XGB PLC Hardware Users Manual V1.6 PDF
XGB PLC Hardware Users Manual V1.6 PDF
XGB PLC Hardware Users Manual V1.6 PDF
LSIS strives to maximize customers' profit in gratitude of choosing us for your partner.
XGB Hardware
XGT Series Users Manual
XBM-DR16S
XBM-DN16S
XBM-DN32S
XBC-DR32H
XBC-DN32H
XBC-DR64H
XBC-DN64H
XBC-DR32HL
XBC-DN32H/DC
XBC-DN64H/DC
XBC-DR32H/DC
XBC-DR64H/DC
http://eng.lsis.biz
Safety Instruction
For your safety and effective operation, please read the safety instructions
thoroughly before using the product.
Instructions are separated into Warning and Caution, and the meaning of
the terms is as follows;
The marks displayed on the product and in the users manual have the
following meanings.
The users manual even after read shall be kept available and accessible to
any user of the product.
Safety Instruction
Warning
Never connect the overload than rated to the output module nor
allow the output circuit to have a short circuit, which may cause a
fire.
Caution
I/O signal or communication line shall be wired at least 100mm
away from a high-voltage cable or power line. If not, it may cause
abnormal output or operation.
Caution
Use PLC only in the environment specified in PLC manual or
general standard of data sheet. If not, electric shock, fire, abnormal
operation of the product or flames may be caused.
Dont let any metallic foreign materials inside the product, which
may cause electric shock, fire or abnormal operation..
Safety Instruction
Warning
Prior to wiring, be sure that power of PLC and external power is
turned off. If not, electric shock or damage on the product may be
caused.
Before PLC system is powered on, be sure that all the covers of
the terminal are securely closed. If not, electric shock may be caused
Caution
Let the wiring installed correctly after checking the voltage rated
of each product and the arrangement of terminals. If not, fire,
electric shock or abnormal operation may be caused.
Dont let any foreign materials such as wiring waste inside the
module while wiring, which may cause fire, damage on the product
or abnormal operation.
Safety Instruction
Warning
Dont touch the terminal when powered. Electric shock or abnormal
operation may occur.
Caution
Dont remove PCB from the module case nor remodel the module.
Fire, electric shock or abnormal operation may occur.
Caution
Product or battery waste shall be processed as industrial waste.
The waste may discharge toxic materials or explode itself.
Revision History
Version Date Remark Page
V 1.0 2006.6 1. First Edition -
2. Contents added
(1) Naming standard added 2-3 ~ 2-6
(2) Caution when selecting IO module added 7-1 ~ 7-6
(3) IO wiring method by using Smart Link board added 7-27 ~ 7-28
(4) Installation and wiring contents added 10-1 ~ 10-18
3. Content modified
(1) Safety instruction modified 1~6
(2) System Configuration modified 2-7 ~ 2-10
(3) High speed counter function modified 8-6 ~ 8-8
(4) External dimension modified App. 2-1 ~ 2-4
The number of Users manual is indicated the right side of the back cover.
LS Industrial Systems Co., Ltd 2006 All Rights Reserved.
About Users Manual
The Uses Manual describes the product. If necessary, you may refer to the following description and order
accordingly. In addition, you may connect our website(http://eng.lsis.biz/) and download the information as a
PDF file.
Chapter 1 Introduction
1.1 Guide to Use This Manual
This manual includes specifications, functions and handling instructions for the XGB series PLC.
This manual is divided up into chapters as follows.
Appendix 1 Flag List Describes the types and contents of various flags.
Appendix 2 Dimension Shows dimensions of the main units and expansion modules.
Compatibility with
Appendix 3 Describes the compatibility with MASTER-K.
MASTER-K
Appendix 4 Instruction List Describes the special relay and instruction list.
1-1
Chapter 1 Introduction
1.2 Features
The features of XGB system are as follows.
XBC-Dx32H 114 * 90 * 64
H type
Basic unit XBC-Dx64H 180 * 90 * 64
XBM-DxxxS 30 * 90 * 64 S type
Extension module XBE-,XBF-,XBL- 20 * 90 * 60 Basis of minimum size
(4) Improved maintenance ability with kinds of register, built-in RTC (H type), comment backup and etc
(a) Convenient programming environment by providing analogue register and index register.
(b) Improved maintenance ability by operating plural programs and task program through module program.
(c) Built-in Flash ROM enabling permanent backup of program without any separate battery.
(d) Improved maintenance ability by types of comment backup.
(e) Built-in RTC function enabling convenient history and schedule management
1-2
Chapter 1 Introduction
(7) Applications expanded through analog-dedicated register design and full attachable mechanism.
(a) All analogue modules can be attachable on extension base. (H type: up to 10 stages available)
(b) With analog dedicated register(U) and monitoring dedicated function, convenient use for I/O is
maximized (can designate operations using easy programming of U area and monitoring function)
1-3
Chapter 1 Introduction
1.3 Terminology
The following table gives definition of terms used in this manual.
1-4
Chapter 1 Introduction
Current flows from the switch to the PLC input terminal if a input
signal turns on.
Z: Input
Sink Input
impedance
Current flows from the PLC input terminal to the switch after a
input signal turns on.
Source Input -
Current flows from the load to the output terminal and the PLC
output turn on.
Sink Output -
Output
Contact
Current flows from the output terminal to the load and the PLC
output turn on.
Source Output -
1-5
Chapter 2 System Configuration
XGB series System Configuration is as follows. Expanded I/O module and special module are available to
connect maximum 7 stages for S type and 10 stages for H type. Expanded communication module is
available to connect maximum 2 stages.
2-1
Chapter 2 System Configuration
Item Description
2-2
Chapter 2 System Configuration
XBC-DN64H AC100~220V power supply, DC24V input 32 point, Transistor output 32 point
H type
XBC-DR32HL AC100~220V power supply, DC24V input 16 point, relay output 16 point
Main Unit
XBC-DR32H/DC DC 24V power supply, DC24V input 16 point, relay output 16 point
XBC-DN32H/DC DC 24V power supply, DC24V input 16 point, TR output 16 point
XBC-DR64H/DC DC 24V power supply, DC24V input 32 point, relay output 32 point
XBC-DN64H/DC DC 24V power supply, DC24V input 32 point, TR output 32 point
XBM-DN16S DC24V Power supply, DC24V Input 8 point, Transistor output 8 point
XBM-DN32S DC24V Power supply, DC24V Input 16 point, Transistor output 16 point S type
XBM-DR16S DC24V Power supply, DC24V Input 8 point, Relay output 8 point
XBE-DC08A DC24V Input 8 point -
XBE-DC16A DC24V Input 16 point -
XBE-DC32A DC24V Input 32 point -
XBE-RY08A Relay output 8 point -
Expansion Unit
2-3
Chapter 2 System Configuration
X B M - D R XX S
DC input
2-4
Chapter 2 System Configuration
X B E - DC XX A
2-5
Chapter 2 System Configuration
X B F - AD XX A
2-6
Chapter 2 System Configuration
X B L - C21
2-7
Chapter 2 System Configuration
Cnet I/F System is used for communication between the main unit and external devices using RS-
232C/RS-422 (485) Interface. The XGB series has a built-in RS-232C port, RS-485 port and has also
XBL-C21A for RS-232C, XBL-C41A for RS-422/485. It is possible to construct communication systems
on demand.
(1) 1:1 communication of an external device (computer) with main unit using a built-in port
(RS-232C/RS-485)
XBC-DR32H
RS-232C / RS-485
(2) 1:1 communication with main unit using a built-in RS-485 port
(In case of built-in RS-232C,it is for connecting to HMI device.)
XBC-DR32H XBM-DN32S
PADT
connection
XP30-TTA
2-8
Chapter 2 System Configuration
(3) 1:1 RS-232C Communication with remote device via modem by Cnet I/F modules
Modem
Modem
XBC-DR32H XBL-C21A
Modem
Modem
(4) 1:1 communication of an external device (monitoring unit) with main unit using a built-in RS-
232C/485 port.
XP30-TTA
2-9
Chapter 2 System Configuration
(1) Using RS-485 built-in function can connect between one computer and multiple main units for up
to 32 stations.
XBC-DN32H
XBM-DN32S XBM-DR16S XBM-DN32S
PADT connection
Can be connected
Max. 32 stations
Built-in RS-232C
Connection
(2) Using RS-485 built-in function/expansion Cnet I/F module can be connect for up to 32 stations.
XBC-DN32H XBL-C41A
XBL-C41A XBL-C41A
XBM-DN32S XBM-DN16S
PADT Connection
Can be connected
Max. 32 stations
Can be connected
Max. 32 stations
Note
2-10
Chapter 2 System Configuration
Ethernet made by cooperation of Xerox, Intel, DEC is standard LAN connection method (IEEE802.3),
which is network connection system using 1.5KB packet with 100Mbps transmission ability. Since
Ethernet can combine a variety of computer by network, it is called as standard specification of LAN and
diverse products. By adopting CSMA/CD method, it is easy to configure the network and collect large
capacity data.
Router or
Gateway
Hub
M
Public line
Router or Hub
Gateway H
HMI
Hub Hub
100Base-TX
HMI
Note
2-11
Chapter 3 General Specifications
Notes
3-1
Chapter 4 CPU Specifications
4- 1
Chapter 4 CPU Specifications
The following table shows the general specifications of the XGB compact type CPU (XBC-DR32/64H,
XBC-DN32/DN64).
Specifications (H type)
Items XBC-DN32H XBC-DR32H XBC-DN64H XBC-DR64H XBC- Remark
(/DC) (/DC) (/DC) (/DC) DR32HL
Cyclic execution of stored program, Time-driven interrupt,
Program control method Process-driven interrupt
Batch processing by simultaneous scan (Refresh method),
I/O control method
Directed by program instruction
Program language Ladder Diagram, Instruction List
Number of Basic 28
instructions Application 687
Processing speed
0.12 /Step
(Basic instruction)
Program capacity 15 Kstep 30kstep
352 point (Main + Expansion 10 384 point (Main + Expansion 10 -
Max. I/O points 352 point
stages) stages)
4- 2
Chapter 4 CPU Specifications
Specifications
Items Remark
S type H type
Controlled by instructions, Auto-tuning, PWM output, Manual
PID control function output, Adjustable operation scan time, Anti Windup, Delta MV
function, SV-Ramp function
Dedicated protocol support
MODBUS protocol support RS-232C 1 port
Cnet I/F function
User defined protocol support RS-485 1 port
-
addition/subtraction method
1 phase pulse input: addition/subtraction counter
Counter 1 phase pulse input: addition/subtraction counter by B
mode phase
2 phase pulse input: addition/subtraction counter
2 phase pulse input: addition/subtraction by
phase differences
Internal/External preset function
Additional Latch counter function
function Comparison output function
Revolution number per unit time function
No. of control axis: 2 axes No. of control axis: 2 axes
Built-in function
Continuous End/Keep/Continuous
Operation method: Single, Operation method: Single,
Repeated operation Repeated operation
Positioning method: Absolute / Incremental TR output
Positioning Address range: -2,147,483,648 ~ 2,147,483,647 type support
function Speed: Max. 100Kpps(setting range 1 ~ 100,000pps)
Acceleration / Deceleration method : trapezoidal method
Origin detection when approximate origin turns off
Return to Origin
Origin detection when approximate origin turns on
Origin detection by approximate origin.
JOG operation Setting range: 1~100,000 ( High / Low speed)
Inching operation, Speed synchronizing operation,
Additional
Position synchronizing operation, linear interpolation
function
operation etc.
10 4 point
50 (P0000 ~ P0003)
Pulse catch
8 point (P0000 ~ P0007) 50 4 point
(P0004 ~ P0007)
10 4 point -
8 point: 50 (P0000 ~ P0003)
External interrupt
(P0000 ~ P0007) 50 4 point
(P0004 ~ P0007)
Input filter Select among 1,3,5,10,20,70,100 (Adjustable)
4- 3
Chapter 4 CPU Specifications
S Type
XBM-DN16S
XBM-DN32S XBM-DR16S
8-1
8-3
8-2
PADT connecting
connector
PADT connecting connector
4- 4
Chapter 4 CPU Specifications
H Type
8-1
8-2
No. Name Description
4- 5
Chapter 4 CPU Specifications
Specification ( H type)
XBC-
Items XBC-DR64H, XBC-DR32H/DC, XBC-DR64H/DC,
DR32H(/HL),
XBC-DN64H XBC-DN32H/DC XBC-DN64H/DC
XBC-DN32H
Rated voltage
AC 100 ~ 240 V DC 24V
(UL warranty voltage)
Input voltage range AC85~264V(-15%, +10%) DC19.2~28.8V(-20%, +20%)
4- 6
Chapter 4 CPU Specifications
XBM-DR16S 400
XBM-DN16S 250
XBM-DN32S 280
XBC-DR32H(/HL) 660
XBC-DR64H 1,040
Main unit XBC-DN32H 260
XBC-DN64H 330
XBC-DR32H/DC 660
XBC-DR64H/DC 1,040
XBC-DN32H/DC 260
XBC-DN64H/DC 330
XBE-DC32A 50
XBE-DC16A 30
XBE-DC08A 20
XBE-RY16A 440
XBE-RY08A 240
XBE-TN32A 80
Expansion I/O module
XBE-TN16A 50
XBE-TN08A 40
XBE-TP32A 80
XBE-TP16A 50
XBE-TP08A 40
XBE-DR16A 250
XBF-AD04A 120
XBF-DV04A 110
XBF-DC04A 110
Expansion special module
XBF-RD04A 100
XBF-RD01A 100
XBF-TC04S 100
XBL-C21A 110
Expansion communication
XBL-C41A 110
module
XBL-EMTA 190
4- 7
Chapter 4 CPU Specifications
In case system is configured as above, since 5V consumption current is total 850mA and 5V output of XGB
standard type main unit is maximum 1.5A, normal system configuration is available.
If system is configured as above, total 5V current consumption is exceeded 1,540 mA and it exceeds the 5V
output of XGB standard type main unit. Normal system configuration is not available. Although we assume
the above example that all contact points are on, please use high-end type main unit which 5V output
capacity is higher than standard type main unit.
4- 8
Chapter 4 CPU Specifications
The above system is an example using XBC-DR32H about system example (2). Unlike (2) example, 5V
output capacity of XBC-DR32H is maximum 2A, normal configuration is available.
Remark
Calculating of consumption current is based on maximum consumption current. In application system,
the consumption current is consumed less than above calculation.
4- 9
Chapter 4 CPU Specifications
4.5 Battery
This contents is only applied to H type.
4.5.1 Battery specification
Item Specification
Voltage/Current DC 3V / 220 mA
Warranty period 3 years (ambient temp.)
Program and data backup,
Purpose
RTC operation in case of power failure
Specification Manganese Dioxide lithium battery
Dimension (mm) 20 X 3.2 mm
4- 10
Chapter 4 CPU Specifications
Yes
ERR LED off?
No
Battery malfunction Complete
4- 11
Chapter 5 Program Configuration and Operation Method
Start -
y Performs the operation in order from the program start to last step.
Output image area refresh
5-1
Chapter 5 Program Configuration and Operation Method
Remark
5-2
Chapter 5 Program Configuration and Operation Method
(1) Scan time = Scan program processing time Interrupt program processing time PLC internal
processing time
y Scan program processing time = processing time of user program not saved as interrupt program
y Interrupt program processing time = Sum of interrupt program proceeding time processed during 1 scan
y PLC internal processing time = Self-diagnosis time I/O refresh time Internal data processing time
Communication service processing time
(2) Scan time depends on whether to execute interrupt program and communication processing.
5- 3
Chapter 5 Program Configuration and Operation Method
1) WDT is the timer used to detect the operation delay by user program error. The detection time of WDT
is set in Basic parameter of XG5000.
2) If WDT detects the excess of detection setting time while watching the elapsed time of scan during
operation, it stops the operation of PLC immediately and keeps or clears the output according to
parameter setting
3) If the excess of Scan Watchdog Time is expected in the program processing of specific part while
performing the user program (FOR ~ NEXT instruction, CALL instruction), clear the timer by using WDT
instruction.
WDT instruction initializes the elapsed time of Scan Watchdog Timer and starts the time measurement
from 0 again.
(For further information of WDT instruction, please refer to Instruction.)
4) To clear the error state of watchdog, we can use the following method : power re-supply, manipulation
of manual reset switch, mode conversion to STOP mode.
WDT
count(ms)0 1 2 3 .. 8 9 0 1 2 012 6 7 0 1 2
Remark
5- 4
Chapter 5 Program Configuration and Operation Method
The XGB series use up count timer. There are 5 timer instructions such as on-delay (TON), off-delay (TOFF),
integral (TMR), monostable (TMON), and re-triggerable (TRTG) timer.
The measuring range of 100msec timer is 0.1 ~ 6553.5 seconds, 10msec timer is 0.01 ~ 655.35 seconds,
and that of 1msec timer is 0.001 ~ 65.53 seconds. Please refer to the XG5000 User manual for details.
Preset value
Timer output relay
Timer type
1) On delay timer
The current value of timer starts to increase from 0 when the input condition of TON instruction turns on.
When the current value reaches the preset value (Current value=Preset value), the timer output relay
(Txxxx) turns on. When the timer input condition is turned off, the current value becomes 0 and the timer
output relay is turned off.
Input condition
t0 t1 t2 t3 t4 t5
Output relay
t0+PT t1 t4+PT t5
Preset value
Current value
t0 t1 t2 t3 t4 t5
Input condition
t0 t1 t2 t3 t5
Output relay
t0 t1+PT t2 t5+PT
Preset value
Current value
t0 t1 t2 t4 t5
5- 5
Chapter 5 Program Configuration and Operation Method
3) Integral timer
In general, its operation is same as on-delay timer. Only the difference is the current value will not be clear
when the input condition of TMR instruction is turned off. It keeps the elapsed value and restart to
increase when the input condition is turned on again. When the current value reaches preset value, the
timer output relay is turned on.
The current value can be cleared by the RST instruction only.
