User Manual M-Bus Master / Modbus Slave

Document code: MN67029_ENG Revision 2.053 Page 1 of 33


Industrial Electronic Devices

User Manual
Revision 2.053
English

M-Bus Master / Modbus Slave on RS232 - Converter


(Order Code: HD67029M-232, HD67029M-232-40, HD67029M-232-80,
HD67029M-232-160, HD67029M-232-250)
HD67029M-232
M-Bus Master / Modbus Slave on RS485 - Converter HD67029M-232-xxx
(Order Code: HD67029M-485, HD67029M-485-40, HD67029M-485-80,
HD67029M-485-160, HD67029M-485-250) HD67029M-485

for Website information: HD67029M-485-xxx


www.adfweb.com?Product=HD67029M-232
www.adfweb.com?Product=HD67029M-485 For other M-Bus products see also the following link:
Converter M-Bus to
for Price information: www.adfweb.com?Product=HD67021 (RS232)
www.adfweb.com?Price=HD67029M-232 www.adfweb.com?Product=HD67022 (RS485)
www.adfweb.com?Price=HD67029M-232-40 www.adfweb.com?Product=HD67030 (Ethernet)
www.adfweb.com?Price=HD67029M-232-80 Analyzer & Scanner M-Bus
www.adfweb.com?Price=HD67029M-232-160 www.adfweb.com?Product=HD67031
www.adfweb.com?Price=HD67029M-232-250 Similiar Extender and Repeater, M-Bus
Products www.adfweb.com?Product=HD67032
www.adfweb.com?Price=HD67029M-485 M-Bus Master/ Modbus TCP Slave - Converter
www.adfweb.com?Price=HD67029M-485-40 www.adfweb.com?Product=HD67044M
www.adfweb.com?Price=HD67029M-485-80
M-Bus Master/ PROFIBUS Slave - Converter
www.adfweb.com?Price=HD67029M-485-160 www.adfweb.com?Product=HD67053M
www.adfweb.com?Price=HD67029M-485-250
Concentrator M-Bus
www.adfweb.com?Product=HD67054M
M-Bus Master/ DeviceNet Slave - Converter
Benefits and Main Features: www.adfweb.com?Product=HD67058M
Very easy to configure
M-Bus Slave/ Modbus Master - Converter
Electrical isolation www.adfweb.com?Product=HD67059M-232
Industrial temperature range:
Do you need to choose a device? do you want help?
-40C / 70C (-40F / 158F)
Ask it to the following link: www.adfweb.com?Cmd=helpme

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 2 of 33
Industrial Electronic Devices

INDEX: UPDATED DOCUMENTATION:

Dear customer, we thank you for your attention and we remind you that you
need to check that the following document is:
Page
Updated
INDEX 2 Related to the product you own
UPDATED DOCUMENTATION 2
REVISION LIST 2 To obtain the most recently updated document, note the document code that
WARNING 2 appears at the top right-hand corner of each page of this document.
TRADEMARKS 2
SECURITY ALERT 3 With this Document Code go to web page www.adfweb.com/download/ and
CONNECTION SCHEME 4 search for the corresponding code on the page. Click on the proper Document
CHARACTERISTICS 8 Code and download the updates.
POWER SUPPLY 9
SET COMMUNICATION PARAMETERS 10 To obtain the updated documentation for the product that you own, note the
CONFIGURATION 10 Document Code (Abbreviated written "Doc. Code" on the label on the product)
FUNCTION MODES 10 and download the updated from our web site www.adfweb.com/download/
USE OF COMPOSITOR SW67029 11
NEW PROJECT / OPEN PROJECT 11
SET COMMUNICATION 12 REVISION LIST:
M-BUS 13
UPDATE DEVICE 25 Revision Date Author Chapter Description
CHARACTERISTICS OF THE CABLE 27 2.020 19/07/2010 Fl All Software changed (v1.900)(v1.200)
MECHANICAL DIMENSIONS 28 2.030 22/09/2010 Fl All Software changed (v2.200)(v2.200)
ORDERING INFORMATIONS 30 2.040 05/11/2010 Fl All Software changed (v2.203)
ACCESSORIES 31 2.050 02/12/2010 Fl All Software changed (v2.300)
DISCLAIMER 32 2.051 19/01/2011 Fl All Revision
OTHER REGULATIONS AND STANDARDS 32 2.052 01/02/2012 Fl All Revision
WARRANTIES AND TECHNICAL SUPPORT 33 2.053 04/03/2013 Nt All Added new chapters
RETURN POLICY 33
PRODUCTS AND RELATED DOCUMENTS 33
WARNING:

ADFweb.com reserves the right to change information in this manual about our
product without warning.
ADFweb.com is not responsible for any error this manual may contain.

TRADEMARKS:

All trademarks mentioned in this document belong to their respective owners.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 3 of 33
Industrial Electronic Devices

SECURITY ALERT:

GENERAL INFORMATION
To ensure safe operation, the device must be operated according to the instructions in the manual. When using the device are required for
each individual application, legal and safety regulation. The same applies also when using accessories.

