REF615 Parameter Settings

This document contains settings parameters for three-phase non-directional overcurrent protection functions for low and high settings. It includes parameters such as start values, time multipliers, operate delay times, measurement modes, and curve parameters. Recommended values are provided for many of the parameters.

Uploaded by

balaeee123
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (3 votes)
3K views65 pages

REF615 Parameter Settings

This document contains settings parameters for three-phase non-directional overcurrent protection functions for low and high settings. It includes parameters such as start values, time multipliers, operate delay times, measurement modes, and curve parameters. Recommended values are provided for many of the parameters.

Uploaded by

balaeee123
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 65

PHLPTOC1 /51P-1(1)/3I>(1) : Three Phase Non Directional Over Current Protection , Low Set 1

PHLPTOC1 Group settings

Parameter Values (Range) Unit Step Default Description Recommended


Start value 0.05...0.50 xIn 0.01 0.05 Start value 2.5
Start Value Multiplier 0.8...10.0 0.1 1 Multiplier for scaling the start value 1
Time Multiplier 0.05...15.00 0.05 1 Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 40...200000 ms 10 40 Operate delay time 500


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time Selection of time delay curve type 15=IEC Def. Time
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate Selection of reset curve type 1=Immediate
2=Def time reset
3=Inverse reset
PHLPTOC1 Non group settings

Parameter Values (Range) Unit Step Default Description Recommended


Operation 1=on 1=on Operation Off / On 1=On
5=off
Num of start phases 1=1 out of 3 1=1 out of 3 Number of phases required for operate 1=1 out of 3
2=2 out of 3 activation
3=3 out of 3
Minimum operate time 20...60000 ms 1 20 Minimum operate time for IDMT curves 20
Reset delay time 0...60000 ms 1 20 Reset delay time 20
Measurement mode 1=RMS 2=DFT Selects used measurement mode 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2 Parameter A for customer programmable 28.2
curve
Curve parameter B 0.0000...0.7120 0.1217 Parameter B for customer programmable 0.1217
curve

Curve parameter C 0.02...2.00 2 Parameter C for customer 2


programmable curve
Curve parameter D 0.46...30.00 29.1 Parameter D for customer 29.1
programmable curve
Curve parameter E 0.0...1.0 1 Parameter E for customer programmable 1
curve
PHLPTOC2 /51P-1(2)/3I>(2) : Three Phase Non Directional Over Current Protection , Low Set 2

PHLPTOC2 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.05...0.50 xIn 0.01 0.05
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset

PHLPTOC2 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Num of start phases 1=1 out of 3 1=1 out of 3
2=2 out of 3
3=3 out of 3
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
Measurement mode 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1


er Current Protection , Low Set 2

Description Recommended
Start value 2.5
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 500


Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Description Recommended
Operation Off / On 1=On

Number of phases required for operate 1=1 out of 3


activation

Minimum operate time for IDMT curves 20


Reset delay time 20
Selects used measurement mode 2=DFT
Selects used measurement mode 2=DFT

Parameter A for customer programmable 28.2


curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
PHHPTOC1 /51P-2(1)/3I>>(1) : Three Phase Non Directional Over Current Protection , HIgh Set 1

PHHPTOC1 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.10...40.00 xIn 0.01 0.1
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset

PHHPTOC1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Num of start phases 1=1 out of 3 1=1 out of 3
2=2 out of 3
3=3 out of 3
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1


Curve parameter E 0.0...1.0 1
ver Current Protection , HIgh Set 1

Description Recommended
Start value 2.5
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 500


Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Description Recommended
Operation Off / On 1=On

Number of phases required for operate 1=1 out of 3


activation

Minimum operate time for IDMT curves 20


Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer programmable 28.2


curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
PHHPTOC2 /51P-2(2)/3I>>(2) : Three Phase Non Directional Over Current Protection , HIgh Set 2

PHHPTOC2 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.10...40.00 xIn 0.01 0.1
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset

PHHPTOC2 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Num of start phases 1=1 out of 3 1=1 out of 3
2=2 out of 3
3=3 out of 3
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1


Curve parameter E 0.0...1.0 1
ver Current Protection , HIgh Set 2

Description Recommended
Start value 2.5
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 500


Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Description Recommended
Operation Off / On 1=On

Number of phases required for operate 1=1 out of 3


activation

Minimum operate time for IDMT curves 20


Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer programmable 28.2


curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
PHIPTOC1 /50P(1)/3I>>>(1) : Three Phase Non Directional Over Current Protection ,Instantaneous Set 1