Timer input
condition
t0 t1 t2 t4 t5
Current value
t0 t1 t2 t3 t5 t5+PT
4) Monostable timer
In general, its operation is same as off-delay timer. However, the change of input condition is ignored
while the timer is operating (decreasing). When current value reaches preset value the timer output relay
is turned off and current value is cleared.
Timer input
condition
t0 t1 t2 t3 t4
Current value
t0 t1 t2 t4
5- 6
Chapter 5 Program Configuration and Operation Method
5) Retriggerable timer
The operation of retriggerable timer is same as that of monostable timer. Only difference is that the
retriggerable timer is not ignore the input condition of TRTG instruction while the timer is operating
(decreasing). The current value of retriggerable timer will be set as preset value whenever the input
condition of TRTG instruction is turned on.
Remark
The Maximum timing error of timers of XGB series is 1 scan time + the time from 0 step to
timer instruction
5- 7
Chapter 5 Program Configuration and Operation Method
The counter counts the rising edges of pulses driving its input signal and counts once only when the input
signal is switched from off to on. XGB series have 4 counter instructions such as CTU, CTD, CTUD, and
CTR. The followings shows brief information for counter operation. Refer to the XGB Instruction Manual for
details.
Down counter decreases the current value at the rising edges of input.
The counter output contact (Cxxx) is turned On when the current value reaches the preset value.
When the reset input is turned On, the counter output contact (Cxxx) is turned Off.
The current value is increased with the rising edge of up-count input signal, and decreased with the
rising edge of down-count input signal. The counter output contact (Cxxx) is turned On when the
current value is same as or more than current value. The counter output contact (Cxxx) is turned Off
when the current value is same as or less than current value.
When the reset input is turned On, the current value is cleared as 0.
5- 8
Chapter 5 Program Configuration and Operation Method
The current value is increased with the rising edge of the counter input signal, and the counter output
contact (Cxxx) is turned on when the current value reaches the preset value. Then the current value and
counter output contact (Cxxx) is cleared as 0 when the next rising edge of the counter input signal is
applied.
When the reset input is turned On, the counter output contact is cleared as 0.
The maximum counting speed of determined by the length of scan time. Counting is possible only when
the on/off switching time of the counter input signal is longer than scan time.
n 1 n : duty (%)
Maximum counting speed C max = ( )
100 tS t S : scan time [s]
Duty is the ratio of the input signals on time to off time as a percentage.
On
Off Off
T1 T2
T1
If T1 T2, n = x 100 [%]
T1+T2
Remark
1) Use of High Speed Counter
In order to counter pulse that is faster than maximum counting speed of normal counter, use
built-in High Speed counter function.
5- 9
Chapter 5 Program Configuration and Operation Method
The program is performed according to the fixed time interval in case that the
required processing time condition is as below.
In case that the faster processing than 1 scan average processing time is
Cycle time interrupt
required
program
In case that the longer time interval than 1 scan average processing time is
required
In case that program is processed with the appointed time interval
External interrupt The external interrupt program is performed process on external interrupt
program signal.
Subroutine Only when some condition is satisfied.(in case that input condition of CALL
program instruction is On)
Start processing
Subroutine program
External interrupt program
Only when some
Scan program
condition is satisfied.
Cycle time program
END processing
5- 10
Chapter 5 Program Configuration and Operation Method
1) Scan program
(1) Function
This program performs the operation repeatedly from 0 step to last step in order prepared by the program
to process the signal that is repeatedly regularly every scan.
In case that the execution condition of interrupt by task interrupt or interrupt module while executing
program is established, stop the current program in execution and perform the related interrupt program.
2) Interrupt program
(1) Function
This program stops the operation of scan program and then processes the related function in prior to
process the internal/external signal occurred periodically/non-periodically.
(2) Type
Task program is divided as below.
Cycle time task program: available to use up to 8.
Internal device task program: available to use up to 8.
I/O (External contact task program): available to use up to 8. (P000 ~ P007)
Remark
(1) Write the interrupt program as shortly as possible. In case same interrupt occurs repeatedly
before completion of interrupt, program is not executed and O/S watch dog error may occur.
(2) Though interrupt which has lower priority occurs many times during execution of interrupt
which has higher priority, interrupt which has lower priority occurs only one time.
5- 11
Chapter 5 Program Configuration and Operation Method
5.2.3 Interrupt
For your understanding of Interrupt function, here describes program setting method of XG5000 which is an XGB
programming S/W. Example of interrupt setting is as shown bellows.
Interrupt setting
Interrupt source Interrupt name priority Task No. Program
Initializing Interrupt 0_ - - -
Cycle time 1 Interrupt 1_cycle time 2 0 Cycle time 1
External Interrupt 2_external 2 8 External
Internal device Interrupt 3_internal 3 14 Internal
Cycle time 2 Interrupt 4_cycle time 3 1 Cycle time 2
Scan program
Initializing
(Before INIT_DONE instruction)
Cycle time 1/
Cycle time 1 execution
external occur
simultaneously
External I/O execution
Internal device
Interrupt occur
Cycle time 2
Cycle time 2 execution
occur
Remark
In case that several tasks to be executed are waiting, execute from the highest Task Program in
priority. When the same priority tasks are waiting, execute from the order occurred.
While interrupt executing, if the highest interrupt is occurred, the highest interrupt is executed earliest of
all.
When power On, All interrupts are in the state Disable
Internal device interrupt is executed after END instruction.
5- 12
Chapter 5 Program Configuration and Operation Method
Generate the task in the project window of XG5000 as below and add the program to be performed by each
task. For further information, please refer to XG5000 users manual.
(It can be additional when XG5000 is not connected with PLC.)
Click right button of mouse on project name and click Add item-Task.
The screen of Task setting is shown. Click Initialization in Execution condition and make a Task name.
5- 13
Chapter 5 Program Configuration and Operation Method
Make initializing program. In initializing program, INIT_DONE instruction must be made. If not, Scan
program is not executed.
5- 14
Chapter 5 Program Configuration and Operation Method
Generate the task in the project window of XG5000 as below and add the program to be performed by each
task. For further information, please refer to XG5000 users manual.
(It can be additional when XG5000 is not connected with PLC)
5- 15
Chapter 5 Program Configuration and Operation Method
Task type
Classification Description Remark
Character, number
Task name Make Task name.
available
2 is the highest
Priority Set the priority of task. (2~7)
priority number.
Set the Task number.
Cycle time task (0 ~ 7): 8
Task number -
External I/O task (8 ~ 15): 8
Internal device task (16 ~ 23): 8
Till the execution of
Initialization Set the initial program when running the project. INIT_DONE
instruction
0~4294967295
Cycle time Set the cyclic interrupt.
Execution available
condition P000 ~ P007
I/O Set the external I/O.
available
Set the internal device to interrupt execution.
Internal
Bit: Among Rising, Falling, Transition, On, Off -
device
Word: Among >,>=,<,<=
5- 16
Chapter 5 Program Configuration and Operation Method
5- 17
Chapter 5 Program Configuration and Operation Method
3) Task type
Here describes common processing method and notices for Task program.
5- 18
Chapter 5 Program Configuration and Operation Method
5- 19
Chapter 5 Program Configuration and Operation Method
5- 20
Chapter 5 Program Configuration and Operation Method
5- 21
Chapter 5 Program Configuration and Operation Method
(4) Is program protection for the high priority task needed during program execution?
If other task is inserted during task program execution, complete the task in execution and operate the
standby tasks in the order of high priority. In case that it is not allowed to insert other task in Scan
Program, prevent the insert partially by using DI and EI application instruction. The problem may occur
while processing the global variables used commonly with other program or special or communication
module.
5- 22
Chapter 5 Program Configuration and Operation Method
Scan started
(Initial operation started) Scan program stopped New scan started
PO executed
P1 executed
10ms_Cycle time
Program 2
Internal device_M000
Program 3
External I/O_P000
Time
0 6 7 8 10 12 20 22 24 25 30 32 34
Time () Process
5- 23
Chapter 5 Program Configuration and Operation Method
For operation mode of CPU module, there are 3 types such as RUN mode, STOP mode and DEBUG mode..
Here describes the operation processing of each operation mode.
5- 24
Chapter 5 Program Configuration and Operation Method
3) Debug operation
It describes debug mode.
5- 25
Chapter 5 Program Configuration and Operation Method
(2) Go
Run the program to breakpoint. At break-pointer (stop indicator) is displayed.
5- 26
Chapter 5 Program Configuration and Operation Method
5- 27
Chapter 5 Program Configuration and Operation Method
Remark
5- 28
Chapter 5 Program Configuration and Operation Method
RUN X Run
RUN Remote Run
STOP Remote Stop
STOP
Debug Debug Run
Mode change Previous operation mode
RUN -> STOP - Stop
(1) Remote mode conversion is available only in the state of Remote Enabled: On, Mode switch: Stop.
(2) In case of changing the Remote RUN mode to STOP by switch, operate the switch as follows.
(STOP) RUN STOP .
Warning
In case of changing Remote RUN mode to RUN mode by switch, PLC operation continues the
operation without interruption.
It is available to modify during RUN in RUN mode by switch but the mode change operation by
XG5000 is limited. This should be set only in case that remote mode change is not allowed.
5- 29
Chapter 5 Program Configuration and Operation Method
5.4 Memory
There are two types of memory in CPU module that the user can use. One is Program Memory that saves the
user program written by the user to build the system, and the other is Data Memory that provides the device area
to save the data during operation.
Various Bit Device are provided per function. The indication method is indicated by device type for first digit,
word position by decimal for middle digit and bit position by hexadecimal for the last digit.
L0000 ~ L0000~ Communication device Device to indicate high speed link/P2P service state
L1279f L2047f L information of communication module.
F0000 ~ F0000~ System flag area that manages the flag necessary
Special device F
F255f F1023f for system operation in PLC.
5- 30
Chapter 5 Program Configuration and Operation Method
U00.00 ~ U00.00~ Analog data Register used to read data from special module installed
U07.31 U0A.31 register U in the slot. Bit expression possible
Communication
N0000 ~ N0000~ P2P Service Save area of communication module.
data register
N3935 N5119 Bit expression impossible
N
R0000~
- File register R Register for saving the file
R10239
5- 31
Chapter 5 Program Configuration and Operation Method
5.5.1 S type
Bit data area Word data area
0 ~ F 0000 ~ FFFF
P000 D0000
I/O Relay Data Register Parameter area
(2048 points) (5120 words)
P127 P
M000 D5119 D User Program area
Auxiliary Relay
N0000 (10 K step)
(4096 points)
Comm. Data
M255 M
Register
K000
Keep Relay (3936 words)
5- 32
Chapter 5 Program Configuration and Operation Method
5.5.2 H type
0 ~ F 0000 ~ FFFF
P0000 D0000
I/O Relay Data Register Parameter area
(2048 points) (10240 words)
P1023 P
M0000 D10239 D User Program area
Auxiliary Relay
N0000 (15 K step)
(4096 points)
Comm. Data
M1023 M
Register
K0000
Keep Relay (5120 words)
5- 33
Chapter 5 Program Configuration and Operation Method
Remark
5- 34
Chapter 5 Program Configuration and Operation Method
For keep or reset (clear) operation of latch area data according to PLC operation, please refer to the
below table.
No. Classification Detailed operation Latch 1 Latch 2
1 Power change Off/On Keep Keep
2 Reset by XG5000 Overall reset Reset Keep
3 Program write (online) - Keep Keep
SRAM broken by battery error Reset Reset
4 Data broken
Data broken by other reason Reset Reset
Clear Latch 1 Reset Keep
5 XG5000 online
Clear Latch 2 Reset Reset
5- 35
Chapter 5 Program Configuration and Operation Method
3) Data initialization
In case of Memory Delete state, the memory of all device shall be cleared as 0. In case of giving the data
value at the beginning according to system, please use the initialization task.
5- 36
Chapter 6 CPU Functions
PLC
CPU type Description Reference
Series
XGB-DR16C3 Dedicated product Module type
XGB XGB-XBMS S type : XBM-DN16/32S , XBM-DR16S Module type
Compact
XGB-XBCH H type : XBC-DR32/64H , XBC-DN32/64H
type
Remark
6- 1
Chapter 6 CPU Functions
There are three main options ; Basic Operation Setup , Device Area Setup and Error Operation
Setup.
6- 2
Chapter 6 CPU Functions
This setting is to set and reserve each I/O information. Clicking I/O Parameter in the project
window shows the following setting window.
Clicking Module in Slot Position indicates a list of modules, in which you may set I/O
corresponding to the actual system. Then, the following window is displayed.
6- 3
Chapter 6 CPU Functions
Clicking Details in Slot Position shows the following window to set filter and emergency output.
Remark
If settings are different with I/O module actually accessed, Inconsistent module type error occurs,
displaying error.
Without settings, CPU reads each I/O module information and operates.
[S type] [H type]
Remark
1) Saved data are not deleted until selecting a menu of XG5000 and clicking Delete.
2) H type displays Data and Time.
6- 4
Chapter 6 CPU Functions
6.3.2 Troubleshooting
1) Trouble types
Trouble occurs due to PLC itself, system configuration error or abnormal operation result detected. Trouble
is divided into trouble mode stopping operation for the safety and warning mode generating alert to user
with a mode in trouble.
Remark
1) If any trouble occurs, the unique trouble number is saved in a special relay F****.
2) For details of flag, refer to the appendix 1 Flag List.
6- 5
Chapter 6 CPU Functions
2) Remote RUN/STOP
Remote RUN/STOP is the externally controlled RUN/STOP function.
It is convenient when CPU module is located at a position hard to control or when CPU module within
control panel is to control RUN/STOP function remotely.
3) Remote DEBUG
It manages debugging remotely when remote mode is STOP. Namely, DEBUG operation is to execute
program operation depending on designated operation conditions.
Remote DEBUG is a convenient function when confirming program operation status or data during
system debugging.
4) Remote Reset
Remote reset is to reset CPU module remotely if an error occurs at a place hard to directly control CPU
module.
Like operation by switches, it supports Reset and Overall Reset.
Remark
1) For details regarding remote functions, refer to Online of XG5000 Users Manual.
6- 6
Chapter 6 CPU Functions
Item Description
Move to the beginning and end of I/O area (P000P127)
Move address Move to 8 of I/O area displayed at the very left.
Move to 1 of I/O area.
Application Set whether to allow or not Force I/O
Flag Set whether to allow or not Force I/O by bits.
Single
Data Set Force I/O data on or off by bits.
Select All Set to allow Force I/O with all I/O area on
6- 7
Chapter 6 CPU Functions
6.5.2 Processing time and processing method of Force Input/Output On and Off
1) Forced Input
Regarding input, at the time of input refresh it replaces the data of contact set as Force On/Off among
data read from input module with the data as Force and updates input image area. Therefore, user
program executes operations with actual input data while Force input area is operated with data set as
Force.
2) Forced Output
Regarding output, at the time of output refresh upon the execution user program operation, it replaces
the data of contact set as Force On/Off among data of output image area containing operation results
with data set as Force and outputs the data in output module. Unlike (Force) input, the output image
area is not changed by Force On/Off setting.
This function may be useful when directly reading the status of input contact during program operation by
refreshing I/O by means of IORF instruction or outputting operation results to output contact.
IORF command is operated when M00000 is ON. First operand designates slot number. Second operand
designates the upper 32 bit data as mask data. Third operand designates the lower 32 bit data as mask data.
The bit to refresh set as 1 (hFF) and others set as 0 (h00) (not refreshed).
Remark
6- 8
Chapter 6 CPU Functions
This flag is provided for a user to diagnose any fault of external device and, in turn, execute halt or warning of
the system. Use of this flag displays faults of external device without any complicated program prepared and
monitors fault location without any specific device (XG5000 and etc) or source program.
Example
M000
Error device bit On
FSET F2020
If any trouble occurs, CPU is in error status and operation halts. At this moment, F2020 and F2002 flags
are off (error LED switches on and off every second.)
Example
M000
FSET F2030 Warning device bit On
6- 9
Chapter 6 CPU Functions
System Configuration
Number of
Type I/O allocation Remarks
Connection stage
Input: P0000 ~ P001F
0 XBM-DN32S Basic unit fixed
Output: P0020 ~ P003F
1 XBE-DC32A Input: P0040~P007F Actual input: P0040 ~ P004F
5 XBE-DV04A P0200~P027F -
6- 10
Chapter 6 CPU Functions
System Configuration
Number of
Connection Type I/O allocation Remarks
stage
Input: P0000 ~ P001F
0 XBC-DN32H Basic unit fixed
Output: P0020 ~ P003F
1 XBE-DC32A Input: P0040~P007F Actual input: P0040 ~ P005F
6- 11
Chapter 6 CPU Functions
6- 12
Chapter 6 CPU Functions
3) It turns to program modification mode during run when the program background is changed.
4) Modifying a program.
6- 13
Chapter 6 CPU Functions
7) The program background returns and the program modification during run is completed.
Remark
For parameter modification during run, change each parameter on XG-PD and clickOnline-Write
Modified Program .
6- 14
Chapter 6 CPU Functions
1) ClickOnline-I/O Info. Then, information of each module connected to the system is monitored.
2) If clicking Details after selecting a module, it displays detail information of a selected module.
6- 15
Chapter 6 CPU Functions
6.11 Monitoring
It monitors system information of XGB series system.
Start/Stop Monitoring Designate the start and stop of monitor. Click for reverse turn.
6- 16
Chapter 6 CPU Functions
6- 17
Chapter 6 CPU Functions
6- 18
Chapter 6 CPU Functions
It monitors detail information when an event set by a user occurs. Additional user event may be
registered.
6- 19
Chapter 6 CPU Functions
Double-clicking a number produced monitors the relative values of device and the detail message as
follows.
Remark
6- 20
Chapter 6 CPU Functions
3) In case the user wants to send the clock of PC to PLC, press Synchronize PLC with PC clock.
4) In case the user wants to send the clock the user wants, change the setting value of Time box
and press Send to PLC.