INTENDED USE
Machines and systems must be designed so the faulty conditions do not lead to a dangerous situation for the operator (i.e. independent limit
switches, mechanical interlocks, etc.).

QUALIFIED PERSONNEL
The device can be used only by qualified personnel, strictly in accordance with the specifications.
Qualified personnel are persons who are familiar with the installation, assembly, commissioning and operation of this equipment and who
have appropriate qualifications for their job.

RESIDUAL RISKS
The device is state of the art and is safe. The instrument can represent a potential hazard if they are inappropriately installed and operated
by personnel untrained. These instructions refer to residual risks with the following symbol:

This symbol indicates that non-observance of the safety instructions is danger for people to serious injury or death and / or the
possibility of damage.

CE CONFORMITY
The declaration is made by us. You can send an email to [email protected] or give us a call if you need it.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 4 of 33
Industrial Electronic Devices

CONNECTION SCHEME:

Order Code: HD67029M-232

Figure 1: Connection scheme for HD67029M-232


ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 5 of 33
Industrial Electronic Devices

Order Code: HD67029M-485

Figure 2: Connection scheme for HD67029M-485


ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 6 of 33
Industrial Electronic Devices

Order Code: HD67029M-232-40


Order Code: HD67029M-232-80
Order Code: HD67029M-232-160
Order Code: HD67029M-232-250

Figure 3: Connection scheme for HD67029M-232-xxx

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 7 of 33
Industrial Electronic Devices

Order Code: HD67029M-485-40


Order Code: HD67029M-485-80
Order Code: HD67029M-485-160
Order Code: HD67029M-485-250

Figure 4: Connection scheme for HD67029M-485-xxx


ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 8 of 33
Industrial Electronic Devices

CHARACTERISTICS:

The HD67029M-232-xxx / HD67029M-485-xxx is a M-Bus master to Modbus Slave Converter.

It allows the following characteristics:


Electrical isolation between RS232C/RS485 and M-Bus;
Baud Rate and Parity changeable with software;
Mountable on Rail DIN;
Power Supply 1521V AC or 1835V DC;
Temperature range -40C to 70C.

At the Converter can be connected up to 250 standard M-Bus devices. This number depends of the code expressed by the xxx number:
HD67029M-232 or HD67029M-485 support up to 20 M-Bus devices;
HD67029M-232-40 or HD67029M-485-40 support up to 40 M-Bus devices;
HD67029M-232-80 or HD67029M-485-80 support up to 80 M-Bus devices;
HD67029M-232-160 or HD67029M-485-160 support up to 160 M-Bus devices;
HD67029M-232-250 or HD67029M-485-250 support up to 250 M-Bus devices.

In the case of HD67029M-232-160 and or HD67029M-485-160 the device must be mounted on 35mm DIN rail which is horizontally
mounted on a wall or cabinet back-plate. To avoid obstructions to the airflow around the unit it is recommended to not cover the paths of
air.

In the case of HD67029M-232-250 and or HD67029M-485-250 the device must be mounted on 35mm DIN rail which is horizontally
mounted on a wall or cabinet back-plate. These units have a fan in the top of the enclosure. To avoid obstructions to the airflow around the
unit it is recommended to not cover the paths of air. Take care to not cover the fan. It is recommended to put the device into a ventilated
cabinet.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 9 of 33
Industrial Electronic Devices

POWER SUPPLY:

The devices can be powered at 1521V AC and 1835V DC. The consumption depends to the code of the device. For more details see the
two tables below.

VAC VDC
Vmin Vmax Vmin Vmax
15V 21V 18V 35V

Consumption at 24V DC:

Device No Load [W/VA] Full Load [W/VA]*


HD67029M-232 / HD67029M-485 4
HD67029M-232-40 / HD67029M-485-40 5
HD67029M-232-80 / HD67029M-485-80 3.5 8
HD67029M-232-160 / HD67029M-485-160 14
HD67029M-232-250 / HD67029M-485-250 30
* This value is with all the Slave M-Bus devices of the code (20, 40, 80, 160, 250) connected to the line

Caution: Not reverse the polarity power

HD67029M-232-xxx HD67029M-485-xxx

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 10 of 33
Industrial Electronic Devices

SET COMMUNICATION PARAMETERS:

Configurable Parameters:
Baud Rate of RS232/RS485 from 1200 to 115200 bps and of M-Bus from 300 to 38400 bps;
Parity of RS232/RS485 and M-Bus with None/Odd/Even.

Fixed Parameters:
1 Bit Start;
8 Bit Data;
1 Bit Stop.

The Baud Rate and the Parity of RS232/RS485 and M-Bus are configurable with the software.

CONFIGURATION:

You need Compositor SW67029 software on your PC in order to perform the following:

Define the parameter of Modbus line;


Define the parameter of M-Bus line;
Define which Modbus register contain the M-Bus information;
Update the device.