PHIPTOC1 Group settings

Parameter Values (Range) Unit Step Default Description Recommended


Start value 1.00...40.00 xIn 0.01 1 Start value #REF!
Start Value Multiplier 0.8...10.0 0.1 1 Multiplier for scaling the start value 1
Operate delay time 20...200000 ms 10 20 Operate delay time 20

PHIPTOC1 Non group settings

Parameter Values (Range) Unit Step Default Description Recommended


Operation 1=on 1=on Operation Off / On 1=on
5=off
Num of start phases 1=1 out of 3 1=1 out of 3 Number of phases required for operate 1=1 out of 3
2=2 out of 3 activation
3=3 out of 3
Reset delay time 0...60000 ms 1 20 Reset delay time 20
PHIPTOC2 /50P(2)/3I>>>(2) : Three Phase Non Directional Over Current Protection ,Instantaneous Set 2

PHIPTOC2 Group settings

Parameter Values (Range) Unit Step Default


Start value 1.00...40.00 xIn 0.01 1
Start Value Multiplier 0.8...10.0 0.1 1
Operate delay time 20...200000 ms 10 20

PHIPTOC2 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Num of start phases 1=1 out of 3 1=1 out of 3
2=2 out of 3
3=3 out of 3
Reset delay time 0...60000 ms 1 20
er Current Protection ,Instantaneous Set 2

Description Recommended
Start value #REF!
Multiplier for scaling the start value 1
Operate delay time 20

Description Recommended
Operation Off / On 1=on

Number of phases required for operate 1=1 out of 3


activation

Reset delay time 20


DPHLPDOC1 /67-1(1)/3I>-->(1) : Three Phase Directional Over Current Protection , Low Set 1

DPHLPDOC1 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.05...0.50 xIn 0.01 0.05
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset
Voltage Mem time 0...3000 ms 1 40
Directional mode 1=Non-directional 2=Forward
2=Forward
3=Reverse
Characteristic angle -179...180 deg 1 60
Max forward angle 090 deg 1 80

Max reverse angle 090 deg 1 80

Min reverse angle 090 deg 1 80

Min reverse angle 090 deg 1 80

Pol quantity 2=Pos. seq. volt. 5=Cross pol


1=Self pol
Pol quantity 5=Cross pol

4=Neg. seq. volt.


5=Cross pol

DPHLPDOC1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Num of start phases 1=1 out of 3 1=1 out of 3
2=2 out of 3
3=3 out of 3
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Allow Non Dir 0=False 0=False


1=True
Min operate current 0.01...1.00 xIn 0.01 0.01
Min operate voltage 0.01...1.00 xUn 0.01 0.01
Current Protection , Low Set 1

Description Recommended
Start value 2.5
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 500


Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Voltage memory time


Directional Mode

Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward
direction
Minimum phase angle in reverse
direction
Reference quantity used to determine
fault direction
Reference quantity used to determine
fault direction

Description Recommended
Operation Off / On 1=On

Number of phases required for operate 1=1 out of 3


activation

Minimum operate time for IDMT curves 20


Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer programmable 28.2


curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
Allows prot activation as non-dir when dir
info is invalid
Minimum operating current
Minimum operating voltage
DPHLPDOC2 /67-1(2)/3I>-->(2) : Three Phase Directional Over Current Protection , Low Set 2

DPHLPDOC2 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.05...0.50 xIn 0.01 0.05
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset
Voltage Mem time 0...3000 ms 1 40
Directional mode 1=Non-directional 2=Forward
2=Forward
3=Reverse
Characteristic angle -179...180 deg 1 60
Max forward angle 090 deg 1 80

Max reverse angle 090 deg 1 80

Min reverse angle 090 deg 1 80

Min reverse angle 090 deg 1 80

Pol quantity 2=Pos. seq. volt. 5=Cross pol


1=Self pol
Pol quantity 5=Cross pol

4=Neg. seq. volt.