6- 21
Chapter 6 CPU Functions
07year 9month
12date 14hour
20minute 40second
20XXyear, Wednesday
area Content
K0000 Year, month
K0001 Date, hour
K0002 Minute, second
K0003 Centaury, day
Write clock data to temporary device (P, M, K, L, Z, U, D, R) and turn on/off input contact point
M0000. ( If date and day data is not matched, Write is not available.)
Monitor and check the above special area (F053~F056)
Remark
1) Initially, RTC may not have any clock data.
2) When using the CPU module, first make sure to set the accurate clock data.
3) If any data out of the clock data range is written into RTC, it does not work properly.
i.e.) 14M 32D 25H
4) RTC may stop or have an error due to abnormal battery and other causes. The error is released if a
new clock data is written.
6- 22
Chapter 6 CPU Functions
You can save the user program safely and download the program into the system when program is damaged
without special manipulation by using external memory module.
6.13.1 Structure
RUN LED
WRITE LED
READ LED
(2) Downloading the user program in the external memory module into the main unit
(a) Set the operation mode of main unit into STOP.
- You cant download the program into the main unit in RUN mode.
(b) Set the switch of memory module into 1.
(c) Install the memory module
- Install the memory module at RS-232C port of main unit.
- Program and parameter are downloaded into PLC and LED is on.
- If downloading program and parameter is complete, WRITE LED is off.
(d) Change the operation mode into RUN then PLC operates with newly downloaded program and
parameter.
Note
-. All program, parameter of XG500 and link information of XG-PD are saved .
-. When PLC is RUN mode, remove the external memory module from main unit.
-. Dont remove the memory module from the main unit when READ/WRITE LED is on.
6- 23
Chapter 7 Input/Output Specifications
1) For the type of digital input, there are two types such as current sink input and current source
input.
2) The number of max. Simultaneous input contact point is different according to module type. It
depends on the input voltage, ambient temperature. Use input module after checking the
specification.
3) When response to high speed input is necessary, use interrupt input contact point. Up to 8
interrupt points are supported.
4) In case that open/close frequency is high or it is used for conductive load open/close, use
Transistor output module or triac output module as the durability of Relay Output Module shall
be reduced.
5) For output module to run the conductive (L) load, max. open/close frequency should be used
by 1second On, 1 second Off.
6) For output module, in case that counter timer using DC/DC Converter as a load was used,
Inrush current may flow in a certain cycle when it is ON or during operation. In this case, if
average current is selected, it may cause the failure. Accordingly, if the previous load was
used, it is recommended to connect resistor or inductor to the load in serial in order to reduce
the impact of Inrush current or use the large module having a max. load current value.
7-1
Chapter 7 Input/Output Specifications
100
Open/Close times ( 10000)
50
30
20
10
AC 125V Resistive load
0.5 1 2 3 5 10 100
7-2
Chapter 7 Input/Output Specifications
8) A clamped terminal with sleeve can not be used for the XGB terminal strip. The clamped terminals
suitable for terminal strip are as follows (JOR 1.25-3:Daedong Electricity in Korea).
9) The cable size connected to a terminal strip should be 0.3~0.75 stranded cable and 2.8 thick.
The cable may have different current allowance depending on the insulation thickness.
10) The coupling torque available for fixation screw and terminal strip screw should follow the table below.
11) Relay life graph is not written based on real use. (This is not a guaranteed value). So consider margin.
Relay life is specified under following condition.
12) Noise can be inserted into input module. To prevent this noise, the user can set filter for input delay in
parameter. Consider the environment and set the input filter time.
Input filter time (ms) Noise signal pulse size (ms) Reference
1 0.3
3 1.8 Initial value
5 3
10 6
20 12
70 45
100 60
7-3
Chapter 7 Input/Output Specifications
7-4
Chapter 7 Input/Output Specifications
7-5
Chapter 7 Input/Output Specifications
If it is selected as Clear, the output will be Off and if Hold is selected, the output will be kept.
7-6
Chapter 7 Input/Output Specifications
Specification XBM-DR16S
Input point 8 point
Insulation method Photo coupler insulation
Rated input voltage DC24V
Rated input current About 4 (00~03: About 7 )
Operation voltage range DC20.4~28.8V (ripple rate < 5%)
On Voltage/Current DC19V or higher/ 3 or higher
Off Voltage/Current DC6V or lower/ 1 or lower
Input resistance About 5.6 (P00~P03: about 3.3 )
Response Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default: 3
time On Off
Insulation pressure AC560Vrms / 3Cycle (altitude 2000m)
Insulation resistance 10 or more by Megohmmeter
Common Method 8 point / COM
Proper cable size Twisted pair 0.3~0.75 (external diameter 2.8 or less)
Current consumption () 180 (When Input On LED On)
Operation indicator Input On, LED On
External connection
9 pin terminal block connector
method
Weight 140g
Circuit configuration No. Contact Type
TB1 00
TB2 01 TB1
TB3 02 TB2
0 Photo coupler
TB1
R TB4 03 TB3
TB4
R TB5 04
TB5
7
TB8 Internal
Circuit TB6 05 TB6
TB9
COM
TB7 06 TB7
DC24V
TB8
TB8 07
Terminal block no. TB9
TB9 COM
7-7
Chapter 7 Input/Output Specifications
Specification XBM-DN16S
Input point 8 point
Insulation method Photo coupler insulation
Rated input voltage DC24V
Rated input current About 4 (Contact point 0~3: About 7 )
Operation voltage range DC20.4~28.8V (ripple rate < 5%)
On Voltage/Current DC19V or higher / 3 or higher
Off Voltage/Current DC6V or less / 1 or less
Input resistance About 5.6 (P00~P03: About 3.3 )
Response Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default: 3
time On Off
Insulation pressure AC560Vrms / 3Cycle (altitude 2000m)
Insulation resistance 10 or more by Megohmmeter
Common method 8 point / COM
Proper cable size 0.3
Current consumption 180 (when all point On)
Operation indicator Input On, LED On
External connection method 20 pin connector
Weight 100g
Circuit configuration No. Contact No. Contact Type
B10 00 A10 NC
B09 01 A09 NC
B10 A10
B08 02 A08 NC B09 A09
0
B10 Photo coupler B08 A08
R B07 03 A07 NC
B07 A07
R B06 A06
B06 04 A06 NC
B05 A05
F Internal
B03 B04 A04
circuit B05 05 A05 NC
B02 B03 A03
COM B02 A02
B04 06 A04 NC B01 A01
DC24V
B03 07 A03 NC
Terminal block no.
B02 COM A02 NC
B01 COM A01 NC
7-8
Chapter 7 Input/Output Specifications
Specification XBM-DN32S
Input point 16 point
Insulation method Photo coupler insulation
Rated input voltage DC24V
Rated input current About 4 (Contact point 0~3: About 7 )
Operation voltage range DC20.4~28.8V (ripple rate < 5%)
On Voltage/Current DC19V or higher / 3 or higher
Off Voltage/Current DC6V or less / 1 or less
Input resistance About 5.6 (P00~P03: About 3.3 )
Response Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default: 3
time On Off
Insulation pressure AC560Vrms / 3Cycle (altitude 2000m)
Insulation resistance 10 or more by Megohmmeter
Common method 16 point / COM
Proper cable size 0.3
Current consumption 200 (when all point On)
Operation indicator Input On, LED On
External connection
20 pin connector
method
Weight 110g
Circuit configuration No. Contact No. Contact Type
B10 00 A10 08
B09 01 A09 09
B10 A10
0
B10 Photo coupler B08 02 A08 0A B09 A09
R
B08 A08
R
B07 03 A07 0B B07 A07
B06 A06
F Internal B06 04 A06 0C
A03 B05 A05
B02
circuit B04 A04
COM B05 05 A05 0D B03 A03
B02 A02
DC24V B04 06 A04 0E B01 A01
Terminal block no.
B03 07 A03 0F
B02 COM A02 COM
B01 COM A01 COM
7-9
Chapter 7 Input/Output Specifications
Response Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default: 3
time On Off
Insulation pressure AC560Vrms / 3Cycle (altitude 2000m)
Insulation resistance 10 or more by Megohmmeter
Common method 16 point / COM
Proper cable size 0.3
Current consumption 200 (when all point On)
Operation indicator Input On, LED On
External connection
24 points connecting connector (M3 X 6 screw)
method
Weight 600g 500g
Circuit configuration No. Contact No. Contact Type
TB1 RX
TB2 485+ TB1
TB3 TX TB2
TB3
0
B10
Photocoupler TB4 485- TB4
R
TB5 SG TB5
R TB6 00 TB6
F
TB7
A03 Internal TB7 01 TB8
B02 circuit TB8 02 TB9
COM TB10
TB9 03 TB11
DC24V TB10 04 TB12
TB13
Terminal block no. TB11 05 TB14
TB12 06 TB15
TB13 07 TB16
TB17
TB14 08 TB18
TB15 09 TB19
TB20
TB16 0A TB21
TB17 0B TB22
TB23
TB18 0C TB24
TB19 0D
TB20 0E
TB21 0F
TB22 COM
TB23 24G
TB24 24V
7-10
Chapter 7 Input/Output Specifications
7-11
Chapter 7 Input/Output Specifications
Specification XBM-DR16S
Output point 8 point
Insulation method Relay insulation
Rated load voltage / current DC24V 2A(Resistive load) / AC220V 2A(COS = 1), 5A/COM
Min. load voltage/current DC5V / 1
Max. load voltage/current AC250V, DC125V
Off leakage current 0.1 (AC220V, 60 )
Max. On/Off frequency 3,600 times/hr
Surge absorber None
Mechanical 20 millions times or more
Rated load voltage / current 100,000 times or more
Service
AC200V / 1.5A, AC240V / 1A (COS = 0.7) 100,000 times or more
life Electrical
AC200V / 1A, AC240V / 0.5A (COS = 0.35) 100,000 times or more
DC24V / 1A, DC100V / 0.1A (L / R = 7 ) 100,000 times or more
TB1 20
DC5V TB2 21
TB1
TB3 22 TB2
TB1 TB3
TB4 23
Internal RY
TB4
circuit TB5
TB5 24
TB8 TB6
TB6 25 TB7
TB9
TB8
TB7 26 TB9
Terminal block no.
TB8 27
TB9 COM
7-12
Chapter 7 Input/Output Specifications
Specification XBM-DN16S
Output point 8 point
Insulation method Photo coupler insulation
Rated load voltage DC 12 / 24V
Load voltage range DC 10.2 ~ 26.4V
General output: 0.2A/ 1point,
Max. load voltage
Output for positioning (P20, P21): 01.A/ 1 point, 2A/1COM
Off leakage current 0.1 or less
Max. inrush current 4A / 10 or less
Max. voltage drop (On) DC 0.4V or less
Surge absorber Zener Diode
7-13
Chapter 7 Input/Output Specifications
Specification XBM-DN32S
Output point 16 point
Insulation method Photo coupler insulation
Rated load voltage DC 12 / 24V
Load voltage range DC 10.2 ~ 26.4V
General output: 0.2A/ 1point,
Max. load voltage
Output for positioning (P20, P21): 01.A/ 1 point, 2A/1COM
Off leakage current 0.1 or less
Max. inrush current 4A / 10 or less
Max. voltage drop (On) DC 0.4V or less
Surge absorber Zener Diode
7-14
Chapter 7 Input/Output Specifications
TB5
TB1
AC100
TB2 FG
~ 240V TB1
I RY TB3 TB2
N TB8 TB4 NC TB3
T TB4
COM0 TB9
TB5 20
E TB5
R TB6 21 TB6
N TB10 TB7 22 TB7
A TB8
TB8 23 TB9
l RY
TB13
TB9 COM0 TB10
TB10 24 TB11
C TB12
I COM1 TB14 TB11 25 TB13
R TB12 26 TB14
C TB15
TB15
U TB13 27 TB16
I RY TB14 COM1 TB17
T TB18 TB18
TB15 28 TB19
COM2 TB19 TB16 29 TB20
TB17 2A TB21
TB20 TB22
TB18 2B TB23
RY
TB19 COM2 TB24
TB23 TB20 2C
TB21 2D
COM3 TB24 TB22 2E
TB23 2F
Terminal block no. TB24 COM3
7-15
Chapter 7 Input/Output Specifications
7-16
Chapter 7 Input/Output Specifications
TB05 TB1
DC5V AC100
TB2 FG
R
~240V TB1
TB3
TB08 DC12 TB2
TB4 TB3
I /24V TB4
TB09 TB5 20
N TB5
T DC12/24V TB6 21 TB6
TB10
E TB7 22 TB7
R R TB8 23 TB8
N TB9
TB13
A TB9 COM0 TB10
TB11
l TB14 TB10 24
TB12
DC12/24V TB11 25 TB13
C TB15 TB12 26 TB14
I TB15
R R
TB13 27 TB16
C TB18 TB14 COM1 TB17
U TB15 28 TB18
I TB19 TB19
T
TB16 29 TB20
DC12/24V TB21
TB20 TB17 2A
TB22
TB18 2B TB23
R
TB23 TB19 COM2 TB24
TB20 2C
TB24 TB21 2D
DC12/24V TB22 2E
TB04
TB23 2F
TB24 COM3
Terminal block no.
7-17
Chapter 7 Input/Output Specifications
7-18
Chapter 7 Input/Output Specifications
Specification XBE-DC08A
Input point 8 point
Insulation method Photo coupler insulation
Rated input voltage DC24V
Rated input current About 4
Operation voltage range DC20.4~28.8V (ripple rate < 5%)
On Voltage/Current DC19V or higher / 3 or higher
Off Voltage/Current DC6V or less / 1 or less
Input resistance About 5.6
Response Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default: 3
time On Off
Insulation pressure AC560Vrms / 3Cycle (altitude 2000m)
Insulation resistance 10 or more by Megohmmeter
Common method 8 point / COM
Proper cable size Stranded pair 0.3~0.75 (External diameter 2.8 or less)
Current consumption 30 (when all point On)
Operation indicator Input On, LED On
External connection
9 point terminal block connector
method
Weight 52 g
Circuit configuration No. Contact Type
TB1 0
TB2 1 TB1
0 Photo coupler TB3 2 TB2
TB1
R
TB4 3 TB3
R
TB4
7
TB8 Internal TB5 4
circuit
TB5
TB9
COM
TB6 5 TB6
TB7 6 TB7
DC24V
Terminal block no.
TB8
TB8 7
TB9
TB9 COM
7-19
Chapter 7 Input/Output Specifications
Specification XBE-DC16A
Input point 16 point
Insulation method Photo coupler insulation
Rated input voltage DC24V
Rated input current About 4
Operation voltage range DC20.4~28.8V (ripple rate < 5%)
On Voltage/Current DC19V or higher / 3 or higher
Off Voltage/Current DC6V or less / 1 or less
Input resistance About 5.6
Response Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default: 3
time On Off
Insulation pressure AC560Vrms / 3Cycle (altitude 2000m)
Insulation resistance 10 or more by Megohmmeter
Common method 16 point / COM
Proper cable size Stranded cable 0.3~0.75 (External diameter 2.8 or less)
Current consumption 40 (when all point On)
Operation indicator Input On, LED On
External connection method 8 pin terminal block connector + 10 pin terminal block connector
Weight 53 g
Circuit configuration No. Contact Type
TB1 0
TB2 1 TB1
TB3 2 TB2
TB4 3 TB3
TB4
TB5 4
TB5
TB6 5
TB6
TB7 6 TB7
0 Photo coupler
TB1
R TB8 7 TB8
R TB1 8
TB1
F Internal
TB8
circuit TB2 9 TB2
TB9
COM TB3 A TB3
DC24V TB4 B TB4
Terminal block no. TB5
TB5 C
TB6
TB6 D TB7
TB7 E TB8
TB8 F TB9
TB9 COM TB10
TB10 COM
7-20
Chapter 7 Input/Output Specifications
Specification XBE-DC32A
Input point 32 point
Insulation method Photo coupler insulation
Rated input voltage DC24V
Rated input current About 4
Operation voltage range DC20.4~28.8V (ripple rate < 5%)
Input Derating Refer to Derating diagram
On Voltage/Current DC 19V or higher / 3 or higher
Off Voltage/Current DC 6V or less / 1 or less
Input resistance About 5.6
Response Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default:3
time On Off
Insulation pressure AC 560Vrms / 3 Cycle (altitude 2000m)
Insulation resistance 10 or more by Megohmmeter
Common method 32 point / COM
Proper cable size 0.3
Current consumption 50 (when all point On)
Operation indicator Input On, LED On
External connection method 40 pin connector
Weight 60g
Circuit configuration No. Contact No. Contact Type
B20 00 A20 10
B19 01 A19 11
0 Photo coupler
B20 R B18 02 A18 12
B17 03 A17 13 B20 A20
R
B19 A19
1F
B03 Internal B16 04 A16 14 B18 A18
B02 circuit B15 05 A15 15 B17 A17
COM B16 A16
B14 06 A14 16
B15 A15
DC24V
Terminal block no. B13 07 A13 17 B14 A14
B12 08 A12 18 B13 A13
Input Derating diagram B12 A12
B11 09 A11 19 B11 A11
100 B10 0A A10 1A B10 A10
90 B09 A09
B09 0B A09 1B B08 A08
80 DC28.8V B08 0C A08 1C B07 A07
On rate (%)
70 B06 A06
B07 0D A07 1D B05 A05
60 B06 0E A06 1E B04 A04
50 B03 A03
B05 0F A05 1F B02 A02
40 A01
0 10 20 30 40 50 55 B04 NC A04 NC B01
7-21
Chapter 7 Input/Output Specifications
Specification XBE-RY08A
Output point 8 point
Insulation method Relay insulation
Rated load voltage / Current DC24V 2A (Resistive load) / AC220V 2A (COS = 1), 5A/COM
Min. load voltage/Current DC5V / 1
Max. load voltage/Current AC250V, DC125V
Off leakage current 0.1 (AC220V, 60 )
Max. On/Off frequency 3,600 times/hr
Surge absorber None
Mechanical 20 millions times or more
Rated load voltage / current 100,000 times or more
Service life AC200V / 1.5A, AC240V / 1A (COS = 0.7) 100,000 times or more
Electrical
AC200V / 1A, AC240V / 0.5A (COS = 0.35) 100,000 times or more
DC24V / 1A, DC100V / 0.1A (L / R = 7 ) 100,000 times or more
TB1 0
DC5V TB2 1
TB3 2 TB1
TB1 TB2
TB4 3 TB3
Internal RY
circuit TB4
TB5 4
TB8 TB5
TB6 5 TB6
TB9
TB7
TB7 6 TB8
Terminal block no. TB9
TB8 7
TB9 COM
7-22
Chapter 7 Input/Output Specifications
Specification XBE-RY16A
Output point 16 point
Insulation method Relay insulation
Rated load voltage/ current DC24V 2A (Resistive load) / AC220V 2A (COS = 1), 5A/COM
Min. load voltage/current DC5V / 1
Max. load voltage/current AC250V, DC125V
Off leakage current 0.1 (AC220V, 60 )
Max. On/Off frequency 3,600 times/hr
Surge absorber None
Mechanical 20 millions times or more
Rated load voltage / current 100,000 times or more
Service
AC200V / 1.5A, AC240V / 1A (COS = 0.7) 100,000 times or more
life Electrical
AC200V / 1A, AC240V / 0.5A (COS = 0.35) 100,000 times or more
DC24V / 1A, DC100V / 0.1A (L / R = 7 ) 100,000 times or more
TB9 TB1 8
TB1
TB2 9 TB2
TB3 A TB3
Terminal block no.
