Hardware Manual - Rel 2 - 20
Hardware Manual - Rel 2 - 20
Hardware Manual - Rel 2 - 20
Hardware Manual
Quality Assurance
ESA elettronicas quality control system has been certified by the CSQ,
EQNet and ITQS (certification N 9115.ESAE) as complying with UNI EN
ISO 9001:2000 standards.
These represent the most comprehensive set of standards within the interna-
tional framework of ISO and cover every aspect of the life-cycle of the
product (planning, development, production, installation and customer
care).
All the products described in this manual comply with the following
standards:
Council Directives
89/336/EEC 92/31/EEC 93/68/EEC
Products bearing the mark cULus have been certified in compliance with
UL 508 and CSA C22.2 N14-M95 safety standards.
RINA Approval
Registro Navale Italiano
No. ELE/797/1
DNV certification
Det Norske Veritas
Certificate No. A-9044
Do not use the VT as a warning device for critical alarms that can cause
operator injury, production stoppage or machine damage. Every critical
alarm indicator or control, must be designed using appropriate stand
alone hardware devices.
Installation Strictly follow the wiring diagram and grounding recommendations con-
and wiring tained in this document, in order to prevent any damaged to the VT or to
the connected devices.
Do not use any voltage beyond the VTs specified range in order to pre-
vent damage or electrical shock.
Make sure power to the unit is off before opening the VT for the calibra-
tion procedure described in this document.
Do not modify the VT for any reason. Doing this may result in electrical
shock or fire, in addition to loss of Certifications like CE or UL.
Use the proper torque shown on the label to tighten the terminal screws.
Excess tightening may cause short circuit, fire or device malfunction.
Usage Do not strike the touch panel with a hard or pointed object, or press on
the touch screen with excessive force. The actuating force is 50 grams
(1.8 oz.).
Do not allow liquids to enter the VT case. This can cause malfunction or
electrical shock.
Do not use the VT where strong jolting or excessive vibration can occur.
Do not use the VT where abrasive chemicals can evaporate or are present
in the air.
Use only allowed chemical substances to clean the VT (see Users Man-
ual chapter on cleaning).
Ensure that no metal debris falls into the VT. This can cause fire, mal-
function or incorrect device operation.
After turning the VT OFF, please wait at least 5 seconds before turning it
ON again, otherwise it may not start up correctly.
Be sure to perform regular back-ups of the VTs data to avoid loss due to
unexpected accidents to your system.
Contents
Foreword
The hardware installation manual is valid for all types of Video Terminal.
The manual The installation manual contains information on securing and connecting
both VTs and optional accessories, on the functions offered by the termi-
nals as well as on the cables connecting them to a device.
Its purpose The manual contains all the notions, concepts and examples necessary to be
able to install quickly and easily.
Conventions Below are listed the symbols and styles found in the manual together with
their respective meanings:
Introduction
What is a A VIDEO TERMINAL (VT) is a device that allows the user to control or
Video simply monitor a productive process. It can send commands using con-
Terminal figured by the user; it can send data determining the process on hand and
can display information deriving from the productive process. The informa-
tion can be in the form of an Alarm, an Information (Info-) Message or in
binary data format.
The VTs can be divided into two groups: those with a keyboard and those
without but equipped with a Touch Screen.
All VTs can be supplemented with accessories to boost and broaden their
performance.
For the VT to function a project must be created and loaded into it. See
Software Manual.
For detailed information on individual VTs see the relevant chapters below.
Essential information
The component that generally creates this impression is the display. The
displays used on the VTs are of two distinct types, one with a passive
matrix called STN (Super Twist Nematic) and the other with an active
matrix called TFT (Thin Film Transistor). Some of their working features
are the same, others depend on the different constructional technology.
One component that requires particular care when being used is the Touch
Screen.
Below we set out a series of points relating to possible behaviors and the
correct use of the VT.
Failure to put some of these notions into practice may damage the
VT.
Graphic The category graphic terminals covers both touch screen and keyboard ter-
terminals minals and includes both those with STN display and those with TFT dis-
play.
With CCFL backlit displays the brightness may be slightly uneven, the
areas where the CCFL lamps are may be lighter.
CCFL lamps
CCFL lamps
All displays posses a certain viewing angle within which the images can
be seen properly. If the viewer is outside the specified angle the images
may be seen with their colors inverted or with different tones from the
original ones, or it may be that no colors are seen, etc. The viewing
angle can be slightly adjusted by regulating the contrast on the display.
9 oclock 3 oclock
g d
12 oclock
a
Viewer
b
6 oclock
The figure above shows the direction of the angles in relation to the
viewing point. The table gives the value of the viewing angles depend-
ing on the type of display.
Direction (Hour)
Type of display
12 - a 6-b 9-g 3-d
STN 30 degrees 60 degrees 60 degrees 60 degrees
TFT 80 degrees 80 degrees 70 degrees 70 degrees
This feature means a difference in viewing (albeit with the same contrast
and temperature levels) when:
Two identical displays may have slightly different brightness levels and
color tones.
E-3
Streaking
Graphic In some cases the display may have some pixels that are white (always
terminals - ON) or black (always OFF). This phenomenon may be visible or invisi-
TFT ble to the user on account of the color showing on the display. This phe-
nomenon is considered normal.
White pixels
Black pixels
Graphic The touch screen is activated by applying pressure equal to 200g which
terminals may be done using a pen or a finger.
Touch Screen
The touch screen also has a peripheral area that should never be sub-
jected to stress above all using pointed objects (pens, etc.). On account
of how the glass is put together this area is very sensitive to pressure and
is fragile.
Useable area
Peripheral area
2mm
2mm
The peripheral area is about 2mm on each side and is outside the touch
sensitive area.
Contents Page
Shielding of It is essential to use suitably shielded cables for communication signal con-
cables nections (total shielding is recommended). The shielding must be con-
nected to the zero potential.
Earthing of With many devices the "0V" is connected to the earth. The signal ground
shielding and must be earthed but it is best to separate the ground of the shields and cir-
electronic cuits from that of the power circuits. Note that the earth can only perform
circuits its function if the "Resistance of the earth circuit" is within the max. limits
prescribed.
Switching of The current peaks which occur when capacitive loads are switched on can
capacitive damage or destroy control devices. Furthermore, the high-frequency com-
loads ponent of the current peak can cause serious disturbance in electronic cir-
cuits as a result of inductive coupling between the connection cables.
Switching off When an inductive load is switched off, the magnetic energy stored tends to
inductive oppose this, discharging a voltage peak down the line which can damage or
loads destroy the control device. Furthermore, the high-frequency component of
the voltage peak can cause disturbance caused by capacitive coupling
between the connection cables.
The physical structure and characteristics of an inductive load make it
impossible to carry out switching without disturbance unless suitable mea-
sures are taken. The disturbance can be at least partially suppressed by fit-
ting a suitable disturbance-suppression module in parallel with the
inductive load. The disturbance-suppression module must not constitute an
additional load during the work phase. Electrical disturbance is propagated
both through the connection cables and electromagnetic transmission. If the
disturbance is propagated by cable or electromagnetic transmission, it is
much more difficult to suppress at the inputs to the units in the danger zone
than it is to suppress the disturbance at its source. If the disturbance is cre-
Disturbance In the following tables there are the specifications of the disturbance sup-
suppression pression filter ciruits.
circuit - RC
and DIODE Table 1.1: Disturbance suppression circuit RC
The residual component has a very low The best results are obtained by sizing
harmonic wave form component. the R/C suitably.
C R
Optimal suppression is obtained as a
Switch-off time delay very low. direct consequence of a significant
de-energizing delay.
S
C
The presence of the capacitor causes a
The effectiveness of the disturbance
Ub L high load current peak when switching
R suppression is not affected by the volt-
on (and can cause pasting of the con-
age value. No switch-on delay.
tact if undersized).
Suitable for both AC and DC; no prob- The RC circuit constitutes an additional
lem with reversed polarity. load when used with AC.
Ub L D
Contents Page
Wiring 2-2
Connection
pins Table 2.1: 4 pin Power Supply Connector
3 Not connected
- +
N.C. 24VDC
4 Earth protection
Wiring The power supply connector will take conductors with a cross-section of
between 0.05 and 2.5mm (30-12AWG) for rigid conductors or from 0.05
to 1.5mm (30-12AWG) in the case of flexible conductors. The length of
the stripped wire must be between 6 and 7.5mm (0.24-0.30in). The recom-
mended screw grip pressure is 0.79Nm (7 lb in).
Connections The connections illustrated below must not be made as they may cause the
to be avoided VT to be damaged.
L1 L1
N N
PE PE
~ ~
- + - +
24V 24V
Recommended We recommend a wiring scheme as set out below in the interests of avoid-
connection ing damaging the VT.
Table 2.3: Power supply with 0Vdc connected to PE
L1
N
PE
- + PLC
24V
PE
+24V
0V
VT
1
2
3
4
Contents Page
Functions 3-8
Accessories 3-12
Help
VT50
F1 F2 F3 F4 F5 Info
Shift
Esc
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Backup/Restore
Bar data
Bit-wise password 8bits
Buttons
Circles
Command: Change language
Command: Report
Command: Restarts reading time-sampled trend
Command: Run pipeline
Command: Save alarms history and trend buffers in flash
Command: Save recipe in data memory
Command: Save recipe received from device in buffer
Command: Save recipe received from device in data memory
Command: Send recipe from video buffer to device
Command: Send recipe to device
Command: Service page
Unless otherwise stated, there is no limit to the number of includable elements, only the size of project memory sets a limit.
*) indicative value determined by the dimensions of the project
E-keys
Equations 32
F-keys
Free terminal
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Labels
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 127
Password
Pipelines (Number/Tot bytes)
Print
Print page (Total/Number of fields per page)
Programmable fonts
Project images
Public variables of ESANET network (Number/Total bytes)
Recipe field for recipe structure
Recipes (Number of variables per recipe)
Rectangles
Redefinable characters 7
Reports
Sequences - Random
64
Sequences - Start/stop
Static bitmaps
Symbolic field: Bit-group-structured dynamic bitmaps
Symbolic field: Single-bit-structured dynamic bitmaps
Symbolic field: Value-structured dynamic bitmaps
System messages
System variables assigned to recipe structure
Time long field
Time short field
Unless otherwise stated, there is no limit to the number of includable elements, only the size of project memory sets a limit.
*) indicative value determined by the dimensions of the project
Touch Area
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Value direct command: AND
Value direct command: OR
Value direct command: SET
Front face
1
Help
VT50
F1 F2 F3 F4 F5 Info
Shift
Esc
Key Function
1 Display
Shift + 2 F-keys
F5
Confirms setting
Help
Next page
Info
Previous page
F4
Start in-putting
F3
Moving cursor between fields
F2
Moving cursor between fields
Info
Shift + Displays information messages
Help
Shift + Displays according to context: info-message help or page help
Standard
series rear
view
A
C
Position Function
CAN series
rear view
C
A
D B
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
T
3
2
1
J2
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity)
or:
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The program VTWIN (see Software Manual) must be used for the transfer,
reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
F1=MODEM - F2= PC
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
F1=FAST - F2=SLOW
The choice should be according to the speed you intend to use for the transfer
(Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding function
. The VT is now ready to receive (see Software Manual for the transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
PROT ERROR
COM BROK
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by rotating the trimmer (C) at
the display the back of the VT (see Page 3-9 or Page 3-10); turn it (using a small screw-
driver or a trimmer tool) in one direction and, if the display quality wors-
ens, turn it the other way.
Contents Page
Functions 4-4
Accessories 4-12
Help F1
Esc
F2
F3
VT60
F4
Shift
Enter
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Backup/Restore
Bar data
Bit-wise password 8bits
Buttons
Circles
Command: Change language
Command: Report
Command: Restarts reading time-sampled trend
Command: Run pipeline
Command: Save alarms history and trend buffers in flash
Command: Save recipe in data memory
Command: Save recipe received from device in buffer
Command: Save recipe received from device in data memory
Command: Send recipe from video buffer to device
Command: Send recipe to device
Command: Service page
Unless otherwise stated, there is no limit to the number of includable elements, only the size of project memory sets a limit.
*) indicative value determined by the dimensions of the project
E-keys
Equations 32
F-keys
Free terminal
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Labels
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 127
Password
Pipelines (Number/Tot bytes)
Print
Print page (Total/Number of fields per page)
Programmable fonts
Project images
Public variables of ESANET network (Number/Total bytes)
Recipe field for recipe structure
Recipes (Number of variables per recipe)
Rectangles
Redefinable characters 7
Reports
Sequences - Random
64
Sequences - Start/stop
Static bitmaps
Symbolic field: Bit-group-structured dynamic bitmaps
Symbolic field: Single-bit-structured dynamic bitmaps
Symbolic field: Value-structured dynamic bitmaps
System messages
System variables assigned to recipe structure
Time long field
Time short field
Unless otherwise stated, there is no limit to the number of includable elements, only the size of project memory sets a limit.
*) indicative value determined by the dimensions of the project
Touch Area
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Value direct command: AND
Value direct command: OR
Value direct command: SET
Front view
Help F1
Esc
F2
1 F3
2
VT60
F4
Shift
Enter
Key Function
1 Display
Shift + 2 F-keys
F4
Opens and confirms setting
Enter
F1
Page up
F2
Page down
F3
Move cursor between fields
Help
Shift + Displays according to context: info-message help or page help
Esc
Standard
series rear
view
A
C
Position Function
CAN series
rear view
C
A
D B
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
T
3
2
1
J2
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
or:
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The program VTWIN (see Software Manual) must be used for the transfer,
reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
F1=MODEM - F2= PC
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
F1=FAST - F2=SLOW
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding func-
tion . The VT is now ready to receive (see Software Manual for the
transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
Driver: xxxxxxxxxxxxx
Ver. : xxxxxxxxxxxxx
Addr. : xxxxxxxxxxxxx
Error : xxxxxxxxxxxxx
PROT ERROR
COM BROK
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by rotating the trimmer (C) at
the display the back of the VT (see Page 4-9 or Page 4-10); turn it (using a small screw-
driver or a trimmer tool) in one direction and, if the display quality wors-
ens, turn it the other way.
Contents Page
Functions 5-4
Accessories 5-14
VT150W
F6 F7 F8 F9 F10
F1 F2 F3 F4 F5
V Y +
PgUp
W Z / Info
X 7 - 8 = 9
M P S
PgDn
N Q T Help
O 4 R 5 U 6
D G J
E H K
F 1 I 2 L 3
A . Clr
shift B
C 0 Space
Esc
Enter
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Backup/Restore
Bar data
Bit-wise password 8bits
Buttons
Circles
Command: Change language
Command: Report
Command: Restarts reading time-sampled trend
Command: Run pipeline
Command: Save alarms history and trend buffers in flash
Command: Save recipe in data memory
Command: Save recipe received from device in buffer
Command: Save recipe received from device in data memory
Command: Send recipe from video buffer to device
Command: Send recipe to device
Command: Service page
Unless otherwise stated, there is no limit to the number of includable elements, only the size of project memory sets a limit.
*) indicative value determined by the dimensions of the project
E-keys
Equations 32
F-keys
Free terminal
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Function: Sequences
Labels
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 1024
Password 10
Reports
Sequences - Random
64
Sequences - Start/stop
Static bitmaps
Symbolic field: Bit-group-structured dynamic bitmaps
Symbolic field: Single-bit-structured dynamic bitmaps
Symbolic field: Value-structured dynamic bitmaps
System messages
Touch Area
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Front view
VT150W
2
F6 F7 F8 F9 F10
F1 F2 F3 F4 F5
3 V
W
Y
Z
+
/ Info
PgUp
X 7 - 8 = 9
M P S
PgDn
N Q T Help
4 5 6
4
O R U
D G J
E H K
F 1 I 2 L 3
A . Clr
shift B
C 0 Space
Esc
Enter
Key Function
1 Display
3 F-keys
PgUp Page up
When in setting phase, edits dynamic text
Key Function
Clr
Quits: setting of data, info-messages, sequence directory, com-
Esc
munication driver
Clr
Shift + Esc
In setting phase restores the initial value of the field
Customizing
label
1 ESA Logo - 65 x 12
2 VT Model - 65 x 12
The total thickness of the label must not exceed 125m (microme-
ters). Do not use either stiff materials or glues.
Standard
series rear
view
C
Position Function
CAN series
rear view
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The program VTWIN (see Software Manual) must be used for the transfer,
reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
Boot forced
F1=MODEM - F2= PC
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
F1=FAST - F2=SLOW
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding func-
tion . The VT is now ready to receive (see Software Manual for the
transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
VT150W
Serial: xxxxxxxxxxxxx
Driver: xxxxxxxxxxxxx
Ver. : xxxxxxxxxxxxx
PgDn PgUp
Press or to display
Addr. : xxxxxxxxxxxxx
Error : xxxxxxxxxxxxx
Up/Down: next page
PROT ERROR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by rotating the trimmer (C) at
the display the back of the VT (see Page 5-11 or Page 5-12); turn it (using a small
screwdriver or a trimmer tool) in one direction and, if the display quality
worsens, turn it the other way.
Contents Page
Functions 6-4
Accessories 6-13
VT160W
F6 F7 F8 F9 F10
F1 F2 F3 F4 F5
V Y +
PgUp
W Z / Info
X 7 - 8 = 9
M P S
PgDn
N Q T Help
O 4 R 5 U 6
D G J
E H K
F 1 I 2 L 3
A . Clr
shift B
C 0 Space
Esc
Enter
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Backup/Restore
Bar data
Bit-wise password 8bits
Buttons
Circles
Command: Change language
Command: Report
Command: Restarts reading time-sampled trend
Command: Run pipeline
Command: Save alarms history and trend buffers in flash
Command: Save recipe in data memory
Command: Save recipe received from device in buffer
Command: Save recipe received from device in data memory
Command: Send recipe from video buffer to device
Command: Send recipe to device
Command: Service page
Unless otherwise stated, there is no limit to the number of includable elements, only the size of project memory sets a limit.
*) indicative value determined by the dimensions of the project, **) not present with VT160I/O driver
E-keys
Equations 32
F-keys
Free terminal
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Function: Sequences
Labels
Macro field
Macros (Total/Commands x macro) 1024/16
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 1024
Password 10
Reports
Sequences - Random
64
Sequences - Start/stop
Static bitmaps
Symbolic field: Bit-group-structured dynamic bitmaps
Symbolic field: Single-bit-structured dynamic bitmaps
Symbolic field: Value-structured dynamic bitmaps
System messages
Touch Area
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Front view
5 6
VT160W
1
7
2 8
F6 F7 F8 F9 F10
F1 F2 F3 F4 F5
3 V
W
Y
Z
+
/ Info
PgUp
X 7 - 8 = 9
9
M P S
PgDn
N Q T Help
4 5 6
4
O R U
D G J
E H K
F 1 I 2 L 3
A . Clr
shift B
C 0 Space
Esc
Enter
Key Function
1 Display
3 F-keys
9 E-keys
PgUp Page up
When in setting phase, edits dynamic text
Key Function
Clr
Quits: setting of data, info-messages, sequence directory, com-
Esc
munication driver
Clr
Shift + Esc
In setting phase restores the initial value of the field
Customizing
label
1
3
The total thickness of the label must not exceed 125m (microme-
ters). Do not use either stiff materials or glues.
Rear view
A B
C D
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is, it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The program VTWIN (see Software Manual) must be used for the transfer,
reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
Boot forced
F1=MODEM - F2= PC
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
F1=FAST - F2=SLOW
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding func-
tion . The VT is now ready to receive (see Software Manual for the
transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
VT160W
Serial: xxxxxxxxxxxxx
Driver: xxxxxxxxxxxxx
Ver. : xxxxxxxxxxxxx
PgDn PgUp
Press or to display
Addr. : xxxxxxxxxxxxx
Error : xxxxxxxxxxxxx
Up/Down: next page
PR ERROR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by rotating the trimmer (C) at
the display the back of the VT (see Page 6-11); turn it (using a small screwdriver or a
trimmer tool) in one direction and, if the display quality worsens, turn it the
other way.
Contents Page
Functions 7-4
Accessories 7-14
VT170W
X0 Power Battery
F1 F2 F3 F4 F5 F6
D G J
E H K
F 1 I 2 L 3
A . PgDn
shift B Enter
C 0 Space
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/128
Arc
Automatic operations
Backup/Restore
Bar data
Bit-wise password 8bits
Buttons
Circles
Command: Change language
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Function: Sequences
Internal registers
Labels
Macro field
Macros (Total/Commands x macro) 1024/16
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 1024
Password 10
Programmable fonts
Project images
Public variables of ESANET network (Number/Total bytes) 128/1024
Rectangles
Redefinable characters 7
Reports 128
Sequences - Random
128
Sequences - Start/stop
Static bitmaps
Symbolic field: Bit-group-structured dynamic bitmaps
Symbolic field: Single-bit-structured dynamic bitmaps
Symbolic field: Value-structured dynamic bitmaps
System messages
Front view
VT170W
4
1
5
X0 Power Battery
F1 F2 F3 F4 F5 F6 6
2
F7 F8 F9 F10 F11 F12
V Y +
W Z / Info Alarm Help
X 7 - 8 = 9
M P S Ack PgUp Clr
N Q T All
4 5 6
3
O R U Ack Esc
D G J
E H K
F 1 I 2 L 3
A . PgDn
shift B Enter
C 0 Space
Key Function
1 Display
2 F-keys
6 Battery LED. Lights up when the battery has nearly run out
Start input
Key Function
PgUp Page up
When in setting phase, edits dynamic text
Clr
Quits: setting of data, info-messages, sequence directory, com-
Esc
munication driver
Ack
All
Ack
Acknowledgment of ISA alarms on display
Clr
shift + Esc
In setting phase restores the initial value of the field
Ack
shift + All
Ack
Acknowledges all ISA alarms
Customizing
label
1 2
1 ESA Logo - 57 x 10
2 VT Model - 57 x 10
The total thickness of the label must not exceed 125m (microme-
ters). Do not use either stiff materials or glues.
Rear view
C H
D G
E F
Position Function
B Battery compartment
F Fuse holder
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
Choose the required transfer mode: MODEM if you intend to use a modem
or PC if you intend to use a serial port; press the corresponding function
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding func-
tion . The VT is now ready to receive (see Software Manual for the
transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
VT170W
Serial: xxxxxxxxxxxxx
Driver: xxxxxxxxxxxxx
Ver. : xxxxxxxxxxxxx
PgDn PgUp
Addr. : xxxxxxxxxxxxx
Error : xxxxxxxxxxxxx
Up/Down = next page
Enter = set clock
Enter
While displaying this page, press to access the clock setting page
Time Date
hh:mm:ss dd/mm/yy
Lf/Rt/Up/Dw = change
Esc=Prj Enter=Memo
PgUp
Possible error messages that can be displayed on the appropriate line are:
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by rotating the trimmer (C) at
the display the back of the VT (see Page 7-11); turn it (using a small screwdriver or a
trimmer tool) in one direction and, if the display quality worsens, turn it the
other way.
Contents Page
Functions 8-4
Accessories 8-14
VT190W
X0 Power Battery
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11
F12 F13 F14 F15 F16 F17 F18 F19 F20 F21 F22
. V Y +
F23 F24 PgUp Clr
W Z / Spare
Space X 7 - 8 = 9 Esc
M P S
Alarm Info shift N Q T
O 4 R 5 U 6
A D G J
Ack PgDn
Help B E H K Enter
All Ack
C 0 F 1 I 2 L 3
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/128
Arc
Automatic operations
Backup/Restore
Bar data
Bit-wise password 8bits
Buttons
Circles
Command: Change language
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Function: Sequences
Internal registers
Labels
Macro field
Macros (Total/Commands x macro) 1024/16
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 1024
Password 10
Programmable fonts
Project images
Public variables of ESANET network (Number/Total bytes) 128/1024
Rectangles
Redefinable characters 7
Reports 128
Sequences - Random
128
Sequences - Start/stop
Static bitmaps
Symbolic field: Bit-group-structured dynamic bitmaps
Symbolic field: Single-bit-structured dynamic bitmaps
Symbolic field: Value-structured dynamic bitmaps
System messages
Front view
4
1
5
VT190W
X0 Power Battery
6
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11
2
F12 F13 F14 F15 F16 F17 F18 F19 F20 F21 F22
.
3
V Y +
F23 F24 Clr
PgUp
W Z / Spare
Space X 7 - 8 = 9 Esc
M P S
Alarm Info shift N Q T
O 4 R 5 U 6
A D G J
Ack PgDn
Help B E H K Enter
All Ack
C 0 F 1 I 2 L 3
Key Function
1 Display
6 Battery LED. Lights up when the battery has nearly run out
7 Alphanumeric keys
Starts input
PgUp Page up
When in setting phase, edits dynamic text
Key Function
Clr
Quits: setting of data, info-messages, sequence directory, com-
Esc
munication driver
Ack
All
Ack
Acknowledgment of ISA alarms on display
Clr
shift + Esc
In setting phase restores the initial value of the field
Ack
shift + All
Ack
Acknowledges all ISA alarms
Customizing
label
1 3
2 4
1 ESA Logo - 73 x 10
3 VT Model - 73 x 10
The total thickness of the label must not exceed 125m (microme-
ters). Do not use either stiff materials or glues.
Rear view
H G
B C D E F
Position Function
A Battery compartment
C Fuse holder
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding func-
tion . The VT is now ready to receive (see Software Manual for the
transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
VT190W
Serial: xxxxxxxxxxxxx
Driver: xxxxxxxxxxxxx
Ver. : xxxxxxxxxxxxx
PgDn PgUp
Addr. : xxxxxxxxxxxxx
Error : xxxxxxxxxxxxx
Up/Down = next page
Enter = settings page
Enter
If while displaying this page you press you will access the page for set-
ting the clock and the contrast
CONTRAST:####
TIME: hh:mm:ss DATE: dd:mm:yy
Left/Right = select. Up/Down = change
ESC = project ENTER = memo
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Clr
Esc
By pressing you pass back to the project page.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 8-11) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
Contents Page
Functions 9-4
Accessories 9-14
VT300W
X0 Power Battery
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11
F12 F13 F14 F15 F16 F17 F18 F19 F20 F21 F22
. V Y +
F23 F24 Clr
PgUp
W Z / Spare
Space X 7 - 8 = 9 Esc
M P S
Alarm Info shift N Q T
O 4 R 5 U 6
A D G J
Ack PgDn
Help B E H K Enter
All Ack
C 0 F 1 I 2 L 3
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Buttons
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Function: Sequences
Labels
Lists of texts
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
128
Sequences - Start/stop
Static bitmaps
System messages
Touch Area
Trend buffers 128
Front view
4
1
5
VT300W
X0 Power Battery
6
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11
2
F12 F13 F14 F15 F16 F17 F18 F19 F20 F21 F22
.
3
V Y +
F23 F24 PgUp Clr
W Z / Spare
Space X 7 - 8 = 9 Esc
M P S
Alarm Info shift N Q T
O 4 R 5 U 6
A D G J
Ack PgDn
Help B E H K Enter
All Ack
C 0 F 1 I 2 L 3
Key Function
1 Display
6 Battery LED. Lights up when the battery has nearly run out
7 Alphanumeric keys
Starts input
PgUp Page up
When in setting phase, edits dynamic text
Key Function
Clr
Quits: setting of data, info-messages, sequence directory, com-
Esc
munication driver
Ack
All
Ack
Acknowledgment of ISA alarms on display
Clr
shift + Esc
In setting phase restores the initial value of the field
Ack
shift + All
Ack
Acknowledges all ISA alarms
Customizing
label
1 3
2 4
1 ESA Logo - 73 x 10
3 VT Model - 73 x 10
The total thickness of the label must not exceed 125m (microme-
ters). Do not use either stiff materials or glues.
