Ubc 1982 PDF
Ubc 1982 PDF
Ubc 1982 PDF
BUILDING
CODE
1982 Edition
Fifth Printing
COPYRIGHT 1984
by
Part !-Administrative
CHAPTER 1. Title, Scope and General
SEC. 101. Title ............... . 25
102. Purpose . 25
103. Scope. 25
104. Application to Existing Buildings and Structures .. . 25
105. Alternate Materials and Methods of Construction ... . 27
106. Modifications . 27
107. Tests .... 27
CHAPTER 2. Organization and Enforcement
SEC. 201. Creation of Enforcement Agency ... 28
202. Powers and Duties of Building Official ......... . 28
203. Unsafe Buildings or Structures .. 29
204. Board of Appeals. 29
205. Violations ... 30
APPENDIX
The following is a sample form for adoption of the Uniform Building Code and
Uniform Building Code Standards.
19
SAMPLE ORDINANCE FOR ADOPTION OF THE
UNIFORM BUILDING CODE AND
UNIFORM BUILDING CODE STANDARDS
ORDINANCE NO. _ _
20
UNIT CONVERSION TABLES
Sl SUPPLEMENTARY UNITS
Quontlly UnH Symbol
Plane angle Radian rad
Solid angle Steradian sr
Sl PREFIXES
Multlpttcetlon Foetor Prwllx Symbol
I 000 000 000 000 000
000 - I 018 ex a E
I 000 000 000 000
000 = 10" pet a p
I 000 000 000
000 = 1012 tera T
I 000 000
000 = 1Q9 giga G
I 000
000 = 10 mega M
I
000 = 10 3 kilo k
100 = 102 hecto h
10 = 10 1 dcka da
0.1 =JOI deci d
0.01 =10 2 centi c
0.001 = J03 milli m
0.000001 =10 6 micro ~
0.000 000 001 = 10 9 nano n
0.000 000 000 001 =IQ-12 pi co p
0. 000 000 000 000 00 I = 10"" femto f
0. 000 000 000 000 000 00 I = J0-18 atto a
(Continued)
21
Sl SYMBOLS AND PREFIXES--(Contlnued)
Sl DERIV~D UNIT WITH SPECIAL NAMES
Ouontlly Un~ Symbol Formula
Frequency (of a periodic phenomenon) hertz Hz lis
Force newton N kgmls 2
Pressure, stress pascal Pa Nlm 2
Energy, work, quantity of heat joule J Nm
Power, radiant flux watt w Jls
Quantity of electricity, electric charge coulomb c As
Electric potential, potential difference,
electromotive force volt v WIA
Capacitance farad F C!V
Electric resistance ohm n VIA
Conductance siemens s A!V
Magnetic flux weber Wb Vs
Magnetic flux density tesla T Wblm 2
Inductance henry H WbiA
Luminous flux lumen lm cdsr
Illuminance lux lx lmlm2
Activity (of radionuclides) becquerel Bq lis
Absorbed dose gray Gy Jlkg
CONVERSION FACTORS
Toconwrt to mu~lply by
LENGTH
I mile (U.S. statute) km 1.609 347
I yd m 0.9144
1ft m 0.3048
mm 304.8
lin mm 25.4
AREA
I mile' (U.S. statute) km' 2.589 99
I acre (U.S. survey) ha 0.404 687
m' 4046.87
I yd 2 m' 0.836 127
I ft2 m' 0.092 903
l in 2 mm 2 645.16
VOLUME, MODULUS OF SECTION
I acre ft m' 1233.49
I yd' m' 0.764 555
100 board ft m' 0.235 974
I ft 3 m' O.o28 316 8
L (dm 3 ) 28.3168
I in 3 mm 3 16 387.1
mL (cm 3 ) 16.3871
I barrel (42 U.S. gallons) m3 .158 987
(Continued)
22
CONVERSION FACTOR5--(Contlnued)
To convert to multiply by
(FLUID) CAPACITY
I gal (U.S. liquid)** L* 3.7~5 41
I qt (U.S. liquid) mL 946.353
I pt (U.S. liquid) mL 473.177
I noz(U.S.) mL 29.5735
I gal (U.S.liquid) m' 0.003 785
"'"'I gallon (UK) approx. 1.2 gal (U.S.)
"'1 liter approx. 0.001 \:ubi~: meter~
SECOND MOMENT OF AREA
I in4 mm4 416 231
m4 0.416 231 X 10-<>
PLANE ANGLE
I' (degree) rad 0.017 453 3
mrad 17.4533
I' (minute) urad 290.888
l"(second) urad 4.848 14
VELOCITY, SPEED
I fli< m/s 0.3048
I mile/h kmih 1.609 344
mls 0.447 04
VOLUME RATE OF FLOW
I ft 3 /s m:-ls 0.028 316 8
1 ft 3/min Us 0.471 947
I gal/min Us 0.063 090 2
I gal/min rn 3 /min 0.0038
I gal/h mL/s 1.051 50
I million galid L/s 43.8126
1 acre ft!s m 3/s 1233.49
TEMPERATURE INTERVAL
I'F "CorK 0.555 556
519'C ~ 519 K
EQUIVALENT TEMPERATURE (toe- T, - 273.15)
!oF I 1 9:s ~o,. + 32
MASS
I ton (short***) metric ton 0.907 185
kg 907.185
lib kg 0.453 592
I oz g 28.3495
""""' 1 long tun (2240 lb) kg 1016.05
MASS PER UNIT AREA
I lb/ftZ kglm' 4.882 43
I o7.iytF gim 2 33.9057
I o7./ft 2 glm2 305.152
(Continued)
23
CONVERSION FACTORS-(Contlnued)
To conv.rt to multiply by
DENSITY (MASS PER UNIT VOLUME)
I lbift3 kg/m 3 16.0185
I lb/yd3 kgim3 0.593 276
I ton/yd3 tJm3 1.186 55
FORCE
I tonf (ton-force) kN 8.896 44
I kip (I 000 lbf) kN 4.448 22
I lbf (pound-force) N 4.448 22
MOMENT OF FORCE, TORQUE
llbHt Nm 1.355 82
I lbf-in Nm 0.112985
I tonHt kNm 2.711 64
I kipft kNm 1.355 82
FORCE PER UNIT LENGTH
llbf/ft Nlm 14.5939
I lbf/in N/m 175.127
I tonf/ft kN/m 29.187 8
PRESSURE, STRESS, MOOULUS OF ELASTICITY (FORCE PER UNIT AREA) (1 Po - 1 Ntrn')
I tonf/in2 MPa 13.7895
I tonf/ft2 kPa 95.7605
1 kiplin2 MPa 6.894 76
I lbf/in2 kPa 6.894 76
I lbf/ft2 Pa 47.8803
Atmosphere kPa 101.3250
I inch mercury kPa 3.376 85
I foot (water column @32'F) kPa 2.988 98
WQRK,ENERGY,HEAT(1J 1Nm = 1Wo)
I kWh (550 ftlbf/s) Mj 3.6
I Btu (Int. Table) kJ 1.055 06
J 1055.06
I ftlbf J 1.355 82
COEFFICIENT OF HEAT TRANSFER
I Btu/(ft2h'F) W/(m2K) 5.678 26
THERMAL CONDUCTIVITY
I Btul(fth'F) W/(mK) 1.730 73
ILLUMINANCE
I lntlft2 (footcandle) lx (lux) 10.7639
LUMINANCE
I cdlft2 cdlm2 10.7639
I foot lambert cdlm2 3.426 26
I lambert kcdlm 2 3.183 01
24
1982 EDITION 101-104
Part/
ADMINISTRATIVE
Chapter 1
TITLE, SCOPE AND GENERAL
Title
Sec.101. These regulations shall be known as the "Unifonn Building Code,"
may be cited as such and will be referred to herein as "this code.''
Purpose
Sec. 102. The purpose of this code is to provide minimum standards to
safeguard life or limb, health, property and public welfare by regulating and
controlling the design. construction, quality of materials, use and occupancy,
location and maintenance of all buildings and structures within this jurisdiction
and certain equipment specifically regulated herein.
Scope
Sec. 103. The provisions of this code shall apply to the construction, alteration,
moving, demolition, repair and use of any building or structure within this
jurisdiction, except work located primarily in a public way, public utility towers
and poles, mechanical equipment not specifically regulated in this code, and
hydraulic flood control structures.
Additions, alterations, repairs and changes of use or occupancy in all buildings
and structures shall comply with the provisions for new buildings and structures
except as otherwise provided in Sections I 04, 307 and 502 of this code.
Where, in any specific case, different sections of this code specify different
materials, methods of construction or other requirements, the most restrictive
shall govern. Where there is a conflict between a general requirement and a
specific requirement, the specific requirement shall be applicable.
I
Wherever in this code reference is made to the appendix, the provisions in the
appendix shall not apply unless specifically adopted.
Application to Existing Buildings and Structures
Sec. 104. (a) General. Buildings and structures to which additions, alterations
or repairs are made shall comply with all the requirements of this code for new
facilities except as specifically provided in this section. See Section 1210 for
provisions requiring installation of smoke detectors in existing Group R, Division
3 Occupancies.
(b) Additions, Alterations or Repairs. Additions, alterations or repairs may
be made to any building or structure without requiring the existing building or
structure to comply with all the requirements of this code, provided the addition,
alteration or repair conforms to that required for a new building or structure.
Additions, alterations or repairs shall not cause an existing building or structure to
become unsafe or overloaded. Any building so altered, which involves a change
25
104 UNIFORM BUILDING CODE
in use or occupancy, shall not exceed the height, number of stories and area
permitted for new buildings. Any building plus new additions shall not exceed the
height, number of stories and area specified for new buildings.
Alterations or repairs to an existing building or structure which are nonstruc-
tural and do not adversely affect any srructural member or any part of the building
or structure having required tire resistance may be made with the same materials
of which the building or structure is constructed.
EXCEYfiON: The installation or replacement of glass shall be as required for
new installations.
(c) Existing Installations_ Buildings in existence at the time of the adoption of
this code may have their existing use or occupancy continued, if such use or
occupancy was legal at the time of the adoption of this code, provided such
continued use is not dangerous to life.
Any change in the use or occupancy of any existing building or structure shall
comply with the provisions of Sections 307 and 502 of this code.
II! For existing buildings, see Appendix Chapter I.
(d) Maintenance. All buildings and structures, both existing and new, and all
parts thereof, shall be maintained in a safe and sanitary condition. All devices or
safeguards which are required by this code shall be maintained in conformance
with the code edition under which installed. The owner or his designated agent
shall be responsible for the maintenance of buildings and structures. To determine
compliance with this subsection, the building official may cause any structure to
be reinspected.
(e) Moved Buildings and Temporary Buildings_ Buildings or structures
moved into or within the jurisdiction shall comply with the provisions of this code
for new buildings or structures.
Temporary structures such as reviewing stands and other miscellaneous struc-
tures, sheds, canopies or fences used for the protection of the public around and in
conjunction with construction work may be erected by special permit from the
building official for a limited period oftime. Such buildings or structures need not
comply with the type of construction or fire-resistive time periods required by this
code. Temporary buildings or structures shall be completely removed upon the
expiration of the time limit stated in the permit.
(f) Historic Buildings. Repairs, alterations and additions necessary for the
preservation, restoration, rehabilitation or continued use of a building or structure
may be made without conformance to all the requirements of this code when
authorized by the building official, provided:
I . The building or structure has been designated by official action of the
legally constituted authority of this jurisdiction as having special historical
or architectural significance.
2. Any unsafe conditions as described in this code are corrected.
3. The restored building or structure will be no more hazardous based on life
safety, fire safety and sanitation than the existing building.
26
1982 EDITION 105-107
27
201-202 UNIFORM BUILDING CODE
Chapter2
ORGANIZATION AND ENFORCEMENT
Creation of Enforcement Agency
Sec. 201. There is hereby established in this jurisdiction a code enforcement
agency which shall be under the administrative and operational control of the
building official.
28
1982 EDITION 202-204
Such person shall discontinue the use within the time prescribed by the building
official after receipt of such notice to make the structure, or portion thereof,
comply with the requirements of this code.
(f) Liability. The building official, or his authorized representative charged
with the enforcement of this code, acting in good faith and without malice in the
discharge of his duties, shall not thereby render himself personally liable for any
damage that may accrue to persons or property as a result of any act or by reason of
any act or omission in the discharge of his duties. Any suit brought against the
building official or employee because of such act or omission performed by him in
the enforcement of any provision of this code shall be defended by legal counsel
provided by this jurisdiction until final termination of such proceedings.
This code shall not be construed to relieve from or lessen the responsibility of
any person owning, operating or controlling any building or structure for any
damages to persons or property caused by defects, nor shall the code enforcement
agency or its parent jurisdiction be held as assuming any such liability by reason
of the inspections authorized by this code or any certificates of inspection issued
under this code.
(g) Cooperation of Other Officials and Officers. The building official may
request, and shall receive so far as is required in the discharge of his duties. the
assistance and cooperation of other officials of this jurisdiction.
Unsafe Buildings or Structures
Sec. 203. All buildings or structures regulated by this code which are struc-
turally unsafe or not provided with adequate egress, or which constitute a fire
hazard, or are otherwise dangerous to human life are, for the purpose of this
section, unsafe. Any use of buildings or structures constituting a hazard to safety,
health or public welfare by reason of inadequate maintenance, dilapidation.
obsolescence, fire hazard, disaster, damage or abandonment is, for the purpose of
this section, an unsafe use. Parapet walls, cornices, spires, towers, tanks, statuary
and other appendages or structural members which are supported by, attached to,
or a part of a building and which are in deteriorated condition or otherwise unable
to sustain the design loads which are specified in this code are hereby designated
as unsafe building appendages.
All such unsafe buildings, structures or appendages are hereby declared to be
public nuisances and shall be abated by repair, rehabilitation, demolition or
removal in accordaoce with the procedures set forth in the Dangerous Buildings
Code or such alternate procedures. as may have been or as may be adopted by this
jurisdiction. As an alternative, the building official, or other employee or official
of this jurisdiction as designated by the governing body, may institute any other
appropriate action to prevent, restrain, correct or abate the violation.
Board of Appeals
Sec. 204. In order to determine the suitability of alternate materials and
methods of construction and to provide for reasonable interpretations of this code,
there shall be and is hereby created a Board of Appeals consisting of members
who are qualified by experience and training to pass upon matters pertaining to
building construction. The building official shall be an ex officio member and
29
204-205 UNIFORM BUILDING CODE
shall act as secretary of the board. The Board of Appeals shall be appointed by the
governing body and shall hold office at its pleasure. The board shall adopt
reasonable rules and regulations for conducting its investigations and shall render
all decisions and findings in writing to the building official with a duplicate copy
to the appellant.
VIolations
Sec. 205. It shall be unlawful for any person, firm or corporation to erect,
construct, enlarge, alter, repair, move, improve, remove, convert or demolish,
equip, use, occupy or maintain any building or structure or cause or permit the
same to be done in violation of this code.
30
1982EDinON 301-302
Chapter3
PERMITS AND INSPECTIONS
Permits
Sec. 301. (a) Permits Required. It shall be unlawful for any person, firm or
corporation to erect, construct, enlarge, alter, repair, move. improve, remove,
convert or demolish any building or structure regulated by this code, except as
specified in Subsection (b) of this section, or cause the same to be done without
first obtaining a separate permit for each building or structure from the building
official.
(b) Exempted Work. A building permit shall not be required for the following:
1. One-story detached accessory buildings used as tool and storage sheds,
playhouses and similar uses, provided the projected roof area does not
exceed 120 square feet.
2. Fences not over 6 feet high.
3. Oil derricks.
4. Movable cases, counters and partitions not over 5 feet high.
5. Retaining walls which are not over 4 feet in height measured from the
bottom of the footing to the top of the wall, unless supporting a surcharge
or impounding flammable liquids.
6. Water tanks supported directly upon grade if the capacity does not exceed
5000 gallons and the ratio of height to diameter or width does not exceed
two to one.
7. Platforms, walks and driveways not more than 30 inches above grade and
not over any basement or story below.
8. Painting, papering and similar finish work.
9. Temporary motion picture, television and theater stage sets and scenery.
10. Window awnings supported by an exterior wall of Group R, Division 3,
and Group M Occupancies when projecting not more than 54 inches.
II. Prefabricated swimming pools accessory to a Group R, Division 3 Occu-
pancy in which the pool walls are entirely above the adjacent grade and if
the capacity does not exceed 5000 gallons.
Unless otherwise exempted, separate plumbing, electrical and mechanical
permits will be required for the above exempted items.
Exemption from the permit requirements of this code shall not be deemed to
grant authorization for any work to be done in any manner in violation of the
provisions of this code or any other laws or ordinances of this jurisdiction.
Application for Permit
Sec. 302. (a) Application. To obtain a permit, the applicant shall first file an
application therefor in writing on a form furnished by the code enforcement
agency for that purpose. Every such application shall:
I. Identify and describe the work to be covered by the permit for which
application is made.
31
302-303 UNIFORM BUILDING CODE
I
Plans for buildings more than two stories in height of other than Groups R,
Division 3 and M Occupancies shall indicate how required structural and fire-
resistive integrity will be maintained where a penetration will be made for
electrical, mechanical, plumbing and communication conduits, pipes and similar
systems.
Permits Issuance
Sec. 303. (a) Issuance. The application, plans and specifications, and other
data, filed by an applicant for permit shall be reviewed by the building official.
Such plans may be reviewed by other departments of this jurisdiction to verify
compliance with any applicable laws under their jurisdiction. If the building
official finds that the work described in an application for a permit and the plans,
specifications and other data filed therewith conform to the requirements of this
code and other pertinent laws and ordinances, and that the fees specified in
Section 304 have been paid, he shall issue a permit therefor to the applicant.
When the building official issues the permit where plans are required, he shall
endorse in writing or stamp the plans and specifications "APPROVED." Such
approved plans and specifications shall not be changed, modified or altered
without authorizations from the building official, and all work shall be done in
accordance with the approved plans.
The building official may issue a permit for the construction of part of a
32
1982 EDITION 303
building or structure before the entire plans and specifications for the whole
building or structure have been submitted or approved, provided adequate infor-
mation and detailed statements have been filed complying with all pertinent
requirements of this code. The holder of such permit shall proceed at his own risk
without assurance that the permit for the entire building or structure will be
granted.
(b) Retention of Plans. One set of approved plans, specifications and com-
putations shall be retained by the building official for a period of not less than 90
days from date of completion of the work covered therein; and one set of approved
plans and specifications shall be returned to the applicant, and said set shall be
kept on the site of the building or work at all times during which the work
authorized thereby is in progress.
(c) Validity of Permit. The issuance or granting of a permit or approval of
plans and specifications shall not be construed to be a permit for, or an approval of,
any violation of any of the provisions of this code or of any other ordinance of the
jurisdiction. No permit presuming to give authority to violate or cancel the
provisions of this code shall be valid.
The issuance of a permit based upon plans, specifications and other data shall
not prevent the building official from thereafter requiring the correction of errors
in said plans, specifications and other data, or from preventing building opera-
tions being carried on thereunder when in violation of this code or of any other
ordinances of this jurisdiction.
(d) Expiration. Every permit issued by the building official under the provi-
sions of this code shall expire by limitation and become null and void if the
building or work authorized by such permit is not commenced within 180 days
from the date of such permit, or if the building or work authorized by such permit
is suspended or abandoned at any time after the work is commenced for a period
of 180 days. Before such work can be recommenced, a new permit shall be first
obtained so to do, and the fee therefor shall be one half the amount required for a
new permit for such work, provided no changes have been made or will be made
in the original plans and specifications for such work; and provided further that
such suspension or abandonment has not exceeded one year.
Any permittee holding an unexpired permit may apply for an extension of the
time within which he may commence work under that permit when he is unable to
commence work within the time required by this section for good and satisfactory
reasons. The building official may extend the time for action by the permittee for a
period not exceeding 180 days upon written request by the permittee showing that
circumstances beyond the control of the permittee have prevented action from
being taken. No permit shall be extended more than once. In order to renew action
on a permit after expiration, the permittee shall pay a new full permit fee.
33
304 UNIFORM BUILDING CODE
Fees
Sec. 304. (a) Permit Fees. The fee for each permit shall be as set forth in Table
No. 3-A.
The determination of value or valuation under any of the provisions of this code
shall be made by the building official. The value to be used in computing the
building permit and building plan review fees shall be the total value of all
construction work for which the permit is issued as well as all finish work,
painting, roofing, electrical, plumbing, heating, air conditioning, elevators, fire-
extinguishing systems and any other permanent equipment.
(b) Plan Review Fees. When a plan or other data are required to be submitted
by Subsection (b) of Section 302, a plan review fee shall be paid at the time of
submitting plans and specifications for review. Said plan review fee shall be 65
percent of the building permit fee as shown in Table No. 3-A.
Where plans are incomplete or changed so as to require additional plan review,
an additional plan review fee shall be charged at the rate shown in Table No. 3-A.
(c) Expiration of Plan Review. Applications for which no permit is issued
within 180 days following the date of application shall expire by limitation, and
plans and other data submitted for review may thereafter be returned to the
applicant or destroyed by the building official. The building official may extend
the time for action by the applicant for a period not exceeding 180 days upon
request by the applicant showing that circumstances beyond the control of the
applicant have prevented action from being taken. No application shall be
extended more than once. In order to renew action on an application after
expiration, the applicant shall resubmit plans and pay a new plan review fee.
(d) Investigation Fees: Work Without a Permit. I. Investigation. Whenever
any work for which a permit is required by this code has been commenced without
first obtaining said permit, a special investigation shall be made before a permit
may be issued for such work.
2. Fee. An investigation fee, in addition to the permit fee, shall be collected
whether or not a permit is then or subsequently issued. The investigation fee shall
be equal to the amount of the permit fee required by this code. The minimum
investigation fee shall be the same as the minimum fee set forth in Table No. 3-A.
The payment of such investigation fee shall not exempt any person from compli-
ance with all other provisions of this code nor from any penalty prescribed by law.
(e) Fee Refunds. I. The building official may authorize the refunding of any
fee paid hereunder which was erroneously paid or collected.
2. The building official may authorize the refunding of not more than 80
percent of the permit fee paid when no work has been done under a permit issued
in accordance with this code.
3. The building official may authorize the refunding of not more than 80
percent of the plan review fee paid when an application for a permit for which a
plan review fee has been paid is withdrawn or canceled before any plan reviewing
is done.
The building official shall not authorize the refunding of any fee paid except
34
1982 EDITION 304-305
upon written application filed by the original permittee not later than 180 days
after the date of fee payment.
Inspections
Sec. 305. (a) General. All construction or work for which a permit is required
shall be subject to inspection by the building official, and certain types of
construction shall have continuous inspection by special inspectors as specified in
Section 306.
A survey of the lot may be required by the building official to verify that the
structure is located in accordance with the approved plans. It shall be the duty of
the permit applicant to cause the work to be accessible and exposed for inspection
purposes. Neither the building official nor the jurisdiction shall be liable for
expense entailed in the removal or replacement of any material required to allow
inspection.
(b) Inspection Requests. It shall be the duty of the person doing the work
authorized by a permit to notify the building official that such work is ready for
inspection. The building official may require that every request for inspection be
filed at least one working day before such inspection is desired. Such request may
be in writing or by telephone at the option of the building official.
It shall be the duty of the person requesting any inspections required by this
code to provide access to and means for proper inspection of such work.
(c) Inspection Record Card. Work requiring a permit shall not be commenced
until the permit holder or his agent shall have posted an inspection record card in a
conspicuous place on the premises and in such position as to allow the building
official conveniently to make the required entries thereon regarding inspection of
the work. This card shall be maintained in such position by the permit holder until
final approval has been granted by the building official.
(d) Approval Required. No work shall be done on any part of the building or
structure beyond the point indicated in each successive inspection without first
obtaining the approval of the building official. Such approval shall be given only
after an inspection shall have been made of each successive step in the con-
struction as indicated by each of the inspections required in Subsection (e).
There shall be a final inspection and approval on all buildings and structures
when completed and ready for occupancy or use.
(e) Required Inspections. Reinforcing steel or structural framework of any
part of any building or structure shall not be covered or concealed without first
obtaining the approval of the building official.
The building official, upon notification from the permit holder or his agent,
shall make the following inspections and shall either approve that portion of the
construction as completed or shall notify the permit holder or his agent wherein
the same fails to comply with this code:
I. FOUNDATION INSPECTION: To be made after trenches are excavated
and forms erected and when all materials for the foundation are delivered on the
job. Where concrete from a central mixing plant (commonly termed "transit
mixed") is to be used. materials need not be on the job.
35
305-306 UNIFORM BUILDING CODE
Special Inspections
Sec. 306. (a) General. In addition to the inspections required by Section 305,
the owner shall employ a special inspector during construction on the following
types of work:
I. CONCRETE: During the taking of test specimens and placing of all
reinforced concrete and pneumatically placed concrete.
I
EXCEPTIONS: I. Concrete for foundations confonning to minimum require-
ments of Table No. 29-A or for Group R, Division 3 or Group M, Division I
O~cupancies, provided the building official finds that a special hazard does not
eXISt.
36
2. For foundation concrete when the structural design is based on af'c no greater
than 2000 psi.
3. Nonstructural slabs on grade, including prestressed slabs on grade when
effective prestress in concrete is less than 150 pounds per square inch.
4. Site work concrete full-supported on earth and concrete where no special
hazard exists.
2. DUCTILE MOMENT-RESISTING CONCRETE FRAME: As required
by Section 2625 (h) of this code.
3. REINFORCING STEEL AND PRESTRESSING STEEL: A. During all
stressing and grouting of prestressed concrete.
B. During placing of reinforcing steel, placing of tendons and prestressing steel
for all concrete required to have special inspection by Item No. 1.
EXCEPTION: The special inspector need not be present during entire reinforc-
ing steel-and prestressing steel-placing operations, provided he has inspected for
conformance with the approved plans, prior to the closing of forms or the delivery of
concrete to the job site.
4. WELDING: A. Ductile moment-resisting steel frames. As required by
Section 2722 (t) of this code.
B. All structural welding, including welding of reinforcing steel.
EXCEPTIONS: I. When welding is done in an approved fabricator's shop.
2. When approved by the building official, single-pass fillet welds when stressed
to less than 50 percent of allowable stresses and floor and roof deck welding and
welded studs when used for structural diaphragm or composite systems may have
periodic inspections in accordance with Section 306 (e) of this code. For periodic
inspection, the inspector shall check qualifications of welders at the start of work
and then make final inspection of all welds for compliance prior to completion of
welding.
5. HIGH-STRENGTH BOLTING: During all bolt installations and tighten-
ing operations.
EXCEPTIONS: I. The special inspector need not be present during the entire
installation and tightening operation, provided he has:
(i) Inspected the surfaces and boll type for conformance to plans and specifica-
tions prior to start of bolting,
(ii) And will, upon completion of all bolting, verify the minimum specified bolt
tension for 10 percent of the bolts for each "type" of connection, for a representa-
tive number of total connections established by the plans and specifications.
2. In bearing-type connections when threads are not required by design to be
excluded from the shear plane, inspection prior to or during installation will not be
required.
6. STRUCTURAL MASONRY: During preparation of masonry wall prisms,
sampling and placing of all masonry units, placement of reinforcement, inspec-
tion of grout space, immediately prior to closing of cleanouts, and during all
grouting operations. Where thef'm is less than 2600 psi and special inspection
stresses are used, test specimens may consist of either one prism test for each 5000
square feet of wall area or a series of tests based on both grout and mortar for the
first three consecutive days and each third day thereafter.
37
306 UNIFORM BUILDING CODE
38
1982 EDITION 306-307
39
307, 3-A UNIFORM BUILDING CODE
hazard will result from occupancy of any building or portion thereof before the
same is completed, he may issue a temporary Certificate of Occupancy for the use
of a portion or portions of a building or structure prior to the completion of the
entire building or structure.
(e) Posting. The Certificate of Occupancy shall be posted in a conspicuous
place on the premises and shall not be removed except by the building official.
(f) Revocation. The building official may, in writing, suspend or revoke a
I
Certificate of Occupancy issued under the provisions of this code whenever the
certificate is issued in error, or on the basis of incorrect information supplied, or
when it is determined that the building or structure or portion thereof is in
violation of any ordinance or regulation or any of the provisions of this code.
40
1982 EDITION 401-402
Part II
DEFINITIONS AND ABBREVIATIONS
Chapter4
DEFINITIONS AND ABBREVIATIONS
Definitions
Sec. 401. General. For the purpose of this code, certain terms, phrases, words
and their derivatives shall be construed as specified in this chapter. Words used in
the singular include the plural and the plural the singular. Words used in the
masculine gender include the feminine and the feminine the masculine.
Where terms are not defined, they shall have their ordinary accepted meanings
within the context with which they are used. Webster's Third New International
Dictionary of the English Language, Unabridged, copyright 1961, shall be
considered as providing ordinarily accepted meanings.
A
Sec. 402. ADDITION is an extension or increase in floor area or height of a
building or structure.
AGRICULTURAL BUILDING is a structure designed and constructed to
house farm implements, hay, grain, poultry, livestock or other horticultural
products. This structure shall not be a place of human habitation or a place of
employment where agricultural products are processed, treated or packaged; nor
shall it be a place used by the public.
ALLEY is any public space or thoroughfare less than 16 feet but not less than
10 feet in width which has been dedicated or deeded to the public for public use.
ALTER or ALTERATION is any change, addition or modification in con-
struction or occupancy. ..
APARTMENT HOUSE is any building or portion thereof which contains Ill
three or more dwelling units. Iii
APPROVED, as to materials and types of construction, refers to approval by
the building official as the result of investigation and tests conducted by him, or
by reason of accepted principles or tests by recognized authorities, technical or
scientific organizations.
APPROVED AGENCY is an established and recognized agency regularly
engaged in conducting tests or furnishing inspection services, when such agency
has been approved by the building official.
APPROVED FABRICATOR is an established and qualified person, firm or
corporation approved by the building official pursuant to Section 306 (f) of this
code.
AREA. (See "Floor Area.'')
ASSEMBLY BUILDING is a building or portion of a building used for the
gathering together of 50 or more persons for such purposes as deliberation,
41
402-404 UNIFORM BUILDING CODE
I
ATRIUM is an opening through two or more floor levels other than enclosed
stairways, elevators, hoistways. escalators, plumbing, electrical, air-conditioning
or other equipment, which is closed at the top and not defined as a mall.
AUTOMATIC, as applied to fire protection devices, is a device or system
providing an emergency function without the necessity of human intervention and
activated as a result of a predetermined temperature rise, rate of rise of tempera-
ture or increase in the level of combustion products such as is incorporated in an
automatic sprinkler system, automatic fire door, etc.
B
Sec. 403. BALCONY is that portion of the seating space of an assembly room,
the lowest part of which is raised 4 feet or more above the level of the main floor.
BALCONY, EXTERIOR EXIT. See Section 3301 (b).
BASEMENT is any floor level below the first story in a building, except that a
floor level in a building having only one floor level shall be classified as a
basement unless such floor level qualifies as a first story as defined herein.
BOILER, HIGH PRESSURE, is a boiler furnishing steam at pressures in
excess of 15 pounds per square inch or hot water at temperatures in excess of
250F., or at pressures in excess of 160 pounds per square inch.
BOILER, LOW-PRESSURE HOT WATER AND LOW-PRESSURE
STEAM, is a boiler furnishing hot water at pressures not exceeding 160 pounds
per square inch and at temperatures not more than 250F., or steam at pressures
not more than 15 pounds per square inch.
BOILER ROOM is any room containing a steam or hot-water boiler.
BUILDING is any structure used or intended for supporting or sheltering any
use or occupancy.
BUILDING, EXISTING, is a building erected prior to the adoption of this
code, or one for which a legal building permit has been issued.
BUILDING OFFICIAL is the officer or other designated authority charged
with the administration and enforcement of this code, or his duly authorized
representative.
c
Sec. 404. CAST STONE is a precast building stone manufactured from
portland cement concrete and used as a trim, veneer or facing on or in buildings or
structures.
CENTRAL HEATING PLANT is comfort heating plant equipment installed
in such a manner to supply heat by means of ducts or pipes to areas other than the
room in which the equipment is located.
CHIEF OF THE FIRE DEPARTMENT is the head of the fire department or
his regularly authorized deputy.
I! COMBUSTIBLE LIQUID. See Fire Code.
42
1982 EDITION 404-407
CO URI' is a space, open and unobstructed to the sky, located at or above grade
level on a lot and bounded on three or more sides by walls of a building.
D
Sec. 405. DANGEROUS BUILDINGS CODE is the Uniform Code for the
Abatement of Dangerous Buildings promulgated by the International Conference
I
of Building Officials, as adopted by this jurisdiction.
DISPERSAL AREA, SAFE. See Section 3323 (b)
DORMITORY is a room occupied by more than two guests.
DWELLING is any building or portion thereof which contains not more than
two dwelling units.
DWELLING UNIT is any building or portion thereof which contains living
facilities, including provisions for sleeping, eating. cooking and sanitation, as
required by this code, for not more than one family.
E
Sec 406. EFFICIENCY DWELLING UNIT is a dwelling unit containing
only one habitable room.
ELECTRICAL CODE is the National Electrical Code promulgated by the
National Fire Protection Association, as adopted by this jurisdiction.
I
EXISTING BUILDINGS. (See "Building, Existing.")
EXIT. See Section 3301 (b).
EXIT COURf. See Section 3301 (b).
EXIT PASSAGEWAY. Sec Section 3301 (b).
F
Sec. 407. FAMILY is an individual or two or more persons related by blood or
marriage or a group of not more than five persons (excluding servants) who need
not be related by blood or marriage living together in a dwelling unit.
43
407-409 UNIFORM BUILDING CODE
with the rain and weathering tests ofU.B.C. Standard No. 32-7.
All materials shall bear identification showing the fire performance rating
thereof and, if intended for exterior use, shall be further identified to indicate
suitability for exposure to the weather. Such identifications shall be issued by an
approved agency having a service for inspection of materials at the factory.
~ FLAMMABLE LIQUID. See Fire Code.
FLOOR AREA is the area included within the surrounding exterior walls of a
building or portion thereof, exclusive of vent shafts and courts. The floor area of a
building, or portion thereof, not provided with surrounding exterior walls shall be
the usable area under the horizontal projection of the roof or floor above.
FOOTING is that portion of the foundation of a structure which spreads and
transmits loads directly to the soil or the piles.
FRONT OF LOT is the front boundary line of a lot bordering on the street and,
in the case of a corner lot, may be either frontage.
G
I
Sec. 408. GARAGE is a building or portion thereof in which a motor vehicle
containing flammable or combustible liquids or gas in its tank, is stored, repaired
or kept.
GARAGE, PRIVATE, is a building or a portion of a building, not more than
1000 square feet in area, in which only motor vehicles used by the tenants of the
building or buildings on the premises are stored or kept. (See Section II 0 I . )
GARAGE, PUBLIC, is any garage other than a private garage.
GRADE (Adjacent Ground Elevation) is the lowest point of elevation of the
finished surface of the ground, paving or sidewalk within the area between the
building and the property line or, when the property line is more than 5 feet from
the building. between the building and a line 5 feet from the building.
GRADE (Lumber) is the classification of lumber in regard to strength and
utility.
GUEST is any person hiring or occupying a room for living or sleeping
purposes.
GUEST ROOM is any room or rooms used or intended to be used by a guest
for sleeping purposes. Every 100 square feet of superficial floor area in a
dormitory shall be considered to be a guest room.
H
Sec. 409. HABITABLE SPACE (ROOM) is space in a structure for living,
sleeping, eating or cooking. Bathrooms, toilet compartments, closets, halls,
storage or utility space, and similar areas, are not considered habitable space.
HEIGHT OF BUILDING is the vertical distance above a reference datum
measured to the highest point of the coping of a flat roof or to the deck line of a
mansard roof or to the average height of the highest gable of a pitched or hipped
roof. The reference datum shall be selected by either of the following, whichever
yields a greater height of building:
I. The elevation of the highest adjoining sidewalk or ground surface within a
44
1982 EDITION 409-413
5-foot horizontal distance of the exterior wall of the building when such
sidewalk or ground surface is not more than 10 feet above lowest grade.
2. An elevation 10 feet higher than the lowest grade when the sidewalk or
ground surface described in Item I above is more than 10 feet above lowest
grade.
The height of a stepped or terraced building is the maximum height of any
segment of the building.
HELIPORT. A heliport is an area of land or water or a structural surface which
is used, or intended for use, for the landing and takeoff of helicopters, and any
appurtenant areas which are used, or intended for use, for heliport buildings and
other heliport facilities.
HELISTOP. A helistop is the same as a heliport, except that no refueling,
maintenance, repairs or storage of helicopters is permitted.
HORIZONTAL EXIT. See Section 3301 (b).
HOTEL is any building containing six or more guest rooms intended or
designed to be used, or which are used, rented or hired out to be occupied, or
which are occupied for sleeping purposes by guests.
J
Sec. 411. JURISDICTION, as used in this code, is any political subdivision
which adopts this code for administrative regulations within its sphere of
authority.
K
Sec. 412. No definitions.
L
Sec. 413. LINTEL is a structural member placed over an opening or a recess in
a wall and supporting construction above.
LIQUID is any material which has a fluidity greater than that of 300 penctra
tion asphalt when tested in accordance with the Uniform Fire Code Standards.
When not otherwise identified, the term "liquid" is both flammable and combus-
tible liquids.
LIQUID STORAGE ROOM is a Group H, Division 2 Occupancy in which
the quantities of flammable or combustible liquids do not exceed the limits set
forth in the Fire Code.
LIQUID STORAGE WAREHOUSE is a Group H, Division 2 Occupancy
used for the storage of flammable or combustible liquids in an unopened con-
dition only in unlimited quantities.
LISTED and LISTING arc terms referring to equipment and materials which
are shown in a list published by an approved testing agency, qualified and
equipped for experimental testing and maintaining an adequate periodic inspec-
45
413-416 UNIFORM BUILDING CODE
tion of current productions and whose listing states that the equipment complies
with recognized safety standards.
LOADS. See Chapter 23.
I
LODGING HOUSE is any building or portion thereof containing not more
than five guest rooms which are used by not more than five guests where rent is
paid in money, goods, labor or otherwise.
M
Sec. 414. MARQUEE is a permanent roofed structure attached to and sup
ported by the building and projecting over public property. Marquees are regu-
lated in Chapter 45.
MASONRY is that form of construction composed of stone, brick, concrete,
gypsum, hollow clay tile, concrete block or tile or other similar building units or
materials or combination of these materials laid up unit by unit and set in mortar.
MASONRY, SOLID, is masonry of solid units built without hollow spaces.
MECHANICAL CODE is the Uniform Mechanical Code promulgated jointly
by the International Conference of Building Officials and the International Asso-
ciation of Plumbing and Mechanical Officials, as adopted by this jurisdiction.
II MEZZANINE or MEZZANINE FLOOR is an intermediate floor placed
II within a room.
MOTEL shall mean hotel as defined in this code.
N
Sec. 415. NONCOMBUSTIBLE as applied to building construction material
means a material which, in the form in which it is used, is either one of the
following:
I. Material of which no part will ignite and burn when subjected to fire. Any
material conforming to U.B.C. Standard No. 4-1 shall be considered
noncombustible within the meaning of this section.
2. Material having a structural base of noncombustible material as defined in
Item No. I above, with a surfacing material not over 1/s inch thick which
has a flame-spread rating of 50 or less.
"Noncombustible" does not apply to surface finish materials. Material
required to be noncombustible for reduced clearances to flues, heating appliances
or other sources of high temperature shall refer to material conforming to Item
No. I. No material shall be classed as noncombustible which is subject to increase
in combustibility or flame-spread rating, beyond the limits herein established,
through the effects of age, moisture or other atmospheric condition.
Flame-spread rating as used herein refers to rating obtained according to tests
conducted as specified in U.B.C. Standard No. 42-1.
0
Sec. 416. OCCUPANCY is the purpose for which a building, or part thereof,
is used or intended to be used.
ORIEL WINDOW is a window which projects from the main line of an
enclosing wall of a building and is carried on brackets or corbels.
46
1982 EDITION 416-420
s
Sec. 420. SHAFT is a vertical opening through a building for elevators,
dumbwaiters, mechanical equipment or similar purposes.
SHALL, as used in this code, is mandatory.
SMOKE DETECTOR is an approved detector which senses visible or invisi-
ble particles of combustion. The detector shall bear a label or other identification
issued by an approved testing agency having a service for inspection of materials
and workmanship at the factory during fabrication and assembly.
STAGE is a partially enclosed portion of an assembly building which is
designed or used for the presentation of plays, demonstrations or other entertain-
ment wherein scenery, drops or other effects may be installed or used, and where
the distance between the top of the proscenium opening and the ceiling above the
stage is more than 5 feet. ttl
STORY is that portion of a building included between the upper surface of any
floor and the upper surface of the floor next above, except that the topmost story
shall be that portion of a building included between the upper surface of the
topmost floor and the ceiling or roof above. If the finished floor level directly
above a usable or unused under-floor space is more than 6 feet above grade as
defined herein for more than 50 percent of the total perimeter or is more than 12
feet above grade as defined herein at any point, such usable or unused under-floor
space shall be considered as a story.
47
42().424 UNIFORM BUILDING CODE
48
1982 EDITION 424-427
49
501503 UNIFORM BUILDING CODE
Part III
REQUIREMENTS BASED ON OCCUPANCY
ChapterS
CLASSIFICATION OF ALL BUILDINGS
BY USE OR OCCUPANCY AND GENERAL
REQUIREMENTS FOR ALL OCCUPANCIES
Occupancy Classified
Sec. 501. Every building, whether existing or hereafter erected, shall be
classified by the building official, according to its use or the character of its
occupancy, as a building of Group A, B, E, H, I, M orR as defined in Chapters 6,
7, 8. 9, 10, II and 12. (See Table No. 5-A.)
Any occupancy not mentioned specifically or about which there is any question
shall be classified by the building official and included in the group which its use
most nearly resembles, based on the existing or proposed life and fire hazard.
Change In Use
Sec. 502. No change shall be made in the character of occupancies or use of any
building which would place the building in a different division of the same group
of occupancy or in a different group of occupancies. unless such building is made
to comply with the requirements of this code for such division or group of
occupancy.
EXCEPTION: The character of the occupancy of existing buildings may be
changed subject to the approval of the building official, and the building may be
occupied for purposes in other groups without conforming to all the requirements of
this code for tho>e groups, provided the new or proposed use is less hazardous,
based on life and fire risk, than the existing use.
No change in the character of occupancy of a building shall be made without a
Certificate of Occupancy, as required in Section 307 of this code. The building
official may issue a Certificate of Occupancy pursuant to the intent of the above
exception without certifying that the building complies with all provisions of this
code.
Mixed Occupancy
Sec. 503. (a) General. When a building is used for more than one occupancy
purpose, each part of the building comprising a distinct "Occupancy," as
described in Chapters 5 through 12, shall be separated from any other occupancy
as specified in Section 503 (d).
When a building houses more than one occupancy, each portion of the building
shall conform to the requirements for the occupancy housed therein. The area of
the building shall be such that the sum of the ratios of the actual area divided by the
allowable area for each separate occupancy shall not exceed one.
Where minor accessory uses do not occupy more than 10 percent of the area of
any floor of a building, nor more than the basic area permitted in the occupancy by
50
1982EDinON 503
Table No. 5-C for such minor use, for the purpose of determining allowable area
the major use of the building shall determine the occupancy classification,
provided the uses are separated as specified in Section 503 (d). Except for
buildings containing Group H. Division I through Division 4 Occupancies, the
provisions of this paragraph are applicable to buildings constructed under the
provisions of Section 506 (b) for unlimited area.
An occupancy shall not be located above the story or height set forth in Table
No. 5-D, except as provided in Section 507.
(b) Forms of Occupancy Separations. Occupancy separations shall be verti-
cal or horizontal or both or, when necessary, of such other form as may be required
to afford a complete separation between the various occupancy divisions in the
building.
Where the occupancy separation is horizontal, structural members supporting
the separation shall be protected by equivalent fire-resistive construction.
(c) Types of Occupancy Separations. Occupancy separations shall be classed
as "four-hour fire-resistive," "three-hour fire-resistive,' "two-hour fire-resis-
tive," and "one-hour fire-resistive." (See U.B.C. Standard No. 43-7 for fire
dampers in air ducts piercing occupancy separations.)
I. A "four-hour fire-resistive occupancy separation" shall have no openings
therein and shall be of not less than four-hour fire-resistive construction.
2. A "three-hour fire-resistive occupancy separation'' shall be of not less than
three-hour fire-resistive construction. All openings in walls forming such separa-
tion shall be protected by a fire assembly having a three-hour fire-protection
rating. The total width of all openings in any three-hour fire-resistive occupancy
separation wall in any one story shall not exceed 25 percent of the length of the
wall in that story and no single opening shall have an area greater than 120 square
feet.
All openings in floors forming a "three-hour fire-resistive occupancy separa-
tion" shall be protected by vertical enclosures extending above and below such
openings. The walls of such vertical enclosures shall be of not less than two-hour
fire-resistive construction and all openings therein shall be protected by a fire
assembly having a one and one-half-hour fire-protection rating.
3. A "two-hour fire-resistive occupancy separation" shall be of not less than
two-hour fire-resistive construction. All openings in such separation shall be
protected by a fire assembly having a one and one-half-hour fire-protection rating.
4. A "one-hour fire-resistive occupancy separation" shall be of not less than
one-hour fire-resistive construction. All openings in such separation shall be
protected by a fire assembly having a one-hour fire-protection rating.
(d) Fire Ratings for Occupancy Separations. Occupancy separations shall be
provided between the various groups and divisions of occupancies as set forth in
Table No. 5-B.
EXCEPTIONS: I. Where an approved spray booth constructed in accordance
with the Fire Code is installed, such booth need not be separated from other Group H
Occupancies or from Group B Occupancies.
2. In Groups A, Division 1, E and I Occupancies a three-hour occupancy
51
503-504 UNIFORM BUILDING CODE
Location on Property
Sec. 504. (a) General. Buildings shall adjoin or have access to a public space,
yard or street on not less than one side. Required yards shall be permanently
maintained.
For the purpose of this section, the center line of an adjoining street or alley
shall be considered an adjacent property line.
Eaves over required windows shall be not less than 30 inches from the side and
rear property lines. For eaves, see Section 1710.
(b) Fire Resistance of Walls. Exterior walls shall have fire resistance and
opening protection as set forth in Table No. 5-A, Part JII, and in accordance with
such additional provisions as are set forth in Part IV and Part VI!. Distance shall
be measured at right angles from the property line. The above provisions shall not
apply to walls at right angles to the property line.
Projections beyond the exterior wall shall not extend beyond:
I. A point one third the distance to the property line from an exterior wall: or
2. A point one third the distance from an assumed vertical plane located
where fire-resistive protection of openings is first required due to location
on property, whichever is the least restrictive.
When openings in exterior walls are required to be protected due to distance
from property line, the sum of the area of such openings shall not exceed 50
percent of the total area of the wall in each story.
(c) Buildings on Same Property and Buildings Containing Courts. For the
I purposes of determining the required wall and opening protection and roof-
covering requirements, buildings on the same property and court walls of build-
ings over one story in height shall be assumed to have a properly line between
them.
52
1982 EDITION 504-505
I
buildings, and the floor area of any single story shall not exceed that permitted for
a one-story building.
(c) Mezzanines. Unless considered as a separate story, the floor area of all
mezzanines shall be included in calculating the allowable floor area of the stories
in which the mezzanines are located.
(d) Basements. A basement need not be included in the total allowable area,
provided such basement does not qualify as a story nor exceed the area permitted
for a one-story building.
(e) Area Separation Walls. Each portion of a building separated by one or
more area separation walls may be considered a separate building, provided the
area separation walls meet the following requirements:
1. Area separation walls shall be not less than four-hour fire-resistive con-
struction in Types I, 11-F.R., IJJ and IV buildings and two-hour fire-resistive
construction in Types II One-hour, 11-N or V buildings. The total width of all
openings in such walls shall not exceed 25 percent of the length of the wall in each
story. All openings shall be protected by a fire assembly having a three-hour fire-
protection rating in four-hour fire-resistive walls and one and one-half-hour fire-
protection rating in two-hour fire-resistive walls.
2. Area separation walls shall extend to the outer edges of horizontal projecting
elements such as balconies, roof overhangs, canopies, marquees or architectural
projections.
EXCEPTION: When horizontal projecting elements do not contain concealed
spaces, the area separation wall may tenninate at the exterior wall.
When the horizontal projecting elements contain concealed spaces, the area
separation wall need only ex.tend through the concealed space to the outer edges of
the projecting elements.
53
505-506 UNIFORM BUILDING CODE
The exterior walls and the projecting elements above shall be of not less than one-
I hourfrre-resistive construction fora distance not less than the depth of the projecting
elements on both sides of the area separation wall. Openings within such widths
shall be protected by fire assemblies having a fire-protection rating of not less than
three-fourths hour.
3. Area separation walls shall extend from the foundation to a point at least 30
inches above the roof.
EXCEPTIONS: I. Area separation walls may terminate at the underside of the
roof sheathing, deck or slab, provided the roof-ceiling assembly is of at least two-
hour fire-resistive construction.
2. 1\vo-hour area separation walls may terminate at the underside of the roof
sheathing, deck or slab, provided:
A. Where the roof-ceiling framing elements are parallel to the walls, such framing
and elements supporting such framing shall be of not less than one-hour fire-
resistive construction for a width of not less than 5 feet on each side of the wall.
B. \Vherc roof-ceiling framing elements are perpendicular to the wall, the entire
span of such framing and elements supporting such framing shall be of not less
than one-hour fire-resistive construction.
C. Openings in the roof shall not be located within 5 feet of the area separation wall.
3. Two-hour area separation walls may terminate at roofs of entirely noncombusti-
ble construction.
54
1982 EDITION 506-507
2. Separation on three sides. Where public space, streets or yards more than
20 feet in width extend along and adjoin three sides of the building, floor areas
may be increased at a rate of 2 Yz percent for each foot by which the minimum
width exceeds 20 feet, but the increase shall not exceed 100 percent.
3. Separation on all sides. Where public space, streets or yards more than 20
feet in width extend on all sides of a building and adjoin the entire perimeter, floor
areas may be increased at a rate of 5 percent for each foot by which the minimum
width exceeds 20 feet. Such increases shall not exceed 100 percent, except for
buildings not exceeding two stories in height of Group B, Division 4 Occupancy
and one-story buildings housing aircraft storage hangars and as further limited in
Section 902 (b) for aircraft repair hangars.
(b) Unlimited Area. The area of any one- or two-story building of Group B and
Group H, Division 5 Occupancies shall not be limited, if the building is provided
with an approved automatic sprinkler system throughout, as specified in Chapter
38, and entirely surrounded and adjoined by public space, streets or yards not less
than 60 feet in width.
The area of a Group B, Division 4 Occupancy in a one-story Type 11, Type Ill
One-hour or Type IV building shall not be limited if the building is entirely
surrounded and adjoined by public space, streets or yards not less than 60 feet in
width.
(c) Automatic Sprinkler Systems. The areas specified in Table No. 5-C and
Section 505 (b) may be tripled in one-story buildings and doubled in buildings of
more than one story if the building is provided with an approved automatic
sprinkler system throughout. The area increases permitted in this subsection may
be compounded with that specified in paragraphs I, 2 or3 of Subsection (a) of this
section. The increases permitted in this subsection shall not apply when automatic
sprinkler systems are installed under the following provisions:
I. Section 507 for an increase in allowable number of stories.
2. Section 3802 (t) for Group H, Divisions I and 2 Occupancies.
3. Substitution for one-hour fire-resistive construction pursuant to Section 508.
4. Section 1715, Atriums. I
Maximum Height of Buildings and Increases
Sec. 507, The maximum height and number of stories of every building shall be
dependent upon the character of the occupancy and the type of construction and
shall not exceed the limits set forth in Table No. 5-D, except as provided in this
section and as specified in Section 503 (a) for mixed occupancy buildings.
The story limits set forth in Table No. 5-D may be increased by one story if the
building is provided with an approved automatic sprinkler system throughout.
The increase in the number of stories for automatic sprinkler systems shall not
apply when the automatic sprinkler systems throughout are installed under the
following provisions:
I. Section 3802 (t) for Group H, Divisions I and 2 Occupancies.
2. Section 506, for an increase in allowable area.
3. Substitution for one-hour fire-resistive construction pursuant to Section 508.
55
507510 UNIFORM BUILDING CODE
Fire-resistive Substitution
Sec. 508, Where one-hour fire-resistive construction throughout is required by
this code, an approved automatic sprinkler system, as specified in Chapter 38,
56
1982 EDITION 510-511
similarly finished to a height of 4 feet and, except for structural elements. the
materials used in such walls shall be of a type which is not adversely affected by
moisture.
In all occupancies, accessories such as grab bars, towel bars, paper dispensers 1
.
and soap dishes, etc., provided on or within walls, shall be installed and scaled to
protect structural elements from moisture.
Showers in all occupancies shall be finished as specified above to a height of
not less than 70 inches above the drain inlet. Materials other than structural
elements used in such walls shall be of a type which is not adversely affected by
moisture.
57
511513 UNIFORM BUILDING CODE
I Yz inches between the grab bar and adjacent surface. Grab bars need not be
provided in Group R, Division I apartment houses.
5. When it can be established that the facilities arc usable by a person in a
wheelchair, dimensions other than those above shall be acceptable.
(b) Access to Lavatories, Mirrors and Thwel Fixtures. In other than Group
R, Division 3; Group M; Group R, Division I apartment houses and Group B,
Divisions 2 and 4 storage occupancies, toilet room facilities shall be as follows:
I. Except for the projection of bowls and waste piping, a clear unobstructed
space 30 inches in width, 29 inches in height and 17 inches in depth shall be
provided under at least one lavatory.
2. Where mirrors are provided, at least one shall be installed so that the
bottom of the mirror is within 40 inches of the floor.
3. Where towel and disposal fixtures are provided, they shall be accessible to
the physically handicapped and at least one shall be within 40 inches of the
floor.
(c) Water Fountains. Where water fountains are provided, at least one shall
have a spout within 33 inches of the floor and shall have up-front, hand-operated
controls. When fountains are located in an alcove, the alcove shall be not less than
32 inches in width.
(d) Telephones. Where public telephones are provided, at least one shall be
installed so that the handset, dial and coin receiver are within 54 inches of the
floor. Unobstructed access within 12 inches of the telephone shall be provided.
Such access shall be not less than 30 inches in width.
Compressed Gases
Sec. 512. The storage and handling of compressed gases shall comply with the
Fire Code.
I
Premises Identification
Sec. 513. Approved numbers or addresses shall be provided for all new
buildings in such a position as to be plainly visible and legible from the street or
road fronting the property.
58
TABLE NO.5-A-WALL AND OPENING PROTECTION OF OCCUPANCIES BASED ON LOCATION ON PROPERTY
TYPES II ONE-HOUR, IIN AND V CONSTRUCTION: For exterior wall and opening_ protection of Types II One-hour, 11-N and V
-
~
N
buildings, see table below. Exceptions to limitation for Types II One-hour, 11-N and Type V construction, as provided In Sections :!;
709, 1903 and 2203 apply. For Types 1,11-F.R.,III and IV construction, see Sections 1803, 1903,2003 and 2103. :::j
0
GROUP DESCRIPTION OF OCCUPANCY
FIRE RESISTANCE OF
EXTERIOR WALL.S
OPENINGS IN
EXTERIOR WALLS
z
1-Any assembly building with a stage and an occupant load of 1000 or more
in the building Not applicable (See Sections 602 and 603)
2-Any building or portion of a building having an assembly room with an
occupant load ofless than l 000 and a stage Not pennitted less
2.1-Any building or portion of a building having an assembly room with an 2 hours less than l 0 than 5 feet
occupant load of 300 or more without a stage, including such buildings feet, I hour elsewhere Protected less than
used for educational purposes and not classed as a Group E 10 feet
or Group B, Division 2 Occupancy
A
See also
Section 3-Any building or portion of a building having an assembly room with an 2 hours less than 5 feet, Not permitted less than
602 occupant load of less than 300 without a stage, including such buildings used l hour less than 40 feet 5 feet
for educational purposes and not classed as a GroupE or Group B, Division Protected less than l 0 feet
2 Occupancy
4--Stadiums, reviewing stands and amusement park structures not included l hour less than 10 feet Protected less than 10 feet
within other Group A Occupancies
1---Gasoline service stations, garages where no repair work is done except
exchange of parts and maintenance requiring no open flame, welding, or use
of flammable liquids
B
2-Drinking and dining establishments having an occupant load of less than 50, Not pennitted less than 5
See also wholesale and retail stores, office buildings, printing plants, municipal l hour less than 20 feet feet
Section police and fire stations, factories and workshops using material not highly
702 Protected less than 10 feet
flammable or combustible, storage and sales rooms for combustible goods,
paint stores without bulk handling
Buildings or portions of buildings having rooms used for educational
putpases, beyond the 12th grade, with less than 50 occupants in any room
(Continued)
TABLE NO. 5-A-Contlnued
TYPES II ONE-HOUR, 11-N AND V ONLY
I
3-Mental hospitals, mental sanitariums, jails, prisons, reformatories and 2 hours less than 5 feet, Not permitted less than 5
buildings where personal liberties of inmates are similarly restrained I hour elsewhere feet, protected less than
lO feet
M' !-Private garages, carports, sheds and agricultural buildings I hour less than 3 feet Not permitted less than 3
(See also Section 1101, Division 1.) (or may be protected on feet
the exterior with
materials approved for
1-hour fire-resistive
construction)
2-Fences over 6 feet high, tanks and towers Not regulated for fire resistance
R !-Hotels and apartment houses I hour less than 5 feet Not permitted less than
See also Convents and monasteries (each accommodating more than 10 persons) 5 feet
Section
3-Dwellings and lodging houses I hour less than 3 feet Not permitted less than
1202
3 feet
2For agncultural butldmgs, see AppendiX Chapter II.
NOTES: (I) See Section 504 for types of walls affected and requirements covering percentage of openings permitted in exterior walls.
(2) For additional restrictions, see chapters under Occupancy and Types of Construction.
(3) For walls facing streets, yards and public ways, see Part IV.
~ (4) Openings shall be protected by a fire assembly having a three-fourths-hour fire-protection rating.
TABLE NO. 5-8-REQUIRED SEPARATION IN BUILDINGS OF MIXED OCCUPANCY
(In Hours)
A-1 A-2 A-2.1 A-3 A-4 B-1 B-2 B-3 B-4 E H1 H-2 H3 H-4-5 I M2 R1 R-3
A1 --......... N N N N 4 3 3 3 N 4 4 4 4 3 I I I
A-2 N ............ N N N 3 I I I N 4 4 4 4 3 I I I
A-2.1 N N --......... N N 3 I I I N 4 4 4 4 3 I I I
A-3 N N N --......... N 3 N I N N 4 4 4 4 3 I I I
A-4 N N N N --......... 3 I I I N 4 4 4 4 3 I I I
B-1 4 3 3 3 3 --......... I I I 4 2 I I I 4 I 3' I
B-2 3 I I N I I """'-.... I I I 2 I I I 2 I I N
B-3 3 I I I I I I .~ I I 2 I I I 4 I I N
B-4 3 I I N I I I I ............ I 2 I I I 4 N I N
E N N N N N 4 I I I '"-...._ 4 4 4 4 I I I I
H-1 4 4 4 4 4 2 2 2 2 4 ~ I I I 4 I 4 4
H-2 4 4 4 4 4 I I I I 4 I '"-...._ I I 4 I 3 3
H-3 4 4 4 4 4 I I I I 4 I I ~ I 4 I 3 3 c:
z
H-4-5 4 4 4 4 4 I I I I 4 I I I '"-...._ 4 I 3 3
~
I 3 3 3 3 3 4 2 4 4 I 4 4 4 4 '"-...._ I I I :XI
il:
M2 I I I I I I I I N I I I I I I ............ I I al
c:
R1 I I I I I 3' I I I I 4 J J J I I ~ N
6
R-3 I I I I 1 I N N N I 4 J 3 3 I I N '"-...._ z
(;)
Note: For detailed requirements and exceptions. see Section 503. 0
llbe three-hour separation may be reduced to two hours where the Group B, Division I Occupancy is limited to the storage of passenger motor 0
vehicles having a capacity of not more than nine persons. This shall not apply where provisions of Section 702 (a) apply. lil
2for agricultural buildings. see also Appendix Chapter II.
TABLE NO. 5-C-BASIC ALLOWABLE FLOOR AREA FOR BUILDINGS ONE STORY IN HEIGHT&
(In Square Feet)
-
!m
c
TYPES OF CONSTRUCTION g
I II JL Ill II IY H v z
OCCUPANCY F.R. F.R. ONE-HOUR I N ILONE-HOUR L N II H.T. I ONE-HOUR I N
A-I Unlimited 29,900 Not Permitted
A}2-2.1 Unlimited 29,900 13,500 Not 13,500 Not 13,500 10,500 Not
Permitted Permitted Permitted
A}3-4 Unlimited 29,900 13,500 9,100 13,500 9,100 13,500 10,500 6,000
B}l-2-3 1 Unlimited 39,900 18,000 12,000 18,000 12,000 18,000 14,000 8,000
B-4 Unlimited 59,900 27,000 18,000 27,000 18,000 27,000 21,000 12,000
E Unlimited 45,200 20,200 13,500 20,200 13,500 20,200 15,700 9,100
H) 1-2 2 15 000 12 400 5 600 3 700 5 600 3,700 5 600 4 400 2 500
H)3-4-5 Unlimited 24,800 11,200 7,500 11,200 7,500 11,200 8,800 5,100
n 1-2 Unlimited 15,100 6,800 Not 6,800 Not 6,800 5,200 Not
Permitted Permitted Permitted
1-3 Unlimited 15,100 Not Permitted3
M4 See Chapter II
R-1 Unlimited I 29,900 I 13,500 9, 100' II 13,soo I 9,100' Jlt3,soo I 10,500 L 6,000 5
R-3 Unlimited
1For open parking garages, see Section 709.
2See Section 903.
3See Section I 002 (b) N-No requirements for fire resistance
4For agricultural buildings, see also Appendix Chapter 11.
F.R.-Fire resistive
5For limitations and c~ceptiom, see Section 1202 (b). H. T.-Heavy Timber
6 For multistory buildings, see Section 505 (b).
"'..,
TABLE NO. 5-0-MAXIMUM HEIGHT OF BUILDINGS
TYPES OF CONSTRUCTION
I II II II Ill IV II y
OCCUPANCY F.R. D F.R. I ONE HOUR J N IIONEHOUR I N II H.T. II ONEHOUR I N
MAXIMUM HEIGHTIN FEET
Unlimited n 160 65 55 I 65 55 II 65 II 50 40
Chapter&
REQUIREMENTS FOR GROUP A OCCUPANCIES
Group A Occupancies Defined
Sec. 601. Group A Occupancies shall be:
Division I. Any assembly building with a stage and an occupant load of 1000
or more in the building.
Division 2. Any building or portion of a building having an assembly room
with an occupant load ofless than 1000 and a stage.
Division 2.1. Any building or portion of a building having an assembly room
with an occupant load of 300 or more without a stage, including such buildings
used for educational purposes and not classed as a GroupE or Group B. Division 2
Occupancy.
Division 3. Any building or portion of a building having an assembly room
with an occupant load of less than 300 without a stage, including such buildings
used for educational purposes and not classed as a GroupE or Group B, Division 2
Occupancy.
Division 4. Stadiums, reviewing stands and amusement park structures not
included within other Group A Occupancies. Specific and general requirements
for grandstands, bleachers and reviewing stands are to be found in Chapter 33.
For occupancy separations, see Table No. 5-B.
I
(b) Special Provisions. Stages and enclosed platforms as defined in Sections
417 and 420 shall be constructed in accordance with Chapter 39.
The slope of the main floor of the assembly room shall not exceed the slopes
permitted by Section 3307.
Division 2.1 Occupancies with an occupant load of 1000 or more shall be of
'IYpe I, 'IYpe II-F.R., 'IYpe II One-hour, 'IYpe Ill One-hour or 'IYpe IV con-
struction, except that the roof framing system for one-story portions of buildings
of 'IYpe II One-hour or "IYpe Ill One-hour construction may be of unprotected
construction when such roof framing system is open to the room and does not
contain concealed spaces.
Division 3 Occupancies located in a basement or above the first story shall be of
not less than one-hour fire-resistive construction.
65
602-605 UNIFORM BUILDING CODE
Group A assembly rooms having an occupant load of I 000 or more shall not be
located in the basement.
EXCEPTION: Basements of buildings of'!Ype 1 or 11-F.R. construction.
Division 3 Occupancies with an occupant load of 50 or more, which are located
over usable space, shall be separated from such space by not less than one-hour
fire-resistive construction.
For attic space partitions and draft stops, see Section 2516 (f).
(c) Division 4 Provisions. Erection and structural maintenance of structures
housing Division 4 Occupancies shall confonn to the requirements of this code.
Structures housing Division 4 Occupancies, other than those of open skeleton-
frame type, when more than one story in height or400 square feet in area, shall be
of not less than one-hour fire-resistive construction.
When the space under a Division 4 Occupancy is used for any purpose,
including exits, it shall be separated from all parts of such Division 4 Occupancy,
including exits, by walls, floor and ceiling of not less than one-hour fire-resistive
construction.
EXCEPTIONS: 1. Exits under temporary grandstands need not be separated.
2. The underside of continuous steel deck grandstands when erected outdoors
need not be fire protected when occupied for public toilets.
The building official may cause all Division 4 structures to be reinspected at
least once every six months.
Location on Property
Sec. 603. Buildings housing Group A Occupancies shall front directly upon or
have access to a public street not less than 20 feet in width. The access to the
public street shall be a minimum 20-foot-wide right-of-way, unobstructed and
maintained only as access to the public street. The main entrance to the building
shall be located on a public street or on the access way. The main assembly floor of
Division I Occupancies shall be located at or near the adjacent ground level.
For fire-resistive protection of exterior walls and openings, as detennined by
location on property, see Section 504 and Part IV.
Exit Facilities
Sec. 604. (a) General. Stairs, exits and smokeproof enclosures shall be
provided as specified in Chapter 33. (See also Sections 3317 and 3318.)
(b) Amusement Structures. Exits and exit signs for Division 4, Amusement
Structures, shall be approved by the building official and, where practicable, shall
comply with the requirements specified in Chapter 33.
66
1982 EDITION 605-608
Special Hazards
Sec. 608. Stages shall be equipped with automatic ventilators as required in
Section 3901.
Chimneys and heating apparatus shall conform to the requirements of Chapter
37 of this code and the Mechanical Code.
Motion picture machine booths shall conform to the requirements of Chapter
40.
Proscenium curtains shall conform to the requirements set forth in U.B.C.
Standard No. 6-1.
Flammable liquids shall not be placed or stored in any Group A Occupancy.
67
608-609 UNIFORM BUILDING CODE
68
1982 EDITION 701-702
Chapter 7
REQUIREMENTS FOR GROUP B OCCUPANCIES
I
Group B Occupancies Defined
Sec. 701. Group B Occupancies shall be:
Division 1. Gasoline service stations. garages where no repair work is done
except exchange of parts and maintenance requiring no open flame, welding or
use of flammable liquids.
Division 2. Drinking and dining establishments having an occupant load of less
than 50, wholesale and retail stores, office buildings, printing plants, municipal
police and fire stations, factories and workshops using materials not highly
flammable or combustible, storage and sales rooms for combustible goods, paint
stores without bulk handling. (See Section 402 for definition of assembly
buildings.)
Buildings or portions of buildings having rooms used for educational purposes
beyond the 12th grade with less than 50 occupants in any room.
Division 3. Aircraft hangars where no repair work is done except exchange of
parts and maintenance requiring no open flame, welding or the use of highly
flammable liquids.
Open parking garages.
Heliports.
Division 4. Ice plants, power plants, pumping plants, cold storage and
creameries.
Factories and workshops using noncombustible and nonexplosive materials.
Storage and sales rooms of noncombustible and nonexplosive materials.
For occupancy separations, see Table No. 5-B.
Construction, Height and Allowable Area
Sec. 702. (a) General. Buildings or parts of buildings classed in Group B
Occupancy because of the use or character of the occupancy shall be limited to the
types of construction set forth in Tables No. 5-C and No. 5-D and shall not
exceed, in area or height, the limits specified in Sections 505, 506 and 507.
Other provisions of this code notwithstanding, a Group B, Division I Occupan-
cy located in the basement or first story of a building housing a Group B, Division
2 or a Group R, Division I Occupancy may be classed as a separate and distinct
building for the purpose of area limitation, limitation of number of stories and
type of construction, when all of the following conditions are met:
I. The Group B, Division I Occupancy is of '!ype l construction.
2. There is a three-hour occupancy separation between the Group B, Division
I Occupancy and all portions of tbe Group B, Division 2 or Group R,
Division l Occupancy.
3. The basement or first story is restricted to the storage of passenger vehicles
(having a capacity of not more than nine persons per vehicle), but may
contain laundry rooms and mechanical equipment rooms incidental to the
operation of the building.
69
702-705 UNIFORM BUILDING CODE
4. The maximum building height in feet shall not exceed the limits set forth in
Table No. 5-D for the least type of construction involved.
(b) Special Provisions. Marine or motor vehicle service stations including
canopies and supports over pumps shall be of noncombustible, fire-retardant
treated wood or of one-hour fire-resistive construction.
EXCEPTIONS: I. Roofs of one-story service stations may be of heavy-timber
construction.
2. Canopies conforming to Section 5213 may be erected over pumps.
In areas where motor vehicles, boats or airplanes are stored, and in gasoline
service stations, floor surfaces shall be of noncombustible, nonabsorbent mate-
rials. Floors shall drain to an approved oil separator or trap discharging to sewers
in accordance with the Plumbing Code.
EXCEPTION: Floors may be surfaced or waterproofed with asphaltic paving
materials. in areas where motor vehicles or airplanes are stored or operated.
Stordge areas in excess of 1000 square feet in connection with wholesale or
retail sales in Division 2 Occupancies shall be separated from the public areas by a
one-hour fire-resistive occupancy separation as defined in Chapter 5. Such areas
may be increased to 3000 square feet when sprinklers, not otherwise required, are
installed in the storage area.
EXCEPTION: A one~hour fire-resistive occupancy separation is not required
where an approved automatic sprinkler system is installed throughout the building.
Area increases also shall be permitted as specified in Section 506 (c).
Storage garages in connection with Group R, Division I Occupancies shall
have an unobstructed headroom clearance of not less than 6 feet 6 inches above the
finish floor to any ceiling, beam, pipe or similar construction, except for wall-
mounted shelves, storage surfaces, racks or cabinets.
In Division 4 Occupancies, fire protection of the underside of roof framing may
be omitted in all types of construction.
For attic space partitions and draft stops, see Section 2516 (f).
For smoke and heat venting, see Section 3206.
Location on Property
Sec. 703. For fire-resistive protection of exterior walls and openings, as
determined by location on property, see Section 504 and Part IV.
Exit Facilities
Sec. 704. Stairs, exits and smokeproof enclosures shall be provided as spec-
ified in Chapter 33.
Light, Ventilation and Sanitation
Sec. 705. All portions of Group B Occupancies customarily used by human
beings shall be provided with natural light by means of exterior glazed openings
with an area equal to one tenth of the total floor area, and natural ventilation by
means of exterior openings with an area not less than one twentieth of the total
floor area, or shall be provided with artificial light and a mechanically operated
ventilating system as specified in Section 605.
70
1982 EDITION 705-706
In all buildings or portions thereof where flammable liquids arc used. exhaust
ventilation shall be provided sufficient to produce four air changes per hour. Such
exhaust ventilation shall be taken from a point at or ncar the fl<lOr level.
In all enclosed parking garages used for storing or handling of automobiles
operating under their own power and on all loading platforms in bus terminals,
ventilation shall be provided capable of exhausting a minimum of I . 5 cfm per
square foot of gross floor area. The building official may approve an alternate
ventilation system designed to exhaust a minimum of 14.000 dm for each
operating vehicle. Such system shall be based upon the anticipated instantaneous
movement rate of vehicles but not less than 2.5 percent tor nne vehicle) of the
garage capacity. Automatic CO sensing devices may be employed to modulate the
ventilation system to maintain a maximum average concentration of C'O of 50
ppm during any eight-hour period. with a maximum concentration not greater
than 200 ppm for a period not exceeding one hour. Connecting offices, waiting
rooms, ticket booths, etc., shall be supplied with conditioned air under positive
pressure.
EXCEPTION: In gasoline service stations without lulxi~atiun pit-.. -:toragc
garages and aircraft hangars not exceeding an area of 5000 square feet. the huilJing
official may authorize the omission of such ventilating equipment where. in his
opinion, the building is supplied with unobstructed openings tn the outer air which
are sufficient to provide the necessary ventilation.
Every building or portion thereof where persons arc employed shall be pro-
vided with at least one water closet. Separate facilities shall be provided for each
sex when the number of employees exceeds four and both sexes arc employed.
Such toilet facilities shall be located either in such building or conveniently in a
building adjacent thereto on the same property.
Such water closet rooms in connection with food establishments where food is
prepared, stored or served shall have a nonabsorbent interior finish as specified in
Section 510 (b), shall have hand-washing facilities therein or adjacent thereto. and
shall be separated from food preparation or storage rooms as specified tn Section
510 (a).
Toilet rooms shall be provided with a fully openabk exterior window at least
square feet in area; or a vertical duct not less than I 00 square inches in area for the
31
toilet facility, with 50 additional inches for each additional facJiity: or a mechan-
ically operated exhaust system capable of providing a complete change nf air
every 15 minutes. Such systems shall be connected directly to the outside. and the
point of discharge shall be at least 5 feet from any open able window.
For other requirements, on water closets, see Section 5 I 0.
Shaft Enclosures
Sec. 706. Exits shall be enclosed as specified in Chapter 33.
Elevator shafts, vent shafts and other vertical openings shall be enclosed. and
the enclosure shall be as specified in Section 1706.
EXCEPTION: In Group B, Divi<;.ion 4 Occupamics. exit~ ~hall he enclosed as
specified in Chapter 33, but other vertical opening::-. need not be I.!IK(t1~1.."d.
I
71
707-709 UNIFORM BUILDING CODE
Sprinkler Systems
Sec. 707. When required by other provisions of this code. automatic sprinkler
systems and standpipes shall be installed as specified in Chapter 38.
Special Hazards
Sec. 708. Chimneys and heating apparatus shall conform to the requirements of
Chapter 37 of this code and the Mechanical Code.
Storage of volatile flammable liquids shall not be allowed in Group B. Divi-
sions I, 2 and 3 Occupancies and the handling and use of gasoline, fuel oil and
other flammable liquids shall not be permitted in any Group B Occupancy unless
such use and handling comply with the Fire Code.
Devices generating a glow or flame capable of igniting gasoline vapor shall not
be installed or used within 18 inches of the floor in any room in which volatile
flammable liquids or gas are used or stored.
Every room containing a boiler or central heating plant shall be separated from
the rest of the building by not less than a one-hour fire-resistive occupancy
separation.
EXCEPTION: Boilers or central heating plants where the largest piece of fuel
equipment does not exceed 400,000 Btu per hour input.
Buildings erected or converted to house high-piled combustible stock shall
comply with the Fire Code.
Open Parking Garages
Sec. 709. (a) Scope. Except where specific provisions are made in the follow-
ing subsections, other requirements of this code shall apply.
(b) Defmition. For the purpose of this section, an open parking garage is a
structure of Type I or II construction which is open on two or more sides totaling
not less than 40 percent of the building perimeter and which is used exclusively
for parking or storage of private pleasure cars. For a side to be considered open.
the total area of openings distributed along the side shall be not less than 50
percent of the exterior area of the side at each tier. The area of openings may be
reduced below the minimum 50 percent for 40 percent of the perimeter, provided
the percentage of the perimeter in which the openings are contained is increased
proportionately.
EXCEPTION: The grade-level tier may contain an office, waiting and toilet
rooms having a total area of not more than 1000 square feet and such area need not be
separated from the open parking garage.
Open parking garages are further classified as either ramp-access or mechan-
ical-access. Ramp-access open parking garages are those employing a series of
continuously rising floors or a series of interconnecting ramps between floors
permitting the movement of vehicles under their own power from and to the street
level. Mechanical-access parking garages are those employing parking machines,
lifts, elevators or other mechanical devices for vehicles moving from and to street
level and in which public occupancy is prohibited above the street level.
(c) Construction. Construction shall be of noncombustible materials. Open
parking garages shall meet the design requirements of Chapter 23. Adequate
72
1982 EDITION 709
I
larger tier shall be more than 200 feet horizontally from such an opening. In
addition, each such opening shall face a street or yard accessible to a street with a
width of at least 30 feet for the full length of the opening, and standpipes shall be
provided in each such tier.
Structures ofType 11-F.R.; Type II One-hour or Type 11-N construction, with all
sides open. may be unlimited in area when the height does not exceed 75 feet. For
a side to be considered open, the total area of openings along the side shall be not
less than 50 percent of the exterior area of the side at each tier, and such openings
shall be equally distributed along the length of the tier. All portions of tiers shall
be within 200 feet horizontally from such openings.
(f) Location on Property. When located adjacent to interior property lines,
exterior walls shall be of the degree of fire resistance set forth in Table No. 7-B
and such walls shall be without openings.
(g) Stairs and Exits. Where persons other than parking attendants are permit-
ted, stairs and exits shall meet the requirements of Chapter 33, based on an
occupant load of 200 square feet per occupant. Where no persons other than
parking attendants are permitted there shall be not less than two stairs 3 feet wide.
Lifts may be installed for use of employees only, provided they are completely
enclosed by noncombustible materials.
(h) Standpipes. Standpipes shall be installed when required by the provisions
of Chapter 38.
(i) Sprinkler Systems. When required by other provisions of this code.
73
709710 UNIFORM BUILDING CODE
Helistops
Sec. 710. (a) General. Helistops may be erected on buildings or other locations
if they are constructed in accordance with this section.
(b) Size. The touchdown or landing area for helicopters of less than 3500
pounds shall be a minimum of20 feet by 20 feet in size. The touchdown area shall
be surrounded on all sides by a clear area having a minimum average width at roof
level of 15 feet but with no width less than 5 feet.
(c) Design. Helicopter landing areas and supports therefor on the roof of a
building shall be of noncombustible construction. Landing areas shall be
designed to confine any flammable liquid spillage to the landing area itself and
provision shall be made to drain such spillage away from any exit or stairway
serving the helicopter landing area or from a structure housing such exit or
stairway.
(d) Exits and Stairways. Exits and stairways from helistops shall comply with
the provisions of Chapter 33 of this code, except that all landing areas located on
buildings or structures shall have two or more exits. For landing platforms or roof
areas less than 60 feet in length, or less than 2000 square feet in area, the second
exit may be a fire escape or ladder leading to the floor he low.
(e) Federal Aviation Approval. Before operating helicopters from helistops,
approval must be obtained from the Federal Aviation Administration.
74
1982 EDITION 7-A, 7B
HEIGHT
MECHANICALACCESS
Automatic
Flre-extlngul&hlng
System
TYPE OF AREA PEA TIER
CONSTRUCTION RAMP-ACCESS
(Squ1re Feet) No Yoa
I Unlimited Unlimited Unlimited Unlimited
II- F.R. 125,000 12 Tiers 12 Tiers 18 Tiers
II- 1-hour 50,000 10 Tiers 10 Tiers 15 Tiers
U-N 30,000 8 Tiers 8 Tiers 12 Tiers
75
801-802 UNIFORM BUILDING CODE
ChapterS
REQUIREMENTS FOR GROUP E OCCUPANCIES
Group E Occupancies Defined
Sec. 801. GroupE Occupancies shall be:
Division 1. Any building used for educational purposes through the 12th grade
by 50 or more persons for more than 12 hours per week or four hours in any one
day.
Division 2. Any building used for educational purposes through the 12th grade
by less than 50 persons for more than 12 hours per week or four hours in any one
day.
Division 3. Any building used for day-care purposes for more than six
children.
For occupancy separations, see Table No. 5-B.
Construction, Height and Allowable Area
Sec. 802. (a) General. Buildings or parts of buildings classed in Group E
because of the use or character of the occupancy shall be limited to the types of
construction set forth in Tables No. 5-C and No. 5-D and shall not exceed, in area
or height, the limits specified in Sections 505, 506 and 507, except that the area
may be increased by 50 percent when the maximum travel distance specified in
Section 3303 (d) is reduced by 50 percent.
(b) Atmospheric Separation Requirements. I . Definitions. For the purpose
of this chapter, the following definitions are applicable:
COMMON ATMOSPHERE. A common atmosphere exists between rooms,
spaces or areas within a building, which are not separated by an approved smoke
and draft-stop barrier.
SEPARATE ATMOSPHERE. A separate atmosphere exists between rooms,
spaces or areas that are separated by an approved smoke and draft-stop barrier.
SMOKE AND DRAFT BARRIER. A smoke and draft barrier consists of
walls, partitions, floors and openings therein of such construction as will prevent
the transmission of smoke or gases through the construction.
2. General Provisions. The provisions of this subsection shall apply only to
the requirements for providing separate atmospheres.
Walls, partitions and floors forming all of, or part of, an atmospheric separation
shall be of materials consistent with the requirements for the type of construction,
but of construction not less effective than a smoke or draft-stop barrier. Glass
lights of approved wired glass set in steel frames may be installed in such walls or
partitions.
Every door opening therein shall be protected with a fire assembly as required
elsewhere in the code, but not Jess than a self-closing or automatic-closing, tight-
fitting smoke barrier and fire assembly having a fire-protection rating of not less
than 20 minutes when tested in accordance with U.B.C. Standard No. 43-2
without the hose stream test.
Ducts penetrating atmospheric separation walls, partitions or floors shall be
76
1982 EDITION 802-805
Exit Facilities
Sec. 804. Stairs, exits and smokeproof enclosures shall be provided as spec-
ified in Chapter 33. (See also Section 3319.)
Light, Ventilation and Sanitation
Sec. 805. All portions of GroupE Occupancies shall be provided with light and
ventilation, either natural or artificial, as specified in Section 605.
Water closets shall be provided on the basis of the following ratio of water
closets to the number of students:
Boys Girls
Elementary Schools ............................... . 1:100 1:35
Secondary Schools ........................ . 1:100 1:45
In addition, urinals shall be provided for boys on the basis of I :30 in elementary
and secondary schools.
n
805-809 UNIFORM BUILDING CODE
There shall be provided at least one lavatory for each two water closets or
urinals, and at least one drinking fountain on each floor for elementary and
secondary schools.
For other requirements on water closets, see Section 510.
Shaft Enclosures
Sec. 806. Exits shall be enclosed as specified in Chapter 33. Elevator shafts,
vent shafts and other vertical openings shall be enclosed, and the enclosure shall
be as specified in Chapter 17.
Sprinkler Systems
Sec. 807, Where required, automatic sprinkler systems and standpipes shall be
installed as specified in Chapter 38.
Special Hazards
Sec. 808. Chimneys and heating apparatus shall conform to the requirements of
Chapter 37 of this code and the Mechanical Code.
Motion picture machine rooms shall conform to the requirements of Chapter
40.
All exterior openings in a boiler room or rooms containing central heating
equipment, if located below openings in another story or if less than I 0 feet from
other doors or windows of the same building, shall be protected by a fire assembly
having a three-fourths-hour fire-protection rating. Such fire assemblies shall be
fixed, automatic- or self-closing. Every room containing a boiler or central
heating plant shall be separated from the rest of the building by not less than a one-
hour fire-resistive occupancy separation.
EXCEPTION: Boilers or central heating plants where the largest piece of fuel
equipment does not exceed 400,000 Btu per hour input.
When the opening for a heater or equipment room is protected by a pair of ftre
doors, the inactive leaf shall be normally secured in the closed position and shall
be openable only by the use of a tool. An astragal shall be provided and the active
leaf shall be self-closing.
Flammable liquids shall not be placed, stored or used in any GroupE Occupan-
cies, except in approved quantities as necessary in laboratories and approved
utility rooms, and such liquids shall be kept in tight or sealed containers when not
in actual use and shall be stored within a storage cabinet for flammable liquid
approved by the fire department.
Firs Alarms
Sec. 809. Approved fire alarms shall be provided for all Group E Occupancies
with an occupant load of more than 50 persons. In every Group E Occupancy
provided with an automatic sprinkler or detection system, the operation of such
system shall automatically activate the school fire alarm system, which shall
include an alarm mounted on the exterior of the building.
78
1982 EDITION 901-902
Chapter9
REQUIREMENTS FOR GROUP H OCCUPANCIES
Group H Occupancies Defined
Sec. 901. (a) General. Group H Occupancies shall be:
Division l. Storage, handling, use or sale of hazardous and highly flammable
or explosive materials other than flammable liquids.
EXCEYfiON: The storage, handling, use or sale of hazardous materials or
chemicals that do not exceed the quantities listed in 'Thble No. 9-A are pennitted in
other occupancies, provided the storage, handling, use or sale of such hazardous
materials or chemicals is in compliance with the Fire Code.
Division 2. Storage, handling, use or sale of Classes I, II and III-A liquids; dry
cleaning plants using Class I, II or III-A liquids; paint stores with bulk handling;
paint shops and spray-painting rooms and shops.
EXCEYfiON: The storage. handling, use or sale of liquids in quantities that do
not exceed those set forth in Table No. 9-A are pennitted in other occupancies,
provided the storage, handling, use or sale is in compliance with the provisions of
the Fire Code.
Division 3. Woodworking establishments, planing mills, box factories, buff-
ing rooms for tire-rebuilding plants and picking rooms; shops, factories or
warehouses where loose combustible fibers or dust are manufactured, processed,
generated or stored; and pin-refinishing rooms.
Division 4. Repair garages not classified as a Group B, Division I . I
DivisionS. Aircraft repair hangars.
(b) Special Provisions. In buildings used for educational purposes, vocational
shops, laboratories and similar areas need not be classified as Group H Occupan-
cies, provided:
I. Such areas are separated from classrooms other than the classroom directly
related to the use by not less than a one-hour fire-resistive occupancy
separation.
2. Such areas are separated from each other by not less than a one-hour fire-
resistive occupancy separation unless the uses are determined to be
compatible.
3. The requirements of Sections 908, 910 and the Fire Code shall be met
when applicable.
For occupancy separations, see Table No. 5-B.
Where an approved spray booth constructed as specified in the Fire Code is
installed, such booth need not be separated from other Group H or Group B
Occupancies.
79
902 UNIFORM BUILDING CODE
(b) Special Provisions. Division 5 Occupancies shall have exterior walls of not
less than one-hour fire-resistive construction or shall be surrounded by public
space, streets or yards not less than 60 feet in width.
The area increases allowed by Section 506 (a) shall not exceed 500 percent for
aircraft repair hangars.
In areas where motor vehicles, boats or airplanes are stored, repaired or
operated and where flammable liquids are stored or used, floor surfaces shall be of
noncombustible nonabsorbent materials.
EXCEPTION: Floors may be surfaced or waterproofed with asphaltic paving
materials where no repair work is done.
For special provisions and hazardous chemicals and magnesium, see also the
Fire Code.
A Division 4 Occupancy having a floor area not exceeding 2500 square feet
shall have exterior walls of not less than two-hour fire-resistive construction when
less than 5 feet from a property line and of not less than one-hour fire-resistive
construction when more than 5 feet but less than lO feet from a property line.
For smoke and heat venting, see Section 3206.
(c) Special Occupancies. I. Liquid storage rooms. The design and con-
struction of liquid storage rooms in which Class I, II or III-A liquids are stored
shall be in accordance with the requirements for a Group H, Division 2 Occupan-
cy and the following:
A. Floors shall be of noncombustible liquid-tight construction designed to
prevent liquids from flowing to adjacent rooms by any of the following
methods:
(i) Recessing the floor at least 4 inches lower than the floor of adjacent
rooms.
(ii) Installation of liquid-tight sills at least 4 inches in height. Sills may be
omitted at openings when trenches are constructed in accordance with
Item (iii) below.
(iii) Installation of an open-grate trench which drains to an approved
location.
B. Shelving, racks, dunnage, scuffboards, floor overlay and similar installa-
tions shall be of noncombustible construction or wood not less than l-inch
nominal thickness.
2. Inside liquid rooms. Rooms that do not have an exterior wall may be used
for the storage or the storage and use, dispensing or mixing of Class I, II or III-A
liquids, provided they do not exceed 500 square feet in area and are separated
from other areas by occupancy separations having a fire-resistive rating not less
than one hour for rooms up to 150 square feet in area and not less than two hours
where the room is more than 150 square feet in area. Separations from other
occupancies shall be not less than required by Table No. 5-B.
3. Liquid storage warehouses. The design and construction of liquid storage
warehouses in which flammable or combustible liquids are stored shall be in
accordance with the requirements for a Group H, Division 2 Occupancy and this
80
1982 EDITION 902-905
section. Liquid storage warehouses shall be used for the storage of flammable or
combustible liquids only and shall be separated from all other uses by a four-hour
area separation wall.
All liquid storage warehouses shall be provided with adequate drainage.
Drainage systems shall be sized and designed to carry off any anticipated spill,
plus the minimum calculated fire flow of the sprinkler system to a safe location. If
connected to a public drain or sewer system, a clarifier shall be installed.
Floors and equipment in liquid storage warehouses shall comply with the
applicable provisions of Subsection (c) I, Items A and B, above.
Location on Property
Sec. 903. For fire-resistive protection of exterior walls and openings, as
determined by location on property, see Section 504 and Part IV.
Group H, Division 1 Occupancies shall be located 60 feet from all property
lines including property lines adjacent to public ways.
Group H, Division 2 Occupancies containing hazardous materials in excess of
the amounts listed in Table No. 9-A shall not exceed 1500 square feet in area
I
unless there is more than 30 feet from all property lines including property lines
adjacent to public ways.
When a building is of mixed occupancy and contains a Group H, Division 2
Occupancy, the Group H, Division 2 Occupancy shall be separated from the other
occupancy as required in Table No. 5-B. Such Group H, Division 2 Occupancies
shall be on the outer perimeter of the building and all walls of the Group H,
Division 2 Occupancy shall be located a minimum of 30 feet from property line.
EXCEPTION: Inside liquid rooms that comply with the limitations in Section
902 (c) 2.
Exit Facilities
Sec. 904. Stairs, exits and smokeproof enclosures shall be provided as spec-
ified in Chapter 33. (See also Section 3320.)
81
905-908 UNIFORM BUILDING CODE
minute. Connecting offices and waiting rooms shall be supplied with conditioned
air under positive pressure.
EXCEPTION: In public repair garages and aircraft hangars not exceeding an
area of 5000 square feet, the building official may authorize the omission of such
ventilating equipment where, in his opinion, the building is supplied with unob-
structed openings to the outer air which are sufficient to provide the necessary
ventilation.
Every building or portion thereof where persons are employed shall be pro-
vided with at least one water closet. Separate facilities shall be provided for each
sex when the number of employees exceeds four and both sexes are employed.
Such toilet facilities shall be located either in such building or conveniently in a
building adjacent thereto on the same property.
Toilet rooms shall be provided with a fully openable exterior window at least 3
square feet in area; or a vertical duct not less than I 00 square inches in area for the
toilet facility, with 50 additional inches for each additional facility; or a mechan-
ically operated exhaust system capable of providing a complete change of air
every 15 minutes. Such systems shall be connected directly to the outside, and the
point of discharge shall be at least 5 feet from any openable window.
For other requirements on water closets, see Sections 510 and 511.
Shaft Enclosures
Sec. 906. Exits shall be enclosed as specified in Chapter 33.
Elevator shafts, vent shafts and other vertical openings shall be enclosed, and
the enclosure shall be as specified in Section 1706.
Doors which are a part of an automobile ramp enclosure shall be equipped with
automatic closing devices.
Sprinkler Systems
Sec. 907. When required by other provisions of this code, automatic sprinkler
systems and standpipes shall be installed as specified in Chapter 38.
Special Hazards
Sec. 908. Chimneys and heating apparatus shall conform to the requirements of
Chapter 37 of this code and the Mechanical Code.
Every boiler or central heating plant shall be separated from the rest of the
building by a two-hour fire-resistive occupancy separation.
In Divisions I and 2, there shall be no openings in such occupancy separations
except for necessary ducts and piping.
In any room in a Group H, Division I, 2 or 3 Occupancy in which volatile,
flammable liquids or hazardous materials are stored or used, energy-consuming
equipment shall not be used unless such equipment has been listed specifically for
the hazardous atmosphere that may develop.
In Division 4 Occupancies, devices which generate a spark or glow capable of
igniting gasoline vapors shall not be installed or used within I8 inches of the floor.
82
1982 EDITION 908-910
The use, handling and sale of Classes I, II and III-A liquids shall be in
accordance with the Fire Code.
Dry-cleaning plants shall comply with the Fire Code.
Equipment or machinery which generates or emits combustible or explosive
dust or fibers shall be provided with an adequate dust-collecting and exhaust
system installed in conformance with the Mechanical Code.
The storage and handling of cellulose nitrate plastics other than film shall be in
accordance with the Fire Code. Storage and handling of combustible fiber in
amounts beyond the exemptions of Table No. 9-A shall be in accordance with the
Fire Code.
Combustible fiber storage rooms or vaults having a capacity exceeding 500
cubic feet shall be separated from the remainder of the building by a two-hour fire-
resistive occupancy separation.
I
Buildings erected or converted to house high-piled combustible stock shall
comply with the Fire Code.
Fire Alarms
Sec. 909. An approved fire alarm system shall be installed in Group H, .
Division 2 Occupancies used for the manufacturing of organic coatings as
specified in the Fire Code.
Explosion Venting
Sec. 910. (a) Flammable Dusts. Rooms or portions of a building wherein
flammable dusts are stored, manufactured, processed or used and may be in
suspension in the air continuously or intermittently, shall conform with the
following:
1. Wall and ceiling surfaces shall be smooth. Ledges shall be beveled at 60
degrees to the horizontal to prevent the accumulation of dust.
2. Every dust-producing process shall be provided with a dust-collection
system adequate in capacity to prevent hazardous concentrations of dust within
the room.
3. Effective venting devices equal in area to at least I square foot for each 80
cubic feet of volume shall be provided for every flammable dust-collection or
storage container having a volume exceeding 250 cubic feet.
The venting devices shall be of light noncombustible construction and shall
vent directly to the exterior of the building. Venting devices shall be located in
walls facing yards 30 feet or more in width, or located in roofs where there are no
snow loads.
(b) Flammable Liquids. Rooms used for dispensing of Class I-B liquids and
rooms used for storage or dispensing of Class 1-A liquids shall have roofs or walls
designed to relieve internal explosion forces.
Group H, Division 2 Occupancies involving chemical operations such as
oxidation, reduction, polygenization, hydrogenation, alcoholization, polymer-
ization and similar chemical processes shall have roofs or walls designed to
relieve explosion forces.
83
9-A UNIFORM BUILDING CODE
I
'The quantities of alcoholic beverages in retail sales or storage uses are unlimited, provided
the liquids are packaged in individual containers not exceeding 4liters.
The quantities of medicines, foodstuffs and cosmetics, containing not more than 50
percent by volume of water-miscible liquids and with the remainder of the solution not
being flammable, in retail sales or storage occupancies are unlimited when packaged in
individual containers not exceeding 4 liters.
'Quantities may be increased by 100 percent in areas which are not accessible to the public.
In buildings where automatic fire-extinguishing systems are installed, the quantities may
be increased 100 percent in areas accessible to the public.
'Containing not more than the exempt amounts of Class 1-A, 1-B or 1-C flammable liquids.
"Quantities of smokeless powder may be increased to a maximum of l 00 pounds, providing
I
those amounts exceeding 20 pounds are stored in an approved Class II magazine as
specified in the Uniform Fire Code.
'Quantities of black sporting powder may be increased to a maximum of 5 pounds,
providing said amount is stored in an approved Class II magazine as specified in the
Uniform Fire Code.
84
1982 EDITION 1001-1003
Chapter 10
REQUIREMENTS FOR GROUP I OCCUPANCIES
location on Property
Sec. 1003. For fire-resistive protection of exterior walls and openings, as
determined by location on property, see Section 504 and Part IV.
85
1004-1009 UNIFORM BUILDING CODE
Exit Facilities
Sec. 1004. Stairs, exits and smokeproof enclosures customarily used by human
beings shall be provided as specified in Chapter 33. (See also Section 3321.)
Shaft Enclosures
Sec. 1006. Exits shall be enclosed as specified in Chapter 33.
Elevator shafts, vent shafts and other vertical openings shall be enclosed, and
the enclosure shall be as specified in Section 1706.
Sprinkler Systems
Sec. 1007. When required by other provisions of this code, automatic sprinkler
systems and standpipes shall be installed as specified in Chapter 38.
Special Hazards
Sec. 1008. Chimneys and heating apparatus shall conform to the requirements
of Chapter 37 of this code and the Mechanical Code.
Motion picture projection rooms shall conform to the requirements of Chapter
40.
Storage of volatile flammable liquids shall not be allowed in Group I Occupan-
cies and the handling of such liquid shall not be permitted in any Group I
Occupancies in quantities of more than one gallon unless such handling complies
with the Fire Code.
All exterior openings in a boiler room or room containing central heating
equipment if located below openings in another story, or if less than I 0 feet from
the other doors or windows of the same building, shall be protected by a fire
assembly having a three-fourths-hour fire-protection rating. Such fire assemblies
shall be fixed, automatic- or self-closing. Every room containing a boiler or
central heating plant shall be separated from the rest of the building by not less
than a one-hour fire-resistive occupancy separation.
EXCEPTION: Boilers or central heating plants where the largest piece of fuel
equipment does not exceed 400,000 Btu-per-hour input.
Fire Alarms
Sec. 1009. An approved fire alarm system shall be provided for all Group I
Occupancies. Audible alarm devices shall be used in all nonpatient areas. Visible
alarm devices may be used in lieu of audible devices in patient-occupied areas.
86
1982 EDITION 1101-1104
Chapter 11
REQUIREMENTS FOR GROUP M OCCUPANCIES
Location on Property
Sec. 1103. For fire-resistive protection of exterior walls and openings, as
determined by location on property, see Section 504 and Part IV.
Special Hazards
Sec. 1104. Chimneys and heating apparatus shall conform to the requirements
of Chapter 37 and the Mechanical Code.
Under no circumstances shall a private garage have any opening into a room
used for sleeping purposes.
Flammable liquids shall not be stored, handled or used in Group M Occupan-
cies unless such storage or handling shall comply with the Fire Code.
87
1105-1106 UNIFORM BUILDING CODE
88
1982EDinON 12011203
Chapter12
REQUIREMENTS FOR GROUP R OCCUPANCIES
I
Division 2. Not used.
Division 3. Dwellings and lodging houses.
For occupancy separations, see Thble No. 5-B.
A complete code for construction of detached one- and two-family dwellings is
in Appendix Chapter 12 of this code. When adopted, as set forth in Section 103, it
will take precedence over the requirements set forth in Parts I through X and
Chapter 60 of this code.
Location on Property
Sec. 1203. For frre-resistive protection of exterior walls and openings. as
determined by location on property, see Section 504 and Part IV.
89
1204-1205 UNIFORM BUILDING CODE
Exit Facilities
Sec. 1204. Stairs, exits and smokeproof enclosures shall be as specified in
Chapter 33.
Every sleeping room below the fourth story shall have at least one operable
m window or exterior door approved for emergency escape orrescue. The units shall
be operable from the inside to provide a full clear opening without the use of
separate tools.
II All escape or rescue windows from sleeping rooms shall have a minimum net
clear opening of 5.7 square feet. The minimum net clear opening height dimen-
sion shall be 24 inches. The minimum net clear opening width dimension shall be
II 20 inches. Where windows are provided as a means of escape or rescue they shall
have a finished sill height not more than 44 inches above the floor.
Bars, grilles, grates or similar devices may be installed on an emergency escape
or rescue windows or doors, provided:
I. Such devices are equipped with approved release mechanisms which are
openable from the inside without the use of a key or special knowledge or
effort; and
2. The building is equipped with smoke detectors installed in accordance with
Section 1210.
90
1982 EDITION 1205-1207
onto a street or public alley or a yard or court located on the same lot as the
building.
EXCEPTION: Required windows may open into a roofed porch where the
porch:
I. Abuts a street, yard or court; and
2. Has a ceiling height of not less than 7 feet; and
3. Has the longer side at least 65 percent open and unobstructed.
(b) Sanitation. Every building shall be provided with at least one water closet.
Every hotel or subdivision thereof where both sexes are accommodated shall
I
contain at least two separate toilet facilities which are conspicuously identified for
male or female use, each of which contains at least one water closet.
Additional water closets shall be provided on each floor for each sex at the rate
of one for every additional 10 guests, or fractional part thereof, in excess of 10.
Every dwelling unit shall be provided with a kitchen equipped with a kitchen
sink. Every dwelling unit and every lodging house shall be provided with a
bathroom equipped with facilities consisting of a water closet, lavatory and either
a bathtub or shower. Each sink, lavatory and either a bathtub or shower shall be
equipped with hot and cold running water necessary for its normal operation.
For other requirements on water closets, see Section 510.
Yarda and Courts
Sec. 1206. (a) Scope. This section shall apply to yards and courts having
required windows opening therein.
(b) Yards. Every yard shall be not less than 3 feet in width for one-story and
two-story buildings. For buildings more than two stories in height, the minimum
width of the yard shall be increased at the rate of I foot for each additional story.
For buildings exceeding 14 stories in height, the required width of yard shall be
computed on the basis of 14 stories.
(c) Courts. Every court shall be not less than 3 feet in width. Courts having
windows opening on opposite sides shall be not less than 6 feet in width. Courts
bounded on three or more sides by the walls of the building shall be not less than
10 feet in length unless bounded on one end by a street or yard. For buildings more
than two stories in height, the court shall be increased I foot in width and 2 feet in
length for each additional story. For buildings exceeding 14 stories in height, the
required dimensions shall be computed on the basis of 14 stories.
Adequate access shall be provided to the bottom of all courts for cleaning
purposes. Every court more than two stories in height shall be provided with a
horizontal air intake at the bottom not less than 10 square feet in area and leading
to the exterior of the building unless abutting a yard or public space. The
construction of the air intake shall be as required for the court walls of the
building, but in no case shall be less than one-hour fire resistive.
Room Dimensions
Sec. 1207. (a) Ceiling Heights. Habitable space shall have a ceiling height of
not less than 7 feet 6 inches except as otherwise permitted in this section.
Kitchens, halls, bathrooms and toilet compartments may have a ceiling height of
91
1207-1210 UNIFORM BUILDING CODE
not less than 7 feet measured to the lowest projection from the ceiling. Where
exposed beam ceiling members are spaced at less than 48 inches on center, ceiling
height shall be measured to the bottom of these members. Where exposed beam
ceiling members are spaced at 48 inches or more on center, ceiling height shall be
measured to the bottom of the deck supported by these members, provided that
the bottom of the members is not less than 7 feet above the floor.
If any room in a building has a sloping ceiling, the prescribed ceiling height for
the room is required in only one half the area thereof. No portion of the room
measuring less than 5 feet from the finished floor to the finished ceiling shall be
included in any computation of the minimum area thereof.
If any room has a furred ceiling, the prescribed ceiling height is required in two
thirds the area thereof, but in no case shall the height of the furred ceiling be less
than 7 feet.
(b) Floor Area. Every dwelling unit shall have at least one room which shall
have not less than 150 square feet of floor area. Other habitable rooms except
kitchens shall have an area of not less than 70 square feet. Efficiency dwelling
units shall comply with the requirements of Section 1208.
(c) Width. Habitable rooms other than a kitchen shall be not less than 7 feet in
any dimension.
Efficiency Dwelling Units
Sec. 1208. An efficiency dwelling unit shall conform to the requirements of the
code except as herein provided:
I. The unit shall have a living room of not less than 220 square feet of
superficial floor area. An additionai!OO square feet of superficial floor area shall
be provided for each occupant of such unit in excess of two.
2. The unit shall be provided with a separate closet.
3. The unit shall be provided with a kitchen sink, cooking appliance and
refrigeration facilities, each having a clear working space of not less than 30
inches in front. Light and ventilation conforming to this code shall be provided.
4. The unit shall be provided with a separate bathroom containing a water
closet, lavatory and bathtub or shower.
Shaft Enclosures
Sec. 1209. Exits shall be enclosed as specified in Chapter 33.
Elevator shafts, vent shafts, dumbwaiter shafts, clothes chutes and other
vertical openings shall be enclosed and the enclosure shall be as specified in
Section 1706.
Fire-warning and Sprinkler Systems
Sec. 1210 (a) Fire-warning Systems. Every dwelling unit and every guest
room in a hotel or lodging house used for sleeping purposes shall be provided with
smoke detectors conforming to U.B.C. Standard No. 43-6. In dwelling units,
detectors shall be mounted on the ceiling or wall at a point centrally located in the
corridor or area giving access to rooms used for sleeping purposes. In an
efficiency dwelling unit, hotel sleeping room and in hotel suites, the detector shall
92
1982 EDITION 1210-1212
be centrally located on the ceiling of the main room or hotel sleeping room. Where
sleeping rooms are on an upper level, the detector shall be placed at the center of
the ceiling directly above the stairway. All detectors shall be located in accordance
with approved manufacturer's instructions. When actuated, the detector shall
provide an alarm in the dwelling unit or guest room.
When alterations, repairs or additions requiring a permit and having a valuation
in excess of $1000 occur, or when one or more sleeping rooms are added or
created in existing Group R, Division 3 Occupancies, the entire building shall be
provided with smoke detectors located as required for new Group R, Division 3
Occupancies.
In new construction, required smoke detectors shall receive their primary
power from the building wiring when such wiring is served from a commercial
source. Wiring shall be permanent and without a disconnecting switch other than
those required for overcurrent protection. Smoke detectors may be battery oper-
I
ated when installed in existing buildings, or in buildings without commercial
power, or in buildings which undergo alterations, repairs or additions regulated by
the second paragraph of this section.
A smoke detector shall be installed in the basement of dwelling units having a
stairway which opens from the basement into the dwelling. Such detector shall be
connected to a sounding device or other detector to provide an alarm which will be
audible in the sleeping area.
(b) Sprinkler Systems. When required by other provisions of this code,
automatic sprinkler systems and standpipes shall be installed as specified in
Chapter 38.
Heating
See. 1211. Every dwelling unit and guest room shall be provided with heating
facilities capable of maintaining a room temperature of 70F. at a point 3 feet
above the floor in all habitable rooms.
Special Hazards
See. 1212. Chimneys and heating apparatus shall conform to the requirements
of Chapter 37 and the Mechanical Code.
The storage and handling of gasoline, fuel oil or other flammable liquids in
Division I Occupancies shall be in accordance with the Fire Code.
In Division I Occupancies, doors leading into rooms in which volatile flam-
mable liquids are stored or used shall be protected by a fire assembly having a one-
hour fire-protection rating. Such fire assembly shall be self-closing and shall be
posted with a sign on each side of the door in l-inch block letters stating: FIRE
DOOR-KEEP CLOSED.
Every room containing a boiler or central heating plant in Division 1 Occupan-
cies shall be separated from the rest of the building by not less than a one-hour
fire-resistive occupancy separation.
EXCEPTION: A separation shall not be required for such rooms with equip-
ment serving only one dwelling unit.
93
1213-1214 UNIFORM BUILDING CODE
To determine the total number of accessible units, more than one structure on a
I
building site shall be considered as one building. Habitable rooms, bathrooms,
toilet compartments, halls and utility rooms in units that are required to be
accessible to the physically handicapped shall be accessible by level floors, ramps
or elevators, and doorways to such rooms shall have a clear unobstructed width of
not less than 32 inches.
Toilet facilities in accessible units shall comply with Section 511.
Modifications
Sec. 1214. A one-story carport entirely open on two or more sides need not
have a fire separation between the carport and the dwelling.
Windows between the carport and the dwelling shall not be openable. Doors
.. may be of any type, provided that any sash used in a door be fixed; doors between
a dwelling and a carport shall be self-closing .
Chapters 1316
NO REQUIREMENTS
94
1982 EDITION 1701-1704
Part IV
REQUIREMENTS BASED ON TYPES OF
CONSTRUCTION
Chapter 17
CLASSIFICATION OF ALL BUILDINGS BY TYPES OF
CONSTRUCTION AND GENERAL REQUIREMENTS
General
Sec. 1701. The requirements of Part IV are for the various types of construction
and represent varying degrees of public safety and resistance to fire. Every
building shall be classified by the building official into one of the types of
construction set forth in Table No. 17-A. Any building which does not entirely
conform to a type of construction set forth in Table No. 17-A shall be classified by
a building official into a type having an equal or lesser degree of fire resistance.
A building or portion thereof shall not be required to conform to the details of a
type of construction higher than that type which meets the minimum requirements
based on occupancy (Part Ill) even though certain features of such building
actually conform to a higher type of construction.
Where specific materials, types of construction or fire-resistive protection are
required, such requirements shall be the minimum requirements, and any mate-
rials, types of construction or fire-resistive protection which will afford equal or
greater public safety or resistance to fire, as specified in this code, may be used.
Portions of buildings separated as specified in Section 505 (e) may be consid-
ered a separate building for classification of types of construction. When there is
no such separation, the area of the entire building shall not exceed the least area
permitted for the types of construction involved.
Structural Frame
Sec. 1702. The structural frame shall be considered to be the columns and the
girders, beams, trusses and spandrels having direct connections to the columns
and all other members which are essential to the stability of the building as a
whole. The members of floor or roof panels which have no connection to the
columns shall be considered secondary members and not a part of the structural
frame.
Usable Space Under Floors
Sec. 1703. Usable space under the first story shall be enclosed except in Groups
R, Division 3 and M Occupancies, and such enclosure when constructed of metal
or wood shall be protected on the side of the usable space as required for one-hour
fire-resistive construction. Doors shall be self-closing, of noncombustible con-
struction or solid wood core, not Jess than I '14 inches in thickness.
Roofs
Sec. 1704. Roof coverings shall be as specified in Section 3202 (b).
95
1705 UNIFORM BUILDING CODE
96
1982 EDITION 1705-1706
Shaft Enclosures
Sec. 1706. (a) General. Openings extending vertically through floors shall he
enclosed in a shaft of fire-resistive construction having the time period set forth in
Table No. 17A for "Shaft Enclosures." Protection for stairways shall be as
specified in Sections 3309 and 3310.
EXCEPTIONS: 1. In other than Group I Occupancies, an enclosure will not be
required for openings which serve only one adjacent floor and are not connected
with opening~ serving other floors and which are not concealed within the building
construction.
2. In buildings housing Group B Occupancies equipped with automatic sprinkler
systems throughout, enclosures shall not be required for escalators where the top of
the escalator opening at each story is provided with a draft curtain and automati~ fire
sprinklers are installed around the perimeter of the opening within 2 feet of the draft
curtain. The draft curtain shall enclose the perimeter of the unenclosed opl'ning and
extend from the ceiling downward at least 12 inches on all side~. The ~pacing
between sprinklers shall not exceed 6 feet.
3. In Type V buildings, chutes and dumbwaiter shafts with a cross-sectional area
of nul more than 9 square feet may be unenclosed if lined on the inside with lath and
plaster or gypsum wallboard, with such lining covered with not leo;.:-. than No. 26
galvanized sheet metal gauge with all joints in such :-.hcct metal locklapped. All
openings into any such enclosure shall be protected by metal or metal-dad door~
with either metal or metal-cladjambs, casings or frames.
4. Exit enclosures shall conform to the applicable provision~ of Sections 3309 ami
J310.
5. In one- and two-story buildings of other than Group I Occupancies. ~hafts fm
97
1706-1707 UNIFORM BUILDING CODE
gas vents and for ducts or piping which extend through not more than two floors need
not comply with Table No. 17-A.
I
6. Gas vents and noncombustible piping installed in walls of buildings passing
through three floors or less need not comply with Table No. 17-A. Such shafts shall
be effectively draft-stopped at each floor or ceiling.
(b) Protection of Openings. Every opening into a shaft enclosure shall be
protected by a self-closing fire assembly conforming to Section 4306 and having a
fire-protection rating of one hour for openings through one-hour walls and one
and one-half hours for openings through two-hour walls.
EXCEPTIONS: I. Openings to the exterior may be unprotected when so permit-
ted by Table No. 5-A.
2. Openings produced by air ducts piercing shaft enclosure walls may be pro-
tected by fire dampers conforming to C .B.C. Standard No. 43-7.
I
(c) Rubbish and Linen Chutes. In other than Group R. Division 3 Occupan-
cies, rubbish and linen chutes shall terminate in rooms separated from the
remainder of the building by a one-hour fire-resistive occupancy separation.
Openings into the chutes and termination rooms shall not be located in exit
corridors or stairways.
(d) Elevator Shafts. Shafts housing elevators and extending through more than
two stories shall be vented to the outside. The area of vents shall be not less than
3 1/, percent of the area of the elevator shaft, with a minimum of 3 square feet per
elevator.
Weather Protection
Sec. 1707. (a) Weather-resistive Barriers. All weather-exposed surfaces shall
have a weather-resistive barrier to protect the interior wall covering. Such barrier
shall be equal to that provided for in U.B.C. Standard No. 17-1 for kraft
waterproof building paper or U .B.C. Standard No. 32-1 for asphalt-saturated rag
felt. Building paper and felt shall be free from holes and breaks other than those
created by fasteners and construction system due to attaching of the building
paper. and shall be applied over studs or sheathing of all exterior walls. Such felt
or paper shall be applied over studs or sheathing of all exterior walls. Such felt or
paper shall be applied weatherboard fashion, lapped not less than 2 inches at
horizontal joints and not less than 6 inches at vertical joints.
Weather-protective barrier may be omitted in the following cases:
I. When exterior covering is of approved weatherproof panels.
2. In back-plastered construction.
3. When there is no human occupancy.
4. Over water-repellent panel sheathing.
5. Under approved paperbacked metal or wire fabric lath.
6. Behind lath and portland cement plaster applied to the underside of roof
and eave projections.
(b) Flashing and Counterflashing. Exterior openings exposed to the weather
shall be flashed in such a manner as to make them weatherproof.
All parapets shall be provided with coping of approved materials. All flashing,
98
1982 EDITION 1707-1710
counterflashing and coping, when of metal, shall be of not less than No. 26 U.S.
gauge corrosion-resistant metal.
(c) Waterproofing Weather-exposed Areas. Balconies, landings, exterior
stairways and similar surfaces exposed to the weather and sealed underneath shall
be waterproofed.
(d) Dampproofing Foundation Walls. Unless otherwise approved by the
building official, foundation walls enclosing a basement below finished grade
shall be dampproofed outside by approved methods and materials.
I
.
Parapets
Sec. 1709. (a) General. Parapets shall be provided on all exterior walls of
buildings.
EXCEPTIONS: I. Walls which are not required to be of fire-resistive
construction.
2. Walls which terminate at roofs of not less than two-hour fire-resistive con-
struction or roofs constructed entirely of noncombustible materials.
3. Walls where, due to location on property, unprotected openings are permitted.
4. Walls on all buildings having a floor area of not more than 1000 square feet per
floor.
(b) Construction. Parapets shall have the same degree of fire resistance
required for the wall upon which they are erected. The height of the parapet shall
be not less than 30 inches above the point where the roof surface and the wall
intersect. Where the roof slopes toward a parapet at slopes greater than 2: 12, the
parapet shall extend to the same height as any portion of the roof that is within the
distance where protection of wall openings would be required, but in no case shall
the height be less than 30 inches.
Projections
Sec. 1710. Cornices, eave overhangs, exterior balconies and similar architec-~
tural appendages extending beyond the floor area as defined in Section 407 shall
conform to the requirements of this section. (See Section 3305 for additional
requirements applicable to exterior exit balconies.)
Projections from walls of 1Ype I or II construction shall be of noncombustible
materials.
Projections from walls of Type III, IV or V construction may be of noncombus-
tible or combustible materials.
Combustible projections located where openings are not permitted or where
protection of openings is required shall be of one-hour frre-resistive or heavy
timber construction conforming to Section 2106.
99
1710-1712 UNIFORM BUILDING CODE
Projections shall not extend more than 12 inches into the areas where openings
are prohibited.
For projections extending over public property, see Chapter 45.
For combustible ornamentation, see Section 1705 (d).
Guardrails
Sec. 1711. All unenclosed floor and roof openings, open and glazed sides of
landings and ramps, balconies or porches which are more than 30 inches above
grade or floor below, and roofs used for other than service of the building shall be
protected by a guardrail. Guardrails shall be not less than 42 inches in height.
Open guardrail and stair railings shall have intermediate rails or an ornamental
I pattern such that a sphere 6 inches in diameter cannot pass through. The height of
stair railings on open sides may be as specified in Section 3306 (j) in lieu of
providing a guardrail. Ramps shall, in addition, have handrails when required by
Section 3307.
EXCEPTIONS: I. Guardrails need not be provided on the loading side of
loading docks.
2. Guardrails for Group R, Division 3 and Group M, Division I Occupancies may
be 36 inches in height.
3. Interior guardrails within individual dwelling units or guest rooms of Group R,
Division l Occupancies may be 36 inches in height.
4. The open space between the intermediate rails or ornamental pattern of
guardrails in areas of commercial and industrialtype occupancies which are not
accessible to the public may be increased such that a 12-inch-diameter sphere cannot
pass through.
5. Guardrails on a balcony immediately in front ofthe first row of fixed seats and
which are not at the end of an aisle may be 26 inches in height.
100
1982 EDITION 1712
vided by Section 1712 (c) or by other sections of this code, foam plastics may be
used as follows:
I. Masonry or concrete construction. Foam plastics may be used without the
thennal barrier described above, regardless of the type of construction, when the
foam plastic is covered by a minimum of l-inch thickness of masonry or concrete
in a wall, floor or roof system.
2. Attics and crawl spaces. Within an attic or crawl space where entry is made
only for service of utilities, foam plastics shall be protected against ignition by
1Y2-inch-thick mineral fiber insulation, '!-inch-thick plywood, hardboard or
gypsum wallboard, corrosion-resistant sheet metal having a base metal thickness
not less than 0.0160 inch at any point, or other approved material installed in such
a manner that the foam plastic is not exposed.
3. Cold storage construction. Foam plastic installed and meeting the require-
ments of (a) above when tested in a thickness of 4 inches may be used in a
thickness up to 10 inches in cold storage buildings, ice plants, food-processing
rooms and similar areas. For rooms within a building, the foam plastic shall be
protected by a thermal barrier on both sides having an index of 15.
Foam plastic insulation may be used in freestanding coolers and freezers
without the thermal barrier when the foam plastic has a flame-spread rating of 25
or less when tested in the thickness intended for use, is covered by not less than
0.032 inch of aluminum or corrosion-resistant steel having a base metal thickness
not less than 0.0160 inch at any point and is protected by an automatic sprinkler
system. When such a cooler or freezer is within a building, both the cooler or
freezer and that part of the building in which the room is located shall be
sprinklered.
EXCEPTION: Freestanding walk-in coolers and freezer units having an aggre
gate floor area less than 400 square feet need meet only the flame-spread and smoke
requirements of Section 1712 (a) above.
101
1712-1713 UNIFORM BUILDING CODE
thickness bonded with exterior glue, with edges supported by blocking, tongue-
and-groove joints or other approved type of edge support, or an equivalent
material. The thermal barrier requirement is waived.
For all roof applications, the smoke-developed rating shall not be limited.