TB4 B TB4
TB5 C TB5
TB6 D TB6
TB7 E TB7
TB8
TB8 F
TB9
TB9 COM
7-23
Chapter 7 Input/Output Specifications
Specification XBE-TN08A
Output point 8 point
Insulation method Photo coupler insulation
Rated load voltage DC 12 / 24V
Load voltage range DC 10.2 ~ 26.4V
Max. load voltage 0.5A / 1 point
Off leakage current 0.1 or less
Max. inrush current 4A / 10 or less
Max. voltage drop (On) DC 0.4V or less
Surge absorber Zener Diode
DC5V TB02 1
TB01 TB01
TB03 2 TB02
R TB04 3 TB03
Internal TB04
circuit TB05 4 TB05
TB08
TB06 5 TB06
TB07
TB09 TB07 6
TB08
TB10 TB08 7 TB09
DC12/24V DC12 TB10
TB09
Terminal block no.
/24V
TB10 COM
7-24
Chapter 7 Input/Output Specifications
Specification XBE-TN16A
Output point 16 point
Insulation method Photo coupler insulation
Rated load voltage DC 12 / 24V
Load voltage range DC 10.2 ~ 26.4V
Max. load voltage 0.2A / 1 point, 2A / 1COM
Off leakage current 0.1 or less
Max. inrush current 4A / 10 or less
Max. voltage drop (On) DC 0.4V or less
Surge absorber Zener Diode
7-25
Chapter 7 Input/Output Specifications
Specification XBE-TN32A
Output point 32 point
Insulation method Photo coupler insulation
Rated load voltage DC 12 / 24V
Load voltage range DC 10.2 ~ 26.4V
Max. load voltage 0.2A / 1 point, 2A / 1COM
Off leakage current 0.1 or less
Max. inrush current 0.7A / 10 or less
Max. voltage drop (On) DC 0.4V or less
Surge absorber Zener Diode
Off On 1 or less
Response time
On Off 1 or less (Rated load, resistive load)
Common method 32 point / COM
Proper cable size 0.3
Current consumption 120 (when all point On)
7-26
Chapter 7 Input/Output Specifications
Easy wiring is available by connecting the IO connector with smart link board.
The available smart link and IO cable are as follows.
Item Specification
Rated voltage AC/DC 125[V]
Rated current Max. 1[A]
Withstanding
600V 1min
voltage
Insulation
100 (DC500V)
resistor
Cable
1.25[] or below
specification
Terminal/screw M3 X 8L
6.2 f. or
Torque
above
Terminal
PBT, UL94V-0
material
Weight 186g
7-27
Chapter 7 Input/Output Specifications
XBM-DN32S
SLT-CT101-XBM
SLP-T40P
At this time, relationship of XGB IO signal and Smart link board terminal number is as follows.
The following figure describes signal allocation when SLT-CT101-XBM is used as connection cable.
When the user makes the cable, make sure that wring is done as figure below.
7-28
Chapter 8 Built-in High-speed Counter Function
8-1
Chapter 8 Built-in High-speed Counter Function
Description
Classification
S type H type
Count Enable To be set through program (count available only in enable status)
Classification Spcification
Input current 4
P00 P00
P01 P01
P02 P02
P03 P03
P04 P04
Structure P05 P05
P06 P06
P07 P07
COM
COM
COM
8-2
Chapter 8 Built-in High-speed Counter Function
(a) S type
Terminal Names Usage
No. 1-phase 2-phase 1-phase 2-phase
P000 Ch0 counter input Ch0 A-phase input Counter input terminal A-phase input
P001 Ch1 counter input Ch0 B-phase input Counter input terminal B-phase input
P002 Ch2 counter input Ch2 A-phase input Counter input terminal A-phase input
P003 Ch3 counter input Ch2 B-phase input Counter input terminal B-phase input
P004 Ch0 preset 24V Ch0 preset 24V Preset input terminal Preset input terminal
P005 Ch1 preset 24V - Preset input terminal No use
P006 Ch2 preset 24V Ch2 preset 24V Preset input terminal Preset input terminal
P007 Ch3 preset 24V - Preset input terminal No use
COM0 Input common Input common Common terminal Common terminal
(b) H type
8-3
Chapter 8 Built-in High-speed Counter Function
Operation
Terminal
I/O Internal circuit guaranteed
No. 1-phase 2-phase
voltage
Ch 0 Ch 0 On 20.4~28.8V
3.3 k P00
Pulse input A-phase input Off 6V or less
Ch 1 Ch 0 On 20.4~28.8V
3.3 k P01
Pulse input B-phase input Off 6V or less
Ch 2 Ch 2 On 20.4~28.8V
P02
3.3 k Pulse input A-phase input Off 6V or less
Ch 3 Ch 2 On 20.4~28.8V
P03
3.3 k Pulse input B-phase input Off 6V or less
Input
Ch 0 Ch 0 On 20.4~28.8V
P04
5.6 k Preset input Preset input Off 6V or less
Ch 1 On 20.4~28.8V
P05 -
Preset input Off 6V or less
5.6 k
Ch 2 Ch 2 On 20.4~28.8V
P06
5.6 k Preset input Preset input Off 6V or less
Ch 2 On 20.4~28.8V
P07 -
5.6 k
Preset input Off 6V or less
COM0 COM (input common)
8-4
Chapter 8 Built-in High-speed Counter Function
Signal On/Off
Operation
Terminal
I/O Internal circuit guaranteed
No. 1-phase 2-phase
voltage
Ch 0 Ch 0 On 20.4~28.8V
P0000
2.7 k Pulse input A-phase input Off 6V or less
Ch 1 Ch 0 On 20.4~28.8V
P0001
2.7 k Pulse input B-phase input Off 6V or less
Ch 2 Ch 2 On 20.4~28.8V
P0002
2.7 k Pulse input A-phase input Off 6V or less
Ch 3 Ch 2 On 20.4~28.8V
P0003
2.7 k Pulse input B-phase input Off 6V or less
Ch 4 Ch 4 On 20.4~28.8V
P0004
2.7 k Pulse input A-phase input Off 6V or less
Ch 5 Ch 4 On 20.4~28.8V
P0005
2.7 k Pulse input B-phase input Off 6V or less
Ch 6 On 20.4~28.8V
Ch 6
2.7 k P0006 A-phase
Pulse input Off 6V or less
input
2.7 k
Ch 6 On 20.4~28.8V
Ch 7
P0007 B-phase
Pulse input Off 6V or less
Input 5.6 k input
Ch 0 Ch 0 On 20.4~28.8V
P0008
5.6 k Preset input Preset input Off 6V or less
Ch 1 On 20.4~28.8V
P0009 -
5.6 k Preset input Off 6V or less
Ch 2 Ch 2 On 20.4~28.8V
P000A
5.6 k Preset input Preset input Off 6V or less
Ch 3 On 20.4~28.8V
P000B -
5.6 k Preset input Off 6V or less
Ch 4 Ch 4 On 20.4~28.8V
P000C
Preset input Preset input Off 6V or less
5.6 k
Ch 5 On 20.4~28.8V
P000D -
5.6 k Preset input Off 6V or less
Ch 6 Ch 6 On 20.4~28.8V
P000E
5.6 k Preset input Preset input Off 6V or less
Ch 7 On 20.4~28.8V
P000F -
Preset input Off 6V or less
8-5
Chapter 8 Built-in High-speed Counter Function
Operation example
Count value 10 11 12 13 12 11 10 11
8-6
Chapter 8 Built-in High-speed Counter Function
Operation example
Count value 7 8 9 10 9 8 7 8
Increasing Decreasing Increasing
Operation example
Increasing Decreasing
8-7
Chapter 8 Built-in High-speed Counter Function
Operation example
7 8 9 10 11 10 9 8 7
Count value
Increasing Decreasing
8-8
Chapter 8 Built-in High-speed Counter Function
2 types of count can be selected for the applicable use based on functions.
A) Linear counter
Linear Count range: -2,147,483,648 ~ 2,147,483,647
If count value reaches the maximum value while increased, Carry will occur, and if count
value reaches the minimum value while decreased, Borrow will occur.
If Carry occurs, count stops and increasing is not available but decreasing is available.
If Borrow occurs, count stops and decreasing is not available but increasing is available.
+2,147,483,647
Decreasing Increasing
-2,147,483,648
Count start point
Borrow
Carry
B) Ring count
Ring Count range: user-defined minimum value ~ user-defined maximum value
Count display: If Ring Counted, user-defined minimum value of Ring Count is counted and
displayed, but the value is not displayed.
8-9
Chapter 8 Built-in High-speed Counter Function
Carry occurred
Ring Count
maximum value
Preset value
Present position :Not included
:Included
Ring Count
minimum value
Ring Count
maximum value
Present position
Preset value
:Not included
:Included
Ring Count
Minimum value (0)
Borrow occurred
(3) Operation when setting Ring Count based on present count value (during increasing
count)
If present count value exceeds user-defined range when setting Ring Count
- Error (code no. 27) is occurred and it operates linear counter.
If present count value is within user-defined range when setting Ring Count
- Present count value starts to increase up to the user-defined maximum value and
down to the user-defined minimum value and keeps counting after Carry occurs.
- Not the maximum but the minimum value only is displayed with count kept on as
shown below.
8-10
Chapter 8 Built-in High-speed Counter Function
Carry occurred
2,147,483,647
Carry occurred
Ring Count
maximum value
Present position
Ring Count
minimum value (0) :Not included
:Included
Present position
-2,147,483,648
If out of the user-defined If within the user-defined range
range
(4) Operation when setting Ring Count based on present count value (during decreasing count)
If present count value exceeds user-defined range when setting Ring Count
- Error (code no. 27) is occurred and it operates linear counter.
If present count value is within user-defined range when setting Ring Count
- Present count value starts to decrease down to the user-defined minimum value and up to
the user-defined maximum value and keeps counting after Borrow occurs.
2,147,483,647
Ring Count
maximum value Present position
Present
Ring Count position
minimum value Borrow occurred
:Not included
:Included
Borrow occurred
-2,147,483,648
If out of the user- If within the user-
defined range defined range
Remark
1. Based on count value within or out of user-defined range, count will be decided to be within or out
of the range when setting Ring Count.
2. Ring Count setting when count value is out of the range is regarded as users mistake. The count
is not available within the Ring Count range.
3. Use preset function or the like when using Ring Count so to surely position the count value within
the range.
8-11
Chapter 8 Built-in High-speed Counter Function
3) Compared output
(a) High Speed counter module has a compared output function used to compare present count
value with compared value in size to output as compared.
(b) Available compared outputs are 2 for 1 channel, which can be used separately.
(c) Compared output conditions are 7 associated with >, =, < .
(d) Parameter setting
Compared output mode setting
In order to make actual comparison enabled after compared output condition set, the
compared enable signal is to be On.
Area per channel
Classification Operation
Ch. 0 Ch. 1 Ch. 2 Ch. 3
Count enable signal K2600 K2700 K2800 K2900 0: N/A, 1: enable
8-12
Chapter 8 Built-in High-speed Counter Function
In order to make external output, the compared equivalent output signal (P20~P27) must be
set. If Compared output contact is Off, Compared coincidence output signal (internal device)
is only output.
Area per channel
Classification Operation
Ch. 0 Ch. 1 Ch. 2 Ch. 3
0: Compared output not
Compared equivalent equivalent
K2612 K2712 K2812 K2912
output signal 1: Compared output
equivalent
8-13
Chapter 8 Built-in High-speed Counter Function
Compared Output
Enable
Compared Output
output signal
External output
(in case of
designated output)
Compared Output
Enable
Compared Output
output signal
External output
(in case of
designated output)
8-14
Chapter 8 Built-in High-speed Counter Function
Compared Output
Enable
Compared Output
output signal
External output
(in case of
designated output)
Compared Output
123460
Min. set value
Compared Output
Enable
Compared Output
output signal
External output
(in case of
designated output)
8-15
Chapter 8 Built-in High-speed Counter Function
Compared Output
123459
Min. set value
Compared Output
Enable
Compared Output
signal
External output
(in case of
designated output)
F) Mode 5 (Compared output Min. set value Count value Compared output Max. set value)
If present count value is greater than or equal to compared output Min. value and less than
or equal to compared output Max. set value, output is sent out, and if count value
increases/decreases to exceed compared values range, output is not sent out.
Count value
123456 123457 123458 123459 123460 123461 123462
Compared Output
Min. set value
123458
Compared Output
Max. set value 123460
Compared Output
Enable
Compared Output
signal
External Output
(in case of
designated output)
8-16
Chapter 8 Built-in High-speed Counter Function
G) Mode 6 (Count value Compared output Min. value, Count value Compared output
Max. value)
If present count value is less than or equal to compared output Min. value and greater than
or equal to compared output Max. value, output is sent out, and if count value
increases/decreases to exceed compared values range, output is not sent out.
Count value
123456 123457 123458 123459 123460 123461 123462
Compared Output
Min. set value
123457
Compared Output
Max. set value 123461
Compared Output
Enable
Compared Output
output signal
External output
(in case of
designated output)
8-17
Chapter 8 Built-in High-speed Counter Function
4) Carry signal
A) Carry signal occurs
(1) When count range maximum value of 2,147,483,647 is reached during Linear Count.
(2) When user-defined maximum value of Ring Count changed to the minimum value during Ring
Count.
B) Count when Carry Signal occurs
(1) Count stops if Carry occurs during Linear Count.
(2) Count does not stop even if Carry occurs during Ring Count.
C) Carry reset
(1) The Carry generated can be cancelled by Carry/Borrow reset signal On.
5) Borrow signal
A) Borrow signal occurs
(1) When count range minimum value of -2,147,483,648 is reached during Linear Count.
(2) When user-defined minimum value of Ring Count changed to the maximum value during
Ring Count.
B) Count when Borrow signal occurs
(1) Count stops if Borrow occurs during Linear Count.
(2) Count does not stop even if Borrow occurs during Ring Count.
C) Borrow reset
(1) The Borrow generated can be cancelled by Carry/Borrow reset signal On..
8-18
Chapter 8 Built-in High-speed Counter Function
6) Revolution/Unit time
While auxiliary mode enable signal is On, it counts the number of input pulses for a specified time.
A) Setting
(1) Unit time setting
1) Input unit time and pulse number per 1 revolution
Setting value is saved at the following special K are and user can designate it directly.
Device area per channel
Classification
Channel 0 Channel 1 Channel 2 Channel 3
Unit time (1~60000)*3) K322 K352 K382 K412
*3)
If revolution per unit time is enabled and unit time value is other than 1~60000ms, error code
34 occurs.
2) Input pulse number per 1 revolution
Device area per channel
Classification
Channel 0 Channel 1 Channel 2 Channel 3
Pulse number /revolution
K323 K353 K383 K413
(1~60000)*4)
*4)
If revolution per unit time is enabled and pulse number/revolution is other than 1~60000,
error code 35 occurs.
3) If Count function of revolution per unit time is used, enable signal set by On.
Device area per channel
Classification
Channel 0 Channel 1 Channel 2 Channel 3
Revolution/unit time
K2605 K2705 K2805 K2905
command
B) Count function of Revolution per Unit time is used to count the number of pulses for a
specified time while Enable signal is On.
8-19
Chapter 8 Built-in High-speed Counter Function
C) With the displayed number of pulses updated for a specified time and the number of
pulses per revolution input, Revolution/Unit time can be counted.
D) Number of Revolution per 1 second is indicated after number of pulse per 1 revolution is
set and time is set to 1 second (1000ms). In order to indicate by Revolutions per minute
(RPM), the operation is executed in program.
E) The example that number of pulse per 1 revolution set to 1 and time is set to 1000 ms is
as shown below. (Ch0)
Command
1000
700
Count value
500 500
400
300 350
0
F) In order to indicate revolution per minute (RPM), the program is as shown below. In case
of DMUL operation, RPM value is saved 64 bit in D100~D103. If operated RPM value is
used, it can use to Word or Dword type according to system (case of RPM value is small
number).
8-20
Chapter 8 Built-in High-speed Counter Function
G) The example that number of pulse per 1 revolution set to 10 and time is set to 60,000 ms
is as shown below.
Command
1000
700
Count value
500 500
400
300 350
0
Revolution 30 10 30 20
per time
60000 60000 60000 60000
7) Count latch
(a) When Count latch signal is On, present count value is latched.
(b) Setting
If present counter value is to latch, Count Latch function is set Use.
Device area per channel
Classification
Channel 0 Channel 1 Channel 2 Channel 3
Count latch command K2606 K2706 K2806 K2906
Count latch function is operated when Count latch signal is On. Namely, counter value is not
cleared when power supply Off =>On and mode change, it is counted from previous value.
In latch counter function, internal or external preset function has to use for clearing present
value.