FUNCTION MODES:

For the device HD67029M-232 and HD6702M-485 it is possible to update the microprocessor program. Therefore there are two functions to
select from the boot jumper:
NORMAL MODE (factory setting, without BOOT jumper): with this setting the HD67029M-232 or HD67029M-485 is able to function as
an adapter M-Bus to Modbus on RS232/RS485;
BOOT MODE (with BOOT jumper): the boot mode is activated when the HD67029M-232 or HD67029M-485 is turned on. Eventual
program updates are available on the site www.adfweb.com

When the RUN Led blinks at frequency of about 1 second, the device functions in Normal Mode, otherwise if the run LED blinks more quickly
the device is in Boot Mode.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 11 of 33
Industrial Electronic Devices

USE OF COMPOSITOR SW67029 or SW67029_40_80_160_250:

To configure the Converter, use the available software that runs


with Windows, called SW67029 or SW67029_40_80_160_250. It
is downloadable on the site www.adfweb.com and its operation is
described in this document. (This manual is referenced to the last
version of the software present on our web site). The software
works with MSWindows (MS 2000, XP, Vista, Seven).

When launching the SW67029 the right window appears (Fig. 5).

Figure 5: Main window for SW67029 and SW67029_40_80_160_250

NEW PROJECT / OPEN PROJECT:

The New Project button creates the folder which contains the entire device configuration.
A device configuration can also be imported or exported:

To clone the configurations of a Programmable M-Bus / Modbus - Converter in order to configure another device in the same manner,
it is necessary to maintain the folder and all its contents;
To clone a project in order to obtain a different version of the project, it is sufficient to duplicate the project folder with another name
and open the new folder with the button Open Project;
When a new project is created or an existent project is open, it will be possible to access the various sections of the software:

Set Communication;
M-Bus;
Update Device.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 12 of 33
Industrial Electronic Devices

SET COMMUNICATION:

This section define the fundamental communication parameters of two buses, Modbus and M-Bus.

By Pressing the Set Communication button from the main window for SW67029 (Fig. 5) the
window Set Communication appears (Fig. 6).
The window is divided in two sections, one for the Modbus line (Serial) and the other for the M-Bus.

The means of the fields for Serial are:


If the device is HD67029M-232, the field RS232 must be checked, otherwise if is the
HD67029M-485 it is possible to check the field RS232 or RS485;
In the field Baudrate the baudrate of the serial line in use is defined;
In the field Parity the parity of the serial line is defined;
In the field ID Dev. the ID for the Modbus side is defined.
In the subsection Protocol it is possible to select the protocol to use in Modbus line from
the following:
Modbus RTU;
Modbus ASCII;
JBUS;
Binary: simple protocol defined by Us, whose functions are described in the document
Simple Protocol downloadable at
www.adfweb.com/download/filefold/Simple_Protocol_ENG.pdf;
ASCII: simple protocol defined by Us, whose functions are described in the document
Simple Protocol downloadable at
www.adfweb.com/download/filefold/Simple_Protocol_ENG.pdf.

The means of the fields for M-Bus are:


In the field Baudrate the baudrate of the M-Bus net is defined;
In the field Parity the parity of the M-Bus line is defined;
If the field M-Bus Poll on request is checked, the Converter makes the request only if a
Modbus register is requested; otherwise if Cyclic request is checked, the Converter
makes the request in M-bus network each time the time defined under passes;
In the field Delay insert a time expressed in seconds. This time is used for the Cyclic
request.

Figure 6: Set Communication window


ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 13 of 33
Industrial Electronic Devices

M-BUS

By Pressing the M-Bus button from the main window for SW67029 (Fig. 5) the window M-Bus Network appears (Fig. 7).

SECTION NODES:
In the section Nodes it is possible to create the nodes of M-Bus
line. In order to create a new node it is necessary to select which
address use, selecting Primary ID or Secondary ID, to makes
the requests and then insert the Primary Address (from 1 to 250)
or the Secondary Address (from 0 to 99999999) of M-Bus device in
the field ID Node M-Bus. In the field Description it is possible
to write a short description of the node.
In the field Node State it is possible to insert an address Modbus
that contain the Status of the M-Bus device. If you dont need to
know this, put this register at 0.
In the field Identification Number it is possible to insert an
address Modbus that contain the Identification Number of the M-Bus
device. You have to read two consecutive registers for knowing the
value. If you dont need to know this, put this register at 0.
If the field Convert BCD in Integer Identification Num. is
checked the Converter converts the Identification Number that is
normally expressed in BCD in a Integer.
In the field Swap Identification Num. it is possible to select the
swap mode of the Identification Number. If swap isnt necessary you
have to select None; otherwise see the section Swap
Identification (page 21) of this document for select the swap mode.
If the field Send SND_NKE is checked, the Converter send the
SND_NKE frame to start the communication.
In the field Send Reset App. Is checked the Converter send the
Application Reset command to the slave. In the field Variables
List it is possible to select which type of variables definition to use.
Figure 7: M-Bus Network window
If is selected By Type it is necessary to fill all fields, in the section
Variables, with the correct values; otherwise if By Position is selected you can insert the progressive number of the variable that you need
(page 15-16 for more information).
After that, pressing the ADD NODE button, a new node appears in the left side of the window. In order to modify a created node it is
necessary to select the desired node, change the wrong items and then press the MODIFY NODE button.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 14 of 33
Industrial Electronic Devices