6. Doors. Where doors are permitted without a fire-resistive rating, foam
plastic having a flame-spread rating of 75 or less may be used as a core material
when the door facing is metal having a minimum thickness of 0.032-inch alumi-
numor steel having a base metal thickness not less than 0.0160 inch at any point.
The thermal barrier requirement is waived.
7. Siding backer board. Foam plastic of not more than 2000 Btu per square
foot as determined by U.B.C. Standard No. 17-2 may be used as siding backer
board with a maximum thickness of V2 inch, provided it is separated from the
interior of the building by not less than 2 inches of mineral fiber insulation or
equivalent in lieu of the thermal barrier, or when it is applied as residing over
existing wall construction.
(c) Specltlc Approval. Plastic foam or assemblies using foam plastics may be
specifically approved based on approved tests such as, but not limited to, tunnel
tests conducted in accordance with U .B.C. Standard No. 42-1, fire tests related to
actual end use such as a set forth in U.B.C. Standard No. 17-5 and an ignition
temperature test establishing a minimum self-ignition temperature of 650F.
underU.B.C. Standard No. 52-3. The specific approval may be based on the end
use, quantity, location and similar considerations where such tests would not be
applicable or practical.
Insulation
Sec. 1713. (a) General. Thermal and acoustical insulation located on or within
floor-ceiling and roof-ceiling assemblies, crawl spaces, walls, partitions and
insulation on pipes and tubing shall comply with this section. Duct insulation and
insulation in plenums shall conform to the requirements of the Uniform Mechan-
ical Code.
EXCEPTION: Roof insulation shall comply with Section 3204.
(b) Insulation and Covering on Pipe and Thbing. Insulation and covering on
pipe and tubing shall have a flame-spread rating not to exceed 25 and a smoke
density not to exceed 450 when tested in accordance with U.B.C. Standard No.
42-1.
EXCEPTION: Foam plastic insulation shall comply with Section 1712.
(c) Insulation. All insulation materials including facings, such as vapor barri-
ers or breather papers installed within floor-ceiling assemblies, roof-ceiling
assemblies, walls, crawl spaces or attics shall have a flame-spread rating not to
exceed 25 and a smoke density not to exceed 450 when tested in accordance with
U.B.C. Standard No. 42-1.
EXCEPTIONS: I. Foam plastic insulation shall comply with Section 1712.
2. When such materials are installed in concealed spaces oflYpes III, IV and V
construction, the flame-spread and smoke-developed limitations do not apply to
102
1982 EDITION 17131715
facings, provided that the facing is installed in substantial contact with the unex-
posed surface of the ceiling, floor or wall finish.
Solar Energy Collectors
Sec. 1714. Collectors which function as building components shall comply
with the applicable provisions of the code.
Collectors located above or upon a roof and not functioning as building
components shall not reduce the required fire resistance nor fire-retardancy
classification of the roof covering materials.
EXCEPTIONS: I. Collectors installed on one- and two-family dwellings.
2. Noncombustible collectors located on buildings not over three stories in height
or 9000 square feet in total floor area.
3. Collectors that comply with the provisions of Section 5214.
Atriums
Sec. 1715. (a) General. Buildings of other than Group H Occupancy with
automatic sprinkler protection throughout may have atriums complying with the
provisions of this section. Such atriums shall have a minimum opening area and
dimension as set forth in Table No. 17-B.
(b) Smoke-control System. A mechanically operated air-handling system
shall be installed that will exhaust smoke either entering or developed within the
atrium. Exhaust openings shall be located in the ceiling or in a smoke trap area
immediately adjacent to the ceiling of the atruim. The lowest level of the exhaust
openings shall be located above the top of the highest portion of door openings
into the atrium. Supply openings sized to provide a minimum of 50 percent of the
exhaust volume shall be located at the lowest level of the atrium.
When the height of the atrium is 55 feet or Jess, supply air may be introduced by
gravity, provided smoke control is accomplished. When the height of the atrium is
more than 55 feet, supply air shall be introduced mechanically from the floor of
the atrium and be directed vertically toward the exhaust outlets. In atriums over
six stories in height or where tenant spaces above the second story are open to the
atrium, supplemental supply air may be introduced at upper levels. The exhaust
and supply system for the atrium shall operate automatically upon the actuation of
the automatic sprinkler system within the atrium or areas open to the atrium or by
the actuation of two or more smoke detectors required by this section. The exhaust
and supply equipment shall also be manually operable by controls designed for
ftre department use. The smoke-control system may be separate or integrated
with other air-handling systems. When the smoke-control mode is actuated, air-
handling systems which would interfere with the smoke-control system shall be
automatically shut down.
Enclosed tenant spaces shall be provided with a smoke-control system comply-
ing with the requirements of a sprinklered building in Section 1807 (g), Item No.
2or 3.
The atrium smoke-control system shall exhaust not Jess than the following
quantities of air:
I. For atriums having a volume of not more than 600,000 cubic feet, includ-
ing the volume of any levels not physically separated from the atrium, not
103
1715 UNIFORM BUILDING CODE
less than six air changes per hour nor less than 40,000 cfm. A lesser cfm is
acceptable if it can be shown by test that smoke will not migrate beyond the
perimeter of the atrium.
2. For atriums having a volume of more than 600,000 cubic feet, including
the volume of any levels not physically separated from the atrium. not less
than four air changes per hour.
Smoke detectors which will automatically operate the atrium smoke-control
system shall be installed at the perimeter and on the ceiling of the atrium and on
the ceiling of each floor level that is open to the atrium. In floor levels open to the
atrium, such detectors shall be within 15 feet of the atrium. Detectors shall be
located in accordance with their listing.
(c) Enclosure or Atriums. Atriums shall be separated from adjacent spaces by
not less than one-hour fire-resistive construction.
EXCEPTION: Open exit balconies are permitted within the atrium.
Openings in the atrium enclosure other than fixed glazing shall be protected by
tight-filling doors which are maintained automatic closing, in accordance with
Section 4306 (b). by actuation of a smoke detector, or self-closing.
Fixed glazed openings in the atrium cnclo~ure shall be equipped with fire
windows having a fire-resistive rating of not less than three-fourths hour, and the
total area of such openings shall not exceed 25 percent of the area of the common
wall between the atrium and the room into which the opening is provided.
EXCEPTIONS: 1. In Group R. Division I Occupancies, openings may he
unprotected when the floor area of each guest room or dwelling unit does not exceed
1000 square feet and each room or unit has an approved exit not entering the atrium.
2. In occupancies other than Group R, Division I, the tenant space may be
separated from the atrium by a wired, tempered or laminated glass wall. subject to
the following:
A. The glass shall be protected by a sprinkler system equipped with 135F. heads.
The sprinkler system shall completely wet the entire surface of the glass wall
when actuated. Where there are walking surfaces on both sides of the glass, both
sides ofthe glass shall be so protected.
B. The glass shall be in a gasketed frame so installed that the glazing system may
deflect without breaking (loading) the glass before the sprinkler system
operates.
C. Obstructions such as curtain rods, drapery traverse rods, curtains, drapes or
similar materials, shall not be installed between the sprinkler and the glass.
The separation between the tenant space and the atrium as specified within
Exception 2 may be omitted on a maximum of any three floor levels, provided the
remaining floor levels are separated as specified herein.
(d) Travel Distance. When a required exit enters the atrium space, the travel
distance from the doorway of the tenant space to an enclosed stairway, horizontal
exit, exterior door or exit passageway shall not exceed 100 feet.
(e) Group I Occupancy Exits. In Group I Occupancies, other than jails,
prisons and reformatories, sleeping rooms shall not be permitted to have required
exits through the atrium.
(t) Occupancy Separation Exceptions. The vertical portion ofthe occupancy
104
1982 EDITION 1715-1716
105
1716 UNIFORM BUILDING CODE
106
TABLE NO. 17A-TYPES OF CONSTRUCTION-FIRE-RESISTIVE REQUIREMENTS ....
(In Hours)
For Details see Chapters under Occupancy and Types of Construction and for Exceptions see Section 1705. !m
TYPE I TYPE Ill TYPE IV TYPEV
c
TYPE II
3
NONCOMBUSTIBLE COMBUSTIBLE 0
z
Fire Fire-
BUILDING ELEMENT Realatlve Realsllwe 1-Hr. N 1-Hr. N H.T. 1Hr. N
4
4 4 4 4
Exterior Bearing Walls Sec. 1903 (a) I N 2103(a) I N
1803 (a) 2003 (a) 2003 (a)
Interior Bearing \Valls 3 2 1 N 1 N 1 1 N
S tructnral F mme 1 2 1 N N 1 or
3 1 H.T. 1 N
lor
Partitions - Permanent 1' 1' 12 N 1 N H.T. l N
I I
Shaft Enclosures 2 2 1 I 1 l 1 1706 1706
Floors 2 2 l N l N H.T. 1 N
Roofs 2 l 1 N N H.T. l N
Sec. 1806 1906 1906 1
Exterior Doors and Sec. l903(b) 1903 (b) 1903(b 2l0.1(b) 2203 220:1
Windows 1803 (b) 2003 (b) 2003 (b)
MINIMUM
HEIGHT IN STORIES CLEAR OPENING' (Ft.) MINIMUM AREA (Sq. Ft.)
3-4 20 400
5-7 30 900
8 or more 40 1600
1The specified dimensions are the diameters of inscribed circles whose centers fall on a
common axis for the full height of the atrium.
108
1982 EDITION 18011804
Chapter 18
TYPE I FIRE-RESISTIVE BUILDINGS
Definition
Sec. 1801. The structural elements in TYpe I fire-resistive buildings shall be of
steel, iron, concrete or masonry.
Walls and permanent partitions shall be of noncombustible fire-resistive con-
struction except that permanent nonbearing partitions of one-hour or two-hour
fire-resistive construction, which are not part of a shaft enclosure, may have fire-
retardant treated wood (see Section 407) within the assembly.
Materials of construction and fire-resistive requirements shall be as specified in
Chapter 17.
Structural Framework
Sec. 1802. Structural framework shall be of structural steel or iron as specified
in Chapter 27, reinforced concrete as in Chapter 26, or reinforced masonry as in
Chapter 24.
For additional requirements for Group H Occupancies, see Section 902.
Floors
Sec. 1804. Where wood sleepers are used for laying wood flooring on masonry
or concrete fire-resistive floors, the space between the floor slab and the underside
of the wood flooring shall be filled with noncombustible material or fire-stopped
in such a manner that there will be no open spaces under the flooring which will
exceed 100 square feet in area and such space shall be filled solidly under all
109
1804-1807 UNIFORM BUILDING CODE
Stair Construction
Sec. 1805. Stairs and stair platforms shall be constructed of reinforced con-
crete, iron or steel with treads and risers of concrete, iron or steel. Brick, marble,
tile or other hard noncombustible materials may be used for the finish of such
treads and risers.
Stairs shall be designed and constructed as specified in Chapter 33.
Roofs
Sec. 1806. Roofs and their members other than the structural frame more than
25 feet above any floor, balcony or gallery may be of unprotected noncombustible
materials. Heavy timber members in accordance with Section 2106 may be used
for such unprotected members in one-story buildings.
When every part of the structural framework of the roof of a Group A or E
Occupancy is not less than 25 feet above any floor, balcony or gallery, fire
protection of all members of the roof construction including those of the structural
frame may be omitted. Heavy timber members in accordance with Section 2106
may be used for such unprotected members in one-story buildings.
Where every part of the structural steel framework of the roof of a Group A orE
Occupancy is more than 18 feet and less than 25 feet above any floor, balcony or
gallery, the roof construction shall be protected by a ceiling of not less than one-
hour fire-resistive construction.
Roof covering shall be fire-retardant roofing as specified in Section 3202 (b).
110
1982 EDITION 1807
111
1807 UNIFORM BUILDING CODE
112
1982 EDITION 1807
handling system shall provide a minimum of one exhaust air change each 10
minutes for the area involved.
3. Any other approved design which will produce equivalent results.
(h) Elevators. Elevators and elevator lobbies shall comply with the provisions
of Chapter 51 and the following:
NOTE: A bank of elevators is a group of elevators or a single elevator controlled
by a common operating system; that is, all those elevators which respond to a single
call button constitute a bank of elevators. There is no limit on the number of cars
which may be in a bank or group but there may be not more than four cars within a
common hoistway.
I . Elevators on all floors shall open into elevator lobbies which are separated
from the remainder of the building, including corridors and other exits, by walls
extending from the floor to the underside of the fire-resistive floor or roof above.
Such walls shall be of not less than one-hour fire-resistive construction. Openings
through such walls shall conform to Section 3305 (h).
EXCEPTIONS: I. The main entrance level elevator lobby in office buildings.
2. Elevator lobbies located within an atrium complying with the provisions of
Section 1715.
2. Each elevator lobby shall be provided with an approved smoke detector
located on the lobby ceiling. When the detector is activated, elevator doors shall
not open and all cars serving that lobby are to return to the main floor and be under
manual control only. If the main floor detector or a transfer floor detector is
activated, all cars serving the main floor or transfer floor shall return to a location
approved by the fire department and building official and be under manual control
only. The smoke detector is to operate before the optical density reaches 0.03 per
foot. The detector may serve to close the lobby doors.
3. Elevator hoistways shall not be vented through an elevator machine room.
Cable slots entering the machine room shall be sleeved beneath the machine room
floor and extend to not less than 12 inches below the shaft vent to inhibit the
passage of smoke into the machine room.
(i) Standby Power, Light and Emergency Systems. I. Standby power.
Standby power generating system conforming to U. B.C. Standard No. 18-1 shall
be provided. The system shall be equipped with suitable means for automatically
starting the generator set upon failure of the normal electrical supply systems and
for automatic transfer of all functions required by this section at full power within
60 seconds of such normal service failure. System supervisions with manual start
and transfer features shall be provided at the central control station.
An on-premise fuel supply sufficient for not less than two hours full demand
operation of the system shall be provided.
The standby system shall have a capacity and rating that would supply all
equipment required to be operational at the same time. The generating capacity
need not be sized to operate all the connected electrical equipment
simultaneously.
All power, lighting, signal and communication facilities specified in (d), (e),
(f), (g), (h), (i) and (j) as applicable; fire pumps required to maintain pressure,
113
1807 UNIFORM BUILDING CODE
standby lighting and normal circuits supplying exit signs and exit illumination
shall be transferable to the standby source.
2. Standby lighting. Standby lighting shall be provided as follows:
A. Separate lighting circuits and fixtures sufficient to provide light with an
intensity of not less than one footcandle measured at floor level in all exit
corridors, stairways, smokeproof enclosures, elevator cars and lobbies and
other areas which are clearly a part of the escape route.
B. All circuits supplying lighting for the central control station and mechan-
ical equipment room.
3. Emergency systems. The following are classified as emergency systems
and shall operate within 10 seconds of failure of the normal power supply:
A. Exit sign and exit illumination as required by Sections 3313 and 3314.
B. Elevator car lighting.
G) Exits. Exits shall comply with other requirements of this code and the
following:
1. All stairway doors which are to be locked from the stairway side shall have
the capability of being unlocked simultaneously without unlatching upon a signal
from the central control station.
2. A telephone or other two-way communications system connected to an
approved emergency service which operates continuously shall be provided at not
..
less than every fifth floor in each required stairway where other provisions of this
code permit the doors to be locked .
(k) Seismic Considerations. In Seismic Zones No. 2, No. 3 and No. 4, the
anchorage of mechanical and electrical equipment required for life safety sys-
tems, including fire pumps and elevator drive and suspension systems, shall be
designed in accordance with the requirements of Section 2312.
(1) Areas of Refuge (Compartmentation) Alternate. Areas of refuge con-
forming to the following may be provided as an alternate to the automatic
sprinkler system:
1. Every story shall be divided into two or more areas of approximately the
same size with no single area exceeding 15,000 square feet. The wall and door
shall be constructed as required for a horizontal exit in Section 3308.
2. Each area of refuge (compartment) shall contain one elevator to the main
floor and a minimum of one enclosed exit stairway.
3. Openings in exterior walls, where such openings are within 5 feet of each
other horizontally on vertically adjacent floors, shall be protected by approved
flame barriers either extending 30 inches beyond the exterior wall in the plane of
the floor or by approved vertical panels not less than 3 feet in height above the
floor.
4. Horizontal exit walls used for compartmenting a building shall have a fire-
resistance rating of not less than two hours. Duct penetrations of this wall shall not
be permitted. Ferrous or copper piping and conduit may penetrate or pass through
the wall only if the openings are caulked with impervious noncombustible
materials sufficiently tight to prevent the transfer of smoke or combustion gases
114
1982 EDITION 1807
from one side of the wall to the other and are so maintained. The fire door serving
as the horizontal exit between compartments shall be so installed, fitted and
gasketed that it will provide a substantial barrier to the passage of smoke.
5. The fire-resistive floor or the floor-ceiling construction shall extend to and be
tight against the exterior wall so that the fire-resistive integrity between stories is
maintained. No penetrations or other installations which will impair the fire-
resistive integrity of the floor or floor-ceiling assembly shall be permitted.
6. A manual fire alarm system (pull boxes) shall be installed in accordance with
U.B.C. Standard No. 18-1.
(m) Automatic Sprinkler System Alternatives. When a complete approved
automatic sprinkler system complying with this section is installed in a building,
the following modifications of code requirements are permitted:
1. The fire-resistive time periods set forth in Table No. 17-A may be reduced by
one hour for interior bearing walls, exterior bearing and nonbearing walls, roofs
and the beams supporting roofs, provided they do not frame into columns.
Vertical shafts other than stairway enclosures and elevator shafts may be reduced
to one hour when sprinklers are installed within the shafts at alternate floors.
2. Except for corridors in Group B, Division 2 and Group R, Division 1
Occupancies and partitions separating dwelling units or guest rooms, all interior
nonbearing partitions required to be one-hour fire-resistive construction by Table
No. 17-A may be of noncombustible construction without a fire-resistive time
period.
3. Fixed tempered glass may be used in lieu of openable panels for smoke
control purposes.
4. 'fravel distance from the most remote point in the floor area to a horizontal
exit or to an enclosed stairway may be 300 feet.
5. The manually operated fire alarm system required in the compartmented
building is not required.
6. Spandrel walls, eyebrows and compartmentation are not required; however,
the fire resistance of the floors and juncture of exterior walls with each floor must
be maintained.
7. Fire dampers, other than those needed to protect floor-ceiling assemblies to
maintain the fire resistance of the assembly, are not required except for those
which may be necessary to bypass smoke to the outside, those provided to convert
from recirculated air to 100 percent outside air, and those which may be required
to protect the fresh air supply intake against smoke which may be outside the
building.
8. Emergency windows required by Section 1204 are not required.
115
1901-1903 UNIFORM BUILDING CODE
Chapter 19
TYPE II BUILDINGS
Definition
Sec. 1901. The structural elements in 1Ype II fire-resistive buildings shall be of
steel, iron, concrete or masonry.
The structural elements of 'IYpe II One-hour or 11-N buildings shall be of
noncombustible materials.
Walls and permanent partitions of 'IYpe 11-F.R. buildings shall be of noncom-
bustible fire-resistive construction except that permanent nonbearing partitions of
one-hour or two-hour fire-resistive construction, which are not part of a shaft
enclosure, may have fire-retardant treated wood (see Section 407) within the
assembly.
'IYpe II One-hour buildings shall be of noncombustible construction and one-
hour fire resistive throughout except that permanent nonbearing partitions may
use fire-retardant treated wood (see Section 407) within the assembly, provided
fire-resistive requirements are maintained.
Walls and permanent partitions of'IYpe 11-N buildings shall be of noncombusti-
ble materials.
Materials of construction and fire-resistive requirements shall be as specified in
Chapter 17.
For requirements due to occupancy, see Chapters 6 to 12 inclusive.
Structural Framework
Sec. 1902. Structural framework shall be as specified in Chapter 27 for iron and
steel, Chapter 26 for concrete and Chapter 24 for masonry.
Exterior Walls and Openings
Sec. 1903. (a) Exterior Walls. Exterior walls and all structural members shall
comply with the requirements specified in Section 504 and the fire-resistive
provisions set forth in Table No. 17-A. For fire protection of exterior walls as
determined by location on property, see Table No. 5-A for 1Ype II One-hour and
1Ype 11-N buildings.
EXCEPTIONS: 1. Nonbearing walls fronting on streets or yards having a width
of at least 40 feet may be of unprotected noncombustible construction.
2. In Groups R, Division I, and B Occupancies, exterior bearing walls ofJYpeii-
F.R. buildings may be of two-hour fire-resistive noncombustible construction where
openings are permitted.
3. In other than Group H Occupancies, exterior nonbearing walls ofJype II-F.R.
buildings may be of one-hour fire-resistive noncombustible construction where
unprotected openings are permitted and two-hour fire-resistive noncombustible
construction where fire protection of openings is required.
4. In a Group B Occupancy a fire-resistive time period will not be required for an
exterior wall of a one-story JYpe li-N building, provided the floor area of the
building does not exceed I 000 square feet and such wall is located not less than 5 feet
from a property line.
(b) Openings in Walls. All openings in exterior walls of 1Ype II-F. R. buildings
116
1982 EDITION 19031907
shall conform to the requirements of Section 504 (b) and shall be protected by a
fire assembly having a three-fourths-hour fire-protection rating when they are less
than 20 feet from an adjacent property line or the center line of a street or public
space.
No openings shall be permitted in exterior walls of 'JYpe II-F.R. buildings
housing Groups A, E, I, Hand B, Divisions 1, 2 and 3 Occupancies less than 5
feet from the property line, and no openings in Groups B, Division 4, R, and M
Occupancies less than 3 feet from the property line.
For fire protection of exterior wall openings of'JYpe II One-hour and 'JYpe 11-N
buildings as determined by location on property, see Section 504 and Table
No. 5-A.
Floors
Sec. 1904. Where wood sleepers are used for laying wood flooring on masonry
or concrete fire-resistive floors of 'JYpe II-F.R. buildings, the space between the
floor slab and the underside of the wood flooring shall be filled with noncombusti-
ble material or fire-stopped in such a manner that there will be no open spaces
under the flooring which will exceed 100 square feet in area and such space shall
be filled solidly under all permanent partitions so that there is no communication
under the flooring between adjoining rooms.
EXCEPTION: Firestopping need not be provided in such floors when at or
below grade level in gymnasiums.
Floor construction of 'JYpe II One-hour and 'JYpe 11-N buildings shall be of
noncombustible material, provided, however, that a wood surface or finish may be
applied over such noncombustible material.
Stair Construction
Sec. 1905. Stairs and stair platforms of 'JYpe 11-F.R. buildings shall be con-
structed of reinforced concrete, iron or steel with treads and risers of concrete,
iron or steel. Brick, marble, tile or other hard noncombustible materials may be
used for the finish of such treads and risers. Stairs of 'JYpe II One-hour and 'JYpe
li-N buildings shall be of noncombustible construction.
Stairs shall be designed and constructed as specified in Chapter 33.
Roof Construction
Sec. 1906. Roofs shall be of noncombustible construction, except that in 'JYpe
II-F.R. and 'JYpe II One-hour buildings, roofs may be as specified in Section
1806.
Roof covering shall be a fire-retardant roofing as specified in Section 3202 (b).
117
2001-2004 UNIFORM BUILDING CODE
Chapter20
TYPE Ill BUILDINGS
Definition
Sec. 20CU. Structural elements in '!Ype III buildings may be of any materials
permitted by this code.
'!Ype III One-hour buildings shall be of one-hour fire-resistive construction
throughout.
Structural Framework
Sec. 2002. Structural framework shall be of steel or iron as specified in Chapter
27, concrete as in Chapter 26, masonry as in Chapter 24, or wood as in Chapter 25
and this chapter.
Exterior Walls, Openings and Partitions
Sec. 2003. (a) Exterior Walls. Exterior walls shall be constructed of noncom-
bustible materials and shall comply with the fire-resistive requirements set forth
in Section 504 and Table No. 17-A.
EXCEPTIONS: I. Nonbearing walls fronting on streets, or yards having a width
of at least 40 feet may be unprotected when entirely of noncombustible material.
2. In other than Groups Hand I Occupancies, exterior nonbearing walls may be
noncombustible one-hour fire resistive where unprotected openings are permitted
and noncombustible two-hour fire resistive where protection of openings is
required.
3. In Groups R, Division I, and B Occupancies exterior noncombustible bearing
walls may be two-hour fire resistive where openings are permitted.
4. Approved fire-retardant treated wood framing may be used within the assembly
of exterior walls as permitted by Exceptions I , 2 and 3, provided the required fire
resistance is maintained and the exposed outer and inner faces of such walls are
noncombustible.
5. Wood columns and arches conforming to heavy timber sizes may be used
externally where exterior walls are permitted to be unprotected, noncombustible
construction or where one-hour fire-resistive noncombustible exterior walls are
permitted.
(b) Openings in Walls. Openings in exterior walls shall conform to the
requirements of Section 504 (b) and shall be protected by a fire assembly having a
three-fourths-hour fire-resistive rating when they are less than 20 feet from an
adjacent property line or the center line of a street or public space.
No openings shall be permitted in exterior walls of Groups A, E, I, Hand B,
Divisions 1, 2 and 3 Occupancies less than 5 feet from the property line, and no
openings in Groups B, Division 4, Rand M Occupancies less than 3 feet from the
property line.
118
1982 EDITION 2004-2005
119
2101-2104 UNIFORM BUILDING CODE
Chapter 21
TYPE IV BUILDINGS
Definition
Sec. 2101. Structural elements of 1Ype IV buildings may be of any materials
permitted by this code.
1Ype IV construction shall conform to Section 2106 except that permanent
partitions and members of the structural frame may be of other materials,
provided they have a fire resistance of not less than one hour.
Structural Framework
Sec. 2102. Structural framework shall be of steel or iron as specified in Chapter
27, concrete as in Chapter 26, masonry as in Chapter 24, or wood as in Chapter 25
and this chapter.
Exterior Walls, Openings and Partitions
Sec. 2103. (a) Exterior Walls. Exterior walls shall be constructed of noncom-
bustible materials and shall comply with the fire-resistive requirements set forth
in Section 504 and Table No. 17-A.
EXCEPTIONS: I. Nonbearing walls fronting on streets, or yards having a width
of at least 40 feet may be unprotected when entirely of noncombustible material.
2. In other than Groups H and I Occupancies exterior nonbearing walls may be
noncombustible one-hour fire resistive where unprotected openings are permitted
and noncombustible two-hour fire resistive where protection of openings is
required.
3. In Groups R, Division I, and B Occupancies exterior noncombustible bearing
walls may be two-hour fire resistive where openings are permitted.
4. Approved fire-retardant treated wood framing may be used within the assembly
of exterior walls as permitted by Exceptions I , 2 and 3, provided the required fire
resistance is maintained and the exposed outer and inner faces of such walls are
noncombustible.
5. Wood columns and arches conforming to heavy timber sizes may be used
externally where exterior walls are permitted to be unprotected, noncombustible
construction or where one-hour frre-resistive noncombustible exterior walls are
permitted.
(b) Openings in Walls. Openings in exterior walls shall conform to the
requirements of Section 504 (b) and shall be protected by a fire assembly having a
three-fourths-hour fire-resistive rating when they are less than 20 feet from an
adjacent property line or the center line of a street or public space.
No openings shall be permitted in exterior walls of Groups A, E, I, H and B,
Divisions 1, 2 and 3 Occupancies less than 5 feet from the property line and no
openings in Groups B, Division 4, Rand M Occupancies less than 3 feet from the
property line.
120
1982 EDITION 2104-2106
121
2106 UNIFORM BUILDING CODE
support. Floors shall not extend closer than IJ2 inch to walls. Such 1/2-inch space
shall be covered by a molding fastened to the wall and so arranged that it will not
obstruct the swelling or shrinkage movements of the floor. Corbeling of masonry
walls under floors may be used in place of such molding.
(f) Roof Decks. Roofs shall be without concealed spaces and roof decks shall
be of planks, splined or tongue and groove, of not less than 2-inch thickness, or
IIJs-inch tongue-and-groove plywood with exterior glue, or of a double thickness
of l-inch boards with tongue-and-groove joints, or with staggered joints, of
lumber not less than 3 inches nominal in width, set on edge close together and laid
as required for floors.
(g) Construction Details. Approved wall plate boxes or hangers shall be
provided where wood beams, girders or trusses rest on masonry or concrete walls.
Girders and beams shall be closely fitted around columns, and adjoining ends
shall be cross tied to each other, or intertied by caps or ties, to transfer horizontal
loads across the joints. Wood bolsters may be placed on top of columns which
support roof loads only.
Where intermediate beams are used to support a floor, they shall rest on top of
the girders, or shall be supported by ledgers or blocks securely fastened to the
sides of the girders, or they may be supported by approved metal hangers into
which the ends of the beams shall be closely fitted.
In heavy timber roof construction, every roof girder and at least every alternate
roof beam shall be anchored to its supporting member; roof decks, where
supported by a wall, shall be anchored to such wall at intervals not exceeding 20
feet; every monitor and every sawtooth construction shall be anchored to the main
roof construction. Such anchors shall consist of steel or iron bolts of sufficient
strength to resist vertical uplift of the roof.
(h) Mechanically Laminated Floors and Roof Decks. Mechanically lami-
nated floors and roof decks conforming to Section 2516 (I) may be used as heavy
timber floors or roof decks, provided the minimum thickness and other applicable
requirements of the section are followed.
(i) Partitions. Partitions shall be of solid wood construction formed by not less
than two layers of l-inch matched boards or laminated construction of 4-inch
thickness, or of one-hour fire-resistive construction.
(j) Stairs. Stairs shall be constructed with wood treads and risers of not less
than 2-inch thickness, except where built on laminated or plank inclines as
required for floors, when they may be of l-inch thickness or may be constructed
as required in 'tYpe I buildings. Stair stringers shall be a minimum of 3 inches in
I thickness and not less than 10 inches in depth.
122
1982 EDITION 2201-2204
Chapter22
TYPE V BUILDINGS
Definition
Sec. 2201. 'JYpe V buildings may be of any materials allowed by this code.
'JYpe V One-hour buildings shall be of one-hour fire-resistive construction
throughout.
Materials of construction and ftre-resistive requirements shall be as specified in
Chapter 17.
For requirements due to occupancy, see Chapters 6 to 12 inclusive.
Structural Framework
Sec. 2202. Structural framework shall be of steel or iron as specified in Chapter
27, concrete as in Chapter 26, masonry as in Chapter 24, or wood as in Chapter 25
and this chapter.
Exterior Walls and Openings
Sec. 2203. For ftre protection of exterior walls and openings as determined by
location on property, see Section 504 and Table No. 5-A.
EXCEPTION: Exterior walls of a 'fYpe V nonrated building fronting on streets
or yards having a width of at least 40 feet may be of unprotected construction.
Stair Construction
Sec. 2204. Stair construction may be of any type permitted in this code and
shall conform to the requirements of Chapter 33.
123
2301-2303 UNIFORM BUILDING CODE
PartV
ENGINEERING REGULATIONs-QUALITY
AND DESIGN OF THE MATERIALS OF
CONSTRUCTION
Chapter23
GENERAL DESIGN REQUIREMENTS
Scope
Sec. 2301. This chapter prescribes general design requirements applicable to
all structures regulated by this code.
Definitions
Sec. 2302. The following definitions give the meaning of certain terms used in
this chapter:
DEAD LOAD is the vertical load due to the weight of all permanent structural
and nonstructural components of a building, such as walls, floors, roofs and fixed
service equipment.
LIVE LOAD is the load superimposed by the use and occupancy of the
building not including the wind load, earthquake load or dead load.
LOAD DURATION is the period of continuous application of a given load, or
the aggregate of periods of intermittent application of the same load.
Design Methods
Sec. 2303. (a) General. All buildings and portions thereof shall be designed
and constructed to sustain, within the stress limitations specified in this code, all
dead loads and all other loads specified in this chapter or elsewhere in this code.
Impact loads shall be considered in the design of any structure where impact loads
occur.
EXCEPTION: Unless otherwise required by the building official, buildings or
portions thereof which are constructed in accordance with the conventional framing
requirements specified in Chapter 25 of this code shall be deemed to meet the
requirements of this section.
(b) Rationality. Any system or method of construction to be used shall be
based on a rational analysis in accordance with well-established principles of
mechanics. Such analysis shall result in a system which provides a complete load
path capable of transferring all loads and forces from their point of origin to the
load-resisting elements. The analysis shall include but not be limited to the
following:
1. Distribution of horizontal shear. The total lateral force shall be distributed
to the various vertical elements of the lateral force-resisting system in proportion
to their rigidities considering the rigidity of the horizontal bracing system or
diaphragm. Rigid elements that are assumed not to be part of the lateral force-
124
1982 EDITION 2303-2304
resisting system may be incorporated into buildings, provided that their effect on
the action of the system is considered and provided for in the design.
2. Horizontal torsional moments. Provision shall be made for the increased
forces induced on resisting elements of the structural system resulting from
torsion due to eccentricity between the center of application of the lateral forces
and the center of rigidity of the lateral force-resisting system. Forces shall not be
decreased due to torsional effects. For accidental torsion requirements for seismic
design, see Section 2312 (e) 4.
3. Stability against overturning. Every building or structure shall be designed
to resist the overturning effects caused by the lateral forces specified in this
chapter. See Section 2311 (e) for wind and Section 2312 (f) for seismic.
4. Anchorage. Anchorage of the roof to walls and columns, and of walls and
columns to foundations, shall be provided to resist the uplift and sliding forces
which result from the application of the prescribed forces. For additional require-
ments for masonry or concrete walls, see Section 2310.
(c) Critical Distribution of Live Loads. Where structural members are
arranged so as to create continuity, the loading conditions which would cause
maximum shear and bending moments along the member shall be investigated.
(d) Stress Increases. All allowable stresses and soil-bearing values specified in
this code for working stress design may be increased one-third when considering
wind or earthquake forces either acting alone or when combined with vertical
loads. No increase will be allowed for vertical loads acting alone.
(e) Load Factors. Load factors for ultimate strength design of concrete and
plastic design of steel shall be as indicated in the appropriate chapters on the
materials.
(f) Load Combinations. Every building component shall be provided with
strength adequate to resist the most critical effect resulting from the following
combination of loads (floor live load shall not be included where its inclusion
results in lower stresses in the member under investigation):
I. Dead plus floor live plus roof live (or snow). 1
2. Dead plus floor live plus wind I (or seismic).
3. Dead plus floor live plus wind plus snow/2. 1
4. Dead plus floor live plus snow plus wind/2. 1
5. Dead plus floor live plus snow2 plus seismic.
!Crane hook loads need not be combined with roof live load nor with more than three
fourths of the snow load or one-half wind load.
2Snow loads over 30 psf may be reduced 75 percent upon approval of the building official,
and snow loads 30 psf or less need not be combined with seismic.
Floor Design
Sec. 2304. (a) General. Floors shall be designed for the unit loads set forth in
Table No. 23-A. These loads shall be taken as the minimum live loads in pounds
per square foot of horizontal projection to be used in the design of buildings for
the occupancies listed, and loads at least equal shall be assumed for uses not listed
in this section but which create or accommodate similar loadings.
125
2304-2305 UNIFORM BUILDING CODE
Roof Design
Sec. 2305. (a) General. Roofs shall sustain, within the stress limitations ofthis
code, all "dead loads" plus unit "live loads" as set forth in Table No. 23-C. The
live loads shall be assumed to act vertically upon the area projected upon a
horizontal plane.
(b) Distribution of Loads. Where uniform roof loads are involved in the
design of structural members arranged so as to create continuity, consideration
may be limited to full dead loads on all spans in combination with full live loads
on adjacent spans and on alternate spans.
EXCEPTION: Alternate span loading need not be considered where the uniform
roof live load is 20 pounds per square foot or more and the provisions of Section
.. 2305 (d) are met.
126
1982 EDITION 2305-2306
(c) Unbalanced Loading. Unbalanced loads shall be used where such loading
will result in larger members or connections. Trusses and arches shall be designed
to resist the stresses caused by unit live loads on one half of the span if such
loading results in reverse stresses, or stresses greater in any portion than the
stresses produced by the required unit live load upon the entire span. For roofs
whose structure is composed of a stressed shell, framed or solid, wherein stresses
caused by any point loading are distributed throughout the area of the shell, the
requirements for unbalanced unit live load design may be reduced 50 percent.
(d) Snow Loads. Snow loads full or unbalanced shall be considered in place of
loads set forth in Table No. 23-C, where such loading will result in larger
members or connections.
Potential accumulation of snow at valleys, parapets, roof structures and offsets
in roofs of uneven configuration shall be considered. Where snow loads occur, the
snow loads shall be determined by the building official.
Snow loads in excess of 20 pounds per square foot may be reduced for each
degree of pitch over 20 degrees by R s as determined by the following formula:
R=.J_ _ _!_
s 40 2
WHERE:
R s = Snow load reduction in pounds per square foot per degree of pitch over
20 degrees.
S = Total snow load in pounds per square foot.
(e) Special-purpose Roofs. Roofs to be used for special purposes shall be
designed for appropriate loads as approved by the building official.
Greenhouse roof bars, purlins and rafters shall be designed to carry a 100-
pound-minimum concentrated load in addition to the live load.
(f) Water Accumulation. All roofs shall be designed with sufficient slope or
camber to assure adequate drainage after the long-time deflection from dead load
or shall be designed to support maximum loads including possible ponding of
water due to deflection. See Section 2307 for deflection criteria.
Reduction of Live Loads
Sec. 2306. The design live load determined using the unit live loads as set forth
in Table No. 23-A for floors and Table No. 23-C, Method 2, for roofs may be
reduced on any member supporting more than 150 square feet, including flat
slabs, except for floors in places of public assembly and for live loads greater than
100 pounds per square foot, in accordance with the following formula:
R=r(A-150) .................... (6-1)
The reduction shall not exceed 40 percent for members receiving load from one
level only, 60 percent for other members, nor R as determined by the following
formula:
R = 23.1 (1 + DIL) ................... (6-2)
127
2306-2308 UNIFORM BUILDING CODE
WHERE:
R = Reduction in percent.
r = Rate of reduction equal to .08 percent for floors. See Table No. 23-C for
roofs.
A Area of floor or roof supported by the member.
D = Dead load per square foot of area supported by the member.
L = Unit live load per square foot of area supported by the member.
For storage live loads exceeding l 00 pounds per square foot, no reduction shall
be made, except that design live loads on columns may be reduced 20 percent.
The live load reduction shall not exceed 40 percent in garages for the storage of
private pleasure cars having a capacity of not more than nine passengers per
vehicle.
Deflection
Sec. 2307. The deflection of any structural members shall not exceed the values
set forth in Table No. 23-D, based upon the factors set forth in Table No. 23-E.
The deflection criteria representing the most restrictive condition shall apply.
Deflection criteria for materials not specified shall be developed in a manner
consistent with the provisions of this section. See Section 2305 (f) for camber
requirements. Span tables for light wood frame construction as specified in
Sections 2517 (d) and 2517 (h) 2 shall conform to the design criteria contained
therein, except that where the dead load exceeds 50 percent of the live load, Table
No. 23-D shall govern. (For aluminum, see Section 2803.)
Special Design
Sec. 2308. (a) General. In addition to the design loads specified in this chapter,
the design of all structures shall consider the special loads set forth in Table No.
23-B and in this section.
(b) Retaining Walls. Retaining walls shall be designed to resist the lateral
pressure of the retained material in accordance with accepted engineering prac-
tice. Walls retaining drained earth may be designed for pressure equivalent to that
exerted by a fluid weighing not less than 30 pounds per cubic foot and having a
depth equal to that of the retained earth. Any surcharge shall be in addition to the
equivalent fluid pressure.
(c) Heliport and Helistop Landing Areas. In addition to other design require-
ments of this chapter, heliport and helistop landing or touchdown areas shall be
designed for the maximum stress induced by the following:
l . Dead load plus actual weight of the helicopter.
2. Dead load plus a single concentrated impact load covering l square foot of
0. 75 times the fully loaded weight of the helicopter if it is equipped with
hydraulic-type shock absorbers, or 1.5 times the fully loaded weight of the
helicopter if it is equipped with a rigid or skid-type landing gear.
3. The dead load plus a uniform live load of 100 pounds per square foot. The
required live load may be reduced in accordance with the formula in
Section 2306.
128
1982 EDITION 2309-2311
129
2311 UNIFORM BUILDING CODE
formula:
P = c, cq qJ ....................... (ll-I)
WHERE:
p = Design wind pressure.
C, = Combined height, exposure and gust factor coefficient as given in Table
No. 23-G.
C q = Pressure coefficient for the structure or portion of structure under
consideration as given in Table No. 23-H.
qs = Wind stagnation pressure at the standard height of 30 feet as set forth in
Table No. 23-F.
I = Importance factor as set forth in Section 2311 (h).
(e) Primary Frames and Systems. The primary frames or load-resisting
system of every structure shall be designed for the pressures calculated using
Formula (Il-l) and the pressure coefficients, C , of either Method lor Method 2.
In addition, design of the overall structure anlits primary load-resisting system
shall conform to Section 2303.
The base overturning moment for the entire structure, or for any one of its
individual primary lateral resisting elements, shall not exceed two thirds of the
dead-load-resisting moment. The weight of earth superimposed over footings
may be used to calculate the dead-load-resisting moment.
l. Method 1 (Normal Force Method). Method l shall be used for the design
of gabled rigid frames and may be used for any structure. In the Normal Force
Method, the wind pressures shall be assumed to act simultaneously normal to all
exterior surfaces. For pressures on leeward walls, C, shall be evaluated at the
mean roof height.
2. Method 2 (Projected Area Method). Method 2 may be used for any
structure less than 200 feet in height except those using gabled rigid frames. This
method may be used in stability determinations for any structure less than 200 feet
high. In the Projected Area Method, horizontal pressures shall be assumed to act
upon the full vertical projected area of the structure, and the vertical pressures
shall be assumed to act simultaneously upon the full horizontal projected area.
(f) Elements and Components of Structures. Design wind pressures for each
element or component of a structure shall be determined from Formula ( 11-1) and
C values from Table No. 23-H, and shall be applied perpendicular to the surface.
Fcir outward acting forces the value of C e shall be obtained from Table No. 23-G
based on the mean roof height and applied for the entire height of the structure.
Each element or component shall be designed for the more severe of the following
loadings:
l. The pressures determined using C values for elements and components
acting over the entire tributary area of theqelement.
2. The pressures determined using C values for local areas at discontinuities
such as comers, ridges and eaves. Thes~ local pressures shall be applied over a
distance from a discontinuity of 10 feet or 0.1 times the least width of the
structure, whichever is less.
130
1982 EDITION 2311-2312
The wind pressures from Subsections (e) and (f) need not be combined.
(g) Miscellaneous Structures. Greenhouses, lath houses, agricultural build-
ings or fences 12 feet or Jess in height shall be designed in accordance with
Section 2311. However, three fourths of qs, but not Jess than 10 pounds per square
foot, may be substituted for q, in Formula (11-1). Pressures on local areas at
discontinuities need not be considered.
(h) Importance Factor. A factor of 1.15 shall be used for essential facilities
which must be safe and usable for emergency purposes after a windstorm in order
to preserve the health and safety of the general public. Such facilities shall
include:
I. Hospitals and other medical facilities having surgery or emergency treat-
ment areas.
2. Fire and police stations.
3. Municipal government disaster operation and communication centers
deemed to be vital in emergencies.
4. Buildings where the primary occupancy is for assembly use for more than
300 people.
A factor of 1.0 shall be used for all other buildings.
Earthquake Regulations
Sec. 2312. (a) General. Every building or structure and every portion thereof
shall be designed and constructed to resist stresses produced by lateral forces as
provided in this section. Stresses shall be calculated as the effect of a force applied
horizontally at each floor or roof level above the base. The force shall be assumed
to come from any horizontal direction.
Structural concepts other than set forth in this section may be approved by the
building official when evidence is submitted showing that equivalent ductility and
energy absorption are provided.
Where prescribed wind loads produce higher stresses, such loads shall be used
in lieu of the loads resulting from earthquake forces.
(b) Definitions. The following definitions apply only to the provisions of this
section:
BASE is the level at which the earthquake motions are considered to be
imparted to the structure or the level at which the structure as a dynamic vibrator is
supported.
BOX SYSTEM is a structural system without a complete vertical load-
carrying space frame. In this system the required lateral forces are resisted by
shear walls or braced frames as hereinafter defined.
BRACED FRAME is a truss system or its equivalent which is provided to
resist lateral forces in the frame system and in which the members are subjected
primarily to axial stresses.
DUCTILE MOMENT-RESISTING SPACE FRAME is a moment-resisting
space frame complying with the requirements for a ductile moment-resisting
space frame as given in Section 2312 (j).
131
2312 UNIFORM BUILDING CODE
132
1982 EDITION 2312
The value of K shall be not less than that set forth in Thble No. 23-1. The value
of C and S are as indicated hereafter except that the product of CS need not exceed
0.14.
The value of C shall be determined in accordance with the following formula:
1
c= 1svr ....................... (12-2)
where the values of .f; represent any lateral force distributed approximately in
accordance with the principles of Formulas (12-5), (12-6) and (12-7) or any other
133
2312 UNIFORM BUILDING CODE
rational distribution. The elastic deflections, I>;, shall be calculated using the
applied lateral forces,!; .
In the absence of a determination as indicated above, the value of T for
buildings may be determined by the following formula:
0.05hn
T = VD ....................... (12-3A)
The value of S shall be determined by the following formulas, but shall be not
less than 1. 0:
+ L F; ..................... (12-5)
11
v= F,
i =I
The concentrated force at the top shall be determined according to the following
formula:
F, = 0.077V ........................ (12-6)
134
1982 EDITION 2312
I
of the lateral forces in structures which have highly irregular shapes, large
differences in lateral resistance or stiffness between adjacent stories, or other
unusual structural features, shall be determined considering the dynamic charac-
teristics ofthe structure.
4. Accidental torsion. In addition to the requirements of Section 2303 (b) 2,
where the vertical resisting elements depend on diaphragm action for shear
distribution at any level, the shear-resisting elements shall be capable of resisting
a torsional moment assumed to be equivalent to the story shear acting with an
eccentricity of not less than 5 percent of the maximum building dimension at that
level.
(f) Overturning. At any level the incremental changes of the design overturn-
ing moment, in the story under consideration, shall be distributed to the various
resisting elements in the same proportion as the distribution of the shears in the
resisting system. Where other vertical members are provided which are capable
of partially resisting the overturning moments, a redistribution may be made to
these members if framing members of sufficient strength and stiffness to transmit
the required loads are provided.
Where a vertical resisting element is discontinuous, the overturning moment
carried by the lowest story of that element shall be carried down as loads to the
foundation.
(g) Lateral Force on Elements of Structures and Nonstructural Compo
nents. Parts or portions of structures, nonstructural components and their
anchorage to the main structural system shall be designed for lateral forces in
accordance with the following formula:
The values of CP are set forth in Table No. 23-J. The value of the I coefficient
shall be the value used for the building.
135
2312 UNIFORM BUILDING CODE
136
1982 EDITION 2312
I
Section 2312 (d). Connections shall be designed to develop the full capacity of the
members or shall be based on the above forces without the one-third increase
usually permitted for stresses resulting from earthquake forces.
Braced frames in buildings shall be composed of axially loaded bracing
members of A36, A441, A500 Grades 8 and C, A501, A572 (Grades 42, 45, 50
and 55) or A588 structural steel, or reinforced concrete members conforming to
the requirements of Section 2627.
H. Reinforced concrete shear walls for all buildings shall conform to the
requirements of Section 2627.
I. In structures where K = 0.67 and K = 0.80, the special ductility require-
ments for structural steel or reinforced concrete specified in Section 2312 (j) 1 F,
shall apply to all structural elements below the base which are required to transmit
to the foundation the forces resulting from lateral loads.
2. Design requirements. A. Minor alterations. Minor structural alterations
may be made in existing buildings and other structures, but the resistance to lateral
forces shall be not less than before such alterations were made, unless the building
as altered meets the requirements of this section.
8. Reinforced masonry or concrete. All elements within structures located in
Seismic Zones No. 2, No. 3 and No. 4 which are of masonry or concrete shall be
reinforced so as to qualify as reinforced masonry or concrete under the provisions
of Chapters 24 and 26. Principal reinforcement in masonry shall be spaced 2 feet
maximum on center in buildings using a moment-resisting space frame.
C. Diaphragms. Floor and roof diaphragms and collectors shall be designed to
resist the forces determined in accordance with the following formula:
n
~F, .................. (12-9)
F,.. = ----=-1--=x_ _ w,..
1-x
w,
137
2312 UNIFORM BUILDING CODE
WHERE:
F1 = the lateral force applied to Ievell.
w1 = the portion of W at Ievell.
wpx = the weight of the diaphragm and the elements tributary thereto at
level x, including 25 percent of the floor live load in storage and
warehouse occupancies.
The force Fpx determined from Formula (12-9) need not exceed 0.30Ziwpx.
When the diaphragm is required to transfer lateral forces from the vertical
resisting elements above the diaphragm to other vertical resisting elements below
the diaphragm due to offsets in the placement of the elements or to changes in
stiffness in the vertical elements, these forces shall be added to those determined
from Formula (12-9).
However, in no case shall lateral force on the diaphragm be less than
0.14Z/wpx.
Diaphragms supporting concrete or masonry walls shall have continuous ties
between diaphragm chords to distribute, into the diaphragm, the anchorage forces
specified in this chapter. Added chords may be used to form subdiaphragms to
transmit the anchorage forces to the main cross ties. Diaphragm deformations
shall be considered in the design ofthe supported walls. See Section 2312 (j) 3 A
for special anchorage requirements of wood diaphragms.
3. Special requirements. A. Wood diaphragms providing lateral support
for concrete or masonry walls. Where wood diaphragms are used to laterally
support concrete or masonry walls the anchorage shall conform to Section 2310.
In Zones No.2, No.3 and No.4 anchorage shall not be accomplished by use of
toenails or nails subjected to withdrawal; nor shall wood framing be used in cross-
grain bending or cross-grain tension.
B. Pile caps and caissons. Individual pile caps and caissons of every building
or structure shall be interconnected by ties, each of which can carry by tension and
compression a minimum horizontal force equal to 10 percent of the larger pile cap
or caisson loading, unless it can be demonstrated that equivalent restraint can be
provided by other approved methods.
C. Exterior elements. Precast or prefabricated nonbearing, nonshear wall
panels or similar elements which are attached to or enclose the exterior shall be
designed to resist the forces determined from Formula ( 12-8) and shall accommo-
date movements of the structure resulting from lateral forces or temperature
changes. The concrete panels or other similar elements shall be supported by
means of cast-in-place concrete or mechanical connections and fasteners in
accordance with the following provisions:
Connections and panel joints shall allow for a relative movement between
stories of not less than two times story drift caused by wind or (3.0/K) times the
calculated elastic story displacement caused by required seismic forces, or Y2
inch, whichever is greater. Connections to permit movement in the plane of the
panel for story drift shall be properly designed sliding connections using slotted or
oversized holes or may be connections which permit movement by bending of
steel or other connections providing equivalent sliding and ductility capacity.
138
1982 EDITION 2312
139
23-A UNIFORM BUILDING CODE
residential balconies 1 60 0
4. Exit facilities s 100 os
S. Garages General storage and/ or repair 100 3
140
1982 EDITION 23-A, 238
grounds, plazas, terraces and similar occupancies which are generally accessible to the public.
'Exit facilities shall include such uses as corridors serving an occupant load of I0 or more per-
sons, exterior exit balconies, stairways, fire escapes and similar uses.
6 Residential occupancies include private dwellings, apartments and hotel guest rooms.
7Rest room loads shall be not less than the load for the occupancy with which they are associ-
ated, but need not exceed SO pounds per square foot.
8Individual stair treads shall be designed to support a 30Q-pound concentrated load placed in a
position which would cause maximum stress. Stair stringers may be designed for the uniform
load set forth in the table.
VERTICAL LATERAL
USE LOAD LOAD
(Pounds per S~uara Foot
Category Deacrlptlon Unless Dtherw se Noted)
I. Construction, public Walkway, See Sec. 4406 !50
access at site (live
load) Canopy, See Sec. 4407 150
2. Grandstands, Seats and footboards 1202 See
reviewing stands and Footnote
bleachers (live load) 3
3. Stage accessories, Gridirons and fly
see Sec. 3902 (live galleries 75
load)
Loft block wells4 250 250
Head block wells and
sheave beams 4 250 250
4. Ceiling framing (live Over stages 20
load)
All uses except over
stages J05
5. Partitions and
interior walls, see
Sec. 2309 (live
load) 5
6. Elevators and 2 by Total
dumbwaiters (dead loads
and live load)
7. Mechanical and Total loads
electrical equipment
(dead load)
8. Cranes (dead and live Total load including 1.25 by Total 0.10 by Total
load) 6 impact increase load6 load 7
9. Balcony railings, Exit facilities serving an
guardrails and occupant load greater
handrails than 50 50 8
Other 20 8
I 0. Storage racks Over 8 feet high Total loads9 See Table No.
23-J
(Footnotes onfollowmg page)
141
23-B UNIFORM BUILDING CODE
9 Verticalmembers of storage racks shall be protected from impact forces of operating equipment or racks
shall be designed so that failure of one vertical member will not cause collapse of more than the bay or
bays directly supported by that member.
142
1982 EDITION 23-C
METHOD 1 METHOD 2
TRIBUTARY LOADED AREA IN
SQUARE FEET FOR ANY RATE OF MAXIMUM
STRUCTURAL MEMBER REDUC REDUC
UNIFORM TIONr TION R
ROOF SLOPE Oto 200 201 to600 Over600 LOAD2 (Percent) (Percent)
I. Flat or rise less
than 4 inches
per fool. Arch
or dome with 20 16 12 20 .OR 40
ri~c less than
one eighth of
span
2. Rise 4 inches
per fool to less
than 12 inches
per fool. Arch
or dome with 16 14 12 16 .06 25
rise one eighth
of span to les;
than three
eighths of span
3. Rise 12 inches
per foot and
greater. Arch
or dome with 12 12 12 12
ri~c three
eighths of span
or greater
I Where snow loads occur, the roof structure shall be designed for such
loads as determined by the building official. See Section 2305 (d). For
special purpose roofs, see Section 2305 (e).
2See Section 2306 for live load reductions. The rate of reduction r in Section
2306 Formula (6-1) shall be as indicated in the table. The maximum
reduction R shall not exceed the value indicated in the table.
3As defined in Section 4506.
4 See Section 2305 (e) for concentrated load rec'";rements for greenhouse
roof members.
143
23-D, 23-E, 23-F, 23-G UNIFORM BUILDING CODE
144
1982 EDITION 23-H
STRUCTURE OR
PART THEREOF DESCRIP110N Cq FACTOR
(Continued)
145
23-H UNIFORM BUILDING CODE
STRUCTURE OR
PART THEREOF DESCRIPTION Cq FACTOR
Open-frame
towers' 4 2.0 any direction
Signs, flagpoles,
lightpoles, minor
structures 1.4 any direction
1A structure with more than 30 percent of any one side open shall be considered an open
structure. Nonimpact-resistant glazing shall be considered as an opening.
2Local pressures shall apply over a distance from the discontinuity of 10 feet orO.! times the
least width of the structure, whichever is smaller.
3 The area to which the design pressure shall be applied shall be the projected area of all
elements other than those in planes parallel to the direction of application.
4 For radio and transmission towers, the area shall be the projected area of the members on
one face multiplied by 2.0 for rectangular towers and 1.8 for triangular towers.
146
1982 EDITION 23-1
I
following design criteria:
a. The frames and shear walls or braced frames shall resist the total
lateral force in accordance with their relative rigidities considering the
interaction of the shear walls and frames 0.80
b. The shear walls or braced frames acting independently of the ductile
moment-resisting portions of the space frame shall resist the total
required lateral forces
c. The ductile moment-resisting space frame shall have the capacity to
resist not less than 25 percent of the required lateral force
4. Buildings with a ductile moment-resisting space frame designed in
accordance with the following criteria: The ductile moment-resisting
space frame shall have the capacity to resist the total required 0.67
lateral force
5. Elevated tanks plus full contents, on four or more cross-braced legs and
not supported by a building 2.5 3
6. Structures other than buildings and other than those set forth in Table
No. 23-J 2.00
'Where wind load as specified in Section 2311 would produce higher stresses, this load
shall be used in lieu of the loads resulting from earthquake forces.
2See Figures Nos. I, 2 and 3 in this chapter and definition of Z as specified in Section
2312 (c).
3The minimum value of KC shall be 0.12 and the maximum value of KC need not exceed
0.25.
The tower shall be designed for an accidential torsion of 5 percent as specified in
Section 2312 (e) 4. Elevated tanks which are supported by buildings or do not conform to
type or arrangement of supporting elements as described above shall be designed in
accordance with Section 2312 (g) using CP = . 3.
147
23-J UNIFORM BUILDING CODE
I
5. Suspended ceiling framing systems (applies to Any 0.34 7
Seismic Zones Nos. 2, 3 and 4 only)--see also direction
Section 4701 (e)
6. Connections for prefabricated structural elements Any 0.3 5
other than walls, with force applied at center of direction
gravity of assembly
1CP for elements laterally self-supported only at the ground level may be two thirds of value
shown.
2 W, for storage racks shall be the weight of the racks plus contents. The value ofC, for racks
over two storage support levels in height shall be 0.24 for the levels below the top two
levels. In lieu of the tabulated values steel storage racks may be designed in accordance
with U.B.C. Standard No. 27-11.
Where a number of storage rack units are interconnected so that there are a minimum of
four vertical elements in each direction on each column line designed to resist horizontal
forces, the design coefficients may be as for a building with K values from Table No. 23-1,
CS = 0.2 for use in the formula V = Z!KCSWand Wequal to the total dead load plus 50
percent of the rack-rated capacity. Where the design and rack configurations are in
accordance with this paragraph, the design provisions in U .B.C. Standard No. 27-11 do
not apply.
3 For flexible and flexibly mounted equipment and machinery, the appropriate values of c,
shall be determined with consideration given to both the dynamic properties of the
equipment and machinery and to the building or structure in which it is placed but shall be
not less than the listed values. The design of the equipment and machinery and their
anchorage is an integral part of the design and specification of such equipment and
machinery.
For essential facilities and life safety systems, the design and detailing of equipment
which must remain in place and be functional following a major earthquake shall consider
drifts in accordance with Section 2312 (k).
148
1982 EDITION 23-J, 23-K
"Ceiling weight shall include all light fixtures and other equipment which is laterally
supported by the ceiling. For purposes of determining the lateral force, a ceiling weight of
not less than 4 pounds per square foot shall be used.
5The force shall be resisted by positive anchorage and not by friction.
6 See also Section 2309 (b) for minimum load and deflection criteria for interior partitions.
7Does not apply to ceilings constructed of lath and plaster or gypsum board screw or nail
attached to suspended members that support a ceiling at one level extending from wall to
wall.
I
See Section 2312 (k) for definition and additional requirements for essential facilities.
149
...
lOS
- ,,. ... ...
~
.,...,.. ... ...~
o-
"'Ci)
c:
i:u
m
Cllz
00
s..
{II ...
iS: I
CD en
2.m
-u;
::rs::
CD_
c:o
:IN
::;:0
!.z
enm
-s::
a,.
:,
:.,..
- 0
CD-t
>x
'tim c:
z
"ic:
:::IZ
o.-
SEISMIC RISK MAP OF THE UNITED STATES ~~ 1 o ~ .r~ ~
--1 ZONE 0 No damage. :D
)Cm ,.., ZONE 1 - Minor damage; distant earthquakes may causa 3:
oc damage to structures with fundamental periods ID
::ren grester than 1.0 second; corresponds to c:
-t
"2.>
CD-I
"'m
Intensities V and VI of the M.M.' Scale.
ZONE 2 - Moderete damage; corresponds to Intensity VII of
the M.M.' Scale.
I
-+- -J j \ ----r- ;=
c
z
ZONE 3 - Major damage; corresponds to Intensity VII and
~en higher of the M.M.' Scale.
C)
ZONE 4 - Thosa areas within Zone No. 3 determined by the 0
proximity to certain major fault systems. 0
~
- -
'Modified Mercalll Intensity Scale of 1931
PACIFIC OCAN
FIGURE N0.2
KAUAI
~I HAD
~HU
2
FIGURE N0.3
151
~
...
~ f
"'I
m
c
;
z
!:t
t
Ul
=
n
:
i
en
1 H- '
r.,..j ..s
S'
! c:
lk~~r
z
f 2j
:
~
:a
31:
::r
-=
Ul
0
c .' c:
r=
tf l f
~
"(! l t I
Chapter 24
MASONRY
Scope
Sec. 2401. All masonry shall conform to the regulations of this code.
Definitions
Sec. 2402. For the purpose of this chapter, certain terms are defined as follows:
DIMENSIONS. Dimensions given are nominal; actual dimensions of unit
masonry may not be decreased by more than Y2 inch.
GROSS CROSS-SECTIONAL AREA OF HOLLOW UNITS, the total area
including cells of a section perpendicular to the direction of loading. Re-entrant
spaces are included in the gross area, unless these spaces are to be occupied in
masonry by portions of adjacent units.
GROUT LIFT is an increment of grout height within the total pour; a pour may
consist of one or more lifts.
GROUT POUR is the total height of masonry wall to be poured prior to the
erection of additional masonry. A pour will consist of one or more lifts.
MASONRY CLEANOUT is an aperture at the bottom of cells or walls to be
grouted of such frequency and size as to permit removal of debris or obstructions
from the wall which might prevent proper grouting.
MASONRY UNIT, any brick, tile, stone or block conforming to the require-
ments specified in Section 2403.
NET CROSS-SECTIONAL AREA OF HOLLOW UNITS, the gross cross-
sectional area of a section minus the average area of ungrouted cores of cellular
spaces.
VIRTUAL ECCENTRICITY, the eccentricity of a resultant axial load
required to produce axial and bending stresses equivalent to those produced by
applied axial loads and moments.
Materials
Sec. 2403. (a) General. The quality, testing and design of masonry used
structurally in buildings or structures shall conform to the requirements specified
in this chapter and to the applicable standards listed in Chapter 60.
(b) Brick Made from Clay or Shale. Building brick of clay or shale shall be
of a quality at least equal to the requirements set forth in U.B.C. Standard
No. 24-1. When in contact with the ground, brick shall be of at least Grade MW.
Where severe frost action occurs in the presence of moisture, brick shall be at least
Grade SW.
(c) Brick Made from Sand-lime. Building brick made from sand-lime shall
be of a quality at least equal to the requirements set forth in U.B.C. Standard
No. 24-2. When in contact with the ground, brick shall be of at least Grade MW.
Where severe frost action occurs in the presence of moisture, brick shall be at least
Grade SW.
(d) Concrete Brick. Building brick of concrete shall be of a quality at least
153
2403 UNIFORM BUILDING CODE
154
1982 EDITION 2403
the total volume. Plastic or waterproofed cements so manufactured shall meet the
requirements for portland cement as set forth in U.B.C. Standard No. 26-1 except
in respect to the limitations on insoluble residue, air-entrainment and additions
subsequent to calcination.
(p) Lime. Quicklime shall conform to U.8.C Standard No. 24-17. Hydrated
lime shall conform to the requirements of U.8.C. Standard No. 24-18. Lime
putty shall be made from quicklime or hydrated lime.
If made from other than processed pulverized quicklime, the lime shall be
slaked and then screened through a No. 16 mesh sieve. After slaking, screening,
and before using, it shall be stored and protected for not Jess than 10 days. The
resulting lime putty shall weigh not Jess than 83 pounds per cubic foot.
Processed pulverized quicklime conforming to U.8.C. Standard No. 24-19
shall be slaked for not Jess than 48 hours and shall be cool when used.
(q) Mortar. I. General. Mortar used in masonry construction shall be classi- I
tied in accordance with (a) the materials and proportions set forth in Table
No. 24-A, or (b) the properties as established by laboratory tests as set forth in
U.8.C. Standard No. 24-20. Tests made to classify mortar by compressive
strength shall be as set forth in U. 8. C. Standard No. 24-20, using the proportions
and materials proposed for use. Aggregates for mortar shall conform to the
provisions set forth in U.8.C. Standard No. 24-21.
2. Admixtures. Admixtures shall not be added to the mortar unless approved
by the building official.
Only pure mineral oxide colors shall be used for color.
3. Strength. The strength of mortar using cementitious materials set forth in
Table No. 24-A shall meet the minimum compressive strength shown in U.8.C.
Standard No. 24-20. The building official may require field tests to verify
compliance with this section. Such tests shall be made in accordance with U. 8. C.
Standard No. 24-22.
(r) Grout. l. General. Grout shall be proportioned by volume and shall have
sufficient water added to produce consistency for pouring without segregation.
Aggregate shall conform to the requirements set forth in U. 8. C. Standard
No. 24-23.
2. TYpe. Fine grout shall be composed of one part portland cement, to which
may be added not more than one-tenth part hydrated lime or lime putty, and two
and one-fourth to three parts sand.
Coarse grout shall be composed of one part portland cement to which may be
added not more than one-tenth part hydrated lime or lime putty, and two to three
parts sand, and not more than two parts gravel.
EXCEPTION: "JYpe M or S mortar may be used for grout in fireplaces and their
chimneys.
Coarse grout may be used in grout spaces in brick masonry 2 inches or more in
horizontal dimension and in grout spaces in filled-cell construction 4 inches or
more in both horizontal dimensions.
3. Strength. Grout shall attain a minimum compressive strength of 2000
pounds per square inch at 28 days. The building official may require a compres-
155
2403-2404 UNIFORM BUILDING CODE
sive field strength test of grout made in accordance with U .B.C. Standard
No. 24-22.
4. Aluminum equipment. Grout shall not be handled nor pumped utilizing
aluminum equipment unless it can be demonstrated with the materials and
equipment to be used that there will be no deleterious effect on the strength of the
grout.
(s) Mortar Limitations. Masonry units used in foundation walls and footings
shall be laid up in 'iype S or 'iype M mortar. 'iype 0 mortar may be used only in
interior nonstructural walls. See Sections 2412 (b), 2414 (a) and 2418 (a).
(t) Aggregates. Aggregates for mortar shall be of a quality at least equal to that
set forth in U.B.C. Standard No. 24-21.
(u) Rate of Absorption. At the time of laying, burned clay units and sand-
lime units shall have a rate of absorption not exceeding 0.025 ounce per square
inch during a period of one minute. In the absorption test the surface of the unit
shall be held Vs inch below the surface of the water.
(v) Reuse of Masonry Units. Masonry units may be reused when clean,
whole and conforming to the other requirements of this section, except that the
allowable working stresses shall be 50 percent of that permitted for new masonry
units. Such units may not be used under the provisions of Section 2418 (c) 2 B.
Tests
Sec. 2404. (a) General. Tests of materials shall be made in accordance with
the standard method prescribed for the material in question.
(b) Load Tests. When a load test is required, the member or portion of the
structure under consideration shall be subject to a superimposed load equal to
twice the design live load plus one half of the dead load. This load shall be left in
position for a period of 24 hours before removal. If, during the test or upon
removal of the load, the member or portion of the structure shows evidence of
failure, such changes or modifications as are necessary to make the structure
adequate for the rated capacity shall be made; or where lawful, a lower rating shall
be established. A flexural member shall be considered to have passed the test if the
maximum deflection D at the end of the 24-hour period neither exceeds
L L2
D= -norD=
200 - - . . . .. . . .. . . . . .. . . . . (41)
4000t -
and the beams and slabs show a recovery of at least 75 percent of the observed
deflection within 24 hours after removal of the load.
WHERE:
L = span of the member in feet.
t = thickness or depth of the member in feet.
(c) Determination of Masonry Design Strength. 1. General. The value of
f' shall be determined by tests of masonry assemblies in accordance with the
pr';;visions of paragraph 2 of this subsection or shall be assumed in accordance
156
1982 EDITION 2404
WHERE:
H = height of specimen, in inches.
d = minimum dimension of specimen, in inches.
Intermediate values may be interpolated.
C. Storage of test prisms. Test prisms shall be stored for seven days in air at a
temperature of 70 degrees, plus or minus 5 degrees, in a relative humidity
exceeding 90 percent, and then in air at a temperature of70 degrees, plus or minus
5 degrees, at a relative humidity of 30 percent to 50 percent until tested. Those
constructed in the field shall be stored undisturbed for from 48 to 96 hours under
wet material to simulate 90 percent humidity, then transported to laboratory for
continued curing as above. Prisms shall be capped and tested in compression
similar to tests for molded concrete cylinders as specified in U.B.C. Standard
No. 26-13.
D. Sampling. Not less than five specimens shall be made for each initial
preliminary test to establishf'm Not less than three shall be made for each field
157
2404-2405 UNIFORM BUILDING CODE
test to confirm that the materials are as assumed in the design. The standard age of
test specimens shall be 28 days, but seven-day tests may be used, provided the
relation between the seven-day and 28-day strengths of the masonry is established
by adequate test data for the materials used.
3. Assumed ultimate compressive strength. When prism tests are not made
as in paragraph 2./'m may be assumed as:
Solid Clay Units-14,000 psi gr:Jss ....................... f'm = 5300
Solid Clay Units-10,000 psi gross ....................... f'm = 4000
Solid Clay Units--6000 psi gross ........................ I'm = 2600
Solid Units-3000 psi gross ............................. f'm = 1800
Solid Units-2500 psi gross ............................. f'm = 1500
Solid Load-bearing Concrete Masonry Units-
Grade N ........................................... f'm = 1080
Hollow Concrete Units-Grade N ......................... f'm = 1350
Hollow Concrete Units-Grade N
grouted solid ....................................... f'm = 1500
Concrete Building Brick-Grade N
(3500 psi units) ..................................... I'm = 2100
Hollow Clay Units-Grade LB
(llf4-inch minimum face shell) ......................... I'm = 1350
Hollow Clay Units-Grade LB
(llf4-inch minimum face shell) grouted ................... f'm = 1500
Hollow Clay Units-T)'pe I
5000 psi net ........................................ f'm = 2500
I (grout used shall equal or exceed 1.33/'m)
For solid units, intermediate values may be interpolated.
Compressive tests of solid clay units shall be conducted in accordance with
U.B.C. Standard No. 24-24.
Where the assumedf'm exceeds 2600 pounds per square inch, field tests in
accordance with Section 2404 (c) 2 shall be required.
158
1982 EDITION 2405-2407
(d) Stresses. All masonry of unburned clay units shall be so constructed that
the unit stresses do not exceed those set forth in Table No. 24-B. Bolt values shall
not exceed those set forth in Table No. 24-C.
Reinforced Gypsum Concrete
Sec. 2406. (a) General. Reinforced gypsum concrete shall conform to
..I
U.B.C. Standard No. 24-12.
Reinforced gypsum concrete shall develop the minimum ultimate compressive
strength in pounds per square inch set forth in Table No. 24-D when dried to
constant weight, with tests made on cylinders 2 inches in diameter and 4 inches
long or on 2-inch cubes.
Tests, when required, shall follow the procedure set forth in U.B.C. Standard
No. 47-17.
For special inspection, see Section 306.
(b) Design. The minimum thickness of reinforced gypsum concrete shall be 2
inches except the thickness may be reduced to l Y2 inches, provided all of the
following conditions are satisfied:
1. The overall thickness including the formboard is not less than 2 inches.
2. The clear span of the gypsum concrete between supports does not exceed 2
feet 9 inches.
3. Diaphragm action is not required.
4. The design live load does not exceed 40 pounds per square foot.
(c) Stresses. The maximum allowable unit working stresses in reinforced
gypsum concrete shall not exceed the values set forth in Table No. 24-E except as
specified in Chapter 23. Bolt values shall not exceed those set forth in Table No.
24-F.
Allowable shear in poured-in-place reinforced gypsum concrete diaphragms
using standard hot-rolled bulb tee subpurlins shall be determined by U .B.C.
Standard No. 24-12. (See Table No. 24-12-A in the standard for values for
commonly used roof systems.)
Glass Masonry
Sec. 2407. (a) General. Masonry of glass blocks may be used in nonload-
bearing exterior or interior walls and in openings which might otherwise be filled
with windows, either isolated or in continuous bands, provided the glass block
panels have a minimum thickness of 3 inches at the mortar joint and the mortared
surfaces of the blocks are treated for mortar bonding.
(b) Horizontal Forces. The panels shall be restrained laterally to resist the
horizontal forces specified in Chapter 23 for bearing walls.
(c) Size of Panels. Glass block panels for exterior walls shall not exceed 144
square feet of unsupported wall surface nor 15 feet in any dimension. For interior
walls, glass block panels shall not exceed 250 square feet of unsupported area nor
25 feet in any dimension.
(d) Mortar. Glass block shall be laid in TYpe S mortar. Both vertical and
horizontal mortar joints shall be at least Y4 inch and not more than % inch thick
and shall be completely filled.
159
24072409 UNIFORM BUILDING CODE
(e) Expansion Joints. Every exterior glass block panel shall be provided with
Y2-inch expansion joints at the sides and top. Expansion joints shall be entirely
free of mortar and shall be filled with resilient material.
Stone Masonry
Sec. 2408. (a) General. Stone masonry is that form of construction made
with natural or cast stone in which the units are laid and set in mortar, with all
joints thoroughly filled.
(b) Construction. In ashlar masonry, bond stones uniformly distributed shall
be provided to the extent of not less than 10 percent of the area of exposed facets.
Rubble stone masonry 24 inches or less in thickness shall have bond stones with
a maximum spacing of3 feet vertically and 3 feet horizontally and, if the masonry
is of greater thickness than 24 inches, shall have one bond stone for each 6 square
feet of wall surface on both sides.
(c) Minimum Thickness. Stone masonry walls shall in no case have a mini-
mum thickness of less than 16 inches.
(d) Stresses. The allowable unit working stresses in stone masonry shall not
exceed the values set forth in Table No. 24-B. Bolt values shall not exceed those
set forth in Table No. 24-G.
160
1982 EDITION 2409-2411
Solid Masonry
Sec. 2411. (a) General. Solid masonry shall be brick, concrete brick or solid
load-bearing concrete masonry units laid contiguously in mortar.
All units shall be laid with full shoved mortar joints, and all head, bed and wall
joints shall be solidly filled with mortar.
(b) Construction. In each wythe of bearing and nonbearing walls, except
masonry veneer, not less than 75 percent of the units in any transverse vertical
plane shall lap the ends of the units above and below a distance not less than 1 Y2
inches or one half the height of the units, whichever is greater, or the masonry
shall be reinforced longitudinally as required in Section 2416 (I) for masonry laid
in stack bond. Adjacent wythes in bearing and nonbearing walls shall be bonded
by either of the following methods:
1. Headers. The facing and backing shall be bonded so that not less than 4
percent of the exposed face area is composed of solid headers extending not less
than 4 inches into the backing. The distance between adjacent full-length headers
shall not exceed 24 inches vertically or horizontally. Where the backing consists
of two or more wythes the headers shall extend not less than 4 inches into the most
distant wythe, or the backing wythes shall be bonded together with separate
headers whose area and spacing conform to the foregoing.
161
2411-2412 UNIFORM BUILDING CODE
2. Metal ties. The facing and backing shall be bonded with corrosion-resistant
unit metal ties or cross wires of approved joint reinforcement conforming to the
requirements of Section 2409 (b) for cavity walls. Unit ties shall be of sufficient
length to engage all wythes, with ends embedded not less than l inch in mortar, or
shall consist of two lengths, the inner embedded ends of which are hooked and
lapped not less than 2 inches.
Where the space between metal tied wythes is solidly filled with mortar the
allowable stresses and other provisions for masonry bonded walls shall apply.
Where the space is not filled, metal tied walls shall conform to the allowable
stress, lateral support, thickness (excluding cavity), height, and mortar require-
ments for cavity walls.
(c) Moisture Content. For moisture content, see Section 2403 (u).
(d) Stresses. All solid masonry shall be so constructed that the unit stresses do
not exceed those set forth in Table No. 24-B. Bolt values shall not exceed those set
forth in Table No. 24-G.
Grouted Masonry
Sec. 2412. (a) General. Grouted masonry is that form of construction made
with brick or solid concrete brick units in which interior joints of masonry are
filled by pouring grout therein as the work progresses.
(b) Materials. At the time of laying, all masonry units shall be free of
excessive dust and dirt. For moisture content, see Section 2403 (u). Only TYpe M
or TYpe S mortar consisting of a mixture of portland cement, hydrated lime and
aggregate shall be used.
(c) Low-lift Grouted Construction. Requirements for construction shall be as
follows:
I . All units in the two outer tiers shall be laid with full-shoved head and bed
mortar joints. Masonry headers shall not project into the grout space.
2. All longitudinal vertical joints shall be grouted and shall be not less than%
inch in thickness. In members of three or more tiers in thickness, interior bricks
shall be embedded into the grout so that at least % inch of grout surrounds the
sides and ends of each unit. All grout shall be puddled with a grout stick
immediately after pouring.
3. One exterior tier may be carried up 18 inches before grouting, but the other
exterior tier shall be laid up and grouted in lifts not to exceed six times the width of
the grout space with a maximum of 8 inches.
4. If the work is stopped for one hour or longer, the horizontal construction
joints shall be formed by stopping all tiers at the same elevation and with the grout
l inch below the top.
(d) High-lift Grouted Construction. Requirements for construction shall be
as follows:
I. All units in the two tiers shall be laid with full head and bed mortar joints.
2. The two tiers shall be bonded together with wall ties. Ties shall be not less
than No. 9 wire in the form of rectangles 4 inches wide and 2 inches in length less
than the overall wall thickness. Kinks, water drips or deformations shall not be
162
1982 EDITION 24122414
permitted in the ties. One tier of the wall shall be built up not more than 16 inches
ahead of the other tier. Ties shall be laid not to exceed 24 inches on center
horizontally and 16 inches on center vertically for running bond and not more than
24 inches on center horizontally and 12 inches on center vertically for stack bond.
3. Cleanouts shall be provided for each pour by leaving out every other unit in
the bottom tier of the section being poured, or by cleanout openings in the
foundation. During the work, mortar fins and any other foreign matter shall be
removed from the grout space. The cleanouts shall be sealed after inspection and
before grouting.
4. The grout space (longitudinal vertical joint) shall be not less than 3 inches in
width and not less than the thickness required by the placement of steel with the
required clearances and shall be poured solidly with grout. Masonry walls shall
cure at least three days to gain strength before pouring grout.
EXCEPTION: If the grout space contains no horizontal steel, it may be reduced
to 2 inches.
5. Vertical grout barriers or dams shall be built of solid masonry across the
grout space the entire height of the wall to control the flow of the grout horizon-
tally. Grout barriers shall be not more than 30 feet apart.
6. Grout shall be a plastic mix suitable for pumping without segregation ofthe
constituents and shall be mixed thoroughly. Grout shall be placed by pumping or
by an approved alternate method and shall be placed before any initial set occurs
and in no case more than one and one-half hours after water has been added.
7. Grouting shall be done in a continuous pour, in lifts not exceeding 6 feet. It
shall be consolidated by puddling or mechanical vibrating during placing and
reconsolidated after excess moisture has been absorbed but before plasticity is
lost. The grouting of any section of a wall between control barriers shall be
completed in one day with no interruptions greater than one hour.
8. Special inspection during grouting shall be provided in accordance with
Section 306; however, the work shall not qualify for the stresses entitled "Special
Inspection" in Table No. 24-H unless fully inspected.
(e) Stresses. All grouted masonry shall be so constructed that the unit stresses
do not exceed those set forth in Table No. 24-B. Bolt values shall not exceed those
set forth in Table No. 24-G.
Reinforced Grouted Masonry
Sec. 2413. (a) General. Reinforced grouted masonry shall conform to all of
the requirements for grouted masonry specified in Section 2412 and also the
requirements of this section.
(b) Construction. The thickness of grout or mortar between masonry units and
reinforcement shall be not Jess than lf4 inch, except that lf4-inch bars may be laid in
horizontal mortar joints at least lf2 inch thick and steel wire reinforcement may be
laid in horizontal mortar joints at least twice the thickness of the wire diameter.
(c) Stresses. See Section 2417 (a).
Reinforced Hollow Unit Masonry
Sec. 2414. (a) General. Reinforced hollow unit masonry is that type of
163
2414 UNIFORM BUILDING CODE
construction made with hollow masonry units in which certain cells are continu-
ously filled with concrete or grout and in which reinforcement is embedded.
Requirements for construction shall be as follows:
1. All units shall be laid with full mortar beds on the face shells. All head joints
shall be filled solidly with mortar for a distance in from the face of the unit not less
than the thickness of the longitudinal face shells.
2. Only JYpe M or JYpe S mortar consisting of portland cement, lime and
aggregate shall be used.
3. End walls and cross webs forming cells to be filled shall be full bedded in
mortar to prevent leakage of grout unless the wall is to be poured solid.
4. Bond shall be provided by lapping units in successive vertical courses or by
equivalent mechanical anchorage.
5. Vertical cells to be filled shall have vertical alignment sufficient to maintain
a clear, unobstructed continuous vertical cell measuring not less than 2 inches by 3
inches. If walls are battered or if alignment is offset, the 2-inch by 3-inch clear
opening shall be maintained as measured from course to course. Excessive mortar
fins and any other obstructions shall be removed from the cells to be grouted.
6. At the time of laying, all masonry units shall be free of excessive dust and
dirt.
7. All cells containing reinforcement shall be filled solidly with grout. Grout
shall be a workable mix suitable for pumping without segregation and shall be
thoroughly mixed. Grout shall be placed by pumping or an approved alternate
method and shall be placed before initial set or hardening occurs. Grout shall be
consolidated by puddling or mechanical vibration during placing and reconsoli-
dated after excess moisture has been absorbed but before workability is lost. The
grouting of any section of a wall shall be completed in one day with no interrup-
tions greater than one hour.
8. Where the grout pour exceeds 4 feet in height, cleanouts shall be provided by
suitable openings in the face shells in the bottom course of each cell to be grouted,
or other approved locations. The cleanouts shall be sealed after inspection and
before grouting.
9. When the grouting is stopped for one hour or longer, horizontal construction
joints shall be formed by stopping the pour of grout approximately Y2 inch above
or below a bed joint.
10. All reinforcing shall be in place prior to grouting. Vertical reinforcing bars
shall be held in position at the top, bottom and at intervals not farther apart than
192 bar diameters.
(c) High-lift Grouted Construction. Units may be laid to the full height ofthe
wall and grouts shall be placed in 4-foot (maximum) lifts, and special inspection
shall be provided during grouting. Special inspection at time of grouting shall not
qualify the work for the stresses entitled "Special Inspection" in Table No. 24-H
unless fully inspected.
164
1982 EDITION 2415
165
2416 UNIFORM BUILDING CODE
General Design
Sec. 2416. (a) General. Masonry shall be designed to withstand all vertical
and horizontal loads as specified in Chapter 23, and with due allowance for the
effect of eccentric loads.
(b) Combination of Units. In walls or other structural members composed of
different kinds or grades of units, materials or mortars, the maximum stress in any
portion shall not exceed the allowable stress permitted for the material of that
portion. The net thickness of any facing unit which is used to resist stress shall be
not less than 1Y2 inches.
(c) Thickness of Walls. For thickness limitations of walls as specified in this
chapter, nominal thickness shall be used. Stresses shall be determined on the basis
of the net thickness of the masonry, with consideration for reduction such as raked
joints.
The thickness of masonry walls shall be designed so that allowable maximum
stresses specified in this chapter are not exceeded and so that all masonry walls
shall not exceed the height- or length-to-thickness ratio nor the minimum thick-
ness as specified in this chapter and as set forth in Table No. 24-1.
EXCEPTION: The height- or length-to-thickness ratio may be increased and the
minimum thickness may be decreased when data are submitted which justify a
reduction in the requirements specified in this section.
(d) Piers. Every structural pier whose width is less than three times its
thickness shall be designed and constructed as required for columns.
(e) Chases and Recesses. Chases and recesses in masonry walls shall be
designed and constructed so as not to reduce the required strength or required fire
resistance of the wall.
I
(f) Pipes and Conduits Embedded in Masonry. Pipe or conduit shall not be
embedded in any masonry so as to reduce the capacity to less than that necessary
for required stability or required fire protection.
EXCEPTIONS: I. Rigid electric conduits may be embedded in structural
masonry when their location has been detailed on the approved plan.
2. Any pipe or conduit may pass vertically or horizontally through any masonry
by means of a sleeve at least large enough to pass any hub or coupling on the pipe
line. Such sleeves shall be placed not closer than three diameters, center to center,
nor shall they unduly impair the strength of construction.
3. Placement of pipes or conduits in unfilled cores of hollow unit masonry shall
not be considered as embedment.
(g) Arches and Lintels. Members supporting masonry shall be of noncombus-
tible materials.
(h) Anchorage. Masonry walls that meet or intersect shall be bonded or
anchored as required in Section 2310.
Structural members framing into or supported by walls or columns shall be
anchored.
(i) End Support. Beams, girders or other concentrated loads supported by a
wall or pier shall have bearing at least 3 inches in length upon solid masonry not
less than 4 inches thick or upon a metal bearing plate of adequate design and
166
1982 EDITION 2416-2417
dimensions to distribute the loads safely on the wall or pier, or upon a continuous
reinforced masonry member projecting not less than 3 inches from the face of the
wall, or by other approved methods.
Joists shall have bearing at least 3 inches in length upon solid masonry at least
2 Y4 inches thick; or other provisions shall be made to distribute safely the loads on
the wall or pier.
(j) Distribution of Concentrated Loads. In calculating wall stresses, concen-
trated loads may be distributed over a maximum length of wall not exceeding the
center-to-center distance between loads.
Where the concentrated loads are not distributed through a structural element,
the length of wall considered shall not exceed the width of the bearing plus four
times the wall thickness.
Concentrated loads shall not be considered as distributed by metal ties nor
distributed across continuous vertical joints.
(k) Bolt Values. The allowable loads on bolts shall not exceed the values set
forth in Table No. 24-G.
(I) Stack Bond. In unreinforced masonry where masonry units are laid in stack
bond, longitudinal reinforcement consisting of not less than two continuous wires
each with a minimum aggregate cross-sectional area of .017 square inch shall be
provided in horizontal bed joints spaced not more than 16 inches on center
vertically.
(m) Bed Joints. The initial bed joint thickness shall be not less than V4 inch nor
more than 1 inch; subsequent bed joints shall be not less than V4 inch nor more
than Sfs inch in thickness. See Section 3707 (c) for firebrick.
POUNDS PER
TENSILE STRESS: SQUARE INCH
For deformed bars with a yield strength of 60,000 pounds per square
inch or more and in sizes No. 11 and smaller .................. . 24,000
Joint reinforcement, 50 percent of the minimum yield point specified in
U.B.C. Standards for the particular kind and grade of steel used, but in
no case to exceed ........................................ . 30,000
For all other reinforcement ................................. . 20,000
167
2417 UNIFORM BUILDING CODE
168
1982 EDITION 2417
load, live load and other forces as determined by the principle of continuity and
relative rigidity.
2. Distance between lateral supports. The clear distance between lateral
supports of a beam shall not exceed 32 times the least width of the compression
flange or face.
(f) Width in Flexural Computation. In computing flexural stresses for
masonry where reinforcement occurs, the effective width b shall be not greater
I
than six times the wall thickness in running bond nor more than three times the
wall thickness in stacked bond.
(g) Combined Axial and Flexural Stresses. Members subject to combined
axial and flexural stresses shall be designed in accordance with accepted princi-
ples of mechanics or in accordance with the following formula:
Ffa + Ffb hi
s a I not exceed l
a b
WHERE:
fa Computed axial unit stress, determined from total axial load and effec-
tive area.
Fa Axial unit stress permitted by this code at the point under consideration,
if member were carrying axial load only, including any increase in
stress allowed by this section.
fb = Computed flexural unit stress.
F b = Flexural unit stress permitted by this code if member were carrying
bending load only, including any increase in stress allowed by this
section.
(h) Shear and Diagonal Thnsion. l. Shearing unit stress. The shearing unit
stress v in reinforced masonry flexural members shall be computed by
v=
v
bjd ......................... (18-l)
WHERE:
b = The width of a rectangular section or the width of the web in I or T
sections.
Where the values of the shearing unit stress computed by Formula ( 18-l)
exceeds the shearing unit stress vm permitted on masonry, web reinforcement shall
be provided to carry the entire stress.
2. Types of web reinforcement. Web reinforcement may consist of:
A. Stirrups or web reinforcement bars perpendicular to the longitudinal steel,
or
B. Stirrups or web reinforcement bars welded or otherwise rigidly attached to
the longitudinal steel and making an angle of 30 degrees or more thereto, or
C. Longitudinal bars bent so that the axis of the inclined portion of the bar
169
2417 UNIFORM BUILDING CODE
Vs
Av = fvid ......... , .......... (18-2)
A
v
= -vSin
f. , . .................... (18-3)
v 01
Av = --:----,;....::._
Vs ____ ................. (18-4)
fvjd (sin 01 + cos 01)
u= "i.ojd
v
...................... (18-5)
in which V is the shear at that section and Lo is taken as the perimeter of all
170
1982 EDITION 2417
effective bars crossing the section on the tension side. To be effective the bars
must be properly developed by hooks, lap or embedment on each side of the
section. Bent-up bars that are not more than d/3 from the level of the main
longitudinal reinforcement may be included. Critical sections occur at the face of
the support, at each point where tension bars terminate within a span and at the
point of inflection.
Bond shall be similarly computed on compressive reinforcement, but the shear
used in computing the bond shall be reduced in the ratio of the compressive force
assumed in the bars to the total compressive force at the section. Anchorage shall
be provided by embedment past the section to develop the assumed compressive
force in the bars at the bond stress in Table No. 24-H.
2. Anchorage requirements. Tensile negative reinforcement in any span of a
continuous, restrained or cantilever beam, or in any member of a rigid frame shall
be adequately anchored by bond, hooks or mechanical anchors in or through the
supporting member. Within any such span every reinforcing bar except in a
lapped splice whether required for positive or negative moment shall be extended
at least 12 diameters beyond the point at which it is no longer needed to resist
stress.
No flexural bar shall be terminated in a tension zone unless one of the following
conditions is satisfied:
A. The shear is not over one half that normally permitted, including allowance
for shear reinforcement, if any.
B. Additional stirrups in excess of those required are provided each way from
the cutoff, a distance equal to the depth of the beam. The stirrup spacing
shall not exceed d/8rb where rb is the ratio of the area of bars cut off to the
total area of bars at the section.
C. The continuing bars provide double the area required for flexure at that
point or double the perimeter required for flexural bond.
At least one third of the total reinforcement provided for negative moment at
the support shall be extended beyond the extreme position of the point of
inflection a distance sufficient to develop by bond one half the allowable stress in
such bars, not Jess than one sixteenth of the clear span length or not less than the
depth of the member, whichever is greater. The maximum tension in any bar must
be developed by bond on a sufficient straight or bent embedment or by other
anchorage.
The bar may be bent across the web at an angle of not less than 15 degrees with
the longitudinal portion of the bar and be made continuous with the reinforcement
which resists moment of opposite sign.
Of the positive reinforcement in continuous beams not less than one fourth the
area shall extend along the same face of the beam into the end support a distance
of6 inches.
In simple beams, or at the freely supported end of continuous beams, at least
one third the required positive reinforcement shall extend along the same face of
the beam into the support a distance of 6 inches.
Compression steel in beams and girders shall be anchored by ties or stirrups not
171
2417 UNIFORM BUILDING CODE
less than Y4 inch in diameter, spaced not farther apart than 16 bar diameters or 48
tie diameters. Such ties or stirrups shall be used throughout the distance where
compression steel is required.
3. Plain bars in tension. Plain bars in tension shall terminate in standard
hooks except that hooks shall not be required on the positive reinforcement at
interior supports of continuous members.
4. Anchorage of web reinforcement. Single separate bars used as web rein-
forcement shall be anchored at each end by one of the following methods:
A. Welding to longitudinal reinforcement.
B. Hooking tightly around the longitudinal reinforcement through at least 180
degrees.
C. Embedment above or below the mid-depth of the beam on the compression
side, a distance sufficient to develop the stress to which the bar will be
subject at a bond stress of not to exceed the bond stresses permitted in Table
No. 24-H.
D. By a standard hook, considered as developing 7500 pounds per square
inch, plus embedment sufficient to develop by bond the remaining stress in
the bar at the unit stress set forth in Table No. 24-H. The effective
embedded length shall not be assumed to exceed the distance between the
mid-depth of the beam and the tangent of the hook.
The extreme ends of bars forming a simple U-stirrup or multiple U-stirrups
shall be anchored by one of the methods of this subsection or shall be bent through
an angle of at least 90 degrees tightly around a longitudinal reinforcing bar not less
in diameter than the stirrup bar, and shall project beyond the bend at least 12
diameters of the stirrup bar.
The loops or closed ends of such stirrups shall be anchored by bending around
the longitudinal reinforcement through an angle of at least 90 degrees or by being
welded or otherwise rigidly attached thereto.
Between the anchored ends, each bend in the continuous portion of aU- or
multiple U-stirrup shall be made around a longitudinal bar. Hooking or bending
stirrups around the longitudinal reinforcement shall be considered effective only
when these bars are perpendicular to the longitudinal reinforcement.
Longitudinal bars bent to act as web reinforcement shall, in a region of tension,
be continuous with the longitudinal reinforcement. The tensile stress in each bar
shall be fully developed in both the upper and the lower half of the beam by
adequate anchorage through bond or hooks.
5. Hooks. The term "hook" or "standard hook" as used herein shall mean
either:
A. A complete semicircular tum with a radius of bend on the axis ofthe bar of
not less than three and not more than six bar diameters, plus an extension of
at least four bar diameters at the free end of the bar.
B. A 90-degree bend having a radius of not less than four bar diameters plus an
extension of 12 bar diameters.
C. For stirrup anchorage only, a 135-degree tum with a radius on the axis of
the bar of three diameters, plus an extension of at least six bar diameters at
172
1982 EDITION 2417
WHERE:
Compressive unit axial stress in masonry wall.
Ultimate compressive masonry stress as determined by Section
2404 (c). The value of f'm shall not exceed 6000 pounds per square
inch.
t = Thickness of wall in inches.
h = Clear unsupported distance in inches between supporting or enclosing
members (vertical or horizontal stiffening elements).
3. Reinforcement. All walls using stresses permitted for reinforced masonry
shall be reinforced with both vertical and horizontal reinforcement. The sum of
the areas of horizontal and vertical reinforcement shall be at least 0.002 times the
gross cross-sectional area of the wall, and the minimum area of reinforcement in
either direction shall be not less than 0.0007 times the gross cross-sectional area
of the wall. The reinforcement shall be limited to a maximum spacing of 4 feet on
center. The minimum diameter of reinforcement shall be 3fs inch except that joint
173
2417 UNIFORM BUILDING CODE
WHERE:
P = Maximum concentric column axial load.
A 8 = The gross area of the column.
I'm = Ultimate compressive masonry strength as determined by Section
2404 (c). The value of f'm shall not exceed 6000 pounds per square
inch.
p8 Ratio of the effective cross-sectional area of vertical reinforcement
to A 8
f. = Allowable stress in reinforcement [See Section 2417 (b)].
t = Least thickness of columns in inches.
h = Clear height in inches.
174
1982 EDITION 24172418
Bearing Walls
Sec. 2418. (a) Partially Reinforced Masonry. Partially reinforced masonry
shall be designed as unreinforced masonry, except that reinforced areas or
elements may be considered as resisting stresses in accordance with the design
criteria specified in Section 2417, provided such elements fully comply with the
175
2418 UNIFORM BUILDING CODE
176
1982 EDITION 2418
177
2418 UNIFORM BUILDING CODE
Ratio of height to thickness (hit) 2.0 2.5 3.0 3.5 4.0 4.5 5.0
Correction factor 1 0.82 0.85 0.88 0.91 0.94 0.98 1.00
1Interpolate to obtain intermediate values.
In no case, however, shall a value off'min excess of 6000 pounds per square inch
be used in the design.
Method No. 2 - Brick Tests. When the compressive strength of the brick
masonry is not determined by prism tests and the units, mortar and workmanship
conform to all applicable requirements of this subsection, the allowable stresses
may be based upon an assumed value off'm interpolated from the values in Table
No. 24-J. Compressive strength tests of brick shall be conducted in accordance
with U.B.C. Standard No. 24-24.
4. AUowable stresses. Except as provided elsewhere in this code, the allow-
able stresses in unreinforced brick masonry shall not exceed the values set forth in
Table No. 24-K.
5. Design. A. Notations. The following notations are used forthe engineered
design of unreinforced brick masonry:
A8 = Gross cross-sectional area.
c. Eccentricity coefficient.
C, Slenderness coefficient.
e = Virtual eccentricity [see Section 2418 (c) 5 G].
e1 Smaller virtual eccentricity at lateral supports (at either top or bottom of
member).
e2 Larger virtual eccentricity at lateral supports (at either top or bottom of
member).
fm Allowable compressive or bearing stress in masonry.
f'm Compressive strength of masonry at 28 days, unless otherwise
specified.
!, = Allowable flexural tensile stress in masonry.
h = Effective height [see Section 2418 (c) 5 D and E].
P = Allowable vertical load.
r = Radius of gyration.
t = Effective thickness [see Section 2418 (c) 5 F].
~ ~ 10 ( 3- :: ) ................... (19-1)
178
1982 EDITION 2418
NOTE: Value of e11e2 is positive where member is bent in single curvature, and
negative where member is bent in double or reverse curvature. Where e 1 and e 2 are
both equal to zero, e 11e 2 shall be assumed to be zero.
The slenderness ratio of a column shall be the greater value obtained by
dividing the effective height h in any direction by the effective thickness t in the
corresponding direction and shall not exceed the value computed by
Where walls or columns meet all other requirements of this code, limits on
slenderness ratios may be waived when approved after a review of a written
justification.
C. Slenderness coefficient. The slenderness coefficient C s shall be computed
by the following formula:
For cavity walls loaded on one wythe only, the effective thickness shall be taken
as the actual thickness of the loaded wythe.
For rectangular columns, the effective thickness shall be taken as its actual
thickness in the direction considered.
For nonrectangular columns, the effective thickness shall be taken as equal to
3.464 times its radius of gyration r about the axis considered.
Where raked mortar joints are used, the thickness of the member shall be
reduced in accordance with the depth of the raking.
G. Eccentricity normal to plane of member. In calculating the virtual
eccentricity of loads on walls or columns, consideration shall be given to the
effects of lateral load, eccentricity of vertical load, and the deflection, thermal
and other movements of members.
(i) Bending in one direction. In solid walls and columns, the eccentricity of
the load shall be considered with respect to the centroidal axis of the member.
In cavity walls loaded on one wythe, the eccentricity shall be considered with
respect to the centroidal axis of the loaded wythe.
In cavity walls loaded on both wythes, the load shall be distributed to each
wythe according to the eccentricity of the load about the centroidal axis of the
wall.
For members composed of different kinds or grades of units or mortar, the
variation in the moduli of elasticity shall be taken into account and the eccentricity
shall be considered with respect to the center of resistance or the centroidal axis of
the transformed area of the member.
(ii) Eccentricity coefficient. Where the maximum virtual eccentricity e is
equal to or less than t/20, the eccentricity coefficient C e shall be taken as 1. 0.
Where the maximum virtual eccentricity e exceeds t/20 but is equal to or less
than t/6, C, shall be computed by the following formula:
c -
-
_1._3_
1 +6~
+ _!_
2
k -_!_XI
\1 20
- e,)
e, ........... (19-4)
Where the maximum virtual eccentricity e exceeds t/6 but is equal to or less
than t/3, C, shall be computed by the following formula:
For members subject to transverse loads greater than 10 pounds per square foot
between lateral supports, c.
shall be based on Formula (19-6) or (19-5), which-
ever is applicable, except e/e 2 shall be taken as + 1.0.
(iii) Bending about both principal axes. Where walls and columns are sub-
ject to bending about both principal axes and e 1 b + ebt is equal to or less than
bt/20, the eccentricity coefficient C, shall be taken as 1.0 where e, = virtual
180
1982 EDITION 2418
eccentricity about the principal axis which is normal to the thickness t of the
member and eb = virtual eccentricity about the principal axis which is normal to
the width b of the member.
Where e1b + ebt exceeds bt/20 but is equal to or less than bt/6, the eccentricity
coefficient C. shall be computed by Formula(l9-6), except that e1 b + ebtlbt shall
be substituted for e/t.
Where e,b + ebt exceeds bt/6 but does not exceed bt/3, C, shall be computed
by Formula (19-5), except that e,b + ebt shall be substituted for eft.
H. Cross-sectional area. For solid walls and columns, A$ shall be taken as the
actual gross cross-sectional area of the member. For metal-tied walls, A shall be
determined as for cavity walls unless the collar joints in such walls are fiiled with
mortar or grout.
For cavity walls loaded on one wythe, A 8 shall be taken as the actual gross
cross-sectional area of the loaded wythe.
For cavity walls loaded on both wythes, A~ shall be taken as the actual gross
cross-sectional area of the wythe under consioeration.
Where raked mortar joints are used, the thickness used in determining A 8 shall
be reduced accordingly.
I. Allowable vertical loads on unreinforced walls and columns. Allowable
vertical loads P on unreinforced walls and columns shall be computed as follows:
Where the maximum virtual eccentricity e does not exceed t/3,
P = C, CJmA 8 . . . . . . . . . . (19-6)
WHERE:
Ce = eccentricity coefficient.
C, = slenderness coefficient.
fm = allowable axial compressive stress.
A8 = gross cross-sectional area.
NOfE: The value of C, C, fm is the average allowable compressive stress
permitted in the member. Accordingly, this value should not be taken as the
maximum compressive stress permitted in the extreme fiber.
Where the maximum virtual eccentricity e exceeds t/3, the maximum tensile
stress in the masonry, assuming linear stress distribution, shall not exceed the
values given in Table No. 24-K. Where these values are exceeded, the member
shall be designed in accordance with the requirements of Section 2417.
Allowable vertical loads on rectangular unreinforced walls and columns sub-
ject to bending about both principal axes shall be computed as follows:
Where e,b + ebt does not exceed bt/3, the allowable vertical load shall be
computed in accordance with the above formula, except that the eccentricity
coefficient C, shall be determined in accordance with Section 2418 (c) 5 G.
Where e,b + ebt exceeds bt/3, walls and columns shall be reinforced and
designed in accordance with Section 2417.
J. Concentrated loads. The bearing stress under beams, lintels and girders
181
2418 UNIFORM BUILDING CODE
and from similar concentrated loads supported on unreinforced masonry shall not
exceed the values set forth in Table No. 24-K.
K. Shear walls. (i) Eccentricity. In unreinforced shear walls, the virtual
eccentricity e1 about the principal axis which is normal to the length l of the shear
wall shall not exceed an amount which will produce tension. In unreinforced shear
walls subject to bending about both principal axes, e,l + e1t shall not exceed tl/3
where e, = virtual eccentricity about the principal axis which is normal to the
thickness t of the shear wall. Where the virtual eccentricity exceeds the values
given in this section, shear walls shall be designed in accordance with Section
2417 or 2418 (a).
(ii) Allowable vertical loads. Allowable vertical loads on unreinforced shear
walls shall be determined in accordance with Section 2418 (c) 5 I, except that the
value of h used in determining C5 shall be taken as the minimum vertical or
horizontal distance between lateral supports.
(iii) Allowable shear stress. The allowable shear stresses in unreinforced shear
walls shall be taken as the allowable stresses given in Table No. 24-K, plus one
fifth of the average compressive stress due to dead load at the level being
analyzed. In no case, however, shall the allowable shear stresses exceed the
maximum values given in Table No. 24-K.
(iv) Intersecting waDs. Where shear walls intersect a wall or walls to form
symmetrical Tor I sections, the effective flange width shall not exceed one sixth
of the total wall height above the level being analyzed, and its overhanging width
on either side of the shear wall shall not exceed six times the actual thickness of the
intersected wall. Where shear walls intersect a wall or walls to form L or C
sections, the effective overhanging flange width shall not exceed one sixteenth of
the total wall height above the level being analyzed nor six times the actual
thickness of the intersected wall. Limits on effective flange width may be waived
when approved after a review of a written justification.
In computing the shear resistance of the wall, only the web shall be considered.
L. Anchorage of diaphragms. Anchorage of diaphragms to walls shall be in
accordance with Section 2310 and shall be sufficient to transmit all forces.
6. Construction. A. General. In addition to the construction requirements of
Sections 2409 (b), 2411 (b) and (c) and 2415, unreinforced brick masonry
designed in accordance with Section 2418 (c) shall also comply with the require-
ments of this subsection.
8. Mortar joints. All brick shall be laid with full head and bed joints and all
interior joints that are designed to receive mortar shall be filled. The average
thickness of head and bed joints shall not exceed V2 inch.
C. Bonding unreinforced load-bearing walls and shear walls. Where two
unreinforced load-bearing walls meet or intersect, or where shear walls intersect a
wall [see Section 2418 (c) 5 K], the intersections shall be bonded by laying in a
true bond at least 50 percent of the units at the intersection, or the intersecting
walls shall be regularly toothed or blocked with 8-inch maximum offsets and the
joints provided with metal anchors having a minimum section of 1/4 inch by 1112
inches with ends bent up at least 2 inches, or with cross pins to form anchorage.
182
1982 EDITION 24182419, 24A
Such anchors shall be at least 2 feet long and the maximum spacing shall be 4 feet.
Nonbearlng Walls
Sec. 2419. (a) General. Nonbearing walls may be constructed of any masonry
as specified in this chapter. Reinforced masonry nonbearing walls shall be
reinforced as specified in Section 2417 U) 3.
(b) Thickness. Every nonbearing masonry wall shall be so constructed and
have a sufficient thickness to withstand all vertical loads and horizontal loads,
where specifically required by Chapter 23, but in no case shall the thickness of
such walls (including plaster when applied) be less than the values set forth in
Table No. 24-1.
(c) Anchorage. All nonbearing partitions shall be anchored along the top edge
to a structural member or a suspended ceiling, or shall be provided with equiv-
alent anchorage along the sides.
PARTS BY
PARTS BY VOLUME OF AGGREGATE
MORTAR VOLUME OF PARTS BY VOLUME HYDRATED MEASURED IN A
TYPE PORTLAND OF MASONRY LIME OR DAMP, LOOSE
p~l
CEMENT CEMENT CONDITION
M
I I -
I - ~ Not less than 2 ~
s !lz 1
over~
- to !1:! and not more
than 3 times the
1 - sum of the
-1 1 - volumes of the
N
- over !1:! to 1 ~ cements and lime
used
0 - 1 -
1 - over 1 ~to 2!/z
1When plastic or waterproof cement is used as specified in Section 2403 (o), hydrated lime
or putty may be added but not in excess of one tenth the volume of cement.
183
24B UNIFORM BUILDING CODE
.. 7. Stone masonry
Cast stone
Natural stone
8. Unburned clay
masonry
400
140
30
360
120
30
8
8
8
4
4
4
-
-
-
-
-
-
320
100
- -
8
8
-
4
4
1 Allowable axial or flexural compressive stresses in pounds per square inch gross cross-
sectional area (except as noted). The allowable working stresses in bearing directly under
concentrated loads may be 50 percent greater than these values.
2This value of tension is based on tension across a bed joint, i.e., vertically in the normal
masonry work.
3No tension allowed in stack bond across head joints.
4The values shown here are for tension in masonry in the direction of running bond, i.e.,
horizontally between supports.
SNet area in contact with mortar or net cross-sectional area.
184
1982 EDITION 24-C, 24-D, 24-E
*% 1.'5
18
300
400
1 21 500
1% 24 600
COMPRESSIVE MODULUS OF
STRENGTH ELASTICITY Es/EI MODULUS OF
CLASS PSI (fu) PSI (E) (n) RIGIDITY (G)
CLASS A CLASS B
TYPE OF STRESS FACTOR (Pounds per Sq. Inch)
185
24-F,24-G UNIFORM BUILDING CODE
% Bolt 4 325
% Bolt 5 450
% Bolt 5 650
% Deformed Dowel 6 325
% Deformed Dowel 6 450
The bolts or dowels shall be spaced not closer than 6 inches on center.
2The tabulated values may be increased one third for bolts or dowels resisting
wind or seismic forces.
% 4 .'350 550
% 4 500 750
5 750 1100
*% 6 1000 1500
1850 2
1 7 1250
1% 8 1500 2250 2
I Anadditional 2 inches of embedment shall be provided for anchor bolts located
in the top of columns for buildings located in Seismic Zones Nos. 2, 3 and 4.
2Permitted only with not less than 2500 pounds per square inch units.
186
1982 EDITION 24-H
187
24-1,24-J UNIFORM BUILDING CODE
MAXIMUM
RATIO
UNSUPPORTED NOMINAL
HEIGHT OR MINIMUM
LENGTH TO THICKNESS
TYPE OF MASONRY THICKNESS (lnchea)
BEARING WALLS:
I. Unburned Clay Masonry 10 16
2. Stone Masonry 14 16
3. Cavity Wall Masonry 18 8
4. Hollow Unit Masonry 18 8
5. Solid Masonry 20 8
6. Grouted Masonry 20 6
7. Reinforced Grouted Masonry 25 6
8. Reinforced Hollow Unit Masonry 25 41
NON BEARING WALLS:
9. Exterior Unreinforced Walls 20 2
10. Exterior Reinforced Walls 30 2
II. Interior Partitions Unreinforced 36 2
12. Interior Partitions Reinforced 48 2
1Nominal 4-inch-thick load-bearing reinforced hollow clay unit masonry walls
with a maximum unsupported height or length to thickness of 27 may be
permitted, provided net area unit strength exceeds 8000 psi, units are laid in
running bond, bar sizes do not exceed Vz inch with no more than two bars or one
splice in a cell, and joints are flush cut, concave or a protruding V section.
Minimum bar coverage where exposed to weather may be I Vz inches.
188
1982 EDITION 24-K
189
25012502 UNIFORM BUILDING CODE
Chapter 25
WOOD
General
Sec. 2501. (a) Quality and Design. The quality and design of wood members
and their fastenings shall conform to the provisions of this chapter and to the
applicable standards listed in Chapter 60.
(b) Workmanship. All members shall be framed, anchored, tied and braced
so as to develop the strength and rigidity necessary for the purposes for which they
are used.
(c) Fabrication. Preparation, fabrication and installation of wood members
and their fastenings shall conform to accepted engineering practices and to the
requirements ofthis code.
(d) Rejection. The building official may deny permission for the use of a wood
member where permissible grade characteristics or defects are present in such a
combination that they affect the serviceability of the member.
(e) Minimum Quality. Minimum capacity of structural framing members may
be established by performance tests. When tests are not made, capacity shall be
based upon allowable stresses and design criteria specified in this code.
Studs, joists, rafters, foundation plates or sills, planking 2 inches or more in
depth, beams, stringers, posts, structural sheathing and similar load-bearing
members shall be of at least the minimum grades set forth in Table No. 25-A-1 or
No. 25-A-2. Approved end-jointed lumber may be used interchangeably with
solid-sawn members of the same species and grade. Such use shall include, but
not be limited to, light framing joists, planks and decking.
Plywood shall be of species Group I, 2, 3 or 4 and shall be one of the grades
specified in U.B.C. Standard No. 25-9.
I Particleboard shall conform to U .B.C. Standard No. 25-25.
Approved fire-retardant treated wood shall be dried, following treatment, to a
maximum moisture content as follows: solid-sawn lumber 2 inches in thickness or
less to 19 percent, and plywood to 15 percent.
(f) Shrinkage. Consideration shall be given in the design to the possible effect
of cross-grain dimensional changes considered vertically which may occur in
lumber fabricated in a green condition.
Definitions and Symbols
Sec. 2502. (a) Definitions. The following terms used in this chapter shall have
the meanings indicated in this section:
FIBERBOARD is a fibrous-felted, homogeneous panel made from lig-
nocellulosic fibers (usually wood or cane) and having a density of less than 31
pounds per cubic foot but more than 10 pounds per cubic foot, conforming to
U.B.C. Standard No. 25-24.
GLUED BUILT-UP MEMBERS are structural elements, the sections of
which are composed of built-up lumber, plywood or plywood in combination with
lumber, all parts bonded together with adhesives.
190
1982 EDITION 2502
I
utility i.n accordance with the grading rules of an approved lumber grading
agency.
HARDBOARD is a fibrous-felted, homogeneous panel made from ligno-
cellulosic fibers consolidated under heat and pressure in a hot press to a density
not less than 31 pounds percubicfoot conforming to U .B.C. Standard No. 25-26.
NOMINAL SIZE (Lumber), the commercial size designation of width and
depth, in standard sawn lumber and glued-laminated lumber grades; somewhat
larger than the standard net size of dressed lumber, in accordance with U. B.C.
Standard No. 25-1 for sawn lumber and U .B.C. Standard No. 25-10 for structural
glued-laminated timber.
NORMAL WADING, a design load that stresses a member or fastening to the
I
full allowable stress tabulated in this chapter. This loading may be applied for
approximately 10 years, either continuously or cumulatively, and 90 percent of
this load may be applied for the remainder of the life of the member or fastening.
PARTICLEBOARD is a mat-formed panel consisting of particles of wood or
combinations of wood particles and wood fibers bonded together with synthetic
resins or other suitable bonding system by a bonding process in accordance with
U.B.C. Standard No. 25-25.
PLYWOOD, a built-up panel of laminated veneers conforming to U.B.C.
Standard No. 25-9.
STRUCTURAL GLUED-LAMINATED TIMBER, any member compris-
ing an assembly of laminations of lumber in which the grain of all laminations is
approximately parallel longitudinally, in which the laminations are bonded with
adhesives, and which is fabricated in accordance with U .B.C. Standards No.
25-10 and No. 25-ll.
TREATED WOOD, wood treated with an approved preservative under the
treating and quality control requirements specified in U.B.C. Standard No.
25-12.
WOOD OF NATURAL RESISTANCE TO DECAY, the heartwood of bald
cypress, black locust, black walnut, the cedars and redwood.
(b) Symbols. The symbols used in this chapter have the following definitions:
A = area of cross section.
b breadth (width) of rectangular member.
C = coefficient, constant or factor.
Cc = curvature factor.
C F = size effect factor.
C1 = form factor.
Cs = slenderness factor.
c = distance from neutral axis to extreme fiber.
D = diameter.
d = depth of rectangular member, or least dimension of compression
member.
191
2502 UNIFORM BUILDING CODE
E = modulus of elasticity.
e = eccentricity.
F b = allowable unit stress for extreme fiber in bending.
F'b = allowable unit stress for extreme fiber in bending, adjusted for
slenderness.
fb = actual unit stress for extreme fiber in bending.
Fe = allowable unit stress in compression parallel to grain.
F'c = allowable unit stress in compression parallel to grain adjusted for lid
ratio where dis the least dimension.
fc = actual unit stress in compression parallel to grain.
Fc.l... = allowable unit stress in compression perpendicular to grain.
fc.l... = actual unit stress in compression perpendicular to grain.
F n = allowable unit stress acting perpendicular to the inclined surface psi
(Hankinson's Formula).
Fr = allowable unit radial stress.
fr = actual unit radial stress.
Frc = allowable unit radial stress in compression.
frc = actual unit radial stress in compression.
Frr = allowable unit radial stress in tension.
frr = actual unit radial stress in tension.
F, = allowable unit stress in tension parallel to grain.
f, = actual unit stress in tension parallel to grain.
Fv = allowable unit horizontal shear stress.
fv = actual unit horizontal shear stress.
h = rise.
I = moment of inertia.
L = span length of beam, or unsupported length of column, feet.
l = span length of beam, or unsupported length of column, inch.
12 distance from center of connector in end blocks to center of spacer
block.
M bending moment.
m unit bending moment.
N = acting perpendicular to the inclined surface "lb" (Hankinson's Formu-
la).
P = total concentrated load, or axial compression load.
PIA = induced axial load per unit of cross-sectional area.
Q = statical moment of an area about the neutral axis.
R = radius of curvature.
RH = horizontal reaction.
Rv = vertical reaction.
192
1982 EDITION 2502-2504
r = radius of gyration.
S = section modulus.
T = total axial tension load.
t = thickness.
V = total vertical shear.
W = total uniform load.
w = uniform load per unit of length .
.:lA = allowable deformation or deflection .
.:la = actual deformation or deflection.
(} = angle between the direction of load and the direction of grain, degrees
(Hankinson's Formula).
Size of Structural Members
Sec. 2503. Sizes of lumber and structural glued-laminated timber referred to in
this code are nominal sizes. Computations to determine the required sizes of
members shall be based on the net dimensions (actual sizes) and not the nominal
sizes.
Stresses
Sec. 2504. (a) General. Except as hereinafter provided, stresses shall not
exceed the allowable unit stresses for the respective species and grades or
fabricated products as set forth in Tables No. 25-A-1 and No. 25-A-2 for lumber,
and Tables No. 25-C and No. 25-D for structural glued-laminated timber.
The values for Fb and Fe tabulated in Table No. 25-A-1 for visually stress-rated
lumber and in Table No. 25-A-2 for machine stress-rated lumber are for the design
of structures when the strength of an individual member is premised on the
assumption that each individual piece carries its design load.
The repetitive member design values for F b tabulated in Table No. 25-A-1 and
Table No. 25-A-2 may be used for the design of an assembly of repetitive framing
such as joists, rafters and studs not over 4 inches in thickness spaced not more than
24 inches, not less than three in number and joined by transverse load-distributing
elements adequate to support the design load.
Values for species and grades not tabulated shall be approved by the building
official.
Values for plywood shall be in accordance with Table No. 25-B. All plywood
when designed to be exposed in outdoor applications shall be ofthe exterior type,
except as provided in Sections 2516 (i) and 2517 (h) 7. I
(b) Wood Poles or Piles. The values tabulated in Table No. 25-E shall be used
for the design of round timber poles and piles.
Poles and piles shall conform to the requirements set forth in U. B. C. Standards
No. 25-13 and No. 25-14.
(c) Adjustment of Stresses. 1. General. The allowable unit stresses specified
in this chapter shall be subject to the adjustments set forth in the footnotes to the
appropriate stress tables and to the requirements of this subsection.
193
2504 UNIFORM BUILDING CODE
CF = (12/d)l/9
WHERE:
CF = size factor.
d = depth of beam in inches.
For beams of circular cross section that have a diameter greater than 13.5
inches, or 12-inch or larger square beams loaded in the plane of the diagonal, the
size factor CF may be determined on the basis of an equivalent conventionally
loaded square beam of the same cross-sectional area.
Size factor adjustments are cumulative with form factor adjustments specified
in Section 2504 (c) 7, except for lumber I beams and box beams, but are not
194
1982 EDITION 2504
cs = f!?-
in which
Cs = slenderness factor.
le = effective length of beam, inches, from the following table.
d = depth of beam, inches.
b = breadth of beam, inches.
VALUE OF
EFFECTIVE
TYPE OF BEAM SPAN ANO NATURE OF LOAD LENGTH,/0
Single-span beam, load concentrated at center 1.61/u
Single-span beam, uniformly distributed load 1.92/u
Single-span beam, equal end moments 1.84/u
Cantilever beam, load concentrated at unsupported end 1.69/u
Cantilever beam, uniformly distributed load 1.06/u
Single-span or cantilever beam, any other load 1.92/u
lu = unsupported length of beam, inches.
When the slenderness factor C5 does not exceed 10, the full allowable unit
stress in bending F b may be used.
When the slenderness factor Cs is greater than lO but does not exceed Ck, the
allowable unit stress in bending F' b shall be determined from the following
formula:
in which
ck = V3Et5Fb
E = modulus of elasticity.