8-21
Chapter 8 Built-in High-speed Counter Function
8) Preset function
It changes the current value into preset value.
There are two types of preset function, internal preset and external preset. External preset is fixed
as input contact point.
Preset command is specified through the following special K area, external preset is used by
executing the designated input contact point after allowance bit is on.
Area per each channel (Bit)
Type Ref.
Ch.0 Ch.1 Ch.2 Ch.3
Internal preset
K2601 K2701 K2801 K2901 -
command
External preset
K2602 K2702 K2802 K2902 -
allowance
External preset
P008 P009 P00A P00B -
command
8-22
Chapter 8 Built-in High-speed Counter Function
Operation example
Count value 10 11 12 13 12 11 10 11
8-23
Chapter 8 Built-in High-speed Counter Function
Operation example
Count value 7 8 9 10 9 8 7 8
Increasing Decreasing Increasing
Operation example
Increasing Decreasing
8-24
Chapter 8 Built-in High-speed Counter Function
Operation example
7 8 9 10 11 10 9 8 7
Count value
Increasing Decreasing
2) Counter mode
2 types of count (Linear counter, Ring counter) can be selected for the applicable use based on
functions.
8-25
Chapter 8 Built-in High-speed Counter Function
A) Linear counter
Linear Count range: -2,147,483,648 ~ 2,147,483,647
If count value reaches the maximum value while increased, Carry will occur, and if count
value reaches the minimum value while decreased, Borrow will occur.
If Carry occurs, count stops and increasing is not available but decreasing is available.
If Borrow occurs, count stops and decreasing is not available but increasing is available.
+2,147,483,647
Decreasing Increasing
-2,147,483,648
Count start point
Borrow
Carry
B) Ring count
Set Ring Counter Min. Value and Max. value. Preset value and compared set value should
be in range of ring counter min. value and max. value.
Ring counter max. and min value is saved at the following special K area.
Area per each channel (Double word)
type Ref.
Ch.0 Ch.1 Ch.2 Ch.3 Ch.4 Ch.5 Ch.6 Ch.7
Ring counter
K308 K338 K368 K398 K2228 K2258 K2288 K2318 -
min. value
Ring counter
K310 K340 K270 K400 K2230 K2260 K2290 K2320 -
max. value
8-26
Chapter 8 Built-in High-speed Counter Function
Range of Ring counter: user defined min. value ~ user defined max. value
Counter display: in case of using ring counter, user defined max. value is not displayed.
a. During increasing count
Even if count value exceeds user-defined maximum value during increasing count,
Carry only occurs and count does not stop differently to Linear Count.
Carry occurred
Ring Count
maximum value
Preset value
Present position :Not included
:Included
Ring Count
minimum value
Ring Count
maximum value
Present position
Preset value
:Not included
:Included
Ring Count
Minimum value (0)
Borrow occurred
c. Operation when setting Ring Count based on present count value (during increasing
count)
If present count value exceeds user-defined range when setting Ring Count
- Error (code no. 27) is occurred and it operates linear counter.
If present count value is within user-defined range when setting Ring Count
- Present count value starts to increase up to the user-defined maximum value and
down to the user-defined minimum value and keeps counting after Carry occurs.
- Not the maximum but the minimum value only is displayed with count kept on as
shown below.
8-27
Chapter 8 Built-in High-speed Counter Function
Carry occurred
2,147,483,647
Carry occurred
Ring Count
maximum value
Present position
Ring Count
minimum value (0) :Not included
:Included
Present position
-2,147,483,648
If out of the user-defined If within the user-defined range
range
d. Operation when setting Ring Count based on present count value (during decreasing count)
If present count value exceeds user-defined range when setting Ring Count
- Error (code no. 27) is occurred and it operates linear counter.
If present count value is within user-defined range when setting Ring Count
- Present count value starts to decrease down to the user-defined minimum value and up to
the user-defined maximum value and keeps counting after Borrow occurs.
2,147,483,647
Ring Count
maximum value Present position
Remark
1. Based on count value within or out of user-defined range, count will be decided to be within or out
of the range when setting Ring Count.
2. Ring Count setting when count value is out of the range is regarded as users mistake. The count
is not available within the Ring Count range.
3. Use preset function or the like when using Ring Count so to surely position the count value within
the range.
8-28
Chapter 8 Built-in High-speed Counter Function
8-29
Chapter 8 Built-in High-speed Counter Function
In order to output the compared output signal, compared output enable flag set to 1 after
compared output condition set.
Area per channel
Classification Operation
Ch. 0 Ch. 1 Ch. 2 Ch. 3 Ch. 4 Ch. 5 Ch. 6 Ch. 7
Count enable 0:disable, 1:
K2600 K2700 K2800 K2900 K21800 K21900 K22000 K22100
signal enable
Compared 0 0: disable, 1:
K2604 K2704 K2804 K2904 K21804 K21904 K22004 K22104
enable signal enable
Compared 1 0: disable, 1:
K2607 K2707 K2807 K2907 K21807 K21907 K22007 K22107
enable signal enable
In order to make external output, the compared coincidence output signal (P20~P2F) must
be set. If Compared output contact is Off at Special Module Parameter Setting of XG5000,
Compared coincidence output signal (internal device) is only output.
Area per channel
Classification Operation
Ch. 0 Ch. 1 Ch. 2 Ch.4 Ch.5 Ch. 6 Ch.7
Compared coincidence 0: Compared output Off
K2612 K2712 K2812 K2912 K21812 K22012 K22112
output signal 0 1: Compared output On
Compared coincidence 0: Compared output Off
K2613 K2713 K2813 K2913 K21813 K22013 K22113
output signal 1 1: Compared output On
8-30
Chapter 8 Built-in High-speed Counter Function
Compared output 0
Enable
Compared output 0
Output Signal
External output
(in case of
designated output)
Compared Output 0
Enable
Compared Output 0
output signal
External output
(in case of
designated output)
8-31
Chapter 8 Built-in High-speed Counter Function
Compared Output 0
Enable
Compared Output 0
output signal
External output
(in case of designated output)
Compared Output 0
Enable
Compared Output 0
output signal
External output
(in case of designated output)
8-32
Chapter 8 Built-in High-speed Counter Function
Compared Output 0
output Enable
Compared Output 0
output signal
External output
(in case of designated output)
F) Mode 5
(Section comparison: Min. set value of Compared Output 0 Count value Max. set value
of Compared Output 0)
If present count value is greater than or equal to the minimum set value of compared
output 0 and less than or equal to the maximum set value of compared output 0, output is
sent out, and if count value increases/decreases to exceed compared values range,
output is not sent out.
Compared Output 0
output Enable
Compared Output 0
output signal
External output
(in case of designated output)
8-33
Chapter 8 Built-in High-speed Counter Function
G) Mode 6 (Count value Min. set value of Compared Output 0 or Count value Max. set
value of Compared Output 0)
If present count value is less than or equal to the minimum set value of compared 0 and
greater than or equal to the maximum set value of compared 0, output is sent out, and if
count value increases/decreases to exceed compared values range, output is not sent out.
Compared Output 0
output signal
External output
(in case of designated
8-34
Chapter 8 Built-in High-speed Counter Function
4) Carry signal
A) Carry signal occurs
(1) When count range maximum value of 2,147,483,647 is reached during Linear Count.
(2) When user-defined maximum value of Ring Count changed to the minimum value during Ring
Count.
B) Count when Carry Signal occurs
(1) Count stops if Carry occurs during Linear Count.
(2) Count does not stop even if Carry occurs during Ring Count.
C) Carry reset
(1) The Carry generated can be cancelled by Carry/Borrow reset signal On.
5) Borrow signal
A) Borrow signal occurs
(1) When count range minimum value of -2,147,483,648 is reached during Linear Count.
(2) When user-defined minimum value of Ring Count changed to the maximum value during
Ring Count.
B) Count when Borrow signal occurs
(1) Count stops if Borrow occurs during Linear Count.
(2) Count does not stop even if Borrow occurs during Ring Count.
C) Borrow reset
(1) The Borrow generated can be cancelled by Carry/Borrow reset signal On.
8-35
Chapter 8 Built-in High-speed Counter Function
6) Revolution/Unit time
While the Flag about the number of revolution per unit time is On, it counts the number of input
pulses for a specified time.
A) Setting
(1) Unit time setting
1) Set the unit time and the number of pulse per 1 revolution.
Setting value is saved at the following special K area and user can designate directly.
2) In case of using Rev/unit time function, enable the following special K area
Device per each channel (Word)
Class Operation
Ch.0 Ch.1 Ch.2 Ch.3 Ch.4 Ch.5 Ch.6 Ch.7
Rev/unit
0: disable
time K2605 K2705 K2805 K2905 K21805 K21905 K22005 K22105
1: enable
command
8-36
Chapter 8 Built-in High-speed Counter Function
B) Count function of Revolution/Unit time is used to count the number of pulses for a
specified time while auxiliary mode enable signal is On.
C) With the displayed number of pulses updated for a specified time and the number of
pulses per revolution input, Revolution/Unit time can be counted.
D) Number of Revolution per 1 second is indicated after number of pulse per 1 revolution is
set and time is set to 1 second (1000ms). In order to indicate by Revolutions per minute
(RPM), the operation is executed in program.
E) The example that number of pulse per 1 revolution set to 1 and time is set to 1000 ms is
as shown below. (Ch0)
Command
1000
700
Count value
500 500
400
300 350
0
F) In order to indicate revolution per minute (RPM), the program is as shown below. In case
of DMUL operation, RPM value is saved 64 bit in D100~D103. If operated RPM value is
used, it can use to Word or Dword type according to system (case of RPM value is small
number).
8-37
Chapter 8 Built-in High-speed Counter Function
G) The example that number of pulse per 1 revolution set to 10 and time is set to 60,000 ms
is as shown below.
Command
1000
700
Count value
500 500
400
300 350
0
Revolution 10 30 20 15
per time
60000 60000 60000 60000
7) Count latch
Count latch function is operated when Count latch signal is On. Namely, counter value is not
cleared when power supply Off =>On and mode change, it is counted from previous value.
In latch counter function, internal or external preset function has to use for clearing present
value.
8-38
Chapter 8 Built-in High-speed Counter Function
8) Preset function
It changes the current value into preset value.
There are two types of preset function, internal preset and external preset. External preset is fixed
as input contact point.
Preset command is specified through the following special K area, external preset is used by
executing the designated input contact point after allowance bit is on.
Area per each channel (Bit)
Type Ref.
Ch.0 Ch.1 Ch.2 Ch.3 Ch.4 Ch.5 Ch.6 Ch.7
Internal
preset K2601 K2701 K2801 K2901 K21801 K21901 K22001 K22101 -
command
External
preset K2602 K2702 K2802 K2902 K21802 K21902 K22002 K22102 -
allowance
External
preset P008 P009 P00A P00B P00C P00D P00E P00F -
command
8-39
Chapter 8 Built-in High-speed Counter Function
24V
Pulse Generator
CHSC
COM
24V
8-40
Chapter 8 Built-in High-speed Counter Function
8-41
Chapter 8 Built-in High-speed Counter Function
(1) S type
(a) Parameter setting
Internal
preset value -2,147,483,648 ~ 2,147,483,647 K304 K334 K364 K394 DWord
setting
External
preset value -2,147,483,648 ~ 2,147,483,647 K306 K336 K366 K396 DWord
setting
8-42
Chapter 8 Built-in High-speed Counter Function
1 ~ 60,000 DWord
Pulse/Rev.value K323 K353 K383 K413
8-43
Chapter 8 Built-in High-speed Counter Function
8-44
Chapter 8 Built-in High-speed Counter Function
(2) H type
(a) Parameter setting
h0001 (Magnitude)
Comp. K302 K332 K362 K392
h0002 (Magnitude) =
Output 0
h0003 (Magnitude) Word
mode
h0004 (Magnitude) >
setting
h0005 (Range) Include K2222 K2252 K2282 K2312
h0006 (Range) Exclude
h0000 (Magnitude) <
h0001 (Magnitude)
Comp. K303 K333 K363 K393
h0002 (Magnitude) =
Output 1
h0003 (Magnitude) Word
mode
h0004 (Magnitude) >
setting
h0005 (Range) Include K2223 K2253 K2283 K2313
h0006 (Range) Exclude
Internal K304 K334 K364 K394
preset value -2,147,483,648 ~ 2,147,483,647 DWord
K2224 K2254 K2284 K2314
setting
External K306 K336 K366 K396
preset value -2,147,483,648 ~ 2,147,483,647 DWord
K2226 K2256 K2286 K2316
setting
8-45
Chapter 8 Built-in High-speed Counter Function
8-46
Chapter 8 Built-in High-speed Counter Function
8-47
Chapter 8 Built-in High-speed Counter Function
Comp. output 0 enabling K2604 K2704 K2804 K2904 K21804 K21904 K22004 K22104
Comp. output 1 enabling K2607 K2707 K2807 K2907 K21807 K21907 K22007 K22107
Enabling of revolution time
K2605 K2705 K2805 K2905 K21805 K21905 K22005 K22105
per unit time
Designation of latch
K2606 K2706 K2806 K2906 K21806 K21906 K22006 K22100
counter
Carry signal (Bit) K2610 K2710 K2810 K29100 K21810 K21910 K22010 K22110
Borrow signal K2611 K2711 K2811 K29101 K21811 K21911 K22011 K22111
Comp. output 0 signal K2612 K2712 K2812 K29102 K21812 K21912 K22012 K22112
Comp. output 1 signal K2613 K2713 K2813 K29103 K21813 K21913 K22013 K22113
Current counter value K262 K272 K282 K292 K2182 K2192 K2202 K2212
Revolution per unit time K264 K274 K284 K294 K2184 K2194 K2204 K2214
8-48
Chapter 8 Built-in High-speed Counter Function
Remark
If two and more errors occur, the module saves the latter error code and removes
the former one.
8-49
Chapter 8 Built-in High-speed Counter Function
B) Selecting high-speed counter opens a window to set high-speed counter parameters as follows.
For details regarding each parameter setting, refer to 8.1~8.3.
(Every parameter settings are saved in the special K device area.)
8-50
Chapter 8 Built-in High-speed Counter Function
D) To use additional functions of the high-speed counter, you needs to turn on the flag allowing
an operation command.
* Refer to 2. Operation Command, <8.3.1 Special K Area for High-speed Counter>
For instance, turn on 2605 bit if among additional functions, rotation number function is used.
8-51
Chapter 8 Built-in High-speed Counter Function
8-52
Chapter 8 Built-in High-speed Counter Function
Item Description
FLAG Monitor Show flag monitoring and command window of high-speed counter
Start Monitoring Start monitoring each item (special K device area monitor).
Write each item setting to PLC.
Test
(Write the setting to special K device)
Close Close monitor
8-53
Chapter 8 Built-in High-speed Counter Function
C) Clicking Start Monitoringshows the high-speed counter monitor display, in which you
may set each parameter. At this moment, if any, changed values are not saved if power off=>
on or mode is changed.
D) ClickingFLAG Monitor shows the monitor of each flag in high-speed counter, in which
you may direct operation commands by flags (clicking commands reverse turn).
8-54
Chapter 9 Installation and Wiring
Danger
Please design protection circuit at the external of PLC for entire system to operate safely because an
abnormal output or an malfunction may cause accident when any error of external power or malfunction
of PLC module.
(1) It should be installed at the external side of PLC to emergency stop circuit, protection circuit,
interlock circuit of opposition action such as forward /reverse operation and interlock circuit for
protecting machine damage such as upper/lower limit of positioning.
(2) If PLC detects the following error, all operation stops and all output is off.
(Available to hold output according to parameter setting)
(a) When over current protection equipment or over voltage protection operates
(b) When self diagnosis function error such as WDT error in PLC CPU occurs
In case of error about IO control part that is not detected by PLC CPU, all output is off.
Design Fail Safe circuit at the external of PLC for machine to operate safely. Refer to 10.2 Fail Safe
circuit.
(1) Because of error of output device, Relay, TR, etc., output may not be normal. About output signal that
may cause the heavy accident, design supervisory circuit to external.
In case load current more than rating or over current by load short flows continuously, danger of heat, fire
may occur so design safety circuit to external such as fuse.
Design for external power supply to be done first after PLC power supply is done. If external power
supply is done first, it may cause accident by misoutput, misoperation.
In case communication error occurs, for operation status of each station, refer to each communication
manual.
In case of controlling the PLC while peripheral is connected to CPU module, configure the interlock circuit
for system to operate safely. During operation, in case of executing program change, operation status
change, familiarize the manual and check the safety status. Especially, in case of controlling long
distance PLC, user may not response to error of PLC promptly because of communication error or etc.
Limit how to take action in case of data communication error between PLC CPU and external device
adding installing interlock circuit at the PLC program.
9 1
Chapter 9 Installation and Wiring
Danger
Dont close the control line or communication cable to main circuit or power line. Distance should be more
than 100mm. It may cause malfunction by noise.
In case of controlling lamp load, heater, solenoid valve, etc. in case of Off -> On, large current (10 times of
normal current) may flows, so consider changing the module to module that has margin at rated current.
Process output may not work properly according to difference of delay of PLC main power and external
power for process (especially DC in case of PLC power On-Off and of start time.
For example, in case of turning on PLC main power after supplying external power for process, DC output
module may malfunction when PLC is on, so configure the circuit to turn on the PLC main power first
Or in case of external power error or PLC error, it may cause the malfunction.
Not to lead above error to entire system, part causing breakdown of machine or accident should be
configured at the external of PLC
9 2
Chapter 9 Installation and Wiring
(1) example of system design (In case of not using ERR contact point of power module)
In case of AC In case of AC . DC
Power
Power
F0045 DC power
F0045
(2) ( ERR ) Pm
Pm Fuse
F009C
F009C Pm Timer setting
Pm which DC input
Start
PLC RUN output Pm
switch Program
Start available as Tm signal is
RA1 configured.