Standard
series rear
view A
B C D E
Position Function
CAN series
rear view
A
B C D E
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
Memory Card has been inserted in the VT terminal (see Page 9-18). The
function to press depends on which port you intend to use (MSP or
ASP). The VT is now ready to receive (refer to Software Manual for
transfer procedure)
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
F1=SLOW F2=FAST
The choice should be according to the speed you intend to use for the transfer
(Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding function
. The VT is now ready to receive (see Software Manual for the transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
Port : xxxxxxxxxxxxxxxxxxxxx
Driver : xxxxxxxxxxxxxxxxxxxxx
Ver : xxxxxxxxxxxxxxxxxxxxx
Addr VT : xxxxxxxxxxxxxxxxxxxxx
Error : xxxxxxxxxxxxxxxxxxxxx
There is one of these pages for each communication port; you can move
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
Right=next page Enter=set
PgUp PgDn
CONTRAST : ##
Up/Down=change Enter=memo
PgUp PgDn
Enter
Use and/or to effect any variation and for the confirmation.
PgUp PgDn
To be able to set the clock use or to select the SET CLOCK option
Enter
that is displayed in reverse colors and press ; the following mask will
appear:
hh:mm:ss dd/mm/yy
PgUp PgDn
Enter
To use the Memory Card either switch on the VT with held down or, if
shift Enter
the VT is already on, press + together; in both cases it will be nec-
essary to wait a moment before the following mask appears on the VT:
Press F3=MemoCARD (if the key is not on screen, see Page 9-15) and
the following mask will appear:
For the meaning and function of the keys see Chapter 33 -> Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Esc
When is pressed you quit the display of information regarding the
driver.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 9-17) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
Contents Page
Functions 10-4
Accessories 10-14
F12 F16
F13 F17
F14 F18
F15 F19
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11
. V Y +
F20 F21 PgUp Clr
W Z / Spare
Space X 7 - 8 = 9 Esc
M P S
Alarm Info shift N Q T
O 4 R 5 U 6
A D G J
Ack PgDn
Help B E H K Enter
All Ack
C 0 F 1 I 2 L 3
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Buttons
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Function: Sequences
Labels
Lists of texts
Macro field
Macros (Total/Commands x macro) 1024/16
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
128
Sequences - Start/stop
Static bitmaps
System messages
Touch Area
Trend buffers 128
Front view
1
F12 F16 3
F13 F17
2 6
F14 F18
F15 F19
7
VT310W X0 Power Battery
4 8
F1 F2 F3 F4 F5 F6 F7 F8 F9 F10 F11
.
5
V Y +
F20 PgUp
F21 Space
W
X 7
Z
- 8
/
= 9
Spare Clr
Esc
M P S
Alarm Info shift N Q T
O 4 R 5 U 6
A D G J
Ack PgDn
Help B E H K Enter
All Ack
C 0 F 1 I 2 L 3
Key Function
1 Display
8 Battery LED. Lights up when the battery has nearly run out
9 Alphanumeric keys
Starts input
Key Function
PgUp Page up
When in setting phase, edits dynamic text
Clr
Quits: setting of data, info-messages, sequence directory, com-
Esc
munication driver
Ack
All
Ack
Acknowledgment of ISA alarms on display
Clr
shift + Esc
In setting phase restores the initial value of the field
Ack
shift + All
Ack
Acknowledges all ISA alarms
Customizing
label
1 4
2 5
3 6
1 F-key customization F - 16 x 92
2 ESA Logo - 91 x 10
4 F-key customization F - 16 x 92
5 VT Model - 91 x 10
The total thickness of the label must not exceed 125m (microme-
ters). Do not use either stiff materials or glues.
Rear view
C D E F
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding func-
tion . The VT is now ready to receive (see Software Manual for the
transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
Port : xxxxxxxxxxxxxxxxxxxxx
Driver : xxxxxxxxxxxxxxxxxxxxx
Ver : xxxxxxxxxxxxxxxxxxxxx
Addr VT : xxxxxxxxxxxxxxxxxxxxx
Error : xxxxxxxxxxxxxxxxxxxxx
There is one of these pages for each communication port; you can move
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
PgUp PgDn
CONTRAST : ##
PgUp PgDn
Enter
Use and/or to effect any variation and for the confirmation.
PgUp PgDn
To be able to set the clock use or to select the SET CLOCK option
Enter
that is displayed in reverse colors and press ; the following mask will
appear:
hh:mm:ss dd/mm/yy
PgUp PgDn
Enter
To use the Memory Card either switch on the VT with held down or, if
shift Enter
the VT is already on, press + together; in both cases it will be
necessary to wait a moment before the following mask appears on the VT:
Press F3=MemoCARD (if the key is not on the screen, see Page 10-15)
and the following mask will appear:
For the meaning and function of the keys see Chapter 33 -> Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Esc
When is pressed you quit the display of information regarding the
driver.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 10-17) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
Contents Page
Functions 11-4
Accessories 11-13
V Y +
W Z /
X 7 - 8 = 9
F19 F24
M P S
N Q T
O 4 R 5 U 6
F20 F25
D G J
E H K
F 1 I 2 L 3
F21 F26
A .
shift B
C 0
F22 F27
space
F23 F28
F1 F2 F3 F4 F5 F6 F7 F8 F9
PgDn
Enter
F10 F11 F12 F13 F14 F15 F16 F17 F18
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously)
Arc
Automatic operations 32
Backup/Restore
Bar data
Buttons
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Function: Sequences
Labels
Lists of texts
Macro field
Macros (Total/Commands x macro) 1024/16
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
128
Sequences - Start/stop
Static bitmaps
System messages
Touch Area
Trend buffers 128
Front view
2 1 3 8
V Y +
W Z /
X 7 - 8 = 9
F19 F24
M P S
N Q T
O 4 R 5 U 6
F20 F25
D G J
E H K
F 1 I 2 L 3
F21 F26
A .
shift B
C 0
F22 F27
space
F23 F28
F1 F2 F3 F4 F5 F6 F7 F8 F9
PgDn
Enter
F10 F11 F12 F13 F14 F15 F16 F17 F18
4 5 6 7
Key Function
1 Display
7 Battery LED. Lights up when the battery has nearly run out
Key Function
8 Alphanumeric keys
Starts input
PgUp Page up
When in setting phase, edits dynamic text
Clr
Quits: setting of data, info-messages, sequence directory, com-
Esc
munication driver
Ack
All Ack Acknowledgment of ISA alarms on display
Clr
shift + Esc
In setting phase restores the initial value of the field
Ack
shift + All Ack Acknowledges all ISA alarms
Customizing
label
1 4
The total thickness of the label must not exceed 125m (microme-
ters). Do not use either stiff materials or glues.
Rear view
A B
C D E F
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
F1=SLOW F2=FAST
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding func-
tion . The VT is now ready to receive (see Software Manual for the
transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
Port : xxxxxxxxxxxxxxxxxxxxx
Driver : xxxxxxxxxxxxxxxxxxxxx
Ver : xxxxxxxxxxxxxxxxxxxxx
Addr VT : xxxxxxxxxxxxxxxxxxxxx
Error : xxxxxxxxxxxxxxxxxxxxx
There is one of these pages for each communication port; you can move
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
PgUp PgDn
In order to access the contrast setting, use or to select the SET CON-
Enter
TRAST option that is displayed in reverse colors and press ; the following
mask will appear:
CONTRAST : ##
PgUp PgDn
Enter
Use and/or to effect any variation and for the confirmation.
PgUp PgDn
To be able to set the clock use or to select the SET CLOCK option
Enter
that is displayed in reverse colors and press ; the following mask will
appear:
hh:mm:ss dd/mm/yy
PgUp PgDn
Enter
To use the Memory Card either switch on the VT with held down or, if
shift Enter
the VT is already on, press + together; in both cases it will be nec-
essary to wait a moment before the following mask appears on the VT:
Press F3=MemoCARD (if the key is not on screen, see Page 11-14); and
For the meaning and function of the keys see Chapter 33 -> Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Esc
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 11-17) and changing the value (from +63 to -64) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 12-4
Accessories 12-14
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 256/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 64
Page help 64
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 32
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 24
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Front view
All buttons and signals are defined using the programming software (see
Software Manual).
Standard
series rear
view
B C
Position Function
Profibus-DP
series rear
view
B C
Position Function
CAN series
rear view
B C
Position Function
Ethernet
series rear
view
B C
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Methods of There are two ways of mounting the VT155 on the container, horizontally
mounting or vertically. Once you have chosen the direction that means you can see
the project properly and you are in the project creation phase, choose the
terminal with the same orientation (see Software Manual Chapter 5 ->
New).
Once the orientation has been defined, you are recommended not
to change it, as the project created could then become unusable.
To orientate the terminal correctly use the logo on the front fascia
as a reference.
Below are listed the terminals with their respective correct orientations.
Upper part
Calibration of The screen of VT155W is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
J1
C
3
2
1
J1
Touch the corner indicated in the figure; then the following page appears
on screen
Touch the corner indicated in the figure to complete the calibration pro-
cedure; the following page now appears
Wait a few moments until the VT displays either the following mask or
the project page (the page may be slightly different in its wording
depending on which series the terminal belongs to)
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
Introducing This paragraph relates only to the Ethernet series. The Media Access Control
the MAC (MAC) address unambiguously identifies each terminal connected in the Ether-
address net network. The terminal is acquired with the address already programmed
and is shown on the display of the terminal in the transfer page.
MAC addr:
00.0E.0E.xx.xx.xx
This operation must be carried out only with the advice of the
ESA Customer Care Department.
Terminals with no valid MAC address when switched present a mask for its
insertion. If no MAC address belonging to the terminal is available, pro-
ceed as follows:
00.0E.0E
xx.xx.xx
00.0E.0E
xx.xx.xx
Make a note of the number on the label (e.g. 00.0E.0E.00.00.01)
ESC
Use the arrow to make the setting. Once the address has been con-
firmed the following page is displayed
MAC addr:
00.0E.0E.00.00.01
Should a wrong MAC address have been inserted contact the ESA
Customer Care Department.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
and wait a moment, or, using the appropriate button (see Page 12-24),
till the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The following mask will appear
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
The choice should be according to the speed you intend to use for the transfer
(Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the display.
The VT is now ready to receive (see Software Manual for the transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST : ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 12-23) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it, decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on).
Contents Page
Functions 13-4
Accessories 13-13
Hist
Ack
Info Help All
Ack
Alarm
F13 F21
Space
A C E
B D F
F14 F22
G I K M
H J L N
F15 F23 O Q S U
P R T V
F17 F25
_
; * (
- 7 8 9
F18 F26
+ : % [
= 4 5 6
F19 F27
) / \ ]
0 1 2 3
F20 F28
PgUp
Ctrl Spare Clr
PgDn
Tab Enter
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Buttons
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Internal command
Function: Macro
Function: None
Function: Sequences
Labels
Lists of texts
Macro field
Macros (Total/Commands x macro) 1024/16
Message field
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
128
Sequences - Start/stop
Static bitmaps
System messages
Touch Area
Trend buffers 128
Front view
4 1 5
Hist
Ack
Info Help All
Ack
Alarm
F13 F21
Space
A C E
B D F
F14 F22
G I K M
H J L N
F15 F23 O Q S U
P R T V
PgUp
Ctrl Spare Clr
PgDn
Tab Enter
3 6 7 8
Key Function
1 Display
8 Battery LED. Lights up when the battery has nearly run out
Starts input
PgUp Page up
When in setting phase, edits dynamic text
Key Function
Hist
Displays ISA alarms
Alarm
Ack
All
Ack
Acknowledgment of ISA alarms on display
shift + Ack
All
Ack
Acknowledges all ISA alarms
Hist
shift + Displays the contents of the alarm buffer
Alarm
Customizing
label
1 2
The total thickness of the label must not exceed 125m (microme-
ters). Do not use either stiff materials or glues.
Rear view
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The program VTWIN (see Software Manual) must be used for the transfer,
reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
F1=SLOW F2=FAST
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), press the corresponding func-
tion . The VT is now ready to receive (see Software Manual for the
transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
Port : xxxxxxxxxxxxxxxxxxxxx
Driver : xxxxxxxxxxxxxxxxxxxxx
Ver : xxxxxxxxxxxxxxxxxxxxx
Addr VT : xxxxxxxxxxxxxxxxxxxxx
Error : xxxxxxxxxxxxxxxxxxxxx
There is one of these pages for each communication port; you can move
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
PgUp PgDn
CONTRAST : ##
PgUp PgDn
Enter
Use and/or to effect any variation; use for the confirmation.
PgUp PgDn
To be able to set the clock use or to select the SET CLOCK option
Enter
that is displayed in reverse colors and press ; the following mask will
appear:
hh:mm:ss dd/mm/yy
PgUp PgDn
Enter
To use the Memory Card either switch on the VT with held down or, if
shift Enter
the VT is already on, press + together; in both cases it will be nec-
essary to wait a moment before the following mask appears on the VT:
Press F3=MemoCARD (if the key is not on screen, see Page 13-14); the
following mask will appear:
F9= EXIT
For the meaning and function of the keys see Chapter 33 -> Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
Esc
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 13-17) and changing the value (from +63 to -64) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 14-4
Accessories 14-12
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 256/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Page 150
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 32
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 24
Front view
All buttons and signals are defined using the programming software (see
Software Manual).
Standard
series rear
view
B C
Position Function
Ethernet
series rear
view
B C
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Methods of There are two ways of mounting the VT185W on the container, horizon-
mounting tally or vertically. Once you have chosen the direction that means you can
see the project properly and you are in the project creation phase, choose
the terminal with the same orientation (see Software Manual Chapter 5 ->
New).
Once the orientation has been defined, you are recommended not
to change it, as the project created could then become unusable.
To orientate the terminal correctly use the logo on the front fascia
as a reference.
Below are listed the terminals with their respective correct orientations.
Upper part
Calibration of The screen of VT185W is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
C
3
2
1
J1
Touch the corner indicated in the figure; then the following page appears
on screen
Touch the corner indicated in the figure to complete the calibration pro-
cedure; the following page now appears
Wait a few moments until the VT displays either the following mask or
the project page (the page may be slightly different in its wording
depending on which series the terminal belongs to)
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Introducing This paragraph relates only to the Ethernet series. The Media Access Control
the MAC (MAC) address unambiguously identifies each terminal connected in the Ether-
address net network. The terminal is acquired with the address already programmed
and is shown on the display of the terminal in the transfer page.
MAC addr:
00.0E.0E.xx.xx.xx
This operation must be carried out only with the advice of the
ESA Customer Care Department.
Terminals with no valid MAC address when switched present a mask for its
insertion. If no MAC address belonging to the terminal is available, pro-
ceed as follows:
00.0E.0E
xx.xx.xx
00.0E.0E
xx.xx.xx
Make a note of the number on the label (e.g. 00.0E.0E.00.00.01)
ESC
Use the arrow to make the setting. Once the address has been con-
firmed the following page is displayed
MAC addr:
00.0E.0E.00.00.01
Should a wrong MAC address have been inserted contact the ESA
Customer Care Department.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
and wait a moment, or, using the appropriate button (see Page 14-21),
till the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The following mask will appear
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the transfer
(Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the display.
The VT is now ready to receive (see Software Manual for the transfer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock, while displaying the above illustrated page, press
PROG
; the following mask appears
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Contents Page
Functions 15-5
Accessories 15-12
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Wrapping
Type Antiflame PC/ABS halogen-free (UL94 5VA at 2.5mm)
Drop test 1 m.
Connection cable
Type Antiflame shielded cable halogen and silicone-free
Radius of curve (moving/fixed) 120mm/60mm
Conductors (number/section) 25x0,25mmq (AWG24)
System shut-down button
Positions 2 (Normal - Pushed)
Contacts 1 NC + 1 NC (NC1/NC2 + NC3/NC4)
Maximum tension 30Vdc
Maximum/minimum current 500mA/5mA
Conforms to the following standard(s) EN 60947-5-1, UL-508, CSA 22.2. No. 14)
Enabling button
Positions 3 (Normal - Pushed - Panic)
Contacts 1 NC/NO + 1 NC/NO (NC1/NO1/C1 + NC2/NO2/C2)
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Load recipe from data memory
Command: Report
Command: Restarts reading time-sampled trend
Command: Run pipeline
Command: Save alarms history and trend buffers in flash
Command: Save recipe in data memory
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Macro field
Macros (Total/Commands x macro) 1024/16
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 128
Password 10
Project images
Rectangles
Redefinable characters
Reports
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 24
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Front view
1 2 3
F1 F6
F2 F7
6 F3 F8
F4 F9
F5 F10
5 4
Key Function
4 F-keys
5 F-keys
Other buttons and signals are defined using the programming software (see
Software Manual).
Rear view
A B C D
Position Function
B Identification label
Dimensions
and Cut-out
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
Connection The terminal is provided with a 10m long (AWG24) 25x0.25mmq shielded
cable cable already attached (see Chapter 32 -> Connection cable for H Series
terminals).
Adjusting The strap can be altered to adjust the grip for different hand sizes. To alter
holding strap strap:
for grip
Open the leather cover
Detach the strap ends
Adjust the holding strap length
Secure strap ends again
Close leather cover
Calibration of The screen of VT505H is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
F2 F7
F4 F9
F5 F10
F1 F6
F2 F7
Touch screen calibration
F3 Press bottom left point F8
F4 F9
F5 F10
Touch the corner indicated in the figure; then the following page appears
on screen
F1 F6
F2 F7
Touch screen calibration
F3 Press top right point F8
F4 F9
F5 F10
Touch the corner indicated in the figure to complete the calibration pro-
cedure; the following page now appears
F1 F6
F2 F7
Touch screen calibration
F3 Press bottom right point F8
F4 F9
F5 F10
Wait a few moments until the VT displays either the following mask or
the project page (the page may be slightly different in its wording
depending on which series the terminal belongs to)
F4 F9
F5 F10
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
F3 F8
*** WAIT FOR BOOT FORCED ***
F4 F9
F5 F10
and wait a moment, or, using the appropriate button (see Page 15-20),
till the VT displays the following mask
F3 F8
SELECT: MODEM PC EXIT
F4 F9
F5 F10
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
F3 F8
SELECT: SLOW FAST
F4 F9
F5 F10
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
F4 F9
F5 ESC F10
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
F1 F6
SET CONTRAST : ##
F2 F7
F3 SET CLOCK : F8
ddd,dd/mm/yy
hh:mm:ss
F4 F9
F5 ESC F10
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
F1 F6
F2 CONTRAST : ## F7
F3 F8
F4 F9
F5 ESC F10
Use the arrow for any variation (see Chapter 36 -> Operation of
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
F1 F6
F2 F7
ESC
F3 F8
F4 F9
F5 F10
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
F2 F7
F4 F9
F5 F10
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 15-19) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it, decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 16-4
Accessories 16-13
V T505W
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Load recipe from data memory
Command: Report
Command: Restarts reading time-sampled trend
Command: Run pipeline
Command: Save alarms history and trend buffers in flash
Command: Save recipe in data memory
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 128
Password 10
Project images
Rectangles
Redefinable characters
Reports
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 24
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Front view
V T505W
All buttons and signals are defined using the programming software (see
Software Manual).
Standard
series rear
view
A
B
Position Function
CAN series
rear view
A
B
Position Function
Ethernet
series rear
view
C B
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Calibration of The screen of VT505W is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
Standard, Can
Ethernet J1 C
1 2 3
Touch the corner indicated in the figure; then the following page appears
on screen
Touch the corner indicated in the figure to complete the calibration pro-
cedure; the following page now appears
Wait a few moments until the VT displays either the following mask or
the project page (the page may be slightly different in its wording
depending on which series the terminal belongs to)
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
Introducing This paragraph relates only to the Ethernet series. The Media Access Control
the MAC (MAC) address unambiguously identifies each terminal connected in the Ether-
address net network. The terminal is acquired with the address already programmed
and is shown on the display of the terminal in the transfer page.
MAC addr:
00.0E.0E.xx.xx.xx
This operation must be carried out only with the advice of the
Terminals with no valid MAC address when switched present a mask for its
insertion. If no MAC address belonging to the terminal is available, pro-
ceed as follows:
00.0E.0E
xx.xx.xx
00.0E.0E
xx.xx.xx
Use the arrow to make the setting. Once the address has been con-
firmed the following page is displayed
MAC addr:
00.0E.0E.00.00.01
Should a wrong MAC address have been inserted contact the ESA
Customer Care Department.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
and wait a moment, or, using the appropriate button (see Page 16-24),
till the VT displays the following mask
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
CONTRAST : ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the driver.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 16-23) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it, decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 17-4
Accessories 17-13
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 256/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Load recipe from data memory
Command: Report
Command: Restarts reading time-sampled trend
Command: Run pipeline
Command: Save alarms history and trend buffers in flash
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 128
Password 10
Project images
Rectangles
Redefinable characters
Reports
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 24
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Front view
All buttons and signals are defined using the programming software (see
Software Manual).
Standard
series rear
view
A
B
Position Function
CAN series
rear view
A
B
Position Function
Ethernet
series rear
view
C B
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Calibration of The screen of VT515W is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
Standard, Can
Ethernet J1 C
1 2 3
Touch the corner indicated in the figure; then the following page appears
on screen
Touch the corner indicated in the figure to complete the calibration pro-
cedure; the following page now appears
Wait a few moments until the VT displays either the following mask or
the project page (the page may be slightly different in its wording
depending on which series the terminal belongs to)
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
Introducing This paragraph relates only to the Ethernet series. The Media Access Control
the MAC (MAC) address unambiguously identifies each terminal connected in the Ether-
address net network. The terminal is acquired with the address already programmed
and is shown on the display of the terminal in the transfer page.
MAC addr:
00.0E.0E.xx.xx.xx
This operation must be carried out only with the advice of the
Terminals with no valid MAC address when switched present a mask for its
insertion. If no MAC address belonging to the terminal is available, pro-
ceed as follows:
00.0E.0E
xx.xx.xx
00.0E.0E
xx.xx.xx
Use the arrow to make the setting. Once the address has been con-
firmed the following page is displayed
MAC addr:
00.0E.0E.00.00.01
Should a wrong MAC address have been inserted contact the ESA
Customer Care Department.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
and wait a moment, or, using the appropriate button (see Page 17-24),
till the VT displays the following mask
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
CONTRAST : ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the driver.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 17-23) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it, decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 18-5
Accessories 18-12
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Wrapping
Type Antiflame PC/ABS halogen-free (UL94 5VA at 2.5mm)
Drop test 1 m.
Connection cable
Type Antiflame shielded cable halogen and silicone-free
Radius of curve (moving/fixed) 120mm/60mm
Conductors (number/section) 25x0,25mmq (AWG24)
System shut-down button
Positions 2 (Normal - Pushed)
Contacts 1 NC + 1 NC (NC1/NC2 + NC3/NC4)
Maximum tension 30Vdc
Maximum/minimum current 500mA/5mA
Conforms to the following standard(s) EN 60947-5-1, UL-508, CSA 22.2. No. 14)
Enabling button
Positions 3 (Normal - Pushed - Panic)
Contacts 1 NC/NO + 1 NC/NO (NC1/NO1/C1 + NC2/NO2/C2)
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 256/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Macro field
Macros (Total/Commands x macro) 1024/16
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 150
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 32
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 24
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Front view
1 2 3
F1 F6
F2 F7
6 F3 F8
F4 F9
F5 F10
5 4
Key Function
4 F-keys
5 F-keys
Other buttons and signals are defined using the programming software (see
Software Manual).
Rear view
A B C D
Position Function
B Identification label
Dimensions
and Cut-out
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
Connection The terminal is provided with a 10m long (AWG24) 25x0.25mmq shielded
cable cable already attached (see Chapter 32 -> Connection cable for H Series
terminals).
Adjusting The strap can be altered to adjust the grip for different hand sizes. To alter
holding strap strap:
for grip
Open the leather cover
Detach the strap ends
Adjust the holding strap length
Secure strap ends again
Close leather cover
Calibration of The screen of VT525H is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
F2 F7
F4 F9
F5 F10
F1 F6
F2 F7
Touch screen calibration
F3 Press bottom left point F8
F4 F9
F5 F10
Touch the corner indicated in the figure; then the following page appears
on screen
F1 F6
F2 F7
Touch screen calibration
F3 Press top right point F8
F4 F9
F5 F10
Touch the corner indicated in the figure to complete the calibration pro-
cedure; the following page now appears
F1 F6
F2 F7
Touch screen calibration
F3 Press bottom right point F8
F4 F9
F5 F10
Wait a few moments until the VT displays either the following mask or
the project page (the page may be slightly different in its wording
depending on which series the terminal belongs to)
F4 F9
F5 F10
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
F3 F8
*** WAIT FOR BOOT FORCED ***
F4 F9
F5 F10
and wait a moment, or, using the appropriate button (see Page 18-21),
till the VT displays the following mask
F3 F8
SELECT: MSP ASP EXIT
F4 F9
F5 F10
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The VT is now ready to receive (refer to
Software Manual for transfer procedure).
F3 F8
SELECT: MODEM PC EXIT
F4 F9
F5 F10
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
F3 F8
SELECT: SLOW FAST
F4 F9
F5 F10
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
F4 F9
F5 ESC F10
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
F1 F6
SET CONTRAST : ##
F2 F7
F3 SET CLOCK : F8
ddd,dd/mm/yy
hh:mm:ss
F4 F9
F5 ESC F10
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
F1 F6
F2 CONTRAST : ## F7
F3 F8
F4 F9
F5 ESC F10
Use the arrow for any variation (see Chapter 36 -> Operation of
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
F1 F6
F2 F7
ESC
F3 F8
F4 F9
F5 F10
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
F2 F7
F4 F9
F5 F10
The on-screen to press depends on the port you intend to use (MSP
or ASP). The VT terminal is now ready to receive (consult Software
Manual for information on the transmission procedure).
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 18-20) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it, decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 19-4
Accessories 19-14
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 256/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 150
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 32
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 24
Trend buffers
Trends (Trends x page/Channels x trend)
Trends sampled automatically (Memory/Trends/Readings)
Trends sampled on command (Memory/Trends/Readings)
Value direct command: ADD
Front view
All buttons and signals are defined using the programming software (see
Software Manual).
Standard
series rear
view
A
C
Position Function
Profibus-DP
series rear
view
Position Function
CAN series
rear view
Position Function
Ethernet
series rear
view
C B
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Calibration of The screen of VT525W is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
J1 C
1 2 3
Touch the corner indicated in the figure; then the following page appears
on screen
Touch the corner indicated in the figure to complete the calibration pro-
cedure; the following page now appears
Wait a few moments until the VT displays either the following mask or
the project page (the page may be slightly different in its wording
depending on which series the terminal belongs to)
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
J4 T
1 2 3
Introducing This paragraph relates only to the Ethernet series. The Media Access Control
the MAC (MAC) address unambiguously identifies each terminal connected in the Ether-
address net network. The terminal is acquired with the address already programmed
and is shown on the display of the terminal in the transfer page.
MAC addr:
00.0E.0E.xx.xx.xx
This operation must be carried out only with the advice of the
ESA Customer Care Department.