SECTION VARIABLES (BY TYPE):

Selecting the desired node it is possible to add a variable. In order


to create a new variable it is necessary to fill these items:

To use the created variable the field Enable Variable


must be checked. If you have created a variable but for the
moment it is unused it is possible to uncheck the field
Enable Variable without delete it;
In the field Description it is possible to write a
description of the variable (it isnt a necessary information,
it helps the readability of the tree of network);
The field Type of Data is used to select the unit of
measure;
In the field VIF ASCII String insert the string of VIF. It
is possible to use this field only if the Type of Data is VIF
is in ASCII;
In the field Function Field it is necessary to select the
type of data;
The field Dimension is used to select the dimension of
the variable (8, 16, 24, 32, 32 real, 48, 64 bit, Variable
Length);
In the field Length(Variable Len) insert the length of
the data in the case of the dimension is Variable Length;
In the field Unit if it is necessary it is possible to select
the unit of that variable. The Unit is used for indicates from
which device the data come;
In the field Modbus Register it is necessary to insert the
value of Modbus Register that contains the data of the M-Bus device. It is possible to insert from Modbus Register 1 to 60000;
In the field Modbus Re Scale it is necessary to insert the value of Modbus Register that contains the value of measure scale. If the
scale is not necessary, you have to insert the number 0 in this field. It is possible to insert from Modbus Register 1 to 60000;
In the field Storage Number if it is necessary it is possible to insert the value of storage counter of that variable. With this field
the slave can indicate and transmit various stored counter states or historical values, in the order in which they occur;
In the field Tariff if it is necessary it is possible to insert the value of the tariff of that variable. The Tariff is used for indicates from
which device the data come;
In the field VIFE it is possible to select a sub-type of Type of Data;

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 15 of 33
Industrial Electronic Devices

If the field Use Five Modbus Register and the Type of Data is Time Point it is possible to read the information of Year, Month,
Day, Hour, Minutes on five consecutive Modbus registers without decoding the data (if not selected the values are the same of the
reply of the slave device, so coded with a determinate structure). You have to insert the first Modbus Register.
If the field From BCD to Integer is checked the Converter converts the BCD value of variable in Integer format. This happens only
if the variable is in BCD format; if it isnt nothing changes.
If the field Convert in Float is checked the Converter converts the data into Float type. Every variable occupies two consecutive
Modbus Registers and the first one is the one defined in Modbus Register. In this case the float value is multiplied by the Modbus
Re Scale automatically.

Having completed this fields, to add the variable the button ADD VARIABLE must be pressed.

In order to modify a created variable it is necessary to select the desired variable, change the wrong items and then press the MODIFY
VARIABLE button.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 16 of 33
Industrial Electronic Devices

SECTION VARIABLES (BY POSITION):

Selecting the desired node it is possible to add a variable. In order


to create a new variable it is necessary to fill these items:
To use the created variable the field Enable Variable
must be checked. If you have created a variable but for the
moment it is unused it is possible to uncheck the field
Enable Variable without delete it;
In the field Description it is possible to write a
description of the variable (it isnt a necessary information,
it helps the readability of the tree of network);
The field Dimension is used to select the dimension of
the variable (8, 16, 24, 32, 32 real, 48, 64 bit, Variable
Length);
In the field Length(Variable Len) insert the length of
the data in the case of the dimension is Variable Length;
In the field Modbus Register it is necessary to insert the
value of Modbus Register that contains the data of the M-
Bus device. It is possible to insert from Modbus Register
1 to 60000;
In the field Modbus Re Scale it is necessary to insert the
value of Modbus Register that contains the value of
measure scale. If the scale is not necessary, you have to
insert the number 0 in this field. It is possible to insert
from Modbus Register 1 to 60000;
If the field Use Five Modbus Register and the Type of Data is Time Point it is possible to read the information of Year, Month,
Day, Hour, Minutes on five consecutive Modbus registers without decoding the data (if not selected the values are the same of the
reply of the slave device, so coded with a determinate structure (page 22 for more information)). You have to insert the first Modbus
Register.
If the field From BCD to Integer is checked the Converter converts the BCD value of variable in Integer format. This happens only
if the variable is in BCD format; if it isnt nothing changes;
If the field SWAP is checked the byte of data of that variable are swapped. Example: from 0x01020304 to 0x04030201;
In the field Position insert the number of the variable that you want on Modbus.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 17 of 33
Industrial Electronic Devices

Example:

0x68 - Start Byte


0xBD - L Fied
0xBD - L Field
0x68 - Start Byte
0x08 - C Field
0x02 - A Field
0x72 - CI Field
Identification Number (or Secondary Address) put in the
0x71 - Identification Number (Byte 4of4)
0x65 - Identification Number (Byte 3of4) selected register if Identification Number is checked
0x45 - Identification Number (Byte 2of4)
0x28 - Identification Number (Byte 1of4)
0x4D - Manufacturer (Byte 2of2)
0x6A - Manufacturer (Byte 1of2)
0x81 - Version
Fixed Data Header
0x04 - Medium
0x3E - Access Number
0x27 - Status
0x00 - Signature (Byte 2of2) Status of the meter put in the selected register if Node
0x00 - Signature (Byte 1of2) State is checked
0x04 - DIF
0x79 - VIF Identification
0x00 - Data (Byte 4of4)
0x00 - Data (Byte 3of4)
First Variable ( 1 )
0x00 - Data (Byte 2of4)
0x00 - Data (Byte 1of4)

0x04 - DIF
0x06 - VIF Energy
0x00 - Data (Byte 4of4)
0x00 - Data (Byte 3of4)
Second Variable ( 2 ) To be use in the Position field
0x00 - Data (Byte 2of4)
0x00 - Data (Byte 1of4)

0x44 - DIF
0x06 - VIF Energy
0x00 - Data (Byte 4Of4)
0x00 - Data (Byte 3Of4)
Third Variable ( 3 )
0x00 - Data (Byte 2Of4)
0x00 - Data (Byte 1Of4)

Other Variables

0x55 - Check Sum


0x16 - Stop Byte

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 18 of 33
Industrial Electronic Devices

SECTION DELETE ITEMS:

If it is necessary to delete a node or a variable, you have to select


the node or the variable and then press the DELETE ITEM
button.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 19 of 33
Industrial Electronic Devices

Possible choices for the fields used to create a variable:

Type of Data: Function Field:


|_Energy (Wh) |_Instantaneous Value
|_Energy (J) |_Minimum Value
|_Volume (m3) |_Maximum Value
|_Mass (Kg) |_Value During Error State
|_On Time
|_Operating Time
|_Power (W) Dimension (bit):
|_Power (J/h) |_8
|_Volume Flow (m3/h) |_16
|_Volume Flow Ext. (m3/min) |_24
|_Volume Flow Ext. (m3/s) |_32
|_Mass Flow (Kg/h) |_32 real
|_Flow Temperature (C) |_48
|_Return Temperature (C) |_64
|_Temperature Difference (K) |_Variable Length
|_External Temperature (C)
|_Pressure (bar)
|_Averaging Duration
|_Actuality Duration
|_Type of data in VIFE
|_Time Point
|_VIF is in ASCII
|_Unit for H.C.A.
|_Fabrication No
|_(Enhaced) Identification
|_Bus Address

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 20 of 33
Industrial Electronic Devices

VIFE:
|_ Not Selected |_ Period of tariff months(s)
|_ Credit of the nominal local legal currency units |_ Period of tariff year(s)
|_ Debit of the nominal local legal currency units |_ dimensionless/ no VIF
|_ Access Number (transmission count) |_ Volts
|_ Medium (as in fixed header) |_ Ampere
|_ Manufacturer (as in fixed header) |_ Reset counter
|_ Parameter set identification |_ Comulation counter
|_ Model/Version |_ Control signal
|_ Hardware Version # |_ Day of week
|_ Firmware Version # |_ Week number
|_ Software Version # |_ Time point of day change
|_ Customer Location |_ State of parameter activation
|_ Customer |_ Special supplier information
|_ Access Code User |_ Duration since last comulation [hour(s)..year(s)]
|_ Access Code Operator |_ Operation time battery [hour(s)..year(s)]
|_ Access Code System Operator |_ Date and time of battery change
|_ Access Code Developer |_ Energy MWh
|_ Password |_ Energy GJ
|_ Error flags (binary) |_ Volume
|_ Error mask |_ Mass
|_ Digital Output (binary) |_ Volume 0,1 feet^3
|_ Digital Input (binary) |_ Volume 0,1 american gallon
|_ Baudrate [Baud] |_ Volume 1 american gallon
|_ response delay time [bittimes] |_ Volume flow 0,001 american gallon/min
|_ Retry |_ Volume flow 1 american gallon/min
|_ First storage # for cyclic storage |_ Volume flow 1 american gallon/h
|_ Last storage # for cyclic storage |_ Power MW
|_ Size of storage block |_ Power GJ/h
|_ Storage interval [sec(s)..day(s)] |_ Flow Temperature
|_ Storage interval month(s) |_ Return Temperature
|_ Storage interval year(s) |_ Temperature Difference
|_ Duration since last readout[sec(s)..day(s)] |_ External Temperature
|_ Start (date/time) of tariff |_ Cold/Warm Temperature Limit F
|_ Duration of tariff (nn=01..11:min to day) |_ Cold/Worm Temperature Limit C
|_ Period of tariff [sec(s) to day(s)] |_ Cumul. count max power