Stop
SW Input module
Start Program
switch
device ()
(a) PLC
Emergency stop,
Output module Output module Output for warning
Stop by limit (Lamp or buzzer)
Run by F009C
Configure part that
lead opposite operation
or breakdown such as Output module
interlock circuit
forward, reverse
revolution by external Power Off to
interlock circuit output device
(Emergency
stop,
Start sequence of power stop by limit
In case of AC switch)
(1) Turn on power
(2) Run CPU.
(3) Turn on start switch
(4) Output device runs by program through Start sequence of power
magnetic contactor (MC) [On] In case of AC DC
Run CPU after power is on
(1) Turn on RA2 as DC power on
(2) Turn on timer after DC power is stable.
(3) Turn on start switch
(4) Output device runs by program through
magnetic contactor (MC) [On]
9 3
Chapter 9 Installation and Wiring
(2) System design circuit example (In case of using ERR contact point of power module)
Power
Pm
Start stop circuit F009C Fuse
Pm Timer setting
PLC RUN output Pm which DC input
Available to start as Tm signal is
RA1 Tm configured.
Start Program
SW
Pn
Stop by ERR
ERR
RA3
Error Off
Output module
9 4
Chapter 9 Installation and Wiring
System example
- +
0.5s 0.5s 0V
DC24
T1 T2
CPU unit MC
Output module
Since P80 turn on/off every 0.5s, use TR output.
9 5
Chapter 9 Installation and Wiring
(d) Average power consumption by output voltage drop of the output module(power consumption of
simultaneous On point)
Wout = Iout X Vdrop X output point X simultaneous On rate (W)
Iout : output current (actually used current) (A)
Vdrop: voltage drop of each output module (V)
I24V
DC24V
Voltage
load
AC power
DC 100V~240V
power
24V
9 6
Chapter 9 Installation and Wiring
The calculation of temperature rise within the control panel is displayed as follows.
T = W / UA [C]
W : power consumption of the entire PLC system (the above calculated value)
A : surface area of control panel [m2]
U : if equalizing the temperature of the control panel by using a fan and others - - - 6
If the air inside the panel is not ventilated - - - - - - - - - - 4
If installing the PLC in an air-tight control panel, it needs heat-protective(control) design considering the
heat from the PLC as well as other devices. If ventilating by vent or fan, inflow of dust or gas may affect
the performance of the PLC system.
9 7
Chapter 9 Installation and Wiring
Caution in handling
Use PLC in the range of general specification specified by manual.
In case of using out of range, it may cause electric shock, fire, malfunction, damage of product.
Warning
Module must be mounted to hook for fixation properly before its fixation. The module may be damaged
from over-applied force. If module is not mounted properly, it may cause malfunction.
9 8
Chapter 9 Installation and Wiring
Get up the hook for fixation of upper part and lower part and disconnect it.
Detach the module with two hands. (Dont force over-applied force.)
Caution
When separating module, dont force over-applied power. If so, hook may be damaged.
9 9
Chapter 9 Installation and Wiring
Panel
9 10
Chapter 9 Installation and Wiring
*1
30 or above
Panel
PLC
20 or above*3
*1
30 or above
5 or above*1 5 or above
*1 : In case height of wiring duct is less than 50 mm (except this 40mm or above)
*2 : In case of equipping cable without removing near module, 20mm or above
*3 : In case of connector type, 80mm or above
9 11
Chapter 9 Installation and Wiring
To avoid radiation noise or heat, keep the distance between PLC and device (connector and relay) as far as the
following figure.
Device installed in front of PLC: 100 or above
Device installed beside PLC: 50 or above
100mm or above
50mm or above
50mm or above
9 12
Chapter 9 Installation and Wiring
(c) Environment
In case of wiring IO module, if device or material that induce high heat is too close or oil contacts wire
too long time, it may cause short, malfunction or error.
(d) Polarity
Before supplying power of module which has terminal block, check the polarity.
(e) Wiring
In case of wiring IO with high voltage line or power line, induced obstacle may cause error.
Let no cable pass the IO operation indication part (LED).
(You cant discriminate the IO indication.)
In case induced load is connected with output module, connect the surge killer or diode load to load
in parallel. Connect cathode of diode to + side of power.
Induced load
OUT
Output module
Surge killer
COM
+
Output module
-
Diode
COM
(g) Dont impact to IO module or dont disassemble the PCB from case.
9 13
Chapter 9 Installation and Wiring
9.3 Wire
Danger
When wiring, cut off the external power.
If all power is cut, it may cause electric shock or damage of product.
In case of flowing electric or testing after wiring, equip terminal cover included in product. It not, it may cause
electric shock.
Caution
Do D type ground (type 3 ground) or above dedicated for PLC for FG and LG terminal. It may cause electric
shock or malfunction.
When wiring module, check the rated voltage and terminal array and do properly.
If rating is different, it may cause fire, malfunction.
For external connecting connector, use designated device and solder.
If connecting is not safe, it may cause short, fire, malfunction.
For screwing, use designated torque range. If it is not fit, it may cause short, fire, malfunction.
Let no foreign material enter such as garbage or disconnection part into module. It may cause fire, malfunction,
error.
9.3.1Power wiring
(1) In case voltage regulation is larger than specified, connect constant voltage transformer.
BA BA
In:24V D C , 7m A 20 20
19 19
00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0F 18 18
17 17
16 16
10 11 12 13 14 15 16 17 18 19 1A 1B 1C 1D 1E 1F 15 15
XBC- DR64H IN 14 14
13 13
PWR 12 12
O UT 11 11
RUN 20 21 22 23 24 25 26 27 28 29 2A 2B 2C 2D 2E 2F RS-232C
10 10
ERR 09 09
08 08
AC power
30 31 32 33 34 35 36 37 38 39 3A 3B 3C 3D 3E 3F
07 07
1 85VA 50/60H z 06 06
05 05
04 04
100V~240V
03 03
02 02
01 01
AC power AC100-240V
Constant
voltage
transformer
(2) Connect noise that include small noise between line and earth.
(When there are many noise, connect insulated transformer.)
9 14
Chapter 9 Installation and Wiring
(3) Isolate the PLC power, I/O devices and power devices as follows.
Main unit
Main PLC
power power Constant
AC220V Voltage
Transformer AC100-240V
IO power
(a) Do not connect DC24V of several power modules in parallel. It may cause the destruction of a module.
(b) If a power module can not meet the DC24V output capacity, supply DC24V externally as presented
below.
24V 24V I
I
O
CPU CPU
O
DC 24V
24V
I
CPU Power
O
Supply
(5) AC110V/AC220V/DC24V cables should be compactly twisted and connected in the shortest distance.
(7) AC110V/ DC24V cables should not be installed close to main circuit cable(high voltage/high current) and I/O
signal cable. They should be 100mm away from such cables
9 15
Chapter 9 Installation and Wiring
(8) To prevent surge from lightning, use the lightning surge absorber as presented below.
PLC
I/O device
E1 E2
Note
(1) Isolate the grounding(E1) of lightning surge absorber from the grounding(E2) of the PLC.
(2) Select a lightning surge absorber type so that the max. voltage may not the specified
allowable voltage of the absorber.
(9) When noise may be intruded inside it, use an insulated shielding transformer or noise filter.
(10) Wiring of each input power should be twisted as short as possible and the wiring of shielding transformer or
noise filter should not be arranged via a duct.
9 16
Chapter 9 Installation and Wiring
(1) The size of I/O device cable is limited to 0.3~2 mm2 but it is recommended to select a size(0.3 mm2) to use
conveniently.
(2) Please isolate input signal line from output signal line.
(3) I/O signal lines should be wired 100mm and more away from high voltage/high current main circuit cable.
(4) Batch shield cable should be used and the PLC side should be grounded unless the main circuit cable and
power cable can not be isolated.
input
RA
output
DC
(5) When applying pipe-wiring, make sure to firmly ground the piping.
(1) The PLC contains a proper noise measure, so it can be used without any separate grounding if there is a
large noise. However, if grounding is required, please refer to the followings.
(2) For grounding, please make sure to use the exclusive grounding.
For grounding construction, apply type 3 grounding(grounding resistance lower than 100 )
(3) If the exclusive grounding is not possible, use the common grounding as presented in B) of the figure below.
(4) Use the grounding cable more than 2 mm2. To shorten the length of the grounding cable, place the grounding
point as close to the PLC as possible.
(5) If any malfunction from grounding is detected, separate the FG of the base from the grounding.
9 17
Chapter 9 Installation and Wiring
9 18
Chapter 10 Maintenance
Chapter 10 Maintenance
Be sure to perform daily and periodic maintenance and inspection in order to maintain the PLC in the best
conditions.
Run LED Check that the LED is On during Run. On (flickering indicates an error) See chapter 5.
LED ERR LED Check that the LED is Off during Run. Off(On indicates an error) See chapter 5.
indicator On when input is On,
Input LED Check that the LED turns On and Off. See chapter 5.
Off when input is off.
On when output is On,
Output LED Check that the LED turns On and Off See chapter 5.
Off when output is off
101
Chapter 10 Maintenance
Corrective
Check Items Checking Methods Judgment
Actions
Ambient
0 ~ 55 C Adjust to general
temperature -. Measure with thermometer
Ambient standard
Ambient Humidity and hygrometer 5 ~ 95%RH (Internal environmental
environment
-. measure corrosive gas There should be no standard of control
Ambient pollution
section)
level corrosive gases
Looseness, The module should be move The module should be
PLC Ingress the unit mounted securely.
Retighten screws
Conditions dust or foreign
Visual check No dust or foreign material
material
Loose terminal
Re-tighten screws Screws should not be loose Retighten
screws
Distance between
Connecting Visual check Proper clearance Correct
terminals
conditions
Retighten connector
Connectors should not be
Loose connectors Visual check mounting
loose.
screws
Measure voltage between
Line voltage check DC24V: DC20.4 ~ 28.8V Change supply power
input terminals
102
Chapter 11 Troubleshooting
Chapter 11 Troubleshooting
The following explains contents, diagnosis and corrective actions for various errors that can occur during system
operation.
1) Visual checks
Check the following points.
Machine operating condition (in stop and operation status)
Power On/Off
Status of I/O devices
Condition of wiring (I/O wires, extension and communications cables)
Display states of various indicators (such as POWER LED, RUN LED, ERR LED and I/O LED)
After checking them, connect peripheral devices and check the operation status of the PLC and the
program contents.
2) Trouble Check
Observe any change in the error conditions during the following.
Switch to the STOP position, and then turn the power on and off.
3) Narrow down the possible causes of the trouble where the fault lies, i.e.:
Inside or outside of the PLC ?
I/O module or another module?
PLC program?
11.2 Troubleshooting
This section explains the procedure for determining the cause of troubles as well as the errors and corrective
actions.
Symptoms
Is the power LED turned Flowchart used when the POWER LED is turned Off.
Off ?
Is the ERR LED flickering ? Flowchart used when the ERR LED is flickering.
Are the RUN LED turned Flowchart used when the RUN turned Off.
Off ?
I/O module doesnt operate Flowchart used when the output load of the output module
properly. doesnt turn on.
Program cannot be written. Flowchart used when a program cant be written to the
PLC.
11-1
Chapter 11 Troubleshooting
11.2.1 Troubleshooting flowchart used when the PWR (Power) LED turns Off.
The following flowchart explains corrective action procedure used when the power is supplied or the power LED
turns Off during operation.
No Yes
Yes Does the power LED
turns On?
No
Is the voltage within the Supply the power
rated power? properly.
Yes
Yes Yes
Does the power LED
turns On?
No
No Yes
Does the power LED
turns On?
Complete
11-2
Chapter 11 Troubleshooting
11.2.2 Troubleshooting flowchart used with when the ERR (Error) LED is flickering
The following flowchart explains corrective action procedure use when the power is supplied star
ts or the ERR LED is flickering during operation.
No
See Appendix 1 Flag list
Warning error?
and remove the cause of
the error.
Yes
No
Is ERR LED still
flicking ?
Complete
Yes
Warning
Though warning error appears, PLC system doesnt stop but corrective action is needed
promptly. If not, it may cause the system failure.
11-3
Chapter 11 Troubleshooting
11.2.3 Troubleshooting flowchart used with when the RUN , STOP LED turns Off.
The following flowchart explains corrective action procedure to treat the lights-out of RUN LED when the power
is supplied, operation starts or operation is in the process.
No
Is RUN/ STOP LED Off?
Yes
11-4
Chapter 11 Troubleshooting
11.2.4 Troubleshooting flowchart used when the I/O part doesnt operate normally.
The following flowchart explains corrective action procedure used when the I/O module doesnt
operate normally.
No
I\s the output LED of SOL1
On?
Yes
Measure the voltage of terminal Correct wiring. Replace the connector of Check the status of SOL1 by
in SOL1 by Tester. the terminal block.
XG5000.
No No
No
Yes Is the Yes Is it normal condition?
Is the measured value Is the output
terminal connector
normal? wiring correct? appropriate?
Yes
Yes
Yes
Separate the external
wiring than check the
condition of output module.
Continue
Yes No
Is it normal condition?
11-5
Chapter 11 Troubleshooting
Continue
No
Are the indicator LED of the
switch 1 and 2 on?
Yes
Is the
Yes
Is the measured value Is the measured value terminal screw tighten
normal? normal? securely?
No No
Yes No Yes
Input unit replacement Check the status of the switch 1 Input unit replacement is
is Needed. and 2. Check from the beginning. Needed.
11-6
Chapter 11 Troubleshooting
When problems have been met during operation of the XGC series, please write down this Questionnaires and
contact the service center via telephone or facsimile.
y For errors relating to special or communication modules, use the questionnaire included in the Users manual
of the unit.
11-7
Chapter 11 Troubleshooting
~ ~
External device External device
Input signal Leakage current of external device (Drive by y Connect an appropriate register, which will make
doesnt turn switch with LED indicator) the voltage higher than the OFF voltage across the
off.
input module terminal and common terminal.
DC input
DC input
Leakage current
R R
External device
Input signal y Sneak current due to the use of two y Use only one power supply.
y Connect a sneak current prevention diode.
doesnt turn different power supplies.
off.
DC input
DC input
E E1
L L
E E
11-8
Chapter 11 Troubleshooting
When the output yLoad is half-wave rectified inside (in some y Connect registers of tens to hundreds K
is off, excessive cases, it is true of a solenoid) across the load in parallel.
voltage is yWhen the polarity of the power supply is as
applied to the shown in , C is charged. When the polarity is R
Load Load
When the load y Leakage current by surge absorbing circuit, y Drive the relay using a contact and drive the
is C-R type which is connected to output element in parallel. C-R type timer using the since contact.
timer, time y Use other timer than the CR contact some
Output
constant timers have half-ware rectified internal circuits
Load
fluctuates. C therefore, be cautious. Timer
~ T
R Leakage current
Output X
~
The load does y Sneak current due to the use of two different y Use only one power supply.
not turn off. power supplies. y Connect a sneak current prevention diode.
Output Output
Load
Load
E1 E
E2 E
11-9
Chapter 11 Troubleshooting
Outpu
Off current
Loa
Loa
E
E1 R E
turned on.
Output
11-10
Chapter 11 Troubleshooting
11-11
Chapter 11 Troubleshooting
11-12
Appendix 1 Flag List
App. 1-1
Appendix 1 Flag List
App. 1-2
Appendix 1 Flag List
App. 1-4
Appendix 1 Flag List
App. 1-4
Appendix 1 Flag List
App. 1-6
Appendix 1 Flag List
1. High-speed Link 1
App. 1-6
Appendix 1 Flag List
2. High-speed Link2
App. 1-7
Appendix 1 Flag List
3. Common area
App. 1-9
Appendix 1 Flag List
N0000~0004 _P1B00RD1 Word Saves area device 1 to read P2P parameter 1, 01 block.
N005 _P1B00RS1 Word Saves area size 1 to read P2P parameter 1, 01 block.
N0006~0009 _P1B00RD2 Word Saves area device 2 to read P2P parameter 1, 01 block.
N010 _P1B00RS2 Word Saves area size 2 to read P2P parameter 1, 01 block.
N0011~0014 _P1B00RD3 Word Saves area device 3 to read P2P parameter 1, 01 block.
N015 _P1B00RS3 Word Saves area size 3 to read P2P parameter 1, 01 block.
N0016~0019 _P1B00RD4 Word Saves area device 4 to read P2P parameter 1, 01 block.
N020 _P1B00RS4 Word Saves area size 4 to read P2P parameter 1, 01 block.
N0021~0024 _P1B00WD1 Word Saves area device 1 to save P2P parameter 1, 01 block.
N025 _P1B00WS1 Word Saves area size 1 to save P2P parameter 1, 01 block.
N0026~0029 _P1B00WD2 Word Saves area device 2 to save P2P parameter 1, 01 block.
N030 _P1B00WS2 Word Saves area size 2 to save P2P parameter 1, 01 block.
N0031~0034 _P1B00WD3 Word Saves area device 3 to save P2P parameter 1, 01 block.
N035 _P1B00WS3 Word Saves area size 3 to save P2P parameter 1, 01 block.
N0036~0039 _P1B00WD4 Word Saves area device 4 to save P2P parameter 1, 01 block.
N040 _P1B00WS4 Word Saves area size 4 to save P2P parameter 1, 01 block.