5=Cross pol

DPHLPDOC2 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Num of start phases 1=1 out of 3 1=1 out of 3
2=2 out of 3
3=3 out of 3
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Allow Non Dir 0=False 0=False


1=True
Min operate current 0.01...1.00 xIn 0.01 0.01
Min operate voltage 0.01...1.00 xUn 0.01 0.01
Current Protection , Low Set 2

Description Recommended
Start value 2.5
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 500


Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Voltage memory time


Directional Mode

Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward
direction
Minimum phase angle in reverse
direction
Reference quantity used to determine
fault direction
Reference quantity used to determine
fault direction

Description Recommended
Operation Off / On 1=On

Number of phases required for operate 1=1 out of 3


activation

Minimum operate time for IDMT curves 20


Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer programmable 28.2


curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
Allows prot activation as non-dir when dir
info is invalid
Minimum operating current
Minimum operating voltage
DPHHPDOC1 /67-2/3I>>--> : Three Phase Directional Over Current Protection , High Set

DPHHPDOC1 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.10...40.00 xIn 0.01 0.1
Start Value Multiplier 0.8...10.0 0.1 1
Directional mode 1=Non-directional 2=Forward
2=Forward
3=Reverse
Time Multiplier 0.05...15.00 0.05 1

Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time


3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset
Operate delay time 40...200000 ms 10 40
2=Forward
3=Reverse
Characteristic angle -179...180 deg 1 60
Max forward angle 090 deg 1 80

Max reverse angle 090 deg 1 80

Min reverse angle 090 deg 1 80

Min reverse angle 090 deg 1 80

Voltage Mem time 0...3000 ms 1 40


Pol quantity 2=Pos. seq. volt. 5=Cross pol
1=Self pol
4=Neg. seq. volt.
5=Cross pol

DPHHPDOC1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
Operation 1=on
5=off
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Allow Non Dir 0=False 0=False
1=True
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Min operate current 0.01...1.00 xIn 0.01 0.01
Min operate voltage 0.01...1.00 xUn 0.01 0.01
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Num of start phases 1=1 out of 3 1=1 out of 3


2=2 out of 3
3=3 out of 3
rrent Protection , High Set

Description Recommended
Start value 2.5
Multiplier for scaling the start value 1
Directional Mode

Time multiplier in IEC/ANSI IDMT curves 1

Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Operate delay time 500

Characteristic angle
Maximum phase angle in forward
direction
Maximum phase angle in reverse
direction
Minimum phase angle in forward
direction
Minimum phase angle in reverse
direction
Voltage memory time
Reference quantity used to determine
fault direction

Description Recommended
Operation Off / On 1=On
Operation Off / On 1=On

Minimum operate time for IDMT curves 20


Reset delay time 20
Allows prot activation as non-dir when dir
info is invalid
Selects used measurement mode 2=DFT

Minimum operating current


Minimum operating voltage
Parameter A for customer programmable 28.2
curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
Number of phases required for operate 1=1 out of 3
activation
EFLPTOC1/51N-1(1)/Io>(1):Non-directional earth-fault protection -Low stage 1

EFLPTOC1 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.010...5.000 xIn 0.005 0.01
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset

EFLPTOC1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2
Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Io signal Sel 1=Measured Io 1=Measured Io


2=Calculated Io
n -Low stage 1

Description Recommended
Start value 0.2
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 300


Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Description Recommended
Operation Off / On 1=On

Minimum operate time for IDMT curves 20


Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer programmable 28.2


curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
Selection for used Io signal
EFLPTOC2/51N-1(2)/Io>(2):Non-directional earth-fault protection -Low stage 2

EFLPTOC2 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.010...5.000 xIn 0.005 0.01
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset

EFLPTOC2 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2
Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Io signal Sel 1=Measured Io 1=Measured Io


2=Calculated Io
n -Low stage 2

Description Recommended
Start value 0.2
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 300


Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Description Recommended
Operation Off / On 1=On

Minimum operate time for IDMT curves 20


Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer programmable 28.2


curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
Selection for used Io signal
EFHPTOC1/51N-2(1)/Io>>(1):Non-directional earth-fault protection -High stage 1

EFHPTOC1 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.10...40.00 xIn 0.01 0.1
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset

EFHPTOC1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Io signal Sel 1=Measured Io 1=Measured Io


2=Calculated Io
ction -High stage 1

Description Recommended
Start value 0.2
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 300


Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Description Recommended
Operation Off / On 1=On

Minimum operate time for IDMT curves 20


Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer programmable 28.2


curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
Selection for used Io signal
EFHPTOC2/51N-2(2)/Io>>(2):Non-directional earth-fault protection -High stage 2

EFHPTOC2 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.10...40.00 xIn 0.01 0.1
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
3=ANSI Norm. inv.
5=ANSI Def. Time
9=IEC Norm. inv.
10=IEC Very inv.
12=IEC Ext. inv.
15=IEC Def. Time
17=Programmable
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset

EFHPTOC2 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Io signal Sel 1=Measured Io 1=Measured Io


2=Calculated Io
ction -High stage 2

Description Recommended
Start value 0.2
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT curves 1

Operate delay time 300


Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Description Recommended
Operation Off / On 1=On

Minimum operate time for IDMT curves 20


Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer programmable 28.2


curve
Parameter B for customer programmable 0.1217
curve

Parameter C for customer 2


programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer programmable 1
curve
Selection for used Io signal
EFIPTOC2/50N/Io>>>:Non-directional earth-fault protection Instantaneous stage 1

EFIPTOC1 Group settings

Parameter Values (Range) Unit Step Default


Start value 1.00...40.00 xIn 0.01 0.1
Start Value Multiplier 0.8...10.0 0.1 1
Operate delay time 20...200000 ms 10 20

EFIPTOC1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Reset delay time 0...60000 ms 1 20
Io signal Sel 1=Measured Io 1=Measured Io
2=Calculated Io
stantaneous stage 1

Description Recommended
Start value 0.2
Multiplier for scaling the start value 1
Operate delay time 300

Description Recommended
Operation Off / On 1=On

Reset delay time 20


Selection for used Io signal
DEFLPDEF1 /67N-1(1)/Io>-->(1) : Directional Earth Fault Protection , Low Stage 1

DEFLPDEF1 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.010...5.000 xIn 0.005 0.01
Start Value Multiplier 0.8...10.0 0.1 1
Directional mode 1=Non-directional 2=Forward
2=Forward
3=Reverse
Time Multiplier 0.05...15.00 0.05 1

Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time


2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset
Operate delay time 40...200000 ms 10 40
Operation mode 1=Phase angle 1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
Characteristic angle -179...180 deg 1 -90
Max forward angle 0...180 deg 1 88

Max reverse angle 0...180 deg 1 88

Min reverse angle 0...180 deg 1 88

Min reverse angle 0...180 deg 1 88

Voltage start value 0.010...1.000 xUn 0.001 0.01


Enable voltage limit 0=False 1=True
Enable voltage limit 1=True
1=True

DEFLPDEF1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Reset delay time 0...60000 ms 1 20
Minimum operate time 60...60000 ms 1 60
Allow Non Dir 0=False
1=True
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Min operate current 0.005...1.000 xIn 0.001 0.005
Min operate voltage 0.01...1.00 xUn 0.01 0.01
Correction angle deg 0.0...10.0 deg 0.1 0
Pol reversal 0=False 0=False
1=True
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Io signal Sel 1=Measured Io 1=Measured Io


2=Calculated Io
Pol signal Sel 1=Measured Uo 1=Measured Uo
2=Calculated Uo
3=Neg. seq. volt.
on , Low Stage 1

Description Recommended
Start value 0.2
Multiplier for scaling the start value 1
Directional mode 1=Non-directional

Time multiplier in IEC/ANSI IDMT curves 1

Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Operate delay time 300


Operation criteria 1=Phase angle

Characteristic angle -90


Maximum phase angle in forward 88
direction
Maximum phase angle in reverse 88
direction
Minimum phase angle in forward 88
direction
Minimum phase angle in reverse 88
direction
Voltage start value 0.01
Enable voltage limit 0=False
Enable voltage limit 0=False

Description Recommended
Operation Off / On
1=On

Reset delay time 20


Minimum operate time for IDMT curves 20
Allows prot activation as non-dir when dir
info is invalid 0=False

Selects used measurement mode


2=DFT

Minimum operating current 0.005


Minimum operating voltage 0.01
Angle correction 0
Rotate polarizing quantity 0=False

Parameter A for customer programmable


28.2
curve
Parameter B for customer programmable
curve 0.1217

Parameter C for customer


2
programmable curve
Parameter D for customer
29.1
programmable curve
Parameter E for customer programmable
1
curve
Selection for used Io signal

Selection for used polarization signal


DEFLPDEF2/67N-1(2)/Io>-->(2) : Directional Earth Fault Protection , Low Stage 2

DEFLPDEF2 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.010...5.000 xIn 0.005 0.01
Start Value Multiplier 0.8...10.0 0.1 1
Directional mode 1=Non-directional 2=Forward
2=Forward
3=Reverse
Time Multiplier 0.05...15.00 0.05 1

Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time


2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset
Operate delay time 40...200000 ms 10 40
Operation mode 1=Phase angle 1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
Characteristic angle -179...180 deg 1 -90
Max forward angle 0...180 deg 1 88

Max reverse angle 0...180 deg 1 88

Min reverse angle 0...180 deg 1 88


Min reverse angle 0...180 deg 1 88

Voltage start value 0.010...1.000 xUn 0.001 0.01


Enable voltage limit 0=False 1=True
1=True

DEFLPDEF2 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Reset delay time 0...60000 ms 1 20
Minimum operate time 60...60000 ms 1 60
Allow Non Dir 0=False
1=True
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Min operate current 0.005...1.000 xIn 0.001 0.005
Min operate voltage 0.01...1.00 xUn 0.01 0.01
Correction angle deg 0.0...10.0 deg 0.1 0
Pol reversal 0=False 0=False
1=True
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Io signal Sel 1=Measured Io 1=Measured Io


2=Calculated Io
Pol signal Sel 1=Measured Uo 1=Measured Uo
2=Calculated Uo
3=Neg. seq. volt.
on , Low Stage 2

Description Recommended
Start value 0.2
Multiplier for scaling the start value 1
Directional mode 1=Non-directional

Time multiplier in IEC/ANSI IDMT curves 1

Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Operate delay time 300


Operation criteria 1=Phase angle

Characteristic angle -90


Maximum phase angle in forward 88
direction
Maximum phase angle in reverse 88
direction
Minimum phase angle in forward 88
direction
Minimum phase angle in reverse 88
direction
Voltage start value 0.01
Enable voltage limit 0=False

Description Recommended
Operation Off / On
1=On

Reset delay time 20


Minimum operate time for IDMT curves 20
Allows prot activation as non-dir when dir
info is invalid 0=False

Selects used measurement mode


2=DFT

Minimum operating current 0.005


Minimum operating voltage 0.01
Angle correction 0
Rotate polarizing quantity 0=False

Parameter A for customer programmable


28.2
curve
Parameter B for customer programmable
curve 0.1217

Parameter C for customer


2
programmable curve
Parameter D for customer
29.1
programmable curve
Parameter E for customer programmable
1
curve
Selection for used Io signal

Selection for used polarization signal


DEFHPDEF1 /67N-2/Io>>--> : Directional Earth Fault Protection , High Stage 1

DEFHPDEF1 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.10...40.00 xIn 0.01 0.1
Start Value Multiplier 0.8...10.0 0.1 1
Directional mode 1=Non-directional 2=Forward
2=Forward
3=Reverse
Time Multiplier 0.05...15.00 0.05 1

Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time


3=ANSI Norm. inv.
5=ANSI Def. Time
15=IEC Def. Time
17=Programmable
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset
Operate delay time 40...200000 ms 10 40
Operation mode 1=Phase angle 1=Phase angle
2=IoSin
3=IoCos
4=Phase angle 80
5=Phase angle 88
Characteristic angle -179...180 deg 1 -90
Max forward angle 0...180 deg 1 88

Max reverse angle 0...180 deg 1 88

Min reverse angle 0...180 deg 1 88

Min reverse angle 0...180 deg 1 88

Voltage start value 0.010...1.000 xUn 0.001 0.01


Enable voltage limit 0=False 1=True
1=True

DEFHPDEF1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Reset delay time 0...60000 ms 1 20
Minimum operate time 40...60000 ms 1 40
Allow Non Dir 0=False
1=True
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Min operate current 0.005...1.000 xIn 0.001 0.005
Min operate voltage 0.01...1.00 xUn 0.01 0.01
Correction angle deg 0.0...10.0 deg 0.1 0
Pol reversal 0=False 0=False
1=True
Curve parameter A 0.0086...120.0000 28.2

Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1

Io signal Sel 1=Measured Io 1=Measured Io


2=Calculated Io
Pol signal Sel 1=Measured Uo 1=Measured Uo
2=Calculated Uo
3=Neg. seq. volt.
High Stage 1

Description Recommended
Start value 0.2
Multiplier for scaling the start value 1
Directional mode 1=Non-directional

Time multiplier in IEC/ANSI IDMT curves 1

Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Operate delay time 300


Operation criteria 1=Phase angle

Characteristic angle -90


Maximum phase angle in forward 88
direction
Maximum phase angle in reverse 88
direction
Minimum phase angle in forward 88
direction
Minimum phase angle in reverse 88
direction
Voltage start value 0.01
Enable voltage limit 0=False