When the slenderness factor Cs is greater than Ck but less than 50, the allowable
unit stress in bending F' b shall be determined by the following formula:
F' b
196
1982 EDITION 2504-2506
The average modulus of elasticity E values listed in the tables shall be multi-
plied by I - Cv or 1 - 1.65 Cv to obtain a modulus of elasticity E value exceeded
by 84 percent or 95 percent individual pieces, respectively.
The duration-of-load adjustments specified in Item No. 4 do not apply to
modulus of elasticity values.
9. Temperature. The allowable unit stresses specified in this chapter and as
modified in this section apply to uses within the range of climatic temperature
ordinarily encountered in buildings. When manufacturing or equipment pro-
cesses subject members to prolonged temperatures above this range, but not
exceeding l50F., the allowable design stresses shall be decreased by the appro-
priate reduction factors specified in U. B.C. Standard No. 25-27. Wood members
shall not be used in areas subject to temperatures above 150F. unless the exposure
is infrequent and any permanent loss in strength is accounted for in the design.
Identification
Sec. 2505. All lumber, plywood, particleboard, structural glued-laminated
timber, end-jointed lumber, fiberboard sheathing (when used structurally),
hardboard siding (when used structurally), piles and poles regulated by this I
I
chapter shall conform to the applicable standards or grading rules specified in this
code and shall be so identified by the grade mark or a Certificate of Inspection
issued by an approved agency.
All lumber, timber, plywood and poles required to be Treated Wood under
Section 2516 (c) shall be identified by the quality mark of an approved inspection
agency which maintains continued supervision, testing and inspection over the
quality of the product as specified in U .B.C. Standard No. 25-12.
197
2506 UNIFORM BUILDING CODE
trated load from a critically loaded beam to adjacent parallel beams shall be
calculated.
(c) Horizontal Shear. The maximum horizontal shear stress in a solid-sawn or
glued-laminated wood beam shall not exceed that calculated by means of the
formula:
The actual unit shear stressfv shall not exceed the allowable for the species and
grade as given in Table No. 25-A for solid-sawn lumber and in Tables No. 25-C
and No. 25-D for glued-laminated lumber, adjusted for duration of loading, as
provided in Section 2504 (c) 4.
When calculating the total vertical shear V, distribution of load to adjacent
parallel beams by flooring or other members may be considered and all loads
within a distance from either support equal to the depth of the beam may be
neglected.
(d) Horizontal Shear in Notched Beams. Where girders, beams or joists are
notched at points of support, they shall meet design requirements for net section in
bending and in shear. The shear at such point shall not exceed the value calculated
by the following formula:
WHERE:
d' = actual depth of beam at the notch.
d = total depth of beam.
198
1982 EDITION 2506
lb + .375
lb
in which lb is the length of bearing in inches measured along the grain of the
wood.
The multiplying factors for indicated lengths of bearing on such small areas as
plates and washers may be:
LENGTH OF
BEARING &OR
(In lnchea) 1,.2 1 11-2 2 3 4 MORE
Factor 1.75 1.38 1.25 1.19 1.13 1.10 1.00
In using the preceding formula and table for round washers or bearing areas,
use a length equal to the diameter.
In joists supported on a ribbon or ledger board and spiked to the studding, the
allowable stress in compression perpendicular to grain may be increased 50
percent.
(g) Lateral Support. Solid-sawn rectangular lumber beams, rafters and joists
shall be supported laterally to prevent rotation or lateral displacement in accor-
dance with the following:
If the ratio of depth to thickness, based on nominal dimensions, is:
1. 1\vo to 1, no lateral support is required.
2. Three to 1 or 4 to 1, the ends shall be held in position, as by full-depth solid
blocking, bridging, nailing or bolting to other framing members, approved
hangers or other acceptable means.
3. Five to 1, one edge shall be held in line for its entire length.
4. Six to 1, bridging, full-depth solid blocking or cross bracing shall be
installed at intervals not exceeding 8 feet unless both edges are held in line.
5. Seven to I, both edges shall be held in line for their entire length.
If a beam is subject to both flexure and compression parallel to grain, the ratio
may be as much as 5 to I if one edge is held firmly in line. If the dead load is
I
sufficient to induce tension on the underside of the rafters, the ratio for the beam
may be 6to 1.
In lieu of providing lateral support by the methods specified in Items Nos. 2
through 5 above, the allowable stresses shall be reduced by the slenderness factor
set forth in Section 2504 (c) 6.
(h) Lateral Deflection - Arches and Thp Chords of Trusses. Where roof
joists, not purlins, are used between arches or the top chords of trusses, the depth,
rather than the breadth, of the arch or top chord member (compression member)
may be taken as its least dimension in determining the IId. The roof joists shall be
placed so that their upper edges are at least Yz inch above the tops of the arch or
chord but also placed low enough to provide adequate lateral support.
When roof joists or planks are placed on top of an arch or top chord of a truss
199
2508-2507 UNIFORM BUILDING CODE
and are well spiked or otherwise securely fastened to the arch or top chord and to
blocking placed between the joists, or when sheathing is nailed properly to the top
chord of trussed rafters, the depth of the arch or individual chord members may be
used as the least dimension din determining lid.
Column Design
Sec. 2507. (a) Column Classifications. l. Simple solid wood columns.
Simple columns consist of a single piece or of pieces properly glued together to
form a single member.
2. Spaced columns, connector joined. Spaced columns are formed of two or
more individual members with their longitudinal axes parallel, separated at the
ends and middle points of their length by blocking and joined at the ends by timber
connectors capable of developing the required shear resistance. See U. B.C.
Standard No. 25-15 for design.
3. Built-up columns. Built-up columns, other than connector-joined spaced
columns and glued-laminated columns, shall not be designed as solid columns.
(b) Limitation on lid Ratios. For simple solid columns, lid shall not exceed
50.
For individual members of a spaced column, lid shall not exceed 80, nor shall
12 /d exceed 40.
(c) Simple Solid-column Design. These formulas for simple solid columns are
based on pin-end conditions but may be applied also to square-end conditions.
The effective length of the column for design purposes shall be increased where
column-end conditions provide less stability than pin-end conditions and may be
reduced where column-end conditions provide greater stability.
Allowable unit stresses in pounds per square inch of cross-sectional area of
square or rectangular simple solid columns shall be determined by the following
formulas, but such unit stresses shall not exceed values for compression, parallel
to grain Fein Tables Nos. 25-A, 25-C, 25-D and 25-E adjusted in accordance with
provisions of Section 2504.
K = 0.671 Vf. c
200
1982EDmON 25072508
Where machine stress-unit lumber is used as provided for in Table No. 25-A-2,
stresses may be determined in accordance with the following formula:
Intermediate columns:
K = 0.792 \~iii;
Long columns:
F' = 0.418
c (l/d)2
WhereO~J~ 1
(c) Spaced Columns. In the case of spaced columns, this combined stress
I
formula may be applied only if the bending is in a direction parallel to the greater d
of the individual member.
(d) Truss Compression Chords. Effects of buckling of a 2 by 4 or smaller
truss compression chord having effective buckling lengths of 96 inches or less and
with %-inch or thicker plywood sheathing nailed to the narrow face of the chord in
201
2508-2509 UNIFORM BUILDING CODE
accordance with Table No. 25-P shall be determined from the formula:
Cr = I + 0.002 le
WHERE:
Cr = buckling stiffness factor.
t. = effective buckling length used in design of chord for compression
loading.
The values of Cr determined from this formula are for wood seasoned to a
moisture content of 19 percent or less at the time the plywood is nailed to the
chord. For wood that is unseasoned or partially seasoned at the time of plywood
attachment, Cr shall be determined from the formula:
Cr = I + 0.0011.
For chords with an effective buckling length greater than 96 inches, Crshall be
taken as the value for a chord having an effective length of 96 inches.
The buckling stiffness factor does not apply to short columns or to trusses used
under wet conditions. The allowable unit compressive stress shall be modified by
the buckling stiffness factor when a truss chord is subjected to combined flexure
and compression and the bending moment is in the direction that induces com-
pression stresses in the chord face to which the plywood is attached.
The buckling stiffness factor Cr shall be applied as follows:
Short columns (lid of II or less):
202
1982 EDITION 2510
203
2510.2511 UNIFORM BUILDING CODE
For wood-to-wood joints, the spacing center to center of nails in the direction of
stress shall be not less than the required penetration. Edge or end distances in the
direction of stress shall be not less than one half of the required penetration. All
spacing and edge and end distances shall be such as to avoid splitting of the wood.
Holes for nails, where necessary to prevent splitting, shall be bored of a
diameter smaller than that of the nails.
(g) Joist Hangers and Framing Anchors. Connections depending upon
joist hangers or framing anchors, ties, and other mechanical fastenings not
otherwise covered may be used where approved.
(h) Metal Plate Connectors. The material and workmanship during fabrica-
tion and the design of metal plate connectors employed as joint connectors for
light wood trusses shall conform with the requirements of U.B.C. Standard No.
25-17.
Each truss manufacturer shall retain an approved agency having no financial
interest in the plant being inspected to make nonscheduled inspections of truss
fabrication and delivery and operations. The inspection shall cover all phases of
truss operation, including lumber storage, handling, cutting, fixtures, presses or
rollers, fabrication, bundling and banding, handling and delivery.
204
1982 EDITION 2511
in which
t = thickness of lamination in inches.
R = radius of curvature of inside face of lamination in inches, and t/R shall
not exceed Ywo for hardwoods and southern pine, or Ym for other
softwoods.
No curvature factor shall be applied to stress in the straight portion of an assembly,
regardless of curvature elsewhere.
4. Radial tension or compression. The maximum radial stress induced in a
curved member of constant rectangular cross section by a bending moment is:
3M
!, = 2Rbd
WHERE:
f, = radial stress in pounds per square inch.
M = bending moment in inch pounds.
R = radius of curvature at center line of member in inches.
b = width of cross section in inches.
d = depth of cross section in inches.
For curved bending members having a varying cross section, the maximum radial
stress induced,f,, is given by:
6M
f, = K, bd2
WHERE:
M = bending moment at midspan in inch-pounds.
b = width of cross section, inches.
d = depth of cross section at the apex in inches.
K, = radial stress factor determined from the following relationship:
Rm + c(...!L)
K = A+ B(..JL) 2
r Rm
WHERE:
Rm = radius of curvature at the center line of the member at midspan in
inches.
205
2511 UNIFORM BUILDING CODE
and 13 = angle between the upper edge of the member and the horizontal in
degrees.
Values of K r for intermediate values of 13 may be interpolated linearly.
When M is in the direction tending to decrease the curvature (increase the
radius), the stress in tension across the grain (Fr,) is limited to:
A. One third the allowable unit stress in horizontal shear of all species for
wind and earthquake loads.
B. Fifteen psi for Douglas fir, larch, hem-fir, western woods and other soft-
woods for other types of loading.
C. One third the allowable unit stress in horizontal shear for southern pine,
redwood and hardwoods for all types of loading.
When M is in the direction tending to increase curvature (decrease the radius),
the radial stress is in compression and shall be limited to the allowable stress in
compression perpendicular to the grain.
When the beam is loaded with a uniform load, Kr may be modified by
multiplying by the reduction factor C r as calculated by the following formula:
cr =A + B(~,) + c( ::) + v( Lr
+ E( :: r F( :: )( ~' )
+
+ G( ~, r H( :: r
+
WHERE:
cr = reduction factor
L = span of beam
L, = length of beam between tangent points
A,B, ... H
= constants for a given 13 as follows:
206
1982 EDITION 2511
/3 A B c D E F G H
2.3 -.142 .418 -2.358 -.053 - - .002 -
9.7 .143 .376 - .541 -.060 - - .003 -
14.9 .406 .293 - .927 -.041 - - .002 -
20.0 .423 .364 -1.022 -.067 - .146 - -
25.ZO .540 .360 -1.061 -.070 - .156 - -
29.8 .502 .372 - -.076 -3.712 .138 .004 4.336
and f3 = angle between the upper edge of the member and the horizontal in
degrees. Values of C, for intermediate values may be interpolated linearly.
Lt
207
2511 UNIFORM BUILDING CODE
For intennediate depths, straight line interpolation may be used. For continu-
ous beams or beams cantilevered over a support, determine the size factor
assuming the members to be equivalent to simply supported members with a
uniformly distributed load, the length of the equivalent span being the actual
distance between supports.
Values as detennined above will be sufficiently accurate for most design
situations. For lid ratios other than 21 and other conditions of loading where
greater accuracy may be desired, see U .B.C. Standard No. 25-11.
6. Ponding. Roof framing members shall be designed for the deflection criteria
and ponding requirements specified in Sections 2305 (f) and 2307. In no case
shall the roof slope provide a positive vertical displacement less than that equiv-
alent to Y4 inch per foot of horizontal distance between the level of the drain and
the high point of the roof for drainage. Such slope shall be in addition to the
camber in glued-laminated timbers of one and one-half times the calculated dead
load deflection. The calculation of the required slope shall not include any
vertical displacement created by short taper cuts.
Roofs having insufficient slope for drainage shall be investigated by a rational
analysis to assure stability under ponding conditions, but in no case shall the
deflection of such glued-laminated timbers exceed Y2 inch for a 5-pound-per-
square-foot unifonn load.
(e) Thpered Faces. No sawn tapered cuts shall be pennitted on the tension face
of any simple beam. Pitched or curved beams shall be so fabricated that the
laminations are parallel to the tension face. Straight, pitched or curved beams may
have sawn tapered cuts on the compression face.
For other members subject to bending, the slope of tapered faces, measured
from the tangent to the lamination of the section under consideration, shall be not
steeper than 1:24 on the tension side.
EXCEPTIONS: I. This requirement shall not apply to arches.
2. Taper may be steeper at sections increased in size beyond design requirements
for architectural projections.
(f) Manufacture and Fabrication. The manufacture and fabrication of struc-
tural glued-laminated timber shall be in accordance with U.B.C. Standard
No. 25-10. All work shall be under the supervision of qualified personnel.
208
1982 EDITION 2511-2513
structure and are exposed to weather and not properly protected by a roof, eave
overhangs or similar covering shall be pressure treated with an approved preserva-
I
tive or be manufactured from wood of natural resistance to decay.
Design of Glued Built-up Members
Sec. 2512. Plywood components shall be designed, fabricated and identified
in accordance with U.B.C. Standard No. 25-18.
Wood Diaphragms
Sec. 2513. (a) General. Lumber and plywood diaphragms may be used to
resist horizontal forces in horizontal and vertical distributing or resisting ele-
ments, provided the deflection in the plane of the diaphragm, as determined by
calculations, tests or analogies drawn therefrom, does not exceed the permissible
deflection of attached distributing or resisting elements. See U.B.C. Standard
No. 25-9 for a method of calculating the deflection of a blocked plywood
diaphragm.
Permissible deflection shall be that deflection up to which the diaphragm and
any attached distributing or resisting element will maintain its structural integrity
under assumed load conditions, i.e., continue to support assumed loads without
danger to occupants of the structure.
Connections and anchorages capable of resisting the design forces shall be
provided between the diaphragms and the resisting elements. Openings in dia-
phragms which materially affect their strength shall be fully detailed on the plans
and shall have their edges adequately reinforced to transfer all shearing stresses.
Size and shape of diaphragms shall be limited as set forth in Table No. 25-1.
In buildings of wood frame construction where rotation is provided for, the
depth of the diaphragm normal to the open side shall not exceed 25 feet nor two
thirds the diaphragm width, whichever is the smaller depth. Straight sheathing
shall not be permitted to resist shears in diaphragms acting in rotation.
EXCEPTIONS: I. One-story, wood-framed structures with the depth normal to
the open side not greater than 25 feet may have a depth equal to the width.
2. Where calculations show that diaphragm deflections can be tolerated, the
depth normal to the open end may be increased to a depth-to-width ratio not greater
than I \12: I for diagonal sheathing or 2: I for special diagonal sheathed or plywood
diaphragms.
In masonry or concrete buildings, lumber and plywood diaphragms shall not be
considered as transmitting lateral forces by rotation.
Diaphragm sheathing nails or other approved sheathing connectors shall be
driven flush but shall not fracture the surface of the sheathing.
(b) Diagonally Sheathed Diaphragms. 1. Conventional construction. Such
lumber diaphragms shall be made up of l-inch nominal sheathing boards laid at an
angle of approximately 45 degrees to supports. Sheathing boards shall be directly
nailed to each intermediate bearing member with not less than two 8d nails for l-
inch by 6-inch nominal boards and three 8d nails for boards 8 inches or wider;
and, in addition, three 8d nails and four 8d nails shall be used for 6-inch and 8-
inch boards, respectively, at the diaphragm boundaries. End joints in adjacent
boards shall be separated by at least one joist or stud space, and there shall be at
209
2513 UNIFORM BUILDING CODE
least two boards between joints on the same support. Boundary members at edges
of diaphragms shall be designed to resist direct tensile or compressive chord
stresses and shall be adequately tied together at corners.
Conventional lumber diaphragms of Douglas fir-larch or southern pine may be
used to resist shear due to wind or seismic forces not exceeding 300 pounds per
lineal foot of width. The allowable strength shall be adjusted by the factors 0.82
and 0. 65 where nails are used with sheathing and framing of Group III or IV wood
species as listed in Table No. 25-17-J ofU.B.C. Standard No. 25-17.
2. Special construction. Special diagonally sheathed diaphragms shall con-
form to conventional construction and, in addition, shall have all elements
designed in conformance with the provisions of this code.
Each chord or portion thereof may be considered as a beam loaded with a
uniform load per foot equal to 50 percent of the unit shear due to diaphragm
action. The load shall be assumed as acting normal to the chord, in the plane of the
diaphragm and either toward or away from the diaphragm. The span of the chord,
or portion thereof, shall be the distance between structural members of the
diaphragm, such as the joists, studs and blocking, which serve to transfer the
assumed load to the sheathing.
Special diagonally sheathed diaphragms shall include conventional dia-
phragms sheathed with two layers of diagonal sheathing at 90 degrees to each
other and on the same face of the supporting members.
Special diagonally sheathed diaphragms of Douglas fir-larch or southern pine
may be used to resist shears due to wind or seismic loads, provided such shears do
not stress the nails beyond their allowable safe lateral strength and do not exceed
600 pounds per lineal foot of width. The allowable strength shall be adjusted by
the factors 0.82 and 0.65 where nails are used with sheathing and framing of
Group III or IV wood species as listed in Table No. 25-17-J ofU.B.C. Standard
No. 25-17.
(c) Plywood Diaphragms. Horizontal and vertical diaphragms sheathed with
plywood may be used to resist horizontal forces not exceeding those set forth in
Table No. 25-J for horizontal diaphragms and Table No. 25-K for vertical dia-
phragms, or may be calculated by principles of mechanics without limitation by
using values of nail strength and plywood shear values as specified elsewhere in
this code. Plywood for horizontal diaphragms shall be as set forth in Table
No. 25-S for corresponding joist spacing and loads. Plywood in shear walls shall
be at least 5/16 inch thick for studs spaced 16 inches on center and 3fs inch thick
where studs are spaced 24 inches on center.
Maximum spans for plywood subfloor underlayment shall be as set forth in
Table No. 25-T. Plywood used for horizontal and vertical diaphragms shall
conform to U.B.C. Standard No. 25-9.
All boundary members shall be proportioned and spliced where necessary to
transmit direct stresses. Framing members shall be at least 2-inch nominal in the
dimension to which the plywood is attached. In general, panel edges shall bear on
the framing members and butt along their center lines. Nails shall be placed not
Jess than 3fs inch in from the panel edge, shall be spaced not more than 6 inches on
210
1982 EDITION 25132516
center along panel edge bearings, and shall be firmly driven into the framing
members. No unblocked panels less than 12 inches wide shall be used.
Fiberboard Sheathing Diaphragms
Sec. 2514. Wood stud walls sheathed with fiberboard sheathing complying
with U.B.C. Standard No. 25-24 may be used to resist horizontal forces not
exceeding those set forth in Table No. 25-P. The fiberboard sheathing, 4 feet by 8
feet, shall be applied vertically to wood studs not less than 2-inch nominal in
thickness spaced 16 inches on center. Nailing shown in Table No. 25-P shall be
provided at the perimeter of the sheathing board and at intermediate studs.
Blocking not less than 2-inch nominal in thickness shall be provided at horizontal
joints when wall height exceeds length of sheathing panel, and sheathing shall be
fastened to the blocking with nails sized as shown in Table No. 25-P spaced 3
inches on centers each side of joint. Nails shall be spaced not less than Ys inch
from edges and ends of sheathing. Marginal studs of shear walls or shear-resisting
elements shall be adequately anchored at top and bottom and designed to resist all
forces. The maximum height-width ratio shall be 11/z: I.
Wood Combined with Masonry or Concrete
Sec. 2515. (a) Dead Load. Wood members shall not be used to permanently
support the dead load of any masonry or concrete.
EXCEPTIONS: I . Masonry or concrete nonstructural floor or roof surfacing
not more than 4 inches thick may be supported by wood members.
2. Any structure may rest upon wood piles constructed in accordance with the
requirements of Chapter 29.
3. Masonry or concrete fireplace with a factory-built chimney conforming to
Chapter 37 may be supported by wood framing.
4. Veneer of brick, concrete or stone applied as specified in Section
3006 (b) may be supported by approved treated wood foundations when the maxi-
mum height of veneer does not exceed 25 feet above the foundation. Such veneer
used as an interior wall finish may also be supported on wood floors which are
designed to support the additional load, and be designed to limit the deflection and
shrinkage to V.1oo of the span of the supporting members.
(b) Horizontal Force. Wood members shall not be used to resist horizontal
forces contributed by masonry or concrete construction in buildings over one
story in height.
EXCEPTION: Wood floor and roof members may be used in horizontal trusses
and diaphragms to resist horizontal forces imposed by wind, earthquake or earth
pressure, provided such forces are not resisted by rotation of the truss or diaphragm.
General Construction Requirements
Sec. 2516. (a) General. The requirements in this section apply to all wood
frame construction.
(b) Preparation of Building Site. All stumps and roots shall be removed from
the soil to a depth of at least 12 inches below the surface of the ground in the area
to be occupied by the building.
All wood forms which have been used in placing concrete, if within the ground
or between foundation sills and the ground, shall be removed before a building is
occupied or used for any purpose. Before completion, loose or casual wood shall
be removed from direct contact with the ground under the building.
211
2516 UNIFORM BUILDING CODE
I
approved mechanical means or by openings in exterior foundation walls. Such
openings shall have a net area of not less than 1 square foot for each 150 square
feet of under-floor area. Openings shall be located as close to comers as practical
and shall provide cross ventilation. The required area of such openings shall be
approximately equally distributed along the length of at least two opposite sides.
212
1982 EDITION 2516
They shall be covered with corrosion-resistant wire mesh with mesh openings of
V4 inch in dimension. Where moisture due to climate and groundwater conditions
is not considered excessive, the building official may allow operable louvers and .
may allow the required net area of vent opening to be reduced to 10 percent of the
I
above, provided the under-floor ground surface area is covered with an approved
vapor barrier.
7. Wood and earth separation. Protection of wood against deterioration as set
forth in the previous paragraphs for specified applications is required. In addition,
wood used in construction of permanent structures and located nearer than 6
inches to earth shall be treated wood or wood of natural resistance to decay, as
defined in Section 2502 (a). Where located on concrete slabs placed on earth,
wood shall be treated wood or wood of natural resistance to decay. Where not
subject to water splash or to exterior moisture and located on concrete having a
minimum thickness of 3 inches with an impervious membrane installed between
concrete and earth, the wood may be untreated and of any species.
Where planter boxes are installed adjacent to wood frame walls a 2-inch-wide
air space shall be provided between the planter and the wall. Flashings shall be
installed when the air space is less than 6 inches in width. Where flashing is used
provisions shall be made to permit circulation of air in the air space. The wood
frame wall shall be provided with an exterior wall covering conforming to the
provisions of Subsection (g) of this section.
8. Wood supporting roofs and floors. Wood structural members supporting
moisture permeable floors or roofs which are exposed to the weather such as
concrete or masonry slabs shall be approved wood of natural resistance to decay
or treated wood unless separated from such floors or roofs by an impervious
moisture barrier.
9. Moisture content of treated wood. When wood pressure treated with a
water-borne preservative is used in enclosed locations where drying in service
cannot readily occur, such wood shall be at a moisture content of 19 percent or less
before being covered with insulation, interior wall finish, floor covering or other
material.
10. Retaining walls. Wood used in retaining or crib walls shall be treated
wood.
11. Weather exposure. In geographical areas where experience has demon-
strated a specific need, approved wood of natural resistance to decay or treated
wood shall be used for those portions of wood members which form the structural
supports of buildings, balconies, porches or similar permanent building appurte-
nances when such members are exposed to the weather without adequate protec-
tion from a roof, eave, overhang or other covering to prevent moisture or water
accumulation on the surface or at joints between members. Depending on local
experience, such members may include: horizontal member such as girders, joists
and decking; or vertical members such as posts, poles and columns; or both
horizontal and vertical members.
(d) Wall Framing. The framing of exterior and interior walls shall be in
accordance with provisions specified in Section 2517 unless a specific design is
furnished.
213
2516 UNIFORM BUILDING CODE
Wood stud walls and bearing partitions shall not support more than two floors
and a roof unless an analysis satisfactory to the building official shows that
shrinkage of the wood framing will not have adverse effects upon the structure nor
any plumbing, electrical, mechanical systems nor other equipment installed
therein due to excessive shrinkage or differential movements caused by
shrinkage. The analysis shall also show that the roof drainage system and the
foregoing systems or equipment will not be adversely affected or, as an alternate,
such systems shall be designed to accommodate the differential shrinkage or
movements.
(e) Floor Framing. Wood-joisted floors shall be framed and constructed and
anchored to supporting wood stud or masonry walls as specified in Chapter 23.
(f) Fire and Draft Stops. I. General. In combustible construction, firestop-
ping and draftstopping shall be installed to cut off all concealed draft openings
(both vertical and horizontal) and shall form an effective barrier between floors,
between a top story and a roof or attic space, and shall subdivide attic spaces,
concealed roof spaces and floor-ceiling assemblies. The integrity of all fire and
draft stops shall be maintained.
2. Fire stops, where required. Firestopping shall be provided in the following
locations:
A. In concealed spaces of stud walls and partitions, including furred spaces, at
the ceiling and floor levels and at 10-foot intervals along the length of the wall.
EXCEPTION: Fire stops may be omitted at floor and ceiling levels when
approved smoke-actuated fire dampers are installed at these levels.
214
1982 EDITION 2516
concealed space does not exceed 1,000 square feet. Draftstopping shall divide the
concealed space into approximately equal areas.
(ii) 1\vo or more dwelling units and hotels. Draft stops shall be installed in
floor-ceiling assemblies of buildings having more than one dwelling unit and in
hotels. Such draft stops shall be in line with walls separating tenants from each
other and separating tenants from other areas.
(iii) Other uses. Draft stops shall be installed in floor-ceiling assemblies of
buildings or portions of buildings used for other than dwelling or hotel occupan-
cies so that the area of the concealed space does not exceed 1,000 square feet and
so that the horizontal dimension between stops does not exceed 60 feet.
EXCEPTION: Where approved automatic sprinklers are installed within the
concealed space, the area between draft stops may be 3,000 square feet and the
horizontal dimension may be 100 feet.
B. Attics. (i) Single-family dwellings. None required.
(ii) 1\voormore dwelling units and hotels. Draft stops shall be installed in the
attics, mansards, overhangs, false fronts set out from walls and similar concealed
spaces of buildings containing more than one dwelling unit and in hotels. Such
draft stops shall be above and in line with the walls separating tenant spaces from
each other and from other uses.
EXCEPTIONS: I. Draft stops may be omitted along one of the corridor walls,
provided draft stops at tenant separation walls extend to the remaining corridor draft
stop.
2. Where approved sprinklers are installed, draftstopping may be as specified in
the exception to Item (iii) below.
(iii) Other uses. Draft stops shall be installed in attics, mansards, overhangs,
false fronts set out from walls and similar concealed spaces of buildings having
uses other than dwellings or hotels so that the area between draft stops does not
exceed 3,000 square feet and the greatest horizontal dimension does not exceed 60
feet.
EXCEPTION: Where approved automatic sprinklers are installed the area
between draft stops may be 9,000 square feet and the greatest horizontal dimension
may be 100 feet.
5. Draft stop construction. Drafts topping materials shall be not less than 1/z-
inch gypsum board, Ys-inch plywood or other approved materials adequately
supported.
Openings in the partitions shall be protected by self-closing doors with auto-
matic latches constructed as required for the partitions.
Ventilation of concealed roof spaces shall be maintained in accordance with
Section 3205.
6. Draft or fire stops in other locations. Firestopping of veneer on noncom-
bustible walls shall be in accordance with Item No.2 A above.
For firestopping of wood floors on masonry or concrete floors, see Sections
1804 and 1904.
For firestopping ceilings applied against noncombustible construction, see
Section 4203, Item No. I.
215
2516 UNIFORM BUILDING CODE
I
For firestopping penetrations in walls required to have protected openings, see
Section 4304 (e).
For firestopping penetrations through floors, see Section 4305 (a).
(g) Exterior Wall Coverings. 1. General. Exterior wood stud walls shall be
covered on the outside with the materials and in the manner specified in this
section or elsewhere in this code. Studs or sheathing shall be covered on the
outside face with a weather-resistive barrier when required by Section 1707 (a).
Exterior wall coverings of the minimum thickness specified in this section are
based upon a maximum stud spacing of 16 inches unless otherwise specified.
2. Siding. Siding shall have a minimum thickness of 3fs inch unless placed
over sheathing permitted by this code.
Siding patterns known as rustic, drop siding or shiplap shall have an average
thickness in place of not less than 19/32 inch and shall have a minimum thickness of
not less than 3fs inch. Bevel siding shall have a minimum thickness measured at
the butt section of not less than 7/16 inch and a tip thickness of not less than
3Jt6 inch. Siding of lesser dimensions may be used, provided such wall covering is
placed over sheathing which conforms to the provisions specified elsewhere in
this code.
All weatherboarding or siding shall be securely nailed to each stud with not less
than one nail, or to solid l-inch nominal wood sheathing or Y2-inch plywood
sheathing with not less than one line of nails spaced not more than 24 inches on
center in each piece of the weatherboarding or siding.
3. Plywood. Where plywood is used for covering the exterior of outside walls,
it shall be of the Exterior type not less than 3fs inch thick. Plywood panel siding
shall be installed in accordance with Table No. 25-M. Unless applied over l-inch
wood sheathing or Y2-inch plywood sheathing, joints shall occur over framing
members and shall be protected with a continuous wood batten, approved caulk-
ing, flashing, vertical or horizontal shiplaps; or joints shall be lapped horizontally
or otherwise made waterproof.
4. Shingles or shakes. Wood shingles or shakes and asbestos cement shingles
may be used for exterior wall covering, provided the frame of the structure is
covered with building paper as specified in Section 1707 (a). All shingles or
shakes attached to sheathing other than wood sheathing shall be secured with
approved corrosion-resistant fasteners or on furring strips attached to the studs.
Wood shingles or shakes may be applied over fiberboard shingle backer and
sheathing with annular grooved nails. The thickness of wood shingles or shakes
between wood nailing boards shall be not less than 3fs inch. Wood shingles or
shakes and asbestos shingles or siding may be nailed directly to approved
I fiberboard nailbase sheathing not less than Y2-inch nominal thickness with annu-
lar grooved nails. Fiberboard nail base sheathing and shingle backer shall comply
with U.B.C. Standard No. 25-24.
The weather exposure of wood shingle or shake siding used on exterior walls
shall not exceed maximums set forth in Table No. 25-L.
216
1982 EDITION 2516
Standard No. 25-25, not less than % inch thick when applied over approved
sheathing, not less than 5fs inch thick when applied directly to framing spaced 16
inches on center and not less than % inch thick when applied directly to framing
spaced 24 inches on center. Panels shall be gapped Ys inch and nails shall be
spaced not less than% inch from edges and ends of sheathing. Unless applied over
%-inch net wood sheathing or Y2-inch plywood sheathing or 1/2-inch particleboard
sheathing, joints shall occur over framing members and shall be covered with a
continuous wood batt; or joints shall be lapped horizontally or otherwise made
waterproof to the satisfaction of the building official. Particleboard shall be sealed
and protected with exterior quality finishes.
6. Hardboard. Where hardboard siding is used for covering the outside of
exterior walls, it shall conform to U .B.C. Standard No. 25-26 and Table No. 25-
0. Lap siding shall be installed horizontally direct to studs. Comer bracing shall
be installed in conformance with Section 2517 (g) 3. A weather-resistive barrier
shall be installed under the lap siding as required by Section 1707 (a).
Square-edged nongrooved panels and shiplap grooved or nongrooved siding
shall be applied vertically to sheathed or unsheathed walls. Siding that is grooved
shall be not less than Y4 inch thick in the groove.
Nail size and spacing shall follow Table No. 25-0 and shall penetrate framing
! 1/2 inches. Lap siding shall overlap I inch minimum and be nailed through both
courses and into framing members with nails located 1/2 inch from bottom of the
overlapped course. Square-edged nongrooved panels shall be nailed% inch from
the perimeter of the panel and intermediately into studs. Shiplap edge panel siding
with %-inch shiplap shall be nailed % inch from the edges on both sides of the
shiplap. The %-inch shiplap shall be nailed% inch from the edge and penetrate
through both the overlap and under lap. Top and bottom edges of the panel shall be
nailed % inch from the edge.
Shiplap and lap siding shall not be force fit. Square-edged panels shall maintain
a Yl6-inch gap at joints. All joints and edges of siding shall be over framing
members and shall be made resistant to weather penetration with battens, horizon-
tal overlaps or shiplaps to the satisfaction of the building official. A Ys-inch gap
shall be provided around all openings.
7. Nailing. All fasteners used for the attachment of siding shall be of a
corrosion-resistant type.
(h) Structural Floor Sheathing. Structural floor sheathing shall be designed
in accordance with the general provisions of this code and the special provisions
in this subsection.
Sheathing used as subflooring shall be designed to support all loads specified in
this code and shall be capable of supporting concentrated loads of not less than
300 pounds without failure. The concentrated load shall be applied by a loaded
disc, 3 inches or smaller in diameter.
Flooring, including the finish floor, underlayment and subfloor, where used,
shall meet the following requirements:
Deflection under uniform design load limited to 11360 of the span between
supporting joists or beams.
217
2518 UNIFORM BUILDING CODE
I Plywood roof sheathing exposed on the underside shall be bonded with exterior
glue.
(j) Fastenings. 1. Nailing requirements. The number and size of nails con-
necting wood members shall be not less than that set forth in Table No. 25-Q.
Other connections shall be fastened so as to provide equivalent strength. End and
edge distances and nail penetrations shall be in accordance with the applicable
I
provisions of Section 2510. Fasteners required to be corrosion resistant shall be
either zinc-coated fasteners conforming to U.B.C. Standard No. 25-17, Section
25.1717 (a), aluminum alloy wire fasteners conforming to U.B.C. Standard No.
25-17, Section 25.1716 (e), or stainless steel fasteners conforming to U.B.C.
Standard No. 25-17, Section 25.1716 (h).
2. Joist hangers and framing anchors. Connections depending upon joist
hangers or framing anchors, ties and other mechanical fastenings not otherwise
covered may be used where approved.
(k) Water Splash. Where wood frame walls and partitions are covered on the
interior with plaster, tile or similar materials and are subject to water splash, the
framing shall be protected with approved waterproof paper conforming to Section
1707 (a).
(I) Mechanically Laminated Floors and Decks. A laminated lumber floor or
deck built up of wood members set on edge, when meeting the following
requirements, may be designed as a solid floor or roof deck of the same thickness,
and continuous spans may be designed on the basis of the full cross section using
the simple span moment coefficient.
Nail length shall be not less than two and one-half times the net thickness of
each lamination. When deck supports are 4 feet on center or less, side nails shall
218
1982 EDITION 2516-2517
be spaced not more than 30 inches on center and staggered one third of the spacing
in adjacent laminations. When supports are spaced more than 4 feet on center, side
nails shall be spaced not more than 18 inches on center alternately near top and
bottom edges, and also staggered one third of the spacing in adjacent laminations.
1\vo side nails shall be used at each end of butt-jointed pieces.
Laminations shall be toenailed to supports with 20d or larger common nails.
When the supports are 4 feet on center or less, alternate laminations shall be
toenailed to alternate supports; when supports are spaced more than 4 feet on
center, alternate laminations shall be toenailed to every support.
A single-span deck shall have all laminations full length.
A continuous deck of two spans shall have not more than every fourth lamina-
tion spliced within quarter points adjoining supports.
Joints shall be closely butted over supports or staggered across the deck but
within the adjoining quarter spans.
No lamination shall be spliced more than twice in any span.
(m) Post-beam Connections. Where post and beam or girder construction is
used, the design shall be in accordance with the provisions ofthis code. Positive
connection shall be provided to ensure against uplift and lateral displacement.
Conventional Construction Provisions
Sec. 2517. (a) General. The requirements contained in this section are
intended for conventional, light-frame construction. Light-frame construction of
unusual shape, size or split levels shall, when located within Seismic Zones No.
2, No. 3 and No. 4, be designed to resist lateral forces in accordance with other
provisions of this code. Other methods may be used, provided a satisfactory
design is submitted showing compliance with other provisions of this code.
(b) Foundation Plates or Sills. Foundations and footings shall be as specified
in Chapter 29. Foundation plates or sills resting on concrete or masonry founda-
tions shall be bolted as required by Section 2907 (e).
(c) Girders. Girders shall be designed to support the loads specified in this
code. Girder end joints shall occur over supports. When a girder is spliced over a
support, an adequate tie shall be provided. The end of beams or girders supported
on masonry or concrete shall have not less than 3 inches of bearing.
(d) Floor Joists. 1. General. Spans for joists shall be in accordance with
Table No. 25-U-J-1.
2. Bearing. Except where supported on a l-inch by 4-inch ribbon strip and
nailed to the adjoining stud, the ends of each joist shall have not less than
1Y2 inches of bearing on wood or metal, nor less than 3 inches on masonry.
3. Framing details. Joists shall be supported laterally at the ends and at each
support by solid blocking except where the ends of joists are nailed to a header,
band or rim joist or to an adjoining stud or by other approved means. Solid
blocking shall be not less than 2 inches in thickness and the full depth of joist.
Notches on the ends of joists shall not exceed one fourth the joist depth. Holes
bored in joists shall not be within 2 inches of the top or bottom of the joist, and the
diameter of any such hole shall not exceed one third the depth of the joist. Notches
219
2517 UNIFORM BUILDING CODE
in the top or bottom of joists shall not exceed one sixth the depth and shall not be
located in the middle third ofthe span.
Joists framing from opposite sides of a beam, girder or partition shall be lapped
at least 4 inches or the opposing joists shall be tied together in an approved
manner.
Joists framing into the side of a wood girder shall be supported by framing
anchors or on ledger strips not Jess than 2 inches by 2 inches.
4. Framing around openings. Trimmer and header joists shall be doubled, or
of lumber of equivalent cross section, when the span of the header exceeds 4 feet.
The ends of header joists more than 6 feet long shall be supported by framing
anchors or joist hangers unless bearing on a beam, partition or wall. Tail joists
over 12 feet long shall be supported at header by framing anchors or on ledger
strips not less than 2 inches by 2 inches.
5. Supporting bearing partitions. Bearing partitions perpendicular to joists
shall not be offset from supporting girders, walls or partitions more than the joist
depth.
Joists under and parallel to bearing partitions shall be doubled.
6. Blocking. Floor joists shall be blocked when required by the provisions of
Sections 2506 (g) and 2517 (d) 3.
(e) Subflooring. I. Lumber subfloor. Sheathing used as a structural subfloor
shall conform to the limitations set forth in Tables No. 25-R-1 and No. 25-R-2.
Joints in subflooring shall occur over supports unless end-matched lumber is
used, in which case each piece shall bear on at least two joists.
Subflooring may be omitted when joist spacing does not exceed 16 inches and
l-inch nominal tongue-and-grooved wood strip flooring is applied perpendicular
to the joists.
2. Plywood. Where used as structural subflooring, plywood shall be as set
forth in Tables No. 25-S-1 and No. 25-S-2. Plywood combination subfloor-
underlayment shall have maximum spans as set forth in Table No. 25-T.
When plywood floors are glued to joists with an adhesive conforming to
U.B.C. Standard No. 25-19, in accordance with the adhesive manufacturer's
directions, fasteners may be spaced a maximum of 12 inches on center at all
supports.
3. Plank flooring. Plank flooring shall be designed in accordance with the
general provisions of this code.
In lieu of such design, 2-inch tongue-and-groove planking may be used in
accordance with Table No. 25-U. Joints in such planking may be randomly
spaced, provided the system is applied to not less than three continuous spans,
planks are center-matched and end-matched or splined, each plank bears on at
least one support and joints are separated by at least 24 inches in adjacent pieces.
One-inch nominal strip square-edged flooring, Y2-inch tongue-and-groove floor-
ing, or %-inch plywood shall be applied over random-length decking used as a
floor. The "strip'' and tongue-and-groove flooring shall be applied at right angles
to the span of the planks. The %-inch plywood shall be applied with the face grain
at right angles to the span of the planks.
220
1982 EDITION 2517
221
2517 UNIFORM BUILDING CODE
C. Plywood sheathing with a thickness not less than 5/16 inch for 16-inch stud
spacing and not less than 3fs inch for 24-inch stud spacing in accordance
with Tables No. 25-M and No. 25-N.
I D. Fiberboard sheathing 4-foot by 8-foot panels not less than lf2 inch thick
applied vertically on studs spaced not over 16 inches on center when
installed in accordance with Section 2514 and Table No. 25-P.
E. Gypsum sheathing panels not less than lf2 inch thick on studs spaced not
over 16 inches on center when installed in accordance with Table No. 47-1.
I F. Particleboard Exterior TYpe 2-M-l sheathing panels not less than 3fs inch
thick on studs spaced not more than 16 inches on center.
G. Gypsum wallboard not less than lf2 inch thick on studs spaced not over 24
inches on center when installed in accordance with Table No. 47-1.
H. Portland cement plaster on studs spaced 16 inches on center installed in
accordance with Table No. 47-1.
222
1982 EDITION 2517
this paragraph and together with their supporting systems shall be designed to
support the loads specified in this code. All openings 4 feet wide or less in bearing
walls shall be provided with headers consisting of either two pieces of 2-inch
framing lumber placed on edge and securely fastened together or 4-inch lumber of
equivalent cross section. All openings more than 4 feet wide shall be provided
with headers or lintels. Each end of a lintel or header shall have a length of bearing
of not less than 11/2 inches for the full width of the lintel.
I
6. Pipes in walls. Stud partitions containing plumbing, heating, or other pipes
shall be so framed and the joists underneath so spaced as to give proper clearance
for the piping. Where a partition containing such piping runs parallel to the floor
joists, the joists underneath such partitions shall be doubled and spaced to permit
the passage of such pipes and shall be bridged. Where plumbing, heating or other
pipes are placed in or partly in a partition, necessitating the cutting of the soles or
plates, a metal tie not less than Ys inch thick and 1Y2 inches wide shall be fastened
to the plate across and to each side ofthe opening with not less than four 16d nails.
7. Bridging. Unless covered by interior or exterior wall coverings or sheathing
meeting the minimum requirements of this code, all stud partitions or walls with
studs having a height-to-least-thickness ratio exceeding 50 shall have bridging not
less than 2 inches in thickness and of the same width as the studs fitted snugly and
nailed thereto to provide adequate lateral support.
8. Cutting and notching. In exterior walls and bearing partitions, any wood
stud may be cut or notched to a depth not exceeding 25 percent of its width.
Cutting or notching of studs to a depth not greater than 40 percent of the width of
the stud is permitted in nonbearing partitions supporting no loads other than the
weight of the partition.
9. Bored holes. A hole not greater in diameter than 40 percent of the stud width
may be bored in any wood stud. Bored holes not greater than 60 percent of the
width of the stud are permitted in nonbearing partitions or in any wall where each
bored stud is doubled, provided not more than two such successive doubled studs
are so bored.
In no case shall the edge of the bored hole be nearer than % inch to the edge of
the stud. Bored holes shall not be located at the same section of stud as a cut or
notch.
(h) Roof and Ceiling Framing. 1. General. The framing details required in
this subsection apply to roofs having a minimum slope of 3: 12 or greater. When
the roof slope is less than 3:12, members supporting rafters and ceiling joists such
as ridge board, hips and valleys shall be designed as beams.
2. Spans. Allowable spans for ceiling joists shall be in accordance with Table
No. 25-U-J-6. Allowable spans for rafters shall be in accordance with Tables No.
25-U-R-1 through No. 25-U-R-14, where applicable.
3. Framing. Rafters shall be framed directly opposite each other at the ridge.
There shall be a ridge board at least 1-inch nominal thickness at all ridges and not
less in depth than the cut end of the rafter. At all valleys and hips there shall be a
single valley or hip rafter not less than 2-inch nominal thickness and not less in
depth than the cut end of the rafter.
223
2517 UNIFORM BUILDING CODE
I
6. Blocking. Roof rafters and ceiling joists shall be supported laterally to
prevent rotation and lateral displacement when required by Section 2506 (g). Roof
trusses shall be supported laterally at points of bearing by solid blocking to
prevent rotation and lateral displacement.
7. Roof sheathing. Roof sheathing shall be in accordance with Tables No. 25-
S-1 and No. 25-S-2 for plywood or No. 25-R-1 and No. 25-R-2 for lumber.
Joints in lumber sheathing shall occur over supports unless approved end-
matched lumber is used. in which case each piece shall bear on at least two
supports.
Plywood used for roof sheathing shall be bonded by intermediate or exterior
I glue. Plywood roof sheathing exposed on the underside shall be bonded with
exterior glue.
8. Roof planking. Planking shall be designed in accordance with the general
provisions of this code.
In lieu of such design. 2-inch tongue-and-groove planking may be used in
accordance with Table No. 25-U. Joints in such planking may be randomly
spaced, provided the system is applied to not less than three continuous spans,
planks are center-matched and end-matched or splined, each plank bears on at
least one support, and joints are separated by at least 24 inches in adjacent pieces.
224
....
!m
TABLE NO. 25-A-1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504) 0
3
z
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Compnts Compnts-
Eng!- Tension sion per sion MODULUS U.B.C. STDS.
SIZE neered Repetitive Parallel Horizontal pendlcuier Parallel OF UNDER
SPECIES AND CLASSIFI Uses member to Grain Shear to Grain to Grain ELASTICITY WHICH
COMMERCIAL GRADE CATION (SingleI Uses F, Fv Fc1- Fe E GRADED
ASPEN (BIGTOOTH-QUAKING) (Surfaced dry or surfaced green. Used at 190Jo max. m.c.)
Select Structural 1300 1500 775 60 185 850 1,100,000
No.I 2" to 4" IIOO 1300 650 60 185 675 1,100,000
No.2 thick 925 1050 525 60 185 550 1,000,000
No.3 2" to 4" 500 575 300 60 185 325 900,000
Appearance wide IIOO 1300 650 60 185 825 1,100,000 25-4
Stud 500 575 300 60 185 325 900,000 25-5
and25-8
Construction 2" to 4" 650 750 400 60 185 625 900,000 (See footnotes
Standard thick 375 425 225 60 185 500 90j),OOO 2 through 8,
Utility 4" wide 175 200 100 60 185 325 900,000 13, 15 and 16)
Select Structural II 50 1300 750 60 185 750 1,100,000
No.I 2" to 4" 950 1100 650 60 185 675 1,100,000
No.2 thick 775 900 425 60 185 575 1,000,000
No. 3 and Stud 5" and 450 525 250 60 195 375 900,000
Appearance wider 950 IIOO 650 60 185 825 1,100,000
(Continued)
N
N
(II
N N
N TABLE NO. 25A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Conlinued)
~....
Cl)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
~
Spacias and commercial grade Single- shaar WHICH
classification Repetitiw to grain to grain to grain elasticity
member member Fv GRADED
F, F .L F. E
uses uses
BALSAM FIR (Surfaced dry or surfaced green. Used at 19% max. m.c.) i.
:::~
:;:;:
Select Structural 2'"to 4'' 1750 2000 1000 70 185 1350 1,500,000
I
No.1 thick 1450 1700 850 70 185 1050 1,500,000
No.2 2'" to 4'" 1200 1400 700 70 185 850 1,300,000
No.3 wide 675 775 400 70 185 525 1,200,000
Appearance 1450 1700 850 70 185 1250 1,500,000 25-5
Stud 675 775 400 70 185 525 1,200,000 25-8 :::::
(See footnotes ~=~==
Construction 2'" to4'" 875 1000 525 70 185 950 1,200,000 1 through 9)
Standard
Utility
thick
4'" wide
500
225
575
275
275
125
70
70
185
185
775
525
1,200,000
1,200,000 tlt
Select Structural 2'" to 4'" 1500 1700 1000 70 185 1200 1,500,000
No.1
No.2
thick
5'" and
1250
1050
1450
1200
850
550
70
70
185
185
1050
900
1,500,000
1,300,000 I c:z
~~~
No.3 wider 600 700 325 70 185 575 1,200,000 ::::: :;;
Appearance 1250 1450 850 70 185
185
1250 1,500,000 r 0
Stud 600 700 325 70 575 1,200,000 if ::D
3:
Select Structural Beams and 1350 -- 900 65 185 950 1,400,000
No.1 Stringers 1100 -- 750 65 185 800 1,400,000 Ill
c:
Select Structural Posts and 1250 -- 825 65 185 1000 1,400,000 j=
No.1 Timbers 1000 -- 675 65 185 875 1,400,000 0
Select Decking -- 1650 -- -- -- -- 1,500,000 25-8 z
C)
Commercial -- 1400 -- -- -- -- 1,300,000 (See footnotes
0
1 through 9)
0
Jil
....
IN
m
c
3
0
BLACK COTIONWOOD (Surfaced dry or surfaced green. Used at 190Jo max. m.c.) z
Select Structural 1000 1200 600 50 100 725 1,200,000
No.I 2" to 4" 875 1000 500 50 100 575 1,200,000
No.2 thick 725 825 425 50 100 450 1,100,000
No.3 2" to 4" 400 450 225 50 100 275 900,000
Appearance wide 875 1000 500 50 100 700 1,200,000
Stud 400 450 225 50 100 275 900,000
25-2
Construction 2" to 4" 525 600 300 50 100 525 900,000 (See footnotes
Standard thick 300 325 175 50 100 425 900,000 2 through 9,
Utility 4" wide 150 150 75 50 100 275 900,000 II, 13,
15 and 16)
Select Structural 875 1000 600 50 100 650 1,200,000
No.I 2" to 4" 750 875 500 50 100 575 1,200,000
No.2 thick 625 700 325 50 100 475 1,100,000
No. 3 and Stud 5" and 350 425 175 50 100 300 900,000
Appearance wider 750 875 500 50 100 700 1,200,000
CALIFORNIA REDWOOD (Surfaced dry or surfaced green. Used at 190Jo max. m.c.)
4" & less
Clear Heart Structural thick, any 2300 2650 1500 145 425 2150 1,400,000 25-7
Clear Structural width 2300 2650 1500 145 425 2150 1,400,000 (See footnotes
2 through 7
2" to 4" 9, 13, 15
Select Structural thick 2050 2350 1200 80 425 1750 1,400,000 and 16)
Select Structural, Open 2" to 4" 1600 1850 950 80 270 1300 1,100,000
gram wide
(Continued)
TABLE NO. 25-A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber- VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Com pres Com pres
Eng~ Tension sion per sion MODULUS U.B.C.STDS
SIZE neered Repetitlv Parallel ~orizontal pendicular Parallel OF UNDER
SPECIES AND CLASSIFI- Uses member to Grain Shear to Grain to Grain ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses F, F. F~ F. E GRADED
No. I, Open grain thick 1150 1350 775 80 270 1050 1,100,000
No.2
No. 2, Open grain
s and 1200
950
1400
1100
6SO
500
80 425
270
1200
875
1,250,000
wider 80 1,000,000
No. 3 and Stud 700 800 375 80 425 725 1,100,000
No.3, Open grain 550 650 3SO 80 270 525 900,000
Construction 2" to 4" 750 875 450 65 290 800 1,300,000 25-2
Standard thick 425 500 250 65 290 650 1,300,000 (See footnotes
Utility 4" wide 200 225 125 65 290 425 1,300,000 2 through 9, II,
13, 15 and 16)
Select Structural 1300 1500 850 65 290 975 1,700,000
No.I 2" to 4" 1100 1250 725 65 290 875 1,700,000
No.2 thick 900 1050 475 65 290 750 1,500,000
No. 3 and Stud 5" and 525 575 275 65 290 475 1,300,000
Appearance wider 1100 1250 725 65 290 1050 1,700,000
(Continued)
N
w TABLE NO. 25-A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
0
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Com pres Compres
Engl- Tension slonper slon MODULUS U.B.C.STDS
SIZE nee reel Repetltlv Pat'llllel Horizontal pendlcular Pat'llllel OF UNDER
SPECIES AND CLASSIFI Uses member IDGt'llln Shear toGt'llln toGI'IIIn ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single} Uses F, F. F.,..L Fe E GRADED
COAST SPECIES (Surfaced dry or surfaced green. Used at 190fo max. m.c.)
Select Structural 1500 1700 850 65 235 1100 1,500,000
1250 1450 65 875
fi;
No.I 2" to 4" 750 235 1,500,000
No.2
No.3
thick
2" to 4"
1050
575
1200
675
625
350
65
65
235
235
700
425
1,400,000
1,200,000
~i
Appearance wide 1250 1450 725 65 235 1050 1,500,000
Stud 575 675 350 65 235 425 1,200,000 '
Construction 2" to 4" 750 875 450 65 235 800 1,200,000
Standard thick 425 500 250 65 235 650 1,200,000 :
Utility 4" wide 200 225 125 65 235 425 1,200,000 25-2 .
(See footnotes :
Select Structural 1300 1500 875 65 235 975 1,500,000 2 through 9,
No.I 2" to 4" 1100 1250 725 65 235 875 1,500,000 II, 13,
No.2 thick 900 1050 .r15 65 235 750 1,400,000 15and 16)
No. 3 and Stud 5" and 525 600 Z15 65 235 475 1,200,000
Appearance wider 1100 1250 725 65 235 1050 1,500,000
DOUGLAS FIR- LARCH (Surfaced dry or surfaced green. Used at 19"7o max. m.c.)
DOUGLAS FIR -LARCH (North)
Dense Select Structural 2450 2800 1400 95 455 1850 1,900,000
Select Structural 2100 2400 1200 95 385 1600 1,800,000
Dense No. I 2050 2400 1200 95 455 1450 1,900,000
No.I 2" to 4" 1750 2050 1050 95 385 1250 1,800,000
Dense No.2 thick 1700 1950 1000 95 455 1150 1,700,000
No.2 2" to 4" 1450 1650 850 95 385 1000 1,700,000
No.3 wide 800 925 475 95 385 600 1,500,000 25-2
Appearance 1750 2050 1050 95 385 1500 1,800,000 25-3
Stud 800 925 475 95 385 600 1,500,000 and
25-4
Construction 1050 1200 625 95 385 1150 1,500,000 (See footnotes
2" to 4
Standard 600 615 350 95 385 925 1,500,000 2 through 9,
thick
Utility 275 325 175 95 385 600 1,500,000 II, 13,
4" wide 15 and 16)
Dense Select Structural 2100 2400 1400 95 455 1650 1,900,000
Select Structural 1800 2050 1200 95 385 1400 1,800,000
Dense No. I 2" to 4" 1800 2050 1200 95 455 1450 1,900,000
No.I thick 1500 1750 1000 95 385 1250 1,800,000
Dense No.2 5" and 1450 1700 775 95 455 1250 1,700,000
No.2 wider 1250 1450 650 95 385 1050 1,700,000
No. 3 and Stud 725 850 375 95 385 675 1,500,000
Appearance 1500 1750 1000 95 385 1500 1,800,000
(Continued)
.....
Dense Select Structural 1900 - 1100 8S 455 1300 1,700,000 25-2
!m
Select Structural Beams and 1600 - 950 8S 385 1100 1,600,000 (See footnotes
Dense No. I Stringers 1550 - 715 85 4.55 1100 1,700,000 2 through 9
c
No.I 1300 - 615 8S 385 925 1,600,000 and II)
3
Dense Select Structural 1750 - 1150 8S 455 1350 1,700,000 0
z
Select Structural Posts and 1500 - 1000 8S 385 1150 1,600,000 25-2
Dense No.I TID!bers 1400 - 950 8S 455 1200 1,700,000 (See footnotes
No.I 1200 - 825 8S 385 1000 1,600,000 2 through 9
Select Decking 1750 ;roo - - 385 - 1,800,000 and II)
Commercial 1450 1650 - - 385 - 1,700,000
DOUGLAS FIR SOUTH (Surfaced dry or surfaced green. Used at 190Jo max. m.c.)
Select Structural z
to 4. 2000 2300 1150 90 335 1400 1,400,000
No. I & Appearance thick 1700 1950 915 90 335 1150 1,400,000 25-4
No.2 2" to 4" 1400 1600 825 90 335 900 1,300,000 (See footnotes
No.3 wide 775 875 450 90 335 550 1,100,000 2 through 10,
Stud 715 875 450 90 335 550 1,100,000 13, 15 and 16)
Construction 2" to 4" 1000 1150 600 90 335 1000 1,100,000
Standard thick 550 650 325 90 335 850 1,100,000
Utility 4" wide 275 300 150 90 335 550 1,100,000
Select Structural 2" to 4" 1700 1950 1150 90 335 1250 1,400,000
No. I & Appearance thick 1450 16.50 915 90 335 1150 1,400,000
No.2 5" and 1200 1350 625 90 335 950 1,300,000
No. 3 and Stud wider 700 800 3.50 90 335 600 1,100,000
Select Structural Beams and 1550 - 1050 85 335 1000 1,200,000
No.I Stringers 1300 - 850 85 335 850 1,200,000
Select Structural Posts and 1400 - 950
715
85 335 1050 1,200,000
No.I Timbers ll50 - 85 335 925 1,200,000
Selected Decking Decking - 1900 - - - - 1,400,000
Commercial ~king - 1600 - - - - 1,300,000
Selected Decking Decking - 2050 (Stresses for Decking apply at 1,500,000
Commercial ~>.:!~king - 1750 150Jo moisture content) 1,300,000
(Continued)
TABLE NO. 25-A-1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
EASTERN HEMLOCK (Surfaced dry or surfaced green. Used at 19% ma><. m.c.l
Select Structrual 1750 2050 1050 85 360 1350 1,200,000
No.1 2" to 4" 1500 1750 875 85 360 1050 1,200,000
No.2 thick 1250 1450 725 85 360 850 1,100,000
No.3 2" to 4" 675 800 400 85 360 525 1,000,000
Appearance wide 1500 1750 875 85 360 1250 1,200,000
Stud 675 800 400 85 360 525 1,000,000
Construction 2" to 4" 900 1050 525 85 360 950 1,000,000
Standard thick 500 575 300 85 360 800 1,000,000 25-8
Utility 4" wide 250 275 150 85 360 525 1,000,000 (See footnotes
Select Structural 2" to 4" 1550 1750 1000 85 360 1200 1,200,000 1 through 9)
No.1 thick 1300 1500 875 85 360 1050 1,200,000
No.2 5" and 1050 1250 550 85 360 900 1,100,000 c:
No.3 wider 625 700 325 85 360 575 1.000,000 z
Appearance 1300 1500 875 85 360 1250 1,200,000 :;;
Stud 625 700 325 85 360 575 1.000,000 0
Select Structural Beams and 1350 -- 925 80 360 950 1,200,000 ::D
No.1 Stringers 1150 -- 775 80 360 800 1,200,000 3:
al
Select Structural Posts and 1250 - 850 80 360 1000 1,200,000 c:
No.1 Timbers 1050 -- 700 80 360 875 1,200,000 F
c
z
C)
0
0
i
.....
EASTERN HEMLOCK-TAMARACK (Surfaced dry or surfaced green. Used at 19% max. m.c.)
~
m
EASTERN HEMLOCK-TAMARACK (NORTH)
Select Structural 1800 2050 1050 85 365 1350 1,300,000 c
No.I 1500 1750 900 85 365 1050 1,300,000 3
No.2 2" to 4" 1250 1450 725 85 365 850 1,100,000 0
No.3 thick 700 800 400 85 365 525 1,000,000 z
Appearance 2" to 4" 1300 1500 875 85 365 1300 1,300,000
wide 525 1,000,000 25-2
Stud 700 800 400 85 365
25-5
Construction 2" to 4" 900 1050 525 85 365 975 1,000,000 and
Standard thick 500 575 300 85 365 800 1,000,000 25-8
Utility 4" wide 250 275 150 85 365 525 1,000,000 (See footnotes
2 through 9,
Select Structural 1550 1750 1050 85 365 1200 1,300,000 11, 13,
No.I 2" to 4" 1300 1500 875 85 365 1050 1,300,000
S7S 85 365 900 1,100,000 IS and 16)
No.2 thick 1050 1200
No. 3 and Stud s and 625
1300
725
1500
325 85
85
365
365
575
1300
1,000,000
1,300,000
Appearance wider 875
1,200,000 25-2
Select Structural Posts and 1300 -- 875 80 365 1000 (See footnotes
No.I Timbers 1050 -- 700 80 365 875 1,200,000
I through 9
and 11)
Select Decking 1500 1700 -- -- -- -- 1,300,000
Commercial 1250 1450 -- -- -- -- 1,100,000
(Continued)
N
EXTREME FIBER IN
--
BENDING Fb
c_... c......,...
Eng~ T-lon slonpsr slon MODULUS U.B.C.STOS
SIZE R-Utl- P...llel Hortzonllll pendlcular Per811el OF UNDER
SPECIES AND CLASSIFI- u... to Groin 5"- to Groin to Groin ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) u... F, F. F.-J. Fe E GRADED
Select Structural Beams and 1400 - 925 80 365 950 1.200,000 25-5
No.I Stringers 1150 - 775 80 365 800 1,200,000 25-8
(See footnotes
Select Structural Posts and 1300 - 875 80 365 1000 1,200,000
No.I Timbers 1050 - 700 80 365 875 1,200,000 2 through 9)
25-8
Select Decking 1500 1700 -
-
-
-
- -
-
1,300,000 (See footnotes
Commercial 1250 1450 - 1,100,000 2 through 9)
(Continued)
N
Ul
...~
TABLE NO. 25-A-1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
...,
Allowable Unit Stresses for Structural Lumber- VISUAL GRADING Y'
(Normal loading. See also Section 2504) ...~
~:;:
Design values in pounds per square inch ~~=
~~;
I
Extreme fiber in
Species and commercial grade Size bending Fb Tension Horizontal Compression Compresston Modulus U.B.C. STDS
classification parallel shear perpendicular parallel of UNDER
WHICH
Single Repetitive- to grain F. to grain to grain elasticity GRADED
member member F. Fc.l. Fe E
f~~
uses uses
EASTERN SPRUCE (Surfaced dry or surfaced green. Used at 19% mu. m.c.l
Select Structural 2" to 4" 1400 1600 800 70 230 1050 1,500,000
No.1
No.2
thick
2" to4"
1200
975
1350
1100
700
575
70
70
230
230
825
650
1,500,000
1,400,000
,f
No.3 wide 550 625 325 70 230 400 1,200,000 =~:
:~
Stud 2" to 4 thick 525 600 300 65 220 400 1,000,000 25-2,25-5
2" to 4" wide and25-8
(See footnotes
Construction 2" to 4" 700 800 400 65 220 750 1,000,000 2 through 9,11
Standard thick 375 450 225 65 220 625 1,000,000 12, 13 and 14)
Utility 4" wide 175 200 100 65 220 400 1,000,000
Select Structural Beams and 1050 - 700 65 220 675 1,100,000 25-8
No.I Stringers 875 - 600 65 220 575 1,100,000 (See footnotes
2 through 9)
Select Structural Posts and 975 - 650 65 220 725 1,100,000
No.I Timbers 800 - 525 65 220 625 1,100,000
(Continued)
N
U1
...~
TABLE NO. 25-A-1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued) N
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504) ~.....
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Compres Com pre
Eng~ Tension slonper slon MODULUS U.B.C.STDS
SIZE neered Repelltlv Perallal Horizonl81 pendlculer Parella! OF UNDER
SPECIES AND CLASSifl. Uses member to Grein Shur to Grein to Grein ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) u... F, F. Fe~ Fe E GRADED
25-2
and25-8
Select Decking 900 1050 - - - - 1,200,000 (See footnotes
Commercial 775 875 -- - - - 1,100,000 2 through 9,
11 and 12)
EASTERN WOODS (Surfaced dry or surfaced green. Used at 190Jo max. m.c.)
Select Structural 1300 1500 775 60 185 850 1,100,000
No.I 2" to 4 1100 1300 650 60 185 675 1,100,000
No.2 thick 925 1050 525 60 185 550 1,000,000
No.3 2" to 4" 500 515 300 60 185 325 900,000 25-5
Stud wide 500 575 300 60 185 325 900,000 and25-8
(See footnotes
lc:
n
Construction 2" to 4 650 750 400 60 185 625 900,000 2 through9
Standard thick 375 425 225 60 185 500 900,000 13, IS and 16)
Utility 4" wide 175 200 100 60 185 325 900,000
Appearance 2" to 4" thick 1100 1300 650 60 185 825 1,100,000
2 to 4" wide
li
Select Structural 1150 1300 750 60 185 750 1,100,000
No.I 2" to4" 950 1100 650 60 185 675 1,100,000 25-S
No.2 thick 775 900 425 60 185 575 1,000,000 (See footnotes
No. 3 and Stud 5" and 450 525 250 60 185 375 900,000 2 through 9,
Appearance wideT 950 1100 650 60 185 825 1,100,000 15 and 16)
....
~
ENGELMANN SPRUCE-ALPINE FIR (ENGELMANN SPRUCE-LODGEPOLE PINE) (Surfaced dry or surfaced green. Used at 191Jo max. m.c.)
Select Structural 1350 1550 800 70 195 950 1,300,000
No.I 2" to 4 1150 1350 675 70 195 750 1,300,000 m
No.2 thick 950 1100 550 70 195 600 1,100,000 0
No.3 2" to 4"
wide
525
1150
600 300
675
70
70
195
195
375
900
1,000,000
1,300,000
3
Appearance 1350 0
Stud 525 600 300 70 195 375 1,000,000 z
Construction 2" to 4" 700 800 400 70 195 675 1,000,000
Standard thick 375 450 225 70 195 550 1,000,000
Utility 4" wide 175 200 100 70 195 375 1,000,000
Selected Decking Decking - 1400 (Surfaced at 151Jo max. m.c. and 1,300,000
Commercial Decking - 1200 used at 151Jo max. m.c.) 1,200,000
(Continued)
N
....
~
TABLE NO. 25A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
EXTREME FIBER IN
BENDING Fb
Compres- Compres-
Eng I Tension sionper- sion MODULUS U.B.C.STDS
SIZE nee red Repetitive- Parallel Horizontal pendicular Parallel OF UNDER
SPECIES AND CLASSIFI Uses member to Grain Shear to Grain to Grain ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses F, F. Fc.L Fe E GRADED
Selected Decking Decking - 1700 (Surfaced at 15"7o max. m.c. and 1,600,000
Commercial Decking - 1450 used at 15"7o max. m.c.) 1,400,000
(Continued)
N
t TABLE NO. 25-A-1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
Extreme fiber in
bending Fb Tension Compression Compression Modulus U.B.C.STDS
Species and Size parallel Horizontal
perpendicular parallel of UNDER
commercial grade classification Single- Repetitive to grain
shear
to grain to grain elasticity WHICH
member member F, F. E GRADED
Fci- F.
uses uses
HEM-FIR (NORTH I (Surfaced dry or surfaced green. Used at 19% max. m.c.l
Select Structural 2" to 3" 1600 1800 925 75 235 1300 1,500,000
No.1 thick 1350 1550 800 75 235 1050 1,500,000
No.2 2" to 4" 1100 1300 650 75 235 800 1,400,000
No.3 wide 625 700 350 75 235 500 1,200,000
Appearance 1350 1550 800 75 235 1250 1,500,000
Stud 625 700 350 75 235 500 1,200,000
Construction 2" to 4" 800 925 475 75 235 925 1,200,000
Standard thick 450 525 275 75 235 775 1,200,000
4"wide 125 235 1,200,000 25-2
Utility 225 250 75 500
(See footnotes
Select Structural 2" to4" 1350 1550 900 75 235 1150 1,500,000 1 through 9
No.1 thick 1150 1350 775 75 235 1050 1,500,000 and 11)
No.2 5" and 950 1100 500 75 235 850 1,400,000
No.3 wider 550 650 300 75 235 550 1,200,000
Appearance 1150 1350 775 75 235 1250 1,500,000
Stud 550 650 300 75 235 550 1,200,000
Select Structural Beams and 1250 -- 725 70 235 900 1,300,000
No. 1 Stringers 1000 -- 500 70 235 750 1,300,000
Select Structural Posts and 1150 -- 775 70 235 950 1,300,000
No.1 Timbers 925 -- 625 70 235 850 1,300,000
Select Decking 1350 1500 -- -- 235 -- 1,500,000 '
Commercial 1100 1300 -- -- 235 -- 1,400,000
....
!m
3
0
IDAHO WHITE PINE (Surfaced dry or surfaced green. Used at 190Jo max. m.c.)
z
Select structural 1350 1550 715 70 190 IIOO 1,400,000
No.I 2" to 4" 1150 1300 650 70 190 875 1,400,000
No.2 thick 925 1050 550 70 190 675 1,300,000
No.3 2" to 4" 525 600 300 70 190 425 1,200,000
Appearance wide II 50 1300 650 70 190 1050 1,400,000
Stud 525 600 300 70 190 425 1,200,000
(Continued)
TABLE NO. 25-A-1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Com pres- Compres
Eng I Tension slonper slon MODULUS U.B.C.STDS
SIZE nee red Repetltlv Parallel Horizontal pendlcular Persllel OF UNDER
SPECIES AND CLASSIFI u... member toGrsln Shear toGrsln toGrsln ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses F, F, F.,.l. Fe E GRADED
LODGEPOLE PINE (Surfaced dry or surfaced green. Used at 190Jo max. m.c.)
Select Structural 1500 1750 875 70 250 1150 1,300,000
No.I 2" to 4" 1300 1500 750 70 250 900 1,300,000
No.2 thick 1050 1200 625 70 250 700 1,200,000
No.3 2" to 4 600 675 350 70 250 425 1,000,000
Appearance wide 1300 1500 750 70 250 1050 1,300,000
Stud 600 675 350 70 250 425 1,000,000
(Continued)
TABLE NO. 25-A-1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Com pres Compres-
Eng!- Tension slonper sion MODULUS U.B.C.STDS
SIZE nee red Repetillv Parallel Horizontal pendicular Parallel OF UNDER
SPECIES AND CLASSIFI Uses member to Grain Shear to Grein to Grein ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses Fr F. F.-L F. E GRADED
MOUNTAIN HEMLOCK-HEM-FIR (Surfaced dry or surfaced green. Used at 19"7o max. m.c.)
Select Structural 1650 1900 975 75 245 1250 1,300,000
No. I 2" to 4" 1400 1600 825 75 245 1000 1,300,000
No.2 thick 1150 1350 675 75 245 775 1,100,000
No.3 2" to 4" 650 725 375 75 245 475 1,000,000
Appearance wide 1400 1600 825 75 245 1200 1,300,000
Stud 650 725 375 15 245 475 1,000,000
Select Structural 2" to 4" 1400 1650 950 75 245 1100 1,300,000 25-4
No.I 1200 1400 *10 75 245 1000 1,300,000 (See footnotes
thick
No.2 S"and 1000 1150 525 75 245 825 1,100,000 2 through 10,
No. 3 and Stud 575 675 300 75 245 525 1,000,000 13, IS and 16) c:
wider
Appearance 1200 1400 *10 75 245 1200 1,300,000 z
Select Structural Beams and 1250 - 850
725
70 245 875 1,100,000 ~
No. I Stringers 1050 - 70 245 750 1,100,000 :D
31:
Select Structural Posts and 1200 - 800 70 245 925 1,100,000 ID
No. I Timbers 950 - 650 70 245 800 1,100,000 c:
r=
c
- - -
Selected Decking
Commercial Decking
Decking
-
1600
1350 - -
-
-
-
-
1,300,000
1,100,000 z
C)
Selected Decking Decking - 1700 (Surfaced at 15"7o max. m.c. and 1,300,000 0
Commercial Decking - 1450 used at 15"7o max. m.c.) 1,200,000
0
1ft
....
:i
N
m
0
3
0
z
NORTHERN ASPEN (Surfaced dry or surfaced green. Used at 19'1o max. m.c.)
Select Structural 1300 1500 750 60 195 850 1,400,000
No.I 2" to 4" 1100 1250 650 60 195 675 1,400,000
No.2 thick 900 1050 525 60 195 525 1,200,000
No.3 2" to 4" 500 575 275 60 195 325 1,100,000
Appearance wide 1100 1250 650 60 195 800 1,400,000
Stud 500 575 275 60 195 325 1,100,000 25-2
(See footnotes
Construction 2" to 4 650 750 375 60 195 600 !,100,000 2 through 9
Standard thick 350 425 200 60 195 500 1,100,000 11, 13
Utility 4" wide 175 200 100 60 195 325 1,100,000 15 and 16)
(Continued)
TABLE NO. 25A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber- VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Compres Com pres-
Engi Tension sion per sion MODULUS U.B.C.STDS
SIZE nee red Repelilive- Parallel Horizontal pendlcular Parallel OF UNDER
SPECIES AND CLASSIFI Uses member to Grain Shear to Grain to Grain ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses F, Fv F~ F, E GRADED
NORTHERN PINE (Surfaced dry or surfaced green. Used at 19o/o max. m.c.)
Select Structural 1650 1850 950 70 280 1200 1.400.000
No.I 2" to 4" 1400 1600 825 70 280 975 1.400.000
No.2 thick 1150 1300 675 70 280 775 1,300,000
No.3 2" to 4" 625 725 375 70 280 475 1,100,000
Appearance wide 1200 1400 800 70 280 1150 1,400,000
Stud 625 725 375 70 280 475 1,100,000
Construction 2" to 4" 825 950 475 70 280 875 1,100,000 25-5
Standard thick 450 525 275 70 280 725 1,100,000 and25-8
Utility 4" wide 225 250 125 70 280 475 1,100,000 (See footnotes
2 through 9,
Select Structural 1400 1600 950 70 280 13, 15 and 16) c
No.I
2" to4"
1200 1400 m 70 280
1100
975
1,400,000
1,400,000
z
~
thick
No.2 s and 950 1100 525 70 280 825 1,300,000
No. 3 and Stud wider 575 650 300 70 280 525 1,100,000 %1
Appearance 1200 1400 m 70 280 1150 1,400,000 3:
IJI
Select Structural Beams and 1250 - 850 65 280 850 1,300,000 c
No. I Stringers 1050 - 700 65 280 725 1,300,000 ;=
0
Select Structural
No.I
Posts and
Timbers
1150 -
-
800 65 280 900 1,300,000 z
C)
950 650 65 280 800 1,300,000
0
Select Decking 1350 1550 - - - - 1,400,000 25-8 0
Commercial 1150 1300 - - - - 1,300,000 (See footnotes
2 through 9) ~
....
"'
CD
N
m
c
3
0
z
NORTHERN SPECIES (Surfaced dry or surfaced green. Used at I 90Jo max. m.c.)
~
Select Structural 1350 1550 775 65 220 1050 1,100,000
No.I 2"to 3" 1150 1300 675 65 220 825 1,100,000 :~
No.2 thick 925 1050 550 65 220 650 1,000,000 '
No.3 2"to4" 525 600 300 65 220 400 900,000
Appearance wide 1150 1300 675 65 220 975 1,100,000
Stud 525 600 300 65 220 400 900,000
25-2
Construction 2" to 4" 675 775 400 65 220 750 900,000 (See footnotes
Standard thick 375 425 225 65 220 600 900,000 2 through 9,
Utility 4" wide 175 200 100 65 220 400 900,000 II, 13,
IS and 16)
Select Structural 1150 1300 775 65 220 900 1,100,000
No. I 2" to4" 975 1150 650 65 220 825 1,100,000
No.2 thick goo 925 425 65 220 675 1,000,000
No. 3 and Stud s and 475 550 250 65 220 425 900,000
Appearance wider 975 1150 650 65 220 850 1,100,000
(Continued)
TABLE NO. 25A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING F
Com pres Compres
Engl. Tension sion per sion MODULUS U.B.C.STDS
SIZE nee red Repellllve Parallel Horizontal pendk:ular Parallel OF UNDER
SPECIES AND CLASSIFJ. Uses member to Grain Shear to Grain to Grain ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses F, F. Fc.l. Fe E GRADED
NORTHERN WHITE CEDAR (Surfaced dry or surfaced green. Used at 19% max. m.c.)
Select Structural 1150 1350 700 65 205 875 800,000
No.I 2" to 4" 1000 1150 600 65 205 675 800,000
No.2 thick 825 950 500 65 205 550 700,000
No.3 2" to 4" 450 525 275 65 205 325 600,000
Appearance wide 850 1000 575 65 205 825 800,000
Stud 450 525 275 65 205 325 600,000
(Continued)
~
Ul
w
TABLE NO. 25-A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING F0
Com pres Compres
Engi Tension sion per sion MODULUS U.B.C.STDS
SIZE neared Repetitive Parallel Horizontal pendicular Parallel OF UNDER
SPECIES AND CLASSIFI- Uses member to Grain Shear to Grain to Grain ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses F, Fv Fc.L Fe E GRADED
RED PINE (Surfaced dry or surfaced green. Used at I9"1o max. m.c.)
Select Structural 1400 1600 800 70 280 1050 1,300,000
No.I 1200 1350 700 70 280 825 1,300,000
2" to 3" 975 575 70 280 1,200,000
No.2 1100 650
thick 525 625 325 70 280 1,000,000
No.3 2" to 4" 400
Appearance 1200 1350 700 70 280 975 1,300,000
wide 525 625 325 70 280 1,000,000
Stud 400
(Continued)
N
Ul
Ul
TABLE NO. 25-A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Contlnued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING N
en
(Normal loading. See also Section 2504)
~
....
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Com pres- Compres-
Eng~ Tension sionper- sion MODULUS U.B.C.STDS
SIZE neered Repelilive- Perallel Horizonlal pendlcular Parallel OF UNDER
SPECIES AND CLASSIFI- Uses member to Grain Sheer to Grain to Grein ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses F, Fv F~ Fe E GRADED
SOUTHERN PINE (Surfaced at 15"7o moisture content, K.D. Used at 150Jo max. m.c.)
Select Structural 2150 2500 1250 105 405 1800 1,800,000
Dense Select Structural 2500 2900 1500 105 475 2100 1,900,000
No.I 1850 2100 1050 105 405 1450 1,800,000
No.I Dense 2" to 4" 2150 2450 1250 105 475 1700 1,900,000
No.2 thick 1550 1750 900 95 405 1150 1,600,000
No. 2Dense 2" to 4" 1800 2050 1050 95 475 1350 1,700,000
No.3 wide 850 975 500 95 405 675 1,500,000
No.3 Dense 1000 1150 575 95 475 800 1,500,000
Stud 850 975 500 95 405 675 1,500,000
25-6
(See footnotes
Construction 2" to4" 1100 1250 650 105 405 1300 1,500,000 3,4, 9,13,
Standard thick 625 725 375 95 405 1050 1,500,000 IS, 16,
Utility 4" wide 275 300 175 9~ 405 675 1,500,000 !Sand 19) c:
z
Select Structural
Dense Select Structural
1850
2200
2150
2500
1200
1450
95
95
405
475
1600
1850
1,800,000
1,900,000 ~
:a
No.I 1600 1850 1050 95 405 1450 1,800,000
No.I Dense 2" to 4" 1850 2150 1250 95 475 1700 1,900,000 3:
No.2 thick 1300 1500 675 95 405 1200 1,600,000 Ill
5" and 1750 475 1,700,000
c:
No.2 Dense
No.3 wider
1550
750 875
800
400
95
95 405
1400
725 1,500,000 r=
c
No.3 Dense
Stud
875
800
1000
900
450
400
95
95
475
405
850
725
1,500,000
1,500,000
z
G)
0
0
~
...
Dense Standard Dec:kina 2"to4" 2150 2450 12SO lOS 475 1700 1,900,000
!m
17SO
Select Deckina
Dense Select Dec:kina
Commercial Dec:kina
thick
2" and
wider
IS 50
1800
1550
2050
1750
900
1050
900
95
9S
95
405
475
405
11SO
l3SO
I ISO
1,600,000
1,700,000
1,600,000
2S-6
(See
3
0
Dense Commercial Dec:kina Deckina 1800 2050 lOSO 9S 475 13SO 1,700,000 footnotes z
4, 9, 15, 16
Dense Structura116 2800 3250 1900 165 475 2300 1,900,000 18 and 19)
2" to 4" 475 l9SO
Dense Structura172 thick
2400 2750 1600 135 1,900,000
Dense Structural 6S 2150 2450 1450 125 475 1750 1,900,000
SOUTHERN PINE (Surfaced dry. Used at 19'1t max. m.c. l
Select Structural 2000 2300 1150 100 405 1550 1,700,000
Dense Select Structural 2350 2700 1350 100 475 1800 1,800,000
No.I 2" to 4" 1700 1950 1000 100 405 1250 1,700,000
No. I Dense thick 2000 2300 1150 100 475 1450 1,800,000
No.2 2" to 4" 1400 1650 825 90 405 975 1,600,000
No.2 Dense wide 1650 1900 975 90 475 1150 1,600,000
No.3 775 900 450 90 405 575 1,400,000 25-6
No.3 Dense 925 1050 525 90 475 675 1,500,000 See footnotes
Stud 775 900 450 90 405 575 1,400,000 3, 4, 9, 13, IS,
16, 18 and 19)
Construction 2" to 4" 1000 1150 600 100 405 1100 1,400,000
Standard thick 51S 61S 3SO 90 405 900 1,400,000
Utility 4" wide 275 300 ISO 90 405 575 1,400,000
(Continued)
TABLE NO. 25-A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Compres- Compres
slon per. slon MODULUS
SPECIES AND
SIZE
CLASSifl.
.!.'Uses
1!d RepetltiY
member
Tension
Parallel
to Grein
Hortzonbll
Shear
pendlcular
to Grein
Parallel
to Grein
OF
ELASTICITY
U.B.C.STDS
UNDER
WHICH
COMMERCIAL GRADE CATION (Single} u... F, F. Fc-L Fe E GRADED
Dense Standard Decking 2" to4" 2000 2300 1150 100 475 1450 1,800,000
Select Decking thick 1400 1650 825 90 405 975 1,600,000
Dense Select Decking 2" and 1650 1900 975 90 475 1150 1,600,000
Commercial Decking wider 1400 1650 825 90 405 975 1,600,000 25-6
Dense Commercial Decking 1650 1900 975 90 475 1150 1,600,000 (See footnotes
Decking 3,4, 9, 13,
15,16, 17,
Dense Structural 86 2600 3000 1750 155 475 2000 1,800,000 18 and 19)
2" to 4" 1450
Dense Structural 72 2200 2550 130 475 1650 1,800,000
thick
Dense Structural65 2000 2800 1300 115 475 1500 1,800,000
95 ITO c:
Select Structural 1600
1850
1850
2150
925
1100 95 315
1050
1200
1,500,000
1,600,000
z
~
Dense Select Structural
No.I 2X"to4" 1350 1550 800 95 ITO 825 1,500,000
No.I Dense thick 1600 1800 925 95 315 950 1,600,000 ::u
No.2 2X" to4" 1150 1300 675 8S ITO 650 1,400,000 31:
No. 2Dense wide 1350 ISOO 775 8S 315 750 1,400,000 Ill
No.3 625 725 375 8S ITO 400 1,200,000 c:
No.3 Dense 725 850 425 8S 315 450 1,300,000 ;=
8S ITO c
Stud 625 725 375 400 1,200,000
z
C)
Construction 2X"to4" 825 925 475 95 ITO 725 1,200,000 0
Standard thick 475 525 ITS 8S ITO 600 1,200,000 0
ITO
Utility 4" wide D) 259 125 8S 400 1,200,000
~
....
iN
m
c
3
0
z
Select Structural 1400 1600 900 85 Z70 900 1,500,000
Dense Select Structural 1600 18SO 1050 8S 315 1050 1,600,000
No.I 1200 13SO 775 8S Z70 825 1,500,000
No.I Dense 2X"to4" 1400 1600 925 8S 315 950 1,600,000
No.2 thick 975 1100 500 85 Z70 675 1,400,000
No.2 Dense 5" and llSO 1300 600 8S 315 800 1,400,000
No.3 wider 550 650 300 8S Z70 425 1,200,000
No.3 Dense 650 750 350 8S 315 475 1,300,000
Stud 575 675 300 8S Z70 425 1,200,000
Dense Standard Decking 2Vz" to4" 1600 1800 925 9S 315 9SO 1,600,000
Select Decking thick 1150 1300 675 8S Z70 6SO 1,400,000
Dense Select Decking 2" and 13SO 1500 775 8S 315 750 1,400,000 25-6
Commercial Decking wider 1150 1300 675 8S Z70 6SO 1,400,000 (See footnotes
Dense Commercial Decking Decking 1350 1500 775 8S 315 750 1,400,000 3,4, 9, 13
15,16, 17,
18 and 19)
No.ISR 1350 - 875 110 Z70 775 1,500,000
No. I Dense SR 5" and 1550 - 1050 110 315 925 1,600,000
No. 2SR thicker 1100 - 725 95 Z70 625 1,400,000
No. 2 Dense SR 1250 - 850 95 315 725 1,400,000
(Continued)
N
Ul
CD
TABLE NO. 25-A-1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PEA SQUARE INCH
EXTREME ABEA IN
BENDING Fb
Compres- Compres-
Eng!- Tension slonper- slon MODULUS U.B.C.STDS
SIZE neered Repetitive Parallel Horizontal pendicular Parallel OF UNDER
SPECIES AND CLASSIFI Uses member to Grain Shear to Grain to Grain ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) uses F, F. Fe.l. Fe E GRADED
(Continued)
TABLE NO. 25A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING F0
Compras- Compras.
Eng~ Tension sion per sion MODULUS U.B.C.STDS
SIZE neerad Repetitive Parallel Horizontal pendicular Parallel OF UNDER
SPECIES AND CLASSIFI Uses member to Grain Shear to Grain to Grain ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses F, F, Fc.L Fe E GRADED
Select Structural Beams and 1150 - 775 70 265 875 1,000,000
No.I Stringers 975 - 650 70 265 725 1,000,000
Select Structural Posts and 1100 - 725 70 265 925 1,000,000 25-4
No. I Timbers 875 - 600 70 265 800 1,000,000 (See footnotes
2 through I 0)
Selected Decking Decking - 1450 - - - - 1,100,000
Commercial Decking - 1200 - - - - 1,000,000
Selected Decking Decking - 1550 (Surfaced at 15o/o max. m.c. and 1,100,000
Commercial Decking - 1300 used at 15% max. m.c.) 1,000,000
WESTERN HEMLOCK (Surfaced dry or surfaced green. Used at 19% max. m.c.)
WESTERN HEMLOCK (NORTH)
1800 2100 1050 90 280 1450 1,600,000
~
Select Structural 25-2
No.I
2" to 4" 1550 1800 900 90 280 1150 1,600,000
thick 1300 1450 750 90 280 900 1,400,000 (See
No.2
2" to 4" 700 800 425 90 280 550 1,300,000 footnote 11) :~
No.3 25-3 ~
wide 1550 1800 900 90 280 1350 1,600,000
Appearance and 25-4
700 800 425 90 280 550 1,300,000
Stud (See footnotes
Construction 2" to 4" 925 1050 550 90 280 1050 1,300,000 2 through 9,
Standard thick 525 600 300 90 280 850 1,300,000 13. 15 and 16)
Utility 4" wide 250 275 150 90 280 550 1,300,000
.....
CD
~
m
c
::::j
0
z
Select Structural 1550 1800 IOSO 90 280 1300 1,600,000 2S-3
No.I 2" to4" 13SO 1550 900 90 280 1150 1,600,000 and 2S-4
No.2 thick 1100 1250 S7S 90 280 975 1,400,000 (See footnotes
No. 3 and Stud s and 650 750 32S 90 280 625 1,300,000 2 through 9,
13, IS and 16)
Appearance wider 1350 1550 900 90 280 1350 1,600,000
Select Structural Beams and 1400 - 825 85 280 1000 1,400,000
No.I Stringers 1150 - 575 85 280 850 1,400,000
Select Structural Posts and 1300 - 875 85 280 1100 1,400,000 2S-3
No.I Timbers 1050 - 700 85 280 950 1,400,000 (See footnotes
2 through 9)
Select Dex Decking 1500 1750 - - 280 - 1,600,000
Commercial Dex 1300 1450 - - 280 - 1,400,000
(Continued)
N
Cll
~
.....
TABLE NO. 2S.A1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
ALLOWABLE UNIT STRESSES IN POUNDS PER SQUARE INCH
EXTREME FIBER IN
BENDING Fb
Com pres Com pres-
Eng~ Tension slon per slon MODULLIS U.B.C.STDS
SIZE neered Repetlllv Par11llal Horizontal pencllcular Par11llal OF UNDER
SPECIES AND CLASSIFI- Uses member toGr11ln Shear toGr11ln toGI'IIIn ELASTICITY WHICH
COMMERCIAL GRADE CATION (Single) Uses F, F, F,.L Fe E GRADED
WESTERN WHITE PINE (Surfaced dry or surfaced green. Used at 190fo max. m.c.)
Select Structural 1350 1550 775 65 235 1100 1,400,000
No.I 2" to 4 1150 1300 675 65 235 875 1,400,000
No.2 thick 925 1050 550 65 235 675 1,300,000
No.3 2" to 4" 525 600 300 65 235 425 1,200,000
Appearance wide 1150 1300 650 65 235 1050 1,400,000
Stud 525 600 300 65 235 425 1,200,000
Selected Decking Decking - 1400 (Surfaced at ISOTo max. m.c. and 1,100,000
Commercial Decking - 11SO used at ISOTo max. m.c.) 1,000,000
(Continued)
N
Ql
Cll
TABLE NO. 25-A-1-ALLOWABLE UNIT STRESSES-STRUCTURAL LUMBER-(Continued)
Allowable Unit Stresses for Structural Lumber-VISUAL GRADING
(Normal loading. See also Section 2504)
Extreme fiber in
bending Fb
Design values in pounds per square inch
U.B.C.STDS
I
Tension
Horizontal Compression Compression Modulus
Size parallel perpendicular parallel of UNDER
Species and commercial grade shear WHICH
classification Single- Repetitive- to grain to grain to grain elasticity
member member Fv E GRADED
Fr Fc.L Fe
uses uses
YELLOW-POPLAR (Surfaced dry or surfaced green. Used at 19% max. m.c.)
Select Structural 2" to 3" 1500 1700 875 80 270 1050 1,500,000
No.1 thick 1250 1450 750 80 270 825 1,500,000
No.2 2" to 4" 1050 1200 625 75 270 650 1,300,000
No.3 wide 575 675 350 75 270 400 1,200,000
Stud 575 675 350 75 270 400 1,200,000
Construction 2"" to 4" 750 875 450 so 270 750 1,200,000 255
Standard thick 425 500 250 75 270 625 1,200,000 See footnotes
Utility 4"wide 200 225 125 75 270 400 1,200,000 1 through 9)
Select Structural 2" to 4" 1300 1500 850 75 270 925 1,500,000 '
No.1 thick 1100 1250 725 75 270 825 1.500.000
No.2 5" and 900 1050 475 75 270 700 1,300,000
No.3 wider 525 600 275 75 270 425 1,200,000
Appearance 1100 1250 725 75 270 1000 1,500,000
Stud 525 600 275 75 270 425 1,200,000 ,.
FOOTNOTES FOR TABLE NO. 25-A-1 ....
CD
'Where eastern spruce and balsam fir are shipped in a combination, the tabulated values for balsam fir shall apply. Cll
N
2The design values shown in Table No. 25-A-l are applicable to lumber that will be used under dry conditions such as in most covered structures. For 2- m
inch- to 4-inch-thick lumber the DRY surfaced size shall be used. In calculating design values, the natural gain in strength and stiffness that occurs as c
lumber dries has been taken into consideration as well as the reduction in size that occurs when unseasoned lumber shrinks. The gain in load-carrying 3
0
capacity due to increased strength and stiffness resulting from drying more than offsets the design effect of size reductions due to shrinkage. For 5- z
inch and thicker lumber, the surfaced sizes also may be used because design values have been adjusted to compensate for any loss in size by shrinkage
which may occur.
3Values for Fb F, and Fe for the grades of Construction, Standard and Utility apply only to 4-inch widths.
4The values in Table No. 25-A-1 for dimension 2 inches to 4 inches are based on edgewise use. Where such lumber is used flatwise, the recommended
design values for extreme fiber stress in bending may be multiplied by the following factors:
WIDTH THICKNESS
2" 3" 4"
2 inches to 4 inches 1.10 1.04 1.00
S inches and wider 1.22 1.16 1.11
Values for decking may be increased by 10 percent for 2-inch decking and 4 percent for 3-inch decking.
5When 2-inch- to 4-inch-thick lumber is manufactured at a maximum moisture content of 15 percent and used in a condition where the moisture content
does not exceed 15 percent, the design values shown in Table No. 25-A-1 for surfaced dry and surfaced green may be multiplied by the following
factors:
TENSION HORIZONTAL COMPRESSION COMPRESSION
EXTREME FIBER IN PARALLEL SHEAR PERPENDICULAR TO PARALLEL TO MODULUS OF
BENDING Fb TO GRAIN F, F. GRAIN F0 .l. GRAIN Fe ELASTICITY E
1.08 1.08 1.05 1.00 1.17* 1.05*
8Tbe tabulated horizontal shear values shown herein for lumber 4 inches and thinner shall be multipled by a factor of 0.92 when such lumber is
manufactured unseasoned.
Specific horizontal shear values may be established by using the following tables when the length of split or check is known:
GRADE
(2 lnct.e to 4 Inc'- thick, 5 lnct.e and wider) Multiply tabulated F, values by
(21h Inc'- to 4 Inc'- thick, 5 lnct.e and wider)
(Includes "Dense" grades) 5 lnct.e and& lnct.e wide Slnct.ewlda 10 lnct.e and wider
Stud 1.00
I6Design values for all species of Stud grade in 5-inch and wider size classifications apply to 5-inch and 6-inch widths only.
17Repetitive member design values for extreme fiber in bending for southern pine grades of Dense Structural 86, 72 and 65 apply to 2-inch to 4-inch
thicknesses only.
IBWben 2-inch- to 4-inch-thick southern pine lumber is surfaced dry or at 15 percent maximum moisture content (KD) and is designed for use where the
moisture content will exceed 19 percent for an extended period of time, the design values in Table No. 25-A-l for the corresponding grades of 2Y2-
inch- to 4-inch-thick surfaced green southern pine lumber shall be used. The net green size may be used in such designs.
I9Wben 2-inch- to 4-inch-thick southern pine lumber is surfaced dry or at 15 percent maximum moisture content (KD) and is designed for use under dry
conditions, such as in most covered structures, the net DRY size shall be used in design. For other sizes and conditions of use, the net green size may
be used in design.
20Values apply only to ponderosa pine graded under U .B.C. Standard No. 25-2.
c:
z
~
::u
31:
IJI
c:
;::::
c
z
C)
0
0
i
!-
TABLE NO. 25-A-2-ALLOWABLE UNIT STRESSES FOR MACHINE STRESS RATED STRUCTURAL LUMBER
8
(Values listed are for normal loading conditions. See also Section 2504. )
;; m
p
Design values In pounds per square Inch 9
i c
Extreme fiber In
Grading rules bending Fb 7 Tension Compression Modulus
Size
U.B.C. Std. No. parallel parallel of
Grade Designation IO ClassHicatlon
(See footnotes Single- Repetitive- to grain to grain elaatlcity E
1,2,3,4) member member F, Fe
uses uses 1
900f-1.0E
1200f1.2E
1350f-1.3E
3.4
1,2,3.4
2.4
900
1200
1350
1050
1400
1550
350
600
750
725
950
1075 II
1,000,000
1,200,000
1,300,000
Ij
1450f-1.3E 1,3,4 1450 1650 800 1150 1,300,000
1500f-1.3E
1500f-1.4E
1650f-1.4E
2
1,2,3,4
2
1500
1500
1650
1750
1750
1900
900
900
1020
I 1200
1200
1:i20
1,300,000
1,400,000
1,400,000
1650f-1.5E 1,2,3,4 1650 1900 1020 1320 1,500,000
1800f-1.6E
195Cf-1.5E
1,2,3.4
2
Machine
rated
1800
1950
2050
2250
1175
1375
1450
1550
1,600,000
1,500,000
I
,.
lumber 1950 2250 1375
1950f-1.7E 1,2.4
2" thick
1550 1,700,000 i
2100f-1.8E 1,2.3.4 2100 2400 1575 1700 1,800,000
or less
22501-1.6<: 2 All widths 2250 2600 1750 1800 1,600,000
2250f-1.9E 1,2,4 2250 2600 1750 1800 1,900,000
2400f-1.7E
2400f-2.0E
2
1.2.3.4
1,2,4
I 2400
2400
2550
2750
2750
2950
1925
1925
2050
1925
1925
2050
1,700,000
2,000,000
2,100,000
)i
25501-2.1 E
III
2700f-2.2E 1,2,3.4 2700 3100 2150 2150 2,200,000
2850f-2.3E 2 2850 3300 2300 2300 2,300,000
3000f-2.4E 1,2 3000 3450 2400 2400 2,400,000
3150f-2.5E 2 3150 3600 2500 2500 2,500,000
3300f-2.6E 2 3300 3800 2650 2650 2,600,000
Nominal
width (in.) 3" 4" 5" 6" 8" 10" 12" 14"
Factor 1.06 1.10 1.12 1.15 1.19 1.22 1.25 1.28
Sfootnotes I, 2, 9, II and 19 to Table No. 25-A-1 apply also to machine stress rated lumber. c
9Design values for horizontal shear Fv and compression perpendicular to grain Fc;-1. for lumber used under dry conditions are as follows: z
~
:II
31:
IJI
c
r=
0
zt:)
0
~
-
IN
m
~
Douglas
Rr-lMch
I Rr-south
Douglas I Hem-Fir
Western
Hemlock Pine
E=nn
Cedar
Southern Pine
KD S.DRY
Mixed
Speclest
0
z
Horizontal Shear Fv
95 I 90 I 75 90 70 70 75 95 90 70
Compression Perpendicular to Grain Fe_!_
STRUCTURAL I CD
(Use Group 1 Stresses)
STRUCTURAL II CD
(Use Group 3 Stresses)
CD SHEATHING
m
0
::::j
4. Shear, rolling, in the Marine and i5
plane of plies Structural I 63 75 63 75
z
Parallel or perpendicular to
face grain Structural II 49 56 49 56
(at 45 to face grain use I '13 FJ All Other 44 53 44 53 48
5. Bearing (on face) I 210 340 210 340 340
Perpendicular to plane 2,3 135 210 135 210 210
of plies 4 105 160 105 160 160
6. Modulus of elasticity I 1,500,000 1,800,000 1,500,000 1,800,000 1,800,000
In bending in plane of plies 2 1,300,000 1,500,000 1,300,000 1,500,000 1,500,000
Face grain parallel or 3 1,100,000 1,200,000 1,100,000 1,200,000 1,200,000
perpendicular to span 4 900,000 1,000,000 900,000 1,000,000 1,000,000
I See U.B.C. Standard No. 25.9forplywood species groups. ForC-C and C- IDENTIFICATION INDEX
D, the combination of Identification Index and panel thickness determines
the species group and therefore the stress permitted, as in the following THICKNESS
(Inches) 1210 1610 20/0 24/0 32/16 42/20 48/24
table.
2Wet condition of use corresponds to a moisture content of 16 percent or Y,, 4 3 I
more. Y. 4 3 I
3Dry condition of use corresponds to a moisture content of less than 16 1
/o 4 I
percent.
Y. 3 I
.y. 3 I
!. 4 3
*30/12-1.", and 36/16-Y. "-Use Group 4 stresses.
...,
..., c.n
a,
.....
c.n
TABLE NO. 25-C1 PART A-ALLOWABLE UNIT STRESSES FOR STRUCTURAL GLUED-LAMINATED TIMBER
FOR NORMAL LOADING DURATION1 2 3 4
Members stressed principally In bending with load applied perpendicular to the wide faces of the laminations
I' I'
lo Wide flees at to Wide FIC8I at
t..ninltlonl I.Mninltions
AXIALLY LOADED
SPECIES
co.lfiA.
OUTBI LAJII.
NAT10fj$/
l10N CORE y
SYIIIOI. X
~
11()NS5 EJ1rlme fiber In Bending Compreuion Perpendlcuia'
Fou to Grain Fe l. u
Modulus
~
rtn.lcn Ellrlme Compmsion Tenrioll Compmsion
Zone Horizontal Modulus at Fiber in ~leu- Horizonlll Modulus at Pnllel Pnllel at
SM. Bencling6 11 to Grain
~ ~
Stnuedin Streaed In Elasllcily SM. Elasllcily toGnin to Gnln
rtn.Jcnl Tenrion7 Tonsion Face FlfV( E.. F~~yy Felw F.,.. Ey,. F, Fe
pol pol pol psi psi 110 .. psi pol psi psi 110 .. psi pol psi 110 .. psi
1 2 3 4 5 6 7 8 9. 10 11 12 13 14 15
Visually Graded Western Species
c:
16F-V1 DFIWW 385 8 9 385 8 140 1.3 950 190 130 1.1 675 975 1.1 z
16F-V2
16F-V3
HFIHF
DF/DF
1600 800
385 8 9
38510
385 8 165
24510
1.5
155
1450
1.4
385
1250
145
245
1.5 950
135
1550
1.3 875 1300 1.3
1.5
a
::u
3:
The following two combinations are lnlltnded for atralght or slightly cambsred members for dry usa and industrial appeara,__, IJI
c:
i6F-V4 joF!N3WW 450 385 8 9010 1.5 900 i90 130 1.3 650 600 1.3 r=
0
1600 800
16F-V5 DF/M3DF 450 385 8 9013 1.6 1000 270 135 1.5 750 875 1.5 z
C)
0
0
~
The following two combinations are balanced and arelnt8nded for members continuous or c:antlleWnld over supports and provide
equal capacHy In both positive and negative banding.
9 385 8
16F-V6 DF/DF 385 8 165 1.5 1450 385 145 1.4 950 1550 1.5
1600 1600 10
16F-V7 HFIHF 245 245 10 155 1.4 1200 245 135 1.3 850 1350 1.3
20F-V1 DF!WW 450 385 8 140 1.4 1000 190 130 1.2 750 1000 1.2
20F-V2 HFIHF 385 10 245 10 155 1.5 1200 245 135 1.4 975 1350 1.4
2000 1000
20F-V3 DF/DF 450 385 10 165 1.6 1450 385 145 1.5 1000 1550 1.5
4108 9 385 10 165 1.6 1450 145
20F-V4 DFIDF 385 1.6 1000 1550 1.6
The following two comblnlltlons are Intended for lltralght or slightly cambared mambars for dry use and industrial appearance."
20F-V5 pF!N3WW 450 385 10 90" 1.6 1000 190 135 1.3 750 725 1.3
2000 1000
20F-V6 DFIM3DF 450 385 10 90" 1.6 1000 270 135 1.5 775 900 1.5
The following three combinations are balanced and are Intended for mambars continuous or cantilevered over supports and provide
equal c:apacHy In both positive and negative banding.
20F-V7 DF/DF 450 450 165 1.6 1450 385 145 1.6 1000 1600 1.6
9 4108 9
20F-V8 DF/DF 2000 2000 4108 165 1.7 1450 385 145 1.6 1000 1600 1.6
20F-V9 HFIHF 385 10 385 10 155 1.5 1400 245 135 1.4 975 1400 1.4
22F-VI DF!WW 450 385 8 140 1.6 1050 190 130 1.3 850 1100 1.3
22F-V2 HFIHF 385 10 385 10 155 1.5 1250 245 135 1.4 950 1350 1.4
2200 1100
22F-V3 DF/DF 450 385 8 165 1.7 1450 385 145 1.6 1050 1500 1.6
410" 9 385 8 165 1.7 1450 145
22F-V4 DF/DF 385 1.6 1000 1550 1.6
The following two comblnlltlons are Intended for lltralght or slightly cambared members for dry use and lndulltrlal appearance. 11
22F-V5 _Ef!N3WW 450 385 8 90" 1.6 1100 190 135 1.4 800 725 1.4
2200 1100
22F-V6 DF/M3DF 450 385 8 90" 1.7 1250 270 135 1.6 900 925 1.6
(Continued)
TABLE NO. 25-C-1 PART A-ALLOWABLE UNIT STRESSES FOR STRUCTURAL GLUED-LAMINATED TIMBER
FOR NORMAL LOADING DURATION1 2 3 4 -(Continued)
Members stressed principally In bending with load applied perpendicular to the wide faces of the laminations
t'
to Wide flees of to Wide Faces of
I'
Umlnltions LaminationS
rTi
SPECIES
COIIBINA- OUTER LAlli-
NATlONSI
y w-Y AXIALLY L.OAilED
TlON CORE y
SYIIBOL X
L.AJIINA.
l10NSS Extnme F1ber in Bending Compression Perpendicular
Fou to Grain Fe .Lu
Tension eanr:lon Extnme Comp!ISSion TWision Compresalon Modulus
Bending" 18 ~iar
Zone Horizontal Modulus of Fiber in Horizontal Modulus of Patallel Patallel at
sr- Elssticity to Grain sr- Elasticity
~
Stnaedin Stnaedln Elasticity to Grain to Grain
Tention6 TW1slon7 Tension Face Fvu E.. Fow Fe.Lyy Fvyy Eyy F, Fe E
psi psi psi psi psi 1 tO""psi psi psi psi x10"" psi psi psi x10"" psi
1 2 3 4 s 6 7 8 9 tO 11 12 13 14 15
Visually Graded Western Species -(Continued)
The following three combinations are balanced and are intandad lor members continuous or cantilevered over supports and provide
equal capacity in both positive and nagative bending. c:
22F-V7 DFIDF 450 450 i65 1.8 1450 385 145 1.6 1100 1650 1.6 z
22F-V8 DF/DF 2200 2200 410" 9 4108 9 165 1.7 1450 385 145 1.6 1050 1650 1.6 ~
::D
22F-V9 HFIHF 385 10 385 10 155 1.5 1250 245 135 1.4 975 1400 1.4 3::::
ID
24F-V1 DF/WW 450 450 140 1.7 1250 190 130 1.4 1000 1300 1.4 c:
j=
24F-V2 HFIHF 38510 385 10 155 1.5 1250 245 135 1.4 950 1300 1.4 c
24F-V3 DFIDF 2400 1200 450 385 8 i65 1.7 1500 385 145 1.6 1100 1600 1.6
z
C)
24F-V4 DFIDF 450 450 165 1.8 1500 385 145 1.6 1150 1650 1.6 0
0
24F-V5 DFIHF 450 450 155 1.7 i350 245 140 1.5 1100 1450 1.5 Iii
....
CD
~
The following two combinations are Intended for straight or slightly cambered members for dry use and Industrial appearance." m
0
24F-V6 jDFIN3WW 450 385 8 90" 1.7 1200 190 140 1.5 950 800
2400 !200
1.5
3
24F-V7 DF/M3DF\ 450 385 8 9013 1.7 1250 270 135 1.6 900 950 1.6 0
z
The following threa combinations are balanced an~~re Intended for members continuous or cantilevered over supports and provide
equal ca~ ac In both positive and negative bending.
24F-V8 DF/DF 450 450 165 1.8 1450 385 145 1.6 1100 1650 1.6
24F-V9 HFIHF 2400 2400 385 10 385 10 !55 1.5 1500 245 135 1.4 1000 1450 1.4
24F-VIO DFIHF 450 450 155 1.8 1400 245 140 1.6 1150 1600 1.6
Wet-use factors 2 0.8 0.8 0.667 0.667 0.875 0.833 0.8 0.667 0.875 0.833 0.8 0.73 0.833
E-Rated Western Species
l6F-El WWIWW 19014 19014 140 1.3 1050 190 125 1.2 725 925 1.2
16F-E2 16 HF/HF 1600 800 245 15 245 15 !55 1.4 1250 245 135 1.3 825 1200 1.3
16F-E3 DFIDF 385 15 385 15 165 1.6 1450 385 145 1.5 975 1600 1.5
The following two combinations are Intended tor straight or slightly cambered members for dry use and Industrial appearance.''
16F-E4 jDFIN3WW 385 15 385 15 9012 1.6 900 190 130 1.3 675 675 1.3
1600 800
16F-E5 DF/M3DF 385 15 385 15 9013 1.6 1050 270 135 1.5 700 900 1.5
The following two combinations are balanced and are Intended lor members continuous or cantilevered over supports and provide
equal capacity In both positive and negative bending.
16F-E6 DF/DF 385 15 385 15 165 1.6 1500 385 145 1.5 1000 1600 1.5
1600 1600
!6F-E7 16 HFIHF 245 15 245 15 !55 1.4 1250 245 135 1.3 850 1150 1.3
20F-El WW!WW !9014 !9014 140 1.6 1100 190 125 1.3 800 1050 1.3
20F-E2 16 HFIHF 2000 1000 385 15 385 15 !55 1.6 1400 245 135 1.4 925 1550 1.4
20F-E3 DFIDF 385 15 385 15 165 1.7 1550 385 145 1.6 1050 1650 1.6
(Continued)
N N
Cll TABLE NO. 25-C-1 PART A-ALLOWABLE UNIT STRESSES FOR STRUCTURAL GLUED-LAMINATED TIMBER Ul
0
FOR NORMAL LOADING DURATION 1 2 3 4 -(Continued)
Members stressed principally in bending with load applied perpendicular to the wide faces of the laminations
9....
BENDING ABOUT X-X AXIS BENDING ABOUT YY AXIS
L.olded Perpendicullr loldod Plnllel
I' ~
lo Wide Ftc:el ol to Wide Faces ol
l..aminlllona lMninltions
rr1
w-Y
AXIALlY LOADED
SPECIES y
C()l8ljA. OUTER LAlli-
110N NATIONSI
CORE y
SYJ8JL u.NA- X
11()NS5
,_
Exlnme Fiber in Bending Compression Pelpondicullr
to Gl1in Fc.lu
~
Tenlioll Extreme Compression Tension Compression Modulus
Zalle Horizonlal llodulusol Fiber in ~icullr Horizonlal Modulus of Parallel Parallel ol
.,..,.,.
Stlwuedln SIIWued In
~
g_. Ellsllcily Bending' 18 to Gnlin g_. Ellsllcily to Grain to Gl1in Elllllcily
psi
Tension' Tension Flee
psi psi psi '"""
psi
fxx
110-" psi
Fbyy
psi
'J..I'Y
psi
Fvyy
psi
~
110-" psi
F,
psi '
psi
E
110-" psi
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
E-Rated Western Species-(Continued)
The following two combinations are lnlanded for straight or slightly cambered members for dry use and Industrial appearance. 11
c
20F-E4 joFIN3WW 450 385 15 9()12 !.6 1100 190 130 1.4 800 700 1.4 z
20F-E5 DF!N3DF
2000 1000
385 15 385 15 9()13 1.7 1300 270 135 1.6 825 975 1.6 ~
:0
The following two combinations are balanced and are intended for members continuous or cantilevered over supports and provide 3:::
equal capacity in both poaithre and negative bending. Ill
20F-E6 OF/OF 385 15 385 15 165 1.7 1600 385 145 1.6 1150 i650 1.6 c
2000 2000 r=
c
20F-E7 16 HFIHF 385 15 385 15 155 1.6 1500 245 135 1.4 1050 1550 1.4
22F-EI OF/OF 450 385 15 165 1.7 i550 385 145 1.6 1050 1600 1.6
z
C)
2200 1100 0
22F-E2 16 HFIHF 385 15 385 15 155 1.6 1400 245 135 1.4 950 1400 1.4 0
~
The following two combinations are lntandad for straight or slightly cambered members for dry usa and Industrial appearance. 11 .....
22F-E3 jDFINJWW! 450 385" 9012 1.7 1250 190 135 1.4 825 750 1.4
iN
22f-E4 DFIN3Df
2200 1100
450 1.8 1350 270 1.6 950 950 1.6
m
385" 90" 135 0
The following two combinations are balanced and are Intended for members continuous or cantilevered over supports and provide ::::j
aqual capacity In both posltfw and negatfw banding. 5
z
22F-E5 DFIDF 450 450 165 1.7 1650 385 145 1.6 1100 1650 1.6
2200 2200
22f-E6 16 Hf!HF 385" 385" 155 1.7 1550 245 135 1.5 1050 1500 1.5
24f-E1 Df/Df 450 450 165 1.8 1550 385 145 1.6 1100 1600 1.6
24f-E2 16 HFIHF 385" 385" 155 1.7 1450 245 135 1.5 1000 1400 1.5
24f-E3 Df!HF 450 385" 155 1.8 1500 245 135 1.5 1050 1550 1.5
2400 1200
24f-E4 DF/DF 450 450 165 1.8 1650 385 145 1.7 1100 1700 1.7
24F-E5 Df/DF 450 385" 165 1.8 1650 385 145 1.6 1100 1550 1.6
24F-E6 16HFIWW 385" 385" 140 1.8 1250 190 130 1.4 925 1350 1.4
The following th- combinations arelnllended for straight or slightly cambered members for dry usa and Industrial appearance. 11
24F-E7 pFIN3WW 450 450 9012 1.9 1400 190 135 1.6 975 875 1.6
24F-E8 DFIN3DF 2400 1200 450 450 90" 1.9 1400 270 135 1.7 1000 1050 1.7
24f-E9 16 HFIN3HF 385" 385" 9012 1.8 1350 245 135 1.6 950 825 1.6
The following four combinations are balanced and are lntanded for members continuous or cantilevered ovar supports and provide
equal capacity In both positive and negative bending.
24F-EIO Df/DF 450 450 165 1.9 1850 385 145 1.7 1300 1750 1.7
24F-EI1 16 HFIHF 385" 385" 155 1.8 1600 245 135 1.5 1150 1550 1.5
2400 2400
24F-EI2 Df!HF 450 450 155 1.9 1750 245 135 1.6 1200 1600 1.6
24F-E13 DF/DF 450 450 165 1.8 1950 385 145 1.7 1250 1700 1.7
Wet-use factor.; 2 0.8 0.8 0.667 0.667 0.875 0.833 0.8 0.667 0.875 0.833 0.8 0.73 0.833
I>)
Cll
..... (Continued)
N
CD
N
TABLE NO. 25-C-1 PART A-ALLOWABLE UNIT STRESSES FOR STRUCTURAL GLUED-LAMINATED TIMBER
FOR NORMAL LOADING DURATIONt 2 3 4 -(Continued)
Members stressed principally in bending with load applied perpendicular to the wide faces of the laminations
I' I'
toWidt~of toWidt~of
Lllninlliona Uminlliona
AXIAllY LOADED
SPECIES
COIIIIIIb\- OUTER WI-
110N NAl10NSI
SYIIIOL CORE y X
LAIINA-
TJONS5 Eitr.M Fllllr In Bending Comp'lulon f'llpendicuia'
Fbu to Gnlin Fe .1.""
~ ~
Tension Eitr.M Compnulon Tension lladulus
Zone Horizolllll lladulus of Aberln ~icu- Horizontlll Modulus of Pnllll of
Elllticlty Bending' 11 toGnln
~
Stnaedln Stnaed In Sllelr Sllelr Elllticlty to Gnln to Gnln Elllticlty
TIIISicJn8 Tension' Tension Flee Fona E.x F~~yy Fe.LYI' F.,. fyy F, Fe E
poi poi poi poi poi 110 ... poi poi poi poi 110 ... poi poi poi 110 ... poi
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Visually Graded Southern Pine
16F-V1 SPISP 385 8 9 3858 200 1.4 1450 385 175 1.3 950 1450 1.3 c:
z
385 8 385 8
~
16F-V2 SP/SP 1600 9 200 1.4 1600 175 1.4 1.4
800 385 1000 1550
16F-V3 SPISP 450 450 200 1.4 1450 385 175 1.3 975 1450 1.3 ::u
31:
The following combination Is Intended for atl'lllght or slightly cambered members for dry use and Industrial appearance." ID
16F-V4 SP/SP 1600 800 385 8 9 385 8 90" 1.3 975 270 150 1.2 650 950 1.2 c:
r=
c
zC)
0
0
~
.....
The lot lowing combination Ia balanced and lnlendecllor members continuous or cantllewred over supports and provideS equal capacity IN
In both positive and negative banding.
m
16F-V5 SP/SP 1600 1600 385 8 9 385 8 9 200 1.4 1600 385 175 1.4 1000 1550 1.4 c
20F-Vl SP/SP 450 385 8 200 1.5 1450 385 175 1.4 1000 1450 1.4 3
0
20F-V2 SP/SP 2000 1000 450 385 8 200 1.6 1450 385 175 1.4 1050 1550 1.4 z
9 200 175
20F-V3 SPISP 385 8 385 8 1.4 1600 385 1.4 1000 1500 1.4
The fOllowing combination Is lnlendecllor straight or slightly cambarad members lor dry usa and Industrial appearance."
20F-V4 SP/SP 2000 1000 450 385 8 9()17 1.5 1100 270 !50 1.3 725 950 1.3
The fOllowing combination Is balanced and lntandecllor members continuous or cantilevered over supports and provideS equal capacity
In both positive and negative banding.
20F-V5 SP/SP 2000 2000 450 450 200 1.6 1450 385 175 1.4 1050 1550 1.4
22F-Vl SPISP 450 450 200 1.6 1600 385 175 1.5 1050 1650 1.5
22F-V2 SP/SP 2200 1100 385 8 9 385 8 200 1.4 1600 385 175 1.4 1000 1500 1.4
22F-V3 SP/SP 450 385 8 200 1.6 1500 385 175 1.4 1050 1500 1.4
The fOllowing combination Is lnlendecllor straight or slightly cambered membara lor dry usa and Industrial appearance.''
22F-V4 SP/SP 2200 1100 450 385 8 9()17 1.6 1250 270 !55 1.4 825 1000 1.4
The lotlowtng combination Is balanced and lnlendecllor members continuous or cantilevered over supports and provideS equal capacity
In both positive and negative banding.
22F-V5 SP/SP 2200 2200 450 450 200 1.6 1600 385 175 1.5 1050 1600 1.5
24F-Vl SP/SP 450 385 8 200 1.7 1500 385 175 1.5 1100 1350 1.5
24F-V2 SP/SP 2400 1200 450 450 200 1.7 1600 385 175 1.5 1100 1600 1.5
24F-V3 SP/SP 450 450 200 1.8 1600 385 175 1.6 [[50 1700 1.6
The lotlowtng combination Is lnlendecllor straight or slightly cambered members lor dry usa and Industrial appearance.''
SP/SP 2400 1200 450 385 8 9()17 1.7 1250 270 !55 1.4 1.4
24F-V4 850 1050
(Continued)
TABLE NO. 25-C-1 PART A-ALLOWABLE UNIT STRESSES FOR STRUCTURAL GLUED-LAMINATED TIMBER
FOR NORMAL LOADING DURATION, 2 3 4 -{Continued)
Members stressed principally In bending with load applied perpendicular to the wide faces of the laminations
.CJ I'
Loeded l'lrplndlc:ullr Loeded Pnllll
to Wide "-of to W"ode " - of
LlrnirllticJIIs LlrnirllticJIIs
AXIALLY LOADED
SPECIES
Ol1TER I..AJII.