Remark
App. 1-9
Appendix 2 Dimension
XBM-DN16S
PWR
RUN
ERR
RS-232C
RUN
P00~07 P20~27
-. XBM-DR16S
XBM-DR16S
PWR
RUN
ERR
RS-232C
RUN
P00~07 P20~27
App.2
Appendix 2 Dimension
-. XBC-DR32H (/DC)
App.2
Appendix 2 Dimension
-. XBC-DN64H (/DC)
-. XBC-DR64H (/DC)
App.2
Appendix 2 Dimension
B A
20
19
18
17
16
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
-. XBE-RY16A
App.2
Appendix 2 Dimension
-. XBE-DR16A, XBE-RY08A
App.2
Appendix 3 Compatibility with MASTER-K (Special Relay)
MASTER-K XGB
App. 3-1
Appendix 3 Compatibility with MASTER-K (Special Relay)
MASTER-K XGB
App. 3-2
Appendix 3 Compatibility with MASTER-K (Special Relay)
MASTER-K XGB
- F0098 N/A
App. 3-3
Appendix 3 Compatibility with MASTER-K (Special Relay)
MASTER-K XGB
App. 3-4
Appendix 3 Compatibility with MASTER-K (Special Relay)
MASTER-K XGB
F0500~ F050F Max. Scan time _SCAN_MAX F0500~ F050F Max. Scan time
F0510~ F051F Min. Scan time _SCAN_MIN F0510~ F051F Min. Scan time
F0520~ F052F Current Scan time _SCAN_CUR F0520~ F052F Current Scan time
Clock data
F0530~ F053F _YEAR_MON F0530~ F053F Clock data (year/month)
(year/month)
F0540~ F054F Clock data (day/hr) _DAY_TIME F0540~ F054F Clock data(day/hr)
F0550~ F055F Clock data (min/sec) _MIN_SEC F0550~ F055F Clock data(min/sec)
Clock data
F0560~ F056F _HUND_WK F0560~ F056F Clock data(100year/weekday)
(100year/weekday)
_FPU_LFlag_I F0570 -
_FPU_LFlag_U F0571 -
_FPU_LFlag_O F0572 -
_FPU_LFlag_Z F0573 -
_FPU_LFlag_V F0574 -
_FPU_Flag_U F057B -
_FPU_Flag_O F057C -
_FPU_Flag_Z F057D -
_FPU_Flag_V F057E -
_FPU_Flag_E F057F -
App. 3-5
Appendix 4 Instruction List
App. 4-1
Appendix 4 Instruction List
A
OR LOAD A,B Block Parallel-Connected
B
App. 4-2
Appendix 4 Instruction List
3) Reverse instruction
Support
Classification Designations Symbol Description
XGK XGB
Previous Operation results
Reverse NOT
Reverse
5) Output instruction
Support
Classification Designations Symbol Description
XGK XGB
7) End instruction
Support
Classification Designations Symbol Description
XGK XGB
End END END Program End
8) Non-process instruction
Support
Classification Designations Symbol Description
XGK XGB
Non-Process Instruction, used
Non-Process NOP Ladder not displayed
in Nimonic
App. 4-3
Appendix 4 Instruction List
9) Timer instruction
Support
Classification Designations Symbol Description
XGK XGB
Input
TON TON T t t
T
Input
TOFF TOFF T t t
T
Input t1+t2 = t
TMR TMR T t t1 t2
Timer
T
Input
t
TMON TMON T t
T
Input
TRTG TRTG T t t
T
Reset
Count
Pulse Setting
CTD CTD C c
Present
Output
Reset
Count
Pulse Setting
CTU CTU C c
Present
Output
Counter Reset
Increased
Pulse
Decreased
Pulse
CTUD CTUD C U D c
Setting
Present
Output
Reset
Count
Pulse Setting
CTR CTR C c
Present
Output
App. 4-4
Appendix 4 Instruction List
DMOV DMOV S D
32 bits
(S+1,S) (D+1,D )
Transfer
DMOVP DMOVP S D
b15 b0
BMOV BMOV S D N (S)
Specified Bits
Transfer (D)
BMOVP BMOVP S D N * Z: Control Word
(S) b15 b0
GBMOV GBMOV S D Z N : N
Specified Bits (S+N)
(D)
Group Transfer
:
GBMOVP GBMOVP S D Z N
(D+N)
* Z: Control Word
App. 4-5
Appendix 4 Instruction List
(Sb):Bit, BIN(0~9)
BCD4 BCD4 Sb Db
b15 b0
To 4bit BCD
BCD4P BCD4P Sb Db
4/8 Bits (Db): Bit
BCD
Conversion (Sb):Bit, BIN(0~99)
BCD8 BCD8 Sb Db
b15 b0
To 8bit BCD
BCD8P BCD8P Sb Db
(Db):Bit
GBCD GBCD S D N
Data (S) to N converted to BCD, and
(D) to N saved
Group GBCDP GBCDP S D N
BCD,BIN
Conversion GBIN GBIN S D N
Data (S) to N converted to BIN, and
(D) to N saved
GBINP GBINP S D N
App. 4-6
Appendix 4 Instruction List
To INT
L2I L2I S D (S+3,S+2,S+1,S) (D)
Whole Double Real Range
Long L2IP L2IP S D
Real/Integer
Conversion L2D L2D S D
To DINT
(S+3,S+2,S+1,S) (D+1,D)
Whole Double Real Range
L2DP L2DP S D
Remark
1) Integer value and Real value will be saved respectively in quite different format. For such reason, Real
Number Data should be converted as applicable before used for Integer Operation.
App. 4-7
Appendix 4 Instruction List
4) Comparison instruction
Support
Classification Designations Symbol Description
XGK XGB
CMP CMP S1 S2
CMP(S1,S2) and applicable Flag SET
Unsigned
(S1, S2 is Word)
Compare CMPP CMPP S1 S2
with Special
Relay DCMP DCMP S1 S2
CMP(S1,S2) and applicable Flag SET
used
(S1, S2 is Double Word)
DCMPP DCMPP S1 S2
CMP4 CMP4 S1 S2
CMP(S1,S2) and applicable Flag SET
(S1, S2 is Nibble)
CMP4P CMP4P S1 S2
4/8 Bits
Compare
CMP8 CMP8 S1 S2
CMP(S1,S2) and applicable Flag SET
(S1, S2 is Byte)
CMP8P CMP8P S1 S2
CMP(S1,S2))
TCMP TCMP S1 S2 D
:
CMP(S1+15,S2+15)
Table TCMPP TCMPP S1 S2 D Result:(D) ~ (D+15), 1 if identical
Compare
DTCMP DTCMP S1 S2 D CMP((S1+1,S1),(S2+1,S2))
:
CMP((S1+31,S1+30),(S2+31,S2+30))
DTCMPP DTCMPP S1 S2 D Result:(D) ~ (D+15)
GEQ GEQ S1 S2 D N
GEQP GEQP S1 S2 D N
GGT GGT S1 S2 D N
GGTP GGTP S1 S2 D N
GLT GLT S1 S2 D N
Compares S1 data to S2 data word
Group GLTP GLTP S1 S2 D N by word, and saves its result in
Compare Device (D) bit by bit from the lower
(16 Bits) GGE GGE S1 S2 D N bit
( N 16 )
GGEP GGEP S1 S2 D N
GLE GLE S1 S2 D N
GLEP GLEP S1 S2 D N
GNE GNE S1 S2 D N
GNEP GNEP S1 S2 D N
Remark
1) CMP(P), DCMP(P), CMP4(P), CMP8(P), TCMP(P) & DTCMP(P) Instructions all process the results of
Unsigned Compare. All the other Compare Instructions will perform Signed Compare.
App. 4-8
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
GDEQ GDEQ S1 S2 D N
GDEQP GDEQP S1 S2 D N
GDGT GDGT S1 S2 D N
GDGTP GDGTP S1 S2 D N
GDLT GDLT S1 S2 D N
Compares S1 data to S2 data 2 by
Group GDLTP GDLTP S1 S2 D N 2 words, and saves its result in
Compare Device (D) bit by bit from the lower
(32 Bits) GDGE GDGE S1 S2 D N bit
( N 16 )
GDGEP GDGEP S1 S2 D N
GDLE GDLE S1 S2 D N
GDLEP GDLEP S1 S2 D N
GDNE GDNE S1 S2 D N
GDNEP GDNEP S1 S2 D N
App. 4-9
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
LOAD= = S1 S2
LOAD> > S1 S2
16 Bits Compares (S1) to (S2), and saves
Data LOAD< < S1 S2
its result in Bit Result(BR) (Signed
Compare Operation)
LOAD>= >= S1 S2
(LOAD)
LOAD<= <= S1 S2
LOAD<> <> S1 S2
AND= = S1 S2
AND> > S1 S2
Performs AND operation of (S1) &
16 Bits
AND< < S1 S2 (S2) Compare Result and Bit Result
Data
(BR), and then saves its result in BR
Compare AND>= >= S1 S2 (Signed Operation)
(AND)
AND<= <= S1 S2
AND<> <> S1 S2
OR= = S1 S2
Performs OR operation of (S1) &
16 Bits
(S2) Compare Result and Bit Result
Data
OR<= (BR), and then saves its result in BR
Compare <= S1 S2
(Signed Operation)
(OR)
OR<> <> S1 S2
LOADD= D= S1 S2
LOADD> D> S1 S2
32 Bits Compares (S1) to (S2), and saves
Data LOADD< D< S1 S2
its result in Bit Result(BR) (Signed
Compare Operation)
LOADD>= D>= S1 S2
(LOAD)
LOADD<= D<= S1 S2
LOADD<> D<> S1 S2
Remark
Comparison instruction for input process the result of Signed comparison instruction generally. To process
Unsigned comparison, Use comparison instruction for input.
App. 4-10
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
ANDD= D= S1 S2
ANDD> D> S1 S2
32 Bits Performs AND operation of (S1) &
Data ANDD< D< S1 S2
(S2) Compare Result and Bit Result
Compare (BR), and then saves its result in
ANDD>= D>= S1 S2
(AND) BR (Signed Operation)
ANDD<= D<= S1 S2
ANDD<> D<> S1 S2
ORD= D= S1 S2
ORD> D> S1 S2
ORD<= D<= S1 S2
ORD<> D<> S1 S2
LOADR= R= S1 S2
LOADR> R> S1 S2
LOADR<= R<= S1 S2
LOADR<> R<> S1 S2
ANDR= R= S1 S2
ANDR> R> S1 S2
ANDR<= R<= S1 S2
ANDR<> R<> S1 S2
App. 4-11
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
ORR= R= S1 S2
ORR> R> S1 S2
ORR<= R<= S1 S2
ORR<> R<> S1 S2
LOADL= L= S1 S2
LOADL> L> S1 S2
LOADL<= L<= S1 S2
LOADL<> L<> S1 S2
ANDL= L= S1 S2
ANDL> L> S1 S2
ANDL<= L<= S1 S2
ANDL<> L<> S1 S2
App. 4-12
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
ORL= L= S1 S2
ORL> L> S1 S2
ORL<= L<= S1 S2
ORL<> L<> S1 S2
LOAD$= $= S1 S2
LOAD$> $> S1 S2
LOAD$<= $<= S1 S2
LOAD$<> $<> S1 S2
AND$= $= S1 S2
AND$> $> S1 S2
AND$<= $<= S1 S2
AND$<> $<> S1 S2
App. 4-13
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
OR$= $= S1 S2
OR$> $> S1 S2
OR$<= $<= S1 S2
OR$<> $<> S1 S2
LOADG= G= S1 S2 N
LOADG> G> S1 S2 N
Compares (S1), (S1+1), ,
16 Bits LOADG< G< S1 S2 N (S1+N) to (S2), (S2+1), ,
Data (S2+N) 1 to 1, and then saves
Group Compare LOADG>= G>= S1 S2 N 1 in Bit Result(BR) if each
(LOAD) value compared meets given
condition
LOADG<= G<= S1 S2 N
LOADG<> G<> S1 S2 N
ANDG= G= S1 S1 N
ANDG> G> S1 S1 N
Performs AND operation of
16 Bits ANDG< G< S1 S1 N
(S1), (S1+1), , (S1+N) &
Data (S2), (S2+1), , (S2+N) 1 to
Group Compare 1 Compare Result and Bit
(AND) ANDG>= G>= S1 S1 N
Result (BR), and then saves its
result in BR
ANDG<= G<= S1 S1 N
ANDG<> G<> S1 S1 N
ORG= G= S1 S2 N
ORG> G> S1 S2 N
ORG<= G<= S1 S2 N
ORG<> G<> S1 S2 N
App. 4-14
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGX XGB
LOADDG= DG= S1 S2 N
LOADDG> DG> S1 S2 N
Compares (S1), (S1+1), ,
32 Bits
LOADDG< DG< S1 S2 N (S1+N) to (S2), (S2+1), ,
Data
(S2+N) 1 to 1, and then saves
Group
LOADDG>= DG>= S1 S2 N 1 in Bit Result(BR) if each
Compare value compared meets given
(LOAD) condition
LOADDG<= DG<= S1 S2 N
LOADDG<> DG<> S1 S2 N
ANDDG= DG= S1 S1 N
ANDDG> DG> S1 S1 N
Performs AND operation of
32 Bits
ANDDG< (S1), (S1+1), , (S1+N) &
Data DG< S1 S1 N
(S2), (S2+1), , (S2+N) 1 to
Group
1 Compare Result and Bit
Compare ANDDG>= DG>= S1 S1 N
Result(BR), and then saves its
(AND) result in BR
ANDDG<= DG<= S1 S1 N
ANDDG<> DG<> S1 S1 N
ORDG= DG= S1 S2 N
ORDG> DG> S1 S2 N
Performs OR operation of
32 Bits
ORDG< DG< S1 S2 N (S1), (S1+1), , (S1+N) &
Data
(S2), (S2+1), , (S2+N) 1 to
Group
1 Compare Result and Bit
Compare Result(BR), and then saves its
ORDG>= DG>= S1 S2 N
(OR) result in BR
ORDG<= DG<= S1 S2 N
ORDG<> DG<> S1 S2 N
App. 4-15
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
LOAD3= 3= S1 S2 S3
LOAD3> 3> S1 S2 S3
LOAD3<= 3<= S1 S2 S3
LOAD3<> 3<> S1 S2 S3
AND3= 3= S1 S2 S3
AND3> 3> S1 S2 S3
Performs AND operation of (S1),
Three 16-Bit AND3< 3< S1 S2 S3 (S2), (S3) Compare Result by
Data Compare given condition and Bit Result
(AND) AND3>= 3>= S1 S2 S3 (BR), and then saves its result in
BR
AND3<= 3<= S1 S2 S3
AND3<> 3<> S1 S2 S3
OR3= 3= S1 S2 S3
OR3> 3> S1 S2 S3
OR3<= 3<= S1 S2 S3
OR3<> 3<> S1 S2 S3
LOADD3= D3= S1 S2 S3
LOADD3> D3> S1 S2 S3
LOADD3<= D3<= S1 S2 S3
LOADD3<> D3<> S1 S2 S3
App. 4-16
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
ANDD3= D3= S1 S2 S3
ANDD3> D3> S1 S2 S3
ANDD<> D3<> S1 S2 S3
ORD3= D3= S1 S2 S3
ORD3> D3> S1 S2 S3
ORD3<= D3<= S1 S2 S3
ORD3<> D3<> S1 S2 S3
App. 4-17
Appendix 4 Instruction List
5) Increase/Decrease instruction
Support
Classification Designations Symbol Description
XGK XGB
INC INC D
(D)+1 (D) 2
INCP INCP D
4-94
DINC DINC D
BIN Data (D+1,D)+1 (D+1,D) 2
Increase DINCP DINCP D
/
Decrease DEC DEC D
(Signed) (D)-1 (D) 2
DECP DECP D
4-96
DDEC DDEC D
(D+1,D)-1 (D+1,D) 2
DDECP DDECP D
INCU INCU D
(D)+1 (D)
2
INCUP INCUP D
4-98
DINCU DINCU D
(D+1,D)+1 (D+1,D)
BIN Data 2
Increase DINCUP DINCUP D
/
Decrease DECU DECU D
(D)-1 (D)
(Unsigned) 2
DECUP DECUP D
4-99
DDECU DDECU D
(D+1,D)-1 (D+1,D)
2
DDECUP DDECUP D
App. 4-18
Appendix 4 Instruction List
6) Rotation instruction
Support
Classification Designations Symbol Description
XGK XGB
ROL ROL D n
b15 b0
CY D
ROLP ROLP D n
Rotate to Left
DROL DROL D n b31 b15 b0
CY D+1 D
DROLP DROLP D n
ROR ROR D n
b15 b0
D CY
RORP RORP D n
Rotate to Right
DROR DROR D n b31 b15 b0
D+1 D CY
DRORP DRORP D n
b+3 b
ROR4 ROR4 Db n D CY
ROR4P ROR4P Db n
4/8 Bits
Rotate to Right b+7 b
ROR8 ROR8 Db n D CY
ROR8P ROR8P Db n
RCL RCL D n
b15 b0
CY D
Rotate to Left RCLP RCLP D n
(including
Carry) DRCL DRCL D n b31 b15 b0
CY D+1 D
DRCLP DRCLP D n
b+3 b
RCL4 RCL4 Db n CY D
4/8 Bits
RCL4P RCL4P Db n
Rotate to Left
(including b+7 b
RCL8 RCL8 Db n D
Carry) CY
RCL8P RCL8P Db n
RCR RCR D n
b15 b0
Rotate D CY
RCRP RCRP D n
to Right
(including
DRCR DRCR D n b31 b15 b0
Carry) D+1 D CY
DRCRP DRCRP D n
b+3 b
RCR4 RCR4 Db n D CY
4/8 Bits
RCR4P RCR4P Db n
Rotate to Right
(including b+7 b
RCR8 RCR8 Db n D
Carry) CY
RCR8P RCR8P Db n
App. 4-19
Appendix 4 Instruction List
7) Move instruction
Support
Classification Designations Symbol Description
XGK XGB
St Ed
BSFT BSFT St Ed b15 b0
Bits Move
BSFTP BSFTP St Ed
0
b15 b0
BSFL BSFL D n
(D)
BSFLP BSFLP D n CY 0
Move to Higher
Bit b31 b0
DBSFL DBSFL D n
(D+1, D)
DBSFLP DBSFLP D n CY 0
b+3 b
BSFL4 BSFL4 Db n
D
BSFL8P BSFL8P Db n CY 0
b15 b0
BSFR BSFR D n (D)
0
BSFRP BSFRP D n CY
Move to Lower
Bit b31 b0
DBSFR DBSFR D n (D+1, D)
0
DBSFRP DBSFRP D n CY
b+3 b
BSFR4 BSFR4 Db n D
0 CY
Move to Lower BSFR4P BSFR4P Db n
Bit within 4/8 b+7 b
Bits range BSFR8 BSFR8 Db n D
CY
BSFR8P BSFR8P Db n 0
Word Move ..
