Dm-Iaq Standard PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

400

Section Four
Building Vitality

42 pOH=?aCX=aT>p4
401 Chapter 1: Ventilation and Air Quality

401.01 Minimum Ventilation Requirements for Adequate Indoor Air Quality

All new and existing air conditioned buildings must be mechanically or mixed mode
ventilated and must comply with the minimum requirements of ASHRAE Standard
62-2007.
Occupancy density for each space is determined based on its activity in accordance
with the requirements of Dubai Municipality if available or using the default occupancy
density values in ASHRAE 62-2007

401.02 Air Quality during Construction, Renovation or Decoration

For all buildings under construction or renovation, building occupant and systems
must be protected from airborne contaminants which are generated or spread
during construction or renovation inside the buildings. Including toxic substances
or substances harmful to the human body, such as asbestos, lead, pesticides, heavy
metals, mold, dust, fumes, paint, ...etc
Unless it is required to provide ventilation during construction, the supply and return
heating, ventilation, and air conditioning (HVAC) system openings must be closed and
protected from contamination. All duct and other related air distribution component
openings must be covered with tape, plastic, sheet metal or other methods to prevent
dust or debris from collecting in the system.
If the HVAC system is used during construction or renovation, temporary return
air filters must be installed with a Minimum Efficiency Reporting Value (MERV) in
accordance with ASHRAE Standard 52.2-2007 or an equivalent standard.
Immediately prior to occupancy, the temporary return air filters must be removed and
replaced with permanent filters having Minimum Efficiency Reporting Value (MERV) in
accordance with ASHRAE Standard 52.2-2007 or an equivalent standard.

401.03 Air Inlets and Exhausts

For all new and existing buildings:


All ventilation system outdoor air intakes, including doors and operable windows, that
are part of a mixed mode ventilation system, must be located at suitable distance from
potential sources of contamination to reduce the possibility of odor, smoke or other
air contaminants entering the ventilation system as required by Dubai Municipality, if
any, or refer to ASHRAE Standard 62-2007 Table (5.1)
Exhausted air must be discharged in a manner to avoid it being drawn back into the
building or the building ventilation system and to ensure that it does not become a
nuisance to the building occupants or other buildings occupants or pedestrians.

pOH=?aCX=aT> p4 43
401.04 Isolation of Pollutant Sources

For all new and existing buildings, where activities produce hazardous fumes or
chemicals, spaces must be provided with separate air extraction systems to create
negative pressure and exhaust the fumes or chemicals to ensure they do not enter
adjacent rooms.
Dangerous Goods must be stored in accordance with Dubai Municipality
Requirements.

401.05 Openable Windows

For all new buildings, opening windows must be provided in accordance with Dubai
Municipality Building Regulations unless there is safety requirements restricting
opening these windows.

401.06 Indoor Air Quality Compliance - New Buildings


For all new buildings, suitable ventilation for the building occupants and ensure the air
quality in accordance with the technical guidelines issued by Dubai Municipality.
The buildings which optionally apply the following procedures will be awarded indoor
air quality certificate by Dubai municipality.
A. Indoor air quality testing must be carried out prior to occupancy. The maximum
limit for indoor air contaminants included in Table 401.6(1) must not be exceeded.
A report which shows compliance with these requirements must be submitted to
Dubai Municipality.
Table 401.6(1) - Schedule, Duration of Sampling, and Maximum Limit for Contaminants

Sampling Sampling
Type of Samples Maximum Acceptable
Schedule Duration
Pre-Occupancy Formaldehyde < 0.08 parts per million (ppm) 8- hour
continuous
Total Volatile Organic monitoring
< 300 micrograms/m3
Compound (TVOC) (8 hour time-
weighted
Suspended Particulates average
< 150 micrograms/m3
(<10 microns) [TWA])

B. Air Quality testing must be carried out by an air testing company or laboratory
accredited by Dubai Municipality (DM), and the Compliant test results must be
submitted to DM.
C. Air quality testing equipment must have initial and periodical calibration certificate
as per manufacturer requirement from an external calibration facility accredited by
DM or at least annual calibration certificate. The initial and periodical calibration
certificates must be saved in a special register to be checked by DM in order to
ensure the accuracy of the readings as condition of renewal the indoor air quality
certificate.

44 pOH=?aCX=aT>p4
401.07 Indoor Air Quality Compliance - Existing Buildings
For all existing hotels, shopping mall, educational, health and government buildings,
buildings which are used to provide health care, mosques and worship buildings,
theatres, cinemas or any other existing buildings to be determined by DM later, suitable
ventilation for the building occupants and ensure the air quality in accordance with
the technical guidelines issued by Dubai Municipality.
The buildings which optionally apply the following procedures will be awarded indoor
air quality certificate by Dubai municipality.
A.Indoor air testing for the contaminants listed in Table 401.7 (1) must be carried out
to ensure the air quality in a building is suitable for occupation, the maximum limit
for indoor air contaminants included in Table 401.7 (1) must not be exceeded.