COIIIIINA- NATIOIISI
TIOH CORE
SYMBOl. y X
LAJIINA.
l1()N55 Exnme Fiber in Bending Compmslon l'lrplndlc:ullr
Fbu to Grain Fciu
~
Ex1rlme
~ ~
Tension Tension Modulus
Zone Horizontal Modulus of Rber in Horizon1al Modulus of Pnllll of
Slnaedin Slnaedin Compmslon ~ Elasticity Bendtngl' to Grain ~ Elalticity to Grain to Grain Elulicily
Tension" Tension' Tension Face Face FVJVt E.. F~~yy Fc.l.yy Fvyy fyy F, Fe E
psi psi psi psi psi 110"" psi psi psi psi 110"" psi psi psi 110"" psi
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Visually Graded Southern Pine -{Continued)
The following combination Is balanced and Intended for members continuous or cantlleverad over supports and provides equal capacity
In both poaltlve and negative banding.
c
24F-V5 SP/SP 2400 2400 450 450 200 1.7 1600 385 175 1.5 1150 1700 1.5 z
Wet-use factor2 0.8 0.8 0.667 0.667 0.875 0.833
E-Rated Southern Pine
0.8 0.667 0.875 0.833 0.8 0.73 0.833 a
:a
3:
16F-E1 SP/SP 1600 800 385 15 385 15 200 1.6 1550 385 175 1.5 1050 1600 1.5 al
c
The following combination Is Intended for straight or slightly cambarad members for dry usa and Industrial appearance.'' r=
c
16F-E2 SPISP 1600 800 385 15 385 1' 9()17 1.6 950 270 145
The following combination Is balanced and Intended for members continuous or cantlleverad over supports and provides equal capacity
1.3 700 1050 1.3 z
G')
In both poaltlve and negative banding. 0
0
16F-E3 SP/SP 1600 1600 385 1' 385 1' 200 1.6 1700 385 175 1.5 1100 1650 1.5
20F-E1 SP/SP 2000 1000 385 1' 385 1' 200 1.7 1600 385 175 1.5 1050 1600 1.5
Iii
....
!m
The following combination Ia lnlended for straight or slightly cambered membars for dry u.. and Industrial appearance.'' c
20F-E2 SPISP 2000 1000 450 385" 90" 1.6 1100 270 150 1.4 750 1000 1.4 3
0
The following combination Ia balanced and inllllnded for membara continuous or cantllewred over supports and provides equal capacity
In both poaltlw and negatiw banding.
z
20F-E3 SPISP 2000 2000 385" 385" 200 1.7 1800 385 175 1.5 1150 1700 1.5
22F-EI SP/SP 2200 1100 450 385" 200 1.7 1600 385 175 1.5 1050 1650 1.5
The following combination Ia lnlended for straight or slightly cambered membara for dry u.. and industrial appearance.''
22F-E2 SPISP 2200 1100 450 385" 90" 1.6 1250 270 155 1.4 850 1050 1.4
The following combination Ia balanced and lnlended for mambars continuous or cantl'-red over supports and provides equal capacity
In both poaltlw and negative banding.
22F-E3 SP/SP 2200 2200 450 450 200 1.7 1750 385 175 1.5 1150 1650 1.5
24F-E1 SPISP 450 385" 200 1.8 1600 385 175 1.6 1100 1750 1.6
2400 1200
24F-E2 SP/SP 450 450 200 1.9 1700 385 175 1.6 1150 1700 1.6
The following combination Ia lnlended for straight or slightly cambered members for dry u.. and industrial appearance.''
24F-E3 SP/SP 2400 1200 450 450 90" 1.8 1300 270 155 1.5 950 1100 1.5
The following combination Ia balanced and lnllllnded for mambars continuous or cantil-red over supports and provides equal capacity
In both poaltlw and negative banding.
24F-E4 SP/SP 2400 2400 450 450 200 1.8 2000 385 175 1.6 1250 1750 1.6
Wet-use facto~ 2 0.8 0.8 0.667 0.667 0.875 0.833 0.8 0.667 0.875 0.833 0.8 0.73 0.833
(Continued)
N
Ul
c;,
....
(Continued)
N
011
Ql
I The combinations in this table are applicable to members consisting of four or more laminations and are intended primarily for members stressed in
bending due to loads applied perpendicular to the wide faces of the laminations. Design values are tabulated, however, for loading both perpendicular
and parallel to the wide faces of the laminations. For combinations and design values applicable to members loaded primarily axially or parallel to the
wide faces of the laminations, see Table No. 25-C-1, Part B. For members oftwo or three laminations, see Table No. 25-C-1, Part B.
2The tabulated design values are for dry conditions of use. To obtain wet-use design values, multiply the tabulated values by the factors shown at the end
of the table.
3Tbe tabulated design values are for normal duration of loading. For other durations of loading, see Section 2504 (c) 4.
4The 22F and 24F combinations for members 15 inches and less in depth may not be readily available and the designer should check on availability prior
to specifying. The 16F and 20F combinations are generally available for members 15 inches and less in depth.
5Tbe symbols used for species are DF =Douglas fir-larch, HF =hem-fir, WW =western woods or Canadian softwood species, and SP =southern pine.
(N3 refers to No. 3 structural joists and planks or structural light framing grade.)
6Tbe tabulated design values in bending are applicable to members 12 inches or less in depth. For members greater than 12 inches in depth, the
requirements of Section 2511 (d) 5 apply.
7Design values in this column are for extreme fiber stress in bending when the member is loaded such that the compression zone laminations are
subjected to tensile stresses. The values in this column may be increased 200 psi where end joint spacing restrictions are applied to the compression
zone when stressed in tension.
SWhere specified, this value may be increased to 450 psi by providing in the bearing area at least one dense 2-inch nominal thickness lamination of
Douglas fir-larch for western species combinations, or southern pine for southern pine combinations. These dense laminations must be backed by a
medium grain lamination of the same species.
9For bending members greater than 15 inches in depth, the design value for compression stress perpendicular to grain is 450 psi on the tension face. c:
z
IOWhere specified, this value may be increased by providing at least two 2-inch nominal thickness Douglas fir-larch laminations in the bearing area.
The compression perpendicular to grain design values for Douglas fir-larch are 385 psi for medium grain and 450 psi for dense. ~
::D
II These combinations are for dry conditions of use only because they may contain wane. They are recommended for industrial appearance grade and for 3:
straight or slightly cambered members only. If wane is omitted these restrictions do not apply. IJI
12Where specified, this value may be increased from 90 psi to 140 psi for western woods and from 90 psi to 155 psi for hem-fir by eliminating wane. c:
13Wbere specified, this value may be increased from 90 psi to 140 psi by eliminating either coarse grain material or wane throughout the member, and
r=c
from 90 psi to 165 psi by eliminating both coarse grain material and wane. z
C)
0
0
~
14The compression perpendicular to grain design value of 190 psi is based on the lowest strength species of the western woods group. If at least one 2- ....
inch nominal thickness lamination of -rated hem-fir with the same E value, or -rated Douglas fir-larch 200,000 psi higher in modulus of elasticity I
~
()than that specified is used in the bearing area on the face of the member subjected to the compression perpendicular to grain stress, Fc..L may be
increased to 245 psi. If at least two 2-inch nominal thickness laminations of -rated hem-fir with the same E value, or -rated Douglas fir-larch m
0
200,000 psi higher in modulus of elasticity than that specified are used in the bearing area on the face of the member subjected to the compression ::::;
perpendicular to grain stress, Fc..L may be increased to 385 psi. 0
I5Where specified, this value may be increased to 450 psi by providing in the bearing area at least one 2-inch nominal thickness lamination of Douglas z
fir-larch for western species combinations, or one 2-inch nominal thickness lamination of southern pine for southern pine combinations having a
modulus of elasticity() value 200,000 psi higher than theE value specified.
16-rated Douglas fir-larch 200,000 psi higher in modulus of elasticity may be substituted for the specified -rated hem-fir.
I7Where specified, this value may be increased from 90 psi to 140 psi by eliminating either coarse grain material or wane throughout the member, and
from 90 psi to 200 psi by eliminating both coarse grain material and wane.
ISfootnote 6 to Table No. 25-C-1, Part B, also applies.
~
Ul
~
C
.....
c;,
....
N
CD
TABLE NO. 25-C-1 PART B-ALLOWABLE UNIT STRESSES FOR STRUCTURAL GLUED-LAMINATED TIMBER
CD FOR NORMAL LOADING DURATIONt 2 3
Members stressed principally in axial tension or compression or In bending with load applied parallel
to the wide faces of the laminations
I? I'
oll..aminations dic:ullr
AXIAllY LOADED toWoclo
Fecesol
Tension Comprtssion
. l.Mnlna-
lions
y
(Continued)
TABLE NO. 25-C-1 PART B-ALLOWABLE UNIT STRESSES FOR STRUCTURAL GLUED-LAMINATED TIMBER
FOR NORMAL LOADING DURATION' 2 3.-(Contlnued)
Members stressed principally in axial tension or compression or in bending with load applied parallel
to the wide faces of the laminations
Tension Compression
Parallel to Parallel Exlrlme Fiber
COMPRES. Grain to Grain Exlrlme Fiber in Bending& F0 yy Horizontal Shear7 Fvrt in Bending' F0 . , Horizon.
SIONPER F, Fe tal Shear
MODULUS PENDIC- F..,
OF ULAR TO 2lsms 4or 2or
COIIBINA- ELASTICITY GRAIN 2 or Mole 4 or Mole 4or Mole 4 or Mole to 15in. Mole Mole
nON E Fcl_ Lama Lama 2 or 3 lAms Lama 3 Lama 2 lAms Lama 3 lAms 2Lams Deep" Lama Lama
SYIIBDL SPECIES4 GRADE X 10-<lpsl psi psl psl psl psl psl psl psl psl psl psi psl psl
t 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
c:
E-Rated Western Species z
A-27
I--
V2-1.8E 1.8 385 900 1750 1200 1450 1250 1000 145 135 125 1250 1500 165 ~
:::D
A-28 V2-2.0E 2.0 450 1100 2000 1400 1450 1250 1000 145 135 125 1500 1750 165 3:
I-- Ill
A-29 12-2.2E
1 2.2 450 1250 2300 1550 1650 1400 1150 145 135 125 1700 2000 165 c:
I-- DF r=
A-30 '/-l.8E 1.8 385 1550 2100 1700 2400 2400 2100 145 135 125 1800 2100 165
c
I--
A-31
1--
'16-2.0E 2.0 450 1800 2400 1900 2400 2400 2400 145 135 125 2100 2400 165 z
C)
A-32 1
/-2.2E 2.2 450 1800 2400 2100 2400 2400 2400 145 135 125 2300 2400 165 0
0
~
....
I
1\)
A-33 12-1.5E
1 1.5 245 800 1050 950 1200 1050 850 135 130 115 1100 1300 155 m
- c
A-34
- A-35
'IJ-1.8E 1.8 385 900 1300 1200 1450 1250 1000 135 130 115 1250 1500 155 3
0
12-2 OE
1 2.0 385 1100 1550 1400 1450 1250 1000 135 130 115 1500 1750 155 z
r---
A-36
HF
V-l.5E 1.5 245 1200 1450 1300 2100 1900 1700 135 130 115 1400 1650 155
- A-37 V-1.8E 1.8 385 1550 1950 1700 2400 2400 2100 135 130 115 1800 2100 155
r---
A-38 /-2.0E
1 2.0 385 1800 2400 1900 2400 2400 2400 135 130 115 2100 2400 155
A-39 V2-1.5E 1.5 190 800 1200 950 1200 1050 850 120 115 105 1100 1300 140
'-----
A-40 '12-1.8E 1.8 190 900 1500 1200 1450 1250 1000 120 115 105 1250 1500 140
r---
A-41 V2-2.0E 2.0 190 1100 1750 1400 1450 1250 1000 120 115 105 1500 1750 140
f---- ww
A-42 V-l.5E 1.5 190 1200 1550 1300 2100 1900 1700 120 115 105 1400 1650 140
r---
A-43 1.8 190 1550 1950 1700 2400 2400 2100 120 115 105 1800 140
'I-1.8E 2100
r--
A-44 Vrr2.0E 2.0 190 1800 2200 1900 2400 2400 2400 120 115 105 2100 2400 140
Visually Graded Southern Pine
A-45 N3C 1.1 270 325 850 550 550 550 550 120 115 105 450 - 140
r--
A-46 N3M 1.3 385 900 1500 675 1450 1250 1000 175 165 150 1000 - 200
r---
A-47 N2M 12 1.4 385 11 1200 1900 1150 1750 1550 1300 175 150
165 1400 1600 200
r---
A-48 N2D 12 1.7 450 1400 2200 1350 2000 1800 1500 175 165 150 1600 1900 200
f---- SP
A-49 NIM 12 1.7 385 11 1350 2100 1450 1950 1750 1500 175 165 150 1800 2100 200
f----
A-50 NID 12 1.9 450 1550 2300 1700 2300 2100 1750 175 165 150 2100 2400 200
r---
A-51 SSM 1.7 385 11 1300 1900 1600 2100 1950 1650 175 165 150 1750 2100 200
f----
A-52 SSD 1.9 450 11 1500 2200 1850 2400 2300 1950 175 165 150 2100 2400 200
(Continued)
N
Ul
TABLE NO. 25-C-1 PART B-ALLOWABLE UNIT STRESSES FOR STRUCTURAL GLUED-LAMINATED TIMBER
FOR NORMAL LOADING DURATION1 2 3-(Continued)
c;,....
Members stressed principally in axial tension or compression or in bending with load applied parallel
to the wide faces of the laminations
I' t'
toWideFoces Perpen-
of Laminations dicular
AXIALLY LOAOED to Wide
Faces of
Lamina-
lions
X y
Compression
Tension Parallel Extreme Fiber
Parallel to to Grain Extreme Fiber in Bending& Foyy Horizontal Shear7 Fvyy in Bending& Fou
COMPRES. Grain Fe Horizon-
SIONPER Fr tal Shear
MODULUS PENDtC. ! - - - - F,.,
OF ULAR TO 2Lams 4or 2or
COMBINA ELASTICITY GRAIN 2 Of More 4 or More 4or More 4or More to 15 in. More More
T10N E F0 1 Lams Lams 2or 3 Lams Lams 3 Lams 2 Lams Lams 3 Lams 2Lams Deep!' Lams'" Lams
SYMBOL SPECIES4 GRAOE5 X 10-6psi psl psi psi psi psi psi psi psi psi psi psi psi psi
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
c
E-Rated Southern Pine z
A-53
f---
lfz-1.8E 1.8 385 900 1900 1200 1450 1250 1000 175 165 150 1250 1500 200 ~
:II
A-54 lfz-2.0E 2.0 450 1100 2300 1400 1450 1250 1000 175 165 150 1600 1750 200 3:
f--- CD
A-55 'lz-2.2E 2.2 450 1250 2400 1550 1650 1400 1150 175 165 150 1700 2000 200 c
1---
A-56
SP
lf-l.8E !.8 385 1550 1850 1700 2400 2400 2100 175 165 150 1800 2100 200 r=0
f---
A-57 lf2.0E 2.0 450 1800 2400 1900 2400 2400 2400 175 165 150 2100 2400 200 z
C)
f---
A-58 'lo-2.2E 2.2 450 1800 2400 2100 2400 2400 2400 175 165 150 2300 2400 200 0
0
~
Wet-use factors' - 0.833 0.667 0.8 0.73 0.73 0.8 0.8 0.8 0.875 0.875 0.875 0.8 0.875 0.875
1The combinations in this table are intended primarily for members loaded either axially or in bending with the loads acting parallel to the wide faces of C
the laminations. Design values for bending due to loading applied perpendicular to the wide faces of the laminations are also included; however, the z
combinations in Table No. 25-C-1 Part A are usually better suited for this condition of loading. The design values for bending about the X-X axis
(Fbxx) shown in Column 15 are for members from two laminations to 15 inches deep without tension laminations. Design values approximately 15
percent higher for members with four or more laminations are shown in Column 16. These higher design values, however, require special tension
laminations which may not be readily available.
2The tabulated design values are for dry conditions of use. To obtain wet-use design values, multiply the tabulated values by the factors shown at the end
of the table.
3 The tabulated design values are for normal duration of loading. For other durations of loading, see Section 2504 (c) 4.
4 The symbols used for species are DF =Douglas fir-larch, HF =hem-fir, WW =western woods and Canadian softwood species, and SP =southern
pine.
5Grade designations are as follows:
VIsually Graded Southern Pine
Ll is Ll laminating grade (dense for Douglas fir-larch).
LID is Ll dense laminating grade for hem-fir.
Ll CL is L1 close grain laminating grade.
L2D is L2laminating grade (dense).
L2 is L2 laminating grade (medium grain).
L3 is L3laminating grade (medium grain for Douglas fir-larch and hem-fir).
SSD is dense select structural, structural joists and planks, or structural light framing grade (dense).
SS is select structural, structural joists and planks, or structural light framing grade (medium grain for Douglas fir-larch).
NID is dense No. I structural joists and planks, or structural light framing grade (dense).
Nl is No. I structural joists and planks, or structural light framing grade (medium grain for Douglas fir-larch).
N2D is dense No. 2 structural joists and planks, or structural light framing grade (medium grain for Douglas fir-larch).
N3M is No. 3 structural joists and planks, or structural light framing grade (medium grain).
N3C is No. 3 structural joists and planks, or structural light framing grade (coarse grain).
N3 is No. 3 structural joists and planks, or structural light framing grade.
(Continued)
(Continued)
N
N
f
~
VIsually Graded Southern Pine
SSD is dense select structural, structural joists and planks, or structural light framing grade (dense). ....
SSM is select structural, structural joists and planks, or structural light framing grade (medium grain).
NID is No. I dense structural joists and planks, or structural light framing grade or No. I boards graded as dense.
NIM is No. I structural joists and planks, or structural light framing grade or No. I boards all with a medium grain rate of growth.
N2D is No. 2 dense structural joists and planks, or structural light framing grade or No. 2 boards graded as dense.
N2M is No. 2 structural joists and planks, or structural light framing grade or No. 2 boards all with a medium grain rate of growth.
N3M is No. 3 structural joists and planks, or structural light framing grade or No. 3 boards all with a medium grain rate of growth.
N3C is No. 3 structural joists and planks, or structural light framing grade or No. 3 boards all with coarse grain rate of growth.
ERated Grades-All Species
V6-2.2E has \16 edge characteristic with 2.2E.
\16-2.0E has \16 edge characteristic with 2.0E.
\16-l. 8E has 1/6 edge characteristic with I. 8E.
V.-1.5E has V. edge characteristic with 1.5E.
~-2.2E, ~-2.0E, \12-I.SE, 112-1.5E are E-rated grades with edge characteristics occupying up to one half of cross section.
6'fhe values ofFlryy were calculated based on members 12 inches in depth (bending about Y-Y axis). When the depth is less than 12 inches, the values of
F byy can be increased by multiplying by the following factors:
Depth, Inches Multiplying Factor
10.75 1.01
8.75 1.04 c
6.75 1.07 z
5.125
3.125
1.10
1.14 ~
::11
7The design values in horizontal shear contained in this table are based on members without wane. 3:
8The tabulated design values in bending are applicable to members 12 inches or less in depth. For members greater than 12 inches in depth, the ID
c
requirements of Section 2511 (d) 5 apply. j=
9'fhe design values in Column 15 are for members of from two laminations to 15 inches in depth without tension laminations. c
1<YJ'he design values in Column 16 are for members of four or more laminations in depth and require special tension laminations. When these values are z
C)
used in design and the member is specified by combination symbol, the designer should also specify the required design value in bending. 0
0
~
II When tension laminations are used to obtain the design value for Fbu shown in Column 16, the compression perpendicular to grain value, Fc.l.., for
the tension face may be increased to 450 psi for Douglas fir-larch and southern pine, and to 385 psi for hem-fir because the tension laminations are
...
ID
required to be dense. ~
12Combinations 47, 48, 49 and 50 have more restrictive slope of grain requirements than the basic slope of grain of the grades of lumber used in order to m
obtain highertension parallel to grain values and design values in bending when loaded perpendicular to the wide faces of the laminations. The slopes
c
of grain used to calculate the design values in Table No. 25-C-1, Part B, were: Combination 47, 1:14; Combination 48, I: 14; Combination 49, 1:16;
3
0
and Combination 50, I: 14. When design stresses are lower than the design values shown, or when a less restrictive slope of grain provides the same z
design value, a less restrictive slope of grain may be used. The following table gives the design values of these combinations for various slopes of
grain: Values of Fbxx in column 5 are for members of two laminations to 15 inches in depth without tension laminations, and values in Column 6 are
for members of four or more laminations with tension laminations.
(Continued)
(Continued)
1The allowable unit stresses in bending obtained from Table No. 25-D apply when the wide faces of the laminations are normal to the direction of the c
load. z
~
2 AIIowable stresses for dry conditions of use shall be applicable when the moisture content in service is 16 percent or less as in most covered structures.
For wet conditions of use the following maximum percentage of the dry-use stresses shall be permitted: ::D
Fb (bending) and F, (tension) 80 percent FY (horizontal shear 88 percent 3:
Ill
Fe (compression parallel to grain) 70 percent Fcl.. (compression perpendicular to grain) 67 percent c
E (modulus of elasticity) 83 percent ;=
0
3for modification of allowable unit stresses for structural glued-laminated lumber, see Section 2504.
4 Factors for knot sizes of 0.1 and 0.2 are identical in case of extreme fiber in bending and in tension parallel to grain because slope of grain of I: 16 is a
z
C)
greater limitation than knot size. The smaller knot size may be specified for reasons other than strength. 0
0
5When laminations of different thicknesses are used, divide the depth of the member by the thickest lamination used and then assume the quotient to be
the number of laminations in the member for use in determining the allowable stress. ~
1982 EDITION 25-E
I. Pacific
Coast
Douglas
Fir 1 2 1250 2450 115 230 1,500,000
2. Southern
Pine 1 3 1200 2400 110 250 1,500,000
301
TABLE NO. 25-F-HOLDING POWER OF BOLTS 1 2. 4 FOR DOUGLAS FIR-LARCH, CALIFORNIA REDWOOD (CLOSE GRAIN)
AND SOUTHERN PINE
(See U.B.C. Standard No. 25-17 where members are not of equal size and for values In other species.)
6d 2 12Vz I Vs 51
8d 2Vz IIVz IV. 63
IOd 3 IOVz IVz 76 See
U.B.C.
12d 3V IOVz I Vz 76
Standard
16d 3 1/z 10 IVz 82 No.
25-17
20d 4 9 1'/s 94
30d 4Vz 9 1'/s 94
40d 5 8 1% 108
COMMON NAILS
6d 2 IIVz IV 63
8d 2 1/z IOV I Vz 78
IOd 3 9 1'/s 94 See
U.B.C.
12d 3V 9 1'/s 94
Standard
16d 3Vz 8 13!4 108 No.
25-17
20d 4 6 2Vs 139
30d 4 1/z 5 2'/ 155
40d 5 4 2Vz 176
50d 5Vz 3 23!4 199
60d 6 2 27!s 223
I Thesafe lateral strength values may be increased 25 percent where metal side
plates are used.
2For wood diaphragm calculations these values may be increased 30 percent.
(See U.B.C. Standard No. 25-17.)
304
1982 EDITION 25-H, 25-1
HORIZONTAL VERTICAL
DIAPHRAGMS DIAPHRAGMS
MATERIAL Maximum Maximum
Span-Width HeightWidth
Ratios Ratios
305
r
N
TABLE NO. 25-J-ALLOWABLE SHEAR IN POUNDS PER FOOT FOR HORIZONTAL PLYWOOD DIAPHRAGMS
WITH FRAMING OF DOUGLAS FIR-LARCH OR SOUTHERN PINE1
STHl'CH'HAL 1
ild 11 c ~.~ -1 210 I 360 530 600 240 1il0
'3 '300 400 600 675 265 200
lOcl 1 ;,, 12 2 320 425 640 730 2 285 215
3 '360 480 720 820 320 240
-1 170 225 ' 335 380 150 110
1 190 250 i .380 4.30 170 12.5
I Gel 1'
3S 2 11l5 1 250 1 '375 420 165 12S
i j 210 280 i 420 475 185 i 140 c
1
z
I
C-D, C-C, STRUCTURAL 11
~ ..... I
I
-1
'3
240
2.70
320
360
! 480
i 540
S4.5
610
2l.S
:240 I
160
180 ~
::D
and other grade' CO\ cred Sd J 1" s:::
in U.B.C. Standard No. 25-9 1:.! 0 :270 , 360 S30 600
j :240 I ISO Ill
3 ! '300 1 4001 600 67S 265 200 c
r=
12 I
0 290 ! 38.5 .S75 65.S 2 2.55 190 c
JOel Is . . I 3
I 'J25 I 430 ' 6.50 I 73.S
I 290 215 z
0
' '
I
I
:2
3
I 32o 425 I 64o ! 730 2
1360 480
I
720 ! 820
i
:285
320
i
'
:215
240 I) "c
n
0
m
....
I These values are for short-time loads due to wind or earthquake and must be reduced 25 percent for normal loading. Space nails 10 inches on center for
floors and 12 inches on center for roofs along intermediate framing members.
~
m
Allowable shear values for nails in framing members of other species set forth in Table No. 25-17 -J of U. B.C. Standards shall be calculated for all 0
::::j
grades by multiplying the values for nails in STRUCTURAL I by the following factors: Group III, 0.82 and Group IV, 0.65.
2framing shall be 3-inch nominal or wider and nails shall be staggered where nails are spaced 2 inches or 2 Y2 inches on center, and where I Od nails
having penetration into framing of more than I 'Is inches are spaced 3 inches on center.
I 0z
LOAD
DIAPHRAGM BOUNDAI'IY
Case 5 Case 6
L oad+ + Framing L oad Framing
~ct----
: ""fJ; --
: Blocking
' Blocking --
J..
~
'- /v
' 77
~ Continuous Panel Joints ,;;;
r
N
w
c
.....
"'c
CXI
~-
TABLE NO. 25-K-ALLOWABLE SHEAR FOR WIND OR SEISMIC FORCES IN POUNDS PER FOOT FOR
PLYWOOD SHEAR WALLS WITH FRAMING OF DOUGLAS FIR-LARCH OR SOUTHERN PINE 1
MINIMUM PLYWOOD APPLIED DIRECT TO FRAMING PLYWOOD APPLIED OVER V2-INCH
MINIMUM NAIL NAIL SIZE NAIL SIZE GYPSUM SHEATHING
NOMINAL PENETRA (Common (Common
Nail Spacing at Plywood Panel Edges Nail Spacing at Plywood Panel Edges
~~6~Z~~s
TIONIN or or
FRAMING Galvanized Galvanized
PLYWOOD GRADE (Inches) (Inches) Box) 6 4 3 2' Box) 6 4 3 2'
;llt. II/.- 6d 200 JOO 390 510 8d 200 300 390 510
STRCCTCRAL I "/k 11/o 8d 230' 360' -+60' 610' IOd 280 -+30 55(F 730 "
C-D.C-C
i
I
STRl'CTCRAL YJr. 1'/, 6d !80 270 350 450 8d 180 270 350 450
II and other
grades
covered in -YR 11/o 8d 220 3 320-' 410-' 5303 J()d 260 380 490' 640
U.B.C.
Standard No. X
25-9. 1
/o !Yx !Od 310 460 600' 770 - - - - -
I.%" 3 16 2
2. '12'' 4 24
'In reference to Section 2517 (g) 3, blocking of horizontal JOints ts not requued.
310
1982 EDITION 250
I. LAP SIDING
2. SQUARE EDGE
PANEL SIDING
Direct to studs Ys" 24" o.c. 6d2 6" o.c. 4" o.c.
edges; edges;
12" o.c. at 8" o.c.
intermed. intermed.
supports supports
3. SHIPLAP EDGE
PANEL SIDING
1Siding nail.
311
25-P, 25-Q UNIFORM BUILDING CODE
CONNECTION NAILING'
I. Joist to sill or girder, toenail 3-8d
2. Bridging to joist, toenail each end 2-8d
3. I" x 6" subfloor or less to each joist, face nail 2-8d
4. Wider than I" x 6" subfloor to each joist, face nail 3-8d
5. 2" subfloor to joist or girder, blind and face nail 2-16d
6. Sole plate to joist or blocking, face nail 16d at 16" o.c.
7. Top plate to stud, end nail 2-16d
8. Stud to sole plate 4-8, toenail or
2-16d, end nail
9. Double studs, face nail 16d at 24" o.c.
10. Doubled top plates, face nail 16d at 16" o.c.
II. Top plates, laps and intersections, face nail 2-16d
12. Continuous header, two pieces 16d at 16" o.c.
along each edge
13. Ceiling joists to plate, toenail 3-8d
14. Continuous header to stud, toenail 4-8d
15. Ceiling joists, laps over partitions, face nail 3-16d
16. Ceiling joists to parallel rafters, face nail 3-16d
17. Rafterto plate, toenail 3-8d
18. I" brace to each stud and plate, face nail 2-8d
19. I" x 8" sheathing or less to each bearing, face nail 2-8d
20. Wider than I" x 8" sheathing to each bearing, face nail 3-8d
21. Built-up comer studs 16d at 24" o.c.
22. Built-up girder and beams 20d at 32" o.c. at top
and bottom and staggered
2-20d at ends and at
each splice
(Contmued)
312
1982 EDITION 25-Q
CONNECTION NAILING'
23. 2" planks 2-16d at each bearing
24. Particleboard:5
Wall Sheathing (to framing):
Ys"-V2" 6d 3
Sfg"-3f4" 8d3
25. Plywood:5
Subftoor, roof and wall sheathing (to framing):
W' and less 6d 2
Ys"-Y4" 8d 3 or 6d 4
7jg"-lll 8d 2
IW'-IV4' IOd3 or 8d4
Combination Subftoor-underlayment (to framing):
.Y." and less 6d 4
/s"-1"
7
8d 4
IW'-Iv.'' 10d3 or 8d4
26. Panel Siding (to framing):
W' or less 6d 6
'Is" 8d 6
27. Fiberboard Sheathing: 7
V2" No. II ga 8
6d 3
No. 16ga 9
2Yl2 11 No. llga 8
8d 3
No. 16 ga 9
313
25-R-1, 25-R-2 UNIFORM BUILDING CODE
I. 24
2. 16 *
% 1 .2=>
H
:\:!
ROOFS
*
% I
~~
H
3. 24 %
I H
* I ~3
'Installation details shall confonn to Sections 2517 (e) I and 2517 (h) 7 for
floor and roof sheathing, respectively.
2Maximum 19 percent moisture content.
3 Floor or roof sheathing confonning with this table shall be deemed to meet
the design criteria of Section 2516.
314
1982 EDITION 25-R-3, 25-S-1
~
NON BEARING
BEARING WALLS WALLS
SUPPORTING SUPPORTING SUPPORTING
ROOF AND ONE FLOOR, TWO FLOORS,
STUD STUD CEILING ROOF AND ROOF AND STUD
SIZE HEIGHT ONLY CEILING CEILING HEIGHT SPACING
(Inches) (Feel) (Inches) (Inches) (Inches) (Feel) (Inches)
I. 2 X 32 10 - - - 10 16
2. 2X 4 10 24 16 - 14 24
3. 3X 4 10 24 24 16 14 24
4. 2X 5 10 24 24 - 16 24
5. 2X 6 10 24 24 16 20 24
'Utility grade studs shall not be spaced more than 16 inches on center, nor support more than
a roof and ceiling, nor exceed 8 feet in height for exterior walls and load bearing or I 0 feet
for interior nonload-bearing walls.
2Shall not be used in exterior walls.
ROOF2
Maximum
Span Load (In Pounds
(In Inches) per Square Foot) FLOOR
PANEL PLYWOOD MAXIMUM
IDENTIFICATION THICKNESS Edges Edges Total Live SPAN
INDEX3 (Inch) Blocked Unblocked Load Load (In Inches)
I. 1210 Y16 12 155 150 0
2. 16/0 Y16, 3fs 16 95 75 0
3. 20/0 5/16, 3jg 20 75 65 0
4. 24/0 3jg 24 16 65 50 0
5. 24/0 y, 24 24 65 50 0
6. 30/12 y, 30 26 70 50 12 5
7. 32116 y,, 5jg 32 28 55 40 167
8. 36/16 3!4 36 30 55 50 167
9. 42120 %, 3!4, 7/g 42 32 406 35 6 207, 8
10. 48124 3!4, 7jg 48 36 406 35 6 24
'These values apply for C-C, C-D, Structural I and II grades only. Spans shall be hm1ted to
values shown because of possible effect of concentrated loads.
2Uniform load deflection limitations: Y18o of the span under live load plus dead load, '/240
under live load only. Edges may be blocked with lumber or other approved type of edge
support.
(Continued)
315
25-S-1, 25-S-2 UNIFORM BUILDING CODE
(Continued)
3 Jdentification index appears on all panels in the construction grades listed in Footnote
No. I.
4 Plywood edges shall have approved tongue-and-groove joints or shall be supported with
blocking unless V-inch minimum thickness underlayment, or I Y2 inches of approved
1
cellular or lightweight concrete is placed over the subfloor, or finish floor is 25/32-inch
wood strip. Allowable uniform load based on deflection of V360 of span is 165 pounds per
square foot.
5 May be 16 inches if'Y32-inch wood strip flooring is installed at right angles to joists.
6 For roof live load of 40 pounds per square foot or total load of 55 pounds per square foot,
decrease spans by 13 percent or use panel with next greater identification index.
7 May be 24 inches if2 5/32-inch wood strip flooring is installed at right angles to joists.
8 May be 24 inches where a minimum of I y, inches of approved cellular or lightweight
concrete is placed over the subfloor and the plywood sheathing is manufactured with
exterior glue.
9 Floor or roof sheathing conforming with this table shall be deemed to meet the design
criteria of Section 2516.
316
1982 EDITION 25-T, 25-U
ROOFS
l/240 170,000
20 I fiO 2.'5(),000
l/.360
l/240 256,000
4 .30 l/.3()0 210 884,000
l/240 :140,000
40 l/.'3()0 270 .)12,000
l /240 242,000
20 200 :)0.'5,000
l /:360
l/240 ;)():),000
4.5 .'30 l/:3()0 270 10.'5,000
l /240 :)50 ll->4,000
40 l /.'3()0 725,000
l/240 .'3.32,000
20 2.'50
l /360 500,000
1/240 495,000
5.0 .30 l/3()0 330
742,000
l/240 660,000
40 420
1/.360 1,000,000
(Continued)
317
25-U UNIFORM BUILDING CODE
20 l/240 442,000
l/360 300 660,000
5.5 30 l/240 400 662,000
l/360 998,000
40 l/240 500 884,000
l/360 1,330,000
318
TABLE NO. 25-U-J-1-ALLOWABLE SPANS FOR FLOOR JOISTs--40 LBS. PER SQ. FT. LIVE LOAD
DESIGN CRITERIA: Deflection-For 40 lbs. per sq. ft. live load. Umited to span in inches divided by 360. Strength-Live load of 40 lbs.
per sq. ft. plus dead load of 10 lbs. per sq. ft. determines the required fiber stress value. -
CD
~
JOIST Modulus of E.. stlclty, E,ln 1,000,000 pal m
SIZE SPACING c
(Ill) (IN) 0.8 0.9 1.0
9-2
1.1 1.2
9-9
1.3
10-0
1.4
10-3
1.5
10-6
1.6
10-9 10-11
1.7 1.8
11-2
1.9
11-4
2.0 2.2
11-11
3
8-6 8-10 9-6 11-7 0
12.0 720 780 830 890 940 990 1040 1090 1140 1190 1230 1280 1320 1410 z
7-9 8-0 8-4 8-7 8-10 9-1 9-4 9-6 9-9 9-11 10-2 10-4 10-6 10-10
2x6 16.0 790 860 920 980 1040 1090 1150 1200 1250 1310 1360 1410 1460 1550
6-9 7-0 7.3 7-6 7-9 7-11 8-2 8-4 8-6 8-8 8-10 9-0 9-2 9-6
24.0 900 980 1050 ll20 1190 1250 1310 1380 1440 1500 1550 1610 1670 1780
11-3 ll-8 12-1 12-6 12-10 13-2 13-6 13-10 14-2 14-5 14-8 15-0 15-3 15-9
12.0 720 780 830 890 940 990 1040 1090 ll40 1190 1230 1280 1320 1410
10-2 10-7 11-0 ll-4 11-8 12-0 12-3 12-7 12-10 13-1 13-4 13-7 13-10 14-3
2x8 16.0 790 850 920 980 1040 1090 1150 1200 1250 1310 1360 1410 1460 1550
8-11 9-3 9-7 9-11 10-2 10-6 10-9 11-0 ll-3 11-5 11-8 11-11 12-1 12-6
24.0 900 980 1050 1120 1190 1250 1310 1380 1440 1500 1550 1610 1670 1780
14-4 14-ll 15-5 15-11 16-5 16-10 17-3 17-8 18-0 18-5 18-9 19-1 19-5 20-1
12.0 720 780 830 890 940 990 1040 1090 ll40 1190 1230 1280 1320 1410
13-0 13-6 14-0 14-6 14-11 15-3 15-8 16-0 16-5 16-9 17-0 17-4 17-8 18-3
2x10 16.0 790 850 920 980 1040 1090 1150 1200 1250 1310 1360 1410 1460 1550
ll-4 11-10 12-3 12-8 13-0 13-4 13-8 14-0 14-4 14-7 14-11 15-2 15-5 15-11
24.0 900 980 1050 ll20 1190 1250 1310 1380 1440 1500 1550 1610 1670 1780
17-5 18-1 18-9 19-4 19-11 20-6 21-0 21-6 21-11 22-5 22-10 23-3 23-7 24-5
12.0 720 780 830 890 940 990 1040 1090 1140 1190 1230 1280 1320 1410
15-10 16-5 17-0 17-7 18-1 18-7 19-1 19-6 19-11 20-4 20-9 21-1 21-6 22-2
2x12 16.0 790 860 920 980 1040 1090 1150 1200 1250 1310 1360 1410 1460 1550
13-10 14-4 14-11 15-4 15-10 16-3 16-8 17-0 17-5 17-9 18-1 18-5 18-9 19-4
24.0 900 980 1050 1120 1190 1250 1310 1380 1440 1500 1550 1610 1670 1780
NOTES:
(!)The required extreme fiber stress in bending (Fb) in pounds per square inch is shown below each span.
(2)Use single or repetitive member bending stress values (Fb) and modulus of elasticity values() from Tables Nos. 25-A-1 and 25-A-2.
(3)For more comprehensive tables covering a broader range of bending stress values (F b) and modulus of elasticity values(). other spacing of members and
other conditions of loading, see U.B.C. Standard No. 25-21.
(4)The spans in these tables are intended for use in covered structures or where moisture content in use does not exceed 19 percent.
TABLE NO. 25-U-J-6--ALLOWABLE SPANS FOR CEILING JOISTs-10 LBS. PER SQ. FT. LIVE LOAD
w
1\)
(Drywall Ceiling)
0 DESIGN CRITERIA: Deflection-For 10 lbs. per sq. ft. live load. Limited to span in inches divided by 240. Strength-Live load of 10
lbs. per sq. ft. plus dead load of Sibs. per sq. ft. determines the required fiber stress value.
JOIST Modulus of Elasticity, E, In 1,000,000 psi
SIZE SPACING
(IN) (IN) 0.8 0.9 1.0 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.2
9-10 10-3 10-7 10-11 11-3 11-7 11-10 12-2 12-5 12.8 12-11 13-2 13-4 13-9
12.0 710 770 830 880 930 980 1030 1080 1130 1180 1220 1270 1310 1400
8-11 9-4 9-8 9-11 10-3 10-6 10-9 11-0 11-3 11-6 11-.: 11-11 12-2 12-6
2x4 16.0 780 850 910 970 1030 1080 1140 1190 1240 1290 1340 1390 1440 1540
7-10 8-1 8-5 8-8 8-11 9-2 9-5 9-8 9-10 10-0 10-3 10-5 10-7 10-11
24.0 900 970 1040 1110 1170 1240 1300 1360 1420 1480 1540 1600 1650 1760
15-6 16-1 16-8 17-2 17-8 18-2 18-8 19-1 19-6 19-ll 20-3 20-8 2!-0 21-8
12.0 710 770 830 880 930 980 1030 1080 1130 1180 1220 1270 1310 1400
14-1 14-7 15-2 15-7 16-1 16-6 16-11 17-4 17-8 18-1 18-5 18-9 19-1 19-8
2x6 16.0 780 850 910 970 1030 1080 1140 1190 1240 1290 1340 1390 1440 1540
12-3 12-9 13-3 13-8 14-1 14-5 14-9 15-2 15-6 15-9 16-1 16-4 16-8 17-2
24.0 900 970 1040 1110 1170 1240 1300 1360 1420 1480 1540 1600 1650 1760
20-5 21-2 21-1 22-8 23-4 24-0 24-7 25-2 25-8 26-2 26-9 27-2 27-8 28-7
12.0 710 770 830 880 930 980 1030 1080 1130 1180 1220 1270 1310 1400
18-6 19-3 19-1 20-7 21-2 21-9 22-4 22-10 23-4 23-10 24-3 24-8 25-2 25-11
2x8 16.0 780 850 910 970 1030 1080 1140 1190 1240 1290 1340 1390 1440 1540
16-2 16-H 17-5 18-0 18-6 19-0 19-6 19-11 20-5 20-10 21-2 21-7 21-11 22-8
24.0 900 970 1040 1110 1170 1240 1300 1360 1420 1480 1540 1600 1650 1760
26-0 27-1 28-0 28-11 29-9 30-7 31-4 32-1 32-9 33-5 34-1 34-8 35-4 36-5 c
12.0 710 770 830 880 930 980 1030 1080 1130 1180 1220 1270 1310 1400
z
2xl0 16.0
23-8
780
24-7 25-5
910
26-3
970
27-1
1030
27-9
1080
28-6
1140
29-2
1190
29-9
1240
30-5 31-0 31-6 32-1 33-1 ~
:u
850 1290 1340 1390 1440 1540
20-8 21-6 22-3 22-11 23-8 24-3 24-10 25-5 26-0 26-6 27-1 27-6 28-0 28-11 i:
24.0 900 970 1040 1110 1170 1240 1300 1360 1420 1480 1540 1600 1650 1760 tD
c
NOTES: r=
c
( 1)The required extreme fiber stress in bending (F b) in pounds per square inch is shown below each span.
(2)Use single or repetitive member bending stress values (Fb) and modulus of elasticity values() from Tables Nos. 25-A-1 and 25-A-2.
z
C)
(3)For more comprehensive tables covering a broader range of bending stress values (F b) and modulus of elasticity values(). other spacing of members and 0
other conditions of loading. see U.B.C. Standard No. 25-21 0
(4)The spans in tbese tables are intended for use in covered structures or where moisture content in use does not exceed 19 percent. ~
TABLE NO. 25-U-R-1-ALLOWABLE SPANS FOR LOW- OR HIGH-SLOPE RAFTERS
20 LBS. PER SQ. FT. LIVE LOAD (Supporting Drywall Ceiling) ....
DESIGN CRITERIA: Strength-15 lbs. per sq. ft. dead load plus 20 lbs. per sq. ft. live load determines required fiber stress. II)
Deflection-For 20 lbs. per sq. ft. live load. Limited to span in inches divided by 240. RAFTERS: Spans are measured along the co
N
horizontal projection and loads are considered as applied on the horizontal projection. m
c
RAnER
SIZE SPACING
Allowable Extreme Fiber Stress In Bending fb(psl). 3
(IN) (IN) 600 llOO 0
500 700 BOO 900 1000 1200 1300 1400 1500 1600 1700 1800 1900
z
1>-6 9-4 10-0 10-9 11-5 12-0 12-7 !.1-2 11-8 1-!-2 !Hi 15-2 !5-R 16-1 16-7
12.0 0.26 0-..1.5 0.4-! 0.54 0.6-! 0.75 0.86 0.98 !.II 1.24 1.17 !.51 1.66 -1.81 1.96
r.-- - --
--- ---
7-4 1>-1
--
8-8 9-4- 9-10 rro-.5
--
lO-ll
~-
2:'3-3 24-3
2,12 16.0 0.23 0.30 0.38 0.46 0.55 0.65 0.75 0.85 0.97 1.07 1.19 1.11 144 !.56 !.70
20-6- '2r::3 ~f'il 22-8- 2'3 ..1 23-11
---
12-3 13-5 14-6 15-6 16-6 r-17-4 l8T 19-0 19-10
24.0 0.19 0.25 0.31 0.38 0.45 0.53 0.61 0.70 0.78 0.88 097 107 1.17 1.28 1.39
N<YfES:
(!)The required modulus of elasticity() in I ,000,000 pounds per square inch is shown below each span.
(2)Use single or repetitive member bending stress values (Fb) and modulus of elasticity values() from Tables Nos. 25-A-1 and 25-A-2. For duration of load
stress increases, see Section 2504 (c) 4.
(3)For more comprehensive tables covering a broader range of bending stress values (F b) and modulus of elasticity values(), other spacing of members and
other conditions of loading, see U.B.C. Standard No. 25-21.
(4)The spans in these tables are intended for use in covered structures or where moisture content in use does not exceed 19 percent.
TABLE NO. 25UR2-ALLOWABLE SPANS FOR LOW OR HIGH-SLOPE RAFTERS
30 LBS. PER SQ. FT. LIVE LOAD (Supporting Drywall Ceiling)
DESIGN CRITERIA: Strength-15 lbs. per sq. ft. dead load plus 30 lbs. per sq. ft. live load determines required fiber stress.
Deflection-For 30 lbs. per sq. ft. live load. Limited to span in inches divided by 240. RAFTERS: Spans are measured along the
horizontal projection and loads are considered as applied on the horizontal projection.
RAFTER Allowable Extreme Fiber Stress In Bending Fb (psi).
SIZE SPACING
(IN) (IN) 500 600 700 800 900 1000 llOO 1200 1300 1400 1500 1600 1700 1800 1900
7-6 8-28-10 9-6 !0-0 10-7 11-1 11-7 12-1 12-6 11-0 1.'3-5 1'3-10 14-2 14-7
12.0 0.27 0.45 0.55 0.66
0.'36 0.77 0.89 l.OI 1.14 1.28 lA! !.56 1.7 I 1.86 2.02
- ---- -- --
~T ~ f--8~ 8-8 ~g:z- 9~ 10-0 10~5- W-iO 11-'3 IT-7- II~ IT '12~4 12-8
6-6
2x6 160 0.24 0 ..39 0.48 0.57
0 ..31 1-c----1-cc--- 0.67 0.77 0.88 0.99 1.10 1.22 I.'35 1.48 1.61 1.75
- - 5~4 c-5~10" ----
7~1 7-6-- 7-10 8-2
- - -
8~6- s:-1o 9-2
--c--
>)~{,- CJ.9
-~
2x8 16.0 0.24 0 ..31 0.39 0.48 0.57 0.67 0.77 0.88 0.99 1.10 1.22 1.'3.5 1.48 1.61 1.75
7-0 'i.8 8-3 8-To 9-4 c-q:-fo- r-w=-4- 10-10 ~ 11='8 1z:-i 12~6- I2-io 1'3-3 13-7
24.0 0.19 0.25 0 ..32 0 ..'39 0.46 0.54 0.6.'3 0 72 0.81 0.90 1.00 J.IO 1.2 I 1..31 1.43
12-7 I3-9 14-11 15-11 16-11 17-10 18-8 Hl-6 20-4 21-1 21-10 22-6 2'3 . .3 23-11 24-6
!2.0 0.27 0 ..36 0.45 0.55 0.66 0.77 0.89 1.01 1.14 1.28 1.41 ] ..56 1.71 1.86 2.02
-- f-c- 1 --
10-11 11-11 12-11 1'3-9 ITs -TS-5- "!6~2- !6Ji 17-7 18-3 Iii~ J-9-:6- 20:1- 'w~s 21-=:3
2xl0 -16.0 0.24 0.31 0.'39 0.48 0.57 0.67 077 0.88 0.99 1.10 1.22 1..1.5 1.48 1.61 1.75
-- --- ~-----
s:-f! 9-9 16-:.6 11-3- 11-11 l'f""f "1.3-2- "!3-9- 14-4 14-II 15-.5 1-5-11 16--5 ]6:11 17-4
24.0 O.I9 0.25 0 ..32 0.39 0.46 (J..5.J 0.63 0.72 0.81 0.90 1.00 1.10 1.21 1.31 1.43 c::
15-4 16-9 18-1 19-4 20-6 21-8 22-8 23.9 24-8 2.5-7 26-6 27-5 213-3 29-1 29-10 z
12.0 0.27 0.36 0.45 0.55 0.66 0.77 0.89 1.01 -1.14 --
1.28 f-_--1.41
1.3-3- ~4-6 15-8 16.917-9 1--Js:9- !9:s- 20-6 21-5 22-2- 23-0 23:9- 24-5 25-2 25-10
!.56 1.7 I 1.86 2.02
~::0
2xl2 16.0 0.24 0 ..31 0.39 .0.48 0.57 0.67 0.77 0.88 0.99 1.10 1.22 1..'35 1.48 1.61 1.75 3:::
-:c;-;c-
10-10 11-10 12-10 1.3-8 I4T f-15-4 16-1 161l l7-5 18-1 IH-9 '!9-4 20-0 20-6 21-1 Ill
24.0 0.19 0.25 0.32 0 ..39 0.46 0.54 0.6.3 0.72 0.81 0.90 1.00 1.10 1.21 1.31 1.43 !:
r
NOTES: (1 )The required modulus of elasticity() in 1.000,000 pounds per square inch is shown below each span. c
(2)Use single or repetitive member bending stress values (Fb) and modulus of elasticity values() from Tables Nos. 25-A-1 and 25-A-2. For duration of load zC)
stress increases, see Section 2504 (c) 4.
(3)For more comprehensive tables covering a broader range of bending stress values (Fb) and modulus of elasticity values(). other spacing of members and 0
other conditions of loading, see U.B.C. Standard No. 25-21. 0
(4 )The spans in these tables are intended for use in covered structures or where moisture content in use does not exceed 19 percent. ~
TABLE NO. 25-U-R-7-ALLOWABLE SPANS FOR LOW-SLOPE RAFTERS, SLOPE 31N 12 OR LESS
20 LBS. PER SQ. FT. LIVE LOAD (No Ceiling Load) ....
DESIGN CRITERIA: Strength-10 lbs. per sq. ft. dead load plus 20 lbs. per sq. ft. live load determines required fiber stress. IN
Deflection-For 20 lbs. per sq. ft. live load. Limited to span in inches divided by 240. RAFTERS: Spans are measured along the
horizontal projection and loads are considered as applied on the horizontal projection. m
0
RAffiR ::::;
Allowable Extreme Fiber Stress In Bending Fb(psl).
SIZE SPACING
(IN) (IN) 500 600 700 800 900 1000 llOO 1200 1300 1400 1500 1600 1700 1800 1900
0z
9-2 10-0 10-10 11-7 12-4 J.1-0 1.'3-7 14-2 14-9 15-4 1.5-11 16-5 16-11 17-5 17-10
12.0 0 .."3"3 0.44 0.55 0.67 0.80 0.94 1.09 1.24 1.40 1.56 1.71 1.91 2.09 2.28 2.47
-r.-c- -
10-0 10-8 11-.'3 11-9 12-4- 12-IO J.1-.3 n:9-
- --
7-11 8-8 9-5 14~2- 14-8 15-1 15-6
2x6 16.0 0.29 0 ..'38 0.48 0.58 0.70 0.82 0.94 .. --
1.07 1.21 1.15 ISO 1.6.5 - 1.81 1.97 2.14
8-8 !--~ 9-7 i0-0- 1o:s-- 10-10 11-:3 -
-~
2x8 16.0 0.29 0.38 0.48 0.58 0.70 0.82 0.94 1.07 1.21 1.15 1..50 1.65 1.81 1.97 2.14 -
----;c-
10-1 10-10 U-6~ l--i2-l 1--12-ll- 1.3 ..3 lf-9 14-4 14-1-0
~--,-
10-11 11-11 12-11 1.3-9 14-8 15-5 ](3:2 ~6=-11 17-=-7- Hl:::f r8:TI 19-6 20-1 20-8 21-3
24.0 0.24 0 ..31 0.:39 0.48 0.57 0.67 0.77 0.88 0.99 1.10 1.22 1.1.5 1.48 1.61 1.75
18-9 20-6 22-2 2.'3-9 25-2 26-6 27-10 29-1 .'30-.3 .31-4 12-6 .'33-G 14-7 .'35-7 .36-7
12.0 0 ..3.'3 0.44 0 ..55 0.67 0.80 0.94 1.09 1.24 1.40 1.56 1.7:3 1.91 2.09 2.28 2.47
-.-:o- 1--.--
17:9 19-.3 ~o-=-6 it=-9 21-0 24="1 2.5=2 26-2
[-;o-~-,-
16-1 '27-2 -2~2 29-1 -2!i--ll 36-16 .31-"8-
2xl2 16.0 0.29 0 ..38 0.48 0.58 0.70 O.H2 0.94 1.07 1.21 1.15 150 1.6.5 1.81 1.97 2.14
1-o-c-.-- - --
2.3-9 24-5- 25T zs:ro
-c-c-
J.1-.3 14-6 15.8 16=-9- I f f 18-9 19-8 20-6- 21-.) 22-2 2:3-0
24.0 0.24 0 ..31 0 ..'39 0.48 0.57 0.67 0.77 0.88 0.99 1.10 1.22 1..35 1.48 1.61 1.75
NOTES: (!)The required modulus of elasticity() in 1.000.000 pounds per square inch is shown below each span.
(2)Use single or repetitive member bending stress values (Fb) and modulus of elasticity values() from Tables 1\ios. 25-A-1 and 25-A-2. For duration of load
stress increases, see Section 2504 (c) 4.
(3)For more comprehensive tables covering a broader range of bending stress values (Fb) and modulus of elasticity values(). other spacing of membe" and
other conditions of loading. see U.B.C. Standard No. 25-21.
(4)The spans in these tables are intended for use in covered structures or where moisture content in use does not exceed 19 percent.
TABLE NO. 25-U-R-8-ALLOWABLE SPANS FOR LOW-SLOPE, RAFTERS SLOPE 3 IN 12 OR LESS
30 LBS. PER SQ. FT. LIVE LOAD (No Ceiling Load)
N
DESIGN CRITERIA: Strength-10 lbs. per sq. ft. dead load plus 30 lbs. per sq. ft. live load determines required fiber stress. en
Oeflectio~For 30 lbs. per sq. ft. live load. Limited to span in inches divided by 240. RAFTERS: Spans are measured along the C::
horizontal projection and loads are considered as applied on the horizontal projection.
::D
RAFTER Allowable Extreme Fiber Stress In Bending Fo (psi). c!o
SIZE SPACING
(IN) (IN) 500 600 700 800 900 1000 1!00 1200 1300 1400 1500 1600 1700 1800 1900
7-11 8-8 9-5 10-0 10-8 11-.3 11-9 12--1 12-10 1.3-3 1.3-9 14-2 14-8 15-1 15-6
12.0 0.32 0.4.3 0.54 0.66 0.78 0.92 1.06 1.21 1..36 !.52 1.69 1.86 2.04 2.22 2.41
6-11 1-6 8-2 8-8 9-3 9-9 10~2 To-8 ll-1 11-6 11-11 liT 12-8 13-1 13-5
2x6 16.0 0.28 0.37 0.47 0.57 0.68 0.80 0.92 1.05 1.18 1..32 JA6 1.61 1.76 1.92 2.08
----
5-7 6-2 6-8 7-1 7-6 i-ll 8-4 8-8 9-1 9.:-s- 9-9 ~0-0- ~---.-
10-4 To:8 10-11
24.0 0.23 0 ..30 0.38 0.46 0.55 0.6.5 0.75 0.85 0.96 1.08 1.19 1..31 1.44 1.57 1.70
10-6 11-6 12-5 13-3 14-0 14-10 15-6 16-.3 16-10 17-6 18-2 18-9 19-4 19-10 20-5
12.0 0.32 0.4.3 0.54 0.66 0.78 0.92 1.06
--
1.21
---
1.36 1.52 1.69 1.86 2.04 2.22 2.41
9-1 9-11 10-9 11-6 12-2 12-10 13-5 14-0 14-7 15-2 15-8 16-3 16-9 11:2 17-8
2x8 16.0 0.28 0.37 0.47 0.57 0.68 0.80 0.92 1.05 1.18 1.32 1.46 1.61 1.76 1.92 2.08
7-5 8-1 8-9 9-4 9-11 10-6 11-0 11-6 11-11 12-5 12-10 13-3 13-8 14-0 14-5
24.0 0.23 0 ..'30 0.38 0.46 0.55 0.65 0.75 0.85 0.96 1.08 1.19 1..31 1.44 1.57 1.70
13-4 14-8 15-10 16-11 17-11 18-11 19-10 20-8 21-6 22-4 23-2 2.'3-11 24-7 25-4 26-0
12.0 0.32 0.43 0.54 0.66 0.78 0.92 1.06 1.21 1.36 1.52 1.69 1.86 2.04 2.22 2.41
11-7 12-8 13-8 14-8 15-6 16-4 17-2 17-11 18-8 19-;C ~0- 'zo~8 2-1-4 21-11 22-6
2x10 16.0 0.28 0.37 0.47 0.57 0.68 0.80 0.92 1.05 1.18 1..32 1.46 1.61 1.76 1.92 2.08
9-5 10-4 11-2 11-11 12-8 13-4 14-0 14-8 15-3 15-10 16-4 16-11 17-5 17-ll 18-5
24.0 0.23 0.30 0.38 0.46 0.55 0.65 0.75 0.85 0.96 1.08 1.19 1..'31 1.44 1.57 1.70 c:
z
12.0
16-3
0.32
14-1
17-9
0.43
15-5
19-.3
0.54
16-8
20-6
0.66
17-9
21-9
0.78
18-10
23-0
0.92
19-11
24-1 25-2
1.06 1.21
20-10 21-9
26-2
1.36
22-8
27-2 28-2 29-1
1.52 1.69 1.86
23-6 24-4 25-2
29-11
2.04
25-ll
30-10 31-8
2.22 2.41
26-8-1--27-5
a
:a
3:::
2x12 16.0 0.28 0.37 0.47 0.57 0.68 0.80 0.92 1.05 1.18 1.32 1.46 1.61 1.76 1.92 2.08
tJI
11-6 12-7 13-7 14-6 15-5 16-3 17-0 17-9 18-6 19-3 19-11 20-6 21-2 21-9 22-5 c:
24.0 0.23 0.30 0.38 0.46 0.55 0.6.5 0.75 0.85 0.96 1.08 1.19 1..31 1.44 1.57 1.70 r0
NafES: (I )The required modulus of elasticity ()in I ,000,000 pounds per square inch is shown below each span.
(2)Use single or repetitive member bending stress values (F b) and modulus of elasticity values() from Tables Nos. 25-A-1 and 25-A-2. For duration of load
z
C)
stress increases. see Section 2504 (c) 4. 0
(3 )For more comprehensive tables covering a broader range of bending stress values (Fb) and modulus of elasticity values (), other spacing of members and 0
other conditions of loading. see U .B.C. Standard No. 25-21.
(4 )The spans in these tables are intended for use in covered structures or where moisture content in use does not exceed 19 percent.
~
TABLE NO. 25-U-R-10-ALLOWABLE SPANS FOR HIGH-SLOPE RAFTERS, SLOPE OVER 31N 12
20 LBS. PER SQ. FT. LIVE LOAD (Heavy Roof Covering) ....
DESIGN CRITERIA: Strength--15 lbs. per sq. ft. dead load plus 20 lbs. per sq. ft. live load determines required fiber stress.
Deflection-For 20 lbs. per sq. ft. live load. Limited to span In inches divided by 180. RAFTERS: Spans are measured along the
!m
horizontal projection and loads are considered as applied on the horizontal projection. 0
RAfTER Allowable Extreme FlberStresaln Bending fb(pal). 3
SIZE SPACING 0
(Ill) (Ill) 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 z
5-5 5-ll 6-5 6-10 7-3 7-8 8-0 8-4 8-8 9-0 9-4 9-8 9-ll 10-3 10-6
12.0 0.20 0.26 0.33 0.40 0.48 0.56 0.65 0.74 0.83 0.93 1.03 1.14 1.24 1.36 1.47
4-8 5-1 5-6 5-11 6-3 6-7 6-ll 7-3 7-6 7-10 8-1 8-4 8-7 8-10 9-1
2x4 16.0 0.17 0.23 0.28 0.35 0.41 0.49 0.56 0.64 0.72 0.80 0.89 0.98 1.08 1.17 1.27
3-10 4-2 4-6 4-10 5-1 5-5 5-8 5-11 6-2 6-5 6-7 6-10 7-0 7-3 7-5
24.0 0.14 0.18 0.23 0.28 0.34 0.40 0.46 0.52 0.59 0.66 0.73 0.80 0.88 0.96 1.04
8-6 9-4 10-0 10-9 11-5 12-0 12-7 13-2 13-8 14-2 14-8 15-2 15-8 16-1 16-7
12.0 0.20 0.26 0.33 0.40 0.48 0.56 0.65 0.74 0.83 0.93 1.03 1.14 1.24 1.36 1.47
7-4 8-1 8.8 9-4 9-10 10-5 10-11 ll-5 11-10 12-4 12-9 13-2 13.7 13-11 14-4
2x6 16.0 0.17 0.23 0.28 0.35 0.41 0.49 0.56 0.64 0.72 0.80 0.89 0.98 1.08 1.17 1.27
6-0 6-7 7-1 7-7 8-1 8-6 8-ll 9-4 9-8 10-0 10-5 10-9 11-1 11-5 11-8
24.0 0.14 0.18 0.23 0.28 0.34 0.40 0.46 0.52 0.59 0.66 0.73 0.80 0.88 0.96 1.04
11-2 12-3 13-3 14-2 15-0 15-10 16-7 17-4 18-0 18-9 19-5 20-0 20-8 21-3 21-10
12.0 0.20 0.26 0.33 0.40 0.48 0.56 0.65 0.74 0.83 0.93 1.03 1.14 1.24 1.36 1.47
9-8 10-7 11-6 12-3 13-0 13-8 14-4 15-0 15-7 16-3 16-9 17-4 17-10 18-5 18-11
2x8 16.0 0.17 0.23 0.28 0.35 0.41 0.49 0.56 0.64 0.72 0.80 0.89 0.98 1.08 1.17 1.27
7-11 8-8 9-4 10-0 10-7 ll-2 11-9 12.3 12-9 13-3 13-8 14-2 14-7 15-0 15-5
24.0 0.14 0.18 0.23 0.28 0.34 0.40 0.46 0.52 0.59 0.66 0.73 0.80 0.88 0.96 1.04
14-3 15-8 16-ll 18-1 19-2 20-2 21-2 22-1 23-0 23-11 24-9 25.6 26-4 27-1 27-10
12.0 0.20 0.26 0.33 0.40 0.48 0.56 0.65 0.74 0.83 0.93 1.03 1.14 1.24 1.36 1.47
12-4 13-6 14-8 15-8 16-7 17-6 18-4 19-2 19-11 20-8 21-5 22-1 22-10 23-5 24-1
2x10 16.0 0.17 0.23 0.28 0.35 0.41 0.49 0.56 0.64 0.72 0.80 0.89 0.98 1.08 1.17 1.27
10-1 11-1 11-11 12-9 13-6 14-3 15-0 15-8 16-3 16-11 17-6 18-1 18-7 19-2 19-8
24.0 0.14 0.18 0.23 0.28 0.34 0.40 0.46 0.52 0.59 0.66 0.73 0.80 0.88 0 96 1.04
N
!'IOTES: (I )The required modulus of elasticity ()in 1,000.000 pounds per square inch is shown below each span. U1
(2)Use single or repetitive member bending stress values (Fb) and modulus of elasticity values() from Tables Nos. 25-A-1 and 25-A-2. For duration of load C:
stress increases. see Section 2504 (c) 4. :p....
(})For more comprehensive tables covering a broader range of bending stress values (Fb) and modulus of elasticity values(). other spacing of members and 0
other conditions of loading, see U.B.C. Standard No. 25-21.
(4 )The spans in these tables are intended for use in covered structures or where moisture content in use does not exceed 19 percent.
TABLE NO. 25-U-R-11-ALLOWABLE SPANS FOR HIGH-SLOPE RAFTERS, SLOPE OVER 31N 12
30 LBS. PER SQ. FT. LIVE LOAD (Heavy Roof Covering)
DESIGN CRITERIA: Strength-15 lbs. per sq. ft. dead load plus 30 lbs. per sq. ft. live load determines required fiber stress.
Deflection-For 30 lbs. per sq. ft. live load. Limited to span in inches divided by 180. RAFTERS: Spans are measured along the
horizontal projection and loads are considered as applied on the horizontal projection.
RAFTER Allowable Extreme Fiber Stress In Bending Fb (psi).
SIZE SI'ACIHG
(IN) (IN) 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900
4-9 5-3 5-8 6-0 6-5 6-9 7-1 7-5 7.8 8-0 ll-3 8-6 8-9 9-0 9-3
12.0 0.20 0.27 0.34 0.41 0.49 0.58 0.67 0.76 0.86 0.96 1.06 1.17 1.28 1.39 1.51
4-1 4.6 4-11 5-3 5-6 5-10 6-1 6-5 6-8 6-11 7-2 7-5 7-7 7-10 8-0
2x4 16.0 0.18 0.23 0.29 0.36 0.43 0.50 0.58 0.66 0.74 0.8.3 0.92 1.01 11.1 . 1.21 1.31
.3-4 3-8 4-0 4-3 4-6 4-9 5.0 5-3 5-5 5-8 5-10 6-0 6-.3 6.5 6-7
24.0 0.14 0.19 0.24 0.29 0.35 0.41 0.47 0.54 0.61 0.68 I 0.75 0.8.3 0.90 0.99 1.07
7-6 8-2 8-10 9.6 10-0 10-7 11-1 11-7 12-1 12-6 1.3-0 1.3-5 1.3-10 14-2 14-7
12.0 0.20 0.27 0.34 0.41 0.49 0.58 0.67 0.76 0.86 0.96 1.06 1.17 1.28 1.39 1.51
6-6 7-1 7-8 8-2 8-8 9-2 9-:r- To-o 10-5 ioTo 11-.3 11-7 11-11 12-4 12-8
2x6 16.0 0.18 0.2.3 0.29 0 ..36 0.43 0.50 0.58 0.66 0.74 0.83 0.92 1.01 1.11 1.21 1..31
5-4 5.10 6-3 6-8 7-1 7-6 7.10 8-2 8-6 8-10 9-2 9.6 9-9 10-0 10-4
24.0 0.14 0.19 0.24 0.29 0.35 0.41 0.47 0.54 0.61 0.68 0.75 0.8.3 0.90 0.99 1.07
9-10 10-10 11-8 12-6 1.3-.3 1.3-1114-8 15-.3 15-11 16-6 17-1 17-8 18-2 18-9 19-3
12.0 0.20 0.27 0 ..34 0.41 0.49 0.58 0.67 0.76 0.86 0.96 1.06 1.17 1.28 1..39 1.51
8-7 9-4 10-1 10.10 11-6 12-1 "12-8 1.3-.3 1:3-9 14-4 J.l-1 0 15-3 15-9 16-3 16-8
2x8 16.0 0.18 0.2.3 0.29 0 ..36 0.4.3 0.50 0.58 0.66 0.74 0.83 0.92 1.01 1.11 1.21 1.31
7-0 7-8 8-3 8-10 9-4 9-10 10.4 10-10 11-.3 11-8 12-1 12-6 12-10 13-3 13-7
24.0 0.14 0.19 0.24 0.29 0.35 0.41 0.47 0.54 0.61 0.68 0.75 0.8.3 0.90 0.99 1.07 c
12-7 13.9 14-11 15-11 16-11 17-10 18-8 19-6 20-4 21-1 21-10 22-6 23-3 23-11 24-6 z
12.0 0.20 0.27
10-11 11-11
0.34 0.41
12-11 1.3-9
0.49
14-8
058 0.67
15-5 16-2
0.76
16-11
0.86
17.7
0_:9~- 1.06
18-.3 '18-11
1.17
19-6
1.28 1..39
20-1 20-8
1.51
21-3 ~:n
2x10 16.0 0.18 0.2.3 0.29 0.36 0.43 0.50 0.58 0.66 0.74 0.8.3 0.92 1.01 1.11 1.21 1.31 3:
8-11 9.9 10-6 11-3 11-11 12-7 1.3-2 13-9 14-4 14-11 15-5 15-11 16-5 16-11 17-4 ID
24.0 0.14 0.19 0.24 0.29 0.35 0.41 0.47 0.54 0.61 0.68 0.75 0.83 0.90 0.99 1.07 c
N<ITES: (I )The required modulus of elasticity() in 1.000.000 pounds per square inch is shown below each span.
r=0
(2)Use single or repetitive member bending stress values (Fb) and modulus of elasticity values() from Tables Nos. 25-A-1 and 25-A-2. For duration of load
stress increases. see Section 2504 (c) 4.
z
C)
(3)For more comprehensive tables covering a broader range of bending stress values (F b) and modulus of elasticity values(). other spacing of members and 0
other conditions of loading. see U.B.C. Standard No. 25-21. 0
(4)The spans in these tables are intended for use in covered structures or where moisture content in use does not exceed 19 percent. ~
TABLE NO. 25-U-R-13--ALLOWABLE SPANS FOR HIGH-SLOPE RAFTERS, SLOPE OVER 31N 12
20 LBS. PER SQ. FT. LIVE LOAD (Light Roof Covering) ...
CD
DESIGN CRITERIA: Strength--7 lbs. per sq. ft. dead load plus 20 lbs. per sq. ft. live load determines required fiber stress. co
N
Deflection-For 20 lbs. per sq. ft. live load. Limited to span in inches divided by 180. RAFTERS: Spans are measured along the m
horizontal projection and loads are considered as applied on the horizontal projection. c
RAFTER
::::j
Allowable Extreme Fiber Stress In Bending Fb (psi).
SIZE SPACING 0
(IN) (IN) 500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 z
6-2 6-9 7-3 7.9 8-3 8-8 9-1 9-6 9-11 10-3 10-8 11-0 11-4 11-8 12-0
12.0 0.29 o.:j8 0.49 0.590.71 0.83 0.96 1.09 1.23 1.37 1.52 1.68 1.84 2.00 2.17
5-4 5-10 6~ '6:9 7-2 7-6 7-i 1 8-3 8-7 8-11 9-3 9-6 9-10 10-1 10-5"
2x4 16.0 0.25 0.33 0.42 0.51 0.61 0.72 0.83 0.94 1.06 1.19 1..'32 1.4.5 1.59 1.73 1.88
4-4 4-9 5-2 5-6 5-10 6-2 6-5 6-9 7-0 7-3 7-6 7-9- 8-0 ~ 8~
24.0 0.21 0.27 0.34 0.42 0.50 0.59 0.68 0.77 0.87 0.97 1.08 1.19 1..'30 1.41 1.53
9-8 10-7 11-5 12-3 13-0 1'3-8 14-4 15-0 15-7 16-2 16-9 17-3 17-10 18-4 18-10
12.0 0.29 0 ..'38 0.49 0.59 0.71 0.83 0.96 1.09 1.23 1..'37 1.52 1.68 1.84 2.00 2.17
8-4 9-2 9-11 10-7 11-3 11-10 12-5 13-0 13-6 14-0 14-6 15-0 15-5 15-11 16-4
2x6 16.0 0.25 0.33 0.42 0.51 0.61 0.72 0.83 0.94 1.06 1.19 1..'32 1.45 1.59 1.73 1.88
-~
-~-- -- - - - ~
6-10 7-6 8-1 8-8 9-2 9-8 10-2 10-7 11-0 11-5 11-10 12-3 12_--7 13-0 1.3-4
24.0 0.21 0.27 0.34 0.42 0.50 0.59 0.68 0.77 0.87 0.97 1.08 1.19 1..30 1.41 1.53
12-9 13-11 15-1 16-1 17-1 18-0 18-11 19-9 20-6 21-4 22-1 22-9 2.'3-6 24-2 24-10
12.0 0.29 0.38 0.49 0.59 0.71 0.83 0.96 1.09 1.23 1 ..37 1..52 1.68 1.84 2.00 2.17
11-0 12-1 1.3-1 13-11 14-10 15-7 16-4 17-1' !i-ff 18--5 f--]g::--1~ i9T 20-4 20-11 21-6
2x8 16.0 0.25 0 ..3.'3 0.42 0.51 0.61 0.72 0.83 0.94 1.06 1.19 1..32 1.45 1.59- - 1.73 1.88
24.0
9-0 9-10
0.21 0.27
10-8 11-5 12-1
0.34 0.42 0.50
12-9
0.59
1'lT 1.3-11
0.68 0.77
------
14-6 15-1
0.87 0.97
---
rs--=r f-;-;---
1.08 1.19
16-1
---
16-7 17-1
1.30 1.41
17=7-
1.53
16-'3 17-10 19-3 20-7 21-10 23-0 24-1 25-2 26-2 27-2 28-2 29-1 30-0 .'30.10 31-8
12.0 0.29 0.38 0.49 0.59 0.71 0.8.3 0.96 1.09 1.2.'3 1.37 1..52 1.68 1.84 2.00 2.17
14-1 15-5 16-8 17-10 18-11 19-11 20-10 21-10 22:8 23-7- 24~.5 25-2 25-11 26_--8 27---:5
2x10 16.0 0.25 0.3.'3 0.42 0.51 0.61 0.72 0.83 0.94 1.06 1.19 1.12 1.45 1.59 1.73 1.88
11-6 12.7 13-7 14-6 15-5 16-3 l7.i- 17:-10 _1s-=-6 19-=:3' f--yg: 11 20-7 21-2 21-10 22-5
24.0 0.21 0.27 0 ..'34 0.42 0.50 0.59 0.68 0.77 0.87 0.97 1.08 1.19 1..'30 1.41 1.-'53
N<ITES: (I )The required modulus of elasticity() in 1.000.000 pounds per square inch is shown below each span.
(2)l!se single or repetitive member bending stress values iFb) and modulus of elasticity values i) from Tables :\'os. 25-A-1 and 25-A-2. For duration of load
stress increases. see Section 2504 (c) 4.
(3 )for more comprehensive tables covering a broader range of bending stress values (Fh) and modulus of elasticity values(). other spacing of members and
other conditions of loading. see C .B.C. Standard No. 25-21.
(4)The spans in these tables are intended for use in covered structures or where moisture content in use does not exceed 19 percent.
TABLE NO. 25-U-R-14-ALLOWABLE SPANS FOR HIGH-SLOPE RAFTERS, SLOPE OVER 31N 12
30 LBS. PER SQ. FT. LIVE LOAD (Light Roof Covering)
DESIGN CRITERIA: Strength-7 lbs. per sq. ft. dead load plus 30 lbs. per sq. ft. live load determines required fiber stress.
Deflection-For 30 lbs. per sq. ft. live load. Limited to span in inches divided by 180. RAFTERS: Spans are measured along the
horizontal projection and loads are considered as applied on the horizontal projection.
RAFTER
SIZE SPACING
Allowable Extreme Fiber Stress In Bending Fb (psi).
(IN) (IN) 500 600 700 800 900 1000 llOO 1200 1300 1400 1500 1600 1700 1800 100
5-3 5-9 6-3 6-8 7-1 7-5 7-9 8-2 8-6 8-9 9-1 9-5 9-8 10-0 10-3
12.0 0.27 0.36 0.45 0.55 0.66 0.77 0.89 1.02 1.15 1.28 1.42 1..57 1.72 1.87 2.03
1-o;-- --
4-7 5-0 5-5 53'1 6-r- 6-5- 6-9 rr:-r- 7-4-- 7~ 7-ll 8-2 8-5 8-8 8-10
2x4 16.0 0.24 0.:31 0.39 0.48 0.57 0.67 0.77 0.88 0.99 1.11 1.2.'3 !..'36 1.49 1.62 1.76
3-9 4-1 4-5
-~
11-6
-- --
12-0 !2-.5 12-9
--cc-
1'3-2
-
-~
1:3-7 T:WT
2x6 16.0 0.24 0.:31 0.39 0.48 0.57 0.67 0.77 0.88 0.99 1.11 - - 1.23 1..'36 1.49 1.62 1.76
9-9 1o-r' ~-
--
5-10 6-5 6-11 1-5 1=-Io- '8::'3 ll-ll 9-1 9-5 10-9 11-1 11-5
24.0 0.!9 0.25 0.:32 0.39 0.47 0 ..5.5 0.63 0.72 0.81 0.9! 1.01 !.II 1.21 1..'32 1.4:3
10-!1 11-11 12-10 13-9 14-7 !5-.5 16-2 16-10 17-7 !8-2 18-10 19-G 20-l 20-8 21-:3
12.0 0.27 0.36 0.45 0.5.5 0.66 0.77 ----;-
0.84 1.02 !.!.5 1.28 1.42 !..57 1.72 1.87 2.0:3
ll-2 11TI 12-8 11-4 14-:() r4-::r 1.5-2 I iT
-~
Chapter 26
CONCRETE
NOTE: This chapter has been revised In Its entirety.
Scope
Sec. 2601. The design of structures in concrete of cast-in-place or precast
construction, plain, reinforced or prestressed, shall conform to the rules and
principles specified in this chapter.
Definitions
Sec. 2602. The following terms are defined for general use in this code.
Specialized definitions appear in individual chapters.
ADMIXTURE is material other than water, aggregate, or hydraulic cement
used as an ingredient of concrete and added to concrete before or during its mixing
to modify its properties.
AGGREGATE is inert material that is mixed with hydraulic cement and water
to produce concrete.
AGGREGATE, LIGHTWEIGHT, is aggregate with a dry, loose weight of
70 pounds per cubic foot or less.
AIR-DRY WEIGHT is the unit weight of a lightweight concrete specimen
cured for seven days with neither loss nor gain of moisture at 60 to 80F. and dried
for 21 days in 50 7 percent relative humidity at 73.4 2F.
ANCHORAGE. See Section 2612. Also, the means by which the prestress
force is permanently transferred to the concrete.
BONDED TENDON is a prestressing tendon that is bonded to concrete either
directly or through grouting.
COLUMN is a member with a ratio of height-to-least-lateral dimension of 3 or
greater used primarily to support axial compressive load.
COMPOSITE CONCRETE FLEXURAL MEMBERS are concrete flex-
ural members of precast and cast-in-place concrete elements or both constructed
in separate placements but so interconnected that all elements respond to loads as
a unit. See Section 2617.
CONCRETE is a mixture of portland cement or any other hydraulic cement,
fine aggregate, coarse aggregate and water, with or without admixtures.
CONCRETE, STRUCTURAL LIGHTWEIGHT, is concrete containing
lightweight aggregate which conforms to Section 2603 (d) and having an air-dry
unit weight as determined by definition above, not exceeding 115 pcf. In this
code, a lightweight concrete without natural sand is termed "all-lightweight
concrete" and lightweight concrete in which all fine aggregate consists of normal
weight sand is termed "sand-lightweight concrete."
CURVATURE FRICTION is friction resulting from bends or curves in the
specified prestressing tendon profile.
DEFORMED REINFORCEMENT is deformed reinforcing bars, bar and
rod mats, deformed wire, welded smooth wire fabric and welded deformed wire
329
2602 UNIFORM BUILDING CODE
330
1982 EDITION 2602
331
2602-2603 UNIFORM BUILDING CODE
332
1982 EDITION 2603
333
2603 UNIFORM BUILDING CODE
farther apart than 16 inches in direction of primary flexural reinforcement and, for
wire with a specified yield strengthfv exceeding 60,000 psi,JY shall be the stress
corresponding to a strain of0.35 percent.
3. Plain reinforcement. Plain bars for spiral reinforcement shall conform to
the specification for A615, A616 and A617 contained in U.B.C. Standard No.
26-4, including additional requirements of Section 2603 (f) 2 A and the first
paragraph of Section 2603 (f) 2 B.
Smooth wire for spiral reinforcement shall conform to U.B.C. Standard No.
24-15 except that for wire with a specified yield strengthfy exceeding 60,000 psi,
fv shall be the stress corresponding to a strain of0.35 percent.
4. Prestressing tendons. Wire, strands and bars for tendons in prestressed
concrete shall conform to U .B.C. Standard No. 26-7.
Wire, strands and bars not specifically listed in U .B.C. Standard No. 26-7 may
be used, provided they conform to minimum requirements of these specifications
and do not have properties that make them less satisfactory than those listed.
5. Structural steel, steel pipe or tubing. Structural steel used with reinforc-
ing bars in composite compression members meeting requirements of Section
2610 (o) 7 or 2610 (o) 8 shall conform to U.B.C. Standard No. 27-1, Grades A36,
A242, A441, A572 and A588.
Steel pipe or tubing for composite compression members composed of a steel-
encased concrete core meeting requirements of Section 2610 (o) 6 shall conform
to U.B.C. Standard No. 27-1, Grades A53, A500 and A501.
(g) Admixtures. Admixtures to be used in concrete shall be subject to prior
approval by the building official.
An admixture shall be shown capable of maintaining essentially the same
composition and performance throughout the work as the product used in estab-
lishing concrete proportions in accordance with Section 2604 (c).
Admixtures containing chloride ions shall not be used in prestressed concrete
or in concrete containing aluminum embedments if their use will produce a
deleterious concentration of chloride ions in the mixing water.
Air-entraining admixtures shall conform to U.B.C. Standard No. 26-9.
Water-reducing admixtures, retarding admixtures, accelerating admixtures,
water-reducing and retarding admixtures, and water-reducing and accelerating
admixtures shall conform to U.B.C. Standard No. 26-9.
Fly ash or other pozzolans used as admixtures shall conform to U.B.C.
Standard No. 26-9.
(h) Storage of Materials. Cement and aggregate shall be stored in such manner
as to prevent deterioration or intrusion of foreign matter. Any material that has
deteriorated or has been contaminated shall not be used for concrete.
(i) Material and Test Standards. The quality, testing and design of concrete
used structurally in buildings or structures shall conform to the requirements
specified in this chapter and the applicable standards listed in Chapter 60.
The welding of reinforcing steel, metal inserts and connections in reinforced
concrete construction shall conform to U .B.C. Standard No. 26-8.
334
1982 EDITION 2604
335
2604 UNIFORM BUILDING CODE
336
1982 EDITION 2604
337
2604 UNIFORM BUILDING CODE
338
1982 EDITION 2605
339
2605-2606 UNIFORM BUILDING CODE
340
1982 EDITION 2606
except when that portion of the structure in combination with remaining forming
and shoring system has sufficient strength to support safely its weight and loads
placed thereon.
Sufficient strength may be demonstrated by field-cured test cylinders and by a
structural analysis considering proposed loads in relation to field-cured cylinder
strengths and strength of the forming and shoring system. Such analysis and
strength test data shall be furnished by the contractor to the building official when
so required.
Construction loads exceeding the combination of superimposed dead load plus
specified live load shall not be supported on any unshored portion of the structure
under construction, unless analysis indicates adequate strength to support such
additional loads.
Forms shall be removed in such manner as not to impair safety and ser-
viceability of the structure. All concrete to be exposed by form removal shall have
sufficient strength not to be damaged thereby.
Form supports for prestressed concrete members may be removed when suffi-
cient prestressing has been applied to enable prestessed members to carry their
dead load and anticipated construction loads.
(c) Conduits and Pipes Embedded in Concrete. 1. Conduits, pipes and
sleeves of any material not harmful to concrete and within limitations of this
subsection may be embedded in concrete with approval of the building official,
provided they are not considered to replace structurally the displaced concrete.
2. Conduits and pipes of aluminum shall not be embedded in structural con-
crete unless effectively coated or covered to prevent aluminum-concrete reaction
or electrolytic action between aluminum and steel.
3. Conduits, pipes and sleeves passing through a slab, wall or beam shall not
impair significantly the strength of the construction.
4. Conduits and pipes, with their fittings, embedded within a column shall not
displace more than 4 percent of the area of cross section on which strength is
calculated or which is required for fire protection.
5. Except when plans for conduits and pipes are approved by the building
official, conduits and pipes embedded within a slab, wall or beam (other than
those merely passing through) shall satisfy the following:
A. They shall be not larger in outside dimension than one third the overall
thickness of slab, wall or beam in which they are embedded.
8. They shall be spaced not closer than three diameters or widths on center.
C. They shall not impair significantly the strength of the construction.
6. Conduits, pipes and sleeves may be considered as replacing structurally in
compression the displaced concrete, provided:
A. They are not exposed to rusting or other deterioration,
B. They are of uncoated or galvanized iron or steel not thinner than standard
Schedule 40 steel pipe, and
C. They have a nominal inside diameter not over 2 inches and are spaced not
less than three diameters on centers.
341
2606 UNIFORM BUILDING CODE
342
1982 EDITION 2606-2607
343
2607 UNIFORM BUILDING CODE
344
1982 EDITION 2607
Individual bars within a bundle terminated within the span of flexural members
shall terminate at different points with at least 40db stagger.
Where spacing limitations and minimum concrete cover are based on bar
diameter db, a unit of bundled bars shall be treated as a single bar of a diameter
derived from the equivalent total area.
3. Prestressing tendons and ducts. Clear distance between pretensioning
tendons at each end of a member shall be not less than 4db for wire, nor 3db for
strands. See also the second paragraph of Section 2603 (d). Closer vertical
spacing and bundling of strands may be permitted in the middle portion of a span.
Posttensioning ducts may be bundled if it is shown that concrete can be
satisfactorily placed and if provision is made to prevent the tendons, when
tensioned, from breaking through the duct.
(h) Concrete Protection for Reinforcement. 1. Cast-in-place concrete
(nonprestressed). The following minimum concrete cover shall be provided for
reinforcement:
MINIMUM COVER, INCHES
345
2607 UNIFORM BUILDING CODE
346
1982 EDITION 2607
347
2607 UNIFORM BUILDING CODE
348
1982 EDITION 2607
C. Ties shall be arranged such that every corner and alternate longitudinal bar
shall have lateral support provided by the corner of a tic with an included angle of
not more than 135 degrees and a bar shall be not farther than o inches clear on each
side along the tie from such a laterally supported bar. Where longitudinal bars arc
located around the perimeter of a circle, a complete circular tic may be used.
D. In Seismic Zones Nos 0 and I, column lateral tics shall be as specified in
Section 2607 (b) 3. In Seismic Zones Nos. 2, 3 and 4. lateral tic'> shall have a IJ'i-
degree minimum tum plus an extension of at least six bar diameters. but not less
than 4 inches at the free end.
Additional ties which engage at least four vertical column bars shall be
provided around anchor bolts which arc set in the top of a column for buildings
located in Seismic Zones Nos. 2. 3 and 4. Such tics shall be within 'i inches of the
top of the column and shall consist of two No.4 or three No.3 bars.
E. Ties shall be located vertically not more than half a tic spacing above the top
of footing or slab in any story and shall be spaced as provided herein to not more
than half a tie spacing below the lowest horizontal reinforcement in members
supported above.
F. Where beams or brackets frame into all sides of a column. tics may be
terminated not more than 3 inches below the lowest reinforcement in such bcatm
or brackets.
(I) Lateral Reinforcement for Flexural Members. Compression reinforce-
ment in beams shall be enclosed by tics or stirrups satisfying the size and spacing
limitations in Section 2607 (k) 3 or by welded wire fabric of equivalent area. Such
ties or stirrups shall be provided throughout the distance where compn.:ssion
reinforcement is required.
Lateral reinforcement for flexural framing members subject to stress reversals
or to torsion at supports shall consist of closed tics. closed stirrups. or spirab
extending around the flexural reinforcement.
Closed ties or stirrups may be formed in one piece by overlapping standard
stirrup or tie end hooks around a longitudinal bar. or formed in one or two pieces
lap spliced with a Class C splice (lap of 1.7/"). or anchored in accordance with
Section 2612 (o).
(m) Shrinkage and Temperature Reinforcement. Reinforcement for
shrinkage and temperature stresses normal to flexural reinforcement shall be
provided in structural floor and roof slabs where the flexural reinforcement
extends in one direction only.
349
2607-2608 UNIFORM BUILDING CODE
Shrinkage and temperature reinforcement shall be spaced not farther apart than
five times the slab thickness nor 18 inches. At all sections where required,
reinforcement for shrinkage and temperature stresses shall develop the specified
yield strengthfv in tension in accordance with Subsection 2612 (b) or 2612 (q).
350
1982 EDITION 2608
20 (I - P ;b p' ) percent
The modified negative moments shall be used for calculating moments at
sections within the spans.
Redistribution of negative moments shall be made only when the section, at
which moment is reduced, is so designed that p or p - p' is not greater than
0.50 pb, where
87,000
87,000 +!y ................ (8- 1)
352
1982 EDITION 2608
Solid or ribbed slabs built integrally with supports, with clear spans not more
than 10 feet, may be analyzed as continuous slabs on knife edge supports with
spans equal to the clear spans of the slab and width of beams otherwise neglected.
(i) Columns. Columns shall be designed to resist the axial forces from factored
loads on all floors or roof and the maximum moment from factored loads on a
single adjacent span of the floor or roof under consideration. Loading condition
giving the maximum ratio of moment to axial load shall also be considered.
In frames or continuous construction, consideration shall be given to the effect
of unbalanced floor or roof loads on both exterior and interior columns and of
eccentric loading due to other causes.
In computing moments in columns due to gravity loading, far ends of columns
built integrally with the structure may be considered fixed.
Resistance to moments at any floor or roof level shall be provided by distribut-
ing the moment between columns immediately above and below the given floor in
proportion to the relative column stiffnesses and conditions of restraint.
U) Arrangement of Live Load. Live load may be considered to be applied
only to the floor or roof under consideration, and far ends of columns built
integrally with the structure may be considered fixed.
Arrangement of live load may be limited to combinations of:
I. Factored dead load on all spans with full-factored live load on two adjacent
spans, and
2. Factored dead load on all spans with full-factored live load on alternate
spans.
(k) T-beam Construction. l. In T-beam construction, the flange and web shall
be built integrally or otherwise effectively bonded together.
2. Width of slab effective as aT-beam flange shall not exceed one fourth the
span length of the beam, and the effective overhanging slab width on each side of
the web shall not exceed:
A. Eight times the slab thickness, nor
B. One halfthe clear distance to the next web.
3. For beams with a slab on one side only, the effective overhanging flange
width shall not exceed:
A. One twelfth the span length of the beam,
B. Six times the slab thickness, nor
C. One half the clear distance to the next web.
4. Isolated beams, in which the T-shape is used to provide a flange for
additional compression area, shall have a flange thickness not less than one half
the width of web and an effective flange width not more than four times the width
of web.
5. Where primary flexural reinforcement in a slab that is considered as a T-
beam flange (excluding joist construction) is parallel to the beam, reinforcement
perpendicular to the beam shall be provided in the top of the slab in accordance
with the following:
353
2608 UNIFORM BUILDING CODE
(m) Separate Floor Finish. A floor finish shall not be included as part of a
structural member unless placed monolithically with the floor slab or designed in
accordance with requirements of Section 2617. All concrete floor finishes may be
considered as part of required cover or total thickness for nonstructural
considerations.
354
1982 EDITION 2609
355
2609 UNIFORM BUILDING CODE
except that where D or L reduces the effect of H, 0.9D shall be substituted for
356
1982 EDITION 2609
1.4D and zero value of L shall be used to determine the greatest required strength
U. For any combination of D, L and H, required strength U shall be not less than
Formula (9-l ).
5. If resistance to lateral liquid pressure F is included in design, load combina-
tions of Section 2609 (c) 4 shall apply, except that 1.4F shall be substituted for
l. 7H. Vertical liquid pressure shall be considered as dead load D, with due regard
to variation in liquid depth.
6. If resistance to impact effects is taken into account in design, such effects
shall be included with live load L.
7. Where structural effects T of differential settlement, creep, shrinkage or
temperature change may be significant in design, required strength U shall be at
least equal to
357
2609 UNIFORM BUILDING CODE
(e) Design Strength for Reinforcement. Designs shall not be based on a yield
strength of reinforcement fy in excess of 80,000 psi, except for prestressing
tendons.
(f) Control of Deflections. l. General. Reinforced concrete members subject
to flexure shall be designed to have adequate stiffness to limit deflections or any
deformations that may adversely affect strength or serviceability of a structure at
service loads. (See Section 2307 for deflection limits.)
2. One-way construction (nonprestressed). A. Minimum thickness stipu-
lated in Table No. 26-D shall apply for one-way construction not supporting or
attached to partitions or other construction likely to be damaged by large deflec-
tions, unless computation of deflection indicates a lesser thickness may be used
without adverse effects.
B. Where deflections are to be computed, deflections that occur immediately
on application of load shall be computed by usual methods or formulas for elastic
deflections, considering effects of cracking and reinforcement on member
stiffness.
C. Unless stiffness values are obtained by a more comprehensive analysis,
immediate deflection shall be computed with the modulus of elasticity Ec for
concrete as specified in Section 2608 (f) (normal weight or lightweight concrete)
and with the effective moment of inertia as follows, but not greater than I 8 .
3 3
/e = ( Mer
Ma ) /g +[ l -(Mer
Ma ) ] fer .............. . (9-7)
WHERE:
-
Mer- fJg ........................ (9-8)
Yr
and for normal-weight concrete
358
1982 EDITION 2809
F. Deflection computed in accordance with this section shall not exceed limits
stipulated in Section 2307.
3. 1\vo-way construction (nonprestressed). Minimum thickness of slabs of
other two-way construction designed in accordance with provisions of Section
2613 and having a ratio of long to short span not exceeding 2 shall be governed by
Formulas (9-10), (9-ll) and (9-12) and the other provisions ofthis section.
In (800 + 0.005/,)
h == [ ( )] ..... (9-10)
36,000 + 5000{3 am - 0.5 (l - /3
5
) l +~
but not less than
However, the thickness shall be not less than the following values:
For slabs without beams or drop panels ...................... 5 inches
For slabs without beams, but with drop
panels conforming to the following paragraph ............... 4 inches
For slabs with beams on all four edges
with a value of am at least equal to 2.0 ................... 3Y2 inches
For slabs without beams, but with drop panels extending in each direction from
center line of support, a distance not less than one sixth the span length in that
direction measured center-to-center of supports, and a projection below the slab at
least one fourth the slab thickness beyond the drop, thickness required by Formula
(9-10), (9-ll) or (9-12) may be reduced by l 0 percent.
At discontinuous edges, an edge beam shall be provided with a stiffness ratio a
not less than 0.80; or the minimum thickness required by Formula (9-10), (9-11),
(9-12) or the previous paragraph, shall be increased by at least 10 percent in the
panel with a discontinuous edge.
Slab thickness less than the minimum thickness required by this section may be
used if shown by computation that deflection will not adversely affect strength or
serviceability of a structure at service loads. Deflections shall be computed taking
into account size and shape of panel, conditions of support, and nature of
restraints at panel edges. For deflection computations, modulus of elasticity Ec
for concrete shall be as specified in Section 2608 (f). Effective moment of inertia
359
2609-2610 UNIFORM BUILDING CODE
shall be that given by Formula (9-7); other values may be used if computed
deflection is in reasonable agreement with results of comprehensive tests. Addi-
tional long-time deflection shall be computed in accordance with Section 2609 (f)
2F.
4. Prestressed concrete construction. For flexural members designed in
accordance with provisions of Section 2618, immediate deflection shall be
computed by usual methods or formulas for elastic deflections, and the moment
of inertia of the gross concrete section may be used for uncracked sections.
Additional long-time deflection of prestressed concrete members shall be
computed taking into account stresses in concrete and steel under sustained load
and including effects of creep and shrinkage of concrete and relaxation of steel.
Deflection shall not exceed limits stipulated in Section 2307.
5. Composite construction. A. Shored construction. If composite flexural
members are supported during construction so that, after removal of temporary
supports, dead load is resisted by the full composite section, the composite
member may be considered equivalent to a monolithically cast member for
computation of deflection. For nonprestressed members, the portion of the
member in compression shall determine whether values in Table No. 26-D for
normal-weight or lightweight concrete shall apply. If deflection is computed,
account should be taken of curvatures resulting from differential shrinkage of
precast and cast-in-place components, and of axial creep effects in a prestressed
concrete member.
Deflection shall not exceed limits stipulated in Section 2307.
B. Unshored construction. If the thickness of a nonprestressed precast flex-
ural member meets the requirements of Table No. 26-D, deflection need not be
computed. If the thickness of a nonprestressed composite member meets the
requirements of Table No. 26-D, deflection occurring after the member becomes
composite need not be computed, but the long-time deflection of the precast
member should be investigated for magnitude and duration of load prior to
beginning of effective composite action.
Deflection shall not exceed limits stipulated in Section 2307.
Flexure and Axial Loads
Sec. 2610. (a) Notations.
a = depth of equivalent rectangular stress block as defined in Section 2610
(c) 7.
A = effective tension area of concrete surrounding the flexural tension
reinforcement and having the same centroid as that reinforcement,
divided by the number of bars or wires, square inches. When the
flexural reinforcement consists of different bar or wire sizes, the num-
ber of bars or wires shall be computed as the total area of reinforcement
divided by the area of the largest bar or wire used.
Ac = area of core of spirally reinforced compression member measured to
outside diameter of spiral, square inches.
A 8 = gross area of section, square inches.
360
1982 EDITION 2610
361
2610 UNIFORM BUILDING CODE
362
1982 EDITION 2610
equivalent compression zone bounded by edges of the cross section and a straight
line located parallel to the neutral axis at a distance a = {3 1c from the fiber of
maximum compressive strain.
8. Distance c from fiber of maximum strain to the neutral axis shall be
measured in a direction perpendicular to the axis.
C. Factor {3 1 shall be taken as 0.85 for concrete strengthsf'c up to and including
4000 psi. For strengths above 4000 psi, {3 1 shall be reduced continuously at a rate
of 0.05 for each 1000 psi of strength in excess of 4000 psi, but {3 1 shall not be
taken less than 0.65.
(d) General Principles and Requirements. 1. Design of cross section subject
to flexure or axial loads or to combined flexure and axial loads shall be based on
stress and strain compatibility using assumptions in Section 2610 (c).
2. Balanced strain conditions exist at a cross section when tension reinforce-
ment reaches the strain corresponding to its specified yield strength f,. just as
concrete in compression reaches its assumed ultimate strain of0.003.
3. For flexural members, and for members subject to combined flexure and
compressive axial load when the design axial load strength cpP n is less than the
smaller of 0. 10f' c A!( or cpP b , the ratio of reinforcement p provided shall not
exceed 0.75 of the ratio pb that would produce balanced strain conditions for the
section under flexure without axial load. For members with compression rein-
forcement, the portion of Pb equalized by compression reinforcement need not be
reduced by the 0. 75 factor.
4. Compression reinforcement in conjunction with additional tension rein-
forcement may be used to increase the strength of flexural members.
5. Design axial load strength cpP n of compression members shall not be taken
greater than the following:
A. For nonprestressed members with spiral reinforcement conforming to
Section 2607 (k) 2 or composite members conforming to Section 2610 (o):
C. For prestressed members, design axial load strength cpP n shall not be taken
greater than 0.85 (for members with spiral reinforcement) or 0.80 (for members
with tie reinforcement) of the design axial load strength at zero eccentricity cpP 0
6. Members subject to compressive axial load shall be designed for the
maximum moment that can accompany the axial load. The factored axial load P u
at given eccentricity shall not exceed that given in Section 2610 (d) 5. The
maximum factored moment M u shall be magnified for slenderness effects in
accordance with Section 2610 (k).
(e) Distance Between Lateral Supports of Flexural Members. Spacing of
363
2610 UNIFORM BUILDING CODE
lateral supports for a beam shall not exceed 50 times the least width b of
compression flange or face.
Effects of lateral eccentricity of load shall be taken into account in determining
spacing of lateral supports.
(f) Minimum Reinforcement of Flexural Members. I. At any section of a
flexural member, except as provided in Sections 2610 (f) 2 and 2610 (f) 3 where
positive reinforcement is required by analysis, the ratio p provided shall be not
less than that given by:
In T-beams and joists where the web is in tension, the ratio p shall be computed for
this purpose using width of web.
2. Alternatively, area of reinforcement provided at every section, positive or
negative, shall be at least one-third greater than that required by analysis.
3. For structural slabs of uniform thickness, minimum area and maximum
spacing of reinforcement in the direction of the span shall be as required for
shrinkage and temperature according to Section 2607 (m).
(g) Distribution of Flexural Reinforcement in Beams and One-way Slabs.
I . This section prescribes rules for distribution of flexural reinforcement to
control flexural cracking in beams and in one-way slabs (slabs reinforced to resist
flexural stresses in only one direction).
2. Distribution of flexural reinforcement in two-way slabs shall be as required
by Section 2613 (e).
3. Flexural tension reinforcement shall be well distributed within maximum
flexural tension zones of a member cross section as required by Section
2610 (g) 4.
4. When design yield strengthfy for tension reinforcement exceeds 40,000 psi,
cross sections of maximum positive and negative moment shall be so propor-
tioned that the quantity z given by
364
1982 EDITION 2610
smaller. If the effective flange width exceeds one tenth the span, some longitudi-
nal reinforcement shall be provided in the outer portions of the flange.
7. If the depth of the web exceeds 3 feet longitudinal reinforcement having a
total area equal to at least I 0 percent of the area of the flexural tension, reinforce-
ment shall be placed near the side faces of the web and distributed in the zone of
flexural tension with a spacing not more than the web width nor 12 inches. Such
reinforcement may be included in strength computations only if a strain com-
patibility analysis is made to determine stresses in the individual bars or wires.
(h) Deep Flexural Members. I. Flexural members with overall depth to clear
span ratios greater than two fifths for continuous spans, or four fifths for simple
spans, shall be designed as deep flexural members, taking into account nonlinear
distribution of strain and lateral buckling.
2. Design of deep flexural members for shear effects shall be in accordance
with Section 2611 (i).
3. Minimum flexural tension reinforcement shall conform to Section 2610 (f).
4. Minimum horizontal and vertical reinforcement in the side faces of deep
flexural members shall be the greater of the requirements of Section 2611 (i) 8 or
Section 2614 (c) 9.
365
2610 UNIFORM BUILDING CODE
3. Ratio of spiral reinforcement p5 shall be not less than the value given by
A
Ps = 0.45 (~- I ) f' f: ................... (10-5)
where fY is the specified yield strength of spiral reinforcement but not more than
60,000 psi.
(k) Slenderness Effects in Compression Members. 1. Design of compres-
sion members shall be based on forces and moments determined from analysis of
the structure. Such analysis shall take into account influence of axial loads and
variable moment of inertia on member stiffness and fixed-end moments, effect of
deflections on moments and forces and the effects of duration of loads.
2. In lieu of the procedure prescribed in Section 2610 (k) 1, slenderness effects
in compression members may be evaluated in accordance with the approximate
procedure presented in Section 2610 (1).
3. The detailed requirements of Section 2610 (I) need not be applied if
slenderness effects in compression members are evaluated in accordance with
Section 2610 (k) I .
(I) Approximate Evaluation of Slenderness Effects. 1. Unsupported length
of compression members. A. Unsupported length lu of a compression member
shall be taken as the clear distance between floor slabs, beams or other members
capable of providing lateral support for that compression member.
8. Where column capitals or haunches are present, unsupported length shall be
measured to the lower extremity of capital or haunch in the plan considered.
2. Effective length of compression members. A. For compression members
braced against sidesway, effective length factor k shall be taken as 1.0, unless
analysis shows that a lower value may be used.
8. For compression members not braced against sides way, effective length
factor k shall be determined with due consideration of cracking and reinforcement
on relative stiffness, and shall be greater than 1.0.
3. Radius of gyration. Radius of gyration r may be taken equal to 0. 30 times
the overall dimension in the direction stability is being considered for rectangular
compression members and 0.25 times the diameter for circular compression
members. For other shapes, r may be computed for the gross concrete section.
4. Consideration of slenderness effects. A. For compression members braced
against sides way, effects of slenderness may be neglected when kl)r is less than
34- 12M/M2 .
B. For compression members not braced against sidesway, effects of slender-
ness may be neglected when kl)r is less than 22.
C. For all compression members with kl)r greater than 100, an analysis as
defined in Section 2610 (k) I shall be made.
5. Moment magnification. A. Compression members shall be designed using
the factored axial load P u from a conventional frame analysis and a magnified
366
1982 EDITION 2610
Me = 5M2 . . . . . . . . . . . . . . . . . . . (10-6)
WHERE:
5 =
em
---,1,..--(--P-=-1"':-P-)- ~ l.O ................. (l 0-7)
- u ' c
AND
7T2[
p c = (klu )2 ....... (10-8)
or conservatively
C. In Formula ( 10-7). for members braced against sides way and without
transverse loads between supports, em
may be taken as
MI
em= 0.6 + OAM .................... 00-ll)
2
but not less than 0.4. For all other cases, emshall be taken as 1.0.
D. If computations show that there is no moment at both ends of a compression
member or that computed end eccentricities are less than (0.6 + 0.03h) inches,
M 2 in Formula (10-6) shall be based on a minimum eccentricity of (0.6 + 0.03h)
inches about each principal axis separately. RatioM 1 1M2 in Formula (lO-ll) shall
be determined by either of the following:
(i) When computed end eccentricities are less than (0.6 + 0.03h) inches,
computed end moments may be used to evaluate M 1 1M 2 in Formula
(lO-ll).
(ii) If computations show that there is essentially no moment at both ends of a
compression member, the ratio M 1 IM 2 shall be taken equal to one.
6. Moment magnifier 5 for unbraced frames. A. In frames not braced
against sides way, the value of 5 shall be computed for an entire story, assuming all
columns to be loaded.
B. In Formula ( 10-7), P u and P c shall be replaced by the summations "i.P u and
"i.P c for all columns in a story.
367
2610 UNIFORM BUILDING CODE
C. For design of each column within a story, 8shall be taken as the larger of the
values computed for the entire story according to Section 2610 (I) 6 B or as
computed for the individual column assuming column ends to be braced against
sides way.
D. In frames not braced against sidesway, flexural members shall be designed
for the total magnified end moments of the compression members at the joint.
7. Moment magnifier 8 for biaxial bending. For compression members
subject to bending about both principal axes, moment about each axis shall be
magnified by 8, computed from corresponding conditions of restraint about that
axis.
(m) Axially Loaded Members Supporting Slab System. Axially loaded
members supporting slab system included within the scope of Section 2613 (b)
shall be designed as provided in Section 2610 and in accordance with the
additional requirements of Section 2613.
(n) Transmission of Column Loads Through Floor System. When the
specified compressive strength of concrete in a column is greater than I .4 times
that specified for a floor system, transmission of load through the floor system
shall be provided by one of the following:
I. Concrete of strength specified for the column shall be placed in the floor
about the column for an area four times the column area. Column concrete shall
be well integrated into floor concrete and shall be placed in accordance with
Section 2606 (d).
2. Strength of a column through a floor system shall be based on the lower value
of concrete strength with vertical dowels and spirals as required.
3. For columns laterally supported on four sides by beams of approximately
equal depth or by slabs, strength of the column may be based on an assumed
concrete strength in the column joint equal to 75 percent of column concrete
strength plus 35 percent of floor concrete strength.
(o) Composite Compression Members. I. Composite compression members
shall include all such members reinforced longitudinally with structural steel
shapes, pipe or tubing with or without longitudinal bars.
2. Strength of a composite member shall be computed for the same limiting
conditions applicable to ordinary reinforced concrete members.
3. Any axial load strength assigned to concrete of a composite member shall be
transferred to the concrete by members or brackets in direct bearing on the
composite member concrete.
4. All axial load strength not assigned to concrete of a composite member shall
be developed by direct connection to the structural steel shape, pipe or tube.
5. For evaluation of slenderness effects, radius of gyration of a composite
section shall be not greater than the value given by:
(EJg!5) + EJ,
r = E A 15) E A .................. (I0-!2)
( c g + s I
For computing P c in Formula ( 10-8), E/ of the composite section shall be not
368
19112 I:IJITION 2610
greater than
_ EJ !5
El- I +8 {3d + EJ,. ................... (10-13)
369
2610 UNIFORM BUILDING CODE
(q) Bearing Strength. 1. Design bearing strength on concrete shall not exceed
<f>(0.85f'cA 1 ), except as follows:
A. When the supporting surface is wider on all sides than the loaded area,
design bearing strength on the loaded area may be multiplied by YA;iA"1 , but not
more than 2.
B. When the supporting surface is sloped or stepped, A 2 may be taken as the
area of the lower base of the largest frustum of a right pyramid or cone contained
wholly within the support and having for its upper base the loaded area, and
having side slopes of 1 vertical to 2 horizontal.
2. Section 2610 (q} does not apply to posttensioning anchorages.
370
1982 EDITION 2611
371
2611 UNIFORM BUILDING CODE
372
1982 EDITION 2611
373
2611 UNIFORM BUILDING CODE
(b) Shear Strength. 1. Design of cross sections subject to shear shall be based
on
vu ~ cfNn ......................... (I 1-1)
where V u is factored shear force at section considered and V n is nominal shear
strength computed by
vn = vc + vs ....................... (11-2)
where Vc is nominal shear strength provided by concrete in accordance with
Section 2611 (d) or Section 2611 (e), and v. is nominal shear strength provided by
shear reinforcement in accordance with Section 2611 (f) 6. When determining Vn
the effect of openings shall be taken into consideration.
2. In determining shear strength Vc, whenever applicable, effects of axial
tension due to creep and shrinkage in restrained members shall be considered and
effects of inclined flexural compression in variable-depth members may be
included.
3. When the reaction, in direction of applied shear, introduces compression into
the end regions of a member, calculation of maximum factored shear force V u
shall be as follows:
A. For nonprestressed members, sections located less than a distanced from
face of support may be designed for the same shear Vu as that computed at a
distance d.
8. For prestressed members, sections located less than a distance h 12 from face
of support may be designed for the same shear vu as that computed at a distance
h/2.
4. For deep flexural members, brackets and corbels, walls and slabs and
footings, the special provisions of Section 2611 (i) through (I) shall apply.
(c) Lightweight Concrete. 1. Provisions for shear strength V c and torsional
moment strength Tc apply to normal-weight concrete. When lightweight aggre-
gate concrete is used, one of the following modifications shall apply:
A. When fer is specified and concrete is proportioned in accordance with
Section 2604 (c), provisions for Vc and Tc shall be modified by substitutingfc,/6.7
for v'J':.,
but the value offc,/6. 7 shall not exceed v'J':..
B. When fer is not specified, all values of v'J':.
affecting Vc, Tc, and Mer shall
be multiplied by 0.75 for "all-lightweight" concrete and 0.85 for "sand-light-
weight" concrete. Linear interpolation may be used when partial sand replace-
ment is used.
(d) Shear Strength Provided by Concrete for Nonprestressed Members. 1.
Shear strength Vc shall be computed by provisions of Section 2611 (d) 1 A
through D unless a more detailed calculation is made in accordance with Section
2611 (d) 2.
A. For members subject to shear and flexure only,
374
1982 EDITION 2611
but not greater than 3.5v'l'c bw d. Quantity Vu d!Mu shall not be taken greater
than 1.0 in computing Vc by Formula (11-6), where Mu is factored moment
occuring simultaneously with Vu at section considered.
B. For members subject to axial compression, Formula (11-6) may be used to
compute Vc withMm substituted for Mu and Vud!Mu not then limited to 1.0, where
375
2611 UNIFORM BUILDING CODE
Vc = 10.6
\' ..VJ'J''
c +
700 Vud
M, ) b .,d ......... (11-10)
but Vc need not be taken less than 2Yf'c bwd nor shall Vc be taken greater than
sYf'c bwdnorthe value given in Section 2611 (e) 2 D. The quantity Vud!Mu shall
not be taken greater than 1.0, where Mu is factored moment occurring simul-
taneously with V u at section considered. When applying Formula (Il-l 0), din the
term Vud!M u shall be the distance from extreme compression fiber to centroid of
prestressed reinforcement.
2. Shear strength Vc may be computed in accordance with Section 2611 (e) A
and 8, where Vc shall be the lesser of Vci or Vcw.
A. Shear strength Vci shall be computed by
Alternatively, Vcw may be computed as the shear force corr~nding to dead load
plus live load that results in a principal tensile stress of 4 V f' c at centroidal axis of
376
1982 EDITION 2611
member, or at intersection of flange and web when centroidal axis is in the flange.
In composite members, principal tensile stress shall be computed using the cross
section that resists live load.
C. In Formulas (11-11) and ( 11-13), d shall be the distance from extreme
compression fiber to centroid of prestressed reinforcement of 0. 8h , whichever is
greater.
D. In a pretensioned member in which the section at a distance h/2 from face of
support is closer to end of member than the transfer length of the prestressing
tendons, the reduced prestress shall be considered when computing Vcw. This
value of Vcw shall also be taken as the maximum limit for Formula (11-10).
Prestress force may be assumed to vary linearly from zero at end of tendon to a
maximum at a distance from end of tendon equal to the transfer length, assumed to
be 50 diameters for strand and 100 diameters for single wire.
377
2611 UNIFORM BUILDING CODE
A. = ~ ~ !_ (d ............. (11-15)
so /y d Vii;,
A. + 2A, = SO bwS
/y
................ (11-16)
V5 = A./fl
s
.................... (11-17)
378
1982 EDITION 2611
379
2611 UNIFORM BUILDING CODE
0.8 vfc""ix'y
+ ( 0.4 Vu
)l ............. (11-22)
C,Tu
380
1982 EDITION 2611
perimeter of the closed stirrups, shall not exceed 12 inches. At least one longitudi-
nal bar shall be placed in each comer of the closed stirrups.
9. Design of torsion reinforcement. A. Where factored torsional moment Tu
exceeds torsional moment strength cf>Tc, torsion reinforcement shall be provided
to satisfy Formulas (II-20) and (II-21 ), where torsional moment strength T5 shall
be computed by
_ A,a,x 1 Ydy
Ts- ..................... (11-23)
s
where A, is the area of one leg of a closed stirrup resisting torsion within a distance
s, and a, = [0.66 + 0.33 (y 1/x 1 )] but not more than 1.50. Longitudinal bars
distributed around the perimeter of the closed stirrups A, shall be provided in
accordance with Section 2611 (g) 9 C.
B. A minimum area of closed stirrups shall be provided in accordance with
Section 2611 (f) 5 E.
C. Required area of longitudinal bars A 1 distributed around the perimeter of the
closed stirrups A, shall be computed by
A I-
_ 2A I ( X1 +S Y1) . . . . . . . . . . . . . . . . . (11-24)
or by
~ 2A
SObws .or
1
/y
D. Torsional moment strength Ts shall not exceed 4Tc.
(h) Shear Friction. Provisions of this section may be applied where it is
appropriate to consider shear transfer across a given plane such as an existing or
potential crack, an interface between dissimilar materials or an interface between
two concretes cast at different times.
1. A crack shall be assumed to occur along the shear plane, with relative
displacement along the assumed crack resisted by friction maintained by shear-
friction reinforcement across the assumed crack. Shear-friction reinforcement
shall be placed approximately perpendicular to the assumed crack.
2. Design of cross sections subject to shear transfer shall be based on Formula
381
2611 UNIFORM BUILDING CODE
Vn = 32 ( 10 + dIn ) vfcbwd
r::;- ............... (11-27)
382
1982 EDITION 2611
3. Critical section for shear measured from face of support shall be taken at a
distance 0.15/n for uniformly loaded beams and 0.50a for beams with concen-
trated loads, but not greater than d.
4. Unless a more detailed calculation is made in accordance with Section
2611 (i) 5,
shall not exceed 2.5, and Vc shall not be taken greater than 6V'j')wd. Mu is
factored moment occurring simultaneously with Vu at the critical section defined
in Section 2611 (i) 3.
6. Where factored shear force Vu exceeds shear strength <f>Vc, shear reinforce-
ment shall be provided to satisfy Formulas (11-1) and (11-2), where shear strength
Vs shall be computed by
Vs = [ Av S
(1 +12 ~) + ~(11-12 ~)] /yd
Sz ....... (11-30)
383
2611 UNIFORM BUILDING CODE
shall not be taken greater than twice the depth of bracket or corbel at outside edge
of bearing area.
Brackets and corbels with a shear-span-to-depth ratio aid of one half or less,
may be designed in accordance with provisions of Section 2611 (h), except that all
limitations on quantity and spacing of reinforcement in this section shall apply.
I. Design of brackets and corbels shall be based on Formula (Il-l), where
shear strength V n shall be computed in accordance with Section 2611 (j) 2 or 2611
(j) 3.
2. For brackets and corbels subject to tension due to restrained creep and
shrinkage,
where p shall not exceed 0. 13 f' Jfv and N uc!Vu shall not be taken less than 0. 20.
Tensile force N uc shall be regarded as a live load even when tension results from
creep, shrinkage or temperature change.
3. When provisions are made to avoid tension due to restrained creep and
shrinkage, so that bracket or corbel is subject to shear and moment only,
384
1982 EDITION 2611
Design for horizontal shear forces in plane of wall shall be in accordance with
Section 2611 (k) 2 through 8.
2. Design of horizontal section for shear in plane of wall shall be based on
Formulas (11-1) and (ll-2), where shear strength Vc shall be in accordance with
Section 2611 (k) 5 or 2611 (k) 6 and shear strength Vs shall be in accordance with
Section 2611 (k) 9.
3. Shear strength V" at a!!Y horizontal section for shear in plane of wall shall not
be taken greater than IOVf'chd.
4. For design for horizontal shear forces in plane of wall, d shall be taken equal
to 0.8 lw. A larger value of d, equal to the distance from extreme compression
fiber to center of force of all reinforcement in tension may be used when
determined by a strain compatibility analysis.
5. Unless a more detailed calculation is made in accordance with Section 2611
(k) 6, shear strength Vc shall not be taken greater than 2 Yl'chd for walls subject to
N u in compression, or Vc shall not be taken greater than the value given in Section
2611 (d) 2 C for walls subject toN u in tension.
6. Shear strength Vc may be computed by Formulas (ll-33) and (ll-34), where
V,. shall be the lesser of Formula (11-33) or (11-34).
~ Iii;
Vc = 3.3y'/ chd +
Nwd
41 w
.............. (11-33)
or
Vc= 0.6v.r:-+
lw (!.25v.f;+
M I
0.2-fh-)~ hd ....... (l!-34)
....:..:=.JL- .!.ll
[ VM 2
385
2611 UNIFORM BUILDING CODE
V=~
s s . . . . . . . . . . . . . . . . . . . . . (11-35)
2
nor 0.0025, but need not be greater than the required horizontal shear
reinforcement.
E. Spacing of vertical shear reinforcement s 1 shall not exceed lw/3, 3h nor 18
inches.
(I) Special Provisions for Slabs and Footings. 1 . Shear strength of slabs and
footings in the vicinity of concentrated loads or reactions is governed by the more
severe of two conditions:
A. Beam action for slab or footing, with a critical section extending in a plane
across the entire width and located at a distance d from face of concentrated load
or reaction area. For this condition, the slab or footing shall be designed in
accordance with Section 2611 (b) through (f).
B. Tho-way action for slab or footing, with a critical section perpendicular to
plane of slab and located so that its perimeter b0 is a minimum, but need not
approach closer than d/2 to perimeter of concentrated load or reaction area. For
this condition, the slab or footing shall be designed in accordance with Section
2611 (I) 2 through 4.