Terminals with no valid MAC address when switched present a mask for its
insertion. If no MAC address belonging to the terminal is available, pro-
ceed as follows:
00.0E.0E
xx.xx.xx
00.0E.0E
xx.xx.xx
Use the arrow to make the setting. Once the address has been con-
firmed the following page is displayed
MAC addr:
00.0E.0E.00.00.01
Should a wrong MAC address have been inserted contact the ESA
Customer Care Department.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
and wait a moment, or, using the appropriate button (see Page 19-25),
till the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The VT is now ready to receive (refer to
Software Manual for transfer procedure).
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST : ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
The on-screen to press depends on the port you intend to use (MSP
or ASP). The VT terminal is now ready to receive (consult Software
Manual for information on the transmission procedure).
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 19-25) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it, decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 20-4
Accessories 20-12
VT555W
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Object - Indicator
Object - Potentiometer knob
Object - Selector knob
Object - Sliding potentiometer
Object - Sliding selector
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 48
Front view
VT555W
All buttons and signals are defined using the programming software (see
Software Manual).
Standard
series rear
view
G
A
F
C D E
Position Function
CAN series
rear view
E
A
D
B C
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
and wait a moment, or, using the appropriate button (see Page 20-18),
till the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The VT is now ready to receive (refer to
Software Manual for transfer procedure)
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
Driver : xxxxxxxxxxxxxxxxxxxxx
TRAN
Ver : xxxxxxxxxxxxxxxxxxxxx PAGE
Addr VT : xxxxxxxxxxxxxxxxxxxxx
Error : xxxxxxxxxxxxxxxxxxxxx
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST: ##
SET CLOCK:
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST: ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
Which on-screen you touch depends on the port you intend using.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 20-17) and changing the value (from +31 to -32) in evidence at
that moment. Increase the value to darken the display; to lighten it, decrease
the value.
Contents Page
Functions 21-4
Accessories 21-11
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Object - Indicator 64
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 64
Front view
All buttons and signals are defined using the programming software (see
Software Manual).
Rear view
B C
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
and wait a moment, or, using the appropriate button (see Page 21-16),
till the VT displays the following mask
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST : ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
accessories).
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
The on-screen to press depends on the port you intend to use (MSP
or ASP). The VT terminal is now ready to receive (consult Software
Manual for information on the transmission procedure).
TRAN
PAGE
While displaying the driver information page, press and the fol-
lowing mask will appear:
Touch the MemoCARD on the screen (if the key is not on screen,
see Page 21-12) and the following mask will appear:
BACKUP RESTORE
ERASE EXIT
For the meaning and the functions of the keys see Chapter 33 ->
Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 21-15) and changing the value (from +63 to -64) in evidence at
that moment. Increase the value to darken the display; to lighten it, decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 22-4
Accessories 22-11
VT565W
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Object - Indicator 64
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Touch Area 64
Front view
VT565W
All buttons and signals are defined using the programming software (see
Software Manual).
Rear view
A
F
H D E
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation The program VTWIN (see Software Manual) must be used for the transfer,
for reception but the terminal must be set up to receive. This means carrying out the fol-
lowing steps:
and wait a moment, or, using the appropriate button (see Page 22-17),
till the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The VT is now ready to receive (refer to
Software Manual for transfer procedure). The MemoCARD appears if
the Memory Card has been inserted in the VT (see Page 22-18)
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST : ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
The on-screen to press depends on the port you intend to use (MSP
or ASP). The VT terminal is now ready to receive (consult Software
Manual for information on the transmission procedure).
TRAN
PAGE
While displaying the driver information page, press and the fol-
lowing mask will appear:
Touch the MemoCARD on the screen (if the key is not on screen,
see Page 22-12) and the following mask will appear:
BACKUP RESTORE
ERASE EXIT
For the meaning and the functions of the keys see Chapter 33 ->
Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 22-16) and changing the value (from +63 to -64) in evidence at
that moment. Increase the value to darken the display; to lighten it, decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 23-4
Accessories 23-14
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Front view
All buttons and signals are defined via the programming software (see Soft-
ware Manual).
Standard
series rear
view
A
C D
Position Function
Profibus-DP
series rear
view
A
C D
Position Function
CAN series
rear view
A
C D
Position Function
Ethernet
series rear
view
A
C D
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Calibration of The screen of VT575W is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
J11
C
1 2 3
Touch the corner indicated in the figure; then the following page appears on screen
Wait a few moments until the VT displays either the following mask or
the project page
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
J14
1
2
3 T
Introducing This paragraph relates only to the Ethernet series. The Media Access Control
the MAC (MAC) address unambiguously identifies each terminal connected in the Ether-
address net network. The terminal is acquired with the address already programmed
and is shown on the display of the terminal in the transfer page.
MAC addr:
00.0E.0E.xx.xx.xx
This operation must be carried out only with the advice of the
ESA Customer Care Department.
Terminals with no valid MAC address when switched present a mask for its
insertion. If no MAC address belonging to the terminal is available, pro-
ceed as follows:
00.0E.0E
xx.xx.xx
00.0E.0E
xx.xx.xx
Use the arrow to make the setting. Once the address has been con-
firmed the following page is displayed
MAC addr:
00.0E.0E.00.00.01
Should a wrong MAC address have been inserted contact the ESA
Customer Care Department.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The programme VTWIN must be used for the transfer (see Software Man-
reception ual), but the terminal must be prepared for reception.
and wait a few moments, alternatively use the button provided (see Page
23-21), until the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The VT is now ready to receive (refer to
Software Manual for transfer procedure). The MemoCARD appears if
the Memory Card has been inserted in the VT (see Page 23-27)
Choose the required transfer mode: MODEM if you intend to use a modem
or PC if you intend to use a serial port; touch the relevant on the display
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST: ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
The on-screen to press depends on the port you intend to use (MSP
or ASP). The VT terminal is now ready to receive (consult Software
Manual for information on the transmission procedure).
TRAN
PAGE
While displaying the driver information page, press and the fol-
lowing mask will appear:
Touch the MemoCARD on the screen (if the key is not on screen,
see Page 23-21) and the following mask will appear:
BACKUP RESTORE
ERASE EXIT
For the meaning and the functions of the keys see Chapter 33 ->
Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 23-25) and changing the value (from +63 to -64) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 24-4
Accessories 24-14
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Front view
All buttons and signals are defined via the programming software (see Soft-
ware Manual).
Standard
series rear
view
A
C D
Position Function
Profibus-DP
series rear
view
A
C D
Position Function
CAN series
rear view
A
C D
Position Function
Ethernet
series rear
view
A
C D
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Calibration of The screen of VT580W is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
J11
C
1 2 3
Touch the corner indicated in the figure; then the following page appears on screen
Wait a few moments until the VT displays either the following mask or
the project page
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
J14
1
2
3 T
Introducing This paragraph relates only to the Ethernet series. The Media Access Control
the MAC (MAC) address unambiguously identifies each terminal connected in the Ether-
address net network. The terminal is acquired with the address already programmed
and is shown on the display of the terminal in the transfer page.
MAC addr:
00.0E.0E.xx.xx.xx
This operation must be carried out only with the advice of the
ESA Customer Care Department.
Terminals with no valid MAC address when switched present a mask for its
insertion. If no MAC address belonging to the terminal is available, pro-
ceed as follows:
00.0E.0E
xx.xx.xx
00.0E.0E
xx.xx.xx
Use the arrow to make the setting. Once the address has been con-
firmed the following page is displayed
MAC addr:
00.0E.0E.00.00.01
Should a wrong MAC address have been inserted contact the ESA
Customer Care Department.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The programme VTWIN must be used for the transfer (see Software Man-
reception ual), but the terminal must be prepared for reception.
and wait a few moments, alternatively use the button provided (see Page
24-21), until the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The VT is now ready to receive (refer to
Software Manual for transfer procedure). The MemoCARD appears if
the Memory Card has been inserted in the VT (see Page 24-27)
Choose the required transfer mode: MODEM if you intend to use a modem
or PC if you intend to use a serial port; touch the relevant on the display
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST: ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
The on-screen to press depends on the port you intend to use (MSP
or ASP). The VT terminal is now ready to receive (consult Software
Manual for information on the transmission procedure).
TRAN
PAGE
While displaying the driver information page, press and the fol-
lowing mask will appear:
Touch the MemoCARD on the screen (if the key is not on screen,
see Page 24-21) and the following mask will appear:
BACKUP RESTORE
ERASE EXIT
For the meaning and the functions of the keys see Chapter 33 ->
Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 24-25) and changing the value (from +63 to -64) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 25-4
Accessories 25-13
VT585W
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Front view
VT585W
All buttons and signals are defined via the programming software (see Soft-
ware Manual).
Customizing
label
1
The total thickness of the label must not exceed 125m (microme-
ters). Do not use either stiff materials or glues.
Standard
series rear
view A
Position Function
CAN series
rear view
A
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Calibration of The screen of VT585W is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
Touch the corner indicated in the figure; then the following page appears on screen
Please wait
Touch the corner indicated in the figure; then the following page appears
on screen
Touch the corner indicated in the figure; then the following page appears
on screen
Touch the corner indicated in the figure to complete the calibration pro-
cedure. Wait a few moments until the VT displays either the following
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The programme VTWIN must be used for the transfer (see Software Man-
reception ual), but the terminal must be prepared for reception.
and wait a few moments, alternatively use the button provided (see Page
25-19), until the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The VT is now ready to receive (refer to
Software Manual for transfer procedure). The MemoCARD appears if
the Memory Card has been inserted in the VT (see Page 25-26)
Choose the required transfer mode: MODEM if you intend to use a modem
or PC if you intend to use a serial port; touch the relevant on the display
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST: ##
SET CLOCK:
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST: ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
The on-screen to press depends on the port you intend to use (MSP
or ASP). The VT terminal is now ready to receive (consult Software
Manual for information on the transmission procedure).
TRAN
PAGE
While displaying the driver information page, press and the fol-
lowing mask will appear:
Touch the MemoCARD on the screen (if the key is not on screen,
see Page 25-19) and the following mask will appear:
BACKUP RESTORE
ERASE EXIT
For the meaning and the functions of the keys see Chapter 33 ->
Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 25-24) and changing the value (from +63 to -64) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
We advise this to be done at typical room temperature and with the terminal
at operating temperature (about 30 minutes after switching on and with the
screen saver disabled - see Software Manual).
Contents Page
Functions 26-4
Accessories 26-14
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Front view
All buttons and signals are defined via the programming software (see Soft-
ware Manual).
Standard
series rear
view A
C D
Position Function
Profibus-DP
series rear
view A
C D
Position Function
CAN series
rear view
A
C D
Position Function
Ethernet
series rear
view A
C D
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Calibration of The screen of VT585WB is made of resistive, sensitive glass; for this type
Touch Screen of glass to work properly it requires a calibration procedure (the terminal
is already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
J11
C
1 2 3
Touch the corner indicated in the figure; then the following page appears on screen
Wait a few moments until the VT displays either the following mask or
the project page
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
J14
1
2
3 T
Introducing This paragraph relates only to the Ethernet series. The Media Access Control
the MAC (MAC) address unambiguously identifies each terminal connected in the Ether-
address net network. The terminal is acquired with the address already programmed
and is shown on the display of the terminal in the transfer page.
MAC addr:
00.0E.0E.xx.xx.xx
This operation must be carried out only with the advice of the
ESA Customer Care Department.
Terminals with no valid MAC address when switched present a mask for its
insertion. If no MAC address belonging to the terminal is available, pro-
ceed as follows:
00.0E.0E
xx.xx.xx
00.0E.0E
xx.xx.xx
Use the arrow to make the setting. Once the address has been con-
firmed the following page is displayed
MAC addr:
00.0E.0E.00.00.01
Should a wrong MAC address have been inserted contact the ESA
Customer Care Department.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The programme VTWIN must be used for the transfer (see Software Man-
reception ual), but the terminal must be prepared for reception.
and wait a few moments, alternatively use the button provided (see Page
26-21), until the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The VT is now ready to receive (refer to
Software Manual for transfer procedure). The MemoCARD appears if
the Memory Card has been inserted in the VT (see Page 26-27)
Choose the required transfer mode: MODEM if you intend to use a modem
or PC if you intend to use a serial port; touch the relevant on the display
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST: ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
The on-screen to press depends on the port you intend to use (MSP
or ASP). The VT terminal is now ready to receive (consult Software
Manual for information on the transmission procedure).
TRAN
PAGE
While displaying the driver information page, press and the fol-
lowing mask will appear:
Touch the MemoCARD on the screen (if the key is not on screen,
see Page 26-21) and the following mask will appear:
BACKUP RESTORE
ERASE EXIT
For the meaning and the functions of the keys see Chapter 33 ->
Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 26-25) and changing the value (from +63 to -64) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
Contents Page
Functions 27-4
Accessories 27-14
Technical The following table lists the principal technical characteristics of the prod-
characteristics uct in question.
Functions The following table lists in alphabetical order all the functions of the VT in
question.
Alarm statistics
Alarms (Total/active simultaneously) 1024/256
Arc
Automatic operations 32
Backup/Restore
Bar data
Circles
Command: Hardcopy
Command: Report
Date field
Day-of-the-week field
E-keys
Equations 32
F-keys
Free terminal
Function: Disables key
Function: Go to page
Function: Macro
Function: None
Function: Reset bit permanently
Function: Sequences
Function: Sets bit permanently
Labels
Lists of texts
Message field
Page 1024
Password 10
Programmable fonts
Project images
Rectangles
Redefinable characters
Reports 128
Sequences - Random
Sequences - Start/stop
Static bitmaps
System messages
Front view
All buttons and signals are defined via the programming software (see Soft-
ware Manual).
Standard
series rear
view A
C D
Position Function
Profibus-DP
series rear
view A
C D
Position Function
CAN series
rear view
A
C D
Position Function
Ethernet
series rear
view A
C D
Position Function
Dimensions
and Cut-out
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Calibration of The screen of VT595W is made of resistive, sensitive glass; for this type of
Touch Screen glass to work properly it requires a calibration procedure (the terminal is
already calibrated when supplied), that is, the resistive area of the glass
has to be adjusted to the visible are of the display.
The procedure must be carried out with great care as the preci-
sion of the keys area depends on the calibration.
J11
C
1 2 3
Touch the corner indicated in the figure; then the following page appears on screen
Wait a few moments until the VT displays either the following mask or
the project page
The calibration procedure has finished; if the calibration has be carried out
wrongly or imprecisely, repeat the procedure.
Termination of This paragraph applies only to the CAN series. The VT in question inte-
CAN line grates the termination resistances of the serial line (typically 120 ohms)
which can be inserted by means of a jumper (preset on 1-2, line not termi-
nated). To activate the termination:
J14
1
2
3 T
Introducing This paragraph relates only to the Ethernet series. The Media Access Control
the MAC (MAC) address unambiguously identifies each terminal connected in the Ether-
address net network. The terminal is acquired with the address already programmed
and is shown on the display of the terminal in the transfer page.
MAC addr:
00.0E.0E.xx.xx.xx
This operation must be carried out only with the advice of the
ESA Customer Care Department.
Terminals with no valid MAC address when switched present a mask for its
insertion. If no MAC address belonging to the terminal is available, pro-
ceed as follows:
00.0E.0E
xx.xx.xx
00.0E.0E
xx.xx.xx
Use the arrow to make the setting. Once the address has been con-
firmed the following page is displayed
MAC addr:
00.0E.0E.00.00.01
Should a wrong MAC address have been inserted contact the ESA
Customer Care Department.
Transfer PC -> For everything to function properly, the first time the VT operator terminal
VT is switched on it needs to be correctly loaded, that is it needs to have trans-
ferred to it:
Firmware
Communication driver
Project
(Given that the transfer of the three files in practice occurs with a single
operation, it will be defined as Project transfer for the sake of simplicity.)
For this it is essential that the VT be prepared to receive the transfer. (See
also Chapter 37 -> Command area).
Preparation for The programme VTWIN must be used for the transfer (see Software Man-
reception ual), but the terminal must be prepared for reception.
and wait a few moments, alternatively use the button provided (see Page
27-21), until the VT displays the following mask
Choose the port you intend to use for the transfer (MSP or ASP); touch
the relevant on the display. The VT is now ready to receive (refer to
Software Manual for transfer procedure). The MemoCARD appears if
the Memory Card has been inserted in the VT (see Page 27-27)
Choose the required transfer mode: MODEM if you intend to use a modem
or PC if you intend to use a serial port; touch the relevant on the display
If the choose made is PC, the VT is ready to receive (see Software Manual
for transfer), if, on the other hand, you choose MODEM, the following
mask will appear
The choice should be according to the speed you intend to use for the trans-
fer (Slow=9600bit/sec or Fast=38400bit/sec), touch the relevant on the
display. The VT is now ready to receive (see Software Manual for the trans-
fer).
Information After the project has been transferred, the VT can make available informa-
relating to tion relating to what has been loaded. The information regards:
driver
Serial ports present
The name of the driver loaded
The version of the driver loaded
Network address of the VT
Last error to have occurred
ESC
To set the clock and the contrast, while displaying the above illus-
PROG
trated page, press ; the following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
ESC
To set the contrast touch the words SET CONTRAST on the display;
you will see the following mask
CONTRAST: ##
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
To set the clock touch the words SET CLOCK on the display; the
following mask appears
SET CONTRAST : ##
SET CLOCK :
ddd,dd/mm/yy
hh:mm:ss
hh:mm:ss dd/mm/yy
ESC
Use the arrow for any variation (see Chapter 36 -> Operation of
terminal with touch screen).
The on-screen to press depends on the port you intend to use (MSP
or ASP). The VT terminal is now ready to receive (consult Software
Manual for information on the transmission procedure).
TRAN
PAGE
While displaying the driver information page, press and the fol-
lowing mask will appear:
Touch the MemoCARD on the screen (if the key is not on screen,
see Page 27-21) and the following mask will appear:
BACKUP RESTORE
ERASE EXIT
For the meaning and the functions of the keys see Chapter 33 ->
Memory card.
PR ERR
COM BROKEN
An error message followed by [*] indicates that the error is not currently
present but was and has since disappeared.
ESC
When is pressed you quit the display of information regarding the
driver.
Improving To improve the color quality, adjust the contrast of the display: if the colors
display color are too dark increase the contrast; if, on the other hand, the colors are too
quality light, decrease the contrast.
Adjusting the To improve the quality of the representation on the display it may be neces-
contrast on sary to adjust its contrast. This can be done by going to the page proposed
the display (see Page 27-25) and changing the value (from +63 to -64) in evidence at
that moment. Increase the value to darken the display; to lighten it decrease
the value.
Contents Page
Label 28-2
Warnings 28-2
Notes 28-4
This chapter consists of 4 pages.
VT terminals are supplied with labels already set in the appropriate spaces.
If it is necessary to customize keys, the logo or the model the labels can be
replaced with the neutral ones supplied in kit with the terminal (only for
F-keys) or by inserting labels of other materials provided they conform
with the points set out below.
Label The label must be of a material that is flexible and does not exceed 125m
(micrometers).
Warnings Before starting to insert the customized label the following points MUST
BE observed:
Correct insertion:
Compromised
adhesion
Compromised
adhesion
The labels illustrated generate pressure that over time could cause the
keyboard to scollare.
The oversize part of the label must go under the back cover or in the
appropriate fixing points (the choice is determined by the type of VT
being used).
Back cover
Notes Here are some tips to make it easier to insert the label:
If there seems to be some resistance pull the label out and reinsert it.
If more than one label is used, insert them all at the same time.
Label 1 Label 2
Take care not to exceed the total thickness permitted (see Page
28-2 -> Label).
Do not bend the label at right angles and/or do not bend them so sharply
that they might be damaged.
Slightly bend the label lengthwise to make it stiffer.
Contents Page
The VT comes supplied with the elements necessary for mounting it within
the host container and fixing the sealing gasket giving the declared level of
IP protection.
There are three kinds of terminal: those with the gasket already in place and
the mounting within the container being secured by means of nuts, and
those where the gasket is to be fitted in the installation phase and the means
of securing are hooks and those with seal already attached which are fixed
to the container using external support.
Using nuts The figure below shows the front and back views of a VT inserted in a con-
tainer. Under the figure is to be found the sequence of operations to be car-
ried out to ensure that the fixing is correct.
Cut-out of a Pre-applied
Stud
container gasket
Using hooks The illustrations appearing below show in front and rear views the
sequence of actions for mounting a VT within a container.
Cut-out of a
Video Terminal
container
Insert the gasket in the VT the right way round as indicated by the cen-
tering notches
Fixing hook
The number and position of the hooks do not influence the fixing
procedure. The illustrations are to show the way the hooks work.
Fixing using The figure below shows the hook to use to mount those VTs requiring a
external support external to the container.
support
Hook for Cross-section
mounting terminal (1) of container
Wedge to adjust
tilt of terminal (2)
Before proceeding with the explanation of the steps required to mount the
terminal it needs to be said that the hook allows the terminal to be posi-
tioned at various heights and angles, so the exact position must be defined.
To help do this, the following figure shows the maximum movement possi-
ble from the operators view point, depending on how the tilt adjustment
wedge is positioned (intermediate positions for intermediate tilt angles).
Do not alter the original form of the mounting hook or the tilt
adjustment wedge.
A
0 0
B
0-A 120mm
0-C 620mm
Position the hook (preferably on a smooth surface) and secure using the
screws supplied. If a 3MA threaded hole is made, just use the screws,
otherwise use the washer and nut.
The tilt adjustment wedge must be positioned (position 0-A, 0-B or inter-
mediate) using the same criterion as with the previous point
Final
position
Tightening the For the best possibile grip of the basket to the container, you are advised:
fixing screws
To respect the screwing sequenze illustrated.
Using nuts
6
1 4 1 4
3 2 3 2
5
8 6 10 6 8
1 4 1 4
3 2 3 2
5 7 7 5 9
Using hooks
1 4
1 4
3 2
3 2
10 6 8
1 6 4
1 4
3 2
3 5 2
7 5 9
Contents Page
All VTs communicate with other devices by means of serial and/or parallel
communication ports. We list on the following page the individual ports
with the respective type of communication and the function of the connec-
tion pins.
General notes Serial communication is particularly prone to disturbances. To limit the influ-
ence of these disturbances it is necessary to use good quality shielded cables.
The table immediately below lists the characteristics of the cable we recom-
mend for serial connection.
Always:
Find the shortest route
Lay disturbed cables separately
Necessary To have the communication ports (MSP, ASP, ASP-9 or ASP-8) function-
steps ing properly, certain pins on the VT side need to be jump-connected. The
ASP-15L port requires no jumpers.Which pins need to be connected
depends on which communication standard is to be used (RS232, RS422,
RS485 or C.L.TTY-20mA).
MSP serial The MSP (Multi Serial Port) is present on all VTs and is used to connect other
port devices including the PC used to transfer the project. It consists of a connector
(D-Sub 25 pin female) and can communicate using RS232, RS422, RS485 and
C.L. (TTY-20mA).
MSP
Multi Serial Port
25 pin female
Pin 16 does not provide for commuting any kind of load (coils etc.);
an input disturbance at Pin 16 can cause the VT and therefore also
the industrial process itself to malfunction.
ASP serial The ASP (Auxiliary Serial Port) consists of a D-Sub 15 pin female connec-
port tor and can communicate using RS232 and RS485.
ASP
Auxiliary Serial Port
15 pin female
Pin 13 does not provide for commuting any kind of load (coils
etc.); an input disturbance at Pin 13 can cause the VT and there-
fore also the industrial process itself to malfunction.
ASP-15L serial The ASP (Auxiliary Serial Port) consists of a D-Sub 15 pin female connec-
port tor and can communicate using RS232 and RS485. Unlike the ASP it does
not carry all signals.
ASP-15L
Auxiliary Serial Port
15 pin female
ASP-9 serial The ASP-9 serial port (Auxiliary Serial Port) consists of a D-Sub 9 pin
port male connector and can communicate using RS232.
ASP-9
Auxiliary Serial Port
9 pin male
ASP-8 serial The ASP-8 (Auxiliary Serial Port) consists of a Minidin 8 pin female con-
port nector and can communicate using RS232.
ASP
Auxiliary Serial Port
8 pin female
Pin 8 does not provide for commuting any kind of load (coils etc.);
an input disturbance at Pin 8 can cause the VT and therefore also
the industrial process itself to malfunction.
LPT parallel The LPT parallel port consists of a D-Sub 25 pin female connector. It is
port used to connect directly with the printer.
LPT
25 pin female
Ethernet port The Ethernet port comprises an RJ45 8 pin female connector and is dedi-
cated to creating network links with other terminals, with PCs and any other
device that supports this standard.
Ethernet
RJ45
8 pin female
Led
Meaning
ACT LINK
Cable disconnected, interrupted or
Off Off
participants off
NETWORK1
9 pin female
OUT
Pin 5 does not provide for commuting any kind of load (coils etc.);
an input disturbance at Pin 5 can cause the VT and therefore also
the industrial process itself to malfunction.
NETWORK2
9 pin male
IN
9 pin female
Pin 6 does not provide for commuting any kind of load (coils etc.);
an input disturbance at Pin 6 can cause the VT and therefore also
the industrial process itself to malfunction.
CAN port The communication port consists of a 5 pin female terminal block (optoiso-
lated interface).
CAN
5 pin female
RS485 serial The communication port consists of a 9-pin male D-Sub connector.
port
9 pin male
PC/VT serial The communication port consists of a 9-pin male D-Sub connector for con-
port necting a PC or VT in RS232.
PC/VT
9 pin male
PC <-> VT To transfer the communication firmware, the communication driver and the
connection project the VT must be connected to the PC (see Software Manual) and can
be done using either Serial or Modem.
RS232
Modem
PC side VT side
9 pin female CVCOM11102 25 pin male
TxD 3 3 RxD
RxD 2 2 TxD
GND 5 7 GND
25
RTS 7 4 RTS
CTS 8 5 CTS
DSR 6 15
DTR 4 18
Max. 15 m.
The cable in the above figure, together with the relevant adapters, can be
used for all serial port connections of the VT. Below we list the adapters
and the combinations necessary for the various connections.
CVCOM25F9M CVAD25M9M
CVAD259 CVAD2515
CVCOM25F8M
CVAD259 CVAD2515
The table shows how to combine adaptors and cables connection to the var-
ious ports.
Contents Page
Telephone
line
AT commands Modems need a series of commands, some of which can be used to set the
to be sent Modem. The table below lists the commands (supported by the majority of
modems) necessary for setting the Modem as the VTs require. The com-
mand also comprises the parameter required.
Command Effect
AT&H0
or Disables the RTS/CTS flow check.
AT&K0
AT&R1 The modem ignores the RTS and considers it always active.
Set the volume of the modem, where n can have a value from
ATLn
1 to 3 (1=Min - 3=Max).
Sending To send the commands connect the modem to the serial port of the PC
commands using a standard serial cable.
RS232
Once the connection and access are established the modem runs the Hyper-
Terminal program (supplied with the PCs operating system) by clicking on
Start > Programs > Accessories > Communications > HyperTerminal
Set as in fig.
If the message OK
appears it means the
connection is active.
If the modem is switched off the settings are lost. If they need to be
kept, the settings can be saved using the appropriate command.
Contents Page
In order to simplify the connection with the other devices you should use
the VTHCB board (optional). This interface transforms the signals from the
terminal serial line into the ESA standard (MSP, ASP-15L), allowing to use
standard connection cables (see Chapter 40 -> Connessione del Terminale
ai Dispositivi).
The serial line used directly on the cable DOES NOT allow the use
of ESA standard connection cables (see Chapter 40 -> Connes-
sione del Terminale ai Dispositivi).