Table 102.02 (1)

Sampling Sampling
Type of Samples Maximum Acceptable
Schedule Duration
Initial test 8- hour continuous
Formaldehyde < 0.08 ppm
completed monitoring (8 hour
by 31 time-weighted
December Total Volatile Organic average [TWA])
< 300 micrograms/ m3
2011. Compound (TVOC)
Respirable Dust
Further < 150 micrograms/ m3
(<10 microns)
testing
within 5
years of last Ozone 0.06 ppm (120 micrograms/ m3)
compliant
test.
Carbon Dioxide 800 ppm (1440 microgram/ m3)

Carbon Monoxide 9 ppm (10 micrograms/ m3)

Bacteria 500 CFU/ m (Algar plate)

Fungi 500 CFU/ m (Algar plate)

B. Air Quality testing must be carried out by an air testing company or laboratory
accredited by Dubai Municipality (DM) and the Compliant result must be
submitted to DM.

C. Air quality testing equipment must have initial and periodical calibration certificates
as per manufacturer requirement from an external calibration facility accredited by
DM or at least annual calibration certificate. The initial and periodical calibration
certificates must be saved in a special register to be checked by DM in order to
ensure the accuracy of the readings as condition of renewal the indoor air quality
certificate.

pOH=?aCX=aT> p4 45
401.08 Inspection and Cleaning of HVAC Equipment

For all new and existing buildings, the cleanness of HVAC equipment and
systems must be maintained and all its parts must be inspected and cleaned in
accordance with the standard specifications approved by Dubai Municipality and
in accordance with the technical guidelines issued by Dubai Municipality. While
specialized maintenance companies approved by Dubai Municipality must carry
out Inspection and cleaning or provide a proof that maintenance shall be done
by building operator if he has a qualified personnel and equipment to do the job.

401.09 Parking Ventilation

For all buildings with enclosed parking:


A. Mechanical ventilation must be provided to ensure that the Carbon Monoxide
(CO) concentration in the enclosed parking area is maintained below fifty (50)
parts per million (ppm) by:
- Providing a minimum of six (6) outside air changes per hour, or
- Installing a variable volume ventilation system controlled in response to input
from a minimum of one CO sensor per four hundred square meters (400 m2)
floor area of parking.
B. A supply of outdoor air must be provided to each parking level.
C. Occupied areas such as offices, shopping centres, hotels, waiting rooms,
and ticket booths connected to enclosed parking, must be supplied with
conditioned air under positive pressure compared with adjoining parking area
D. Ventilation systems must be capable of providing ten (10) air changes per hour
for smoke clearance purposes in case of a fire incident.
E. CO monitoring equipment must be installed with a minimum of one CO sensor
per four hundred square meters (400 m2) floor area of parking. Sound alarm
triggers when the CO concentration reaches or exceeds seventy five (75) ppm
in, at least, five percent (5%) of the monitored locations.
F. Where a Building Management System (BMS) or Central Control and Monitoring
System (CCMS) is installed, the CO concentration must be monitored to allow
real-time profiling and management of air quality.
G. CO monitoring equipment must be checked and recalibrated every six (6)
months or according to manufacturer specification by a specialized calibration
company certified by Dubai Municipality. Test results and calibration certificates
must be kept onsite and be readily available for inspection by DM staff.

46 pOH=?aCX=aT>p4
401.08 Environmental Tobacco Smoke

A.Smoking is strictly prohibited in all public in accordance with Local Order No


11 2003 including but not limited to shopping centres, hotels, restaurants,
government buildings, hospitals, healthcare facilities, commercial buildings,
common accommodation, coffee shops and amusement and entertainment or
any other places determined by Dubai Municipality except for places in which
smoking is permitted

B.Places in which smoking is permitted are determined in accordance with the


conditions listed in the Manual of Regulating Smoking in Public Places issued
by Dubai Municipality by administrative resolution no 92 for the year 2009 in
which public places where smoking is strictly prohibited and places where
smoking is permitted are determined according to specific conditions.

C.Smoking designated areas must be at least twenty five (25) feet away from the
building entrances of the building, doors and operable windows and ventilation
system outdoor air intakes

D.An annual permit is issued from the Public Health and Safety Department of
Dubai Municipality for all places in which smoking is permitted after providing
all required documents and drawings mentioned in the guide

402 Chapter 2: Thermal Comfort

402.01 Thermal Comfort

For all new and existing buildings, the heating, ventilation and air conditioning
(HVAC) system must be capable of providing the following range of conditions for
ninety five percent (95%) of the year:

Lower Limit Upper Limit


Dry bulb temperature DB: 22.5 C DB: 25.5 C
Relative humidity RH: 30% (min) RH: 60% (max)

For occupant comfort, normal occupied spaces should have an average air velocity
between (0.2 0.3) m/s.

pOH=?aCX=aT> p4 47
403 Chapter 3: Acoustic Comfort

403.01 Acoustical Control


For all new buildings, the acoustic performance relating to Internal Noise Criteria from
External Noise Sources, Internal Noise Criteria from Mechanical Services Noise, Internal
Airborne Sound Insulation Guidance Values, and Internal Impact Sound Pressure Levels
meet the control requirements set out in Table 403.01 (1).