2. Design of slab or footing for two-way action shall be based on Formula
( 11-1 ), where shear strength V, shall not be taken greater than shear strength Vc
given by Formula ( 11-37), unless shear reinforcement is provided in accordance
with Section 2611 (I) 3 or 4.
Vc = ( + ;c )~b,d ............. ..
2 (11-37)
but not greater than 4Yf'cb 0 d. f3c is the ratio of long side to short side of
concentrated load or reaction area and bo is perimeter of critical section defined in
Section 2611 (1).
386
1982 EDITION 2611
387
2611 UNIFORM BUILDING CODE
column face to end of shearhead arm. Critical section shall be located so that its
perimeter b0 is a minimum, but need not approach closer than d/2 to perimeter of
column section.
H. Shear strength Vn shall not be taken greater than 4v'f'c b0 d, on the critical
section defined in Section 2611 (I) 4 G. When shearhead reinforcement is
provided, shear strength vn shall not be taken greater than 7v'f'cbod on the
critical section defined in Section 2611 (I) I B.
I. A shearhead may be assumed to contribute a moment resistance Mv to each
slab column strip computed by
388
1982 EDITION 2611-2612
'Yv =I -
I + 213 Jc C]
1 + d ............ (11-40)
-=.....L--'---.:;--
+d
389
2612 UNIFORM BUILDING CODE
390
1982 EDITION 2612
391
2612 UNIFORM BUILDING CODE
392
1982 EDITION 2612
where db is strand diameter in inches, andfps andfse are expressed in kips per
square inch.
Investigation may be limited to cross sections nearest each end of the member
that are required to develop full design strength under specified factored loads.
Where bonding of a strand does not extend to the end of a member, bonded
development length specified in above shall be doubled.
(I) Development of Flexural Reinforcement-General. 1. Tension rein-
forcement may be developed by bending across the web to be anchored or made
continuous with reinforcement on the opposite face of member.
2. Critical sections for development of reinforcement in flexural members are
at points of maximum stress and at points within the span where adjacent
reinforcement terminates or is bent. Provisions of Section 2612 (m) 3 must be
satisfied.
3. Reinforcement shall extend beyond the point at which it is no longer
required to resist flexure for a distance equal to the effective depth of member or
12db, whichever is greater, except at supports of simple spans and at free end of
cantilevers.
4. Continuing reinforcement shall have an embedment length not less than the
development length ld beyond the point where bent or terminated tension rein-
forcement is no longer required to resist flexure.
5. Flexural reinforcement shall not be terminated in a tension zone unless one
of the following conditions is satisfied:
A. Shear at the cutoff point does not exceed two thirds that permitted, including
shear strength of shear reinforcement provided.
B. Stirrup area in excess of that required for shear and torsion is provided along
each terminated bar or wire over a distance from the termination point equal to
three fourths the effective depth of member. Excess stirrup area Av shall be not
less than 60bws lfy Spacings shall not exceed d!8{3b where {3b is the ratio of area of
reinforcement cut off to total area of tension reinforcement at the section.
C. For No. 11 bar and smaller, continuing reinforcement provides double the
area required for flexure at the cutoff point and shear does not exceed three fourths
that permitted.
6. Adequate end anchorage shall be provided for tension reinforcement in
flexural members where reinforcement stress is not directly proportional to
moment, such as: sloped, stepped or tapered footings; brackets; deep flexural
members; or members in which tension reinforcement is not parallel to compres-
sion face.
(m) Development of Positive Moment Reinforcement. 1. At least one third
the positive moment reinforcement in simple members and one fourth the positive
moment reinforcement in continuous members shall extend along the same face
of member into the support. In beams, such reinforcement shall extend into the
support at least 6 inches.
2. When a flexural member is part of a primary lateral load-resisting system,
positive moment reinforcement required to be extended into the support by
Section 2612 (m) I shall be anchored to develop the specified yield strengthfy in
393
2612 UNIFORM BUILDING CODE
Id <
- M.n
Vu + Ia . . . . . . . . . . . . . . . . . . . . (12-l)
WHERE:
M n is nominal strength assuming all reinforcement at the section to be
stressed to the specified yield strengthfy.
V u is factored shear force at the section.
la at a support shall be the sum of the embedment length beyond the center
of support and the equivalent embedment length of any hook or
mechanical anchorage provided.
Ia at a point of inflection shall be limited to the effective depth or member
of 12 db, whichever is greater.
394
1982 EDITION 2612
395
2612 UNIFORM BUILDING CODE
396
1982 EDITION 2612-2613
varies fromfy in compression to one half !y or less in tension, lap splices, butt
welded splices, mechanical connections or end bearing splices may be used. Total
tensile strength provided in each face of the column by splices alone or by splices
in combinations with continuing unspliced bars at specified yield strengthfv shall
be at least twice the calculated tension in that face of the column but not less than
required by Section 2612 (s) 3.
2. Where factored load stress in longitudinal bars in a column, calculated for
any loading combination, exceeds one halffy in tension, lap splices designed to
develop the specified yield strengthfv in tension, or full-welded splices or full
mechanical connections in accordance with Section 2612 (p) 3 C and D.
3. At horizontal cross sections of columns where splices are located, a mini-
mum tensile strength in each face of the column equal to one fourth the area of
vertical reinforcement in that face multiplied by !y shall be provided.
(t) Splices of Welded Deformed Wire Fabric in Thnsion. Minimum length of
lap for lap splices of welded deformed wire fabric measured between the ends of
each fabric sheet shall be not less than 1. 71d nor 8 inches, and the overlap
measured between outermost cross wires of each fabric sheet shall be not less than
2 inches, ld shall be the development length for the specified yield strengthfv in
accordance with Section 2612 (i).
Lap splices of welded deformed wire fabric, with no cross wires within the lap
splice length, shall be determined as for deformed wire.
(u) Splices of Welded Smooth Wire Fabric in Thnsion. Minimum length of
lap for lap splices of welded smooth wire fabric shall be in accordance with the
following:
I. When area of reinforcement provided is less than twice that required by
analysis at splice location, length of overlap measured between outermost cross
wires of each fabric sheet shall be not less than one spacing of cross wires plus 2
inches, nor less than I . 5 Id nor 6 inches, Id shall be the development length for the
specified yield strengthfy in accordance with Section 2612 U).
2. When area of reinforcement provided is at least twice that required by
analysis at splice location, length of overlap measured between outermost cross
wires of each fabric sheet shall be not less than 1.5 ld2, nor 2 inches, ld shall be the
development length for the specified yield strengthfv in accordance with Section
2612 U). .
397
2613 UNIFORM BUILDING CODE
398
1982 EDITION 2613
stiffness of the slabs and beams at a joint taken in the direction of the
span for which moments are being determined.
Kec
L (Ks + Kb)
amin minimum acto satisfy Section 2613 (h) 10 A.
a1 a in direction of / 1
a2 a in direction of /2
{30 ratio of dead load per unit area to live load per unit area (in each case
without load factors).
{31 = ratio of torsional stiffness of edge beam section to flexural stiffness of a
width of slab equal to span length of beam, center-to-center of supports.
EcbC
2Ec)s
Bs factor defined by Formula (13-5). See Section 2613 (h) 10.
'Y, = fraction of unbalanced moment transferred by flexure at slab-column
connections. See Section 2613 (d) 6.
(b) Scope. 1. The provisions of this section shall apply for design of slab
systems reinforced for flexure in more than one direction with or without beams
between supports.
2. A slab system may be supported on columns or walls. If supported by
columns, no portion of a column capital shall be considered for structural
purposes that lies outside the largest right circular cone or pyramid with a 90-
degree vertex that can be included within the outlines of a supporting element.
3. Solid slabs and slabs with recesses or pockets made by permanent or
removable fillers between ribs or joists in two directions are included within the
scope of this section.
4. Slabs with paneled ceilings are included within the scope of this section,
provided the panel of reduced thickness lies entirely within middle strips, and is
not less than two thirds the thickness ofthe remainder of the slab, exclusive of the
drop panel, nor less than 4 inches thick.
5. Minimum thickness of slabs designed in accordance with this section shall
be as required by Section 2609 (f) 3.
(c) Definitions. 1. Column strip is a design strip with a width on each side of a
column center line equal to 0.25/2 or 0.2511 , whichever is less. Column strip
includes beams, if any.
2. Middle strip is a design strip bounded by two column strips.
3. A panel is bounded by column, beam or wall center lines on all sides.
4. For monolithic or fully composite construction, a beam includes that portion
of slab on each side of the beam extending a distance equal to the projection of the
beam above or below the slab, whichever is greater, but not greater than four times
the slab thickness.
(d) Design Procedures. I. A slab system may be designed by any procedure
satisfying conditions of equilibrium and geometrical compatibility if shown that
399
2613 UNIFORM BUILDING CODE
the design strength at every section is at least equal to the required strength
considering Section 2609 (c), and that all serviceability conditions, including
specified limits on deflections, are met.
2. A slab system, including the slab and beams (if any) between supports, and
supporting columns or walls may be designed by either the direct design method
[Section 2613 (h)] or the equivalent frame method [Section 2613 (i)].
3. The slab and beams (if any) between supports shall be proportioned for
factored moments prevailing at every section.
4. When gravity load, wind, earthquake or other lateral forces cause transfer of
moment between slab and column, a fraction of the unbalanced moment shall be
transferred by flexure in accordance with Section 2613 (b) 5.
The fraction of unbalanced moment not transferred by flexure shall be trans-
ferred by eccentricity of shear in accordance with Section 2611 (m) 2.
5. The fraction of the unbalanced moment given by
1
y1 =
1 + ?:_~c 1 + d ................. (13-1)
3 c~ +d
shall be considered transferred by flexure over an effective slab width between
lines that are one and one-half slab or drop panel thickness ( 1.5h) outside opposite
faces of the column or capital.
Concentration of reinforcement over the column by closer spacing or additional
reinforcement may be used to resist moment on the effective slab width.
6. Design for transfer of load from slab to supporting columns or walls through
shear and torsion shall be in accordance with Section 2611 .
(e) Slab Reinforcement. I. Area of reinforcement in each direction for two-
way slab systems shall be determined from moments at critical sections but shall
be not less than required by Section 2607 (m).
Spacing of reinforcement at critical sections shall not exceed two times the slab
thickness, except for portions of slab area that may be of cellular or ribbed
construction. In the slab over cellular spaces, reinforcement shall be provided as
required by Section 2607 (m).
2. Positive moment reinforcement perpendicular to a discontinuous edge shall
extend to the edge of slab and have embedment, straight or hooked, at least 6
inches in spandrel beams, columns or walls.
3. Negative moment reinforcement perpendicular to a discontinuous edge
shall be bent, hooked or otherwise anchored, in spandrel beams, columns or
walls, to be developed at face of support according to provisions of Section 2612.
4. Where a slab is not supported by a spandrel beam or wall at a discontinuous
edge or where a slab cantilevers beyond the support, anchorage of reinforcement
may be within the slab.
5. In slabs with beams between supports with a value of a greater than 1.0,
special top and bottom slab reinforcement shall be provided at exterior comers in
accordance with the following:
400
1982 EDITION 2613
A. The special reinforcement in both top and bottom of slab shall be sufficient
to resist a moment equal to the maximum positive moment (per foot of width) in
the slab.
8. Direction of moment shall be assumed parallel to the diagonal from the
comer in the top of the slab and perpendicular to the diagonal in the bottom of the
slab.
C. The special reinforcement shall be provided for a distance in each direction
from the comer equal to one fifth the longer span.
D. In either the top or bottom of the slab, the special reinforcement may be
placed in a single band in the direction of the moment or in two bands parallel to
the sides of the slab.
6. Where a drop panel is used to reduce amount of negative moment reinforce-
ment over the column of a flat slab, size of drop panel shall be in accordance with
the following:
A. Drop panel shall extend in each direction from center line of support a
distance not less than one sixth the span length measured from center-to-center of
supports in that direction.
8. Projection of drop panel below the slab shall be at least one fourth the slab
thickness beyond the drop.
C. In computing required slab reinforcement, thickness of drop panel below
the slab shall not be assumed greater than one fourth the distance from edge of
drop panel to edge of column or column capital.
(f) Details of Reinforcement in Slabs Without Beams. In addition to the other
requirements of Section 2613 (e), reinforcement in slabs without beams shall have
minimum bend point locations and extensions for reinforcement as prescribed in
Figure No. 26-l.
Where adjacent spans are unequal, extension of negative reinforcement beyond
the face of support as prescribed in Figure No. 26-1 shall be based on require-
ments oflonger span. Bent bars may be used only when depth-span ratio permits
use of bends 45 degrees or less.
For slabs in frames not braced against sidesway and for slabs resisting lateral
loads, lengths of reinforcement shall be determined by analysis but shall be not
less than those prescribed in Figure No. 26-1.
(g) Openings in Slab Systems. I . Openings of any size may be provided in
slab systems if shown by analysis that the design strength is at least equal to the
required strength considering Section 2609 (c) and (d), and that all serviceability
conditions, including the specified limits on deflections, are met.
2. In lieu of special analysis as required by Section 2613 (g) I, openings may
be provided in slab systems without beams when in accordance with the
following:
A. Openings of any size may be located in the area common to intersecting
middle strips, provided total amount of reinforcement required for the panel
without the opening is maintained.
B. In the area common to intersecting column strips, not more than one eighth
the width of column strip in either span shall be interrupted by openings. An
401
2613 UNIFORM BUILDING CODE
a 1l/
a 2[ 2
1
(13-2)
C. Where the transverse span of panels on either side of the center line of
supports varies, /2 in Formula (13-3) shall be taken as the average of adjacent
transverse spans.
D. When the span adjacent and parallel to an edge is being considered, the
distance from edge to panel center line shall be substituted for 12 in Formula
(13-3).
E. Clear span In shall extend from face to face of columns, capitals, brackets or
402
1982 EDITION 2613
walls. Value of In used in Formula (13-3) shall be not less than 0.651 1 . Circular or
regular polygon-shaped supports shall be treated as square supports with the same
area.
3. Negative and positive factored moments. Negative factored moments
shall be located at face of rectangular supports. Circular or regular polygon-
shaped supports shall be treated as square supports with the same area.
In an interior span, total static moment M 0 shall be distributed as follows:
Negative factored moment ................................... 0.65
Positive factored moment. ................................... 0.35
Intenor 10-
. f actored moment. . . . . . . . . . . . . . . . . . . 0 . 75 - - -
. negative
1 +1-
ace
. negative
Extenor . f actored moment ......................... -0.65
--
1
1+-
aer
where aec is computed in accordance with Section 2613 (i) 7 for the exterior
column.
Negative moment sections shall be designed to resist the larger of the two
interior negative factored moments determined for spans framing into a common
support unless an analysis is made to distribute the unbalanced moment in
accordance with stiffness of adjoining elements.
Edge beams or edges of slab shall be proportioned to resist in torsion their share
of exterior negative factored moments.
4. Factored moments in column strips. Column strips shall be proportioned
to resist the following percentage of interior negative factored moments:
403
2613 UNIFORM BUILDING CODE
404
1982 EDITION 2613
panels and the center lines of the adjacent panels parallel to the long sides.
Beams with (o: 1/ 2 11 1) less than 1.0 may be proportioned to resist shear obtained
by linear interpolation, assuming beams carry no load at o: = 0. In addition to
shears calculated according to this section, beams shall be proportioned to resist
shears caused by factored loads applied directly on beams.
Slab shear strength may be computed on the assumption that load is distributed
to supporting beams in accordance with the preceding paragraph. Resistance to
total shear occurring on a panel shall be provided.
Shear strength shall satisfy requirements of Section 2611.
9. Factored moments in columns and walls. Columns and walls built inte-
grally with a slab system shall resist moments caused by factored loads on the slab
system.
At an interior support, supporting elements above and below the slab shall
resist the moment specified by Formula (13-4) in direct proportion to their
stiffnesses unless a general analysis is made.
Os=l+~~~~(~-~)
!Jja o,,,,
............... (13-5)
where {30 is ratio of dead load to live load, per unit area (in each case without load
factors).
(i) Equivalent Frame Method. I. Design of slab systems by the equivalent
frame method shall be based on assumptions given in Section 2613 (i) 2 through
6, and all sections of slabs and supporting members shall be proportioned for
moments and shears thus obtained.
Where metal column capitals are used, account may be taken of their contribu-
tions to stiffness and resistance to moment and to shear.
Change in length of columns and slabs due to direct stress, and deflections due
to shear, may be neglected.
2. Equivalent frame. The structure shall be considered to be made up of
405
2613 UNIFORM BUILDING CODE
406
1982 EDITION 2613
K
,= l 9E'",C
~e(~-~r ................... (l3-7)
where c2 and /2 relate to the transverse spans on each side of column. The constant
C in Formula ( 13-7) may be evaluated for the cross section by dividing it into
separate rectangular parts and carrying out the following summation:
Where beams frame into columns in the direction of the span for which
moments are being determined, value of K, as computed by Formula (13-6) shall
be multiplied by the ratio of moment of inertia of slab with such beam to moment
of inertia of slab without such beam.
6. Arrangement of live load. When loading pattern is known, the equivalent
frame shall be analyzed for that load.
When live load is variable but does not exceed three fourths the dead load, or
the nature of live load is such that all panels will be loaded simultaneously,
maximum factored moments may be assumed to occur at all sections with full
factored live load on entire slab system.
For loading conditions other than those defined in the preceding paragraph,
maximum positive factored moment near midspan of a panel may be assumed to
occur with three fourths the full factored live load on the panel and on alternate
panels; and maximum negative factored moment in the slab at a support may be
assumed to occur with three fourths the full live load on adjacent panels only.
Factored moments shall not be taken less than those occurring with full factored
live load on all panels.
7. Factored moments. At interior supports, critical section for negative fac-
tored moment (in both column and middle strips) shall be taken at face of
rectilinear supports, but not greater than 0.175/ 1 from center of a column.
At exterior supports provided with brackets or capitals, critical section for
negative factored moment in the span perpendicular to an edge shall be taken at a
distance from face of supporting element not greater than one half the projection
of bracket or capital beyond face of supporting element.
Circular or regular polygon-shaped supports shall be treated as square supports
with the same area for location of critical section for negative design moment.
Slab systems within limitations of Section 2613 (h) l, when analyzed by the
equivalent frame method, may have resulting computed moments reduced in such
proportion that the absolute sum of the positive and average negative moments
used in design need not exceed the value obtained from Formula (13-3).
Moments at critical sections across the slab-beam strip of each frame may be
407
26132614 UNIFORM BUILDING CODE
distributed to column strips, beams and middle strips as provided in Section 2613
(h) 4, 5 and 6 if the requirement of Section 2613 (h) I F is satisfied.
Moments determined for the equivalent columns in the frame analysis shall be
used in design of the actual columns above and below the slab beams.
Walls
Sec. 2614. (a) Notations.
AR gross area of section, square inches.
f'c specified compressive strength of concrete, psi.
h overall thickness of member, inches.
(. vertical distance between supports, inches.
Pnw nominal axial load strength of wall designed by Section 2614 (c).
cf> = strength reduction factor. See Section 2609 (d).
(b) Structural Design. Walls shall be designed for any lateral or other loads to
which they are subjected. Proper provisions shall be made for eccentric loads and
lateral forces.
Unless designed in accordance with Section 2614 (c), walls subject to com-
bined flexure and axial loads shall be designed under the provisions of Section
2610 (p).
(c) Empirical Design Method. I. Walls may be designed by the empirical
provisions under this section if resultant of the factored axial load is located within
the middle third of the overall thickness of wall and all limits of this section are
satisfied.
EXCEPTION: Limits of thickness and quantity of reinforcement required by
this section may be waived where structural analysis shows adequate strength and
stability.
2. Design axial load strength cf>P nw of a wall within limitations of Section 2614
(c) I shall be computed by
408
1982 EDITION 2614-2615
6. Exterior basement walls, foundation walls, fire walls and party walls shall
be not less than 8 inches thick.
7. Overall thickness of panel and enclosure walls shall be not less than 4
inches, nor less than YJo the distance between supporting or enclosing members.
8. Walls shall be anchored to floors, roofs, or to columns, pilasters, buttresses
and intersecting walls.
9. Area of horizontal reinforcement shall be not less than 0.0025 times gross
area of wall. For reinforcement with specified yield strength of 60,000 psi or
greater, and not larger than No. 5 bar or W31 or 031 welded wire fabric,
reinforcement ratio may be reduced to 0.0020.
Area of vertical reinforcement shall be not less than 0. 0015 times gross area of
wall. For reinforcement with specified yield strength of 60,000 psi or greater, and
not larger than No. 5 bar or W31 or 031 welded wire fabric, reinforcement ratio
may be reduced to 0.0012.
10. Walls greater than 10 inches thick, except basement walls, shall have
reinforcement for each direction placed in two layers parallel with faces of wall in
accordance with the following:
A. One layer consisting of not less than one half and not more than two thirds
the total reinforcement required for each direction shall be placed not less than 2
inches nor more than one third the thickness of wall from exterior surface.
B. The other layer, consisting of the balance of required reinforcement in that
direction, shall be placed not less than 3f4 inch nor more than one third the
thickness of wall from interior surface.
C. Bars, if used, shall be not less than No.3 and spaced not more than 18 inches
on centers. Welded wire fabric, if used, shall be in flat sheet form.
II. In addition to the minimum reinforcement required by Section 2614 (c) 9,
not less than two No. 5 bars shall be provided around all (window or door)
openings. Such bars shall extend at least 24 inches beyond the corners of
openings.
12. Where bearing walls consist of studs or ribs tied together by other rein-
forced concrete members at each floor or roof level, such studs or ribs may be
considered as columns.
(d) Walls as Grade Beams. Walls designed as grade beams shall have top and
bottom reinforcement as required for moment in accordance with provisions of
Section 2610 (c) through (h). Design for shear shall be in accordance with
provisions of Section 2611.
Portions of grade beam walls exposed above grade also shall meet requirements
of Section 261 0 (p) or Section 2614 (c).
Footings
Sec. 2615. (a) Notations.
dP = diameter of pile at footing base.
Yf"'c = square root of specified compressive strength of concrete, psi.
{3 = ratio of long side to short side of footing.
cf> = strength reduction factor. See Section 2609 (d).
409
2615 UNIFORM BUILDING CODE
(b) Scope. Provisions of this section shall apply for design of isolated footings
and, where applicable, to combined footings and mats.
Additional requirements for design of combined footings and mats are given in
Section 2615 (k).
(c) Loads and Reactions. Footings shall be proportioned to resist the factored
loads and induced reactions, in accordance with the appropriate design require-
ments of this code and as provided in this section.
External forces and moments* applied to footings shall be transferred to
supporting soil without exceeding permissible soil pressures.
For footings on piles, computations for moments and shears may be based on
the assumption that the reaction from any pile is concentrated at pile center.
Base area of footing or number and arrangement of piles shall be determined
from the external forces and moments* (transmitted by footing to soil or piles) and
permissible soil pressure or permissible pile capacity selected through principles
of soil mechanics.
(d) Footings Supporting Circular or Regular Polygon-shaped Columns or
Pedestals. Circular or regular polygon-shaped concrete columns or pedestals
may be treated as square members with the same area for location of critical
sections for moment, shear and development of reinforcement in footings.
*External forces and moments are those resulting from unfactored loads (D, L, Wand E)
specified in Chapter 23.
410
1982 EDITION 2615
411
2615 UNIFORM BUILDING CODE
412
1982 EDITION 2615-2616
413
2616-2617 UNIFORM BUILDING CODE
414
1982 EDITION 2617
415
2618 UNIFORM BUILDING CODE
Prestressed Concrete
Sec. 2618. (a) Notations.
A area of that part of cross section between flexural tension face and
center of gravity of gross section, square inches.
area of concrete at cross section considered, square inches.
Aps = area of prestressed reinforcement in tension zone, square inches.
As = area of nonprestressed tension reinforcement, square inches.
A's = area of compression reinforcement, square inches.
b = width of compression face of member, inches.
d= distance from extreme compression fiber to centroid of prestressed
reinforcement, or to combined centroid when nonprestressed tension
reinforcement is included, inches.
D dead loads or related internal moments and forces.
base of Napierian logarithms.
specified compressive strength of concrete, psi.
square root of specified compressive strength of concrete, psi; or square
root of compressive strength of concrete at time of initial prestress, psi.
compressive strength of concrete at time of initial prestress, psi.
average compressive stress in concrete due to effective prestress force
only (after allowance for all prestress losses), psi.
fps stress in prestressed reinforcement at nominal strength, psi.
fpu specified tensile strength of prestressing tendons, psi.
!py specified yield strength of prestressing tendons, psi.
!, = modulus of rupture of concrete, psi.
f., = effective stress in prestressed reinforcement (after allowance for all
prestress losses), psi.
fy = specified yield strength of nonprestressed reinforcement, psi.
h overall thickness of member, inches.
K wobble friction coefficient per foot of prestressing tendon.
I length of prestressing tendon element from jacking end to any point x,
feet. See Formulas ( 18-1) and ( 18-2); or length of span of two-way flat
plates in direction parallel to that of the reinforcement being deter-
mined, inches. See Formula (18-7).
live loads or related internal moments and forces.
tensile force in concrete due to unfactored dead load plus live load
(D + L).
prestressing tendon force at jacking end.
prestressing tendon force at any point x.
total angular change of prestressing tendon profile in radians from
tendon jacking end to any point x.
416
1982 EDITION 2618
417
2618 UNIFORM BUILDING CODE
cracking loads, straight-line theory may be used with the following assumptions:
A. Strains vary linearly with depth through entire load range.
B. At cracked sections, concrete resists no tension.
(e) Permissible Stresses in Concrete--Flexural Members. l. Stresses in
concrete immediately after prestress transfer (before time-dependent prestress
losses) shall not exceed the following:
A. Extreme fiber stress in compression ...................... 0.60f'c;
B. Extreme fiber stress in tension except
as permitted in C ...................................... 3Yf'c;
C. Extreme fiber stress in tension at ends of
simply supported members .............................. 6Yf'c;
Where computed tensile stresses exceed these values, bonded auxiliary reinforce-
ment (nonprestressed or prestressed) shall be provided in the tensile zone to resist
the total tensile force in concrete computed with the assumption of an uncracked
section.
2. Stresses in concrete at service loads (after allowance for all prestress losses)
shall not exceed the following:
A. Extreme fiber stress in compression ....................... 0.45f'c
B. Extreme fiber stress in tension in precompressed
tensile zone .......................................... 6Yf'c
C. Extreme fiber stress in tension in precompressed
tensile zone of members (except two-way slab
systems) where analysis based on transformed
cracked sections and on bilinear moment-deflection
relationships show that immediate and long-time
deflections comply with requirements of Section
2609 (f) 4, and where cover requirements comply
with Section 2607 (h) 3 B .............................. 12Yf'c
3. Permissible stresses in concrete of Section 2618 (e) I and 2 may be exceeded
if shown by test or analysis that performance will not be impaired.
418
1982 EDITION 2618
When (Kl + p..a) is not greater than 0.3, effect of friction loss may be computed
by
Ps = Px (l + Kl + p..a) ................... (18-2)
butfps in Formula (18-4) shall not be taken greater thanfPY nor ifse + 60,000).
3. Nonprestressed reinforcement conforming to Section 2603 (f) 2, if used
with prestressing tendons, may be considered to contribute to the tensile force and
419
2618 UNIFORM BUILDING CODE
420
1982 EDITION 2618
where design yield strengthfy shall not exceed 60,000 psi. Bonded rein-
forcement shall be uniformly distributed over precompressed tensile zone
as close as practicable to extreme tension fiber.
C. In negative moment areas at column supports, minimum area of bonded
reinforcement in each direction shall be computed by
+~ -
20 ( 1 - w
0 30 w' ) percent
422
1982 EDITION 2618
423
2618-2619 UNIFORM BUILDING CODE
424
1982 EDITION 2619
(b) Scope and Definitions. l. Provisions of this section shall apply to design of
thin-shell concrete structures and only to the thin-shell portions of such
structures .
2. All provisions of this code not specifically excluded, and not in conflict with
provisions of this section shall apply to thin-shell structures.
3. Thin shells are curved or folded slabs whose thicknesses are small compared
to other dimensions. Thin shells are characterized by three-dimensional load-
carrying behavior, determined by geometrical shape, boundary conditions and
nature of applied load.
4. Thin shells are usually bounded by supporting members and edge members
provided to stiffen the shell and distribute or carry load in composite action with
that shell.
5. Elastic analysis of thin shells is any structural analysis involving assump-
tions that are suitable approximations of three-dimensional elastic behavior.
(c) General. I. Elastic behavior shall be the accepted basis for determining
internal forces, displacements and stability of thin shells. Equilibrium checks of
internal forces and external loads shall be made to ensure consistency of results.
2. Approximate methods of analysis that do not satisfy compatibility of strains
or stresses in thin shells may be used where experience has shown such analyses to
provide safe designs.
3. Thin-shell elements shall be proportioned for the required strength in
accordance with provisions of this code.
4. Investigation of thin shells for stability shall include consideration of
possible reduction in buckling capacity caused by large deflections, creep effects
and deviation between actual and theoretical shell surface.
5. Supporting members. A. Supporting members shall be designed in accor-
dance with applicable provisions of this chapter.
B. A portion of the shell equal to the effective flange width as specified in
Section 2608 (k) may be assumed to act with supporting members.
C. Within the effective flange width of shell assumed to act with supporting
members, reinforcement perpendicular to supporting member shall be at least
equal to that required for aT-beam flange as specified in Section 2608 (k) 5.
6. Model analysis. A. Analyses based on results of elastic model tests
approved by the building official shall be considered as valid elastic analyses.
B. When model analysis is used, only those portions of the thin shell structure
that significantly affect items under study need be simulated.
C. Every attempt shall be made to ensure that elastic model tests reveal
quantitative behavior of prototype structure.
(d) Design Assumptions. In elastic analysis of thin shells, material may be
assumed to be ideally elastic, homogeneous and isotropic.
Poisson's ratio may be assumed equal to zero.
(e) Design Strength of Materials. 1. Specified compressive strength of
concretef'c at 28 days shall be not less than 3000 psi.
2. Specified yield strength of reinforcement/Y shall not exceed 60,000 psi.
425
2619 UNIFORM BUILDING CODE
426
1982 EDITION 2619-2620
427
2620 UNIFORM BUILDING CODE
428
1982 EDITION 2620-2622
No safety measures shall interfere with load test procedures or affect results.
429
2622-2625 UNIFORM BUILDING CODE
Members of space frames which are designed to resist seismic forces shall be
designed, in accordance with the provisions of this section, so that shear failures
will not occur if the frame is subjected to lateral displacements in excess of yield
displacements.
(b) Definitions.
CONFINED CONCRETE is concrete which is confined by closely spaced
special transverse reinforcement which is provided to restrain the concrete in
directions perpendicular to the applied stresses.
SPECIAL TRANSVERSE REINFORCEMENT is spirals, stirrup ties or
hoops and supplementary cross ties provided to restrain the concrete to make it
qualify as confined concrete.
STIRRUP TIES OR HOOPS are continuous reinforcing steel of not less than
a No. 3 bar bent to form a closed hoop which encloses the longitudinal reinforcing
430
1982 EDITION 2625
and the ends of which have a standard 135-degree bend with a I 0-bar-diameter
extension or equivalent.
(c) Symbols and Notations. The following symbols and notations apply only
to the provisions of this section:
Ach area of rectangular or circular core of column measured out-to-out of
hoop or spiral, square inches.
A8 = gross area of column, square inches.
A, effective cross-sectional area of nonprestressed reinforcement, square
inches.
A's effective cross-sectional area of nonprestressed compression reinforce-
ment, square inches.
Ash total cross-sectional area of hoop reinforcement, including supplemen-
tary cross ties having a spacing of sh and crossing a section with a core
dimension of he, square inches.
bw = web width, or diameter of circular section, inches.
d = distance from extreme compression fiber to centroid of tension rein-
forcement, inches.
db = nominal diameter of bar, inches.
f' c= specified compressive strength of concrete, psi.
!y specified yield strength of nonprestressed reinforcement, psi.
!yh specified yield strength of hoop reinforcement, psi.
h largest core dimension of rectangular tied column, inches.
Pe maximum design axial load on a column during an earthquake.
p = Aslbd = ratio of nonprestressed tension reinforcement.
p' = A')bd = ratio of nonprestressed compression reinforcement.
sh = center-to-center spacing of hoops, inches.
Vd = applied shear force at section due to dead load.
V1 = applied shear force at section due to live load.
Vu = total applied design shear force at section.
(d) Physical Requirements for Concrete and Reinforcing Steel. I. Con-
crete. The minimum specified 28-day strength of the concretef'c, shall be 3000
pounds per square inch. The maximum specified strength for lightweight concrete
shall be limited to 4000 psi.
2. Reinforcement. All longitudinal reinforcing steel in columns and beams
shall comply with U .B.C. Standard No. 26-4. Reinforcing not conforming to the
low-alloy steel requirements of U .B.C. Standard No. 26-4 shall comply with the
following additional requirements:
A. Reinforcing shall be limited to billet steel, Grade 40 or 60 bars.
B. The actual yield stress, based on mill tests, shall not exceed the minimum
specified yield stress, fy, by more than 18,000 psi. Retests shall not exceed
431
2625 UNIFORM BUILDING CODE
ab
where Ma and Mb are the ultimate moment capacities of opposite sense at each
hinge location of the member and Vd + V 1 is the simple span shear. Lab is the
432
1982 EDITION 2625
distance between Ma and Mb. The ultimate moment capacities shall be computed
without the cfJ factor reduction and assuming the maximum reinforcing yield
strength based on 25 percent over specified yield.
Ultimate shear capacities shall be computed with the cfJ factor reduction.
B. Stirrups shall be spaced at no more than d/2 throughout the length of the
member.
C. Stirrup-ties, at a maximum spacing of not over d/4, eight bar diameters, 24
stirrup-tie diameters or 12 inches, whichever is least, shall be provided in the
following locations:
(i) At each end of all flexural members. The first stirrup-tie shall be located
not more than 2 inches from the face of the column and the last, a distance
of at least twice the member depth from the face of the columns.
(ii) Wherever ultimate moment capacities or plastic hinges may be developed
in the flexural members under inelastic lateral displacement of the frame.
(iii) Wherever required compression reinforcement occurs in the flexural
members.
D. In regions where stirrup-ties are required, longitudinal bars shall have
lateral support conforming to the provisions of ties for tied columns. Single or
overlapping stirrup-ties and supplementary cross-ties may be used.
(f) Columns Subject to Direct Stress and Bending. 1. Dimensional limita-
tions. The ratio of minimum to maximum column thickness shall be not less than
0.4 nor shall any dimension be less than 12 inches.
2. Vertical reinforcement. The reinforcement ratio, p, in tied columns shall be
not less than 0.01 nor greater than 0.06.
3. Splices. Lap splices shall be made within the center half of column height,
and the splice length shall be not less than 30 bar diameters. Continuity may also
be effected by welding or by approved mechanical devices, provided not more
than alternate bars are welded or mechanically spliced at any level and the vertical
distance between these welds or splices of adjacent bars is not less than 24 inches.
4. Special transverse reinforcement. The cores of columns shall be confined
by special transverse reinforcement as specified herein or as required to meet
shear requirements.
A. The volumetric ratio of spiral reinforcement shall be not less than that
required by Formula (10-3) of Section 2610 (j) nor
f'c
0.12 ~ ......................... (25-4)
lyh
whichever is greater.
B. The total cross-section area (Ash) of rectangular hoop reinforcement shall be
not less than the greater of
or
f'e
0.12shhe .,..-- ....................... (25-6)
Jyh
434
1982 EDITION 2625-2626
435
2626-2627 UNIFORM BUILDING CODE
provided, further, that 2.0 shall be used in Formulas (27-1) and (27-2) in
calculating shear and diagonal tension stresses in shear walls of buildings other
than those complying with requirements for buildings with K = 0.67.
(b) Braced Frames. Reinforced concrete members of braced frames subjected
primarily to axial stresses shall have special transverse reinforcing as specified in
Section 2625 (f) 4 throughout the full length of the member. Tension members
shall additionally meet the requirements for compression members.
436
1982 EDITION 2627-2628
(c) Vertical Boundary Members for Shear Walls. Special vertical boundary
elements shall be provided at the edges of concrete shear walls in buildings whose
lateral force resisting system is as described in Table No. 23-1 for aK of .80. These
elements shall be composed of concrete-encased structural steel elements of A36,
A441 , A500 Grades B and C, A50 I, A572 (except Grades 60 and 65) or A588, or
shall be concrete reinforced as required for columns in Section 2625 (f) with
special transverse reinforcement as described in Section 2625 (f) 4 for the full
length of the element. The longitudinal reinforcing in these concrete boundary
elements shall conform to the requirements of Section 2625 (d) 2.
EXCEPTION: The special transverse reinforcement may be omitted in Seismic
Zones No. I and No.2 when the combined dead load, live load and seismic stresses
are not over one half of those otherwise allowed.
The boundary vertical elements and such other similar vertical elements as may
be required shall be designed to carry all the vertical stresses resulting from the
wall loads in addition to tributary dead and live loads and from the horizontal
forces as prescribed in Section 2312. Horizontal reinforcing in the walls shall be
fully anchored to the vertical elements.
EXCEPTION: In Seismic Zones No. I and No. 2 the vertical boundary ele-
ments may be designed to carry all vertical stresses resulting from tributary dead and
live loads not supported by the shear walls acting as bearing walls.
Similar confinement of horizontal and vertical boundaries at wall openings also
shall be provided unless it can be demonstrated that the unit compressive stresses
at the opening have a load factor two times that required by Formulas (27 -1) and
(27-2) above.
(d) Wall Reinforcement. Wall reinforcement required to resist wall shear
shall be terminated with not less than a 90-degree bend plus a six-bar-diameter
extension beyond the boundary reinforcing at vertical and horizontal end faces of
wall sections. Wall reinforcement terminating in boundary columns or beams
shall be fully anchored into the boundary elements.
438
1982 EDITION 2628
A. Flexure.
Extreme fiber stress in compression
B. Shear.+
Beams and one-way slabs and footings:
Shear carried by concrete, vc l.lvfc
Maximum shear carried by
concrete plus shear reinforcement
Joists.*
Shear carried by concrete, v c 1.2vfc
Two-way slabs and footings:
Shear carried by concrete, vet (1 + 21{3)vfc
but not greater than 2vfc
C. Bearing on load area** 0.3f'c
+ For more detailed calculation of shear stress carried by concrete v c and shear values for
lightweight aggregate concrete, see Section 2628 (i).
*Designed in accordance with Section 2608 (I) of this code.
tif shear reinforcement is provided, see Sections 2628 (I) 4 and 2628 (I) 5.
**When the supporting surface is wider on all sides thal!._!he loaded area, permissible
bearing stress on the loaded area may be increased by VAz!A 1 but not more than 2. When
the supporting surface is sloped or stepped, A 2 may be taken as the area of the lower base of
the largest frustum of a right pyramid or cone contained wholly within the support and
having for its upper base the loaded area and having side slopes of I vertical to 2 horizontal.
2. Tensile stress in reinforcementfs shall not exceed the following:
A. Grade 40 or Grade 50 reinforcement 20,000 psi
B. Grade 60 reinforcement or greater and welded wire fabric
(smoothed or deformed) 24,000 psi
C. For flexural reinforcement, 3fs inch or less in diameter,
in one-way slabs of not more than 12-foot span 0.50 fy
but not greater than 30,000 psi
(e) Development and Splices of Reinforcement. Development and splices of
reinforcement shall be as required in Section 2612. In satisfying requirements of
Section 2612 (m), Mn shall be taken as computed moment capacity assuming all
positive moment tension reinforcement at the section to be stressed to the
permissible tensile stressfs, and Vu shall be taken as unfactored shear force at the
section.
(f) Flexure. For investigation of stresses at service loads, straight-line theory
(for flexure) shall be used with the following assumptions:
I. Strains vary linearly as the distance from the neutral axis, except for deep
flexural members with overall depth-span ratios greater than 215 for continuous
spans and 4/5 for simple spans, a nonlinear distribution of strain shall be consid-
ered. [See Section 2610 (h).]
2. Stress-strain relationship of concrete is a straight line under service loads
within permissible service load stresses.
439
2628 UNIFORM BUILDING CODE
v =
v ........................ (28-1)
bd
w
440
1982 EDITION 2628
441
2628 UNIFORM BUILDING CODE
every 45-degree line, extending toward the reaction from middepth of member
d/2 to longitudinal tension reinforcement, shall be crossed by at least one line of
shear reinforcement.
When ( v- v) exceeds 2 VI';, maximum spacing given by this subsection shall
be reduced by one half.
5. Minimum shear reinforcement. A minimum area of shear reinforcement
shall be provided in all reinforced concrete flexural members where design shear
stress v is greater than one half the permissible shear stress vc carried by concrete,
except:
A. Slab and footings.
B. Concrete joist construction defined by Section 2608 (!)of this code.
C. Beams with total depth not greater than 10 inches, two and one-half times
thickness of flange or one half the width of web, whichever is greater.
Minimum shear reinforcement requirements of this subsection may be waived
if shown by test that required ultimate flexural and shear strength can be devel-
oped when shear reinforcement is omitted.
Where shear reinforcement is required by this subsection or by analysis,
minimum area of shear reinforcement shall be computed by
bws
Av = 5 0 T ....................... (28-5)
where bw and s are in inches.
6. Design of shear reinforcement. Where design shear stress v exceeds shear
stress carried by concrete vc, shear reinforcement shall be provided in accordance
with this subsection.
When shear reinforcement perpendicular to axis of member is used,
(v-v)b~
Av = fs ..................... (28-6)
When included stirrups are used as shear reinforcement,
(v-vc)b~
A
v
= f s (sm
. et + cos et ) .................. (28-7)
442
1982 EDITION 2628
portion of a member, required area shall be computed as the sum of the various
types separately. In such computations, vc shall be included only once.
Value of (v- vc) shall not exceed 4.4 V'f'c.
(k) Shear Friction. Where it is appropriate to consider shear transfer across a
given plane such as an existing or potential crack, an interface between dissimilar
materials, or an interface between two concretes cast at different times, shear
friction provisions of Section 2611 (h) may be applied with limiting maximum
stress for shear taken as 55 percent of that given in Section 26II (h) 3. Permissible
stress in shear friction reinforcement shall be that given in Section 2628 (d) 2.
(I) Special Provisions for Slabs and Footings. I. Shear capacity of slabs and
footings in the vicinity of concentrated loads or reactions is governed by the more
severe of two conditions:
A. Beam action for slab or footing with a critical section extending in a plane
across the entire width and located at a distance d from face of concentrated load
or reaction area. For this condition, the slab or footing shall be designed in
accordance with Section 2628 (h) through (j).
B. 'IWo-way action for slab or footing with a critical section perpendicular to
plane of slab and located so that its perimeter is a minimum but need not approach
closer than d/2 to perimeter of concentrated load or reaction area. For this
condition, the slab or footing shall be designed in accordance with Sections 2628
(I) 2 and 2628 (I) 3.
2. Design shear stress v shall be computed by
v=
v ........................ (28-9)
bd
0
where V and b0 shall be taken at the critical section defined in Section 2628 (I) I B.
3. Design shear stress v shall not exceed vc given by Formula (28-10) unless
shear reinforcement is provided.
but vc shall not exceed 2 Yf'c. f3c is the ratio of long side to short side of
concentrated load or reaction area. When lightweight aggregate concrete is used,
the modifications of Section 2628 (i) 6 shall apply.
4. If shear reinforcement consisting of bars or wires is provided in accordance
with Section 26II (1) 3, vc shall not exceed Yf'c, and v shall not exceed 3 Yf'c.
5. If shear reinforcement consisting of steel I or channel shapes (shearheads) is
provided in accordance with Section 26II (I) 4 of this code, v on the critical
section defined in Section 2628 (I) I B shall not exceed 3.5 Yf'c and von the
critical section defined in Section 26II (I) 4 G shall not exceed 2 Yf'c. In
Formulas (11-38) and (II-39), design shear force V shall be multiplied by 2 and
substituted for Vu.
(m) Special Provisions for Other Members. For design of deep flexural
members, brackets and corbels and walls, the special provisions of Section 2611
443
2628 UNIFORM BUILDING CODE
shall be used with shear strengths provided by concrete and limiting maximum
strengths for shear taken as 55 percent of the values given in Section 2611. In
Section 2611 (k) 6, the design axial load shall be multiplied by 1.2 if compression
and 2.0 if tension and substituted for Nu.
(n) Composite Concrete Flexural Members. For design of composite con-
crete flexural members, permissible horizontal shear stress vh shall not exceed 55
percent of the horizontal shear strengths given in Section 2617 (f) 4.
444
1982 EDITION 26-1
z
Q_
~"' Q MINIMUM
ii' UJ~
... ~-'
PERCENT-~ WITHOUT DROP PANELS WITH DROP PANELS
t;; ~a:> AT SECTION
~ ~
!--d---1
50
...
Q_
."'
cr
0
f.-b-l -1
r/r
Rematnder
..."'
r
"'
;;: 3" Max --1 Max 0.1251
...cr ......"'
0 50
Max. 0 125} --:-:-1 _~24 bar d1a or 12" Mtn ,
Q_ "' 0
Rematnder I
all bars 6"-l
I
~
a:>
~ f.-6"
I ?-'--,J:.~.;;; ;;:>-=""+ I
z
"'3
F
\--d- b---1 1--e-
8 50 '
Q_
...
0
--I l+b- ; -e-\-i f--b-- I
..
*"'"'
..."'
Remomder
I \
'r/-o- ! --o---\1
1'
5a:>
......"'
0
50
l MaxO 125/
24bor dto or 12"M1n 6'. ~
. _6"
0 Remamder
a:>
"'""~"'-~~""--.<V~
3" Max_,
~: Edge af drop """-'""""'"\'
~ ~c-j f--c~'
.....
I
K1 Q_ f--c- -c---1
~ 100
a:>
r~ r"
Q_
..~
r
;o:>
......"'
0
0
a:>
50
Remotnder
lu.L6. Max 0 15/
3"Max --+~3" Max
Mox015j
6"- H
I
:
UJ
50
i5 Q_
*.."' ~
0
:i 1-a f--c\..J I<:
cr Remotader ! I;
..."'z / I \.
~:~,.:,. ~
~
"'
0 50
:::::
0 i
"' Rematnder
-6" 6"-- ~-
c -clear span-/ n~ c ~earspan-1 n . ~
~Center
I(
Face of support
to center span -R
Exterior support
.I
I(
Interior support
Face of support
Center to center span -1 =:j
Exterior support I(
(No slab continuity) (Continuity provided) (No slab continuity)
* Bent bars at uterOf supports
may be used tf a oenerol BAR LENGTH FROM FACE OF SUPPORT
analysts ts mode MINIMUM LENGTH IMAXIMUM LENGTH
MARK a I b I c I d I e I f I g
LENGTH 014.1'n [o2otnlontn lo 30/n lo33ln 020/n lo24ln I
445
26-A, 26-B UNIFORM BUILDING CODE
:-~
Strength, Ratio by Ratio by 94-lb. B8g
f'c peP w.lght Weight of Cement
11\venty-eight-day strength. With most materials, water-cement ratios shown will provide
average strengths greater than indicated in Section 2604 (d) I as being required.
2for strengths above 4500 psi (nonair-entrained concrete) and 4000 psi (air-entrained
concrete), proportions shall be established by methods of Section 2604 (d) or (e).
3,11 6to 10
lf2 5 to9
:v. 4to8
I 3.5 to 6.5
IVz 3 to 6
2 2.5 to 5.5
3 1.5 to4.5
446
1982 EDITION 26-C-1, 26-C-2, 26-D
MINIMUM THICKNESS, h
SIMPLY ONE END BOTH ENDS CANT!-
SUPPORTED CONTINUOUS CONTINUOUS LEVER
Member1 not eu~rtlng or Mtlchecl to partition or other
MEMBER conlltructlon II ely to be demged by lerge dellectlon1
447
26-E, 26-F UNIFORM BUILDING CODE
448
1982 EDITION 26-G, 26-H
50 75 100
Equal lOOT
greater than 2 Class A Class A Class B
449
2701 UNIFORM BUILDING CODE
Chapter 27
STEEL
450
1982 EDITION 2701
or
451
2701 UNIFORM BUILDING CODE
127T 2 E
23(Klt>/r1,)2
452
1982 EDITION 2701
7T'El .
P, = - -,- (kips)
1
py Plastic axial load; equal to profile area times specified minimum yield
stress (kips).
Ratio of effective profile area of an axially loaded member to its total
profile area.
Q,, Axial stress reduction factor where width-thickness ratio of unstiffened
elements exceeds limiting value given in section.
R Reaction or concentrated transverse load applied to beam or girder,
(kips).
s Spacing of secondary members in a flat roof (feet).
Section modulus of steel beam used in composite design, referred to the
bottom flange.
s,, = Section modulus of transformed composite cross section, referred to
the bottom flange, based upon maximum permitted effective width of
concrete flange, Section 2708 (a).
Tb = Specified pretension of a high strength bolt, in kips.
V = Statical shear on beam.
Vh Total horizontal shear to be resisted by connectors under full composite
action.
V' h Total horizontal shear to be resisted by connectors in providing partial
composite action (kips). See Section 2708 (d).
Vu Statical shear produced by "ultimate" load in plastic design.
Y = Ratio of yield point of web steel to yield point of stiffener steel.
a = Clear distance between transverse stiffeners.
453
2701 UNIFORM BUILDING CODE
a' Distance required at ends of welded partial length cover plate to develop
stress.
b = Effective width of concrete slab; actual width of stiffened compression
element.
be = Effective width of stiffened compression element.
b1 = Flange width of rolled beam or plate girder.
c = Distance from neutral axis to extreme fiber of beam.
d = Depth of beam or girder. Also diameter of roller or rocker bearings, or
major diameter of fastener.
d, Column web depth clear of fillets.
e = Horizontal displacement, in the direction of the span, between top and
bottom of simply supported beam at its ends.
f = Axial compression load on member divided by effective area (kips per
square inch).
fa Computed axial stress.
fb Computed bending stress.
f'c Specified compression strength of concrete.
fp Computed bearing stress.
!,= Computed tensile stress.
fv = Computed shear stress.
fvs Shear between girder web and transverse stiffeners, in kips per linear
inch of single stiffener or pair of stiffeners.
g = Transverse spacing between fastener gauge lines.
h = Clear distance between flanges of a beam or girder.
k = Coefficient relating linear buckling strength of a plate to its dimensions
and condition of edge support. Also, distance from outer face of flange
to web toe of fillet.
I = Actual unbraced length, in inches.
lb = Actual unbraced length in plane of bending, in inches.
Ia = Critical unbraced length adjacent to plastic hinge, in inches.
n = Modular ratio; equal toE lEe.
n, = Number of studs in one rib not to exceed three in calculations.
q = Allowable horizontal shear to be resisted by a shear connector.
r = Governing radius of gyration.
rb = Radius of gyration about axis of concurrent bending.
ry = Lesser radius of gyration.
s = Spacing (pitch) between successive holes in line of stress.
t = Girder, beam or column web thickness.
tb = Beam flange thickness at rigid beam-to-column connection.
r1 = Flange thickness.
454
t, Thickness of thinner part joined by partial penetration groove weld.
v Poisson's ratio, may be taken as 0.3 for steel.
w Length of channel shear connectors.
x = Subscript relating symbol to strong axis bending.
y = Subscript relating symbol to weak axis bending.
a = Ratio of hybrid girder web yield stress to flange yield stress.
~ = Displacement of the neutral axis of a loaded member from its position
when the member is not loaded.
{3 = Ratio S,,IS5 or S,.ff!S,.
Allowable Unit Stresses
Sec. 2702. (a) General. Except as provided in Sections 2703, 2704, 2707,
2708 and 2721, all components of the structure shall be so proportioned that the
stress in kips per square inch shall not exceed the values specified in this section.
Allowable stresses for web-tapered members may be governed by these provi-
sions or by other approved methods.
(b) Structural Steel. I. Tension. Except for pin-connected members, F,
shall not exceed 0.6F, on the gross area nor 0.5Fu on the effective net area.
For pin-connected members, F, = 0.45F, on the net area.
For tension on threaded parts, see Table No. 27-A.
2. Shear. On the gross section (for shear calculation, the gross section of
rolled and fabricated shapes may be taken as the product of the overall depth and
the thickness of the web).
At beam end connections where the top flange is coped, and similar situations
where failure might occur by shear along a plane through the fasteners or by a
combination of shear along a plane through the fasteners plus tension along a
perpendicular plane, on the area effective in resisting tearing failure:
WHERE:
The effective area is the minimum net surface, bounded by the bolt holes.
See Section 2707 for reduction required for thin webs.
3. Compression. On the gross section of axially loaded compression mem-
bers whose cross sections meet the provisions of Section 2706 when Kllr, the
largest effective slenderness ratio of any unbraced segment as defined in Section
2705, is less than Cc.
. ................. (2-1)
455
2702 UNIFORM BUILDING CODE
WHERE:
F S _ f.. f. _ 5 3(Kl/r) (Kl/r) 3
. . - actor o sa ety - 3 + ~ - Bc,.:l
AND
On the gross section of axially loaded bracing and secondary members, when
II r exceeds 120 (for this case K is taken as unity).
Fa= 0.60FY
On the web of rolled shapes at the toe of the fillet for crippling
Fa= 0.75FY
Web stiffeners shall be provided as specified in Section 2707 (j) when the
compressive stress of the web toe exceeds the allowable stress specified in the
preceding paragraph.
4. Bending. Except for hybrid girders and members of A514 steel, tension
and compression on extreme fibers of compact hot-rolled or built-up members
symmetrical about, and loaded in, the plane of their minor axis and meeting the
requirements of this section shall not exceed:
PROVIDED:
(i) The flange is continuously connected to the web or webs.
(ii) The width-thickness ratio of unstiffened projecting elements of the com-
pression flange as defined in Section 2706 does not exceed:
65
~
456
1982 EDITION 2702
nor:
257
--when
~
yI'
.II
> 0.16
(
1950 + 1200 M,) F~
M, 1
457
2702 UNIFORM BUILDING CODE
Members qualj_fying for Fb = 0.66 F,, except that br12trexceeds 65/~ but is
less than 95.0/VF,. may have an allowable bending stress of:
Fb = 0.75 F,
Rectangular tubular sections bent about their minor axis and meeting the
requirements of subparagraphs (i), (iii) and (iv) above may be designed on the
basis of an allowable bending stress of
Fb = 0.66F,
Lateral torsional buckling need not be investigated for a box section whose
depth is less than six times its width. Lateral support requirements for box
sections of larger depth-to-width ratios must be determined by special analysis.
Tension on extreme fibers of flexural members not previously covered in this
subsection on bending shall not exceed Fb = 0.60F,.
Compression on extreme fibers of flexural members included under the preced-
ing paragraph and meeting the requirements of Subsection 2706 (a), having an
axis of symmetry in and loaded in the plane of their web, and compression on
extreme fibers of channels bent about their major axis shall not exceed the larger
of Formulas (2-6a) or (2-6b) and (2-7), when applicable, but not more than
0.60Fv.
Only Formula (2-7) is applicable to channels. See Section 2707 for further
limitations to plate girder flange stress.
458
1982 EDITION 2702
WHEN:
WHEN:
F _ 12 (10'1 ) Cr,
IJ- ld!At .................... (2-7)
WHERE:
I = distance between cross sections braced against twist or lateral displace-
ment of the compression flange. For cantilevers braced against twist at
the support only "I" may conservatively be taken as the actual length.
r, = radius of gyrations of a section comprising the compression flange plus
one third of the compression web area, taken about an axis in the plane
of the web.
but not more than 2.3 (Cb may be conservatively taken as unity) where M 1 is the
smaller and M 2 the larger bending moment at the ends of the unbraced length,
taken about the strong axis of the member, and where M/M2 , the ratio of end
moments, is positive when there is reverse curvature bending and negative when
there is single curvature bending. When the bending moment at any point within
an unbraced length is larger than that at both ends of this length, Cb shall be unity.
When computing F bx and F b to be used in Formula ( 3-1 a), Cb may be computed
by the formula given above for frames subject to joint translation, and it shall be
taken as unity for frames braced against joint translation. c, may be con-
servatively taken as 1.0 for cantilever beams.
459
2702 UNIFORM BUILDING CODE
For hybrid plate girders, FY in Formulas (2-6a) and (2-6b) is the yield stress of
the compression flange. Formula (2-7) shall not apply to hybrid girders.
Compression on extreme fibers of flexural members not previously covered in
this subsection on bending and meeting the requirements of Section 2706 (a),
which do not qualify for Formulas (2-6a), (2-6b) and (2-7), and provided that
sections bent about their major axis are braced laterally in the region of compres-
sion stress at intervals not exceeding 76. Ob/YF; shall not exceed
where F u is the minimum tensile strength of the connected parts. Also see Section
2713 (d) and (e).
460
1982 EDITION 2702
(d) Welds. Except as modified by Section 2704, weld stresses shall comply
with Table No. 27-B.
(e) Effective Areas of Weld Metal. The effective area of groove and fillet
welds shall be considered as the effective length of the weld times the effective
throat thickness.
The effective shearing area of plug and slot welds shall be considered as the
nominal cross-sectional area of the hole or slot in the plane of the faying surface.
The effective area of fillet welds in holes and slots shall be computed as
specified above for fillet welds, using for effective length the length of center line
of the weld through the center of the plane through the throat. However, in the case
of overlapping fillets, the effective area shall not exceed the nominal cross-
sectional area of the hole or slot in the plane of the faying surface.
The effective length of a fillet weld shall be the overall length of full-size fillet
including returns.
The effective length of a groove weld shall be the width of the part joined.
The effective throat thickness of a fillet weld shall be the shortest distance from
the root to the face of the diagrammatic weld. However, for fillet welds made by
the submerged arc process, the effective throat thickness shall be the leg size for
Ys inch and smaller fillet welds and equal to the theoretical throat plus 0.11 inch
for fillet welds over Ys inch.
The effective throat thickness of a complete penetration groove weld (i.e., a
groove weld conforming to the requirements of U .B.C. Standard No. 27-6) shall
be the thickness of the thinner part joined.
The effective throat of a partial joint penetration groove weld shall be the depth
of chamfer, less Ys inch for grooves having an included angle less than 60 degrees,
but not less than 45 degrees at the root of the groove, when deposited by shielded
metal arc or submerged arc welding, or when deposited in vertical or overhead
positions by gas metal arc or flux-cored welding.
The effective throat of a partial joint penetration groove weld shall be the depth
of chamfer for grooves:
(i) having an included angle of 60 degrees or greater at the root of the groove
when deposited by any of the following welding processes; shielded metal
arc, submerged arc, gas metal arc, flux-cored arc orelectrogas welding; or
(ii) having an included angle not less than 45 degrees at the root of the groove
when deposited in flat or horizontal positions by gas metal arc or flux-
cored arc welding.
The effective throat thickness for flare groove welds when flush to the surface
of the solid section of the bar shall be as shown in Table No. 27-F.
l. Random sections of production welds for each welding procedure, or such
test sections as may be required, shall be used to verify that the effective throat is
consistently obtained.
2. Where for a given set of procedural conditions it can be established that
consistently larger effective throats than those shown in Table No. 27-F can be
provided, such larger effective throats may be established by qualification.
461
2702-2703 UNIFORM BUILDING CODE
Combined Stresses
Sec. 2703. (a) Axial Compression and Bending. Members subject to both
axial compression and bending stresses shall be proportioned to satisfy the
following requirements:
WHEN:
fa/Fa~ 0.15, Formula (3-2) may be used in lieu of Formulas (3-la) and (3-1 b):
462
1982 EDITION 2703
(b) Axial Thnsion and Bending. Members subject to both axial tension and
bending stresses shall be proportioned at all points along their length to satisfy the
requirements of Formula (3-1 b) where fb is the computed bending tensile stress.
However, the computed compressive stress, taken alone, shall not exceed the
applicable value permitted by Section 2702 (b) 4.
(c) Shear and Thnsion. Rivets and bolts subject to combined shear and tension
shall be so proportioned that the tension stress, in kips per square inch, on the
nominal area Ab produced by forces applied to the connected parts shall not
exceed the following:
For A502 Grade I rivets F, 30- J.3fv~23
For A502 Grade 2 rivets F, 38 - 1.3fv~29
For A307 bolts F, 26 - 1.8fv~20
For A449 bolts over I Vz-inch
diameter and threaded
parts, threads not excluded F 1 = .43fu - 1.8fv~33Fu
For A449 bolts over I Vz-inch
diameter and threaded
parts, threads excluded
For A325 bearing bolts,
threads not excluded
For A325 bearing bolts,
threads excluded
For A490 bearing bolts,
threads not excluded
For A490 bearing bolts,
threads excluded
The shear stressfv produced by the same forces shall not exceed the allowable
value for shear specified in Section 2702 (c). When allowable stresses are
increased for wind or seismic loads in accordance with Section 2303 (d), the
constants in the above formulas may be increased one third, but the factor
coefficient applied tofv shall not be increased.
For bolts in friction-type joints, the shear stress allowed in Section 2702 (c)
shall be reduced so that:
463
2703-2706 UNIFORM BUILDING CODE
464
1982 EDITION 2706-2707
bending shall be considered as fully effective when the ratio of width to thickness
is not greater than the following:
Single-angle struts; double-angle struts with separators ........... 76/YF";
Struts comprising double angles in contact; angles or plates
projecting from girders, columns or other
compression members; compression flanges
of beams; stiffeners on plate girders ......................... 95/v-F:,
Stems of tees ........................................... 127 rVFY
When the actual width-to-thickness ratio exceeds these values, the design shall
be governed by other approved methods.
(b) Stiffened Elements Under Compression. Stiffened compression ele-
ments are those having lateral support along both edges which are parallel to the
direction of the compression stress. The width of such elements shall be the
distance between nearest lines of fasteners or welds, or between the roots of
flanges of rolled sections.
Stiffened elements subject to axial compression or to uniform compression due
to bending, such as the flange of a flexural member [see Section 2707 (b) and (f)],
shall be considered fully effective when the ratio of width to thickness does not
exceed the following:
Flanges of square and rectangular box sections
of uniform thickness ................................... 238/YF";
Unsupported width of cover plates perforated
with a succession of access holes ......................... 317 ;v-F:,
(Assumes net area of plate at widest hole in computing compression
stress.)
All other uniformly compressed stiffened
elements ............................................. 253/YF";
Except in the case of perforated cover plates, when the actual width-to-
thickness ratio exceeds these values the design shall be governed by other
approved methods.
(c) Circular Thbular Elements. Circular tubular elements subject to axial
compression shall be considered as fully effective when the ratio of diameter to
thickness is not greater than 3300/ FY.
Plate Girders and Rolled Beams
Sec. 2707. (a) Proportions. Riveted and welded plate girders, cover-plated
beams and rolled or welded beams shall be proportioned by the moment of inertia
of the gross section. No deduction shall be made for shop or field rivet or bolt
holes in either flange, except that in cases where the reduction of the area of either
flange by such holes, calculated in accordance with the provisions of Section
2711 (b), exceeds 15 percent of the gross flange area, the excess shall be
deducted.
Hybrid girders may be proportioned by the moment of inertia of their gross
section (web stresses produced by the bending moment are unlimited except as
regulated in Section 2704 and U.B.C. Standard No. 27-3), subject to the other
provisions of this section, provided they do not resist an axial force exceeding
465
2707 UNIFORM BUILDING CODE
0. 15F v times the gross section where F is the yield stress of the flange material.
Hybrid girders must have flanges of eq~al areas at any section and have the same
grade of steel.
(b) Web. The clear distance between flanges in inches shall not exceed
14,000 (t)
+ 16 ..5)
VF,, (F,,
WHERE:
F .. = Yield stress of the compression flanges. A limiting value of 2000
(t)l~ may be used, provided there are transverse stiffeners spaced
not more than 1.5 times the girder depth.
(c) Flanges. The thickness of outstanding parts of flanges shall conform to the
requirements of Section 2706 (a).
The total cross-sectional area of cover plates of riveted girders shall not exceed
70 percent of the total flange area. Provision shall be made for stresses resulting
from abrupt changes in flange direction and other conditions that introduce stress
concentration.
(d) Flange Development. Rivets, high-strength bolts or welds connecting
flange to web, or cover plate to flange, shall be proportioned to resist the total
horizontal shear resulting from the bending forces on the girder. The longitudinal
distribution of these rivets, bolts or of intermittent welds shall be in proportion to
the intensity of the shear. But the longitudinal spacing shall not exceed the
maximum permitted, respectively, for compression or tension members in Sec-
tion 2715 (c) or (d). In addition, rivets or welds connecting flange to web shall be
proportioned to transmit to the web loads applied directly to the flange except
where provision is made to transmit such loads by direct bearing.
Partial length cover plates shall be extended beyond the theoretical cutoff point
and the extended portion shall be attached to the beam or girder by rivets, high-
strength bolts or fillet welds adequate to develop the cover plate's portion of the
flexural stresses in the beam or girder at the theoretical cutoff point. In addition,
for welded cover plates, the welds connecting the cover plate termination to the
beam or girder in the length a', defined below, shall be adequate to develop the
cover plate's portion of the flexural stresses in the beam or girder at the distance a'
from the end of the cover plate. The length a', measured from the end of the cover
plate, shall be:
I. A distance equal to the width of the cover plate when there is a continuous
weld equal to or larger than three fourths of the plate thickness across the
end of the plate and continued welds along both edges of the cover plate in
the length a'.
2. A distance equal to one and one-half times the width of the cover plate
when there is a continuous weld smaller than three fourths of the plate
thickness across the end of the plate and continued welds along both edges
of the cover plate in the length a'.
3. A distance equal to two times the width of the cover plate when there is no
weld across the end of the plate but continuous welds along both edges of
466
1982 EDITION 2707
WHERE:
45,000k 0
F
,. = ___
2.H9 [c,,. + us VI+ (a/h)z J s:
I - c.
- o4Fu ......... (7-2)
Subject to the limitations of Section 2707 (b), intermediate stiffeners are not
required when the ratio hit is less than 260 and the maximum web shear stressfv is
less than that permitted by Formula (7 -1 ).
The spacing of intermediate stiffeners, when stiffeners are required, shall be
467
2707 UNIFORM BUILDING CODE
such that the web shear stress will not exceed the value for Fv given by Formula
(7-1) or (7-2), as applicable and the ratio alh shall not exceed:
2
260)
( hTt nor 3.0.
For girders designed for tension field action, the spacing between stiffeners at
end panels and panels containing large holes and panels adjacent thereto shall be
such thatf,. does not exceed the value given by Formula (7 -1 ).
The moment of inertia of a pair of intermediate stiffeners or a single intermedi-
ate stiffener about an axis in the web plane shall be not less than (h/50)4.
The gross area, in square inches, of intermediate stiffeners spaced in accor-
dance with Formula (7-2) shall be not less than that computed by Formula (7-3).
A ~ I ~C.[!!_~ ] YDh
'' ~ '>
-
I
I
V 1(a/h)2
II .
+(a !)2
t ............ (7-3)
WHERE:
C,. is as defined in Section 2707 (e).
Y = yield stress of web steel/yield stress of stiffener steel.
D 1.0 for stiffeners furnished in pairs.
1.8 for single angle stiffeners.
2.4 for single plate stiffeners.
When the greatest shear stressfv in a panel is less than that permitted by Formula
(7-2), this gross area requirement may be reduced in like proportion.
Intermediate stiffeners required by the provisions of Formula (7-2) shall be
connected for a shear transfer in kips per linear inch of single or pairs of stiffeners
not less than
.
j,..,=h {fli>F
~
340
)'l ................... (7-4)
WHERE:
F" = yield stress of web steel.
This shear transfer may be reduced in the same proportion that the largest
computed shear stress fv in the adjacent panels is less than that permitted by
Formula (7-2). However, rivets and welds in intermediate stiffeners which are
required to transmit to the web an applied concentrated load or reaction shall be
proportioned for not less than the applied load or reaction.
Intermediate stiffeners may be stopped short of the tension flange, provided
bearing is not needed to transmit a concentrated load or reaction. The weld by
which intermediate stiffeners are attached to the web shall be terminated not
closer than four nor more than six times the web thickness from the toe of the web
468
1982 EDITION 2707
to flange weld. When single stiffeners are used they shall be attached to the
compression flange, if it consists of a rectangular plate, to resist any uplift
tendency due to torsion in the plate. When lateral bracing is attached to a stiffener
or a pair of stiffeners these, in tum, shall be connected to the compression flange
to transmit I percent of the total flange stress, unless the flange is composed only
of angles.
Rivets connecting stiffeners to the girder web shall be spaced not more than 12
inches on center. If intermittent fillet welds are used, the clear distance between
welds shall be not more than 16 times the web thickness nor more than I 0 inches.
(f) Reduction in Flange Stress. When the web depth-to-thickness ratio
exceeds 760/-vfi";,, the maximum stress in the compression flange shall not
exceed:
The maximum stress in either flange of a hybrid girder shall not exceed F 'h in
Formula (7-5) nor
a - a"l)l
F'
fJ
<
=
F'
fJ [1 :... 12+ (A")
9
f
-A (3
+ 2 (A ./A ) .. . . . (7-6)
11 1
WHERE:
o: = ratio of web yield stress to flange yield stress.
(g) Combined Shear and Tension Stress. Plate girder webs shall be so
proportioned that the bending tensile stress due to moment in the plane of the
girder web shall not exceed:
The allowable shear stress in webs of girders having A514 flanges and webs
shall not exceed that determined by Formula (7 -I) if the flexural stress in the
flange exceeds 0. 75Fh.
(h) Splices. Groove welded splices in plate girders and beams shall develop the
full strength of the smaller spliced section. Other types of splices in cross sections
of plate girders and in beams shall develop the strength required by the stresses at
the point of splice.
(i) Horizontal Forces. The flanges of plate girders supporting cranes or other
moving loads shall be proportioned to resist the horizontal forces produced by
such loads.
The lateral force on crane runways shall be 20 percent of the sum of the weights
of the lifted load and of the crane trolley, applied at the top of rail, one half on each
469
2707 UNIFORM BUILDING CODE
side of the runway; and shall be considered as acting in either direction normal to
the runway rail.
The longitudinal force shall be 10 percent of the maximum wheel loads of the
crane applied at the top of rail.
(j) Web Crippling. Webs of beams and welded plate girders shall be so
proportioned that the compressive stress at the web toe of the fillets, resulting
from concentrated loads not supported by bearing stiffeners, does not exceed
0.75Fy.
The compressive stress at the web top of the fillets shall be computed using the
following formulas:
For interior loads:
WHERE:
N = length of bearing in inches (not less thank for end reactions).
Bearing stiffeners shall be provided where the compressive stress exceeds that
determined by Formulas (7-8) and (7-9).
Webs of welded plate girders also shall be so proportioned or stiffened that the
sum of the compression stresses resulting from concentrated and distributed loads
bearing directly on or through a flange plate, upon the compression edge of the
web plate and not supported directly by bearing stiffeners does not exceed the
following:
When the flange is restrained against rotation,
4 ] 10,000
[ .5 ..5 + (a/h)t (h/t)t ................. (7-10)
[
2 + _4_]
(a/h)2
10,000
(h/W ................... (7-11)
470
Composite Construction
Sec. 2708. (a) Definition. Composite construction shall consist of steel beams
or girders supporting a reinforced concrete slab, so interconnected that the beam
and slab act together to resist bending. When the slab extends on both sides of the
beam, the effective width of the concrete flange shall be taken as no more than one
fourth of the span of the beam, and its effective projection beyond the edge of the
beam shall not be taken as more than one half the clear distance to the adjacent
beam nor more than eight times the slab thickness. When the slab is present on
only one side of the beam. the effective projection of the concrete flange shall be
taken as not more than one twelfth of the beam span nor six times its thickness nor
one half the clear distance to the adjacent beam. Composite construction may also
be permitted using a metal deck with a structural concrete fill and designed by an
approved method of analysis.
Beams totally encased 2 inches or more on their sides and soffit in concrete cast
integrally with the slab may be assumed to be interconnected to the concrete by
natural bond, without additional anchorage, provided the top of the beam is not
less than I Yz inches below the top and 2 inches above the bottom of the slab, and
provided that the encasement has adequate mesh or other reinforcing steel
throughout the depth and across the soffit of the beam. When shear connectors are
provided in accordance with Section 2708 (d), encasement of the beam to achieve
composite action is not required.
(b) Design Assumptions. Encased beams shall be proportioned to support
unassisted all dead loads applied prior to the hardening of the concrete except
where these loads are supported temporarily on shoring. The beams acting in
conjunction with the slab shall support all dead and live loads applied after
hardening of the concrete, without exceeding a computed bending stress of
0.66FY, where FY is the yield stress of the steel beam. The bending stress
produced by loads after the concrete has hardened shall be computed on the basis
of the section properties of the composite section. Concrete tension stress shall be
neglected. Alternatively, the steel beam may be proportioned to resist unassisted
the positive moment produced by all loads, live and dead, using a bending stress
equal to 0. 76FY, in which case temporary shoring is not required.
When shear connectors are used in accordance with Section 2708 (d) the
composite section shall be proportioned to support all of the loads without
exceeding the allowable stress prescribed in Section 2702 (b) 4. This includes
composite sections where the structural steel is not shored during construction.
When using shear transfer devices on a noncompositely designed beam, those
devices must be able to resist the combined effects produced by composite action
plus shear transfer loads. In calculations involving composite sections in positive
moment areas, the steel cross section is exempt from compactness requirements
of subparagraphs (ii), (iii) and (v) of Section 2702 (b) 4.
Reinforcement parallel to the beam within the effective width of the slab, when
anchored in conformance with Chapter 26, may be included in the properties of
composite sections, provided shear connectors comply with Section 2708 (d).
The section properties of the composite section shall be computed in accordance
with the elastic theory. Concrete tension stresses shall be neglected. For stress
471
2708 UNIFORM BUILDING CODE
Seff
;v;;:- (S,,
= S, + vv::- - S,) ......... (8-1)
For construction without temporary shoring, stress in the steel section may be
computed from the total dead plus live load moment and the actual transformed
section modulus S, except that the numerical value of S, so used shall not exceed
that of Formula (8-2). These stresses shall not exceed the appropriate value of
Section 2702. Section 2303 (d) shall not apply to stresses in the negative moment
area computed under the provisions of this paragraph.
WHERE:
ML moment caused by loads applied after concrete has attained 75 percent
of its required strength.
M0 moment caused by loads applied prior to this time.
At sections subject to positive bending moment, the stress shall be computed
for the steel tension flange. At sections subject to negative bending moment, the
stress shall be computed for the steel tension and compression flanges. These
stresses shall not exceed the appropriate value of Section 2702.
The steel beam alone, supporting the loads before the concrete has hardened,
shall not be stressed to more than the applicable bending stress given in Section
2702 (b).
Provisions shall be made to prevent cracking of the slab spanning perpendicular
to the beam.
The actual section modulus of the transformed composite section shall be used
in calculating the concrete flexural compression stress and, for construction
without temporary shores, this stress shall be based upon loading applied after the
concrete has reached 75 percent of its required strength. The stress in the concrete
shall not exceed 0.45f' c.
(c) End Shear. The web and the end connections of the steel beam shall be
designed to carry the total reaction.
(d) Shear Connectors. The horizontal shear between the steel beam and
concrete slab shall be transferred by shear connectors welded to the beam and
embedded in the concrete except as specified in Section 2708 (a). For full
472
1982 EDITION 2708
composite action with concrete subject to flexural compression, the total horizon-
tal shear between the point of maximum positive moment and points of zero
moment shall be the smaller of the following:
v, = o.Hsr.A,....................... (8-3)
AND
A'Jy)2 shall be added to the right hand side of Formula (8-3) if longitudinal
reinforcing steel with area A's located within the effective width of the concrete
flange is included in the properties of the composite section.
In continuous composite beams where longitudinal reinforcing steel is consid-
ered to act compositely with the steel beam in the negative moment regions, the
total horizontal shear resisted by shear connectors between an interior support and
each adjacent point of contraflexure shall be:
For full composite action, the number of connectors resisting the horizontal shear
obtained from Formula (8-3) or (8-4) shall be not less than that determined by the
following formula:
vh
N 1 = - .......................... (8-6)
q
Working values for flat soffit concrete slabs with aggregates not conforming
with U.B.C. Standards No. 26-2 and No. 26-3, and for connectors other than
shown in Table No. 27-C, must be established by an approved test program.
For partial composite action with concrete subject to flexural compression, V'h
in Formula (8-1) shall be q multiplied by the number of connectors furnished
between the point of maximum moment and the nearest point of zero moment.
The value of V' h shall be not less than one fourth the smaller value of Formula
(8-3), using the maximum permitted effective width of the concrete flange, and
Formula (8-4). The effective moment of inertia for deflection computations shall
be determined by:
473
2708 UNIFORM BUILDING CODE
rM M@(max)
1 J................. (8-8)
,B-1
WHERE:
M The moment (less than the maximum moment) at a concentrated load
point.
N1 Number of connectors required between point of maximum moment
and point of zero moment determined by the relationship Vh/q or V'hlq,
as applicable.
- s,, ~ .
,B - S, or S" , as applicable.
474
1982 EDITION 2708-2709
5. Total slab thickness including ribs shall be used in determining the effec-
tive width of concrete flange.
6. The slab thickness above the steel deck shall be at least 2 inches.
(f) Deck Ribs Oriented Perpendicular to Steel Beam or Girder.
I. Concrete below the top of the steel deck shall be neglected when determin-
ing section properties and in calculating A, for Formula (8-3).
2. The allowable shear load per stud connector determined from Table No.
27-C shall be multipled by the reduction factor
475
2709-2711 UNIFORM BUILDING CODE
AND
> 25S 4
Id = 1()6
WHERE:
C = 32L_, L/
," HF I,,
3 vSL 4
C =~
' HF I_,
For trusses and joists l, shall be decreased by 15 percent when used in the above
formulas. A steel deck shall be considered a secondary member when it is directly
supported by the primary members.
Total bending stress due to dead loads, live loads and ponding shall not exceed
0.8F v for primary and secondary members. Stresses due to wind or seismic forces
need not be included in the ponding analysis.
Gross and Net Areas
Sec. 2711. (a) General. The gross area of a member at any point shall be
determined by summing the products of the thickness and the gross width of each
element as measured normal to the axis of the member. The net area shall be
determined by substituting for the gross width the net width computed in accor-
dance with Subsections (b) through (e).
(b) Net Area and Effective Net Area. I. In the case of a chain of holes
extending across a part in any diagonal or zigzag line, the net width of the part
476
1982 EDITION 2711
shall be obtained by deducting from the gross width the sum of the diameters of all
the holes in the chain, and adding, for each gauge space in the chain, the quantity
s>
4g
WHERE:
s = longitudinal spacing (pitch, in inches) of any two consecutive holes.
g = transverse spacing (gauge, in inches) of the same two holes.
The critical net area An of the part is obtained from that chain which gives the
least net width.
In determining the net area across plug or slot welds, the weld metal shall not be
considered as adding to the net area.
2. Unless a larger coefficient can be justified by tests or by other recognized
criteria, the effective net area A, of axially loaded tension members whose profile
consists of segments not in a common plane and which are connected by some,
but not all, of these segments by rivets or bolts, shall be computed as follows:
A. W. M, or S shapes with flange width not less than two thirds the depth, and
structural tees cut from these shapes, Ae = 0.90An, provided the connection is to
the flanges and has no fewer than three fasteners per line.
B. For all other shapes, including built-up cross sections, A, = 0.85An,
provided the connection has no fewer than three fasteners per line.
C. All members whose connections have only two fasteners per line, A, =
0.75An.
3. Riveted and bolted splice and gusset plates and other connection fittings
subject to tensile force shall be designed in accordance with the provisions of
Section 2702 (b) I, where the effective net area shall be taken as the actual net area
except that, for the purpose of design calculations, it shall be taken as not greater
than 85 percent of the gross area.
(c) Angles. The gross width of angles shall be the sum of the widths of the legs
less the thickness. The gauge for holes in opposite legs shall be the sum of the
gauges from back of angles less the thickness.
(d) Size of Holes. In computing net area the width of a rivet or bolt hole shall be
taken as Yt6 inch greater than the nominal dimension of the hole normal to the
direction of applied stress.
(e) Pin-connected Members. Eyebars shall be of uniform thickness without
reinforcement at the pinholes. They shall have "circular" heads in which the
periphery of the head beyond the pinhole is concentric with the pinhole. The
radius of transition between the circular head and the body of the eye bar shall be
equal to or greater than the diameter of the head.
The width of the body of the eye bar shall not exceed eight times its thickness,
and the thickness shall be not less than Yz inch. The net area of the head through
the pinhole, transverse to the axis of the eyebar, shall be not less than 1.33 nor
more than 1.50 times the cross-sectional area of the body of the eyebar. The
477
2711-2712 UNIFORM BUILDING CODE
diameter of the pin shall be not less than seven eighths the width of the body of the
eye bar. The diameter of the pinhole shall be not more than V32 inch greater than the
diameter of the pin. For steels having a yield stress greater than 70 ksi, the
diameter of the pinhole shall not exceed five times the plate thickness.
In pin-connected plates other than eyebars, the tensile stress on the net area,
transverse to the axis of the member, shall not exceed the stress allowed in Section
2702 (b) 5, and the bearing stress on the projected area of the pin shall not exceed
the stress allowed in Section 2702 (b) 5. The net area beyond the pinhole, parallel
to the axis of the member, shall be not less than two thirds of the net area across the
pinhole.
The corners beyond the pinhole may be cut at 45 degrees to the axis of the
member, provided the net section beyond the pinhole on a plane perpendicular to
the cut is not less than that required beyond the pinhole parallel to the axis of the
member.
The distance transverse to the axis of a pin-connected plate or any individual
element of a built-up member, from the edge of the pinhole to the edge of the
member or element, shall not exceed four times the thickness at the pinhole. The
diameter of the pinhole shall be not less than I . 25 times the smaller of the
distances from the edge of the pin hole to the edge of a pin-connected plate or
separated element of a built-up member at the pinhole. For pin-connected mem-
bers in which the pin is expected to provide for relative movement between
connected parts while under full load, the diameter of the pinhole shall be not
more than V32 inch greater than the diameter of the pin.
The corners beyond the pinhole may be cut at 45 degrees to the axis of the
member, provided the net area beyond the pinhole on a plane perpendicular to the
cut is not less than that required beyond the pinhole parallel to the axis of the
member.
Thickness limitations on both eyebars and pin-connected plates may be waived
whenever external nuts are provided so as to tighten pin plates and filler plates into
snug contact. When the plates are thus contained, the allowable stress in bearing
shall be no greater than as specified in Section 2702 (b) 5.
Connections
Sec. 2712. (a) Minimum Connections. Connections shall be designed for all
tributary forces and shall be capable of supporting not less than six kips.
EXCEPTION: Lacing, sag bars and girts may be designed only for tributary
forces.
(b) Eccentric Connections. Members and their connections shall be designed
for eccentricity where the gravity axes of the connected members do not meet at a
point.
(c) Placement of Rivets, Bolts and Welds. Except as hereinafter provided,
groups of rivets, bolts or welds at the ends of any member transmitting axial stress
into that member shall have their centers of gravity on the gravity axis of the
member unless provision is made for the effect of the resulting eccentricity.
Except in members subject to repeated variation in stress as defined in U. B. C.
Standard No. 27-3, disposition of fillet welds to balance the forces about the
478
1982 EDITION 2712
neutral axis or axes for end connections of single angle, double angle and similar-
type members is not required. Eccentricity between the gravity axes of such
members and the gauge lines for their riveted or bolted end connections may be
neglected in statically loaded members and shall be considered in members
subject to fatigue loading.
(d) Unrestrained Members. Beam, girder or truss connections may be pro-
portioned for the reaction shears only where the connections are flexible.
Flexible beam connections shall accommodate end rotations of unrestrained
(simple) beams. To accomplish this, inelastic action in the connection is
permitted.
(e) Restrained Members. Fasteners or welds for end connections of beams,
girders and trusses shall be designed for the combined effect of forces resulting
from moment and shear induced by the rigidity of the connections.
When flanges or moment connection plates for end connections of beams and
girders are welded to the flange of an 1- or H-shape column, pairs of column-web
stiffeners having an area given by Formula ( 12-1) shall be provided whenever the
calculated value of As, is positive.
WHERE:
A,.,= area of pair of column-web stiffeners.
A1 = area of flange delivering concentrated force.
thickness of column web.
k = distance between outerface of column flange and web toe of its fillet, if
column is rolled shape, or equivalent distance if column is welded
shape.
thickness of flange or moment connection plate delivering concentrated
force.
tl = thickness of column flange.
de = column-web depth clear of fillets.
pbf = the computed force delivered by the flange or moment connection plate
times 5/1 when the computed force is due to live and dead load only, or 4f3
when the computed force is due to live and dead load in conjunction
with wind or earthquake forces in Seismic Zones Nos. I and 2, except
that for ductile moment-resisting frames in Seismic Zone No. 2 and all
moment-resisting frames in Seismic Zones Nos. 3 and 4, P bf = AfFv,.
beam yield stress.
column yield stress.
F"'' stiffener yield stress.
In addition, stiffeners shall be provided opposite the compression flange when
479
2712 UNIFORM BUILDING CODE
4100t'\IF;
de> pbf ................... (12-2)
480
1982 EDITION 2712
481
2712-2713 UNIFORM BUILDING CODE
used instead of curb level. Penthouses may be excluded in computing the height of
structure.
WHERE:
P force transmitted by one fastener to the critical connected part, kips.
F u = specified minimum tensile strength of the critical connected part, kips
per square inch.
t = thickness of the critical connected part, inches.
B. Oversized and slotted holes: The distance required for standard holes in
Item A above, plus the applicable increment C 1 in Table No. 27 -D-2, but the clear
distance between holes shall be not less than one bolt diameter.
(c) Minimum Edge Distance. I. The distance from the center of a standard
hole to an edge of a connected part shall be not less than the applicable value in
Table No. 27-D-1 nor the value from Subsection 2 or 3 below, as applicable.
2. Along a line of transmitted force, in the direction of the force, the distance
from the center of a standard hole to the edge of the connected part shall be not less
than
3. At end connections bolted to the web of a beam and designed for beam shear
reaction only (without use of an analysis which accounts for the effects induced by
fastener eccentricity), the distance from the center of the nearest standard hole to
482
the end of the beam web shall be not less than
WHERE:
PR = beam reaction, in kips, divided by the number of bolts.
Alternatively, this requirement may be waived, provided the bearing stress
induced by the fastener is limited to not more than 0. 90F u
4. The distance from the center of any oversized or slotted hole to an edge of a
connected part shall be not less than that required for a standard hole by Item No.
I, 2 or 3 above, as applicable, plus the applicable increment C2 in Table No. 27-
D-3.
(f) Maximum Edge Distance. The maximum distance from the center of any
rivet or bolt to the nearest edge of parts in contact with one another shall be 12
times the thickness of the plate, but shall not exceed 6 inches.
I
Welds
Sec. 2714. (a) General. Welder qualification requirements, welding proce-
dure and welding electrodes for other than sheet steel shall conform to U.B.C.
Standard No. 27-6. Welder qualification requirements, welding procedure and
welding electrodes for sheet steel shall conform to U .B.C. Standard No. 27-13.
(b) Maximum Effective Size of Fillet Welds. The maximum size fillet welds
that may be used along edges of connected parts shall be:
I . Along edges of material less than Y4 inch thick, the maximum size may be
equal to the thickness of the material.
2. Along edges of material Y4 inch or more in thickness, the maximum size
shall be Y16 inch less than the thickness of the material, unless the weld is
especially designated on the drawings to be built out to obtain full throat
thickness.
(c) Minimum Size of Fillet Welds and Partial Penetration Welds. The
minimum size of fillet weld shall be as shown in Table No. 27-E-1. The minimum
effective throat of partial penetration groove weld shall be as shown in Table No.
27-E-2. Weld size is determined by the thicker of the two parts joined, except that
the weld size need not exceed the thickness of the thinner part joined unless a
larger size is required by calculated stress. For this exception, particular care
should be taken to provide sufficient preheat for weld soundness.
(d) Length of Fillet Welds. The minimum effective length of a strength fillet
weld shall be not less than four times the nominal size, or else the size of the weld
shall be considered not to exceed one fourth of its effective length.
If longitudinal fillet welds are used alone in end connections of flat bar tension
members, the length of each fillet weld shall be not less than the perpendicular
distance between them. The transverse spacing of longitudinal fillet welds used in
end connections shall not exceed 8 inches, except where transverse bending is
provided for in the connection.
(e) Intermittent Fillet Welds. Intermittent fillet welds may be used to transfer
483
2714 UNIFORM BUILDING CODE
calculated stress across a joint or faying surfaces, when the strength required is
less than that developed by a continuous fillet weld of the smallest permitted size,
and to join components of built-up members. The effective length of any segment
of intermittent fillet welding shall be not less than four times the weld size with a
minimum of ! 1/2 inches.
(f) Lap Joints. The minimum amount of laps on lap joints shall be five times
the thickness of the thinner part joined and not less than I inch. Lap joints joining
plates or bars subjected to axial stress shall be fillet welded along the edge of both
lapped parts except where the deflection of the lapped parts is sufficiently
restrained to prevent opening of the joint under maximum loading.
(g) End Returns of Fillet Welds. Side or end fillet welds terminating at ends
or sides, respectively, of parts or members shall, wherever practicable, be
returned continuously around the corners for a distance not less than twice the
nominal size of the weld. This provision shall apply to side and top fillet welds
connecting brackets, beam scats and similar connections, on the plane about
which bending moments are computed.
(h) Fillet Welds in Holes and Slots. Fillet welds in holes or slots may be used
to transmit shear in lap joints or to prevent the buckling or separation of lapped
parts and to join components of built -up members. Such fillet welds may overlap,
subject to the provisions of Section 2702 (e). Fillet welds in holes or slots shall not
be considered as plug or slot welds.
(i) Plug and Slot Welds. Plug or slot welds may be used to transmit shear in a
lap joint or to prevent buckling of lapped parts and to join component parts of
built-up members.
The diameter of the holes for a plug weld shall be not less than the thickness of
the part containing it plus Y16 inch, rounded to the next greater odd \116 inch, nor
greater than two and one-fourth times the thickness of the weld metal.
The minimum center-to-center spacing of plug welds shall be four times the
diameter of the hole.
The length of slot for a slot weld shall not exceed I 0 times the thickness of the
weld. The width of the slot shall be not less than the thickness of the part
containing it, plus Y16 inch, rounded to the next greater odd 1/16 inch, nor shall it be
greater than two and one-fourth times the thickness of the weld. The ends of the
slot shall be semicircular or shall have the comers rounded to a radius not less than
the thickness of the part containing it, except those ends which extend to the edge
of the part.
The minimum spacing of lines of slot welds in a direction transverse to their
length shall be four times the width of the slot. The minimum center-to-center
spacing in a longitudinal direction on any line shall be two times the length of the
slot.
The thickness of plug or slot welds in material % inch or less in thickness shall
be equal to the thickness of the material. In material over% inch in thickness, it
shall be at least one half the thickness of the material but not less than 5fs inch.
(j) Welding Sheet Steel. Arc welding of sheet steels or strip steels, or both,
I including cold-formed members, 0.180 inch or less in thickness shall conform to
484
1982 EDITION 2714-2715
l27t
~
but not more than 12 inches.
When rivets, bolts or welds are staggered
190t
VF;,
but not more than 18 inches on each gauge line.
WHERE:
t = thickness of thinner outside plate in inches.
The maximum longitudinal spacing of rivets, bolts or intermittent welds
connecting two rolled shapes in contact with one another shall not exceed 24
inches.
485
2715 UNIFORM BUILDING CODE
486
1982 EDITION 2715-2719
487
2719-2721 UNIFORM BUILDING CODE
components of any bending moments which may result from fixation or partial
fixation of columns. Provisions shall be made for oversize holes. See U. B.C.
Standard No. 27-2.
Fabrication
Sec. 2720. The fabrication, erection and painting of structural steel shall
conform to U.B.C. Standard No. 27-2.
Plastic Design
I
Sec. 2721. (a) Scope. Subject to the requirements specified in this section,
simple or continuous beams, braced and unbraced planar rigid frames, and similar
portions of structures rigidly constructed so as to be continuous over at least one
interior support may be proportioned on the basis of their maximum strength,
otherwise known as plastic design. This strength, as determined by rational
analysis, shall be not less than that required to support a factored load of I. 7 times
the live load and dead load or 1.3 times these loads acting in conjunction with 1.3
times wind or earthquake forces.
For one- or two-story frames, the maximum strength may be determined by a
plastic analysis procedure and the frame instability effect Pl:l may be ignored. For
braced multistory frames, provisions should be made to include the frame
instability effect in the design of bracing system and frame members. For
unbraced multistory frames, the frame instability effect shall be included directly
in the calculations for maximum strength.
Plastically designed members of braced multistory steel frames shall not be
part of the required seismic force resisting system in Seismic Zone No.2, No.3 or
No.4.
Rigid frames shall be assumed to have beam-to-column connections of suffi-
cient rigidity to hold virtually unchanged the original angles between intersecting
members in the plane of the frame. Members between rigid frames may be
connected at ends of shear only and be free to rotate under loads.
Connections joining a portion of a structure designed on the basis of plastic
behavior with a portion not so designed need be no more rigid than seat-and-cap
angle or standard web connections.
Where plastic design is used as the basis for proportioning continuous beams
and structural frames, the provisions relating to allowable stress contained in the
other sections of this chapter are waived. The provisions of this chapter shall
apply except as modified by this section.
Crane runways shall not be designed continuous over interior vertical supports
on the basis of maximum strength. Rigid frame bents supporting crane runways
may be considered as coming within the scope of this section.
(b) Material. Structural steel shall conform to U .B.C. Standard No. 27-1.
(c) Stability of Braced Frames. The vertical bracing system for a plastically
designed braced multistory shall be adequate, as determined by a rational analy-
sis, to prevent buckling of the structure under factored gravity loads and to
maintain the lateral stability of the structure, including the overturning effects of
drift, under factored gravity plus factored horizontal loads.
488
The vertical bracing system may be considered to function together with in-
plane shear-resisting exterior and interior walls, floor slabs and roof decks, if they
are secured to the structural frames. The columns, girders, beams and diagonal
members, when used as the vertical bracing system, may be considered to
comprise a vertical-cantilever, simply-connected truss in the analyses for frame
buckling and lateral stability. Axial deformation of all members in the vertical
bracing system shall be included in the lateral stability analysis. The axial force in
these members caused by factored gravity plus factored horizontal loads shall not
exceed 0.85PY, where PY is the product of yield stress times area of the member.
Girders and beams included in the vertical bracing system of a braced multisto-
ry frame shall be proportioned for axial force and moment caused by the con-
current factored horizontal and gravity loads, in accordance with Formula (21-2),
with Pcr taken as the maximum axial strength of the beam, based on the actual
slenderness ratio between braced points in the plane of bending.
(d) Stability of Unbraced Frames. The strength of an unbraced multistory
frame shall be determined by a rational analysis which includes the effect of frame
instability and column axial deformation. Such a frame shall be designed to be
stable under (I) factored gravity loads and (2) factored gravity plus factored
horizontal loads. The axial force in the columns at factored load levels shall not
exceed 0.75 Pv.
(e) Columns. In the plane of bending of columns, which would develop a
plastic hinge at ultimate loading, the slenderness ratio 1/r shall not exceed Cc, as
defined in Section 270 I (c).
The maximum strength of an axially loaded compression member shall be:
WHERE:
A = gross area of the member
Fa = See Formula (2-1) in Section 2702 (b).
Members subject to combined axial load and bending moment shall satisfy the
following conditions:
~ l 0
_f_
p
,.,.
+( C"'M
l--p M"'
p) - . ................ (21-2)
,.
P,, _M__
E_+ ~ 1 0 M -~ M ,................. (21-3)
l.IHM"-.'
489
2721 UNIFORM BUILDING CODE
(f) Shear. Unreinforced webs of columns, beams, and girders, including areas
within the boundaries of the connections, shall be so proportioned that:
(g) Web Crippling. Web stiffeners are required on a member at a point of load
application where a plastic hinge would form.
Web stiffeners arc required at points where concentrated compression loads arc
delivered by the flanges to the web as required by Section 2712 (e).
(h) Minimum Thickness (Width-thickness Ratios). The width-thickness
ratio for flanges of rolled "I,'' wide flange and similar built-up single-web shapes
that would be subjected to compressions involving hinge rotation under ultimate
loading shall not exceed the following values:
F, btl2tt
36 8.5
42 8.0
45 7.4
50 7.0
55 6.6
60 6.3
65 6.0
d
1= 4I2 p)
rr;:- ( I - I.4 P, ............... (21-6a)
vF., ,
WHERE: p
-p > 0.27
'I
d 2.57
~ .................... (21-6b)
t
490
1982 EDITION 2721
WHERE:
rv the radius of gyration of the member about its weak axis.
M the lesser of the moments at the ends of the unbraced segment.
MIMP the end moment ratio, is positive when the segment is bent in reverse
curvature and negative when bent in single curvature.
EXCEPTION: Laterally unsupported lengths greater than specified above may
be justified by an analysis based upon the amount of restraint present at the ends of
the segment in the plane of the computed bending moments.
The foregoing provisions need not apply in the region of the last hinge to form
nor in members oriented with their weak axis normal to the plane of bending.
However, in the region of the last hinge to form and in regions not adjacent to a
plastic hinge, the maximum distance between points of lateral support shall be
such as to satisfy the requirements of Formulas (2-6a), (2-6b), (2-7), (3-la) and
491
2721-2722 UNIFORM BUILDING CODE
(3-1 b) in this chapter. For this case the value of fa and fb shall be computed from
the moment and axial force at factored loading, divided by the applicable load
factor.
Members built into a masonry wall and having their web perpendicular to the
wall can be assumed to be laterally supported with respect to their weak axis of
bending.
(k) Fabrication. The provisions of U .B.C. Standard No. 27-2 with respect to
workmanship shall govern the fabrication of structures, or portions of structures,
designed on the basis of maximum strength, subject to the following limitations:
The use of sheared edges shall be avoided in locations subject to plastic
hinge rotation of factored loading. If used they shall be finished smooth by
grinding, chipping or planing.
In locations subject to plastic hinge rotation at factored loading, holes for
rivets or bolts in the tension area shall be subpunched and reamed or drilled full
size.
Steel Ductile Moment-resisting Space Frames-Seismic Zones
Nos. 3and 4
Sec. 2722. (a) General. Design and construction of steel framing in ductile
moment-resisting space frames in Seismic Zones No. 3 and No. 4 shall conform
to the requirements of the code and to all the requirements of this section. Welding
shall comply with U.B.C. Standard No. 27-6.
(b) Definitions. I. Joints. The joint is the entire assemblage at the intersec-
tions of the members.
2. Connections. The connection consists of only those elements that connect
the member to the joint.
I (c) Materials. Structural steel shall conform to A36, A441, A500 (Grades B
and C), A501, A572 (Grades 42, 45, 50 and 55), or A588.
EXCEPTION: Structural steel A283 Grade D may be used for base plates and
anchor bolts.
(d) Connections. Each beam or girder moment connection to a column shall
be capable of developing in the beam the full plastic capacity of the beam or
girder.
EXCEPTION: The connection need not develop the full plastic capacity of the
beam or girder if it can be shown that adequately ductile joint displacement capacity
is provided with a lesser connection.
For steel whose specified ultimate strength is less than 1.5 of the specified yield
strength, plastic hinges in beams formed during inelastic deformations of the
frame shall not occur at locations in which the beam flange area has been reduced
such as by holes for bolts.
(e) Local Buckling. Members in which hinges will form during inelastic
displacement of the frames shall comply with the requirement for "plastic design
sections."
(f) Nondestructive Testing. Welded connections between the primary mem-
bers of ductile moment-resisting space frames shall be tested by nondestructive
492
1982 EDITION 2722-2725
methods for compliance with U. B. C. Standard No. 27-6 and job specifications.
This testing shall be a part of the special inspection requirements of Section 306.
A program for this testing shall be established by the person responsible for
structural design and as shown on plans and specifications.
As a minimum, this program shall include the following: I. All complete
penetration groove welds contained in joints and splices shall be tested I 00
percent either by ultrasonic testing or by radiography.
EXCEPTION: When approved, the nondestructive testing rate for an individual
welder or welding operator may be reduced to 25 percent, provided the reject rate is
demonstrated to be 5 percent or less of the welds tested for the welder or welding
operator. A sampling of at least 40 completed welds for a job shall be made for such
reduction evaluation. Reject rate is defined as the number of welds containing
rejectable defects divided by the number of welds completed. For evaluating the
reject rate of continuous welds over 3 feet in length where the effective throat
thickness is I inch or less, each 12-inch increment or fraction thereof shall be
considered as one weld. For evaluating the reject rate on continuous welds over 3 feet
in length where the effective throat thickness is greater than I inch, each 6 inches of
length or fraction thereof shall be considered one weld.
When approved by the building official and outlined in the project plans and
specifications, this nondestructive ultrasonic testing may be performed in the shop
of an approved fabricator utilizing qualified test techniques in the employment of the
fabricator.
2. Partial penetration groove welds when used in column splices shall be tested
either by ultrasonic testing or radiography when required by the plans and
specifications.
3. Base metal thicker than 11/z inches, when subjected to through-thickness
weld shrinkage strains, shall be ultrasonically inspected for discontinuities
directly behind such welds after joint completion.
Any material discontinuities shall be accepted or rejected on the basis of the
defect rating in accordance with the (larger reflector) criteria of Table No. 27-6-E
ofU.B.C. Standard No. 27-6.
Steel Ductile Moment-resisting Space Frames-Seismic Zones
Nos.1 and 2
Sec. 2723. (a) General. Compliance with this section shall be deemed to meet
the requirements for a ductile moment-resisting space frame of Section 2312 Ul
and Table No. 23-1 for buildings in Seismic Zones No. I and No. 2.
(b) Design and Construction. The design and construction for steel ductile
moment-resisting space frames for buildings located in Seismic Zones No. I and
No. 2 shall conform to all applicable requirements of this code except Section
2722.
Steel Storage Racks
Sec. 2724. Steel storage racks may be designed in conformance with U. B. C.
Standard No. 27-11.
Steel Cables
Sec. 2725. Structural use of steel cables shall conform with the provisions of
U.B.C. Standard No. 27-12.
493
27-A UNIFORM BUILDING CODE
494
....
li
TABLE NO. 27-B-ALLOWABLE STRESS N
m
c
REQUIRED WELD :::::j
TYPE OF WELD AND STRESS' ALLOWABLE STRESS STRENGTH LEVEL2 3
0z
COMPLETE PENETRATION GROOVE WELDS
I. Tension normal to the Same as base metal "Matching" weld metal must be used; see Table
effecti'e area No. 27-6-EofU.B.C. Standard No. 27-6
2. Compression normal to Same as base metal
the effective area
3. Temion or compre"ion Same as base metal Weld metal v. ith a strength le\el equal to or le"
parallel to the axis of than "matching" weld metal may be used
the v.eld
-1. Shear on the 0.30 X nominal tensile strength of weld metal (ksi),
effecti'e area except shear stress on base metal shall not exceed
0.40 X yield stress of base metal
PARTIAL PENETRATION GROOVE WELDS4
(Continued)
TABLE NO. 278 (Continued)
FILLET WELDS
9. Shear on effective area 0.30 x nominal tensile strength of weld metal (ksi),
except shear stress on base metal shall not exceed
0.40 X yield stress of base metal Weld metal with a strength level equal to or less
10. Tension or compression than "matching" metal may be used
Same as base metal
parallel to axis of welds
PLUG AND SLOT WELDS
II. Shear parallel to faying 0.30 X nominal tensile strength of weld metal (ksi), Weld metal wirh a strength level equal ro or le"
surfaces (on effective except shear stress on base metal shall not exceed than "marching" weld metal may be used
area) 0.40 x yield stress of base metal
Air Dry Unit Weight, pcf. 90 9S 100 lOS 110 liS 120
Coefficient./'c ~ 4.0 ksi. 0.73 0.76 0.78 0.81 0.83 0.86 0.88
Coefficient./' c ~ S.O ksi. 0.82 0.8S 0.87 0.91 0.93 0.96 0.99
V2 'Is .y.
lis I Vs 'Is
'14 I V I
7/s IV2 !Vs
I I.Y. I V
!Vs 2 IV2
IV 2V Pis
Over IV. I% x Diameter I V. x Diameter
1For oversized or slotted holes, see Section 2713 (e) 4.
2AIJ edge distances in this column may be reduced 1/11 inch when the hole is at a point where stress does not
exceed 25 percent of the maximum allowed stress in the element.
497
27-D-2, 27-D-3, 27-E-1 UNIFORM BUILDING CODE
SLOTTED HOLES
NOMINAL Perpendicular Perallelto
DIAMETER OVERSIZED to Un.olforce
OF FASTENER HOLES LIMo! Force Short Slota Long Slot.'
'When length of slO! is less than maximum allowable, C1 may be reduced by the difference between the
maximum and actual slO!lengths.
,.;;7jg y,. Ys
I Ys Ys Y.d 0
;.I Ys Ys y,.
1When length of slot is less than maximum allowable, C 2 may be reduced by one half the
difference between the maximum and actual slot lengths.
To Y. inclusive Y.
OverY. toY, x.
OverY, toY. Y.
OverY. x.
1Leg dimension of fillet welds.
498
1982 EDITION 27-E-2, 27-F
To Y. inclusive Yo
OverY. toY, x.
OverY, toY. Y.
OverY. to IY, x.
Over I Y, to 2Y. Y.
Over 2Y. to 6 y,
Over6 r.
1See Section 2702 (e)
499
2801 UNIFORM BUILDING CODE
Chapter 28
ALUMINUM
Material Standards and Symbols
Sec. 2801. (a) General. The quality, design, fabrication and erection of alu-
minum used structurally in buildings and structures shall conform to the require-
ments of this chapter, to other applicable requirements of this code and to U .B.C.
Standard No. 28-1.
(b) Alloys. The use of aluminum alloys and tempers other than those covered
by this chapter shall be permitted for structural members and assemblies, pro-
vided standards of performance not less than those required by this chapter are
substantiated to the satisfaction of the building official. When required by the
building official, certification that the alloys and tempers called for on the plans
have been furnished shall be provided.
(c) Symbols and Notations. The symbols and notations used in these regula-
tions are defined as follows:
A = area, inches2.
Aw = area of cross section lying within 1.0 inch of a weld, inches2.
a1 shorter dimension of rectangular panel, inches.
a2 = longerdimensionofrectangularpanel, inches.
a, = equivalent width of rectangular panel, inches.
B,D,C,
= buckling formula constants, with following subscript:
c - compression in columns
p - compression in flat plates
t - compression in round tubes
tb - bending in round tubes
b - bending in rectangular bars
s - shear in flat plates
b = width of sections, inches.
bit = width-to-thickness ratio or rectangular element of a cross section.
c = distance from neutral axis to extreme fiber, inches.
D = diameter, inches.
d = depth of section or beam, inches.
E = compressive modulus of elasticity, ksi.
f = calculated stress, ksi.
fa average compressive stress on cross section of member produced by
axial compressive load, ksi.
fb maximum bending stress (compressive) caused by transverse loads or
end moments, ksi.
fs = shear stress caused by torsion or transverse shear, ksi.
F = allowable stress, ksi.
500
1982 EDITION 2801
compressive yield strength across a butt weld (0.2 percent offset in tO-
inch gauge length), ksi.
7T2f[n,(Lir)2]. where Llr is slenderness ratio for member considered as
a column tending to fail in the plane of the applied bending moments,
ksi.
F" allowable stress for cross section 1.0 inch or more from weld, ksi.
allowable stress on cross section, part of whose area lies within 1.0 inch
of a weld, ksi.
F, allowable shear stress for members subjected only to torsion or shear.
ksi.
shear ultimate strength, ksi.
shear ultimate strength within 1.0 inch of a weld, ksi.
shear yield strength, ksi.
F.\\'W
shear yield strength within 1.0 inch of a weld, ksi.
tensile ultimate strength. ksi.
Ftuw tensile ultimate strength across a butt weld, ksi.
tensile yield strength, ksi.
tensile yield strength across a butt weld (0.2 percent offset in 10-inch
gauge length), ksi.
either F,, or F ... whichever is smaller, ksi.
g spacing of rivet or bolt holes perpendicular to direction of load, inches.
G modulus of elasticity in shear, ksi.
h clear height of shear web, inches.
moment of inertia, inches 4 .
111 moment of inertia of horizontal stiffener, inches 4 .
l, moment of inertia of transverse stiffener to resist shear buckling,
inches 4 .
I, moment of inertia of a beam about axis perpendicular to web, inches 4 .
I, moment of inertia of a beam about axis parallel to web. inches 4 .
J torsion constant, inches 4
501
2801 UNIFORM BUILDING CODE
502
1982 EDITION 2801-2802
(b) Welded Structural Members. Allowable unit stresses for structural mem-
bers whose entire cross-sectional area lies within I inch of the center line of a butt
weld of the heel of a fillet weld shall be determined by means of the formulas of
Table No. 28-C utilizing the applicable minimum expected mechanical proper-
ties for welded aluminum alloys listed in U .B.C. Standard No. 28-1. The tensile
ultimate strength, Fruw, shall be 90 percent of the ASME weld qualification test
value of ultimate strength. Except as modified by U.B.C. Standard No. 28-1,
buckling constants determined in accordance with the formulas of Tables
Nos. 28-E and 28-G shall be calculated using the nonwelded mechanical proper-
ties of the respective aluminum alloys.
If less than 15 percent of the area of a given cross section lies within I inch of
the center line of a butt weld or the heel of a fillet weld, the effect of the weld may
be neglected and allowable stresses for nonwelded structural members may be
used.
If the area of a cross section that lies within I inch of a weld is between 15
percent and 100 percent of the total area of the cross section, the allowable stress
503
2802-2804 UNIFORM BUILDING CODE
WHERE:
allowable stress on cross section part of whose area lies within 1.0 inch
of a weld.
Fn allowable stress for cross section 1.0 inch or more from weld.
F w = allowable stress on cross section if entire area were to lie within 1.0 inch
of a weld.
Aw = area of cross section lying within 1.0 inch of a weld.
A = net area of cross section of a tension member or tension flange of a
beam, or gross area of cross section of a compression member or
compression flange of a beam, inches2. (A beam flange is considered to
consist of that portion of the member further than 2c/3 from the neutral
axis, where cis the distance from the neutral axis to the extreme fiber.)
For columns and beams with welds at locations other than at their supported
ends (not farther from the supports than 0.05 L from the ends), and for cantilever
columns and single web beams with transverse welds at or near the supported end,
the effect of welding on allowable stresses shall be determined in accordance with
the provisions of U.B.C. Standard No. 28-1.
(c) Rivets and Bolts. Allowable stresses in aluminum rivets and bolts shall be
as set forth in Table No. 28-A.
(d) Fillet Welds. Allowable sheer stresses in fillet welds shall be as set forth in
Table No. 28-B.
Design
Sec. 2803. (a) Combined Stresses. Members subjected to combinations of
compression and bending or shear, compression and bending shall be propor-
tioned in accordance with the provisions of U .B.C. Standard No. 28-1.
(b) Light Gauge Members. Where the design of light gauge structural mem-
bers is involved, the special provisions of U.B.C. Standard No. 28-1 shall be
applied.
(c) Structural Rooting and Siding. The live load deflection of structural
roofing and siding made of formed sheet shall not exceed one sixtieth of the span
length.
(d) Connections. The design of mechanical and welded connections shall be
in accordance with this chapter and the provisions ofU.B.C. Standard No. 28-1.
504
1982 EDITION 2804
505
28A, 288 UNIFORM BUILDING CODE
2024-T4 37 16 26
6061-T6 27 12 18
7075-T73 40 17 28
1Also applies to 6061-T6 pins.
2Yalues apply to either turned bolts or unfinished bolts in holes not more than Y,,
inch oversized.
5356
FILLER ALLOY 1100 4043 5554 5556
Parent Alloy
1100
3003
Alclad 3004
8.2
.
:1.2
4.8
5
.5 7
.
0
8
0
5052 0
s 7 0
5083
.
0
7
0
8.5
8.5
5086
5454
.545()
0
.5
0
7
. 8.5
8.5
8.5
G061
6063 .5 6.5 6.5
*Not permitted.
506
TABLE NO. 28C-GENERAL FORMULAS FOR DETERMINING ALLOWABLE STRESSES
-:g
N
m
TYPE OF STRESS TYPE OF MEMBER OR COMPONENT
SPEC.
NO.
ALLOWABLE STRESS.
KSI
c
:::::j
TENSION. axial, 5
net section
Any tension member:
1 F,,fn,or F,.J(Jc,n.) z
Rcctan&Uiar tubes, structural
shapes bent about strona axis -I -[}-I V'\- 2 F,,Jn, or F,.J(k,n.)
TENSION IN
BEAMS.
extreme fiber.
net sectlon
Round or oval tubes -o-oo- 3 1.11F11 /rt 1 or 1.24F,./(A:,n.)
ALLOWABLE
STRESS, KSI, SLENDERNESS ALLOWABLE STRESS, K~ SLENDERNESS ALLOWABLE STRESS,
SLENDERNESS UMIT, S, SLENDERNESS UMIT, S, KSI
BETWEEN S1 AND S, SLENDERNESS ~ S,
<S,
COMPRESSION
B _ n.F~,
IN COLUMNS,
axial, gross
All columns
7
F,
.!:=~ f.(.B,- D,!)' ;=Cr .-!!3_
n. (Lir)'
section "'" ' D,
COMPRESSION
ftanges and legs
I r-r 8
"'"
~=~
r 5.10,.
n. ' "t
~-~
r 5.1 n. (5.lblt)'
Curved plates
(Continued)
TABLE NO. 28C-GENERAL FORMULAS FOR DETERMINING ALLOWABLE STRESSES-(Continued)
ALLOWABLE
STRESS, K~. ALLOWABLE STRESS, KSI ALLOWABLE STRESS,
SPEC. SLENDERNESS SLENDERNESS SLENDERNESS KSI
TYPE Of STRESS TYPE OF MEMBER OR COMPONENT SLENDERNESS UMIT, S,
NO. UMrT, S1 BETWEEN s 1 AND S, SUENDERNESS ~ S,
<51
- ..
SlaJI<wobbeams
benl aboul strona -I-T-E- 11 ~ ~.1.2(11,-F,,l
' D,
;!:(.-~)
1.21,
~ -uc.
'
..c
"(l../1.11,)
Round or oval
tubes ~64 12
1.17F,
n,
~=r
'
.. -117F"r
o,,
~s .. -v..(!)
Ro
--
I
(:-
-;;:-v,.-v, 1
' Same as Spe<ifk:otioa 10
1
"E
=(.-l.l7F.. r ~8,-D,~)
-:r
1.17F,,
Curved Sections ~ R
-=c,
COMPRFSSION
IN BEAMS,
~
12
n, I D, I l6n, (~)( l+
extreme
.. d
fiber,,......
section Solid rectangular
beams
-it-
-EE 13 ~ ~Jfi II,- I.JF,,
I 2.30,
.!.(B,- 2.)0,~~)
" d I
d!i-;;-uc.
I
..E.
S.29,1<i/I)'(Lo/ll
c:
z
Rectangular tubes
d box sectioas -0- 14 ..
~ w-e'- ~'")'
I, 1.60_. !;J.- 1.6D .J) 4f.-
I, 1.6
(f.!)' ..E.
2.S6oi,(W,/l,)
~::u
3:
COMPRFSSION
OUtstaadlag
~-; I- -; .......
-t t-
.. .,.. t,v'i;
ID
c:
IN COMPONENTS
OF BEAMS,
(compoaeal
laages
I [ T\J"
15 !:!. ~- B,-F_.,
I S.ID,
-!;J.,.
'
-s.w.~)
I
~-
I S.ID, ,(S.II>/1) r=
c
z
uader uaiform
compression),
arosssection
Flat plates wilb
bolbedges
!llpported
-;r-- -1t-
Trv- 16 ..
!:!. ~_II,-
I
F,,
1.6D, ..
.!.(II, - 1.60,~), ~- .!o!!..
I 1.6D,
t,v'i;
... (1.61>/1)
"
0
0
~
...
ID
~
m
c
3
0
z
Root plain with
ffiMPR~ION
IN COMPONENTS
IYBEAMS,
mmprased ode
heteouioa
aJaesupported
17 ..
l.lF~.
_!_(s. - J.5o.~)
., I n. (3.5bft)Z
11~ ..
(compoDHt Root plain with
uader bendlaa hothodiOS 18 I.JF,! ~-B.- t.lF,, _!_(s.- o.67o.~) k,v'ii;:E
iaowa !llpporlod I 0.610, " I n, (0.67hlt)
plaa.),
l'lllt plain with
..
lrDSI
horizontal stiffener, ... s. k, Vii;:E
secdoa
holhodaes 19 l.lF,,
_!_(s. - o:~o.~)
llr. I
It
, - 0.290, n, (0.29h/r)
!llpportod
SHEAR
IN WEBS,
Unstiffenod
lat webs IDI 20 h
t
8,- F,,
l.'lSD. n, (1.25h/t)2
aross
section Stiffened ftat webs [tiTII...fi::::fi}
... ..j.;o +0. 7(o, to1)1 21
F.,
n,
.,---.:zw.-..
8,-"F,,
~ _ __s_
t - 1.25 na ( 1.25a, /1)2
I For F bl t
values greater than S 2 , the allowable bending shall be determined from the formula for tubes in compression, Specification I 0, using the
formula that is appropriate for the particular value of Rblt. Note that in this case Rblt may be either less or greater than the value of S 2 for tubes in
compression.
28-D, 28-E UNIFORM BUILDING CODE
Building
And
Similar 'I)'pe
Structures
I. Tension Members
F.S. on tensile strength, n" ... 1.95
F.S. on yield strength, ny. 1.65
2. Columns
F.S. on buckling strength, n".. . . .......... . 1.95
F.S. on crippling strength of thin sections, n" . . 1.95
F.S. on yield strength for short columns, ny 1.65
3. Beams
F.S. on tensile strength, n" .......... . 1.95
F.S. on tensile yield strength, n,. . . ......... . 1.65
F.S. on compressive yield strength for short beams, n,. 1.65
F.S. on buckling strength, ny ... 1.65
F. S. on crippling strength of thin sections, nY . 1.65
F.S. on shear buckling of webs, na .. 1.20
4. Connections
F.S. on bearing strength ... ... 1.2 X 1.95 = 2.34
F. S. on bearing yield strength. nY .. ................. 1.65
F.S. on shear strength of rivets and bolts. 1.2 X 1.95 = 2.34
F.S. on shear strength of fillet welds .. 1.2 X 1.95 = 2.34
F.S. on tensile strength of butt welds, n". 1.95
F.S. on tensile yield strength of butt welds, n, 1.65
r
AND STRESS INTERCEPT, KSI SLOPE, KSI INTERSECTION
+~)" ]
2
~0
I. Compression in Columns 28,
and Beam Flanges B,=F,y[l D,= (6: C,= 3D,
2. Compression in Flat
Plates
- [ J!d
BP-F<Y I+ 7.6
1/3] B (68
Dp=To- T r2 _.3z_
CP- 3D"
3. Compression in Round
Thbes Under Axial End
- [
B,-F,, I+
Jfal_
.
5 8
115] D,= :.1 (i )"' c,
Load
4. Compressive Bending
-
Bb-l.3F,y [I+ J!d "'] -~(~)1/2 28b
Stress in Solid Rectan- 7 Db- 20 E Cb=JD;
gular Bars
5. Compressive Bending
Stress in Round Thbes
- l.5FY [I+ J!L
B,b- .