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 21 of 33
Industrial Electronic Devices

|_ per second |_ Duration of limit exceed


|_ per minute |_ Duration of first/last
|_ per hour |_ Date(/time) of first/last begin/end
|_ per day |_ Multiplicative currection factor
|_ per week |_ Additive correction constant * unit of VIF (offset)
|_ per month |_ Moltiplicative correction factor: 10^3
|_ per year |_ future value
|_ per revolution/measurement |_ next VIFE's and data of this block are manufacturer specific
|_ increment per input pulse on input channel |_ None
|_ increment per output pulse on output channel |_ Too many DIFE's
|_ per liter |_ Storage number not implemented
|_ per m^3 |_ Unit number not implemented
|_ per kg |_ Tariff number not implemented
|_ per K (Kelvin) |_ Function not implemented
|_ per kWh |_ Data class not implemented
|_ per GJ |_ Data size not implemented
|_ per kW |_ Too many VIFE's
|_ per (K*l)(Kelvin*liter) |_ Illegal VIF-Group
|_ per V (Volt) |_ Illegal VIF-Exponent
|_ per A (Ampere) |_ VIF/DIF mismatch
|_ multiplied by sek |_ Unimplemented action
|_ multiplied by sek/V |_ No data available (undefined value)
|_ multiplied by sek/A |_ Data overflow
|_ start date(/time) of |_ Data underflow
|_ VIF contains uncorrected unit instead of corrected unit |_ Data error
|_ Accumulation only if positive contributions |_ Premature end of record
|_ Accumulation of abs value only if negative contributions
|_ upper/lower limit value
|_ # of exceeds of lower/upper limit
|_ Date(/time) of begin/end of first/last lower/upper limit exceed

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 22 of 33
Industrial Electronic Devices

Swap Identification:

This field is used for select the Swap mode of Identification Number.

At the moment there are these possibilities:


None;
Type 1.

Examples:

- Identification Number (Secondary Address): 12345678; Address Register 1000; Convert BCD in Integer Identification Num. not checked.

None Type 1
1000: 0x1234 1000: 0x5678
1001: 0x5678 1001: 0x1234

- Identification Number (Secondary Address): 12345678; Address Register 1000; Convert BCD in Integer Identification Num. checked.

None Type 1
1000: 0x00BC 1000: 0x614E
1001: 0x614E 1001: 0x00BC

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 23 of 33
Industrial Electronic Devices

To know the meaning of value read in the Modbus Re Scale field, you must follow this table (x = Value read in Modbus Re Scale):

Description Range Coding Range


Energy 10 (x 3) Wh 0.001 Wh to 10000 Wh
Energy 10 (x) J 0.001 kJ to 10000 kJ
(x 6)
Volume 10 m3 0.001 l to 10000 l
(x 3)
Mass 10 kg 0.001 kg to 10000 kg
x=0 Seconds
x=1 Minutes
On Time
x=2 Hours
x=3 Days
Operating Time coded like On Time
Power 10 (x 3) W 0.001 W to 10000 W
Power 10 (x) J/h 0.001 kJ/h to 10000 kJ/h
Volume Flow 10 (x 6) m3/h 0.001 l/h to 10000 l/h
(x 7) 3
Volume Flow Ext. 10 m /min 0.0001 l/min to 1000 l/min
(x 9)
Volume Flow Ext. 10 m3/s 0.001 ml/s to 10000 ml/s
(x 3)
Mass Flow 10 kg/h 0.001 kg/h to 10000 kg/h
Flow Temperature 10 (x 3) C 0.001 C to 1 C
(x 3)
Return Temperature 10 C 0.001 C to 1 C
Temperature Difference 10 (x 3) K 1 mK to 1000 mK
(x 3)
External Temperature 10 C 0.001 C to 1 C
Pressure 10 (x 3) bar 1 mbar to 1000 mbar
Averaging Duration coded like On Time
Actuality Duration coded like On Time
x=0 Date Data type G
Time Point
x=1 Time&Date Data type F
Unit for H.C.A. dimensionless

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 24 of 33
Industrial Electronic Devices

Data type F:
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
15 14 13 12 11 0 9 8
2 2 2 2 2 21 2 2
23 22 21 0 19 18 17 16
2 2 2 22 2 2 2 2
31 30 29 28 27 26 25 24
2 2 2 2 2 2 2 2

Min (0 59);
Hour (0 23);
Day (1 31);
Month (1 12);
Year (0 99);
Time Invalid (0=Valid, 1=Invalid);
Summer Time (0=Standard Time, 1=Summer Time);
Reserved (0).

Data type G:
7 6 5 4 3 2 1 0
2 2 2 2 2 2 2 2
15 14 13 12 11 0 9 8
2 2 2 2 2 21 2 2

Day (1 31);
Month (1 12);
Year (0 99).

For example, if you have defined:


Type of Data= Energy (J);
Function Field=Instantaneous Value;
Dimension= 32 bit;
Modbus Register=150 (Register 151 declared implicitly because the dimension is 32 bit);
Modbus Re Scale=152.
After the request, in Modbus register 150 you read 0x0004, in 151 you read 0x5678 and in register 152 is write 0x0006. The value obtained
is: 284280 x10(6) J.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 25 of 33
Industrial Electronic Devices

UPDATE DEVICE:

By pressing the Update Device button it is possible to load the created Configuration into the
device; and also the Firmware, if is necessary.