Table 403.01(1) Acoustical Control requirements

Building Type Document Reference


Villas / Residential*
Buildings Building Regulations Approved Document E (revised 2003) (UK)

Healthcare Facilities Health Technical Memorandum 08-01 (UK)

Educational Facilities** Building Bulletin 93: Acoustic Design of Schools A design


Guide (UK)
BS8233:1999 Sound insulation and noise reduction for buildings
Commercial Buildings
code of practice. (UK)
BS8233:1999 Sound insulation and noise reduction for buildings
Industrial
code of practice. (UK)
BS8233:1999 Sound insulation and noise reduction for buildings
Public
code of practice. (UK)

* Residential buildings include Villas, Apartments, Labour Accommodations and Student


Accommodations.
** Educational Facilities include Nursery Schools, Primary Schools, Secondary Schools,
Colleges and Universities.

404 Chapter 4: Hazardous Materials

404.01 Low Emitting Material: Paints and Coatings


For all buildings, including new applications in existing buildings, all paints and coatings
used in the building should not exceed allowed limits of Volatile Organic Compound
(VOC), these paints and coatings must be accredited/certified from Dubai Central Lab
or any source approved by Dubai Municipality.

48 pOH=?aCX=aT>p4
404.02 Low Emitting Material: Adhesives and Sealants
For all buildings, including new applications in existing buildings, all adhesives,
adhesive bonding primers, adhesive primers, sealants and sealant primers used in
the building should not exceed allowed limits of Volatile Organic Compound (VOC),
these materials must be accredited/certified from Dubai Central Lab or any source
approved by Dubai Municipality.

404.03 Carpet Systems


For all new and existing public and commercial buildings, each new carpet system used
must be certified / accredited from Dubai Central Lab or any other source approved by
Dubai Municipality (DM).
Carpet are not allowed to be used in labor accommodation, educational facilities or
any other places determined by DM.

405 Chapter 5: Day lighting and Visual Comfort

405.01 Provision of Natural Daylight


For all new buildings, other than industrial buildings, provision for adequate natural
daylight must be made in order to reduce their reliance on electrical lighting and
to improve conditions for the building occupants and provide lighting openings in
accordance with Dubai municipality building regulation and specification.

405.02 Views
All new office, residential and public buildings must provide direct line of sight (views)
to the outdoor environment in accordance with Dubai municipality building regulation
and specification.

pOH=?aCX=aT> p4 49
406 Chapter 6: Water Quality

406.01 Legionella Bacteria and Building Water Systems


For all new and existing buildings must apply the technical guidelines issued by Dubai
Municipality which includes:
A. All water systems and networks which creates a water spray or aerosol including
but not limited to cooling towers, evaporative condensers, hot and cold water
systems, showers, evaporative air coolers, spas, fountains, misters, ..etc must
be periodically maintained, cleaned, disinfected and checked periodically to
minimize the risk of Legionella bacteria or germs contamination in accordance
with the technical guidelines issued by Dubai Municipality regarding the control
of Legionella bacteria in water systems.
B. All water systems equipments and accessories including but not limited to
potable water network, hot and cold water systems, water tanks, pumps, pipes
and fittings, must be maintained, cleaned and disinfected.
C. Sampling and testing must be carried out for the presence of bacteria/germs
and Legionella bacteria
D. All equipments and devices of swimming pools, spa pools, whirlpool baths,
hydrotherapy pools and Jacuzzi must be maintained, cleaned, disinfected and
checked periodically.
D. All equipments and devices of irrigation system must be maintained, cleaned,
disinfected and checked periodically
Specialized companies approved by Dubai Municipality must do water tests and sampling.
All test results must be recorded and kept along with the records of maintenance
and remedial works at site to be checked by Dubai Municipality.

406.02 Water Quality of Water Features


For all new and existing buildings, all Water Features with a water storage volume of
over 1,000 liters and which creates a water spray or aerosol including but not limited
to waterfalls, ponds, streams, ...etc must be maintained, cleaned, disinfected and
checked periodically to minimize the risk of Legionella bacteria or germs contamination
and not exceed the maximum limits outlined in the technical guidelines issued by
Dubai Municipality.

50 pOH=?aCX=aT>p4

You might also like