5 8
I/'] (BT )"' C,b--(~)'
D,b= 2B~; D,,-D,
510
1982 EDITION 28-F, 28-G
NONWELDED OR
REGIONS FARTHER THAN REGIONS WITHIN 1.0
ALLOY AND TEMPER 1.0 INCH FROM A WELD INCH OF A WELD
2014-T6, -T651
1.25
1.12 - I
-
Alclad 2014-T6, -T651 1.25 1.12 - -
6061-T6, -T651 1.0 1.12 1.0 1.0
6063-T5, -T6, -T83 1.0 1.12 1.0 1.0
All Others Listed in
U.B.C. Standard 1.0 1.10 1.0 1.0
No. 28-1
1
1f the weld yield strength exceeds 0.9 of the parent metal yield strength, the
allowable compressive stress within 1.0 inch of a weld should be taken equal
to the allowable stress for nonwelded material.
2. Compression in Flat
Plates
[
BP=r;, I
(F )
+"fft Jill
B (B
Dp=-=.t r
T
2
-
CP-0.41 DP
~
3. Compression in Round
Tubes Under Axial End
Load
-
B,-F,,. [ I+ J!d_
_
87
Ji5]
D,= :5 (i r, c, *
*C, can be found from a plot of the curves of allowable stress based on elastic and inelastic buckling or
by a trial-and-error solution.
511
1982 EDITION 2901-2903
Part VI
DETAILED REGULATIONS
Chapter29
EXCAVATIONS, FOUNDATIONS AND RETAINING WALLS
Scope
Sec. 2901. This chapter sets forth requirements for excavation and fills for any
building or structure and for foundations and retaining structures.
Reference is made to Appendix Chapter 70 for requirements governing excava-
tion, grading and earthwork construction, including fills and embankments.
Quality and Design
Sec. 2902. The quality and design of materials used structurally in excava-
tions, footings and foundations shall conform to the requirements specified in
Chapters 23, 24, 25, 26 and 27 of this code.
Excavations and Fills
Sec. 2903. (a) General. Excavation or fills for buildings or structures shall be
so constructed or protected that they do not endanger life or property.
Cut slopes for permanent excavations shall be not steeper than 2 horizontal to I
vertical and slopes for permanent fills shall be not steeper than 2 horizontal to 1
vertical unless substantiating data justifying steeper slopes are submitted. Devia-
tion from the foregoing limitations for slopes shall be permitted only upon the
presentation of a soil investigation report acceptable to the building official.
No fill or other surcharge loads shall be placed adjacent to any building or
structure unless such building or structure is capable of withstanding the addi-
tionalloads caused by the fill or surcharge.
Existing footings or foundations which may be affected by any excavation shall
be underpinned adequately or otherwise protected against settlement and shall be
protected against lateral movement.
Fills to be used to support the foundations of any building or structure shall be
placed in accordance with accepted engineering practice. A soil investigation
report and a report of satisfactory placement of fill, both acceptable to the
building official, shall be submitted.
(b) Protection of Adjoining Property. The requirements for protection of
adjacent property and depth to which protection is required shall be as defined by
prevailing law. Where not defined by law, the following shall apply: Any person
making or causing an excavation to be made to a depth of 12 feet or less below the
grade shall protect the excavation so that the soil of adjoining property will not
cave in or settle, but shall not be liable for the expense of underpinning or
extending the foundation of buildings on adjoining properties where his excava-
tion is not in excess of 12 feet in depth. Before commencing the excavation, the
person making or causing the excavation to be made shall notify in writing the
513
2903-2905 UNIFORM BUILDING CODE
owners of adjoining buildings not less than I 0 days before such excavation is to be
made that the excavation is to be made and that the adjoining buildings should be
protected.
The owners of the adjoining properties shall be given access to the excavation
for the purpose of protecting such adjoining buildings.
Any person making or causing an excavation to be made exceeding 12 feet in
depth below the grade shall protect the excavation so that the adjoining soil will
not cave in or settle and shall extend the foundation of any adjoining buildings
below the depth of 12 feet below grade at his own expense. The owner of the
adjoining buildings shall extend the foundation of these buildings to a depth of 12
feet below grade at his own expense, as provided in the preceding paragraph.
Soil Classification-Expansive Soil
Sec. 2904. (a) Soil Classification: General. For the purposes of this chapter,
the definition and classification of soil materials for use in Table No. 29-B shall
be according to U.B.C. Standard No. 29-1.
(b) Expansive Soil. When the expansive characteristics of a soil are to be
determined, the procedures shall be in accordance with U.B.C. Standard
No. 29-2 and the soil shall be classified according to Table No. 29-C. Founda-
tions for structures resting on soils with an expansion index greater than 20, as
determined by U .B.C. Standard No. 29-2, shall require special design considera-
tion. In the event the soil expansion index varies with depth, the weighted index
shall be determined according to Table No. 29-D.
Foundation Investigation
Sec. 2905. (a) General. The classification of the soil at each building site
shall be determined when required by the building official. The building official
may require that this determination be made by an engineer or architect licensed
by the state to practice as such.
(b) Investigation. The classification shall be based on observation and any
necessary tests of the materials disclosed by borings or excavations made in
appropriate locations. Additional studies may be necessary to evaluate soil
strength, the effect of moisture variation on soil-bearing capacity, compressibility
and expansiveness.
(c) Reports. The soil classification and design bearing capacity shall be
shown on the plans, unless the foundation conforms to Table No. 29-A. The
building official may require submission of a written report of the investigation
which shall include, but need not be limited to, the following information:
I. A plot showing the location of all test borings and/or excavations.
2. Descriptions and classifications of the materials encountered.
3. Elevation of the water table, if encountered.
4. Recommendations for foundation type and design criteria including bear-
ing capacity, provisions to minimize the effects of expansive soils and the
effects of adjacent loads.
5. Expected total and differential settlement.
(d) Expansive Soils. When expansive soils are present, the building official
514
1982 EDITION 2905-2907
may require that special provisions be made in the foundation design and con-
struction to safeguard against damage due to this expansiveness. He may require a
special investigation and report to provide this design and construction criteria.
(e) Adjacent Loads. Where footings are placed at varying elevations the effect
of adjacent loads shall be included in the foundation design.
(f) Drainage. Provisions shall be made for the control and drainage of surface
water around buildings.
Allowable Foundation and Lateral Pressures
Sec. 2906. The allowable foundation and lateral pressures shall not exceed the
values set forth in Table No. 29-B unless data to substantiate the use of higher
values are submitted. Table No. 29-B may be used for design of foundations on
rock or nonexpansive soil for l)tpes II One-hour, 11-N and V buildings which do
not exceed three stories in height or for structures which have continuous footings
having a load of less than 2000 pounds per lineal foot and isolated footings with
loads of less than 50,000 pounds.
Footings
Sec. 2907. (a) General. Footings and foundations, unless otherwise specifi-
cally provided, shall be constructed of masonry, concrete or treated wood in
conformance with U .B.C. Standard No. 29-3 and in all cases shall extend below
the frost line. Footings of concrete and masonry shall be of solid material.
Foundations supporting wood shall extend at least 6 inches above the adjacent
finish grade. Footings shall have a minimum depth below finish grade as indicated
in Table No. 29-A unless another depth is recommended by a foundation
investigation.
(b) Bearing Walls. Bearing walls shall be supported on masonry or concrete
foundations or piles or other approved foundation system which shall be of
sufficient size to support all loads. Where a design is not provided, the minimum
foundation requirements for stud bearing walls shall be as set forth in Table
No. 29-A.
EXCEPTIONS: I. A one-story wood or metal frame building not used for
human occupancy and not over 400 square feet in floor area may be constructed with
walls supported on a wood foundation plate when approved by the building official.
2. The support of buildings by posts embedded in earth shall be designed as
specified in Section 2907 (f). Wood posts or poles embedded in earth shall be
pressure treated with an approved preservative. Steel posts or poles shall be pro-
tected as specified in Section 2908 (h).
(c) Stepped Foundations. Foundations for all buildings where the surface of
the ground slopes more than l foot in l 0 feet shall be level or shall be stepped so
that both top and bottom of such foundation are level.
(d) Footing Design. Except for special provisions of Section 2909 covering
the design of piles, all portions of footings shall be designed in accordance with
the structural provisions of this code and shall be designed to minimize differen-
tial settlement.
(e) Foundation Plates or Sills. Foundation plates or sills shall be bolted to the
foundation or foundation wall with not less than 1/z-inch nominal diameter steel II
515
2907 UNIFORM BUILDING CODE
WHERE:
A _ 2.34P
S 1b
p Applied lateral force in pounds.
Allowable lateral soil-bearing pressure as set forth in Table No. 29-B
based on a depth of one third the depth of embedment.
Allowable lateral soil-bearing pressure as set forth in Table No. 29-B
based on a depth equal to the depth of embedment.
b Diameter of round post or footing or diagonal dimension of square post
or footing (feet).
h Distance in feet from ground surface to point of application of "P."
d = Depth of embedment in earth in feet but not over 12 feet for purpose of
computing lateral pressure.
Constrained. The following formula may be used to determine the depth of
embedment required to resist lateral loads where constraint is provided at the
ground surface, such as a rigid floor or pavement.
( - 4 ..25 .!'..!!._
[2 - s1 !! }
Plies-General Requirements
Sec. 2908. (a) General. Pile foundations shall be designed and installed on
the basis of a foundation investigation as defined in Section 2905 where required
by the building official.
The investigation and report provisions of Section 2905 shall be expanded to
include but not be limited to the following:
I. Recommended pile types and installed capacities.
2. Driving criteria.
3. Installation and field inspection procedures.
4. Pile load test requirements.
The use of piles not specifically mentioned in this chapter shall be permitted,
subject to the approval of the building official upon submission of acceptable test
data, calculations or other information relating to the properties and load-carrying
capacities of such piles.
(b) Determination of Allowable Loads. The allowable axial and lateral loads
on piles shall be determined by an approved formula, by load tests or by a
foundation investigation.
(c) Static Load Thsts. When the allowable axial load of a single pile is
determined by a load test, one of the following methods shall be used:
Method 1. It shall not exceed 50 percent of the yield point under test load. The
517
2908 UNIFORM BUILDING CODE
yield point shall be defined as that point at which an increase in load produces a
disproportionate increase in settlement.
Method 2. It shall not exceed one half of the load which causes a net settle-
ment, after deducting rebound, of .01 inch per ton of test load which has been
applied for a period of at least 24 hours.
Method 3. It shall not exceed one half of that load under which, during a 40-
hour period of continuous load application, no additional settlement takes place.
(d) Column Action. All piles standing unbraced in air, water or material not
capable of lateral support, shall conform with the applicable column formula as
specified in this code. Such piles driven into firm ground may be considered fixed
and laterally supported at 5 feet below the ground surface and in soft material at I 0
feet below the ground surface unless otherwise prescribed by the building official
after a foundation investigation by an approved agency.
(e) Group Action. Consideration shall be given to the reduction of allowable
pile load when piles are placed in groups. Where soil conditions make such load
reductions advisable or necessary, the allowable axial load determined for a single
pile shall be reduced by any rational method or formula approved by the building
official.
(f) Piles in Subsiding Areas. Where piles are driven through subsiding fills or
other subsiding strata and derive support from underlying firmer materials,
consideration shall be given to the downward frictional forces which may be
imposed on the piles by the subsiding upper strata.
Where the influence of subsiding fills is considered as imposing loads on the
pile, the allowable stresses specified in this chapter may be increased if satisfacto-
ry substantiating data are submitted.
(g) Jetting. Jetting shall not be used except where and as specifically permit-
ted by the building official. When used, jetting shall be carried out in such a
manner that the carrying capacity of existing piles and structures shall not be
impaired. After withdrawal of the jet, piles shall be driven down until the required
resistance is obtained.
(h) Protection of Pile Materials. Where the boring records of site conditions
indicate possible deleterious action on pile materials because of soil constituents,
changing water levels or other factors, such materials shall be adequately pro-
tected by methods or processes approved by the building official. The effective-
ness of such methods or processes for the particular purpose shall have been
thoroughly established by satisfactory service records or other evidence which
demonstrates the effectiveness of such protective measures.
(i) Allowable Loads. The allowable loads based upon soil conditions shall be
established in accordance with Section 2908.
EXCEPTION: Any uncased cast-in-place pile may be assumed to develop a
frictional resistance equal to one sixth of the bearing value of the soil material at
minimum depth as set forth in Table No. 29-B but not to exceed 500 pounds per
square foot unless a greater value is allowed by the building official after a soil
investigation as specified in Section 2905 is submitted. Frictional resistance and
bearing resistance shall not be assumed to act simultaneously unless recommended
after a foundation investigation as specified in Section 2905.
518
(j) Use of Higher Allowable Pile Stresses. Allowable compressive stresses
greater than those specified in Section 2909 shall be permitted when substantiat-
ing data justifying such higher stresses are submitted to and approved by the
building official. Such substantiating data shall include a foundation investigation
including a report in accordance with Section 2908 (a) by a soil engineer defined
as a civil engineer experienced and knowledgeable in the practice of soil
engineering.
Specific Pile Requirements
Sec. 2909. (a) Round Wood Piles. I. Material. Except where untreated
piles are permitted, wood piles shall be pressure treated in accordance with
U.B.C. Standard No. 25-12. Untreated piles may be used only when it has been
established that the cutoff will be below lowest groundwater level assumed to exist
during the life of the structure. Every wood pile shall conform to U .B.C. Standard
I
No. 25-14.
2. Allowable stresses. The allowable unit stresses for round wood piles shall
not exceed those set forth in Table No. 25-E.
The allowable values listed in Table No. 25-E for compression parallel to the
grain at extreme fiber in bending are based on load sharing as occurs in a pile
cluster. For piles which support their own specific load, a safety factor of 1.25
shall be applied to compression parallel to the grain values and 1.30 to extreme
fiber in bending values.
(b) Uncased Cast-in-place Concrete Piles. 1. Material. Concrete piles
cast-in-place against earth in drilled or bored holes shall be made in such a manner
as to ensure the exclusion of any foreign matter and to secure a full-sized shaft.
The length of such pile shall be limited to not more than 30 times the average
diameter. Concrete shall have an ultimate compressive strengthf'c of not less than
2500 pounds per square inch.
2. Allowable stresses. The allowable compressive stress in the concrete shall
not exceed 0.33f'c. The allowable compressive stress of reinforcement shall not
exceed 34 percent of the yield strength of the steel nor 25,500 psi.
(c) Metal-cased Concrete Piles. I. Material. All concrete used in metal-
cased concrete piles shall have an ultimate compressive strengthf'c of not less
than 2500 pounds per square inch.
2. Installation. Every metal casing for a concrete pile shall have a sealed tip
with a diameter of not less than 8 inches.
Concrete piles cast in place in metal shells shall have shells driven for their full
length in contact with the surrounding soil and left permanently in place. The
shells shall be sufficiently strong to resist collapse and sufficiently watertight to
exclude water and foreign material during the placing of concrete.
Piles shall be driven in such order and with such spacing as to ensure against
distortion of or injury to piles already in place. No pile shall be driven within four
and one-half average pile diameters of a pile filled with concrete less than 24
hours old unless approved by the building official.
3. Allowable stresses. Allowable stresses shall not exceed the values specified
519
2909 UNIFORM BUILDING CODE
in Section 2909 (b) 2, except that the allowable concrete stress may be increased
to a maximum value of 0.40/' c for that portion of the pile meeting the following
conditions:
1. The thickness of the metal casing is not less than No. 14 gauge.
2. The casing is seamless or is provided with seams of equal strength and is of
a configuration which will provide confinement to the cast-in-place
concrete.
3. The design/' c shall not exceed 5000 pounds per square inch and the ratio of
metal yield strength shall be not less than 6.
4. The pile diameter is not greater than 16 inches.
(d) Precast Concrete Piles. 1. Material. Precast concrete piles prior to driv-
ing and at 28 days after pouring shall develop an ultimate compressive strengthf 'c
of at least 3000 pounds per square inch.
2. Reinforcement ties. The longitudinal reinforcement in driven precast con-
crete piles shall be laterally tied with steel ties or wire spirals. Ties and spirals
shall be spaced not more than 3 inches apart, center to center, for a distance of 2
feet from the ends and not more than 8 inches elsewhere. The gauge of ties and
spirals shall be as follows:
For piles having a diameter of 16 inches or less, wire shall be not smaller than
No.5 gauge.
For piles having a diameter of more than 16 inches and less than 20 inches, wire
shall be not smaller than No.4 gauge.
For piles having a diameter of 20 inches and larger, wire shall be not smaller
than Y4 inch round or No. 3 gauge.
3. Allowable stresses. Precast concrete piling shall be designed to resist
stresses induced by handling and driving as well as by loads. The allowable
stresses shall not exceed the values specified in Section 2909 (b) 2.
(e) Precast Prestressed Concrete Piles (Pretensioned). 1. Material. Pre-
cast prestressed concrete piles shall develop a compressive strength of not less
than 4000 pounds per square inch before driving and an ultimate compressive
strengthf'c at 28 days after pouring of not less than 5000 pounds per square inch.
2. Reinforcement. The longitudinal reinforcement shall be high-tensile
seven-wire strand conforming to U.B.C. Standard No. 26-7. Longitudinal rein-
forcement shall be laterally tied with steel ties or wire spirals.
Ties or spiral reinforcement shall be spaced not more than 3 inches apart center
to center for a distance of 2 feet from the ends and not more than 8 inches
elsewhere.
At each end of the pile, the first five ties or spirals shall be spaced l inch center
to center.
For piles having a diameter of 24 inches or less, wire shall be not smaller than
No. 5 gauge. For piles having a diameter greater than 24 inches but less than 36
inches, wire shall be not smaller than No. 4 gauge. For piles having a diameter
greater than 36 inches, wire shall be not smaller than Y4 inch round or No. 3
gauge.
520
1982 EDITION 2909
WHERE:
fpc is the effective prestress stress on the gross section.
Effective prestress shall be based on an assumed loss of 30,000 pounds per
square inch in the prestressing steel. The allowable stress in the prestressing steel
shall not exceed the values specified in Section 2618.
(f) Structural Steel Piles. l. Material. Structural steel piles, steel pipe piles
and fully welded steel piles fabricated from plates shall conform to U .B.C.
Standard No. 27-1 and be identified in accordance with Section 2701 (b).
2. Allowable stresses. The allowable stresses shall not exceed 0.35 of the
minimum specified yield strength F Y , provided such yield strength shall not be
assumed greater than 36,000 pounds per square inch for computational purposes.
EXCEPTION: When justified in accordance with Section 2908 (j), the allow-
able stresses may be increased to 0. 50 FY
Combined stresses shall not exceed those in Chapter 27.
3. Minimum dimensions. Sections of driven H-piles shall comply with the
following:
A. The flange projection shall not exceed 14 times the minimum thickness of
metal in either the flange or the web, and the flange widths shall be not less
than 80 percent of the depth of the section.
B. The nominal depth in the direction of the web shall be not less than 8,
inches.
C. Flanges and webs shall have a minimum nominal thickness of 3fs inch.
Sections of driven pipe piles shall have an outside diameter of not less than 10
inches and a minimum thickness of not less than Y4 inch.
(g) Concrete-filled Steel Pipe Piles. l. Material. Steel pipe piles shall
conform to U .B.C. Standard No. 27-l and shall be identified in accordance with
Section 2701 (b). The concrete-filled steel pipe piles shall have an ultimate
compressive strength f' c of not less than 2500 pounds per square inch.
2. Allowable stresses. The allowable stresses shall not exceed 0.35 of the
minimum specified yield strength FY on the steel plus 0.33 of the ultimate
compressive strength/' c of the concrete, provided FY shall not be assumed greater
than 36,000 pounds per square inch for computational purposes.
521
2909, 29-A, 29-B UNIFORM BUILDING CODE
EXCEPTION: When justified in accordance with Section 2908 UJ, the allow-
able stresses may be increased to 0.50 Fy.
Combined stresses shall not exceed those in Chapter 27.
3. Minimum dimensions. Driven piles of uniform section shall have a nomi-
nal outside diameter of not less than 8 inches.
I
NUMBER OF THICKNESS OF DEPTH BELOW
FLOORS FOUNDATION WALL WIDTH OF THICKNESS UNDISTURBED
SUPPORTED (Inches) FOOTING OF FOOTING GROUND
BY THE UNIT (Inches) (Inches) SURFACE
FOUNDATION3 CONCRETE MASONRY (Inches)
I 6 6 12 6 12
2 8 8 15 7 18
3 10 10 18 8 24
1Where unusual conditions or frost conditions are found, footings and foundations shall be
as required in Section 2907 (a).
2The ground under the floor may be excavated to the elevation of the top of the footing.
I 3Foundations may support a roof in addition to the stipulated number of floors. Foundations
supporting roofs only shall be as required for supporting one floor.
522
1982 EDITION 29-B, 29-C, 29-D
inches and a minimum depth of 12 inches into natural grade. Except as in Footnote 7
below, increase of 20 percent allowed for each additional foot of width and/or depth to a
maximum value of three times the designated value.
4 May be increased the amount of the designated value for each additional foot of depth to a
maximum of 15 times the designated value. Isolated poles for uses such as flagpoles or
signs and poles used to support buildings which are not adversely affected by a \12-inch
motion at ground surface due to short-term lateral loads may be designed using lateral
bearing values equal to two times the tabulated values.
5 Coefficient to be multiplied by the dead load.
6 Lateral sliding resistance value to be multiplied by the contact area. In no case shall the
lateral sliding resistance exceed one half the dead load.
7 No increase for width is allowed.
0-1 0.4
12 0.3
2-3 0.2
3-4 0.1
Below 4 0
1The weighted expansion index for nonuniform soils is determined by multiplying the
expansion index for each depth interval by the weight factor for that interval and summing
the products.
2Depth in feet below the ground surface.
523
3001-3004 UNIFORM BUILDING CODE
Chapter 30
VENEER
Scope
Sec. 3001. (a) General. All veneer and its application shall conform to the
requirements of this code. Wainscots not exceeding 4 feet in height measured
above the adjacent ground elevation for exterior veneer or the finish floor eleva-
tion for interior veneer may be exempted from the provisions of this chapter if
approved by the building official.
(b) Limitations. Exterior veneer shall not be attached to wood frame con-
struction at a point more than 25 feet in height above the adjacent ground elevation
except when approved by the building official considering special construction
designed to provide for differential movement.
Definitions
Sec. 3002. For the purpose of this chapter, certain terms are defined as
follows:
BACKING as used in this chapter is the surface or assembly to which veneer is
attached.
VENEER is nonstructural facing of brick, concrete, stone, tile, metal, plastic
or other similar approved material attached to a backing for the purpose of
ornamentation, protection or insulation.
Adhered Veneer is veneer secured and supported through adhesion to an
approved bonding material applied over an approved backing.
Anchored Veneer is veneer secured to and supported by approved mechanical
fasteners attached to an approved backing.
Exterior Veneer is veneer applied to weather-exposed surfaces as defined in
Section 424.
Interior Veneer is veneer applied to surfaces other than weather-exposed
surfaces as defined in Section 424.
Materials
Sec. 3003. Materials used in the application of veneer shall conform to the
applicable requirements for such materials as set forth elsewhere in this code.
For masonry units and mortar, see Chapter 24.
For precast concrete units, see Chapter 26.
For portland cement plaster, see Chapter 4 7.
Anchors, supports and ties shall be noncombustible and corrosion resistant.
Design
Sec. 3004. (a) General. The design of all veneer shall comply with the
requirements of Chapter 23 and this section.
Veneer shall support no load other than its own weight and the vertical dead
load of veneer above.
Surfaces to which veneer is attached shall be designed to support the additional
vertical and lateral loads imposed by the veneer.
524
1982 EDITION 3004-3005
(d) Application. In lieu of the design required by Sections 3004 (a) and (b)
adhered veneer may be applied by one of the following application methods:
I . A paste of neat portland cement shall be brushed on the backing and the back
of the veneer unit. Type S mortar then shall be applied to the backing and the
veneer unit. Sufficient mortar shall be used to create a slight excess to be forced
out the edges of the units. The units shall be tapped into place so as to completely
fill the space between the units and the backing. The resulting thickness of mortar
in back of the units shall be not less than 1/2 inch nor more than I \14 inch.
2. Units of tile, masonry, stone or terra cotta, not over I inch in thickness shall
be restricted to 81 square inches in area unless the back side of each unit is ground
or box screeded to true up any deviations from plane. These units and glass
mosaic units of tile not over 2 inches by 2 inches by 3f8 inch in size may be adhered
by means of portland cement. Backing may be of masonry, concrete or portland
cement plaster on metal lath. Metal lath shall be fastened to the supports in
accordance with the requirements of Chapter 47. Mortar as described in Table No.
30-A shall be applied to the backing as a setting bed. The setting bed shall be a
minimum of % inch thick and a maximum of % inch thick. A paste of neat
portland cement or half portland cement and half graded sand shall be applied to
the back of the exterior veneer units and to the setting bed and the veneer pressed
and tapped into place to provide complete coverage between the mortar bed and
veneer unit. A portland cement grout shall be used to point the veneer.
(e) Plastic Veneer. When used within a building, plastic veneer shall comply
with the interior finish requirements of Chapter 42.
525
3005-3006 UNIFORM BUILDING CODE
Anchored Veneer
Sec. 3006. (a) Permitted Backing. Backing may be of any material permit-
ted by this code. Exterior veneer including its backing shall provide a
weatherproof covering.
(b) Height and Support Limitations. Anchored veneer shall be supported on
footings, foundations or other noncombustible support except as provided under
Section 2515.
Where anchored veneer is applied more than 25 feet above the adjacent ground
elevation, it shall be supported by noncombustible, corrosion-resistant, structural
framing having horizontal supports spaced not over 12 feet vertically above the
25-foot height.
Noncombustible, noncorrosive lintels and noncombustible supports shall be
provided over all openings where the veneer unit is not self-spanning. The
deflections of all structural lintels and horizontal supports required by this
subsection shall not exceed Ysoo of the span under full load of the veneer.
(c) Area Limitations. The area and length of anchored veneer walls shall be
unlimited, except as required to control expansion and contraction and by
Section 300 l (b).
(d) Application. In lieu of the design required by Sections 3004 (a) and (c),
anchored veneer may be applied in accordance with the following:
I. Masonry and stone units (5 inches maximum in thickness). Masonry and
stone veneer not exceeding 5 inches in thickness may be anchored directly to
structural masonry, concrete or studs in one of the following manners:
(i) Anchor ties shall be corrosion resistant, and if made of sheet metal, shall
have a minimum size of No. 22 gauge by I inch or, if of wire, shall be a minimum
of No.9 gauge. Anchor ties shall be spaced so as to support not more than 2 square
feet of wall area but not more than 24 inches on center horizontally. In Seismic
Zones No. 3 and No. 4 anchor ties shall be provided to horizontal joint reinforce-
ment wire of No. 9 gauge or equivalent. The joint reinforcement shall be
continuous with butt splices between ties permitted.
When applied over stud construction, the studs shall be spaced a maximum of
16 inches on centers and approved paper shall first be applied over the sheathing
or wires between studs except as otherwise provided in Section 1707, and mortar
shall be slushed into the l-inch space between facing and paper.
526
1982 EDITION 3006
527
3006, 30-A UNIFORM BUILDING CODE
528
1982 EDITION 3201-3202
Chapter 31
NO REQUIREMENTS
Chapter 32
ROOF CONSTRUCTION AND COVERING
General
Sec. 3201. Roofs shall be as specified in this code and as otherwise required by
this chapter.
Roof Construction and Materials
Sec. 3202. (a) Roof Construction and Materials. Roof coverings shall be
securely fastened to the supporting roof construction and shall provide weather
protection for the building at the roof.
Spaced sheathing for wood roofs shall be spaced not to exceed 6 inches clear
nor more than the nominal width of the sheathing board. Sheathing boards shall be
not less than I inch by 4 inches nominal dimensions.
Plywood roof sheathing, unless of exterior type, shall have no surface or edge
exposed to the weather.
Diagonal and sway bracing shall be used to brace all roof trusses.
(b) Fire Retardancy, When Required. Roof coverings shall be fire retardant I
except in 1)'pes III, IV and V buildings, where it may be as follows:
I . Ordinary roof coverings may be used on buildings of Group R, Division 3 or
Group M Occupancies.
2. Ordinary roof coverings may be used on buildings of Group R, Division I
Occupancies which are not more than two stories in height and have not more than
3000 square feet of projected roof area and there is a minimum of I 0 feet from the
extremity of the roof to the property line on all sides except for street fronts.
(c) Quality of Materials. The quality and design of roofing materials and their
fastenings shall conform to the applicable standards listed in Chapter 60.
Roof Coverings
Sec. 3203. (a) General. Roof coverings shall be as specified in this section.
(b) Definitions. For purposes of this chapter certain terms are designated as
follows:
BASE SHEET is one layer of felt or combination sheet secured to the deck
over which may be applied additional felts, a cap sheet, organic or inorganic fiber
shingles, smooth coating or mineral aggregate.
BUILT-UP ROOF COVERING is two or more layers of roofing consisting of
a base sheet, felts and cap sheet, mineral aggregate, smooth coating or similar
surfacing material.
CAP SHEET is roofing made of organic or inorganic fibers, saturated and
coated on both sides with a bituminous compound, surfaced with mineral gran-
ules, mica, talc, ilmenite, inorganic fibers or similar materials.
CEMENTING is solidly mopped application of asphalt, cold liquid asphalt
compound, coal tar pitch or other approved cementing material.
COMBINATION SHEET is a glass fiber felt integrally attached to kraft
paper.
CORROSION-RESISTANT is any nonferrous metal or any metal having an
unbroken surfacing of nonferrous metal, or steel with not less than 10 percent
chromium or with not less than 0.20 percent copper.
FELT is matted organic or inorganic fibers, saturated with bituminous
compound.
FELT, NONBITUMINOUS SATURATED, is matted asbestos fibers with
I binder for use with wood shingle and wood shake assemblies as specified in
Section 3203 (g).
GLASS FIBER FELT is a glass fiber sheet coated on both sides with
bituminous compound.
INTERLAYMENT is a layer of felt or non bituminous saturated asbestos felt
not less than 18 inches wide, shingled between each course of roof covering.
INTERWCKING ROOFING TILES are individual units, typically of clay
or concrete, possessing matching ribbed or interlocking vertical side joints that
restrict lateral movement and water penetration.
METAL ROOFING is metal shingles or sheets for application on solid roof
surfaces, and corrugated or otherwise shaped metal sheets or sections for applica-
tion on solid roof surfaces or roof frameworks.
NON-NAILABLE DECK is any deck which is incapable of retaining an
approved fastener.
PREPARED ROOFING is any manufactured or processed roofing material,
other than untreated wood shingles and shakes, as distinguished from built-up
coverings.
ROOFING SQUARE is 100 square feet ofroofing surface.
530
1982 EDITION 3203
531
3203 UNIFORM BUILDING CODE
4. Fasteners. Fasteners shall be as set forth herein or in Table No. 32-B and
shall be long enough to penetrate into the sheathing % inch or through the
thickness of the sheathing, whichever is less.
Built-up roofing nails for wood board deck shall be No. 12 gauge, 7/16-inch
head, driven through tin caps or approved nails with integral caps. For plywood,
use No. II gauge ring shank nails driven through tin caps or approved nails with
integral caps. For gypsum decks, insulating concrete, cementitious wood fiber
and others, fasteners recommended by the deck manufacturer shall be used.
All fasteners except those used in built-up roofing installed on poured gypsum
or insulating concrete roof decks shall be corrosion resistant complying with the
requirements ofU .B.C. Standard No. 25-17, Section 25.1716 (e), 25.1716 (h) or
25.1717 (a).
5. Wire. Attaching wire for slate shingle and clay or concrete tile shall be not
smaller than No. 14 gauge and shall comply with U.B.C. Standards Nos. 32-6
and 32-13.
(d) Application. I. General. Application of roof-covering materials listed in
Table No. 32-B shall be in accordance with the provisions thereof.
2. Built-up roofs. Built-up roofing shall be applied on clean and dry decks in
accordance with the manufacturer's instructions and this code. Wood nailers shall
be installed at the perimeter of all non-nailable decks and at the top of all curbs.
Adequate attachment shall be provided on all vertical surfaces. Reglets shall be
provided in walls or parapets receiving metal counterflashing. Insulated decks
shall have wood insulation stops at all edges of the deck. Suitable cant strips shall
be used at all vertical intersections.
The base sheet shall be cemented or spot mopped to non-nailable decks as
required by the type of deck material, using not less than 20 pounds per square of
asphalt for solid mopping ( 10 pounds per square for spot mopping), or not less
than I Yz gallons of cold bituminous compound in accordance with manufacturer's
published specifications, or 30 pounds per square of coal tar pitch.
Over approved nailable decks, the base sheet shall be nailed using not less than
one fastener per each 11/3 square foot.
Successive layers shall be cemented using no less cementing material than that
specified for a solidly cemented base sheet.
Mineral aggregate surfaced roofs shall be surfaced with not less than 60 pounds
of asphalt or 70 pounds of pitch in which is embedded not less than 400 pounds of
gravel or other approved surfacing materials or 300 pounds of crushed slag per
roofing square. See Section 3203 (f) 3 for minimum amounts of mineral aggre-
gate and asphalt or pitch on ordinary roofs. (See U.B.C. Standard No. 32-5 for
mineral roofing aggregate weighing less than 60 pounds per cubic foot.)
Cap sheets shall be cemented to the base sheet or felts using no less cementing
material than that specified for solidly cemented base sheets.
Asphalt for use as hot cement and mopping coat for built-up roof covering shall
comply with U.B.C. Standard No. 32-2.
Asphalt shall be applied at a temperature not less than 375F. nor more than
475F. for high-melt types. Low-melt types shall not be applied at a temperature
532
3203
Tile roofs shall have an underlayment of not Jess than two layers of Type 15 felt
or one layer of '!Ype 30 felt.
G. Wood shingles. Shingles may be applied to roofs with solid or spaced
sheathing.
Shingles shall be laid with a side lap of not Jess than 1Yz inches between joints in
adjacent courses, and not in direct alignment in alternate courses. Spacing
between shingles shall be not less than Y4 inch nor more than 3fs inch. Each shingle
shall be fastened with two nails only, positioned approximately% inch from each
edge and approximately I inch above the exposure line. Starter course at the eaves
shall be doubled.
Weather exposures shall not exceed those set forth in Table No. 32-A. Hip and
ridge weather exposures shall not exceed those permitted for the field of the roof.
H. Wood shakes. Shakes may be applied to roofs with solid or spaced
sheathing. In wind-driven-snow areas sheathing shall be solid and the shakes shall
be applied over an underlayment of not less than Type 15 felt.
Shakes shall be laid with a side lap of not Jess than 1Yz inches between joints in
adjacent courses. Spacing between shakes shall be not less than 3fs inch nor more
than 5fs inch.
Shakes shall be fastened to the sheathing with two nails only, positioned
approximately 1 inch from each edge and approximately 2 inches above the
exposure line. The starter course at the eaves shall be doubled. The bottom or first
layer may be either shakes or shingles.
Fifteen-inch or 18-inch shakes may be used for the final course at the ridge.
Shakes shall be laid with not Jess than 18-inch-wide strips of not Jess than '!Ype
30 felt shingled between each course in such a manner that no felt is exposed to the
weather below the shake butts.
Weather exposures shall not exceed those set forth in Table No. 32-A. Hip and
ridge weather exposures shall not exceed those permitted for the field of the roof.
4. Other roof coverings. A. Asbestos-cement. Corrugated asbestos-cement
roofing shall be applied in an approved manner.
B. Metal roofing. Flat sheets shall be applied only to solidly sheathed roofs.
Metal roofing shall be applied in an approved manner.
C. Sheet roofing. Sheet roofing shall comply with the provisions of U.B.C.
Standard No. 32-3.
5. Flashing. Roof valley flashings shall be provided for shingles as follows:
A. Asphalt shingles. The roof valley flashing shall be the same as required for
wood shingles or shall be of laced asphalt shingles applied in an approved manner
with an underlayment of not Jess than Type 15 felt extending 18 inches from the
center line each way, or shall be of two layers of 90-pound mineral surfaced cap
sheet cemented together with the bottom layer not Jess than 12 inches wide laid
face down and the top layer not Jess than 24 inches wide laid face up.
B. Metal shingles. The roof valley flashing shall be provided of not Jess than
No. 28 galvanized sheet gauge corrosion-resistant metal applied over an under-
Iayment of not less than Type 15 felt. The metal shall extend at least 8 inches from
the center line each way and shall have a splash diverter rib not less than % inch
534
1982 EDITION 3203
high at the flow line formed as part of the flashing. Sections of flashing shall have
an end lap of not less than 4 inches.
C. Asbestos-cement shingles, slate shingles, and clay and concrete tile.
The roof valley flashing shall be provided of not less than No. 28 galvanized sheet
gauge corrosion-resistant metal applied over an underlayment of not less than
lYpe 15 felt. The metal shall extend at least II inches from the center line each
way and shall have a splash diverter rib not less than I inch high at the flow line
formed as part of the flashing. Sections of flashing shall have an end lap of not less
than 4 inches.
D. Wood shingles and wood shakes. The roof valley flashing shall be pro-
vided of not less than No. 28 galvanized sheet gauge corrosion-resistant metal
applied over an underlayment of not less than lYpe 15 felt. The metal shall extend
at least 8 inches from the center line each way for wood shingles and II inches
from the center line each way for wood shakes. Sections of flashing shall have an
overlap of not less than 4 inches.
(e) Fire-retardant Roof Coverings. A fire-retardant roof covering shall be
any one of the following roofings:
I. Any Class A orB built-up roofing assembly.
2. Any mineral aggregate surfaced built-up roof for application to roofs
having a slope not more than 3 inches to 12 inches applied as specified in
Section 3203 (d) I consisting of not less than the following:
Roof Deck
Solid surface on noncombustible materials or minimum of 1/z-inch
plywood or l-inch nominal boards or other material approved by the
building official.
Base Sheet and Plies
Four layers oflYpe 15 perforated organic fiber felt, or
Three layers oflYpe 15 organic or inorganic fiber felt, and
Surfacing Material
400 pounds per roofing square of gravel, crushed rock, ceramic or
approved similar surfacing material, or
300 pounds per roofing square of crushed slag.
(See U.B.C. Standard No. 32-5 for mineral roofing aggregate weighing
less than 60 pounds per cubic foot.)
3. Any built-up roof for application to roofs having a slope not less than 1/2
inch to 12 inches applied as specified in Section 3203 (d) I, consisting of
not less than the following:
Roof Deck
Solid surface on noncombustible materials or mm1mum of Vz-inch
plywood or l-inch nominal boards or other material approved by the
building official.
Base Sheet and Plies
Two layers of'fYpe 15 organic fiber felt, or
One layer of 14-pound glass fiber felt base sheet, or combination sheet, or
535
3203 UNIFORM BUILDING CODE
536
1982 EDITION 3203-3204
addition, the deck shall be constructed of %-inch plywood with exterior glue or l-
inch nominal T and G boards, overlaid with a layer of approved asbestos felt
lapped 2 inches on the horizontal and vertical joints. An 18-inch-wide strip of the
same asbestos felt shall be shingled in between each course of shakes in such
manner that no felt is exposed to the weather below the shake butts. As an
alternate, an underlayment of Y2-inch Type X gypsum board shall be placed under
the solid or spaced sheathing.
2. Wood shingles. Special purpose wood shingle roofing shall conform to
grading and application requirements of this chapter. In addition, the deck,
whether of spaced boards or solid, shall be overlaid with a layer of approved
asbestos felt lapped 2 inches on the horizontal and vertical joints or an underlay-
ment of Y2-inch Type X gypsum board shall be placed under the solid or spaced
sheathing.
3. Asbestos felt. Approved asbestos felt for special purpose roofing shall
weigh not less than 12 pounds per 100 square feet, be not less than .022 inch in
thickness, nonbituminous saturated, containing a fire- and water-retardant binder,
and be reinforced with glass fibers running lengthwise of the sheet not more than
Y4 inch apart.
(h) Slope of Roof. Roof covering materials shall be installed as set forth in
Table No. 32-B except as follows:
EXCEPTIONS: I. In addition to the application requirements of Table No. 32-
B, built-up roofing on slopes greater than I inch in 12 inches for gravel surface or 2
inches in 12 inches for smooth or cap sheet surface shall be blind nailed through tin
caps into the deck, wood nailers or wood insulation stops at not more than 18 inches
on center to secure all underlying plies.
Built-up roofing on slopes exceeding 3 inches in 12 inches shall be installed with
plies laid parallel to the slope of the deck, and the surfacing material shall be other
than gravel or slag.
2. Asphalt shingles laid with double coverage may be installed on slopes as low as
2 inches in 12 inches, provided the shingles are approved self-sealing or are hand-
sealed and are installed with an underlayment consisting of two layers of Type 15 felt
applied shingle fashion.
3. Asbestos cement shingles may be installed on slopes as low as 3 inches in 12
inches where the underlayment consists of two layers of Type 15 asbestos felt
applied shingle fashion.
4. Wood shakes may be installed on a slope not less than 3 inches in 12 inches
when installed over an underlayment of not less than Type 15 felt and when approved
by the building official.
5. Interlocking roof tiles may be installed on slopes below 3 inches in 12 inches
where underlayment consists of two layers of Type 15 felt or heavier applied shingle
fashion and solid-mopped together with approved cementing material between the
plies.
Roof Insulation
Sec. 3204. The use of combustible roof insulation shall be permitted, provided
it is covered with approved roof covering applied directly thereto. For foam
plastic, see Section 1712.
Insulation shall be of a rigid type suitable for application of a roof covering.
537
3204-3206 UNIFORM BUILDING CODE
I (b) Draft Stops. Attics, mansards, overhangs and other concealed roof spaces
formed of combustible construction shall be draft stopped as specified in Section
2516 (f).
(c) Ventilation. Where determined necessary by the building official due to
atmospheric or climatic conditions, enclosed attics and enclosed rafter spaces
formed where ceilings are applied direct to the underside of roof rafters shall have
cross ventilation for each separate space by ventilating openings protected against
the entrance of rain and snow. The net free ventilating area shall be not less than
Y15o of the area of the space ventilated, except that the area may be YJoo, provided
at least 50 percent of the required ventilating area is provided by ventilators
located in the upper portion of the space to be ventilated at least 3 feet above eave
or cornice vents with the balance of the required ventilation provided by eave or
..
I cornice vents. The openings shall be covered with corrosion-resistant metal mesh
with mesh openings of 1/4 inch in dimension .
538
1982 EDITION 3206-3207
(c) Types of Vents. Vents shall be fixed in the open position or shall open
automatically in the event of fire and may consist of skylights, exterior wall
windows or other openings leading directly to the exterior of the building. Vents
shall be at or near the highest elevation of the ceiling and in no case lower than the
upper one third of the smoke curtain. Where plain glass is used, provision shall be
made to protect the occupants from glass breakage. In no case shall vents be
located closer than 20 feet to an adjoining property line.
(d) Releasing Devices. Releasing devices for automatically opening vents
shall be activated by temperature. The temperature-releasing device shall be
operated normally at a maximum temperature of 165F.; special circumstances
warranting higher releasing temperatures may be approved by the building offi-
cial. Noncorrodible materials shall be used for hinges, latches and related details
to prevent sticking and consequent failure to open.
(e) Size and Spacing of Vents. I. Effective venting area. The effective
venting area is the minimum cross-sectional area through which the hot gases
must pass en route to atmosphere. The effective venting area shall be not less than
16 square feet with no dimension less than 2 feet.
2. Spacing. The maximum center-to-center spacing between vents within the
building shall be:
A. In Group 8 Occupancies: 120 feet.
B. In Group H Occupancies: 100 feet.
3. Venting ratios. The following ratios of effective area of vent openings to
floor areas shall be:
A. In Group 8 Occupancies: 1: I 00.
8. In Group H Occupancies: 1:50.
(f) Curtain Boards. I. General. Curtain boards shall be provided to subdivide
a vented building in accordance with the provisions of this subsection.
2. Construction. Curtain boards shall be sheet metal, asbestos board, lath and
plaster, gypsum wallboard or other approved materials which provide equivalent
performance.
3. Location and depth. Curtain boards shall extend down from the ceiling for
a minimum depth of 6 feet but need not extend closer than 8 feet to the floor. In
Group H Occupancies, the minimum depth shall be 12 feet except that it need not
be closer than 8 feet to the floor, provided the curtain is not less than 6 feet in
depth.
4. Spacing. The distance between curtain boards shall not exceed 250 feet and
the curtained area shall be limited to 50,000 square feet. In Group H Occupan-
cies, the distance between curtain boards shall not exceed 100 feet and the
curtained area shall be limited to 15,000 square feet.
Roof Drainage
Sec. 3207. (a) General. Roof systems not designed to support accumulated
water shall be sloped for drainage. See Section 2305 (f).
(b) Roof Drains. Unless roofs are sloped to drain over roof edges or are
539
3207-3208, 32-A UNIFORM BUILDING CODE
designed to support accumulated water, roof drains shall be installed at each low
point of the roof.
Roof drains shall be adequate in size to convey the water tributary to the roof
drains.
(c) Overflow Drains and Scuppers. Where roof drains are required, over-
flow drains having the same size as the roof drains shall be installed with the inlet
flow line located 2 inches above the low point of the roof, or overflow scuppers
havmg three times the size of the roof drains may be installed in adjacent parapet
walls with the inlet flow line located 2 inches above the low point of the adjacent
roof and having a minimum opening height of 4 inches.
Overflow drains shall be connected to drain lines independent from the roof
drains.
(d) Concealed Piping. Roof drains and overflow drains, when concealed
within the construction of the building, shall be installed in accordance with the
Plumbing Code.
(e) Over Public Property. Roof drainage water from a building shall not be
permitted to flow over public property.
EXCEPTION: Groups R, Division 3, and M Occupancies.
Flashing
Sec. 3208. At the juncture of the roof and vertical surfaces, flashing and
counterflashing shall be provided as required in Section 1707 (b).
For roof valley flashing see Section 3203 (d).
540
.....
iN
m
0
3
TABLE NO. 32B-ROOF COVERING APPLICATION 1 0
z
BUILT-UP ROOFING (SeeSecllon3203(d}2)
ROOF SLOPE
3
Non-nailable deck cement per 3203 (d) 2 or nailable deck nail with at
I. Base Sheet 0:12 I: 12 least one approved fastener for each I Y, square foot, Section 3203 (c)
4
2. Felts 0:12 I: 12 3 Cement each sheet with 20 lbs. per sq. asphalt or 30 lbs. per sq.
pitch, Section 3203 (d) 2
3
3. Glass Fiber Felts 0:12 I: 12 Cement each sheet with 25 lbs. per sq. asphalt, Section 3202 (d) 2
3 Cement with 20 lbs. per sq. asphalt, Section 3203 (d) 2
4. Cap Sheets /::12
1
2:12
2 Embed in 60 lbs. per sq. of asphalt or 70 lbs. per sq. of pitch 2
5. Gravel-4001bs.pcr,q. 0:12 3:12
2
6. Slag-300 lbs. per sq. 0:12 3:12 Embed in 60 lbs. per sq. of asphalt or 70 lbs. per sq. of pitch 2
(Continued)
TABLE NO. 328-ROOF COVERING APPLICATION 1-(Conlinued)
NAILS
MINIMUM Minimum Minimum
ROOF MATERIAL SLOPE UNDERLAYMENT 3 NUMBER OF FASTENERS STAPLES Gauge Head
7. Asphalt Shingles 4:12 3 One Type 15 felt applied 4 per 36 inch strip .j
12 X
per Section 3203 (d) 3 A 2 per 18 inch '>hingle
8. A'>bestos-Cement Shingles 5:12 1 One Type 15 asbestos felt 4 per shingle-' NP 11
,.;,
applied per Section 3203 (d) 3 A
9. Metal Shingles 3:12 One Type 30 felt applied .j .j
.j .j
Chapter 33
EXITS
NOTE: This chapter has been revised In Its entirety.
General
Sec. 3301. (a) General. Every building or portion thereof shall be provided
with exits as required by this chapter.
(b) Definitions. For the purpose of this chapter, certain terms are defined as
follows:
BALCONY, EXTERIOR EXIT, is a landing or porch projecting from the
wall of a building, and which serves as a required exit. The long side shall be at
least 50 percent open, and the open area above the guardrail shall be so distributed
as to prevent the accumulation of smoke or toxic gases.
CONTINENTAL SEATING is the configuration of fixed seating where the
number of seats per row exceeds 14 and required exits from the seating area are
side exits.
EXIT is a continuous and unobstructed means of egress to a public way and
shall include intervening aisles, doors, doorways, corridors, exterior exit bal-
conies, ramps, stairways, smokeproof enclosures, horizontal exits, exit passage-
ways, exit courts and yards.
EXIT COURT is a yard or court providing access to a public way for one or
more required exits.
EXIT PASSAGEWAY is an enclosed exit connecting a required exit or exit
court with a public way.
HORIZONTAL EXIT is an exit from one building into another building on
approximately the same level, or through or around a wall constructed as required
for a two-hour occupancy separation and which completely divides a floor into
two or more separate areas so as to establish an area of refuge affording safety
from fire or smoke coming from the area from which escape is made.
PANIC HARDWARE is a door-latching assembly incorporating an unlatch-
ing device, the activating portion of which extends across at least one half the
width of the door leaf on which it is installed.
PRIVATE STAIRWAY is a stairway serving one tenant only.
PUBLIC WAY is any street, alley or similar parcel of land essentially unob-
structed from the ground to the sky which is deeded, dedicated or otherwise
permanently appropriated to the public for public use and having a clear width of
not less than 10 feet.
SPIRAL STAIRWAY is a stairway having a closed circular form in its plan
view with uniform section shaped treads attached to and radiating about a
minimum diameter supporting column. The effective tread is delineated by the
nosing radius line, the exterior arc (center line of railing) and the overlap radius
line (nosing radius line of tread above). Effective tread dimensions are taken
along a line perpendicular to the center line of the tread.
543
3301-3302 UNIFORM BUILDING CODE
(c) Exit Obstruction. Obstructions shall not be placed in the required width of
an exit except projections permitted by this chapter.
(d) Changes in Elevation. Within a building, changes in elevation of less than
12 inches along any exit serving an occupant load of I 0 or more shall be by ramps.
EXCEPTION: Group R, Division 3 Occupancies and along aisles adjoining
seating areas.
(e) Building Accessibility. Portions of buildings shall be accessible to the
physically handicapped as required by Table No. 33-A, and at least one primary
entrance to a building which is required to be accessible shall be usable by the
physically handicapped and be on a level that would provide accessibility to the
elevators where provided.
Occupant load
Sec. 3302. (a) Determination of Occupant Load. In determining the occu-
pant load, all portions of a building shall be presumed to be occupied at the same
time.
EXCEPTION: Accessory use areas which ordinarily are used only by persons
who occupy the main areas of an occupancy shall be provided with exits as though
they are completely occupied, but their occupant load need not be included in
computing the total occupant load of the building.
The occupant load for a building shall be determined in accordance with the
following:
I. General. For areas without fixed seats, the occupant load shall be not less
than the number determined by dividing the floor area assigned to that use by the
occupant load factor set forth in Table No. 33-A. Where an intended use is not
listed in Table No. 33-A the building official shall establish an occupant load
factor based on a listed use which most nearly resembles the intended use.
For a building or portion thereof which has more than one use, the occupant
load shall be determined by the use which gives the largest number of persons.
The occupant load for buildings or areas containing two or more occupancies
shall be determined by adding the occupant loads of the various use areas as
computed in accordance with the applicable provisions of this section.
2. Fixed seating. For areas having fixed seat and aisles, the occupant load shall
be determined by the number of fixed seats installed therein. The required width
of aisles serving fixed seats shall not be used for any other purpose.
For areas having fixed benches or pews, the occupant load shall be not less than
the number of seats based on one person for each 18 inches of length of pew or
bench.
Where booths are used in dining areas, the occupant load shall be based on one
person for each 24 inches of booth length or major portion thereof.
3. Reviewing stands, grandstands and bleachers. The occupant load for
reviewing stands, grandstands and bleachers shall be calculated in accordance
with this section and the specific requirements contained in Sections 3323 and
3324.
(b) Maximum Occupant Load. The maximum occupant load for other than an
544
1982 EDITION 3302-3303
assembly use shall not exceed the capacity of exits as determined in accordance
with this chapter.
The maximum occupant load for an assembly use shall not exceed the occupant
load as determined in accordance with Section 3302 (a).
EXCEPTION: The occupant load for an assembly building or portion thereof
may be increased, when approved by the building official, if all the requirements of
this code are met for such increased number of persons. The building official may
require an approved aisle, seating or fixed equipment diagram to substantiate such
an increase, and may require that such diagram be posted.
(c) Posting of Room Capacity. Any room having an occupant load of 50 or
more where fixed seats are not installed, and which is used for classroom,
assembly or similar purpose, shall have the capacity of the room posted in a
conspicuous place on an approved sign near the main exit from the room. Such
signs shall be maintained legible by the owner or his authorized agent and shall
indicate the number of occupants permitted for each room use.
(d) Revised Occupant Load. After a building is occupied, any change in use
or increase in occupant load shall comply with this chapter. See Section 502.
Exits Required
Sec. 3303. (a) Number of Exits. Every building or usable portion thereof shall
have at least one exit, not less than two exits where required by Table No. 33-A
and additional exits as required by this subsection.
For purposes of this section, basements and occupied roofs shall be provided
with exits as required for stories.
Floors complying with the provisions for mezzanines as specified in Section
1716 shall be provided with exits as specified therein.
The second story shall be provided with not less than two exits when the
occupant load is 10 or more.
EXCEPTIONS: I. Except as provided in Table No. 33-A, only one exit need be
provided from the second story within an individual dwelling unit. Refer to Section
1204 for emergency escape or rescue requirements from sleeping rooms.
2. Two or more dwelling units on the second story may have access to only one
common exit when the total occupant load does not exceed I 0.
Occupants on floors above the second story and in basements shall have access
to not less than two separate exits from the floor or basement.
EXCEPTIONS: I. Floors and basements used exclusively for service of the
building may have one exit. For the purposes of this exception, storage rooms,
laundry rooms, maintenance offices and similar uses shall not be considered as
providing service to the building.
2. Basements within an individual dwelling unit having an occupant load of less
than 10 may have one exit.
3. Storage rooms, laundry rooms and maintenance offices not exceeding 300
square feet in floor area may be provided with only one exit.
For special requirements see the following sections: Group A, Sections 3317
and 3318; GroupE, Section 3319; Group H, Section 3320; Group I, Section
3321; Boiler, Furnace and Incinerator Rooms and Cellulose Nitrate Handling
545
3303 UNIFORM BUILDING CODE
546
1982 EDITION 3303-3304
system throughout. These distances may be increased 100 feet when the last 150
feet is within a corridor, complying with Section 3305. See Section 3319 for
GroupE Occupancy and Section 3320 for Group H Occupancy travel distances.
In a one-story Group B, Division 4 Occupancy classified as a factory or
warehouse and in one-story airplane hangars, the exit travel distance may be
increased to 400 feet if the building is equipped with an automatic sprinkler
system throughout and provided with smoke and heat ventilation as specified in
Section 3206.
In an open parking garage, as defined in Section 709, the exit travel distance
may be increased to 250 feet.
(e) Exits Through Adjoining Rooms. Rooms may have one exit through an
adjoining or intervening room which provides a direct, obvious and unobstructed
means of travel to an exit corridor, exit enclosure or until egress is provided from
the building, provided the total distance of travel does not exceed that permitted
by other provisions of this code. In other than dwelling units, exits shall not pass
through kitchens, store rooms, rest rooms, closets or spaces used for similar
purposes.
EXCEPTIONS: I. Rooms within dwelling units may exit through more than one
intervening room.
2. Rooms with a cumulative occupant load of 10 or less may exit through more
than one intervening room.
Foyers, lobbies and reception rooms constructed as required for corridors shall
not be construed as intervening rooms.
Doors
Sec. 3304. (a) General. This section shall apply to every exit door serving an
area having an occupant load of 10 or more, or serving hazardous rooms or areas,
except that Subsections (c), (h) and (i) shall apply to all exit doors regardless of
occupant load. Buildings or structures used for human occupancy shall have at
least one exterior exit door that meets the requirements of Subsection (e).
(b) Swing. Exit doors shall swing in the direction of exit travel when serving
any hazardous area or when serving an area having an occupant load of 50 or
more.
Double-acting doors shall not be used as exits when any of the following
conditions exist:
I. The occupant load served by the door is I 00 or more.
2. The door is part of a fire assembly.
3. The door is part of a smoke- and draft-control assembly.
4. Panic hardware is required or provided on the door.
A double-acting door shall be provided with a view panel of not less than 200
square inches.
(c) Type of Lock or Latch. Exit doors shall be openable from the inside
without the use of a key or any special knowledge or effort.
EXCEPTIONS: I. This requirement shall not apply to exterior exit doors in a
Group B Occupancy if there is a readily visible, durable sign on or adjacent to the
547
3304 UNIFORM BUILDING CODE
548
1982 EDITION 3304-3305
I. Six inches maximum between rails and leading edge of door at the closest
point in its arc of travel.
2. Six inches maximum between rails and the door in open position.
3. Two inches minimum between rail at hinge side and door in open position.
4. Two inches maximum between freestanding rails and jamb or other adjacent
surface.
(h) Floor Level at Doors. Regardless of the occupant load, there shall be a
floor or landing on each side of a door. The floor or landing shall be not more than
1
/2 inch lower than the threshold of the doorway. When doors open over landings,
the landing shall have a length of not less than 5 feet.
EXCEPTIONS: I. When the door opens into a stair of a smokeproof enclosure,
the landing need not have a length of 5 feet.
2. In Group R, Division 3 Occupancies and within individual units of Group R,
Division I Occupancies, a door may open on the top step of a flight of stairs or on an
exterior landing, provided the door does not swing over the top step or exterior
landing and the landing is not more than 7 '12 inches below the floor level.
3. In Group R, Division 3 Occupancies, screen doors and storm doors may swing
over stairs, steps or landings.
4. In Group R, Division 3 Occupancies and private garages and sheds when a door
opens over a landing, the landing shall have a length equal to the width of the door.
(i) Door Identification. Glass doors shall conform to the requirements spec-
ified in Section 5406.
Exit doors shall be so marked that they are readily distinguishable from the
adjacent construction.
(j) Additional Doors. When additional doors are provided for egress purposes,
they shall conform to all provisions of this chapter.
EXCEPTION: Approved revolving doors having leaves which will collapse
under opposing pressures may be used in exit situations, provided:
I. Such doors have a minimum width of 6 feet 6 inches.
2. At least one conforming exit door is located adjacent to each revolving door.
3. The revolving door shall not be considered to provide any exit width.
549
3305 UNIFORM BUILDING CODE
550
1982 EDITION 3305-3306
bear an approved label or other identification showing the rating thereof, the name
of the manufacturer and the identification of the service conducting the inspection
of materials and workmanship at the factory during fabrication and assembly.
Doors shall be maintained self-closing or shall be automatic closing by actuation
of a smoke detector in accordance with Section 4306 (b). Smoke- and draft-
control door assemblies shall be provided with a gasket so installed as to provide a
seal where the door meets the stop on both sides and across the top.
EXCEPTIONS: I. Viewports may be installed if they require a hole not larger
than I inch in diameter through the door, have at least a Y-inch-thick glass disc and
the holder is of metal which will not melt out when subject to temperatures of
1700F.
2. Protection of openings in the interior walls of exterior exit balconies is not
required.
2. Openings other than doors. Interior openings for other than doors or ducts
shall be protected by fixed, approved V-inch-thick wired glass installed in steel
frames. The total area of all openings, other than doors, in any portion of an
interior corridor shall not exceed 25 percent of the area of the corridor wall of the
room which it is separating from the corridor. For duct openings, see Section
4306.
EXCEPTION: Protection of openings in the interior walls of exterior exit
balconies is not required.
(i) Location on Property. Exterior exit balconies shall not be located in an area
where openings are required to be protected due to location on the property.
Stairways
Sec. 3306. (a) General. Every stairway having two or more risers serving any
building or portion thereof shall conform to the requirements of this section.
EXCEPTION: Stairs or ladders used only to attend equipment are exempt from
the requirements of this section.
(b) Width. Stairways serving an occupant load of 50 or more shall be not less
than 44 inches in width. Stairways serving an occupant load of 49 or less shall be
not less than 36 inches in width. Private stairways serving an occupant load ofless
than 10 shall be not less than 30 inches in width.
Handrails may project into the required width a distance of 3Y2 inches from
each side of a stairway. Other nonstructural projections such as trim and similar
decorative features may project into the required width lY2 inches on each side.
(c) Rise and Run. The rise of every step in a stairway shall be not less than 4
inches nor greater than ?Y2 inches. Except as permited in Subsections (d) and (f),
the run shall be not less than 10 inches as measured horizontally between the
vertical planes of the furthermost projection of adjacent treads. Except as permit-
ted in Subsections (d), (e) and (f), the largest tread run within any flight of stairs
shall not exceed the smallest by more than 3fs inch. The greatest riser height within
any flight of stairs shall not exceed the smallest by more than 3fs inch.
EXCEPTIONS: I. Private stairways serving an occupant load of less than 10
and stairways to unoccupied roofs may be constructed with an 8-inch maximum rise
and 9-inch minimum run.
551
3306 UNIFORM BUILDING CODE
2. Where the bottom riser adjoins a sloping public way, walk or driveway having
an established grade and serving as a landing, a variation in height of the bottom riser
of not more than 3 inches in every 3 feet of stairway width is permitted.
(d) Winding Stairways. In Group R, Division 3 Occupancies and in private
stairways in Group R, Division 1 Occupancies, winders may be used if the
required width of run is provided at a point not more than 12 inches from the side
of the stairway where the treads are the narrower, but in no case shall any width of
run be less than 6 inches at any point.
(e) Circular Stairways. Circular stairways may be used as an exit, provided
the minimum width of run is not less than 10 inches and the smaller radius is not
less than twice the width of the stairway. The largest tread width or riser height
within any flight of stairs shall not exceed the smallest by more than 3fs inch.
(f) Spiral Stairways. In Group R, Division 3 Occupancies and in private
stairways within individual units of Group R, Division 1 Occupancies, spiral
stairways may be installed. Such stairways may be used for required exits when
the area served is limited to 400 square feet.
The tread must provide a clear walking area measuring at least 26 inches from
the outer edge of the supporting column to the inner edge of the handrail. A run of
at least ?Y2 inches is to be provided at a point 12 inches from where the tread is the
narrowest. The rise must be sufficient to provide 6-foot 6-inch headroom. The
rise shall not exceed 9Y2 inches.
(g) Landings. Every landing shall have a dimension measured in the direction
of travel equal to the width of the stairway. Such dimension need not exceed 4 feet
when the stair has a straight run. A door swinging over a landing shall not reduce
the width of the landing to less than one half its required width at any position in
its swing nor by more than 7 inches when fully open. See Section 3304 (h).
EXCEPTION: Stairs serving an unoccupied roof are exempt from these
provisions.
(h) Basement Stairways. When a basement stairway and a stairway to an upper
story terminate in the same exit enclosure, an approved barrier shall be provided
to prevent persons from continuing on into the basement. Directional exit signs
shall be provided as specified in Section 3314.
(i) Distance Between Landings. There shall be not more than 12 feet vertically
between landings.
(j) Handrails. Stairways shall have handrails on each side, and every stairway
required to be more than 88 inches in width shall be provided with not less than
one intermediate handrail for each 88 inches of required width. Intermediate
handrails shall be spaced approximately equally across with the entire width of the
stairway.
EXCEPTIONS: I. Stairways 44 inches or less in width and stairways serving
one individual dwelling unit in Group R, Division I or 3 Occupancies may have one
handrail, except that such stairways open on one or both sides shall have handrails
provided on the open side or sides.
2. Private stairways 30 inches or less in height may have handrails on one side
only.
3. Stairways having less than four risers and serving one individual dwelling unit
552
1982 EDITION 3306
553
3306-3308 UNIFORM BUILDING CODE
Ramps
Sec. 3307. (a) General. Ramps used as exits shall conform to the provisions of
this section.
(b) Width. The width of ramps shall be as required for stairways.
(c) Slope. The slope oframps required by Table No. 33-A shall be not steeper
than I vertical to 12 horizontal. The slope of other ramps shall not be steeper than
I vertical to 8 horizontal.
When provided with fixed seating, the main floor of the assembly room of a
Group A, Division I, Division 2, 2.1 or 3 Occupancy may have a slope not steeper
than I vertical to 5 horizontal.
(d) Landings. Ramps having slopes steeper than I vertical to 15 horizontal
shall have landings at the top and bottom, and at least one intermediate landing
shall be provided for each 5 feet of rise. Top landings and intermediate landings
shall have a dimension measured in the direction of ramp run of not less than 5
feet. Landings at the bottom of ramps shall have a dimension in the direction of
ramp run of not less than 6 feet.
Doors in any position shall not reduce the minimum dimension of the landing to
less than 42 inches and shall not reduce the required width by more than 3 Y2
inches when fully open.
(e) Handrails. Ramps having slopes steeper than I vertical to 15 horizontal
shall have handrails as required for stairways, except that intermediate handrails
shall not be required. Ramped aisles need not have handrails on sides serving
fixed seating.
(f) Construction. Ramps shall be constructed as required for stairways.
(g) Surface. The surface of ramps shall be roughened or shall be of slip-
resistant materials.
Horizontal Exit
Sec. 3308. (a) Used as a Required Exit. A horizontal exit may be considered
as a required exit when conforming to the provisions of this chapter. A horizontal
exit shall not serve as the only exit from a portion of a building, and when two or
more exits are required, not more than one half of the total number of exits or total
exit width may be horizontal exits.
(b) Openings. All openings in the two-hour fire-resistive wall which provides a
horizontal exit shall be protected by a fire assembly having a fire-protection rating
of not less than one and one-half hours. Such fire assembly shall be automatic
closing as provided in Section 4306 (b) upon actuation of a smoke detector.
554
1982 EDITION 33083310
(c) Discharge Areas. A horizontal exit shall lead into a floor area having
capacity for an occupant load not less than the occupant load served by such exit.
The capacity shall be determined by allowing 3 square feet of net clear floor area
per ambulatory occupant and 30 square feet per nonambulatory occupant.
Stairway, Ramp and Escalator Enclosures
Sec. 3309. (a) General. Every interior stairway, ramp or escalator shall be
enclosed as specified in this section.
EXCEPTIONS: I. In other than Group I Occupancies, an enclosure will not be
required for a stairway, ramp or escalator serving only one adjacent floor and not
connected with corridors or stairways serving other floors. For enclosure of escala-
tors serving Group B Occupancies, see Chapter 17.
2. Stairs in Group R, Division 3 Occupancies and stairs within individual
apartments in Group R, Division I Occupancies need not be enclosed.
3. Stairs in open parking garages, as defined in Section 709, need not be enclosed.
(b) Enclosure Construction. Enclosure walls shall be of not less than two-
hour fire-resistive construction in buildings more than four stories in height or of
Types I and II fire-resistive construction and shall be of not less than one-hour fire-
resistive construction elsewhere.
(c) Openings into Enclosures. There shall be no openings into exit enclosures
except exit doorways and openings in exterior walls. All exit doors in an exit
enclosure shall be protected by a fire assembly having a fire-protection rating of
not less than one hour where one-hour shaft construction is permitted and one and
one-half hours where two-hour shaft construction is required. Doors shall be
maintained self-closing or shall be automatic closing by actuation of a smoke
detector as provided for in Section 4306 (b). The maximum transmitted tempera-
ture end point shall not exceed 450F. above ambient at the end of 30 minutes of
the fire exposure specified in U .B.C. Standard No. 43-2.
(d) Extent of Enclosure. Stairway and ramp enclosures shall include landings
and parts of floors connecting stairway flights and shall also include a corridor on
the ground floor leading from the stairway to the exterior of the building.
Enclosed corridors or passageways are not required from unenclosed stairways.
Every opening into the corridor shall comply with the requirements of Section
3309 (c).
EXCEPTION: In office buildings classed as a Group B, Division 2 Occupancy,
a maximum of 50 percent of the exits may discharge through a street-floor lobby,
provided the required exit width is free and unobstructed and the entire street floor is
protected with an automatic sprinkler system.
(e) Barrier. A stairway in an exit enclosure shall not continue below the grade
level exit unless an approved barrier is provided at the ground-floor level to
prevent persons from accidentally continuing into the basement.
(f) Use of Space Under Stair. There shall be no enclosed usable space under
stairways in an exit enclosure, nor shall the open space under such stairways be
used for any purpose.
Smokeproof Enclosures
Sec. 3310. (a) General. A smokeproof enclosure shall consist of a vestibule
555
3310 UNIFORM BUILDING CODE
and continuous stairway enclosed from the highest point to the lowest point by
walls of two-hour fire-resistive construction. The supporting frame shall be
protected as set forth in Table No. 17-A.
In buildings with air-conditioning systems or pressure air supply serving more
than one story, an approved smoke detector shall be placed in the return-air duct or
plenum prior to exhausting from the building or being diluted by outside air. Upon
activation, the detector shall cause the return air to exhaust completely from the
building without any recirculation through the building. Such devices may be
installed in each room or space served by a return-air duct.
(b) When Required. In a building having a floor used for human occupancy
which is located more than 75 feet above the lowest level of fire department
vehicle access, all of the required exits shall be smokeproof enclosures.
EXCEPTION: Smokeproof enclosures may be omitted, provided all enclosed
exit stairways are equipped with a barometric dampered relief opening at the top and
the stairway is supplied mechanically with sufficient air to discharge a minimum of
2500 cubic feet per minute through the relief opening while maintaining a minimum
positive pressure of 0.25-inch water column in the shaft relative to atmospheric
pressure with all doors closed. Activation of the mechanical equipment shall be in
accordance with Section 3310 (g) 6.
(c) Outlet. A smokeproof enclosure shall exit into a public way or into an exit
passageway leading to a public way. The exit passageway shall be without other
openings and shall have walls, floors and ceiling of two-hour fire-resistive
construction.
(d) Barrier. A stairway in a smokeproof enclosure shall not continue below the
grade level unless an approved barrier is provided at the ground level to prevent
persons from accidentally continuing into the basement.
(e) Access. Access to the stairways shall be by way of a vestibule or open
exterior exit balcony constructed of noncombustible materials.
(f) Smokeproof Enclosure by Natural Ventilation I. Doors. When a vesti-
bule is provided, the door assembly into the vestibule shall have a one and one-
half-hour fire-protection rating, and the door assembly from the vestibule to the
stairs shall be a smoke- and draft-control assembly having not less than a 20-
minute fire-protection rating. Doors shall be maintained self-closing or shall be
automatic closing by actuation of a smoke detector.
When access to the stairway is by means of an open exterior exit balcony, the
door assembly to the stairway shall have a one and one-half-hour fire-protection
rating and shall be maintained self-closing or shall be automatic closing by
actuation of a smoke detector.
2. Open-air vestibule. The vestibule shall have a minimum dimension of 44
inches in width and 72 inches in direction of exit travel. The vestibule shall have a
minimum of 16 square feet of opening in a wall facing an exterior court, yard or
public way at least 20 feet in width.
(g) Smokeproof Enclosures by Mechanical Ventilation. I. Doors. The door
assembly from the building into the vestibule shall have a one and one-half-hour
fire-protection rating, and the door assembly from the vestibule to the stairway
556
1982 EDITION 3310
shall be a smoke- and draft-control assembly having not less than a 20-minute
fire-protection rating. The door to the stairways shall be provided with a drop-sill
or other provision to minimize the air leakage. The doors shall be automatic
closing by actuation of a smoke detector or in the event of a power failure.
2. Vestibule size. Vestibules shall have a minimum dimension of 44 inches in
width and 72 inches in direction of exit travel.
3. Vestibule ventilation. The vestibule shall be provided with not less than one
air change per minute, and the exhaust shall be 150 percent of the supply. Supply
air shall enter and exhaust air shall discharge from the vestibule through separate
tightly constructed ducts used only for that purpose. Supply air shall enter the
vestibule within 6 inches of the floor level. The top ofthe exhaust register shall be
down from the top of the smoke trap and shall be entirely within the smoke trap
area. Doors, when in the open position, shall not obstruct duct openings. Duct
openings may be provided with controlling dampers if needed to meet the design
requirements but are not otherwise required.
4. Smoke trap. The vestibule ceiling shall be at least 20 inches higher than the
door opening into the vestibule to serve as a smoke and heat trap and to provide an
upward-moving air column. The height may be decreased when justifed by
engineering design and field testing.
5. Stair shaft air movement system. The stair shaft shall be provided with a
dampered relief opening at the top and supplied mechanically with sufficient air
to discharge a minimum of 2500 cubic feet per minute through the relief opening
while maintaining a minimum positive pressure of 0.05 inch of water column in
the shaft relative to atmosphere with all doors closed and a minimum ofO. 10-inch
water column difference between the stair shaft and the vestibule.
6. Operation of ventilating equipment. The activation of the ventilating
equipment shall be initiated by a smoke detector installed outside the vestibule
door in an approved location. The activation of the closing device on any door
shall activate the closing devices on all doors of the smokeproof enclosure at all
levels. When the closing device for the stair shaft and vestibule doors is activated
by a smoke detector or power failure, the mechanical equipment shall operate at
the levels specified in Items Nos. 3 and 5.
7. Standby power. Standby power for mechanical ventilation equipment shall
be provided by an approved self-contained generator set to operate whenever
there is a loss of power in the normal house current. The generator shall be in a
separate room having a minimum one-hour fire-resistive occupancy separation
and shall have a minimum fuel supply adequate to operate the equipment for two
hours. See Section 1807 (i) for standby power requirements for high-rise Group
B, Division 2 offices and Group R, Division I Occupancies.
8. Acceptance testing. Before the mechanical equipment is accepted by the
building official, it shall be tested to confirm that the mechanical equipment is
operating in compliance with these requirements.
9. Emergency lighting. The stair shaft and vestibule shall be provided with
emergency lighting. A standby generator which is installed for the smokeproof
enclosure mechanical ventilation equipment may be used for such stair shaft and
557
3310-3313 UNIFORM BUILDING CODE
vestibule power supply. See Section 1807 (i) for emergency lighting requirements
for high-rise Group B, Division 2 offices and Group R, Division I Occupancies.
Exit Courts
Sec. 3311. (a) General. Every exit court shall discharge into a public way or
exit passageway.
(b) Width. Exit court minimum widths shall be determined in accordance with
provisions of Section 3303 based on the occupant load and such required width
shall be unobstructed to a height of 7 feet, except for projections permitted in
corridors by Section 3305. The minimum exit court width shall be not less than 44
inches.
When the width is reduced from any cause, the reduction shall be affected
gradually by a guardrail at least 3 feet in height and making an angle of not more
than 30 degrees with the axis of the exit court.
(c) Number of Exits. Every exit court shall be provided with exits as deter-
mined by Section 3303.
(d) Construction and Openings. When an exit court serving a building or
portion thereof having an occupant load of 10 or more is less than 10 feet in width,
the exit court walls shall be a minimum of one-hour fire-resistive construction for
a distance of I 0 feet above the floor of the court, and all openings therein shall be
protected by fire assemblies having a fire-protection rating of not less than three-
fourths hour.
Exit Passageways
Sec. 3312. (a) Construction and Openings. The walls of exit passageways
shall be without openings other than required exits and shall have walls, floors and
ceilings of the same period of fire resistance as required for the walls, floors and
ceilings of the building served with a minimum of one-hour fire-resistive con-
struction. Exit openings through the enclosing walls of exit passageways shall be
protected by fire assemblies having a three-fourths-hour fire-protection rating.
(b) Detailed Requirements. Except for construction and opening protection as
specified in Subsection (a) above, exit passageways shall comply with the require-
ments for corridors as specified in Section 3305.
Exit Illumination
Sec. 3313. (a) General. Except within individual dwelling units, guest rooms
and sleeping rooms, exits shall be illuminated at any time the building is occupied
with light having intensity of not less than I footcandle at floor level.
EXCEPTION: In auditoriums, theaters, concert or opera halls and similar
assembly uses, the illumination at floor level may be reduced during performances
to not less than 0. 2 footcandle.
Fixtures required for exit illumination shall be supplied from separate circuits
or sources of power where these are required by Subsection (b).
(b) Power Supply. I. Separate branch circuits. The power supply for exit
illumination shall be provided by two separate branch circuits of the normal
premises wiring system, unless an emergency system is installed, where the
558
1982 EDITION 3313-3314
559
3314-3315 UNIFORM BUILDING CODE
exit illumination by Section 3313 (b) 2, power to one of the lamps for exit signs
shall be from storage batteries or an on-site generator set and the system shall be
installed in accordance with the Electrical Code. For high-rise buildings, see
Section 1807.
Aisles
Sec. 3315. (a) General. Aisles leading to required exits shall be provided from
all portions of buildings.
(b) Width. Aisle widths shall be provided in accordance with the following:
I. In areas serving employees only, the minimum aisle width may be 24
inches but not less than the width required by the number of employees
served.
2. In public areas of Group B, Division 2 Occupancies, and in assembly
occupancies without fixed seats, the minimum clear aisle width shall be 36
inches where tables, counters, furnishings, merchandise or other similar
obstructions are placed on one side of the aisle only and 44 inches when
such obstructions are placed on both sides of the aisle.
3. In assembly occupancies with fixed seats.
A. With standard seating, every aisle shall be not less than 3 feet when
serving seats on only one side and not less than 42 inches wide when
serving seats on both sides. Such minimum width shall be measured
from the point furthest from the exit, cross aisle or foyer and such
minimum width shall be increased by I Y2 inches for each 5 feet of
length toward the exit, cross aisle or foyer.
B. With continental seating as specified in Section 3316, side aisles shall
be provided and be not less than 44 inches in width.
(c) Distances to Nearest Exit. In areas occupied by seats and in Group A
Occupancies without seats, the line of travel to an exit door by an aisle shall be not
more than 150 feet. Such travel distance may be increased to 200 feet if the
building is provided with an approved automatic sprinkler system.
(d) Aisle Spacing. With standard seating, aisles shall be so located that there
will be not more than six intervening seats between any seat and the nearest aisle.
With continental seating, the number of intervening seats may be increased,
provided the seating configuration conforms with the requirements specified in
Section 3316.
When benches or pews are used, the number of seats shall be based on one
person for each 18 inches of length of pew or bench.
(e) Cross Aisles. Aisles shall terminate in a cross aisle, foyer or exit. The width
of the cross aisle shall be not less than the sum of the required width of the widest
aisle plus 50 percent of the total required width of the remaining aisles leading
thereto. In Groups A and E Occupancies, aisles shall not have a dead end greater
than 20 feet in length.
(f) Vomitories. Vomitories connecting the foyer or main exit with the cross
aisles shall have a total width not less than the sum of the required width of the
widest aisle leading thereto plus 50 percent of the total required width of the
560
1982 EDITION 3315-3317
561
3317-3319 UNIFORM BUILDING CODE
be provided with a minimum of two exits. Balcony exits shall open directly to an
exterior stairway or other approved stairway or ramp. When there is more than one
balcony, exits shall open into an exterior or enclosed stairway or ramp. Balcony
exits shall be accessible from a cross aisle. The number and distribution of exits
shall be as otherwise specified in this chapter.
(d) Panic Hardware. An exit door from a Group A, Division I Occupancy
having an occupant load of 50 or more shall not be provided with a latch or lock
unless it is panic hardware.
Group A, Divisions 2, 2.1, 3 and 4 Occupancies
Sec. 3318. (a) Group A, Divisions 2, 2.1 and 3. Group A, Divisions 2 and 2.1
Occupancies shall have exits as required by Section 3317. In Group A, Division 3
Occupancies having an occupant load of 50 or more, exit doors shall not be
provided with a latch or lock unless it is panic hardware.
EXCEPTION: Group A, Divisions 2.1 and 3 Occupancies, such as restaurants,
bars, bowling alleys, auditoriums and similar commercial uses, and in churches,
panic hardware may be omitted from the main exit when the main exit consists of a
single door. A key locking device may be used in place of the panic hardware,
provided there is a readily visible durable sign adjacent to the doorway stating THIS
DOOR MUST REMAIN UNLOCKED DURING BUSINESS HOURS. The sign
shall be in letters not less than I inch high on a contrasting background. When
unlocked, the single door must be free to swing without operation of any latching
device. Flush, edge or surface bolts or any other type of device that may be used to
close or restrain the door other than by operation of the locking device are pro-
hibited. The use of this exception may be revoked by the building official for due
cause.
(b) Group A, Division 4. In Group A, Division 4 Occupancies having an
occupant load of 50 or more, exit doors shall not be provided with a latch or lock
unless it is panic hardware.
Group E Occupancies
Sec. 3319. (a) Definitions. For the purpose of this section, the following
definitions apply:
INTERIOR ROOM is a room whose only exit is through an adjoining or
intervening room which is not an exit corridor.
ROOM is a space or area bounded by any obstructions to exit passage which at
any time enclose more than 80 percent of the perimeter of the area. In computing
the unobstructed perimeter, openings less than 3 feet in clear width and less than 6
feet 8 inches high shall not be considered.
SEPARATE EXIT SYSTEM is a path of exit travel separated in such a
manner from other required exits as to provide an atmospheric separation which
precludes contamination of both paths by the same fire.
(b) Separate Exit Systems Required. Every room with an occupant load of
more than 300 shall have one of its exits into a separate exit system. When three or
more exits are required from a room, no more than two required exits shall enter
into the same exit system.
(c) Distance to Exits. I. The distance from any point in a room shall be not
562
more than 75 feet from an exit corridor, an enclosed stairway or the exterior of the
building.
EXCEPTIONS: I. In buildings not more than two stories in height and protected
throughout with smoke detectors, the distance may be increased to 90 feet.
2. In buildings protected throughout by an automatic sprinkler system, the
distance may be increased to II 0 feet.
2. All portions of unsprinklered building shall be not more than !50 feet from
either an exterior exit door, a horizontal exit, an exit passageway or an enclosed
stairway measured along the line of travel. In a building protected throughout with
an automatic sprinkler system such distance may be increased to 225 feet. In
buildings not more than two stories in height protected throughout with smoke
detectors, the distance may be increased to 175 feet.
(d) Exits Through Adjoining Rooms. Interior rooms may exit through adjoin-
ing or intervening rooms, provided the total distance of travel through such rooms
to an exit corridor does not exceed that specified in Subsection (c) I above and is a
direct, obvious and unobstructed path of travel. Such paths of exit travel shall not
pass through kitchens, storerooms, rest rooms, closets, laboratories using haz-
ardous materials, industrial shops or other similar places.
Foyers and lobbies constructed as required for exit corridors shall not be
construed as adjoining or intervening rooms.
When the only means of exit from a room is through an adjoining or intervening
room, smoke detectors shall be installed throughout the area of the common
atmosphere through which the exit must pass. The detectors shall actuate alarms
audible in the interior room and shall be connected to the school fire alarm system.
EXCEPTIONS: I. When the aggregate occupant load of the interior room or
rooms is 10 or less.
2. When the enclosures forming interior rooms are less than two thirds of the
floor-to-ceiling height and do not exceed 8 feet.
3. Rooms used exclusively for mechanical and public utility service to the
buildings.
(e) Corridors and Exterior Exit Balconies. Corridor walls and ceilings shall
be of not less than one-hour fire-resistive construction with openings protected as
required in Section 3305 (h).
EXCEPTION: When each room used for instruction has at least one exit door
directly to the exterior at ground level and when rooms used for assembly purposes
have at least one half of the required exits directly to the exterior ground level, one-
hour fire-resistive construction of corridor walls and ceilings is not required.
Any change in elevation of less than 2 feet in a corridor or exterior exit balcony
shall be by means of ramps.
The width of a corridor in a GroupE, Division I Occupancy shall be the width
required by Section 3303, plus 2 feet, but not less than 6 feet.
EXCEPTION: When the number of occupants served is 100 or less, the corridor
may be 44 inches wide.
(f) Exit Serving Auditoriums in Group E, Division 1 Occupancy. An exit
serving an auditorium and other rooms need provide only for the capacity of
563
3319-3321 UNIFORM BUILDING CODE
whichever requires the greater width if the auditorium is not to be used simul-
taneously with the other rooms.
(g) Stairs. Each floor above or below the ground floor level shall have not less
than two exit stairs and the required exit width shall be equally divided between
such stairs, provided that stairs serving an occupant load of 100 or more shall be
not less than 5 feet in clear width.
EXCEPTION: This subsection does not apply to rooms used for maintenance,
storage and similar purposes.
(h) Doors. The width of exit doors shall be sufficient to accommodate the
occupant load served.
(i) Basement Rooms. Exit stairways from a basement shall open directly to the
exterior of the building without entering the first floor corridor.
(j) Panic Hardware. Exit doors from rooms having an occupant load of 50 or
more and from corridors shall not be provided with a latch or lock unless it is panic
hardware.
(k) Fences and Gates. School grounds may be fenced and gates therein
equipped with locks, provided safe dispersal areas are located not less than 50 feet
from the buildings. Dispersal areas shall be sized to provide an area of not less
than 3 square feet per occupant. Gates shall not be installed across corridors or
passageways leading to such dispersal areas unless they comply with exit require-
ments. See Section 3323 for exits from dispersal areas.
Group H Occupancies
Sec. 3320. Every portion of a Group H Occupancy having a floor area of 200
square feet or more shall be served by at least two separate exits.
In Divisions I and 2, all portions of any room shall be within 75 feet of an exit.
Doors leading to a corridor of fire-resistive construction shall have a minimum
three-fourths-hour fire-protection rating; shall have not more than 100 square
inches of wired glass set in steel frames; shall be maintained self-closing or shall
be automatic closing as defined in Section 4306 (b); and shall open in the direction
of exit travel.
Group I Occupancies
Sec. 3321. (a) Exterior Doors. All required exterior exit doors shall open in
the direction of exit travel.
(b) Minimum Size of Exits. Every exit opening through which patients are
transported in wheelchairs, stretchers or beds shall be of sufficient width to
permit the ready passage of such equipment but shall have a clear width of not less
than 44 inches. There shall be no projections within the 44-inch clear width.
(c) Corridors. The minimum clear width of a corridor shall be 44 inches,
except that corridors serving any area housing one or more nonambulatory
persons shall be not less than 8 feet in width. Any change in elevation of the floor
in a corridor serving nonambulatory persons shall be made by means of a ramp.
(d) Basement Exits. One exit accessible to every room below grade shall lead
directly to the exterior at grade level.
564
1982 EDITION 3321-3323
565
3323 UNIFORM BUILDING CODE
that a person within the area will not be closer than 50 feet from the stand or
building. Dispersal area capacity shall be determined by allowing 3 square feet of
net clear area per person.
FOOTBOARDS are that part of a raised seating facility other than an aisle or
cross aisle upon which the occupant walks to reach a seat.
GRANDSTANDS are tiered or stepped seating facilities wherein an area of
more than 3 square feet is provided for each person.
OPEN-AIR GRANDSTANDS AND BLEACHERS are seating facilities
which are located so that the side toward which the audience faces is unroofed and
without an enclosing wall.
PERMANENT STANDS are those seating facilities which remain at a loca-
tion for more than 90 days.
REVIEWING STANDS are elevated platforms accommodating not more than
50 persons. Seating facilities, if provided, are normally in the nature of loose
chairs. Reviewing stands accommodating more than 50 persons shall be regulated
as grandstands.
TEMPORARY SEATING FACILITIES are those which are intended for use
at a location for not more than 90 days.
(c) Height of Grandstands and Bleachers. Grandstands or bleachers employ-
ing combustible members in the structural frame shall be limited to 11 rows or 9
feet in height. Seat boards, toe boards, bearing or base pads and footboards may be
of combustible materials.
(d) Design Requirements. See Chapter 23 and Section 2907 (h).
(e) General Requirements. 1. Row spacing. There shall be a clear space of
not less than 12 inches measured horizontally between the back or backrest of
each seat and the front of the seat immediately behind it. The minimum spacing of
rows of seats measured from back to back shall be:
A. Twenty-two inches for seats without backrests.
B. Thirty inches for seats with backrests.
C. Thirty-three inches for chair seating.
2. Rise between rows. The maximum rise from one row of seats to the next
shall not exceed 16 inches unless the seat spacing from back to back measured
horizontally is 40 inches or more.
3. Seating capacity determination. When bench-type seating is used, the
number of seats shall be based on one person for each 18 inches of length of the
bench.
4. Aisles. A. Aisles required. Aisles shall be provided in all seating facilities
except that aisles may be omitted when all of the following conditions exist:
(i) Seats are without backrests.
(ii) The rise from row to row does not exceed 12 inches per row.
(iii) The number of rows does not exceed 11 in height.
(iv) The top seating board is not over 10 feet above grade.
(v) The first seating board is not more than 20 inches above grade.
566
1982 EDITION 3323
567
3323-3324 UNIFORM BUILDING CODE
568
1982 EDITION 3324
569
3324, 33-A UNIFORM BUILDING CODE
Cross aisles located within the seating area shall be provided with guardrails
not less than 26 inches high along the front edge of the aisle.
EXCEPTION: When the backs of the seats in front of the cross aisle project 24
inches or more above the surface of the cross aisle, guardrails may be omitted.
TABLE NO. 33-A-MINIMUM EGRESS AND ACCESS REQUIREMENTS
MINIMUM OF ACCESS BY
TWO EXITS MEANS OFA
OTHER THAN RAMP OR AN
ELEVATORS ARE ELEVATOR MUST
REQUIRED OCCU- BE PROVIDED
WHERE PANT FOR THE
NUMBER OF LOAD PHYSICALLY
USE1
OCCUPANTS IS
AT LEAST
~~CT0~)9
Sq. Ft.
HANDICAPPED
AS INDICATED2
I. Aircraft Hangars
(no repair) 10 500 Yes
2. Auction Rooms 30 7 Yes
3. Assembly Areas, Concen-
trated Use (without fixed seats) 50 7 Yes 3 4
Auditoriums
Bowling Alleys (Assembly areas)
Churches and Chapels
Dance Floors
Lodge Rooms
Reviewing Stands
Stadiums
4. Assembly Areas, Less-con-
centra ted Use 50 15 Yes3 Jo
Conference Rooms
Dining Rooms
Drinking Establishments
Exhibit Rooms
Gymnasiums
Lounges
Stages
5. Children's Homes and
Homes for the Aged 6 80 Yes 5
6. Classrooms 50 20 Yes II
7. Dormitories 10 50 Yes 5
8. Dwellings 10 300 No
9. Garage, Parking 30 200 Yes 6
10. Hospitals and Sanitariums-
Nursing Homes 6 80 Yes
II. Hotels and Apartments 10 200 YesH
12. Kitchen-Commercial 30 200 No
13. Library Reading Room 50 50 Yes 3
14. Locker Rooms 30 50 Yes
15. Mechanical Equipment Room 30 300 No
16. Nurseries for Children
(Day-care) 7 35 Yes
(Continued)
570
1982 EDITION 33-A
MINIMUM OF ACCESS BY
TWO EXITS MEANS OF A
OTHER THAN RAMP OR AN
ELEVATORS ARE ELEVATOR MUST
REQUIRED OCCU- BE PROVIDED
WHERE PANT FOR THE
NUMBER OF LOAD PHYSICALLY
~~~~;
OCCUPANTS IS HANOICAPPED
USE 1 AT LEAST AS INDICATED2
17. Offices 30 100 Yes5
18. School Shops and Vocational
Rooms 50 50 Yes
19. Skating Rinks 50 50 on Yes 3
the
skating
area;
15 on the
deck
20. Stores-Retails Sales Rooms
Basement 7 20 Yes
Ground Floor 50 30 Yes
Upper Floors 10 50 Yes
21. Swimming Pools 50 50 for Yes3
the pool
area;
15 on the
deck
22. Warehouses 30 300 No
23. Lobby Accessory to Assembly
Occupancy 50 7 Yes
24. Malls (see Appendix Chapter 7)
25. All others 50 100
1Refer to Sections 3320 and 3321 for other specific requirements.
2 Elevators shall not be construed as providing a required exit.
3Access to secondary areas on balconies or mezzanines may be by stairs only, except when
such secondary areas contain the only available toilet facilities.
4 Reviewing stands, grandstands and bleachers need not comply.
5 Access to floors other than that closest to grade may be by stairs only, except when the only
available toilet facilities are on other levels.
6 Access to floors other than that closest to grade and to garages used in connection with
apartment houses may be by stairs only.
7See Section 3303 for basement exit requirements.
8See Section 1213 for access to buildings and facilities in hotels and apartments.
9Th is table shall not be used to determine working space requirements per person.
10 Access requirements for conference rooms, dining rooms, lounges and exhibit rooms that
are part of an office use shall be the same as required for the office use.
II When the floor closest to the grade offers the same programs and activities available on
other floors, access to the other floors may be by stairs only, except when the only
available toilet facilities are on other levels.
571
3401 UNIFORM BUILDING CODE
Chapter 34
SKYLIGHTS
Skylights
Sec. 3401. In other than Types Ill, IV and V buildings, all skylight frames shall
be constructed of noncombustible materials. All skylights shall be designed to
carry all tributary roof loads as specified in Section 2305. All skylights, the
glazing of which is set at an angle of less than 45 degrees from the horizontal,
shall be mounted at least 4 inches above the plane of the roof on a curb constructed
as required for the frame.
Spacing between supports in one direction for flat wired glass in sky lights shall
not exceed 25 inches. Corrugated wired glass may have supports 5 feet apart in the
I
,
direction of the corrugation. All glass in skylights shall be wired glass, laminated
glass with an approved interlayer having a minimum thickness of 0.030 inch or
tempered glass, minimum thickness 7/12 inch, except that skylights over vertical
shafts extending through two or more stories shall be glazed with plain glass as
specified in this section, provided that wired glass may be used if ventilation equal
to not less than one-eighth the cross-sectional area of the shaft but never less than
4 square feet is provided at the top of such shaft.
g Any glass not laminated glass with an approved interlayer having a minimum
I thickness of 0.030 inch, wired glass or fully tempered glass shall be protected
above and below with a screen constructed of wire not smaller than No. 12 U.S.
gauge with a mesh not larger than I inch. The screen shall be substantially
supported below the glass.
Ordinary glass may be used in the roofs and skylights for greenhouses,
provided the height of the greenhouse at the ridge does not exceed 20 feet above
the grade. The use of wood in the frames of skylights will be permitted in
greenhouses if the height of the skylight does not exceed 20 feet above the grade,
but in other cases metal frames and metal sash bars shall be used.
Glass used for the transmission of light, if placed in floors or sidewalks, shall be
supported by metal or reinforced concrete frames, and such glass shall be not less
than Y2 inch in thickness. Any such glass over 16 square inches in area shall have
wire mesh embedded in the same or shall be provided with a wire screen
underneath, as specified for skylights in this section. All portions of the floor
lights or sidewalk lights shall be ofthc same strength as is required by this code for
floor or sidewalk construction, except in cases where the floor is surrounded by a
railing not less than 3 feet 6 inches in height, in which case the construction shall
be calculated for not less than roof loads.
For requirements applicable to plastic skylights, sec Section 5207.
Chapter 35
SOUND TRANSMISSION CONTROL
572
1982 EDITION 3601-3602
Chapter 36
PENTHOUSES AND ROOF STRUCTURES
Penthouses and Roof Structures
Sec. 3601. (a) Height. No penthouse or other projection above the roof in
structures of other than Type I construction shall exceed 28 feet in height above the
roof when used as an enclosure for tanks or for elevators which run to the roof and
in all other cases shall not extend more than 12 feet in height above the roof.
(b) Area. The aggregate area of all penthouses and other roof structures shall
not exceed 33 Y3 percent of the area of the supporting roof.
(c) Prohibited Uses. No penthouse, bulkhead or any other similar projection
above the roof shall be used for purposes other than shelter of mechanical
equipment or shelter of vertical shaft openings in the roof. Penthouses or
bulkheads used for purposes other than permitted by this section shall conform to
the requirements of this code for an additional story.
(d) Construction. Roof structures shall be constructed with walls, floors and
roof as required for the main portion of the building.
EXCEPTIONS: I. On Types I and II-F.R. buildings, the exterior walls and roofs
of penthouses which are 5 feet or more from an adjacent property line may be of one-
hour fire-resistive noncombustible construction.
2. On Types III and IV buildings, walls not less than 5 feet from a property line
may be of one-hour fire-resistive noncombustible construction.
3. Enclosures housing only mechanical equipment and located at least 20 feet
from adjacent property lines may be of unprotected noncombustible construction.
4. On one-story buildings, unroofed mechanical equipment screens, fences or simi-
lar enclosures may be of combustible construction when located at least 20 feet from
adjacent property lines and when not exceeding 4 feet in height above the roof surface.
The restrictions of this subsection shall not prohibit the placing of wood flagpoles
or similar structures on the roof of any building.
Towers and Spires
Sec. 3602. Towers or spires when enclosed shall have exterior walls as required
for the building to which they are attached. Towers not enclosed and which extend
more than 75 feet above grade shall have their framework constructed of iron,
steel or reinforced concrete. No tower or spire shall occupy more than one fourth
of the street frontage of any building to which it is attached and in no case shall the
base area exceed 1600 square feet unless it conforms entirely to the type of
construction requirements of the building to which it is attached and is limited in
height as a main part of the building. If the area of the tower or spire exceeds I 00
square feet at any horizontal cross section, its supporting frame shall extend
directly to the ground. The roof covering of spires shall be as required for the main
roof of the rest of the structure.
Skeleton towers used as radio masts and placed on the roof of any building shall
be constructed entirely of noncombustible materials when more than 25 feet in
height and shall be directly supported on a noncombustible framework to the
ground. They shall be designed to withstand a wind load from any direction as
specified in Section 2311 in addition to any other loads.
573
3701-3702 UNIFORM BUILDING CODE
Chapter 37
MASONRY OR CONCRETE CHIMNEYS,
FIREPLACES AND BARBECUES
Scope
Sec. 3701. Chimneys, flues, fireplaces and barbecues, and their connections,
carrying products of combustion shall conform to the requirements of this
chapter.
Definitions
Sec. 3702. BARBECUE is a stationary open hearth or brazier, either fuel
fired or electric, used for food preparation.
CHIMNEY is a hollow shaft containing one or more passageways, vertical or
nearly so, for conveying products of combustion to the outside atmosphere.
CHIMNEY, FACTORY-BUILT, is a chimney manufactured at a location
other than the building site and composed of listed factory-built components
assembled in accordance with the terms of the listing to form the completed
chimney.
MASONRY CHIMNEY is a chimney of masonry units, bricks, stones or
listed masonry chimney units lined with approved flue liners. For the purpose of
this chapter, masonry chimneys shall include reinforced concrete chimneys.
CHIMNEY CLASSIFICATIONS:
Chimney, Residential Appliance-type, is a factory-built or masonry chimney
suitable for removing products of combustion from residential-type appliances
producing combustion gases not in excess of I 000F. measured at the appliance
flue outlet.
Chimney, Low-heat Industrial Appliance-type, is a factory-built, masonry
or metal chimney suitable for removing the products of combustion from fuel-
burning low-heat appliances producing combustion gases not in excess of I 000F.
under normal operating conditions but capable of producing combustion gases of
1400F. during intermittent forced firing for periods up to one hour. All tempera-
tures are measured at the appliance flue outlet.
Chimney, Medium-heat Industrial Appliance-type, is a factory-built,
masonry or metal chimney suitable for removing the products of combustion from
fuel-burning medium-heat appliances producing combustion gases not in excess
of 2000F. measured at the appliance flue outlet.
Chimney, High-heat Industrial Appliance-type, is a factory-built, masonry
or metal chimney suitable for removing the products of combustion from fuel-
burning high-heat appliances producing combustion gases in excess of 2000F.
measured at the appliance flue outlet.
CHIMNEY CONNECTOR is the pipe or breeching which connects a fuel-
burning appliance to a chimney. (See Chapter 9, Mechanical Code.)
CHIMNEY LINER is a lining material of fireclay or other approved material
that meets the requirements of U. B.C. Standard No. 37-1.
574
1982 EDITION 3702-3704
Chimneys, General
Sec. 3703. (a) Chimney Support. Chimneys shall be designed, anchored,
supported and reinforced as required in this chapter and applicable provisions of
Chapters 23, 24, 26, 27 and 29 of this code. A chimney shall not support any
structural load other than its own weight unless designed as a supporting member.
(b) Construction. Each chimney shall be so constructed as to safely convey
flue gases not exceeding the maximum temperatures for the type of construction
as set forth in Table No. 37-B and shall be capable of producing a draft at the
appliance not less than that required for safe operation.
(c) Clearance. Clearance to combustible material shall be as required by Table
No. 37-B.
(d) Lining. When required by Table No. 37-B, chimneys shall be lined with
fireclay flue tile, firebrick, molded refractory units or other approved lining not
less than Ys inch thick as set forth in Table No. 37-B. Chimney liners shall be
carefully bedded in approved mortar with close-fitting joints left smooth on the
inside.
(e) Area. Chimney passageways shall be not smaller in area than the vent
connection on the appliance attached thereto nor less than that set forth in Table
No. 37-A, unless engineering methods approved by the building official have
been used to design the system.
(f) Height and Termination. Every chimney shall extend above the roof and
the highest elevation of any part of a building as shown in Table No. 37-B. For
altitudes over 2000 feet, the building official shall be consulted in determining the
height of the chimney.
All incinerator chimneys shall terminate in a substantially constructed spark
arrester having a mesh not exceeding Yz inch.
(g) Cleanouts. Cleanout openings shall be provided at the base of every
masonry chimney.
Masonry Chimneys
Sec. 3704. (a) Design. Masonry chimneys shall be designed and constructed
to comply with Section 3703 (b) and Section 3704 (b).
(b) Walls. Walls of masonry chimneys shall be constructed as set forth in Table
No. 37-B.
575
3704-3707 UNIFORM BUILDING CODE
576
1982 EDITION 3707
(c) Fireplace Walls. Masonry walls of fireplaces shall be not less than 8 inches
in thickness. Walls of fireboxes shall be not less than 10 inches in thickness,
except that where a lining of firebrick is used such walls shall be not less than a
total of 8 inches in thickness. The firebox shall be not less than 20 inches in depth.
Joints in firebrick shall not exceed Y4 inch.
(d) Hoods. Metal hoods used as part of a fireplace or barbecue shall be not less
than No. 19 gauge copper, galvanized steel or other equivalent corrosion-resistant
ferrous metal with all seams and connections of smokeproof unsoldered con-
structions. The hoods shall be sloped at an angle of 45 degrees or less from the
vertical and shall extend horizontally at least 6 inches beyond the limits of the
firebox. Metal hoods shall be kept a minimum of 18 inches from combustible
materials unless approved for reduced clearances.
(e) Metal Heat Circulators. Approved metal heat circulators may be installed
in fireplaces.
(f) Smoke Chamber. Front and side walls shall be not less than 8 inches in
thickness. Smoke chamber back walls shall be not less than 6 inches in thickness.
(g) Chimneys. Chimneys for fireplaces shall be constructed as specified in
Sections 3703, 3704 and 3705 for residential-type appliances.
(h) Clearance to Combustible Material. Combustible material shall not be
placed within I inch of fireplace, smoke chamber or chimney walls. Combustible
material shall not be placed within 6 inches of the fireplace opening. No such
combustible material within 12 inches of the fireplace opening shall project more
than Ys inch for each l-inch clearance from such opening.
No part of metal hoods used as part of a fireplace or barbecue shall be less than I
18 inches from combustible material. This clearance may be reduced to the
minimum requirements specified in the Mechanical Code.
(i) Areas of Flues, Throats and Dampers. The net cross-sectional area of the
flue and of the throat between the firebox and the smoke chamber of a fireplace
shall be not less than as set forth in Table No. 37-A. Metal dampers equivalent to
not less than No. 12 gauge steel shall be installed. When fully opened, damper
openings shall be not less than 90 percent of the required flue area.
U) Lintel. Masonry over the fireplace opening shall be supported by a non-
combustible lintel.
(k) Hearth. Masonry fireplaces shall be provided with a brick, concrete, stone
or other approved noncombustible hearth slab. This slab shall be not less than 4
sn
3707, 37-A UNIFORM BUILDING CODE
578
...
!m
0
TABLE NO. 378-CONSTRUCTION, CLEARANCE AND TERMINATION REQUIREMENTS FOR MASONRY 3
AND CONCRETE CHIMNEYS 0
z
Clearance to
Height Height Combustible
Above Above any Part Construction
Thickness Roof of Building (Inches)
(Min. Inches) Opening within (Feet) Int. Ext.
Chimneys Serving Walls Lining (Feet) 10 25 50 lnst. In st.
I. RESIDENTIAL-TYPE APPLIANCES I 2
(Low Btu Input) 43 5/8 fire-
Clay, Shale or Concrete Brick 43 clay tile lor
Reinforced Concrete 48 or 2 fire- 2 2 I y,
Hollow Masonry Units 12 brick gypsum4
Stone
8 4% fire-
Unlmrned Clay Units hrick
i
2. BUILDING HEATING AND I
INDUSTRIAL-TYPE LOW-HEAT
APPLIANCES I 2 ( Iooo F. operating
temp.-!400F. Maximum) 8 5/8 fire- 3 2 2 2
Clay, Shale or Concrete Brick
Hollow l\fasonry Units 88 clay tile
, or 2 fire-
Reinforced Concrete 8
Stone 12 brick
i I
(Continued)
....,
Ul
CD
TABLE NO. 378-CONSTRUCTION, CLEARANCE AND TERMINATION REQUIREMENTS FOR MASONRY
AND CONCRETE CHIMNEYS-(Continued)
Height Clearance to
Above any Part Combustible
Height Construction
Thickness Above of Building
(Min. Inches) within (Feet) (Inches)
Roof
Opening Int. Ext.
Chimneys Serving Walls Lining (Feet) 10 25 50 In st. In st.
3. MEDIUM-HEAT INDUSTRIAL-
lYPE APPLIANCES I 5
(2000F. Maximum)
Clay, Shale or Concrete Brick 8 10 10 4 4
8 4 1 2 Medium
Hollow Masonry Units duty fire-
(Grouted Solid) brick
Reinforced Concrete 8
Stone 12
4. IDGH-HEAT INDUSTRIAL-TYPE
APPLIANCES'' (Over zoooF.)
Clay, Shale or Concrete Brick 16 6 7
16 6 4 12 High 20 20 7
Hollow ~1asonry Units duty fire-
(Grouted Solid) brick
Reinforced Concrete 16 6 c
Same as for Residential-Type Appliances as shown above
z
5. RESIDENTIAL-TYPE INCINERATORS
~
6. CHUTE-FED AND FLUE-FED INCIN- :0
ERATORS WITH COMBINED HEARTH 3:
AND GRATE AREA 7 SQ. FT. OR LESS m
c
Clay, Shale or Concrete Brick 4 1 2 :-.tedium
3 2
rc
or Hollow Units duty fire- 2 2
Portion extending to 10 ft. hrick z
C)
above combustion chamber roof 4 5/8 fire-
0
Portion more than 10ft. above clay tile 0
combustion chamber roof 8 liner
~
7. OIUTE-FED AND FLUE-FED .....
INCINERATORS-COMBINED
HEARTH AND GRATE AREAS i
1\)
lARGER THAN 7 SQ. FT. m
Clay, Shale or Concrete Brick 4% Medium c
or Hollow Units Grouted Solid duty fire- 3
or Reinforced Concrete brick 0
z
Portion extending to 40 ft. 5/8 fire-
above combustion chamber roof 4 clay tile 10 2 2
Portion more than 40ft. above liner
combustion chamber roof 8 4% ~tedium
Reinforced Concrete 8 duty fire-
brick
laid in medium
duty refract
mortar
8. COMMERCIAL OR INDUSTRIAL-
lYPE INCINERATORS 2
Clay or Shale Solid Brick 8 4% Medium
Reinforced Concrete 8 duty fire-
brick
laid in medium 10 4 4
duty refract
mortar
1See Table No. 9-A of the Mechanical Code for types of appliances to be used with each type of chimney.
2Lining shall extend from bottom to top of chimney.
3Chimneys having walls 8 inches or more in thickness may be unlined.
"Chimneys for residential-type appliances installed entirely on the exterior of the building.
5Lining to extend from 24 inches below connector to 25 feet above.
6'fwo 8-inch walls with 2-inch air space between walls. Outer and inner walls may be of solid masonry units or reinforced concrete or any
combination thereof.
7 Clearance shall be approved by the building official and shall be such that the temperature of combustible materials will not exceed l60F.
BEquivalent thickness including grouted cells when grouted solid. The equivalent thickness may also include the grout thickness between the liner
g: and masonry unit .
....
3801 UNIFORM BUILDING CODE
Chapter 38
FIRE-EXTINGUISHING SYSTEMS
Scope
Sec. 3801. (a) General. All fire-extinguishing systems required in this code
shall be installed in accordance with the requirements of this chapter.
Fire hose threads used in connection with fire-extinguishing systems shall be
National Standard hose thread or as approved by the fire department.
(b) Approvals. All fire-extinguishing systems including automatic sprinkler
systems, Classes I, II and III standpipe systems, combined systems, special
automatic extinguishing systems and basement pipe inlets shall be approved and
shall be subject to such periodic tests as may be required. The location of all fire
department hose connections shall be approved by the fire department.
(c) Definitions. For the purpose of this chapter, certain terms are defined as
follows:
AUTOMATIC FIRE-EXTINGUISHING SYSTEM is an approved system
of devices and equipment which automatically detects a fire and discharges an
approved fire-extinguishing agent onto or in the area of a fire.
COMBINED SYSTEM is a system of water piping which serves 2 1/2-inch
hose outlets for use by the fire department and also supplies water to fire
sprinklers.
FIRE DEPARTMENT HOSE CONNECTION is a connection through
which the fire department can pump water.
STANDPIPE SYSTEM is a wet or dry system of piping, valves, outlets and
related equipment designed to provide water at specified pressures and installed
exclusively for the fighting of fires and classified as follows:
Class I is a dry standpipe system without a directly connected water supply and
equipped with 2 V2-inch outlets for use by the fire department or trained personnel.
Class II is a wet standpipe system directly connected to a water supply and
equipped with I V2-inch outlets intended for use by the building occupants.
Class III is a combination standpipe system directly connected to a water
supply and equipped with both 1V2-inch outlets for use by the building occupants
and 2Vz-inch outlets for use by the fire department or trained personnel.
(d) Standards. Fire-extinguishing systems shall comply with U. B.C. Stan-
dards Nos. 38-1 and 38-2.
EXCEPTIONS: I. Automatic fire-extinguishing systems not covered by
U.B.C. Standard No. 38-1 or 38-2 shall be approved and installed in accordance
with the Fire Code.
2. Automatic sprinkler systems may be connected to the domestic water-supply
main when approved by the building official, provided the domestic water supply is
of adequate pressure, capacity and sizing for the combined domestic and sprinkler
requirements. In such case, the sprinkler system connection shall be made between
the public water main or meter and the building shutoff valve, and there shall not be
intervening valves or connections. The fire department connection may be omitted
when approved by the fire department.
582
1982 EDITION 3802
583
3802 UNIFORM BUILDING CODE
I
the floor area exceeds 12,000 square feet on any floor or 24,000 square feet on all
floors or in Group B, Division 2 retail sales occupancies more than three stories in
height.
In buildings used for high-piled combustible storage, fire protection shall be in
accordance with the Fire Code.
(e) Group E Occupancies. I. Basements. An automatic sprinkler system
shall be installed in basements classified as a Group E Occupancy when the
basement is larger than 1500 square feet in floor area.
2. Stairs. An automatic sprinkler system shall be installed in enclosed usable
space below or over a stairway in GroupE Occupancies. See Section 3309 (t).
(t) Group H Occupancies. I. Division 1. A fire-extinguishing system shall be
installed in Group H, Division I Occupancies larger than 1500 square feet in floor
area.
2. Division 2. A fire-extinguishing system shall be installed in Group H,
Division 2 Occupancies exceeding 1500 square feet in area.
A fire-extinguishing system shall be installed in rooms of Group H, Division 2
Occupancies when flammable or combustible liquids are stored or handled in
excess of the quantities set forth in Table No. 9-A, or any combination of
flammable liquids exceeds 240 gallons.
A fire-extinguishing system shall be installed in paint spray booths or rooms.
3. Division 3. A fire-extinguishing system shall be installed in Group H,
Division 3 Occupancies larger than 3000 square feet in floor area.
4. Division 4. A fire-extinguishing system shall be installed in Group H,
Division 4 Occupancies more than one story in height.
(g) Group I Occupancies. An automatic sprinkler system shall be installed in
Group I Occupancies.
EXCEPTIONS: I. In hospitals of Types I, II Fire-resistive and II One-hour
584
1982 EDITION 3802-3804
construction, the automatic sprinkler system may be omitted from operating, deliv-
ery, cardiac, X-ray and intensive care rooms and patient sleeping rooms not exceed-
ing 450 square feet in area when each such room is provided with smoke detectors
connected to a continuously attended station or location within the building.
Increases for area and height specified in Sections 506 (c) and 507 shall not apply
when this exception is used.
2. In jails, prisons and reformatories, the piping system may be dry, provided a
manually operated valve is installed at a continuously monitored location. Opening
of the valve will cause the piping system to be charged. Sprinkler heads in such
systems shall be equipped with fusible elements or the system shall be designed as
required for deluge systems in U .B.C. Standard No. 38-1.
Sprinkler System Alarms
Sec. 3803. When serving more than 100 sprinklers, automatic sprinkler sys-
tems shall be supervised by an approved central, proprietary or remote station
service or a local alarm which will give an audible signal at a constantly attended
location.
585
380S-3806 UNIFORM BUILDING CODE
Standpipes
Sec. 3805. (a) General. Standpipes shall comply with the requirements of this
section and U .B.C. Standard No. 38-2.
(b) Where Required. Standpipe systems shall be provided as set forth in Table
No. 38-A.
(c) Location of Class I Standpipes. There shall be a Class I standpipe outlet
connection at every floor level above the first story of every required stairway and
on each side of the wall adjacent to the exit opening of a horizontal exit. Outlets at
stairways shall be located within the exit enclosure or in the case of smokeproof
enclosures, within the vestibule or exterior balcony, giving access to the stairway.
Risers and laterals of Class I standpipe systems not located within an enclosed
stairway or smokeproof enclosure shall be protected by a degree of fire resistance
equal to that required for vertical enclosures in the building in which they are
located.
EXCEPTION: In buildings equipped with an approved automatic sprinkler
system, risers and laterals which are not located within an enclosed stairway or
smokeproof enclosure need not be enclosed within fire-resistive construction.
There shall be a three-way outlet above the roofline when the roof has a slope of
Jess than 4 inches in 12 inches.
In buildings where more than one standpipe is provided, the standpipes shall be
interconnected at the bottom.
(d) Location of Class II Standpipes. Class II standpipe outlets shall be
accessible and shall be located so that all portions of the building are within 30
feet of a nozzle attached to I 00 feet of hose.
In Group A, Divisions I, 2 and 2.1 Occupancies, with occupant loads of more
than 1000, outlets shall be located on each side of any stage, on each side of the
rear of the auditorium and on each side of the balcony.
Fire-resistant protection of risers and laterals of Class II standpipe systems is
not required.
(e) Location of Class III Standpipes. Class III standpipe systems shall have
outlets located as required for Class I standpipes in Section 3805 (c) and shall have
Class II outlets as required in Section 3805 (d).
Risers and laterals of Class III standpipe systems shall be protected as required
for Class I systems.
EXCEPTIONS: I. In buildings equipped with an approved automatic sprinkler
system, risers and laterals which are not located within an enclosed stairway or
smokeproof enclosure need not be enclosed within fire-resistive construction.
2. Laterals for Class II outlets on Class III systems need not be protected.
In buildings where more than one Class III standpipe is provided, the stand-
pipes shall be interconnected at the bottom.
Buildings Under Construction
Sec. 3806. (a) General. During the construction of a building and until the
permanent fire-extinguishing system has been installed and is in service, fire
protection shall be provided in accordance with this section.
(b) Where Required. Every building six stories or more in height shall be
provided with not less than one standpipe for use during construction. Such
586
1982 EDITION 3806-3807, 38-A
standpipes shall be installed when the progress of construction is not more than 50
feet in height above grade. Such standpipe shall be provided with fire department
hose connections at accessible locations adjacent to usable stairs and the stand-
pipe outlets shall be located adjacent to such usable stairs. Such standpipe systems
shall be extended as construction progresses to within one floor of the highest
point of construction having secured decking or flooring.
In each floor there shall be provided a 2 Y2-inch valve outlet for fire department
use. Where construction height requires installation of a Class III standpipe, fire
pumps and water main connections shall be provided to serve the standpipe.
(c) Thmporary Standpipes. Temporary standpipes may be provided in place
of permanent systems if they are designed to furnish 75 gallons of water per
minute at 50 pounds per square inch pressure with a standpipe size of not less than
4 inches. All outlets shall be not less than 2 1/2 inches. Pumping equipment
sufficient to provide this pressure and volume shall be available at all times when a
Class III standpipe system is required.
(d) Detailed Requirements. Standpipe systems for buildings under con-
struction shall be installed as required for permanent standpipe systems.
Basement Pipe Inlets
Sec. 3807. For basement pipe inlet requirements, see Appendix Section 3807.
TABLE NO 38-A-STANDPIPE REQUIREMENTS
NONSPRINKLERED SPRINKLERED
BUILDING2 BUILDING 4
Standpipe Hoaa Standpipe Hoaa
OCCUPANCY' Class Raqulnoment Class Raqulnoment
I. Occupancies exceeding 150ft.
III Yes III No
in height and more than one
story
2. Occupancies 4 stories or more [I and IJ5] 6
but less than 150 ft. in height, l(oriii) No
(or III) Yes
except Group R, Div. 3
3. Group A Occupancies with No
II Yes No
occupant load exceeding 1000 requirement
4. Group A, Div. 2.1
Occupancies over 5000 square II Yes II Yes
feet in area used for exhibition
5. Groups I, H, B, Div. I, 2 or 3
Occupancies less than 4 stories No
in height but greater than
IJ5 Yes
requirement
No
20,000 square feet per floor
'Class II standpipes need not be provided in assembly areas used solely for worship.
'Except as otherwise specified in Item No. 4 of this table, Class II standpipes need not be provided in
basements having an automatic fire-extinguishing system throughout.
3 Combined systems with their related water supplies may be used in sprinklered buildings.
4 Portionsof otherwise sprinklered buildings which are not protected by automatic sprinklers shall have
Class II standpipes installed as required for the unsprinklered portions.
'In open structures where Class II standpipes may be damaged by freezing, the building official may
authorize the use of Class I standpipes which are located as required for Class II standpipes.
"Hose is required for Class II standpipes only.
587
3901-3902 UNIFORM BUILDING CODE
Chapter 39
STAGES AND PLATFORMS
Stage Ventilators
Sec. 3901. (a) General. There shall be one or more ventilators constructed of
metal or other noncombustible material near the center and above the highest part
of any working stage raised above the stage roof and having a total ventilation area
equal to at least 5 percent of the floor area within the stage walls. The entire
equipment shall conform to the requirements in Subsections (b) to (i) of this
section or their equivalent.
(b) Opening Action. Ventilators shall open by spring action or force of gravity
sufficient to overcome the effects of neglect, rust, dirt, frost, snow or expansion
by heat or warping of the framework.