VT DEVICE
Side Side
SHD
COM 1
RTS RS232 OUT - MSP
Signal GND
SHD
VT DEVICE
Side Side
SHD
COM 1
RTS RS232 OUT - MSP CTS
COM 2
Signal GND
SHD
RS485 connection:
VT DEVICE
Side Side
SHD
RX RS232 IN - MSP
COM 1
CTS RS232 IN - MSP
COM 2
Signal GND
SHD
VT Side
25 pin female
RX RS232 IN - MSP
2 TxD
RTS RS232 OUT - MSP 3 RxD
7 GND
CTS RS232 IN - MSP
Signal GND
Standard For the connection of board VTHCB, please refer to its respective chapter
series (seeChapter 33 -> Accessori per terminali video).
connections
with VTHCB
CAN series The CAN terminal is not expected to be used with the accessory board
connections VTHCB, which is why connections must be carried out directly on the
cable.
VT Side
25 pin female
Signal GND
Enabling button
NC1 NC1
NC1
Pushing C1 C1
C1
C2 C2
C2
NC1 NC1
Releasing C1 C1
C2 C2
Contents Page
Protfilm4/6/6H/10/12 33-22
The video terminals are made to take a series of accessories that increase
their capacity and/or functionality. This chapter shows how these accesso-
ries relate to the various products. The table below shows which terminals
will take which accessories.
Protfilm12 VT585W
VT505, VT60, VT150W5, VT160W, VT170W, VT190W, VT300W4-5, VT310W4, VT320W4, VT330W4, VT155W5,
Interbus-S module
VT185W5, VT505W5, VT515W5, VT525W5, VT555W5, VT56xW, VT575W, VT580W, VT585W4, VT585WB, VT595W
VT505, VT60, VT150W5, VT160W, VT170W, VT190W, VT300W4-5, VT310W4, VT320W4, VT330W4, VT155W5,
Profibus-DP module
VT185W5, VT505W5, VT515W5, VT525W5, VT555W5, VT56xW, VT575W, VT580W, VT585W4, VT585WB, VT595W
VT505, VT60, VT150W5, VT160W, VT170W, VT190W, VT300W5, VT310W, VT320W, VT330W, VT155W5, VT185W5,
Connection card for PC-NET
VT505W5, VT525W5, VT515W5, VT555W5, VT56xW, VT575W, VT580W, VT585W, VT585WB, VT595W
VT505, VT60, VT150W5, VT160W, VT170W, VT190W, VT300W4-5, VT310W4, VT320W4, VT330W4, VT155W5,
Adapter for external CAN network
VT185W5, VT505W5, VT525W5, VT515W5, VT555W5, VT56xW, VT575W, VT580W, VT585W4, VT585WB, VT595W
Notes:
1 - Already present on purchase A - For terminals up to Rev. 3
2 - To be used as backup B - For terminals up to Rev. 4
3 - To be used as expansion C - For terminals from Rev. 4
4 - Can be fixed to back cover D - For terminals from Rev. 5
5 - Not applicable in the case of CAN series terminals
-- : not connectable
Notes:
1 - Already present on purchase A - For terminals up to Rev. 3
2 - To be used as backup B - For terminals up to Rev. 4
3 - To be used as expansion C - For terminals from Rev. 4
4 - Can be fixed to back cover D - For terminals from Rev. 5
5 - Not applicable in the case of CAN series terminals
-- : not connectable
1/2AA Battery The function of the battery is both to maintain the contents of the RAM
(work recipes) and to keep the internal clock going when there is no power
supply.
Battery to be used
Lithium 3.6V AA
The battery needs to be changed either when the Battery LED (on the VT
keyboard) comes on or when indicated by the Chapter 37 -> Status
area for the terminal. Failure to change the battery will lead to the con-
tents of the data memory being lost.
The battery must be substituted with the VT power off. At this point a
high capacity condenser will momentarily preserve the RAM memory
information (information is typically retained for 24 hours).
Cell battery The function of the battery is both to maintain the contents of the RAM
(work recipes) and to keep the internal clock going when there is no power
supply.
Battery to be used
The battery needs to be changed either when the Battery LED (on the VT
keyboard) comes on or when indicated by the Chapter 37 -> Status
area for the terminal. Failure to change the battery will lead to the con-
tents of the data memory being lost.
The battery must be substituted with the VT power off. At this point a
high capacity condenser will momentarily preserve the RAM memory
information (information is typically retained for 24 hours).
Flash module
ESA
For more information regarding functions and technical details see Page
33-13 -> Memory card.
Insert the spacers (A) in the holes (B) taking care which way round they
are put; then insert the flash module into the terminal.
ESA
ESA
To extract the connector (A), pull lightly, then pull on the corners, one
by one, and at the same time press down on tyhe head of the spacer (B).
ESA
A B
For information regarding the operation of the card, see Page 33-16 ->
Using the Memory Card:.
Fixing hook
for Hand Held
Do not alter the original form of the mounting hook or the tilt
adjustment wedge.
Various ways of fixing the device are possible. For details see Chapter 29
-> Fixing using external support.
Interface for
connecting
Hand Held
with
MSP/ASP-15L
VTHCB
The table below lists the principal technical characteristics of the product
under discussion.
Connector block
Number of connection points (X1/X2) 30/14
Section of connectable wire 0,05-1,5 mmq (30-16AWG)
Stripped length of connectable wire 5-6 mm
Technical data
Power supply 24Vdc (18..32Vcc)
Power absorbed at 24Vdc 0,5W
Protection level --
Operating temperature 0..50C
Storage and transportation temperature -20..+60C
Humidity (non-condensing) 85%
Weight 250gr
Dimensions
External W x H x D [mm] 136 x 82 x 54,5
Cut-out W x H [mm] --
See Chapter 2 -> Power Supply for connecting the power supply.
Dimensions:
HCB
DIN EN 50022
A
B
DIN EN 50035
A
B
DIN EN 50045
A
B
Hook the upper part of the plate onto the DIN rail.
Press the device in the direction indicated. (Arrow A)
To make it easier to hook on, pull the spring-clip in the direction indi-
cated. (Arrow B)
Connection cable :
Connection Connection
VT <-> VTHCB VTHCB <-> Electrical panel
Connector Connector Internal
Command and/or signal unit Cable from VT
block X1 block X2 switchboard
Yellow-Green 19
Red 1
Black 16
Pink 13
Other signals relating to opera- White 28
tion of board Blue 29
--
Green 30
Yellow 17
White-Grey 14
Yellow-White 15
Blue-Brown 5
VT525H only
White-Red 20
NC1 White-Black 6 7 See electrical
System shut-down NC2 Brown-Pink 21 14 lay-out for end user
button NC3 White-Blue 22 13
NC4 Brown-Grey 7 6
C1 Brown-Red 23 12
NC1 Yellow-Brown 8 5
Enabling button
C2 Violet 24 11
NO2 Green-Brown 9 4
NO Green-White 11 2
Black button
C White-Pink 10 3
Luminous green NO Red-Blue 26 9
button C Grey-Pink 25 10
- Brown 27 8
Bulb
+ Grey 12 1
Never alter the length of the connection cable as this may cause
malfunctioning.
Internal
swirtchboard
circuit
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
VTHCB
Memory card
This is a removable device in which you can store the information con-
tained in the VT terminal.
The types of information that can be stored on the Memory Card are:
Firmware
Project
Recipes
Alarm history buffer
Start-up language
Password
The following table lists the principal technical characteristics of the prod-
uct in question.
Technical data
Memory 4Mb or 8Mb
Insert the memory card in its housing, checking that it is the right way
round.
Contacts for
electrical con-
nection
Once the memory card fits in the groove, press lightly as shown in the
figure till you feel it click into place.
Press lightly on the fixing tab of the memory card (see figure below) in
the direction of the arrow.
Once the memory card is unhooked (see figure) remove it following the
direction of the arrow.
The graphic form of the page, the contents of the menus and their meaning
depend on the type of terminal being used.
Erase
Restore
Backup
Exit
Erase:
Restore:
Backup:
Exit:
Makes it possible to quit the menu page and return to the pre-
vious page.
Backup ALL
Backup FW/PRJ
Backup RECIPES
Backup ALARMS
Restore ALL
Restore FW/PRJ
Restore RECIPES
Restore ALARMS
Exit
Backup ALL:
This function allows you to clear the memory card of its data,
all its contents being definitively lost, and then to transfer to it
all the data contained in VT memory.
Backup FW/PRJ:
This function allows you to clear the relevant section of the mem-
ory card of its data, all its contents being definitively lost, and then
to transfer to it the project (Start-up language and Password
included) and the firmware contained in VT memory.
Backup RECIPES:
Backup ALARMS:
Restore ALL:
Restore FW/PRJ:
This function allows you to transfer the project and the firm-
ware contained in the memory card into the VT.
Restore RECIPES:
Restore ALARMS:
Exit:
Makes it possible to quit the menu page and return to the pre-
vious page.
Memory
module
This is a removable device capable of saving the VTs firmware and its
project.
The following table lists the principal technical characteristics of the prod-
uct under discussion.
Technical data
Memory 512Kbytes
Integrated
Interbus-S
module
NETWORK2
D-SUB
NETWORK1
D-SUB
The integrated module shown above allows you to connect a number of ter-
minals in an Interbus-S network. For more details concerning the network
connection of the terminals see Chapter 34 -> Network connection.
Insert the spacers (A) into the holes (B), checking the they are the right
way round; now insert the module into the terminal.
A
B
B A
D-SUB D-SUB
NETWORK1 NETWORK2
Set the network address using the appropriate Dip-Switch (not present on
this module).
Replace the back cover.
Reconnect the power supply of the VT.
Integrated
Profibus-DP
module
ON
1 2 3 4 5 6 7 8
NETWORK1
D-SUB
The integrated module shown above enables a number of terminals to be
connected in a Profibus-DP network. (For further details on how terminals
are connected in the network see Chapter 34 -> Network connection.)
The NETWORK1 communication port consists of a 9-pin female D-Sub
connector (see Chapter 30 -> Profibus-DP port).
See Page 33-19 for how to insert the module in the VT.
RS485 Serial
module
NETWORK1
D-SUB
See Page 33-19 for how to insert the module into the VT.
Protfilm4/6/6H/
10/12
201.0
160.0
149.0
94.0
PROTFILM4 PROTFILM6
250.0
201.0
139.0
PROTFILM6H
187.0
PROTFILM10
279.0
206.0
PROTFILM12
Remove any trace of dirt or grease from the terminal using denaturized
ethyl alcohol
Dry the area thoroughly
Locate the adhesive part of the transparent film
Position the film near the upper edge and smooth it down delicately
VT155/185W VT505/515/525/555/56xW
VT575W VT580W
VT585W VT585WB
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
VT595W VT505/525H
VT155/185W VT505/515/525/555/56xW
VT575W VT580W
VT585W VT585WB
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
VT595W VT505/525H
VT155/185W VT505/515/525/555/56xW
VT575W VT580W
VT585W VT585WB
F1 F6
F2 F7
F3 F8
F4 F9
F5 F10
VT595W VT505/525H
Interbus-S and
Profibus-DP
card
The casing is the same both for the Interbus-S and the Profi-
bus-DP networks; a label is attached to indicate which network is
contained.
The table below lists the principal technical characteristics of the product
under discussion.
Technical data
Power supply 24Vdc (18..32Vdc)
Power absorbed at 24Vdc 3W
Protection level --
Operating temperature 0..50C
Storage and transportation temperature -20..+60C
Humidity (non-condensing) 85%
Weight 800gr
Dimensions
External W x H x D [mm] 48,8 x 107,2 x 139,4
Cut-out W x H [mm] --
The device incorporates the Interbus-S and Profibus-DP network cards (see
Page 33-19 and Page 33-21 for information); it also contains a power sup-
ply card with a communication port composed of a 9 pin male D-Sub con-
nector for connecting a PC or VT in RS232 (see Chapter 30 -> PC/VT
serial port).
The external power supply for this card can also come via a 4-pin connector
or a jack.
See Chapter 2 -> Power Supply for connecting the power supply.
DEVICE VT Side
Side MSP
9 pin female 25 pin male
TxD 3 3 RxD
RxD 2 2 TxD
GND 5 7 GND
25
4 RTS
5 CTS
15
18
Max. 15 m.
DEVICE VT Side
Side ASP-9
9 pin female 9 pin female
TxD 3 2 RxD
RxD 2 3 TxD
GND 5 5 GND
7 RTS
8 CTS
Max. 15 m.
DEVICE VT Side
Side ASP
9 pin female 15 pin male
TxD 3 2 RxD
RxD 2 3 TxD
GND 5 7 GND
10 RTS
11 CTS
Max. 15 m.
DEVICE PC
Side Side
9 pin female 9 pin female
TxD 3 2 RxD
RxD 2 3 TxD
GND 5 5 GND
7 RTS
8 CTS
6 DSR
4 DTR
Max. 15 m.
DEVICE PC
Side Side
9 pin female 25 pin female
TxD 3 3 RxD
RxD 2 2 TxD
GND 5 5 GND
7 RTS
8 CTS
6 DSR
20 DTR
Max. 15 m.
Dimensions:
The device is supplied with a special molded plate for attaching to the DIN
rail. The following figure shows how to fit the plate to the device.
Spring clip
Connection
card for
PC-NET
The table below lists the principal technical characteristics of the product
under discussion.
Technical data
Power supply 24Vdc (18..32Vdc)
Power absorbed at 24Vdc 3W
Protection level --
Operating temperature 0..50C
Storage and transportation temperature -20..+60C
Humidity (non-condensing) 85%
Weight 800gr
User memory
Project [Bytes] 16K
Definible groups 255*
Objects per group 255*
Simultaneously active groups 10
Dimensions
External W x H x D [mm] 48,8 x 107,2 x 139,4
Cut-out W x H [mm] --
See Chapter 2 -> Power Supply for connecting the power supply.
DEVICE PC
Side Side
9 pin female 9 pin female
TxD 3 2 RxD
RxD 2 3 TxD
GND 5 5 GND
7 RTS
8 CTS
6 DSR
4 DTR
Max. 15 m.
DEVICE PC
Side Side
9 pin female 25 pin female
TxD 3 3 RxD
RxD 2 2 TxD
GND 5 5 GND
7 RTS
8 CTS
6 DSR
20 DTR
Max. 15 m.
Dimensions:
Various ways of fixing the device are possible. For details see Page 33-32,
Page 33-32 and Page 33-33.
Adapter for
external CAN
network
The table below lists the principal technical characteristics of the product
under discussion.
Technical data
Power supply 24Vdc (18..32Vdc)
Power absorbed at 24Vdc 5W
Protection level --
Operating temperature 0..50C
Storage and transportation temperature -20..+60C
Humidity (non-condensing) 85%
Weight 580gr
Dimensions
External W x H x D [mm] 152,4 x 107,2 x 31,7
Cut-out W x H [mm] --
See Chapter 2 -> Power Supply for connecting the power supply.
DEVICE VT Side
Side MSP
8 pin male 25 pin male
TxD 2 3 RxD
RxD 1 2 TxD
GND 7 7 GND
RTS 4 25
CTS 5 4 RTS
5 CTS
5 15
8
7 4
2 MiniDin
6
1 Front 18
3
View
Max. 15 m.
Dimensions:
The device is supplied with a special molded plate for attaching to the DIN
rail. The following figure shows how to fit the plate to the device.
Spring clip
A
B
20 key serial
keyboard
The following table lists the principal technical characteristics of the prod-
uct in question.
Keyboard
Non-customizable function keys --
Customizable function keys 20
Function key LEDs 20
Alphanumeric keys --
Operational keys --
Operational key LEDs --
Diagnostic LEDs --
Technical data
Power supply --
Power absorbed at 24Vdc --
Protection level IP65 (front-end)
Operating temperature 0..50C
Storage and transportation temperature -20..+60C
Humidity (non-condensing) 85%
Weight 550gr
Dimensions
External W x H x D [mm] 148 x188 x 27
Cut-out W x H [mm] 114 x 174
Front view:
Key Function
2 F-keys
Rear view:
Position Function
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
The explanation of the connection method applies to all terminals with this
accessory (See Page 33-2).
A
B
When supplied the cable will already be fixed to the keyboard at point A,
leaving point B to be connected at the other end.
Blank
keyboard
The following table lists the principal technical characteristics of the prod-
uct in question.
Technical data
Power supply --
Power absorbed at 24Vdc --
Protection level IP65 (front-end)
Operating temperature 0..50C
Storage and transportation temperature -20..+60C
Humidity (non-condensing) 85%
Weight 100gr
Dimensions
External W x H x D [mm] 148 x188
Cut-out W x H [mm] 114 x 174
Front view:
This accessory allows the user to fit and wire buttons. Any kind of key-pad
can be used.
To fix the sealing gasket and secure the VT to the container see Chapter 29
-> Mounting the terminal within the container.
Contents Page
Profibus-DP 34-3
Interbus-S 34-10
ESA-Net 34-14
ETHERNET 34-21
CAN 34-24
This chapter consists of 28 pages.
Contents Page
VT terminals have two ways of exchanging data with the network master:
one called ESA Profile and the other known as Standard Profile. In practice
the difference lies in the size of the I/O area: with ESA Profile the I/O area
is 32bytes + 32bytes and is handled by a FB (Function Block) (not available
on all devices) that has the task of allowing the VT read and write access to
all the data areas of the device; the Standard profile can use an I/O area of
up to 128bytes + 128bytes, corresponding to the maximum data area
dimensions visible to the VT.
A network can contain more than one master and more than one slave,
while there can only be one configurator.
The slave address of the VT must coincide with the network configuration.
ON
1 2 3 4 5 6 7 8
D-SUB
Profibus-DP The slave VTs are seen generally as dedicated areas of memory in the
(ESA profile): PLCs I/O area, or alternatively in other data areas made accessible by the
VT operation configurator of the master, which are used by the PLC and VT to exchange
data. The size of the I/O area of each VT participating in the network is
defined by the user with a 4 to 16 word limit (8-32byte).
Note that the greater are the dimensions of the I/O area the faster the han-
dling of the information, though this also means a greater effort on the part
of the CPU of the PLC and thus an increase in the scanning time.
Profibus-DP There are 4 types of software that play a part in configuring the network:
(ESA profile):
Configuration VTWIN
software FB
File with extension GSD
Configuration software for network master
VTWIN:
The parameters that must be set in the VTWIN project of every ter-
minal connected in the network are:
FB:
Profibus-DP Below is a logical diagram of the VT <-> Profibus-DP (ESA profile) con-
(ESA profile): nections. The diagram indicates how and at what level the FBs supplied by
Logical ESA interact with the system. The FB INIT takes care of the initial config-
diagram uration of the system (input and output areas, etc.), while the FB DRIVER
takes care of the data exchange between the PLC memory and the VTs, and
viceversa. The number of FB calls within the PLC must be equal to the
number of VTs connected in the system.
PLC BUS VT
VT#1
PARAMETRIZED PARAMETRIZED
PROFIBUS-DP
FB INIT FB DRIVER
INTEG RATED
MODULE
ESA HM I ESA HMI
OR
PROFILE PROFILE
Supplied by Supplied by PROFIBUS-DP
ESA elettronica ESA elettronica MODULE
LENGTH
8-32 BYTES O UTPUT
INPUT
I/O
GSD File LENGTH
8-32 BYTES
LENGTH
8-32 BYTES INPUT
OUTPUT
VT#n
PARAMETRIZED PARAMETRIZED
PROFIBUS-DP
FB INIT FB DRIVER
INTEG RATED
MODULE
ESA HM I ESA HMI
OR
PROFILE PROFILE
Supplied by Supplied by PROFIBUS-DP
ESA elettronica ESA elettronica MODULE
LENGTH
8-32 BYTES O UTPUT
INPUT
I/O
GSD File LENGTH
8-32 BYTES
LENGTH
8-32 BYTES INPUT
OUTPUT
ESA module
All VTs
Profibus-DP
Profibus-DP The slave VTs are seen generally as dedicated areas of memory in the
(Standard): VT PLCs I/O area, or alternatively in other data areas made accessible by the
operation configurator of the master, which are used by the PLC and VT to exchange
data. The size of the I/O area of each VT participating in the network is
defined by the user with a 4 to 64 word limit (8-128byte).
Profibus-DP There are 3 types of software that play a part in configuring the network:
(Standard):
Configuration VTWIN
software File with extension GSD
Configuration software for network master
VTWIN:
The parameters that must be set in the VTWIN project of every ter-
minal connected in the network are:
PLC MASTER in
DATA PROFIBUS-DP
MEMORY
VT#1
PROFIBUS-DP
INTEGRATED
MODULE
OR
PROFIBUS-DP
MODULE
LENGTH
8-128 BYTES OUTPUT
INPUT
I/O
GSD File LENGTH
8-128 BYTES
LENGTH
8-128 BYTES INPUT
OUTPUT
VT#n
PROFIBUS-DP
INTEGRATED
MODULE
OR
PROFIBUS-DP
MODULE
LENGTH
8-128 BYTES OUTPUT
INPUT
I/O
GSD File LENGTH
8-128 BYTES
LENGTH
8-128 BYTES INPUT
OUTPUT
ESA Module
All VTs
Profibus-DP
Master
A
B B B A
Slave
As can be seen from the above diagram the connections for devices at either
end of the line (A) are different from the internally positioned ones (B).
Indeed, the connectors at A have inside them the termination resistances of
the line. There follow the types of connection existing within the connec-
tors.
TxRx+
6 P5V 3
(B)
470
1/4 W TxRx-
TxRx+
3 8
(B) (A)
220
1/4 W
TxRx-
8
(A)
470
1/4 W
5 GND
Use the materials listed in the table below when making connection cables.
6ES7972-0BA10-0XA0
6ES7972-0BB10-0XA0
6ES7972-0BB40-0XA0
6GK1500-0EA00
103 648
103 658
103 663
103 649
Erni www.erni.com
103 659
104 329
104 577
104 322
For further details contact the retailer and/orvisit the appropriate WEB site.
Interbus-S: VT The slave VTs are seen generally as dedicated areas of memory in the
operation PLCs I/O area, or alternatively in other data areas made accessible by the
configurator of the master, which are used by the PLC and VT to exchange
data. The size of the I/O area of each VT participating in the network is 4
words (8byte).
Interbus-S: There are 3 types of software that play a part in configuring the network:
Configuration
software VTWIN
FB
Configuration software for network master
VTWIN:
The parameters that must be set in the VTWIN project of every ter-
minal connected in the network are:
FB:
Interbus-S: Below is a logical diagram of the VT <-> Interbus-S connections. The dia-
Logical gram indicates how and at what level the FBs supplied by ESA interact
diagram with the system. The FB INIT takes care of the initial configuration of the
system (input and output areas, keys area, etc.), while the FB DRIVER
takes care of the data exchange between the PLC memory and the VTs, and
viceversa. The number of FB calls within the PLC must be equal to the
number of VTs connected in the system.
PLC BUS VT
VT#1
PARAMETRIZED PARAMETRIZED
INTERBUS
FB INIT FB DRIVER
INTEGRATED
MODULE
ESA HM I ESA HM I
OR
PROFILE PROFILE
Supplied by Supplied by INTERBUS
ESA elettronica ESA elettronica MODULE
LENGTH
8 BYTES OUTPUT
INPUT
I/O
LENGTH
8 BYTES
LENGTH
8 BYTES INPUT
OUTPUT
VT#n
PARAMETRIZED PARAMETRIZED
INTERBUS
FB INIT FB DRIVER
INTEGRATED
MODULE
ESA HM I ESA HM I
OR
PROFILE PROFILE
Supplied by Supplied by INTERBUS
ESA elettronica ESA elettronica MODULE
LENGTH
8 BYTES OUTPUT
INPUT
I/O
LENGTH
8 BYTES
LENGTH
8 BYTES INPUT
OUTPUT
ESA Module
All VTs
Interbus-S
ESA Module
All VTs
Interbus-S
Interbus-S: Below is a diagram of the connections between the VTs and the devices in
Connection Interbus-S network.
In
Master
Out
A
B
Slave
Parameter n stands for the maximum number of terminals that can be con-
nected in the network, which depends on the size of the memory available
in the master device for the input and output of process data. Each VT con-
nected occupies 64 bits for the data input area and 64 bits for the process
data output; thus
Connector A Connector B
D-Sub 9 pin male D-Sub 9 pin female
green
/DO2 6 6 /DO1
DO2 1 yellow
1 DO1
pink
/DI2 7 7 /DI1
Use the materials listed in the table below when making connection cables.
Phoenix 27 18 28 0 www.phoenixcontact.com
For further details contact the retailer and/orvisit the appropriate WEB site.
27 58 47 3
Phoenix www.phoenixcontact.com
27 58 48 6
103 650
103 651
103 661
104 319
For further details contact the retailer and/orvisit the appropriate WEB site.
ESA-Net: VT To help clarify the concept of ESA-Net, we offer the data-flow diagram
operation below showing how a terminal assumes the function of client, server and
server/client.
D D D
V VP V VP V VP V
1 2 3 4
MAX. 32 Participants
8 7 6 5
V V VP V VP
D D
In the ESA-Net network the server terminal is the one that makes all or
some of the variables available to the other terminals; these variables are
called Public Variables.
The client terminal is the one that uses the public variables made available
by the server terminal. The terminal that uses public variables and, in its
turn, makes others available is known as the server/client. Generally, the
client terminal has no device of any kind connected.
The area colored green (VP) represents the public variables, the area col-
ored yellow (V) represents the variables; the device is indicated schemati-
cally in violet (D). The two central rings, one represented by a continuous
red line indicates the VTs response to a request (the dotted lined traced in
blue indicates the request for information.
A network can have more than one server, more than one client and more
than one server/clients, the total being 32 terminals.
The network participants must each have a different address; the address of
the terminal is configured using the VTWIN (see Software Manual).
ESA-Net: Since serial communications are highly subject to disturbances, the follow-
Connecting ing advice should be followed to reduce as much as possible such prob-
the terminals lems:
It is absolutely necessary to use a fully shielded twisted serial cable, with
a pair of conductors having a minimum section of 0.22 mm and a char-
acteristic impedance of 120 Ohms.
It is absolutely necessary to use a fully shielded connector.
The termination resistances must be placed exclusively at the physical
extremes of the ESA-NET network.
Insert the polarization resistances of the appropriate value (typically 470
Ohms).
The shield of the cable must be soldered or mechanically connected to
the metal shells of the connectors that are connected subsequently to the
VTs in the network.
The table below shows the three connectors that can be used (MSP - ASP -
Field network) for ESA-NET network connections alongside the various
types of wiring according to position held within the network.
VCC 16
470
1/4 W
TxRx+ 22
220
MSP - Connection: type A 1/4 W
TxRx- 10
470
25-pin connector with polari- 1/4 W
GND 7
zation and termination resi-
25
stances.
RTS 4
CTS 5
15
18
TxRx+ 22
120
MSP - Connection: type B 1/4 W
TxRx- 10
TxRx+ 22
25-pin connector.
GND 7
25
RTS 4
CTS 5
15
18
VCC 13
470
1/4 W
ASP - Connection: type D TxRx+ 8
220
1/4 W
15-pin connector with polari- TxRx- 15
470
zation and termination resi- 1/4 W
stances. GND 7
RTS 10
CTS 11
RTS 10
CTS 11
RTS 10
CTS 11
There follows a table to use when making the ESA-NET network cable. To
use this table proceed as follows:
the layout of the VTs to be connected in the network;
define the port to be used for the network connection of each VT;
identify which VTs are physically at the extremes of the network;
specify which of the terminals at the extremes of the network will be first
and which last.