In order to load the parameters or update the firmware in the Converter, follow these
instructions:
Turn off the Device;
Connect the Null Modem Cable form your PC to the Converter;
Insert the Boot Jumper (For more info see Fig. 1,2,3,4);
Select the COM port and press the Connect button;
Turn on the device;
Check the BOOT Led. It must blink quickly (For more info see Fig. 1,2,3,4);
Press the Next button;
Select which operations you want to do. You can select only
Firmware, only Project or both of them;
Press the Execute update firmware button to start the upload;
When all the operations are OK turn off the device;
Disconnect the Boot jumper;
Disconnect the RS232 Cable;
Turn on the device.

At this point the configuration/firmware on the device is correctly update.

Figure 8: Update Device windows


ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 26 of 33
Industrial Electronic Devices

Note:
When you install a new version of the software it is better if the first time you do the update of the Firmware in the HD67029M-232-
xxx or HD67029M-485-xxx device.

Warning:
If the Fig. 9 appears when you try to do the Update before require assistance try these points:
Check if the serial COM port selected is the correct one;
Check if the serial is connected between the PC and the device;
Try to repeat the operations for the updating;
If you are using a dongle try with a native COM port or change the dongle;
Try with another PC;
Try to restart the PC;
If you are using the program inside a Virtual Machine, try to use in the main
Operating System.

Figure 9: Protection window

In the case of HD67029M-232 you have to use the software SW67029: www.adfweb.com/download/filefold/SW67029.zip.

In the case of HD67029M-232-40, HD67029M-232-80, HD67029M-232-160, HD67029M-232-250 you have to use the software
SW67029 40 80 160 250: www.adfweb.com/download/filefold/SW67029_40_80_160_250.zip.

In the case of HD67029M-485 you have to use the software SW67029: www.adfweb.com/download/filefold/SW67029.zip.

In the case of HD67029M-485-40, HD67029M-485-80, HD67029M-485-160, HD67029M-485-250 you have to use the software
SW67029 40 80 160 250: www.adfweb.com/download/filefold/SW67029_40_80_160_250.zip.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 27 of 33
Industrial Electronic Devices

CHARACTERISTICS OF THE CABLE:

RS232:

The connection from RS232 socket to a serial port (example one from a personal computer) must be made with a NULL MODEM cable (a
serial cable where the pins 2 and 3 are crossed).
It is recommended that the RS232C Cable not exceed 15 meters.

Figure 10: Null modem cabling

M-BUS:

A two wire standard telephone cable (JYStY N*2*0.8 mm) is used as the transmission medium for the M-Bus. The maximum distance
between a slave and the repeater is 350m; this length corresponds to a cable resistance of up 29. This distance applies for the standard
configuration having Baud rates between 300 and 9600 Baud, and a maximum of 250 slaves. The maximum distance can be increased by
limiting the Baud rate and using fewer slaves, but the bus voltage in the space state must at no point in a segment fall below 12V, because
of the remote powering of the slaves. In the standard configuration the total cable length should not exceed 1000m, in order to meet the
requirement of a maximum cable capacitance of 180nF. (Taken from M-Bus specifics)

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 28 of 33
Industrial Electronic Devices

MECHANICAL DIMENSIONS:

Figure 11: Mechanical dimensions scheme for HD67029M-232 Figure 12: Mechanical dimensions scheme for HD67029M-232-40,
HD67029M-485-80

Figure 13: Mechanical dimensions scheme for HD67029M-485 Figure 14: Mechanical dimensions scheme for HD67029M-485-40,
HD67029M-485-80
ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31
User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 29 of 33
Industrial Electronic Devices

Figure 15: Mechanical dimensions scheme for HD67029M-232-160 Figure 16: Mechanical dimensions scheme for HD67029M-232-250

Figure 17: Mechanical dimensions scheme for HD67029M-485-160 Figure 18: Mechanical dimensions scheme for HD67029M-485-250

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 30 of 33
Industrial Electronic Devices

ORDERING INFORMATIONS:

The ordering part number is formed by a valid combination of the following:

HD67029M xxx yyy

Maximum number of slaves supported


20: up to 40 standard slaves (1.5mA consumption) connected to M-Bus
40: up to 40 standard slaves (1.5mA consumption) connected to M-Bus
80: up to 80 standard slaves (1.5mA consumption) connected to M-Bus
160: up to 160 standard slaves (1.5mA consumption) connected to M-Bus
250: up to 250 standard slaves (1.5mA consumption) connected to M-Bus