Ed (End Word)
WSFTP WSFTP Et Ed
D2
Word Data WSFLP WSFLP D1 D2 N
Move to
Left/Right WSFR WSFR D1 D2 N D1
..
N
h0000 D2
WSFRP WSFRP D1 D2 N
App. 4-20
Appendix 4 Instruction List
8) Exchange instruction
Support
Classification Designations Symbol Description
XGK XGB
XCHG XCHG D1 D2
(D1) (D2)
XCHGP XCHGP D1 D2
Data
Exchange
DXCHG DXCHG D1 D2
(D1+1, D1) (D2+1, D2)
DXCHGP DXCHGP D1 D2
b15 b0
Higher/Lower SWAP SWAP D (D) Upper Byte Lower Byte
Byte
Exchange (D) Lower Byte Upper Byte
SWAPP SWAPP D
App. 4-21
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
ADD ADD S1 S2 D
(S1)+(S2) (D)
ADDP ADDP S1 S2 D
Integer Addition
(Signed)
DADD DADD S1 S2 D
(S1+1,S1)+(S2+1,S2)
(D+1,D)
DADDP DADDP S1 S2 D
SUB SUB S1 S2 D
(S1)-(S2) (D)
Integer SUBP SUBP S1 S2 D
Subtraction
(Signed) DSUB DSUB S1 S2 D (S1+1,S1)-(S2+1,S2)
(D+1,D)
DSUBP DSUBP S1 S2 D
MUL MUL S1 S2 D
(S1)(S2) (D+1,D)
Integer MULP MULP S1 S2 D
Multiplication
(Signed) DMUL DMUL S1 S2 D (S1+1,S1)(S2+1,S2)
(D+3,D+2,D+1,D)
DMULP DMULP S1 S2 D
ADDU ADDU S1 S2 D
(S1)+(S2) (D)
ADDUP ADDUP S1 S2 D
Integer Addition
(Unsigned)
DADDU DADDU S1 S2 D (S1+1,S1)+(S2+1,S2)
(D+1,D)
DADDUP DADDUP S1 S2 D
SUBU SUBU S1 S2 D
(S1)-(S2) (D)
MULU MULU S1 S2 D
(S1)(S2) (D+1,D)
App. 4-22
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
DIVU DIVU S1 S2 D
(D) Quotient
(S1)(S2)
(D+1) Remainder
DIVUP DIVUP S1 S2 D
Integer Division
(Unsigned) (S1+1,S1)(S2+1,S2)
DDIVU DDIVU S1 S2 D
(D+1,D) Quotient
$ADD $ADD S1 S2 D
String Connects S1 String with S2 String
Addition to save in D
$ADDP $ADDP S1 S2 D
App. 4-23
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
ADDB ADDB S1 S2 D
(S1)+(S2) (D)
ADDBP ADDBP S1 S2 D
BCD Addition
DADDB DADDB S1 S2 D (S1+1,S1)+(S2+1,S2)
(D+1,D)
DADDBP DADDBP S1 S2 D
SUBB SUBB S1 S2 D
(S1)-(S2) (D)
SUBBP SUBBP S1 S2 D
BCD Subtraction
DSUBB DSUBB S1 S2 D
(S1+1,S1)-(S2+1,S2)
(D+1,D)
DSUBBP DSUBBP S1 S2 D
MULB MULB S1 S2 D
(S1)(S2) (D+1,D)
MULBP MULBP S1 S2 D
BCD
Multiplication
DMULB DMULB S1 S2 D (S1+1,S1)(S2+1,S2)
(D+3,D+2,D+1,D)
DMULBP DMULBP S1 S2 D
(D+3,D+2) Remainder
DDIVBP DDIVBP S1 S2 D
App. 4-24
Appendix 4 Instruction List
Basic
Classification Designations Symbol Description Page
Steps
WOR WOR S1 S2 D
Word OR
(S1) (S2) (D)
WORP WORP S1 S2 D
Logic Addition
DWOR DWOR S1 S2 D DWord OR
(S1+1,S1)(S2+1,S2) (D+1,D)
DWORP DWORP S1 S2 D
WXOR WXOR S1 S2 D
Word Exclusive OR
(S1) (S2) (D)
WXORP WXORP S1 S2 D
Exclusive
OR
DWXOR DWXOR S1 S2 D DWord Exclusive OR
(S1+1,S1)(S2+1,S2) (D+1,D)
DWXORP DWXORP S1 S2 D
WXNR WXNR S1 S2 D
Word Exclusive NOR
(S1) (S2) (D)
WXNRP WXNRP S1 S2 D
Exclusive
NOR
DWXNR DWXNR S1 S2 D
DWord Exclusive NOR
(S1+1,S1)(S2+1,S2) (D+1,D)
DWXNRP DWXNRP S1 S2 D
App. 4-25
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
b15 b0
BSUM BSUM S D S
1s number
BSUMP BSUMP S D D
Bit Check
b31 b15 b0
DBSUM DBSUM S D S S
1s number
DBSUMP DBSUMP S D D
BRST BRST D N
Bit Reset Resets N Bits (starting from D) to 0
BRSTP BRSTP D N
S D
ENCO ENCO S D n
... ...
Encode
N bits
ENCOP ENCOP S D n N
2 bits 2binary
S D
DECO DECO S D n
... ...
Decode
N bits
DECOP DECOP S D n
2binary 2N bits
Disconnect &
Connect UNI UNI S D n D ...
D+1
D+N-1
.. ...
S
...
UNIP UNIP S D n ...
S Lower D
WTOB
..
WTOB S D n Higher Lower h00
h00 Higher D+1
S+N-1 Higher Lower h00 Lower
Word/ WTOBP WTOBP S D n h00 Higher
Byte
Conversion BTOW BTOW S D n D h00 Lower Higher Lower
.. S
D+1 h00 Higher
h00 Lower Higher Lower S+N-1
BTOWP BTOWP S D n h00 Higher
SCH SCH S1 S2 D N
SCHP SCHP S1 S2 D N
Finds S1 value within S2 ~ N range
Data and saves the first identical valued
Search position in D and S1s identical valued
DSCH DSCH S1 S2 D N
total number in D+1
DSCHP DSCHP S1 S2 D N
MAX MAX S D n
Saves the max value in D among N
words starting from S
MAXP MAXP S D n
Max. Value
Search
DMAX DMAX S D n
Saves the max value in D among N
double words starting from S
DMAXP DMAXP S D n
App. 4-26
Appendix 4 Instruction List
Designatio Support
Classification Symbol Description
ns XGK XGB
MIN MIN S D n
Saves the min value in D among N
words starting from S
MINP MINP S D n
Min. Value
Search
DMIN DMIN S D n
Saves the min value in D among N
double words starting from S
DMINP DMINP S D n
SUM SUM S D n
Adds up N words starting from S to
save in D
SUMP SUMP S D n
Sum
DSUM DSUM S D n
Adds up N double words starting
from S to save in D
DSUMP DSUMP S D n
AVE AVE S D n
Averages N words starting from S
to save in D
AVEP AVEP S D n
Average
DAVE DAVE S D n
Averages N double words starting
from S to save in D
DAVEP DAVEP S D n
N D
MUXP MUXP S1 S2 D N
MUX
DMUX DMUX S1 S2 D N S2+1 S2 S1st data
N D+1 D
DMUXP DMUXP S1 S2 D N
App. 4-27
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
Support
Classification Designations Symbol Description
XGK XGB
SEG SEG S D Z
7 Segment Converts S Data to 7-Segment as
Display adjusted in Z Format so to save in D
SEGP SEGP S D Z
App. 4-28
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
BCDDA BCDDA S D
Converts S of 1-word BCD to ASCII
Convert BCD Cord to save in starting D
BCDDAP BCDDAP S D
to Decimal
ASCII
Cord DBCDDA DBCDDA S D
Converts S of 2-word BCD to ASCII
Cord to save in starting D
DBCDDAP DBCDDAP S D
DABIN DABIN S D
Converts S S+2,S+1,Ss Decimal
ASCII Cord to BIN to save in D
Convert DABINP DABINP S D
Decimal ASCII
to BIN DDABIN DDABIN S D Converts S+5~Ss Decimal ASCII
Cord to BIN value to save in D+1 &
DDABINP DDABINP S D D
HABIN HABIN S D
Converts S+1,Ss Hexadecimal ASCII
Cord to BIN value to save in D
Convert HABINP HABINP S D
Hexadecimal
ASCII to BIN DHABIN DHABIN S D
Converts S+3~Ss Hexadecimal ASCII
Cord to BIN to save in D
DHABINP DHABINP S D
DABCD DABCD S D
Converts S+1,Ss Decimal ASCII
Cord to BCD to save in D
Convert DABCDP DABCDP S D
Decimal ASCII
to BCD DDABCD DDABCD S D
Converts S+3~Ss Decimal ASCII
Cord to BCD to save in D
DDABCDP DDABCDP S D
LEN LEN S D
String Saves String Length with S starting
Length Detect in D
LENP LENP S D
App. 4-29
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
STR STR S1 S2 D
Adjusts S2 saved word
data to S1 saved place
number to convert to String
STRP STRP S1 S2 D
and save in D
Convert BIN16/32 to
String Adjusts S2 saved double
DSTR DSTR S1 S2 D
word data to S1 saved
place number to convert to
DSTRP DSTRP S1 S2 D
String and save in D
VAL VAL S D1 D2
Adjusts S saved string to
number to save in word
D1 and saves the place
VALP VALP S D1 D2
number in D2
Convert String to
BIN16/32 Adjusts S saved string to
DVAL DVAL S D1 D2
number to save in double
word D1 and saves the
DVALP DVALP S D1 D2
place number in D2
Adjusts Floating decimal
RSTR RSTR S1 S2 D
point point Real Number
Data (S1: number, S2:
RSTRP RSTRP S1 S2 D places) to String format to
Convert Real Number to save in D
X
String Adjusts Floating decimal
LSTR LSTR S1 S2 D
point point Double Real
Number Data (S1:number,
LSTRP LSTRP S1 S2 D S2:places) to String format
to save in D
STRR STRR S D Converts String S to Floating
decimal point point Real
Convert String to Real STRRP STRRP S D Number Data to save in D
Number X
STRL STRL S D
Converts String S to
Floating decimal point
point Double Real Number
STRLP STRLP S D
Data to save in D
ASC ASC S D cw
Converts BIN Data to
ASCII in Nibble unit,
ASCII Conversion
based on cws format from
ASCP ASCP S D cw
S to save in D
Converts 2N ASCII saved
HEX HEX S D N
in N words from S in byte
HEX Conversion unit to Nibble unit of
HEXP HEXP S D N Hexadecimal BIN so to
save in D
RIGHT RIGHT S D N Extracts n string from S
String Extract from
strings final letter to save
Right
RIGHTP RIGHTP S D N in starting D
MID MID S1 S2 D
Extracts string which
conforms to S2 condition
String Random Extract
among S1 string to save in
MIDP MIDP S1 S2 D
starting D
App. 4-30
Appendix 4 Instruction List
Basic
Classification Designations Symbol Description Page
Steps
RBCD RBCD S1 S2 D
Adjusts Floating decimal point
point Real Number Data S1 to
S2 place to convert to BCD,
RBCDP RBCDP S1 S2 D
and then to save in D
Parse Real
X
Number to BCD Adjusts Floating decimal point
LBCD LBCD S1 S2 D
point Double Real Number
Data S1 to S2 place to convert
LBCDP LBCDP S1 S2 D
to BCD, and then to save in D
BCDR BCDR S1 S2 D
Adjusts BCD Data S1 to S2
place to convert to Floating
decimal point point Real
Convert BCD BCDRP BCDRP S1 S2 D
Number, and then to save in D
Data to Real Adjusts BCD Data S1 to S2 X
Number BCDL BCDR S1 S2 D
place to convert to Floating
decimal point point Double
BCDLP BCDLP S1 S2 D Real Number, and then to
save in D
App. 4-31
Appendix 4 Instruction List
Basic
Classification Designations Symbol Description Page
Steps
SIN SIN S D
SIN Operation SIN(S+1,S) (D+1,D)
SINP SINP S D
COS COS S D
COS
COS(S+1,S) (D+1,D)
Operation
COSP COSP S D
TAN TAN S D
TAN Operation TAN(S+1,S) (D+1,D)
TANP TANP S D
SQRT SQRT S D
Square Root
Operation (S+1,S) (D+1,D)
SQRTP SQRTP S D
App. 4-32
Appendix 4 Instruction List
Basic
Classification Designations Symbol Description Page
Steps
LIMIT LIMIT S1 S2 S3 D
DZONE DZONE S1 S2 S3 D
VZONE VZONE S1 S2 S3 D
If S1 < -S2(S3/100), then
D = S1-S2+S2(S3/100)
VZONEP VZONEP S1 S2 S3 D
If S2(S3/100) <S1< S2(S3/100),
Vertical-zone
then
Control
D = (100/S3)S1
DVZONE DVZONE S1 S2 S3 D
If S1 < S2(S3/100), then
D = S1+S2-S2(S3/100)
DVZONEP DVZONEP S1 S2 S3 D
App. 4-33
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
ADDCLK ADDCLK S1 S2 D
Adds S1 ~ S1+2 & S2 ~ S2+2 Time
Time Data
Data to save in D ~ D+2 in Time X
Increase
Data format (Hr/Mn/Sd)
ADDCLKP ADDCLKP S1 S2 D
SUBCLK SUBCLK S1 S2 D
Extracts S2 ~ S2+2s Time Data from
Time Data
S1 ~ S1+2 to save in D ~ D+2 in X
Decrease
Time Data format (Hr/Mn/Sd)
SUBCLKP SUBCLKP S1 S2 D
SECOND SECOND S D
Converts Time Data S ~ S+2 to
X
seconds to save in double word D
Time Data SECONDP SECONDP S D
Format
Conversion HOUR HOUR S D
Converts the seconds saved in
double word S to Hr/Mn/Sd to save X
in D ~ D+2
HOURP HOURP S D
Support
Classification Designations Symbol Description
XGK XGB
App. 4-34
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
FOR FOR N
Operates FOR~NEXT section n
Loop times
NEXT NEXT
Instruction
BREAK BREAK Escapes from FOR~NEXT section
Support
Classification Designations Symbol Description
XGK XGB
Support
Classification Designations Symbol Description
XGK XGB
Self Diagnosis
Error Display FALS FALS n
(Error Display )
On during n1 Scan, Off during n2
Scan Cluck DUTY DUTY D n1 n2
Scan
WDT WDT
WDT
Watch Dog Timer Clear
Initialize
WDTP WDTP
Support
Classification Designations Symbol Description
XGK XGB
App. 4-35
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
NEG NEG D
Saves D value again in D with 2s
complement taken
NEGP NEGP D
2s
complement
DNEG DNEG D Saves (D+1,D) value again in
(D+1,D) with 2s complement
DNEGP DNEGP D taken
RNEG RNEG D
Reverses D Real Number Sign then
to save again
Real Number RNEGP RNEGP D
Data Sign
Reverse LNEGR LNEG D
Reverses D Double Real Number
Sign then to save again
LNEGP LNEGP D
ABS ABS D
Converts D highest Bit to 0
ABSP ABSP D
Absolute Value
Operation
DABS DABS D
Converts (D+1,D)
highest Bit to 0
DABSP DABSP D
Support
Classification Designations Symbol Description
XGK XGB
RSET RSET S
Block Changes Block Number of file register
X
Conversion to S Number
RSETP RSETP S
o X
Flash EDMOV EDMOV S1 S2 D
Double Word Transfers S2+1, S2 double word data
Data in S1 Block to D+1, D
Transfer EDMOVP EDMOVP S1 S2 D
App. 4-36
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
Sets opposite station No. for P2P
Station No. Set P2PSN P2PSN n1 n2 n3 Communication. n1:P2P No., X
n2:Block, n3:Station No.
Sets word data Read Area
Read Area Set n1:P2P No., n2:Block, n3:Variable
P2PWRD P2PWRD n1 n2 n3 n4 n5 X
(WORD) sequence, n4:Variable Size,
n5:Device
Support
Classification Designations Symbol Description
XGK XGB
GET GET sl S D N
Reads data of special module
memory is installed on
Special GETP GETP sl S D N
Module
Read/Write PUT PUT sl S1 S2 N
Writes data on special module
memory is installed on
PUTP PUTP sl S1 S2 N
App. 4-37
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
Instructions Positioning Modules ax
Return to Origin
ORG ORG sl ax axis installed on sl slot to return to
Point
Origin Point
Instructions Positioning Modules ax
Floating Origin
FLT FLT sl ax axis installed on sl slot to set
Point
Floating Origin Point
Instructions Positioning Modules ax
axis installed on sl slot to start
Direct Start DST DST sl ax n1 n2 n3 n4 n5 directly with Target Position(n1),
Target Speed(n2), Dwell Time(n3),
M Code(n4) & Control Word(n5)
Instructions Positioning Modules ax
Indirect Start IST IST sl ax n axis installed on sl slot to start n
step indirectly
App. 4-38
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
App. 4-39
Appendix 4 Instruction List
Support
Classification Designations Symbol Description
XGK XGB
App. 4-40
Warranty
1. Warranty Period
The product you purchased will be guaranteed for 18 months from the date of manufacturing.
2. Scope of Warranty
Any trouble or defect occurring for the above-mentioned period will be partially replaced or repaired. However,
please note the following cases will be excluded from the scope of warranty.
(1) Any trouble attributable to unreasonable condition, environment or handling otherwise specified in the
manual,
(2) Any trouble attributable to others products,
(3) If the product is modified or repaired in any other place not designated by the company,
(4) Due to unintended purposes
(5) Owing to the reasons unexpected at the level of the contemporary science and technology when delivered.
(6) Not attributable to the company; for instance, natural disasters or fire
3. Since the above warranty is limited to PLC unit only, make sure to use the product considering the safety for
system configuration or applications.
Environmental Policy
LS Industrial Systems Co.,Ltd supports and observes the environmental policy as below.
http://eng.lsis.biz
10310000693