Beginning End
Extremes
#1 #2 #n-1 #n
Field
MSP ASP ASP
network
If, for any reason, the extremes are connected by a Field network
connector, one of the intermediate VT connections must still be
type A or D (depending on which connector is available).
The following page shows the cable needed for the connection as in the fig-
ure using 3 VT terminals.
16
470
1/4 W
TxRx+ 22
220
1/4 W
TxRx- 10
VT1 connection using 470
25 pin MSP 1/4 W
GND 7
25
RTS 4
CTS 5
15
18
TxRx+ 8
Connection using
TxRx+ 3
9 pin 120
RS485 serial module 1/4 W
(For this option see Chapter 33 -> TxRx- 8
RS485 Serial module)
This software requires that you set parameters that coincide one with the other.
VTWIN:
The parameters that need to be set in the VTWIN project of each ter-
minal connected in the network are:
ETHERNET VT terminals equipped with the right interface can be connected in a net-
work with other devices functioning by means of Transfer Control Proto-
col/Internet Protocol (TCP/IP).
The advantage of the Ethernet connection lies in the high speed of data
exchange it gives, (from 10Mbit/s to 100Mbit/s depending on the device
connected); secondly cabling is simplified indeed, the VT does not need
to be connected directly to the device but they can be interconnected using
a network concentrator; in addition, the number of possible network partic-
ipants is so high as to be practically limitless.
ETHERNET: There are two types of software that come into play when configuring this
Configuration network:
software
VTWIN
Software for configuring the device
These softwares require the setting of parameters that depend on the type of
network to which the terminal is connected.
VTWIN:
The parameters that need to be set in the VTWIN project of each ter-
minal connected in network are as follows:
IP Address
Subnet Mask
Any other parameters depending on the device connected
ETHERNET: The figure below shows two examples of connections: the first example
Connections shows a connection between a VT and a device using a direct connection,
while the second example shows a connection between VT and device
using a company network.
VT Device
Direct connection
Crossed Ethernet cable
Tx+ 1 1 Tx+
Rx+ 3 3 Rx+
Tx- 2 6 Rx-
Rx- 6 2 Tx-
8 8
7 7
6 6
5 5
4 4
3 3
2 2
1 1
Front Front
View View
The first three numbers of the IP address assigned must be the same as
those of the device with which it is to be connected, the fourth number must
be different. Example VT - 192.168.100.1, Device - 192.168.100.5
VT Device
Ethernet
If the connection and the settings have been executed correctly, response
strings will appear that contain the IP address requested. If, on the other
hand, what appears are strings indicating failure of the request this means
that there are connection problems; in this case the whole procedure includ-
ing the connection cable must be checked.
The CAN network differs from other types of network in its low cost, high
level performance in difficult electrical conditions, exceptional ability to
respond in real time and operational simplicity.
This type of network has a master/slave structure. The master device takes
care of initializing and configuring the slave stations, and further with con-
trolling the communication state of the devices in the network. The slave
devices are concerned exclusively with exchange of information. To be
able to communicate, the slave devices must be initialized (operational
state) and parameterized by the master device.
CAN: VT The VTs communicate with the devices using logical channels to which
functioning in there correspond virtual communication lines which are independent of one
CAN network another and definible using certain parameters.
SDO channels concern themselves with the exchange of parameters for set-
ting, configuring and other information regarding the setting of the device.
PDO channels, on the other hand, concern themselves exclusively with
exchanging information related to the process underway.
The network participants must each have a different address; the address of
the terminal is configured using VTWIN (see Software Manual).
CAN: There is only one type of software that can effect the configuration of this
Configuration network:
software
VTWIN
This software requires the setting of parameters that coincide with one
another.
CAN: The figure below shows the connection of VT with devices in a CAN net-
Connection work, in a master VT and slave formation.
Master
A
B B B A
Slave
Master
A
B B B A
Slave
Theoretically the network admits 128 devices, but the real limit depends on
how many logical channels are activated. The maximum number of chan-
nels is 64 SDO and 64 PDO.
Example:
Suppose each devices possess 2 SDOs and 3 PDOs. If all are activated, the
maximum number of the devices that can be connected is 21, i.e. the overall
number of channels admissible divided by the number of PDO channels for
each device (because the PDO channels, being more numerous, determine
the limit).
As can be seen from the figure above, the connections for the devices at the
ends of the line (A) are different from the internal ones (B). Indeed, the A
connectors require cabling with a termination resistance for the line.
3 Shield
4 CAN +
3 Shield
2 CAN -
4 CAN + 1 V-
120
1/4 W
2 CAN -
1 V-
Connection Connection
type A type B
White-Grey Shield
Yellow-White CAN +
White-Grey Shield
Blue CAN -
Yellow-White CAN + Green V-
Contents Page
The contents of this chapter apply to all the VT terminals of the same fam-
ily that have a keyboard. As the of the various models differ in certain
details, the following explanations will indicate, for each , the respective
model.
The way a key functions changes according to the type of field to be varied.
Changing value To be able to carry out a change in any editable variable field, the cursor
of variable field must first be positioned over the field involved by using
F2 F3
or
VT50
VT50 VT60 Others VT60 Others
F4 F4
Enter Enter
VT150W
VT50 VT60 VT160W Others
The edit mode can be quit in two ways: either by saving after completing
the input of a value and pressing
F5 F4
Enter
Enter Enter
VT150W
VT50 VT60 VT160W Others
Help
F1 Esc
Clr
Esc Esc
Esc
Total change
Partial change
Total change This is the default mode adopted by the VT when enabling a change in a
field: numerical and alphanumeric fields behave differently.
Numerical fields:
The cursor flashes on the rightmost digit of the field. When the first
digit is introduced the rest of the field goes to zero, while the succes-
sive introductions make the digits shift to the left.
The cursor flashes on the leftmost digit of the field. When the new
string is introduced sequentially the cursor moves one character to
the right.
F2 F3
or
VT50
VT50 VT60 Others VT60 Others
Help F1 Info F2
or
VT50 VT60 VT50 VT60
enables the change of only that digit or character pointed to by the cursor;
to change the adjacent digits or characters the cursor must be positioned
manually (the figure above applies only to VT50 and VT60).
Examples of The examples below are offered to clarify how this works. For the sake of
varying fields simplicity we have chosen a single product, VT170W, but conceptually
what is said applies to all VTs, irrespective of what is written on the .
D
E
Sample page
Press 1 to enter the first digit of
F
Field 1 1
0001 the new value; the field assumes
the value 1.
G J M
H K N
2 3 4
Press I L O
to complete
Sample page
Field 1 4
-1234 the new value; press Space
to
Enter
attribute a sign and to confirm
the change.
J
K
Sample page
Press 3 to enter the first digit of
L
Field 2 3
0000003 the new value; the field assumes
the value 3.
Sample page G
H
D
E
1 2
Field 2 1
0000321 Press I
to complete the
F
Field 2 .
000321.
Press + Space
to introduce the
decimal point.
S P
T Q
6 5
Sample page Press U
to complete the
R
Field 2 5
0321.65 introduction of the new value.
Enter
Press to confirm the change.
A
B
Field 3 B
000B first digit of the new value; the
field assumes in sequence the val-
ues 0, A and B.
G J A
H K B
Field 3 C
B23C times to complete the new value;
Enter
Press to confirm the change.
Sample page A
B
field 3 BA3C
A press 0 twice to change the digit
C
to the value A.
field 3 A
BABA
to change the digit to the value A.
Enter
Press to confirm the change.
Sample page V
W
7
Field 4 Press once to enter the first
X
V
VOTOR 1 character of the new value.
by pressing or .
Entering [A] as the second character will cause the cursor to move
automatically.
J V
K W
3 7
Sample page Press L
3 times, X
once and
D
Field 4 E
1
VALVE
E 1 F
twice to complete word
VALVE.
Sample page
Press Space
to leave a space in the
Field 4 J
VALVE 3 K
3
field and then L
4 times.
shift
Press + Space
to enter the char-
Sample page P
Q
5
Field 4 acter [.]; press R
4 times to com-
VALVE 3.5
5
Enter
plete the new value; press to
confirm the change.
PgUp
Information When an event occurs which has an information message assigned to it the
messages LEDs of the following keys start flashing:
Info Help
Info Info
Esc
VT150W
VT50 VT60 VT160W Others
Information messages can be seen only when the event triggering them is
still present. When you press
Info Help
Shift + Info Info
Esc
VT150W
VT50 VT60 VT160W Others
you enter display mode, indicated by a fixed LED light (where terminals
have them), which is so structured as to allow one page for each message,
that page have the following format (formats vary according to the type of
VT).
The VT can provide an automatic sequential display of information mes-
sages on command from the device (see Chapter 37 -> Command area).
VT50 Format:
info-messages
Two rows of 20 characters for the text of the message.
Pressure exceeds
safety limit
First message
Info
Help
Pressure exceeds
safety limit
First message
VT60 Format:
info-messages
Four rows of 20 characters for the text of the message.
Pressure exceeds
safety limit
First message
F2
When you press the next message is displayed:
F1
When you press the first message is displayed again.
Pressure exceeds
safety limit
First message
VT150W - Format:
VT160W
info-messages Two rows of 20 characters for the text of the message.
One row for any data field (which in that particular situation could indi-
cate a safety or warning limit value).
The first display is indicated by two characters [**] on the far right of the
third line of the display. These symbols are not present if the message
appeared when the display mode for information messages was accessed
on a previous occasion.
Pressure exceeds
safety limit
125.5 ** First message
PgDn
PgUp
Pressure exceeds
safety limit
125.5 ** First message
VT170W Format:
info-messages
Two rows of 20 characters for the text of the message.
One row for any data field (which in that particular situation could indi-
cate a safety or warning limit value).
One row for the date and time the signal occurred.
The first display is indicated by two characters [**] on the far right of the
third line of the display. These symbols are not present if the message
appeared when the display mode for information messages was accessed
on a previous occasion.
Pressure exceeds
safety limit
125.5 ** First message
01/07/1998 10:45
PgDn
PgUp
Pressure exceeds
a limit
125.5 ** First message
01/07/1998 10:45
VT190W Format:
info-messages
Two rows of 40 characters for the text of the message.
One row for any data field (which in that particular situation could indi-
cate a safety or warning limit value).
One row for the date and time the signal occurred.
The first display is indicated by two characters [**] on the far right of the
third line of the display. These symbols are not present if the message
appeared the last time the display mode for information messages was
accessed.
PgDn
PgUp
VT300W - Format:
VT310W -
VT320W Five rows of 30 characters with character height of X1 or two rows of 15
info-messages with character height of X2 for the text of the message (VT300W -
VT310W).
Five rows of 36 characters with character height of X1 or two rows of 18
with character height of X2 for the text of the message (VT320W).
One row for any data field (which in that particular situation could indi-
cate a safety or warning limit value).
One row for the date and time the signal occurred.
The first display is indicated by a closed envelope [ ] at the top left of
the display. This symbol is not present if the message appeared the last
time the display mode for information messages was accessed.
Pressure exceeds
safety limit
First
message
125.5
01-07-1998 10:45a HELP PgDn
PgDn
shift
When you press + the second page containing the second message
appears. NB: having already appeared before, this message is not accompa-
nied by a closed envelope:
PgUp
shift
When you press + the previous page is displayed again.
Pressure exceeds
safety limit
First
message
125.5
01-07-1998 10:45a HELP Up
Temperature exceeds Down
safety limit
Second
message
1700
01-07-1998 10:55a HELP PgDn
PgDn
When you press you select the second message displayed as the cur-
rent message (the black bar indicates message has been selected). NB: hav-
ing already appeared before, this message is not accompanied by a closed
envelope:
Pressure exceeds
safety limit
First
message
125.5
01-07-1998 10:45a HELP Up
Temperature exceeds Down
safety limit
Second
message
1700
01-07-1998 10:55a HELP PgDn
PgDn
When you press again you select the third message displayed as the
current message:
PgUp
shift
When you press + the previous page appears containing the first
and second messages:
Pressure exceeds
safety limit
First
message
125.5
01-07-1998 10:45a HELP Up
Temperature exceeds Down
safety limit
Second
message
1700
01-07-1998 10:55a HELP PgDn
VT330W Format:
info-messages
Four rows of 70 characters x1 high or two rows of 35 characters of dou-
ble height (x2) for the text of the message.
One row for any data field (which in that particular situation could indi-
cate a safety or warning limit value).
One row for the date and time the signal occured.
The first display is indicated by a closed envelope [ ] at the top left of
the display. This symbol is not present if the message appeared the last
time the display mode for information messages was accessed.
PgDn
When you press you select the second message displayed as the cur-
rent message (the black bar indicates message has been selected). NB: hav-
PgDn
When you press again you select the third message displayed as the
current message:
PgDn
shift
When you press + the next page containing the fifth message
appears
PgUp
shift
When you press + the previous page returns containing the first
four messages:
ISA-1A alarms When an event occurs to which an alarm has been assigned, the following
LEDs begin to flash:
Hist Alarm
Alarm
ISA alarms are displayed from the time when the event triggering the alarm
occurs (Event in) until there is an individual acknowledgment operation
using
Ack
Ack
All All Ack
Ack
Ack
Ack
Shift + All
Ack
Shift + All Ack
For further details on how ISA-1A Alarms work see Software Manual.
Hist Alarm
Alarm
you enter display mode, signaled by the fixed light LED of that coming
on, where the first page has the format set out below (the format changes
according to the type of VT).
Alarm
When you press again you enter the second page whose format is set
out below (valid only for VT170W and VT190W).
Alarm n. 420
Pressure over the
maximum limit First page of the first alarm
150.0 !
The character [!] indicates that the alarm has not yet been acknowledged.
Ack
All
Ack
The acknowledgment operation, pressing , changes the character sig-
nalling the status of the event to [*]:
Alarm n. 420
Pressure over the
maximum limit First page of the first alarm
150.0 *
Alarm
When you press the second page appears:
Alarm n. 420
>01-07-1998 11:32a
#01-07-1998 11:38a Second page of the first alarm
Clr
Alarm Esc
When you press or the first page is appears again; by pressing
Clr
Esc
again you quit display mode for the ISA-1A alarms.
PgDn
If, while displaying the first page of the alarm, you pressing , the next
alarm message appears:
Alarm n. 470
Water level lower
than stop threshold First page of the second alarm
10 #
Alarm
When you press the second page appears:
Alarm n. 470
>01-07-1998 11:32a
<01-07-1998 11:37a Second page of the second alarm
The character [<] followed by the date and time, indicates that the event
triggering the alarm disappeared before the acknowledgment operation.
the character [#] for the date and time of the Event acknowledged
but still present.
the character [<] for the date and time of the Event out but not
acknowledged.
Alarm n. 420
The pressure in the tank exceeds First page of the first alarm
the maximum limit
150.0 !
Il character [!] indicates that the alarm has not yet been acknowledged; this
Ack
All Ack
is emphasized by the LED of flashing; by pressing this key, the alarm
is acknowledged and the character indicating the status of the event
changes to [*] and the LED goes out.
Alarm n. 420
The pressure in the tank exceeds First page of the first alarm
the maximum limit
150.0 *
Alarm
When you press the second page appears:
Alarm n. 420
>01-07-1998 11:32a Second page of the first alarm
#01-07-1998 11:38a
Clr Clr
Alarm Esc Esc
When you press or , the first page appears again; by pressing
again you quit display mode of the ISA-1A alarms.
PgDn
If, while displaying the first page of the alarm, you press , the next
alarm message appears
Alarm n. 470
Water level is lower than First page of the second alarm
the threshold stopping the process
10 #
Alarm
When you press the second page appears:
Alarm n. 420
>01-07-1998 11:32a Second page of the second
<01-07-1998 11:37a alarm
The character [<] followed by the date and time, indicates that the event
triggering the alarm disappeared before the acknowledgment operation.
PgDn
shift
When you press + the second page appears containing the second
alarm. Note that the second alarm is accompanied by the character [<] fol-
lowed by the date and time, indicating that the event triggering the alarm
disappeared before the acknowledgment operation. All this is also empha-
sized by the appropriate symbol.
PgDn
shift
When you press + the next page appears containing the third
alarm. Note that the second alarm is accompanied by the character [#] fol-
lowed by the date and time, indicating that the event triggering the alarm is
present and acknowledged. All this is also emphasized by the appropriate
symbol.
PgUp
shift
When you press + the previous page appears again.
Example with three alarms (VT310W and VT320W).
PgDn
When you press you select the second alarm as the current alarm. Note
that the second alarm is accompanied by the character [<] followed by the
date and time, indicating that the event triggering the alarm disappeared
before the acknowledgment operation. All this is also emphasized by the
appropriate symbol.
PgDn
When you press again you select the third alarm as the current alarm.
PgUp
shift
When you press + the previous page appears containing the first
and second alarms. Note that the second alarm is accompanied by the char-
acter [#] followed by the date and time, indicating that the event triggering
the alarm is present and acknowledged. All this is also emphasized by the
appropriate symbol.
PgDn
When you press you select the second alarm as the current alarm. Note
that the second alarm is accompanied by the character [<] followed by the date
and time, indicating that the triggering event of the alarm disappeared before
being acknowledged. The situation as a whole is highlighted by the appropriate
alarm status symbol. Third alarm is accompanied by the character [#] followed by
the date and time, indicating that the triggering event of the alarm is present and
has been acknowledged. The situation as a whole is highlighted by the appropri-
ate alarm status symbol.
ISA-1A alarm When an event occurs to which an alarm has been assigned the terminal
history buffer registers it chronologically in an area of the internal memory called the
Alarm history buffer. If, while displaying the first page of the alarm, you
Enter
press , or at any point
you enter display mode, signaled by the fixed light LED of that coming
on.
Alarm
When you press again you enter the second page whose format is set
out below (valid only for VT170W and VT190W).
The buffer of the Alarm history can be emptied (the elimination of all the
messages registered) only by means of a command from the device (see
Once the buffer is full, new alarms are no longer registered. You
are advised to consult the chapter Status area of the VT Chapter
37 -> Status area for the terminal (see also Software Manual) to be able
to tell when the buffer is full.
The format is similar to that of the alarms except that a character [H] is
added in front of the number of the alarm (see the formats of the various
products).
Alarm
When you press the second page appears:
H - Alarm n. 420
>01-07-1998 11:32a
#01-07-1998 11:38a Second page of history buffer of the first alarm
<01-07-1998 11:52a
Clr Clr
Alarm Esc Esc
When you press or the first page appears again; by pressing
again you quit the display mode for the history buffer.
PgDn
If, while displaying the first page of the history buffer, you press the
next message is displayed:
H - Alarm n. 470
Water level lower
than stop threshold First page of history buffer of the second alarm
10
Alarm
When you press the second page appears:
H - Alarm n. 470
>01-07-1998 11:32a
#01-07-1998 11:47a Second page of the second alarm
<01-07-1998 11:37a
Alarm
When you press the second page appears:
H - Alarm n. 420
>01-07-1998 11:32a Second page of the history
#01-07-1998 11:38a buffer of the first alarm
<01-07-1998 11:52a
Clr
Alarm Esc
When you press or the first page is appears again; by pressing
Clr
Esc
again you quit display mode of the history buffer.
PgDn
If, while displaying the first page, you press , the next history buffer is
displayed:
H - Alarm n. 470
Water level lower than First page of the history buffe
threshold stopping process of the second alarm
10
Alarm
When you press the second page appears:
H - Alarm n. 470
>01-07-1998 11:32a Second page of the history
#01-07-1998 11:47a buffer of the second alarm
<01-07-1998 11:37a
PgDn
shift
When you press + the next page appears containing the following
alarm:
PgDn
shift
When you press + the next page appears containing the following
alarm:
PgUp
shift
When you press + the previous page appears again. When you
Esc
press you quit display mode of the history buffer.
PgDn
When you press you select the third alarm as the current alarm:
PgUp
shift
When you press + the previous page now appears containing the
first and second alarms:
Esc
When you press you quit display mode for the history buffer.
Esc
When you press you quit display mode for the history buffer.
Help When there is a help message the LED of the following keys flashes
messages
Help Help
Help Help
Esc
VT150W
VT50 VT60 VT160W Others
Help Help
Shift + Shift + Help Help
Esc
VT150W
VT50 VT60 VT160W Others
you enter display mode, indicated by the fixed light of the LED (in the case
of those terminals that have it). When you press
Help
F1 Esc
Clr
Esc Esc
Esc
you quit display mode for help messages and return to the previous display
mode.
Contents Page
The contents of this chapter apply to all the VT terminals of the same fam-
ily that have a touch screen.
Changing value To be able to carry out a change in any editable variable field you must
of variable field touch the chosen field on the display and a page appears offering the
needed to modify the field.
The edit mode is quit by pressing the appropriate (see Table 36.1,
Chapter 36 -> Keys displayed used for settings .) after setting the value, or
automatically when the input timeout (see Software Manual) elapses,
whereby the variation is quit.
Keys Function
Keys Function
Total change
Partial change
Total change This is the default mode adopted by the VT when enabling a change in a
numerical field.
Numerical fields:
The cursor flashes on the rightmost digit of the field. When the first
digit is introduced the rest of the field goes to zero, while the succes-
sive introductions make the digits shift to the left.
Partial change With the edit mode enabled, the change of the individual digit or character
being pointed to by the cursor is enabled by pressing the arrow and then
entering a digit, or by means of increasing the character (see Table 36.1,
Chapter 36 -> Keys displayed used for settings .). To change the adjacent
digits or characters the cursor has to be positioned manually.
Examples of The examples below are offered to clarify how this works. For the sake of
varying fields simplicity we have chosen a single product, VT555W, but conceptually
what is said applies to all the products of the same family.
Sample page
Field 1 9999
9999
0 1 2 3 ESC
. 4 5 6
+/- 7 8 9
0001
0 1 2 3 ESC
. 4 5 6
+/- 7 8 9
-1234
0 1 2 3 ESC
. 4 5 6
+/- 7 8 9
Sample page
Field 2 10.3256
10.3256
0 1 2 3 ESC
. 4 5 6
+/- 7 8 9
0000003
0 1 2 3 ESC
. 4 5 6
+/- 7 8 9
0000321
0 1 2 3 ESC
. 4 5 6
+/- 7 8 9
000321.
0 1 2 3 ESC
. 4 5 6
+/- 7 8 9
0321.65
0 1 2 3 ESC
. 4 5 6
+/- 7 8 9
Sample page
Field 3 1A3F
1A3F
SHIFT 7 8 9
000B
SHIFT 7 8 9
B23C
SHIFT 7 8 9
Sample page
Field 3 B23C
B23C
SHIFT 7 8 9
B23C
SHIFT 7 8 9
BA3C
SHIFT 7 8 9
BABC
SHIFT 7 8 9
BABA
SHIFT 7 8 9
Sample page
Field 4
MOTOR 1
VOTOR 1
ESC
VATOR 1
ESC
VALVE 3.5
ESC
Sample page
Field 5
SETUP
SETUP
ESC
STOP
ESC
MANUAL
ESC
Sample page
Field 6
ESC
ESC
ESC
Sample page
Field 7 1010
1010
0 1 ESC
1111
0 1 ESC
Sample page
Field 8
MAX: 100
ESC
VAL: 100
MIN: 0
MAX: 100
ESC
VAL: 50
MIN: 0
Information When an event occurs which has an information message assigned to it the
messages display shows
VT5xxH - Format:
VT1x5/505/515
/525/555/56xW Five rows of 30 characters with character height of X1 or two rows of 15
info-msgs with character height of X2 for the text of the message.
One row for any data field (which in that particular situation could indi-
cate a safety or warning limit value).
One row for the date and time the signal occurred.
The first display is indicated by a closed envelope [ ] at the top left of
the display. This symbol is not present if the message appeared the last
time the display mode for information messages was accessed.
Pressure exceeds
safety limit
First
message
125.5 ESC
01-07-1998 10:45a HELP
Temperature over
safety limit
Second
message
1700
01-07-1998 10:55a HELP
Vertical Format:
VT1x5W
info-messages Five rows of 21 characters with character height of X1 or three rows of
10 with character height of X2 for the text of the message.
One row for any data field (which in that particular situation could indi-
cate a safety or warning limit value).
One row for the date and time the signal occurred.
The first display is indicated by a closed envelope [ ] at the top left of
the display. This symbol is not present if the message appeared the last
time the display mode for information messages was accessed.
HELP
Pressure exceeds
safety limit
125.5
First
message
01-07-1998 10:45a
ESC
HELP
Water lev.
lower than
min. limit
-10
Second
message
01-07-1998 11:00a
ESC
VT575W - Format:
VT580W-
VT585W - Four rows of 70 characters x1 high or two rows of 35 characters of dou-
VT585WB ble height (x2) for the text of the message.
info-messages One row for any data field (which in that particular situation could indi-
cate a safety or warning limit value).
One row for the date and time the signal occured.
The first display is indicated by a closed envelope [ ] at the top left of
the display. This symbol is not present if the message appeared the last
time the display mode for information messages was accessed.
ESC
VT595W Format:
info-messages
Four rows of 89 characters x1 high or two rows of 44 characters of dou-
ble height (x2) for the text of the message.
One row for any data field (which in that particular situation could indi-
cate a safety or warning limit value).
One row for the date and time the signal occured.
The first display is indicated by a closed envelope [ ] at the top left of
the display. This symbol is not present if the message appeared the last
time the display mode for information messages was accessed.
ISA-1A alarms When an event occurs to which an alarm has been assigned the screen
shows.
ISA alarms are displayed from the time when the event triggering the alarm
occurs (Event in) until there is an individual acknowledgment operation - touch-
ing the symbol on the screen related to the alarm to be acknowledged (Event
acknowledged) - and the triggering event is no longer present (Event out).
For further details on how ISA-1A Alarms work see Software Manual.
When the symbol on the screen is touched you enter display mode, where
each page contains up to two alarms whose format is set out below.
HIST
HELP
0001
The pressure in
the tank exceeds
the max. limit
150.0
First
alarm
>01-07-1998 11:32a
ESC HIST
HELP
0032
Water level is
lower than the
stop threshold
of the process
10
Second
alarm
>01-07-1998 11:32a
<01-07-1998 11:37a
ESC HIST
HELP
0006
Temperature
over the
safe lim.
1600
Third
alarm
>01-07-1998 12:28p
#01-07-1998 12:29p
ESC HIST
ISA-1A alarm When an event occurs to which an alarm has been assigned the terminal
history buffer registers it chronologically in an area of the internal memory called the
Alarm history buffer. If, while displaying the alarm page, you touch the
HIST on the screen, you access the history buffer.
The buffer of the Alarm history can be emptied (the elimination of all the
messages registered) only by means of a command from the device (see
Chapter 37 -> Command area).
Once the buffer is full, new alarms are no longer registered. You
are advised to consult the chapter Status area of the VT Chapter
37 -> Status area for the terminal (see also Software Manual) to be able
to tell when the buffer is full.
The format is similar to that of the alarms except that a character [H] is added
in front of the number of the alarm (see the formats of the various products).
H
0001
The pressure in
the tank exceeds
the max. limit
150.0
First
alarm
>01-07-1998 11:32a
<01-07-1998 11:33a
#01-07-1998 11:55a
ESC
To explain the way the help messages work, it is necessary to divide them
into two categories: on the one hand messages related to alarms and to
information messages, on the other hand help messages related to pages.
Help and If, when you are in a context of displaying alarms or information messages,
information there is a help message present, the word HELP appears. If you touch the
messages alarm or the message accompanying the word HELP the help messaage is
relating to displayed. Touching the ESC on the screen takes you back to the previ-
alarms ous screenful.
Contents Page
As the Area for Messages does not depend on the type of VT, but is com-
pletely configurable using VTWIN, it will no longer be mentioned in this
chapter.
