVM
TABLE A-I:
NEUTRAL AND TERTIARY CURRENTS FOR BOTH FAULTS ON THE AUTOTRANSFORMER HIGH SIDE AND LOW SIDE
Fault Location Neutral Current (Amperes) Tertiary Current (Amperes)
ZL kVH Z M + Z0 MS kVH
Autotransformer High Side I N = 3 K 0 I0 HF 1
kV
I0 L = K 0 I0 HF
+ +
Z L Z M Z 0 MS M Z L + Z M + Z0 MS kVL 3
ZL kVM ZH + Z0 HS kVM
Autotransformer Low Side I N = 3 S0 I0 LF 1
I0 L = S0 I0 LF
Z + Z + Z 0 HS kVH
Z + Z + Z kV
L H L H 0 HS L 3
13
VII. ACKNOWLEDGMENTS
The authors gratefully acknowledge the contributions of
Bill Fleming, Armando Guzmn, Hctor Altuve, and Luis
Perez of Schweitzer Engineering Laboratories, Inc. for their
insight during the original event data analysis and
understanding of this topic. Shawn Jacobs of Oklahoma Gas
and Electric is greatly appreciated for sharing the real-world
event data that provided the basis for this technical paper.
VIII. REFERENCES
[1] D. Costello, Lessons Learned From Commissioning and Analyzing
Data From Transformer Differential Relay Installations, presented at
the 33rd Annual Western Protective Relay Conference, Spokane, WA.
[Online] Available: http://www.selinc.com/techpprs.htm.
[2] SEL-387-0, -5,-6 Instruction Manual, Schweitzer Engineering
Laboratories, Inc., Pullman, WA.
[Online] Available: http://www.selinc.com/instruction_manual.htm.
[3] Applied Protective Relaying, Westinghouse Electric Corporation,
[457] p. in various pages: ill.; 29 cm. Newark, N.J.: Westinghouse
Electric Corp., Relay-Instrument Division, 1976. TK 2861 A66 1976.
[4] Symmetrical Components, 1st Edition, C. F. Wagner and R. D. Evans,
1933, McGraw-Hill.
[5] Protective Relaying: Principles and Applications, 2nd Edition, J. Lewis
Blackburn, 1998, Marcel Dekker.
[6] E. O. Schweitzer, III and J. Roberts, Distance Relay Element Design,
presented at the 46th Annual Conference for Protective Relay Engineers,
Brazil. [Online] Available: http://www.selinc.com/techpprs.htm.
[7] C. Labuschagne and N. Fischer, Transformer Fault Analysis Using
Event Oscillography, presented at the 33rd Annual Western Protective
Relay Conference, Spokane, WA.
IX. BIOGRAPHIES
Normann Fischer received a Higher Diploma in Technology, with honors,
from Witwatersrand Technikon, Johannesburg in 1988, a BSc in Electrical
Engineering, with honors, from the University of Cape Town in 1993, and an
MSEE from the University of Idaho in 2005. He joined Eskom as a protection
technician in 1984 and was a senior design engineer in Eskoms Protection
Design Department for three years. He then joined IST Energy as a senior
design engineer in 1996. In 1999, he joined Schweitzer Engineering
Laboratories, Inc. as a power engineer in the Research and Development
Division. He was a registered professional engineer in South Africa and a
member of the South Africa Institute of Electrical Engineers.
Derrick Haas graduated from Texas A&M University in 2002 with a BSEE.
He worked as a distribution engineer at CenterPoint Energy in Houston, Texas
from 2002 to 2006. In April 2006, Derrick joined Schweitzer Engineering
Laboratories, Inc. and works as a field application engineer in Houston,
Texas.
David Costello graduated from Texas A&M University in 1991 with a BSEE.
He worked as a system protection engineer at Central Power and Light and
Central and Southwest Services in Texas and Oklahoma. He has served on the
System Protection Task Force for ERCOT. In 1996, David joined Schweitzer
Engineering Laboratories, Inc. where he has served as a field application
engineer and regional service manager. He presently holds the title of senior
application engineer and works in Boerne, Texas. He is a senior member of
IEEE and a member of the planning committee for the Conference for
Protective Relay Engineers at Texas A&M University.