(c) Glass. Glass, if used in ventilators, must be protected against falling on the
stage. A wire screen, if used under the glass, must be so placed that if clogged it
cannot reduce the required ventilating area or interfere with the operating mecha-
nism or obstruct the distribution of water from the automatic sprinkler systems.
(d) Design. Ventilators, penthouses and supporting framework shall be
designed in accordance with Chapter 23.
(e) Automatic Openings. Each ventilator shall be arranged to open automat-
ically after the outbreak of fire by the use of an approved automatic closing device
as defined in Chapter 43. The fusible link and operating cable shall hold each door
closed against a minimum 30-pound counterforce exerted by springs or counter-
weights. This minimum counterforce shall be exerted on each door through its
entire arc of travel and for a minimum 115 degrees. A manual control shall be
provided.
(f) Spring Actuation. Springs, when employed to actuate ventilator doors,
shall be capable of maintaining full required tension indefinitely. Springs shall not
be stressed more than 50 percent of their rated capacity and shall not be located
directly in the air stream, nor exposed to the elements.
(g) Location of Fusible Links. A fusible link shall be placed in the cable
control system on the underside of the ventilator at or above the roof line, or as
approved by the building official, and shall be so located as not to be affected by
the operation of sprinkler systems.
(h) Control. Remote, manual or electrical control shall provide for both open-
ing and closing of the ventilator doors for periodic testing and shall be located at a
point on the stage designated by the building official. When remote control of
ventilator is electrical, power failure shall not affect its instant operation in the
event of fire. Hand winches may be employed to facilitate operation of manually
controlled ventilators.
(i) Curb Construction. Curbs shall be constructed as required for the roof.
Gridirons
Sec. 3902. Gridirons, fly galleries and pinrails shall be constructed of non-
combustible materials, and fire protection of steel and iron may be omitted.
588
1982 EDITION 3902-3906
The head block well must be provided with an adequate strongback or lateral
brace to offset torque.
Rooms Accessory to Stage
Sec. 3903. In buildings having a stage, the dressing room sections, workshops
and storerooms shall be located on the stage side of the proscenium wall and shall
be separated from each other and from the stage by not less than a one-hour fire-
resistive occupancy separation, as defined in Chapter 5.
Proscenium Walls
Sec. 3904. A stage as defined in Section 420 shall be completely separated
from the auditorium by a proscenium .wall of not less than two-hour noncombusti-
ble construction. The proscenium wall shall extend not less than 4 feet above the
roof over the auditorium.
Proscenium walls may have, in addition to the main proscenium opening, one
opening at the orchestra pit level and not more than two openings at the stage floor
level, each of which shall be not more than 25 square feet in area.
All openings in the proscenium wall of a stage shall be protected by a fire
assembly having a one and one-half-hour fire-resistive rating. The proscenium
opening, which shall be the main opening for viewing performances, shall be
provided with a self-closing fire-resistive curtain as provided in U .B.C. Standard
No. 6-1.
Stage Floors
Sec. 3905. All parts of stage floors shall be of JYpe I construction except the
part of the stage extending back from and 6 feet beyond the full width of the
proscenium opening on each side, which may be constructed of steel or heavy
timbers covered with a wood floor of not less than 2-inch nominal thickness. No
part of the combustible construction except the floor finish shall be carried
through the proscenium opening. All parts of the stage floor shall be designed to
support not less than 125 pounds per square foot.
Openings through stage floors shall be equipped with tight-fitting trap doors of
wood of not less than 2-inch nominal thickness.
Platforms
Sec. 3906. (a) Ventilators. Enclosed platforms shall be provided with one or
more ventilators conforming to the requirements of Section 390 l . When more
than one ventilator is provided, they shall be so spaced as to provide proper
exhaust ventilation.
Ventilators shall not be required for enclosed platforms having a floor area of
500 square feet or less.
(b) Construction. Walls and ceiling of an enclosed platform in an assembly
room shall be of not less than one-hour fire-resistive construction.
Any usable space having headroom of 4 feet or more under a raised platform of
an assembly room shall be of not less than one-hour fire-resistive construction.
(c) Accessory Rooms. In buildings having an enclosed platform, the dressing-
room section, workshops, and storerooms shall be separated from each other and
589
3906-3908 UNIFORM BUILDING CODE
from the rest of the building by not less than a one-hour fire-resistive occupancy
separation as defined in Chapter 5, except that a chair-storage area having
headroom of not more than 4 feet need not be so separated.
Stage Exits
Sec. 3907. At least one exit not less than 36 inches wide shall be provided from
each side of the stage opening directly or by means of a passageway not less than
36 inches in width to a street or exit court. An exit stair not less than 2 feet 6 inches
wide shall be provided for egress from each fly gallery. Each tier of dressing
rooms shall be provided with at least two means of egress each not less than 2 feet
6 inches wide and all such stairs shall be constructed as specified in Chapter 33.
The stairs required in this section need not be enclosed.
Miscellaneous
.. Sec. 3908. A protecting hood shall be provided over the full length of the stage
switchboard .
590
1982 EDITION 4001-4005
Chapter 40
MOTION PICTURE PROJECTION ROOMS
General
Sec. 4001. (a) Scope. The provisions of this chapter shall apply where ribbon-
type cellulose acetate or other safety film is used in conjunction with electric arc,
Xenon or other light-source projection equipment which develops hazardous
gases, dust or radiation. Where cellulose nitrate film is used, projection rooms
shall comply with the Fire Code.
(b) Projection Room Required. Every motion picture machine projecting
film as mentioned within the scope of this chapter shall be enclosed in a projection
room. Appurtenant electrical equipment, such as rheostats, transformers and
generators, may be within the projection room or in an adjacent room of equiv-
alent construction.
There shall be posted on the outside of each projection room door and within
the projection room itself a conspicuous sign with l-inch block letters stating:
SAFETY FILM ONLY PERMITTED IN THIS ROOM.
Construction
Sec. 4002. Every projection room shall be of permanent construction consis-
tent with the construction requirements for the type of building in which the
projection room is located. Openings need not be protected.
The room shall have a floor area of not less than 80 square feet for a single
machine and at least 40 square feet for each additional machine. Each motion
picture projector, floodlight, spotlight or similar piece of equipment shall not be
used unless approved and shall have a clear working space not less than 30 inches
by 30 inches on each side and at the rear thereof, but only one such space shall be
required between two adjacent projectors.
The projection room and the rooms appurtenant thereto shall have a ceiling
height of not less than 7 feet 6 inches.
Exits
Sec. 4003. Exits shall be provided as required in Chapter 33.
Projection Ports and Openings
Sec. 4004. The aggregate of openings for projection equipment shall not
exceed 25 percent of the area of the wall between the projection room and the
auditorium.
All openings shall be provided with glass or other approved material so as to
completely close the opening.
Ventilation
Sec. 4005. (a) General. Ventilation shall be provided in accordance with the
provisions of this section.
(b) Projection Booth. I. Supply air. Each projection room shall be provided
with two or more separate fresh-air inlet ducts with screened openings terminating
within 12 inches of the floor and located at opposite ends of the room. Such air
591
4005-4007 UNIFORM BUILDING CODE
inlets shall be of sufficient size to permit an air change every three minutes. Fresh
air may he supplied from the general building air-conditioning system, but when
this is done it shall be so arranged that the projection booth will continue to receive
one change of air every three minutes, regardless of the status of the general air-
conditioning system.
2. Exhaust air. Each projection room shall be provided with one or more
exhaust-air outlets which may be manifolded into a single duct outside the booth.
Such outlets shall be so located as to ensure circulation throughout the room.
Projection room exhaust-air systems shall be independent of any other air systems
in the buildings. Exhaust-air ducts shall terminate at the exterior ofthe building in
such a location that the exhaust air cannot be readily recirculated into the supply-
air system. The exhaust system shall be mechanically operated and of such a
capacity as to provide a minimum of one change of air every three minutes. The
blower motor shall be outside the duct system. The projection room ventilation
system may also serve appurtenant rooms, such as the generator room and the
rewind room.
(c) Projection Equipment Ventilation. Each projection machine shall be
provided with an exhaust duct which will draw air from each lamp and exhaust it
directly to the outside of the building in such a fashion that it will not be picked up
by supply inlets. Such a duct shall be of rigid materials, except for a continuous
flexible connector approved for the purpose. The lamp exhaust system shall not be
interconnected with any other system.
I. Electric arc projection equipment. The exhaust capacity shall be 200
cubic feet per minute for each lamp connected to the lamp exhaust system, or as
recommended by the equipment manufacturer. Auxiliary air may be introduced
into the system through a screened opening to stabilize the arc.
2. Xenon projection equipment. The lamp exhaust system shall exhaust not
less than 300 cubic feet per minute per lamp nor less than that exhaust volume
required or recommended by the equipment manufacturer, whichever is the
greater. The external temperature of the lamp housing shall not exceed l30F.
when operating.
Miscellaneous Equipment
Sec. 4006. Each projection room shall be provided with rewind and film
storage facilities.
A maximum of four containers for flammable liquids not greater than 16-ounce
capacity and of a nonbreakable type may be permitted in each projection booth.
Sanitary Facilities
Sec. 4007. Every projection room shall be provided with a lavatory. Every
projection room serving an assembly occupancy shall be provided with a water
closet.
EXCEPTION: A water closet shall not be required in a projection room where
completely automated projection equipment is installed which does not require a
projectionist in attendance for projection or rewinding film.
592
1982 EDITION 42014203
Chapter 41
(SEE UNIFORM BUILDING SECURITY CODE)
Part VII
FIRE-RESISTIVE STANDARDS FOR
FIRE PROTECTION
Chapter42
INTERIOR WALL AND CEILING FINISH
General
Sec. 4201. Interior wall and ceiling finish shall mean interior wainscoting.
paneling or other finish applied structurally or for decoration. acoustical correc-
tion, surface insulation or similar purposes. Requirements for finishes in this
chapter shall not apply to trim defined as picture molds, chair rails, baseboards
and handrails; to doors and windows or their frames. nor to materials which are
less than Y2s inch in thickness cemented to the surface of walls or ceilings. if these
materials have flame-spread characteristics no greater than paper of this thickness
cemented to a noncombustible backing.
Foam plastics shall not be used as interior finish except as provided in Section
1712. For foam plastic trim. see Section 1705 (e).
Testing and Classification of Materials
Sec. 4202. (a) Testing. Tests shall be made by an approved testing agency to
establish surface-burning characteristics and to show that materials when
cemented or otherwise fastened in place will not readily become detached when
subjected to room temperatures of 300F. for 25 minutes. Surface-burning charac-
teristics shall be determined by one of the following methods:
I. The surface-burning characteristics as set forth in U.B.C. Standard No.
42-1.
2. Any other recognized method of test procedure for determining the surface-
burning characteristics of finish materials that will give comparable results to
those specified in method No. I above.
(b) Classification. The classes of materials based upon their flame-spread
index shall be as set forth in Table No. 42-A. The smoke density shall be no
greater than 450 when tested in accordance with U. B.C. Standard No. 42-1 in the
way intended for usc.
593
4203-4204 UNIFORM BUILDING CODE
as specified in Section 4202 and regulated for purposes of limiting flame spread
by the following provisions:
I . When walls and ceilings are required by any provision in this code to be of
fire-resistive or noncombustible construction, the finish material of any class
shall be applied directly against such fire-resistive construction or to furring strips
not exceeding I% inches applied directly against such surfaces. The intervening
spaces between such furring strips shall be filled with inorganic or Class I material
or shall be fire-stopped not to exceed 8 feet in any direction.
2. Where walls and ceilings are required to be of fire-resistive or noncombusti-
ble construction and walls are set out or ceilings are dropped distances greater
than specified in paragraph 1 of this section, Class I finish materials shall be used
except where the finish materials are protected on both sides by automatic
sprinkler systems or are attached to a noncombustible backing or to furring strips
installed as specified in paragraph 1. The hangers and assembly members of such
dropped ceilings that are below the main ceiling line shall be of noncombustible
materials except that in l)'pes III and V construction fire-retardant treated wood
may be used. The construction of each set-out wall shall be of fire-resistive
construction as required elsewhere in this code. See Section 2516 (f) for fire and
draft stops.
3. Wall and ceiling finish materials of all classes as permitted in this chapter
may be installed directly against the wood decking or planking of l)'pe IV heavy-
timber construction or to wood furring strips applied directly to the wood decking
or planking installed and fire-stopped as specified in paragraph 1.
4. All interior wall or ceiling finish other than Class I material which is less
than V4 inch thick shall be applied directly against a noncombustible backing
unless the qualifying tests were made with the material suspended from the
noncombustible backing.
594
1982 EDITION 42-A, 42-B
I 0- 25
II 26- 75
III 76-200
A I II III
E I II III
I I II II'
H I II IIF
B I II III
R-1 I II III
R-3 III III III'
M NO RESTRICTIONS
lin rooms in which personal liberties of inmates are forcibly restrained, Class I material
only shall be used.
2 0ver two stories shall be of Class II.
-'Flame-spread provisions are not applicable to kitchens and bathrooms of Group R,
Division 3 Occupancies.
4 Foam plastics shall comply with the requirements specified in Section 1712.
5finish classification is not applicable to interior walls and ceilings of exterior exit
balconies.
595
4301-4302 UNIFORM BUILDING CODE
Chapter 43
FIRE-RESISTIVE STANDARDS
General
Sec. 4301. In addition to all the other requirements of this code, fire-resistive
materials shall meet the requirements for fire-resistive construction given in this
chapter.
Fire-resistive Materials
Sec. 4302. (a) General. Materials and systems used for fire-resistive pur-
poses shall be limited to those specified in this chapter unless accepted under the
procedure given in Section 4302 (b) and shall conform to the following standards.
For standards for the specific materials of construction referred to in this chapter,
see the appropriate chapter in this code or the Uniform Building Code Standards
specifically regulating such materials as listed in Chapter 60.
The materials and details of construction for the fire-resistive systems
described in this chapter shall be in accordance with all other provisions of this
code except as modified herein.
(b) Tests. For the purpose of determining the degree of fire resistance
afforded, the materials of construction listed in this chapter shall be assumed to
have the fire-resistance rating indicated. Any material or assembly of materials of
construction tested in accordance with the requirements set forth in U. B.C.
Standard No. 43-1 shall be rated for fire resistance in accordance with the results
and conditions of such tests.
As an alternate to Tables Nos. 43-A, Band C, fire-resistive construction may be
approved by the building official on the basis of evidence submitted by the person
responsible for the structural design showing that the construction meets the
required fire-resistive classification.
Fire-resistive assemblies tested under U.B.C. Standard No. 43-1 shall not be
considered to be restrained unless evidence satisfactory to the building official is
furnished by the person responsible for the structural design showing that the
construction qualifies for a restrained classification in accordance with Section
43.144 of U .B.C. Standard No. 43-1. Restrained construction shall be identified
on the plans.
(c) Concrete. Grade A concrete is made with aggregates such as limestone,
calcareous gravel, trap rock, slag, expanded clay, shale, slate silicons or any other
aggregates possessing equivalent fire-resistive properties and containing 40 per-
cent or less quartz, chert or flint.
Grade B concrete is all concrete other than Grade A concrete and includes
concrete made with aggregates containing more than 40 percent quartz, chert or
flint.
(d) Pneumatically Placed Concrete. Pneumatically placed concrete without
coarse aggregate shall be classified as Grade A or B concrete in accordance with
aggregate used.
596
1982 EDITION 4303
597
4303-4304 UNIFORM BUILDING CODE
598
1982 EDITION 4304-4305
I
roof-ceiling construction.
EXCEPTION: Where penetrations are protected as shaft enclosures as required
in Section 1706.
When materials are incorporated into an otherwise fire-resistive assembly
which may change the capacity for heat dissipation, fire test results or other
substantiating data shall be made available to the building official to show that the
required fire-resistive time period is not reduced.
(b) Floors. Fire-resistive floors shall be continuous and all openings for
mechanical and electrical equipment shall be enclosed as specified in Section
1706.
EXCEPTIONS: I. Occasional pipes, conduits, sleeves and electrical outlets of
copper, sheet steel or ferrous construction may be installed within or through fire-
resistive floor systems, provided such installations do not unduly impair the required
fire resistance of the assembly.
599
4305-4306 UNIFORM BUILDING CODE
2. The provisions of this section shall not apply when such openings are in
accordance with the results of tests conducted pursuant to the provisions of Section
4302 (b).
..
(c) Roofs. Fire-resistive roofs may have the same openings as permitted for
floors and may contain other openings as permitted by this code. See Chapter 34
for skylight construction .
(d) Ceiling Panels. Where the weight of lay-in roof-ceiling panels, used as
part of fire-resistive floor-ceiling assemblies is not adequate to resist an upward
force of one pound per square foot, wire or other approved devices shall be
installed above the panels to prevent vertical displacement under such upward
force.
(e) Wiring in Plenums. Factory-assembled multiconductor cable which is
specifically listed for such use may be used within concealed spaces, such as
spaces over suspended ceilings, used for environmental air-handling purposes
when the building is protected by an automatic sprinkler system or the plenum
space is protected by a smoke-detection system which, upon activation of either
system, will cause the air-moving equipment to shut down.
I
doors, fire windows and fire dampers shall have a label or other identification
showing the fire protection rating. Such label shall be approved and shall be
permanently affixed. The label shall be applied at the factory where fabrication
and assembly are done. Inspection shall be made by an approved inspection
agency during fabrication and assembly.
600
1982 EDITION 4306
(d) Installation of Fire Door Hardware, Fire Door Frames and Anchorage.
Approved fire door hardware and fire door frames including the anchorage
I
thereof shall be installed in accordance with their listing.
(e) Fire-resistive Thsts. The fire-protection rating of all types of required fire
assemblies shall be determined in accordance with the requirements specified in
U.B.C. Standards No. 43-2 and No. 43-4.
(f) Hardware. Every fire assembly required to have a three-hour fire-protec-
tion rating shall be of an automatic-closing type as specified in Section 4306 (b).
Every fire assembly required to have a one and one-half hour, one-hour, or three-
fourths-hour fire-protection rating shall be of an automatic- or self-closing type as
specified in Section 4306 (b).
EXCEPTIONS: I. Dual fire-exit doors shall have closing devices as specified in
Chapter 33.
2. Swinging fire door assemblies shall be automatic closing by a smoke detector
when installed in the locations listed below. All hold-open devices shall be an
approved type which will release the door in the event of power failure.
A. Cross-corridor doors.
B. Horizontal exit doors.
C. Area separation walls other than doors serving as the entrance into hotel guest
rooms or apartment dwelling units.
D. Occupancy separation walls having a minimum two-hour fire-resistive time
period.
Heat-actuated devices used in automatic fire assemblies providing three-hour
fire protection shall be installed, one on each side of the wall at the top of the
opening and one on each side of the wall at the ceiling height where the ceiling is
more than 3 feet above the opening.
Fire assemblies protecting openings required to have one and one-half, one or
three-fourths-hour fire-protection rating, and which are not exit doors, may be
activated in a similar manner or by a single fusible link in the opening incorpo-
rated in the closing device.
Smoke detectors shall meet the approval of the building official as to installa-
tion and locations and shall be subject to such periodic tests as may be required.
(g) Glazed Openings in Fire Doors. Glazed openings in fire doors shall not
be permitted in a fire assembly required to have a three-hour fire-resistive rating.
The area of glazed openings in a fire door required to have one and one-half
hour or one-hour fire-resistive rating shall be limited to 100 square inches with a
minimum dimension of 4 inches. When both leaves of a pair of doors have
observation panels, the total area of the glazed openings shall not exceed 100
square inches for each leaf.
Glazed openings shall be limited to 1296 square inches in wood and plastic-
faced composite or hollow metal doors, per light, when fire-resistive assemblies
are required to have a three-fourths-hour fire-resistive rating.
(h) Glazed Openings in Fire Windows. Windows required to have a three-
fourths-hour fire-resistive rating may have an area not greater than 84 square feet
with neither width nor height exceeding 12 feet.
601
4306-4307 UNIFORM BUILDING CODE
(i) Glazing. Glazing shall be glass not less than 1/4 inch thick and shall be
reinforced with wire mesh No. 24 gauge or heavier embedded in the glass with
openings not larger than 1 inch square. Glass not conforming to these require-
ments may be used when qualified by tests in accordance with U.B.C. Standard
No. 43-2 (for doors) or No. 43-4 (for windows). Glass shall be held in place by
steel glazing angles except that in casement windows wire clips may be used.
(j) Fire Dampers. Except where fire tests have shown that fire dampers are not
necessary to maintain the required fire resistance of the construction, fire dampers
complying with the requirements of U .B.C. Standard No. 43-7 shall be installed
and be readily accessible for servicing in the following locations:
I. Duct penetrations of area or occupancy separation walls. When the wall is
required to have a rating of more than two hours, a fire door meeting the
requirements ofU.B.C. Standard No. 43-2 is required.
2. Ducts passing through horizontal exit walls.
3. Duct penetrations of fire-rated shafts unless exhaust or return-air sub-ducts
extend 22 inches vertically in a vented shaft.
4. Ducts penetrating the ceiling of fire-resistive floor-ceiling or roof-ceiling
assemblies.
5. Ducts penetrating fire-rated corridor walls having openings into the
corridor.
(k) Tin-clad Doors. If constructed as specified in U .B.C. Standard No. 43-3,
tin-clad fire doors installed on each side of openings requiring protection shall be
considered as providing a fire assembly having a three-hour fire-protection rating,
provided each door bears the label of an approved testing agency showing the
classification thereof.
(I) Installation. Fire assemblies shall be installed in accordance with their
listing.
I (m) Signs. When required by the building official, a sign shall be displayed
permanently near or on each required fire door in letters not less than I inch high
to read as follows:
FIRE DOOR
DO Nar OBSTRUCT
Roof Coverings
Sec. 4307. Fire-retardant roof coverings shall be as specified in Sections 3202
(b) and 3203.
602
TABLE NO. 43-A-MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR
VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS ....
:i
N
MINIMUM THICKNESS OF m
INSULATING MATERIAL FOR
FOLLOWING FIRE-RESISTIVE
c
STRUCTURAL
PARTS TO BE ITEM PERIODS (In Inches) 3
0
PROTECTED NUMBER INSULATING MATERIAL USED 4Hr. 3Hr. 2Hr. 1 Hr. z
1 Grade A concrete, members 6"x 6" or greater (not including 2Yz 2 1Yz 1
sandstone, granite and siliceous gravel).1
8 4" Hollow clay tile in two 2" layers; Yz" mortar between tile and 4
column; Y." metal mesh (wire diameter = .046") in horizontal
joints; tile fill.1
9 2" Hollow clay tile; V." mortar between tile and column; Y." metal 3
mesh (.046" wire diameter) In horizontal joints; Grade A concrete
filii; plastered with V." gypsum plaster.
10 2" Hollow clay tile with outside wire ties (.08" diameter) at each 3
course of tile or Y." metal mesh (.046" diameter wire) in horizontal
joints; Grade A concrete fill 1 extending I " outside colwnn on all sides .
(Continued)
TABLE NO. 43-A-MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR
VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS"-(Continued)
MINIMUM THICKNESS OF
INSULATING MATERIAL FOR
STRUCTURAL
PARTS TO BE ITEM
FOLL~~:~g:~,~~~~~~~~TIVE
PROTECTED NUMBER INSULATING MATERIAL USED 4Hr. 3Hr. 2Hr. 1 Hr.
2" Hollow clay tile with outside wire ties (.08" diameter) at each
II course of tile with or without Grade A concrete fill; %" mortar be- 2
tween tile and column.
Steel Portland cement plaster over metal lath wire tied to %" cold-rolled
Columns 12 vertical channels with No. 18 gauge wire ties spaced 3" to 6" on 2Y2 2
;.
and All center. Plaster mixed I :2 Y2 by volume, cement to sand.
Members
of Primary Vermiculite concrete, I :4 mix by volume over paper backed wire
Trusses fabric lath wrapped directly around column with additional 2" x
13 2" No. 16/16 gauge wire fabric placed Y." from outer concrete 2
surface. Wire fabric tied with No. 18 gauge wire spaced 6" on
center for inner layer and 2" on center for outer layer.
c:
Perlite or vermiculite gypsum plaster over metal lath wrapped z
14
around column and furred IY." from column flanges. Sheets
lapped at ends and tied at 6" intervals with No. 18 gauge tie wire. !Yz I ~
::u
Plaster pushed through to flanges. 3:
IJI
c:
r
c
z
C)
0
0
lfi
....
~
m
Perlite or vermiculite gypsum plaster over self-furring metal lath 0
15 wrapped directly around column, lapped I" and tied at 6" in- IV. I Y, I 3
tervals with No. 18 gauge wire. 0
z
Perlite or vermiculite gypsum plaster on metal lath applied 10 '!."
16 cold-rolled channels spaced 24 inches a par! verrically and wrapped I 1/2
flat wise around column.
(Continued)
TABLE NO. 43-A-MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR
VARIOUS NONCOMBUSTIBLE INSULATING MATERIALSL-(Continued)
MINIMUM THICKNESS OF
INSULATING MATERIAL FOR
STRUCTURAL
PARTS TO BE ITEM FOLL~~:~gt~~~~~~~~~~TIVE
PROTECTED NUMBER INSULATING MATERIAL USED 4Hr. 3 Hr. 2Hr. 1 Hr.
3 4
Multiple layers of '!:!" gypsum wallboard adhesively secured to
column flanges and successive layers. Wallboard applied without
20 horizontal joints. Corner edges of each layer staggered. Wall- 2 I
board layer below outer layer secured to column with doubled No.
18 gauge wire ties spaced 15" on center. Exposed corners taped
and treated.
Steel Three layers of Y." Type "X" gypsum wallboard~ First and second
Columns layer held in place by Y," diameter by I Y." long ring shank nails
and All with Y,." diameter heads spaced 24" on center at corners. Middle
Members 21 layer also secured with metal straps at mid-height and 18" from 1/,
of Primary each end, and by metal corner bead at each corner held by the
Trusses metal straps. Third layer attached to corner bead with I" long gyp-
sum wallboard screws spaced 12" on center. c:
z
3
~
::0
Three layers of Y." Type "X" gypsum wallboard, each layer screw i:
attached to I Y." steel studs (No. 25 gauge) at each corner of Ill
column. Middle layer also secured with No. 18 gau~e double c:
22 strand tie wire, 24" on center for inner layer, No.6 by I Y." spaced IY, ;=
12" on center for middle layer and No.8 by 2'!." spaced 12" on 2
center for outer layer.
z
C)
0
0
~
....
!m
0
Wood-fibered gypsum plaster mixed I: I by weight gypsum to sand
Steel aggregate applied over metal lath. Lath lapped I" and tied 6" on 3
Columns 0
center at all ends, edges and spacers with No. 18 gauge tie wire. z
and All Lath applied over 'lz" spacers made of 'li" furring channel with 2"
Members 23 IY,
legs bent around each corner. Spacers located I" from top and
of Primary bottom of member and a maximum of 40" on center and wire tied
Trusses with a single strand of No. 18 gauge wire. Corner bead tied to the
(Cont'd.) lath at 6" on center along each corner to provide plaster thickness.
(Continued)
TABLE NO. 43-A-MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR
VARIOUS NONCOMBUSTIBLE INSULATING MATERIALSIL....-(Continued)
MINIMUM THICKNESS OF
INSULATING MATERIAL FOR
STRUCTURAL FOLLOWING FIRERESISTIVE
ITEM PERIODS (In lnchesl
PARTS TO BE
PROTECTED NUMBER INSULATING MATERIAL USED 4Hr. 3Hr. 2Hr. 1 Hr.
long screws installed in the vertical leg of the bottom corner angles.
The outer layer of wallboard is attached with No. 6 2 !/.o long
screws spaced 8" on center. One screw is also installed at the mid-
depth of the bracket in each layer. Bottom corners are finished as
described above.
Bonded
Pretensioned Grade A 6 Beams or girders 47 37 2Y, 7 IY2
Reinforcement 30 concrete Solid slabs s 2 IY2 I
in Prestressed
Concrete 5
Bonded or Grade A or B Concrete
Unbonded Unrestrained Members:
Posttensioned Solid Slabss 2 I'/'
31 Beams and Girders I 1
Tendons in
Prest res sed 8 in. wide 4Y2 2Y, I:V..
Concrete 5 JO > 12in. wide 3 2Y, 2 I y,
(Continued)
....
01 TABLE NO. 43-A-MINIMUM PROTECTION OF STRUCTURAL PARTS BASED ON TIME PERIODS FOR
0 VARIOUS NONCOMBUSTIBLE INSULATING MATERIALS"-(Continued)
MINIMUM THICKNESS OF
INSULATING MATERIAL FOR
STRUCTURAL ITEM FOLLOWING FIRE-RESISTIVE PERIODS
PARTS TO BE tiSULATING MATERIAL USED
NUMBER (In Inches)
PROTECTED
4Hr. 3Hr. 2Hr. 1 Hr.
Hollow brick units at least 60 percent solid, cells filled with ::D
3:
8 perlite loose fill insulation. 8 IJJ
c:
4-in. nominal thick units at least 75 percent solid backed with r=
c
a hat shaped metal furring channel '!. inch thick formed from
0.021-inch sheet metal attached to the brick wall on 24-inch z
C)
9 centers with approved fasteners; and '12-inch Type X gypsum 54
0
wallboard 7 attached to the metal furring strips with l-inch long 0
TypeS screws spaced 8 inches on center.
~
.....
Brick of Gay Cavity wall consisting of two 3-inch nominal thick solid clay
!m
or Shale 10 units with air space_ 8 c
3
One cell in wall thickness, units at least 50 percent solid, plastered 0
II each side with Y. gypsum plaster_ 4'1. z
Hollow Clay
Tile, Non- 12 Two cells in wall thickness, units at least 45 percent solid. 6
load-bearing
(End or Two cells in wall thickness, units at least 45 percent solid.
Side Con- 13 Plastered each side withY. gypsum plaster. 7
struction)
Two cells in wall thickness, units at least 60 percent solid.
14 Plastered each side with Y." gypsum plaster. 5
01
..... (Continued)
w
TABLE NO. 43-B--RATED FIRE-RESISTIVE PERIODS FOR VARIOUS WALLS AND PARTITIONS 1--(Continued)
MINIMUM FINISHED THICKNESS
FACTTO-FACE'
ITEM (lnlnc~Ms)
MATERIAL NUMBER CONSTRUCTION
4Hr. 3Hr. 2Hr. 1 Hr.
Hollow Clay Three cells in wall thickness, units at least 43 percent solid.
Tile, Load- 24 Plastered each side with Y, gypsum plaster. 9
bearing
(End or Three cells in wall thickness, units at least 40 percent solid.
25 Plastered each side with Y, gypsum plaster. 13
Side Con-
struction) Hollow cavity wall consisting of two 4" nominal clay tile units
(at least 40 percent solid) with air space between. Plastered one
26 side (exterior) with % portland cement plaster and other side 10
with Y," gypsum plaster. Portland cement plaster mixed I :3 by
volume, cement to sand.
.
Solid
Concrete 34 percent. (Three-fourths as much for welded wire Grade B z
fabric.) 1Yz 6Yz sv, 44
One 2" unit cored 15 percent maximum and one 4" unit cored
35 25 percent maximum with V." mortar filled collar joint. Unit 6,
positions reversed in alternate courses.
One 2" unit cored 15 percent maximum and one 4" unit cored
40 percent maximum with Y. " mortar filled collar joint. Plas-
36 tered one side with V. gypsum plaster. Two wythes tied together 6'!.
Glazed or every fourth course with No. 22 gauge corrugated metal ties.
Unglazed
Facing Tile, One unit with three cells in wall thickness, cored 29 percent
Nonload- 37 maximum. 6
bearing
One 2" unit cored 22 percent maximum and one 4" unit cored
41 percent maximum with y," mortar filled collar joint. Two
38 wythes tied together every third course with No. 22 gauge cor- 6
ruga ted metal ties.
One 4" unit cored 25 percent maximum with 1;4" gypsum
39 plaster on one side. 4'!.
One 4" unit with two cells in wall thickness, cored 22 percent
maximum. 4
40
(Continued)
TABLE NO. 43-8--RATED FIRE-RESISTIVE PERIODS FOR VARIOUS WALLS AND PARTITIONS 1-(Contlnued)
MINIMUM FINISHED THICKNESS
FACT'JO.FACE2
ITEM (lnlncMs)
MATERIAL NUMBER CONSTRUCTION
4Hr. 3Hr. 2Hr. 1 Hr.
Solid Neat
Wood % w by No. 16 gauge cold-rolled channels, I r on center with 2.5-
Fibered 50 pound flat metal lath applied to one face and tied with No. 18 24
Gypsum gauge wire at 6w spacing. Neat gypsum plaster applied each side.
Plaster
7
Solid One full-length layer y,w Type "X" gypsum wallboard 1aminated
Gypsum to each side of I" full length V-edge gypsum coreboard with
Wallboard 51 approved laminating compound. Vertical joints of face layer 24
Partition and core board staggered at least 3".
7
One full-length layer of Y." Type "X" gypsum wallboard attached
to both sides of wood or metal top and bottom runners laminated
to each side of l"x6" full-length gypsum coreboard ribs
52 spaced 24" on center with approved laminating compound. Ribs 2Y44
Hollow centered at vertical joints of face plies and joints staggered 24"
(Studless) in opposing faces. Ribs may be recessed 6w from the top and
Gypsum bottom.
Wallboard
Partition I" regular gypsum "V" edge full-length backing board attached
to both sides of wood or metal top and bottom runners with
nails or I Y, drywall screws at 24" on center. Minimum width
53 of runners I Y," . Face layer of y, n regular full-length gypsum 4Y,4
wallboard laminated to outer faces of backing board with
approved laminating compound.
(Continued)
TABLE NO. 43-B-RATED FIRE-RESISTIVE PERIODS FOR VARIOUS WALLS AND PARTITIONS 1--(Continued)
MINIMUM FINISHED THICKNESS
FACE-TO-FACE 2
ITEM (In Inches)
MATERIAL NUMBER CONSTRUCTION 4Hr. 3Hr. 2Hr. 1 Hr.
MINIMU~rb~~~~~~CE 2
(lnlnchnl
ITEM
MATERIAL NUMBER CONSTRUCTION 4Hr. 3Hr. 2Hr. 1Hr.
2"x 4" wood studs 16" on center withY." perforated gypsum lath
Wood Studs with I" hexagonal mesh of No. 20 gauge wire furred out ?'[," and
Interior I" perlite or vermiculite ~~sum plaster each side. Lath nailed with
Partition 1Y." by No. 13 gauge by head plasterboard blued nails spaced
with Plaster 65 11 5" on center. Mesh attached by I~" by No. 12 gauge by Y." head 6Y.
Each Side nails withY." furrings, spaced 8" on center. For three-coat work
the plaster mix for the second coat shall not exceed 100 pounds of
gypsum to 2 Yz cubic feet of aggregate.
2"x 4" wood studs 16" on center with two layers%" regular gyp-
sum wallboard 7each side, 4d cooler nails 8 on center first layer, Sd
cooler nails 8" on center second layer with laminating compound
6911 between layers. Joints staggered. First layer applied full length ver- 5
tically, second layer applied horizontally or vertically.
Wood
Studs-
Interior 2"x 4" wood studs 16" on center with two layers Yz" regular gyp-
Partition sum wallboard 7applied vertically or horizontally each side, joint
7011 staggered. Nail base layer with Sd cooler nails at 8" on center, face 5Y,
with layer with Sd cooler nails at 8 on center.
Gypsum
Wallboard 2" x 4" wood studs 24" on center with y, Type "X" gypsum
Each Side wallboard7 applied vertically or horizontally nailed with 6d cooler
7Jl1 nails 7 on center with end joints on nailing members. Stagger joints 4Y.
on each side.
2"x 4" fire-retardant treated wood studs spaced 24" on center wi~~
one layer of%" thick Type "X" gypsum wallboard 7applied wit
72ll face paper grain (long dimension) parallel to studs. Wallboard at 4Y.4
tached with 6d cooler nails spaced 7 on center.
(Continued)
TABLE NO. 43-B-RATED FIRE-RESISTIVE PERIODS FOR VARIOUS WALLS AND PARTITIONS" 1-(Continued)
MINIMUM FINISHED THICKNESS
FACETO-FACE2
(In Inches)
ITEM
MATERIAL NUMBER CONSTRUCTION 4Hr. 3Hr. 2Hr. 1 Hr.
2"x 4" wood studs 16" on center with two layers Yo" Type "X"
gypsum wallboard7each side. Base layers applied vertically and
Wood nailed with 6d cooler nails 9" on center. Face layer applied ver-
Studs- 73 11 tically or horizontally and nailed with 8d cooler nails 7" on center. 6
Interior For nail-adhesive application, base layers are nailed 6" on center.
Partition Face layers applied with coating of approved wallboard adhesive
With and nailed 12" on center.
Gypsum
Wallboard 2" x 3" fire-retardant treated wood studs spaced 24" on center with
Each Side one layer of Yo" thick Type "X" gypsum wallboard 7applied with
7411 face paper grain (long dimension) at right angles to studs. 3Y,4
Wallboard attached with 6d cement coated box nails spaced 7" on
center.
Exterior surface with 3f.. drop siding or Yo exterior type plywood
over \12 gypsum sheathing on 2"x 4" wood studs at 16" on center;
interior surface treatment as required for one-hour rated exterior c
or interior 2"x 4" wood stud partitions. Gypsum sheathing nailed
z
7511
with 1% by No. II gauge by ;.-;, head galvanized nails at 8" on Varies ~:D
center. Siding nailed with 7d galvanized smooth box nails.
Plywood nailed with 6d galvanized siding or casing nails, 6" on 3:::
center around the perimeter and 12" on center elsewhere. ID
c
;=
Exterior or c
Interior 2"x 4" wood studs 16" on center with metal lath and 3f.. exterior z
cement plaster 12 on each side. Lath attached with 6d common nails
Walls
7611 7" on center driven to I on center driven to I minimum penetra-
tion and bent over. Plaster mix I :4 for scratch coat and I :5 for
5Y. "
0
0
brown coat, by volume, cement to sand . ~
....
~
m
2" x 4" wood studs 16" on center withY." exterior cement plaster c
(measured from the face of studs) on the exterior surface with 3
77ll interior surface treatment as required for interior wood stud Varies 0
z
partitions in this table. Plaster mix I :4 for scratch coat and I :5 for
brown coat, by volume, cement to sand.
(Continued)
TABLE NO. 43-~TED FIRE-RESISTIVE PERIODS FOR VARIOUS WALLS AND PARTITIONS 1-(Contlnued)
MINIMUM FINISHED THICKNESS
FACETO-FACE2
ITEM (In lncheal
MATERIAL NUMBER CONSTRUCTION
4Hr. 3Hr. 2Hr. 1 Hr.
2" x 6" fire-retardant treated wood studs 16" on center. Interior face has two layers
of 'h" Type "X" gypsum wallboard7 with the base layer placed vertically and
attached with 6d box nails 12" on center. The face layer is placed horizontally and
attached with 8d box nails 8" on center at joints and 12" on center elsewhere. The
exterior face has a base layer of 'h" Type "X'' gypsum wallboard placed vertically
gou with 6d box nails 8" on center at joints and 12" on center elsewhere. An approved
buildinf paper is next applied, followed by self-furred exterior lath attached with
211!", I gauge galvanized roofing nails with a "h" diameter head and spaced 6" on SY.
center along each stud. Exterior cement plaster consisting of a 1-7" brown coat is
then applied. The scratch coat is mixed in the proportion of I :3 by weight, cement
to sand with I 0 pounds of hydrated lime and 3 pounds of asbestos fiber per sack of
cement. The brown coat is mixed in the proportion of I :4 by weight, cement to sand
with the same amounts of hydrated lime and asbestos fiber used in the scratch coat.
Exterior or
Interior
Walls
2" x 6" wood studs 16" on center. The exterior face has a layer of 'h" Type "X"
gypsum wallboard7 placed vertically with 6d box nails 8" on center at joints and 12"
on center elsewhere. An approved building paper is next applied, followed by I" by
No. 18 ga~ge self-furred exterior lath attached with 8d by 2\.7" long galvanized
roofing nails spaced 6" on center along each stud. Exterior cement plaster consist-
ing of a 1-7" scratch coat, a bonding agent and a W brown coat and a fmish coat is
then applied. The scratch coat is mixed in the proportion of I :3 by weight, cement
to sand with I 0 pounds of hydrated lime and 3 pounds of asbestos fiber per sack of
8P 1 cement. The brown coat is mixed in the proportion of I :4 by weight, cement to sand
with the same amounts of hydrated lime and asbestos fiber used in the scratch coat. 8~
The interior is covered with "h" gypsum lath with I" hexagonal mesh of No. 20
~ woven wire lath furred out y,. and I" r,:rJite or vermiculite gypsum plaster.
Lath nailed with I 14" by No. 13 ga~ge by 1% head plasterboard blued nails spaced
s on center. Mesh attached by I'14" by No. 12 ga~ge by "h" head nails with "h"
furrings, spaced 8" on center. The plaster mix shall not exceed 100 pounds of
gypsum to 21-7 cubic feet of aggregate.
2" x 6" wood studs at 16" on center. The exterior face has a layer of 5111"
'JYpe "X" gypsum wallboanP placed vertically with 6d box nails 8" on
center at joints and 12" on center elsewhere. An approved building paper
is next applied, followed by I Vz" by No. 17 gauge self-furred exterior lath
attached with 8d by 2\12" long galvanized roofing nails spaced 6" on
center along each stud. Exterior cement plaster consisting of a \12'' scratch
coat, and a \12'' brown coat is then applied. The plaster may be placed by
machine. The scratch coat is mixed in the proportion of 1:4 by weight,
82 11 plastic cement to sand. The brown coat is mixed in the proportion of I :5 8Y,
by weight, plastic cement to sand. The interior is covered with W'
gypsum lath with I" hexagonal mesh of No. 20 gauge woven wire lath
furred out 'Y16" and I" perlite or vermiculite gypsum plaster. Lath nailed
with II-i!" by No. 13 gauge by I%o" head plasterboard blued nails spaced
Exterior or 5" on center. Mesh attached by 14' by No. 12 gauge by W' head nails
Interior with ~ furrings, spaced 8" on center. The plaster mix shall not exceed
Walls 100 pounds of gypsum to 2\12 cubic feet of aggregate.
type may be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard and the joints on the face layer
are reinforced and the entire surface is covered with a minimum of \116-inch gypsum veneer plaster. The gypsum base for veneer plaster and the l
veneer plaster shall comply with U. B.C. Standard No. 4 7-15. :~::
ssee also Footnote 2. The equivalent thickness may include the thickness of portland cement paster or I .5 times the thickness of gypsum plaster c:
applied in accordance with the requirements of Chapter 47 of the code. z
~
9 Studs are welded truss wire studs with No. 7 gauge flange wire and No. 7 gauge truss wires.
10Nailable metal studs consist of two channel studs spot welded back-to-back with a crimped web forming a nailing groove.
:::D
11 Plywood may be installed between the fire protection and the wood studs on either the interior or exterior side of the wood frame assemblies in this s:::
table, provided the length of the fasteners used to attach the fire protection are increased by an amount at least equal to the thickness of the plywood. IJI
121 h;ee pounds of asbestos fiber added for each bag of portland cement. c:
r=
0
z
C)
0
0
lil
.....
IN
TABLE NO. 43-C-MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS 1 m
c
THICKNESS OF FLOOR
OR ROOF SLAB
MINIMUM THICKNESS
OF CEILING
3
0
ltam
IIRI~ ... llnl1""'"'' z
FLOOR OR ROOF CONSTRUCTION Number CEILING CONSTRUCTION 4 Hr. 3 Hr. 2 Hr. 1 Hr. 4Hr. 3Hr. 2Hr. 1 Hr.
Concrete-Excluding Ex-
panded Clay Shale or
Slate (by Rotary Kiln I Slab (no ceiling required). 6Y2 3\-'22
Process) or Expanded
Slag.
Concrete - Expanded Clay
Shale or Slate (by Rotary
Kiln Process) or Expanded 2 Slab (no ceiling required). 5 4 3
Slag.
Slab with suspended ceil
ing of vermiculite gypsum
plaster over metal lath at-
Reinforced Concrete tached to 3.4 cold-rolled
Joists 3 channels spaced 12" on 3 2
center. Ceiling located 6"
minimum below joists.
(Continued)
TABLE NO. 43-C-MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS 1--{Continued)
THICKNESS OF FLOOR MINIMUM THICKNESS
OR ROOF SLAB OF CEILING
Item (In Inches) (In Inches)
FLOOR OR ROOF CONSTRUCTION Number CEILING CONSTRUCTION
4Hr. 3Hr. 2Hr. 1Hr. 4Hr. 3Hr. 2Hr. 1 Hr.
(Continued)
TABLE NO. 43-C-MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS 1-(Continued)
THICKNESS OF FLOOR MINIMUM THICKNESS
OR ROOF SLAB OF CEILING
Item (In Inches} (In Inches}
FLOOR OR ROOF CONSTRUCTION Numbe CEILING CONSTRUCTION 4Hr. 3Hr. 2Hr. 1 Hr. 4Hr. 3Hr. 2Hr. 1 Hr.
(Continued)
TABLE NO. 43-C--MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS 1-(Contlnued)
(Continued)
TABLE NO. 43-C-MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS 1-(Continued)
THICKNESS OF FlOOR MINIMUM THICKNESS
OR ROOF SLAB OF CEILING
FLOOR OR (In Inches) (In Inches)
II em
ROOF CONSTRUCTION Number CEILING CONSTRUCTION
4 Hr. 3 Hr. 2Hr. 1 Hr. 4Hr. 3 Hr. 2 Hr. 1 Hr.
(Continued)
TABLE NO. 43-C-MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS 1-(Continued)
THICKNESS OF FLOOR MINIMUM THICKNESS
OR(I~~~:t!;,'B ~r.~:~:!~?
FLOOR OR ROOF CONSTRUCTION IN~:.r::.. CEILING CONSTRUCTION 4Hr. 3Hr. 2Hr. 1 Hr. 4Hr. 3Hr. 2Hr. 1 Hr.
(Continued)
TABLE NO. 43-C-MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS 1--(Contlnued)
THICKNESS OF FLOOR MINIMUM THICKNESS
OR ROOF SLAB OF CEILING
Item (In Inches) (In Inches)
FLOOR OR ROOF CONSTRUCTION Number CEILING CONSTRUCTION 14Hr. 13 Hr. 12 Hr. 1 Hr. 4Hr. 3Hr. 2Hr. 1 Hr.
(Continued)
TABLE NO. 43-C-MINIMUM PROTECTION FOR FLOOR AND ROOF SYSTEMS 8 1-(Continued)
THICKNESS OF FLOOR MINIMUM THICKNESS
OR ROOF SLAB OF CEILING
(In Inches) (In Inches)
Item
FLOOR OR ROOF CONSTRUCTION !NUmber CEILING CONSTRUCTION 4 Hr. 3 Hr. 2 Hr. 1 Hr. 4Hr. 3 Hr. 2 Hr. 1 Hr.
Perlite concrete proportioned I :6
(portland cement to perlite aggre-
gate) poured to Ifs-inch thickness
above top of corrugations of IVI6-
inch-deep galvanized steel deck
maximum span 8' 0" for No. 24
gauge or 6' 0" for No. 26 gauge with
deck supported by individually pro-
tected steel framing. Approved
polystyrene foam plastic insulation
board having a flame spread not
exceeding 75 (I" to 4" thickness
with vent holes which approximate
3 percent of the board surface area)
placed on top of perlite slurry. A 2' 32 None Varies
by 4' insulation board contains six
23!4' diameter holes. Boards covered
with 2V4' minimum perlite concrete c:
slab. Slab reinforced with mesh z
consisting of No. 19 gauge (0.041"
galvanized) steel wire twisted ~
:II
together to form 2" hexagons with :1:
straight No. 16 gauge (0.0625" gal- Ul
vanized) steel wire woven into mesh c:
and spaced 3". Alternate slab rein- ;::::
forcement may consist of 4 by 8, 2
No.l214SWG,or2by2,No.14114
z
Ci')
SWG welded wire fabric. Fire-retar-
dant roof covering on top. 8
Iii
....
!m
FOOTNOTES TO TABLE NO. 43-C c
a<Jeneric fire resistance ratings (those not designated by company code letter) as listed in the Fire Resistance Design Manual, Tenth Edition 3
(1981 ), as published by the Gypsum Association-may be accepted as if herein listed. 0
1Staples with equivalent holding power and penetration may be used as alternate fasteners to nails for attachment to wood framing.
z
2The thickness may be reduced to 3 inches where limestone aggregate is used.
3For all of the construction with gypsum wallboard described in Table No. 43-C, gypsum base for veneer plaster of the same size, thickness and
core type may be substituted for gypsum wallboard, provided attachment is identical to that specified for the wallboard and the joints on the face
layer are reinforced and the entire surface is covered with a minimum of \116-inch gypsum veneer plaster. The gypsum base for veneer plaster and
the veneer plaster shall comply with U.B.C. Standard No. 47-15.
4 Slab thickness over steel joists measured at the joists for metal lath form and at the top of the form for steel form units.
5Portland cement plaster with 40 pounds of asbestos fiber per bag of cement.
6Portland cement plaster with 15 pounds of hydrated lime and 3 pounds of asbestos fiber per bag of cement.
70ne-inch by No. 20 gauge hexagonal wire mesh installed below lath and tied to each furring channel at joints between lath.
8No. 14 gauge wires spaced 11.3 inches on center or 10 inches on center (for channel spacing of 16 inches and 12 inches, respectively) installed
below lath sheets in a diagonal pattern. Wires tied to furring channels or clips at lath edges.
9furring channels spaced 12 inches on center.
IOSix-inch hollow clay tile with 2-inch concrete slab above.
''Four-inch hollow clay tile with 1 '12-inch concrete slab above.
12Thickness measured to bottom of steel form units.
Dfive-eighths inch of vermiculite gypsum plaster plus '12 inch of approved vermiculite acoustical plastic.
' 4Double wood floor may be either of the following:
(a) Subfloorof l-inch nominal boarding, a layer of asbestos paper weighing not less than 14 pounds per 100 square feet and a layer of l-inch
nominal tongue-and-groove finish flooring; or
(b) Subfloor of l-inch nominal tongue-and-groove boarding or '12-inch interior-type plywood with exterior glue and a layer of l-inch nominal I
tongue-and-groove finish flooring or ~-inch interior-type plywood finish flooring or a layer of Type I Grade M-1 particleboard not less than t~
~ inch thick. f
I5The ceiling may be omitted over unusable space, and flooring may be omitted where unusable space occurs above. ::;:
16Tbickness measured on top of steel deck unit.
4401-4405 UNIFORM BUILDING CODE
Part VIII
Chapter 44
PROTECTION OF PEDESTRIANS
DURING CONSTRUCTION OR DEMOLITION
General
Sec. 4401. No person shall use or occupy a street, alley or public sidewalk for
the performance of work under a building permit except in accordance with the
provisions of this chapter.
No person shall perform any work on any building or structure adjacent to a
public way in general use by the public for pedestrian travel, unless the pedestri-
ans are protected as specified in this chapter.
Any material or structure temporarily occupying public property, including
fences and walkways, shall be adequately lighted between sunset and sunrise.
Temporary Use of Streets and Alleys
Sec. 4402. The use of public property shall meet the requirements of the public
agency having jurisdiction. Whenever requested, plot plans and construction
details shall be submitted for review by the agencies concerned.
Storage on Public Property
Sec. 4403. Material and equipment necessary for work to be done under a
permit shall not be placed or stored on public property so as to obstruct free and
convenient approach to and use of any fire hydrant, fire or police alarm box,
utility box, catch basin or manhole or so as to interfere with the free flow of water
in any street or alley gutter.
Mixing Mortar on Public Property
Sec. 4404. The mixing or handling of mortar, concrete or other material on
public property shall be done in a manner that will not deface public property or
create a nuisance.
Protection of Utilities
Sec. 4405. A substantial protective frame and boarding shall be built around
and over every street lamp, utility box, fire or police alarm box, fire hydrant, catch
basin and manhole that may be damaged by any work being done under the
permit. This protection shall be maintained while such work is being done and
shall not obstruct the normal functioning of the device.
642
1982 EDITION 4406-4407
Walkway
Sec. 4406. A walkway not less than 4 feet wide shall be maintained on the
sidewalk in front of the building site during construction, alteration or demolition
unless the public agency having jurisdiction authorizes the sidewalk to be fenced
and closed. Adequate signs and railings shall be provided to direct pedestrian
traffic. Railings shall be provided when required by Section 4407.
The walkway shall be capable of supporting a uniform live load of 150 pounds
per square foot. A durable wearing surface shall be provided.
Pedestrian Protection
Sec. 4407. (a) Protection Required. Pedestrian traffic shall be protected by a
railing on the street side when the walkway extends into the roadway, by a railing
adjacent to excavations and by such other protection as set forth in Table No. 44-
A. The construction of such protective devices shall be in accordance with the
provisions of this chapter.
(b) Railings. Railings shall be substantially built and, when of wood, shall be
constructed of new material having a nominal size of at least 2 inches by 4 inches.
Railings shall be at least 3 feet 6 inches in height and when adjacent to excavations
shall be provided with a midrail.
(c) Fences. Fences shall be solid and substantially built, be not less than 8 feet
in height above grade and be placed on the side of the walkway nearest to the
building site. Fences shall extend the entire length of the building site and each
end shall be returned to the building line.
Openings in such fences shall be protected by doors which normally are kept
closed.
All fences shall be provided with 2-inch by 4-inch plate, top and bottom, and
shall be well braced. The fence material shall be a minimum of %-inch boards or
Y4-inch plywood. Plywood fences shall conform to the following requirements:
1. Plywood panels shall be bonded with an adhesive identical to those for
exterior plywood.
2. Plywood Y4 inch or 5/16 inch in thickness shall have studs spaced not more
than 2 feet on center.
3. Plywood 3fs inch or Y2 inch in thickness shall have studs spaced not more than
4 feet on center, provided a 2-inch by 4-inch stiffener is placed horizontally at the
midheight when the stud spacing exceeds 2 feet on center.
4. Plywood 5fs inch or thicker shall not span over 8 feet.
(d) Canopies. The protective canopy shall have a clear height of 8 feet above
the walkway. The roof shall be tightly sheathed. The sheathing shall be 2-inch
nominal wood planking or equal. Every canopy shall have a solid fence built
along its entire length on the construction side.
If materials are stored or work is done on the roof of the canopy, the street sides
and ends of the canopy roof shall be protected by a tight curb board not less than 1
foot high and a railing not less than 3 feet 6 inches high.
The entire structure shall be designed to carry the loads to be imposed on it,
provided the live load shall be not less than !50 pounds per square foot. In lieu of
643
4407-4409, 44-A UNIFORM BUILDING CODE
such design a protection canopy supporting not more than 150 pounds per square
foot may be constructed as follows:
1. Footings shall be continuous 2-inch by 6-inch members with scabbed joints.
2. Posts not less than 4 inches by 6 inches in size shall be provided on both sides
of the canopy and spaced not more than 12 feet, center to center.
3. Stringers not less than 4 inches by 12 inches in size shall be placed on edge
upon the posts.
4. Joists resting upon the stringers shall be at least 2 inches by 8 inches in size
and shall be spaced not more than 2 feet, center to center.
5. The deck shall be of planks at least 2 inches thick nailed to the joists.
6. Each post shall be knee-braced to joists and stringers by members 4 feet
long, not less than 2 inches by 4 inches in size.
7. A curb not less than 2 inches by 12 inches in size shall be set on edge along
the outside edge of the deck.
EXCEPTION: Protection canopies for new, light-frame construction not
exceeding two stories in height may be designed for a live load of 75 pounds per
square foot or the loads to be imposed on it, whichever is the greater.
Maintenance and Removal of Protective Devices
Sec. 4408. (a) Maintenance. Such protection shall be maintained in place
and kept in good order for the entire length of time pedestrians may be
endangered.
(b) Removal. Every protection fence or canopy shall be removed within 30
days after such protection is no longer required by this chapter for protection of
pedestrians.
Demolition
Sec. 4409. The work of demolishing any building shall not be commenced
until the required pedestrian protection structures are in place.
The building official may require the permittee to submit plans and a complete
schedule for demolition. Where such are required, no work shall be done until
such plans and/or schedule are approved by the building official.
TABLE NO. 44A-TYPE OF PROTECTION REQUIRED FOR PEDESTRIANS
644
1982 EDITION 4501-4504
Chapter 45
PERMANENT OCCUPANCY
OF PUBLIC PROPERTY
General
Sec. 4501. No part of any structure or any appendage thereto, except signs,
shall project beyond the property line of the building site, except as specified in
this chapter.
Structures or appendages regulated by this code shall be constructed of mate-
rials as specified in Section 1710.
The projection of any structure or appendage shall be the distance measured
horizontally from the property line to the outermost point of the projection.
Nothing in this code shall prohibit the construction and use of a structure
between buildings and over or under a public way, provided the structure complies
with all requirements of this code.
No provisions of this chapter shall be construed to permit the violation of other
laws or ordinances regulating the use and occupancy of public property.
645
4504-4506 UNIFORM BUILDING CODE
Awnings
Sec. 4506. (a) Definitions. For the purpose of this section:
AWNING is a temporary shelter supported entirely from the exterior wall of a
building.
(b) Construction. Awnings shall have noncombustible frames but may have
combustible coverings. Every awning shall be collapsible, retractable or capable
of being folded against the face of the supporting building. When collapsed,
retracted or folded, the design shall be such that the awning does not block any
required exit.
EXCEPTION: A fixed awning not more than 10 feet in length may be erected
over a doorway to the building.
646
1982 EDITION 4506-4507
(c) Projection. Awnings may extend over public property not more than 7 feet
from the face of a supporting building, but no portion shall extend nearer than 2
feet to the face of the nearest curb line measured horizontally. In no case shall the
awning extend over public property greater than two thirds of the distance from
the property line to the nearest curb in front of the building site.
(d) Clearances. All portions of any awning shall be at least 8 feet above any
public walkway.
EXCEPTION: Any valance attached to an awning shall not project above the
roof of the awning at the point of attachment and shall not extend more than 12
inches below the roof of the awning at the point of attachment, but in no case shall
any portion of a valance be less than 7 feet in height above a public way.
Doors
Sec. 4507. Doors, either fully opened or when opening, shall not project more
than 1 foot beyond the property line, except that in alleys no projection beyond the
property line is permitted.
Chapter 46
NO REQUIREMENTS
647
4701 UNIFORM BUILDING CODE
Part IX
Chapter 47
INSTALLATION OF WALL
AND CEILING COVERINGS
Scope
Sec. 4701. (a) General. The installation of lath, plaster and gypsum board
shall be done in a manner and with materials as specified in this chapter and, when
required for fire-resistive construction, also shall conform with the provisions of
Chapter 43.
Other approved wall or ceiling coverings may be installed in accordance with
the recommendations of the manufacturer and the conditions of approval.
(b) Inspection. No lath or gypsum board or their attachments shall be covered
or finished until it has been inspected and approved by the building official in
accordance with Section 305 (e).
(c) Thsts. The building official may require tests to be made in accordance
with approved standards to determine compliance with the provisions of this
chapter, provided the permit holder has been notified 24 hours in advance of the
time of making such tests.
The testing of gypsum and gypsum products shall conform with U.B.C.
Standard No. 47-17.
(d) Definitions. For purposes of this chapter, certain terms are defined as
follows:
CORNER BEAD is a rigid formed unit or shape used at projecting or external
angles to define and reinforce the comers of interior surfaces.
CORNERITE is a shaped reinforcing unit of expanded metal or wire fabric
used for angle reinforcing and having minimum outstanding legs of not less than 2
inches.
CORROSION-RESISTANT MATERIALS are materials that are inherently
rust resistant or materials to which an approved rust-resistive coating has been
applied either before or after forming or fabrication.
EXTERIOR SURFACES are weather-exposed surfaces as defined in Section
424.
EXTERNAL CORNER REINFORCEMENT is a shaped reinforcing unit
for external comer reinforcement for portland cement plaster formed to ensure
mechanical bond and a solid plaster comer.
648
1982 EDITION 4701-4703
649
4704-4705 UNIFORM BUILDING CODE
Horizontal Assemblies
Sec. 4704. (a) General. In addition to the requirements of this section, sup-
ports for horizontal assemblies of plaster or gypsum board shall be designed to
support all loads as specified in Chapter 23 of this code.
EXCEPTION: Wood-framed assemblies meeting the requirements of Section
2517 need not be designed.
(b) Wood Framing. Wood stripping or suspended wood systems, where used,
shall be not less than 2 inches nominal thickness in the least dimension except that
furring strips not less than l-inch by 2-inch nominal dimension may be used over
solid backing.
(c) Hangers. Hangers for suspended ceilings shall be not less than the sizes set
forth in Table No. 47-A, fastened to or embedded in the structural framing,
masonry or concrete.
Hangers shall be saddle-tied around main runners to develop the full strength of
the hangers. Lower ends of flat hangers shall be bolted with %-inch bolts to runner
channels or bent tightly around runners and bolted to the main part of the hanger.
(d) Runners and Furring. The main runner and cross-furring shall be not less
than the sizes set forth in Table No. 47-A, except that other steel sections of
equivalent strength may be substituted for those set forth in this table. Cross-
furring shall be securely attached to the main runner by saddle-tying with not less
than one strand of No. 16 or two strands of No. 18 U.S. gauge tie wire or approved
equivalent attachments.
Interior Lath
Sec. 4705. (a) General. Gypsum lath shall not be installed until weather
protection for the installation is provided. Where wood frame walls and partitions
are covered on the interior with portland cement plaster or tile of similar material
and are subject to water splash, the framing shall be protected with an approved
moisture barrier.
Showers and public toilet walls shall conform to Section 510 (b).
(b) Application of Gypsum Lath. The thickness, spacing of supports and the
method of attachment of gypsum lath shall be as set forth in Tables No. 47-B and
No. 47-C. Approved wire and sheet metal attachment clips may be used.
Gypsum lath shall be applied with the long dimension perpendicular to sup-
ports and with end joints staggered in successive courses. End joints may occur on
one support when stripping is applied the full length of the joints.
Where electrical radiant heat cables are installed on ceilings, the stripping, if
conductive, may be omitted a distance not to exceed 12 inches from the walls.
Where lath edges are not in moderate contact and have joint gaps exceeding Ys
inch, the joint gaps shall be covered with stripping or comerite. Stripping or
comerite may be omitted when the entire surface is reinforced with not less than l-
inch No. 20 U.S. gauge woven wire. When lath is secured to horizontal or vertical
supports not used as structural diaphragms, end joints may occur between sup-
ports when lath ends are secured together with approved fasteners. Vertical
assemblies also shall comform with Section 2309 (b).
650
1982 EDITION 4705-4706
Exterior Lath
Sec. 4706. (a) General. Exterior surfaces are weather-exposed surfaces as
defined in Section 424. For eave overhangs required to be fire resistive, see
Section 1710.
(b) Corrosion Resistance. All lath and lath attachments shall be of corrosion-
resistant material. See Section 4 701 (d).
(c) Backing. Backing or a lath shall provide sufficient rigidity to permit
plaster application.
Where lath on vertical surfaces extends between rafters or other similar project-
ing members, solid backing shall be installed to provide support for lath and
attachments.
Gypsum lath or gypsum board shall not be used, except that on horizontal
supports of ceilings or roof soffits it may be used as backing for metal lath or wire
I
fabric lath and portland cement plaster.
Backing is not required under metal lath or paperbacked wire fabric lath.
(d) Weather-resistive Barriers. Weather-resistive barriers shall be installed
as required in Section 1707 (a) and, when applied over wood base sheathing, shall
include two layers of Grade D paper.
(e) Application of Metal Plaster Bases. The application of metal lath or wire
fabric lath shall be as specified in Section 4705 (c) and they shall be furred out
from vertical supports or backing not less than V4 inch except as set forth in
Footnote No.2, Table No. 47-B.
651
4706-4707 UNIFORM BUILDING CODE
Where no external comer reinforcement is used, lath shall be furred out and
carried around comers at least one support on frame construction.
A weep screed shall be provided at or below the foundation plate line on all
exterior stud walls. The screed shall be placed a minimum of 4 inches above grade
and shall be of a type which will allow trapped water to drain to the exterior of the
building. The weather-resistive barrier and exterior lath shall cover and terminate
on the attachment flange of the screed.
Interior Plaster
Sec. 4707. (a) General. Plastering with gypsum plaster or portland cement
plaster shall be not less than three coats when applied over metal lath or wire fabric
lath and shall be not less than two coats when applied over other bases permitted
by this chapter. Showers and public toilet walls shall conform to Section 510 (b).
Plaster shall not be applied directly to fiber insulation board. Portland cement
plaster shall not be applied directly to gypsum lath, gypsum masonry or gypsum
plaster except as specified in Section 4706 (c).
When installed, grounds shall assure the minimum thickness of plaster as set
forth in Table No. 47-D. Plaster thickness shall be measured from the face of lath
and other bases.
(b) Base Coat Proportions. Proportions of aggregate to cementitious mate-
rials shall not exceed the volume set forth in Table No. 47-E for gypsum plaster
and Table No. 47-F for portland cement and portland cement-lime plaster.
(c) Base Coat Application. Base coats shall be applied with sufficient mate-
rial and pressure to form a complete key or bond.
I . Gypsum plaster. For two-coat work, the first coat shall be brought out to
grounds and straightened to a true surface, leaving the surface rough to receive the
finish coat. For three-coat work, the surface of the first coat shall be scored
sufficiently to provide adequate bond for the second coat and shall be permitted to
harden and set before the second coat is applied. The second coat shall be brought
out to grounds and straightened to a true surface, leaving the surface rough to
receive the finish coat.
2. Portland cement plaster. The first two coats shall be as required for the
first coats of exterior plaster, except that the moist-curing time period between the
first and second coats shall be not less than 24 hours and the thickness shall be as
set forth in Table No. 47-D. Moist curing shall not be required where job and
weather conditions are favorable to the retention of moisture in the portland
cement plaster for the required time period.
(d) Finish Coat Application. Finish coats shall be applied with sufficient
material and pressure to form a complete bond. Finish coats shall be proportioned
and mixed in an approved manner. Gypsum and lime and other interior finish
coats shall be applied over gypsum base coats which have hardened and set.
Thicknesses shall be not less than Y16 inch.
Portland cement and lime finish coats may be applied over interior portland
cement base coats which have been in place not less than 48 hours.
Approved acoustical finish plaster may be applied over any base coat plaster,
over lean masonry or concrete, or other approved surfaces.
652
1982 EDITION 4707-4708
653
4708-4709 UNIFORM BUILDING CODE
654
1982 EDITION 4709-4711
Gypsum Wallboard
Sec. 4711. (a) General. All gypsum wallboard shall conform to U.B.C.
Standard No. 47-11 and shall be installed in accordance with the provisions of this
section. Gypsum wallboard shall not be installed on exterior surfaces. See
Section 424. For use as backing under stucco, see Section 4706 (c).
Gypsum wallboard shall not be installed until weather protection for the
installation is provided.
Shower and public toilet walls shall conform to Section 510 (b).
Water-resistant gypsum backing board shall conform to U.B.C. Standard No.
47-14.
(b) Supports. Supports shall be spaced not to exceed the spacing set forth in
Table No. 47-G for single-ply application and Table No. 47-H for two-ply
application. Vertical assemblies shall conform with Section 4703. Horizontal
assemblies shall comply with Section 4704.
(c) Single-ply Application. All edges and ends of gypsum wallboard shall
occur on the framing members, except those edges and ends which are perpendic-
ular to the framing members. All edges and ends of gypsum wallboard shall be in
moderate contact except in concealed spaces where fire-resistive construction or
diaphragm action is not required.
The size and spacing of fasteners shall conform with Table No. 47-G except
where modified by fire-resistive construction meeting the requirements of Sec-
tion 4302 (b). Fasteners shall be spaced not less than Ys inch from edges and ends
of gypsum wallboard. Fasteners at the top and bottom plates of vertical assem-
blies, or the edges and ends of horizontal assemblies perpendicular to supports,
and at the wall line may be omitted except on shear-resisting elements or fire-
resistive assemblies. Fasteners shall be applied in such a manner as not to fracture
the face paper with the fastener head.
Gypsum wallboard may be applied to wood framing members with an approved
adhesive conforming with U.B.C. Standard No. 47-2. A continuous bead of the
655
4711-4713 UNIFORM BUILDING CODE
adhesive shall be applied to the face of all framing members, except top and
bottom plates, of sufficient size as to spread to an average width of I inch and
thickness of Y16 inch when the gypsum wallboard is applied. Where the edges or
ends of two pieces of gypsum wallboard occur on the same framing member, two
continuous parallel beads of adhesive shall be applied to the framing member.
Fasteners shall be used with adhesive application in accordance with Table
No. 47-G.
(d) 1Wo-ply Application. The base of gypsum wallboard shall be applied with
fasteners of the type and size as required for the nonadhesive application of
single-ply gypsum wallboard. Fastener spacings shall be in accordance with Table
No. 47-H except where modified by fire-resistive construction meeting the
requirements of Section 4302 (b).
The face ply of gypsum wallboard may be applied with gypsum wallboard joint
compound or approved adhesive furnishing full coverage between the plies or
with fasteners in accordance with Table No. 47-H. When the face ply is installed
with joint compound or adhesive, the joints of the face ply need not occur on
supports. Temporary nails or shoring shall be used to hold face ply in position
until the joint compound or adhesive develops adequate bond.
(e) Joint Treatment. Gypsum wallboard single-layer fire-rated assemblies
shall have joints treated except where the wallboard is to receive a decorative
finish such as wood paneling, battens, acoustical finishes or any similar applica-
tion which would be equivalent to the joint treatment.
EXCEPTION: Assemblies tested without joint treatment.
Gypsum wallboard tape and joint compound shall conform with the provisions
of U .B.C. Standard No. 47-6.
Softwood Plywood Paneling
Sec. 4712. All softwood plywood paneling shall conform with the provisions
of Chapters 25 and 42 and shall be installed in accordance with Table No. 47-J.
Shear-resisting Construction with Wood Frame
Sec. 4713. (a) General. Portland cement plaster, gypsum lath and plaster,
gypsum veneer base, gypsum sheathing board and gypsum wallboard may be
used on wood studs for vertical diaphragms if applied in accordance with this
section. Shear-resisting values shall not exceed those set forth in Table No. 47-1.
656
1982 EDITION 4713
tion 2517 (g) for bearing walls, and studs shall be spaced not farther apart than
16 inches center to center. Marginal studs and plates shall be anchored to resist all
design forces.
(d) Height-to-length Ratio. The maximum allowable height-to-length ratio ~
for the construction in this section shall be 2 to I. Wall sections having height-to-
length ratios in excess of I Yz to I shall be blocked.
(e) Application. End joints of adjacent courses of gypsum lath, gypsum
veneer base, gypsum sheathing board or gypsum wallboard sheets shall not occur
over the same stud.
Where required in Table No. 47-1, blocking having the same cross-sectional
dimensions as the studs shall be provided at all joints that are perpendicular to the
studs.
The size and spacing of nails shall be as set forth in Table No. 47-1. Nails shall
be spaced not less than .lfs inch from edges and ends of gypsum lath, gypsum
veneer base, gypsum sheathing board, gypsum wallboard or sides of studs,
blocking and top and bottom plates.
I. Gypsum lath. Gypsum lath shall be applied perpendicular to the studs.
Maximum allowable shear values shall be as set forth in Table No. 47-I.
2. Gypsum sheathing board. Four-foot-wide pieces may be applied parallel
or perpendicular to studs. Two-foot-wide pieces shall be applied perpendicular to
the studs. Maximum allowable shear values shall be as set forth in Table No. 47-I.
3. Gypsum wallboard or veneer base. Gypsum wallboard or veneer base
may be applied parallel or perpendicular to studs. Maximum allowable shear
values shall be as set forth in Table No. 47-I.
657
TABLE NO. 47A-SUSPENDED AND FURRED CEILINGS 1
(For Support of Ceilings Weighing Not More than 10 Pounds per Square Foot)
SIZE AND TYPE OF CROSS FURRING MAXIMUM SPACING OF RUNNERS MAXIMUM SPACING OF CROSS
OR SUPPORTS FURRING MEMBERS (TRANSVERSE)
'A. " diameter pencil rods 2'0" 12"
%" diameter pencil rods 2'0" 19"
% " diameter pencil rods 2'6" 12"
3'0" 24"
~ "-.3 pound per foot, cold- or hot-rolled channel 3'6" 16"
4'0" 12"
4'0" 24"
1 "-.410 pound per foot, hot-rolled channel 4'6" 19"
5'0" 12"
I Metal suspension systems for acoustical tile and lay-in panel ceiling systems weighing not more than 4 pounds per square foot, including light
fixtures and all ceiling-supported equipment and conforming to U.B.C. Standard No. 47-18, are exempt from Table No. 47-A.
For furred and suspended ceilings with metal lath construction, see U.B.C. Standard No. 47-4.
2AII rod hangers shall be protected with a zinc or cadmium coating or with a rust-inhibitive paint.
3All flat hangers shall be protected with a zinc or cadmium coating or with a rust-inhibitive paint.
4 Inserts, special clips or other devices of equal strength may be substituted for those specified.
5Two loops of No. 18 gauge wire may be substituted for each loop of No. 16 gauge wire for attaching steel furring to steel or wood joists.
VERTICAL
(In Inches)
Metal HORIZONTAL
(In Inches)
MINIMUM WEIGHT Solid
(Per Squant Yard~ Plaatar Wood or
TYPE OF LATH GAUGE AND MESH IZE Wood Partitions Other Concntta Metal
I. Expanded Metal Lath
(Diamond Mesh)
2. Flat Rib Expanded
2.5
3.4
2.75
J63
163
16
163
163
16
12
16
16
12
16
16
12
16
16
I
Metal Lath 3.4 19 24 19 19 19
3. Stucco Mesh Expanded 1.8 and 164 -
Metal Lath 3.6 - - -
3.4 24 245 24 24 24
4. W' Rib Expanded Metal Lath 4.0 24 24 5 24 24 24
5. Sheet Lath 4.5 24 5 24 24 24
I. 95 pounds, No. II gauge, 2" x 2" 24 24 24 24 24
Welded 1.16 pounds, No. 16 gauge, 2" x 2" 16 16 16 16 16
6. Wire Fabric Lath
1.4 pounds, No. 18 gauge, I" x J"6 164 - - - - I c:
z
1.1 pounds, No. 18 gauge, I Y2'' Hexagonal6 24 16 16 16 24
Woven4 1.4 pounds, No. 17 gauge, I Y2'' Hexagonal6 24 16 16 24 16 ~
::u
1.4 pounds, No. 18 gauge, I" Hexagonal6 24 16 16 24 16
iii:
7. lis" Gypsum Lath ID
(perforated)
16 - 167 16 16 c:
F
8. W' Gypsum Lath (plain) 16 - J67 16 16 2
9. Y2'' Gypsum Lath
z
C)
(perforated)
16 - 167 16 16 0
0
10. Y2'' Gypsum Lath (plain) 24 - 24 24 24
~
-
C l)
~
m
1For fire-resistive construction, see Tables No. 43-A, No. 43-B and No. 43-C. For shear-resisting elements, see Table No. 47-l. Metal lath, wire c
lath, wire fabric lath and metal accessories shall conform with the provisions of U. B.C. Standard No. 4 7-4. Gypsum lath shall conform with the ::::j
I
provisions ofU.B.C. Standard No. 47-8. 6
2Metallath and wire fabric lath used as reinforcement for portland cement plaster shall be furred out away from vertical supports at least v. inch. z
Self-furring lath meets furring requirements. Exception: Furring of expanded metal lath is not required on supports having a bearing surface
width of I VB inches or less.
3Span may be increased to 24 inches with self-furred metal lath over solid sheathing assemblies approved for this use.
4 Wire backing required on open vertical frame construction except under expanded metal lath and paperbacked wire fabric lath.
STAI'LfS 3 4
SCREWS 3 6 Round or Fllttenld WI,.
MAXIMUM SPACING 5 MAX. SPACING 5 MAX. SPACING 56
NAILS 2 3 Vertical Horizontal Vertical 1Horizontal Wire Cau1e Crawn Le1 7 Vertical Horizontal
TYPE OF LATH TJPI and Sill (In lnclln) (In lncllts) No. (In lncllos)
4d blued smooth box
1Vz"II No. 14 gauge 1,
'Metal lath, wire lath, wire fabric lath and metal accessories shall conform with the provisions ofU.B.C. Standard No. 47-4.
2For nailable nonload-bearing metal supports, use annular threaded nails or approved staples.
3For fire-resistive construction, see Tables No. 43-B and No. 43-C. For shear-resisting elements, see Table No. 47-I. Approved wire and sheet
metal attachment clips may be used.
4 With chisel or divergent points.
5Maximum spacing of attachments from longitudinal edges shall not exceed 2 inches.
6Screws shall be an approved type long enough to penetrate into wood framing not less than 5fs inch and through metal supports adaptable for
screw attachment not less than Y inch.
7 When lath and stripping are stapled simultaneously, increase leg length of staple Vs inch.
8 For interiors only.
9 Attach self-furring wire fabric lath to supports at furring device.
'DThree attachments per 16-inch-wide lath per bearing. Four attachments per 24-inch-wide lath per bearing.
~~Supports spaced 24 inches o.c. Four attachments per 16-inch-wide lath per bearing. Five attachments per 24-inch-wide lath per bearing.
~
TABLE NO 47-D-THICKNESS OF PI.ASTER 1
I for frre-resistive construction, see Tables No. 43-A, No. 43-B and No. 43-C.
2When measured from back plane of expanded metal lath, exclusive of ribs, or self-furring lath, plaster thickness shall be %-inch minimum.
3Wben measured from face of support or backing.
4 Because masonry and concrete surfaces may vary in plane, thickness of plaster need not be uniform.
5Wben applied over a liquid bonding agent, finish coat may be applied directly to concrete surface. c:
6 Approved acoustical plaster may be applied directly to concrete, or over base coat plaster, beyond the maximum plaster thickness shown.
z
70n concrete ceilings, where the base coat plaster thickness exceeds the maximum thickness shown, metal lath or wire fabric lath shall be attached ~
::D
to the concrete. 3!1:
8An approved skim-coat plaster '116 inch thick may be applied directly to concrete. ID
c:
;:::
0
z
C)
0
0
Jil
....
!m
TABLE NO. 47E-GYPSUM PLASTER PROPORTIONS 1 IC
3
0
MAXIMUM VOLUME AGGREGATE PER 100 POUNDS NEAT PLASTER 2 3 z
PLASTER BASE (CUIIIC Feet)
NUMBER COAT OR LATH Damp loose sand 4 Perlite er Yermiculit1'4
Wood-fibered gypsum plaster may be mixed in the proportions of 100 pounds of gypsum to not more than I cubic foot of sand where applied on
masonry or concrete.
Gypsum plasters shall conform with the provisions ofU.B.C. Standard No. 47-9.
2For fire-resistive construction, see Tables No. 43-A, No. 43-B and No. 43-C.
3Wben determining the amount of aggregate in set plaster, a tolerance of 10 percent shall be allowed.
4Combinations of sand and lightweight aggregate may be used, provided the volume and weight relationship of the combined aggregate to
gypsum plaster is maintained. Sand and lightweight aggregate shall conform with U.B.C. Standard No. 47-3.
5Ifused for both first and second coats, the volume of aggregate may be 21h cubic feet.
6Wbere plaster is I inch or more in total thickness, the proportions for the second coat may be increased to 3 cubic feet.
TABLE NO. 47-F-PORTLAND CEMENT PLASTERS 1
PORTLAND CEMENT PLASTER
MAXIMUM WEIGHT
(OR VOLUME) LIME MAXIMUM VOLUME
VOLUME PER VOLUME SAND PER VOLUME APPROXIMATE MINIMUM PERIOD MINIMUM INTERVAL
COAT CEMENT CEMENT2 CEMENT' MINIMUM THICKNESS4 MOIST CURING BETWEEN COATS
First I 20 lbs. 4 Ys"5 48 6 Hours 487 Hours
I st and 2nd Coats
Second I 20 lbs. 5 total%"
48 hours 7 Days 8
~~~r:.~= J&~::~
SAND PER COMBINED
VOLUME VOLUMES CEMENT APPROXIMATE MINIMUM PERIOD MINIMUM INTERVAL
COAT CEMENT11 CEMENT AND LIME MINIMUM THICKNESS MOIST CURING BETWEEN COATS
First I I 4 3Js"5 486 Hours 48 7 Hours
I st and 2nd Coats
Second I I 4V2 total W'
48 hours 7 Days 8
J9
I st, 2nd and Finish 8
Finish I 3 Coats 71s"
-
I Exposed aggregate plaster shall be applied m accordance w1th Section 4 709. Mmimum overall thickness shall be 3/4 mch.
2Up to 20 pounds of dry hydrated lime (or an equivalent amount of lime putty) may be used as a plasticizing agent in proportion to each sack (cubic foot) of c
Type I and Type II standard portland cement in first and second coats of plaster. See Section 4708 (a) for use of plastic cement. z
3When determining the amount of sand in set plaster, a tolerance of I 0 percent may be allowed.
4 See Table No. 47-D.
~
::u
~
'Measured from face of support of backing to crest of scored plaster.
m
6 See Section 4707 (c) 2. c
7 Twenty-four hours minimum interval between coats of interior portland cement plaster. For alternate method of application, see Section 4708 (e). ;=
c
8 Finish coat plaster may be applied to interior portland cement base coats after a 48-hour period.
9 For finish coat plaster, up to an equal part of dry hydrated lime by weight (or an equivalent volume of lime putty) may be added to Types I, II and III
z
C)
standard portland cement. 0
10No additions of plasticizing agents shall be made. 0
11 Type I, II or III standard portland cement. See Section 4708 (a) for use of plastic cement. Iii
TABLE NO. 47-G-APPLICATION OF SINGLE-PLY GYPSUM WALLBOARD .....
MAXIMUM
SPACIN& OF MAXIMUM SPACING OF
!m
THICKNESS LON& DIMENSION OF FRAMIN& FASTENERS! c
OF GYPSUM WALLBOARD MEMBERS I (Center I<> Cenlel)
&YPSUM PLANE OF SHEETS IN RELATION (Center to (In Inches) NAILSLTO WOOD 3
WALUOARD FRAMING TO DIRECTION OF Center) 0
(I nell) SURFACE FRAMING MEMBERS (In Inches) Nails 3 Screws4 z
Horizontal Either Direction 16 7 12 No. 13 gauge, !W' long, 1'%" head;
0.098" diameter; !l/4' long, annular
1h Horizontal Perpendicular 24 7 12 ringed; 5d, cooler nail (0.086" dia., I '18'
Vertical Either Direction 24 8 12 long, 1%4' head)
Horizontal
Either Direction 16 16 16 24
'h.
24 As required for 1h" and %" gypsum wall-
or Perpendicular 24 16 24
% board, see above
Vertical Either Direction 24 16 24 5
I for fire-resistive construction, see Tables No. 43-B and No. 43-C. For shear-resisting elements. see Table No. 47-1.
2 Where the metal framing has a clinching design formed to receive the nails by two edges of metal, the nails shall be not less than 'Is inch longer than the
wallboard thickness, and shall have ringed shanks. Where the metal framing has a nailing groove formed to receive the nails, the nails shall have barbed
shanks or be 5d, No. 13'12 gauge, l'h inch long, 1'16-inch head for 112-inch gypsum wallboard; 6d, No. 13 gauge, I Jls inch long, '%-inch head for 'Is-inch
gypsum wallboard.
'Two nails spaced 2 inches to 2112 inches apart may be used where the pairs are spaced 12 inches on center except around the perimeter of the sheets.
4 Screws shall conform with U.B.C. Standard No. 47-5 and be long enough to penetrate into wood framing not less than 'Is inch and through metal framing not
2. Gypsum lath, plain Y." Lath and Unblocked 5 100 No. 13 gauge, I Y." long, '%.'' head, plasterboard
or perforated Y," Plaster blued nail
3. Gypsum sheathing Y," x2' x 8' Unblocked 4 75 No. II gauge, I Y." long, Y,," head, diamond-point,
board galvanized
X" x4' Blocked 4 175
X" x4' Unblocked 7 100
7 100
Unblocked
4 125
X:" 5d cooler nails
7 125
Blocked
4. Gypsum wallboard 4 !50
or veneer base
Blocked 4 175 6d cooler nails
Ys" Blocked Base ply 9 Base ply-6d cooler nails
250
Two-ply Face ply 7 Face ply-8d cooler nails
IThese vertical diaphragms shall not be used to resist loads imposed by masonry or concrete construction. See Sectwn 4713 (b). Values are for
short-time loading due to wind or earthquake and must be reduced 25 percent for normalloadmg.
~ 2 Applies to nailing at all studs, top and bottom plates and blocking.
CD
47-J UNIFORM BUILDING CODE
14 16 1 4d casing or 6 12
finish
% 24 6d casing or 6 12
finish
670
1982 EDITION 4801
Part X
SPECIAL SUBJECTS
Chapter48
CELLULOSE NITRATE
Cellulose Nitrate
Sec. 4801. The handling and storage of cellulose nitrate film shall be in
accordance with the Fire Code.
I
Chapter 49
NO REQUIREMENTS
(See page 722-Appendlx.)
671
5001-5006 UNIFORM BUILDING CODE
Chapter 50
PREFABRICATED CONSTRUCTION
General
Sec. 5001. (a) Purpose. The purpose of this chapter is to regulate materials
and establish methods of safe construction where any structure or portion thereof
is wholly or partially prefabricated.
(b) Scope. Unless otherwise specifically stated in this chapter, all prefabri-
cated construction and all materials used therein shall conform to all the require-
ments of this code. (See Section 105.)
(c) Definition. PREFABRICATED ASSEMBLY is a structural unit, the
integral parts of which have been built up or assembled prior to incorporation in
the building.
Tests of Materials
Sec. 5002. Every approval of a material not specifically mentioned in this code
shall incorporate as a proviso, the kind and number of tests to be made during
prefabrication.
Tests of Assemblies
Sec. 5003. The building official may require special tests to be made on
assemblies to determine their durability and weather resistance.
Connections
Sec. 5004. Every device designed to connect prefabricated assemblies shall be
capable of developing the strength of the members connected, except in the case
of members forming part of a structural frame designed as specified in Chapter
23. The connection device shall be designed as required by the other chapters in
this code. Connections between roofs and supporting walls shall be capable of
withstanding an uplift force equal to the requirements contained in Chapter 23.
Pipes and Conduits
Sec. 5005. In structural design, due allowance shall be made for any material
to be removed for the installation of pipes, conduits or other equipment.
Certificate and Inspection
Sec. 5006. (a) Materials. Materials and the assembly thereof shall be
inspected to determine compliance with this code. Every material shall be graded,
marked or labeled where required elsewhere in this code.
(b) Certificate. A certificate of approval shall be furnished with every pre-
fabricated assembly, except where the assembly is readily accessible to inspection
at the site. The certificate of approval shall certify that the assembly in question
has been inspected and meets all the requirements of this code. When mechanical
equipment is installed so that it cannot be inspected at the site, the certificate of
approval shall certify that such equipment complies with the laws applying
thereto.
(c) Certifying Agency. To be acceptable under this code, every certificate of
approval shall be made by an approved agency.
672
1982 EDITION 5008
673
51015103 UNIFORM BUILDING CODE
Chapter 51
ELEVATORS, DUMBWAITERS, ESCALATORS
AND MOVING WALKS
Scope
Sec. 5101. The provisions of this chapter shall apply to the design, con-
struction, installation, operation, alteration and repair of elevators, dumbwaiters,
escalators and moving walks and their hoistways.
Elevator Enclosures
Sec. 5102. Walls and partitions enclosing elevator and dumbwaiter hoistway
shafts and escalator shafts shall be of not less than the fire-resistive construction
required under l)'pes of Construction in Part IV of this code.
Emergency Operation and Special Provisions
Sec. 5103. (a) Automatic Elevators. Automatic passenger elevators shall
conform to the following:
I. Commandeering switch. In other than dwelling units, elevators shall be
provided with a two-position switch for emergency operation. Such switch shall
be located near the entrance to the elevator at each main floor of the building.
When the switch is in the "on" position, all elevators which are in normal
service shall return nonstop to the floor where the switch is in the "on" position
and the doors shall open, except that an elevator traveling away from the main
floor may reverse at the next available floor without opening its doors. When the
switch is in the "on" position, door-reopening devices for power-operated doors
which may be affected by smoke or heat so as to prevent door closure shall be
rendered inoperative; and elevators equipped with power-operated doors and
standing at a floor other than the main floor, with doors open, shall close their
doors without delay. Except for elevators in emergency service, the switch shall
be connected so that elevators may be returned to normal service by moving the
switch to the "off" position.
2. Heat- and smoke-sensing devices. The return to a main floor may be
initiated by heat- or smoke-sensing devices, or both, in the building indepen-
dently of the switch required by provision I above, except that such devices at the
main floor shall not initiate the return of the elevators. If so, the switch required at
a main floor shall have three positions. The third position shall restore normal
service independent of the heat- or smoke-sensing device, or both.
3. Elevator car emergency switch. A switch shall be provided in or adjacent
to an operating panel of each elevator car. This switch, when operated, shall put
the elevator on emergency service and shall be operable only after the switch
required by provision I above has been activated. When the emergency service
switch in the elevator is actuated:
(i) An elevator shall be operable only by a person in the elevator.
(ii) Elevators on emergency service shall not respond to elevator landing calls.
(iii) The opening of power-operated doors shall be controlled only by continu-
ous-pressure "open" buttons or switches. If the open button or switch is
674
1982 EDITION 5103
released during the "open" motion, the doors shall automatically reclose.
(iv) Door-reopening devices for power-operated doors which may be affected
by smoke or heat so as to prevent door closure shall be rendered
inoperative.
4. Keys for elevator switches. Keys, where permitted for the switches
required by provisions 1 and 3 above, shall be kept on the premises by the person
responsible for the maintenance and operation of the elevators in a location readily
accessible to authorized persons in an emergency but not where they are available
to the public.
(b) Attendant-operated Elevators. Elevators operated only by a designated
operator in the car shall be provided with a signal system to permit signaling the
operator from the main floor to return nonstop to a designated main floor.
Attendant-operated elevators having power-operated doors and door-reopening
devices affected by smoke or heat shall be rendered inoperative, and such doors
and devices shall conform to Subsection (a) 3, (iii) and (iv) above.
(c) Dual-operated Elevators. Elevators arranged for dual operation shall,
when on automatic operation, conform to Subsection 5103 (a) and when atten-
dant operated shall conform to Subsection 5103 (b).
(d) Door Operation. Each elevator lobby or entrance area shall be provided
with an approved smoke detector which will operate before the optical density
reaches 0.03 per foot and conforming to U.B.C. Standard No. 43-6, and which
will not permit the elevator doors to open when the detector is activated.
(e) Access. Each elevator car shall have a height, recessed area or movable
ceiling which will make possible the carrying of a 9-foot-high ladder.
(f) Standby Power. Standby power shall be provided to at least one elevator in
each bank where the highest floor level of human occupancy is more than 75 feet
above the lowest level of fire department vehicle access. Standby power shall be
transferable to all other elevators in the bank and shall be capable of operating the
elevator with a full load at contract speed. Standby power shall be provided by an
approved self-contained generator set to operate whenever there is a loss of power
in the normal house current. The generator shall be in a separate room having at
least a one-hour fire-resistive occupancy separation from the remainder of the
building and shall have a fuel supply adequate to operate the equipment for two
hours.
(g) Restricted or Limited-use Elevators. The building official may waive the
requirements of this section for any elevator designed for limited or restricted use
serving only specific floors or a special function.
(h) Size of Cab. In buildings three or more stories in height served by an
elevator, or a building served by an elevator required by Table No. 33-A, at least
one elevator serving all floors shall be of a size that will accommodate a wheel-
chair. Such elevators shall have horizontal dimensions not less than the following:
Distance between side walls, 68 inches, except that elevators with capacities of
less than 2000 pounds may be reduced to 54 inches minimum.
Distance between wall and door, 54 inches.
Distance between wall and return panel adjacent to the door, 51 inches.
675
5103-5105 UNIFORM BUILDING CODE
I
Emergency Signs
Sec. 5105. Except at the ground floor level, an approved pictorial sign of a
standardized design shall be posted adjacent to each elevator call station which
specifies "IN CASE OF FIRE, DO NOT USE ELEVATORS-USE EXIT
STAIRS."
676
1982 EDITION 5201-5202
Chapter 52
LIGHT-TRANSMITTING PLASTICS
Scope
Sec. 5201. (a) General. The provisions of this chapter shall govern the quality
and methods of application of plastics for use as light-transmitting materials in
buildings and structures. For foam plastics, see Sections 1705 (e) and 1712.
Light-transmitting plastic materials which meet the other code requirements for
walls and roofs may be used in accordance with the other applicable chapters of
the code.
(b) Approval for Use. The building official shall require that sufficient techni-
cal data be submitted to substantiate the proposed use of any light-transmitting
material and, if it is determined that the evidence submitted is satisfactory for the
use intended, he may approve its use subject to the requirements of this chapter.
(c) Identification. Each unit or package of plastic shall be identified with a
mark or decal satisfactory to the building official, which includes identification as
to the material classification in accordance with U.B.C. Standard No. 52-4.
(d) Combination of Glazing and Exterior Wall Panels. Combinations of
plastic glazing and plastic exterior wall panels shall be subject to the area, height,
percentage and separation requirements applicable to the class of plastics as
prescribed for wall panel installation.
(e) Combination of Roof Panels and Skylights. Combinations of plastic roof
panels and plastic skylights shall be subject to the area percentage and separation
requirements applicable to roof panel installation.
Definitions
Sec. 5202. For the purpose of this chapter, certain terms are defined as follows:
APPROVED PLASTIC MATERIALS shall be those having a self-ignition
temperature 650F. or greater when tested in accordance with U.B.C. Standard
No. 52-3 and a smoke-density rating not greater than 450 when tested in accor-
dance with U.B.C. Standard No. 42-1, in the way intended for use, or a smoke-
density rating no greater than 75 when tested in the thickness intended for use by
U.B.C. Standard No. 52-2. Approved plastics shall be classified as either CCI or
CC2, in accordance with U.B.C. Standard No. 52-4.
EXTERIOR WALL PANELS are materials which are not classified as plastic
glazing and which are used as light-transmitting media in exterior walls.
GLASS FIBER REINFORCED PLASTIC is plastic reinforced with glass
fiber having not less than 20 percent of glass fibers by weight.
GLAZING is material which has all edges set in frame or sash and is not held
by mechanical fasteners which pass through the material.
LIGHT-DIFFUSING SYSTEM is construction consisting in whole or in part
of lenses, panels, grids or baffles made with approved plastics positioned below
independently mounted electrical light sources. Lenses, panels, grids and baffles
which are part of an electrical fixture shall not be considered as a light-diffusing
system.
sn
5202-5205 UNIFORM BUILDING CODE
ROOF PANELS are structural panels other than skylights which are fastened
to structural members or structural panels or sheathing and which are used as
light-transmitting media in the plane ofthe roof.
THERMOPLASTIC MATERIAL is a plastic material which is capable of
being repeatedly softened by increase of temperature and hardened by decrease of
temperature.
THERMOSETTING MATERIAL is a plastic material which is capable of
being changed into a substantially nonreformable product when cured.
Design and Installation
Sec. 5203. (a) Structural Requirements. Plastic materials in their assembly
shall be of adequate strength and durability to withstand the design loads as
prescribed elsewhere in this code. Technical data shall be submitted to establish
stresses, maximum unsupported spans and such other information for the various
thicknesses and forms used as may be deemed necessary by the building official.
(b) Fastening. Fastening shall be adequate to withstand design loads as pre-
scribed elsewhere in this code. Proper allowance shall be made for expansion and
contraction of plastic materials in accordance with accepted data on coefficient of
expansion of the material and other material in conjunction with which it is
employed.
Glazing of Unprotected Openings
Sec. 5204. In Type V-N construction, doors, sash and framed openings not
required to be fire protected may be glazed or equipped with approved plastic
material.
In types of construction other than Type V-N, openings not required to be fire
protected may be glazed or equipped with approved plastic, subject to the
following requirements:
l. The aggregate area of plastic glazing shall not exceed 25 percent of the area
of any wall face of the story in which it is installed. The area of a single pane of
glazing installed above the first story shall not exceed 16 square feet and the
vertical dimension of a single pane shall not exceed 4 feet.
EXCEPTION: When an approved automatic sprinkler system is provided
throughout, the area of glazing may be increased to a maximum of 50 percent of the
wall face of the story in which it is installed with no limit on the maximum dimension
or area of a single pane of glazing.
2. Approved flame barriers extending 30 inches beyond the exterior wall in the
plane of the floor, or vertical panels not less than 4 feet in height, shall be installed
between glazed units located in adjacent stories.
3. Plastics shall not be installed more than 65 feet above grade level.
Light-transmitting Exterior Wall Panels
Sec. 5205. In Type V-N construction, approved plastics may be installed in
exterior walls provided the walls are not required to have a fire-resistive rating.
In types of construction other than Type V-N, approved plastics may be
installed in exterior walls, provided the walls are not required to have a fire-
resistive rating, subject to the following requirements:
678
1982 EDITION 5205-5207
I. Approved exterior wall panels shall not be installed more than 40 feet above
grade level.
2. Approved exterior wall panels shall not be installed in exterior walls located
less than 10 feet from the property line.
3. The area and size shall be limited to that set forth in Table No. 52-A.
EXCEPTIONS: I. In structures which are provided with approved flame barri-
ers extending 30 inches beyond the exterior wall in the plane of the floor, there need
be no vertical separation at the floor except that provided by the vertical thickness of
the flame-barrier projection.
2. When an approved automatic sprinkler system is provided throughout the
building, the maximum percentage area of plastic panels in the exterior wall and the
maximum square feet of any individual panel may be increased 50 percent above
that set forth in Table No. 52-A, and the separation requirements, both vertical and
horizontal, as set forth in Table No. 52-A may be reduced by 50 percent.
Roof Panels
Sec. 5206. Approved plastic roof panels may be installed in roofs of buildings
not required to have a fire-resistive rating, subject to the following limitations:
I. Individual roof panels or units shall be separated from each other by
distances of not less than 4 feet measured in a horizontal plane.
2. Roof panels or units shall not be installed within 8 feet of an exterior wall
located where openings in such exterior wall are either prohibited or required to be
protected.
3. Roof panels of Class CCI plastics shall be limited to a maximum individual
panel area of 150 square feet, and the total maximum aggregate area of all panels
shall not exceed 33lfJ percent of the floor area of the room or space sheltered. Roof
panels of Class CC2 plastics shall be limited to a maximum individual panel area
of I00 square feet, and the total maximum aggregate area of all panels shall not
exceed 25 percent of the floor area of the room or space sheltered.
EXCEPTION: Swimming pool shelters are exempt from the area limitations of
Section 5206, provided such shelters do not exceed 5000 square feet in area and are
not closer than 10 feet to the property line or adjacent building.
Skylights
Sec. 5207. (a) General. Skylight assemblies may be glazed with approved
plastic materials in accordance with the following provisions:
1. The plastics shall be mounted at least 4 inches above the plane of the roof by
a curb constructed consistent with the requirements for the type of construction
classification.
EXCEPTION: Curbs may be omitted on roofs of Group R, Division 3 Occupan- I
cies with a minimum slope of 3:12 when self-flashing skylights are used. I
2. Flat or corrugated plastic skylights shall slope at least 4: 12. Dome-shaped
skylights shall rise above the mounting flange a minimum distance equal to I0
percent of the maximum span of the dome but not less than 5 inches.
EXCEPTION: Skylights which pass the Class B Burning Brand Test specified in
U.B.C. Standard No. 32-7.
3. The edges of the plastic lights or domes shall be protected by metal or other I
679
5207-5208 UNIFORM BUILDING CODE
I
is provided.
EXCEPTION: The metal or noncombustible edge is not required where ordi-
nary roof coverings are permitted.
4. Each skylight unit may have a maximum area within the curb of 100 square
feet for CC2 material and 200 square feet for CC l material.
EXCEPTIONS: I. The maximum area within the curb need not be limited if the
building on which the skylights are located is not more than one story in height, the
building has an exterior separation from other buildings of at least 30 feet, and the
room or space sheltered by the roof is not classified in a Group I, Division I or 3
Occupancy or as a required means of egress.
2. Except for Groups A, Divisions I and 2, I and H, Division I Occupancies, the
maximum area within the curb need not be limited where skylights are:
(i) Serving as a fire venting system complying with this code; or
(ii) Used in a building completely equipped with an approved automatic sprinkler
system.
5. The aggregate area of skylights installed in the roof shall not exceed 33Y3
percent of the floor area of the room or space sheltered by the roof when CC l
materials are used and 25 percent when CC2 materials are used.
6. Skylight units shall be separated from each other by a distance of not less
than 4 feet measured in a horizontal plane.
EXCEPTION: Except for Groups A, Divisions I and 2, I and H, Division I
Occupancies, the separation is not required where the skylights are:
(i) Serving as a fire venting system complying with this code; or
(ii) Used in a building completely equipped with an approved automatic sprinkler
system.
7. Skylights shall not be installed within 8 feet of an exterior wall located where
openings in such exterior wall are either prohibited or required to be protected.
(b) Plastics Over Stair Shafts. Approved plastic materials which will not
automatically vent but which are able to be vented may be used over stairways and
shafts, provided the installation conforms to the requirements of Section 5207 (a).
Light-diffusing Systems
Sec:. 5208. (a) General. Plastic diffusers in light-diffusing systems shall be
supported directly or indirectly by the use of noncombustible hangers.
Light-transmitting plastic materials in light-diffusing systems shall comply
with Chapter 42 unless the approved plastic used in the light-diffusing system
meets the following requirements:
l. Diffusers shall fall from their mounting at an ambient temperature of at least
200F. below the ignition temperature of the plastic material as measured by
U.B.C. Standard No. 52-3.
2. Diffusers shall remain in place at an ambient room temperature of l75F. for
a period of not less than 15 minutes.
3. The maximum length of any single plastic panel shall not exceed l 0 feet, and
the maximum area of any single plastic panel shall not exceed 30 square feet.
4. The area of approved plastic materials when used in required exits as defined
680
1982 EDITION 5208-5214
in Chapter 33 shall not exceed 30 percent of the aggregate area of the ceiling in
which they are installed.
EXCEPTION: The aggregate area need not be limited in a building equipped
with an approved automatic sprinkler system.
(b) Plastic light-diffusing system shall not be installed in the areas to be
equipped with automatic sprinklers unless appropriate tests have shown that the
system does not prevent effective operation of the sprinklers or unless sprinklers
are located both above and below the light-diffusing system to give effective
sprinkler protection.
Partitions
Sec. 5210. Light-transmitting plastics may be used in or as partitions, provided
they meet the requirements of this code.
Greenhouses
Sec. 5212. Approved plastics may be used in lieu of plain glass in greenhouses.
Canopies
Sec. 5213. Approved plastic panels may be installed in canopies erected over
motor vehicle service station pumps, provided the panels are located at least 10
feet from any building on the same property and face yards or streets not less than
40 feet in width on the other sides. The aggregate area of plastics shall not exceed
I 000 square feet. The maximum area of any individual panel shall not exceed I 00
square feet.
Solar Collectors
Sec. 5214. Solar collectors having noncombustible sides and bottoms may be
equipped with plastic covers on buildings not over three stories in height or 9,000
square feet in total floor area, provided the plastic cover when exceeding a
thickness of 0.010 inch shall be of approved plastic and the total area shall not
exceed 33YJ percent of the roof area for CCI materials or 25 percent of the roof
area for CC2 materials.
EXCEPTION: Plastic covers having a thickness ofO.OIO inch or less may be of
any plastic, provided the total area of the collectors does not exceed 33 !1J percent of
the roof area.
681
TABLE NO. 52-A
AREA LIMITATION AND SEPARATION REQUIREMENTS FOR EXTERIOR WALL PANELS1
MINIMUM SEPARATION
OF PANELS
MAXIMUM PERCENT AREA MAXIMUM SQUARE FEET MAXIMUM (Feet)
OF EXTERIOR WALLS IN SINGLE INDIVIDUAL PANEL HEIGHT
CLASS OF PLASTIC PLASTIC PANELS PANELS (Feet) Vertical Horizontal
CCI 25 100 16 6 4
CC2 15 75 8 8 4
1The maxtmum percent area of ex tenor walls hmttatwn shall be based upon the mdtvtdual story wall area.
c
z
~
:D
s:::
IJI
c
r0
z
G)
0
0
!il
1982 EDITION 5401-5404
Chapter 53
(SEE APPENDIX CHAPTER 53)
Chapter 54
GLASS AND GLAZING
Scope
Sec. 5401. (a) General. The provisions of this chapter apply to:
I . Exterior glass and glazing in all occupancies except Groups R and M not
over three stories in height; and
2. Interior and exterior glass and glazing in all occupancies subject to human
impact as specified in Section 5406.
(b) Standards. Standards for material shall be as specified in this chapter and
U.B.C. Standard No. 54-I.
Standards for glazing subject to human impact (hazardous location) as spec-
ified in Section 5406 shall be as specified in U.B.C. Standard No. 54-2.
(c) Other Provisions. See Part IV of this code for additional glass require-
ments where openings are required to be fire protected and Section 5204 for
openings glazed with plastics.
Identification
Sec. 5402. Each light shall bear the manufacturer's label designating the type
and thickness of glass. When approved by the building official, labels may be
omitted, provided an affidavit is furnished by the glazing contractor certifying
that each light is glazed in accordance with approved plans and specifications.
Identification of glazing in hazardous locations shall be in accordance with
Section 5406.
Area Limitations
Sec. 5403. Exterior glass and glazing shall be capable of safely withstanding
the loads for cladding set forth in Section 2311 . The area of individual lights shall
be not more than set forth in Table No. 54-A or as adjusted by Table No. 54-B.
Glazing Support
Sec. 5404. Glass firmly supported on all four edges shall be glazed with
minimum laps and edge clearances set forth in Table No. 54-C. For glass not
firmly supported on all four edges, design shall be submitted to the building
official for approval. Glass supports shall be considered firm when deflection of
the support at design load does not exceed 1/m of the span.
683
5405-5406 UNIFORM BUILDING CODE
Louvered Windows
Sec. 5405. Regular plate, sheet or patterned glass in jalousies and louvered
windows shall be no thinner than nominal 7/32 inch and no longer than 48 inches.
When other glass types are used, design shall be submitted to the building official
for approval. Exposed glass edges shall be smooth.
Wired-glass with wire exposed on longitudinal edges shall not be used in
jalousies or louvered windows.
Safety Glazing
Sec. 5406. (a) General. Glazing subject to human impact shall comply with
this section.
EXCEPTION: Louvered windows or jalousies complying with Section 5405
need not comply with Subsection (c) of this section.
(b) Identification. Each light of safety glazing material installed in hazardous
locations as defined in Section 5406 (d) shall be identified by a label which will
specify the labeler, whether the manufacturer or installer, and state that safety
glazing material has been utilized in such installation. For additional identifica-
tion requirements and for limitation on size and use by category classification, see
U.B.C. Standard No. 54-2, Part I.
Each unit of tempered glass shall be permanently identified by the manufac-
turer. The identification shall be etched or ceramic fired on the glass and be visible
when the unit is glazed. Tempered spandrel glass is exempted from permanent
labeling but such glass shall be identified by the manufacturer with a removable
paper label.
(c) Human Impact Loads. Individual glazed areas in hazardous locations
such as those indicated in Section 5406 (d) shall pass the test requirements of Part
I of U .B.C. Standard No. 54-2 or by comparative tests approved by the building
official which shall be proved to produce at least equivalent performance.
EXCEPTION: Polished wired glass complying with Part II of U .B.C. Standard
No. 54-2 may be used in fire assemblies and in locations specified in Items Nos. 6
and 7 of Section 5406 (d).
Plastic glazing used in exterior applications also shall comply with the weather-
ing requirements in Part I of U. B.C. Standard No. 54-2.
(d) Hazardous Locations. The following shall be considered specific haz-
ardous locations for the purposes of glazing:
I. Glazing in ingress and egress doors except jalousies.
2. Glazing in fixed and sliding panels of sliding-type doors other than ward-
robe doors.
3. Glazing in storm doors.
4. Glazing in all unframed swinging doors.
5. Glazing in shower and bathtub doors and enclosures.
6. Glazing, operable or inoperable adjacent to a door in all buildings and
within the same wall plane as the door whose nearest vertical edge is within
12 inches of the door in a closed position and whose bottom edge is less
than 60 inches above the floor or walking surface.
684
1982 EDITION 5406-5407
7. Glazing in fixed panels other than those covered by Item No. 6 which have
a glazed area in excess of 9 square feet and the lowest edge is less than 18
inches above the finished floor level or walking surface within 36 inches of
such glazing. In lieu of safety glazing, such glazed panels may be protected
with a horizontal member not less than I V2 inches in width when located
between 24 and 36 inches above the walking surface.
EXCEPTION: The following products, materials and uses are exempt from the
above hazardous locations:
l. Openings in doors through which a 3-inch sphere is unable to pass.
2. Assemblies of leaded glass or faceted glass and items of carved glass when
used for decorative purposes in doors or in locations described in Section 5406 (d),
Item No. 6or7, above.
3. Glazing materials used as curved glazed panels in revolving doors.
4. Commercial refrigerated cabinet glazed doors.
(e) Wardrobe Doors. Glazing in wardrobe doors shall meet the impact test
requirements for safety glazing as set forth in U .B.C. Standard No. 54-2, Part II.
Laminated glass must also meet the boil test requirements of U. B.C. Standard
No. 54-2, Part II.
EXCEPTION: The impact test shall be modified so that if no breakage occurs
when the impacting object is dropped from the height of 18 inches, the test shall
progress in height increments of6 inches until the maximum of 48 inches is reached.
Hinged Shower Doors
Sec. 5407. Hinged shower doors shall open outward.
685
TABLE NO. 54-A-MAXIMUM ALLOWABLE AREA OF GLASS 1
(In Square Feet)
1.5 27 48 54 60 71 96 12.1 18.1 214 110 150 418 ().17 27 .18 61 7.1 86 124 142 162 207
20 21 16 40 4.5 51 72 92 117 176 212 262 128 478 20 28 47 5.5 64 91 107 122 !55
.10 14 24 27 .30 36 48
I 62 92 117 !55 17.'5 219 319 14 19 .12 .36 4.3 62 71 81 104
'
15 12 21 21 :w 11 41 I 53 79 100 111 !.50 188 271 12 16 27 31 .37 51 61 69 89
!
40 10 18 20 22 27 .36 46 69 H8 116 111 IG4 219 10 14 24 27 12 46 5.3 61 78
I I
45 9 lG
i 18 20 24 32 41 61 I
78 103 117 H6 212 9 11 21 24 29 41 47 54 69
I I
50 8 14 I 16 18 I 21 29 37 5'j 70 93 !0.5 131 191 8 II 19 22 26 37 43 49 62
APPROXIMATE
GLASS TYPE RELATIONSHIP
I. Laminated ................................. . 0.6
2. Wired ..................................... . 0.5
3. Heat-strengthened ........................... . 2.0
4. Fully tempered .............................. . 4.0
5. Factory-fabricated Double Glazing2 .............. . 1.5
6. Rough Rolled Plate .......................... . 1.0
7. Sandblasted ................................ . Varies'
8. Regular Plate, Float or Sheet ................... . 1.0
1To determine the maximum allowable area for glass types listed in Table No. 54-B multiply
the allowable area established in Table No. 54-A by the appropriate adjustment factor.
Example: For Y-inch heat-strengthened glass determine the maximum allowable area for
a 30-pound-per-square-foot wind load requirement. Solution procedure: Use Table No.
54-A to determine the established allowable area for V.-inch plate or float glass. Answer:
36 square feet, then multiply 36 by 2-the heat-strengthened glass adjustment factor.
Answer: 72.
2Use thickness of the thinner of the two lights, not thickness of the unit.
3 To be approved by the building official since adjustment factor varies with amount of
depreciation and type of glass.
~ "2 l!J ,
6. Minimum Glass Edge Clearance. ~' " V.."
Re-
qui red
above
7. Continuous Glazing Rabbet third
and Glass Retainer J . . . . . . . . . story Required
4 Required
8. Resilient Setting Material Not Required
687
54-C UNIFORM BUILDING CODE
CHAPTERS 55-59
NO REQUIREMENTS
688
1982 EDITION 6001
Part XI
UNIFORM BUILDING CODE STANDARDS
Chapter 60
UNIFORM BUILDING CODE STANDARDS
Scope
Sec. 6001. The U. B.C. Standards which are referred to in various parts of this
code shall be the Uniform Building Code Standards, 1982 Edition, and are hereby
declared to be a part of this code.
U.B.C.
STD. AND
SEC. NO. TITLE AND SOURCE
CHAPTER4
4-1;415
Noncombustible Material-Tests. Standard Method of Test E136-79 of the I
ASTM.*
CHAPTER 6
6-1; 608, 3904
Proscenium Curtains. Installation Standard of the International Conference of
Building Officials.
CHAPTER 17
17-1; 1707 (a)
Kraft Waterproof Building Paper. Federal Specification UU-B 790a, February 5,
1968.
17-2; 1712 (b) 7
Test Method to Determine Potential Heat of Building Materials. Test Standard of the
International Conference of Building Officials
17-3; 1712 (a)
Test Method for the Evaluation of Thermal Barriers. Standard of the International
Conference of Building Officials
17-4; 1712 (b) 5
Fire Test Standard for Insulated Roof Deck Construction. Factory Mutual Standard
and Subject 1256 (March, 1974) of the Underwriters Laboratories Inc.
17-5; 1712 (c)
Room Fire Test Standard for Interior of Foam Plastic Systems. Test Standard of the
International Conference of Building Officials.
CHAPTER 18
18-1; 1807 (i), 1807 (I) 6, App. 721
Fire Alarm and Standby Power-generating Systems for High-rise Buildings. Instal-
lation Standard of the International Conference of Building Officials.
689
6001 UNIFORM BUILDING CODE
CHAPTER 23
23-1; 2312 (d)
Determination of the Characteristic Site Period, Ts. Engineering Standard of the
International Conference of Building Officials.
CHAPTER 24
24-1; 2403 (b), 2404 (c) 2 A, 2418 (c) 2 A
Building Brick, Facing Brick and Hollow Brick. (Made from Clay or Shale.)
Standard Specifications C62-58, C216-66 and C652-70 of the ASTM.
24-2; 2403 (c)
Sand-lime Building Brick. Standard Specification C73-67 of the ASTM.
24-3; 2403 (d)
Concrete Building Brick. Standard Specification C55-55 of the ASTM.
24-4; 2403 (e), Table No. 43-B
Hollow Load-bearing Concrete Masonry Units. Standard Specification C90-70 of
the ASTM.
24-5; 2403 (e)
Solid Load-bearing Concrete Masonry Units. Standard Specification Cl45-59 of
the ASTM.
24-6; 2403 (e)
Hollow Nonload-bearing Concrete Masonry Units. Standard Specification C 129-59
of the ASTM.
24-7; 2403 (e)
Method of Test for Concrete Masonry Units. Standard Methods Cl40-70 of the
ASTM.
24-8; 2403 (f)
Structural Clay Load-bearing Wall Tile and Standard Methods of Sampling and
Testing Structural Clay Tile. Standard Specificiation C34-70 and Standard Method
Cll2-70 of the ASTM.
24-9; 2403 (f)
Structural Clay Nonload-bearing Tile. Standard Specification C56-70 of the ASTM.
I Mill Mixed Gypsum Concrete and Poured Gypsum Roof Diaphragms. Standard
Specification C317-70 of the ASTM. Poured Gypsum Roof Diaphragms, based on
reports of test programs by S. B. Barnes and Associates, dated February, 1955;
November, 1956; January, 1958; and February, 1962.
24-13; 2403 (g)
Cast Stone. Specification ACI 704-44 of the American Concrete Institute.
24-14; 2403 (h), 2405 (b)
Unburned Clay Masonry Units and Standard Methods of Sampling and Testing
Unburned Clay Masonry Units. Test Standard of the International Conference of
Building Officials.
24-15; 2403 (m), 2603 (f) 3
I Cold-drawn Steel Wire for Concrete Reinforcement. Standard Specification A82-79
of the ASTM.
690
1982 EDITION 6001
691
6001 UNIFORM BUILDING CODE
I
Structural Glued-laminated Timbers: Softwood and Hardwood Species. Standard
Specifications for Structural Glued-laminated Timber of Softwood Species ( 1979),
American Institute of Timber Construction, and Standard Specification for Hard-
wood Glued-laminated Timber ( 1976), American Institute of Timber Construction.
25-12; 2502 (a), 2505,2516 (c), 2909 (a) I
Preservative Treatment by Pressure Processes and Quality Control Standards. Stan-
dard Specifications CI-74, C2-74, C3-74, C4-74, C9-72, C23-74 and C28-73 of the
I
American Wood Preservers Association and CP-79, LP2-80, LP3-78, LP4-78,
LP5-78, LP7-78, LP22-80, LP33-78, LP44-78, LP55-78, LP77-78 and FDN-80 of
the American Wood Preservers Bureau.
25-13; 2504 (b)
Wood Poles. Specifications and Dimensions for Wood Poles, ANSI 05.1-1972 of
the American National Standards Institute, Inc.
25-14; 2504 (b), 2909 (a) I
Round Timber Piles. Standard Specification D25-73 of the ASTM.
25-15; 2507 (a) 2
Spaced Columns. National Design Specification for Wood Construction (1977),
including the 1980 Supplement, National Forest Products Association.
25-17; 2510 (a), 2510 (b), 2510 (c), 2510 (d), 2510 (e), 2510 (h), 2514 (b) I, 2514 (b) 2,
2516 (j) I, 3203 (c) 4, Tables Nos. 25-F, 25-G, 25-H and 47-H
I
Timber Connector Joints, Bolted Joints, Drift Bolts and Wood Screws, and Lag
Screws. National Design Specification for Wood Construction ( 1977), including the
1980 Supplement, National Forest Products Association. Light Metal Plate Con-
nected Wood Truss Design, Design Specification for Light Metal Plate Connected
692
1982 EDITION 6001
Wood Trusses TPJ-68, Truss Plate Institute. Nails and Staples, Federal Specification
No. FF-N-IOSB (March 17, 1971).
25-18; 2512
Structural Glued Built-up Members-Plywood Components. Design and Fabrica-
tion Specifications of American Plywood Association.
25-19; 2517 (e) 2
Adhesives. Standard Specification D2559-72, Adhesives for Structural Laminated
Wood Products for Use Under Exterior (Wet-use) Exposure Conditions and Stan-
dard Specification D3024-72, Protein Base Adhesive for Structural Laminated
Wood Products for Use Under Interior (Dry-use) Exposure Conditions of the
ASTM, and American Plywood Association Specification AFG-01, September,
1974.
25-20
Test For Glue Joints in Laminated Wood Product. Standard Test Method D II 01-59
of the ASTM, and AITC 200-73 American Institute of Timber Construction refer-
enced in PS 56-73.
25-21; Tables Nos. 25-U-J-1, 25-U-J-6, 25-U-R-1, 25-U-R-2, 25-U-R-7, 25-U-R-8, 25-U-
R-10, 25-U-R-11, 25-U-R-13 and 25-U-R-14
Span Tables for Joists and Rafters. Specification Standard of the International
Conference of Building Officials.
25-22
Plank-and-Beam Framing. Wood Construction Data No.4 (1970) of the National
Forest Products Association.