For the detailed meaning of the various areas see Software Man-
ual.
Status area for The significance of this area depends on the type of VT used:
the terminal With a keyboard
With a touch screen.
With a keyboard:
WATCHDOG
0 0 0 0 0 0 0 0 0 0
Always at Status1
EDIT MODE
1 1 1 1 1 1 1 1 1 1
Status 1 when il terminal is in mode for changing fields
MESSAGES PRESENT
2 2 2 2 -- -- -- -- -- --
Status 1 so long as there is a message to display
MESSAGE PENDING
3 3 3 3 -- -- -- -- -- --
Status 1 so long as there is a message in but not yet consulted
BATTERY FLAT
Status 1 when the battery is near its minimum level for maintain- -- -- -- -- 8 8 8 8 8 8
ing the data in the RAM memory
-- : not present
SEQUENCE IDENTIFIER
Contains a value other than zero if in Project Page context, but
contains zero if in any other context
INFORMATION MESSAGES 0 0 0 0 0 0 0 0 0 0
SEQUENCE DIRECTORY 1 1 1 1 1 1 1 1 1 1
PAGE DIRECTORY -- -- -- -- -- -- -- -- -- --
ISA ALARMS -- -- -- -- 5 5 5 5 5 5
RECIPE DIRECTORY -- -- -- -- 6 6 6 6 6 6
PROJECT INFORMATION 3 3 -- -- 9 9 -- -- -- --
SETTING CLOCK -- -- -- -- 10 10 -- -- -- --
-- : not present
WATCHDOG
0 0 0 0 0 0 0 0 0 0 0 0 0 0
Always at Status1
EDIT MODE
1 1 1 1 1 1 1 1 1 1 1 1 1 1
Status 1 when il terminal is in mode for changing fields
MESSAGES PRESENT
-- -- -- -- -- -- -- -- -- -- -- -- -- --
Status 1 so long as there is a message to display
MESSAGE PENDING
-- -- -- -- -- -- -- -- -- -- -- -- -- --
Status 1 so long as there is a message in but not yet consulted
BATTERY FLAT
Status 1 when the battery is near its minimum level for maintain- -- -- -- -- -- -- -- 8 8 -- -- 8 -- --
ing the data in the RAM memory
-- : not present
-- -- -- -- -- -- -- -- -- -- -- -- -- --
-- : not used
CONTEXT IDENTIFIER
Contains the identifying value of the context if the context is not
Project Page (Word 2 = 0)
INFORMATION MESSAGES 0 0 0 0 0 0 0 0 0 0 0 0 0 0
SEQUENCE DIRECTORY -- -- -- -- -- -- -- -- -- -- -- -- -- --
PAGE DIRECTORY 1 1 1 1 1 1 1 1 1 1 1 1 1 1
ISA ALARMS 5 5 -- -- 5 5 5 5 5 5 5 5 5 5
RECIPE DIRECTORY 6 6 6 6 6 6 6 6 6 6 6 6 6 6
PROJECT INFORMATION -- -- -- -- -- -- -- -- -- -- -- -- -- --
SETTING CLOCK -- -- -- -- -- -- -- -- -- -- -- -- -- --
-- : not present
Status area for This area consists of a maximum of 4 words (numbered from 0 to 3).
internal LEDs
NO. OF WORD NAME OF WORD
0 STATUS WORD for GREEN LEDS
1 STATUS WORD for GREEN LEDS
2 STATUS WORD for RED LEDS
3 STATUS WORD for RED LEDS
Table 37.9: Meaning of the Bits of the Status Word for the Green LEDs
MEANING OF THE BIT
WORD 0 VT VT VT VT VT VT VT VT
NUMBER OF THE BIT VT VT
150 160 170 190 300 310 320 330
50 60
W W W W W W W W
0 -- -- F1 F1 F1 F1 F1 F1 F1 --
1 -- -- F2 F2 F2 F2 F2 F2 F2 --
2 -- -- F3 F3 F3 F3 F3 F3 F3 --
3 -- -- F4 F4 F4 F4 F4 F4 F4 --
4 -- -- F5 F5 F5 F5 F5 F5 F5 --
5 -- -- -- -- F6 F6 F6 F6 F6 --
6 -- -- -- -- F7 F7 F7 F7 F7 --
7 -- -- -- -- F8 F8 F8 F8 F8 --
8 -- -- -- -- F9 F9 F9 F9 F9 --
-- : not present
Table 37.10: Meaning of the Bits of the Status Word for Green LEDs
MEANING OF THE BIT
WORD 1 VT VT VT VT VT VT VT VT
NUMBER OF THE BIT VT VT
150 160 170 190 300 310 320 330
50 60
W W W W W W W W
8 -- -- -- -- -- -- -- -- F25 F25
9 -- -- -- -- -- -- -- -- F26 F26
10 -- -- -- -- -- -- -- -- F27 F27
11 -- -- -- -- -- -- -- -- F28 F28
12 -- -- -- -- -- -- -- -- -- --
13 -- -- -- -- -- -- -- -- -- --
14 -- -- -- -- -- -- -- -- -- --
15 -- -- -- -- -- -- -- -- -- --
-- : not present
Table 37.11: Meaning of the Bits of the Status Word for Red LEDs
MEANING OF THE BIT
WORD 2 VT VT VT VT VT VT VT VT
NUMBER OF THE BIT VT VT
150 160 170 190 300 310 320 330
50 60
W W W W W W W W
0 -- -- -- -- F1 F1 F1 F1 F1 --
1 -- -- -- -- F2 F2 F2 F2 F2 --
2 -- -- -- -- F3 F3 F3 F3 F3 --
3 -- -- -- -- F4 F4 F4 F4 F4 --
4 -- -- -- -- F5 F5 F5 F5 F5 --
5 -- -- -- -- F6 F6 F6 F6 F6 --
6 -- -- -- -- F7 F7 F7 F7 F7 --
7 -- -- -- -- F8 F8 F8 F8 F8 --
8 -- -- -- -- F9 F9 F9 F9 F9 --
-- : not present
Table 37.12: Meaning of the Bits of the Status Word for Red LEDs
MEANING OF THE BIT
WORD 3 VT VT VT VT VT VT VT VT
NUMBER OF THE BIT VT VT
150 160 170 190 300 310 320 330
50 60
W W W W W W W W
2 -- -- -- -- -- F19 F19 -- -- --
3 -- -- -- -- -- F20 F20 -- -- --
4 -- -- -- -- -- F21 F21 -- -- --
5 -- -- -- -- -- F22 F22 -- -- --
6 -- -- -- -- -- -- -- -- -- --
7 -- -- -- -- -- -- -- -- -- --
8 -- -- -- -- -- -- -- -- -- --
9 -- -- -- -- -- -- -- -- -- --
10 -- -- -- -- -- -- -- -- -- --
11 -- -- -- -- -- -- -- -- -- --
12 -- -- -- -- -- -- -- -- -- --
13 -- -- -- -- -- -- -- -- -- --
14 -- -- -- -- -- -- -- -- -- --
15 -- -- -- -- -- -- -- -- -- --
-- : not present
Status area for This area consists of 2 fixed words (numbered from 0 to 1).
external LEDs
NO. OF WORD NAME OF WORD
0 STATUS WORD
1 STATUS WORD
Table 37.13: Meaning of the Bits of the Status Word for External LEDs
NUMBER OF THE BIT
WORD 0 VT150W VT300W - VT310W - VT320W
MEANING OF THE BIT + VT160W +
VT100MT1000 VT100MT1000
E1 0 0 0
E2 1 1 1
E3 2 2 2
E4 3 3 3
E5 4 4 4
E6 5 5 5
E7 6 6 6
E8 7 7 7
E9 8 8 8
E10 9 9 9
E11 10 10 10
E12 11 11 11
E13 12 12 12
E14 13 13 13
E15 14 14 14
E16 15 15 15
-- : not present
Table 37.14: Meaning of the Bits of the Status Word for External LEDs
NUMBER OF THE BIT
WORD 1 VT150W VT300W - VT310W - VT320W
MEANING OF THE BIT + VT160W +
VT100MT1000 VT100MT1000
E17 0 0 0
E18 1 1 1
E19 2 -- 2
E20 3 -- 3
E21 -- -- --
E22 -- -- --
E23 -- -- --
E24 -- -- --
E25 -- -- --
E26 -- -- --
E27 -- -- --
E28 -- -- --
E29 -- -- --
E30 -- -- --
E31 -- -- --
E32 -- -- --
-- : not present
Table 37.15: Meaning of the Bits of the Status Word for Recipes
NUMBER OF THE BIT
WORD 0 VT VT VT VT VT VT VT VT VT VT
MEANING OF THE BIT 50 60 150 160 170 190 300 310 320 330
W W W W W W W W
TIMEOUT FOR RECIPE TRANSFER
Status 1 when the terminal does not respond in the -- -- -- -- 13 13 13 13 13 13
expected time
TRANSFER OVER
Status 1 when the terminal has sent all the relevant -- -- -- -- 14 14 14 14 14 14
data
TRANSFER REQUEST
-- -- -- -- 15 15 15 15 15 15
Status 1 when the terminal wants to start to transfer
-- : not present
Table 37.16: Meaning of the Bits of the Status Word for Recipes
NUMBER OF THE BIT
WORD 0 VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT
MEANING OF THE BIT 155 185 505 505 515 155 185 505 505 525 525 555 56x 575 580 585 585 595
W W H W W W W H W H W W W W W W WB W
TIMEOUT FOR RECIPE TRANSFER
Status 1 when the terminal does not respond in the 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13
expected time
TRANSFER OVER
Status 1 when the terminal has sent all the relevant 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14 14
data
TRANSFER REQUEST
15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
Status 1 when the terminal wants to start to transfer
-- : not present
Status area for The significance of this area depends on the type of VT used:
internal keys With a keyboard
With a touch screen.
37.17: Meaning of the Bits of the Status Word for Internal Keys (Word 0)
37.18: Meaning of the Bits of the Status Word for Internal Keys (Word 1)
37.19: Meaning of the Bits of the Status Word for Internal Keys (Word 2)
37.20: Meaning of the Bits of the Status Word for Internal Keys (Word 3)
37.21: Meaning of the Bits of the Status Word for Internal Keys (Word 4)
37.22: Meaning of the Bits of the Status Word for Internal Keys (Word 5)
37.17: Meaning of the Bits of the Status Word for Internal Keys (Word 0)
The keys enclosed in a box with a bold border put the related bit at 1 when
Shift
pressed with .
The above is valid for VT50 and VT60. In the case of other termi-
nals the bits relating to the function keys are always the same. The
bit of the SHIFT key must also be tested (Word 0 - Bit 15).
Shift
The bit relating to the key is set at 1 only if pressed at the same time as
Clr
Shift Esc
another key (e.g. + ).
The Handshake bit is put at 1 by the VT each time one or more keys are pressed;
the device can put it at 0 in order to find out when the VT is going to write.
Table 37.17: Meaning of the Bits of the Status Word for Internal Keys (Word 0)
WORD 0
BIT
Shift VT50 VT60 VT150W VT160W VT170W VT190W VT300W VT310W VT320W VT330W
HAND HAND HAND HAND HAND HAND HAND HAND HAND HAND
0
SHAKE SHAKE SHAKE SHAKE SHAKE SHAKE SHAKE SHAKE SHAKE SHAKE
Help
1
F1 Clr Clr Clr Clr Clr Clr Clr
Esc
Esc Esc Esc Esc Esc Esc Esc Esc
Esc
2
F2 --
3
F3 F3
4
F4 F4
Enter Enter Enter
5
F5 F4 -- -- Enter Enter Enter Enter Enter Enter
Enter
6
Info F2 PgDn PgDn PgDn PgDn PgDn PgDn PgDn PgDn
7
Help F1 PgUp PgUp PgUp PgUp PgUp PgUp PgUp PgUp
F1 F1
8 Help Help Info Info Info Info Info Info
Esc
F2 F2
9 Info Info Help Help Help Help Help Help
F3 F3 Hist
10 -- -- Alarm Alarm Alarm Alarm Hist
Alarm Alarm
11
F4 F4 -- --
Ack
All
Ack Ack Ack Ack Ack
Ack All Ack All Ack All Ack All Ack All
Ack
Enter
12
F5 -- .
. Space
Space Space Space Space Space Space Space
Help Help
13 -- --
Esc
Info Help
14 -- -- -- -- Spare Spare -- Clr
Esc
-- : not used
Table 37.18: Meaning of the Bits of the Status Word for Internal Keys (Word 1)
WORD 1
BIT
Shift VT50 VT60 VT150W VT160W VT170W VT190W VT300W VT310W VT320W VT330W
A A A A A A A
0 n.p. n.p. B B B B B B B Ctrl
C 0 C 0 C 0 C 0 C 0 C 0 C 0
D D D D D D D
1 n.p. n.p. E E E E E E E Alt
F 1 F 1 F 1 F 1 F 1 F 1 F 1
G G G G G G G
2 n.p. n.p. H H H H H H H Tab
I 2 I 2 I 2 I 2 I 2 I 2 I 2
J J J J J J J
3 n.p. n.p. K K K K K K K Spare
L 3 L 3 L 3 L 3 L 3 L 3 L 3
M M M M M M M
4 n.p. n.p. N N N N N N N
<
O 4 O 4 O 4 O 4 O 4 O 4 O 4 ,
P P P P P P P
>
5 n.p. n.p. Q
5
Q
5
Q
5
Q
5
Q
5
Q
5
Q
5 .
R R R R R R R
S S S S S S S _
6 n.p. n.p. T T T T T T T
U 6 U 6 U 6 U 6 U 6 U 6 U 6 -
V V V V V V V
7 n.p. n.p. W W W W W W W +
X 7 X 7 X 7 X 7 X 7 X 7 X 7 =
Y Y Y Y Y Y Y
8 n.p. n.p. Z Z Z Z Z Z Z --
- 8 - 8 - 8 - 8 - 8 - 8 - 8
+ + + + + + +
9 n.p. n.p. / / / / / / / --
= 9 = 9 = 9 = 9 = 9 = 9 = 9
10 n.p. n.p. -- -- -- -- -- -- -- --
11 n.p. n.p. -- -- -- -- -- -- -- --
12 n.p. n.p. -- -- -- -- -- -- -- --
13 n.p. n.p. -- -- -- -- -- -- -- --
14 n.p. n.p. -- -- -- -- -- -- -- --
15 n.p. n.p. -- -- -- -- -- -- -- --
Table 37.19: Meaning of the Bits of the Status Word for Internal Keys (Word 2)
WORD 2
BIT
Shift VT50 VT60 VT150W VT160W VT170W VT190W VT300W VT310W VT320W VT330W
0 n.p. n.p. F6 F6 )
F1 F1
F1 F1 F1 F1 F1 0
1 n.p. n.p. F7 F7 /
F2 F2
F2 F2 F2 F2 F2 1
2 n.p. n.p. F8 F8 \
F3 F3
F3 F3 F3 F3 F3 2
3 n.p. n.p. F9 F9 ]
F4 F4
F4 F4 F4 F4 F4 3
5 n.p. n.p. -- -- %
F6 F6 F6 F6 F6 5
6 n.p. n.p. -- -- [
F7 F7 F7 F7 F7 6
7 n.p. n.p. -- -- ;
F8 F8 F8 F8 F8 7
8 n.p. n.p. -- -- *
F9 F9 F9 F9 F9 8
9 n.p. n.p. -- -- (
F10 F10 F10 F10 F10 9
10 n.p. n.p. -- -- --
F11 F11 F11 F11 F11
11 n.p. n.p. -- --
F12 F12 F12 F12 F12
--
12 n.p. n.p. -- -- --
F13 F13 F13 F13
--
13 n.p. n.p. -- -- --
F14 F14 F14 F14
--
14 n.p. n.p. -- -- --
F15 F15 F15 F15
--
15 n.p. n.p. -- -- --
F16 F16 F16 F16
--
Table 37.20: Meaning of the Bits of the Status Word for Internal Keys (Word 3)
WORD 3
BIT
Shift VT50 VT60 VT150W VT160W VT170W VT190W VT300W VT310W VT320W VT330W
A
0 n.p. n.p. n.p. n.p. n.p.
F17 F17 F17 F17 B
C
1 n.p. n.p. n.p. n.p. n.p.
F18 F18 F18 F18 D
E
2 n.p. n.p. n.p. n.p. n.p.
F19 F19 F19 F19 F
G
3 n.p. n.p. n.p. n.p. n.p.
F20 F20 F20 F20 H
I
4 n.p. n.p. n.p. n.p. n.p.
F21 F21 F21 F21 J
M
6 n.p. n.p. n.p. n.p. n.p. F23 F23 -- F23 N
O
7 n.p. n.p. n.p. n.p. n.p. F24 F24 -- F24 P
Q
8 n.p. n.p. n.p. n.p. n.p. -- -- -- F25 R
S
9 n.p. n.p. n.p. n.p. n.p. -- -- -- F26 T
U
10 n.p. n.p. n.p. n.p. n.p. -- -- -- F27 V
W
11 n.p. n.p. n.p. n.p. n.p. -- -- -- F28 X
Table 37.21: Meaning of the Bits of the Status Word for Internal Keys (Word 4)
WORD 4
BIT
Shift VT50 VT60 VT150W VT160W VT170W VT190W VT300W VT310W VT320W VT330W
9 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F10
10 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F11
11 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F12
12 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F13
13 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F14
14 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F15
15 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F16
Table 37.22: Meaning of the Bits of the Status Word for Internal Keys (Word 5)
WORD 5
BIT
Shift VT50 VT60 VT150W VT160W VT170W VT190W VT300W VT310W VT320W VT330W
0 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F17
1 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F18
2 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F19
3 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F20
4 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F21
5 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F22
6 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F23
7 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F24
8 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F25
9 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F26
10 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F27
11 n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. n.p. F28
Table 37.23: Meaning of the Bits of the Status Word for Internal Keys (Word 0)
WORD 0
BIT
VT505H VT52H
1 F1 F1
2 F2 F2
3 F3 F3
4 F4 F4
5 F5 F5
6 F6 F6
7 F7 F7
8 F8 F8
9 F9 F9
10 F10 F10
11 -- --
12 -- --
13 -- --
14 -- --
15 -- --
Status area for This area consists of a maximum of 2 words (numbered from 0 to 1).
external keys
NO. OF WORD NAME OF WORD
0 STATUS WORD for EXTERNAL KEYS
1 STATUS WORD for EXTERNAL KEYS
Table 37.24: Meaning of the Bits of the Status Word for External Keys
NUMBER OF THE BIT
WORD 0 VT150W VT300W - VT310W - VT320W
MEANING OF BIT + VT160W +
VT100MT1000 VT100MT1000
E1 0 0 0
E2 1 1 1
E3 2 2 2
E4 3 3 3
E5 4 4 4
E6 5 5 5
E7 6 6 6
E8 7 7 7
E9 8 8 8
E10 9 9 9
E11 10 10 10
E12 11 11 11
E13 12 12 12
E14 13 13 13
E15 14 14 14
E16 15 15 15
-- : not present
Table 37.25: Meaning of the Bits of the Status Word for External Keys
NUMBER OF THE BIT
WORD 1 VT150W VT300W - VT310W - VT320W
MEANING OF BIT + VT160W +
VT100MT1000 VT100MT1000
E17 0 0 0
E18 1 1 1
E19 2 -- 2
E20 3 -- 3
E21 -- -- --
E22 -- -- --
E23 -- -- --
E24 -- -- --
E25 -- -- --
E26 -- -- --
E27 -- -- --
E28 -- -- --
E29 -- -- --
E30 -- -- --
E31 -- -- --
E32 -- -- --
-- : not present
Status area for The significance of this area depends on the type of VT used:
internal keys With a keyboard
(Real Time) With a touch screen.
The keys surrounded by a bold border set the corresponding bit at 1 when
Shift
pressed together with .
The above is valid for VT50 and VT60. In the case of other termi-
nals the bits relating to the function keys are always the same. The
bit of the SHIFT key must also be tested (Word 0 - Bit 15).
Shift
The bit relating to the key is set at 1 only if pressed at the same time as
Clr
Shift Esc
another key (e.g. + ).
The Handshake bit is set at 1 by the VT whenever one or more keys are
pressed; it is set at 0 when no key is pressed.
Status area for This area consists of a maximum of 2 words (numbered from 0 to 1).
external keys
(Real Time) WORD NUMBER NAME OF WORD
0 STATUS WORD FOR EXTERN. KEYS (Real Time)
1 STATUS WORD FOR EXTERN. KEYS (Real Time)
Status area for This area consists of 2 words (numbered from 0 to 1).
printer
NO. OF WORD NAME OF WORD
0 STATUS WORD for ASP
1 STATUS WORD for LPT
Table 37.26: Meaning of the Bits of the Status Word for ASP
NUMBER OF THE BIT
WORD 0 VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT
MEANING OF THE BIT 50 60 150 160 170 190 300 310 320 330 155 185 505 505 515 525 525 555 56x 575 580 585 585 595
W W W W W W W W W W H W W H W W W W W W WB W
STAMPANTE NOT ON
LINE
n.p. n.p. n.p. n.p. 0 0 0 0 0 0 0 0 n.p. n.p. n.p. 0 0 0 0 0 0 0 0 0
Status 1 when one of the
bits from 3 to 8 is set at 1.
TIMEOUT
Status 1 when the printer is
OFFLINE, not connected,
n.p. n.p. n.p. n.p. 1 1 1 1 1 1 1 1 n.p. n.p. n.p. 1 1 1 1 1 1 1 1 1
lacks paper or when there is
any communication problem
follow the command to print.
REPORT PRINTING IN
PROGRESS
n.p. n.p. n.p. n.p. 3 3 3 3 3 3 3 3 n.p. n.p. n.p. 3 3 3 3 3 3 3 3 3
Status 1 as long as the
function lasts
DIRECT PRINTING OF
THE INFORMATION
MESSAGE IN
n.p. n.p. n.p. n.p. 4 4 4 4 4 4 4 4 n.p. n.p. n.p. 4 4 4 4 4 4 4 4 4
PROGRESS
Status 1 as long as the
function lasts
DIRECT PRINTING OF
THE ISA ALARME IN
PROGRESS n.p. n.p. n.p. n.p. 5 5 5 5 5 5 5 5 n.p. n.p. n.p. 5 5 5 5 5 5 5 5 5
Status 1 as long as the
function lasts
PRINTING OF ALARM
HISTORY BUFFER IN
PROGRESS n.p. n.p. n.p. n.p. 6 6 6 6 6 6 6 6 n.p. n.p. n.p. 6 6 6 6 6 6 6 6 6
Status 1 as long as the
function lasts
HARDCOPY IN
PROGRESS
n.p. n.p. n.p. n.p. 7 7 7 7 7 7 7 7 n.p. n.p. n.p. 7 7 7 7 7 7 7 7 7
Status 1 as long as the
function lasts
FORM-FEED IN
PROGRESS
n.p. n.p. n.p. n.p. 8 8 8 8 8 8 8 8 n.p. n.p. n.p. 8 8 8 8 8 8 8 8 8
Status 1 as long as the
function lasts
-- : non used n.p. : not present
Table 37.27: Meaning of the Bits of the Status Word for LPT
NUMBER OF THE BIT
WORD 1 VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT VT
MEANING OF THE BIT 50 60 150 160 170 190 300 310 320 330 155 185 505 505 515 525 525 555 56x 575 580 585 585 595
W W W W W W W W W W H W W H W W W W W W WB W
STAMPANTE NOT ON
LINE
n.p. n.p. n.p. n.p. 0 0 0 0 0 0 n.p. n.p. n.p. n.p. n.p. n.p. n.p. 0 0 0 0 0 0 0
Status 1 when one of the
bits from 3 to 8 is set at 1.
TIMEOUT
Status 1 when the printer is
OFFLINE, not connected,
n.p. n.p. n.p. n.p. 1 1 1 1 1 1 n.p. n.p. n.p. n.p. n.p. n.p. n.p. 1 1 1 1 1 1 1
lacks paper or when there is
any communication problem
follow the command to print.
-- n.p. n.p. n.p. n.p. -- -- -- -- -- -- n.p. n.p. n.p. n.p. n.p. n.p. n.p. -- -- -- -- -- -- --
REPORT PRINTING IN
PROGRESS
n.p. n.p. n.p. n.p. 3 3 3 3 3 3 n.p. n.p. n.p. n.p. n.p. n.p. n.p. 3 3 3 3 3 3 3
Status 1 as long as the
function lasts
DIRECT PRINTING OF
THE INFORMATION
MESSAGE IN
n.p. n.p. n.p. n.p. 4 4 4 4 4 4 n.p. n.p. n.p. n.p. n.p. n.p. n.p. 4 4 4 4 4 4 4
PROGRESS
Status 1 as long as the
function lasts
DIRECT PRINTING OF
THE ISA ALARME IN
PROGRESS n.p. n.p. n.p. n.p. 5 5 5 5 5 5 n.p. n.p. n.p. n.p. n.p. n.p. n.p. 5 5 5 5 5 5 5
Status 1 as long as the
function lasts
PRINTING OF ALARM
HISTORY BUFFER IN
PROGRESS n.p. n.p. n.p. n.p. 6 6 6 6 6 6 n.p. n.p. n.p. n.p. n.p. n.p. n.p. 6 6 6 6 6 6 6
Status 1 as long as the
function lasts
HARDCOPY IN
PROGRESS
n.p. n.p. n.p. n.p. 7 7 7 7 7 7 n.p. n.p. n.p. n.p. n.p. n.p. n.p. 7 7 7 7 7 7 7
Status 1 as long as the
function lasts
FORM-FEED IN
PROGRESS
n.p. n.p. n.p. n.p. 8 8 8 8 8 8 n.p. n.p. n.p. n.p. n.p. n.p. n.p. 8 8 8 8 8 8 8
Status 1 as long as the
function lasts
-- : non used n.p. : not present
TREND NUMBER 10
BUFFER FULL n.p. -- -- -- -- -- 9 9 9 9 -- 9 -- -- -- -- -- 9 9 9 9 9 9 9
Status 1when the buffer is full.
TREND NUMBER 11
BUFFER FULL n.p. -- -- -- -- -- 10 10 10 10 -- 10 -- -- -- -- -- 10 10 10 10 10 10 10
Status 1when the buffer is full.
TREND NUMBER 12
BUFFER FULL n.p. -- -- -- -- -- 11 11 11 11 -- 11 -- -- -- -- -- 11 11 11 11 11 11 11
Status 1when the buffer is full.
TREND NUMBER 13
BUFFER FULL n.p. -- -- -- -- -- 12 12 12 12 -- 12 -- -- -- -- -- 12 12 12 12 12 12 12
Status 1when the buffer is full.
TREND NUMBER 14
BUFFER FULL n.p. -- -- -- -- -- 13 13 13 13 -- 13 -- -- -- -- -- 13 13 13 13 13 13 13
Status 1when the buffer is full.
TREND NUMBER 15
BUFFER FULL n.p. -- -- -- -- -- 14 14 14 14 -- 14 -- -- -- -- -- 14 14 14 14 14 14 14
Status 1when the buffer is full.
TREND NUMBER 16
BUFFER FULL n.p. -- -- -- -- -- 15 15 15 15 -- 15 -- -- -- -- -- 15 15 15 15 15 15 15
Status 1when the buffer is full.