Modbus Communication Port


232: Modbus over RS232
485: Modbus over RS485 and RS232

Enclosure / Connectors Type


M: Modulbox 4M DIN Rail mounting / Fixed Screw Terminal

Device Family
HD67029: M-Bus Master / Modbus Slave - Converter

Order Code: HD67029M-232-20 - M-Bus Master / Modbus Slave (RS232) - Converter (up to 20 slaves connected to M-Bus)
Order Code: HD67029M-232-40 - M-Bus Master / Modbus Slave (RS232) - Converter (up to 40 slaves connected to M-Bus)
Order Code: HD67029M-232-80 - M-Bus Master / Modbus Slave (RS232) - Converter (up to 80 slaves connected to M-Bus)
Order Code: HD67029M-232-160 - M-Bus Master / Modbus Slave (RS232) - Converter (up to 160 slaves connected to M-Bus)
Order Code: HD67029M-232-250 - M-Bus Master / Modbus Slave (RS232) - Converter (up to 250 slaves connected to M-Bus)
Order Code: HD67029M-485-20 - M-Bus Master / Modbus Slave (RS485) - Converter (up to 20 slaves connected to M-Bus)
Order Code: HD67029M-485-40 - M-Bus Master / Modbus Slave (RS485) - Converter (up to 40 slaves connected to M-Bus)
Order Code: HD67029M-485-80 - M-Bus Master / Modbus Slave (RS485) - Converter (up to 80 slaves connected to M-Bus)
Order Code: HD67029M-485-160 - M-Bus Master / Modbus Slave (RS485) - Converter (up to 160 slaves connected to M-Bus)
Order Code: HD67029M-485-250 - M-Bus Master / Modbus Slave (RS485) - Converter (up to 250 slaves connected to M-Bus)

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 31 of 33
Industrial Electronic Devices

ACCESSORIES:

Order Code: APW040 - Power Supply for M-Bus Master device that supports up to 40 Slaves
Order Code: APW080 - Power Supply for M-Bus Master device that supports up to 80 Slaves
Order Code: APW160 - Power Supply for M-Bus Master device that supports up to 160 Slaves
Order Code: APW250 - Power Supply for M-Bus Master device that supports up to 250 Slaves
Order Code: AC34107 - Null Modem Cable Fem/Fem DSub 9 Pin 1,5 m
Order Code: AC34114 - Null Modem Cable Fem/Fem DSub 9 Pin 5 m

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 32 of 33
Industrial Electronic Devices

DISCLAIMER

All technical content within this document can be modified without notice. The content of the document content is a recurring audit.
For losses due to fire, earthquake, third party access or other accidents, or intentional or accidental abuse, misuse, or use under abnormal
conditions repairs are charged to the user. ADFweb.com S.r.l. will not be liable for accidental loss of use or inability to use this product, such
as loss of business income. ADFweb.com S.r.l. shall not be liable for consequences of improper use.

OTHER REGULATIONS AND STANDARDS

WEEE INFORMATION
Disposal of old electrical and electronic equipment (as in the European Union and other European countries with separate
collection systems).
This symbol on the product or on its packaging indicates that this product may not be treated as household rubbish. Instead, it
should be taken to an applicable collection point for the recycling of electrical and electronic equipment. If the product is disposed
correctly, you will help prevent potential negative environmental factors and human health, which could otherwise be caused by
inappropriate disposal. The recycling of materials will help to conserve natural resources. For more information about recycling this
product, please contact your local city office, your household waste disposal service or the shop where you purchased the product.

RESTRICTION OF HAZARDOUS SUBSTANCES DIRECTIVE


The device respects the 2002/95/EC Directive on the restriction of the use of certain hazardous substances in electrical
and electronic equipment (commonly referred to as Restriction of Hazardous Substances Directive or RoHS).

CE MARKING
The product conforms with the essential requirements of the applicable EC directives.

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31


User Manual M-Bus Master / Modbus Slave
Document code: MN67029_ENG Revision 2.053 Page 33 of 33
Industrial Electronic Devices

WARRANTIES AND TECHNICAL SUPPORT:

For fast and easy technical support for your ADFweb.com SRL products, consult our internet support at www.adfweb.com.
Otherwise contact us at the address [email protected]

RETURN POLICY:

If while using your product you have any problem and you wish to exchange or repair it, please do the following:
1) Obtain a Product Return Number (PRN) from our internet support at www.adfweb.com. Together with the request, you need to provide detailed information
about the problem.
2) Send the product to the address provided with the PRN, having prepaid the shipping costs (shipment costs billed to us will not be accepted).

If the product is within the warranty of twelve months, it will be repaired or exchanged and returned within three weeks. If the product is no longer under warranty,
you will receive a repair estimate.

PRODUCTS AND RELATED DOCUMENTS:

Part Description URL


HD67120 Converter Ethernet to RS232/RS485 www.adfweb.com?product=HD67120
HD67119 Converter USB 2.0 to RS485 Isolated www.adfweb.com?product=HD67119
HD67507 Gateway Modbus TCP Server to RTU Master www.adfweb.com?product=HD67507
HD67510 Gateway Modbus TCP Client to RTU Slave www.adfweb.com?product=HD67510

ADFweb.com Srl IT31010 Mareno Treviso INFO: www.adfweb.com Phone +39.0438.30.91.31

You might also like