Description Recommended
Operation Off / On
1=On

Reset delay time 20


Minimum operate time for IDMT curves 20
Allows prot activation as non-dir when dir
info is invalid 0=False

Selects used measurement mode


2=DFT

Minimum operating current 0.005


Minimum operating voltage 0.01
Angle correction 0
Rotate polarizing quantity 0=False

Parameter A for customer programmable


28.2
curve
Parameter B for customer programmable
0.1217
curve
Parameter C for customer
2
programmable curve
Parameter D for customer
29.1
programmable curve
Parameter E for customer programmable
1
curve
Selection for used Io signal

Selection for used polarization signal


INTRPTEF1 /67NIEF/Io>-->IEF : Transient / Intermittent Earth Fault Protection

INTRPTEF1 Group settings

Parameter Values (Range) Unit Step Default


Directional mode 1=Non-directional 2=Forward
2=Forward
3=Reverse
Operate delay time 401200000 ms 10 500
Voltage start value 0.01...0.50 xUn 0.01 0.01

INTRPTEF1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Operation mode 1=Intermittent EF 1=Intermittent EF
2=Transient EF
Reset delay time 0...60000 ms 1 500
Peak counter limit 2...20 2
ult Protection

Description Recommended
Directional mode, Non-directional / 1=Non-directional
Forward / Reverse

Operate delay time 300


Voltage start value 0.01

Description Recommended
Operation Off / On
1=On

Operation criteria

Reset delay time 5


Min requirement for peak counter 2
before start in IEF mode
NSPTOC1 /46(1)/I2>(1) : Negative-sequence overcurrent protection Stage 1

NSPTOC1 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.01...5.00 xIn 0.01 0.3
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset

NSPTOC1 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2
Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1


ection Stage 1

Description Recommended
Start value 0.3
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT 1
curves
Operate delay time 500
Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Description Recommended
Operation Off / On 1=On

Minimum operate time for IDMT 20


curves
Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer 28.2


programmable curve
Parameter B for customer 0.1217
programmable
curve
Parameter C for customer 2
programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer 1
programmable curve
NSPTOC2/46(2)/I2>(2) : Negative-sequence overcurrent protection Stage 2

NSPTOC2 Group settings

Parameter Values (Range) Unit Step Default


Start value 0.01...5.00 xIn 0.01 0.3
Start Value Multiplier 0.8...10.0 0.1 1
Time Multiplier 0.05...15.00 0.05 1

Operate delay time 40...200000 ms 10 40


Operating curve type 1=ANSI Ext. inv. 15=IEC Def. Time
2=ANSI Very inv.
3=ANSI Norm. inv.
4=ANSI Mod. inv.
5=ANSI Def. Time
6=L.T.E. inv.
7=L.T.V. inv.
8=L.T. inv.
9=IEC Norm. inv.
10=IEC Very inv.
11=IEC inv.
12=IEC Ext. inv.
13=IEC S.T. inv.
14=IEC L.T. inv.
15=IEC Def. Time
17=Programmable
18=RI type
19=RD type
Type of reset curve 1=Immediate 1=Immediate
2=Def time reset
3=Inverse reset

NSPTOC2 Non group settings

Parameter Values (Range) Unit Step Default


Operation 1=on 1=on
5=off
Minimum operate time 20...60000 ms 1 20
Reset delay time 0...60000 ms 1 20
Measurement mode 1=RMS 2=DFT
2=DFT
3=Peak-to-Peak
Curve parameter A 0.0086...120.0000 28.2
Curve parameter B 0.0000...0.7120 0.1217

Curve parameter C 0.02...2.00 2

Curve parameter D 0.46...30.00 29.1

Curve parameter E 0.0...1.0 1


ction Stage 2

Description Recommended
Start value 0.3
Multiplier for scaling the start value 1
Time multiplier in IEC/ANSI IDMT 1
curves
Operate delay time 500
Selection of time delay curve type 15=IEC Def. Time

Selection of reset curve type 1=Immediate

Description Recommended
Operation Off / On 1=On

Minimum operate time for IDMT 20


curves
Reset delay time 20
Selects used measurement mode 2=DFT

Parameter A for customer 28.2


programmable curve
Parameter B for customer 0.1217
programmable
curve
Parameter C for customer 2
programmable curve
Parameter D for customer 29.1
programmable curve
Parameter E for customer 1
programmable curve