Table 37.29: Meaning of Bits of Word Commanding External LEDs (fixed light)
BIT NUMBER
WORD 0 VT150W VT300W - VT310W - VT320W
MEANING OF BIT + VT160W +
VT100MT1000 VT100MT1000
E1 0 0 0
E2 1 1 1
E3 2 2 2
E4 3 3 3
E5 4 4 4
E6 5 5 5
E7 6 6 6
E8 7 7 7
E9 8 8 8
E10 9 9 9
E11 10 10 10
E12 11 11 11
E13 12 12 12
E14 13 13 13
E15 14 14 14
E16 15 15 15
-- : not present
Table 37.30: Meaning of Bits of Word Commanding External LEDs (fixed light)
BIT NUMBER
WORD 1 VT150W VT300W - VT310W - VT320W
MEANING OF BIT + VT160W +
VT100MT1000 VT100MT1000
E17 0 0 0
E18 1 1 1
E19 2 -- 2
E20 3 -- 3
E21 -- -- --
E22 -- -- --
E23 -- -- --
E24 -- -- --
E25 -- -- --
E26 -- -- --
E27 -- -- --
E28 -- -- --
E29 -- -- --
E30 -- -- --
E31 -- -- --
E32 -- -- --
-- : not present
Table 37.31: Meaning of Bits of Word Commanding internal red LEDs (fixed light)
MEANING OF BIT
WORD 0 VT VT VT VT VT VT VT VT VT VT
BIT NUMBER 50 60 150 160 170 190 300 310 320 330
W W W W W W W W
0 -- -- -- -- F1 F1 F1 F1 F1 --
1 -- -- -- -- F2 F2 F2 F2 F2 --
2 -- -- -- -- F3 F3 F3 F3 F3 --
3 -- -- -- -- F4 F4 F4 F4 F4 --
4 -- -- -- -- F5 F5 F5 F5 F5 --
5 -- -- -- -- F6 F6 F6 F6 F6 --
6 -- -- -- -- F7 F7 F7 F7 F7 --
7 -- -- -- -- F8 F8 F8 F8 F8 --
8 -- -- -- -- F9 F9 F9 F9 F9 --
-- : not present
Table 37.32: Meaning of Bits of Word Commanding internal red LEDs (fixed light)
MEANING OF BIT
WORD 1 VT VT VT VT VT VT VT VT VT VT
BIT NUMBER 50 60 150 160 170 190 300 310 320 330
W W W W W W W W
2 -- -- -- -- -- F19 F19 -- -- --
3 -- -- -- -- -- F20 F20 -- -- --
4 -- -- -- -- -- F21 F21 -- -- --
5 -- -- -- -- -- F22 F22 -- -- --
6 -- -- -- -- -- -- -- -- -- --
7 -- -- -- -- -- -- -- -- -- --
8 -- -- -- -- -- -- -- -- -- --
9 -- -- -- -- -- -- -- -- -- --
10 -- -- -- -- -- -- -- -- -- --
11 -- -- -- -- -- -- -- -- -- --
12 -- -- -- -- -- -- -- -- -- --
13 -- -- -- -- -- -- -- -- -- --
14 -- -- -- -- -- -- -- -- -- --
15 -- -- -- -- -- -- -- -- -- --
-- : not present
Table 37.33: Meaning of Bits of Word Commanding internal green LEDs (fixed light)
MEANING OF BIT
WORD 0 VT VT VT VT VT VT VT VT VT VT
BIT NUMBER 50 60 150 160 170 190 300 310 320 330
W W W W W W W W
0 -- -- F1 F1 F1 F1 F1 F1 F1 --
1 -- -- F2 F2 F2 F2 F2 F2 F2 --
2 -- -- F3 F3 F3 F3 F3 F3 F3 --
3 -- -- F4 F4 F4 F4 F4 F4 F4 --
4 -- -- F5 F5 F5 F5 F5 F5 F5 --
5 -- -- -- -- F6 F6 F6 F6 F6 --
6 -- -- -- -- F7 F7 F7 F7 F7 --
7 -- -- -- -- F8 F8 F8 F8 F8 --
8 -- -- -- -- F9 F9 F9 F9 F9 --
-- : not present
Table 37.34: Meaning of Bits of Word Commanding internal green LEDs (fixed light)
MEANING OF BIT
WORD 1 VT VT VT VT VT VT VT VT VT VT
BIT NUMBER 50 60 150 160 170 190 300 310 320 330
W W W W W W W W
8 -- -- -- -- -- -- -- -- F25 F25
9 -- -- -- -- -- -- -- -- F26 F26
10 -- -- -- -- -- -- -- -- F27 F27
11 -- -- -- -- -- -- -- -- F28 F28
12 -- -- -- -- -- -- -- -- -- --
13 -- -- -- -- -- -- -- -- -- --
14 -- -- -- -- -- -- -- -- -- --
15 -- -- -- -- -- -- -- -- -- --
-- : not present
Forces
01 -- sequence -- -- -- -- -- -- -- -- -- -- -- -- -- --
02 -- -- Forces page
Forces cur-
03 -- -- --
rent field
-- -- -- -- -- -- -- -- -- -- -- -- -- --
Bit-structured
04 -- -- -- protection
mask
Forces sys-
05 -- -- --
tem context
Sets auto-
06 -- -- -- scroll for mes- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
sages
Sets current
07 -- -- --
language
Priority of
08 -- -- --
messages
-- -- -- -- -- -- -- -- -- -- -- -- --
Operation of
09 -- -- --
messages
Sets auto-
scroll time for
10 -- -- --
information
messages
Sets auto-
11 -- -- -- scroll time for -- -- -- -- -- --
ISA alarms
Sets maximum
time after
12 -- -- --
which the lamp
-- -- -- -- -- -- -- -- --
switches off
Reads current
14 r -- -- --
time
-- -- -- --
Reads current
15 r -- -- --
date
-- -- -- --
Sets current
17 -- -- --
date
-- -- -- --
Reads trend
18 -- -- -- from device -- -- -- -- -- -- -- -- -- -- -- --
buffer
Emptying
19 -- -- -- -- alarm history -- -- -- -- -- --
buffer
Synchroniza-
20 -- -- tion of recipe -- -- -- --
transfer
Request for a
21 -- -- recipe -- -- -- --
Send recipe to
22 -- -- VT without -- -- -- --
overwriting
Send recipe to
23 -- -- VT overwriting -- -- -- --
Command:
24 -- -- internal green -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
LEDs
Command:
flashing of
25 -- -- internal green -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
LEDs
Command:
26 -- -- read and write -- -- -- -- -- -- -- -- -- -- -- --
pipeline
Deletes trend
27 -- -- --
from VT buffer
-- -- -- -- -- -- -- -- -- -- -- --
Reads trend
28 -- -- --
on command
-- -- -- -- -- -- -- -- -- -- -- --
29 -- -- Stop trend -- -- -- -- -- -- -- -- -- -- -- --
30 -- -- Start trend -- -- -- -- -- -- -- -- -- -- -- --
Command:
31 -- -- internal red -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
LEDs
Command:
flashing of
32 -- -- internal red -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
LEDs
Command:
33 -- -- external LEDs -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
Command:
34 -- -- flashing of -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
external LEDs
Report print-
35 -- -- --
ing
-- -- -- -- -- -- --
Printing of the
36 -- -- ISA alarms -- -- -- -- -- -- --
history buffer
37 -- -- -- Hardcopy -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
38 -- -- -- Form-feed -- -- -- -- -- -- --
Zeroes num-
39 -- -- -- ber of print -- -- -- -- -- -- --
pages
Command
makes internal
40 -- -- green LEDs -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
light up flashing
Command
makes inter-
41 -- -- nal red LEDs -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
light up flash-
ing
Command
makes exter-
42 -- -- nal LEDs light -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
up flashing
Acknowledg-
ment of all
43 -- -- -- --
alarms
-- -- -- -- -- --
together
Force transfer
44 -- -- mode -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
Saving the
alarm history
45 -- -- -- --
buffer and
-- -- -- -- -- -- -- -- -- -- -- -- -- -- --
trend buffers
Command for
operating
46 -- -- -- --
working of
-- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
touch screen
Copy recipes
48 -- -- -- -- into the rema- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
nent memory
-- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
-- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
-- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
-- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- --
We list below the commands in detail; unless otherwise indicated all the
parameter values are expressed in binary.
COMMAND 12: Set time for after which lamp switches off
Word Value/Meaning
12
Makes it possible to set the idle time of the terminal after which the display lamp switches off. By idle
0
time we mean no pressing of the keys for a certain time. In the case of touch screens, it means no
pressing of touch screen buttons/keys.
Waiting time
1 Value in minutes (1-30) indicating the time to pass before the display lamp goes off; the value 0 deacti-
vates the function.
2 Not used
3 Not used
Contents Page
List of A list exists showing which devices the VT can communicate with and
protocols including further technical information that may be useful to the program-
mer.
Contents Page
Free terminal The operator terminal has a type of driver called Free terminal that makes
protocol it possible to communicate with any type of intelligent device not supported
by the standard drivers supplied. This driver requires that the device man-
age the VT terminal in all its functions; this happens by sending control
characters that the VT interprets and then sending characters to be dis-
played. When a is pressed, the VT sends the device the value of that
such that the device recognizes and, if necessary, uses it.
To transfer the driver to the VT, the terminal must be set up for reception
(see Setting up for reception of the various terminals) before proceeding
to transfer (see Software Manual).
Once the transfer has been completed the VT displays the following page
This means that the transfer has been effected properly and that the VT is
ready to communicate with the device.
The transfer of the free terminal automatically sets the serial communica-
tion parameters with pre-established values:
VT address -> 00
Speed -> 9600 Baud
Parity -> N
Data bits -> 8
Stop bits -> 2
The above page remains in vision so long as the device connected does not
command it to be canceled and takes over control. The connecting cable is
the same as that used for the transfer (see Chapter 30 -> PC <-> VT con-
nection).
F1 F5
Esc
Editing These values can be changed by pressing + (standard protocol) or
parameters for F1 F5 Help
Esc
VT50 + + (ver.3.0 protocol); the screen shows:
Changes params.
VT Address: 00
Help Info
[Up] [Down] [Enter]
F5
Changes params.
Baud Rate: 9600
Help Info
[Up] [Down] [Enter]
F5
Changes params.
Param: PN,8db,2sb
Help Info
[Up] [Down] [Enter]
F5
F1 F4
Esc
Editing These values can be changed by pressing + Enter
(standard protocol) or
parameters for Help
F4 F1
VT60 Esc
+ Enter
+ (ver.3.0 protocol); the screen shows:
VT Address: 00
Changes params
F1 Info
F4
Enter
F1 Info
F4
Enter
Param: PN,8db,2sb
Changes params
F1 Info
F4
Enter
shift
Editing These values can be changed by pressing twice (standard protocol) or
parameters for Clr PgUp
Esc
VT150/160W + Enter
+ (ver.3.0 protocol); the screen shows:
VT Address: 00
Changes params
PgUp PgDn
Enter
PgUp PgDn
Enter
Param: PN,8db,2sb
Changes params
PgUp PgDn
Enter
Free terminal The VT uses a set of characters that, sent correctly, function as a command
control and enable the VT to carry out certain operations.
characters
For the command to be recognized as such it must be preceded by the con-
trol character <ESC> and followed by the control character <EOT>.
The tables below list the control characters to be used and the commands.
Key codes for As already mentioned, when the are pressed the VT sends a hexadeci-
VT50 mal code to the connected device. The table below lists the association
between code and .
Hexadecimal code
Key
Only key Shift +
F1
Esc
09 14
F2
04 15
F3
02 16
F4
0B 17
F5
0D 18
Help
01 12
Info
03 10
Key codes for As already mentioned, when the are pressed the VT sends a hexadeci-
VT60 mal code to the connected device. The table below lists the association
between code and .
Hexadecimal code
Key
Only key Shift +
F1
01 14
F2
03 15
F3
02 16
F4
0D 17
Enter
Help
09 12
Esc
Key codes for As already mentioned, when the are pressed the VT sends a hexadeci-
VT150/160W mal code to the connected device. The code depends on the the mode set for
the keyboard; whether Numeric or ASCII. The former sends the code
related to the numbers on the keys; the second sends the code of the alpha-
betical characters. The default setting is Numeric, but this can be changed
by sending the command K (see Page 39-6). The table below lists the asso-
ciation between code and .
Table 39.5: Association between keys (Numeric mode) and hexadecimal codes (Part 1 of 2)
Hexadecimal code
Key
Only key shift +
F6
F1
81 86
F7
F2
82 87
F8
F3
83 88
F9
F4
84 89
F10
F5
85 8A
Info 0C 0C
Help 0B 0B
PgUp
01 05
PgDn
03 06
04 04
02 02
. 20 2E
Space
Clr
Esc
27 0A
Reinitializa-
0D
Enter tion of VT
A
B
0
30 30
C
Table 39.5: Association between keys (Numeric mode) and hexadecimal codes (Part 2 of 2)
Hexadecimal code
Key
Only key shift +
D
E
1
31 31
F
G
H
2
32 32
I
J
K
3
33 33
L
M
N
4
34 34
O
P
Q
5
35 35
R
S
T
6
36 36
U
V
W
7
37 37
X
Y
Z
8
38 38
-
+
/
9
39 39
=
In ASCII mode the code relating to the first, second or third letter respec-
tively is sent when the keys F1, F2, or F3 are pressed followed by the key
containing the alphanumeric characters.
Example.
S
F6
T
F1 U 6
Pressing + sends the code relating to the letter S.
Table 39.6: Association between keys (Ascii mode) and hexadecimal codes (Part 1 of 3)
Hexadecimal code
Key
F6 F7 F8
Only key shift +
F1
+
F2
+
F3
+
F6
F1
-- 86 -- -- --
F7
F2
-- 87 -- -- --
F8
F3
-- 88 -- -- --
-- : Send no code
Table 39.6: Association between keys (Ascii mode) and hexadecimal codes (Part 2 of 3)
Hexadecimal code
Key
F6 F7 F8
Only key shift +
F1
+
F2
+
F3
+
F9
F4
84 89 84 84 84
F10
F5
85 8A 85 85 85
Info 0C 0C 0C 0C 0C
Help 0B 0B 0B 0B 0B
PgUp
01 05 01 01 01
PgDn
03 06 03 03 03
04 04 04 04 04
02 02 02 02 02
. 20 2E 20 20 20
Space
Clr
Esc
27 0A 27 27 27
Reinitializa-
0D 0D 0D 0D
Enter tion of VT
A
B
0
30 30 41 42 43
C
D
E
1
31 31 44 45 46
F
G
H
2
32 32 47 48 49
I
J
K
3
33 33 4A 4B 4C
L
M
N
4
34 34 4D 4E 4F
O
P
Q
5
35 35 50 51 52
R
S
T
6
36 36 53 54 55
U
-- : Send no code
Table 39.6: Association between keys (Ascii mode) and hexadecimal codes (Part 3 of 3)
Hexadecimal code
Key
F6 F7 F8
Only key shift +
F1
+
F2
+
F3
+
V
W
7
37 37 56 57 58
X
Y
Z
8
38 38 59 5A 2D
-
+
/
9
39 39 2B 2F 3D
=
-- : Send no code
Code of The table below lists the association between code and .
External keys
for MT1000 Table 39.7: Association between MT1000 keys and hexadecimal codes
and VT160W Hexadecimal code
A0 A1 A2 A3
A4 A5 A6 A7
A8 A9 AA AB
AC AD AE AF
B0 B1 B2 B3
Hexadecimal code
A0 A1 A2 A3 A4 A5
A6 A7 A8 A9 AA AB
AC AD AE AF B0 B1
Free terminal Using the Free terminal protocol the VT can be connected in a RS485
in Network linked network to enable a master device to show information to or request
information from the various connected terminals.
Each connected terminal in this network must have been loaded with the
Free terminal protocol and must have a different network address from any
of the other addresses in the network (01 -> 31). If the address is 00, the ter-
minal is not considered to be a participant in the network.
Once the terminal has been connected to the network (with an address other
than 00) and switched on, the VT terminals behavior is different from that
seen in the previous paragraphs. The VT will not respond to any command
unless it has been addressed. Addressing a terminal means that from that
moment on the master device will communicate exclusively with that ter-
minal. Let us imagine the rotating selector with 31 positions from 0 to 31,
the position of the selector indicates which terminal to communicate with.
Help Info F1
Esc
For example, of the VT buffer contained 3 , and , then the
VT would respond to the first request with "0301" (3 in the buffer, the
first having the code 01Hex). The response to the second request would be
"0203" (2 , code 03Hex); the response to the third request would be
"0102" (1 , code 09Hex). In order to communicate that there are no keys
in its buffer, the VT will respond to any further request with "0000".
Example of Let us suppose we have a VT50 that has to display the text GOOD
handling F5
MORNING OPERATOR centered on the display and, when is
pressed is canceled and replaced by the word READY justified top left.
There are various ways of proceeding, each leading to the same result; what
follows is just one example.
First check that the VT communicates with the device. Send the following
string.
<ESC>Y<EOT>
<OK>
At this point the device must interpret the response and control begins.
<ESC>C<EOT>
The display is cleared and the cursor goes automatically to the top left cor-
ner with the 0,0 (y,x) co-ordinate.
Position the cursor at co-ordinate 0,5 (y,x). Send the following string.
<ESC>A0005<EOT>
Send the first part of the text to be displayed GOOD MORNING. Send
the following string.
GOOD MORNING
GOOD MORNING_
Position the cursor on the co-ordinate 1,5 (y,x). Send the following string.
<ESC>A0105<EOT>
GOOD MORNING
_
Send the rest of the text to be displayed: OPERATOR. Send the follow-
ing string.
OPERATOR
GOOD MORNING
OPERATOR_
At this point the device must be set up to control the keys when pressed;
F5
when is pressed the VT responds with the following character.
<CR>
The device must interpret and send the string for canceling the text. Send
the following string.
<ESC>C<EOT>
The display is now cleared and the cursor positioned automatically in the
top left corner with the coordinate 0,0 (y,x)
Now send the text to be displayed READY. Send the following string.
READY
READY_
The above represents only a simple example of how to use the Free Termi-
nal.
Contents Page
GE DRIVE 40-17
Contents Page
LG PLC 40-52
Contents Page
All VTs communicate with other devices using serial port communication.
In this chapter you will find information on all the cables used to connect
with various devices together with their order codes.
General notes Serial communications are highly susceptible to disturbances, so, in order
to limit as much as possible the influence of these disturbances good quality
shielded cables must be used.
The table below lists the characteristics of the cable to be used for serial
connection.
Always:
Find the shortest route
Lay disturbed cables separately
Connecting It is essential for the interface cables between the VT and the Device be
the cable correctly shielded in order to ensure that serial communication occurs free
shield from all types of external interference. For this reason all the cables listed in
this manual absolutely must be shielded cables and the D-sub connectors
both on the VT side and the Device side must have metal or conductive
plastic shells.
The diagram below shows the correct way of connecting the shield.
Connective shell
Braiding
Securing screw
Connective shell
The interface cable braiding must be electrically connected both to the shell
and the body of the connector at both ends of the cable.
If the connection operation cannot be carried out at the Device side due to
the particular type of serial connector, the braiding will have to be taken
outside the connector and connected to the earth terminal.
This operation must also be carried out if the body of the Devices serial
connector, although of a standard type, is not electrically connected to the
Note that in this situation the shield must still be connected both to the shell
and the body of the connector.
Certain cable diagrams show the pin connections of the shield signals on
the Device side: in these cases, not only does the above apply but the shield
must also be connected to them.
In any event the shield must never be connected on the VT side (pin 1).
MSP<->ASP The cables referred to in this chapter are designed to be connected to the
conversion MSP port of the VT terminal; if you need to use a coded on the ASP port, it
will be necessary to use the adapters listed below.
Rx 2 3 Rx (RS232)
Tx 3 2 Tx
(SeeChapter 40 -> Connecting the cable shield)
RTS 10 4 RTS
CTS 11 5 CTS
GND 7 7 GND
+Vcc 13 16 +Vcc
Max. 15 cm.
CTS 11 5 CTS
GND 7 7 GND
+Vcc 13 16 +Vcc
Max. 15 cm.
Rx 2 3 Rx (RS232)
Tx 3 2 Tx
(SeeChapter 40 -> Connecting the cable shield)
RTS 7 4 RTS
CTS 8 5 CTS
GND 5 7 GND
Max. 15 cm.
TxRx+ 22 A (RS485)
120 120
1/4 W 1/4 W (See Chapter 40 -> Connecting the cable shield)
TxRx- 10 B
GND 7
JUMPER SETTINGS
25
RTS 4
CTS 5 Data Format
15 IEEE
18 BCD
Dip-switch 4
ABB DRIVE
16 1 SHD (RS485)
470
1/4 W
(See Chapter 40 -> Connecting the cable shield)
TxRx+ 22 9 TxRx+
220
1/4 W
TxRx- 10 8 TxRx-
470
1/4 W
GND 7 5 GND
25
RTS 4
CTS 5
15
18
ALLEN-BRADLEY DRIVE
Max. 15 m.
1 SHD (RS232)
RxD 3 3 Tx
N.B.: On the device set protocol Computer Mode with the aid of ATLAS DMC
TxD 2 2 Rx
Users manual.
GND 7 7 GND
25 (See Chapter 40 -> Connecting the cable shield)
RTS 4
CTS 5
15
18
Max. 15 m.
1 SHD (RS422)
TX+ 23 10 RX+
220 N.B.: On the device set protocol Computer Mode with the aid of ATLAS DMC
1/4 W Users manual.
TX- 12 9 RX-
RX+ 13 12 TX+ (See Chapter 40 -> Connecting the cable shield)
220
1/4 W
RX- 24 11 TX-
25 7 GND
GND 7
RTS 4
CTS 5
15
18
BERGER-LAHR DRIVE
CAN- 2 2 CAN_Low For the VT side cable termination see Chapter 34 -> CAN: Connection.
V- 1 1 GND
For the DRIVE side cable termination see Drive manual TLC53x.
NOTE: The max. length of the cable depends on the transmission speed.
15
18
Max. 15 m.
16 1 (RS485)
470 6
1/4 W
Communication card UD71 or UD70 required
TxRx+ 22 7
220
1/4 W UD71:
TxRx- 10 2 Set parameter 0.32 = ANSI2
470
3
1/4 W UD70:
GND 7 Set parameter 17.06 = 5 (ANSI2)
25 Set parameter 17.05 = (Serial address)
RTS 4
Set parameter 17.07 = (Baud rate)
DANFOSS DRIVE
ELAU DRIVE
VCC 16 (RS422)
470
1/4 W
See notes to follow.
Tx+ 23 4 RxD+
220
1/4 W (See Chapter 40 -> Connecting the cable shield)
Tx- 12 5 RxD-
470
1/4 W
GND 7
25
Rx+ 13 3 TxD+
120
1/4 W
Rx- 24 2 TxD-
RTS 4
CTS 5
15
18
Max. 200 m.
Vcc 16 (RS485)
470 3 TxD+
1/4 W
See notes to follow.
TxRx+ 22 4 RxD+
220 120
1/4 W 1/4 W (See Chapter 40 -> Connecting the cable shield)
TxRx- 10 5 RxD-
470
2 TxD-
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
Max. 200 m.
You can use either a 4-wire RS422 or a 2-wire RS485 connection. In the
latter case it is essential to use the ELAU ModBus_v001001.lib library or a
later version. Using the RS485 connection allows you to connect more than
one ELAU device to the same VT port.
N.B. :
Defining the length of the arrays in the programming SW, ELAU puts
the number 1 for the first element of the array; this implies the existence
of an offset of 1 between the address of the array element and the
address specified in the VT variable. E.g.: if, using the VT, you want to
read and edit the element at single word 20 of the array W4000, num-
ber 19 will have to be specified as the address of the VT variable.
To have retentive data in the ELAU device, the relevant array must be
declared as VAR_RETAIN.
Check that the ModBus address assigned in the configuration of the
device in VTWIN corresponds to the value assigned to the parameter
Modbus_SlaveNr of the ELAU Function Block.
EUROTHERM DRIVE
Shild 3 (CAN)
CAN+ 4 5 CAN_H
For the VT side cable termination see Chapter 34 -> CAN: Connection.
CAN- 2 4 CAN_L For the DRIVE side cable termination use the appropriate accessory BUS termi-
V- 1 6 CAN_GND nation plug (see Drive manual) in connector X20/21.
NOTE: The max. length of the cable depends on the transmission speed.
EVER DRIVE
1 SHD (RS232)
RxD 3 2 TxD
(See Chapter 40 -> Connecting the cable shield)
TxD 2 3 RxD
GND 7 7 GND
25 4 RTS
RTS 4 5 CTS
CTS 5 6 DSR
15 8 CD
18 20 DTR
Max. 15 m.
FAGOR DRIVE
Max. 15 m.
VCC 16 (RS422)
470
1/4 W
(See Chapter 40 -> Connecting the cable shield)
Tx+ 23 9 #RxD422
330 330
1/4 W 1/4 W
Tx- 12 8 RxD422
470
1/4 W
GND 7
25
470
1/4 W
Rx+ 13 7 #TxD422
330 330
1/4 W 1/4 W
Rx- 24 6 TxD422
470
1/4 W
RTS 4
CTS 5
15
18
GALIL DRIVE
Max. 15 m.
GE DRIVE
HITACHI DRIVE
(RS422)
TX+ 23 2 RECEIVE
220 (SeeChapter 40 -> Connecting the cable shield)
1/4 W
TX- 12 3 RECEIVE
RX+ 13 5 SEND
220
1/4 W
RX- 24 6 SEND
25
GND 7 8
7
RTS 4 6
5
4
CTS 5 3
2
15 1
18 Front
View
KEB DRIVE
Max. 15 m.
16 (RS485)
470
8
1/4 W (See Chapter 40 -> Connecting the cable shield)
TxRx+ 22 4
220
1/4 W
TxRx- 10 9
470
5
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
INDRAMAT DRIVE
RxD 3 2 TD (RS232)
TxD 2 3 RD
SERIAL PORT 1 connection requires no parametrization, while the TYPE param-
GND 7 7 SG
eter like ASCII HOST needs to be set for SERIAL PORT 2. The MODE parameter
25 must be set as RS232.
RTS 4
CTS 5
(See Chapter 40 -> Connecting the cable shield)
15
18
Max. 12 m.
VCC 16 (RS485)
470
1/4 W
SERIAL PORT 1 connection requires no parametrization, while the TYPE param-
TxRx+ 22 4 RS485+
220 eter like ASCII HOST needs to be set for SERIAL PORT 2. The MODE parameter
1/4 W must be set as RS485.
TxRx- 10 5 RS485-
470 (See Chapter 40 -> Connecting the cable shield)
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
LENZE DRIVE
Max. 15 m.
Shild 3 PE (CAN)
CAN+ 4 HI
For the VT side cable termination see Chapter 34 -> CAN: Connection.
CAN- 2 LO For the DRIVE side cable termination use the related resistence (120Ohms, sup-
V- 1 GND plied with the device) between the HI and LO terminals in the X4 connector (see
also Drive manual).
LUST DRIVE
Max. 15 m.
OMRON DRIVE
OSAI DRIVE
TxD 2 2 Rx (RS232)
RxD 3 3 Tx
See Chapter 40 -> Connecting the cable shield)
GND 7 5 GND
25 7 RTS
RTS 4 8 CTS
CTS 5 6 DSR
15 4 DTR
18
Max. 15 m.
PANASONIC DRIVE
RxD 3 3 Tx (RS232)
TxD 2 5 Rx
(See Chapter 40 -> Connecting the cable shield)
GND 7 4 GND
25
RTS 4
CTS 5
15 5
8
Front 2
18 7 4
View 6
1
3
Max. 15 m.