25-23
Tests for Structural Glued-laminated Lumber. Inspection Manual, AITC 200-73 of
American Institute of Timber Construction, referenced in Voluntary Product Stan-
dard PS 56-73, the basis for U.B.C. Standard No. 25-10 and Standard Methods of
Testing D805-63 of the ASTM.
25-24; 2502 (a), 2514, 2516 (g) 4
Cellulosic Fiber Insulating Board (Fiberboard). Voluntary Product Standard PS
57-73, U.S. Department of Commerce, National Bureau of Standards.
I
25-25; 2502 (a), 2516 (g) 5, 2517 (f)
Mat-formed Wood Particleboard. American National Standard for Mat-formed
Wood Particleboard, ANSI 208.1-1979. I
25-26; 2502 (a), 2516 (g) 6
Hardboard Siding. Voluntary Product Standard PS 60-73 of the United States I
Department of Commerce.
25-27; 2504 (c) 9
Temperature Effects. National Design Specification for Wood Construction ( 1977),
including the 1980 Supplement, National Forest Products Association.
I
CHAPTER 26
26-1; 2403 (o), 2603 (c), 2604 (f) 2
Portland Cement and Blended Hydraulic Cements. Standard Specifications
CIS0-81 andC595-8laoftheASTM. Ill
26-2; 2603 (d), 2708 (d)
Concrete Aggregates. Standard Specification C33-81 of the ASTM. Ill
693
6001 UNIFORM BUILDING CODE
26-3; 2602, 2603 (d), 2604 (b), 2708 (d), Table No. 27-C
Lightweight Aggregates for Structural and Insulating Concrete. Standard Specifica-
Ill tions C330-80 and C332-80 of the ASTM.
26-4; 2403 (!), 2603 (f) 2, 2603 (f) 3, 2625 (d) 2
I Welded Steel Wire Fabric and Deformed Steel Wire. Standard Specifications
Al85-79, A496-78 and A497-79 of the ASTM.
26-7; 2603 (f) 4, 2909 (e) 2
I Steel Wire, Strand and Bar for Prestressing. Standard Specifications A416-80,
A421-80 and A722-75 of the ASTM.
26-8; 2603 (f) I, 2603 (i), 2612 (p) 3
Welding Reinforcing Steel, Metal Inserts and Connections in Reinforced Concrete
I Construction. AWS D1.4-79 of the American Welding Society.
26-9; 2603 (g)
Admixtures for Concrete. Standard Specifications C494-80, C260-77 and C618-80
oftheASTM.
26-10; 2604 (e), 2604 (i) 2, 2604 Ul. 2604 (i) 3
Concrete Tests. Part !-Making and Curing Concrete Test Specimens in the Labora-
tory. Part 11-Making and Curing Concrete Compression and Flexure Test Speci-
mens in the Field. Part III--Obtaining and Testing Drilled Cores and Sawed Beams
of Concrete. Part IV--Compressive and Flexural Tests. Part V- Capping Cylindri-
I
cal Concrete Specimens. Part VI-Sampling Fresh Concrete. Standard Method
C31-69 (1980), Standard Method of Test C39-80, Standard Method C42-77, Stan-
dard Method of Test C78-75 (1978), Standard Method C 192-81, Standard Method
C617 -76 ( 1978) and Standard Method C 172-71 ( 1977) of the ASTM.
26-11; 2604 (h)
Evaluation of Compression Test Results in Field Concrete. American Concrete
Institute Standard 214-65.
26-12; 2602, 2604 (c) 2 H
I Splitting Tensile Strength. Standard Test Method C496-71 (1979) of the ASTM.
26-13; 2605 (b)
I Ready-mixed Concrete. Standard Specification C94-81 of the ASTM.
CHAPTER 27
27-1; 2603 (f) 5, 2721 (b), 2909 (f) I, 2909 (g) I
Material Specifications for Structural Steel. Standard Specifications A27, A36,
A48, A53, Al48, A242, A252, A283, A307, A325, A441, A446, A490, A500,
I A501, A514, A529, A570, A572, A588, A606, A607, A611, A618, A633, A666
and A715 of the ASTM.
27-2; 2701 (b), 2719, 2720, 2721 (k)
Erection, Fabrication, Identification and Painting of Structural Steel. Specifications
for the Design, Fabrication and Erection of Structural Steel for Buildings of the
American Institute of Steel Construction, Inc. (February I, 1969).
694
1982 EDITION 6001
I
of Steel Construction, Inc. (February, 1969).
27-4~ 2701 (b), 2715 (a)
Open Web Steel Joists, Standard Specifications for Open Web Steel Joists, H Series;
Longspan Steel Joists, LH Series; Deep Longspan Steel Joists, DLH Series; and
Joist Girders, 1978 (including 1980 revisions), of the Steel Joist Institute.
27-5; 2713 (a)
Structural Rivet Steel. Standard Specification A502-65 of the ASTM.
27-6; 2702 (e), 2714 (a). 2722 (a). 2722 (f). Table No. 27-B
Welding. American Welding Society. Inc .. Structural Welding Code. D I. 1-Rev.
2-77.
I
27-7; 2713 (a). Table No. 27-A
High-strength Bolts. Specification for Structural Joints Using ASTM A325 or A4\IO
Bolts. February. I \176, as endorsed by the American Imtitute of Steel Construction.
Inc .. and Industrial Fastening Institute.
27-8
Shear Connectors for Composite Construction. Specification for the Design. Fab-~
ric at ion and Erection of Structural Steel for Buildings of the American Institute of
Steel Construction. Inc. (1978). and American Welding Society. Inc .. Structural
Welding Code. DI.I-Rev. 2-77.
27-\1; 2701 (b). 3203 (c) 3
Specifications and Design of Cold-formed Steel Structural Members. Standard
Specifications A36. A242. A441. A446. A52\l, A570. A572. A588. A606. A607
A611 and A 715 of the ASTM and Specifications of the American Iron and Steel
1
Im.titute (I \180).
27-10; 2701 (b)
Specification for the Design of Cold-formed Stainless Steel Structural Members.
Specification Manual. I \174 Edition. American Iron and Steel Institute.
27 -II; 2724. Table No. 23-J
Steel Storage Racks. Interim Specification for the Design. Testing and Utilization of
Industrial Steel Storage Rack<.. I \172. and Supplement No. I to the Specification.
June 18. 1\173. of the Rack Manufacturers Institute.
27-12; 2725
Structural Applications of Steel Cables for Buildings. Criteria for Structural
Applications of Steel Cables for Buildings. 1\173 Edition. and Standard Specifica-
tions A586-68 ( 1\176). A603-70 (I \174) and B6-70 of the ASTM.
27-1.1; 2714 (a). 2714 (j)
Welding Sheet Steel. American Welding Society Specification for Welding Sheet i
Steel. AWS DU-78. fi
CHAPTER 28
28-1; 280 I (a). 2802 (a). 2802 (b). 2803 (a). 2803 (b). 2803 (d). 2804 (c). 2804 (c). 2804 ( 0.
Table No. 28-F
Standard for Aluminum Structures. Specifications for Aluminum Structures. Alu-
minum Association (November. 1967).
CHAPTER 29
2\1-1: 2\104 (a)
Soils Classification. Standard Method D2487-69 of the ASTM.
695
6001 UNIFORM BUILDING CODE
696
1982 EDITION 6001
697
.
6001 UNIFORM BUILDING CODE
698
1982 EDITION 6001
699
6001 UNIFORM BUILDING CODE
CHAPTER 70
70-I;App. 7010(e)
Moisture-density Relations of Soils. Tentative Methods of Test D1557-58T of the
ASTM.
70-2; App. 7010 (e)
In-place Density of Soils. Tentative Method of Test D1556-58Tofthe ASTM.
700
1982 EDITION APPENDIX
APPENDIX
Chapter 1
LIFE SAFETY REQUIREMENTS FOR
EXISTING BUILDINGS
Note: This Is a new Appendix chapter
General
Sec. 108. (a) Purpose. The purpose of this chapter is to provide a reasonable
degree of safety to persons occupying existing buildings that do not conform with
the minimum requirements of this code by providing for alterations to such
existing buildings.
EXCEPTION: Group R, Division 3 or Group M Occupancies.
(b) Effective Date. Within 18 months after the effective date of this appendix,
plans for compliance shall be submitted and approved, and within 18 months
thereafter the work shall be completed or the building shall be vacated until made
to conform.
(c) Alternate Materials and Methods. Alternate materials and methods may
be used, provided such materials or methods comply with the spirit and intent of
this appendix.
The building official may modify any of the provisions of this appendix in
conformance with Section 106 of this code.
Exits
Sec. 109. (a) Number of Exits. Every floor above the first story used for
human occupancy shall have access to at least two separate exits, one of which
may be an exterior fire escape complying with Subsection (d) of this section.
Subject to the approval of the building official, an approved ladder device may be
used in lieu of a fire escape when the construction feature or location of the
building on the property make the installation of a fire escape impracticable.
EXCEPTION: In all occupancies, second stories with an occupant load of 10 or
less may have one exit.
An exit ladder device when used in lieu of a fire escape shall conform with
U.B.C. Standard No. 33-3 and the following:
I. Serves an occupant load of 10 or less or a single dwelling unit or guest
room.
2. The building does not exceed three stories in height.
3. The access is adjacent to an opening as specified for emergency egress or
rescue or from a balcony.
4. Shall not pass in front of any building opening below the unit being served.
5. The availability of activating the device for the ladder is accessible only
from the opening or balcony served.
6. So installed that it will not cause a person using it to be within 6 feet of
exposed electrical wiring.
701
APPENDIX UNIFORM BUILDING CODE
(b) Stair Construction. All required stairs shall have a minimum run of 9
inches and a maximum rise of 8 inches and shall have a minimum width of 30
inches exclusive of handrails. Every stairway shall have at least one handrail. A
landing having a minimum 30-inch run in the direction of travel shall be provided
at each point of access to the stairway.
EXCEPTION: Fire escapes as provided for in this section.
Exterior stairs shall be of noncombustible construction.
EXCEPTION: On buildings of'!Ypes III, IV and V, provided the exterior stairs
are constructed of wood not less than 2-inch nominal thickness.
(c) Corridors. Corridors of Groups A, B, E, I, Hand R, Division I Occupan-
cies serving as an exit for an occupant load of 30 or more shall have walls and
ceilings of not less than one-hour fire-resistive construction as required by this
code. Existing walls surfaced with wood lath and plaster in good condition or 1/2-
inch gypsum wallboard or openings with fixed wired glass set in steel frames are
permitted for corridor walls and ceilings and occupancy separations when
approved. Doors opening into such corridors shall be protected by 20-minute fire
assemblies or solid wood doors not less than I% inches thick. Where the existing
frame will not accommodate the I %-inch-thick door, a !%-inch-thick solid
bonded wood core door or equivalent insulated steel door shall be permitted.
Doors shall be self-closing or automatic-closing by smoke detection. Transoms
and openings other than doors from corridors to rooms shall comply with Section
3305 (h) of this code or shall be covered with a minimum of %-inch plywood or
\12-inch gypsum wallboard or equivalent material on the room side.
EXCEPTION: Existing corridor walls, ceilings and opening protection not in
compliance with the above may be continued when such buildings are protected with
an approved automatic sprinkler system throughout. Such sprinkler system may be
supplied from the domestic water system if it is of adequate volume and pressure.
(d) Fire Escapes. I. Existing fire escapes which in the opinion of the building
official comply with the intent of this section may be used as one of the required
exits. The location and anchorage of fire escapes shall be of approved design and
construction.
2. Fire escapes shall comply with the following:
Access from a corridor shall not be through an intervening room.
All openings within 10 feet shall be protected by three-fourths-hour fire
assemblies. When located within a recess or vestibule, adjacent enclosure walls
shall be of not less than one-hour fire-resistive construction.
Egress from the building shall be by a clear opening having a minimum
dimension of not less than 29 inches. Such openings shall be openable from the
inside without the use of a key or special knowledge or effort. The sill of an
opening giving access shall be not more than 30 inches above the floor of the
building or balcony.
Fire escape stairways and balconies shall support the dead load plus a live load
of not less than 100 pounds per square foot and shall be provided with a top and
intermediate handrail on each side. The pitch of the stairway shall not exceed 60
degrees with a minimum width of 18 inches. Treads shall be not less than 4 inches
in width and the rise between treads shall not exceed 10 inches. All stair and
702
1982 EDITION APPENDIX
balcony railings shall support a horizontal force of not Jess than 50 pounds per
lineal foot of railing.
Balconies shall be not Jess than 44 inches in width with no floor opening other
than the stairway opening greater than Y8 inch in width. Stairway openings in such
balconies shall be not less than 22 inches by 44 inches. The balustrade of each
balcony shall be not less than 36 inches high with not more than 9 inches between
balusters.
Fire escapes shall extend to the roof or provide an approved gooseneck ladder
between the top floor landing and the roof when serving buildings four or more
stories in height having roofs with Jess than 4:12 slope. Fire escape ladders shall
be designed and connected to the building to withstand a horizontal force of I 00
pounds per lineal foot: each rung shall support a concentrated load of 500 pounds
placed anywhere on the rung. All ladders shall be at least 15 inches wide. located
within 12 inches of the building and shall be placed tlatwise relative to the face of
the building. Ladder rungs shall be % inch in diameter and shall be located 12
inches on center. Openings for roof access ladders through cornices and similar
projections shall have minimum dimensions of 30 inches by 33 inches.
The lowest balcony shall be not more than 18 feet from the ground. Fire escapes
shall extend to the ground or be provided with counterbalanced stairs reaching to
the ground.
Fire escapes shall not take the place of stairways required by the codes under
which the building was constructed.
Fire escapes shall be kept clear and unobstructed at all times and maintained in
good working order.
(c) Exit and Fire Escape Signs. Exit signs shall be provided as required by this
code.
EXCEPTION: The use of existing exit signs may be continued when approved
by the building official.
All doors or windows providing access to a fire escape shall be provided with
fire escape signs.
703
APPENDIX UNIFORM BUILDING CODE
704
1982 EDITION APPENDIX
Chapter7
Note: This Is a new Appendix chapter.
Part I
COVERED MALL BUILDINGS
General
Sec. 711. (a) Purpose. The putpose of this chapter is to establish minimum
standards of safety for the construction and use of covered mall buildings having
not more than three levels.
(b) Scope. The provisions of this chapter shall apply to buildings or structures
defined herein as covered mall buildings.
This chapter does not apply to terminals for transportation facilities and lobbies
of hotel, apartment and office buildings.
Covered mall buildings conforming with all other applicable provisions of this
code are not required to comply with the provisions of this chapter.
(c) Definitions. For the purpose of this chapter, certain terms are defined as
follows:
ANCHOR STORE is an exterior perimeter department store or major mer-
chandising center having direct access to a mall but having all required exits
independent of a mall.
COVERED MALL BUILDING is a single building enclosing a number of
tenants and occupancies such as retail stores, drinking and dining establishments,
entertainment and amusement facilities, offices and other similar uses wherein
two or more tenants have a main entrance into one or more malls.
GROSS LEASABLE AREA is the total floor area designed for tenant occu-
pancy and exclusive use. The area of tenant occupancy is measured from the
center lines of joint partitions to the outside of the tenant walls. All tenant areas,
including areas used for storage, shall be included in calculating gross leasable
area.
MALL is a roofed or covered common pedestrian area within a covered mall
building which serves as access for two or more tenants and may have three levels
that are open to each other.
(d) Applicability of Other Provisions. Except as specifically required by this
chapter, covered mall buildings shall meet all applicable provisions of this code.
TYpes of Construction and Required Yards for Unlimited Area
Sec. 712. (a) Type of Construction. One- and two-level malls may be of any
type of construction permitted by this code. Three-level malls shall be at least
l)tpe II One-hour construction.
Anchor stores and parking garages shall be limited in height and area in
accordance with Sections 505, 506 and 507.
(b) Required Yards for Unlimited Area. Covered mall buildings may be of
unlimited area, provided the covered mall building, attached anchor stores and
705
APPENDIX UNIFORM BUILDING CODE
parking garages are adjoined by public space, streets or yards not less than 60 feet
in width along all exterior walls.
Special Provisions
Sec. 713. (a) Automatic Sprinkler Systems. The covered mall building shall
be provided with an automatic sprinkler system conforming to the provisions of
U .B.C. Standard No. 38-1. In addition to these standards, the automatic sprinkler
system shall comply with the following:
I. All automatic sprinkler system control valves shall be electrically super-
vised by an approved central, proprietary or remote station or a local alarm
service which will give an audible signal at a constantly attended location.
2. The automatic sprinkler system shall be complete and operative throughout
all occupied space in the covered mall building prior to occupancy of any of
the tenant spaces. The level of protection provided for unoccupied tenant
space shall be subject to the approval of the building official and fire
department.
3. Sprinkler protection for the mall shall be independent from that provided
for tenant spaces. However, tenant spaces may be supplied by the same
system if they can be independently controlled.
The respective increases for area and height for covered mall buildings,
including anchor stores, specified in Sections 506 and 507 of this code, shall be
permitted.
(b) Standpipes. There shall be a Class I standpipe outlet connected to a system
sized to deliver 250 gallons per minute at each of the following locations for fire
department use:
I. Within the mall at the entrance to an exit passage or exit corridor.
2. At each floor level landing within enclosed stairways opening directly onto
the mall and adjacent to principal exterior entrances to the mall.
Standpipes shall be installed in accordance with the requirements of Chapter 38
of this code.
EXCEPTIONS: I. Risers and laterals of Class I standpipe systems not located
within an enclosed stairway need not be protected by a degree of fire resistance equal
to that required for vertical enclosures in the covered mall building.
2. Piping may be hydraulically sized.
Standpipes in covered mall buildings exceeding 50,000 square feet shall be
charged with water. The source of water may be either by interconnection with the
sprinkler system or may be connected with the domestic water supply by a
minimum of l-inch-diameter pipe. The domestic water supply connection shall
be provided with an approved backflow device.
(c) Smoke-control System. I. Purpose. The purpose of smoke control is to
restrict movement of smoke to the general area of fire origin and to maintain
means of egress in a usable condition.
2. General. Activation of the sprinkler system or smoke detectors shall
activate the smoke-control system. The smoke-control system shall also be
capable of manual operation. A smoke detector shall be provided within the
706
1982 EDITION APPENDIX
return-air portion of heating and cooling systems exceeding 10,000 cfm. The
detector shall be installed ahead of any fresh-air intake. Smoke detectors shall
also be provided on the tenant side at openings into the mall where open-type
security grilles are used. The smoke-control system shall be as follows:
A. The smoke-control equipment for the mall shall be separate from that
serving tenant spaces.
B. The covered mall building shall be compartmented into smoke-control
zones. Except for openings between the mall and tenant spaces, smoke-control
zones shall be separated from each other by construction having a fire-resistive
time period of not less than one hour. Walls between tenant spaces used to separate
smoke-control zones shall extend from the floor to the underside of the floor or
roof above.
C. A smoke control zone shall coincide with the area of coverage of a single
sprinkler supply. Within that sprinkler zone there may be one or more air-moving
systems but no single smoke-control zone shall be larger than the sprinkler area.
D. When a fire occurs within a tenant sprinkler zone, that zone is to go to 100
percent exhaust and the supply air to that zone is to be shut down. All adjoining
tenant areas are to go into normal operation. The mall itself shall go to I 00 percent
fresh air supply.
E. When a fire occurs within the mall, the mall smoke-control equipment shall
go to 100 percent exhaust and the adjoining tenant spaces shall go into normal
operation.
F. The mall smoke-control equipment shall be sized to provide a minimum of
six air changes per hour for malls 600,000 cubic feet or less in volume and four air
changes per hour for malls of greater size. The volume of the mall is measured
from the entrance to tenant spaces and to a height of 12 feet above each pedestrian
area.
G. Mall exhaust inlets shall be not less than 6 feet above the walking surface for
each pedestrian level.
H. During those hours when the building air-conditioning systems are not
operating, smoke detector or sprinkler systems shall be designed so the activation
of either will transmit an alarm as required in Subsection (a), Item No. I, of this
section and shall activate the smoke-control system.
3. Acceptance testing. Before the smoke-control system is accepted by the
building official, it shall be tested in his presence to confirm that the system is
operating in compliance with the requirements of this subsection.
(d) Fire Department Access to Equipment. Rooms or areas containing
controls for air-conditioning systems, automatic fire-extinguishing systems or
other detection, suppression or control elements shall be identified for use by the
fire department.
(e) Thnant Separation. Each tenant space shall be separated from other tenant
spaces by a wall having a fire-resistive rating of not less than one hour. The
separation wall shall extend from the floor to the underside of the ceiling above.
Except as required by other provisions of this code, the ceiling need not be a fire-
resistive assembly. A separation is not required between any tenant space and a
707
APPENDIX UNIFORM BUILDING CODE
mall except for occupancy separations required by Section 715 or for smoke-
control purposes.
(f) Public Address System. Covered mall buildings exceeding 50,000 square
feet in total floor area shall be provided with a public address system accessible
for use by the fire department. Covered mall buildings of 50,000 square feet or
less in total floor area, when provided with a public address system, shall have
such system accessible for use by the fire department.
(g) Plastic Panels and Plastic Signs. Within every story or level and from
sidewall to sidewall of each tenant space or mall, approved plastic panels and
signs shall be limited as follows:
I . They shall not exceed 20 percent of the wall area facing the mall;
2. They shall not exceed a height of 36 inches except that if the sign is vertical
then the height shall not exceed 96 inches and the width shall not exceed 36
inches;
3. They shall be located a minimum distance of 18 inches from adjacent
tenants;
4. All edges and the back shall be fully encased in metal.
(h) Lease Plan. Each covered mall building owner shall provide both the
building and fire departments with a lease plan showing the location of each
occupancy and its exits after the Certificate of Occupancy has been issued. Such
plans shall be kept current. No modifications or changes in occupancy or use shall
be made from that shown on the lease plan without prior approval of the building
official.
(i) Mixed Type of Construction. Openings between an anchor store of Type I,
11-F.R. or II One-hour construction and the mall need not be protected.
U) Standby Power. Covered mall buildings exceeding 50,000 square feet shall
be provided with standby power systems which are capable of operating the public
address system, the exit signs, emergency lighting, the smoke control activation
system and the smoke control equipment from four adjacent zones acting
simultaneously.
Exits
Sec. 714. (a) General. Each tenant space and the covered mall building shall
be provided with exits as required by this section and Chapter 33 of this code.
Where there is a conflict between the requirements of Chapter 33 and the
requirements of this section, the requirements of this section shall apply.
(b) Determination of Occupant Load. The occupant load permitted in any
individual tenant space in a covered mall building shall be determined as required
by Section 3302 of this code. Exit requirements for individual tenant spaces shall
be based on the occupant load thus determined.
The occupant load permitted for the covered mall building, assuming all
portions, including individual tenant spaces and the mall to be occupied at the
same time, shall be determined by dividing the gross leasable area by 30 for
covered mall buildings containing up to 150,000 square feet of gross leasable
area, by 40 for covered mall buildings containing between 150,001 and 350,000
708
1982 EDITION APPENDIX
square feet of gross leasable area, and by 50 for covered mall buildings containing
more than 350,000 square feet of gross leasable area. Exit requirements for the
covered mall building shall be based on the occupant load thus determined.
The occupant load of anchor stores opening into the mall shall not be included
in determining exit requirements for the mall.
(c) Number of Exits. Whenever the distance of travel to the mall from any
location within a tenant space used by persons other than employees exceeds 75
feet or the tenant space exceeds 1500 square feet, not less than two exits shall be
provided.
(d) Arrangement of Exits. Group A, Divisions l, 2 and 2.1 Occupancies,
other than drinking and dining establishments, shall be so located in the covered
mall building that their entrance will be immediately adjacent to a principal
entrance to the mall and shall have not less than one half of their required exits
opening directly to the exterior of the covered mall building.
Required exits for anchor stores shall be provided independently from the mall
exit system.
Malls shall not exit through anchor stores. Malls terminating at an anchor store
where no other means of exit has been provided shall be considered as a dead-end
mall.
(e) Distance to Exits. Within each individual tenant space in a covered mall
building the maximum distance of travel from any point to an exterior exit door,
horizontal exit, exit passageway, enclosed stairway or entrance to the mall shall
not exceed 200 feet.
The maximum distance of travel from any point within a mall to an exterior exit
door, horizontal exit, exit passageway or an enclosed stairway shall not exceed 200
feet.
(f) Access to Exits. Exits shall be so arranged that it is possible to go in either
direction from any point in a mall to a separate exit, except for dead ends not
exceeding a length equal to twice the width of the mall measured at the narrowest
location within the dead-end portion of the mall.
The minimum width of exit from a mall shall be 66 inches.
When exit passageways are present to provide a secondary exit from a tenant
space, doors to the exit passageway shall be one-hour fire doors. Such doors shall
be self-closing and be so maintained or shall be automatic closing by smoke
detector actuation.
Storage is prohibited in exit passageways which are also used for service to the
tenants. Such exit passageways shall be posted with conspicuous signs so stating.
(g) Malls. For the purpose of providing required egress, malls may be consid-
ered as corridors but need not comply with the requirements of Section 3305 (g)
and (h) of this code when the width of mall is as specified in this section.
The minimum width of the mall shall be 20 feet. There shall be a minimum of
I 0 feet clear width to a height of 8 feet between any projection from a tenant space
bordering the mall and the nearest kiosk, vending machine, bench, display or
other obstruction to egress. The mall shall be sufficient to accommodate the
occupant load immediately tributary thereto.
709
APPENDIX UNIFORM BUILDING CODE
Malls which do not conform to the requirements of this section shall comply
with the requirements of Section 3305 (g) and (h) of this code.
(h) Security Grilles and Doors. Horizontal sliding or vertical security grilles
or doors which are a part of a required means of egress shall conform to the
following:
I. They must remain secured in the full open position during the period of
occupancy by the general public.
2. Doors or grilles shall not be brought to the closed position when there are
more than I 0 persons occupying spaces served by a single exit or 50
persons occupying spaces served by more than one exit.
3. The doors or grilles shall be openable from within without the use of any
special knowledge or effort when the space is occupied.
4. When two or more exits are required, not more than one half of the exits
may be equipped with horizontal sliding or vertical rolling grilles or doors.
Occupancy
Sec. 715. (a) General. Covered mall buildings shall be classified as Group B,
Division 2 Occupancies and may contain accessory uses consisting of Groups A,
E orR, Division I Occupancies. The area of individual accessory uses within a
covered mall building shall not exceed three times the basic area permitted by
Table No. 5-C of this code for the type of construction and the occupancy
involved. The aggregate area of all accessory uses within a covered mall building
shall not exceed 25 percent of the gross leasable area.
An attached garage for the storage of passenger vehicles having a capacity of
not more than nine persons and open parking garages may be considered as
separate buildings when they are separated from the covered mall building by an
occupancy separation having a fire-endurance time period of at least two hours.
(b) Mixed Occupancy. Individual tenant spaces within a covered mall building
which comprise a distinct "Occupancy," as described in Chapters 5, 6, 7, 8, II
and 12 of this code, shall be separated from any other occupancy as specified in
Section 503 (d) of this code.
EXCEPTION: A main entrance which opens onto a mall need have no
separation.
Part II
AVIATION CONTROL TOWERS
General
Sec. 716. The provisions of this part apply exclusively to aviation control
towers not exceeding I ,500 square feet per floor. Such buildings shall be classi-
fied as Group B, Division 2 Occupancies and shall be used only for the following
uses:
I. Airport traffic control cab.
2. Electrical and mechanical equipment rooms.
710
1982 EDITION APPENDIX
TYPES OF CONSTRUCTION
1-F.R. I 11-F.R. I II One-hour I Ill One-hour
Unlimited I 240 I 100 I 65
711
APPENDIX UNIFORM BUILDING CODE
Chapter 11
AGRICULTURAL BUILDINGS
Scope
Sec. 1107. The provisions of this chapter shall apply exclusively to agri-
cultural buildings. Such buildings shall be classified as a Group M, Division 3
Occupancy and shall include the following uses:
I. Storage, livestock and poultry.
2. Milking barns.
3. Shade structures.
4. Horticultural structures (greenhouse and crop protection).
Construction, Height and Allowable Area
Sec. 1108. (a) General. Buildings classed as a Group M, Division 3 Occu-
pancy shall be of one of the types of construction specified in this code and shall
not exceed the area or height limits specified in Sections 505, 506 and 507 and
Table No. II-A.
(b) Special Provisions. The area of a Group M, Division 3 Occupancy in a
one-story building shall not be limited if the building is entirely surrounded and
adjoined by public space, street or yards not less than 60 feet in width, regardless
of the type of construction.
The area of a two-story Group M, Division 3 Occupancy shall not be limited if
the building is entirely surrounded and adjoined by public space, streets or yards
not less than 60 feet in width and is provided with an approved automatic sprinkler
system throughout, conforming to U.B.C. Standard No. 38-1.
Buildings using plastics shall comply with TYpe V-N construction. Plastics
shall be approved plastics regulated by Chapter 52. For foam plastic, see Sec-
tion 1712.
EXCEPTIONS: I. When used as skylights or roofs, the areas of plastic sky-
lights shall not be limited.
2. Except where designs must consider snow loads, plastics less than 20 mils
thick may be used without regard to structural considerations. The structural frame
of the building, however, shall comply.
Occupancy Separations
Sec. 1109. Occupancy separations shall be as specified in Section 503 and
Table No. 11-B.
Exterior Walls and Openings
Sec. 1110. Except where Table No. 17-A requires greater protection, exterior
walls of agricultural buildings shall be not less than one-hour fire-resistive
construction when less than 20 feet from property line.
Openings in exterior walls of agricultural buildings which are less than 20 feet
from property lines shall be protected by fire assemblies having a fire-protection
rating of not less than three-fourths hour.
712
1982 EDITION APPENDIX
Exit Facilities
Sec. 1111. Exit facilities shall be as specified in Chapter 33.
EXCEPTIONS: I. The maximum distance of travel from any point in the
building to an exterior exit door, horizontal exit, exit passageway or an enclosed
stairway shall not exceed 300 feet.
2. One exit is required for each 15,000 square feet of floor area and fraction
thereof.
3. Exit openings shall be not less than 2 feet 6 inches by 6 feet 8 inches.
713
,.
'V
TABLE NO. 11A-BASIC ALLOWABLE AREA FOR A GROUP M, DIVISION 3 OCCUPANCY, ONE STORY IN HEIGHT 'V
AND MAXIMUM HEIGHT OF SUCH OCCUPANCY m
z
c
><
I II III&IV v
!-Hour
F-R 1-llour !-Hour
I I " or Type IV
I " I "
Allowable Area'
Unlimited 60,000
I 27,100
I 18,000 27,100
I 18,000 21,100
I 12,000'
1See
Unlimited 1:2
I -4
I
Section 1108 for unlimited area under certain conditions.
:2 -4
I :2 3
I :2
c
TABLE NO. 11B- REQUIRED SEPARATIONS BETWEEN GROUP M, DIVISION 3 AND OTHER OCCUPANCIES z
(In Hours) ~l:J
3:
Occupancy .\ E I H B-1 B-2 B-3 B-4 R-1 R-3 M ID
c
Rating -4 -4 -4 -4 -4 1 1 1 1 1 r=c
" z
C)
0
0
Iii
1982 EDITION APPENDIX
Chapter 12
REQUIREMENTS FOR GROUP R,
DIVISION 3 OCCUPANCIES
General
Sec. 1201. (a) Purpose. The purpose of this chapter is to provide minimum
standards for the protection of life, limb, health, property, environment and for
the safety and welfare of the consumer, general public and the owners and
occupants of Group R, Division 3 Occupancies regulate4 by this code.
(b) Scope. The provisions of this chapter apply to the construction, prefabrica-
tion, alteration, repair, use, occupancy and maintenance of detached one- or two-
family dwellings not more than three stories in height and their accessory
structures.
One and 1\vo Family Dwelling Code Adopted
Sec. 1202. Buildings regulated by this chapter shall be designed and con-
structed to comply with the requirements of the One and Two Family Dwelling
Code, 1979 edition, promulgated jointly by the International Conference of
Building Officials; the Building Officials and Code Administrators International,
Inc., and the Southern Building Code Congress International, Inc.
715
APPENDIX UNIFORM BUILDING CODE
Chapter 23
EARTHQUAKE INSTRUMENTATION
Earthquake Recording Instrumentation
Sec. 2312. I. General. In Seismic Zones No. 3 and No.4 every building over
six stories in height with an aggregate floor area of 60,000 square feet or more,
and every building over 10 stories in height regardless of floor area, shall be
provided with not less than three approved recording accelerographs.
2. Location. The instruments shall be located in the basement, midportion,
and near the top of the building. Each instrument shall be located so that access is
maintained at all times and is unobstructed by room contents. A sign stating
"Maintain Clear Access to This Instrument" shall be posted in a conspicuous
location.
3. Maintenance. Maintenance and service of the instruments shall be pro-
vided by the owner of the building, subject to the approval of the building official.
Data produced by the instruments shall be made available to the building official
upon his request.
4. Instrumentation of existing buildings. All owners of existing structures
selected by the jurisdiction authorities shall provide accessible space for the
installation of appropriate earthquake-recording instruments. Location of said
instruments shall be determined by the jurisdiction authorities. The jurisdiction
authorities shall make arrangements to provide, maintain and service the instru-
ments. Data shall be the property of the jurisdiction, but copies of individual
records shall be made available to the public upon request and the payment of an
appropriate fee.
SEISMIC ZONE TABULATION
For Areas Outside the United States
Location Seismic Zone Location Seismic Zone
ASIA PACIFIC OCEAN AREA
Turkey Caroline Island
Ankara 2 Koror, Paulau 2
Karamursel 3 Po nape 0
ATLANTIC OCEAN AREA Johnston Island I
Azores 2 Kwajalein I
Bermuda I Mariana Islands
CARIBBEAN SEA Guam 3
Bahama Islands I Saipan 3
Canal Zone 2 Tin ian I
Leeward Islands 3 Marcus Island I
Puerto Rico 3 Okinawa 3
Trinidad Island 2 Philippine Islands 3
NORTH AMERICA Samoa Islands 3
Greenland Wake Island 0
Iceland
Keflavik 3
716
1982 EDITION APPENDIX
Chapter 32
RE-ROOFING
General
Sec. 3209. All re-roofing shall conform to the applicable provisions of Chapter
32 of this code.
Roofing materials and methods of application shall comply with Uniform
Building Code Standards or shall follow the manufacturer's installation require-
ments when approved by the building official.
Inspections
Sec. 3210. New roof coverings shall not be applied without first obtaining an
inspection and written approval from the building official. A final inspection and
approval shall be obtained from the building official when the re-roofing is
complete.
Built-up Roofs
Sec. 3211. (a) General. Built-up roof covering shall be completely removed
before applying the new roof covering.
EXCEPTION: The building official may allow existing roof coverings to remain
when inspection reveals that:
I. The structural design is sufficient to sustain the weight of an additional
roof.
2. There is not more than one existing roof on the structure.
3. The existing roof is securely attached to the deck.
4. The roof deck is not rotted and is structurally sound.
5. Existing insulation is not water soaked.
(b) Preparation of Roof and Application of New Covering. When the
conditions specified in Subsection (a) above have been met, the re-roofing shall
be accomplished as follows:
I. Gravel surfaced. The roof shall be cleaned of all loose gravel and debris. All
blisters shall be cut and made smooth. One-half-inch insulation board shall be
nailed or cemented to the existing roofing with hot bitumen applied at the rate of
40 pounds per square, over which a new roof complying with Section 3203 shall
be installed, or all existing gravel shall be removed to provide a smooth surface.
All blisters shall be cut and cemented or nailed smooth. A base sheet as defined in
the code shall be nailed in place. The base sheet shall not be mopped to the old
roofing. New roofing conforming to Section 3203 shall be applied.
2. Smooth or cap-sheet surfaced. All blisters and curled edges shall be cut
and cemented or nailed smooth. A base sheet shall be nailed or, in the case of
nonnailable decks, mopped to the existing roofing. New roofing conforming to
Section 3203 shall be applied.
3. Flashing and edgings. Vent flashings, metal edgings, drain outlets, metal
counterflashing and collars shall be removed and cleaned. Rusted metal shall be
replaced. Metal shall be primed with cutback primer prior to installation. Collars
and flanges shall be flashed per the roofing manufacturer's instructions.
717
APPENDIX UNIFORM BUILDING CODE
718
1982 EDITION APPENDIX
Chapter 35
SOUND TRANSMISSION CONTROL
Sound Transmission Control
Sec. 3501. (a) General. In Group R Occupancies, wall and floor-ceiling
assemblies separating dwelling units or guest rooms from each other and from
public space such as interior corridors and service areas shall provide airborne
sound insulation for walls, and both airborne and impact sound insulation for
floor-ceiling assemblies.
(b) Airborne Sound Insulation. All such separating walls and floor-ceiling
assemblies shall provide an airborne sound insulation equal to that required to
meet a Sound Transmission Class (STC) of 50 (45 if field tested) as defined in
U.B.C. Standard No. 35-1.
Penetrations or openings in construction assemblies for piping, electrical
devices, recessed cabinets, bathtubs, soffits, or heating, ventilating or exhaust
ducts shall be sealed, lined, insulated or otherwise treated to maintain the required
ratings.
Entrance doors from interior corridors together with their perimeter seals shall
have a laboratory-tested Sound Transmission Class (STC) rating of not less than
26 and such perimeter seals shall be maintained in good operating condition.
(c) Impact Sound Insulation. All separating floor-ceiling assemblies
between separate units or guest rooms shall provide impact sound insulation equal
to that required to meet an Impact Insulation Class (II C) of 50 (45 if field tested) as
defined in U.B.C. Standard No. 35-2. Floor coverings may be included in the
assembly to obtain the required ratings and must be retained as a permanent part
of the assembly and may be replaced only by other floor covering that provides the
same sound insulation required above.
(d) Tested Assemblies. Field or laboratory tested wall or floor-ceiling designs
having an STC or IIC of 50 or more as determined by U.B.C. Standard No. 35-1,
35-2 or 35-3 may be used without additional field testing when, in the opinion of
the building official, the tested design has not been compromised by flanking
paths. Tests may be required by the building official when evidence of compro-
mised separations is noted.
(e) Field Testing and Certification. Field testing, when required, shall be
done under the supervision of a professional acoustician who shall be experienced
in the field of acoustical testing and engineering and who shall forward certified
test results to the building official that minimum sound insulation requirements
stated above have been met.
(f) Airborne Sound Insulation Field Thsts. When required, airborne sound
insulation shalf be determined according to the applicable Field Airborne Sound
Transmission Loss Test procedures of U.B.C. Standard No. 35-3. All sound
transmitted from the source room to the receiving room shall be considered to be
transmitted through the test partition.
(g) Impact Sound Insulation Field Test. When required, impact sound
insulation shall be determined in accordance with U .B.C. Standard No. 35-2.
719
APPENDIX UNIFORM BUILDING CODE
720
1982 EDITION APPENDIX
Chapter 38
BASEMENT PIPE INLETS
Basement Pipe Inlets
Sec. 3807. (a) General. All basement pipe inlets shall be installed in accor-
dance with requirements of this section.
(b) Where Required. Basement pipe inlets shall be installed in the first floor
of every store, warehouse or factory having basements.
EXCEPTIONS: I. Where the basement is equipped with an automatic sprinkler
system as specified in Section 3802.
2. Where the basement is used for the storage of permanent archives or valuables
such as safe deposit vaults or similar uses adversely affected by water.
(c) Location. The location of basement pipe inlets shall be as required by the
fire department.
(d) Detailed Requirements. All basement pipe inlets shall be of cast iron,
steel, brass or bronze with lids of cast brass or bronze.
The basement pipe inlet shall consist of a sleeve not less than 8 inches inside
diameter extending through the floor and terminating flush with or through the
basement ceiling and shall have a top flange recessed with an inside shoulder to
receive the lid. The top flange shall be installed flush with finish floor surface.
The lid shall be a solid casting and have a lift recessed in the top. This lid shall be
provided with a cast-in sign reading: FIRE DEPARTMENT ONLY, DO NOT
COVER. The lid shall be installed in such a manner to permit its easy removal
from the flange shoulder.
721
APPENDIX UNIFORM BUILDING CODE
Chapter 49
PATIO COVERS
Patio Covers Defined
Sec. 4901. Patio covers are one-story structures not exceeding 12 feet in
height. Enclosure walls may have any configuration, provided the open area of the
longer wall and one additional wall is equal to at least 65 percent of the area below
a minimum of 6 feet 8 inches of each wall, measured from the floor. Openings
may be enclosed with insect screening or plastic.*
Patio covers may be detached or attached to other buildings as accessories to
Group M, Group R, Division 3, or to single dwelling units in Group R, Division I
Occupancies. Patio covers shall be used only for recreational, outdoor living
purposes and not as carports, garages, storage rooms or habitable rooms.
Design Loads
Sec. 4902. Patio covers shall be designed and constructed to sustain, within the
stress limits of this code, all dead loads plus a minimum vertical live load of 10
pounds per square foot except that snow loads shall be used where such snow
loads exceed this minimum. Such covers shall be designed to resist the minimum
horizontal wind loads set forth in this code, except that where less than 12 feet
high the horizontal wind load shall be as indicated in Table No. 49-A. In addition,
they shall be designed to support a minimum wind uplift equal to the horizontal
wind load acting vertical upward normal to the roof surface, except that for
structures not more than I 0 feet above grade the uplift may be three fourths of the
horizontal wind load. When enclosed with insect screening or plastic,* wind
loads shall be applied to the structure, assuming it is fully enclosed.
Light and Ventilation
Sec. 4903. Windows required for light and ventilation may open into a patio
structure conforming to Section 4901.
Footings
Sec. 4904. A patio cover may be supported on a concrete slab on grade without
footings, provided the slab is not less than 3Y2 inches thick and further provided
that the columns do not support live and dead loads in excess of 750 pounds per
column.
Less than 12 10 13 15 19 23 27 32
*The plastic referenced in Sections 490 I and 4902 is readily removable translucent or
transparent plastic not more than 0. 125 inch in thickness.
722
1982 EDITION APPENDIX
Chapter 51
ELEVATORS, DUMBWAITERS, ESCALATORS
AND MOVING WALKS
NO REQUIREMENTS
Chapter 53
ENERGY CONSERVATION IN NEW
BUILDING CONSTRUCTION
General
Sec. 5301. (a) Purpose. The purpose of this chapter is to regulate the design
and construction of the exterior envelopes and selection of heating, ventilating
and air-conditioning, service water heating, electrical distribution and illuminat-
ing systems and equipment required for the purpose of effective conservation of
energy within a building or structure governed by this code.
(b) Code for Energy Conservation in New Building Construction Adopted.
In order to comply with the purpose of this chapter, buildings shall be designed to
comply with the requirements of the Code for Energy Conservation in New
Building Construction promulgated jointly by the International Conference of
Building Officials (ICBO); the Southern Building Code Congress International,
Inc. (SBCCI); the Building Officials and Code Administrators International, Inc.
(BOCA); and the National Conference of States on Building Codes and Stan-
dards, Inc. (NCSBCS); dated December, 1977.
723
APPENDIX UNIFORM BUILDING CODE
Chapter 55
MEMBRANE STRUCTURES
General
Sec. 5501. (a) Purpose. The purpose of this chapter is to establish minimum
standards of safety for the construction and use of air-supported, air-inflated and
membrane-covered cable or frame structures, collectively known as membrane
structures.
(b) Scope. The provisions of this chapter shall apply to membrane structures
erected for a period of 180 days or longer. Those erected for a shorter period of
time shall comply with applicable provisions of the Uniform Fire Code.
EXCEPTION: Water storage facilities, water clarifiers, water treatment plants,
sewer plants, aquaculture pond covers, residential and agricultural greenhouses and
similar facilities not used for human occupancy need meet only the requirements of
Section 5502 (b) and Section 5505.
(c) Definitions. For the purpose of this chapter, certain terms are defined as
follows:
AIR-INFLATED STRUCTURE is a building where the shape of the structure
is maintained by air pressurization of cells or tubes to form a barrel vault over the
usable area. Occupants of such a structure do not occupy the pressurized area used
to support the structure.
AIR-SUPPORTED STRUCTURE is a building wherein the shape of the
structure is attained by air pressure and occupants of the structure are within the
elevated pressure area. Air-supported structures are of two basic types:
I. Single skin-Where there is only the single outer skin and the air pressure
is directly against that skin.
2. Double skin-Similar to a single skin, but with an attached liner which is
separated from the outer skin and provides an air space which serves for
insulation, acoustic, aesthetic or similar purposes.
A cable-restrained air-supported structure is one in which the uplift is resisted
by cables or webbing which are anchored to either foundations or dead men.
Reinforcing cable or webbing may be attached by various methods to the mem-
brane or may be an integral part of the membrane. This is not a cable-supported
structure.
CABLE STRUCTURE is a nonpressurized structure in which a mast and
cable system provides support and tension to the membrane weather barrier and
the membrane imparts structural stability to the structure.
FRAME-COVERED STRUCTURE is a nonpressurized building wherein
the structure is composed of a rigid framework to support tensioned membrane
which provides the weather barrier.
MEMBRANE is a thin, flexible, impervious material capable of being sup-
ported by an air pressure of 1.5 inches of water column.
NONCOMBUSTIBLE MEMBRANE STRUCTURE is a membrane struc-
ture in which the membrane and all component parts of the structure are noncom-
724
1982 EDITION APPENDIX
725
APPENDIX UNIFORM BUILDING CODE
2. Blowers shall be provided with inlet screens, belt guards and other protec-
tive devices as may be required by the building official to provide protec-
tion from injury.
3. Blowers shall be housed within a weather-protecting structure.
4. Blowers shall be equipped with back draft check dampers to minimize air
loss when inoperative.
5. Blower inlets shall be located to provide protection from air contamination.
Location of inlets shall be approved by the building official.
(c) Emergency Power. Whenever an auxiliary inflation system is required, an
approved standby power generating system shall be provided. The system shall be
equipped with a suitable means for automatically starting the generator set upon
failure of the normal electrical service and for automatic transfer and operation of
all the required electrical functions at full power within 60 seconds of such normal
service failure. Standby power shall be capable of operating independently for a
minimum of four hours.
Section Provisions
Sec. 5504. A system capable of supporting the membrane in the event of
deflation shall be provided in all air-supported and air-inflated structures having
an occupant load of more than 50 or when covering a swimming pool regardless of
occupant load. Such system shall maintain the membrane at least 7 feet above the
floor, seating area or surface of the water.
EXCEPTION: Membrane structures used as a roof for TYpe I or TYpe II fire-
resistant construction must be maintained not less than 25 feet above floor or seating
areas.
Engineering Design
Sec. 5505. All membrane structures shall be structurally designed in accor-
dance with criteria approved by the building official and developed by an engineer
or architect licensed by the state to practice as such.
726
1982 EDITION APPENDIX
Chapter 57
REGULATIONS GOVERNING FALLOUT SHELTERS
Purpose
Sec. 5701. The purpose of this chapter is to establish minimum criteria which
must be met before a building or building space can be constructed, occupied,
used or designated a fallout shelter.
Scope
Sec. 5702. The scope of this chapter extends to building spaces designated for
use as fallout shelters including periods of drill and instruction for this purpose.
Definitions
Sec. 5703. FALLOUT SHELTER is any room, structure or space designated
as such and providing its occupants with protection at a minimum protection
factor of 40 from gamma radiation from fallout from a nuclear explosion as
determined by a qualified fallout shelter analyst certified by the Office of Civil
Defense. Area used for storage of shelter supplies need not have a protection
factor of 40.
DUAL-USE FALWUT SHELTER is a fallout shelter having a normal,
routine use and occupancy as well as an emergency use as a fallout shelter.
SINGLE-PURPOSE FALWUT SHELTER is a fallout shelter having no
use or occupancy except as a fallout shelter.
PROTECTION FACTOR is a factor used to express the relation between the
amount of fallout gamma radiation that would be received by an unprotected
person and the amount that would be received by one in a shelter.
UNIT OF EGRESS WIDTH is 22 inches.
Occupancy Requirements
Sec. 5704. (a) General. Nothing in these regulations shall be construed as
preventing the dual use or multiple use of normal occupancy space as fallout
shelter space, providing the minimum requirements for each use are met.
(b) Mixed Occupancy. The occupancy classification shall be determined by
the normal use of the building. When a normal-use space is designed to have an
emergency use as a fallout shelter in addition to the normal use, the most
restrictive requirements for all such uses shall be met.
(c) Occupancy Separation. No occupancy separation is required between
that portion designated as a fallout shelter and the remainder of the building.
(d) Space and Ventilation. A minimum of 10 square feet of net floor area
shall be provided per shelter occupant. Partitions, columns and area for storage of
federal shelter supplies also may be included in net area. A minimum of 65 cubic
feet of volume shall be provided per shelter occupant. A minimum of 3 cubic feet
of fresh air per minute per person shall be provided.
In addition, the shelter shall have a ventilating rate sufficient to maintain a daily
average effective temperature of not more than 82F. for at least 90 percent of the
days of the year.
727
APPENDIX UNIFORM BUILDING CODE
728
1982 EDITION APPENDIX
Chapter 70
EXCAVATION AND GRADING
Purpose
Sec. 7001. The purpose of this chapter is to safeguard life, limb, property and
the public welfare by regulating grading on private property.
Scope
Sec. 7002. This chapter sets forth rules and regulations to control excavation,
grading and earthwork construction, including fills and embankments; estab-
lishes the administrative procedure for issuance of permits; and provides for
approval of plans and inspection of grading construction.
Permits Required
Sec. 7003. No person shall do any grading without first having obtained a
grading permit from the building official except for the following:
I. Grading in an isolated, self-contained area if there is no danger apparent to
private or public property.
2. An excavation below finished grade for basements and footings of a build-
ing, retaining wall or other structure authorized by a valid building permit. This
shall not exempt any fill made with the material from such excavation nor exempt
any excavation having an unsupported height greater than 5 feet after the comple-
tion of such structure.
3. Cemetery graves.
4. Refuse disposal sites controlled by other regulations.
5. Excavations for wells or tunnels or utilities.
6. Mining, quarrying, excavating, processing, stockpiling of rock, sand, grav-
el, aggregate or clay where established and provided for by law, provided such
operations do not affect the lateral support or increase the stresses in or pressure
upon any adjacent or contiguous property.
7. Exploratory excavations under the direction of soil engineers or engineering
geologists.
8. An excavation which (a) is less than 2 feet in depth, or (b) which does not
create a cut slope greater than 5 feet in height and steeper than one and one-half
horizontal to one vertical.
9. A fill less than I foot in depth and placed on natural terrain with a slope
flatter than five horizontal to one vertical, or less than 3 feet in depth, not intended
to support structures, which does not exceed 50 cubic yards on any one lot and
does not obstruct a drainage course.
Hazards
Sec. 7004. Whenever the building official determines that any ex1stmg
excavation or embankment or fill on private property has become a hazard to life
and limb, or endangers property, or adversely affects the safety, use or stability of
a public way or drainage channel, the owner of the property upon which the
excavation or fill is located, or other person or agent in control of said property,
729
APPENDIX UNIFORM BUILDING CODE
upon receipt of notice in writing from the building official, shall within the period
specified therein repair or eliminate such excavation or embankment so as to
eliminate the hazard and be in conformance with the requirements of this code.
Definitions
Sec. 7005. For the purposes of this chapter the definitions listed hereunder
shall be construed as specified in this section.
APPROVAL shall mean a written engineering or geological opinion con-
cerning the progress and completion of the work.
AS-GRADED is the extent of surface conditions on completion of grading.
BEDROCK is in-place solid rock.
BENCH is a relatively level step excavated into earth material on which fill is
to be placed.
BORROW is earth material acquired from an off-site location for use in
grading on a site.
CIVIL ENGINEER shall mean a professional engineer registered in the state
to practice in the field of civil works.
CIVIL ENGINEERING shall mean the application of the knowledge of the
forces of nature, principles of mechanics and the properties of materials to the
evaluation, design and construction of civil works for the beneficial uses of
mankind.
COMPACTION is the densification of a fill by mechanical means.
EARTH MATERIAL is any rock, natural soil or fill and/or any combination
thereof.
ENGINEERING GEOLOGIST shall mean a geologist experienced and
knowledgeable in engineering geology.
ENGINEERING GEOLOGY shall mean the application of geologic knowl-
edge and principles in the investigation and evaluation of naturally occurring rock
and soil for use in the design of civil works.
EROSION is the wearing away of the ground surface as a result of the
movement of wind, water and/or ice.
EXCAVATION is the mechanical removal of earth material.
FILL is a deposit of earth material placed by artificial means.
GRADE shall mean the vertical location of the ground surface.
Existing Grade is the grade prior to grading.
Rough Grade is the stage at which the grade approximately conforms to the
approved plan.
Finish Grade is the final grade of the site which conforms to the approved
plan.
GRADING is any excavating or filling or combination thereof.
KEY is a designed compacted fill placed in a trench excavated in earth material
beneath the toe of a proposed fill slope.
SITE is any lot or parcel of land or contiguous combination thereof, under the
730
1982 EDITION APPENDIX
731
APPENDIX UNIFORM BUILDING CODE
732
1982 EDITION APPENDIX
Other Fees:
Additional plan review required by changes, additions
I
or revisions to approved plans . . . . . . . . . . . . . . . . . . . . . . . . . . . $15.00 per hour
(minimum charge-~:me-half hour)
The fee for a grading permit authorizing additional work to that under a valid
permit shall be the difference between the fee paid for the original permit and the
fee shown for the entire project.
733
APPENDIX UNIFORM BUILDING CODE
Bonds
Sec. 7008. The building official may require bonds in such form and amounts
as may be deemed necessary to assure that the work, if not completed in
accordance with the approved plans and specifications, will be corrected to
eliminate hazardous conditions.
In lieu of a surety bond the applicant may file a cash bond or instrument of
credit with the building official in an amount equal to that which would be
required in the surety bond.
Cuts
Sec. 7009. (a) General. Unless otherwise recommended in the approved
soils engineering and/or engineering geology report, cuts shall conform to the
provisions of this section.
(b) Slope. The slope of cut surfaces shall be no steeper than is safe for the
intended use. Cut slopes shall be no steeper than two horizontal to one vertical.
(c) Drainage and Terracing. Drainage and terracing shall be provided as
required by Section 7012.
Fills
Sec. 7010. (a) General. Unless otherwise recommended in the approved
soils engineering report, fills shall conform to the provisions ofthis section.
In the absence of an approved soils engineering report these provisions may be
waived for minor fills not intended to support structures.
(b) Fill Location. Fill slopes shall not be constructed on natural slopes steeper
than two to one.
(c) Preparation of Ground. The ground surface shall be prepared to receive
fill by removing vegetation, noncomplying fill, topsoil and other unsuitable
materials scarifying to provide a bond with the new fill and, where slopes are
steeper than five to one and the height is greater than 5 feet, by benching into
sound bedrock or other competent material as determined by the soils engineer.
The bench under the toe of a fill on a slope steeper than five to one shall be at least
I 0 feet wide. The area beyond the toe of fill shall be sloped for sheet overflow or a
paved drain shall be provided. Where fill is to be placed over a cut, the bench
under the toe of fill shall be at least 10 feet wide but the cut must be made before
placing fill and approved by the soils engineer and engineering geologist as a
suitable foundation for fill. Unsuitable soil is soil which, in the opinion of the
building official or the civil engineer or the soils engineer or the geologist, is not
competent to support other soil or fill, to support structures or to satisfactorily
perform the other functions for which the soil is intended.
(d) Fill Material. Detrimental amounts of organic material shall not be per-
mitted in fills. Except as permitted by the building official, no rock or similar
irreducible material with a maximum dimension greater than 12 inches shall be
buried or placed in fills.
EXCEPTION: The building official may permit placement of larger rock when
the soils engineer properly devises a method of placement. continuously inspects its
placement and approves the fill stability. The following conditions shall also apply:
734
1982 EDITION APPENDIX
A. Prior to issuance of the grading permit, potential rock disposal areas shall be
delineated on the grading plan.
B. Rock sizes greater than 12 inches in maximum dimension shall be 10 feet or
more below grade, measured vertically.
C. Rocks shall be placed so as to assure filling of all voids with fines.
(e) Compaction. All fills shall be compacted to a minimum of 90 percent of
maximum density as determined by U.B.C. Standard No. 70-1. Field density
shall be determined in accordance with U .B.C. Standard No. 70-2 or equivalent
as approved by the building official.
(f) Slope. The slope of fill surfaces shall be no steeper than is safe for the
intended usc. Fill slopes shall be no steeper than two horizontal to one vertical.
(g) Drainage and Terracing. Drainage and terracing shall be provided and
the area above fill slopes and the surfaces of terraces shall be graded and paved as
required by Section 7012.
Setbacks
Sec. 7011. (a) General. The setbacks and other restrictions specified by this
section are minimum and may be increased by the building official or by the
recommendation of a civil engineer, soils engineer or engineering geologist, if
necessary for safety and stability or to prevent damage of adjacent properties from
deposition or erosion or to provide access for slope maintenance and drainage.
Retaining walls may be used to reduce the required setbacks when approved by
the building official.
(b) Setbacks from Property Lines. The tops of cuts and toes of fill slopes
shall be set back from the outer boundaries of the permit area, including slope-
right areas and easements, in accordance with Figure No. I and Table No. 70-C.
(c) Design Standards for Setbacks. Setbacks between graded slopes (cut or
fill) and structures shall be provided in accordance with Figure No. 2.
.H
Topof
PA'
I
H.
PA Toe
FIGURE N0.1
735
APPENDIX UNIFORM BUILDING CODE
SETBACKS
H a b'
Under 5 0 I
5- 30 H/2 H/5
Over 30 15 6
If
H/2 but need n..H
exceed I0' max.
FIGURE N0.2
736
1982 EDITION APPENDIX
(d) Disposal. All drainage facilities shall be designed to carry waters to the
nearest practicable drainage way approved by the building official and/or other
appropriate jurisdiction as a safe place to deposit such waters. Erosion of ground
in the area of discharge shall be prevented by installation of nonerosive down-
drains or other devices.
Building pads shall have a drainage gradient of 2 percent toward approved
drainage facilities, unless waived by the building official.
EXCEPTION: The gradient from the building pad may be I percent if all of the
following conditions exist throughout the permit area:
A. No proposed fills are greater than 10 feet in maximum depth.
B. No proposed finish cut or fill slope faces have a vertical height in excess of I 0
feet.
C. No existing slope faces, which have a slope face steeper than I 0 horizontally to
I vertically, have a vertical height in excess of I 0 feet.
(e) Interceptor Drains. Paved interceptor drains shall be installed along the
top of all cut slopes where the tributary drainage area above slopes towards the cut
and has a drainage path greater than 40 feet measured horizontally. Interceptor
drains shall be paved with a minimum of 3 inches of concrete or gunite and
reinforced. They shall have a minimum depth of 12 inches and a minimum paved
width of 30 inches measured horizontally across the drain. The slope of drain
shall be approved by the building official.
Erosion Control
Sec. 7013. (a) Slopes. The faces of cut and fill slopes shall be prepared and
maintained to control against erosion. This control may consist of effective
planting. The protection for the slopes shall be installed as soon as practicable and
prior to calling for final approval. Where cut slopes are not subject to erosion due
to the erosion-resistant character of the materials, such protection may be
omitted.
(b) Other Devices. Where necessary, check dams, cribbing, riprap or other
devices or methods shall be employed to control erosion and provide safety.
Grading Inspection
Sec. 7014. (a) General. All grading operations for which a permit is required
shall be subject to inspection by the building official. When required by the
building official, special inspection of grading operations and special testing shall
be performed in accordance with the provisions of Section 306 and
Subsection 7014 (c).
(b) Grading Designation. All grading in excess of 5000 cubic yards shall be
performed in accordance with the approved grading plan prepared by a civil
engineer, and shall be designated as "engineered grading." Grading involving
less than 5000 cubic yards shall be designated "regular grading" unless the
permittee, with the approval of the building official, chooses to have the grading
performed as "engineered grading."
(c) Engineered Grading Requirements. For engineered grading, it shall be
the responsibility of the civil engineer who prepares the approved grading plan to
incorporate all recommendations from the soils engineering and engineering
737
APPENDIX UNIFORM BUILDING CODE
geology reports into the grading plan. He also shall be responsible for the
professional inspection and approval of the grading within his area of technical
specialty. This responsibility shall include, but need not be limited to, inspection
and approval as to the establishment of line, grade and drainage of the develop-
ment area. The civil engineer shall act as the coordinating agent in the event the
need arises for liaison between the other professionals, the contractor and the
building official. The civil engineer also shall be responsible for the preparation
of revised plans and the submission of as-graded grading plans upon completion
of the work. The grading contractor shall submit in a form prescribed by the
building official a statement of compliance to said as-built plan.
Soils engineering and engineering geology reports shall be required as spec-
ified in Section 7006. During grading all necessary reports, compaction data and
soil engineering and engineering geology recommendations shall be submitted to
the civil engineer and the building official by the soils engineer and the engineer-
ing geologist.
The soils engineer's area of responsibility shall include, but need not be limited
to, the professional inspection and approval concerning the preparation of ground
to receive fills, testing for required compaction, stability of all finish slopes and
the design of buttress fills, where required, incorporating data supplied by the
engineering geologist.
The engineering geologist's area of responsibility shall include, but need not be
limited to, professional inspection and approval of the adequacy of natural ground
for receiving fills and the stability of cut slopes with respect to geological matters
and the need for subdrains or other groundwater drainage devices. He shall report
his findings to the soils engineer and the civil engineer for engineering analysis.
The building official shall inspect the project at the various stages of the work
requiring approval and at any more frequent intervals necessary to determine that
adequate control is being exercised by the professional consultants.
(d) Regular Grading Requirements. The building official may require
inspection and testing by an approved testing agency.
The testing agency's responsibility shall include, but need not be limited to,
approval concerning the inspection of cleared areas and benches to receive fill,
and the compaction of fills.
When the building official has cause to believe that geologic factors may be
involved the grading operation will be required to conform to "engineered
grading'' requirements.
(e) Notification of Noncompliance. If, in the course of fulfilling his respon-
sibility under this chapter, the civil engineer, the soils engineer, the engineering
geologist or the testing agency finds that the work is not being done in con-
formance with this chapter or the approved grading plans, the discrepancies shall
be reported immediately in writing to the person in charge of the grading work and
to the building official. Recommendations for corrective measures, if necessary,
shall be submitted.
(f) Transfer of Responsibility for Approval. If the civil engineer, the soils
engineer, the engineering geologist or the testing agency of record is changed
during the course of the work, the work shall be stopped until the replacement has
738
1982 EDITION APPENDIX
agreed to accept the responsibility within the area of his technical competence for
approval upon completion of the work.
Completion of Work
Sec. 7015. (a) Final Reports. Upon completion of the rough grading work
and at the final completion of the work the building official may require the
following reports and drawings and supplements thereto:
I. An as-graded grading plan prepared by the civil engineer including original
ground surface elevations, as-graded ground surface elevations, lot drainage
patterns and locations and elevations of all surface and subsurface drainage
facilities. He shall provide approval that the work was done in accordance with the
final approved grading plan.
2. A soil grading report prepared by the soils engineer including locations and
elevations of field density tests, summaries of field and laboratory tests and other
substantiating data and comments on any changes made during grading and their
effect on the recommendations made in the soils engineering investigation report.
He shall provide approval as to the adequacy of the site for the intended use.
3. A geologic grading report prepared by the engineering geologist including a
final description of the geology of the site including any new information dis-
closed during the grading and the effect of same on recommendations incorpo-
rated in the approved grading plan. He shall provide approval as to the adequacy
of the site for the intended use as affected by geologic factors.
(b) Notification of Completion. The permittee or his agent shall notify the
building official when the grading operation is ready for final inspection. Final
approval shall not be given until all work including installation of all drainage
facilities and their protective devices and all erosion-control measures have been
completed in accordance with the final approved grading plan and the required
reports have been submitted.
739
1982 EDITION INDEX
INDEX
For Index by parts, chapters and sections, see pages 7 to 18
Section
A-OCCUPANCIES .......... . ChapterS
ACCESS (see also HANDICAPPED)
To attic .................... . 3205 (a)
To building ......................... . 3301 (e)
To residential building 1213
To roof ............................ . 3306 (o)
To toilet facilities .................... . 511 (a)
ACCESSORY BUILDINGS ........... . 1101
ADDITIONS, to buildings ........ . 104
ADHERED VENEER .............. . 3002, 3004 (b), 3005
ADHESIVES, glued construction ...... . 2511, 2512, 2517 (e)
ADJOINING BUILDINGS (see also LOCATION ON PROPERTY)
Foundation to be protected .................. . 2903 (b)
wan protection .......... . 504(c)
ADMINISTRATIVE (see Part 1) .... Chapters 1, 2 and 3
ADMIXTURE. 2403 (q) 2, 2602. 2603 (g)
ADOBE CONSTRUCTION 2403 (h), 2405
AGED, HOMES FOR ... . .... Chapter 10
AGGREGATES
Concrete ......... .. .. ... 2603 (d)
Definition .. . .. . .. .. .. 2602
Masonry, mortar and grout ... . 2403 (r). 2403 (t)
Proportions in concrete ...... . .. 2604 (c)
Storage of ........... . .. ...... 2603 (h)
AGRICULTURAL BUILDINGS
Definition of ................. . .. .. .. .. .. .. . 402
General.... .. .......... .. Chapter 11, Appendix Chapter 11
AIR-CONDITIONED BUILDINGS ..... 3310(a)
AIRCRAFT HANGARS
Areas allowed ............ . 505,902 (b)
Classified .............. . . ........ '.'. 701,901
Exterior walls ....... . 702,902 (b)
Height ............ . 507
Ventilating equipment ..... . 705,905
AIR SPACE
Around timber in masonry ... 2516 (C)
AISLES ...................... . 3315
741
INDEX UNIFORM BUILDING CODE
APPLICATION
For perm1l, details required. . . . . . . . . . . . .. . 302, Appendix 7006 (b)
Of code to buildings or structures . .. .................. 103,104
To changed use or occupancy . . . . . 307 (b), 502
To ex1sl1ng buildings . 104, Appendix Chapter 1
APPROVAL
After called inspection . 305(d)
Final ....................... . 305 (c) and (d)
For storage of materials 1n street . 4403
For use of plastic materials . . 5201 (b)
Of fabricators ..
Of Federal Av1alion Agency .
................. ito;(~!
742
1982 EDITION INDEX
8
B--OCCUPANCIES . 701
BALCONY
Assembly, delinition. 403
Exits. 3317(c)
Extenor exit . 3301 (b), 3305
For smokeproof enclosures . . 3305,3310
May project over public property . 4504
Waterproofing . 1707 (c)
BARBECUES. Chapter 37
BARRICADES, construction. Chapter 44
743
INDEX UNIFORM BUILDING CODE
BARS
For concrete reinforcing (see REINFORCED CONCRETE)
Panic (see PANIC HARDWARE)
BASEMENT
Definition . . .................................. 403
Enclosure 1703
Pipe Inlets .. Appendix 3807
Protection of ce1ling 1703
Smoke detector required, residential. 1210(a)
Sprinklers, when required. 3802 (b)
BASE PLATE (see FOUNDATION PLATES)
BATHROOM
Required 1205 (b), 1208
BEAMS
Construction detatls. 2106 (g)
Reinforced concrete . 2608, 2609,2610, 2611
Retnforced masonry . . ............. 2417
Span, wood. 2506 (a)
Steel .................... . . ......... 2707
Tbeams of reinforced concrete . ..................... 2608 (k)
Wood. 2506,2511
Wood tn heavy timber constructton. . ....... 2106
BEARING
For wood beams and girders. 2506 (f), 2517 (c)
For wood JOists 2517 (d)
BEARING PARTITIONS (see WALLS)
BEARING WALLS (see WALLS)
BENDING MOMENTS (see REINFORCED CONCRETE)
BLEACHERS (see REVIEWING STANDS) . 3323,3324
BLOCKS, CONCRETE (see CONCRETE BLOCKS)
BOARD OF APPEALS. ................... 204
BOILER (see also UNIFORM MECHANICAL CODE)
Deflnillon of. 403
Room for (see BOILER ROOM)
BOILER ROOM
Definition. . ....... 403
Exits. spectal requirements . ....... .. 3322
For occupancy groups. "08" sections of Chapters 61 0; 1212
BOLTS
For foundations. ......................... 2907 (e)
In aluminum . . . . . . . . . . . . . . . . . . . . ......................... 2802 (c)
In masonry. 2405 (d), 2406 (c), 2408 (d), 2409 (d), 2410 (c),
2411 (d),2412(e),2416(k)
In reinforced concrete . ...... 2624
In steel construction. 2712,2713,2719
In wood construction 2510
BOND
For concrete 2612
For veneer .. .............. 3002,3004
Masonry ...... . 2411 (b),2412(d),2416(1)
Retnforcements. 2413,2414,2415,2612
BOX SYSTEM
Definition 2312(b)
BRACING
For foundation studs . 2517(g)
For reinforced concrete forms . . 2606 (a)
For stud walls and partitions. 2517(g)
744
1982 EDITION INDEX
BRIDGING
For concrete joists . . ...... 2610(e)
For wood joists .... 2506(g),2517(d)
BUII.DING CODE
Application 103,104
Enforced .. 202
Purpose. 102
Scope . . . . .......... . 103
Title .................... . 101
BUILDING MATERIALS
May be stored ... 4403
BUILDING OFFICIAL
Approvals required.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ................. . . . . . 304 (d)
Approves special inspector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
ACproves structural frame.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 305 (e), 4701 (b)
g:,~r~~~~~~c:,~k~:~~cy. : : : : : : : . : : : : : : : . : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : : Appendi~ 1~~
Cooperation of other officials . . . . . . . . . . . . . . . . . . . . . . . . . ............. 202 (g)
Definition. . . . . . . . . . . . . . . . . . . . . . . . .................................... 403
Deputies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202 (b)
Excavation report . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2903 (a)
Grading operations inspection . . Appendix 7014
Granting modifications . . . . . . . . . . . . . . . . . . . . . . . ................ 106
Issues permit . . . . . . . . . . . . . .................. 303
Liability.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202 (I), 305 (a)
May approve alternate construction or materials. . . . . . . . . . . . . . . . . . . . . . . . . . 105
May enter premises . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202 (c)
May order occupancy of building discontinued . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202 (e)
May require bonds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Appendix 7008
May require plans by licensed engineer or arcMect.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 302 (b)
May require special inspector. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 306
May require tests.. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107, 2603 (b), 4701 (c)
May stop work... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 202 (d)
Plastics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..................... 5201 (b)
Powers and duties . . . . . . . . . . . . . . . . . . . . .. .................. 202
Retention of plans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303 (b)
Shall make inspections . . . . . . . . . . . ............ 305
Shall require reports........................................................ 306 (c)
BUILDING OFFICIAL'S AUTHORIZATION REQUIRED
Before changing plans. . . . . . . . . . . . . . . . . . . . .............. . . . . . . . . . . . . . . . . . . . . . 303(a)
For changes of use or occupancy .... . . .................. 104 (c), 307 (b), 502
For structural alterations ............. . .............................. 303
BUILDING PERMITS
Expiration ........................ . .............. 303(d)
Fees ...................................... . ............ . .. 304
Issuance ...................................... . ....................... 303(8)
Suspension or revocation ........................ . ........................... 303(e)
Validity ....................... . . ........... 303(c)
When required .............................. . 301, Appendix 7003
BUILDINGS
Air-conditioned.. . . . . . . . . . . . . . . . . . . . . . . ............. . . 3310 (a)
Areas allowable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ............................. 505
Chan9.e in use . . . . . . . . . . . . . . . . . . . . . . . . . . ...................... 104 (c), 307 (b), 502
Classolied by type of construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1701
Classified by use or occupancy. . . . . . . . . . . . . . . . ........................... 501, 503
Definition . . . . . . . . . . . . . . . . . . . . . . . . . . ............................... . . . . . . 403
Drainage, around . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2905 (f)
Enerlly conservation in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Appendix Chapter 53
Existong . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104, 403, Appendix Chapter 1
Height, definition . . . . . . . . . . . . . . . . . . . . . . . . . . . .............. 409
~~~~~ ~~l~bl~........................ . .. . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. . .. .. .. .. . . . . . . . o~~n
. .. i
Location on same property . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 504 (c)
Membrane structures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Appendix Chapter 55
Moving....................................... ...................... 104 (e)
Nonconforming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104, Appendix Chapter 1
Site................................................ ....................... 2516 (b)
Temporary............................................................. 104 (e)
To be condemned. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
To be occupied . . . . . . . . . . . . . . . . . . . . ............................................. 307
To conform to code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103, 104
Two or more on same property. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 504 (c)
Unsafe......... . ........... 203
Unsafe appendages to . . . ................................ 203
745
INDEX UNIFORM BUILDING CODE
c
CANOPIES, CONSTRUCTION. 4505, 4506, 5213
CARPORT. 1214
CAISSONS 2312U)3B
CAST STONE. 404, 2403 (g)
CAVITY WALL MASONRY .. 2409
CEILING
Design load. . . . . . . . . . . . . . . .. . . .. .. . . . . . . . . . . . . . . . . . . 2304
Dropped ........................ . 1207,2516 (f), 4203,4303 (b), 4704
Fire-resistive required, basements . .. ........... 1703
For fire-protection purposes. 4303 (b), 4305
Framing. 2518(h)
Insulation. . . . . . . . . . . ...... . 1713
Mimmum height of dwelling .. 1207(a)
Mimmum height of garages . 709 (d), 1102 (b)
Panels ...................... . 4305 (d)
Suspended, acoustical systems for 4701 (e), 4704
CEMENT, PORTLAND (see PORTLAND CEMENT)
CENTRAL HEATING PLANT
Definition . .. 404
CERTIFICATE
Of Approval . . 5006 (b)
Of lnspect1on ........ . 2505
Of Occupancy, atriums. . . . . . . . . .. . 1715(i)
Of Occupancy, for change of use ... . 307,502
Of Occupancy, for high-rise bU1Id1ngs ........... . 1807(b)
Of Occupancy, issued to owner . . ............ 307
Of Occupancy, revocation . . 307 (f)
Of registration of fabricator .. 306(f)
Post1ng of. 307(e)
Temporary ... 307(d)
746
1982 EDITION INDEX
COMPLIANCE
Determined by inspection .. 305(a)
With code . 103
CONCRETE
Blocks of (see CONCRETE BLOCKS)
Bolts in. 2624
Bracing of forms . 2606 (a)
Combined with wood ........... . 2515
Compressive strength, definition. 2602
Conduits. 2606 (c)
Confined concrete. definition . 2625(b)
Construction 1oints. 2606 (d)
Conveying. 2605 (c)
Curing. 2605 (e)
Definition. 2602
747
INDEX UNIFORM BUILDING CODE
CORBELING
Of masonry walls . 2415(b)
CORRIDORS
As required exits .. ...... . 3305
In GroupE Occupancies. . ........... 3319
In Group H Occupancies 3320
..... 3321
:~ ~~0~~ ~~cf~ff\'~enSCieS.:. 1705(b)
COST (see also VALUATION)
Of permits. 304
748
1982 EDITION INDEX
COURT
Between buildings . 504 (c), 1206
Definition ... 404
Minimum width. 1206
Used as exit 3301 (b), 3311
COVERED MALLS . Appendix Chapter 7, Part I
COVERINGS
For exterior wood stud walls .... .. ........... 2516(g)
For exteriors, weather protection . 1707
For fire protection . 4303, 4304, 4305
For roofs. Chapter32
CURB
Allowed in alley. 4502
For skylights .. 3401' 5207
CURTAIN (see PROSCENIUM CURTAIN)
CURTAIN WALL (see also WALLS, NONBEARING)
Masonry, construction of ......................... . 2419
Reinforced concrete, construction of . . ........... . 2614,2616
D
DAMPERS, FIREPLACE. 3707 (i)
DAMPPROOFING FOUNDATION WALLS 1707(d)
DEFLECTION CRITERIA
General .... 2307
Interior walls .. 2309
DEMOLITION . 203,4409
DEPARTMENT
Creation of. 201
DEPTH OF FOUNDATIONS
Affects excavations ............. . 2903
Governed by frost line ................ . 2907 (a)
Governed by soil conditions . . ............................. . 2905
DESIGN
Aluminum ... . 2803
Concrete ...... . Chapter26
Footings and foundations. Chapter29
General. .............. . Chapter 23
Masonry......... .. ...... Chapter 24
Must be approved by building official. 303
Plastic, steel ... 2721
Retaining walls . 2308 (b)
Structural steel Chapter27
Walls 2309,2310,2416,2614,2616
Wood. Chapter 25
DETECTORS (see SMOKE DETECTORS)
DIMENSIONS
Unit masonry, defined . . ............. . 2402
DISPERSAL AREA, SAFE 3323
DISTANCE, between buildings 504
DOORS
Construction for fire-resistive rating . ................ . .. ... 4306
Corridor .. 3305 (h)
Exit ........................................................ . 3304
Fire-resistive, classification, design, hanging .......... . 4306
Fire-resistive, when required (see under OCCUPANCY
and TYPES OF CONSTRUCTION)
For fire separations . 503
For high-rise buildings ....... . 1807 (h), 0) and (I)
For motion picture machine booths . 4003
For smokeproof enclosures ............... . 3310 (f) and (g)
General requirements 3304,4306
Glass. 5406
749
INDEX UNIFORM BUILDING CODE
E
E-OCCUPANCIES . Chapter 8, 901 (b), 3319
EARTHQUAKES (see also LATERAL FORCE, PROVISIONS)
Anchorage of chimneys. ............... 3704 (c)
Earthquake recording Instruments , Appendix 2312 (I)
General. 2312
Seismic considerations for high-rise buildings . 1807 (c) and (k)
EAVES
Projection. 504 (a) and (b)
Construction . .. ... 1710
EDUCATIONAL USES. ..... 701,801
EGRESS (see Chapter 33)
ELECTRIC WELDING (see WELDING)
750
1982 EDITION INDEX
EMERGENCY EXITS
General. Chapler33
Residential . 1204
ENCLOSURE OF VERTICAL OPENINGS (see also OCCUPANCY,
TYPES OF CONSTRUCTION and STAIRS AND EXITS)
Construction requirements 503 (c), 1706
Ftre reststance required . 1701, 1706
For atriums .. .. .. .. .. .. .. .. 1715 (c)
For open parktng garages . 709 0)
For stairs and ramps . . . . . . 3309
Required . . . . . . . . . . . . "06 sections of Chapters 6-1 0; 1209, 1706, 3309
Smokeproof enclosure . . . . . . . . . . . . . . . . .. .. . . .. .. .. . . . . . . . . 3310
Through occupancy separations . 503 (c)
751
INDEX UNIFORM BUILDING CODE
F
FABRICATOR, APPROVED 306 (f), 402, Chapter 50
FACTORIES
Occupancy classification ........... . 701,901
FALLOUT SHELTERS ........... . Appendix Chapter 57
FAMILY, definition 407
FEES
Additional fee required ....................................... . 303 (d), 304 (d)
For building permits ......................... . .. .. .. .. .. .. 304
Plan-checking. 304 (b), Appendix 7007 (a)
Refund 304(e)
Reinspection. 305(g)
FENCES
Around school grounds . 3319 (k)
Classified 1101
Design in seismic zones. Table No. 23-J
For construction purposes . 4407 (c)
FIBERBOARD ..................................................... . 2514, 2516 (g), 2517' (g)
FILMS, FLAMMABLE ....................................... .. 3322 (b), 4001, Chapter 48
FINAL APPROVAL. 304 (d) and (e)
FINAL INSPECTION .. 304 (d) and (e)
FINISH RATING
Required. Chapter42
FIRE ALARMS
For high-nse buildings. 1807 (d), (e), (f), (I) and (m)
Required. . ..................... . 809,909, 1009, 1202 (b), 1210
FIRE ASSEMBLY
Definition . . . .......... . 4306 (b)
General requirements . . .............. . 4306
Occupancy requirements. 503,505
FIREBRICK
Definition. 3702
For chimney lining . 3703 (d)
For fireplaces ............... . 3707 (c)
FIRE DEPARTMENT
3807, Appendix 3807
~;~~;~ ~oo~~~?~:t7~~ifo~ -i~l-~t~: 1807 (f)
FIRE ESCAPES (see EXTERIOR STAIRWAYS)
752
1982 EDITION INDEX
FIRE-EXTINGUISHING SYSTEMS
Areas increased by ...... . 506 (c)
Automatic, requirements ...... . 3602
Automatic, where required 3602
Basement pipe inlets, where required . Appendix 3607
For alternate to one-hour 506
For atrium ............... . 1715
For high-rise buildings ....... . .. .. .. 1607(c)
For mall ............. .. . . . . . . . . . . . . . . Appendix Chapter 7, Partl
For occupancy groups .. . "07" sections of Chapters 6-10; 1210 (b)
Height increased by .... . 507
Standpipes, requirements .. 3605
FIREPLACES, CONSTRUCTION OF . 3707
FIRE-PROTECTED PASSAGEWAYS
For smokeproof enclosures .. 3310
FIRE PROTECTION (see also TYPES OF CONSTRUCTION)
For buildings under construction . 3606
For spray booths ............. . .. ..... 906
Requirements, detailed . Chapter43
FIRE PUMPS, for standpipe supply .. 3606 (c) and (d)
FIRE RATINGS
~~~ ~':~e~:rsa~~t.i~~~ ............. . .. .. 505(e)
Chapter43
For occupancy separations .. 503(d)
FIRE RESISTANCE (see also FIRE-RESISTIVE STANDARDS)
Definition. . . . .. . . . .. .. .. . .. . . . .. .. ............ . 407
Of area separation walls ....... . 505
Of buildings ..... . Table No. 17-A
Of exterior walls .. 504
Of materials ..... ....... Chapter43
Of occupancy separations .. 503 (c) and (d)
FIRE-RESISTIVE STANDARDS
Ceilings .. .. .. .. .. .. .. .. 4305
Dampers .................... . 4306 Ul
Doors. windows and shutters. 4306
Floors. .. ...... " 4305
General. .. Chapter43
Materials ... 4302
Partitions .. . .. ...... 4304
Protection of structural members. 4303
Roof covenngs. 3203 (e), 4307
Walls .. 504 (b), 4304
FIRE-RETARDANT ROOFS
Construction ........... . 3203 (e)
Required .............. . 3202 (b)
FIRE-RETARDANT WOOD. 407,1705 (b) and (d), 1601,1901,2003,2103,2504 (c), 4203
FIRE SEPARATION
Required for areas ..... . 505 (e), 702 (b), 1002 (b)
Required for occupancy " .. " .. ". 503
FIRE STATIONS .. 701
FIR ESTOPPING
Between chimneys and wooden construction. 3707 (m)
Between stories ............... . 2516 (f)
Between wood sleepers ........ . 1604, 1904
Exterior wood veneer walls. " .. 1705(d)
Floor spaces ........ .. 2516(1)
For wood frame construction . 2516(1)
01 attic spaces.. .. . .. ......... 2516(1)
FIRE WARNING SYSTEM (see also SMOKE DETECTORS and FIRE ALARMS)
In dwelling units ..... . 1210
In guest rooms . 1210
In hazardous occupancy. 909
FLAG POLES ON BUILDINGS .. .. 3601 (d)
FLAME, OPEN, prohibited . 906
FLAME SPREAD . ........ . Chapter42
753
INDEX UNIFORM BUILDING CODE
FLAMMABLE LIQUIDS
Storage, handling, use or sale. .. ........................................... 901
In occupancy groups .... "08" sections of Chapters 6-9; 1104, 1212
FLASHING. 1707 (b), 3208
FLAT SLAB. 2613
FLOOR AREA
Definition .................. . 407
Limited (see OCCUPANCY) . 505,506
FLOOR CONSTRUCTION
Concrete. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chapter 26
Fire-resistive. . . . . . . . . . . . . . . . . . . . . 503 (c), 4305
Framing....................... . . . . . . . . . . . . . . . . . . . . . . . . 2106 (c) and (e), 2516 (e)
Heavy t1mber .. .. .. .. .. . .. .. ..... 2106 (c) and (e)
Insulating material, general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1713
~;r:;\~~~2rtenal underfloonng::.::::::::::: .............. 2166 (h), 251 1 J~1 61[!!
1 5
Mezzanines .. .. .. .. .. .. .. .. 1716
Motion picture machine booths . 4002
Plank floonng .. .. .. .. .. .. .. .. .. .. 2517 (e)
Plywood...................... 2517 (e)
Stages . .. .. .. .. .. .. .. .. .. .. .. .. .. .. .. 3905
Steel joists . . . . . . . .. . . . . . .. .. .. .. . . . . . . . . . . . . . . 2715
~~~~ro~~~rsystem . ............................. 51~6~1~
Wood joists. 2506 (g), 2516 (c), 2517 (d)
Wood sleepers . . . . . . . . . . . .. .. . . . . . . . . . . . . . . . . . . . . .. . 1804, 1904
Wood trusses . .. .. .. .. .. .. .. .. .. .. . 2510 (h)
FLOOR FILL, required. 1804, 1904
FLOOR LEVELS
For Group A Occupancies . 603
Changes in elevation . ................. . 3301 (d), 3304 (h), 3305 (f), 3315 (h)
FLOOR LOADS
Assumed live . 2303,2304
Definitions. 2302
General ............ . 2304
FLOOR OPENINGS
Enclosures of, when required (see VERTICAL
OPENINGS, ENCLOSURE OF)
For atriums . 1715
General 1703,4305
In stages, construction . 3905
FLUES (see also UNIFORM MECHANICAL CODE)
Area required . ...... . 3703 (e), 3707 (i)
Limng for chimneys . 3703 (d)
FLY GALLERIES, construction. 3902
FOAM PLASTICS
General. 1712
Trim 1705(e)
FOOTING
Bleacher. 2907 (h)
Concrete. design .......... . 2615, 2902, 2907
Definition. ................. ~7
Design, general . 2907
Grillage ....... . 2907 (g)
Minimum requirements for bearing walls . 2907 (b)
Stepped. 2907 (c)
Under sidewalk. 4503
FORMS
For concrete construction. 2606
May be removed. 2606 (b)
FOUNDATION
Concrete. design . 2615
754
1982 EDITION INDEX
FUSIBLE LINKS
For doors, automobile ramp enclosums . 906
For tim doors ............ . 4306 (b) and (f)
For stage ventilators ............... . 3901 (g)
For vents supplying air backstage .... . 605
G
GARAGE, OPEN PARKING ... 709
GARAGE, PRIVATE
Carport .. 1101
Classified ................ .. 1101
Connected to dwelling ....... . 1214
Definition ... 408
Floor surface ............... . 1105
GARAGE, PUBLIC
Classified ..... . 701
Definition .......... .. 408
Open parking garage. 709
Ramps .... . 906
Repair ............ . 901
Separations required . ........... . 503
755
INDEX UNIFORM BUILDING CODE
GYMNASIUMS
General .... 601
Live loads. .. ........... 2304
Special construction .. 609,809
GYPSUM
Masonry . . ..... 2406
Partitions, nonbearing. 2419
756
1982 EDITION INDEX
H
H-OCCUPANCIES . ............................................. . Chapter9
HABITABLE ROOM
Definition ................ . 409
Minimum requirements for .. . 1207
HANDICAPPED, REQUIREMENTS FOR
Access to building ........ . 3301 (e), 3304 (e)
Access to building uses 1213, Table No. 33-A
Access to toilet facilities ..... 511 (a) and (b)
Changes in floor elevation . 3303 (d), 3304 (h), 3305 (f), 3315 (h)
Handrails .. 3306 U)
Landings. . ........... . 3304 (h), 3306 (g)
Ramps............. . ........... . 3307
Telephones . . . . . ................ . 511 (d)
Water fountains. 511 (c)
HANDRAILS
Construction .............. . 3306 0)
Design Table No. 23-B, 2308 (a), 3306 (J)
For ramps. 3307 (e)
Measuring stair clear width 3306 (b)
Required for stairways .... 3306 U)
HANGARS, AIRCRAFT
Allowable area. 505, 702, 902
Classified .. .. .. .... 701,901
Ventilating equipment. 705,905
HANGERS, JOIST 2510 (g)
HARDBOARD .. 2502 (a), 2505,2516 (g), 2517 (g)
HAZARDS, SPECIAL (see GROUPS, OCCUPANCY)
HAZARDOUS BUILDINGS ... 203
HAZARDOUS OCCUPANCIES
Highly hazardous (see GROUP H) .............. . 901
Moderately hazardous (see GROUP 8-1, 2, 3) . 701
Nonhazardous (see GROUP 8-4) ................ . 701
HEADERS
Headroom for stairways ..... . 3306 (f) and (p)
Joist, support required ......... . 2517 (d)
Over opening in stud partitions . 2517 (g)
HEAT VENTING
Smoke and heat. 3206
HEIGHT
Additional for roof structures 507,3601
Awnings ............ . 4506
Ceilings. 1207
Definition ............. . 409
Marquees above sidewalk ........... . 4505
757
INDEX UNIFORM BUILDING CODE
I-OCCUPANCIES .. Chapter 10
ILLUMINATION
For exits ........................... . 3313
INFORMATION ON PLANS .......................... . 302 (c)
INNER COURT WALLS (see TYPES OF CONSTRUCTION)
INSPECTION
Final, required ....... . 305 (d)
For change of occupancy ...................... . 307
General. .. ....................... . 305
Grading .................................................. . Appendix 7014
Material for prefabrication . . . ............................................ . 5006
Of foundation ........... . 2905
Of prefabricated construction. 5006
Of wallboard . 305 (e), 4701 (b)
Plastering ........... . 305 (e), 4701 (b)
Record card. . ................................... . 305(c)
Spec1al............................................. . ......... . 306
INSULATION
Floor .. 1705 (g)
For energy conservation . Appendix Chapter 53
For piping ........................ . 1713 (b)
General limitations. . ............ . 1713
Roof .................... . 3204
INTERIOR FINISH
Application of materials. . .. .. .. . . . . . . . . . . .. . . . . . . . . . . . . .. .. .. . .............. .. 4203
Classification of materials. . . . . . . . . . . . . . . . . . . . . . ............. . 4202
Flame spread of .............. . 4202,4204
In atriums .. 1715 (h)
Occupancy requirements . .. ... 4204
Of plastic .. Chapter 52
758
1982 EDITION INDEX
J
JAILS Chapter 10
JOINTS, CONSTRUCTION, in concrete 2606 (d)
JOIST HANGERS . . .......... . 2510 (g)
JOISTS
Bearing ........... . 2416 (i)
Ceiling, dead load. Table No. 23-B
Concrete ...... . 2608(1)
Fire protection .. 4303
Steel 2715
Wood. 2506, 2516 U), 2517 (d)
JURISDICTION, definition . 411
K
KEENE'S CEMENT, specifications . Chapter 50
L
LABELS
Fire doors . 4306
Roofing 3203
Windows 4306
LACING. 2715
LADOERS
Used for ex1t from equipment. 3306 (a), 3322 (a)
LAMINATED
Floors .. 2106 (h), 2511, 2516 (I)
Timber, glued . 2511
LANDING OF STAIRS . 3306 (g)
LATERAL FORCE PROVISIONS . 2311,2312,2515
LATH
Fire-resistive. 4302
Gypsum. 4705, 4706
Inspection . 305 (e)
Metal. 4705, 4706
LAVATORIES
Installation. 511 (b)
Reqwed. 605, 705, 805, 1205 (b), 1208
LIABILITY. 202 (f), 305 (a)
LIBRARIES
General. 601,801
Live loads . 2304
LIGHT
For exits. 3313,3314
For occupancy groups . "OS" sectionsofChapters6-10, 12
LIGHT STEEL CONSTRUCTION. 2701
LIME
For mortar ........ .. . 2403 (p) and (q)
Proportions for plaster . 4707,4708
Specifications . 2403 (p)
759
INDEX UNIFORM BUILDING CODE
LINING
Of chimneys (masonry). 3703 (d)
Of chimneys (metal) . 3706
Of fireplaces 3707 (c)
LINTEL
Definition . .. 413
LIQUID STORAGE ROOM
Definition . 413
Requirements .. 902 (c)
LIQUID STORAGE WAREHOUSE
Definition . . ...... 413
Requirements ..... 902(c)
LIQUIDS (see also FLAMMABLE LIQUIDS)
Definition. 413
LIVE LOADS
Concentrated . 2304 (c)
Definition .... 2302
Floor . . . . . ............ . 2304
Reductions allowed . .. .. .. .. .. . 2306
Required to be posted . . . . . .. . . . . . .. 2304 (e)
Roofs. .. .. .. .. .. .. . 2305
Special considerations . 2303, 2304, 2305
Unit, for certain occupancies . 2304
LOADING PLATFORM. 1705(1)
LOADS (see DEAD, FLOOR, LIVE, ROOF, SEISMIC, WIND)
LOCATION ON PROPERTY
Fills. ....................... Appendix 7010
General requirements .. .. .. .. .. .. . .. .. .. .. .. .. 504
Occupancy groups ... "03" sections of Chapters 6-12
Open parking garages 709(1)
LOCKS ON DOORS, PROHIBITED. 3304 (c), 3317,3318,3319,3320,3321
LODGES (see ASSEMBLY BUILDINGS)
LODGING HOUSES
Definition .. .. .. . .. 413
Occupancy classification ............... . 1201
LOT LINES (see LOCATION ON PROPERTY)
LOT SURVEY. 305(a)
LUMBER (see WOOD) ... Chapter25
M
M-OCCUPANCIES. Chapter 11, Appendix Chapter 11
MAINTENANCE
Of buildin~js ........ . 104(d)
Of protective devices . 4408 (a)
MALLS. . . . . . . . . . . . . . . . . Appendix Chapter 7, Part I
MARQUEES
Defined ......... . 414
General requirements . . ............... 4505
Live load. Table No. 23-A
MASONRY
Adobe .. 2403 (h), 2405
Anchorage .. 2310,2416 (h), 2417 (i), 2419 (c)
Arches and lintels .. . 2416(g)
Area of hollow units .. . 2402
Bearing walls 2418
Bed joints. 2416(m)
Bolts. . .................... 2416 (k)
Brick .. 2403 (b), (c) and (d); 2418 (c)
Cast stone. 2403 (g)
Cavity walls . . 2409
Cement. 2403 (o)
760
1982 EDITION INDEX
MATERIALS
Alternates .............. . 105
Standards for. Chapter SO
MECHANICAL VENTILATION (see VENTILATION)
MENTAL HOSPITALS ...................... . Chapter 10
METAL
As lath (see METAL OR WIRE LATH)
Roof covering . 3203
761
INDEX UNIFORM BUILDING CODE
N
NAILS .. 2510 (f), Table No. 25-Q
NEW MATERIALS OR METHODS. 105
NONBEARING WALLS (see WALLS)
NONCOMBUSTIBLE MATERIAL, definition .. 415
NONCONFORMING BUILDINGS .... 104, Appendix Chapter 1
NOTICES
For inspections by building official. 305
Of approval required .. . 305
Of condemnation ... . 203
Of excavation or fill. 2903
Of violations 202(e)
NURSERIES Chapter 10
NURSING HOMES . 1001
0
OBSTRUCTIONS PROHIBITED
At exits. 3301 (c), 4306 (m)
In ex1t courts . 3311
In street gutter 4403
OCCUPANCY
Certificate . .............. 307
Change in use . 307 (b), 502
762
1982 EDITION INDEX
Classified . 501,503
Definition . 416
Existing ...................................... . ........ 104(c)
In occupancy groups "01" sections of Chapters 6-12
Mixed. . .......................... . 503
Separations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 503, Appendix 114
Temporary, allowed for construction purposes 4402
Violation ............................ . 202 (e), 4501
When not specifically mentioned in code .................. . 501
OCCUPANT LOAD
Determination of. 3302 (a)
Posting of. ................................ . 3302 (c)
OFFICE BUILDINGS
General ........... . 701
Live loads . 2304
OIL
Storage (in occupancy). 708,808,908,1008,1104,1212
OPENINGS
Exterior, to be protected when (see LOCATION ON PROPERTY
and TYPES OF CONSTRUCTION)
In area separation walls. 505(e)
In atriums. . ............ . 1715 (c)
In ceilings . . . . . . . . . . . . . . . . ........................... . 4303 (b)
In occupancy separations . . .......................... . . .................. 5C3(c)
In floors . . .......................... . 4305 (a) and (b)
In walls.................... ................... . ............ . 4304
Protection of, fire assemblies .......................................................... . 4306
Vertical, to be protected when (see VERTICAL OPENINGS, ENCLOSURE OF)
OPEN PARKING GARAGE. . . . . . . . . . . . . . . . . . . . . . .................... . 709
ORIEL WINDOW
Definition. 416
Projection 4504
ORPHANAGES. 1001
OVERCROWDING PROHIBITED. 3302 (b)
OVERTURNING MOMENT
For earthquake calculations . 2312(f)
For wind calculations. 2303 (b)
p
PAINTING
Of aluminum alloy parts . . . ............... . 2804 (d)
Of structural steel. . . ..................... . 2720
Spray .............. . 901
PAINT SHOPS 802 (d), 901
PAINT STORAGE . 901
PAINT STORES . . 701,901
PANEL STRIPS, definition . 2613 (c)
PARAPET WALL
Definition . 424
Required .. 1709
PARKING GARAGE, OPEN . 709
PARTICLEBOARD ............. . 2502 (a), 2505,2516 (g), 2517 (f) and (g)
763
INDEX UNIFORM BUILDING CODE
PARTITIONS
Bearing, combustible .... 2517(g)
Bearing, noncombustible. 2418,2614,2616,2622
'Fire-resistive . ........................... . .. .. .. .. .. .. .. .. 4304
Folding, portable or movable . 1705(c)
For frame construction .................. . 2517 (g)
General (see TYPES OF CONSTRUCTION)
Nonbearing, noncombustible . . .................. . 2419,2614,2616,2622
Temporary ..................................... . 1705(c)
Unprotected materials allowed. . .................. . 1705(b)
PASSAGEWAYS
As discharge for exit courts . . .......................... . 3312
As honzontal exits . . ................ . 3308
As stairway enclosures . . ............. . 3309 (d)
For smokeproof enclosures ........... . 3310 (c)
To be sprinklered .............. . 3802
PATIO
Covers. 5211, Appendix 4901
Design. 2305, Appendix 4902
PEDESTAL
Concrete, definition ............... . .. .. .. .. .. .. .. . 2602
Concrete, design ............................... .. 2615,2622
Footings.. . ........................... .. Appendix 4904
PEDESTRIANS, PROTECTION OF Chapter44
PENTHOUSE
General requirements . 3601
PERMIT
Application. . ................................................ . 302(a)
Definition ............................ . 417
Does not permit violation. . . . . . . . . . . . . . . . ............... . 303(c)
Expiration ................... . 303(d)
Fees. . ................................... . 304
For alteration . ........................................................ . 301
For change of occupancy ...................................................... . 307
For demolishing . .. . . . . . . .. . . . . . . . . . .. . . . .. . . .. ............ .. 301
~m~~- . . . ......... . 301
For new buildings or structures .. 301
For use or occupancy ....................... . 307
Information on plans and specifications . 302(c)
Plans required .................... . 302 (b)
Revocation of 303(e)
Suspens1on of. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ............. . 303(e)
~~~ . . . . . . . . . . ........... . 303(c)
When required .............................................. . 301
Work without .. 304(d)
PERSON, defimtion. 417
PETROLEUM STORAGE 901
PEWS, width. 3302 (a), 3315,3316
PIERS, masonry 2416(d)
PILES, general requirements .................... . 2908,2909
PLAN CHECKING
Fee for ................... .
Required
PLANK AND BEAM CONSTRUCTION . ......................... . 2106,2516 (I) and (m), 2517 (e) 3
PLANS (see also PLAN CHECKING)
Alteralion of. . . . . . . .. .. .. .. .. . . . . . .. .. .. . . . . . . . . . . . . . . . . . . . . 303 ((aa)
Approved by building official . ...................... 303 )
For demolishing . . .. .. . . . . . . . . . .. . . . 4409
Information on . ................ 302 (a) and (c)
Kept on building site. . . . . .. .. .. . . . .. . . . .. . . . .. . . . . . .. .. . . 303 (b)
Required for permit, when. . ............. 302 (b)
Retention of. . . . . .. . .. .. 303 (b)
Shall bear name of whom ............ 302 (a) and (b)
PLASTER AND PLASTERING
Aggregate .......... . 4702
764
1982 EDITION INDEX
765
INDEX UNIFORM BUILDING CODE
Q
QUALITY AND DESIGN OF THE MATERIALS OF CONSTRUCTION
Alum1num .. Chapter28
Masonry. Chapter 24
Reinforced concrete . Chapter 26
Steel and iron. Chapter27
Wood. Chapter 25
R
A-OCCUPANCIES. Chapter 12
RADIO TOWERS . 507, Table No. 23-H, 3602
RAFTERS (see ROOF CONSTRUCTION)
RAIL AROUND OPENINGS . 1711, Table No. 23-B
766
1982 EDITION INDEX
767
INDEX UNIFORM BUILDING CODE
REINSPECTION
May be made .. 305 (g), 602 (c)
REPAIR
Definition. 419
Garages ...... . 901
May be required ..... . 203
Of existing buildings .. . .................. 104
Re-roofing. . ..... Appendix Chapter 32
To historic buildings. 104(1)
REPORTS
Of Board of Appeals .. 204
Of special inspector . 306(c)
Of tests of concrete . 2604
01 tests, general. 107
768
1982 EDITION INDEX
~::~at.
2106 (d), 2517 (h)
3201
Insulation 1713,3204
Of marquee ..... . 4505(f)
Panels, of plastic . 5206
Planking . 2517(h)
Purlins. 2517 (h)
Rafters. 2517 (h)
Rafterties .......... . .. ...... 2517(h)
Sheathing ......... . 2516 (i). 2517 (h)
Spaced sheathing . 3202 (a)
769
INDEX UNIFORM BUILDING CODE
s
SAFEGUARDS, maintenance. 104(d)
SALES ROOMS
For combustible goods ..... 701
For noncombustible goods. 701
SAND
For concrete . 2603 (d)
For mortar. 2403
For plaster . 4702, 4707, 4708
SAND-LIME BRICK (see BRICK, SAND-LIME)
SANITARIUMS Chapter 10
SANITATION . 510;"05" sectionsofChapters6-10, 12
SCHOOLS
Colleges . 701
Exits ................ . 3319
General requirements . 801-809
Live loads . 2304
SCUTTLE
Access to roof space ......... . 3205 (a)
Access to roof, when required . 3306 (o)
Access to underfloor areas . 2516 (c) 2
SEATING
Continental ... 3315,3316
Standard . 3315,3316
SEATING CAPACITY (see OCCUPANT LOAD)
SEATS
Number of, to be posted . . . . . . . . . . . . . . . . . . . . . . 3302 (c)
Spacing. . . . . . . . .. 3315, 3316, 3323 (e), 3324 (d)
Width. 3302 (a), 3315,3316,3323 (e), 3324 (d)
SECURITY PROVISIONS (see also UNIFORM BUILDING SECURITY CODE)
Door latches . 3304 (c)
Door viewports . 3306 (h)
Window gnlles, bars and grates. 1204
SEISMIC DESIGN. 2312
SELF-CLOSING DOOR
Attic partitions . 2516(1)
Automobile ramp enclosure . 906
Basement stairways .. 3306 (h)
Corridors 3305 (h), 4306 (f)
Exit enclosures. 3309 (c)
Exterior stairways . 3306 (I)
Fire doors . 4306 (b)
Smokeproof enclosures . 3310(g)
770
l;:t'Qc; !I;;IJIIIVI...
SEPARATION
Around buildings .. . ........... 506
Of areas ...................... . . ........... 505
Of areas for suspended ceilings . . ....... 2516
Of buildings for seismic action .. 2312(h)
SERVICE STATIONS, GASOLINE (see GASOLINE SERVICE STATIONS)
SHAFT
Definition . 420
Elevator. 1706(d)
Enclosures . 906, 1706 (a) and (b)
SHALL, definition of . 420
SHEAR
Horizontal ....... . 2312 (e), 2506 (c) and (d)
Masonry, stresses . . . . . . . . . . . . . . . . . . . 2405-2418
Reinforced concrete, allowable stresses ... 2609 (d)
Reinforced concrete, design 2611
Structural steel .......... . 2702, 2708 (c) and (d), 2721 (f)
Wall, definitiOn . 2312(b)
Wood. 2504
SHEATHING
Diaphragm .. 2513
Fiberboard . . .......... 2514
Floor. . ...... 2516 (h), 2517 (e)
Roof 2516 (i), 2517 (h), 3202 (a)
Sublloor. ................... 2518(e)
Wall. 2516 (g), 2517 (g) 3
SHELLS (concrete) .. . .......... 2619
SHINGLES AND SHAKES
As roof covering . 3202 (b), 3203 (d) 3
As siding. 2516(g)
SHORING
Of adjoining foundations. 2903
SHOW WINDOWS. 1705(d)
SHUTTERS
For motion picture machine booths . 4004
Required for stage vent ducts. 3901
SIDEWALKS
Glass lights. 3401
Live load for design .... 2304
Railing required around .. 3401
Required to be protected ....... . 4407
Space under, may be occupied . 4503
Walkways . 4406
SIGNS (see also UNIFORM SIGN CODE)
For basement pipe inlets. . . . . . . Appendix 3807
For exits ...... . 3314, Appendix 109 (e)
For fire doors .. 4306 (m)
For live load. 2304 (e)
For room capacity . . 3302 (c)
For stairs. 3306 (q), 3314
For unsafe building .. 203
Over public property 4501
SKYLIGHTS
General requirements (see also TYPES OF CONSTRUCTION). 3401, 3901 (c)
Plastic 5207
SLAB
Gypsum .............................. . 2406
M1mmum thickness, for fire-resistive purposes. 4303,4305
Minimum thickness for floors . ......... . 2608, 2609, 2611' 2623
Reinforced concrete (see CONCRETE)
SLATE, for roof covering . 3203
771
INDEX UNIFORM BUILDING CODE
SLEEPERS, WOOD
On floors ......................................... . 1804,1904
SMOKE CONTROL
In atriums ........ .. . ........................ 1ns
In high-rise buildings. .. ........... 1807(1\\
In malls ........... . . . . . . . Appendix 713 (c)
SMOKE DETECTORS
Defmit1on. .. ............... 420
For doors. . . 4306 (b), 4306 (~
For elevators .
In atriums. . 5103 (a) 2, ~i~~ ~~~
In dwelling units . 1210
In guest rooms ............ . 1210
In high-rise buildings .......................... . 1807ld)
In hospitals ............................... . 3802 g)
SMOKE VENTING
In Group H Occupancies .... 3206
In high-rise buildings .. .. 1807(g)
In one-story buildings 3206
Over stages ............... . 3901
SMOKEPROOF ENCLOSURE, REQUIRED
Construction and design ........................... . 3310
SNOW LOAD ......... .. 2305 (d)
SOIL
Bearing. allowable .. 2906
Classification ..... .. ... 2904
Excavation and grading Appendix Chapter 70
Investigation requ1red . 2904 (b), 2905
Tests required .. 2904
SOLAR ENERGY COLLECTORS. . ..... 1714,5214
SOLID MASONRY (see MASONRY)
SOLID MASONRY WALLS (see WALLS)
SOUND TRANSMISSION CONTROL. . . . Appendix Chapter 35
SPACE FRAME . 2312,2625, 2626,2722,2723
SPECIAL INSPECTOR ................ . .. .. .. 305 (b) and (c)
SPECIAL PURPOSE ROOF COVERING . 3203 (g)
SPECIFICATIONS, required for permit. . . 302(b)
SPIRES (see TOWERS)
SPLICES
Re~nforc1ng steel . 2612
SPRAY-APPLIED FIREPROOFING
Special inspection . . ............... . ...... 306(8)
Structural member protection. . .............. . .. .. 4303 (e)
SPRAY PAINTING
Construction requirements for booths (see UNIFORM FIRE CODE)
Occupancy classification ....................... . 901
STAGE
Classification of occupancy 601
Construction .................. . 602 (b), 3905
Definition . .. .... 420
General. Chapter39
Sprinklers required. ......... 3802 (c)
Standpipes required .............. . . ...................... 3805 (d)
Ventilation .. .. ... 608,3901
STAIRS (STAIRWAY)
Access and arrangement .. 3303 (c), 3305, 3306
Access to roof . . .............. . 3306 (o)
772
1982 EDITION INDEX
773
INDEX UNIFORM BUILDING CODE
774
1982 EDITION INDEX
SUSPENDED CEILINGS
Design ....... . 4701 (e), 4704, Tables Nos. 23-B, 23-J
Draft stops for . . . . . .. .. .. .. . . 2516 (f), 4203
In dwellings . . . . . . . .. 1207
Sprinkler system for . 3801 (d), 4203
SUSPENSION OF PERMIT. 303 (e)
SWITCHBOARD PROTECTION. 3908
T
TANKS
For storage of flammable liquids. 908, 1104
Horizontal forces, design .... 2311,2312
Roof structures .... 3601
Water. 1101
TBEAMS IN REINFORCED CONCRETE. 2608 (k)
TELEPHONES
For handicapped ... 511 (d)
In high-rise buildings. 1807(1)
TELESCOPING SEATING . . 3324
TEMPORARY BUILDINGS . 104(e)
TEMPORARY PARTITIONS . 1705(c)
TERMITE PROVISIONS. 2516 (c)
TERRACING. Appendix 7012
TESTS
Concrete ............. .. 2604 (d)
Concrete aggregates. 2603 (d)
Fire-resistive materials . . . . . ........... . 4302 (b)
~:i'~r7~Ys ~~ J,r6i8ti;icaii~~: :
2404
.............. . 5002
May be required .................... . 107,5002, 5003
New materials and devices. 105
Piles, safe bearing ...... . 2908
Prefabricated construction .. Chapter 50
Soil bearing . 2905
To classify mortars. 2403
Welds. 2722 (f)
THEATERS (see ASSEMBLY BUILDINGS)
TILE
Ceramic ............. . 3005 (I)
Of clay (see CLAY TILE)
Of concrete (see CONCRETE BLOCKS)
Of gypsum (see GYPSUM)
TIMBER (see WOOD)
TOILET ROOM .. .. 511
TRIM .. 1705(e)
TRUSSES
Fire protection of (see also TYPES OF CONSTRUCTION). 4303
Steelframe .. .. .......... 2716 (b)
775
INDEX UNIFORM BUILDING CODE
u
U.B.C. STANDARDS (see UNIFORM BUILDING CODE STANDARDS)
UNBURNED CLAY MASONRY 2403 (h), 2405
UNDERPINNING (see FOUNDATION STUDS)
UNIFORM ADMINISTRATIVE CODE (see UNIFORM ADMINISTRATIVE CODE)
UNIFORM BUILDING CODE STANDARDS .. Chapter60
UNIT STRESSES (see WORKING STRESSES)
UNLAWFUL TO OCCUPY, when . 203,307
UNLIMITED AREA . 506(b)
UNSAFE BUILDINGS . ... 203
URINALS
~~~~i~~g~rid : : : : : :
.. 805
510(b)
USABLE SPACE UNDER FLOOR . . 1703
USE OF BUILDING (see also OCCUPANCY)
Chan~e .. 307 (b), 502
Class1fied ............ . "01" sections of Chapters 6-12
Not specifically mentioned . . . . . . . .. . . . 501
M1xed .. 503
Permitted when. 307(a)
UTILITIES
Protected. 4405
v
VALIDITY
Of permits. 303(c)
VALUATION
Definition ..... 423
Of buildings by building official .. 304(a)
VALUE, definition. 423
VENEER
Adhered. 3005
Anchored. 3006
Definition. 3002
Design. 3004
Of plastic. .. .......... 3005 (e)
Supported by wood . 2515 (a)
Walls of (see WALLS)
VENTILATING CEILING
Definition ... 423
VENTILATION
Attic ...... 3205 (c)
Automobile repair. . 905
Automobile storage ........ . 705, 1104
Dry-cleaning establishments . 908
Motion picture machine booths . .. .............................. 4005
Occupancy groups . "05" sections of Chapters 6-10; 1104. 1205
Open parking garages. . . . . . . . . . .. .. 709(k)
Over stage ....... 3901
Under wood floor . 2516 (c)
776
1982 EDITION INDEX
VENTS
For dry-cleaning plants . 908
For explosion venting . ............ . 910
For motion picture machine booths . 4005
~~; ~~~~e :~~~~sat
9 705,905
3206
For stages. 3901
VENTS, HEATING (see UNIFORM MECHANICAL CODE)
VENT SHAFTS (see VERTICAL OPENINGS)
VERTICAL OPENINGS, ENCLOSURE OF
Construction requirements . 1706
Existing buildings .............. . Appendix 11 0
Fire assemblies for protection of . 4306
For atriums .......... . . ................... 1715 (c)
For occupancy groups. "06 sections of Chapters 6-10; 1209
When required. 1706,3309
w
WALLBOARD, GYPSUM .. 4711,4713
WALLS
Anchonng. 2310,2419 (c)
Area separation . 505(e)
Basement, enclosure 1703
Bearing 424,2417,2418,2517 (g), 2614, 2907(b)
Bracing ........ . 2517(g)
Chases in masonry . .. . . . . . . . . . . . . .. .. .. .. .. 2416(e)
Concentrated loads.. 2416 0), 2614 (c)
Concrete, pla1n. 2622
Coverings. 2516 (g)
Cripple ...................... . 2517(g)
Curtain (see Nonbearing, below)
Definition .. 424
Design. 2309,2416,2417,2614,2616,2622
Eccentricity . 2418(c)
Exterior . 424
Faced, definition. . ........................... ''. 424
F1re-resistiw. 1803, 1903, 2003, 2103, 2203, 4304
Foundation . 2907
Fram~ng. 2516 (d), 2517 (g)
Fronting on streets or yards .. 1705(d)
Height allowed. . ............ . 2409 (c), 2416 (c), 2614 (c), 2622
Hollow unit masonry, reinforced. 2414
Hollow unit masonry, unreinforced 2410
Lintels . '' ......... 2416(g)
Nonbearing ..... . 424,2419,2614 (c)
Of exit enclosures . 3309
Of roof structures ........ . 3601
Of smokeproof enclosures . . ....... '. 3310
Openings "03" sections of Chapters 18-22
Parapet ............ . 1709
Partitions (see PARTITIONS)
Piers. 2416(d)
Plain concrete ........ . 2622
Protection of openings. 504
Remforced concrete ..... 2614
Reinforced grouted masonry ......... . 2413
Reinforced hollow unit masonry . ...... . 2414
Retaining (see RETAINING WALLS)
Sheathing, when required .. 2513, 2514, 2516 (g), 2517 (g)
Solid masonry, fire-resistive rating .. .. ............ 4304
Solid masonry, plain 2411' 2418 (b)
Solid masonry, reinforced. 2417 Ul
Solid masonry, separation of combustible members . . .. 4304
Solid masonry, thickness of . , . . .................. 2416(c)
Solid masonry, working stresses. 2412,2413,2414,2417 (a)
Stone ............... . . ......... ' . . .. .. . . 2403 (i), 2408
Thickness of masonry .. . 2416 (c), 2417 Ul. 2418 (b), 2419 (b)
Veneered .. . . . . . . . . .. . . ....... Chapter30
Water closet . 510 (a), 511 (a)
Water splash 2516 (k)
Wood studs. 2516 (d), 2517 (g)
777
INDEX UNIFORM BUILDING CODE
WAREHOUSE
For storage. 701,901
Live load. 2304
WATER
Accumulation on root . ........... . 2305 (f), 27'1:>
Drainage around buildings . 2905 (f), 3207 (e)
Draina~e from roof. 3207
Fountains ........ . 511 (c)
Heater, definition ... . 424
Removal from excavations . 2605 (a)
Requirements for concrete .......................... . 2603 (e)
Requirements for masonry . 2403 (n)
Retaining walls, design for ................................ . 2308 (b)
Supply for automatic sprinkler system 3801 (d)
Supply for standpipes . 3801 (d)
WATER-CEMENT RATIO
Consistency required . 2604 (f)
Control of proportions. 2604 (f)
778
1982 EDITION INDEX
WIRE
For stucco reinforcing ..... . .. .... 4706
For tieing roofing materials ..... . .. ...... 3203 (c(
Hangers for suspended ceilings .. .. ...... 4704 (c
Masonry joint reinforcement .... . ..... 2403 (m
nes for fire-resistive materials. 4303, 4305 (d
Veneer, anchorage .. 3003,3006
WIRED GLASS
In fire-resistive doors and windows. . . . . ........... . 4306 (g), (h) and (i)
In skylights ..................................... . 3401
Required by location (see LOCATION ON PROPERTY,
DOORS and WINDOWS)
WIRE MESH
For exterior lath 4706
For interior lath . 4705
For skylights .. 3401
For stage ventilators 3901
WIRING IN PLENUMS .. 4305 (e)
WOOD
Allowable stresses . 2504
Anchors and ties 2517
Beams and girders 2506, 2517 (c)
Beams and joists . 2506
Bolted connection .... 2510 (b)
Bracing 2517 (g)
Bridging ............ .. 2517(g)
Clearance above grade . 2516 (c)
Clearance from chimneys. . . 3703 (c)
Columns or posts ... . 2507, 2516 (c)
Combined stresses ......................... . 2508
Combined structurally with masonry or concrete . 2515
Compression at an an91e to grain .... 2509
Compression perpendicular to grain .. 2506 (I)
Concrete, in combination .... 2515
Connections .......... . 2510
Cutting and notching .. . 2517 (d) and (g)
Deflection criteria ..... . 2307
Diaphragms ... 2513
Earth separation ...... . 2516(c)
Fiberboard, definition .. . .. .. .. 2502 (a), 2514
Fire-retardant. .. . ... 407,1705,1801,1901
Floors, laminated ... 2516(1)
Form factors . 2504
Foundations .. .. . 2907 (a)
Foundation sills . 2517 (b), 2907 (e)
Grade, definition ................ . 2502 (a)
Glued built-up members, definition .. 2502 (a), 2512
Glued construction ...... . 2511
Glued-laminated timber, definition .. . .. ...... 2502 (a)
Heavy timber construction .......... . Chapter 21. 2513
Horizontal members, framing details .. .. .. .. . 2506
Horizontal shear . 2506 (c) and (d)
Joists. 2517(d)
Joist hanQers ........... . 2516U)
Masonry, 1n combination. 2515
Masonry, supported . 2415 (c)
Metal plate connectors .. . 2510 (h)
Nails ................ . 2510(1)
Nominal size, definition .. 2502 (a)
Normal loading, definition. 2502 (a)
Partitions, framing details . 2517 (g)
Piles.... .. ............ . . .. .. .. .. .. 2909
Plywood...... .. .. . 2502 (a), 2513 (c), 2516,2517
Plywood exterior covering. 2513 (c), 2516 (g)
Quality and design ................. . 2501
Rafters.... .. .... . 2517(h)
Required sizes, determination ... . 2503
Roofframing ... 2506, 2517 (h)
Shear, horizontal. .. .. .. .. . 2506 (c) and (d)
Sheathing ... 2513 (b), 2514,2516,2517
Siding. 2516(g)
Stressed skin panels ............... . 2512
Structural glued-laminated timber. . . . . . . . . . 2502 (a), 2511
Stud walls, framing details .... 2516 (d) and (1), 2517 (g)
779
INDEX UNIFORM BUILDING CODE
X
NO REQUIREMENTS
y
YARD
Between buildings . ..... 504 (c), 1206
Definition . .. .... 426
Minimum width. 1206
Required ........ . 504(a)
To be maintained .. 504(a)
Used for area increases . .. ....... 506
z
NO REQUIREMENTS
780