Max. 15 m.
RxD 3 3 Tx (RS232)
TxD 2 2 Rx
Dip-Switch SW1:
GND 7 5 GND
1 -> OFF
25 2 -> OFF
RTS 4 3 -> OFF
4 -> OFF
CTS 5
5 -> OFF
15 6 -> OFF
18 7 -> OFF
8 -> OFF
(RS485)
4 TDB
Dip-Switch SW1:
TxRx+ 22 1 RDB
120
1 -> OFF (ON - Only if the last node)
1/4 W 2 -> OFF (ON - Only if the last node)
TxRx- 10 7 RDA 3 -> OFF
4 -> OFF
8 TDA
5 -> OFF
GND 7 6 GND 6 -> OFF
25 7 -> OFF
8 -> OFF
RTS 4
CTS 5 WARNING!!! For Hardware configuration refer to manual 6K Series Hardware
15 Installation Guide.
18
(See Chapter 40 -> Connecting the cable shield)
RxD 3 3 Tx (RS232)
TxD 2 2 Rx
(See Chapter 40 -> Connecting the cable shield)
GND 7 5 GND
25
RTS 4
CTS 5
15
18
Max. 15 m.
ROBOX DRIVE
Max. 15 m.
S.B.C. DRIVE
15 8 SHD (RS422)
18 6 BR+
Device address: 0...31
TX+ 23 2 RX+
220
1/4 W (See Chapter 40 -> Connecting the cable shield)
TX- 12 4 RX-
7 BR-
RX+ 13 1 TX+
220
1/4 W
RX- 24 3 TX-
RTS 4
CTS 5
GND 7
25
8 SHD (RS485)
16 6 BR+
470 Device address: 0...31
1 TX+
1/4 W
TxRx+ 22 2 RX+ (See Chapter 40 -> Connecting the cable shield)
220
1/4 W
TxRx- 10 4 RX-
470
3 TX-
1/4 W
GND 7 7 BR-
25
RTS 4
CTS 5
15
18
SEW-EURODRIVE DRIVE
(RS232)
RxD 3 2 TxD
TxD 2 3 RxD Communication card SEW-EURODRIVE USS21A required
GND 7 5 GND
25 N.B: Not valid for terminals VT50 and VT60.
RTS 4 4 DTR
(See Chapter 40 -> Connecting the cable shield)
CTS 5
15
18
Max. 15 m.
(RS232)
RxD 3 2 TxD
TxD 2 3 RxD Communication card SEW-EURODRIVE USS21A required
GND 7 5 GND
25 (See Chapter 40 -> Connecting the cable shield)
RTS 4
CTS 5
15
18
Max. 5 m.
SIEI DRIVE
16 (RS485)
470
1/4 W WARNING!!!
TxRx+ 22 3 TxRx+
220 If the jumpers S18 and S19 on the regulator card are in position A (serial line gal-
1/4 W vanically isolated from the regulator section), pin 5 and 9 must be connected to
TxRx- 10 7 TxRx- the power unit.
470
1/4 W (See Chapter 40 -> Connecting the cable shield)
GND 7 5 0V
25 9 +5V
RTS 4
CTS 5
15
18
SIEMENS DRIVE
Max. 15 m.
16 (RS485)
470
1/4 W
(See Chapter 40 -> Connecting the cable shield)
TxRx+ 22 3 RS485P
220
1/4 W
TxRx- 10 8 RS485N
470
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
STBER DRIVE
RxD 3 4 Tx (RS232)
TxD 2 2 Rx
(See Chapter 40 -> Connecting the cable shield)
GND 7 5 GND
25
RTS 4
CTS 5
15
18
Max. 15 m.
16 (RS485)
470
3
1/4 W (See Chapter 40 -> Connecting the cable shield)
TxRx+ 22 2 TxRx+
220
1/4 W
TxRx- 10 6 TxRx-
470
7
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
TELEMECANIQUE DRIVE
Max. 15 m.
Rx- 24 7 Tx-
GND 7
25
15 5
8
2
18 7 4
1
6
3
Front
View
ABB PLC
Max. 15 m.
Max. 15 m. NOTE: the cable supplied by ESA does not have the connection represented by
the dotted line.
Max. 15 m.
Max. 15 m.
Front
View
Max. 15 m.
Max. 15 m.
Tx+ 2 6 RD (RS232)
GND 7 4 0V
25
15
8
7
18 6
5
4
3
2
1
Front
View
Max. 15 m.
Max. 15 m.
Max. 15 m.
Front
View
Max. 15 m.
ALLEN-BRADLEY PLC
CVPLC07112
VT SLC500
terminal (DH485)
CVPLC07112 ESA
VT protective SLC500
terminal device (DH485)
6 cm
3x3 cm 19 cm
Allen-Bradley Allen-Bradley
CVPLC07112 Isolated Link cable
VT SLC500
terminal Coupler type: (DH485)
1747-C11
1747-AIC
Example:
N7:0
N7:1
Example:
N7:0
N7:1
Max. 15 m. Example:
N7:0
N7:1
TxRx+ 22 1 TxRx+ Cable valid for several VTs connected to a single PLC.
#Last
TxRx+ 22
220
1/4 W
TxRx- 10
GND 7
25
RTS 4
CTS 5
15
18
ALTUS PLC
Max. 3 m.
Max. 3 m.
VCC 16 (RS485)
470
4 RxD+
1/4 W (See Chapter 40 -> Connecting the cable shield)
TxRx+ 22 3 TxD+
220
1/4 W
TxRx- 10 8 TxD-
470
9 RxD-
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
ATOS PLC
RxD 3 3 Tx (RS232)
TxD 2 2 Rx
(See Chapter 40 -> Connecting the cable shield)
GND 7 5 GND
25
RTS 4
1
CTS 5 2
3
4
15 5
6
18
Front
View
Max. 15 m.
BECKHOFF PLC
Max. 15 m.
Max. 15 m.
Max. 15 m.
VCC 16 (RS485)
470
1/4 W Terminations are not needed on cables of less than 5 meters and a transmission
TxRx+ 22 3 TxRxD+
speed of less than 19200 Baud.
220
1/4 W
TxRx- 10 8 TxRxD- (See Chapter 40 -> Connecting the cable shield)
470
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
BOSCH PLC
Max. 15 m.
Max. 15 m.
Max. 15 m.
FOXBORO PLC
RxD 3 4 Tx (RS232)
TxD 2 5 Rx
(See Chapter 40 -> Connecting the cable shield)
GND 7 6 GND
25
RTS 4
CTS 5
15 8
7
6
18 5
4
3
2
1
Front
View
Max. 15 m.
FUJI PLC
GE FANUC PLC
(RS422)
Tx- 12 10 Rx-
470 (See Chapter 40 -> Connecting the cable shield)
1/4 W
GND 7 7 GND
25
Rx+ 13 13 Tx+
Rx- 24 12 Tx-
RTS 4 6 RTS-
CTS 5 15 CTS-
15 14 RTS+
18 8 CTS+
Front
View
Max. 15 m.
GEFRAN PLC
RxD 3 15 Tx (RS232)
TxD 2 14 Rx
GND 7 13 GND (See Chapter 40 -> Connecting the cable shield)
25 12
RTS 4 11
CTS 5 4
15 5
18
Max. 10 m.
HITACHI PLC
Max. 15 m.
Max. 15 m.
Soldered
end
Max. 15 m.
1 4
Soldered 7
2 5
End 3
8
6
Max. 15 m.
SHD
Series EH150
(RS232)
RxD 3 5 TxD
TxD 2 6 RxD NOTE:
RTS 4 7 CTS 127 PLCs connectable in Hitachi network with 2 Links (0-63 stations per Link).
CTS 5 8 RTS
LUMP:
GND 7 1 GND
25 Parameter Default Values Notes
15 8 01,02 or
7 L FF Address of Link number.
6 FF
18 5
4
3 00-63 or Address of network node (as indicated by
2 U FF
1 FF the network card rotary switches).
Front Address of network node with connection
View M 00 00-63
using COMM-H additional serial cards.
Address of network node with connection
Max. 15 m. P 00 00-63
using COMM-H additional serial cards.
TM:
SHD COMM H
(RS422)
TX+ 23 RxDP
220 (See Chapter 40 -> Connecting the cable shield)
1/4 W
TX- 12 RxDN
RX+ 13 TxDP
220
1/4 W
RX- 24 TxDN
25 RxDG
GND 7 TxDG
RTS 4
CTS 5
15
18
Rx+ 18 2 Rx
IKT 14
RTS 4 7 0V
560
CTS 5
1/4 W
Tx- 11 3 Tx
TX+ 9 1 12Vdc
Soldered 4 3 2 1
End 8 7 6 5
Max. 200 m.
Soldered
end
TxRx+ 22 3 A (RS485)
220
1/4 W N.B. Make sure that the two insertion jumpers of the interface termination resis-
TxRx- 10 7 B tances located in the RS485 hatch (visible on the front part of the PLC) are
GND 7 hooked up (see PLC manual).
25
(See Chapter 40 -> Connecting the cable shield)
RTS 4
CTS 5
15
18
Soldered
end
Max. 15 m.
Rx 3 3 Tx (RS232)
Tx 2 2 Rx
GND 7 5 GND
(See Chapter 40 -> Connecting the cable shield)
25
RTS 4
CTS 5
15
18
Max. 15 m.
KEYENCE PLC
RxD 3 5 SD (RS232)
TxD 2 3 RD
GND 7 4 SG
25
RTS 4
1
CTS 5 2
3
4
15 5
6
18
Front
View
Max. 15 m.
KOYO PLC
Max. 15 m.
Max. 15 m.
Max. 15 m.
Max. 15 m.
KUHNKE PLC
Max. 15 m.
LG PLC
Max. 15 m.
Max. 15 m.
15
18
Max. 15 m.
MATSUSHITA-NAIS PLC
18 Front 6 1
3
View
Soldered
end
Max. 15 m.
MICROLINK PLC
Front
View
Max. 15 m.
MITSUBISHI PLC
Max. 15 m.
Max. 15 m.
Max. 15 m.
OMRON PLC
1 SHD (RS232)
RxD 3 2 TxD
Jump-connect the GR and LG terminals on the PLC terminal block
TxD 2 3 RxD
GND 7 7 GND (See Chapter 40 -> Connecting the cable shield)
25 4 RTS
RTS 4 5 CTS
JUMPER SETTINGS C200H-LK201
CTS 5
15
Rear-fend jumpers Front-end switches
18
Max. 15 m.
HOST
Max. 15 m.
NT
Max. 15 m.
1 SHD (RS232)
RxD 3 2 TxD
(See Chapter 40 -> Connecting the cable shield)
TxD 2 3 RxD
GND 7 9 GND
25 4 RTS
RTS 4 5 CTS
CTS 5
15
18
Max. 15 m.
SAIA PLC
Max. 15 m.
Max. 15 m.
In this way, if you send the PLC in RUN using the SAIA utility S/W, the ERROR
light switches on, but this is normal. To switch the light off, just remove the instruc-
tion "SASI 0" when the PLC is connected with the utility S/W.
Max. 15 m.
Max. 15 m.
Max. 15 m.
SCHLEICHER PLC
(RS232)
RxD 3 4 TxD
TxD 2 5 RxD (See Chapter 40 -> Connecting the cable shield)
GND 7 1 Vo
25
RTS 4
CTS 5
15
18
Max. 15 m.
Max. 15 m.
(RS422)
TX+ 23 RX+
220
N.B: Declare in the PLC program the type of port used.
1/4 W
TX- 12 RX-
(See Chapter 40 -> Connecting the cable shield)
RX+ 13 TX+
220
1/4 W
RX- 24 TX-
25 GND
GND 7
RTS 4
CTS 5
15
18
SIEMENS PLC
16 (RS485)
470
1/4 W SIMATIC S7 200
TxRx+
TxRx+ 22 3
(B) Address of CPU = 1 - 126
220
1/4 W
TxRx- SIMATIC S7 300, S7 400 MPI
TxRx- 10 8
(A)
470 Address of VT: 1...31
1/4 W Address of PLC: 1...31
GND 7
25 To have simultaneous communication between the PLC S7 programming pack-
age and the VT, it is advisable to use the SIEMENS 6ES7972-OBB20-OXAO
RTS 4
passing connector.
CTS 5
15 N.B.: Max. 50m without repeater
18
(See Chapter 40 -> Connecting the cable shield)
Max. 50 m.
(RS485)
6 P5V
470
SIMATIC S7 200
1/4 W
TxRx+ Address of CPU = 1 - 126
TxRx+ 22 3
(B)
220
1/4 W SIMATIC S7 300, S7 400 MPI
TxRx-
TxRx- 10 8 Address of VT: 1...31
(A)
470 Address of PLC: 1...31
1/4 W
GND 7 5 GND
Instead of using a 9 pin connector and integrating the resistances, the following Si-
25 emens connectors can be used with resistances already integrated and insertable
RTS 4 with a sliding switch:
SIEMENS 6ES7972-0BA10-0XA0
CTS 5
SIEMENS 6ES7972-0BA40-0XA0
15 SIEMENS 6GK1500-0EA00
18
For simultaneous communication between the programming package, the PLC S7
and the VT, you are advised to use the following Siemens passing connectors with
resistances already integrated and insertable with a sliding switch:
#n SIEMENS 6ES7972-0BB10-0XA0
SIEMENS 6ES7972-0BB40-0XA0
TxRx- 10
GND 7
25
RTS 4
CTS 5
15
18
#Last
16
470
1/4 W
TxRx+ 22
220
1/4 W
TxRx- 10
470
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
Max. 50 m.
SPRECHER+SCHUH PLC
Max. 15 m.
SQUARE-D PLC
Soldered 4 3 2 1
end 8 7 6 5
Max. 200 m.
TELEMECANIQUE PLC
If the CPU is of a hardware version coded higher than V3 (E.g.. CPU 47/411,
47/425 etc.) the max length of the cable relates to the particular characteristics of
See note the interface in Current loop (max 1000 meters) even without employing the
optoisolating device mentioned above, in so far as the CPUs have an internal cir-
cuitry created to guarantee the optoisolation of the line.
16 (RS485)
470
1/4 W Point to point connection.
TxRx+ 22 14 TxRx+
220 220
1/4 W 1/4 W Address of VT: 4...31
TxRx- 10 7 TxRx- Address of PLC (N): 0
470 Address of PLC module: 254
2
1/4 W
GND 7 3 (See Chapter 40 -> Connecting the cable shield)
25 5
RTS 4 9
CTS 5 10
15 11
18 12
15
18
Soldered
end
(RS485)
TxRx+ 22 7 TxRx+
#n Soldered
end
TxRx+ 22
TxRx- 10
GND 7
25
RTS 4
CTS 5
15
18
#Last
16
470
1/4 W
TxRx+ 22
220
1/4 W
TxRx- 10
470
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
(RS485)
TxRx+ 22 14 TxRx+
220
1/4 W Cable valid for several VTs connected to a single Master PLC.
TxRx- 10 7 TxRx-
GND 7 2 Address of VT: 4...31
Address of PLC (N): 0
25 3
Address of PLC module: 254
RTS 4 5
CTS 5 9 (See Chapter 40 -> Connecting the cable shield)
15 10
18 11
12
15
#n
TxRx+ 22
TxRx- 10
GND 7
25
RTS 4
CTS 5
15
18
#Last
16
470
1/4 W
TxRx+ 22
220
1/4 W
TxRx- 10
470
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
#n In the case of PLCs TSX17, TSX47, TSX67 and TSX87 refer to the PLC man-
ual to see which pins to jump-connect on the network connector to assign
TxRx+ 22
the chosen Slave address.
#Last
16
470
1/4 W
TxRx+ 22
220
1/4 W
TxRx- 10
470
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
Max. 15 m.
VCC 16 (RS422)
330
1/4 W
Tx+ 23 9 Data IN+ NB: Set the protocol in ASCII mode (AUX function of TISOFT from version 1.2
100 upwards).
1/4 W
Tx- 12 10 Data IN- (See Chapter 40 -> Connecting the cable shield)
330
1/4 W
GND 7
25
Rx+ 13 14 Data OUT+
150 220
1/4 W 1/4 W
Rx- 24 16 Data OUT-
RTS 4 19 RTS+
CTS 5 11 CTS+
15 18 RTS-
18 23 CTS-
Max. 15 m.
VCC 16 (RS422)
470
1/4 W
Tx+ 23 9 Data IN+ (*) Valid only in the case of CPU 545 with hardware versions 545-1102, 545-1103
220 and 545-1104. In the case of CPU 545 with lower hardware version see cable
1/4 W CVPLC06202.
Tx- 12 2 Data IN-
470 (See Chapter 40 -> Connecting the cable shield)
1/4 W
GND 7 5 GND
25
Rx+ 13 3 Data OUT+
220
1/4 W
Rx- 24 8 Data OUT-
RTS 4
CTS 5
15
18
TOSHIBA PLC
RTS 4
CTS 5 Soldered
end
(RS232)
RxD 3 1 TxD
TxD 2 3 RxD (See Chapter 40 -> Connecting the cable shield)
CTS 5 5 RTS
RTS 4 2 CTS
GND 7 6 GND
25
15 4
1
18
Soldered 2 5
7
end 3
8
6
Max. 15 m.
(RS232)
RxD 3 3 TxD
TxD 2 2 RxD (See Chapter 40 -> Connecting the cable shield)
CTS 5 7 RTS
RTS 4 8 CTS
GND 7 5 GND
25
15
18
Max. 15 m.
Max. 15 m.
16 (RS485)
470 7 RB
1/4 W
(See Chapter 40 -> Connecting the cable shield)
TxRx+ 22 9 TB
220
1/4 W
TxRx- 10 6 RA
470
8 TA
1/4 W
GND 7
25
RTS 4
CTS 5
15
18
ASCON THERMOREGULATOR
Max. 15 m.
GEFRAN THERMOREGULATOR
Max. 3,5 m.
HENGSTLER THERMOREGULATOR
WEST THERMOREGULATOR
Front
View
Max. 15 m.
Cable The table below lists all the cables mentioned in the chapter together with
information their order codes and a description of the type of device with which it can
summary be used.
Contents Page
All our VTs are built to withstand the effects of the more common chemical
substances encountered in industrial and non-industrial environments. Each
element of the VT that could be exposed to these substances (epoxy coat-
ing, keyboard membrane, screen surface, touch screen and gaskets), is
tested to determine its degree of resistence.
The type of test is not the same for each component but changes according
to the testing authority. Below is an example of a test (carried out by Alca-
tel Bell).
A 2 cm ball of cotton wool was immersed in the test substance and then
placed on the keyboard. Two cotton wool balls with different substances
were placed separately on each keyboard; this was then put in a Petri dish
and kept at a temperature of 25C for an hour; after this, the keyboard was
washed in water and dried.
The substances not appearing in the table were not tested, so there
is no information regarding their effect.
Chemical The table shown below lists all the substances used for the test with their
substances various results.
The following table DOES NOT show any test carried out on the
plastic case of terminals VT, H series. For further information, see
Page 41-7
Notes:
1 - According to Alcatel Bell tests, 2 - According to DIN42115 Parts 2, 3 standards - According to raw material producers, 4 - Tested at 50C
Chromic acid
10% 6M -- -- -- -- -- -- "
20% 6M -- -- -- -- -- -- "
Citric acid 5% 3Y -- -- -- -- -- --
Coca Cola NS -- -- A -- -- -- --
Cooking salt solution NS -- -- -- -- -- E --
Copper sulphate 10% 3Y -- -- -- -- -- --
Crude oil NS 3Y -- -- -- -- -- --
Cutting oil NS -- >24h -- >24h -- -- >24h
Cyclohexanol NS -- >24h -- >24h -- -- >24h
Detergent NS -- -- A -- -- -- --
Diesel fuel NS -- >24h A >24h -- -- >24h
Diethyle ether NS -- >24h -- >24h -- -- >24h
Dioxan NS -- >24h -- >24h -- -- >24h
Domestos NS -- >24h4 -- >24h4 -- -- --
Downey NS -- >24h4 -- >24h4 -- -- --
Edible oil NS 3Y -- -- -- -- -- --
Essence of turpentine substitute NS 3Y -- -- -- -- -- --
Ethanol
NS -- -- A >24h >24h E >24h
96% 3Y -- -- -- -- -- --
Ethanol denat. NS 1M -- -- -- -- -- -- "
Ethylacetate NS -- >24h -- >24h -- -- >24h
Ethylene glycol NS O -- A -- -- -- -- "
Fantastic NS -- >24h4 -- >24h4 -- -- --
NS -- -- A -- -- -- --
Formaldehyde
35Vol. 3Y -- -- -- -- -- --
37% -- >24h -- -- -- -- --
42% -- >24h -- -- -- -- --
5% 3Y -- -- -- -- -- --
Formic acid 10% 3Y -- -- -- -- -- --
<50% -- >24h -- >24h -- -- >24h
Formula 409 NS -- >24h4 -- >24h4 -- -- --
Gasoline/petrol NS 3Y -- A >24h >24h F >24h "
Glacial acetic acid NS -- -- -- <1h -- -- <1h "
Legend:
A - No visible degradation, B - Very slight degradation, C - Slight degradation, D - Damage visible or gross, E - Unlimited use, F - Limitated use, G - Use inad-
visable, S - The surface melts, X - The surface blisters, O - The surface is destroyed, CO - Concentrated, HC - High concentration, LC - Low concentration,
SA - Saturated, NS - Not specified, h - Hour(s), M - Month(s), Y- Year(s), - All the elements tested resist all the substances, " - At least one of the ele-
ments tested may be damaged by the substances in question, # - All the elements tested may be damaged by the substances in question, -- Not tested.
Notes:
1 - According to Alcatel Bell tests, 2 - According to DIN42115 Parts 2, 3 standards - According to raw material producers, 4 - Tested at 50C
Notes:
1 - According to Alcatel Bell tests, 2 - According to DIN42115 Parts 2, 3 standards - According to raw material producers, 4 - Tested at 50C
Nitrocellulose solvents NS -- -- -- -- -- G -- #
Oil NS -- -- -- -- -- E --
Oleic acid NS 3Y -- -- -- -- -- --
Paraffin oil NS 3Y >24h -- >24h -- -- >24h
Perchloroethylene NS -- -- -- >24h -- G >24h "
Persil NS -- >24h4 -- >24h4 -- -- --
10% 3Y -- -- -- -- -- --
Phosphoric acid
20% 3Y -- -- -- -- -- --
50% 3Y -- -- -- -- -- --
<30% -- >24h -- >24h -- -- >24h
Photographic chemicals NS -- -- -- -- -- E --
Potassium carbonate NS -- >24h -- >24h -- -- >24h
Potassium ferrocyanide NS -- >24h -- >24h -- -- >24h
Potassium hydroxide
10% 3Y -- -- -- -- -- --
20% 3Y -- -- -- -- -- --
Sea water NS -- -- -- -- -- E --
Sebacic acid SA 3Y -- -- -- -- -- --
Silicon grease NS -- -- -- -- -- E --
Silicon oil NS -- -- -- >24h -- E >24h
Skydrol NS 6M -- -- -- -- -- -- "
Sodium carbonate SA -- >24h -- -- -- -- --
Sodium chloride 3% 3Y -- -- -- -- -- --
Sodium hydroxide 20% 3Y -- -- -- -- -- --
NS -- >24h -- -- -- -- --
Sodium hypochloride 10% 6M >24h -- -- -- -- -- "
<20% -- -- -- >24h -- -- >24h
Softner NS -- >24h -- >24h -- -- --
<10% -- -- -- -- -- -- >24h
10% 3Y -- -- >24h >24h -- --
Sulphuric acid 28% 3Y -- A -- -- -- --
50% 6M -- -- -- -- -- -- "
CO -- -- -- -- -- G -- #
Tartaric acid SA 3Y -- -- -- -- -- --
Legend:
A - No visible degradation, B - Very slight degradation, C - Slight degradation, D - Damage visible or gross, E - Unlimited use, F - Limitated use, G - Use inad-
visable, S - The surface melts, X - The surface blisters, O - The surface is destroyed, CO - Concentrated, HC - High concentration, LC - Low concentration,
SA - Saturated, NS - Not specified, h - Hour(s), M - Month(s), Y- Year(s), - All the elements tested resist all the substances, " - At least one of the ele-
ments tested may be damaged by the substances in question, # - All the elements tested may be damaged by the substances in question, -- Not tested.
Notes:
1 - According to Alcatel Bell tests, 2 - According to DIN42115 Parts 2, 3 standards - According to raw material producers, 4 - Tested at 50C
Teepol NS 3Y -- -- -- -- -- --
Toluene NS 3Y >24h A >24h -- G >24h "
Tomato juice NS -- B4 -- B4 -- -- -- "
Tomato sauce NS -- B4 -- B4 -- -- -- "
Top Job NS -- >24h4 -- >24h4 -- -- --
Trichloroethylene NS S -- -- >24h -- G >24h "
Turpentine oil NS -- >24h -- -- -- F -- "
Turpentine substitute NS -- -- -- >24h -- -- >24h
Vaselline NS -- -- -- -- -- F -- "
Vim NS -- >24h4 -- >24h4 -- -- --
Vinegar NS -- -- D -- -- -- -- #
Vortex NS -- >24h4 -- >24h4 -- -- --
Washing powders NS -- >24h -- >24h -- E >24h
Water NS -- >24h -- -- -- E --
White spirit NS 3Y -- A -- -- -- --
Windex NS -- >24h 4 -- >24h 4 -- -- --
Wisk NS -- >24h 4 -- >24h 4 -- -- --
Wood oil NS -- -- -- -- -- F -- "
Xilene NS 1Y >24h -- >24h -- -- --
Legend:
A - No visible degradation, B - Very slight degradation, C - Slight degradation, D - Damage visible or gross, E - Unlimited use, F - Limitated use, G - Use inad-
visable, S - The surface melts, X - The surface blisters, O - The surface is destroyed, CO - Concentrated, HC - High concentration, LC - Low concentration,
SA - Saturated, NS - Not specified, h - Hour(s), M - Month(s), Y- Year(s), - All the elements tested resist all the substances, " - At least one of the ele-
ments tested may be damaged by the substances in question, # - All the elements tested may be damaged by the substances in question, -- Not tested.
Notes:
1 - According to Alcatel Bell tests, 2 - According to DIN42115 Parts 2, 3 standards - According to raw material producers, 4 - Tested at 50C
Cleaning the For cleaning the VT we recommend Denaturalised Ethyl Alcohol. Should
VT this be insufficient for removing the impurity making it necessary to use
other products, consult the tables above.
Case for The producer of the raw materials used to manufacture the case does not
terminals VT, supply detailed information regarding the tests performed and the concen-
H Series tration of substances used during the tests. The information below is the
suppliers original text.
Rresins are generally stable to water, weak acid and mineral oil. Mechani-
cal properties and surface appearance, however,can be deteriorated if a
molded part is exposed to hot water, strong acid, alkalis, Ketones and aro-
matic hydrocarbons, etc.
Chemical Effect
Make sure the plastic shell does not come into contact with any
oils containing paraffin clorurate or active nitrogen. These sub-
stances may change the mechanical qualities of the product.
Contents Page
Fax: ++39-031751777
E-Mail: [email protected]
Our International Customer Care service will supply all the necessary infor-
mation for returning a an item.
Compiled by : ...............................................................................................................
Company : ...............................................................................................................
Full address : ...................................................................... Post Code: .....................
Town : ................................................. County: ...........................................
Tel. no. : .................................................. Fax: ...................................................
Name : .................................................................................................................
Tel. no. : .................................................. Fax: ...................................................